Professional Documents
Culture Documents
NCS
Document 51658
2/28/2007
Rev:
P/N 51658:H
H
ECN 06-718
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49
C/32-120 F and at a relative humidity 93% 2% RH (noncondensing) at 32C 2C (90F 3F). However, the useful
life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27 C/60-80 F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
Acclimate Plus, HARSH, NIS, Notifier Integrated Systems, NOTIFIRENET, and ONYXWorks are all trademarks; and FlashScan, NION,
NOTIFIER, ONYX, UniNet, VeriFire, and VIEW are all registered trademarks of Honeywell International Inc. Echelon is a registered trademark and
LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are
registered trademarks of the Microsoft Corporation. LEXAN is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
2007 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
Please note this email address is for documentation feedback only. If you have any technical
issues, please contact Technical Services.
Table of Contents
Section 1: Introduction............................................................................................................. 8
1.1: Related Documentation .................................................................................................................................8
1.2: UL 9th Edition Compliance...........................................................................................................................8
1.3: Notes, Cautions, and Warnings......................................................................................................................9
1.4: Typographic Conventions ..............................................................................................................................9
Section 2: Installation............................................................................................................. 10
2.1: NCS Mounting and Connections .................................................................................................................10
2.1.1: NCS Equipment.................................................................................................................................10
2.1.2: The NCS-NCW/F Board ...................................................................................................................10
2.1.3: Primary and Secondary Power ..........................................................................................................13
2.1.4: Power Requirements..........................................................................................................................13
2.1.5: Connecting the NCS Computer .........................................................................................................13
2.1.6: Connecting the Monitor.....................................................................................................................15
2.1.7: Internal Modem to Telephone System...............................................................................................16
2.1.8: NCS UPS Supervision .......................................................................................................................16
2.1.9: Strain Relief.......................................................................................................................................19
2.2: Peripherals ...................................................................................................................................................19
2.2.1: Printers...............................................................................................................................................19
2.3: PC Configurations .......................................................................................................................................20
2.4: Software .......................................................................................................................................................21
2.4.1: Installing the NCS Software ..............................................................................................................21
2.4.2: NUP Port Auto-Configuration/Serial Port Configuration .................................................................21
2.4.3: Installing Printers...............................................................................................................................21
2.4.4: Read/Write CD ROM ........................................................................................................................22
2.4.5: Windows 2000 Secure Desktop Configuration .................................................................................23
Section 4: Operation............................................................................................................... 56
4.1: Normal Operation ........................................................................................................................................56
4.2: AutoNavigate ...............................................................................................................................................56
4.3: Troubles .......................................................................................................................................................57
4.4: Alarms..........................................................................................................................................................58
4.5: Supervisory, Security, and Other Activation ...............................................................................................59
4.6: Menu Options for Operating the NCS ........................................................................................................60
4.6.1: File Menu...........................................................................................................................................60
4.6.2: Operator Menu...................................................................................................................................60
4.6.3: The Action Menu...............................................................................................................................62
4.6.4: The View Menu .................................................................................................................................67
ONYX NCS Manual P/N 51658:H 2/28/2007
Table of Contents
Table of Contents
Index
.................................................................................................................................. 143
Section 1: Introduction
The Notifier Network Control Station (NCS) is a high performance desktop NCS computer with
text and graphics display capability for all network events and points. Connecting via the NFN
Gateway, the NCS is used with the NOTIFIRENET system, and runs under the user-friendly
Windows environment.
NOTE: The illustrations in this manual depict nodes on a local area network (LAN). Network
addresses differ when using the wide area network option. See the Wide Area Network &
NOTIFY-IP Addendum (51658ADD) for more information.
Document Number
15378
Fire Alarm Control Panel (FACP) and Main Power Supply Installation
Document Number
15511
AM2020/AFP1010 FACP
15088
Document Number
VERIFIRE-TCD
Networking
Document Number
51584
51482
52482
52411
51533
Addendum to the
ONYX
51658ADD
Audio Applications
Document Number
52411
52626
51118
Introduction
The following products have not received UL 864 9th Edition certification and may only be used in
retrofit applications. Operation of the NCS with products not tested for UL 864 9th Edition has not
been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These
applications will require the approval of the local Authority Having Jurisdiction (AHJ).
NFS-3030 Fire Alarm Control Panel
AFP-200 Fire Alarm Control Panel
AFP-300/AFP-400 Fire Alarm Control Panel
AFP1010/AM2020 Fire Alarm Control Panel
NFS-640 Fire Alarm Control Panel
NCA Network Control Annunciator
NCS Network Version 4.0 and lower
Specifies
Example
text in quotes
a reference to a section or a
LCD menu screen
bold text
italic text
a specific document
In a graphic, a key as it
appears on the control panel
Press
Section 2: Installation
2.1 NCS Mounting and Connections
2.1.1 NCS Equipment
The Network Control Station is a kit comprised of:
an NCS Computer
NOTE: The monitor and mouse, as well as the printer (if one is used), must be installed in the same
room as the NCS in order to comply with UL listing requirements.
Components
ONYX NCS computer (p/n NCS5-P4F), mouse,
10
Installation
NOTIFIRENET
EIA-232 CONN
(NUP Port)
CH A
UPS SUPV
N/C
CH B
NOTIFIRENET
Connections
Connections
EARTH
TERM B
EF B
EIA-232 CONN
(NUP Port)
UPS SUPV
N/C
The NCS ships with a
shunt plug over the
UPS SUPV pins.
Remove the shunt to
wire for UPS SUPV.
RX A
RX B
TX B
TX A
A HI
LED7
LED5
LED1
RCDB
PULSE1
RECON
RESET
LED4
LED3
LED7
LED5
LED1
LED3
STATB
LED4
B HI
SW102 SW101
TERM B EF B
1
TERM A EF A
LED100
LED2
LED2
STATA RCDA
LED6
EF A
LED6
STATA RCDA
A HI
TERM A
STATA
RCDA
STATA
RCDA
B HI
LED101
STATB
RCDB
PULSE1
RECON
RESET
Battery, P/N
LITHBATT-3V
(Ships with paper
strip between
battery and
clip/connector.
Paper must be
removed to enable
battery.)
Battery, P/N
LITHBATT-3V
(Ships with paper
strip between
battery and
clip/connector.
Paper must be
removed to enable
battery.)
NCS-NCF
NCS-NCW
Piezo sounder - Pulses on and off when the NCS application is not running properly, or during loss
of power from the NCS. (Not shown)
LEDs - The NCS-NCW board has nine LED indicators; the NCS-NCF board has seven. Table 2.2
lists and describes each. These LEDs are visible when the NCS-NCW/F card is exposed.
LED Name
Color
Description
A HI
Green
STATA
Yellow
RCDA
Green
B HI
Green
STATB
Yellow
RCDB
Green
11
Installation
Green
RECON
Yellow
RESET
Yellow
Source.
PCI EDGE CONNECTOR Powers the NCS-NCW/F board from the NCS computer.
CONNECTIONS Connects the NCS/NFN Gateway through one or more NCMs
to the NOTIFIRENET. Refer to the NOTIFIRENET manual for information on network
connections.
NOTIFIRENET
Battery
The battery on the NCS-NCW/F card powers the piezo sounder. It generates an NCS trouble
message when it is low, and is replaceable (Notifier P/N 31004 (RAYOVAC lithium 3 Volt BR2335)).
EF A, EF B = Disabled.
For further information on the switches below, refer to the NOTIFIRENET manual.
LED101
A HI
LED6
LED2
LED100
STATB
LED4
B HI
SW102 SW101
TERM B EF B
TERM A EF A
Edge
connector
Disable
LED bank
Enable
STATA RCDA
TERM A
EF A
TERM B
EF B
To enable a switch, push it towards the edge connector. To disable a switch, push it towards the LED bank.
In Figure 2.2, TERM A and EF A are enabled. TERM B and EF B are disabled.
NCS-NCW
12
Installation
Total Power
(VA)
Device Type
No. of Devices
NCS5(-W,-F)-ONYX
(@115 VAC, 50/60 Hz)
7.0
NCS5(-W,-F)-ONYX
(@230 VAC, 50/60 Hz)
4.0
MON-17LCD
(@100 240 VAC, 50/60 Hz)
1.8
PRN-6
(@115 VAC, 50/60 Hz)
0.6
PRN-6
(@230 VAC, 50/60 Hz)
0.3
The following steps must be completed when connecting the NCS Computer.
1.
Make sure the power switch on the back of the NCS computer is in the ON position. (See
Figure 2.3.)
2.
3.
Plug the socket end of the power cord into the computer.
4.
Remove the three screws from around the power supply of the NCS Computer (see Figures 2.3
and 2.4). Set the screws aside.
5.
Install a 3/4-inch (19.05 mm) conduit and fitting in the 7/8 inch (22.23 mm) hole of the Power
Cord Locking Bracket cover (see Figure 2.4). Size the 3/4-inch (19.05 mm) conduit so the line
cord can reach the primary AC power source at the other end of the conduit. Thread the power
cord through the cover and conduit.
6.
Attach the PCLB to the computer using the three screws previously set aside. Ensure that the
PCLB holds the power cord socket firmly in place.
7.
Connect power cord to 115 VAC, 50/60 Hz primary power or 230 VAC, 50/60 Hz primary
power as shown in Figure 2.5. Primary power voltage (115 VAC or 230 VAC) depends upon
the position of the voltage selection switch shown in Figures 2.3 and 2.4. All wiring must
remain in conduit.
13
Installation
8.
Connect the monitor to the primary AC power source. (See Connecting the Monitor on
page 15.)
9.
10. Connect the video cable (DB-15) to the VIDEO connector on the back of the computer (see
Figure 2.6). Connect the other end of the video cable to the monitor. Tighten the thumbscrews
for a secure attachment. Do not overtighten.
11. Insert the supplied splitter into the Mouse/Keyboard port at the back of the computer.
12. Connect the keyboard cable to the splitters keyboard port.
13. Connect the mouse cable to the splitters mouse port.
14. Connect the Parallel Port Key on the back of the computer (see Figure 2.3). Tighten the
thumbscrews for a secure attachment. Do not overtighten.
15. Turn computer on using the power switch at the front of the computer. (See Figure 2.11 on
page 22.)
NCS-NCW/F card
See page 10 for
more information.
UPS Supervision
Cable Connection
Microphone Connector
Speaker Connector
Video
connection
EIA-232 Connection
Power
Cord
Socket
Ethernet 1
(see addendum)
Ethernet 2
(not used)
Voltage
Selection
Switch
Power
Switch
EIA-232
COM Ports
1 and 2
NOTIFIRENET
Connections
USB Ports See page 12.
0 and 1
(not used)
Parallel Port Key connection/
graphics printer connection
Mouse/Keyboard Port
Phone
(not used)
Line
sonyxback.wmf
Remove these
screws and reuse
for mounting the
PCLB plate
14
Installation
nrtpwcrd.cdr
PCLB.wmf
Power Cord
Voltage
Selection
Switch
PCLB
Mounting Screws
Neutral - White
NCStoAC.wmf
AC - Black
Conduit
Power Cord
PCLB
Ground - Green
2.
Connect the plug end of the monitors AC/DC adapter to the monitors DC 12V port.
3.
Plug the socket end of the power cord into the monitors AC/DC adapter.
4.
Connect the AC Power Cord to the primary AC power source as shown in Figure 2.6.
5.
Connect the DB-15 video cable from the port labeled RGB on the monitor to the monitor
connection on the NCS computer.
15
Installation
6.
Connect the monitors audio cable from the port labeled PC SOUND on the monitor to the
speaker connection on the back of the NCS/NFN Gateway workstation.
