Generating Set Control
Technical Manual
CONTENTS
IMPORTANT SAFETY INFORMATION
5
1.
6
GENERAL INFORMATION
1.1
Introduction...................................................................................................................
.................................. 6
1.2
Applications...................................................................................................................
.................................. 6
1.3 PowerWizard Variations .................................................................................
.............................................. 6
1.4 PowerWizard Control Module Description .....................................................
.......................................... 7
2.
8
2.1 Hot
Keys..............................................................................................................................
............................. 8
2.2 Control
Keys..............................................................................................................................
....................... 8
2.3 Navigation Keys
......................................................................................................................................
........ 8
2.4 Event Keys and Indicators ............................................................................
................................................ 9
3. DETAILED OPERATION
10
3.1 PowerWizard Menu
Trees...........................................................................................................................
10
3.2 Technical Operation
....................................................................................................................................
.11
3.2.1 Engine Starting Sequence ................................................................................................
.........................................
11
3.2.2 Engine Stopping Sequence .............................................................................................
.........................................
11
3.2.3 Event System ..........................................................................................................................
.......................................
11
4.
INSTALLATION
15
4.1 Power
Requirements................................................................................................................
.................... 15
4.2 Location
Considerations...............................................................................................................
............... 16
5. SETPOINT PROGRAMMING
24
5.1 Digital Input
Programming...............................................................................................................
......... 24
5.1.1 Digital Inputs ...........................................................................................................................
.......................................
24
5.1.2 Dedicated Digital Inputs ...................................................................................................
.........................................
24
6. RETROFITTING POWERWIZARDS
31
6.1 EST Availability and
Licensing.................................................................................................................... 3
1
6.2 Flash Files and Field Replacement Files
................................................................................................... 31
6.3 Possible EST error messages, their cause and suggested action
......................................................... 34
Network.........................................................................................................................
................................. 48
1.6 Reduced Power Mode ......................................................................................
............................................ 48
1.7 Inputs &
Outputs.......................................................................................................................
................... 48
1.7.1 Digital Inputs ...........................................................................................................................
.......................................
48
1.7.2 Digital Outputs .......................................................................................................................
.......................................
48
1.7.3 Relay Outputs...........................................................................................................................
.....................................
48
1.7.4 Analogue Inputs......................................................................................................................
......................................
48
Most accidents that involve product operation, maintenance and repair are caused by
failure to observe basic safety rules or
precautions. An accident can often be avoided by recognizing potentially hazardous si
tuations before an accident occurs. A
person must be alert to potential hazards. This person should also have the necessar
y training, skills and tools to perform these
functions properly.
1.
GENERAL INFORMATION
1.1
Introduction
PowerWizard
1.1
PowerWizard
1.1+
PowerWizard
2.1
AC Power metering
Analogue Inputs
The controller is available in three versions, PowerWizard 1.1, PowerWizard 1.1+ and P
owerWizard 2.1. These are based on different
feature sets.
This Application and Installation Guide is intended to cover the PowerWizard Generatin
g set Control and its application in
generating set systems. The intended audience for this guide includes generating set
system designers, service support
personnel, dealers and service technicians, contractors and customers.
1.2 Applications
The PowerWizard product line of generating set controllers is designed for use in a wi
de range of applications. They can be
used on standby and prime power diesel generating sets including FG Wilson and Oly
mpian brands. The configurability of the
controllers allows them to be used, in some cases, on other applications such as Mari
ne auxiliary generating set, switchgear
applications, industrial engines and generating sets as well as gas generating sets.
6
1.4 PowerWizard Control Module Description
Some of the different features of the three versions, PowerWizard 1.1, PowerWiard 1.1+ and PowerWizard 2.1 ar
e listed in Table 1.
5
6
7
1
8
9
10
11
12
2
3
4
13
14
15
16
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
Display screen
AC overview key
Engine overview key
Main menu or home key
Alarm acknowledge key
Event reset key
Event log key
Auto key
Stop key
Run key
Escape key
Up key
Right key
OK or Enter key
Down key
Left key
Main Menu key The Main Menu key will navigate the display to the main menu sc
reen. Pressing the navigation keys will
allow access to menus at all levels.
Down key is also used during setpoint entry. During numeric data entry the Scroll
Down key is used in order to decrement the
digits (09). If the setpoint requires selection from a list, the Scroll Down key is
used to navigate down through the list.
Scroll Left The Scroll Left key is used during setpoint adjustment. During numeric
data entry, the Scroll Left key is used to
choose which digit is being edited. The Scroll Left key is also used during certain se
tpoint adjustments to select or deselect a
check box. If a box has a check mark inside, pressing the Scroll Left key will cause
the check mark to disappear, disabling the
function. If the box does not have a check mark inside, pressing the Scroll Left key
will cause a check mark to appear, enabling
the function.
8
2.4 Event Keys and Indicators
Yellow Warning Light A flashing yellow light indicates that there are unacknowledg
ed active warnings. A solid yellow light
indicates that there are acknowledged warnings active. If there are any active warn
ings, the yellow light will change from
flashing yellow to solid yellow after the Alarm Acknowledge key is pressed. If there
are no longer any active warnings, the
yellow light will turn off after the Alarm Acknowledge key is pressed.
Red Shutdown Light A flashing red light indicates that there are unacknowledged
active shutdown events. A solid red light
indicates that there are acknowledged shutdown events active. If there are any acti
ve shutdown events the red light will
change from flashing red to solid red after the Alarm Acknowledge key is pressed.
Any condition that has caused a shutdown
event must be manually reset. If there are no longer any active shutdown events, t
he red light will turn off.
Alarm Acknowledge Pressing the Alarm Acknowledge will cause the horn relay out
put to turn off and silence the horn.
Pressing the key will also cause any yellow or red flashing lights to turn off or to be
come solid depending on the active status
of the alarms.
Event Reset Key Pressing the Event Reset key will reset all events when the contr
ol is in the stopped position. However, Reset
All Events will not reset Present events.
Event Log Key Pressing the Event Log key will navigate to the Active Events me
nu. In order to scroll through the events, use
the up and down keys. After highlighting an event, press the OK key to see infor
mation about the event such as the SPN and
the FMI.
