Professional Documents
Culture Documents
PAGE
APPLICATION
Cond. Unit
Model
RCA051
RCA061
RCA071
RCA101
RCA141
RCA201
RCA271
RCA361
Air Handler
Model
V/HCA051
V/HCA071
V/HCA071
V/HCA101
V/HCA141
V/HCA201
V/HCA271
V/HCA361
Nominal
MBH
49.4
61.6
69.5
101.4
127.6
201.9
271.9
339.8
EER*
10.7
10.3
10.1
10.1
9.9
11.0
9.3
9.9
Table 1
Danger Label
DANGER
Signal Words
Warning Label
White lettering on a black background except the word
WARNING which is white with an orange background.
WARNING
Fire Hazard.
Use copper wire only.
WARNING
Caution Label
CAUTION
Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels. Following are
examples of product labels with explanations of the
colors used.
CAUTION
CAUTION
Operational failure of this unit for any reason, including but not limited to mechanical or electrical failure of devices
internal or external to the unit, loss of fuel such as natural or LP gas, or interruption of electric power may result in the
introduction of large volumes of air into the conditioned space that could cause freeze or other damage to property.
It is the responsibility of the installer and/or user of this unit to provide equipment such as a source of emergency
heat, alarm systems, or supervisory systems to warn of such failures.
2
PRODUCT DESCRIPTION
THE CONDENSING UNIT CONSISTS OF THE
FOLLOWING COMPONENTS:
Compressor: A welded hermetic compressor used in
model sizes 051 through 141 and a serviceable semihermetic compressor in model sizes 201 and larger. All
compressors have crankcase heaters and the motors are
equipped
with
internal-overload
protection
(4D
compressors use solid state module).The serviceable
semi-hermetic compressors are also equipped with
isolation valves and oil pressure failure protection.
Condenser: The condenser coils are aluminum plate
finned formed on multiple rows of seamless copper tubing
arranged in a staggered tube configuration.
Condenser Air Fan(s): Each condenser air fan is a
propeller type, electronically balanced and direct-driven.
Condenser air is drawn through the coil(s) horizontally and
discharged vertically. Therefore, heated air can not be
recirculated. A vinyl coated fan guard is provided.
Condenser Fan Motor(s): On standard RCA units the fan
motors are single phase and are controlled by a low
ambient head pressure control, which cycles the fan, or
fans to maintain high side pressure. Units with optional hot
gas reheat are different. One condenser fan is directdriven by a 1075 rpm single phase PSC fan motor, and it is
controlled by a variable speed head pressure control. This
electronic device is factory set for proper operation. The
inherently protected motor has sealed ball bearings that do
not require lubrication. On dual and multiple fan units, the
other condenser fan motor(s) are three phase and are
controlled by a separate low ambient control.
REFRIGERANT CIRCUIT COMPONENTS
Accumulator: A storage tank located in the suction line of
the system. It separates the liquid refrigerant to protect the
compressor from liquid slugging by allowing small amount
of liquid refrigerant to boil away before entering the
compressor.
Filter-Drier (liquid): A filter used in the refrigerant line to
remove moisture and small particles.
High Pressure Safety Control: A manual-reset high
pressure control switch will stop the compressor if the
system pressure exceeds 400 PSIG. This protects the
compressor in case of blockage in the high side of the
system.
Low Pressure Control/Loss of Charge Protector: An
automatic-reset low pressure control switch will stop the
compressor if the low side of the system pressure drops
below 30 PSIG. This is to protect the compressor in case
of blockage in the low side of the system or loss of charge.
This control is also used as an operating control-recycling
pumpdown.
Dual Service Connections: Used for high and low
pressure readings.
