REMKO RKL 290 / RKL 350

Portable Air Conditioner

Operation
Technology
Spare Parts

Edition GB T05

REMKO powerful like a bear.

Operating Instructions
Read these instructions carefully before setting up/operating the unit!!
Our guarantee becomes null and void if the unit is used, set up
or maintained improperly, or if modifications are made to the
supplied unit without our prior consent.
Subject to alterations!

Portable Air Conditioner


REMKO RKL 290 / REMKO RKL 350

Contents

Page

Contents

Page

Safety Instructions

Wiring Diagram

10

Transport and Packaging

Troubleshooting

11

Description of Device

Technical Data

12

Operation

Customer Service and Guarantee

12

Prior to Initial Operation

Environment and Recycling

14

Initial Operation

Exploded View

12

Shutting Down the Unit

Spare Part List

13

Installation of the Wall Lead-through

15

Maintenance and Service

10

Cleaning the Filter

10

Always keep these operating instructions near or on the


unit.

Safety Instructions
Extensive tests have been conducted on the material,
functionality and quality of the REMKO portable air
conditioner to ensure that it is a high-performance unit
with a long service life.
Hazards may nevertheless arise if the unit is used by
persons not familiar with its operation or if the unit is
not used for its intended purpose.
Please make sure to follow these instructions:

Do not place the unit on its side.


Protect all electrical cables from being damaged, for
example, by animals.
Make sure that all extension cables are suitable in
terms of capacity, length and intended use.
Do not lay any lines under carpets.

The unit is not suitable for outdoor operation.

Never operate the unit without the air filter!

Do not set up or operate the unit in rooms susceptible to explosions.

Never aim the air current directly at people!

Ensure that the unit is set up at a safe distance


from flammable materials.
Do not set up or operate the unit if the atmosphere
is contaminated by oil, sulphur or salt.
Do not set the unit up near curtains or drapes.
Minimum distance of 50 cm.
Ensure that the air intake and outlet openings are
always clear of foreign objects.
Ensure that the air conditioner is securely placed
on a level surface.
The unit may only be operated in an upright position.
Do not insert any foreign objects into the air intake
or outlet openings.
Do not place any heavy or warm objects on top of
the unit.
Do not expose the unit to direct streams of water.
Operate the unit only within its permissible operating ranges.
Pay attention to the surrounding temperatures.
This unit may only be connected to a correctly installed, grounded and fused plug socket.
230V / 50Hz, fuse 10A.
When unplugging the unit, do not pull the power
cable too forcefully or bend it too much.
This may result in damage to the cable!
Do not move the unit while in operation. Wait at
least 5 minutes before starting the unit after it has
been moved.
This protects the unit from damage.
Switch the unit off by pressing the Power button.
Do not switch the unit off by unplugging the power
cord.

Do not transport the unit during operation.

Never open the unit housing!


This may cause an electrical shock.
Work on the cooling system and on the electrical
equipment may only be performed by an authorised
service centre.
Operation/handling which does not comply with
these instructions is prohibited!
In cases of non-compliance, we assume no liability
and the guarantee becomes null and void.

Transport and Packaging


All units are subject to continuous quality control and are
carefully packaged before being sent.
The device is shipped in a stable transport box made of
cardboard. Please examine the unit when it is delivered.
Make note of any damage or missing parts on the shipping bill and inform the shipping company and your
contract partner. No liability is assumed for subsequent
claims.
Please observe the following for transport:
Before transporting the unit, switch it off on the control
panel and unplug the power cable.
The unit may only be transported in an upright position.
The unit is equipped with wheels and two handles to
makes transport easier.
Excess condensation is collected in the internal tank
of the unit. We recommend removing this water prior
to transport via the drain at the back of the unit.

Description of Device
The RKL 290-350 air conditioner comes with an infrared remote control and an air outlet hose with a flat
nozzle.
Air directing
plate fins

The unit has been designed for automatic, universal,


smooth air dehumidification. Its compact dimensions
make it easy to transport and set up in all rooms.