EMERGENCY STOP Push button A red lock-down push button that immediately
shuts down the generating set and will
inhibit start until the push button has been released by turning it clockwise. Prior t
o restarting the set, this fault must be reset
by pressing the Stop button on the module and resetting the fault in the Event L
og Menu.
3. DETAILED OPERATION
3.1
onfig
ure
Software Info
Preferences
Event Log
Engine Overview
AC Overview
I/O Status
Network Staus
Digital Inputs
Relay Outputs
Digital Outputs
Analog Inputs
Primary Datalink
Volt/Hz Control
Idle/Rated
Fuel Transfer
Engine Fuel Priming
Security
Inputs & Outputs
All Setpoints
Engine Operating Hours
Generator AC Monitor
Gen Over/Under Frequency
Gen Over/Under Voltage
Digital Inputs
Relay Outputs
Digital Outputs
Analog Inputs
Automatic Start/Stop
Control
Engine Monitor/protectio AVR Desired Voltage
Gov Desired Speed
n
Fuel Transfer
Events
Gen Monitor/protection
Inputs & Outputs
Contrast
Pressure
Temperature
Lamp Test
Language
Digital Inputs
Relay Outputs
Digital Outputs
Analog Inputs
Digital Inputs
Relay Outputs
Digital Outputs
Analog Inputs
PowerWizard 2.1
Menu Structure
Primary Datalink
Accesory Datalink
MODBUS Serial
Volt/Hz
Control
Idle/Rat
ed
Progra
m Cycle Timer
Fuel Tra
Figure
nsfer
Engine
Fuel Priming
Securit
4: Pow
erWizar
y
Inputs
& Outputs
All Setp
d 2.1 M
Digital Inputs
Relay Outputs
Digital Outputs
Analog Inputs
Control
Engine Monitor/protection
Events
Gen Monitor/Protection
Network
Reduced Power Mode
Prog Trip Points
Inputs & Outputs
oints
Engine
Operating Hours
Rest Co
enu Tre
unters
Time &
Date
Crank Counter
Start Counter
Serv Maint Interval
kWh Meter
kVArh Meter
Contras
t
Pressur
e
Temper
ature
Volume
Lamp T
est
Langua
ge
10
Fuel Transfer
Battery Voltage Monitor
Crank/Start Counter
Engine Speed Monitor
Enhanced Engine Monitor
Service Maintenance Interval
Diagnostic Resp Config
Eng Protect Resp Config
Gen Protect Resp Config
Customer Event Resp Config
Other System Resp Config
Automatic Start/Stop
AVR Desired Voltage
Gov Desired Speed
S/D Override
Generator AC Monitor
Gen AC Power Monitor
Generator Over Current
Gen Over/Under Frequency
Gen Over/Under Voltage
Generator Reserve Power
Datalink-Serial
Digital Inputs
Relay Outputs
Digital Outputs
Analog Inputs
The control receives a start command via the RS-485 SCADA Data Link
(PowerWizard 2.1 only)
The control has a program cycle timer (PCT) configured that becomes active (Pow
erWizard 2.1 only).
2 The PowerWizard checks the system before beginning the cranking sequence. The Po
. werWizard checks that there are no
shutdown events present and that all previous shutdown events have been reset.
3 If the engine is equipped with a form of start aid such as thermostart it will enter a p
. restart sequence.
4 The PowerWizard begins the crank sequence by activating the engine crank relay an
. d the fuel control relay.
If the engine reaches the setpoint for crank terminate speed the engine is deeme
d running and the engine crank relay will
be deactivated
If the engine fails to start within a preset duration (normally seven seconds) the P
owerWizard will stop cranking and wait
for a preset time (normally seven seconds) before attempting to start again
If the PowerWizard fails to start within a preset number of crank attempts (normall
y three) the PowerWizard will activate a
Fail to Start shutdown.
The ope The control is in auto and the remote initiate digital input becomes inactive
rator pre
sses the The control receives a stop command via the RS-485 SCADA Data Link
stop Key (PowerWizard 2.1)
The control has a program cycle timer (PCT) configured that becomes inactive (Po
werWizard 2.1 only)
2 The PowerWizard begins the cooldown period. In order to bypass the cooldown hold d
. own the Stop key for 3 seconds. The
options PRESS ENTER TO BYPASS and PRESS ESCAPE TO CONTINUE will be shown
on the display. Press the Enter key to bypass
3 the cooldown sequence or press the Escape key to continue the cooldown sequence.
.
After the cooldown cycle, the PowerWizard stops the engine by turning off the fuel co
ntrol relay.
11
3.2.5 Event Viewing
There are two ways to view events. Pressing the EVENT LOG key navigates directly to
the ACTIVE EVENTS menu. The other way is
.
3
.
4
.
In order to scroll through the events use the Up and Down keys. Events are ordered
with present events first, active events next
and inactive events last. Within these classifications they are ordered by engine run
hours (or real time clock on PowerWizard
2.1).
Press Enter after highlighting an event to see additional information such as SPN, FMI,
3.3 Security
There are 3 levels of password protection on the PowerWizard control panel. All of the
adjustable setpoints are associated with a
specific level of security required to make an adjustment to the parameter. The passw
ords only affect changing setpoints within
the control panel. Changing setpoints with the Service Tool does not require password
s.
The level of password protection that is required for each setpoint is identified on the
parameter setpoint entry screen. A security
level identification number 1, 2 or 3 next to a padlock symbol is displayed on th
e parameter setpoint entry screen. A Level
3 security is used for the most secure setpoints and Level 1 security is used for the le
ast secure setpoints. If the PowerWizard is
currently at the required level of protection when viewing a parameter, the padlock w
ill not appear.
If a parameter is displayed with a padlock but no security level identification number
next to it, the parameter cannot be changed
from the PowerWizard display and the service tool must be used. Levels 1 and 2 pass
words are disabled as shipped from the
factory. Levels 1 Level 2 passwords are user level passwords and can be used if desir
ed.
The PowerWizard 2.1 also has a SCADA password, which can be used to secure remot
e communications.
To view the security menu,
MAIN MENU > CONFIGURE > SECURITY
At the top of the security menu the current security level is displayed. Within the sec
urity menu are the following options,
12
DROP TO MIN LEVEL used to return the current security level to the lowest level s
etup. Highlight and press OK to drop to
minimum level security. If no Levels 1 or 2 passwords are setup the minimum level
will be 2. If a Level 2 password is setup, the
minimum level will be 1 and if a Level 1 password is setup the minimum level will be
0.
