Professional Documents
Culture Documents
3814-AX-SG-000002
Sheet
1/34
Issue
05
05
05.Mar.2015
V.Manerba
A.Guarino
M.Martoglio
04
03.Feb.2015
FINAL ISSUE
V.Manerba
A.Guarino
M.Martoglio
03
10.Nov.2014
V.Manerba
A.Guarino
M.Martoglio
02
23.Jul.2014
V.Manerba
A.Guarino
M.Martoglio
01
14.Apr.2014
FOR COMMENTS
V. Manerba
A. Guarino
M. Martoglio
Issue
Date
Prepared
Checked
Approved
05
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
2/34
Issue
05
CONTENTS
1
SCOPE ................................................................................................................................ 4
3.1
3.2
3.3
4
LANGUAGE ............................................................................................................................ 7
SITE CONDITIONS................................................................................................................... 7
SOIL MECHANICS AND GEOTECHNICAL CONDITIONS ................................................................ 7
DESIGN LOADS ................................................................................................................. 7
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
4.17
5
5.1
5.2
5.3
6
BASINS ............................................................................................................................... 16
COMBINING NOMINAL LOADS USING ALLOWABLE STRESS DESIGN ......................... 16
COMBINING FACTORED LOADS USING STRENGTH DESIGN ...................................... 17
SERVICEABILITY ............................................................................................................. 19
6.1
6.2
6.3
7
7.1
CONCRETE .......................................................................................................................... 21
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
3/34
Issue
05
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.9
7.10
7.11
8
8.1
8.2
8.3
STABILITY ........................................................................................................................... 25
BUOYANCY .......................................................................................................................... 26
FOUNDATION SUPPORTING HEAVY VIBRATING EQUIPMENT ...................................................... 26
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
4/34
Issue
05
SCOPE
This specification contains the general criteria and methods of calculation to be applied for the design
of CONCRETE and STEEL structures for the 2x360 MW Coal-Fired Power Plant, PUNTA CATALINA,
BANI, in DOMINICAN REPUBLIC.
2.1
Local Regulations
Project Specification and drawings
International Codes
Tecnimont standards
Local regulations
R-001 Reglamento sismico
R-028 Reglamento acero
M-009 Especificaciones generals
2.2
3814-AX-SG-000002
Sheet
5/34
Issue
05
International codes
The work shall comply with all Codes and Standards mentioned in this specification. The latest
revision of Codes and Standards shall be used.
American Concrete Institute (ACI)
ACI 224R-01 Control of Cracking in Concrete Structures;
ACI 301/301R Specifications for Structural Concrete for Buildings;
ACI 318/318R Building Code Requirements for Reinforced Concrete and Commentary with
supplements;
ACI 350/350R Code requirements for Environmental Engineering Concrete Structures &
commentary;
ACI 530/530R Building Code Requirements for Masonry Structures.
ACI 351.4R
Foundations for Dynamic Equipment
American Society of Civil Engineers (ASCE)
ASCE 7-05 Minimum Design Loads for Buildings and Other Structures;
ASCE Anchorage Design for Petrochemical Facilities;
ASCE Guidelines for the Seismic Evaluation and Design of petrochemical facilities;
ASCE Wind Loads Anchor Bolt Design for Petrochemical Industries.
American Institute of Steel Construction (AISC)
AISC 360-05 Specification for Structural Steel Buildings (LRFD Method);
AISC 341-05 Seismic Provisions for Structural Steel Buildings;
AISC 358-05 Prequalified Connections for Special and Intermediate Steel Moment Frames for
Seismic Applications;
AISC 303-05 Code of Standard Practice for Steel Buildings and Bridges;
05
3814-AX-SG-000002
Sheet
6/34
Issue
05
Tecnimonts Standards
TM902.14
TM902.1
TM902.2
TM902.3
TM902.4
TM902.5
TM902.11
TM903.8
TM903.10
TM903.16
TM 905.4
TM914.3
TM 914.4
TM914.5
TM914.10
TM914.13
TM914.14
TM922.1
TM922.2
TM904.40
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
7/34
Issue
05
DESIGN REQUIREMENTS
3.1
Language
All design documentation will be in English.
3.2
Site conditions
Design of foundations, steel and concrete structures shall be carried out on the base of the site general
data applicable to the project such as:
Basic wind speed;
Seismic zone;
Design thermal loads due to temperature variation;
Site data shall be in accordance with 3814-YZ-SG-000001 Design basis and site conditions.
