You are on page 1of 16

Topic: Reinforced Concrete (II)- Design in RC Beam and slab-2;

Design in Column.

Shear force in concrete beam

In the previous notes, the bending force in the beam has been discussed. However,
when the beam in loaded, it is also subjected to the shear force. Since shear is usually
associated with tensile stress and since also concrete is not strong in tension,
additional reinforcement would also be required to resist the effect of the shear force.

(1) Shear stress in the concrete

Shear stress in a concrete beam is determined as:


V
v=
b⋅d
where V is the shear force at the section under consideration,
v is the shear stress
b is the width of the beam
d is the effective depth of the beam

Concrete has some shear resisting capacity, v c , and this capacity is not a constant
value; rather it is a function of amount of bending reinforcement used and the
effective depth of the beam as shown in the table below: (Table 1)

-Page 1-
November 2006
Table 1:- Values of v c , design concrete shear stress (for f cu = 25 N / mm 2 )

(2) Shear Reinforcement


Shear reinforcement in beam is usually provided in the form of link (or stirrup in US
terms). Once the size (diameter) of the link is determined, its spacing s v can be
determined as below:-

-Page 2-
November 2006
Asv ⋅ 0.87 f yv
sv =
b(v − vc )

Shear resistance of the beam is:

⎛A ⎞
v ⋅ bd = ⎜⎜ sv 0.87 f yv + bvc ⎟⎟ ⋅ d
⎝ sv ⎠

where V is total shear resistance stress of the beam


Asv is the area of shear reinforcement
sv is the spacing of shear reinforcement
fyv is the strength of shear reinforcement
vc Is the shear resistance strength of concrete
b is the width of beam
d is the effective depth of beam

In most case, links are made of mild steel (fyv=250N/mm2) mainly because the amount
of bending required to form a link. Links are also used at locations where the shear
stress due to the applied load is less than shear resistance of the concrete; it is used to
tie the reinforcing steel together.

On the other hand, it should be noted that maximum shear stress in a beam can not

exceed 0.8 f cu or 5N/mm2 regardless of shear reinforcement is provided. If shear

stress is greater than this value, the size of beam has to be increased. The shear
reinforcement in BS8110 is as shown in Table 2.

-Page 3-
November 2006
Table 2:- Form and area of shear reinforcement in beams

Example:- Design for Shear Reinforcement (refer to Lecture 3 Example 2)


Maximum Shear Stress at the support
V 66.6 x10 3
v= = = 1.02 N / mm 2
b ⋅ d 210 x310

As (steel area) near the support is 1890/2 = 945mm2

-Page 4-
November 2006
Remarks

Design Concrete Shear Stress (vc ) - (using the formula from Table 1)

vc = 0.79(100 As / bv d ) (400 / d ) 4 / γ m
1 1
3

= 0.79[(100 x945) / (210 x310 )] 3 [400 / 310] 4 / 1.25


1 1

→ vc = 0.74 N / mm 2

Refer to Table 2,

0.5vc = 0.5(0.74) = 0.37 N / mm 2


vc + 0.4 = 0.74 + 0.4 = 1.14 N / mm 2
0.8( f cu ) = 0.8( f cu ) = 0.8(25)
1 1 1
2 2 2 = 4 N / mm 2

0.5vc < v < vc + 0.4

0.37 < 1.023 < 1.14

-Page 5-
November 2006
From Table 2, minimum links should be provided for the whole length of the Beam
And providing 8mm diameter TWO-Leg vertical Links or stirrups (Grade 250 steel)

(Area of links, Asy = 2(π / 4 ) ⋅ 8 2 = 100mm 2 )

0.4bv s v
As y >
0.87 f y

Then spacing of the vertical links (or stirrups), s v < Asy 0.87 f y / 0.4bv

< 100(0.87 )(250 ) / 0.4(250 )


= 259mm

Or by table (extracted from BS8110)

However, spacing of Links should be < 0.75d = 0.75 x 330 = 247mm

Then, for the shear reinforcement, providing 8mm diameter links at a spacing of
240mm for the whole length of the beam.

