Professional Documents
Culture Documents
Department:
Kind Attn: Mr.M.S. Karthikumar
Insulation Degradation
There are 5 basic initiators for degradation of the insulation; electrical and mechanical stress,
chemical attack, thermal stress and environmental contamination. Normal cycles of operation will
lead to 'aging' through these mechanisms. The aging of insulation is a slow process of degradation
as these factors interact with each other in a gradual spiral of decline.
The rate of this insulation deterioration is of increasing interest to engineers dealing with electrical
supply networks such as those in Europe and the USA, where large parts of the network were
installed 30 or 40 years ago in a burst of investment in the infrastructure.
Testing
As insulation deteriorates leakage current may increase, the dielectric loss characteristic will
change and the degree of polarisation will alter. Insulation tests look for a change in one of these
responses to indicate the deterioration.
'Spot' Test
This is the simplest insulation test, giving a reading of Insulation Resistance in M. The test is
applied for a short, but specific period of time, after which a reading is taken. The time is typically
60 seconds (allowing the capacitive charging current to reduce).
On installation of the equipment, these readings will be compared to the required minimum
specification. Insulation resistance is significantly temperature dependent and correction factors
can be applied to show a trend more clearly from a history of insulation tests.
Rcorrected = Kt x Rtest
where Kt,, the compensation factor, doubles for each 10C rise
Capacitive Current
This is initially large, but goes to zero as the test piece is charged.
Polarisation Current
Caused by charges in the insulation material moving under the effect of the electric field or by
molecular di-poles lining themselves up with the applied field (orientational polarisation). It is greatly
affected by moisture or contamination in the insulation, as the water molecule has additional
orientational polarisation. This process takes much longer than the capacitive charging.
Leakage current
Steady (resistive) current through the insulation, which is usually represented by a very high
resistor in parallel with the capacitance of the insulation.
Figure 1. Insulation Test Currents
It is immediately apparent that the Insulation Resistance reading is time dependent. In general, it is mainly the
capacitive current that is seen in the first seconds after the test
is started, as the needle on your MEGGER(r) Insulation Tester climbs. Then, at the one minute period most
commonly used for a 'spot' test, the current is a combination of polarisation & leakage current. By 10 minutes
you are reading mainly leakage current, though it can take up to 30 minutes for polarisation effects to be
complete.
Discharge Currents
During the discharge phase the reverse occurs with the exception of the leakage current. There is
no test voltage so the leakage current is insignificant. The capacitive current decays quickly and
the re-absorption current takes several minutes, and perhaps hours, to reduce to zero.
10 minute
DAR
60 seconds
TC
Resistance x
DD
Discharge current (at
Poor
Questionable
OK
Good
1 minute
<1
1 to 2
2 to 4
> 4
15 seconds
<1
1 to 1.4
1.4 to 1.6
> 1.6
Capacitance
60 s)/(V x C)
<100
100 to 800
800 to 2000
>2000
>4
2 to 4
<2
These values can give a guide to condition of insulation, although the figures are better interpreted
in the context of the equipment history. If a PI falls by 30% or more, then remedial action such as
cleaning, or further investigation, should be considered.
(mA/V/F)
The Dielectric Discharge can identify absorbed moisture in an insulation as this affects the
absorption behaviour of the dielectric and is masked by leakage effects if we try to measure it on
the charging cycle.
The use of an a.c. source (often 2.5 or 10 kV) makes the Power Factor test set heavier and more
expensive than a d.c. tester. Also there is a limit to the capacitance that can be tested, but the early
warning given by monitoring this parameter makes it invaluable.
Summary
Diagnostic insulation tests allow more information to be gained from an insulation test which may
prove invaluable in a maintenance program. An a.c. test also provides early information that can
point to future insulation problems. Each type of test helps to give a more complete picture of the
condition of the insulation.
Table 2.
d.c.
charging
tests
d.c.
discharge
tests
Test Type
Definition
Insulation Resistance
(Spot test)
Polarisation Index (PI)
Dielectric Absorption
Ratio (DAR)
Time Constant
Step Voltage (SV)
Dielectric Discharge
(DD)
Recovery Voltage
/Polarisation Spectrum
Analysis
Isothermal Relaxation
Current Analysis
EDA Test
Flash (Hi-Pot)
Partial Discharge
a.c. tests
Power Factor/'Tan
Delta'
VLF (Very Low
Frequency)
Best Regards
Ajay Goyal
International Regional Manager - Southern Asia
P.O.Box No.12052 Mumbai - 400 053
T + 91 22 2631 5114. (Direct)
F + 91 22 2632 8004.
M + 91 9820300932.
E ajay.goyal@megger.com
www.megger.com
Megger
Application
The information contained in this electronic mail message is confidential. It is intended solely for the use
of the individual or entity to whom it is addressed and others authorised to receive it. If the reader of this
message is not the intended recipient, you are hereby notified that any use, copying, dissemination or
disclosure of this information is strictly prohibited.