Professional Documents
Culture Documents
Consulting Engineers
Tel.: 91-22 61547800. Fax.: 91-2225111092
Website : www.knexir.in Email : Knexir@knexir.in
Doc. No.
Revision No.
TENDER DOCUMENT
FOR
PAINTING WORK
Revision
Date
R0
14-05-2013
Prepared By
Faisal Farooqui
Checked By
K C Sanjay Kumar
Approved By
Jagdish Pathak
Status
Comments / Approval
R1
R2
R3
Doc. No.
Revision No.
INDEX
1.0
2.0
2.1
GENERAL ............................................................................................................................................................. 4
2.2
SCOPE ................................................................................................................................................................. 4
2.3
2.4
EQUIPMENT .......................................................................................................................................................... 7
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
GUARANTEE........................................................................................................................................................ 18
2.14
2.15
DOCUMENTATION: ............................................................................................................................................... 18
3.0
4.0
Doc. No.
Revision No.
1.0
GENERAL INFORMATION:
M/s. Carlsberg India Pvt. Ltd.
5th Floor, Paras Twin Towers, Tower B,
: Sector-54, Gurgaon,
Harayana-122 002
1.0
Client
2.0
Plant location
3.0
Project
4.0
5.0
Site data
Access to Site
Ambient data
(As per ISHARE)
DBT ( C)
WBT ( C)
RH (%)
Summer
42.2
25.6
26
Monsoon
32.2
28.3
78
Winter
10.0
6.7
60
By Road
: Patna
Railway Station
: Patna
Nearest Airport
: Patna
Doc. No.
Revision No.
2.0
2.1
General
This engineering standard specification covers the requirements for painting including surface preparation,
method of application, inspection of paints / coating and painted surface for equipment, piping, structures,
electrical, instrumentation equipment for the plants engineered by KCPL
Building / Concrete Painting is not covered under this Specification. For Building / concrete Protection
Painting refer Civil Specification.
2.2
Scope
a.
Scope of work covered in the specification shall include, but not limited to the following:
This specification defines the requirements for surface preparation, selecting and method of application of
paints on external surfaces of equipment, vessels, machinery, piping, ducts, steel structure, electrical and
instrument items. In general all shop fabricated/manufactured equipment will be delivered to job site with
painting in accordance with the requirements of this Specification.
The entire painting job shall be done as per the paint materials specification and apply as per the
specifications for surface preparation, paint system and application method given in the specification.
b.
Extent of Work
All un-insulated CS and SS equipment like columns, vessels, drums, storage tanks, heat exchangers, pump
etc.
All un-insulated carbon and low alloy steel piping, fittings, flanges and valves (Including painting
identification marks), furnaces, ducts and stacks.
All structural steel work, pipe structural steel work, walkways, handrails, ladders, platforms etc.
Identification colour bands on all piping as required including insulated aluminium / galvanised clad,
galvanised, SS and non-ferrous piping.
Identification lettering/ numbering on all painted surfaces of equipment/ piping insulated aluminium /
galvanized clad galvanized, SS and non-ferrous piping.
Supply of all primers, paints and all other materials required for painting other than owners supply.
Painting under insulation for carbon steel and stainless steel piping, vessels, storage tanks etc, if required.
Doc. No.
Revision No.
Repair and repainting of damaged and defective painting of shop applied items as per the instructions of
engineer in charge of site.
All galvanised piping, structural and equipment to be repaired on damaged at site with suitable coating
materials as per the instruction of engineer in charge at site.
c.
d.
2.3
Pipes and equipment shall be painted only after the mechanical completion, testing on systems are
completed including hydro testing as well as after completion of steam purging wherever required.
a.
The latest edition of the following standards including all revisions and addendum shall be applicable.
Works shall also be in accordance with the Paint Manufacturers recommendations.
IS-5
IS-2074 Specification for ready mixed paints, red oxide zinc chrome primer.
Doc. No.
Revision No.
IS-2932 Specification for enamel, synthetic, exterior (a) undercoating (b) finishing
BS-729, 1981 Hot Dip Galvanised Coatings on Iron and Steel Articles
b.
IS 1477 Part I Code of Practice for Painting of Ferrous metal in building (Pre Treatment)
If there is any conflict between the requirements of the above mentioned codes and standards and this
engineering specification, the requirements of the specification shall prevail. All conflicts shall be referred
to KCPL/Owner for clarification before proceeding for the work.
c.
The paint manufacturers latest approved published instruction shall be followed as far as practicable at all
times. Particular attention shall be paid to the following.