2.
3.
To prime the set press the right cursor key, this will initiate a 180 second priming cyc
le.
13
3.6 Fuel Transfer (PowerWizard 2.1)
Fuel pump in connection with fuel level measurement can be controlled to transfer di
esel to the fuel tank.
1
.
2
.
3.
4.
POUTPUT
C1
T OUTPUT
P2
C
T
P
C
T
1
0
2 3 4 5 6 7
- - - - - 0
- - - - - -
14
4. INSTALLATION
4.1
Power Requirements
The PowerWizard series of generating set controls require a nominal voltage of 12 Vdc
WhenSubsystem
connecting
Loads the PowerWizard generating set control to the DC power source, ma
ke sure that there is only one common
connection to the negative potential of the power source. Make extra effort to avoid
any ground loops in the DC electrical
system. A single point common ground for electronics is recommended at the negati
ve battery terminal or Power Distribution
Box. Each electronics subsystem and major engine subsystem should have its own D
C network so that they do not interfere with
each other. An example is shown in Figure 5.
As shown in the figure all electronics are electrically isolated from higher current load
Engine ECM
15
4.2 Location Considerations
When selecting a location for mounting the PowerWizard generating set control, consi
der the following:
16
L1
L2
L3
N
CTC
CTA
CTB
J1939CANDATALINKS
MODBUS
MPU
DATALINK
13 11 9
7
3
5 3
31
4
47 57 39
50 34 42
67 66
62 64 6
POWERWIZARD 2.1
0-600VAC
0-5AAC
RMS
RMS
LCD DISPLAY
69
DISCRETESINKINGOUTPUT1
BATTERY(-)
65
BATTERY(+)
52
Rly1
Rly2
51
61
53
45
Rly3
48
58
Rly4
35
43
Rly5
33
41
Rly6
32
40
Rly7
26
44
Rly8
27
2 25 15
1 24 14 70 55 54
36 28
16 56
46
38
37
30
29
SYSTEM
BATTERY
12or24VDC
RELAY OUTPUTS
(NOTE A)
LOAD
+12or+24VDC
NOTE(B)
13
Phase B
11
Phase C
Nuetral
9
7
13
Phase B
11
Phase C
Nuetral
17
Phase A
P
Phase B
hase B
Phase C
Nuetral
P
hase C
N
uetral
Phase A
Phase B
Phase C
Nuetral
13
9
7
11
9
13
11
13
9
7
11
POWERWIZA
RD
13
Phase A
Phase B
Phase C
Neutral
11
9
7
Figure 13: Wye Configuration of External Potential Transformers (PT) on the
4-wire Wye connected Generator
18
POWERWIZARD
13
Phase A
11
Phase B
Phase C
9
Figure 14: Open Delta Configuration of External Potential Transformers (PT)
on the 3-wire Delta connected
Generating Set
POWERWI
ZARD
13
Phase A
Phase B
Phase C
Neutral
11
One System Control and Data Acquisition (SCADA) Data Link (PowerWizard 2.1 only
).
19
Wiring
The Primary J1939 communication wires are brought out of the PowerWizard as part of
the 70-pin AMP connector. The pins, as
designated on the AMP connector, are shown in Table 2.
Pin #
Name
Description
34
42
Shield
for CAN
50
CAN1 +
Differential (+) for CAN
On Electr
onic Engi
ne
Engine Service
Connector
Termi
CAN SH
F
G
CAN CAN +
nating
Resist
or #1B
120O
hms
Engin J1
e EC
M
50
34
CANI 42
A B
+
CANI
CANI
SH
Termin
ating
Resisto
r #1A
Power J20
Wizar
d
50
1.1/1. 34
1+
42
CANI
+
CANI
CANI
SH
120Ohms
A B
CAN SH
F
G
CAN CAN +
20
4.6.2 Accessary J1939 Data Link
The Accessory J1939 Data Link is supported by the PowerWizard 2.1.
The Accessory Data Link is used for local or remote communication among modules as
sociated with a single generating set. This
includes annunciators and other expansion modules. The Accessory J1939 Data Link ut
ilizes the same SAE standards as CAN1.
Wiring
Pin #
Name
Description
62
63
Shield
for CAN
64
CAN2 +
Differential (+) for CAN
Termin
ating
Resisto
r #1B
120O
hms
Engin
e EC
M
J1
50
34
42
CAN SH
CAN -
CAN +
A B
Termin
CAN SH
CAN -
CAN +
ating
Resistor
#1A
Power
Wizard J20
2.1
50
CANI 34
42
+
CANI
CANI
SH
120Ohms
A B
Terminating
Terminating
Resistor #2A
120Ohms
Resistor #2B
A secondary
Gen Service
Conn may be
tted
120Ohms
Annunciator
(MCM9)
A B
A B
CANI 62
64
+
CANI 63
CANI
SH
63
64
SC1
CANI +
CANI CANI SH
Figure 17: PowerWizard 2.1 CAN Wiring Diagram (with optional module)
21
4.7 Optional Modules
4.7.1 CAN Annunciator (MCM9)
The PowerWizard Annunciator serves to display generating set system alarm condition
s and status indications. The Annunciator
has been designed for use on the PowerWizard J1939 Communication Network.
It is used in Remote applications being mounted separate from the generating set to
provide remote indication of system
operating and alarm conditions.
The PowerWizard Annunciator is configurable to the standards of NFPA 99/110
Emergency Stop
Fail to start
Lamp test
Mains on load
Utility failed
Generating set failed
J1939 network status
22
PowerWizard 1.1,1.1+
CAN 1
133 FT Maximum
Annunciator 1
PowerWizard 2.1
3 ft Maximum
CAN 2
800 ft Maximum
Annu
nciat
or 3
Annunciator 2
Figure 19: Example illustration of Accessory Data Link Modules and Wire Leng
ths
23
5. SETPOINT PROGRAMMING
The engine/generating setpoints affect the proper operation and serviceability of the
engine and the accuracy of information
shown on the display screen. The setpoints are programmed in the PowerWizard at th
e factory.
The setpoints may require changing when the PowerWizard is moved from one engine
to another engine. The setpoints may also
require changing in order to satisfy the requirements of the installation. The setpoints
that are stored in the PowerWizard must
match the specified setpoints of the particular generating set. For a list of all availabl
e setpoints see Appendix B.