LCD MONITOR
AC/DC
Adapter
AC - Black
Ground - Green
Power
Cord
Audio
Cable
Monitor
Connection
Neutral - White
ncsmononyxac.wmf
DB-15 Cable
Speaker Connection
NCS Computer
16
Installation
Negative Bar
Positive Bar
AC Input
To AC Power
of NCS,
Printer, or CRT
AC
Load
AC Line
NC
COMM
NO
DC/AC
Inverter
NCS computer
47k ELR
(optional)
Utility Failure
NCS-NCW
UPS Supervision Port
DC
Output
DC
Output
Charger 1
Charger 2
ncsupsfsonyx.wmf
Low
Current
Rectifier
Failure
Load
Sharing
Remote
Sense (-)
Remote
Sense (+)
Remote
Equalize
Low
Current
Rectifier
Failure
Load
Sharing
Remote
Sense (-)
Remote
Sense (+)
Remote
Equalize
FMM-1
17
Installation
NCS-NCW
UPS Supervision
Port
SPARE
GND
120V AC
Output
Of UPS
120V AC
Output
Of UPS
GND
120V AC
Output
Of UPS
GND
No Connection
N
No Connection
H
Chassis Ground
GND
Input Power
120V AC, 60 Hz
8A AC Maximum
} Resistive Load
AC
Input
Fail
Battery Fail
FMM-1
UPS
System Control
Board
47K
ELR
EMI
Line
Filter
Static
Switch
Transformer
Charger
Inverter
Battery
upsprn1fsonyx.wmf
UL listed UPS
18
Peripherals
Installation
Feed wires to be connected to the terminal block through the back or side access hole of the
protective cover. The hinged covers of the unused access hole can be closed.
2.
3.
Snap the strain relief assembly over the pluggable terminal block. Use tie wrap to secure the
wires to the protective cover (see Figure 2.9).
Protective Cover
(P/N 08275)
strainre.cdr
ncsonyxback.wmf
NCS-NCW card
2.2 Peripherals
2.2.1 Printers
19
Installation
PC Configurations
Connect a line printer (PRN printer) to the NCS to print fire alarm and trouble signals (see
Figure 2.10 and Table 2.4).
DB 9 connector
ncsdb9xonyx.wmf
Cable
Figure 2.10 Serial and Parallel Port Connections for Printers Connected to an
NCS Computer
To connect a PRN printer to the NCS, prepare a cable with the connections shown in Table 2.4.
NCS
DB9
Printer
DB25
4 and 6
jumpered
together
8
20
2.3 PC Configurations
NCS software requires Windows 2000 Professional Edition with Service Pack 4. Beginning with NCS
Version 5.8, Windows XP with Service Pack 2 is also supported.
To run the NCS program you must configure your system as follows:
20
Software
Installation
Large Fonts
2.4 Software
2.4.1 Installing the NCS Software
NOTE: VeriFire Tools must be installed prior to NCS software If you intend to use both applications
on the same workstation.
NOTE: If the NCS is the Master Time Keeper on the network, installing this software will cancel the
setting and a Master Time Keeper will not exist on the network. Enter the date/time in the NCS Local
Programming Dialog Box for the NCS to become the Master Time Keeper again.
1.
2.
If the install program does not automatically start, select Run from the Windows Start menu.
Use the Browse button to navigate to the CD-ROM drive and open the file:
NCS.exe
3.
1.
2.
3.
4.
Click Next. The following items should be selected on the next screens.
The printer must be connected to LPT1.
Select the printer that is to be hooked up to the system.
Select Not Shared.
21
Installation
Software
1.
2.
3.
4.
Click next. The following items should be selected on the next screens.
The printer should be connected to a line printer connection (see Figure 2.10).
Select the printer that is to be hooked up to the system.
Select Not Shared.
Name the printer NCS Line Printer.
NOTE: This entry is case sensitive: the printer name must be entered exactly as shown.
5.
In the printer dialog box, highlight the printer just installed, right click and select properties.
NOTE: If the NCS Line Printer is connected to a serial port, the port settings must match the printer
settings.
22
2.
Read/
Write CD
drive
location
Software
Installation
3.
Double-click on the Create CD icon on the NCS desktop. Easy CD Creator will appear.
4.
Select DATA
5.
6.
Select files for backup. The directory C:\NOTIFIER\NCS contains important information and
should be included in the backup. Click the ADD button after each selection.
7.
Click Create CD button on the toolbar. The CD creation Setup comes up with default
settings.
8.
Click OK. The CD writer will copy the selected files onto the CD. When copying is complete,
the message CD created successfully will appear.
9.
Click OK.
From the Start Menu, select Secure Desktop, then Secure Setup.
2.
The current configuration from will indicate Windows Explorer or Program Manager
(Default). Change that to Secure Desktop Icon Settings and General Options.
This will enable operation of certain applications, such as the NCS and related programs, VeriFire
programs, and CD Burner software. The Windows Explorer Desktop will be replaced with the
Secure Desktop.
23
Section 3: Programming
3.1 Networking the NCS
Through an NFN Gateway, the Network Control Station (NCS) annunciates system signals on
NOTIFIRENET. Equipment that connects to NOTIFIRENET network and communicates
(sends and receives data) with other equipment using the network is referred to as a network node
(examples: NFS-640/NFS2-640, NCA/NCA-2, and NCS) NOTIFIRENET is a peer-to-peer
network, and can be logically grouped together to form systems. For more information refer to the
NOTIFIRENET Manual.
NCS functions include:
NOTE: All network nodes on a NOTIFIRENET network must contain compatible software. Refer to
the NOTIFIRENET manual for more information on networking.
Upon power-up, the NCS checks for the presence of the databases. If it can not find them, a
warning dialog box will be displayed, and a system error message will be logged to the history
manager and current event window. If the Run Time or Administrator database is missing, the NCS
will not be able to execute, and the program will not start. To correct this situation re-load the NCS
software or restore the databases. The NCS will open an existing history database or create a new
one if none exists.
NOTE: The illustrations in this manual depict nodes on a local area network (LAN). Network
addresses differ when using the wide area network option. See the Wide Area Network &
NOTIFY-IP Addendum (51658ADD) for more information.
All alarm and trouble events received by the system. This includes all activation and clearing
of all devices.
All system messages received from the network. This includes remote acknowledge, reset,
signal silence, walk test, etc.
Any command operation performed at the NCS. This includes acknowledge, reset, signal
silence operation, local programming, fire panel programming, and alter status action.
Events are listed from top to bottom, with the top being the most recent event.
24
Power-Up
Programming
3.2 Power-Up
3.2.1 Data Refresh
Upon power-up, the NCS refreshes all programmed nodes. The NCS can refresh the data of up to
five nodes simultaneously to update point information as fast as possible. This may take longer if
the system includes classic panels.
Data refresh updates the alarm, trouble, disabled, and enabled state of all the points programmed
into the graphic screens. It also updates the unacknowledged event box, acknowledged event box
and the detailed event window with any off-normal information found in the system.
The data refresh option is set in the System Administration dialog box under the General NCS tab
(see Figure 3.16 on page 33). It should remain on during normal operation of a network that
includes classic fire panels. However, you may wish to disable it while troubleshooting the
network or to reduce message traffic upon power-up.
25
Programming
The NCS application will automatically start upon power up. To run the program from the
Windows Start Menu, select PROGRAMS>NCS>NCS. (See Figure 3.1.)
26
Programming
Title Bar
Logo Window
Menu Bar
Alarm, Trouble,
Supervisory Alarm,
Security Alarm, and
Other Activation
Banners
Network/Node
Commands
Tool Bar
Events
Window
Graphic
Floor Plan
mainscrn.tif
Acknowledged
Events Window
27
Programming
Title Bar
Menu Bar
ncsTitleBar.tif
ncsmenu.tif
ncsbase.jpg
The graphic floor plan displays selected blueprints of a building, high-rise or campus-type setting.
It allows an operator to see a diagram of any specific area of the monitored network and gives
information about the facility area and the monitored devices. The graphic screen is comprised of
device icons superimposed over bitmapped versions of a floor plan.
Area of
focus
Dorm #3
Cafeteria
Dorm #1
Admin Bldg
Cafeteria
Dorm #2
ncskeymapa.tif
Overall view
of area.
Events Window
The Events window displays the first 12 or 50 unacknowledged, off-normal events on the network,
depending on the preference set in the System Administration Window. Events are grouped by type
(i.e., fire alarm, security alarm, supervisory alarm, and trouble), and sorted by time within the
group, displaying the earliest event first and the most recent event last. The highest priority event
28
Programming
group is displayed on top of the window, the lowest priority event group on the bottom of the
window. All events in this window are color coded. Fire alarms are designated red, Security Alarms
are blue, Supervisory Alarms are orange, Trouble Conditions are yellow, and other events are cyan
(aqua).
Alarm
N226L10D1
Time
ncsfirevent.tif
Address
Time
Event Type
ncsackn.tif
Address
29
Programming
Double click on a device appearing in this box to display the screen containing the device. This
deletes events that have cleared from the unacknowledged event box, unless the cleared event is an
alarm condition that must be acknowledged (i.e., a tracking alarm on an AM2020/AFP1010 that
clears without a reset). In that case, the clear alarm will move to the unacknowledged event box for
further action.
ncsnavig.tif
Forward Arrow
Back Arrow
Print Graphic
Current Screen
Home Screen
(Top Level Screen)
7/8/01
11:15:10 AM
ncsdatime.cdr
Logo Window
This window displays a custom company logo. See Section 6.8 on page 110 for more information.
ncstoolb.tif
Tool Bar
Event Counter
Detailed Events
30
Programming
Supervisory Alarm
Alarm
Other Activation
Security Alarm
Trouble
Figure 3.12 Alarm, Trouble, Supervisory Alarm, Security Alarm and Other Activation
Banners
Command Area
The command area at the top of the screen allows the user to acknowledge, signal silence, or reset
the network or a specific node. Clicking a command button will transmit the appropriate instruction
over the network to all programmed nodes or off-normal nodes assigned to the user. (See
Section 3.5.1 on page 33 for more information.)
OFF-NORMAL NODES
SELECT NODES
ncscomndc.jpg
Additionally, the user can send signal silence and system reset commands to specific nodes on the
network by right-clicking the signal silence or reset button. The resulting pop-up window allows
the following choices. Choose Off-normal nodes in the pop-up window to silence all off-normal
nodes (as opposed to all programmed nodes); or choose Select nodes to send the command to
individual nodes selected from subsequent dialog box. Commands are sent only to nodes assigned
to the user.
NOTE: Assign command permission at the User Information window. The NCS will not send any
commands that are disabled at the User Information window. See User Account Tab on page 36 for
more information.
Acknowledge
31
Programming
The NCS logs successfully completed point and block acknowledge commands into the history
manager and current event window. If the command could not be completed, an error message
appears.
NOTE: Highlighting different events in the various windows does not affect the acknowledge
operation: pressing the Acknowledge button will not individually acknowledge highlighted items in the
Events and Detailed Events windows.
System Reset
Initiating a system reset command transmits a system reset message to all appropriate nodes
assigned to an authorized user. Additionally the operator may send the reset command to a specific
node.
The NCS logs a successfully completed reset command into the history manager and current event
window. If the command could not be completed, an error message appears.
Signal Silence
Initiating a signal silence command transmits a signal silence message to all appropriate nodes
assigned to an authorized user. Additionally the operator may send the signal silence command to a
specific node.
ncscurruserinfo.jpg
ncsope
The current operator field that shows the name of the current operator of the NCS. Pressing the (...)
button to the right will display additional information about the current operator. See User
Account Tab on page 36 for more information.
32
Programming
ncsadmin.
Node Address
Sound (Hz)
Reset/Signal Silence
Option
Port Supervision
History Backup
Data Refresh
UPS Supervision
Expand Event
Displays
NFPA Event
Reminder
Set Time,
(see Fig. 3.18)
Display and
Control Center
Network Version
Selection
Module Confirmation
IP Connection Speed
System Setup-General tab-Notifier.bmp
33
Programming
When the Auto box is checked, the NCM detects whatever port has activity for supervision.