3.3
Design of foundations, structures, earthworks and other concrete works shall be carried out in
accordance with the prescriptions included in the final soil report related to:
Foundations level;
Allowable bearing capacity of soil related to settlements, dimensions and depth of foundations;
Piles vertical and horizontal bearing capacity;
Expected settlements (short term and long term);
Specific weight of soil (dry and wet);
Cohesion and friction angle ();
Elastic modulus E;
Dynamic modulus G;
Westergaard modulus;
Poisson coefficient;
Water table elevation (min. and max);
Permeability;
Soil chemical characteristics;
Shear velocities of each stratum.
DESIGN LOADS
In general, different design conditions have to be considered for the design of buildings and
structures:
- erection/construction;
- test condition;
- operating;
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
8/34
Issue
05
Loading kN/m2
1.0
1.0
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
9/34
Issue
05
The dead load for all the secondary steel element, grating, handrail and etc. is estimated equal to
qsec,St = 0.75 kN/m2
4.2
Loading kN/m2
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
10/34
Issue
05
05
Offices
3.0
Control Room, change rooms,
compressor building and laboratory
5.0
Mechanical equipment areas
10.0
Substations, Electrical equipment battery rooms
10.0
Operating floors in process structures
5.0
Stairs (or moving concentrate load 4.5 kN)
5.0
Ladders moving concentrate load
2.5 kN
Roofs areas for maintenance only
0.75
Purlin on roof (local check)
1.0
Roof used as platform around apparatus
2.5
Cable trays in racks (each tray level)
1.0
Checkered Plate or Grating (All Locations)
5.0
Walkway, platforms (1200mm wide or less)
3.0
Warehouse and Storage areas: to be determined considering
the intended use of the area, but never less than
7.5
Handrails: 0.75 kN/m linear load or concentrate 1 kN in all directions
Pipe loads on racks: 60% of the loads indicated
in TM902.14
1.2
In areas of a lesser amount of piping
0.7
Roving non accumulating point load applied to mid-span of beams to account for
disproportionate concentration of hanging loads: based on rational analysis of hanging
loads, but not less than (2,000 lb) 9.07kN
All content of pipes larger than 12" in diameter shall be considered as concentrated loads at
their point of support.
For the STG top floor, for maintenance, shall be considered as minimum 28.73kN/m2
Uniform and concentrated loads do not occur simultaneously. Concentrated loads shall be placed
upon a space of 1' x 1' (300 mm x 300 mm).
4.3
3814-AX-SG-000002
Sheet
11/34
Issue
05
Equipment test load is the weight of the equipment plus the weight of water necessary to perform
the hydraulic test. In static calculation the weight of water shall be considered as a live load.
Equipment operation (EO)
This load includes the weight of equipment (including platforms and ladders attached to the
equipment), solids e/o liquids normally inside the equipment, connected pipes. In static calculation
this load shall be considered as a dead load.
4.4
Thermal loads
Thermal loads are those forces caused by temperature variations.
The following three different types of thermal loads shall be considered in design of structures and
foundations:
ThT = Loads due to the variation of ambient temperature. Loads caused by the variation of
ambient temperature. It shall be limited by adopting expansion joints at proper distance. A
minimum differential temperature T = 15C shall be considered; it shall not be combined
with other instantaneous loads such as wind, earthquake or impact.
Steel structures have to be designed with expansion joints at a maximum distance of 200 ft
(60m), in which case the thermal load need not be included in the structural design.
For Reinforced Concrete regular structures, the maximum spacing between expansion joints
shall be 165 ft (50m) if temperature differences and the influence of expansion shrinkage and
creep are not considered in the design.
The spacing can be increased if temperature differences and the influence of expansion
shrinkage and creep shall be accounted for in the design.
TeL = Loads caused by the thermal expansion of vessel & exchangers. This load shall be
combined with other instantaneous loads such as wind or earthquake.
TaL = Pipe anchor & guide forces. This load shall be combined with other instantaneous loads
such as wind or earthquake.
FrL = Friction load caused by thermal expansion (hot/cold lines sliding across the pipe rack or
supports). In order to take into account friction forces due to thermal expansion/contraction of
equipment, the following static friction coefficient f shall be used, in absence of any input
from equipment supplier.