5.1
IN
TO
REMOTE
INITIATE
IN
IN
IN
DIGITAL
INPUT
{1}
IN
DIGITAL
INPUT
{2}
IN
DIGITAL
INPUT
{3}
IN
DIGITAL
INPUT
{4}
DIGITAL
INPUT
{5}
DIGITAL
INPUT
{6}
24
5.1.3 Programmable Digital Inputs
The inputs can be programmed through the following menu options:
MAIN MENU > CONFIGURE > INPUTS & OUTPUTS > DIGITAL INPUTS
The usage type can be selected from the following:
Disable Set to a Command or Status; refer to the Command or Status section below
d
Set to System Events and can be configured to trigger warnings or shutdowns in
the control. System event
configurations determine the PowerWizard response to any supported event
Set to SCADA datalink. In this case the state of the input will be placed into the ap
propriate MODBUS register. No alarms or
warnings will be generated by the control.
1. Command or Status
Command/Status can be configured by selecting Parameters and Active State. The su
pported parameters or components are:
ECS in Run
ECS in Auto
ECS in Stop
Raise Voltage
Lower Voltage
Lower Speed
Raise Speed
Auto Load Fuel (PW1.1+ and PW2.1)
2. System Event
System Event can be configured by setting: Event Parameters, Failure Type, Event Del
ay and Active State. The event type is the
selection of the Suspect Parameter Number (SPN) for the input. Table 4 gives a list of
supported event parameters.
Temperatures
Engine coolant temperature
Engine oil temperature
Exhaust temperature
Generator Rear Bearing Temperature
Generator Winding #1 Temperature
Levels
Engine coolant level
Engine oil level
Fuel level
External fuel tank level
Other
Emergency Stop
EPS Supplying Load (PowerWizard 2.1)
Generator Circuit Breaker Closed
Generator Circuit Breaker Open
Battery Charging System Voltage
Custom Event
Fuel Leak Detected
Generator Current
Generator Power
Inlet Manifold Charge Combustion
Air Damper Closed
Battery Charger Failure
Earth Fault
Earth Leakage
Table 4
25
After the SPN is chosen, the Failure Mode Identifier (FMI) is the next setting. The follo
wing FMIs are available:
High Warning (example: High Temperature Warning)
Low Warning (example: Low Temperature Warning)
Status is used when an event is not essentially high or low but simply exists. An exa
mple of this is the Emergency Stop.
3. SCADA Datalink
When a digital input is configured as SCADA Data Link, the state of the input will be
placed into the corresponding MODBUS
register for remote monitoring. The Active State of the input can be selected as HIGH
or LOW. The HIGH option should be used for
a normally closed switch and the LOW option should be used for a normally open swit
ch.
Relay Outputs
Type A
Type C
An output remains in the inactive state when the output is disabled. The control displ
ay and the SCADA shows the status
of the output as Disabled. An output is active based on the internal logic of the cont
Table 5 gives a
of available
statuses
rollist
when
the output
is set and
to a com
status
mands.
COMMAND / STATUS
Status
Table 5
Run Mode
Auto Mode
Stop Mode
Package not in Auto
Fuel Control Relay
Starter Motor Relay
Start Aid
Disable Aux AC Supply
Crank Alert
Engine Start Initiated
Engine Started
Rated Speed
V/Hz within Limits
Engine in Cooldown
Package waiting on Delay on Stop
Horn Control
Common Warning
Common Shutdown
ECU Fault Reset
Command
Air Shutoff
Programmable Cycle Timer Output #2
kW relay Trip #1
kW relay Trip #2
Common Alarm
Breaker #1 Trip
Breaker #2 Trip
Reduced Power Off
Transfer Fuel In
Transfer Fuel Out(1)
Voltage Raise Command
Voltage Lower Command
Speed Raise Command
Speed Lower Command
Nominal Frequency Selection Low / High(1)
Nominal Voltage Selection Low / High(1)
26
The procedures that must be performed in order to program the outputs depend on the us
age type for the output. Usage types
are activated from the menu options below.
MAIN MENU > CONFIGURE > INPUTS & OUTPUTS > RELAY OUTPUTS
MAIN MENU > CONFIGURE > INPUTS & OUTPUTS > DIGITAL OUTPUTS
1. COMMAND / STATUS
Auto Mode Activated after the auto key has been pressed or a Modbus command is
given to set engine operating mode to
auto (register 302) and while the control remains in the auto mode.
Generator Breaker Trip 1 Activated when any event occurs that has an event resp
onse configuration set for Breaker Trip #1.
This deactivates when the event is neither present nor active. This output does not c
ontrol a circuit breaker unless the user makes
the connections to do so. This output type should be viewed as having a generic nam
e because the name does not necessarily
imply the action that is performed.
Breaker Trip 2 Activated when any event occurs that has an event response config
uration set for Breaker Trip #2. This
deactivates when the event is neither present nor active. This output does not control
a circuit breaker unless the user makes the
connections to do so. This output type should be viewed as having a generic name b
ecause the name does not necessarily imply
the action that is performed.
Common Alarm Activated any time that the control initiates and/or detects either a
shutdown event or a warning event. This
deactivates when no warnings or shutdowns are present or active.
Disable Aux AC Supply The Disable Aux AC Supply is intended to be used in ord
er to disconnect the battery charger, heaters
etc when the engine is running. It is activated when the engine start is initiated. This
deactivates when the engine is stopped or
Run Mode Activated after the run key (8) has been pressed or a Modbus command
is given to set the Engine Operating Mode
to Run (register 302) and while the PowerWizard remains in the Run mode.
Start Aid Requires that the set point for Start Aid Activation Time is to be set grea
SYSTEM
ter than zero. It is activated when the
engine EVENT
start is initiated. The engine start also starts theGen
timer.
This deactivates after Start Ai
Pressure
Frequency
d Activation
Engine Oil
Pressure Time expires.