24 Volt Pump Down Solenoid Valve: Shipped loose with
the condensing unit and is to be field installed in the liquid
line as close to the evaporator, at the air handling unit, as
Condenser Coil(s)
Condenser Fan(s)
Refrigerant Connections O.D.*
Face
Fins
Hot Gas
Nom
Area Rows Per
Total
Hot Gas
Reheat
Model Type Tons Sq.Ft. Deep Inch No. HP
CFM
Suction Liquid
Bypass
Ea. of 2
RCA051
H
3 1/2
7.7
3
12
1
1/2
4,000
7/8
3/8
3/8
3/8
RCA061
H
4 1/2
7.7
3
12
1
1/2
4,000
1 1/8
3/8
1/2
3/8
RCA071
H
5
7.7
4
12
1
1/2
3,900
1 1/8
3/8
1/2
1/2
RCA101
H
7 1/2
15.4
3
12
1
1
6,000
1 1/8
1/2
5/8
1/2
RCA141
H
10
15.4
4
12
1
1
5,800
1 3/8
1/2
5/8
1/2
RCA201 SH
15
23.1
3
12
2
1
12,000
1 5/8
5/8
3/4
1/2
RCA271 SH
24
23.1
4
12
2
1
11,600
1 5/8
5/8
3/4
5/8
RCA361 SH
27
38.5
4
12
3
1
18,000
2 1/8
3/4
3/4
5/8
Notes: H = Welded Hermetic
SH = Serviceable Semi-Hermetic
*Optional Hot Gas Reheat is connection size for each of two connections.
For recommended line size, see page 16.
Contact factory for additional models not listed above.
Table 2
Weight
Unit
Oper
265
290
310
525
600
975
1,100
1,470
Unit
Ship
315
340
360
600
675
1,070
1,200
1,600
Face
Fins
Area Rows Per
Sq.Ft. Deep Inch
2.8
4
12
4.5
4
12
8.0
3
12
DWDI
Size
10 x 4
10 x 4
12 x 12
Blower
Motor H.P.
Std.
Opt.
S
M
1/2
NA
1/2
NA
1/2
3/4
VCA141
HCA141
8.0
12
12 x 12
1/2
3/4
VCA201
VCA271
VCA361
HCA201
HCA271
HCA361
14.6
14.6
19.5
4
4
4
12
12
12
15 x 15
15 x 15
15 x 15
3/4
1
1 1/2
1
1 1/2
2
Table 3
Opt.
L
NA
NA
NA
Cond.
Drain
Size
No.
F.P.T.
1
3/4
1
3/4
2
3/4
3/4
1 1/2
2
3
2
2
2
1 1/4
1 1/4
Filters 1"
Metal Mesh
No.
1
2
2
1
2
1
6
6
4
2
Size
20 x 25
16 x 22
16 x 25
20 x 25
16 x 25
20 x 25
16 x 25
16 x 25
20 x 24
20 x 30
Weight
Pounds
Unit
Unit
Oper.
Ship
140
170
210
240
400
440
460
500
780
800
935
840
860
995
V/HCA051
1-9
V/HCA071
1-12
V/HCA141
1-25
V/HCA201
5-39
V/HCA271
V/HCA361
5-50
10-60
UNIT LOCATION
Condensing Unit Location
Locate as near as possible to the inside section in order to
keep connecting refrigerant tubing lengths to minimum and
thus minimize loss of capacity due to long lines (see Table
9 Notes 5 & 6).
An intake louver protects the service end and clearance at
this point should be maintained. A 36" clearance must be
allowed for access to the compressor and electrical panel.
A 24" clearance must be maintained for the air inlet to the
condenser coil(s).
Do not locate the unit under an overhang that will short
circuit hot air to the coil intakes.
When installed at ground level, the unit should be mounted
on a level concrete slab which should extend at least 2"
beyond the unit on all sides. The top of the slab should be
2" above the ground level. The depth of the slab below the
ground level and its structural design is governed by the
type of soil and climatic conditions. The slab must not be in
contact with any part of the building wall or foundation. The
space between the slab and building wall prevents the
possibility of transmitting vibration to the building.
VCA/HCA
071
VCA/HCA
101
VCA/HCA
141
VCA/HCA
201
VCA/HCA
271
VCA/HCA
361
Notes:
CFM
0.4
R.P.M. B.P.H.