-
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
12/34
Issue
05
Estimated pipe friction loads shall not be combined with wind or seismic loads on pipe racks and
their foundations. Only anchor and guide loads, excluding their friction component, shall be
considered with wind and seismic loads.
Pipe anchorage forces from stress analysis shall be dealt in the same way as friction forces in the
load combinations.
4.5
4.6
Earthquake (EL)
Site conditions are described in document 3814-YZ-SG-000001 Design basis and site conditions.
For Seismic load calculation procedure refers to specification n.3814-AX-SG-000003.
4.7
4.8
4.9
4.10
Dead load of vessels plus fluid load is sometime named as operating load.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
13/34
Issue
05
include the maximum wheel loads of the crane and the vertical impact, lateral, and longitudinal
forces induced by the moving crane.
Note:
Impact factors shall be in accordance with SEI/ASCE 7 crane load, or vendor provided criteria.
a) Crane beams, support brackets and connections shall be designed for impact load. Impact
factors shall be as listed below or in vendor provided criteria, whichever is greater:
- To account for impact, the maximum vertical wheel load shall be increased as follows:
- Gantry and bridge crane supports 25%
- Monorail supports and under-hung cranes 25%
- Davits, jib cranes 25%
- Transverse impact shall be as follows:
- Craneway 20% of the lifted load, hoist and trolley. The lateral force shall be assumed to
act horizontally at the traction surface of the runway beam, in either direction
perpendicular to the beam, and shall be distributed with due regard to the lateral
stiffness of the runway beam and supporting structure.
- Davits 20% of the lifted loads
- Longitudinal impact load shall be as follows:
- Craneways 10% of the maximum wheel load applied at the top of the runway
- Monorails 10% of the lifted load, hoist and trolley
- Davits 10% of the lifted load
b) Lifting lugs or pad eyes and internal members (included both end connections) framing into the
joint where the lifting lug or pad eye is located shall be designed for 100% impact.
c) All other structural members transmitting lifting forces shall be designed for 15% impact.
Allowable stresses shall not be increased when combining impact with dead load.
4.11
4.12
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
14/34
Issue
05
4.13
4.14
Elevators
All elevator loads shall be increased by 100% for impact and the structural supports shall be
designed within the limits of deflection prescribed by the elevators vendor.
4.15
Forklift
Where Forklift is to be foreseen it shall be accounted as a live load.
A concentrated load of 60 kN to be distributed on two squares with 20 cm side, 1.2m from each
other. This load shall also be amplified with the impact factor of 1.4. Concentrated loads do not
occur simultaneously with uniform live loads.
4.16
2
3
See TM 922.1
See TM 922.2
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
15/34
Issue
05
4.17
LOADS COMBINATIONS
Allowable Stress Design method will be used for displacement checks, and foundation
geotechnical & stability checks. The load combinations will be according to the ASCE 7-05.
Strength Design Method will be used for the design of reinforced concrete structures reinforced
concrete foundations and steel structures. The load combinations will be according to the ACI
318-08 and AISC 360-05 (LRFD Method).
The loads shown in the following table shall be considered to determine the critical loading
condition for the design of the structural elements (columns, beams, slabs, bracings, anchor bolts,
foundations) and to check the stability of the structure.
When inclusion of fluid loads or live loads results in a less critical loading condition, these loads
shall be excluded. However safety of persons and structures shall be assured during all transient
phases of construction.
Erection
1. Dead loads of structure less: fireproofing (except when the fireproofing is installed at shop) and
piping.
2. Equipment load
3. Temporary loads and forces caused by erection
4. Wind load or Earthquake load whichever is greater
If construction is known to occur during hurricane season and a basic wind speed of 149mph
(240km/h) is used in determining Wp, then temporary wind bracing must be provided.
Test
1. Dead loads of structure plus fireproofing
2. Equipment load
3. Dead load of piping plus insulation
4. Live load from platforms and walkways
5. Wind load (50% of wind pressure)
Operation
1. Dead loads of structure plus fireproofing
2. Equipment load
3. Dead load of piping plus insulation
4. Live load from platforms and walkways
5. Thermal loads
6. Impact loads
7. Wind load or Earthquake Load (whichever is grater)
Maintenance
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
16/34
Issue
05
Basins
Basins shall be designed in accordance with requirement and prescriptions included in ACI 350-06.