Gen Real Power
Gas Pressure
Gen Voltage
Temperature
Primary Data Link
27 Data Link (PW2.1 Only)
Engine Coolant Temperature
SCADA
Engine Oil Temperature
Service Interval Expired
V&Hz
Within
Limits
The
normal
operating
range
is defined Eng
as being
Exhaust Temperature
Unexpected
S/D neither above th
e
high
warning
or
shutdown
thresholds,
Gen Rear Bearing Temp
Earth Fault
nor below the low warning or shutdown thresholds. Activated when measured generato
Gen Winding #1 Temp
Earth Leakage
r voltage and frequency (that is
Levels calculated as a percentage of rated voltage and frequency)
Engine Controller
are both within the normal
Engine operating
Coolant Level
Fuel Leak
range. This deactivates when
Engine either
Oil Level
Air Damper
Closed the normal operati
the measured generator voltage or the frequency
are outside
Fuel Level
Battery
Charger
Fail
ng range.
External
Fuel Level
Gen Breaker Open
2.Tank
SYSTEM
EVENT
Others
Gen Breaker Closed
EVENT PARAMETER and EVENT TRIGGER conditionCustom
need to be
selected for SYSTEM EVEN
Any SPN
Events
T. Table
is a (PW2.1
list of available
Accessory
Data6Link
Only) system
Digital Input #1 Custom Event
Battery Charging Sys Volt
Digital Input #2 Custom Event
Battery Voltage
Digital Input #3 Custom Event
FMI 02 Data Erratic: Intermittent or Incorrect
Emergency Stop Switch
Digital Input #4 Custom Event
Any Shutdown
FMI 03 Voltage Above Normal or Shorted to High Sou
Engine in Cooldown
Digital Input #5 Custom Event
Any Warning or Shutdown
Engine Fail to Start
Digital Input #6 Custom Event
Low Warning
FMI 04 Voltage Below Normal or Shorted to Low Sour
Engine Speed
Analog Input #1 Custom Event
High Warning
FMI 05 Current Below Normal or Open Circuit
Control Not in Auto
Analog Input #2 Custom Event
High / Low Warning
FMI 06 Current Above Normal or Grounded Circuit
Gen Current (Amp)
Analog Input #3 Custom Event
Low Shutdown
FMI 07 Mechanical System Not Responding or Out of
Generator Circuit Breaker Closed
Digital
Input #5 Custom Event
Adjustment
Generator
Circuit Breaker Locked Out
Digital
Input
#6 Custom
Event Pulse Width or Period
High Shutdown
FMI 08
Abnormal
Frequency:
Generator
Circuit
Breaker
Failure
to
Open
AnalogueInput
#1
Custom
High / Low Shutdown
FMI 09 Abnormal Update Event
Rate
Generator
Circuit
Breaker
Failure
to
Close
AnalogueInput
#2 Custom
Low Warning or Shutdown
FMI 10 Abnormal
Rate of Event
Change
Utility
Generator
Transfer Failure
AnalogueInput
#3 Custom
Event
High to
Warning
or Shutdown
FMI 11 Root Cause
Not Known
High / Low Warning or High / Low Shutdown
High / Low Warning or High / Low Shutdown or Diagn
conditions.
Any Diagnostic
Condition Exists
Table 7
28
EVENT TRIGGER is used to select the desired condition in order to trigger the event. Ta
ble 7 is a list of the available trigger
events.
3. SCADA DATALINK
When an output is configured for the SCADA data link, its active state can be sent ov
er the Modbus.
Map
Map 1
Map 2
Map 3
Map 4
Map 5
Map 6
Map 7
Map 8
Map 9
Map 10
Map 11-25
Table 6
Description
VDO Pressure Curve 4
Pressure 246-8150
VDO Temperature Curve 1
Temp 191-6587
VDO Temperature Curve 2
Temp 349-2458
Fozmula Level 1
Linear 0 to 2000 ohm
XQ Fuel 1
XQ Fuel 2
Future Use
29
2. Voltage sender
For a voltage sender, the desired voltage range and corresponding data range need to
be selected. The available voltage ranges
are given in Table 10. The minimum and maximum data points can be set under the
menu of DATA RANGE MIN and DATA RANGE
MAX.
Table 9
30
6. RETROFITTING POWERWIZARDS
When replacing a PowerWizard or when fitting a new one, ensure that the correct con
troller type is selected i.e. PowerWizard 1.1
or PowerWizard 2.1. The differences between these are listed in the PowerWizard Vari
ations section. The Electrical Connection
drawings are shown in the Electrical Connections section.
6.1
Therefore EST is an essential service tool for carrying out service operations on the Po
werWizard.
Instructions on purchasing and licensing EST can be found on the FG Wilson Dealer w
ebsite PowerUp2 or by contacting the EST
Software License and Support Coordinator.
Tel: +44 (0) 28 2826 5228
email: support_tools@fgwilson.com
The Field Replacement Files only exist for controllers that have previously been progra
mmed at the factory. FG Wilson cannot
create Field Replacement Files for controllers that are in the field and that have not pr
eviously been programmed at the factory.
However Field Replacement Files can be used on more than one controller. So if the c
onfiguration you want is the same as a
previous set, the same Field Replacement File can be used.
The same procedure is used again for obtaining this file. Contact the FG Wilson After
Sales Helpdesk supplying the Generating set
Serial Number and they will send you the required Field Replacement File.
Note:
If a Field Replacement File that was created for a PowerWizard 1.1 is loaded onto a Po
werWizard 2.1, some of the items
on the PowerWizard 2.1 will not be configured. To configure these items open EST and
select Configuration (SERVICE
CONFIGURATION).
Field replacement files from a PW X.0 cannot be used on PW X.1.
31
Using EST to load Flash Files
It is recommended to use the latest version of the service tool. While any version from
2004A onwards should work, it is easier to
follow screen shots and menu navigation if the latest version is used.
1. Open EST Winflash (This should be a separate option to Electronic Service Tool from
within the EST sub menu of Windows or
2. it can be accessed from the Service Tool menu by selecting Utilities -> Winflash
3.
4.
Ensure that the service tool is using RP1210 (under Utilities -> preferences ->
communications)
Ensure that the communications adapter is connected to the correct port of the PC
You should have a screen similar to:
Youre finished.
All the (old) setpoints are preserved when the PowerWizard control is re-flashed.
32
Using EST to load Field Replacement Files
1 Open EST ECM Replacement by selecting the Service Copy Configuration ECM Re
. placement menu item, as shown in the
figure below.
2 Select the Field replacement File (.xml file) that you want to load as shown in the scr
. een below.