0.6
R.P.M. B.P.H.
400
780
0.2
900
500
840
0.2
960
600
870
0.2
990
700
940
0.2
1,030
500
720
0.2
840
600
750
0.2
860
700
800
0.2
890
800
840
0.2
930
900
890
0.3
970
900
610
0.2
720
1,100
640
0.2
750
1,300
660
0.2
760
1,500
680
0.3
780
1,100
650
0.2
770
1,400
700
0.3
800
1,700
740
0.4
820
2,000
790
0.5
860
1,500
480
0.3
590
2,000
510
0.4
600
2,500
550
0.5
630
3,000
580
0.7
650
2,500
550
0.4
630
3,000
580
0.7
650
3,500
630
0.9
690
4,000
650
1.2
730
3,200
530
0.6
600
3,800
570
0.8
620
4,400
600
1.2
660
5,000
640
1.6
700
Unshaded areas for S Models.
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.5
0.6
0.3
0.5
0.6
0.8
0.6
0.8
1.1
1.4
0.7
1.0
1.3
1.7
0.8
R.P.M. B.P.H.
1.0
R.P.M. B.P.H.
1.2
R.P.M. B.P.H.
1,030
0.2
1,150
0.2
1,240
1,060
0.2
1,170
0.2
1,260
1,090
0.2
1,190
0.3
1,270
1,120
0.3
1,220
0.3
1,300
960
0.2
1,060
0.2
1,160
980
0.2
1,080
0.2
1,770
1,000
0.2
1,090
0.3
1,190
1,040
0.3
1,110
0.3
1,210
1,070
0.3
1,150
0.4
1,230
820
0.3
910
0.3
990
840
0.3
930
0.4
1,020
850
0.4
950
0.4
1,030
870
0.4
960
0.5
1,040
860
0.3
940
0.4
1,020
880
0.4
960
0.5
1,040
900
0.6
980
0.7
1,050
940
0.7
1,010
0.8
1,080
670
0.4
740
0.5
810
680
0.6
750
0.6
820
690
0.7
760
0.8
830
720
0.9
780
1.1
840
690
0.7
760
0.8
820
720
0.9
780
1.1
830
740
1.2
800
1.4
850
780
1.5
820
1.7
870
660
0.8
720
1.0
780
680
1.2
750
1.3
800
720
1.5
770
1.7
820
750
1.8
800
2.1
850
Light Gray shaded areas for M Models.
1.4
R.P.M. B.P.H.
1.6
R.P.M. B.P.H.
0.3
1,320
0.3
1,410
0.3
0.3
1,330
0.3
1,430
0.4
0.3
1,350
0.3
1,440
0.4
0.4
1,380
0.4
1,450
0.4
0.2
1,260
0.3
1,340
0.3
0.3
1,270
0.3
1,350
0.3
0.3
1,280
0.4
1,360
0.4
0.4
1,290
0.4
1,370
0.5
0.5
1,300
0.5
1,380
0.5
0.4
1,050
0.5
1,120
0.5
0.4
1,080
0.5
1,140
0.6
0.5
1,090
0.6
1,160
0.7
0.6
1,100
0.7
0.5
1,090
0.6
1,160
0.6
0.7
1,120
0.7
1,180
0.8
0.8
1,130
0.8
1,200
0.9
0.9
1,140
1.0
0.6
860
0.7
920
0.8
0.8
870
0.9
930
1.1
1.0
880
1.2
940
1.3
1.3
890
1.5
1.0
880
1.2
940
1.3
1.3
890
1.4
950
1.6
1.6
910
1.7
960
1.9
1.8
1.2
840
1.3
900
1.5
1.5
850
1.7
910
1.8
1.8
870
2.1
920
2.3
2.4
900
2.6
940
2.7
Dark Gray shaded areas for L Models.
