GB162 Series

Wall-Hung Gas Condensing Boiler

Compact & Powerful

Designed for Stand-Alone or Cascades

Ultra-High Efficiencies up to 96% with Low Flue Gas Emissions

Ideal for Smaller Commercial Buildings and Large Residences

Unique Manifold for Easy Installation of Single Units or Cascades

Innovative ALU-plus Condensing Heat Exchanger for Long Life and Easy Servicing

Modulation Ranging from 20% to 100%

2 Models with 290 MBH and 333 MBH Input, Cascades up to 2,664 MBH

Comfortable. Efficient. Intelligent Heating.


The GB162 Series—Good Things Come in Small Packages
The GB162 is a high-performance, compact gas condensing boiler capable of Outstanding Efficiency
achieving ultra-high efficiency levels of 96%. GB162 boilers are available with
individual inputs of 290 MBH or 333 MBH. Each boiler, though, is capable of The GB162 is capable of achieving
modulating down to just 69 MBH when used with natural gas. This ensures that efficiencies of up to 96%. This is due,
efficiency is maintained throughout the year, even when the demand for heat is in part, to its patented, extremely
low. Optimum performance minimizes energy usage and is achieved in the GB162 efficient, aluminum silicate ALU-Plus
through the large, aluminum ALU-Plus heat exchanger, an advanced Energy heat exchanger, but also because
Management System, and by encouraging the condensing process. our advanced Energy Management
System encourages the GB162 to
With systems designed to operate at 190ºF–122ºF, the GB162 can remain in remain in condensing mode.
condensing mode as much as possible, providing energy savings year-round. In
addition to ensuring optimal condensing performance through comprehensive Condensing technology has long been
heating system control, the advanced Energy Management System (EMS) also used in Europe. By condensing the
ensures minimal energy usage, and reduced emissions. water vapor in the flue gases into liquid
water, the maximum amount of heat
Save Space and Energy from the fuel is captured.

The GB162 can be used individually in a residence or commercial operation, but it is


The condensing efficiencies of the
especially well suited for multi-boiler cascades. Typically linking together two to four
GB162 can also be combined with
boilers, cascades may be expanded up to 8 units to meet the required BTU load of
the benefits of a cascading system
the installation.
to ensure you receive every possible
With the GB162's small size, wall-hung attribute, and light weight—only 150 lbs bit of energy from the fuel you are
each—there is a great deal of flexibility in planning an installation. Not only is it burning.

easy to install as a single unit, but it is easy to install as a multi-boiler cascade. The
boilers can be configured back-to-back or in-line by using a simple frame. This is
especially useful when boiler rooms are small or unusually shaped. In fact, a 4-boiler
cascade, delivering over 1,000 MBH, can fit in less than 13 square feet of floor
space. This makes the GB162 ideal for new installations, as well as for replacing an
inefficient heating system and freeing up valuable commercial floor space.

The GB162 is also extremely quiet in operation, thanks to a number of acoustic


insulation measures and the low resistance on water flowing through the boiler.
Combine its compact size, wall-hung versatility, and quiet operation with its vertical or
horizontal venting options, and the GB162 makes heating system planning easier, as
it offers potential placement not just in a traditional boiler room.