The loads shown in the following table shall be considered to determine the critical loading condition for
the design of the structural elements (i.e. design of reinforcement, cracking check etc.) and to check the
stability of the structure. When inclusion of earth passive pressure results in a less critical loading
condition, this load shall be excluded.
Construction
Dead loads of structure
Earth load
Construction Loads
Earthquake load
Operation
Dead loads of structure
Equipment load
Live load from platforms and walkways
Thermal loads
Earth load
Earthquake Load
5.2
The loading combinations shown in the following table shall be considered to determine displacement
checks, and foundation geotechnical & stability checks of the pipe racks and the process structures:
Erection
DL+EE+ThL
DL+EEWLX
DL+EEWLZ
DL+EE 0.7(ELX0.3ELZ)
DL+EE 0.7(0.3ELXELZ)
0.9DL+0.9EEWLX
0.9DL+0.9EEWLZ
0.9DL+0.9EE 0.7(ELX0.3ELZ)
0.9DL+0.9EE 0.7(0.3ELXELZ)
Test
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
17/34
Issue
DL+ET+0.5LL
DL+ET0.25WLX
DL+ET0.25WLZ
DL+ET0.75(0.5WLX+0.5LL)
DL+ET0.75(0.5WLZ+0.5LL)
0.9DL+0.9ET0.5WLX
0.9DL+0.9ET0.5WLZ
Operation
DL+EO+LL+ThL+TaS+FrL
DL+EO+TLSWLX
DL+EO+TLSWLZ
DL+EO+TLS 0.7(ELX0.3ELZ)
DL+EO+TLS0.7(0.3ELX ELZ)
DL+EO+TLS0.75WLX+0.75LL
DL+EO+TLS0.75WLZ+0.75LL
DL+EO+TLS0.75*0.7(ELX+0.3 ELZ)+0.75LL
DL+EO+TLS0.75*0.7(0.3ELXELZ)+0.75LL
0.9DL+0.9EO+0.9TLSWLX
0.9DL+0.9EO+0.9TLSWLZ
0.9DL+0.9EO+0.9TLS 0.7(ELX0.3 ELZ)
0.9DL+0.9EO+0.9TLS 0.7(0.3ELXELZ)
5.3
The loading combinations shown in the following table shall be considered to determine the critical
loading condition for the design of the structural elements:
Erection
1.4DL+1.4EE
1.2DL+1.2EE+1.2ThL
1.2DL+1.2EE1.6WLX
1.2DL+1.2EE1.6WLZ
1.2DL+1.2EE(ELX0.3ELZ)
1.2DL+1.2EE(0.3ELXELZ)
0.9DL+0.9EE1.6WLX
0.9DL+0.9EE1.6WLZ
0.9DL+0.9EE(ELX0.3ELZ)
0.9DL+0.9EE(0.3ELXELZ)
TEST
1.4DL+1.4ET
1.2DL+1.2ET+1.6(0.5LL)
1.2DL+1.2ET0.65WLX+0.5LL
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
05
3814-AX-SG-000002
Sheet
18/34
Issue
05
1.2DL+1.2ET0.65WLZ+0.5LL
0.9DL+0.9ET0.65WLX
0.9DL+0.9ET0.65WLZ
OPERATION
1.4DL+1.4EO
1.2DL+1.2EO+1.2ThL+1.2TaL+1.2FrL+1.6LL+1.6IL
1.2DL+1.2EO+1.2 TaL 1.6WLX+ f1LL
1.2DL+1.2EO+1.2TaL1.6WLZ+ f1LL
1.2DL+1.2EO+1.2TaL(ELX0.3ELZ)+f1LL
1.2DL+1.2EO+1.2TaL(0.3ELXELZ)+f1LL
0.9DL+0.9EO+0.9TaL1.6WLX
0.9DL+0.9EO+0.9TaL1.6WLZ
0.9DL+0.9EO+0.9TaL(ELX0.3ELZ)
0.9DL+0.9EO+0.9TaL(0.3ELXELZ)
Where:
WLX = wind load in 1st principal direction;
WLZ = wind load in 2nd principal direction;
ELX = Earthquake load in 1st principal direction;
ELZ = Earthquake load in 2nd principal direction.
f1 = 0.5 if L<100 psf (4.8 kN/m); If L>100 psf or areas occupied as places of public assembly then f 1 =
1.0
Use of a 1/3 stress increase for allowable stress load combinations involving wind loads should not be
used.
