PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 4 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-ILV-001

Service

Produced Water Line to Degasser

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 300#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
Hydrocarbon + Water

35C
Liquid

11
12

BKDD02-ME-0D-05-002
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

45.2 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
4.95 (VTC)
Standard
300# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

141.7 / 221.5 Bar-a


@ Normal Flow

0.2
37.2
36.9
16
907.5
0.91
8.087
0.88
22.49

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

1. VTC - Vendor to Confirm. VTA - Vendor to Advise.


2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.

5. All wetted material shall confirm to NACE MR 0175 / ISO 15156

@ Min. Flow

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

Notes :

4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PW-0001-A-B
Pipe Material

10

0.0435 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
45.2
-15 / 70
12.53
37.2
36.9
34
1001.4
1
2.174
0.74
18.04

2.394 (VTC)
VTC
85 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 5 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-LV-005

Service

Condensate Line to MP Separator

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 300#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
Hydrocarbon + Water

35C
Liquid

11
12

BKDD02-ME-0D-05-002
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

45.2 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
1.11 (VTC)
Standard
300# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

1. VTC - Vendor to Confirm. VTA - Vendor to Advise.


2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.

5. All wetted material shall confirm to NACE MR 0175 / ISO 15156

@ Min. Flow

62.77 / 71.7 Bar-a


@ Normal Flow

1.53
37.2
28.9
16
745.19
0.74
38.05
0.64
98.38

Notes :

4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PC-0002-A-B
Pipe Material

10

0.266 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
45.2
-15 / 70
2.18
37.2
28.9
30
725.99
0.723
38.13
0.52
103.02

0.372 (VTC)
VTC
85 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 6 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-PV-004

Service

Gas from MP Separator to FG System

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-05-003
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

15.8 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
2.41 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Open
316 SS
Open

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal %r (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

-51.14 / -37.62 C
@ Min. Flow

81.89 / 90.96 Bar-a


@ Normal Flow

4.62
12.8
9.35
42
3.61
0.723

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PG-0002-A-A
Pipe Material

10

0.01
20.98
0.99
1.26
0.025 (VTC)
VTC
50 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
15.8
70
50.13
12.8
4.53
28
8.28
0.74

0.01
21.58
0.97
1.28
0.313 (VTC)
VTC
50 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

MAK

CL

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 7 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-ILV-007

Service

Produced Water to Degasser

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
Hydrocarbon + Water

35C
Liquid

11
12

BKDD02-ME-0D-05-003
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

15.8 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
2.78 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

@ Min. Flow

135.3 / 221.3 Bar-a


@ Normal Flow

0.0016
8.3
8
14
899.7
0.894
0.4836
0.92
23.29

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PW-0003-A-A
Pipe Material

10

0.00094 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
15.8
70
0.05
3.4
3.1
42
994.19
0.994
0.3757
0.62
18.03

0.039 (VTC)
VTC
85 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 8 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-LV-012

Service

Condensate to LP Separator

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
Hydrocarbon + Water

35C
Liquid

11
12

BKDD02-ME-0D-05-003
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

15.8 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
1.11 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

@ Min. Flow

44.49 / 51.35 Bar-a


@ Normal Flow

1.33
8.3
8
13
768.8
0.765
9.283
0.91
113.72

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PC-0003-A-A
Pipe Material

10

0.479 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
15.8
70
1.99
8.3
8
28
746.48
0.744
9.238
0.67
118.41

0.706 (VTC)
VTC
85 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 9 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-PV-006

Service

Gas to Flare Header

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-05-004
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

6.9 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
5.6 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Open
316 SS
Open

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

167.1 / 178.5 C
@ Min. Flow

64.41 / 109.5 Bar-a


@ Normal Flow

8.9
3
2.7
98
2.35
1.81

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PG-0018-A-A-P
Pipe Material

10

0.01
52.58
0.99
1.1
0.242 (VTC)
VTC
50 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
6.9
100
69.18
3
2.7
70
2.71
1.93

0.01
55.66
0.98
1.1
2.289 (VTC)
VTC
65.2 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 10 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-LV-015

