You are on page 1of 19

VOLTAGE STABILITY IMPROVEMENT USING STATIC VAR COMPENSATOR IN

POWER SYSTEM

BY
EMEZUE EMMANUEL C.
12H/0018/EE

A PROJECT RESEARCH SUBMITTED TO THE DEPARTMENT OF ELECTRICAL/


ELECTRONIC SCHOOL OF ENGINEERING TECHNOLOGY, FEDERAL POLYTECHNIC
OWERRI IMO STATE.

IN PARTIAL FULFILLMENT FOR THE REQUIREMENT FOR THE AWARD OF HIGHER


NATIONAL DIPLOMA (HND) IN ELECTRICAL AND ELECTRONIC ENGINEERING.
OCTOBER 2014

CERTIFICATION PAGE
This is to certify that is work Voltage Stability Improvement using Static Var
Compensator in Power System was carried out by EMEZUE EMMANUEL .C. With the
Reg. No: 12H/0018/EE in the Department of Electrical-Electronic Engineering, under
the supervision.
..

Engr. U.S Osondu

Date

(Supervisor)
..

....

Engr. M.U Anyaehie

Date

(Co-coordinator)
..
Engr. (Lady) M.I Aririguzo

Date

(H.O.D)
..
External Examiner

..
Date

TABLE OF CONTENT
TITLE PAGE
CERTIFICATION PAGE

ABSTRACT

ii

TABLE OF CONTENT

iii

CHAPTER ONE
1.0 INTRODUCTION .1
1.1 STATIC VAR COMPENSATOR..3
CHAPTER TWO
2.0 LITERATURE REVIEW4
2.1 SYSTEM MODEL.4
CHAPTER THREE
3.0 METHODOLOGY.7
2

3.1 MODEL OF SVC WITH PSCAD PRESENTATION7


3.2 SIMULATION AND RESULT..10
CHAPTER FOUR
4.0 CONCLUSION..12
REFERENCE ..13

ABSTRACT
This paper investigates the effects of static VAR compensator (SVC) on voltage
stability of a power system. The functional structure for svc built with a Thruster
controlled reactor (TCR), and its model are described. The model is based on representing
the controller as variable impedance that changes with the firing angle of the TCR. A
power

system

computer

aided

Design/Electromagnetic

Transients

including

DC

(PSCAD/EMTDC) is used to carry out simulations of the system under study and detailed
results are shown to access the performance of svc on the voltage stability of the system.

CHAPTER ONE
1.0 INTRODUCTION
Dynamic voltage support and reactive power compensation have been long recognized
as a very significant measure to improve the performance of electric power systems. The
rapid advances in power electronics area have made it both practical and economic to
design powerful thyristor controlled reactive power compensation devices, Static Var
Compensators (SVC) [ 13. Both theoretical analysis and field tests have proved the
excellent SVC performances.
Power systems suffer greatly from voltage instability especially due to excessive
consumption or injection of reactive power by the system elements and the consumers
load.
The voltage instability caused by the variation in the reactive power requirement of
the systems elements and the consumers load either result in excessive high or low
voltage which may cause damage to the system and the consumers load since the system
elements and the consumers load are designed to operate within a specific voltage goes
high if there is excessive injection of reactive power by the system elements or the
consumers load, but goes low if there is excessive consumption of reactive power by the
system elements or the consumers load. As a result the system the systems reactive
power needs to be congruously adjusted through effective reactive power compensation of
3