According to "PIP STC0101015" and to "ASCE Guidelines for seismic evaluation and design of
petrochemical facilities", since the dead loads of non-building structures are known to a higher degree
of accuracy than are the corresponding dead loads of buildings, the dead load factor used for the
seismic uplift in the loadings combinations for displacement checks and foundation checks will be taken
as 0.9 instead of 0.6.
The seismic load on the structure, E, is made up of two components: Eh, horizontal seismic effect,
calculated from the base shear and amplified by redundancy factor , and Ev, vertical seismic effect,
calculated from a percentage of the design spectral response acceleration parameter, SDS, time the
effective seismic weight of the structure.
Response effect due to vertical components of ground motion are not required to be calculated where
SDS is 0.125. Vice versa the vertical earthquake forces are to be considered explicitly in the design or
analysis of the structure:
E = Eh Ev = QE 0.2 SDS DL
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
19/34
Issue
05
SERVICEABILITY
6.1
Crack Limitations
Crack limitation to RCC structures shall be as per ACI 224R-01, Reasonable average crack
widths per Table 4.1 of ACI 224R-01:
Crack width
Exposure condition
Dry air or protective membrane
Humidity, moist air, soil
Deicing chemicals
Seawater and seawater spray, wetting and drying
Water-retaining structures
in
mm
0.016
0.012
0.007
0.006
0.004
0.41
0.30
0.18
0.15
0.10
The prescription of ACI 318 section 10.6.4 shall be carefully applied with service loads to limit the
crack width.
For water retaining structures, maximum tensile stress in reinforcement at service loads, due to
water pressure shall be limited to:
Where:
fs, max = tensile stress in reinforcement at service loads (Mpa) (not less than 120Mpa)
s = center-to-center spacing of deformed bars (mm)
db = nominal diameter of bar (mm)
= 1.25 if thickness of member > 400 mm
= 1.35 if thickness of member < 400 mm
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
20/34
Issue
05
6.2
Allowable deflections
Design deflections of structural steel members (DL+LL) shall not exceed the following values:
For steel structures:
Purlins and roof girders
L/200
Floor beams without equipment
L/300
Floor beams supporting equipment
- Operating state
L/400
- Hydraulic test
L/250
Pipe rack beams
L/300
Girders and joists under masonry walls
L/500
Cantilevers
L/250
Grating: more stringent between resistance at 5 kPa, maximum vertical deflection L/200
but not more than 5mm.
Crane Supports
- Vertical deflection of support runway girders shall not exceed the following limits when loaded
with the maximum wheel load(s), without impact:
Monorails and Under-Running CMAA Class A, B, and C Cranes
L/450
Top-running CMAA Class A, B, and C Cranes
L/600
Top-running CMAA Class D Cranes
L/800
Under-running CMAA Class E and F Cranes
L/1000
- Vertical deflection of jib crane support beams shall not exceed L/225 (where L = the maximum
distance from the support column to load location along the length of the jib beam when loaded
with the maximum lifted plus hoist load(s), without impact.
- Lateral deflection of support runway girders for cranes with lateral moving trolleys shall not
exceed L/400 when loaded with a total crane lateral force not less than 20 percent of the sum
of the weights of the lifted load (without impact) and the crane trolley. The lateral force shall be
distributed to each runway girder with due regard for the lateral stiffness of the runway girders
and the structure supporting the runway girders.
- Building frame lateral deflection at runway beam level from unfactored crane loads or from the
unfactored 1-in-10-yr wind load:
H/100 (pendantoperated crane for CMAA class A, B, C & D)
H/240 (caboperated crane for CMAA class A, B & C)
Where L=theoretical span of beam (for cantilever its twice the projection of beam length)
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
21/34
Issue
05
6.3
Allowable drift limits for pipe racks shall not exceed H/150 (where H = pipe rack height) for
50 yr wind.
Allowable wind drift limits for process structures and personnel access platforms shall not
exceed H/200 (where H = structure height) for 50 yr wind.
Allowable wind drift limits for buildings shall not exceed H/400 for 10 yr wind.
Allowable drift limits for buildings with bridge cranes (pendantoperated crane for CMAA
class A, B, C & D) shall not exceed H/150, for crane lateral load OR 10 yr wind.