Air outlet

The unit meets the basic safety and health requirements found in the relevant EU regulations. It is safe
and easy to operate.

Control panel

Functional principle

IR receiver
Recessed
grip

The portable air conditioner cools the air in the room by


extracting the heat from it. The heat absorbed is expelled to the outside via the exhaust hose and the
cooled air is resupplied to the room where the unit is in
operation via a fan.
Condensation that accumulates drips from the evaporator onto the hot condenser where it condenses and is
then transported via the air outlet hose to the outside.
Excess condensation drips from the condenser into a
collection tray and is resupplied to the condenser by
means of a rotating wheel with blades, where it evaporates and is then expelled with the outgoing air current.

Transport
wheels
Air filter
circulation

Cool circulating air in


the room

Evaporator
Circulation intake
from the room

Air intake
circulation
Air filter exhaust

Fan for circulation

Air outlet hose

Fan for outgoing air

Air outlet exhaust

Compressor

Warm air expelled to the outside


Condenser
Expelled air intake
from the room
Refrigerant
cycle

Condensation drain with


plug

The environmentally-friendly refrigerant, R 407C, transports the absorbed heat within the closed-loop refrigerant cycle.

Cable holder
Air intake exhaust

The units primary function is to air-condition rooms. It


also filters and dehumidifies the air, thus creating a
comfortable climate in the room.
In Fan mode, the unit can also be used to circulate air
with no cooling effect.
The units operates fully-automatically and offers a
range of other options thanks to its microprocessor control. For example, it can be automatically switched off
and on at a preset time via the timer function.
The unit is comfortably operated via the control panel
on the indoor unit or via the infrared remote control that
comes with it.

Operation
Prior to putting the unit into operation, ensure that all
safety instructions have been observed.
Please note that the unit operates most efficiently and
most comfortably when put into operation before the
hottest part of the day, e.g. the morning.
The selected target temperature should be 4 to 7C below the outside temperature. It should never be lower
because the room temperature would feel too cold
when coming from a non-air-conditioned room and people may catch cold.
The selected target temperature does not affect the
performance of the unit! This means that when temperatures in the room are high, it is not practical to adjust the unit to the lowest possible target temperature.

Control Panel
12

14

10

11

13

5 TIMER button

1 I / 0 button
The unit is switched on or off with button 1.
2 MODE button
Button 2 is used to switch between Cooling mode
and Ventilation mode. Each time the button is
pressed, the speed of the fan changes. The LEDs of
display 8 indicate the selected speed.
In Cooling mode, the unit cools the room to a
set value as long as the LED 7 COMP ON is lit
up. The temperature can be set in a range between 18 and 30C. The fan speed can be freely
selected as follows.
Adjusted fan sped:
LED AUTO
Highest fan speed:
LED HI
Medium fan speed :
LED MED
Lowest fan speed:
LED LO
The AUTO setting is used to automatically adjust the fan speed to the desired
cooling capacity. The greater the difference b e
tween the set and current room temperature,
the higher the fan speed.
3 AUTO SWING button
This button is used to set how the air that is discharged from the unit is distributed.
Press button once =continuous swing function
Press button twice =locked swing function
Press button third =continuous swing function
4 / THERMO CONTROL button
This button is used to set the desired target temperature in Cooling mode. If the Up/Down button 4
is pressed, the adjusted target temperature is shown
on the display. The target temperature can be set in
1C increments between 18 and 30C.