The paint materials for any paint system including primer, intermediate coating, finished coating and
thinner shall be from a single approved manufacturer.
d.
Any painting work (Including surface preparation) on piping or equivalent shall commence only after the
system tests have been completed and clearance for taking up painting work is given by the engineer in
charge in writing.
Doc. No.
Revision No.
2.4
Equipment
a.
All tools, brushes, rollers, spray guns, abrasive materials, solvent, hand/power tools for cleaning,
scaffolding materials, shot/wet abrasive blasting, water blasting equipment, air compressors, industrial
vacuum cleaners etc. required to be used shall be suitable for the work and all in good order and shall be
arrange by the contractor at site and insufficient quantity.
b.
Mechanical mixing shall be used for paint mixing operations in case of two-pack system except engineer in
charge may allow the hand mixing of small quantity at his discretion.
2.5
a.
Painting material shall be received, unloaded and stored in a room, which is well ventilated.
b.
In cases where paints are stored outside, adequate protection shall be provided to prevent damage to the
drums.
c.
Warning signboards shall be displayed at places where paints and solvents are stored.
d.
Paints shall not be stored in plant area where there is a fire risk.
e.
Paints and solvents shall be stored and records shall be maintained to ensure their usage before expiry
date.
f.
Containers shall be handled with care. Container of Paint, catalyst and thinners shall not be opened prior
to use except for spot inspection.
g.
Adequate number of fire extinguishers shall be provided in the stores where paint and solvents are stored.
h.
Adequate ventilation and gas masks shall be provided while painting in confined areas.
2.6
a.
Preparatory Work:
i.
The agency undertaking work shall estimate quantity of primer and paint required for the job and
arrange to procure the same prior to commencement of the job.
ii.
Approved brands of paints shall only be used (shall be mentioned supplier wise)
iii.
Check, verify the year of manufacture, Batch No. and expiry date of the paint before starting the work.
iv.
Read the paint manufacturers instruction regarding applications, Incase of conflicting requirement with
this specification, Engineer in charge shall be consulted.
v.
Necessary steel scaffolding, landing mats, etc. required to carry out the job is to be arranged.
Doc. No.
Revision No.
vi.
All workmen deployed on the job shall have personal protection gear such as safety shoes, helmets,
safety belts and goggles.
vii.
viii.
Arranged adequate quantities of consumables such as sand papers, wire brushes, paint brushes and
cloth.
ix.
Arrange sufficient number of air compressor of adequate capacities with spray guns and other
accessories.
x.
Ensure that calibrated DFT (Dry Film Thickness) tester/ elcometer is available at shop/ site.
xi.
xii.
xiii.
Ensure that all electrical appliances are tested and properly earthed.
xiv.
Provide galvanised sheets, tarpaulins etc. to protect equipment and men during abrasive blasting
operation.
xv.
Provide adequate gas masks, goggles, hand gloves and other personal protection gear to the workmen
undertaking abrasive blasting.
b.
Surface Preparation:
In order to achieve maximum durability one or more of following methods of surface preparation shall be
followed, depending on the condition of steel surface and as instructed by engineer in charge. Adhesion of
the paint film to surface depends largely on the degree of cleanliness of the metal surface. Proper surface
preparation contributes more to the success of the paint protective system.
Blast cleaning
For the adequate performance of the painting system, it is absolutely essential that the surfaces to be
painted are adequately prepared. The surface should be dry and free from oil and grease, dust, weld
splatter, burrs, flux, rust, loose scale, dirt and any other foreign matter before any coating is applied.
All surface preparation will be carried out in accordance with the requirement set out in ISO 8501-1: 1988
Preparation of Steel Substrates before Application of Paints and Related Products Visual Assessment
for surface cleanliness
Doc. No.
Revision No.
Doc. No.
Revision No.
Steel grit
Steel shot
Aluminium oxide
Copper Slag
Sand: Should sand be considered as the blasting medium, it shall be delivered to site in
sealed bags. Each bag shall be identified against a Batch No. and each batch has a third party
certificate. The test certificate shall confirm that the blast medium conforms to the
requirements of US-MIL-S-22262 with a maximum chloride level of 0.03%.
Surfaces, which become wet due to rain or moisture, shall be re-blasted prior to application of the
primer. Abrasive blast cleaning shall overlap by at least 25 mm on any adjacent painted surface.
Environmental Conditions for Surface Preparation
Surface preparation by abrasive blast cleaning shall not be carried out when the following
conditions prevail:
The surface temperature of the substrate is less than 3oC above the ambient dew point and
when the relative humidity is greater than 85%. Or the substrate temperature is more than
60oC.