When Dual Port is checked, supervision of both Port A and Port B is forced. There must be
activity on both or a trouble will be reported.
Data Refresh
Checking this box selects the data refresh options required for proper operation of the NCS. See
Data Refresh on page 25.
UPS Supervision
Checking this box enables supervision of any UPS connected to the NCS. A trouble will be
generated if a failure is indicated.
Expand Event Displays
This option allows the toggling of the number of events to be displayed in the Events and
Acknowledged Events windows. When cleared, only the 12 highest priority events will be
displayed. When checked, the 50 highest priority events will be displayed in these windows. In this
mode, a scroll bar may overlay the time display in the third column.
NFPA Event Reminder
When this box is checked, the NCS sends out a trouble condition to all display nodes at 11:00 a.m.
everyday if there are troubles on the NCS.
Display and Control Center
When this box is checked, the NCS participates in dynamic network control. The NCS can assume
or relinquish control of other participating locations. See Appendix F for more information.
When this box is selected, the wide area network option is disabled. (See below.)
Network Version Selection1
Check this box when using NCS Network Version 4.0 and higher. Clear this box when connecting
the NCS to a NOTIFIRENET 3.0 network containing legacy panels only. Over a wide area network,
all NOTIFIRENET networks connecting to the NCS must run identical versions of NFN software.
Confirm Module On/Off
When checked, a confirmation dialog appears when an output module is manually activated. See
Section 4.7 on page 71.
Wide Area Networking
Checking this box enables the NCS to communicate over a wide area network. When selected, the
NCS cannot participate in dynamic network control (DCC). Requires WAN software key
(purchased separately). See Addendum to the ONYX NCS for Wide Area Networks & NOTIFYIP for more information.
Over a wide area network, all NOTIFIRENET networks connecting to the NCS must run identical
versions of NFN software.
Threshold Ports A/B
Set each port to High or Low depending on communication threshold desired. Refer to the
manual for more specific information on threshold settings.
NOTIFIRENET
1. See Section 1.2, UL 9th Edition Compliance, on page 8 for more information.
34
Programming
Checking the All Nodes box allows use of the Reset and Signal Silence command buttons on the
NCS screen for all nodes. Checking the Off-Normal Nodes box will allow use of the Reset and
Signal Silence buttons on the NCS screen for off-normal nodes only. See Figures 3.2 and 3.13.
History Backup
Checking this box enables automatic history backup. Checking the Number of Events: box will
allow the user to limit the number of events to be placed in backup. The number entered must be
between 10000 and 100000. Checking Day of the Month: (1-28) allows the user to enter a value
of 1 to 28 as the day the history backup will be performed.
Operating Mode:
The node address of the current Network Master Time Keeper is displayed. To make the NCS the
network master time keeper, press Set NCS as current Time Keeper (see Figure 3.17). Press Set
Time (see Figure 3.18) to change the NCS computer time.
IP Connection Speed
ncssetdate.jpg
Sets upload speed over the wide area network. Requires WAN software key (purchased separately).
See Addendum to the ONYX NCS for Wide Area Networks & NOTIFY-IP for more
information.
35
Programming
Click on arrows to
set
day/month/year
NCSSETTIME.JPG
Click on
arrows and in
AM or PM
box to set
time of day.
Click OK to save
settings.
Add a user to
the NCS
Add or delete
commands
from a user
account
SysAdminUserAcct.tif
Delete a user
from the NCS
36
Programming
UserInfoGen.tif
Note:
The picture file must
be a bitmap of the
following size:
147w x 177h (pixels)
The Permission tab lists all commands available on the NCS (see Figures 3.21 and 3.22). Clicking
on a check box beside a command selects or deselects it from the user account being edited
(Figure 3.21). For instance, if the box to the left of Alphanumeric Page is checked, the NCS will
allow this user access to alphanumeric paging.
Node Tab
The Node tab assigns node access to a user. All nodes available on the system are displayed in the
Programmed Nodes window (Figure 3.22). Programmed nodes that have been assigned to a user
appear in the Assigned Nodes window. Double-clicking on a node in the Programmed Nodes
window will add that node to the users assignments. Alternately, double-clicking on a node in the
Assigned Nodes window will remove the node from the users assignment. Press OK to accept the
changes.
NOTE: All nodes assigned to a given user will have the same set of commands available to them.
Initially only the Administration Account user can edit accounts; however, any user given access to
the Account Setup command (in the Permission dialog) will also have the ability to edit accounts.
To delete a user account from the NCS, highlight the account and press on the delete button from
the account list dialog box.
37
ncspermissionc.jpg
Programming
ncsuserinfonodes.jpg
The NCS Pager will dial a users pager number and deliver an automatic or manually-generated
alphanumeric message when certain conditions occur.
Click on the Pager tab in the User Information screen to define the users paging information.
38
Programming
When
Default NCS
Message is
selected, this
figure gives
the actual
character
count in the
text window
ncsUIpgrdefault.jpg
Text window
pull-down menu, add it at the pager carrier screens (see Figures 3.32 and 3.33).
PAGER ID: - Enter the users unique pager identification number.
MESSAGE TO SEND ON NCS EVENT -If DEFAULT MESSAGE is selected, type a message into the text
window. This message will automatically be sent to the user when an assigned event occurs. If
CUSTOM NCS MESSAGE is selected, the boxes below the text window will become available for
selection. Checking one or more of these boxes will cause that information to appear when a user
message is generated. Figure 3.24 is an example of such a message.
ncsUIpgrCusta.jpg
Custom
message
listing
event,
device
type,
label,
and
event
time.
39
Programming
ncsusernodeassignmnt.jpg
Screen.
Deleting A Node
Select the node to be removed at the Nodes Assigned for Alphanumeric Paging Screen
(Figure 3.25). Click on the Remove Node button in this screen. The node will be removed from
paging, but will remain on the users account. (To delete a node entirely from a users account, see
Figure 3.22, Editing User Information (Nodes) on page 38.)
40
Programming
These nodes
have been
assigned to the
users account,
but have not
been assigned
for paging
ncsassignpagnodes.jpg
Clicking on
Select All will
select all nodes
on this screen
for paging
assignment.
Clicking on
Clear will
deselect what
you have
already
selected.
ncsclrnodepagevent.jpg
Click
here.
41
Programming
ncsclrnodepagevent.jpg
Click
here.
Printer Tab
In the System Setup dialog box, the Printer tab (Figure 3.29) allows the user to setup the
communications port settings if the printer is connected to a COM port. The NCS supports two
types of printer:
An Event (line) printer that can be attached to either the COM or LPT port for printing of all
events received by the NCS.
A Graphics Printer that can be attached to the LPT Port for printing graphics. If attached, it
must be set as the default printer.
NOTE: If an event (line) and graphic printer are to be used by the NCS, the event printer must be
connected to a COM port.
42
Programming
ncsprntab.jpg
Audio Tab
There are two types of audio messages in the NCS. Those that are linked to an event or command,
and those that are linked to a device. Files which are linked to events or commands must be in the
Waves directory. Files which will be linked to a device must be in the Sounds file directory
(see Figure 3.30).
Events and Command files activate automatically when the event occurs. Select audio message
files for:
Trouble events.
Alter Status Commands (which include enabling or disabling a device and turning a module on
and off).
43
Programming
If a higher priority event interrupts a lower priority event, the current audio message will be halted,
and the new audio message will be started.
ncsvoicec.tif
To select a wave
file for an event,
click under the
Wave File
directory. A dropdown menu lists
available wave
files.
NOTE: On an NCS with NOTIFY-IP installed, do not select any .wav files displayed on this tab.
See Addendum to the ONYX NCS for Wide Area Network and NOTIFY-IP for more information.
NCSgraphictabc.tif
Under this tab the user can program the NCS to invoke the main screen on all systems normal,
display guidance text and/or device documents automatically, play wave files, display device
labels. You can also program the NCS to print device text, guidance text, and graphics. Click in a
box in order to put a check in the category you would like to display or print. See Figure 3.31.
44
Programming
NCSSysAdminpgr.jpg
At the System Setup screen click on the Pager Carrier tab (Figure 3.32). To add, edit or delete
carrier information, click on the appropriate button.
NCSAddCArrier.tif
Include all
numbers,
letters, or
other keys
necessary
for dialing
out of the
building.
45
Programming
defaults when the modem or carrier has limitations or requirements. Either all the fields must be
entered, or none of the fields.
Click on the Apply button to enable the carrier addition. Click OK when done to leave the screen.
Deleting A Carrier
Clicking on the Delete Carrier button (see Figure 3.32) will delete whichever carrier is highlighted,
unless a user is assigned to that carrier. A carrier cannot be deleted if there is one or more users still
assigned to it.
Network Operationss.bmp
For nodes that are programmed into the NCS, the Network Operations Window displays the node
number, node type, label, DCC status, on-line status and signal silence status in a spread-sheet like
view (see Figure 3.34). The label is a 30 character custom label local to the NCS that can be entered
by the user. The on-line status is either on-line or off-line. The signal silence status is N/A, Normal,
Partial, or Full Silence. DCC status will be indicated only if Display and Control Center option is
selected on the General NCS tab. (See pages 3334.)
NOTE: On systems utilizing DCC, all participating nodes must be mapped to all participating
network annunciators.
For more information, see Appendix F, Display and Control Center (DCC) , Appendix G.4.2,
Node Mapping and all other network annunciator manuals.
46
Programming
editnode.tif
While in demo mode or upon initial power-up, the local NCS will be programmed in as node 0. The
operator must change this node number to initiate network communications. (If the system is in
demo mode, the address cannot be changed.) The Network Operations window allows the user to
add, delete and edit nodes. Editing a node will allow the user to enter the 30 character custom label.
The LOCAL NCS cannot be deleted from the network operations window.
rdatamen.tif
NOTE: The information displayed in the Read Database Menu comes from a database stored on the
NCS. The database is only updated during upload and read status commands, and therefore might
not be up-to-date.
1. These panels have been not certified for UL 864 9th Edition compliance. See Section 1.2,
UL 9th Edition Compliance for more information.
ONYX NCS Manual P/N 51658:H 2/28/2007
47
Programming
ncshistc.jpg
The Archive History Database menu option allows the user to archive the current history database,
and open a new one (Figure 3.37).
ncsgraphmenu.jpg
Use the Graphic Menu option to invoke the Graphics Setup Program, bring graphics created in the
GSP to the NCS, or copy graphics data to other NCS workstations.
Graphics in the NCS are programmed using the Graphic Setup Program (GSP). The GSP can be
accessed directly (stand-alone) or via the NCS application. It is used to set up all floor plans, device
icons, links, etc. in the program. All graphics information is stored in graphics.mdb. Refer to the
Section 6, The Graphic Setup Program, on page 92 for more information about this program.
Update Graphic Database
Select this command to update the NCS database with a database modified via the GSP application.
NOTE: You must execute the Update Graphic Database to save any changes to the graphics
database.
Replicate Graphics
This function allows the user to replicate to all or selected NCS servers
the graphics database (graphics.mdb) and all bitmap pictures in the directories, or
Selecting Replicate Graphics from the graphic menu brings up the Database Replication Dialog
screen below.
48
Programming
Click on Data
and Graphics
for replication of
the graphics
database and all
bitmaps in the
directories.
Click on
Graphics Only
to replicate
bitmaps only.
Click this
button to
replicate.
NOTE: All files replicated to the destination NCS will have the same file attributes as those on
the source NCS. When replicating make sure that files on the destination NCS are not marked
read-only. Files marked read-only may cause the replication to fail with an "Access Denied"
error. Use Windows Explorer to change attributes.