Allowable drift limits for buildings with bridge cranes (caboperated crane for CMAA class
A, B & C) shall not exceed H/240, for crane lateral load OR 10 yr wind.
MATERIALS
7.1
Concrete
Material quality for reinforced concrete shall be in accordance with ACI 318/318R "Building Code ,
Concrete design for liquid-containing structures shall also be designed in accordance with ACI
350/350R Requirements for reinforced concrete". Reinforcement details not shown on standard
drawings shall be carried out in accordance with the requirements of ACI SP-66 "ACI Detailing
Manual".
Concrete shall have the Minimum Cylinder Strength listed below:
05
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
22/34
Issue
05
7.2
Reinforcing steel
Deformed reinforcing steel bars shall conform to ASTM A615/A615M, Grade 60, with specified
yield strength fy=60000 psi (414 N/mm2).
Fusion-bonded epoxy coated steel reinforcement (FBECR), of the same steel material as above,
shall be used, below and above ground, for all structures in contact with sea water.
FBECR shall be conforming to ASTM A775/A775M or ASTM A934/A934M grade 60. Coating
thickness shall be between 180 and 300 m.
05
Welded wire fabric shall conform to ASTM A1064 for plain fabric and to ASTM A497 for deformed
fabric with specified yield strength fy=65000 psi (450 N/mm2).
Bar diameters shall be as per dwg. n. 3814-AA-DC-000003 General notes for RC structures.
7.3
Reinforcement cover
The minimum concrete cover shall be as per dwg. n. 3814-AA-DC-000003 General notes for RC
structures.
7.4
Not more than 10 in (250 mm) for bars perpendicular to main bars in slabs, minimum shrinkage
and temperature reinforcing in slabs, and bars in walls.
Not more than 16 in (400 mm) for any other bars not mentioned above.
In walls and floors with a thickness of 10 in (250 mm) or more, reinforcing bars shall be placed on
both sides, over the full section.
In footings and foundations with a thickness of 10 in (250 mm) or more, reinforcing bars shall be
placed on both the top and bottom, over the full section.
7.5
Minimum Reinforcement
The minimum reinforcement for flexural members shall be in accordance with ACI 318 Chapter
10.5 but shall not be less than 0.0035 of the gross concrete area.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
23/34
Issue
05
7.6
Anchor Bolts
The design requirements for anchors in concrete used to transmit structural loads by means of
tension, shear, or a combination of tension and shear shall be in accordance with ACI 318-08
Appendix D and 3814-AI-SG-000001 General Specification for Steel Works.
05
Shear-keys shall be provided under columns which transfer important shear loads (such as braced
frames, shelters with bridge-crane and pipe rack braced bays). Shear-key consists of steel profile
welded under column base plate.
Shear can be transferred to foundation by friction for minor structures, such as walkways, shelters
without bridge-crane, pipe-racks, etc. In these cases the effective compressed area shall be
calculated based on actual vertical load and moment. If the effective shear load exceeds the
maximum shear transferred by friction, shear-key shall be foreseen.
7.7
Joints
Expansion joints, contraction joints, and construction joints shall be detailed in accordance with
ACI 301, ACI 302.1R, and ACI 504R. For detail see specification 3814-AASG-000001.
7.8
Grouting
Grouting shall be in accordance to 3814-AA-SG-000001 General specification for concrete
works.
7.9
Metal Decking
Metal deck shall be designed in accordance with Design Manual for Composite Decks, Form
Decks and Roof Decks No. 31.
When roof or floor metal decking is used as a diaphragm to carry lateral forces, both the metal
deck and the deck attachments to the structural frame shall be designed to transfer the lateral
forces in accordance with the requirements of SDI.
In areas where steel deck is used as form for concrete slab, and in order for the steel decking to
provide lateral bracing to the top flange of beams in a corrosive environments, shear connectors
shall be installed on the top flange at positions providing the desired unbraced length (say at
spacing = lc or lu). The connectors function is to engage the slab providing a positive lateral
brace point at the beam flange. Connector strength shall provide a shear strength equal to or
greater than 2% of the compression strength of the compression element being braced (the
beam).
In a corrosive environment, the decking can corrode away negating the assumption of bracing of
the compression flange by the decking. In areas where corrosion of the deck is not a concern,
deck can be tack welded to the beams.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
24/34
Issue
05
Light equipment and pipe supports with a concentrated load less than 10kN or a distributed load
under 2.5 kN/m2 may be supported directly on the deck.