the variation in the system must be kept within the allowance range. To achieve this
several methods have been used, like the switching in/out the shunt reactive, series
compensation capacitor, synchronous generator etc.
With these methods the desired objectives were at effectively achieved with wear and
tear in the mechanical components and slow response being the major problems.
Research work were carried out leading to the discovery of FACTS devices which have
been mainly used in solving power system steady state control these FACTS devices
include, static VAR comparator (SVC), Thyristor controlled series capacitor (TCSD) static
synchronous compensator (STATCOM) etc.
Todays changing electric power systems create a growing need for flexibility,
reliability, fast response and accuracy in the fields of electric power generation,
transmission, distribution and consumption. Flexible Alternating Current Transmissions
Systems (FACTS) are new devices emanating from recent innovative technologies that are
capable of altering voltage, phase angle and/or impedance at particular points in power
systems. Their fast response offers a high potential for power system stability
enhancement apart from steady-state flow control.
Among the FACTS controllers, Static Var Compensator (SVC) provides fast acting
dynamic reactive compensation for voltage support during contingency events which
would otherwise depress the voltage for a significant length of time.
The primary purpose of SVC applications is to maintain bus voltage at or near a
constant level. In addition SVC may improve transient stability by dynamically
supporting the voltage at key points and steady state stability by helping to increase
swing oscillation damping. The theory of transient stability improvement by SVC is now
well understood in light of the equal area criterion. As for the damping improvement,
although computer simulations and field test results have shown the improvement
[2,3,4], the author feels that some fun damental issues still need to be discussed in order
to explain why power system damping can be improved by SVC applications and how.
This paper attempts to address these issues by using the well-known equal area
criterion.
It is found that a bus voltage controlled SVC does not contribute significantly to
system damping. A significant contribution to system damping can be achieved when an
SVC is controlled by some auxiliary signals superimposed over its voltage control
loop[2,3]. Usually SVC control systems are designed to have a voltage control loop with
continuous auxiliary damping control signal superimposed. It was found in [2] that while
the voltage regulation with continuous damping control signal design has good
performances when system oscillations are small in magnitude, it fails in providing
damping in some critical large oscillation cases. It has been suggested that discontinuous
4

"bang-bang" type of controls should be used for damping large oscillations. In the
application of SVC to a power system its contribution to system damping depends on SVC
location in the system. In the best SVC location to achieve the maximum damping
improvement in a two-area power system was studied by numerical methods. It is found
that the mid-point of the transmission circuit is the best SVC location
SVC also dampens power swings and reduces system losses by optimized reactive
power control. Power System Computer Aided Design/Electromagnetic Transients Direct
Current (PSCAD/EMTDC) has been used in this paper to conduct simulations on voltage
regulation at the point of connection of SVC to the system.
However, the aim of this paper is to enhance voltage stability using static Var
compensator at the event of occurrence of fault in the system.
1.1

SIGNIFICANCE OF THE PROJECT

The main advantage of SVCs over simple mechanically switched compensation schemes is
their near-instantaneous response to changes in the system voltage. For this reason they
are often operated at close to their zero-point in order to maximise the reactive power
correction they can rapidly provide when required.
They are, in general, cheaper, higher-capacity, faster and more reliable than dynamic
compensation

schemes

such

as

synchronous

condensers.

However,

static

VAR

compensators are more expensive than mechanically switched capacitors, so many system
operators use a combination of the two technologies (sometimes in the same installation),
using the static VAR compensator to provide support for fast changes
1.2 CAUSES OF UNDERVOLTAGE AND OVERVOLTAGE
OVERVOLTAGE: The cause of over-voltage on a power system may be broadly divided
into two major categories viz.

Internal causes

External causes

INTERNAL CAUSES: internal cause of over-voltage on the power system is primarily due
to oscillations set up by the sudden changes in the circuit conditions. These circuit
changes may be a normal switching operation such as opening of circuit breaker or it
may be fault condition such as grounding of a line conductor.
Internal causes do not produce surges of large magnitude. Experience shows that sages
due to internal causes are generally taken care of by providing proper insulation to the
equipment in the power system.
5

Internal causes of over-voltage on a power system include the following:

Switching surges

Insulation failure

Arcing ground

Resonance
Switching surges: The over-voltage produced on the power system due to

switching operation is known as switching surges. The following cause can set up overvoltages:
i)

case of an open line

ii)

case of a loaded line

iii)

current chopping
Insulation failure: The most common of insulation failure in the system is the

grounding of conductor i.e. insulation failure between line and earth. Below illustrates
this:-

(-E,E/Zn)
P

(-E,-E/Zn)
Q

Fig.1:
Suppose a line at potential E is earthed at point x. the earthing of the line causes two
equal voltages of E to travel along XO and XP containing currents E/Zn and +E/Zn
respectively. Both these currents pass through X to earth so that current to earth is
2E/Zn (where Zn is the natural impendence given by Zn = L/C).

Arcing ground: this is the phenomenon of intermittent arc taking place in line
to-ground fault of a 3- system with consequent production of transients. These
6

transients are cumulative and may cause serious damage to the equipment in the power
system by causing breakdown of insulation.
Resonance: under resonance, the impedance of the circuit is equal to the

inductance of the circuit and the power factor is unity. Resonance causes high voltages in
the electrical system.
EXTERNAL CAUSE: External causes are mainly surges due to lightening which are
always very severe and may increase the system voltage to several the normal values.
Over-voltage due to lightering is known as voltage spike.
UNDERVOLTAGE: This is generally chronic problem caused by a number of factors
beyond the end users control. These factors which can lead to under voltage may
include. Weather, high demand and others, distribution characteristics of the system can
also contribute to the chronically low voltage situations. For example customers at the
end of a long transmission line may be subject to a permanent voltage drop due to line
loses on top of the utility voltage variations. Even under ideal conditions, most customers
will see a drop in utility voltage levels to over the course of the day as demand begins to
increase around 8.00am and peaks around 3.00pm to 4.00pm.
1.3 THE STATIC VAR COMPENSATOR
A static VAR compensator is a set of electrical devices for providing fast-acting
reactive power on high-voltage electricity transmission networks.[1][2] SVCs are part of the
Flexible AC transmission system

[3][4]

device family, regulating voltage, power factor,

harmonics and stabilizing the system. Unlike a synchronous condenser which is a


rotating electrical machine, a static VAR compensator has no significant moving parts
(other than internal switchgear). Prior to the invention of the SVC, power factor
compensation was the preserve of large rotating machines such as synchronous
condensers or switched capacitor banks.[5]
The SVC is an automated impedance matching device, designed to bring the system
closer to unity power factor. SVCs are used in two main situations:
Connected to the power system, to regulate the transmission voltage

("Transmission SVC")
Connected near large industrial loads, to improve power quality ("Industrial

SVC")
In transmission applications, the SVC is used to regulate the grid voltage. If the power
system's reactive load is capacitive (leading), the SVC will use thyristor controlled
reactors to consume VARs from the system, lowering the system voltage. Under inductive
(lagging) conditions, the capacitor banks are automatically switched in, thus providing a
7

higher system voltage. By connecting the thyristor-controlled reactor, which is


continuously variable, along with a capacitor bank step, the net result is continuously
variable leading or lagging power.
In industrial applications, SVCs are typically placed near high and rapidly varying loads,
such as arc furnaces, where they can smooth flicker voltage.[1][6]
Static Var Compensators are shunt connected static generators/absorbers whose
outputs are varied so as to control the voltage of the electric power system.
They are applied by utilities in transmission application for the several purposes.
The primary purpose is usually for rapid control of voltage at weak points in a network.
Installations may be at the midpoint of transmission interconnections or at the line ends.
In its simple form, SVC is connected as Thyristor Controlled Reactor Fixed
Capacitor (TCR-FC) configuration values, and capacitors (for harmonic filtering through
tuning).