NCSutilmenud.tif
The Utilities Menu allows the user to edit speech files, compact databases, view network
communication statistics and software versions, and perform node maintenance and walk tests. The
Edit Speech File opens up the Audio tab which also can be opened through the System
Administration menu. The Compact Database compacts and saves a database for transferring
information onto a floppy disk.
49
Programming
Network Statistics allows the user to troubleshoot network statistics by displaying traffic within the
network. (See Figure 3.41.) When you initiate this service, you can view the diagnostic information
for a selected node or the entire network from the perspective of any node on the network.
Checking the "Reset All Nodes" option clears all previous network responses in the statistics
screen.
Contact your Technical Services representative to use this information to diagnose problems that
may occur within your network.
ncsnetstats.bmp
ncsnuportstat.jpg
Information for the various NUP ports on the network nodes is listed in the NUP Port Statistics
window, and can be used by Technical Services Support to troubleshoot network problems. Contact
Technical Services Support to use the information to diagnose such problems as overly-long
upload/download times that may occur within your network.
Programming
The Software Version Numbers screen lists the software versions for components on the network
nodes.
NOTE: Version information for primary gateway clients appears in parentheses next to gateway
version information.
ncssftwvrsnmenu.tif
ncssftwrvers.jpg
Press this
button to select
a single node
for viewing
NOTE: Network Statistics, NUP Port Statistics, and Software Version Numbers are available only to
the administrative user.
51
Programming
The Node Maintenance Selection allows the user to change a node address or password.
Enter the
new node
address
ncsnodeaddrchange.jpg
Select the
node that
requires
changing.
Select the
node that
requires
changing.
Press the
Update Button
to complete the
change.
Select
password type
ncsnodepasswdchg.jpg
Enter and
confirm
password
Press the Update
Button to
complete the
change.
52
Programming
Walk Test
The Walk Test screens allow the operator to perform walk tests on selected system nodes. The
Select Nodes for Walk Test screen appears first. It lists all the nodes on the network that can be
put through Walk Test at the NCS.
NFS-3030/NFS2-3030 only - Click in the
numbered Loops boxes to select or deselect a
loop for Walk Test
Click in the
Walk
Test
column to
select or
deselect a
node for
Walk Test.
A check
indicates
selection.
Press this button to start the Walk Test when
the desired nodes have been selected. The
Walk Test Manager screen will appear.
Choose
Advanced
to include
CBE in Walk
Test. Walk
Test event
displays will
latch and
require
pressing the
Next Test
button to
progress.
(See
Fig. 3.46 for
button
location.)
ncsselectwalktstnods.jpg
53
Programming
Pressing this
button invokes
the screen
below it.
Press this
button to
update the
list of
nodes that
will be
placed in
Walk Test.
Click here to
select Node
17 for
addition to the
list of other
nodes that
will be placed
in Walk Test.
(A check
indicates
selection.)
ncswlktstaddnod.jpg
Pressing this
button invokes
the screen
below.
The Loops
selections
are
displayed
here; no
changes
may be
made to
these
selections
at this
screen.
Click here to
select Node 59
for deletion from
the list of other
nodes that will be
placed in Walk
Test. (A check
indicates
selection.)
54
ncshlepmn.jpg
Programming
aboutncsa.bmp
55
Section 4: Operation
4.1 Normal Operation
During normal operation, when no fire alarms or troubles exist, the NCS window appears as shown
below with a System Normal message in top right-side of the window.
ncssysnormc.jpg
4.2 AutoNavigate
When an off-normal event occurs, the NCS will automatically display the floor plan associated
with the highest priority event. This function is called AutoNavigating. If an equal or lower
priority event is received while a higher unacknowledged event exists in the network, the floor plan
will not change.
The AutoNavigate option is set in the Device Parameters dialog. If the AutoNavigate option for the
device received is enabled, the graphic floor plan will change to display the floor plan containing
the icon, bypassing any group associations. See Figure 6.32 for information on setting up grouping
and AutoNavigating for a device.
56
Troubles
Operation
If AutoNavigate is off, and a group is associated with the device, the floor plan containing the
highest level group will be displayed. See Section 6.6, Groups, on page 108 for a more detailed
explanation of groups. Even with the AutoNavigate function enabled, the user can still manually
change screens using the Select Screen dialog box.
4.3 Troubles
When a trouble is received from a fire alarm panel it is reported to the NCS. The NCS will report
the trouble in three ways; the trouble icon in the banner will flash, the trouble will be reported in the
Events window, and it will appear in the Event Counters window. For the highest priority event, the
representative icons banner in the Graphics Display Window will flash. (See Figure 4.2.)
Trouble icon
flashing in the
Banner area.
Trouble
reported in the
Events
Counter Box
under New and
Total
categories.
Trouble
reported in the
Events
window.
ncspointdisablnew.jpg
Detector
flashing the
reported
trouble
57
Operation
Alarms
Trouble icon
stops flashing
in the Banner
area.
Trouble
reported in the
Events
Counter Box
under the Total
category.
ncspointdisablAck.jpg
Trouble moves
to the
Acknowledged
Events
window.
4.4 Alarms
When an alarm is received from a fire alarm panel it is reported to the NCS. The NCS will report
the alarm in three ways; the alarm icon in the banner will flash, the alarm will be reported in the
Events window, and it will show up in the Event Counters window. See Figure 4.4.
Alarm icon
flashing in the
Banner area.
Alarm reported
in the Events
Counter Box
under New and
Total
categories.
Alarm reported
in the Events
window.
ncspointalrmnew.jpg
Detector
showing the
reported alarm
58
Operation
Select Acknowledge to acknowledge that an alarm has been reported. The alarm will then be shown
in the Acknowledged Events window (Figure 4.5). Select Signal Silence to silence NACs, and
select Reset to reset the control panel.
Alarm reported
in the Events
Counter Box
under the Total
category.
ncspointalarmack.jpg
Alarm icon
stops flashing
in the Banner
area.
Alarm moves to
the
Acknowledged
Events window.
59
Operation
ncsfilemen.jpg
The File Menu (Figure 4.6) allows the user to exit the NCS application.
Exit
The Exit command from the file menu exits the NCS program and places the user in the Windows
2000 environment. The user is prompted for a password. After entering the correct password a
warning display indicates the user is exiting the NCS application (Figure 4.7). The user should
either press Ok to exit the NCS application or press Cancel to abort.
WARNING: Fire and Life Safety Functions Disabled!
Exiting the NCS application disconnects the NCS from NOTIFIRENET. The NCSceases to perform
life safety functions and the building is unprotected.
ncsexit.tif
ncsopmen.tif
The Operator Menu allows the user to Login, Logout, and Change Password of the NCS
(Figure 4.8).
Login
The Login command allows the user to gain access to the NCS by selecting his or her name in the
dialog box. Both a user name and a password are required to log on (Figure 4.9). When the NCS is
first powered up, the initial user name is Admin. After initial login, the Administration Account
password must be changed to something other than Admin to ensure system security. The
administration account user should then set up accounts with temporary passwords for all operators
that will be accessing the NCS. Passwords can be from four to 15 characters.
60
Operation
ncslgout.tif
Asterisks are displayed in place of characters when entering a password. After selecting the user
name and entering the password, press Ok to accept the login information. If an error is made while
entering the password during login, a quick warning beep sounds, and the password dialog box
remains on the screen with the user name highlighted.
ncswarn.tif
If the user is already logged into the NCS and clicks the Login command a warning box will appear
stating that the current user will be logged out (Figure 4.10).
Logout
ncslgout.tif
The Logout command is used to exit the NCS. Once logout has been selected, a dialog box appears
asking the user for the password. (Figure 4.11). After entering the password, select Ok to continue
logging out. System commands will not be accessible again until a user logs onto the NCS.
Change Password
The Change Password command allows a user to change their current password. A password can
only be changed by the user who owns the password. Not even the Administration Account user
(the top user account with permanent access to all the NCS commands) can change another user's
password.
When the Change Password command is selected, the change password dialog box (Figure 4.12)
prompts the user for old and new passwords. Asterisks will appear in place of the entered characters
for both the old and new passwords. Type the old password. Type the new password and then
retype it in the confirm password box to verify the first entry. Press OK to accept the new password
information.
NOTE: The password must be between four and 15 characters inclusive.
61
ncschpas.tif
Operation
NCSactionc.jpg
From this menu, the user can acknowledge events, reset the system, perform a signal silence, hide
offline events, show offline events, perform a data refresh (Figure 4.13), upload or download
databases and applications, and page users. If there is an active command center and DCC is
enabled at the panel, Acknowledge, Signal Silence, and System Reset require permission before
they can be processed. See Appendix F for more information.
62
Reset - Allows the function of system reset to be performed across the allowable network
nodes. The user can reset all nodes at one time, all off-normal nodes at one time, or select
individual nodes of choice.
Signal Silence - Allows the function of signal silence to be performed across the allowable
network nodes. The user can signal silence all nodes at one time, all off-normal nodes at one
time, or select individual nodes of choice.
Hide Offline Events - Hides all offline events. For example, if a node is disconnected from a
network with active events, then this selection will mask them from the graphic workstation.
Show Offline Events - Displays all offline events. For example, if a node is disconnected from
a network with active events, this option will unmask offline nodes that have active events.
Data Refresh - Manually initiation from the NCS to update the off-normal points in the NCS.
This is also automatically done when the NCS is powered up. The NCS has the capability to
initiate a data refresh to five nodes simultaneously to update point information as fast as
possible.
Operation
Open Verifire 1020 - Invokes the VeriFire 1020 programming utility. (See VeriFire 1020
Help for more information.)
Open Verifire Tools - Invokes the VeriFire Tools programming utility. (See VeriFire Tools
Help for more information.)
Voice Paging - Invokes the voice paging dialog if NCS has NOTIFY-IP. (See Wide Area
Network and NOTIFY-IP Addendum for ONYX NCS for more information.)
Alphanumeric Paging
To page a user manually, click on the Action pull-down menu at the NCS Screen and choose
Alphanumeric Paging. (Figure 4.14).
NCSMainpager.jpg
Select
Alphanumeric
Paging
NCSpagingperat.jpg
Click here to
bring up the
User
Information
Screen Pager
tab (see
Fig. 3.23.)
Upload/Download (UPDL)
The upload / download window is used to upload or download the database from a node, and to
perform application downloads for those nodes supporting this function. Options are available to
initiate uploads and downloads, schedule uploads, and abort any current actions. Information about
63
Operation
ncsUPDLmainwindow.jpg
the node number, status indication and progress indication will be displayed by the upload /
download. Select UPDL under the Action option in the NCS Window menu bar and the Main
Window will appear showing nodes and their completion percentage. (Figure 4.16.)
Upload - Before an upload is initiated, the NCS will query the user for a database file in which to
store the received information. All uploaded information, including the database version, is saved
to the UPDL database. The NCS will also update the run-time database with the new information.
See Figure 4.17 for a screen example illustrating choices made for uploading databases from nodes.
An AM2020/AFP1010 database file cannot be uploaded to an NFS-3030/NFS2-3030, NFS640/NFS2-640, NFS-320, DVC, or NCA/NCA-2; and vice-versa.1
1. Some of these panels have not been certified for UL 864 9th Edition compliance. See
Section 1.2, UL 9th Edition Compliance for more information.
64
Operation
Click Start to
initiate the
upload.
The download
will be
performed on
highlighted
node(s) in this
box.
Click Start to
initiate the
download.
ncsUPDLdatabdwnload.jpg
1. Some of these panels have not been certified for UL 864 9th Edition compliance. See
Section 1.2, UL 9th Edition Compliance for more information.