This button is used to automatically activate the unit


to switch on and off. When the unit is off, the Timer
On function is programmed in one hour increments
up to 24 hours via the SET button. The LED 10 displays that this function has been activated. When the
unit is on, the Timer Off function is programmed in
one hour increments up to 24 hours via the SET
button. The LED 11 displays that this function has
been activated.
6 RESET button
The programmed timer can be deactivated by pressing the button 6 RESET.
7 COMP. ON button
In cooling mode, the unit operates according to the
programmed target temperature. If the target temperature has been reached, the compressor that creates the cooling capacity switches off. However, the
circulation fan continues to operate. The LED 7
lights up while the compressor is in operation.
8 Cooling mode: AUTO, HI, MED, LO LED
See also point 2.
9 Ventilation mode: FAN LED
In ventilation mode, the air in the room is circulated. The unit does not cool. The fan speed cannot be selected and is automatically set to
MED. The temperature can be changed, however, this does not change the operating mode.
10 TIMING ON LED
This LED indicates whether the timer has been activated to switch the unit on.
11 TIMING OFF LED

Upper button
Lower button

=
=

higher target temperature.


lower target temperature.

This LED indicates whether the timer has been activated to switch the unit off.

12 DRAIN WATER display


This light indicates that the floating switch of the
internal tank has switched off unit operation. The
internal tank does not become full during normal
operation because the exhaust fan transports the
accumulated and evaporated condensation to the
outside via the exhaust hose. In conditions with
very highs levels of humidity, the moisture cannot
be completely expelled and the unit switches off.
To resume unit operation after it has automatically
been switched off due to a malfunction, proceed as
follows:

Infrared Remote Control Functions


All settings can also be made using an infrared remote
control. A description of the button functions can be
found in the Control Panel section. The remote controls range is approx. 5 meters.
Two 1.5 V AAA batteries (included in the scope of the
remote control delivery) power the remote control.

POWER
on / off

THERMO
CONTROL

1. Switch the unit off by pressing the On/Off button and unplug it from the power supply.
2

2. Place a suitable container under the condensation drain of the internal tank.
The condensation drain is located at the bottom
middle at the back of the unit.

MODE

set

TIMER
reset

3. Pull the plug from the condensation drain and


collect the water that drains out.

AUTO
SWING

4. Then replace the plug.


Keep in mind that if there is no plug or it is inserted
incorrectly, water may leak out after the unit has resumed operation.

13 Display
The programmed room temperature is shown on
the display.

1
2
3
4
5

ON/OFF button
MODE button
TIMER button
AUTO SWING button
/ THERMO CONTROL buttons

The current temperature value is increased or decreased by pressing the Up/Down buttons 3 and 4.
If the timer button 5 is pressed, the display switches
to show the remaining hours until the unit is
switched on or off.
If after 5 seconds, no buttons are pushed, the target temperate appears on the display again.
14 Infrared remote control receiver
If the unit is operated using the infrared remote
control, the impulses are received via the receiver.

Infrared Remote Control


Inserting the batteries into the remote control
Prior to initial operation, the batteries supplied with the
unit (2 type AAA batteries) must be inserted into the remote control.
1.
Slide off the cover of the battery slot on the back
of the remote control.
2.
Place the batteries in the slot making sure that
the polarity is correct.
Use the labelling in the slot.
3.
Close the cover.

General Information
The infrared remote control must be protected from
moisture.
When the unit is switched on, each change in the
settings is automatically transferred to the air conditioner. A beep indicates that the data has been properly received.
The transmitter of the infrared remote control must
generally transfer changes to settings in the direction of the air conditioner.
It is only possible for data to be properly transmitted
if there are no objects located between the transmitter and the receiver unit such as doors, drapes,
blinds, etc.
Never use new and old batteries at the same time!
We recommend removing the batteries from the remote control if the unit is taken out of operation for a
longer period of time.
Remove dead batteries and immediately replace
them with new batteries that meet quality standards because otherwise they may leak.

Prior to Initial Operation


The unit is set up in the desired location with the air outlet side facing the room. Follow the safety instructions
when setting up the unit.
There must be a minimum of 20 cm between the
back of the unit and the wall.