ALU-Plus Modern Technology – Modern Efficiency


The Buderus GB162 wall-hung condensing boilers use an advanced, aluminum
ALU-Plus heat exchanger design. This lightweight heat exchanger has a number of
innovative features to prolong its life and increase the efficiency of the boiler. Fins
on the outside of the aluminum tube
increase the exterior surface area. This
means more hot flue gas comes into
contact with the heat exchanger to
maximize heat transfer. A spiral channel
on the inside of the tube increases
the internal surface area and creates
turbulence, bringing more water into
contact with the heating surface, also
ensuring optimal heat transfer. The surface of the heat exchanger tubes are treated
with a patented plasma-polymerization process that leaves the surface so smooth A Safe Economical Choice
that no deposits can adhere to it. In addition to also helping maintain extremely high
efficiency, this keeps the heat exchanger clean. Buderus manufactures with strict quality
procedures. This ensures that all our
Achieve Greater Efficiencies with a Cascade and Reduce Carbon Footprint boilers are fully tested at the factory
and are certified to meet rigorous
Energy efficiency is not just applicable to domestic boilers, even though that is
standards for safety, efficiency, and the
what we most often hear of. Boilers for commercial applications—from offices and
environment.
public buildings to hospitals, schools and colleges, multi-family dwellings, and sports
centers—also have a significant impact on our environment. Companies and owners At Buderus we use only the most reliable
of commercial properties are increasingly looking to improve or upgrade their boiler and efficient components in the design
rooms to maximize energy efficiency, but also to minimize their carbon emissions and and manufacture of our products. All
increase the value of the building. Buderus boilers are built to withstand
heavy and constant use. The GB162
Cascade systems, a relatively new development in heating technology, achieve is no exception. It benefits from the
significant energy savings because their output can be precisely controlled to very latest in high efficiency heating
match the demand for heating. technology with the patented, award
Each individual unit comes into winning ALU-Plus heat exchanger, and a
operation only when the demand is host of energy saving features.
high enough for an additional boiler
in the cascade to fire. A cascade
system adapts particularly well to Award-winning Design
seasonal temperature changes by
allowing heat output to be precisely The GB162 is the proud recipient of the
matched to heating demand whether 2008 iF Product Design award. Every
in summer or winter. year about 2,700 products from 35
countries are judged
The optional 4323 commercial
by renowned experts.
control handles up to 8 GB162
boilers and offers the flexibility to Only the best products
operate the cascade in either series receive the iF seal of
outstanding design
or parallel mode. In serial mode
quality. The iF seal is
the heat demand will fire the first
one the world’s three
boiler and, as load increases, it will
leading design awards.
continue to modulate to 100%. If the heating demand is not satisfied, the control will
It is an internationally
fire additional boilers in the same manner until the load or capacity is met. recognized trademark, recognizing its
To better conserve energy, the boiler cascade can also operate in parallel mode. recipient's place on the cutting edge of
contemporary design.
In parallel mode the first boiler would fire at 20% and, as the heat load increases,
additional boilers would fire at 20% until all boilers are operational. Once all the
boilers in the cascade are firing, the control collectively modulates all the boilers to
satisfy the load. Parallel mode enables the boilers to run at the lowest modulation
rate for the longest period of the heating cycle.

Optional controls also allow a cascade heating system to be configured so that


different zones can be operated with mixed temperature circuits and domestic hot
water priority. To ensure that the system always runs in the most efficient mode of
operation, this is all automatically controlled.
Straight Forward Installation
A single GB162 boiler comes complete with a pump group, wall mounting bracket, Easy Service and
and low loss header to expedite the assembly of the near boiler piping. Quiet Operation

For a multi-boiler cascade system, Buderus has all the necessary fittings and
The compact size and light weight
accessories to allow the installer to simply build the framework and join everything of the GB162 allows for ease of
together. Once the boilers are assembled, they are connected with the factory- installation, even where space is
supplied low-loss header and then covered with the pipe insulation. The result is an limited. A single push button door
easy installation where everything fits perfectly, all the piping is neat, and the boilers release allows access to all parts,
are ready to be connected to the main heating system. The combination of the low- including the heat exchanger, for
loss header and EMS control system ensures worry-free boiler flow rates. servicing. What could be easier?

A ceramic pre-mix burner and


modulating fan provide modulation to
20% of total output and the boiler is
so quiet that it can be located near
1st step: 2nd 1st
step:
step: 3rd step:
2nd step: 4th step:
3rd step: 4th step: living or working areas without causing
The sturdy floor Low-loss header,floor
The sturdy Individual
Low-loss header, GB162 Pump
Individual groups (additional
GB162 Pump groups (additional
standing cascade flow,standing
return and gas
cascade boilers
flow, return aregas
and mounted boilersaccessory) and valves are
are mounted
a disturbance.
accessory) and valves are
framework is pipesframework
are fitted. is securely
pipes are fitted.on the connected
securely on the to boilers and flow connected to boilers and flow
bolted together. bolted together. framework. and return pipe work attached and return pipe work attached
framework.
to the headers. to the headers.