Other issues concerned in reinforced concrete design

(1) Bond
It is very important that steel and concrete work together to form the material called
reinforced concrete. This is achieved by the property call the bond between steel and
concrete. One of the assumptions in reinforced concrete design is that perfect bond
must exist between steel and concrete.

-Page 6-
November 2006
(2) Deflection
This provision in the BS code is to ensure the serviceability of the structure to be
maintained. It is often found that a much shallower member may be used from
strength point of view. However, to avoid excessive deflection, much deeper member
could be required. The tabulated value has including also the creep and shrinkage
effects of concrete under sustained load condition.

Table 3:- Permissible value of span/depth ratio beams and slabs

(3) Minimum reinforcement areas


Thermal and shrinkage cracking may be controlled within acceptable limits by use of
minimum reinforcement quantities specified by BS8110 for general structures except
water-retaining structures. The principle requirements for rectangular section are
summarized as Table 4.

-Page 7-
November 2006
Table 4:- Minimum Reinforcement Areas

(4) Cover
Subject to fire resistance requirements or Code of Practise: Fire Resistance
Construction 1995 (issued by Buildings Department, HKSAR), reinforcement should
have concrete cover and the thickness of such cover (exclusive of plaster or other
decorative finish) should be:
(a) for each end of a reinforcing bar, not les than 25mm nor less than 2 times the
diameter of such bar;
(b) for a longitudinal reinforcing bar in a beam, not less than 25mm nor less than the
diameter of such bar;
(c) for any other reinforcement not less than 15mm nor less than the diameter of such
reinforcement.

-Page 8-
November 2006
Table 5:-Fire resistance Requirement for Columns and Beams (Extract from
COP fire resistance constriction 1995, issued by Buildings Department, HKSAR)

-Page 9-
November 2006
(5) Distance between reinforcement bars

The horizontal distance between two parallel steel reinforcements in reinforced


concrete should usually, except at splices, be not less than the greatest of three
following distances:-
(a) the diameter of either bar if their diameter be equals;
(b) the diameter of the larger bar if their diameters be unequal;
(c) 5mm more than the nominal maximum size of the coarse aggregate used in the
concrete.

A greater distance should be provided where convenient. Where immersion vibrators


are intended to be used, however, the horizontal distance between bars of a group may
be reduced to 2/3 of the nominal maximum size of the coarse aggregate provided that
a sufficient space is left between groups of bars to enable the vibrator to be inserted;
this would normally be a space of 75mm.

The vertical distance between two horizontal main steel reinforcements, or the
corresponding distance at right angles to two inclined main steel reinforcements,
should not less than 15 mm or the nominal size of aggregate, whichever is the greater,
except at splices or where one of such reinforcement is transverse to the other.

(6) Maximum reinforcement areas


An excessive amount of reinforcement usually indicates that a section is undersized
and it may cause difficulty in steel fixing and concreting. Consequently, it results poor
compaction of the concrete around reinforcement. The maximum reinforcement area
specified in BS 8110 is summarized below:-

Table 6:- Maximum Reinforcement Areas

-Page 10-
November 2006
Reinforced Concrete Columns
In most reinforced concrete buildings, the load on the building is eventually
transmitted by columns to the building foundation. Concrete columns can have any
shape. However, in most buildings, concrete column are either square or round or
rectangular.

Relative to design of beams, column design is more complex. Unlike beam, columns
can be subjected to both compression and bending simultaneously which will make
the analysis more difficult. In addition since columns are not supported along it height,
columns could deflect sideways which in combining with the compressive load will
cause additional bending. Since the deflection is a function of column height and
dimension and the supporting condition at both column ends, load carrying capacity
of two columns with the same reinforcement can be very different.

Columns can be braced and unbraced


A braced column in given direction is one where deflection at the ends of that column
is complete eliminated by structural elements such as wall or bracing.

An braced column is given direction is one where the ends of column can moved
laterally with respect to other. therefore, in a building where the lateral force, such as
wind load is resisted by walls or lift shaft, the column in that building are regarded as
braced column. Column in Figure 1 are Unbraced column whereas those in Figure 2
and Figure 3 are Braced column.