5 MIN.

After unpacking the unit, place it on


its transport wheels and let it stand
for a minimum of 5 min. before
switching it on.
Place the unit securely on a level
and firm surface.
An uneven surface can cause vibrations and disruptive noises.
Before plugging in the power cord,
make sure that the required current is
available!
230V / 1~, N, PE / 50 Hz.
If extension cords are necessary,
make absolutely sure that they are
sufficiently thick.
All extensions of the power cords
must be sufficiently thick and may
only be used if they are completely
extended.

Condensation
drain with plug
Exhaust filter
Circulation filter

Make sure that there is a plug for the


condensation drain and that it has
been securely placed.
Water may leak out after the unit becomes operational.
Never operate the unit without the
intake filter.
Without an air intake filter, the plate
fins of the evaporators become dirty
and the units performance is adversely affected.
Make sure that people and objects,
such as plants in the room, are not
directly in the path of the expelled air.

Recommendations for optimum unit operation.


In case of direct sunlight, make sure
to close all curtains and blinds.

Keep doors and windows closed


during operation.

Expelling the warm air


During cooling mode, the unit generates warm air. This
air must be expelled from the room to retain the cooling
effect.
It is therefore necessary to insert the supplied exhaust
hose into the air outlet opening at the back of the unit.
Make sure that the deflector piece
from the top slides down into the
notches on the side until it clicks into
place.
To ensure that the unit operates effectively, do not place the flexible exhaust hose supplied at sharp angles
and make sure there are no kinks.
You may not extend the exhaust hose.
The air expelled from the unit contains a certain
amount of moisture. We therefore recommend expelling the air to the surroundings or the outside.

Different ways of expelling air


You can expel air from the building as follows:

1. With a flat nozzle.


The flat nozzle supplied can be
used in different ways.
It is possible to guide the flat nozzle
through the open window and secure it firmly using straps and suction devices.

The flat nozzle can also be hung


through the partially opened window.

2. With a fixed connection to the exhaust hose (wall lead-through).


The hose supplied is firmly connected to a wall lead-through.
Lead-through kits can be purchased as accessories.
The exhaust hose must always be placed at an incline in the direction the air is flowing!

In some circumstances, low pressure can occur in the


setup room when air is being expelled via a permanently attached exhaust hose, e.g. as a result of closed
windows or doors. If the performance of the unit is adversely affected as a result, make sure that the pressure is
corrected.

Initial Operation
Information about timer mode (timer clock)
Prior to initial operation, the air intake and outlet openings must be inspected for foreign bodies and the air intake filter for dirt. Blocked or dirty grilles and filters must
be cleaned immediately. See the chapter Maintenance
and Service.
Cooling mode
1. Switch the unit on with the I/O button.
2. Select cooling mode with the Mode button.
The AUTO LED must be lit up.
3. Set the target temperature you want with the
THERMO CONTROL buttons.
The selected target temperature appears on the
display.
4. If the set fan speed is too high or too low, the desired fan speed can be set by pressing the MODE
button.
Fan mode (circulation)
1. Switch the unit on with the I/O button

The timer function is reset by pressing the I/O button.


If the SET button is pressed while the timer is activated, the remaining time is shown on the display
and can be changed using the same SET button.
If the timer is programmed, this setting may be lost if
the unit is disconnected from the power supply.

Shutting Down the Unit


To shut down the unit, always switch it off with the
Power button on the control panel or via the remote
control. Only now can you unplug it from the power supply. Never shut the running unit off by pulling the power
plug.

2. Select fan mode with the MODE button. The FAN


LED must be lit up.

Storage

Timer Operation

1. Let the device run for approximately 2 hours in circulation mode (FAN) to dry the surface of the evaporator plate fins.
This removes the remaining moisture from the unit
and prevents unpleasant odours when the device is
put back into operation.