7.10
Grating
Grating shall be in accordance to 3814-AI-SG-000001 General Specification for Steel Works
7.11
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
25/34
Issue
05
Holes: standard size or short-slots perpendicular to load (exception: oversize holes are
permitted for diagonal brace connections, but the connection must be designed as slip-critical
and the oversize hole is permitted in one ply only)
Nominal bearing strength at bolt holes cannot exceed 2.4 d t Fu
Bolts and welds shall not be designed to share force in a joint, or the same force component in
a connection.
FOUNDATION DESIGN
Soil bearing foundations shall be designed to conform to the final soil report and to the following
minimum safety factor requirements under the most critical loading conditions.
Stability checks shall be performed for non-piled structures.
Friction coefficient between soil and concrete foundation may be taken as tan(2/3*).
Over excavation below the specified level shall be filled with mass concrete.
Backfilling shall be as indicated in final soil investigation report.
8.1
Stability
The stability of the structure shall be checked for the non-factored load combinations.
A.
B.
C.
The above safety factors provide for a minimum area of footing under compression of 50%
for erection and 67% for operation and test.
For chimneys, stacks and other similar construction area of footing compression shall be
80%.
The factor of safety against uplift shall be calculated as the minimum downward column
load plus weight of foundation divided by the total uplift force. Factor of safety against uplift
shall be not less than 1.5 for operating plus wind or earthquake and not less than 1.2 for
erection plus wind. The resistance to uplift due to cohesion or friction shall normally be
ignored.
Factor of safety against sliding for retaining walls and similar structures shall be 1.5
minimum.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
26/34
Issue
05
8.2
Buoyancy
The effect of buoyancy shall be considered only when ground water level is expected above the
bottom of the foundation or basin. If ground water level changes with season, maximum
compression (bearing stress) on soil shall be calculated with the water level at the lowest point;
tensions with the water table at the highest point.
Factor of safety against buoyancy shall be 1.2 for operation (without live loads) and 1.1 for
erection.
8.3
A.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
27/34
Issue
05
f.
g.
h.
The foundation shall be designed so that the centroid of mass of machine and
foundation systems coincides with the centroid of the base contact area. In any
case, horizontal eccentricity shall not exceed 5% of the corresponding base
dimension.
For both types of foundations, the thickness of the foundation slab shall not be
generally less than 0.6 + L/30 [m] where L is the longest horizontal dimension of the
foundation slab. Moreover the minimum depth of foundation below ground level
shall not be less than 500 mm and, for alternative machine, not less than thk / 2;
The allowable soil-bearing or allowable pile capacity for foundations for equipment
designed for dynamic loads shall be a maximum of half of the normal allowable for
static loads.
2.
3.
For tabletop construction, the sizing of structure and foundation shall usually conform to
the following:
a.
Beams and slabs shall have spans as short as possible.
b.
The minimum depth of beams shall be 1/4 of the clear span between faces of
columns (disregarding any haunches).
c.
The minimum width of beams shall be 1/5 of the clear span between faces of
columns (disregarding any haunches) or equal to the width of the smaller
column, whichever is less.
d.
Columns shall be dimensioned to carry at least 6 times the vertical load from
beams or slab.
e.
All columns shall have approximately the same ratios of direct load to
cross-sectional area.
f.
The combined centre of gravity of machine and structure shall coincide with the
centre of resistance of all columns. For this purpose, only that portion of the
structure that is above the foundation slab shall be considered.
g.
The weight of the foundation slab shall not be less than the combined weight of
the structure and machine. Only that portion of the structure that is above the
mid-height of columns shall be considered to contribute to the weight of the
structure.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
28/34
Issue
05
h.
4.
5.
6.
7.
8.
9.
10.
11.
12.
The weight of the machine shall include the weights of Turbine, Gear Box, Motor,
sole plates and frame, and any other parts supported by the upper slab and
beams.
Cantilevered construction in the form of overhanging brackets or free-standing columns
shall be avoided where possible. If cantilevered elements must be used the length to
depth ratio shall be less than or equal to unit.