Service

Condensate to Condensate Storage Tank

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Liquid

11
12

BKDD02-ME-0D-05-006
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

6.9 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
2.78 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

@ Min. Flow

31.27 / 38.67 Bar-a


@ Normal Flow

1.26
3
0.8
72
899.7
0.74
0.799
0.55
133.84

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PC-0013-A-A
Pipe Material

10

0.743 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
6.9
100
2.2
3
0.8
88
757.05
0.74
0.6392
0.6
157.83

1.228 (VTC)
VTC
85 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 11 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-PV-023

Service

Condensate Pump Discharge Pressure

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
HC + Condensate

35C
Liquid

11
12

BKDD02-ME-0D-05-005
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

6.9 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
2.78 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Open
316 SS
Open

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

@ Min. Flow

31.27 Bar-a
@ Normal Flow

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

@ Max. Flow
6.9
100

3
3
2.7
88
785.93
0.743
1.351
0.59
157.83

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PC-0044-A-A
Pipe Material

10

57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

1.533 (VTC)
VTC
85 dBA (VTC)
Outlet
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Gauges
Yes
Required
M20
Model
Fisher or Equal
VTA
NA

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 12 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-PV-009

Service

Gas to Flare Header

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-05-007
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

6.9 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
0.93 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Open
316 SS
Open

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

19.99 / 58.93 C
@ Min. Flow

115.8 / 142.1 Bar-a


@ Normal Flow

0.08455
3
2.7
42
1.57
1.02

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PG-0021-A-A
Pipe Material

10

0.01
29.7
0.99
1.21
0.003 (VTC)
VTC
50 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
6.9
70
1.86
3
2.7
31
2.27
1.44

0.01
41.83
0.99
1.2
0.044 (VTC)
VTC
50 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

MAK

CL

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 13 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-LV-016

Service

Produced Water to Storage Tank

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
Water

35C
Liquid

11
12

BKDD02-ME-0D-05-022
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

6.9 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
13.4 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

@ Min. Flow

141.5 / 221.3 Bar-a


@ Normal Flow

0.21
3.9
0.8
19
905.31
0.91
0.8026
0.83
23.48

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-PW-0011-A-A
Pipe Material

10

0.135 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
6.9
70
10.24
3.9
0.8
42
994.31
0.994
0.3756
0.62
18.02

7.368 (VTC)
VTC
85 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 14 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

21-PV-009

Service

Condensate Transfer Pump Discharge Pressure

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
HC + Condensate

35C
Liquid

11
12

BKDD02-ME-0D-05-017
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

6.9 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
3"
25.7 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Open
316 SS
Open

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

31.27 Bar-a
@ Normal Flow
6.9
93
31.8
5.6
4.5
33
785.89
0.786
0.6392
1.25
157.83

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

4"-PC-0046-A-A
Pipe Material

10

57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

15.57 (VTC)
VTC
85 dBA (VTC)
Outlet
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Gauges
Yes
Required
M20
Model
Fisher or Equal
VTA
NA

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 15 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

27-PV-001A

Service

Gas Pressure at Outlet of Sales Gas Super Heater

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 300#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

Gas

11
12

BKDD02-ME-0D-05-011
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

45.2 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
4"
175.02 (VTC)
Standard
300# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

-65.48 / -64.72 C
@ Min. Flow

64.37 / 64.85 Bar-a


@ Normal Flow

20550
35.9
1.4
24
30.5
0.64

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

6"-PG-0010-A-B-P
Pipe Material

10

0.01
18.51
0.91
1.42
32.81 (VTC)
VTC
62.3 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
45.2
90
26227
35.9
1.4
66
26.16
0.65

0.01
18.79
0.93
1.36
136.16 (VTC)
VTC
75.2 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 16 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

27-PV-001B

Service

Gas Pressure at Outlet of Sales Gas Super Heater

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 300#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-05-011
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

45.2 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
4"
175.02 (VTC)
Standard
300# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

