Professional Documents
Culture Documents
System Protection
TECHNICAL SPECIFICATION
FOR
660kV HVDC PROJECT
FROM MATIARI TO LAHORE IN PAKISTAN
VOLUME -1
SYSTEM PROTECTION
Volume -1
System Protection
GENERAL REPORT
SECONDARY SYSTEM
Volume II-1
System Protection
Fig.Volume II-1-1
Fig.Volume II-1-2
Volume II-2
System Communication
Fig.Volume II-2-1
Fig.Volume II-2-2
VOLUME III
Volume III-1
Fig.Volume III-1-1
Fig.Volume III-1-2
Fig.Volume III-1-3
Fig.Volume III-1-4
Fig.Volume III-1-5
Volume III-2
Fig.Volume III-2-1
Fig.Volume III-2-2
Fig.Volume III-2-3
Fig.Volume III-2-4
Fig.Volume III-2-5
VOLUME IV
Fig.Volume IV-1
Fig.Volume IV-2
Tower Outlines
Fig.Volume IV-3
Foundation Outlines
VOLUME V
Volume V-1
Volume V-2
VOLUME VI
System Losses
System Reliability
Volume -1
System Protection
TECHNICAL DEFINITIONS
The following technical definitions apply to this Specification:
Purchaser
Company
HVDC System
HVDC Project
M-L T/L
AC yard
DC yard
Life yard
T area
Transformer area
M-E T/L
M E/G
L-E T/L
L E/G
M C/S
L C/S
M AC busbar
Matiari AC busbar
L AC busbar
Lahore AC busbar
M AC system
Matiari AC system
L AC system
Lahore AC system
Volume -1
System Protection
PI
Pole I
P II
Pole II
Alternating Current
ACI
A/D
Analog to Digital
AN
Audible Noise
ANSI
ASCE
ASTM
BIL
BS
British Standard
BSL
CB
Control Building
CCITT
CT
Current Transformer
CTV
D/A
Digital to Analog
DC
Direct Current
DIN
EEI
EIA
ESCR
ESDD
FAT
HF
High Frequency
HVDC
IEC
Volume -1
System Protection
IEEE
I/O
Input/Output
ISO
LED
MMI
MVU
NFPA
OPGW
P&C
PLC
Power-line Carrier
PT
Potential Transformer
RF
Radio Frequency
RI
Radio Interference
RIV
RTU
RPC
SCADA
SER
SLG
SMC
SPC
SWC
TFR
UPS
VDT
VDU
VF
Voice Frequency
VT
Voltage Transformer
Volume -1
System Protection
VOLUME -1 CONTENTS
1. General ................................................................................................................ 1
1.1
1.2
1.3
2.2
2.3
2.4
3.2
3.3
3.4
Volume -1 -i
1.
General
1.1
Design Basis
Volume -1
System Protection
(1) Program for Feasibility Study on 660kV HVDC PROJECT FROM MATIARI
TO LAHORE IN PAKISTAN
(2) NTDCL Specification P-204:2008
1.2
Project Overview
It is planned to complete the two poles of 660kV HVDC PROJECT FROM
MATIARI TO LAHORE IN PAKISTAN in 2017 which has a bipolar capacity of
4000MW for transmitting power from Matiari converter station to Lahore converter
station.
1.3
Scope of Design
The scope of design for the Project covers the AC system protection (including 500kV
AC transmission line protection, 500kV Busbar protection, 500kV Breaker Failure
protection 500kV shunt reactor protection), dispatch automation, and energy
measurement system for Matiari and Lahore converter station systems.
DC protection and DC/AC filter protection will be considered in the secondary design
of electrical system.
NTDCL Specification P-204:2008 shall be followed for only 500kV AC transmission
line protection, 500kV Busbar protection, 500kV Breaker Failure protection, 500kV
shunt reactor protection. Other AC protection and control (including 500/35kV
step-down transformers protection, 35kV reactor protection , 35kV bus bar protection,
35 kV transformers protection, 10kV transformers protection, fault recorder, etc.) shall
not followed NTDCL Specification P-204:2008.
Volume -1 -1
2.
2.1
Volume -1
System Protection
At present, the 500kV lines in Pakistan power grid are provided with distance
protection and multiplex carrier channels are used to transmit the protection
information. The models of audio interface devices of the multiplex carriers include
ISWT3000, NSD550, and DIP5000.
Recently built 500kV power plants or substations in Pakistan employ computer-based
500kV line protection, bus protection, 500kV circuit breaker protection and fault
recorders.
2.2
2.2.1
(1) R11
Volume -1 -2
Volume -1
System Protection
4.
5.
6.
2.2.2
Four Nos.
One No.
Min 6 Nos. or as approved
scheme.
(1) R15 Breaker failure protection relay panel for three breakers.
The main equipment for relay panels are elucidated below:
Sr. No.
Description.
Quantity.
1.