1st step: 2nd1ststep:


step: 2nd step:3rd step: 3rd step:4th step: 4th step:
The sturdy floor Low-loss
The sturdyheader,
floor Low-lossIndividual
header, GB162 IndividualPump
GB162groups (additional Pump groups (additional
5th step: 5th step:
standing cascade flow, return and
standing gas
cascade flow, return
boilers
andaregasmounted boilers are
accessory)
mountedand valves are accessory) and valves are
Custom-fit insulation is Custom-fit insulation is
framework is pipes are fitted.
framework is pipes aresecurely
fitted. on the securely connected
on the to boilers and flow connected to boilers and flow
added to pipe work added to pipe work
bolted together. bolted together. framework. framework.and return pipe work attachedand return pipe work attached
and fitted around each and fitted around each
2nd step: 3rd step: 3rd step: 4th step: 4th step: to the headers. to the headers.
pump group to pump group to
Low-loss Individual
header, GB162 IndividualPump groups (additional
GB162 Pump groups (additional
minimise heat loss. minimise heat loss.
boilers
flow, return aregas
and mounted boilers accessory)
are mounted and valves are accessory) and valves are
pipes are securely
fitted. on the securelyconnected
on the to boilers and flow connected to boilers and flow
framework. framework.and return pipe work attached and return pipe work attached
5th step: 5th step:
to the headers. to the headers.
Custom-fit insulation is Custom-fit insulation is
added to pipe work added to pipe work
1st step: 2nd step: 3rd step:
and fitted around each 4th step:
and fitted around each
The sturdy floor Low-loss header, Individual GB162 Pump groups (additional
pump group to pump group to
2nd step: 1st step: 3rd
2nd step:
step: standing cascade 3rd
4threturn
flow, step:and gas 4th
boilers are step:
mounted accessory) and valves are
5th step: 5th step: framework is pipes aregroups
fitted. minimise heat loss. on the
securely minimise heat loss.
Low-loss header,
The sturdy floor Individual
Low-loss header,
GB162 Individual
Pump GB162(additional Pump groups (additionalconnected to boilers and flow
Custom-fit
flow, insulation
returnstanding
and is
gas cascade Custom-fit
boilers insulation
flow, return andisgas
bolted together.
are mounted boilers
accessory)are mounted
and valves are
framework.
accessory) and valves are
and return pipe work attached
added to the headers.
pipes aretofitted.
pipe work is
framework added to pipe
securely
pipes work
areon
fitted.
the securely
connected onto the
boilers and flow connected to boilers and flow
and fittedbolted
aroundtogether.
each and fitted around
framework. each framework.
and return pipe work attached and return pipe work attached
pump group to pump group to to the headers. to the headers.
minimise heat loss. minimise heat loss.
5th step:
Custom-fit insulation is
added to pipe work
2nd step: 3rd step: 4th step:
and fitted around each
Low-loss header, 5th step: Individual GB162
5th step: Pump
pump groups
group to (additional
Custom-fit insulation is minimise heat loss.
e flow, return and gas boilers are Custom-fit
mountedinsulation is accessory) and valves are
added to pipe work added to pipe work
pipes are fitted. securely on the connected to boilers and flow
and fitted around each and fitted around each
pump group to
framework.pump group to and return pipe work attached
minimise heat loss. minimise heat loss. to the headers.

5th step:
Custom-fit insulation is
added to pipe work
and fitted around each
pump group to
minimise heat loss.
Complete Your System
4000 Control
Once you have a Buderus boiler, you can add a Buderus indirect fired hot water
tank, or an optional Buderus control — or both. In addition to maximizing comfort
and fuel savings, optional Logamatic control will accommodate specialized heating
applications such as radiant flooring or multiple boilers. Multiple design innovations
increase the versatility of Buderus Logamatic controls. A Buderus boiler combined
with a Logamatic control produces a premium heating system that will provide
years of exceptional comfort and economy.
Optional integrated multi-boiler system
Buderus Controls controller with the following features and
Standard control modules:
AM10 weather compensation module included for single boiler installations
BC10 boiler control included with cascades Control of single and modulating burners
for up to 8 boilers with 4323 control
Options
RC35 control with automatic mode and adjustable programs Automatic and load/switch dependent
ensures energy-saving operation by reducing the room burner rotation
temperature at certain times or shutting down heating
completely (adjustable night setback) to control the heating Operation of boiler pumps, 2, 3, or 4-way
system to ensure optimum heating comfort and minimum valves and system pumps
energy consumption.
MCM10 (cascade module) for 4 boiler installations. RC35 Control Capable of DHW and other external
Expandable to 8 boilers using 2 MCM10 Modules. on-demand loads
4000 series controls