ONYX NCS Manual P/N 51658:H 2/28/2007
65
Operation
Applications files, which contain a panels operating firmware, can be downloaded using this
screen to those network nodes that support downloading. When the Application operation is
selected on the Upload/Download screen, the following screen appears.
Select
Application
The Application
download will be
performed on
highlighted node(s)
in this box. Only
nodes that support
downloading (NCM,
NCA/NCA-2, NCS,
NFS-640/NFS2640, NFS-320, NFS3030/NFS2-3030)
will appear in this
box.
Click Start to initiate
the download.
ncsUPDLappdwnload.jpg
The NCS has the ability to schedule uploads once or on a monthly basis. All scheduling options,
including dates, times, and nodes selected, are saved to the NCS database. Figure 4.20 shows an
example of a Schedule Upload screen. Scheduling options are as follows:
66
Only Once - This option will allow the user to upload a set of panels on a one-shot basis. A
date and time for the upload is entered and the NCS initiates the upload at that time.
Monthly - The NCS has the ability to schedule uploads on a monthly basis. The user can select
the day of the month and time to upload. The NCS can then upload the specified set of nodes
every month at the specified time. To alleviate the problem of how many days are in a month,
the plug-in only allows a range of 1 - 28 for the day specified.
Multiple Panel Upload - The NCS can upload the databases of up to five nodes at a time. If
more than five nodes have been selected, the NCS will upload the first five, then continue by
uploading at a rate of 5 nodes at a time until all databases have been uploaded.
Operation
Selections in this
area have
scheduled a
monthly upload for
the first of each
month at 7:00 p.m.
ncsUPDLscheddatabuplad.jpg
NCSviewc.jpg
From the View Menu, the user can see the number of events that have occurred from the Event
Counter Window, see a detailed list of all events, fire and non-fire, from the Detailed Events
Window, view the last 1,000 events that have happened in the system from the Current Events
Window, disable devices (once the device is disabled, the user can enable it again by doubleclicking on the device, from the window itself), and view disabled device, from the Disable
Devices Window, and view the History Manager (Figure 4.21).
67
Operation
Event Counters
ncseventcounts.jpg
The Event Counter window (Figure 4.22) contains the new and total events on the network. The
information displayed in the window consists of fire alarms, security alarms, supervisory alarms
troubles, and other activations. The new and total field areas are capable of displaying up to 99,999
events.
If there are
counts in the
Other Activation
fields, click on the
+ box. The
window will
expand to show a
breakdown of
these events into
categories.
NCS4detev
Select the
blue button
to view
Details of
Background
Activation.
Figure 4.23 The Detailed Events Dialog Box (Fire Events Shown)
A scroll bar will be provided if more events are present in the system that can be displayed at one
time. The events are sorted by event type (fire alarm, security alarm, supervisory alarm, trouble,
pre-alarm, acknowledged alarm, acknowledged security alarm, acknowledged supervisory alarm,
acknowledged trouble, and acknowledged pre-alarm) and time. This dialog box will be displayed in
68
Operation
the same position as when previously closed. If left open, it will be refreshed every 6 seconds, and
only if new events of equal or lower priority were received by the NCS. If higher priority events
were received, this window would be updated immediately.
All information received from the node that the event happened on will be displayed in this box.
This includes the event type, the device type, the device label, the first zone referenced in the CBE
equation (for panels that provide this information), the first zone label (for panels that provide this
information), the trouble type (for trouble conditions), the time and date (assigned by the NCS), and
a panel specific type index. This box will be updated during receipt of normal events, as well as
during a data refresh operation. In the latter case most of the information will not be available, and
only the information that is available will be displayed. The NCS provides the ability to print all
events in the Detailed Event box by clicking the printer icon on the right side of the events banner.
ncscurrt.tif
The current event window contains all network and local events, as well as system messages
received by the NCS. A maximum of 1000 events can be displayed in the system message box (see
Figure 4.24), with the newest event displayed on the bottom of the window. If more than 1000
events are reached, the oldest event will be deleted. The events displayed in this window are sorted
by time and date, with the date column being displayed first. Events in this window will be color
coded, using the same color scheme as in the Unacknowledged Event Box.
ncsdisdv.tif
The disabled device window contains all disabled devices in the system. A disabled device can be
re-enabled by selecting (double-clicking) it from the list of disable devices. A confirmation dialog
box will be displayed, confirming the enable command. If the point enabled is a AM2020 or
AFP1010 zone, right clicking on the point will bring up another menu.1 This menu will give the
user an option of using the Zone Enable or Group Zone Enable command for the zone. All zones
will be colored to make them stand out within the window.
69
Operation
The Disabled Device window will only be refreshed when the device is disabled or enabled, but at
a rate no greater than 6 seconds. This window will also be displayed in the same position as when
previously closed. All events in the disabled device window may be printed.
History Manager
The user may select the History Manager Window from under the View Menu. The History
Manager is a program that records all operator actions and all events (alarms and troubles) that
have occurred in the system. Refer to Section 5 on page 86 for a detailed description of the History
Manager.
NCSnavmenc.jpg
Select Find Screen to bring up a particular screen. The pull-down menu illustrated in Figure 4.28
will display screens available for viewing.
ncsarrow.tif
Pull-down
menu. Click
on tab to
display
screens
available
for viewing.
70
Read Status/Program
Operation
Section 4.7.1
NFS-3030/NFS2-3030
NFS-640/NFS2-640
NFS-320
Section 4.7.2
DVC
Section 4.7.3
71
Operation
Read Status/Program
ncsdetrdstat.jpg
To perform Read Status on a detector in the system, select the node the detector is connected to
from the Select System dialog box. Select OK. A node dialog box appears. Select the Detector tab.
Enter the address of the detector that is desired to perform Read Status. Select Program. The
Detector dialog box appears. This dialog box displays the current programming for the detector, the
verification counter, percentage of alarm, and whether the detector is in alarm, trouble, or disabled
(see Figure 4.29).
To perform Read Status on a module in the system, select the node the module is connected to from
the Select System dialog box. Select OK. A node dialog box will appear. Select the Module tab.
Enter the address of the module desired to perform Read Status. Select Program. The Module
dialog box will appear. This dialog box displays the current programming for the module and
whether the module is in alarm, trouble, or disabled (see Figure 4.30).
72
Operation
ncsmodrdstat.jpg
Read Status/Program
73
Operation
Read Status/Program
Zones
ncszonrdstat.jpg
To perform Read Status on an AM2020/AFP1010 zone in the system, select the node the zone is
connected to from the Select System dialog box. Select OK. A node dialog box appears. Select the
Zone tab. Enter the zone number desired to perform Read Status. Select Program. The Zone dialog
box will appear. This dialog box displays the current programming for the zone and whether the
zone is in alarm, trouble, or is disabled (see Figure 4.31).
74
Read Status/Program
Operation
Annunciator Points
ncsannrdstat.jpg
To perform Read Status on an annunciator point, select the Annunciator tab from the Node dialog
box. Enter the address of the point desired to perform Read Status. Select Program. The
Annunciator Point dialog box displays. This dialog box shows the type of annunciator point and
whether it is in Alarm, Trouble, or Off (see Figure 4.32).
75
Operation
Read Status/Program
System Data I
ncssysdat1c.jpg
To perform Read Status on system parameters, select the System Data I, II or II tab from the node
dialog box (See Figures 4.33 through 4.35).
ncssysdat2c.jpg
System Data II
76
Read Status/Program
Operation
ncssysdat3c.jpg
77
Operation
Read Status/Program
ncs3030readstatsy
To enter Read Status node, select the desired node from the Network Operations screen (see
Figure 3.34) by double-clicking on the node number at the beginning of the row. The following
screen will appear.
Click the
Refresh button
to update the
screen.
ncs3030reads
Click
Loop
78
Read Status/Program
Operation
For SLC devices, double-click on a Loop row, click on Detectors or Modules, then click on a
particular detector or module address to view Read Status.
For Panel Circuit devices, click on the Panel Circuits row, click on a panel circuit, then click on a
particular panel circuit point to view Read Status.
Panel Circuit
devices:
Click Panel
Circuits, then
the Circuit
number, then
a point
address
Control Modules or panel circuit points Click this button to force the module on.
ncs3030readstatmodule.jpg
SLC devices:
Click Loop,
then
Detectors or
Modules,
then the loop
address
Double click on a zone row to expand the tree to display individual zones.
ncs3030readstatreleas
In this example,
the Releasing
Zones row has
been clicked
and the tree has
expanded to
display the list
of releasing
zones.
Click on a zone
to display its
information.
When a General Zone is selected for Read Status, a Disable button
appears at the bottom of the screen. Clicking the button disables the zone.
79
Operation
Read Status/Program
Annunciators
For Annunciators, click on the annunciator row, click on an ACS device, then click on a particular
annunciator point to view Read Status.
In this example, the
Annunciator row has been
clicked and the tree has
expanded to display the
list of ACS devices.
Click on an ACS
device to display
individual points,
then click on an
Annunciator Point
to display its
information.
Custom Action messages are user-defined messages that can be programmed to appear in device
event display screens.
ncs3030readstatacam.
Click on the
Custom Action
Messages row
to display the
list of
messages.
Click on an
individual
message to
view its
contents.
80
Read Status/Program
Operation
ncs3030readstatoccup
Click on the
Weekly
Occupancy
Schedule row
to display the
list of
schedules.
Click on a
schedule to
view its
contents.
DVCreleasestatus1.jpg
To view read status of a DVC node, select the desired DVC from the Network Operations screen
(see Figure 3.34) by double-clicking on the node number at the beginning of the row. The following
screen will appear.
Click the
Refresh button
to update the
screen.
81
Operation
Read Status/Program
DAA Amplifiers
Select an amplifier in the tree to view its current settings.
DVCreadstatusDAA.bmp
Click
DAA
Expand the DAA AMPLIFIER and SPEAKERS rows, and then select a speaker address to view read
status for an individual DAA speaker output.
Speaker on a DAA:
Expand the Amplifier
and Speakers rows.
Select the
speaker address.
DAAReadStatusSpkrckts.bmp
82
Read Status/Program
Operation
To view read status about individual PAM Points located on a DAA: Expand SPEAKERS,
speaker address (for example, A1S2), and PAM POINTS rows. Select a PAM Point address to display
information for a particular PAM point.
To view read status about individual PAM Points located on a Analog Output: Expand
ANALOG OUTPUTS, AO (individual analog output address), and PAM POINTS rows. Select a PAM
PAM Points on a
DAA:
Expand Speakers,
speaker address, and
PAM Points rows.
DVCDAArdstatPAMpts.bmp
To view read status about individual Network Paging PAM Points located on a DAA:
Expand NETWORK PAGING PAM POINTS. Select a Network Paging PAM Point address to display
information for it.
PAM Points
on a DVC
83
Operation
Read Status/Program
DVC_ALLCALL.bmp
Expand the ALL CALL MAPPING and SPECIAL PAGING MAPPING rows to display nodes that are
mapped to All Call and Special Paging.
Figure 4.48 DVC Read Status - All Call/Special Paging Mapping and Fixed Input
Priorities
16
17
1035
Network Workstation
1037
1038
Local RM-1
1039
Network RM-1
1040
Local AUXB
1041
Network AUXB
1043
Local AUXA
1044
Network AUXA
84
Read Status/Program
Operation
Logic Zones
Expand the Logic Zone row and select an individual logic zone to view its state, status and
equation. The DVC can have up to 2000 logic zones.
Click a
zone to
display its
information.
LogicZonelabel.bmp
General Zones
Expand the General Zone row and select an individual general zone to view it.
Click a zone
to display its
information.