Table 5
DIMENSIONS
DIMENSIONS Continued
DIMENSIONS
10
DIMENSIONS Continued
11
ELECTRICAL
Electrical Data Condensing Unit
Model
RCA051-1E
RCA051-3E
RCA051-4E
RCA051-6E
RCA061-1E
RCA061-3E
RCA061-4E
RCA061-6E
RCA071-1E
RCA071-3E
RCA071-4E
RCA071-6E
RCA101-3E
RCA101-4E
RCA101-6E
RCA141-3E
RCA141-4E
RCA141-6E
RCA201-3E
RCA201-4E
RCA201-6E
RCA271-3E
RCA271-4E
RCA271-6E
RCA361-3E
RCA361-4E
RCA361-6E
Power
208/230-1-60
208/230-3-60
460-3-60
380/415-3-50
208/230-1-60
208/230-3-60
460-3-60
380/415-3-50
208/230-1-60
208/230-3-60
460-3-60
380/415-3-50
208/230-3-60
460-3-60
380/415-3-50
208/230-3-60
460-3-60
380/415-3-50
208/230-3-60
460-3-60
380/415-3-50
208/230-3-60
460-3-60
380/415-3-50
208/230-3-60
460-3-60
380/415-3-50
Compressor
RLA
LRA
21.5
95.4
13.8
82.0
6.9
41.0
6.9
41.0
27.6
125.0
16.0
90.0
7.7
45.0
7.7
45.0
30.8
142.0
19.3
130.0
8.7
65.0
8.7
65.0
27.1
183.0
14.2
91.0
14.2
91.0
34.6
193.0
17.3
97.0
17.3
97.0
48.2
275.0
23.6
138.0
23.6
138.0
86.0
428.0
43.0
214.0
43.0
214.0
118.0
470.0
59.0
235.0
59.0
235.0
No.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
3
3
3
Condenser
Fan Motors(s)
HP
1/2
1/2
1/2
3/4
1/2
1/2
1/2
3/4
1/2
1/2
1/2
3/4
1
1
3/4
1
1
3/4
1
1
3/4
1
1
3/4
1
1
3/4
FLA
3.5
3.5
1.8
2.2
3.5
3.5
1.8
2.2
3.5
3.5
1.8
2.2
6.2
3.1
2.2
6.2
3.1
2.2
6.2
3.1
2.2
6.2
3.1
2.2
6.2
3.1
2.2
Unit
RLA
25.0
17.3
8.7
9.1
31.1
19.5
9.5
9.9
34.3
22.8
10.5
10.9
33.3
17.3
16.4
40.8
20.4
19.5
60.6
29.8
28.0
98.4
49.2
47.4
136.6
68.3
65.6
MCA*
31
21
11
11
38
24
12
12
42
28
13
14
41
21
20
50
25
24
73
36
34
120
60
59
167
84
81
Max
Fuse
Size*
50
30
15
15
60
35
15
15
70
45
20
20
60
35
30
80
40
40
110
50
50
200
100
100
250
125
125
Max. Fuse Size Maximum Time Delay fuse or HACR Circuit Breaker
Table 6
Electrical Data
Air Handler Blower Motor
Motor
Horse
Power
1/2
3/4
1 1/2
Power
208/230-1-60
208/230-3-60
460-3-60
380/415-3-50
208/230-1-60
208/230-3-60
460-3-60
380/415-3-50
208/230-1-60
208/230-3-60
460-3-60
380/415-3-50
208/230-1-60
208/230-3-60
460-3-60
380/415-3-50
208/230-1-60
208/230-3-60
460-3-60
380/415-3-50
208/230-3-60
460-3-60
380/415-3-50
FLA
4.4
2.0
1.0
1.5
5.4
2.8
1.4
2.1
6.4
3.6
1.8
1.9
7.7
4.6
2.3
2.7
13.0
6.2
3.1
3.5
8.0
4.0
4.7
MCA*
6
3
2
2
7
4
2
3
8
5
3
3
10
6
3
4
17
8
4
5
10
5
6
Max
Fuse
Size*
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
25
15
15
15
15
15
15
Table 7
12
Requirements
All electrical work shall conform to the
National Electric Code and Local Codes.
The power supply should be checked
against the unit nameplate characteristics.