Breaker failure relay with Three Nos. for 500 KV
circuit breaker.
two stage timers
Three Nos. OR Six Nos. for
2.
Multiple contact high
each bus bar breaker failure
speed, high burden, hand
protection.
and electrical reset
lockout tripping relay
Two OR Four Nos. for mid
3.
Multiple contact high
breaker B.F.
speed, high burden, hand
and electrical lockout
tripping relay
4.
Electrical Reset Relay
One No.
5.
DC supervision relay
One No.
Quantity as required to suit the
6.
Test block.
scheme.
(2) R16 Trip circuit supervision relay panel for three breakers.
The main equipment for relay panels are elucidated below:
Sr. No.
1.
Quantity.
2.
Description.
Trip circuit supervision
relay for each pole
Auxiliary relays
3.
DC supervision relay
Two Nos.
2.2.3
R17
Bus Protection
The main equipment for relay panels are elucidated below: High impedance bus differential OR
Optional low impedance bus differential relay.
Sr. No.
Description.
Quantity.
1.
Bus bar protection for 500 .
One
KV bus 1
2.
Bus bar protection for 500 .
One
KV bus 2
2.2.4
Volume -1 -3
Volume -1
System Protection
Sr. No.
1.
Description.
Percentage biased
differential relay as
specified
Restricted Earth fault relay
Over current and earth
fault relay
Trip circuit supervision
relay for each pole of
circuit breaker.
Breaker failure relay
Multiple contact, high
speed, high burden, hand
and electrical reset lockout
tripping relay having
(8NO+2NC) contacts
Test block.
2.
3.
4.
5.
6.
7.
2.2.5
Quantity.
One No.
One No.
One No.
Six Nos.
One No.
Quantity required as suit
the scheme.
Three Nos.
Fault Recorder
To analyze the accidents of power system and the action of relay protection devices,
fault recorders should be provided in the relay rooms to record the line current and
voltage, action of protection devices, and operation of protection channels. These
information can be uploaded to the dispatch center via the protection and fault
information slave station.
(1) The fault recorders should be computer-based and in conformance to the
applicable industrial standards.
(2) The fault recorders in the substations should be of the same model and be
networked together, and connected to the relay protection and fault recording
information management slave station for uploading the information to the
dispatch department for accident analysis and resolution.
(3) The fault recorders should be equipped with multiple GPS synchronization
interfaces for better analysis on the occurrence time sequence of faults.
(4) The fault recorders should have optimum analysis and local networking
functions.
(5) The fault recorders should have optimum fault distance measurement function.
2.3
Volume -1 -4
2.4
2.4.1
General Requirements
Volume -1
System Protection
(1) The size of AC system protection panel (including 500kV line protection,
500kV Bus bar protection, 500kV Breaker Failure protection, 500kV shunt
reactor protection) shall be 800 x 800 x 2200 mm.
The size of Other protection & control panel (including 500/35kV step-down
transformers protection, 35kV reactor protection , 35kV bus bar
protection, 35 kV transformers protection, 10kV transformers protection,
fault recorder, etc.) shall be 800 x 600 x 2200 mm.
(2) The protection devices shall have the characteristics matching with those of the
connected current transformers and be adaptive to the CVT or bus PT on the
line side.
(3) The logic circuit of each protection device should be powered by independent
DC-DC converter, and when the DC voltage is lost, the protection device should
not act inadvertently and should provide output contact start event records and
alarm signals.
(4) The protection device should not act inadvertently even if any component is
damaged. In addition, automatic detection function should be provided to give
alarm signals when the circuit is abnormal.
2.4.2
Volume -1 -5
Volume -1
System Protection
(5) Each fault recorder should be provided with one display and its own printer to
print the recorded information when needed.
(6) The resolution of the event records should be less than 1.0ms.
(7) The fault recorders should be provided with synchronization device to receive the
GPS synchronization clock pulses. Such device should be able to indicate the
second, minute, hour, date, month, and year.
Volume -1 -6
3.
3.1
Volume -1
System Protection
3.2.1
Telemetering
Current active power, maximum and minimum transmitted power and power
ramp rate per pole;
Current, voltage, active power and reactive power on the AC side of converter
transformer;
Volume -1 -7
3.2.2
3.2.3
Volume -1
System Protection
Telesignaling
Teleregulation/Telecontrol
Volume -1 -8
3.3
(Bipole) pole current/power step up, step down and stop command;
Volume -1
System Protection
3.4
3.4.1
3.4.2
Volume -1 -9
Volume -1
System Protection
Accuracy
0.2s for active, 1.0s for reactive
0.2s for active, 1.0s for reactive
0.2s for active, 1.0s for reactive
Matiari and Lahore Converter Stations are provided with two sets of energy remote
terminals, to which energy meters are connected through serial ports. The energy
remote terminal shall reliably and accurately collect and store the metering data from
all energy meters and transmit to the network control system.
Volume -1 -10