DVCrdstatGenZon.bmp
85
ncshistoryviewer.jpg
The History Manager, by default, displays the currently active history database. This is indicated by
the program in the title bar. The user can open older history databases under the File menu, Open
Archived History File command (Figure 5.3). This operation will close the current database and
86
archivhs.tif
open the selected one. The History Manager will indicate that the current history file is no longer
displayed by showing the path and file name of the current history database in the title bar. See
Figure 5.4 for an example of an archived history database.
archive.tif
The History Manager provides an Operator List via a control tab on the main screen. This tab, when
invoked, displays all operators who have logged on to the system and the last login time and date.
This list is part of the history database, and therefore will be cleared whenever a new history
database is opened. See Figure 5.5.
ONYX NCS Manual P/N 51658:H 2/28/2007
87
operlis.tif
numevnt.tif
The number of entries in the history database is shown at all times. If a custom filter view is
selected, the number of entries will be equal to the number of events shown (see Figure 5.6).
The history manager will allow the operator to view the events using the following search criteria:
All events
All events by node number, loop number or device number*. They can be independently set.
Events with a particular device status (fire alarm, security alarm, supervisory alarm, point or
system trouble, module activation, disabled device, operator login in/out, system programming
and other events)*.
Events received by device types, including detectors, modules, zones, bell circuits, panel
circuits and other devices.
NOTE: The events marked * may be combined with any other search criteria.
88
custfilt.tif
Searching and displaying events in the history manager wont adversely affect the NCS operation.
Any operation of this type is conducted as a low priority event. See Figure 5.7 for an example of
search dialog box and Figure 5.8 for a search showing only Administration logins.
custadmn.tif
89
Visible columns
viscolm.tif
Select Options, Select Visible Columns to control column types shown in the Event History
Viewer. Clear the box next to the column type to hide it from view (Figure 5.9). The History
Manager saves these preferences for future sessions. In addition, each column in the Event History
Viewer can be resized by dragging its borders.
hisprint.tif
Any graphics printer connected to the NCS can print the current history database (or any archived
history database). The Print command located under the File menu invokes the common printer
dialog box (Figure 5.10) enabling the selection of a printer. The printout consists of the information
shown in the history manager. Columns that are hidden will not print. If a custom filter has been
selected, only the events that are a part of the filter will be printed.
90
hisback.tif
Use the Archive History command under the Administration menu to manually archive a database.
This command opens a dialog box to save the current history database, with a .his extension (see
Figure 5.11). Archiving the current database for backup creates a new, blank history buffer.
The NCS can be automatically configured to back up a history file when the NCS reaches a userselected number of entries (from 10,000 to 100,000 events). In addition, the history database can be
backed up any day of the month, ranging from 1 to 28. (To alleviate the problem of how many days
are in a month, the allowable range of specified days is 1 - 28.)
The current history file will be saved to a file name made up of the current date with an a prefix,
denoting an automatic backup. If more the one backup has occurred in any given day, a 1 will be
added to the file for each backup. For example, a061201-1.his indicates the first file backed up
automatically on June 12th, 2001. An a061201-2.his file indicates that a second file was backed
up that day.
The path and filename of the old history file will be saved in the new history file. All history files
are backed up in the \{install}\HistoryArchives directory.
91
Title Bar
Information Window
Menu Bar
Key-Map Area
Toolbar
Graphics Area
ncsgspintc.jpg
92
Program Layout
ncstree.jpg
ncsgrview.jpg
ncsscview.jpg
93
Program Layout
infowin.jpg
The Information Window contains the information about the current screen that is edited. This
includes the screen Description, keymap file name, guidance text file name, and floor plan file
name. (See Figure 6.5.)
selectfl.jpg
Double-clicking on any of these fields displays a file dialog box. This allows the user to change the
keymap or floor plan, select a new guidance text file, or change the name of the screen that is
currently edited, refer to Figure 6.6 for an example. If a floor plan is changed, a Save Screen
option appears, see Figure 6.7, allowing the user to save all current changes. This option only
appears if changes have been made to the current screen. In addition, double clicking on the floor
screen name in the Tree View Window also saves any current changes that have been made.
savescrn.jpg
94
Create Detector
Create Group
Create Module
System Troubles
Edit Keymap
95
floorpl.jpg
A floor plan can be added to the NCS by selecting the Screens menu option, New Screens
command from the menu bar. A confirmation dialog box is then displayed. This dialog box allows
the user to select an existing floor plan and keymap, or create a new floor plan and key-map. In
both cases, a floor plan title must be selected. (See Figure 6.9.)
floorpic.jpg
If an existing floor plan or keymap is to be added, a dialog box appears allowing the user to select a
floor plan, refer to Figure 6.10 for an example. Once the floor plan and keymap are selected, they
will be displayed in the Graphic Setup Program.
96
selflpln.jpg
The screen selecting command displays a dialog box which contains all screens with their
corresponding floor plan number, and a preview window. It allows the user to select a floor plan for
editing purposes. Once a screen floor plan has been selected, click the OK button and the new floor
plan with all its associations will be displayed. (See Figure 6.11.)
delscrn.jpg
The Graphic Setup Program allows the operator to delete screens. When this operation is selected, a
dialog box containing all screens in the GSP, with the corresponding floor plan number, will be
displayed. In addition, this dialog box will contain a preview of the floor plan belonging to the
screen that is to be deleted. (See Figure 6.12.)
delsrdi.jpg
A confirmation dialog box will be displayed before the floor plan is actually deleted from the
system (Figure 6.13). Deleting a floor plan causes all devices, information labels, navigation
buttons, etc. that are on the screen, to also be deleted. The physical bitmap files for keymaps and
floorplans are not deleted.
97
Keymap Area
gspkeymplk.jpg
Keymap links can be set under the Screens menu, Set Keymap Link command. When this
command is activated, a dialog box appears, displaying all screens in the system (Figure 6.14).
Once the keymap and screen are linked, the floor plan will be displayed when the corresponding
keymap area is selected.
textfl.jpg
Guidance Text can be added to any screen. Guidance text may contain instruction or warnings
applicable to the displayed area. The text is entered using the guidance text viewer/editor
(Figure 6.15). The guidance text can be printed automatically or by device activation from within
the NCS or manually by user selection. To manually print guidance text by user selection, press the
button to display, choose auto display, and select auto print.
98
keymap assigned to it, although the same Keymap may be assigned to different screens. Keymaps
can be customized through Paint. If a keymap link has been created, double-click the keymap while
in the NCS to bring up the associated screen.
gspfile.jpg
Select Exit Setup to close the Graphic Setup Program and return to the NCS (Figure 6.16).
6.4.2 Screens
gspscreen.jpg
Under the Screens menu option, the user can create a new graphic screen, select a previous graphic
screen, delete a graphic screen or set a keymap link to a graphic screen (Figure 6.17).
gspdevicec.jpg
6.4.3 Devices
gspdevgrc.jpg
99
gspgrpsetup.jpg
gspdevdetc.jpg
gspdevsystrb.jpg
gspdevmodc.jpg
100
gspdevzonc.jpg
gspdevinfolc.jpg
gspdevnbc.jpg
101
Device Icons
6.4.4 View
gspview.jpg
The View menu option allows the user to customize the toolbar to the users preference and view
screen statistics. Screen statistics include: device (detectors, modules, zones) count, graphic (labels,
navigation buttons) count and a Total count (combination of both).
6.4.5 Setup
The Setup menu allows the user to edit graphics and set NCS preferences for non-latin language
labels. Select Edit NCS Graphic to edit the site logo. See Section 6.8, Custom Bitmap, on page
110. Choose Nodes for Labels instructs the NCS to display custom labels programmed in the
GSP instead of labels programmed at the panel for the selected nodes. These custom labels will
appear in all NCS windows except read status windows. Allow Remote Site Setup makes the
Graphic Setup Program functional over remote networks.
gsphelpcb.bmp
6.4.6 About
102
Device Icons
6.5.1 Devices
A symbol can be used to graphically represent a device (detector, module or zone) in the fire alarm
system. In addition to a graphical representation of the device, the user can assign device
descriptions and link pictures, documents and sound to the device. The NCS does not permit one
device to be displayed on multiple screens; a device can only appear on one screen.
detbox.jpg
A new device can be added to the system by using the Devices Menu command or through the
toolbar. When using the toolbar, select the appropriate detector, module or zone you would like to
add. After this command is executed, a library of icons will be displayed to select a symbol
representing the device (see Figure 6.30).
newdetbx.jpg
Once a device is selected, a new device dialog box is displayed where the user can enter address
information about the device (Figure 6.31). For detectors, modules and zones, options are available
to link a sound file, document and/or picture to the symbol. In addition, each of these devices can
be linked to a group. If grouping is to be used, the groups and group screens should be created
before actual devices.
103
Device Icons
Devices can also be set to AutoNavigate. In this case the AutoNavigate option must be selected.
The following screen allows the user to set up or edit group and graphic display information for a
device (in this example, a detector).
Display:
Node number,
SLC loop number,
Device address
Display:
GSP Screen number,
Screen name
Customer-defined label
associated with device.
GSP Device.jpg
6.5.2 Detectors
Detectors have other symbols associated with them: an active icon, a trouble icon, a disabled device
icon and a pre-alarm icon. The appropriate icon will be displayed for an event, the device label
blinks if an event is unacknowledged, and is steady if the event is acknowledged.
104
Device Icons
Ground Fault
Battery
AC Fail
Printer Supervisory
6.5.4 Modules
Modules show an active, trouble and disabled device symbol. If the module can be disabled from
the NCS, the Disable Device option must be chosen. If the module is an output module, and can be
activated from the NCS, then the Control On/Off option must be chosen.
6.5.5 Zones
A zone shows an active and disabled device symbol.
105
Device Icons
infolbl.jpg
navbut5.jpg
To create a navigational button link, select the Navigational Button icon on the toolbar or select the
Devices Menu option, New Navigation Button. A dialog box will appear that contains a navigation
button (Figure 6.34). Double-click on the button and drag it to the appropriate area on the graphic
floor plan. After the navigation button is dragged on the screen another dialog box will appear
allowing you to set up a link (Figure 6.35).
106
navbut2.jpg
Device Icons
findcom.jpg
Once many screens are entered, finding a particular device without displaying each floor plan is
difficult. The NCS has a Find command located under the Devices menu option, under each device
category, which allows the user to find a device by entering in its device label or address
(Figure 6.36). Once the label or address is entered, the appropriate floor will be invoked. For easier
viewing, select the Flash Label checkbox to make the device blink for two seconds. For
information labels and navigation buttons, the option to blink the graphic is given (no labels for
these).
A Floor Plan containing Level 1 Groups can contain any Graphic Device.
A Level 2 Group should not be placed on a screen where a Level 1 Group resides.
Any Floor Plan can contain a Navigational Button, which functions as a link to another Floor
Plan.
Any floor Plan can contain Information Labels, which display text when double-clicked.
107
Groups
If any Groups are created (or exist already when beginning an edit session), the default
AutoNavigating setting is set to false.
6.6 Groups
Groups allow the creation of screen hierarchies for displaying the pathway to an off-normal device,
starting at a top level site view. Two levels of grouping, Level 1 and Level 2, are used to associate
devices with a single bitmap. A Level 1 group can have either Level 2 groups or actual devices
associated to it. A Level 2 group must be associated upwards to a Level 1 group (in the floor plan
hierarchy), and will have devices associated below it. The two levels of grouping plus the floor plan
where the actual off-normal device is located offer three main view levels for floor plan navigation.
These levels coupled with Navigation Buttons offer a variety of setup possibilities for graphics.
The graphics are no longer limited to one top screen, therefore the Home Screen is the first screen
created. This screen is shown on NCS / GSP Startup. This ability to have many top screens means
that Level 1 Groups can exist on different screens, each representing the Top Screen of a different
graphic path.
Figure 6.37, below, is a pictorial representation of the group levels and device relationships in an
example consisting of two campus buildings.