It must be within 10% of rated voltage and
not more than 2% phase unbalance. The
power supply cables must be sized to
carry the minimum circuit ampacity listed
on the nameplate.
For your safety, make sure that the unit
has been properly grounded at ground lug
connection. Do not obstruct service panels
or service areas with electrical gear.
ELECTRICAL CONTINUED
LOW VOLTAGE WIRING
Control System Wiring: For commercial equipment the
following table lists the minimum size of 24 volt class 2
wire to be used.
Wire Size
18 AWG
16 AWG
14 AWG
14 AWG
100 x 5 =
215
500
215
2.3%
Note: Wiring Consult the wiring diagram furnished with the unit. These units are custom designed for each application.
The following wiring diagrams are furnished only as a guide to the installing contractor. The unit wiring diagram is located
inside the control panel of each unit.
13
14
15
PIPING
0 to 25
RCA
Model
051
061
071
101
141
201
271
361
Suction Liquid
7/8
3/8
1 1/8
3/8
1 1/8
3/8
1 1/8
1/2
1 3/8
1/2
1 5/8
5/8
1 5/8
5/8
2 1/8
5/8
Notes: 1.
2.
3.
4.
5.
Hot Gas
Bypass
1/2
1/2
1/2
5/8
3/4
3/4
3/4
3/4
Hot Gas
Suction Liquid Bypass
7/8
3/8
1/2
1 1/8
1/2
5/8
1 1/8
1/2
5/8
1 1/8
1/2
5/8
1 3/8
5/8
3/4
1 5/8
5/8
3/4
1 5/8
3/4
3/4
2 1/8
3/4
7/8
51 to 75
Hot Gas
Hot Gas
Reheat
Suction Liquid Bypass
3/8
3/8
7/8
3/8
1/2
1/2
3/8
1 1/8
1/2
5/8
1/2
3/8
1 1/8
1/2
5/8
5/8
3/8
1 3/8
1/2
5/8
5/8
1/2
1 3/8
5/8
3/4
3/4
1/2
1 5/8
3/4
3/4
7/8
1/2
2 1/8
3/4
3/4
7/8
5/8
2 1/8
3/4
7/8
Hot Gas
Reheat
1/2
3/8
1/2
3/8
1/2
3/8
5/8
3/8
5/8
1/2
3/4
1/2
7/8
1/2
7/8
5/8
Line lengths are equivalent, Including all fittings. Use long radius elbows only.
Table 9
Installation of Piping
Read these instructions completely before proceeding
with piping.
! WARNING: This system contains dry nitrogen
under pressure and must be relieved before making
connections Nitrogen is nonpolluting and may be
vented to the atmosphere.
Remove access panels from compressor section. Prepare
to connect the two sections with clean dehydrated
refrigeration grade tubing. Recommended line sizes can
be found in Table 9. In order to assure oil return a velocity
of 1000 FPM must be maintained.
Use standard industry methods to install piping including
traps and risers as recommended for the total equivalent
feet.
Locations where copper tubing will be exposed to
mechanical damage should be avoided. If it is necessary
to use such locations, the tubing should be enclosed in
rigid or flexible conduit.
Horizontal piping runs should be supported enough to
prevent high binding stresses in the tubing. The weight of
vertical piping may be either supported with riser clamps
bearing on structural members of the building or by a
platform at the bottom of the riser.
The suction line, hot gas bypass, and both hot gas reheat
lines (if included) should be insulated with 5/8" minimum
thickness closed cell foamed insulation, to prevent
sweating or heat loss. All lines, except the liquid line, must
16
PIPING Continued
INSTRUCTIONS FOR PIPING HOT GAS BYPASS
Before piping this refrigerant circuit it is important to read
the Installation of Piping Instructions. See page 14.
Locate the hot gas bypass tee (factory installed) at the
evaporator coil. It is located between the thermostatic
expansion valve and the distributor.
Locate the hot gas bypass circuit connection in the
condensing unit. The hot gas bypass valve and solenoid
are factory installed. See Table 9, Notes 5 & 6.