-65.48 / -64.72 C
@ Min. Flow

64.37 / 64.85 Bar-a


@ Normal Flow

20550
35.9
1.4
24
30.5
0.64

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

6"-PG-0010-A-B-P
Pipe Material

10

0.01
18.51
0.91
1.42
32.81 (VTC)
VTC
62.3 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
45.2
90
26227
35.9
1.4
66
26.16
0.65

0.01
18.79
0.93
1.36
136.16 (VTC)
VTC
75.2 dBA (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 17 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

21-PV-001A

Service

Blanket Gas to Condensate Storage Tank A

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-05-016 SHT 1/2


EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

15.1 Barg
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
5.92 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
mmH2O
mmH2O
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-FG-0029-A-A-P
Pipe Material

10

-67.97 / -63.46 C
@ Min. Flow

30.66
77498
77454
31
6.8
0.66
0.01
19.5
0.98
1.29
1.653 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

60.89 / 65.47 Bar-a


@ Max. Flow
15.1
93
306.65
77498
77454
31
6.8
0.66
0.01
19.5
0.98
1.29
2.688 (VTC)
VTC
85 dBA (VTC)
Outlet
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Gauges
Yes
Required
M20
Model
Fisher or Equal
VTA
NA

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 18 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

21-PV-001B

Service

Blanket Gas to Condensate Storage Tank B

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-05-016 SHT 2/2


EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

15.1 Barg
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
5.92 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
mmH2O
mmH2O
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-FG-0023-A-A-P
Pipe Material

10

-67.97 / -63.46 C
@ Min. Flow

30.66
77498
77454
31
6.8
0.66
0.01
19.5
0.98
1.29
1.653 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

60.89 / 65.47 Bar-a


@ Max. Flow
15.1
93
306.65
77498
77454
31
6.8
0.66
0.01
19.5
0.98
1.29
2.688 (VTC)
VTC
85 dBA (VTC)
Outlet
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Gauges
Yes
Required
M20
Model
Fisher or Equal
VTA
NA

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 19 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-PV-013A

Service

Blanket Gas to Produce Water Storage Tank A

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-05-019 SHT 1/2


EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

15.1 Barg
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
5.92 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
mmH2O
mmH2O
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-FG-0024-A-A-P
Pipe Material

10

-67.97 / -63.46 C
@ Min. Flow

30.66
77498
77454
31
6.8
0.66
0.01
19.5
0.98
1.29
1.659 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

60.89 / 65.47 Bar-a


@ Max. Flow
15.1
93
306.65
77498
77454
31
6.8
0.66
0.01
19.5
0.98
1.29
2.708 (VTC)
VTC
85 dBA (VTC)
Outlet
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Gauges
Yes
Required
M20
Model
Fisher or Equal
VTA
NA

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 20 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-PV-013B

Service

Blanket Gas to Produce Water Storage Tank B

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-05-019 SHT 2/2


EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

15.1 Barg
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
5.92 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
mmH2O
mmH2O
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-FG-0026-A-A-P
Pipe Material

10

-67.97 / -63.46 C
@ Min. Flow

30.66
77498
77454
31
6.8
0.66
0.01
19.5
0.98
1.29
1.659 (VTC)
VTC
85 dBA (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

60.89 / 65.47 Bar-a


@ Max. Flow
15.1
93
306.65
77498
77454
31
6.8
0.66

@ Max. Flow
15.1
93

0.01
19.5
0.98
1.29
2.708 (VTC)
VTC
85 dBA (VTC)
Outlet
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Gauges
Yes
Required
M20
Model
Fisher or Equal
VTA
NA

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 21 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-PV-016

Service

Water Re-Injection Pump Discharge Flow

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

4"-WI-0007-A-B
Pipe Material

ASME Class 300#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
Water

35C
Liquid

10
11
12

BKDD02-ME-0D-05-020
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

45.2 Bar-g
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
2"
6.33 (VTC)
Standard
300# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

@ Min. Flow

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

221.3 Bar-a
@ Max. Flow
45.2
93
20
39.9
38.5
43
995.16
0.995
0.3854
0.62
18.02

3.642 (VTC)
VTC
85 dBA (VTC)