CHAPTER TWO
2.0 LITERATURE REVIEW
2.1 SYSTEM MODEL
Studies have being performed on a single machine connected to a constant voltage bus
through two transformers Z1 and Z4 and a transmission line divided equally into two
sections Z2 and Z3 as shown in Fig below. An SVC device is connected at the middle bus.
An SVC

device is connected at the middle bus. The SVC is a combination of the reactor
8

and capacitors. It can be controlled quickly by thyristors switching. The SVC acts as
a variable susceptance. The main inputs to the SVC controller are the reference
susceptance and a fuzzy logic controller. The fuzzy logic controller is adapted using the
identified model.

Fig. 2 Test Power System To Analyzing Svc For Transient Stability.


Static Var Compensator (Svc) Description And Modelling: the SVC uses conventional
thyristors to archive fast control of shunt connected capacitors and reactors which
basically consist of Constance capacitors (C) and a thyristor control reactor (L). The delay
angle control of the thyristor bank determines the equivalent shunt admit ant presented
to the power system (Zhang, 2003a, b),
New version of SVC is basically a shunt connected static var generator /load whose
output is adjusted to exchange capacitive or inductive current so as to maintain or
control special power system variables; typically, the controlled variables is the SVC bus
voltage (Stagg and El- Abiad, 2002; saadat, 2002). One of the major reasons for installing
a SVC is to improve Dynamic voltage control and thus increase system load ability. An
additional stabilizing signal, and supplementary control, super impose on the voltage
control loop of a SVC can provide damping of system oscillation as discussed. In this
paper, the SVC is basically represented by a variable reactance with maximum inductive
and capacitive limits to control block and signals to damp oscillation.
The model considers SVC as shunt- connected variable susceptance, Basic which is
adapted automatically to achieve the voltage control. The equivalent susceptance, Beq is
determined by the firing angle of the thyristors that is instant the fundamental
frequency equivalent neglecting harmonics of the current results (Gyugyi, 1988; Carsten,
2002):

As the reactive power demand at the bus varies, the susceptance is varied subject to the
limits. However, the reactive power is a function of the square of the bus voltage. Hence
the reactive power generated decreases as the voltage decreases

CHAPTER THREE
3.0 METHODOLOGY
3.1 MODEL OF SVC WITH PSCAD REPRESENTATION OF ITS CONTROL
In order to investigate the impact of SVC on power systems, appropriate SVC
model is very important. In this section, SVC and its mathematical model will be
introduced. SVC is built up with reactors and capacitors, controlled by thruster valves
which are in parallel with a fixed capacitor bank. It is connected in shunt with the
transmission line through a shunt transformer and thus, represented in figure 1 (1).
Figure 2 shows the equivalent circuit at which svc is modeled.
3.1.1 FUNCTIONAL AND EQUIVALENT CIRCUIT DIAGRAM OF A TYPICAL SVC

Fig.3: Functional diagram of a TCR-FC SVC

10

Fig.4: Equivalent circuit of the SVC

The model considers SVC as shunt-connected variable susceptance, B svc which is


adapted automatically to achieve the voltage control. The equivalent susceptance, B eq is
determined by the firing angle of the thyristors that is defined as the delay angle
measured from the peak of the capacitor voltage to the firing instant. The fundamental
frequency equivalent neglecting harmonics of the current results in (4);
Beq = BL () +BC
Where
BL () = - 1 -2 sin (), BC = C and O0< <
L

If the real power consumed by the SVC is assumed to be zero, them;


PSVC = O
QSVC = - V2BSVC
Where V is the bus voltage magnitude;
As the reactive power demand at the bus varies, the susceptance is varied subject to
the limits. However, the reactive power is a function of the square of the bus voltage.
Hence the reactive power generated decreases as the voltage decreases.
The SVC can both absorb as well as supply reactive power at the bus it is connected
to by control of the firing angle of the thyristor elements. By controlling the firing angle
of the thyristors (i.e. the angle with respect to the zero crossing of the phase voltage), the
11

device is able to control the voltage magnitude. Changes in results in changes on the
current and hence, the amount of reactive power consumed by the inductor. When =
90o, the inductor is fully activated but is deactivated when = 180 o. Actually, the basic
control strategy is typically to keep the transmission bus voltage within certain narrow
limits defined by a controller droop and the firing angle limits (90o < > 180o).