17
18
CAPACITY CONTROL
Cylinder Unloading
Cylinder Unloading is utilized on all RCA units with semi
hermetic compressors. The unloader pressure switch
MUST be field adjusted on these units. It should be set to
open (unload) at 64 PSIG and close at 78 PSIG. This will
maintain a refrigerant temperature in the evaporator of
approximately 40 degrees F. This is a general
recommended setting and may have to be adjusted in up
or down a few PSIGs for optimum operation. A 14 PSIG
differential should be maintained. If the compressor runs
unloaded for long periods of time, it is an indication that the
control is set too high, or that some other part of the
system needs adjustment. Check airflow, expansion valve
superheat, refrigerant charge or low ambient conditions.
Hot Gas Bypass
The purpose of the hot gas bypass refrigerant circuit is to
maintain evaporator temperature above freezing (32
degrees), thus saving the compressor from failure and
controlling capacity. Compressor capacity modulation by
means of hot gas bypass is used where normal
compressor cycling or the use of cylinder unloading alone
may not be sufficient. This bypass valve is used on all
SEQUENCE OF OPERATION
Control Sequence
Refer to Figure 12 for typical wiring diagrams for these
units.
The field supplied system switch is closed. The R circuit
from the transformer is fed through the system switch to
the coil of the blower motor contactor. This energizes the
coil and closes the contacts which brings power to the
blower motor.
From the low voltage terminal board R is connected to
the G by the closing of the system switch. G is a series
circuit through the compressor lockout thermostat. If the
outdoor temperature is above the setting of the
compressor lockout thermostat, G is connected to the Y
terminal and continues to the coil of the cooling relay. This
energizes the contacts of the cooling pilot relay which
energizes the hot gas bypass solenoid. Another set of
contacts from this relay apply power to the A terminal of
the low voltage terminal board. This energizes the coil of
the liquid line solenoid valve. In a parallel circuit power is
applied to the high pressure control, and the adjustable
time delay. The time delay begins when power is applied
to the timer.
After the time delay closes, the circuit continues through
the low pressure switch, and the compressor overload
protection module (if supplied). The coil of the compressor
contactor is now energized. At this time the coil of the
contactor for the condenser fans is fed through the low
ambient control switch (units with reheat use the variable
speed control). The contacts close and power is applied to
the compressor and fan motors.
On systems with semi-hermetic compressors, the
compressor contactor and condenser fan contactor(s) are
in a series circuit with the oil failure control, and the
optional phase monitor. The unloading pressure control will
energize and de-energize the unloader solenoid on the
compressor as needed.
20
SERVICE
MAINTENANCE
Filters must be checked at least once each month on
commercial operations. It is not recommended that filters
be allowed to load entirely with dirt before replacement
since this practice will permit excess dirt to foul the cooling
coil and introduce service problems by reducing air flow.
Provisions have been made for ease in changing these
items.
Belts and Pulleys should be checked whenever filters are
changed. Make sure belts and setscrews are set tight.
Check for wear, cracking, alignment, tension and motor
amperage.
Condensate Drains should always be checked whenever
filters are changed to ensure the condensate is draining
properly.
Condensate Drain Pan should be cleaned and flushed
every six months.
Bearings require no maintenance since sealed ball
bearings are used in the blower motor and condenser fan
motors. Lubrication is thus provided for the life of the
bearing.
Finishing of the sheet metal parts are done by painting in
an Electro-deposition paint system for a dipped and baked
enamel finish. Appearance can be restored with
automotive wax.
Seacoast Construction. Units furnished with the
Seacoast Construction protection option or other corrosion
protection coating (Heresite or Bronz Glow); it is imperative
to clean and inspect the cabinet, coils and components on
a semi-annual basis. Use a chemical cleaning agent to
neutralize the contaminant. Then rinse thoroughly. Fresh
water rinsing alone doesnt not constitute cleaning.