All parts of machine supports shall be independent from adjacent foundations and
buildings to prevent transmission of vibration. Concrete floor slabs adjacent to the
machine foundation shall be spaced a minimum of 25 mm from the foundation. The
space between the two structural elements shall be filled with a flexible joint filler and
sealer.
High strength, cement based non-shrinking grout shall be utilized for machines and
drivers. Epoxy, non-shrinking grout shall be utilized only when required by Vendors or by
contract.
The geometric layout of the structure shall be basically symmetrical with reference to the
vertical plane passing through the rotational axis of the machine.
Axes of columns and transverse frame beams shall lie in the same vertical plane
perpendicular to the rotational axis of the machine.
Foundations for low speed machines shall be low and wide to provide a foundation
machine system with a high natural frequency.
Groups of reciprocating machinery foundations can be tied together with a common
foundation slab whenever practical.
Pulsation bottles shall have their supports integrated with the compressor foundation.
All reinforcing shall be according to the American Concrete Institute Code, ACI 318,
unless as noted below, and as per OWNER requirements and/or local Codes, whichever
is more stringent.
a.
Minimum vertical reinforcement in columns shall be 0.5 percent of the gross
concrete area.
b.
Ties in columns shall be of 10mm dia. bars minimum. They shall be spaced at 16
longitudinal bar diameters, but not more than 300 mm apart.
c.
Minimum top and bottom reinforcement in beams shall be each 0.25 percent of
the gross concrete area.
d.
Side rebars in beams shall be for each side a minimum of 0.10 percent of gross
concrete area.
They shall not be spaced at more than 350 mm apart.
e.
At least one 10 mm dia. bar shall be used on each side of beams having a depth
of 300 mm or more.
f.
Stirrups in beams shall be of 8 mm dia. bars min. and they shall not be spaced
more than 300 mm.
g.
Open type stirrups shall not be used in beams.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
29/34
Issue
05
h.
i.
l.
m.
n.
13.
Minimum top and bottom steel in mats shall be each 0.125 percent of gross
concrete area each way.
Minimum skin reinforcement: 16mm bar diameter every 300mm (both direction).
Minimum internal/volume reinforcement: 16 mm bar diameter every 600mm (triaxial directions).
Minimum total reinforcement: 50kg/mc.
Adequate pocket reinforcement around anchor bolts of machine.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
30/34
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
Issue
05
3814-AX-SG-000002
Sheet
31/34
Issue
05
Typical anchor Bolt Detail for Rectangular Block Foundations (ref. PIP REIE 686)
B.
Static Condition
1.
For rotary machinery static design shall include loads due to the weight of the
machinery, auxiliary equipment, other applied loads and the following:
a.
50 percent of the dead weight of the machine and base plate considered as
vertical impact.
b.
Lateral forces representing 25% of the weight of each machine, including its
base plate, applied normal to its shaft at a point midway between the end
bearings.
c.
Longitudinal forces representing 25% of the weight of each machine, including its
base plate, applied along the shaft axis.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
32/34
Issue
05
d.
2.
C.
The total lateral and total longitudinal forces per Section b and c above, shall not
be considered to act concurrently.
For reciprocating machinery static design shall include all loads due to the weight of
the machinery, auxiliary equipment, piping and the following:
a.
Unbalanced forces, couples and moments obtained from the machine
manufacturer.
b.
Individual piston forces
Dynamic Condition
1.
Dynamic design for all type of foundations shall be as follows:
a.
b.
c.
2.
The single amplitude of vibration of the foundation in any direction at any point in the
foundation mat or machine supporting block shall be such that it will fall below the zone
"troublesome to persons" for the specific exciting frequency, as given in figure 1. Where
second-order unbalanced forces are present, total amplitude to be considered at the
primary frequency shall be the sum of the primary and the secondary amplitudes.
Moreover it shall be demonstrated that the vibration amplitudes are lower than the
allowable ones given by the Machine Vendor.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
33/34
Issue
05
D.
E' (N/mm2)
30.000
32.000
34.000
37.000
39.000
Note: values higher than f'c=35 N/mm2 will only be considered for prefabricated concrete.
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
3814-AX-SG-000002
Sheet
34/34
Issue
Figure 1 General limits of displacement amplitude for a particular frequency of vibration (from Richart, 1962)
General limits of displacement amplitude for a particular frequency of vibration (from Richart, 1962).
This document is CDEEEs property, and cannot be used by others for any purpose, without prior written consent
05