Studied system

Fig 4. A 230kv power system with svc connected at bus 3


Figure 4 shows a 230KV power network to which SVC is connected as bus 3. The
power system comprises a generator generating 16KV which is stepped up by a
transformer to 230KV. This voltage is transmitted via the transmission line to bus 3. The
models of the generator and the SVC as well as the transformer parameters are the IEEE
standard models of PSCAD/EMTDC (5)
3.2 SIMULATION AND RESULTS
The system under study is carried out in PSCAD/EMTDC when the generator is
operating at its rated power level. The voltage at bus 3 having a load of 4MW and 3MVar
is found approximately to be 230KV. But, when the load is increased to 150MW and
30MVar, the voltage dropped to 229.151KV. So, further increase in load resulted in the
corresponding voltage drop at bus 3 as is shown in Table 1.
However, with SVC connected to bus 3, the voltage required (230KV) is maintained
even at the increase of load. It is observed that the voltage magnitude at bus 3 is
12

maintained averagely to 230.65KV during load variation. When SVC is unconnected, the
firing angle is 180o showing that the inductor is deactivated. However, the inductor is
activated when SVC is connected and the firing angle is 116.9o. Hence optimizing the
reactive power and improving the voltage profile (See figure 5-6).
It should be noted here that changes in firing angle result on changes in the current,
and hence the amount of reactive power consumed by the inductor. As the load
increases, the firing angle decreases and hence more amount of reactive power is
consumed by the inductor and vice versa.

13

CHAPTER FOUR
4.0

PRINCIPLE OF OPERATION
Typically, an SVC comprises one or more banks of fixed or switched shunt capacitors or
reactors, of which at least one bank is switched by thyristors. Elements which may be
used to make an SVC typically include:

Thyristor controlled reactor (TCR), where the reactor may be air- or iron-cored

Thyristor switched capacitor (TSC)

Harmonic filter(s)

Mechanically switched capacitors or reactors (switched by a circuit breaker)

4.1 ONE-LINE DIAGRAM OF A TYPICAL STATIC VAR COMPENSATOR

Fig 5. One-line diagram of a typical SVC configuration; here employing a thyristor controlled
reactor, a thyristor switched capacitor, a harmonic filter, a mechanically switched capacitor and a
mechanically switched reactor.
14

By means of phase angle modulation switched by the thyristors, the reactor may be
variably switched into the circuit and so provide a continuously variable MVAR injection
(or absorption) to the electrical network. [2] In this configuration, coarse voltage control is
provided by the capacitors; the thyristor-controlled reactor is to provide smooth control.
Smoother control and more flexibility can be provided with thyristor-controlled capacitor
switching.

Fig.6 Thyristor Controlled Reactor(TCR), shown with Delta connection

Fig.7 Thyristor Switched Capacitor (TSC), shown with Delta connection


The thyristors are electronically controlled. Thyristors, like all semiconductors, generate
heat and deionized water is commonly used to cool them. [5] Chopping reactive load into
15

the circuit in this manner injects undesirable odd-order harmonics and so banks of highpower filters are usually provided to smooth the waveform. Since the filters themselves
are capacitive, they also export MVARs to the power system.
More complex arrangements are practical where precise voltage regulation is required.
Voltage regulation is provided by means of a closed-loop controller.[7] Remote supervisory
control and manual adjustment of the voltage set-point are also common
4.2 ADVANTAGES OF SVCs OVER COMPENSATION SCHEMES
The main advantage of SVCs over simple mechanically switched compensation schemes
is their near-instantaneous response to changes in the system voltage. For this reason
they are often operated at close to their zero-point in order to maximise the reactive
power correction they can rapidly provide when required.
They are, in general, cheaper, higher-capacity, faster and more reliable than dynamic
compensation schemes such as synchronous condensers. [7] However, static VAR
compensators are more expensive than mechanically switched capacitors, so many
system operators use a combination of the two technologies (sometimes in the same
installation), using the static VAR compensator to provide support for fast changes and
the mechanically switched capacitors to provide steady-state VARs.