Main Campus
Screen 1
Bitmap assigned
Group: 4
Group Level: 1
Description: Bldg A
Bitmap assigned
Group: 5
Group Level: 1
Description: Bldg B
Bldg A
Bldg B
Detector 5
Group 5
Group Level 1
Group Level 1
Detector 6
Group 5
Group Level 1
Group Level 2
Screen 2 with
Bitmap assigned
Group: 6
Group Level: 2
Parent: Group 4,
Level 1
Descr: Bldg A Fl 1
Detector 1
Group: 6
Group Level:2
Descr: Bldg A Fl 1
Labs
Bldg A Fl 1
Detector 2
Group: 6
Group Level:2
Descr: Bldg A Fl 1
Bldg A Fl 2
Screen 3 with
Bitmap assigned
Group: 7
Group Level: 2
Parent: Group 4,
Level 1
Descr: Bldg A Fl 2
Detector 3
Group: 7
Group Level:2
Descr: Bldg A Fl 2
Detector 4
Group: 7
Group Level:2
Descr: Bldg A Fl 2
108
Setup Templates
If a device on a floor plan is associated with a group, then all other devices on that floor plan
are automatically restricted to the groups contained on the screen where the associated group
resides. In other words, if L1D1 is associated with a specific group 2, then L1D2 on that floor
plan must also be associated with group 2, or another group on the screen where group 2
resides.
Screens can contain Level 1 icons or Level 2 icons, but they can not be intermixed. If a floor
plan has a group defined, all other groups on that floor plan must be of the same level, either
Level 1 or Level 2.
109
Custom Bitmap
A hot template is defined for a specific device (the hot template and the device are actually one
item). This allows the user to easily copy information from one device to another. Once the
information for a device hot template is changed, all new devices created from it will have the new
information. Devices created with the hot template before it was changed will not contain the new
information.
editncsg.jpg
The bitmap that appears on the NCS main window next to the keymap area can be customized.
Located in \notifier\ncs\pictures\frontncs.bmp, this bitmap can be changed with any image editing
software. Select the EDIT NCS GRAPHIC command under the SETUP menu to call up the image file
and edit in Paint. When the graphics are updated, changes to the Custom Bitmap are also updated.
The size of this file must be 459 x 65 pixels, and it must be named frontncs.bmp. (See
Figure 6.38.)
110
Template Files
Floor Directories
{install}\Floors\Genfloor.bmp
\Olefloor.bmp
\NotProgF.bmp
2.
Keymap Directories
{install}\Keymaps\Genkey.bmp
\Olefloor.bmp
\NotProgK.bmp
3.
Device Directories
{install}\Device...Detector, Module, Zone BMPs
\Group...Group BMPs
\Inflabel...Device Information label BMPs
\Navigate...Device navigation button BMPs
\Pictures...Device associated bitmaps
\Sounds...Device wave files
\Docs...all text files
NOTE: Groups and Group screens should be created first if grouping is to be used.
111
From Program Manager, go to the File menu (for Windows 2000 users, select Start, then Run).
Select Run and type regedt32. This brings up the Windows 2000 Registry.
2.
3.
4.
Double-click on Windows 2000, followed by Current Version, and then Winlogon. At this
point the screen will be split into two sections. The section on the left side contains the tree
structure of the registry and the right side contains values stored in the registry.
5.
From the Edit menu, select Add Value. A dialog box will pop up. Under Value Name, type
DefaultPassword (do not change the displayed data type).
6.
Press OK. Another dialog box will pop up. Under String, enter the current password of the NT
administrator. The password is case sensitive, so be sure it is entered correctly. Press OK for
the change to take effect.
7.
From the Edit menu, select Add Value again. Under Value Name, type AutoAdminLogon.
Press OK. Under String, enter 1 (do not change the displayed data type).
8.
Verify that the two new variables entered in the previous steps appear on the right side of the
screen. The variables should appear as follows:
AutoAdminLogon:REG_SZ:1
DefaultPassword:REG_SZ:<password> (Password is the password entered by the
administrator in Step 6.)
9.
Exit the Windows 2000 Registry, and reboot Windows 2000. When it starts, the log-on screen
should be bypassed.
112
113
2.
After setup has completed, configure the software by running the Secure Setup program from
the Secure Desktop Program Group.
3.
Select Secure Desktop Icon Settings and General Options instead of Windows Explorer or
Program Manager (Default).
4.
Under Non-Specific User, select Setup, then select F1. Browse to the NCS directory, select
NCS.exe. Be sure to select App Start Enabled. Also select this option for all other programs
that will be selected.
5.
Select F2, browse to the VeriFire Tools directory (if installed), and select nts.exe.
6.
7.
8.
9.
Go to the Password Tab, select Exit Password. Enter a password that is easily remembered.
The default password is admin.
10. Click on the Registry Button. Select Secure Desktop Gina, and select Disable Ctrl-AltDel.. Select Automatic Login Enabled, if that feature is desired.
11. Click on OS Policy, and select Windows 200/ME. Under Task Manager, select Disabled
12. The PC must now be rebooted for the settings to take effect. After the PC powers back up, the
Windows Desktop will be replaced with the Secure Desktop. Click on the setup button to
change any other options.
114
Tamper
Non-Fire
Hazard Alert
Fire Control
Abort Switch
Man. Release
Trouble Mon
Burglar Ala
Silence
Pas Inhibit
System Reset
AFP-200 Message
NCS Message
activated: *Active Non Alm Mon custom point label zone label
N12L1M8 15:21:00 3/06/00
trouble: Trouble Non Alm Mon custom point label zone label
Open Circuit N12L1M8 15:35:00 3/06/00
115
Message Tables
AFP-200
Type I.D.
Smoke Detect
Heat Detect
Water Flow
Pre-Alarm
Messages
AFP-200 Message
NCS Message
*Will be displayed only in History Manager, Current Event window and NonFire Event window in the NCS
116
Messages
AFP-300/400
Type I.D.
Smoke Detect
Heat Detect
Pull Station
Monitor
(blank)
Abort Switch
Man. Release
Silence
System Reset
Security
Trouble MON
PAS Inhibit
AllCall Page
Message Tables
AFP-300/400 Message
NCS Message
117
Message Tables
AFP-300/400
Type I.D.
Tamper
Fire Control
Tele. Page
Comb. Monitor
Sprinkler Sys
Second Shot
Hazard Alert
Supervisory
Waterflow
Control
Relay
Bell Circuit
Messages
AFP-300/400 Message
NCS Message
alarm (short): Alarm: Man Rel Dlay device label zone label
N232L1M21 15:15:00 03/07/00
on: No Annunciation*
on: No Annunciation*
on: No Annunciation*
*Any AFP-300/400 messages that say 'No Annunciation' will be displayed in the History Buffer, only.
118
Messages
Message Tables
AFP-300/400
Type I.D.
AFP-300/400 Message
NCS Message
Strobe Ckt
on: No Annunciation*
on: No Annunciation*
on: No Annunciation*
on: No Annunciation*
trouble: Trouble Rel End Bell device label Invalid Reply N232L1M1
12:07:00 3/16/00
on: No Annunciation*
on: No Annunciation*
trouble: Trouble Rel Ckt ULC device label Invalid Reply N232L1M1
16:55:00 3/16/00
on: No Annunciation*
on: No Annunciation*
on: No Annunciation*
on: No Annunciation*
trouble: Trouble Rel Code Bell device label Invalid Reply N232B1
16:55:00 3/16/00
on: No Annunciation*
Horn Circuit
Audible Ckt
Release Ckt
Rel Audible
Nonreset Stl
Telephone
Instant Rele
Speaker
on: No Annunciation*
on: No Annunciation*
*Any AFP-300/400 messages that say 'No Annunciation' will be displayed in the History Buffer, only.
119
Communication protocols
File sharing
ncsethraddadapt.jpg
To begin, go to Start, Control Panel. Go to ADD & Remove Hardware and double-click.
120
ncsethraddhdw.jpg
This will bring you to the Add/Remove Hardware selection screen. Select Next.
ncsethradddev.jpg
ncsethrsrch.jpg
The screen below will be displayed for a short time. The monitor may flicker when this screen
comes on. This is normal.
121
Setup will automatically display all the devices with Plug and Play properties. Scroll down to the
network card, Intel(R) PRO/100+Management Adapter. Highlight the line, then click on Next.
ncsethradptcard.jpg
Select
this
device
ncsethrsuccesinst.jpg
The Add/Remove Hardware Wizard should display a screen momentarily, giving installation status
and device status. When the hardware has been successfully installed and is working properly, hit
Finish.
122
ncsethrntwkidwiz.jpg
This will bring up the Network Identification Wizard screen. Click on Next at the bottom of the
screen to proceed.
123
ncsethrwodoman.jpg
When the Connecting to the Network screen appears, choose My company uses a network
without a domain. Click Next at the bottom of the screen to proceed.
ncsethrwrkgrp.jpg
NCSGROUP
124
ncsethrwrktyp.jpg
Specify the network type by choosing This computer is part of a business network, and I use it
to connect to other computers at work. Then click Next.
ncsethrnetidfin.jpg
The Wizard will finally bring up the Completing the Network Identification Wizard screen,
which states that network identification has been successful. It also warns that once you hit Finish,
the computer will automatically restart. Click Finish when ready to reboot.
125
ncsethrLACcxprop.jpg
To set up the IP address of your machine, go to Start, then Settings, then Control Panel. Highlight
Network and Dial-up Connections, then double-click. Highlight Local Area Connection, then
right-click. Select Properties.
ncsethrTCPIP.jpg
The Local Area Connection Properties screen will display. Highlight Internet Protocol (TC/IP),
then hit Properties.
126
ncsethrIPprop.jpg
127
File Sharing
ncsethrshare.jpg
128
129
130
NFS-640
NFS2-640
NOTIFIRENET
Network
NFS-640
NFS2-640
NFS-3030
NFS2-3030
NFN Gateway/NCS Workstation
131
Start Interface
Select START INTERFACE command to reconnect the NCS to the NFN Gateway after reconfiguring
COM Port settings with the serial port configuration utility (Section 2.4.2) or through the COM
port settings on the NFN Settings page. (See Figure G.4)
132
The NG HOME PAGE is the default for the NFN Gateway properties window. The NG HOMEPAGE
displays general information about the NFN Gateway software and its network interface card
(NCS-NCW/F). The PROGRAM item displays the name of the application that is running. The DLL
VERSION item displays the current version number of the NFN Gateway application. The NCM
VERSION item displays the version number of the NCS-NCW/F network card installed in the
computer. These version numbers are required for technical service calls.
This information also available through the Help Menu (About).
Site Settings
SITE NAME displays the name of the NFN Gateway. (User-defined)
General Settings
Setting TROUBLE REMINDER to YES initiates a daily 11 a.m. reminder when there are uncleared
Troubles in the system.
133
NCM Settings
This dialog sets the options for the NCS-NCW/F network card installed in the NFN Gateway
computer.
NCS Settings
PRIMARY NCS determines if there should be a primary NCS on this gateway. When a primary
NCS loses communication with the gateway, a trouble is issued to all other nodes on the
network.
If this gateway is on a LAN, set this option must be set to YES.
If this gateway is on a WAN, open the IP Administration dialog to determine the status of the
connecting NCS. An NCS may be the primary NCS for more than one gateway.
See Addendum for more information.
ENABLE AUDIO determines if the user may send live voice messages over the wide area network
to this NFN Gateway. Requires a WANenabled NCS with NOTIFY-IP option. See addendum.
ENABLE FAN MONITORING When enabled the gateway monitors and reports to the NCS when the
cooling fan in the PC stops functioning. The operator must exit the NCS application and restart
it to clear this trouble condition.
134
Communication Settings
COMM PORT determines which of the PCs COM Ports contains the NCS-NCW/F card.
Map/Unmap Node
Map or unmap a node to the NFN Gateway by clicking on the node and selecting an option from
the drop-down menu.
