Type PM-B, 123-145 kV, up to 63 kA

Power circuit breaker

Standard features
- Dead tank design, with one 3-cycle self-blast interrupter per
tank on a galvanized steel frame
- National Board certification of interrupter tanks per the ASME
Pressure Vessel and Boiler Code
- All tanks factory leak tested in a hard-vacuum chamber with a
helium mass spectrometer
- Certified per ANSI C37.04, C37.06, and C37.09 Standards
- Maintenance-free HMB-2 spring-hydraulic mechanism
- Frame mounted NEMA-3R steel control cabinet protected with
TGIC polyester powdercoat finish
- Single tank-mounted gas density monitor and pressure gauge
- Porcelain bushings
- Continuous current ratings through 4000 A
- Ships fully assembled and factory tested with 5 psig SF6 gas
(bushings may be removed for export transit)
Options and accessories
- Condition monitoring with the Circuit Breaker Sentinel (CBS)
- Density monitor and temperature-compensated pressure gauge
directly-mounted on each tank
- Extra creep and/or extra strike bushings for special applications
- Silicone rubber composite bushings
- Tank heaters for operation in ambient temperatures below
-30 C
- High seismic designs
The 123-145 PM-B breaker is designed with interrupter,
mechanism, and bushing technology and expertise that have
been field proven on ABB SF6 dead tank breakers since 1992.
The breaker features interrupting performance through 63
kA without shunt capacitors for short line fault performance,
a high performance interrupter which complies with IEEEs
new C2 capacitive current switching requirements, high
performance interrupters which reduce the potential for
overvoltages, a compact, fully-integrated spring-hydraulic
operating mechanism, and one-piece interrupter assembly
as well as externally accessible current transformers which
enable simple field change-out.

HMB-2 mechanism
A type HMB-2 spring-hydraulic mechanism, located within the
control cabinet, provides the driving force to gang-operate the
breakers high performance interrupters.
Service
ABB HV Service offers an extensive range of available field services,
from technical assistance to turn-key installation, which can
dramatically reduce construction costs and speed time to commercial
operation.

149 1/4" (3790)

SHIPPING AND INSTALLED WIDTH

84 7/16" (2145)

101 5/8" (2582)

MAXIMUM DIM. FOR BUSHING REMOVAL

MAXIMUM DIM. FOR BUSHING REMOVAL

73 9/16" (1868)

73 9/16" (1868)

35 5/16" (897)

PHASE SPACING

PHASE SPACING

20"
(508)

92 1/16" (2339)

ADDITIONAL HEIGHT
REQUIRED FOR
BUSHING REMOVAL

85 11/16" (2176)
70 5/8" (1794)
METAL TO METAL

60 5/16" (1532)
METAL TO METAL

46 1/16"
(1170)

178 3/8"
(4530)

208"
(5283)

MINIMUM
DIM. FOR
BUSHING
REMOVAL

INSTALLED
HEIGHT

VACUUM /
FILLING CONN.

167 11/16"
(4259)

142 1/4"
(3613)

TOP OF
TERMINAL
PAD

SHIPPING
HEIGHT

80

60
PSIG
40

100

120
20
140

DENSITY MONITOR

RUPTURE
DISC

156 3/4"
(3981)
LIVE
PARTS

98 5/8"
(2505)

119"
(3022)

HEIGHT TO
C OF BREAKER

MINIMUM
BUSHING
HEIGHT

70 3/4"
(1797)

BREAKER
OPERATION
COUNTER

33 9/16"
(852)

31 13/16"
(808)

LOCATION OF EXTERNAL
ELECTRICAL OUTLET

BOTTOM OF
CONTROL
CABINET

LEG
EXTENSIONS

60 1/4" (1530)

73 13/16" (1875)

ANCHOR BOLT SPACING

46 1/8" (1172)

CLEARANCE TO REMOVE INTERRUPTER

ANCHOR BOLT SPACING

Rated capabilities
Circuit Breaker
Type

Rated Maximum
Voltage
(kV, rms)

Short Circuit
and Short Time
Current
(kA, rms)

Maximum
Continuous
Current
(A, rms)

Rated Interrupting
Time
(Cycles)

Full Wave
Withstand Voltage
(kV, Peak)

Power Frequency
Insulation
Withstand Voltage
(kV, rms)

2 -sec Chopped
Wave Impulse
Voltage
(kV, Peak)

Closing and
Latching Current
(kA, Peak)

123PM50-20B

123

50

2000

550

260

710

130

123PM50-30B

123

50

3150

550

260

710

130

123PM50-40B*

123

50

4000

550

260

710

130

123PM63-20B

123

63

2000

550

260

710

164

123PM63-30B

123

63

3150

550

260

710

164

123PM63-40-B*

123

63

4000

550

260

710

164

145PM50-20B

145

50

2000

650

310

838

130

145PM50-30B

145

50

3150

650

310

838

130

145PM50-40B*

145

50

4000

650

310

838

130

145PM63-20B

145

63

2000

650

310

838

164

145PM63-30B

145

63

3150

650

310

838

164

145PM63-40B*

145

63

4000

650

310

838

164

*4000A rating available only with porcelain bushings.

For more information please contact:


ABB Inc.
High Voltage Products
Westmoreland Distribution Park East
100 Distribution Circle
Mount Pleasant, Pennsylvania, USA
Phone: +1 (724) 696-1500
Fax:
+1 (724) 696-1502
www.abb.com/highvoltage

Document Number - 2GNM110004 / September 2010

BUSHING
STRIKE

1 1/8"
(29)

You might also like