ØØ
Accommodates single or multiple boiler installations
Can be interfaced to a building management system via LON module
Self diagnostics and system parameter
display


Ø
Modular construction allows for ease of field configuration and
flexibility of installation
Solar Integration Module

SM10 solar DHW module, controls solar pump and sensors for the collector panels
and the tank
WM10 low loss header sensor module and hydraulic decoupler for use with
cascade systems

The Convenience of a Logamatic Control


In addition to manual adjustments, Logamatic controls can be pre-programmed for
automatic night and day functions and pre-set to trigger automatic adjustments
based on outdoor or indoor temperature shifts. This includes adjustment by time,
date, or temperature between various modes of operation. All Logamatic controls
now include summer, winter and vacation modes to efficiently regulate energy
consumption. An optional module is available that enables direct communication
GB162 Series Specifications
GB162/80 GB162/100
General Specifications Natural Gas (NG) Liquid Propane (LP)* Natural Gas (NG) Liquid Propane (LP)*
Rated thermal load input 69,000−290,000 btu/h 58,000−270,000 btu/h 69,000−333,000 btu/h 58,000−315,000 btu/h
Heating capacity / Gross output 61,400−260,000 btu/h 51,600−242,000 btu/h 61,400−298,000 btu/h 51,600−282,000 btu/h
Net IBR 226,000 btu/h 210,000 btu/h 259,000 btu/h 245,000 btu/h
Low Fire 96.1% Low Fire 96.1%
Efficiency rating 93.8% AFUE 93.9% AFUE
High Fire 90.8%** High Fire 90.8%**
De-ration altitudes 2,000–5,000'
2.2 2.3 2.0 2.1
%/1,000 ft.
De-ration altitudes 5,500–8,000'
2.0 2.5 1.7 2.1
%/1,000 ft.
De-ration altitudes 8,000–10,200'
2.8 2.0 2.6 1.9
%/1,000 ft.
Heating
Maximum flow temperature 190˚F (88˚C)
Max. working pressure (boiler) 50 psi (3.6 bar)
Min. water circulation volume 0
Flow temperature 86–190˚F (30–88˚C), can be set on the BC10 basic controller
Resistance at rT = 20 K 3.26 psi (225 mbar) 4.57 psi (315 mbar)

Heating circuit volume of


1.3 gal. (5.0 l)
heat exchanger

Pipe Connections Boiler, Without Pump Group


Gas connection Rp1"
Heating water connection G1½" union nut with female thread enclosed
Condensate connection Ø 1¼" (32 mm)
Flue Gas Valves
Condensate quantity at 122/86˚F
2.4 gal/h (9.0 L/h) 2.85 gal/h (10.8 L/h)
(50/30˚C)
pH value of condensate approx 4.1
Flue gas mass flow rate, full load 35.3 g/s 44.9 g/s
Flue gas temp., full load
153˚F (67˚C) 149˚F (65˚C) 169˚F (76˚C) 165˚F (63˚C)
176/140˚F (80/60˚C)
Flue gas temp., partial load
142˚F (61˚C) 136˚F (58˚C) 142˚F (61˚C) 136˚F (58˚C)
176/140˚F (80/60˚C)
Flue gas temp., full load
118˚F (48˚C) 114˚F (46˚C) 124˚F (51˚C) 120˚F (49˚C)
122/86˚F (50/30˚C)
Flue gas temp., partial load
93˚F (34˚C) 88˚F (31˚C) 93˚F (34˚C) 88˚F (31˚C)
122/86˚F (50/30˚C)
CO2 content at full load 9.3 9.6 9.4 9.7
Free fan feed pressure 0.602 inch w.c. (150 Pa) 0.883 inch w.c. (220 Pa)
Flue Gas Connection
Ø flue gas system,
Ø 4" (100 mm)
room-air dependent
Ø flue gas system,
Ø 4" (100 mm) / 4" (100 mm) parallel
room-air independent