The following screen will then be displayed showing the configuration values.
3 Select Program ECM to load the configuration values onto the controller. Once the co
. nfiguration values have been successfully
loaded the message Programming Complete will be displayed.
33
6.3 Possible EST error messages, their cause and suggested action
The communication adapter was unable to connect to the J1939 data link.
Cause: EST was unable to see the Communication adaptor on the port it is expecting
it to be connected to
resistor(s).
The ECM software file and the ECM are not compatible. Process aborted. - Err
or Code: 163840
Cause: The flash file is not compatible with the PowerWizard. This is usually seen whe
n trying to flash a module with software for a
different module, such as trying to flash a PW1.1 with a flash file for a PW1.1+ or 2.1.
Use a flash file that is compatible with the level of PowerWizard control you are try
ing to flash.
No flash file selected for the ECM
Cause: This error message is seen when trying to use a flash file that is not suitable f
or any level of PowerWizard control.
Use a flash file that is compatible with the level of PowerWizard control you are try
ing to flash.
34
7.
7.1
If Reduced Power Mode is enabled and the generating set is stopped the control will
enter reduced power mode a preset
time (normally 30 minutes) after the last key press. The Control will awaken from Red
uced Power Mode upon a key press, an
Emergency-Stop or a remote start signal.
Enabling Reduced Power Mode on Using EST
1 Open EST
. Ensure that the service tool is using RP1210 (under Utilities -> preferences ->
2
communications)
.
Ensure that the communications adapter is connected to the correct port of the PC.
3
Connect to the PowerWizard control (Press F8).
.
Select Configuration (Service -> Configuration) or (press F5).
4
It will take some tome for the service tool to check which blocks are installed. After a
.
bout 30 seconds the screen will look like
5 this:
.
6
.
35
A Level 3 password is required to allow the user to enter this screen and to enable th
e Reduced Power Mode.
The user may also change the time delay before the Reduced Power Mode is activate
d by entering the screen shown below.
REDUCED POWER MODE
DELAY TIME
30 MINS
Note:
The remote communications (RS485) and the J1939 communications will not oper
ate when the controller is in Reduced
7.3
Setting Language
The PowerWizard module gives the operator the choice of using one of two available l
anguages.
1 Technical English
. Customer Language
2
.
To select your preferred language scroll to the LANGUAGE menu as shown below.
MAIN MENU PREFERENCES LANGUAGE
Use the curser to highlight the preferred language and press the OK key to select it.
Note:
Preferences is the last option on the main menu and Language is the last option i
n Preferences.
36
7.4
VIEWENTER
This takes you to the screen that is used to configure the desired response for the "N
ot In Auto" alarm. The options available can
be viewed or edited.
WARNING
AUDIBLE ALERT
ACTIVE ONLY
A indicates which options are selected. The user may select or remove by using
the left cursor key. If unable to EDIT check
that the generating set is in STOP position and that the required password level is use
d.
7.5
elow:
MAIN MENU > CONFIGURE > SETPOINTS > CONTROL > AUTO START/STOP
Press enter and then scroll down till you come to the START AID ACTIVATION TIME scr
een.
Once at this screen, set the time to 0 seconds.
37
1.1
SPN/FMI List
APPENDIX A
Event Name
External Tank High Fuel Level Shutdown
External Tank Low Fuel Level Shutdown
External Tank Fuel Level Sensor Short High
External Tank Fuel Level Sensor Short Low
External Tank High Fuel Level Warning
External Tank Low Fuel Level Warning
High Starting Air Pressure Shutdown
Low Starting Air Pressure Shutdown
Starting Air Pressure Sensor Short High
Starting Air Pressure Sensor Short Low
High Starting Air Pressure Warning
Low Starting Air Pressure Warning
High Fuel Filter Differential Pressure Shutdown
Low Fuel Filter Differential Pressure Shutdown
Fuel Filter Differential Pressure Sensor Short High
Fuel Filter Differential Pressure Sensor Short Low
High Fuel Filter Differential Pressure Warning
Low Fuel Filter Differential Pressure Warning
High Fuel Level Shutdown
Low Fuel Level Shutdown
Fuel Level Sensor Short High
Fuel Level Sensor Short Low
High Fuel Level Warning
Low Fuel Level Warning
High Engine Oil Level Shutdown
Low Engine Oil Level Shutdown
Engine Oil Level Sensor Short High
Engine Oil Level Sensor Short Low
High Engine Oil Level Warning
Low Engine Oil Level Warning
High Engine Oil Filter Differential Pressure Shutdown
Low Engine Oil Filter Differential Pressure Shutdown
Engine Oil Filter Differential Pressure Sensor Short High
Engine Oil Filter Differential Pressure Sensor Short Low
High Engine Oil Filter Differential Pressure Warning
Low Engine Oil Filter Differential Pressure Warning
Low Engine Oil Pressure Shutdown
Engine Oil Pressure Sensor Short High
Engine Oil Pressure Sensor Short Low
Low Engine Oil Pressure Warning
High Air Filter Differential Pressure Shutdown
Low Air Filter Differential Pressure Shutdown
Air Filter Differential Pressure Sensor Short High
Air Filter Differential Pressure Sensor Short Low
High Air Filter Differential Pressure Warning