16

CHAPTER FIVE
5.0 CONCLUSION
In this paper, the basic structure of an SVC operating under typical bus voltage
control and its model are described. The model; is based on representing the controller
as a variable impedance that changes with the firing angle of the Thyristor Controlled
Reactor (TCR), which is used to control voltage in the
System. Simulations carried out confirmed that static Var compensator could provide
the fast acting voltage support necessary to prevent the possibility of voltage reduction
and voltage collapse at the bus to which it is connected.
In this study, the effectiveness of static Var compensator (SVC) has been studied in
improving the transient stability of a sample two-area power system with various and
different studied such as investigation the response of SVC to transient phenomena due
to various faults such as single line to ground-line to line fault, line to line to ground
fault and finally the three phase to ground faults are investigated.

17

REFERENCES
1.

Arrillaga,, J.; Watson, N. R. Power System Harmonics. Wiley. p. 126. ISBN 978-0-47085129-6.

2.

Acha E., Ambriz-Perez H., Fuertes-Esquivel, Advanced Svc Models For NewtonRaphson Load Flow And Newton Optimal Power Flow Studies, IEEE Transactions On

3.
4.

Power Systems, 15(1),P.129-136,2000.


Agelidis V.G. et al., Power Electronic Control in Electrical Systems, Newness, 2002.
Cai L., Robust Co-ordinate Control Of Facts Devices In Large Power Systems A PhD

5.

Thesis, University Of Duisburg, Germany, Published By Logos Verlag Berlin, 2004.


De Kock, Jan; Strauss, Cobus (2004). Practical Power Distribution for Industry.
Elsevier. pp. 7475. ISBN 978-0-7506-6396-0.

6.

Deb, Anjan K. Power Line Ampacity System. CRC Press. pp. 169171. ISBN 978-08493-1306-6.

7.

Hingorani, N.G. & Gyugyi, L. Understanding FACTS - Concepts and Technology of


Flexible AC Transmission Systems. IEEE. ISBN 0-7803-3455-8.

8.

Manitoba H.V.D.C. Research Centre Inc., PSCAD/EMTDC Manual Version 3.0, 244
Cree Crescent, Winnipeg, Manitoba, Canada R3J 3WI.

9.

Padiyar, K. R. (1998). Analysis of Subsynchronous Resonance in Power Systems.


Springer. pp. 169177. ISBN 978-0-7923-8319-2.

10.

Ryan, H.M. (2001). High Voltage Engineering and Testing. IEE. pp. 160161.
ISBN 978-0-85296-775-1

11.

Song, Y.H., Johns, A.T. Flexible ac transmission systems. IEE. ISBN 0-85296-771-3

12

Abido M. 2009. Power System Stability Enhancement Using FACTS Controllers,


The Arabian Journal for Science and Engineering, Volume 34, pp.153-172

13

Banga A. and Kaushik S. S. 2011. Modeling and Simulation of SVC Controller


for Enhancement of Power System Stability, International Journal of Advances in
Engineering and Technology, Vol. 1, pp.79-84

14

Biswas M. M and Kamol K. D. 2011. Voltage Level Improving by Using Static


VAR Compensator, Global Journal of researches in engineering, Volume 11,pp.12-18

15

Conejo A. J., 2011, Load Flow Lecture, University of Castilla La Mancha

16

Nwohu

M.

N.

2009.

Voltage

Stability

Improvement

using

Static

Var

Compensator in Power Systems, Leonardo Journal of Sciences,


18

17

Issue 14, pp. 167-17

19

You might also like