Figure 1 Figure 2 Figure 3

-Page 11-
November 2006
Long Column and Short column
Columns of the same size could behave quite differently under the same loading if the
conditions at the ends of column are different. Since columns are structural elements
which support direct compression, their mode of failure could be different to other
types of structural elements, such as beams. Column, especially the slender one
(slender means long and thin) frequently failed by buckling rather than by material
failure like beams. Long column will fail by buckling before material reaches it
ultimate capacity. To define whether a column is a long column, the effective length of
a column must be considered.

Effective length
The effective length, LC , of column can be defined as the height of a column that
may be considered equal to the height of similar column with pin pinned ends. The
effective length of columns with different end conditions is as shown in the Figure 4.
below.

Figure 4

A column is classified as a short column if the ratio of effective length to the


dimension of the column, in both directions, is less than 15 in a braced column and
less than 10 in an unbraced column.

Since the column in multi-storey buildings do not have exactly pinned or fixed ends,
the end conditions are determined based on the number and size of beams connected
to that column; the bigger the beams connecting to the column at the top and bottom,
-Page 12-
November 2006
the more the ends like “fixed” and similarly for the number of beams.

Since detailed discussion of column is beyond the scope of this module, only design
braced short column will be discussed in this lecture.

Design of short square columns – Short Braced Axially Loaded Column


This type of column is very common in current precast concrete construction. The
maximum a column can carry is:

N = 0.4 xf cu xAc + 0.75 f y Asc

For rectangular column, the area of concrete can be allowed to be displaced by the
longitudinal reinforcement, the above equation may be modified to:

N = 0.4 f cu bh + Asc (0.75 f y − 0.40 f cu )

where N is ultimate axial load


fcu is the characteristic strength of concrete
Ac is the area of concrete
Asc is the area of longitudinal steel
fy is the characteristic strength of the steel
B is the size of the column

Reinforcement details
The rule governing the minimum and maximum amount of reinforcement are as
follow:-
Longitudinal Steel:
(a) a minimum of four bars is required for a rectangular column (and six bars for a
circular column)
100 As
(b) ≥ 0.4 where As is the total area of longitudinal steel and Acol is the
Acol
cross-section area of the column.

Links:
When the longitudinal bars in a column are subjected to compressive load, they tend
to buckle. To prevent the buckling of main steel which could lead to premature failure,
links are provided to tie these longitudinal bars according to the following rules:

-Page 13-
November 2006
(a) minimum size should be one quarter of the largest bar but not less than 6mm;
(b) maximum spacing equal to 12 times the smallest size of main bars
(c) the links should be arranged so that every corner bar and alternate bar or group in
an outer layer of longitudinal steel is supported by a link passing round the bar
and having an inclined angle of not greater than 135 degree;
(d) all other bars or groups not restrained by a link should be within 150mm of a
restrained bar.

The arrangement of links in columns is shown in the following figures.

Figure 5

-Page 14-
November 2006
Figure 6

Other considerations
In the design of column, it should be bear in mind the sequence of constructing
columns in the field. The space of bars should not be too close to allow room for
concrete be placed and vibrated. The size of column and the cover thickness is also
governed by the Code of Practise Fire Resistance Period.

Example – Axially Loaded Column


Design the longitudinal reinforcement for a 300mm square column which supports an
axial load of 1700kN at the ultimate limit state. The characteristic material strength

f y = 460 N / mm 2 for the reinforcement and f cu = 30 N / mm 2 for the concrete.

-Page 15-
November 2006
Solution:

N = 0.4 f cu bh + Asc (0.75 f y − 0.40 f cu )

1700 x10 3 = 0.4 x30 x300 2 + Asc (0.75 x 460 − 0.4 x30)

Therefore, Asc =
(1700 − 1080) ⋅ 10 3 = 1892mm 2
333

Provide four T25 bars, area = 1960mm2

-End-

-Page 16-
November 2006

You might also like