Low Air Filter Differential Pressure Warning
High Engine Coolant Temperature Shutdown
Engine Coolant Temperature Sensor Short High
Engine Coolant Temperature Sensor Short Low
High Engine Coolant Temperature Warning
Low Engine Coolant Temperature Warning
High Engine Coolant Level Shutdown
38
Low Engine Coolant Level Shutdown
SPN
FMI
38
38
38
38
38
38
82
82
82
82
82
82
95
95
95
95
95
95
96
96
96
96
96
96
98
98
98
98
98
98
99
99
99
99
99
99
100
100
100
100
107
107
107
107
107
107
110
110
110
110
110
111
111
0
1
3
4
15
17
0
1
3
4
15
17
0
1
3
4
15
17
0
1
3
4
15
17
0
1
3
4
15
17
0
1
3
4
15
17
1
3
4
17
0
1
3
4
15
17
0
3
4
15
17
0
1
Event Name
Engine Coolant Level Sensor Short High
Engine Coolant Level Sensor Short Low
High Engine Coolant Level Warning
Low Engine Coolant Level Warning
High Fire Extinguisher Pressure Shutdown
Low Fire Extinguisher Pressure Shutdown
Fire Extinguisher Pressure Sensor Short High
Fire Extinguisher Pressure Sensor Short Low
High Fire Extinguisher Pressure Warning
Low Fire Extinguisher Pressure Warning
Low Battery Charging System Voltage Warning
High Battery Voltage Shutdown
High Battery Voltage Warning
Low Battery Voltage Warning
High Ambient Air Temperature Shutdown
Low Ambient Air Temperature Shutdown
Ambient Air Temperature Sensor Short High
Ambient Air Temperature Sensor Short Low
High Ambient Air Temperature Warning
Low Ambient Air Temperature Warning
High Exhaust Temperature Shutdown
Low Exhaust Temperature Shutdown
Exhaust Temperature Sensor Short High
Exhaust Temperature Sensor Short Low
Exhaust Temperature Signal Abnormal
High Exhaust Temperature Warning
Low Exhaust Temperature Warning
High Engine Oil Temperature Shutdown
Low Engine Oil Temperature Shutdown
Engine Oil Temperature Sensor Short High
Engine Oil Temperature Sensor Short Low
High Engine Oil Temperature Warning
Low Engine Oil Temperature Warning
Engine Over Speed Shutdown
Engine Under Speed Shutdown
Engine Speed Sensor Erratic or Not Present
Engine Speed Sensor Open
Engine Under Speed Warning
Software Version Mismatch
SCADA Data Link Fault
Primary Data Link Fault
Custom Event #1 High Shutdown
Custom Event #1 Low Shutdown
Custom Event #1 High Warning
Custom Event #1 Low Warning
Custom Event #1 Status
Custom Event #2 High Shutdown
Custom Event #2 Low Shutdown
Custom Event #2 High Warning
Custom Event #2 Low Warning
Custom Event #2 Status
Custom Event #3 High Shutdown
Custom Event #3 Low Shutdown
Custom Event #3 High Warning
Custom Event #3 Low Warning
Custom Event #3 Status
Custom Event #4 High Shutdown
Custom Event #4 Low Shutdown
39
SPN
FMI
111
111
111
111
137
137
137
137
137
137
167
168
168
168
171
171
171
171
171
171
173
173
173
173
173
173
173
175
175
175
175
175
175
190
190
190
190
190
234
625
639
701
701
701
701
701
702
702
702
702
702
703
703
703
703
703
704
704
3
4
15
17
0
1
3
4
15
17
17
0
15
17
0
1
3
4
15
17
0
1
3
4
8
15
17
0
1
3
4
15
17
0
1
2
5
17
31
11
11
0
1
15
17
31
0
1
15
17
31
0
1
15
17
31
0
1
Event Name
SPN
FMI
704
704
704
705
705
705
705
705
706
706
706
706
706
707
707
707
707
707
708
708
708
708
708
709
710
711
712
713
714
715
716
924
925
970
1122
1122
1122
1122
1122
1122
1124
1124
1125
1125
1126
1126
1231
1239
1383
1390
1390
1390
1390
1664
2433
2433
2433
2433
15
17
31
0
1
15
17
31
0
1
15
17
31
0
1
15
17
31
0
1
15
17
31
31
31
31
31
31
31
31
31
3
3
31
0
1
3
4
15
17
0
15
0
15
0
15
11
31
11
0
1
15
17
31
0
1
3
4
Event Name
SPN
FMI
2433
2433
2433
2434
2434
2434
2434
2434
2434
2434
2436
2436
2436
2436
2436
2436
2440
2440
2440
2440
2448
2448
2452
2452
2452
2648
3543
3546
3783
3829
3880
3881
3882
3883
3888
3889
3890
3891
3892
3893
3894
3895
3896
3897
3898
3899
3904
3905
3906
3907
3908
3909
3910
3911
3912
3913
3914
3915
8
15
17
0
1
3
8
4
15
17
0
1
2
12
15
17
0
1
15
17
0
15
1
15
17
31
9
11
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
Event Name
SPN
FMI
3920
3921
3922
3923
3924
3925
3926
3927
3928
3929
3930
3931
4000
4001
4002
4003
4004
4005
4006
4007
4009
4010
4011
4012
4013
4014
4015
4015
4016
4017
4018
4019
4028
4029
4256
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
0
15
15
31
31
31
31
31
17
42
1.2 Control
Setpoints > Control > Automatic Start/Stop
Setpoint Name
Min
Max
Value
Value
Units
Description
300
Sec
Crank Duration
300
Sec
300
Sec
20
Sec
20
N/a
Cooldown Duration
30
Min
240
Sec
60
Sec
100
1000
RPM
List
List
List
List
List
List
List
List
34
690
Kpa
34
690
Kpa
400
1800
RPM
Min
Value
Max Min
Units Max
ValueValue
Value
Units Description
Description
Flywheel Teeth
95
The
350Maximum
N/A
Generator Output voltage Bias Percent
Maximum
Generator
Voltage
s
the
Engine
Over Speed
Shutdown
Threshold
400
4330
rpm
Set to 118% of rated speed
0
100
%
Percentage
maximum
value
above
andtobelow
the
Nominal
Voltage
EngineOutput
UnderBias
Speed
Warning Event Threshold
400
4330
rpm
Set
86% of
rated
speed
43
hat
the
Engine Under Speed Warning Event Notification
0.0
20.0Generator
sec.
The
Nominal Output Voltage is the desired
Delay
Generator Nominal Output
100
50000
V
utput
Engine
Under
SpeedDesired
Shutdown
Event Threshold
400
4330
rpm
Set to 82% of rated speed
1.2.3
Governor
Engine
Sp
Voltage
Setpoints
> Engine
Monitor/Protect
Engine
Monitor
Setpoint
Name
MinNotificatio
Max> Enhanced
Units voltage
Description
of the
generating
set. This value is set to ma
Engine
Under
Speed
Shutdown
Event
eed
0.0
20.0
sec.