Doc. No.
Revision No.
Abrasive blast cleaning shall not be carried out during the hours of darkness unless
adequately equipped facility for the purpose is available.
Surface preparation after abrasive blast cleaning: All surfaces that have been prepared using
abrasive blast cleaning will normally have traces of blast debris and dust removed from the
surface. The surface including all pockets and corners shall be cleaned by vacuum cleaning, blowing
with dry oil free compressed air, or brushing with a clean brush made from hair, bristle or fiber.
Surface preparation for hot dipped galvanised steel, stainless steel and non-ferrous metals.
Generally these surfaces are not painted.
If, however painting is required on these surfaces, they shall be lightly abrasive blast cleaned using
aluminium oxide or inert aluminium silicate. Copper from furnace slag shall not be used on
stainless steel. Any zinc salts that have formed on galvanised surfaces shall be removed using clean
water or a solvent wash and thoroughly dried before the abrasive cleaning is undertaken.
Surface Preparation of Concrete Surfaces (NOT APPLICABLE):
Concrete surfaces that require painting shall be clean, dry and free from laitance and have a
degree of roughness to ensure proper adhesive of the paint. The surface shall be blast cleaned or
power wire brushed to obtain the degree of roughness required.
Etching with dilute hydrochloric acid and washing with excess water shall be accepted as a last
choice only. Painting shall not commence on concrete surfaces until the surface has dried to
humidity of 4% by wt or less.
Surface preparation classification is indicated in Table-I below
Surface prepared shall be compared with relevant standard using a comparator.
After surface preparation and prior to any coating application the substrate shall be checked for
soluble salt contamination using a suitable salt contamination meter. Maximum allowable is 5
gm/cm2
Doc. No.
Revision No.
Method of
Cleaning
Solvent Cleaning
Through Hand
Tool Cleaning
Classification
Hand and
Power Tool
Cleaning
St 2
Sa 2 Nearly
80%
Hand and
Power Tool
Cleaning
Flame Cleaning
of new steel
Blast Cleaning to
usually clean
steel
Through Blast
Cleaning
Reference Standard
SIS / ISO
St 1
Very thorough
Hand and Power
Tool Cleaning
Removal of
rust, loose mill
scale
Removal of all
visible rust,
mill scales by
blast.
Commercial
Blast Cleaning
Light Blast
Cleaning
Blast Cleaning
Pickling
Pickling
Weathering
followed by
blast cleaning
Very through
blast cleaning
Weathering
Near White
Blast Cleaning
St 3
F1
Sa 3 100% Pure
Surface
Sa 1
Sa 2
95%
Pure
Doc. No.
Revision No.
Method of
Cleaning
Classification
ISO :
Reference Standard
SIS / ISO
Doc. No.
Revision No.
2.7
2.8
Painting System
The paint system should vary with the type of environment envisaged in and around plant, the service
temperature and the cost effectiveness. These parameters are defined as part of this specification.
Refer to Annexure II
2.9
2.10
a.
Flow Direction
Arrows can also be used to indicate the flow direction as described in Sketch 3
The arrows shall be in white or black colour. Following sizes are recommended:
For pipes diameter 1 to 6 dia., arrow to fit in a 25 mm x 100 mm rectangle.
For pipes diameter 8 dia and above, arrow to fit in a 80 mm x 150 mm rectangle.
Doc. No.
Revision No.
b.
In case of flow of fluid is possible in either direction; two arrows shall be indicated one above the other
and both in same colour.
Arrows and band markings shall be made at the unit battery limits and then on convenient location at
the point of use. It is recommended to adopt one method for the entire plant.
Hazardous Mediums
Where the piping system carries a hazardous product, a panel of equal diagonal stripes (black and yellow
colours) shall be superimposed on the pipe on both ends of the basic identification panels as detailed in
Sketch-4.
c.
Colour:
The Line nos. and equipment nos. shall be painted either in white or in black in order to contrast
clearly with the colour of paint on the pipe or equipment. For insulated lines, the code indications
shall be painted over the cladding of the insulation.
Requirements:
The full name or well-known abbreviations of chemical and symbol of fluid flowing (as per Project
Spec.) inside a pipeline shall be indicated. The line number shall also be painted on the pipelines. The
pressure or temperature of the fluid inside the pipeline shall not be indicated.
Location:
The code indication as described above shall be painted at following locations or such other places
where quick identification is deemed necessary.
Pipelines: At all junctions, both sides of valves, both sides of service appliances and at intervals of 25
m on straight pipe lengths.