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 22 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

20-PV-020

Service

Produced Water Transfer Pump Recycle Flow

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

3"-PC-0048-A-A
Pipe Material

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
Water

35C
Liquid

10
11
12

BKDD02-ME-0D-05-022
EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

6.9 Barg
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
13.4 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Open
316 SS
Open

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

@ Min. Flow

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

221.3 Bar-a
@ Max. Flow
6.9
70
10.4
3.9
3.5
42
994.31
0.994
0.3756
0.62
18.02

6.092 (VTC)
VTC
85 dBA (VTC)

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 23 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

60-PV-001A

Service

Fuel Gas Inlet to Fuel Gas Scrubber

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-06-001 SHT 1/2


EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

45.2 Barg
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1 1/2"
24.20 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

-65.48 / -64.78 C
@ Min. Flow

64.37 / 65.20 Bar-a


@ Normal Flow

2116.87
36.5
28.2
9
8.68
0.65

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

3"-FG-0001-A-A
Pipe Material

10

0.01
19.65
0.96
1.47
4.095 (VTC)
VTC
82.6 (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
45.2
70
4137.47
36.5
22.7
47
11.51
0.66

0.01
19.21
0.96
1.4
8.531 (VTC)
VTC
85.9 (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 24 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

60-PV-001B

Service

Fuel Gas Inlet to Fuel Gas Scrubber

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P
Critical Temp.

Min.
State

Max.

23.3 C
Hydrocarbon

35C
Gas

11
12

BKDD02-ME-0D-06-001 SHT 1/2


EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

45.2 Barg
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1 1/2"
24.20 (VTC)
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

Bar-g
C
Sm3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

dBA
ASTM A216 Gr. WCB

VTC
Equal % (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

-65.48 / -64.78 C
@ Min. Flow

64.37 / 65.20 Bar-a


@ Normal Flow

2116.87
36.5
28.2
9
8.68
0.65

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

Notes :
1. VTC - Vendor to Confirm. VTA - Vendor to Advise.
2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.
4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

3"-FG-0001-A-A
Pipe Material

10

0.01
19.65
0.96
1.47
4.095 (VTC)
VTC
82.6 (VTC)
57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

Outlet
Gauges
Model

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

@ Max. Flow
45.2
70
4137.47
36.5
22.7
47
11.51
0.66

0.01
19.21
0.96
1.4
8.531 (VTC)
VTC
85.9 (VTC)
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Yes
Required
M20
Fisher or Equal
VTA
NA

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS

CONTROL VALVE
REV

DATE

3-Jun-13

BY
NNS

CH

APP

MKR

CL

MAK

REVISION
AFD

PROJECT NAME

KERENDAN GAS FACILITIES

JOB NO

21178

SPECIFICATION NO

REQUSITION NO

DATA SHEET NO

BKDD00-ME-4M-87-001

REV. NO

CONTROL VALVE DATA SHEET


APPLICABLE TO:
FOR
SITE

Page 25 of 25
PURCHASE

INQUIRY

AS BUILT

SALAMANDER ENERGY (BANGKANAI) LTD.


BANGKANAI, CENTRAL KALIMANTAN

Tag Number

60-LV-001

Service

Condensate from Fuel Gas Scrubber to Closed Drain

Line/Equipment No.

Pipe Class
Noise Level

GENERAL

Qty :

ASME Class 150#


85 dBA

CS

P&ID Number

Hazardous Area Classification

Available Air Supply Pr.

Min.

Max.

5 Bar-g

10 Bar-g

Ambient Temperature
Fluid
Corrosive / Erosive / Toxic Components
Max.Shut off D/P

Min.
State

Max.