Value Value Min
Max
n
Setpoint Name
Units
Description
Engine Speed Sensor Configuration
Value
List
The
Maximum
Engine Speed Range is the maximum v
Value
Value
ue List
Maximum
EngineTemperature
Speed Range
0 Installatio
2000
rpm Value
Engine Cylinder
Sensor
Select Installed or Not installed
above and below the Nominal Engine Speed that Powe
n
Wizard
Number of Engine
1
20
n/a
Setpoints
> EngCylinders
Monitor/Protect > Service
Maintenance
Interval
Generator Nominal Output
40
500
Hz
This value is set to match the generator rated frequenc
Setpoints
> Engine Monitor /Min
Protect Max
> BatteryUnits
Voltage Factory
Monitor Default
Frequency
Setpoint
Name
y
Setpoint Name
Value
Value Min
Max Value
Units
44
1.5.4 Generator
1.3.3
Engine Speed
overMonit
curre
or
nt
1.5.1 Enhanced generator monit
or
80
130
%
100
Threshold for the Over Current Warni
(Amp) Warning Event Percentage
Set to Installed when a
Generator Winding Temperature Sensor
Threshold
ng
Value List
temperature module is installe
Installation Status
Time multiplier
setpoint (TM) used
d
Generator Inverse Time Over Current
0.05
10.00
N/A
0.27
n
Number
of Generator
Bearing
Temperatur
(Amp)
Shutdown
Event Time
Multiplier
Value List
equation:
e
Generator Definite Time Over Current
If
current
is
above
this setpoint valu
45
Configurations
can
be: Star/Wye
100
300
%
125
(Amp) Shutdown Event Percentage
e for
Delta/3
Wire
1.3.4
Enhanced
Engine
Monit
Threshold
the specified time (setpoint #4) the
Generator
Connection
Configuration
Value List
1.5
Generator
Monitor / Protect
Delta/4 WireFactory
Max
or
Min
Generator
Definite
Time
Over
Current
Setpoint
Name
Min
Value Single
Units
Units
Description
Setpoint
Name
Phase
2 WireSingle
Phase
10
Time delay
for setpoint
#3 3
(Amp) Shutdown Event Notification Del 0.1
Value
Default
Value 20.0Value
Max sec.
1.5.5 Generator Over / Under Freque
For
direct
sensing
leave
at
default
val
ay
Generator
Over Frequency Warning Event Percentage Threshold
80
120
%
105
ncy
Generator Potential Transformer Primary
ue.
1
50000
Generator
Over Frequency Warning Event Notification
Delay
Ti
0.0 V
120
sec.
10
Winding Rating
For an application requiring a potenti
Generator Over
Frequency
Shutdown
Event
Percentage
Thresh
80.0
120
%
110
1.5.2 Generator AC monitor
al
Generator Over Frequency Shutdown Event Notification Delay
0.0
120
sec. leave at default
2
For
direct
sensing
val
Setpoints > Generator Monitor/Protect
> Generator
Generator
Under
Frequency
Warning
Event
Percentage
Threshol
80.0
120.0
%
95.0
Generator Potential Transformer Secondary
ue.
1
240
V
ACFrequency
MonitorWarning Event Notification
Generator
Under
Delay
0.0
120
sec. requiring10
Winding Rating
For
an application
a potenti
Generator Under Frequency Shutdown Event Percentage Thres
80.0
%
90.0
al120.0
Max
Factory
Setpoint
Name
Min
Units
Generator
Generator
Under
Current
Frequency
Transformer
Shutdown
Primary
Win Notification
Delay
0.0Value
Set120
to current transformer
sec.
primary
4
win
1.3.5
Service
Maintenance
InterEvent
1
7000
A
Value
Default
ding
ding
val
Generator Current
Over Voltage
Warning
Event Percentage Threshold
100
125
%
105
Generator
Transformer
Secondary
1
5
A
Can only be set to 1 or 5
Generator
Over
Voltage
Warning
Event
Notification
Delay
Time
0.0
120
sec.
10
Winding
Rating
Setpoints > Gen Monitor/Protect > Gen AC Power Mon
Generator
Voltage
Shutdown Event Percentage
Threshold
100
125
%
110
Number
of Over
Generator
Poles
0
200
N/A
Name Event Notification
MinDelay
Value
Units sec.
Factory Default
Generator Rated
OverSetpoint
Voltage
Shutdown
0.0 Value 120
2
Generator
Frequency
ValueTim
List Max
Generator
Under
Voltage Security
Warning Level
Eventto
Percentage
60V
100
%
95
Generator
Rated
Voltage
100 Threshold
50000
Customer
Password
Reset
0
3
N/A
3
Generator Rated
Under
Voltage
Warning
Event Notification
Delay
Time
0.0
120
sec.
10
Generator
Energy
Meters
Generator
Power
1
50000
kW
1.5.6
Generator
Over
/
Under
Volt
Generator
Under
Voltage
Shutdown
Event
Threshold
60
100
%
Generator Rated Apparent Power
1
50000
kVA
Min
Max Value 90
Units
Setpoint
Name
age
Generator Under Voltage Shutdown Event Notification Delay Ti
0.0
120
sec.
4
Value
1.4 Events
Generator Reverse Power Warning Event Notification Delay Time
Generator Reverse Power Shutdown Event Percentage Threshold
Generator Reverse Power Shutdown Event Notification Delay Time
1
0
1
0
20
30
20
30
46
47
%
sec.
%
sec.
Setpoint Name
Max Value
Setpoint Name
Value
Value
100
min
Units
N/A
N/A
N/A
N/A
sec.
N/A
Description
Description
1.6 Network
48
1.7 Reduced Power Mod
Setpoints > Inputs & Outputs > Analogue Input (#1 to #3)
e
Min
Max
Resolution Units Factory
Setpoint Name
Value
Value
Default
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Analogue
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Type
Range
Data Identification
Configuration Code
Data Range Min
Data Range Max
High Warning Event Threshold
High Warning Event Delay
Low Warning Event Threshold
Low Warning Event Delay
High Shutdown Event Threshold
High Shutdown Event Delay
Low Shutdown Event Threshold
Low Shutdown Event Delay
Isolated Supply Voltage
Common Supply Voltage
Value list
Value list
Value list
1
-1
-1
0
0
0
0
0
0
0
0
25
1
50000
0.01
50000
0.01
50000
1
240
0.10
50000
1
240
0.10
50000
1
240
0.10
50000
1
240
0.10
Value list
Value list
N/A
N/A
N/A
N/A
sec
N/A
sec
N/A
sec
N/A
sec
0
0
0
1
0
100
100
0
0
0
100
0
0
0
0
0
menu.