The timer can be preset to switch the unit on or off for a


maximum of 12 hours. Pressing the SET button increases the time until the unit is switched on or off by
one hour.
The number of hours is shown on the display.
Timer switches unit off automatically:
1. W h e n
the
unit
is
on,
press
the
SET button; the OFF LED lights up.
2. Set the desired amount of time until the unit is
switched off with SET button.
Keep in mind that after the setting has been made,
the display changes to show the target temperature.
3. After the set amount of time has elapsed, the unit
switches off automatically.
Timer switches unit on automatically:
The unit switches on with the most recently made settings. If you want different settings, you must switch the
unit on, make the changes and then switch the unit off
again.
1. When the unit is switched off, press the SET button ; the ON LED lights up.
2. Set the desired amount of time until the unit is
switched on with the SET button.
Keep in mind that after the setting is made, the display changes to show the target temperature.
3. After the set amount of time has elapsed, the unit
switches on automatically.

If the unit is to be taken out of operation for a longer period of time, for example, over the winter, proceed as
follows:

2. Switch off the unit by pressing the I/O button, unplug the unit from the power supply and roll up the
power cord.
3. Make sure that the cable is not bent and there are
no kinks.
The cable can be attached to the back of the unit.
4. Place a suitable container under the condensation
drain of the internal tank.
The condensation drain is located at the bottom at
the back of the unit.
5. Pull the plug from the condensation drain and collect
the water that drains out.
6. Then replace the plug.
Keep in mind that if there is no plug or it is inserted
incorrectly, water may leak out after the unit has resumed operation.
7. Store the unit in an upright position in a dry location
that is protected from direct sunlight and dust.
8. To prevent dust from getting inside the unit, protect it
with, for example, a plastic cover.

Maintenance and Service

Cleaning the Filter

Regular maintenance and observance of some basic


principles are required to ensure a long service life and
to keep the unit functioning properly.
However, the unit should be inspected at least once a
year and thoroughly cleaned after long periods of use.
The entire cooling system is a low-maintenance, closedloop system and may only be serviced by authorised
service centres.

The unit is equipped with two air intake filters. These


can be removed from the back of the unit. The filters
must be cleaned at regular intervals. Clean the air filters
after no more than 100 hours of operation. If the air is
heavily contaminated, reduce this time period accordingly.

Before performing any work on the unit, make


sure to switch the unit off and unplug the power
cord.

Cleaning the plastic housing:


For cleaning, use only a clean, soft and slightly moist
towel to carefully wipe the housing.
Please observe the following:
Never use chemical cleaners or polish to clean the
unit.
They can damage the surface.
Only use lukewarm water.
Maximum 40C .
Make sure that no moisture gets into the unit.
This can damage the internal components.
Never clean the unit under a stream of water.
Thoroughly clean the air intake and outlet openings
on a regular basis.
This is where the most dirt accumulates in the shortest period of time.

Wiring Diagram
Legend
PCB1 =
PCB2 =
SM
=
M1
=
M2
=
KM
=
CM
=
OLP
=
CX1
=
CX2
=
CX3
=
TH
=
MS1 =

Control panel
Control board
Swing motor
Circulation fan motor
Exhaust fan motor
Water pump
Compressor motor
Overload protection
Capacitor motor (M1)
Capacitor motor (M2)
Capacitor (compressor motor)
Thermostat sensor
Microswitch (water tank full)

Colour code
Y
=
W
=
R
=
BU
=
BR
=
BK
=
GR
=

Yellow
White
Red
Blue
Brown
Black
Grey

10

Never operate the unit without the air filter. The air
filter prevents the condenser from becoming dirty
and the performance of the unit from being adversely affected.
Filter

1. Switch the unit off with the On/


Off button on the control panel
or the infrared remote control.
2. Unplug the unit.
3. Remove the filter from the unit.
4. Clean the dust that has accumulated from the filter.
You can use a vacuum cleaner.
5. If the dust filter is very dirty,
wash it with a lukewarm soap
solution.
6. Let the filter air dry.
7. Replace the filter in the unit.
8. Make sure that the filter is dry
and undamaged.