Note: For long straight lengths of pipelines e.g. transfer lines, the interval of 25 m for code indication
may be varied at the discretion of the Client/KCPL
d.
Size:
The recommended size of lettering to be used for code indications on the insulated as well as uninsulated
pipes shall be as per following:
For Pipes
Diameter 2
25 mm letters
For Pipes
Diameter 2 4
40 mm letters
For Pipes
80 mm letters
Doc. No.
Revision No.
e.
f.
2.11
50 / 80 mm
100 mm
300 mm
600 mm
900 mm
a.
Inspection of various stages during painting is essential to ensure quality of painting. Inspection shall be
performed by owner authorized Field Superintendent.
b.
Surface preparation shall be as per specification; the prepared surface shall be compared with standard
comparator charts available in standards such as SIS or ISO. The basis of acceptance shall be based on
visual comparison only.
c.
Standard surface finish comparator specimens are available, which are approved by reputed test house,
these may also be used after obtaining clients or consultant approval.
d.
Visual examination of the painted surface shall be conducted to check for flaws such as unfinished surface,
drips, wrinkles, blisters, peels, cracks, stains, pin holes, crawls, dust settlement and air pockets.
e.
Area where such defects are noticed shall be marked using some paint of different colour.
f.
Areas where there are no such defects shall be accepted after visual examination.
g.
Thickness of primer and finish coats shall be measured using dry film thickness meter or elco-meter or
owners accepted equal. Thickness shall be measured in accordance with specification of SSPC-PA-A-73T.
h.
Location for verifying thickness shall be decided by engineer-in-charge depending on the size and shape of
the item painted.
Doc. No.
Revision No.
i.
Total three sets of readings shall be carried out at a location, one at the main location and two at the
adjacent points. The average of these three measurements shall be taken as the measured value.
j.
The coating thickness shall be deemed to be accepted if the following conditions are satisfied:
k.
Consultants/ Client may draw sample of paint before or during application for analysis.
l.
Adhesion test shall be performed after the finish coating has dried up, using a scraper comb with 1 mm gap
between teeth. Adhesion shall exceed 80%.
m.
All painting material including primers and thinners brought to site by contractor for application shall be
procured directly from the manufacturer as per the specification and shall be accompanied by
manufacturers test certificates. Paint formulations without certificates are not acceptable.
n.
Engineer in charge at his discretion, may call for tests of paint formulation. Contractor shall arrange to
have such tests performed including batch wise test of wet paints for physical and chemical analysis. All
cost incurred in carrying out tests shall be borne by the contractor. Defective work shall be corrected by
the Painting/Coating Contractor at his sole expense.
2.12
a.
Workmen should be provided with all personal protective gears such as safety shoes, safety goggles/
masks, hand gloves, aprons, safety belts, helmets etc.
b.
Smoking should be totally prohibited in and around painting area and paint storage area.
Doc. No.
Revision No.
c.
Adequate ventilation and lighting shall be provided while painting in a confined area.
d.
While performing shot blasting activity, the area shall be covered adequately so that no shots fly around.
e.
Proper tubular double scaffolding with metallic clamps and landing mats shall be used while working on
higher elevations.
f.
If painting has to be carried out in an almost airtight environment, workmen shall use gas masks.
2.13
Guarantee
The contractor shall guarantee that the chemical and physical properties of paint materials used are in
accordance with the specifications contained herein / to be provided during job execution. The painting
work shall be guaranteed for at least 2 years without any detrimental failures such as loss of adhesion,
under film corrosion, corrosion spots and blisters etc. under the corrosive conditions prevailing in the
plant.
The contractor shall produce test reports from manufacturer regarding the quality of the particular batch
of painted surface. The Engineer in charge shall have the right to test wet samples of paint at random for
quality as per the paint materials specification given in this specification. Batch test report of the
manufacturer for each batch of paints supplied shall be made available by the contractor.
2.14
2.15
Documentation:
The following documents shall be complied and forwarded to consultant. This shall be equipment wise/
line wise:
a.
b.
c.
d.
e.
Doc. No.
Revision No.
f.
g.
h.
Check List
i.
j.
k.
l.
Factory Location
m.
Date of manufacturer
n.
Batch No.
o.
Product Name
p.
Drying Time
q.
Hold up Property
r.
Glossiness
s.
Specific Gravity
t.
Viscosity
u.
Generic Name
v.
Key Composition
Resin
Pigments
Curing Agent
Solvent Name
w.
Density
x.
Fineness
y.
Colour
Doc. No.
Revision No.
z.