* Special order field conversion kit required


** I=B=R Rating based on AHRI BTS2000 spec. 180 degree F supply and 80 degree F return
4.2 With pump group

18.3" (465 mm) 4.1


0.25" (6 mm) Without
0 pump
20.5" (520 mm)group
0
18.3" (465 mm) 0.25" (6 mm) 0 20.5" (520 mm) 0
4.2 With pump group
6" (152 mm) 6" (152 mm) 5.5" (140 mm)
A B A 0B
18.3" (465 mm) 0.25" (6 mm) 0 20.5" (520 mm) 0
A/B A/B

1.2" (30 mm)


0.25" (6 mm) 0 20.5" (520 mm)
1.2" (30 mm)

20" (500 mm) 18.3" (465 mm)


20.5" (520 mm) 6" (152 mm) 6" (152 mm)

4.1" (103.5 mm)A B A B


A/B A/B

1.2" (30 mm)


1.2" (30 mm)
4.1" (103.5 mm)

C C
4.1" (103.5 mm) 4.1" (103.5 mm)

5.3" (135 mm)


C
5.3" (135 mm)

16" (406 mm)


16" (406 mm) C

5.3" (135 mm)


39.5" (1003 mm)
40.55" (1030 mm)
39.5" (1003 mm)

38.58” (980 mm)


40.55" (1030 mm)

5.3" (135 mm)


16" (406 mm)
38.58" (980 mm)

16" (406 mm)

50.4" (1280 mm)


A (LA) = Flue gas connection;

39.5" (1003 mm)


40.55" (1030 mm)
39.5" (1003 mm)

38.58” (980 mm)


40.55" (1030 mm)
38.58" (980 mm)

51.6" (1310 mm)


51.6" (1310 mm)

B (AA) = Air intake connection;


C (WB) = Wall Bracket (not shown)

50.4" (1280 mm)


A (LA

51.6" (1310 mm)


51.6" (1310 mm)
D/F D (VK) = Supply; B (AA
D/F
G E D E F G E D E F E (GAS) = Gas connection to boiler; C (WB
F (RK) = Return;
D/F D (VK
G
D/F G (AKO) = Condensate outlet;
G E D E F G E D E F E (GA
H (PF) = Pump group supply;
24.8" (630 mm) F (RK
I = Gas connection to pump group;
m)
1.4" (35 mm) 1.54" (39 mm)
G G (AK
J (PR) = Pump group return;
1.54" (39 mm)
1.4" (35 mm)
H/J G
H (PF
5.1" (130 mm) 5.1" (130 mm) 5.4" (138 mm)
5.4" (138 mm) 5.1" (130 mm) 5.1" (130 mm)
6.4" (162 mm) 6.4" (162 mm) 24.8" (630 mm)
24.8" (630 mm)
H I J I
1.4" (35 mm) 1.54" (39 mm)
J (PR
1.54" (39 mm)
1.4" (35 mm)
5.4" (138 mm)
5.1" (130 mm) 5.1" (130 mm)
H/J 5.4" (138 mm) G
5.1" (130 mm) 5.1" (130 mm)
6.4" (162 mm) 6.4" (162 mm)
H I J
tions GB162-80 (NG)
unit GB162-80 (LP) GB162-100 (NG) GB162-100 (LP)
Natural gas Propane Natural gas Propane
General specifications - 290,000
btu/h 69,000 58,000 - 270,000
unit 69,000 - 333,000
GB162-80 (NG) 58,000 - 315,000
GB162-80 (LP) GB162-100 (NG
4.2 With pump group
acity, Gas category btu/h Natural gas Propane Natural gas
The required permanent clearances (closet) are:
140°F (80/60°C) Rated thermal load 61,400 - 255,200 51,600 - 237,600 61,400 - 293,000 51,600 - 277,200
18.3" (465 mm) 0.25" (6 mm) 0 20.5" (520 mm) 0

btu/h 69,000 front:


- 290,000
1" (25 mm) 58,000 - 270,000 69,000 - 333,000
20 mm) 0
6" (152 mm) 5.5" (140 mm)

acity,
B A/B btu/h A B
Rated heating capacity, btu/h
1.2" (30 mm)

right side: 0
86°F (50/30°C) 68,300 - 281,300 57,400 - 261,900 68,300 - 326,300
left side: 0 57,400 - 308,700
heating curve 176/140°F (80/60°C)
4.1" (103.5 mm)
61,400 above:
- 255,200 51,600 - 237,600
6" (152 mm) 61,400 - 293,000
max. capacity, % C
Rated heating capacity, btu/h The position selected for installation MUST allow
140°F (80/60°C) 88 adequate space8for 8
heating curve 122/86°F (50/30°C) - 326,300 68,300 - 281,300 servicing57,400 - 261,900 68,300
in front of the boiler of at
5.3" (135 mm)

6 mm) 16" (406 mm)

max. capacity, % least 20" (500 mm).