135
ONLINE - The node was auto-detected by the NFN Gateway, but it will not communicate with NCS until it is
mapped.
2.
3.
4.
UNMAPPED - The default value; the node is either online but not communicating with NCS, or there is no
device detected at that node address. No events or properties will be displayed for unmapped nodes.
136
137
Configure Menu
WARNING: Paging via the NOTIFY-IP is unsuitable for any life safety event!
Paging via the NOTIFY-IP is unsuitable for any life safety event such as fire, emergency, and/or
mass notification signalling. Such operation requires the approval of the local Authority Having
Jurisdiction (AHJ).
To receive live voice messages, a DVC or UL-listed public address amplifier (PAA) must be
connected to the workstations speaker connector. (See Figures G.10 and G.11.). The DVC acts as a
router that sends the live page to DAAs or other analog audio devices. The PAA adjusts the audio
output from the sound card to the required voltage used by the ACT-2.
The AMPLIFIER CONFIGURATION command sets the output of the PAA to the proper level. After
selecting the command, use a screwdriver to adjust the amplifiers MUSIC VOL control until the
PEAK VOL indicator light turns on. Press OK to end the configuration (See Figure G.9). Because the
DVC has automatic gain control, this command is unnecessary when the workstation is connected
to a DVC.
Audio Configuration:
Adjust MUSIC VOL until PEAK LEVEL
indicator light turns on.
NOTE: This command applies to WAN-enabled NCSs with the NOTIFY-IP function installed.
See Wide Area Network & NOTIFY-IP Addendum for more information.
138
Configure Menu
If already connected, unplug monitor audio cable from the workstation speaker connector.
See Figure 2.6 on page 16.
2.
Using p/n 75625, connect the plug into the speaker connector of the NCS workstation.
The PAA must be mounted within six feet (1.83 meters) of the NCS.
3.
Connect bare wires to the MUSIC and GND terminals on the PAA.
4.
Use 18 AWG to 12 AWG twisted-pair cable to connect the COM and 25V terminals on the
PAA to the AUDIO IN terminals on the ACT-2.
5.
To
XPIQ
ACT-2
NCS Workstation
To next
ACT-2
p/n 75625
PAA
NOTES:
The PAA and the NCS must have a common AC power source.
The PAA can drive up to 250 ACT-2 audio coupling transformers. However, the strength and
quality of the audio signal will diminish with increased wire length.
Do not run cable adjacent to or in the same conduit as 120 volts AC service, noisy electrical
circuits that are powering mechanical bells or horns, audio circuits above 25 volts RMS,
motor control circuits, or SCR power circuits.
NOTIFY-IP paging takes the lowest priority at the XPIQ.
See the XPIQ manual for more information about priority configuration.
139
Configure Menu
If already connected, unplug the monitors audio cable from the workstation speaker
connector.
See Section 1.1.7, Connecting the Monitor in the NCS Manual.
2.
Using p/n 75625, connect the plug into the speaker connector of the NCS workstation.
The DVC must be in the same room and mounted within six feet (1.83 meters) of the NCS. The
connection from the NCS to the DVC must be in conduit.
3.
Connect bare wires to either left or right speaker channel (AUXA R or AUXA L) on Auxiliary
Input A (TB4) on the DVC.
Microphone
Connector
Speaker
Connector
NCS Workstation
p/n 72625
DVC
NOTES:
Do not run cable adjacent to or in the same conduit as 120 volts AC service, noisy electrical
circuits that are powering mechanical bells or horns, audio circuits above 25 volts RMS,
motor control circuits, or SCR power circuits.
NOTIFY-IP paging must be set at the lowest priority.
See the DVC Programming Manual or VeriFire Tools Online Help for more information about
priority configuration.
140
Notes
141
Notes
142
Index
Numerics
Data Refresh 34
Manual 25
On Power-Up 25
on the Action Menu 62
database 24
graphics 25
history 24
history, archiving 48
printing 90
see also History Manager
Upload/Download (UPDL) from node 63
Database Replication, settings 120
Date / Time Field 30
DB-15 video cable 15
DCC 129130
See also Display and Control Center
demo mode 47
Detailed Events window 68
Device Icons 102
adding 102
deleting 107
Find command 107
linked files 105
setup rules 107
disabled device window 69
Display and Control Center 34, 129130
DVC 71
A
acknowledge 31, 56, 62
acknowledged event window 29
Administration menu 33
Audio Tab 43
General NCS Tab 33
Graphic Configuration Tab 44
User Account Tab 36
AFP-300/400 71, 72
alarm 58
acknowledge 59
reporting 58
Alphanumeric Paging 63
AM2020/AFP1010 71, 72
Amplifier 138
audio messages 43
Sounds directory 43
Waves directory 43
edit speech files 49
Auto Detect Nodes Button 138
AutoNavigating 56
Auxiliary NCS 134
B
Banners 27, 31, 57, 59
Battery, LITHBATT-3V 11, 12
paper strip removal 12
C
Caution
exiting the NCS 22, 26, 60
NCS Demo mode 26
Channel A and B Threshold 134
Clients 137
colors, PC 21
column types, visibility 90
command area 31
Communications
port settings 42
Setting on the NFN Gateway 135
Compact Database 49
Confirm Module On/Off 34
Connectors 12
current event window 69
current operator field 32
Current Users list 36
to edit 36
ONYX NCS Manual P/N 51658:H 2/28/2007
E
Event Counter window 68
Events window 28
Expand Event displays 34
F
Files, required, NCS 111
Find Screen 70
FMM-1 17, 18
fonts, PC 21
G
General Settings 133
graphic event display 27
graphic floor plan 28
Adding 96
customizing 95
Deleting 97
device icons 102
editing 97
key map, setting links 98
Graphic Replication 48
143
HO
Index
H
Help menu 54
hierarchies, screen 108
History Backup 35
History Backup option 33
History Manager 8691
database 86
display priority 86
Open Archived History File 86
Operator List 87
Refresh Grid 86
search criteria 88
stand alone operation 91
History Manager window 70
Home Screen 108
I
Information Labels 105
adding 106
deleting 107
IP Access 64
IP Connection Speed 35
K
key map area 28, 98
see also Graphic Setup Program
Key Upgrade Utility 113
L
LCD monitor 10
LED indicators 11
Line Printer, connecting 19
LITHBATT-3V 11
paper strip removal 11
Logo Window 30
M
Map/Unmap Node 135
Mapped vs. Unmapped 136
Master Time Keeper 21, 33, 35
Message Tables 115
Miscellaneous Software Installation 114
Modem 16
monitor 10, 15
installing 15
mouse 14
N
Navigational Buttons 106
adding 106
deleting 107
NCA/NCA-2 24
NCM 12
NCM Settings 134
NCS Computer 13
computer connections 14
connecting to power 13
NCS computer 15
NCS functions 24
NCS Model numbers
NCS-F-ONYX 10
NCS-W-ONYX 10
NCS Software installation 21
NCS window 27
NCS-NCW/F Boards 11
Network Command Center 62
network node 24, 37
edit and display 4647
network statistics 50
Network Version 34
NFN Gateway Application 131
NFN Gateway Properties 132
NFN Settings 133
NFPA Event Reminder 34
NFS-3030/NFS2-3030 71
NFS-320 71
NFS-640/NFS2-640 71
Node Address 134
Node Maintenance 49, 52
Node Mapping 135
Nodes
Active NFN 137
Map/Unmap 135
NotiFireNet node address 33
NUP Port 11, 12
Configuration See Serial Port Configuration Utility
O
offline events, show or hide 62
Operating Mode 35
144
Index
PU
Other activation 59
acknowledging 59
P
PAA 138
Pager Carrier 33
Pager Carrier Tab 45
edit carrier information 45
Maximum Characters per Block 46
modem COM port 46
Pager Tab 38
Carrier 39
Message 39
Paging Nodes 40
Paging Time Period 39
Paging, alphanumeric 63
Paint 99, 111
password 60, 61
changing 61
NFN 136
PCLB enclosure 15
photo, to add a user 37
Piezo sounder 11
Port Supervision 34
Power Requirements 13
Power, Primary and Secondary
connecting the NCS computer 13
Power-Up Initialization 25
pre-alarm signal
reporting 59
Primary NCS 134
printer 10
graphic 20, 21, 42
line 21, 42
line, cable connections 20
PRN-6 10, 13
setup 43
UPS Supervision 18
Programming 24
Menu Options 33
Properties 132
NFN Settings 133
Node Mapping 135
Public Address Amplifier 138
R
Read Status 71
annunciator point 75
DVC 81
module 72, 79
NFS-3030 and NFS-640 screens 78
System Data 76
zone 74
Read/Write CD ROM 22
Related Documentation 8
Replication, graphics 48
ONYX NCS Manual P/N 51658:H 2/28/2007
S
Screen Device View 93
screen navigation tools 30
Screen Tree View 93
Secure Desktop Software
Installation 114
security signal 59
acknowledging 59
reporting 59
Serial Port Configuration Utility 21, 113
Settings for data base replication 120
shunt plug and UPS SUPV 11
signal silence 32, 33, 56, 62
Site Name 133
Software Version Numbers 51
Sound (Hz) 33
speaker frequencies, alarm & trouble 33
Strain relief 19
Strain relief, for MIB wires 19
Style 7 134
supervisory signal 59
acknowledging 59
reporting 59
Switches (NCS-NCW Only) 12
system reset 32
T
Templates, setup 109
Termination Resistors 12
Threshold 134
Threshold Ports A/B 34
Time Sync options 33
tool bar 30
Tree View Window 93
trouble 57
acknowledge 57
NCS NUP Communication 71
Network Fail Port A 71
Network Fail Port B 71
Node Communications Failure 71
Trouble Messages 115119
U
Upload/Download 63
UPS 13
UPS Supervision 16, 18, 34
UPS SUPV 11
User Information, editing 37
Utility Programs, NCS 113
145
VW
Index
V
VeriFire Tools
Installation 114
W
Walk Test 49, 53
Wide Area Networking 34
Windows 2000
Disable/re-enable Procedure 112
Windows NT Workstation 20
146
Limited Warranty
NOTIFIER warrants products manufactured by it to be free from
defects in materials and workmanship for eighteen (18) months from
the date of manufacture, under normal use and service. Products are
date stamped at time of manufacture. The sole and exclusive
obligation of NOTIFIER is to repair or replace, at its option, free of
charge for parts and labor, any part that is defective in materials or
workmanship under normal use and service. All returns for credit are
subject to inspection and testing at the factory before actual
determination is made to allow credit. NOTIFIER does not warrant
products not manufactured by it, but assigns to the purchaser any
warranty extended by the manufacturer of such products. This
warranty is void if the product is altered or repaired by anyone other
than NOTIFIER or as expressly authorized by NOTIFIER in
writing, or is serviced by anyone other than NOTIFIER or its
authorized distributors. This warranty is also void if there is a failure to
maintain the products and systems in which they operate in a proper
and workable manner. In case of defect, secure a Return Material
Authorization form from our Return Authorization Department.
This writing constitutes the only warranty made by NOTIFIER, with
respect to its products. NOTIFIER, does not represent that its
products will prevent any loss by fire or otherwise, or that its products
will in all cases provide the protection for which they are installed or
intended. Buyer acknowledges that NOTIFIER, is not an insurer
and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
NOTIFIER GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE,
OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION
ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL
NOTIFIER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO
PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE
NOTIFIERS PRODUCTS. FURTHERMORE, NOTIFIER SHALL
NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH
MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only
warranty made by NOTIFIER. No increase or alteration, written or
verbal, of the obligation of this warranty is authorized.
"NOTIFIER" is a registered trademark.
Warn-NL-04-2005.fm
147
World Headquarters
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118
www.notifier.com