Date of Expiry
aa.
Pot Life
Doc. No.
Revision No.
Dry film
thk.
Description
Max.
Humidity
Temp.
High
Temp. Low
35
85%
45oC
10oC
35
85%
45 C
10 C
PRIMER
01
II
INTERMEDIATE COAT
02
III
FINAL COAT
03
35
85%
45oC
10oC
04
100
85%
45oC
10oC
Sr.
No.
Description of Surface
01
II Coat
III Coat
Final
Coat
Total DFT
(SHOP)
(FIELD)
120
02
Piping System
120
03
Tanks
120
04
100
Remarks
Doc. No.
Revision No.
Contents
Tankages
Colour
Light brown
2.1
Light grey
2.2
Light grey
2.3
Contents
Ground Colour
Second Colour
Band
WATER
1
Cooling
Sea green
French blue
Sea green
Gulf red
Condensate
Sea green
Light brown
Drinking
Sea green
French blue
Signal red
Treated
Sea green
Light orange
Fire water
Fire red
Crimson red
French blue
Canary yellow
Domestic, hot
Sea green
Light grey
Sea green
White
10
Filtered water
Sea green
Light brown
11
Soft water
Sea green
Light brown
Signal red
Doc. No.
Revision No.
12
Chilled water
Sea green
Black
Canary yellow
13
Sea green
White
Signal red
14
Waste water
Sea green
Canary yellow
Signal red
AIR
15
Compressed, up
including 15 Kg/cm2
to
16
Plant air
Sky blue
Silver grey
17
Instrument air
Sky blue
French blue
18
Dry vacuum
White
19
Wet vacuum
White
Dark violet
20
Aluminium to IS 2339
Signal red
21
Aluminium to IS 2339
French blue
22
Aluminium to IS 2339
Gulf red
23
Aluminium to IS 2339
Canary yellow
24
Drainage
Black
OIL
25
Light Brown
Brilliant green
26
Light Brown
27
Furnace fuel
Light Brown
French blue
OTHERS
28
Ammonia
Canary Yellow
Dark violet
29
Chlorine
Canary Yellow
Dark violet
Light Orange
30
Acetylene
Canary Yellow
Service Brown
31
Freon
Canary Yellow
Light grey
Dark violet
Doc. No.
Revision No.
32
Nitrogen
Canary Yellow
Black
33
Oxygen
Canary Yellow
White
34
Ethylene Glycol
Brilliant green
35
Ethylene Di-chloride
Gulf red
36
Acetone
Black
37
Methanol
Deep buff
38
Sulphuric Acid
Dark violet
Brilliant green
Light orange
39
Hydrochloric Acid
Dark violet
Signal red
Light orange
40
Brine
Black
White
41
Mercury
Black
White
Brilliant green
Doc. No.
Revision No.
Pipe
100
50
100
25 mm
2 4
100
50
100
40 mm
6 16
D/2
80 mm
Doc. No.
Revision No.
100
50
50
50
25 mm
2 4
100
50
50
50
40 mm
6 16
D/2
D/2
80 mm
Pipe
400 Max.
200 Max.
G =
200 Max.
400 Max.
Doc. No.
Revision No.
Sketch 3 - With Primary & Secondary Colour Band With Direction By Arrows
J
100
50
25 mm
2 4
100
50
40 mm
6 16
D/2
80 mm
Pipe
Doc. No.
Revision No.
P/2
11-001-16-BBCIH
100
50
50
100
100
25 mm
2 4
100
50
50
100
100
40 mm
6 16
D/2
D/2
80 mm
Pipe
Doc. No.
Revision No.
3.0
PAINTING PROGRAMME
a.
Equipment and Piping Painting work is required to be completed within the time stipulated in the main
Contract.
b.
Key completion dates of various areas of work shall be specified at the time of award of Contract.
c.
The Site Planning Engineer of the Contractor shall be required to work out detailed erection programme
periodically as per completion requirements indicated by Consultant.
d.
The dates of completion for various milestones will be worked out by the Contractor jointly with the
Consultant. It will be the Contractors responsibility to execute the job totally as per agreed programme.
e.
Bi-monthly review meetings will be held at SITE to assess the progress and revise the schedule to ensure
completion as per Contract.
f.
Contractor mobilization to Site is to suit the completion targets and other than Force Majure, no excuses
for delay in completion is acceptable.
g.
The contract envisages liquidated damages (mentioned elsewhere in this document) for delay in
completion and the Contractor to bear the same in mind.
4.0
a.
- Annexure I
b.
- Annexure II
c.
- Annexure-III