Controls require no routine maintenance. The points on the
compressor contactors will become discolored through
usage, but it will not effect system operation, Do not dress
or file contact points. Should a surge of power or unusual
condition damage points, replace them with identical items
from the manufacturer.
PARTS SECURITY CHECK
Before leaving an installation or operating the unit,
determine whether any loose parts should be tightened.
Failure to do this may lead to noisy operation.
Check all setscrews on blowers and fan blades.
Adjust and tighten all thrust collars.
Adjust all belts and check drives.
Retighten all electric connections.
PROCEDURE FOR COMPRESSOR REPLACEMENT
It is standard practice to install a liquid line drier in a
commercial split system. New system must be evacuated
as outlined on page 14 to remove air and noncondensables in the system. The liquid line drier will trap
any moisture left in the system.
System cleaning after compressor failure or burnout.
Isolate the compressor and remove the refrigerant from
system.
Remove the inoperative compressor.
Install a properly sized suction line filter-drier in the
compressor suction line and replace liquid line drier.
Examine expansion valves and solenoid valves to see if
cleaning or replacement is required.
Install the replacement compressor.
Evacuate the compressor and system to 500 microns.
Open the compressor service valves and charge the
system with R-22 after compressor evacuation. See page
18 for instructions on initial start-up procedures.
Operate the system. Check the pressure drop across the
suction and liquid drier after the first 1 1/2 hours of
operation. Pressure drop across a liquid line drier should
not exceed 5 PSI and the suction line filter-drier should not
exceed 3 PSI.
After 8 to 24 hours, take an oil sample and test with an
acid test kit. If the oil dirty or acidic, change the suction line
and liquid line filter drier and recheck after 8 hours of
compressor operation.
After two weeks, recheck oil acidity to see if another
change of suction line and liquid line filter-drier is
necessary.
In some cases non-condensable gases are produced
during the burnout. Compare the equalized head pressure
with the pressure (equivalent) to the outdoor temperature.
If the pressures are different, then the system should be
purged.
System cleaning after compressor mechanical
failures: Mechanical compressor failures such as oil
pump, valve plates, etc. may not necessarily contaminate
the system. Check oil of defective compressor by means of
an oil acid kit and check compressor for shorts, grounds
and continuity- if all checks negative, then it is only
necessary to evacuate replacement or repaired
compressor and install a new liquid line drier. Make an
acid test after 8 hours of operation.
ORDERING PARTS
When reporting shortages or damaged parts, give the
complete unit model and serial number which is stamped
on the unit rating plate. These units are made special to
order and the following parts list should only be used as a
guide. Do not order parts from these lists.
21
POSSIBLE TROUBLE
METHOD OF FINDING
Compressor
Will Not Start.
Compressor
Starts But Cuts
Out On Low
Pressure Switch.
Low on refrigerant.
Airflow restricted.
Compressor
Starts But Cuts
Out On High
Pressure Switch.
Refrigerant overcharged.
Condenser fan control has incorrect setting.
Fan motor defective.
Condenser coil inlet obstructed or dirty.
Air or non-condensables in system.
Defective high pressure switch.
Restriction in discharge or liquid line.
Compressor
Cuts Out On
Thermal Overload.
Low voltage.
Sustained high discharge pressure.
High suction and discharge pressures.
Defective compressor overload.
Defective run capacitor.
Improper refrigerant charge.
Bearings or pistons too tight.
Allow time for compressor to cool.
Check voltage.
Check running amperage and conditions described under high discharge pressure.
Check TXV setting, check for air in system.
Allow compressor to cool for two hours if compressor is hot. Recheck for open circuit.
Check run capacitor for compressor and fan motor.
Check subcooling.
Check for low oil level.
Check dome temperature of compressor.
Compressor
Cuts Out On Oil
Failure Control
(Semi-Hermetic).
Noisy
Compressor.
Reverse wiring at disconnect switch may require blower be rechecked for rotation.
Refrigerant overcharged.
Excess or insufficient oil in compressor crankcase.
Liquid floodback.
Tubing rattle.
Compressor defective.