86°F (50/30°C) Boiler efficiency at max. capacity, 97 % 98 clearance from combustible
Maintain an installation
39.5" (1003 mm)
40.55" (1030 mm)
39.5" (1003 mm)

38.58” (980 mm)


40.55" (1030 mm)

heating curve
btu/h
176/140°F (80/60°C)
261,000
construction from hot88water piping of at least 1" (25 mm).
A (LA) 243,000
= Flue gas connection; 295,000 279,000
50.4" (1280 mm)

Boiler %efficiency
/ 1,000 ftat max. capacity, % connection; 2.0
51.6" (1310 mm)
51.6" (1310 mm)

2,000 - 5,500 ft 2.2 B (AA) =


2.3Air intake 2.1
5,500 - 8,000 ft
heating %
curve
/ 1,000
122/86°F
ft
(50/30°C)
2.0
C (WB) = Wall Bracket (not shown)
2.5 1.7
97 2.1
D/F D (VK) = Supply;
8,000 - 10,200 ft
F CSAG Output
% / 1,000 ft
E D E
2.8
F E (GAS) 2.0
= Gasbtu/h
connection to boiler; 261,000
2.6 243,000
1.9 295,000
F (RK) = Return;
De-ration altitudes 2,000 - 5,500 ft % / 1,000 ft
G (AKO) = Condensate outlet;
2.2 2.3 2.0
G
perature De-ration altitudes
°F (°C) 5,500 - 8,000 ft
24.8" (630 mm)
H (PF) %
= /
Pump1,000 ft
190 (88)
group supply; 2.0 2.5 1.7
I = Gas connection to pump group;
pressure (boiler) De-ration psialtitudes
(bar) 8,000 - 10,200 ft % / 1,000
All non-steel
J (PR) 50 ft(3.6)
combustion
= Pump group return;
2.8pipe materials and fittings
air and vent
1.4" (35 mm) 2.0must comply with the 2.6
1.54" (39 mm)
5.1" (130 mm)
H/J G following and must be UL approved venting material.
Heating
5.4" (138 mm)

