You are on page 1of 7

H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet

Product Name

Security Level

WCDMA NodeB

INTERNAL

Product Version

Total 7 pages

INTERNAL

All Version NodeB

H3I ENVA ZTE Rectifier Integration Guide for


Huawei Cabinet

Huawei Technologies Co., Ltd.

2014-11-10

HUAWEI Confidential

Page 1 of 7

H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet

INTERNAL

Contents
1. Physical configuration PMU ZTE rectifier.............
2. Physical connection PMU ZTE to USLP.................
3. Physical connection USLP ke UEIU.......................
4. Configuration at PMU ZTE...................................
5. Huawei BTS/ NodeB configuration ......................
6. Testing and Alarm Handling................................

2014-11-100

HUAWEI Confidential

Page 2 of 7

H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet

INTERNAL

1. Physical Configuration in PMU ZTE rectifier


Check condition port in ZTE rectifier, for connection using X17, X18, and X19 as picture below use
multimeter, select buzzer in multimeter to check condition on port,

2014-11-100

HUAWEI Confidential

Page 3 of 7

H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet

INTERNAL

2. Physical connection PMU ZTE to USLP:


Physical connection on USLP:

X17

X19

X18

Port 6

Port 5

Port 7

ZTE
Main
3. Physical connection
USLPfailure
ke UPEU:
Rect
Connect LAN cable from USLP to UEIU board ,
UPEU

EXT ALM0

To

EXT ALM1

To

USLP

ZTE
DC
Low
Vlt
OUT0
OUT1

4. Configuration at PMU ZTE:


2014-11-100

HUAWEI Confidential

Page 4 of 7

H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet

INTERNAL

Setting PMU configuration on PMU ZTE Rectifier,

Go to the MENU as below table, use pass 0000

Setting parameter as table below (highlight yelow)


2014-11-100

HUAWEI Confidential

Page 5 of 7

H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet

No
.
1
2
3
4
5
9
10
12
13
14
15

Setting Output
Relay
AC AuxSwitch
Of
AC-in Switch Of
AC power Of
Arrester-C Break
Arrester-D Break
SMR.n Alarm
DC Under Vol
DC Loop.n Break
Bat.n Fuse
Break
Bat.n Under Vol
Ennv. alrm

INTERNAL

Relay marking
A4
A4
A4
A4
A4
A2
A3
A3
A3
A3
A5

5. Huawei BTS/NodeB configuration:


Setting MML command in BTS/NodeB, and check to loop and unloop for alarm in NodeB
SET ENVALMPARA:ALMID=65046,ANM="ZTE Rectifier Main
Failure",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:ALMID=65048,ANM="ZTE Rectifier Module
Failure",ALVL=CRITICAL,ASS=POWER;
SET ENVALMPARA:ALMID=65049,ANM="ZTE Rectifier DC Low
Voltage",ALVL=CRITICAL,ASS=POWER;

SET ALMPORT:CN=0,SRN=0,SN=18,PN=0,SW=ON,AID=65046,PT=BOOL,AVOL=LOW;
SET ALMPORT:CN=0,SRN=0,SN=18,PN=1,SW=ON,AID=65048,PT=BOOL,AVOL=LOW;
SET ALMPORT:CN=0,SRN=0,SN=18,PN=2,SW=ON,AID=65049,PT=BOOL,AVOL=LOW;

2014-11-100

HUAWEI Confidential

Page 6 of 7

H3I ENVA ZTE Rectifier Integration Guide for Huawei Cabinet

INTERNAL

6. Testing and Handling:


Since physical connection already connected and BTS/NodeB configuration done, check the alarm
function

No
.
1
2
3

2014-11-100

Alarm
Handling
ZTE Rectifier
Main Failure
ZTE Rectifier
Module Failure
ZTE Rectifier DC
Low Voltage

Alarm Testing
Switch Of AC power
rectifier (PLN down)
Unplug one Modeule
rectifier (Unplug SMR
Module)
Switch Of AC power
rectifier (PLN down) and
Swich of 1 battery
breaker

HUAWEI Confidential

Page 7 of 7

You might also like