23.3 C
HC + Water

35C
Liquid

11
12

BKDD02-ME-0D-06-001 SHT 1/2


EEx"d" Zone 2, Gr. IIA, T3 , IP65

Critical Pressure

15.1 Barg
Units

13
14
15
16
17
18

PROCESS CONDITIONS

19
20
21
22
23
24
25
26
27
28

CALCULATED RESULT

29
30
31
32
33
34
35
36
37
38

BODY AND TRIM

39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56

ACTUATOR

Design Pressure
Design Temperature
Flow Rate
Inlet Pressure
Pressure Drop
Inlet Temperature
Density
Specific Gravity
Inlet Vapor Pressure
Viscosity
Molecular Weight
Compressibility Factor
Specific Heat Ratio (Cp/Cv)
Flow Coefficient CV
Travel
Sound Pressure Level
Body Type
Material
Body Size
Trim Size
Rated CV
Characteristic
Bonnet Type
Material
Connection Rating
Plug Balance
Flow Direction
Flow Action To
Rated FL / XT
Guiding
No.of Ports
Trim Type
Rated Travel
Plug /Ball /Disc Material
Seat Material
Seal Material
Cage
Stem Material
Gasket Material
Packing Material
Type
Size
Instrument Air Supply min/nor/max
Air Failure Action
Material
Signal Failure
Stroke Speed

Globe
1"
1.90 (VTC)
D
Standard
150# ANSI RF
VTC
VTC
Open
VTC
Cage
Single Seated
VTC
316 SS
410SS
316 SS
Note 3
PTFE
Spring Diaph.
5 / 7 /10 Bar-g
Close
316 SS
Close

Handwheel

No

Travel Indicator
Orientation
Req. Air Supply Pressure
Actuator Force Design Pressure
Manufacture
Model

Yes
VTA
0.2 - 1.0 Bar-g

Top

Fisher or Equals

VTA

36.65 Bar-a
@ Normal Flow

0.448
8.274
7.5
21
753
0.753
8.254
0.845
112.47

dBA
ASTM A216 Gr. WCB

VTC
Linear (VTA)

POSITIONER

ASTM A216 Gr. WCB

SOLENOID
VALVE

Teflon Seal
316 SS

VTC

SWITCHES

AIR SET

PAINT
FILTER /
REGULATOR

5-10 Sec.
TEST

PURCHASE

1. VTC - Vendor to Confirm. VTA - Vendor to Advise.


2. Vendor to Submit Control Valve Sizing calculation for approval.
3. Gasket shall be Spiral Wound 316L SS with Flexible Graphite filler CS inner & Outer Rings "FLEXITALLIC" style CGI or approved equal.

5. On/Off application. Vendor to advise on valve flow characteristics.

@ Min. Flow

Bar-g
C
m3/h
Bar-g
Bar
C
Kg/m3
-Bar-a
cP
----

Notes :

4. Painting shall be as per Spec. no. BKDD00-ME-1L-00-052

Ea

2"-FG-0009-A-A
Pipe Material

10

57 Signal : Inlet
58 Type
59 Bypass
60 Electrical Connection
61 MFC
62 Type
63 When De-Enegr Valve
64 Electrical Connection
65 Type
66 Contacts / Rating
67 Switching Position
68 Electrical Connection
69 Set Pressure
70 Filter
71 Air Connection
72 Make
73 Body
74 Actuator
75 Air Tube Material
76 Fitting Type
77 Min.Size & Connection
78 Hydrostatic Pressure

@ Max. Flow
15.1
60
1.39
13.79
12.79
36
726
0.72
0.5

0.2924 (VTC)
0.819 (VTC)
VTC
VTC
85 dBA (VTC)
85 dBA (VTC)
Outlet
4-20mA(HART)
0.2-1. Bar-g
Smart ElectroPneumatic
Gauges
Yes
Required
M20
Model
Fisher or Equal
VTA
NA

Qty.

Gauges
Model
Yoke
Handwheel
Size
Material

NA

4 Bar-g
5 micron
1/4" NPTF
Fisher or Equal
Note 4
Note 4
316 SS
Swagelok Type
1/2" NPTF
Yes

79 Visual

Yes

80 ANSI / FCI Leakage Class


81 Manufacture
82 Model No.
83 Purchase No.

ANSI Class IV
Fisher or Equals
VTA

Yes
VTA
Note 4
NA
1/4"
316 SS