culation volume Gal/h (l/h) 0


5.1" (130 mm) 5.1" (130 mm)
6.4" (162 mm)
H I J
Maximum °Fflow
(°C)temperature 86-190 (30-88),
Item can °Fbe (°C)
set on the BC10 basic controller
Material United States 190 (88)
Canada
20 K Maximum working pressure (boiler)
psi (mbar) 3.26 (225)4" (100psi (bar)
mm) Vent or(LP)
PVC schedule 40, 4 .5 7
80( 3 15 )
ANSI/ASTM D1785 50 (3.6)
unit GB162-80 (NG) GB162-80 (LP) GB162-100 (NG) GB162-100 PVC-DWV ANSI/ASTM D2665 BH Gas
me of heat exchangerMinimumGal water
(L) circulation volume air pipeGal/h (l/h)
1.3 (5.0)
and fitting 0
venting
Natural gas Propane Natural gas Propane CPVC schedule 40, 80 ANSI/ASTM F441
boiler, without pump group
Flow temperature °F (°C) 86-190 (30-88), can be set on the BC10 basic
systems,
btu/h 69,000 - 290,000 58,000 - 270,000 69,000 - 333,000 58,000 - 315,000 PVC ANSI/ASTM D2564 ULC S636*
in
Resistance at ΔT = 20 K
Pipe cement/ primer
psi (mbar) Rp1" CPVC 3.26 (2ANSI/ASTM
25) F493 4.5
btu/h
nection Heating circuit
61,400 - 255,200 in volume
51,600 of heat
- 237,600 61,400 G1½’’*Components
exchanger
- 293,000 union nut
Galofwith
51,600 (L) female
- 277,200
the certified ventthread
systemsenclosed 1.3systems
must not be interchanged with other vent (5.0)
ction
btu/h in (mm)
Pipe connections boiler, without pumpvent group Ø fittings.
or unlisted pipe 1¼" (32 mm)
Plastic components, and specified primers and glues of the certified
system, must be from a single system manufacturer and not intermixed with other system
68,300 - 281,300 57,400 - 261,900
Gas connection 68,300 - 326,300 57,400
manufacturer’s in - 308,700
vent system parts. Rp1"
ty %
at 104/86°F
Heating water connection in G1½’’ union nut with female thread enclo
88
Gal/h (L/h) 2.4 (9.0) Wall88 terminals 2.85(trade
Flue System (10.8name)
) Supplier
%
Condensate connection in (mm) Ø 1¼" (32 mm)
nsate pH 4" (100 mm) approx.
parallel 4.1 PVC Flex-L/SJTK_DVG
Flue gas values
97 g/s 98
rate, full load 35.3 90°-elbow with inlet screen PVC/stainless 44steel
.9 Z-Flex/Heat Fab
btu/h Condensate quantity
261,000 243,000 at 104/86°F295,000 279,000
ure 176/140 °F °F (°C) 153 (67) 149 (65) 169 (76) 165 (63)
1,000 ft 2.2 (40/30°C) 2.3 2.0 Gal/h (L/h)2.1 2.4 (9.0) 2.8
1,000 ft
ure 176/140 °F 2.0 pH value°Fof(°C) condensate 142 (61)
2.5 1.7 136 (58) pH 2.1 142 (61) 136 (58) approx. 4.1
1,000 ft
oad 2.8 Flue gas mass flow 2.0 rate, full load 2.6 g/s1.9 35.3
ure 122/86 °F Flue gas°F temperature
(°C) 176/140
118 (48) °F 114 (46)°F (°C) 124153 (67)
(51) 120149
(49)(65) 169 (76)
F (°C) (80/60°C), full load 190 (88)
GB162 Series: Wall-Hung Gas Condensing Boiler

GB162 Benefits at a Glance

Ø Compact Dimension, Light Weight,


High Output
Ø
Gas valve
Innovative ALU Plus condensing heat
Fully modulating fan exchanger for the longest possible life and
easy servicing
ØØ
Automatic air vent
Efficiency of up to 94% AFUE
Quick-clip burner release Modulation down to 20% of total output for
year round efficiency
Low NOx ceramic pre-mix burner
ØØ Compact and lightweight
Cascades up to 8 units
Ø
Ceramic glow igniter
& ionization electrode Quick-Install: innovative cascade concept for
easy installation
Combustion chamber
Ø Ideal for smaller commercial buildings and
large domestic properties
ØØ
Flow temperature sensor
No minimum flow rate required
Whisper quiet
ØØ
Finned ALU-Plus heat exchanger
Low flue gas emissions
Condensate collector & drain Integrated BC10 boiler controls with space
for the optional RC35 Digital Programmer
BC10 controller with expansion slot for
and extension modules
ØØ
RC35 controls
LPG conversion kit available
UBA 3 boiler management system 1 year parts, Limited Lifetime warranty on the
heat exchanger
Pump group – available separately
(including isolating valves, gas valve,
custom fit insulation, check valves,
thermometer and pressure gauge

GB162 Approvals and Certifications

(Hidden from view) Deep seal push-fit ®


condense trap

Approval Numbers

AQMD certified under rule
1146.2 Ref# R08061
CRN 7990.7C
MA # G1-00808-30

A Tradition of Excellence
The World’s leader in hydronic heating technologies since 1825, Buderus produced the world’s first
low-temperature hydronic heating systems. Today, Buderus products are acknowledged as the world
standard in high-efficiency, low emissions hydronic heating. All Buderus products are designed to
meet strict safety and environmental regulations.

Buderus boilers are quick and easy to install and will outlast and outperform virtually any other
commercial hot water heating system. They are designed for easy access and service. With
appropriate maintenance, Buderus boilers deliver the highest possible efficiencies throughout the
lifespan of operation.

Bosch Thermotechnology Corp. Subject to change without notice


50 Wentworth Avenue Londonderry, NH 03053 © 2009 Bosch Thermotechnology Corp.
Tel: (603) 552-1100 Fax: (603) 584-1681 www.buderus.net Part Number 44499054 05/09