22
SYMPTOM
POSSIBLE TROUBLE
METHOD OF FINDING
Noisy Operation.
Tubing rattle.
Check blower, motor and drive for faulty adjustment or noisy bearings, loose parts, blower out of
balance.
Check ductwork. Air Velocity too high.
Check for adequate control voltage, check for shorts or breaks, check thermostat, check contactor
points.
Dampen by taping or clamping, bend tubing away from contact where possible.
High Suction
Pressure.
Check for high entering wet bulb temperature. Check for excessive airflow.
Remove head (semi-herm.) inspect valve reeds. Scroll compressors should not be pumped down below
5 PSI.
Recalibrate unloader pressure switch.
Check temperature across check valve.
Check the TXV, ensure bulb is insulated.
High Discharge
Pressure.
TXV setting.
Air inlet to condenser dirty or obstructed.
Condenser fan, motor defective.
Condenser fan control has incorrect setting.
Suction Pressure
Too Low.
Refrigerant undercharge.
Blower running backwards.
Loose blower pulley or belts.
Defective or improperly adjusted expansion valve.
Dirty filter.
Too little airflow or low entering air temperature.
Restriction in suction or liquid line.
Head Pressure
Too Low.
Compressor
Short Cycles.
Air noise.
Chattering contactor.
23
POSSIBLE
METHOD OF FINDING
Running Cycle
Too Long Or Unit
Operates
Continuously.
Refrigerant undercharged.
Dirty filter or evaporator coil.
Dirty or clogged condenser coil.
Air or other non-condensables in system.
Defective compressor.
Restriction in suction and liquid line.
Control contacts stuck.
Check subcooling.
Check filter, coil and airflow.
Check coil and airflow.
Check equalized high side pressure with equivalent outdoor temperature.
See above high suction pressure.
Check for restrictions in refrigerant circuit.
Check thermostat, shorts in wiring, slave relay compressor contactor.
Supply Air
Temperature
Too High.
Supply Air
Temperature
Too Low.
Check evaporator coil, filter, check for closed dampers, grills, drive for loose parts,
belts, misalignment, check external static pressure.
Check entering air wet bulb conditions.
Liquid Line
Too Hot.
Refrigerant undercharged.
High discharge pressure.
Charge by subcooling.
See above high discharge pressure.
Liquid Line
Frosted Or Wet.
Suction Line
Frosting.
Check airflow, check drive for loose parts, belts, closed dampers.
Restriction upstream at point of frosting.
Check bulb of TXV.
Blower Motor
Not Running.
Improper wiring.
Defective motor.
Defective thermostat or control circuit.
Motor off on overload protector.
24
DATE
Customer Name______________________________
Address ____________________________________
City________________________________________
ST, Zip _____________________________________
Phone # ____________________________________
PRODUCT INFORMATION
Unit Model #_________________________________
OPERATING INFORMATION
Supply Voltage L1-L2 ____________________ L2-L3 _______________________L1-L3 _______________________
(Return) Entering Air Temperature __________ DB _________ WB__________
Note: To Calculate Superheat Convert Suction Pressure to Saturation Temperature, Then Subtract the Suction Line
Temperature From the Saturation Temperature of the Evaporator.
Discharge Pressure ______ PSIG
Note: To Caluclate Subcooling Convert Head Pressure to Saturation Temperature, Then Subtract the Liquid Line
Temperature From the Condensing Temperature (Saturation).
Oil Level ___________ Crankcase Heater Operating _____________ Sight Glass Clear ____________
Noise Level ____________ Condition of Unit __________________________________________________________
Compressor(s)
#1 FLA ______Voltage T1-T2 _______ T2-T3 ______ T1-T3 ______ Amperage 1PH _______ 2PH______ 3PH _____
#2 FLA ______Voltage T1-T2 _______ T2-T3 ______ T1-T3 ______ Amperage 1PH _______ 2PH______ 3PH _____
Condenser Fan(s)
CUT-IN
CUT-OUT
CUT-IN
CUT-OUT
25
NOTES
26
NOTES
27
28