Troubleshooting
This unit has been designed using state-of-the-art manufacturing processes and it has been tested repeatedly to
ensure that it is working properly. However, should problems occur, refer to the following list.
Problem

Possible cause

The unit does not start or


Power failure.
switches itself off automatically.
Defective power fuse /
main switch is off.

Check

Remedy

Are all other electrical compo- Check current and wait for the
nents working?
device to start again.
Are all currents for lighting
functional?

Replace power fuse.


Switch on main switch.

Power supply line damaged.

Are all other electrical compo- Maintenance by authorised


nents working?
personnel.

Temperature range is either


too high or too low.

Is the fan still working?

Water tank is full.

Is the Tank Full signal light lit


Empty tank. See page 7.
up?

The surrounding temperature is


Does E1 appear on the disoutside of the operating range
play?
(16 to 35 C).
The unit is either not cooling
at all or only cooling a little The exhaust hose is bent, extended, facing downwards or
bit.
blocked.

Keep the unit within operating


temperature range 20 to 35C.

Do not operate the unit outside of the operating range.

Does the cooling performance


Make sure that the exhaust
improve when the device is
operated without an exhaust
channel is not blocked.
hose and without a filter?

Dirty filter
Input and/or output opening
blocked by foreign matter.

Are the filters dirty?


Does the cooling performance Clean filter and reinsert it into
improve when the device is
the unit.
operated without a filter?

Minimum clearance is insufficient.

Has the minimum distance of


50 cm been maintained?

Windows and doors open /


thermal load increased.

Has something been changed Close windows and doors /


in the design or application?
reduce thermal load.

Maintain minimum distance.

Does the cooling performance


Low pressure in the setup
Correct pressure in the setup
improve when a door or winroom when operating the unit.
room.
dow is opened?
Cooling operating mode not
set.

Is the AUTO, HI, MED or LO Set operation mode to AUTO,


LED lit up in the display?
HI, MED or LO.

Device is switched on with the Is the AUTO, HI, MED, LO or


Press the I / 0 button again.
timer function.
FAN LED lit up?
Temperature setting too high.

Is the temperature setting


higher than the temperature of Lower temperature.
the room?

Excess voltage due to lightning.

Unplug the unit from power


Was there lightning recently in
supply with switch 5 and rethe region?
start.

The unit does not to respond Remote-control batteries are


to the infrared remote con- dead or the transmission distrol.
tance is too far.
Polarity of the batteries is incorrect after replacement.
Condensation water leaks
out of the device.

Replace batteries /
Does the button function work
reduce distance or change loat a distance of approx. 1 m?
cation.
Is the polarity correct?

Insert the batteries correctly.


Pay attention to the labels.

The device is not standing upIs the device upright?


right.

Place upright and make sure it


is firmly in place.

The plug for the condensation


Is water dripping out of the
drain is not inserted correctly
condensation drain?
or is damaged.

Insert the plug correctly or replace if necessary.

Should the unit still not be working despite these checks, please contact an authorised service centre.
Unplug the unit from the power supply before performing any work on it!

11

Technical Data
Type designation
Nominal cooling capacity

RKL290
1)

S-Line

kW

RKL350

S-Line

2.93

Energy efficiency class cooling


Energy efficiency ratio EER

3.45

2.65

2.63

Dehumidification capacity max.

l/h

1.9

2.0

Operational area (size of room), approx.

90

100

C / % r.F.

18 to 35 / 35 to 85

18 to 35 / 35 to 85

R 407 C

R 407 C

kPa

1900 / 2800

1900 / 2800

kg

0.73

0.75

m/h

370 / 410 / 430

380 / 430 / 450

dB(A)

49 / 51 / 52

49 / 51 / 52

V/Ph/Hz

230 / 1~ / 50

230 / 1~ / 50

Protection type

IP

IP 20

IP 20

Nominal power consumption1)

kW

1.12

1.31

5.09

5.98

Operating range indoor unit


Refrigerant
Operating pressure max., refrigeration cycle
Refrigerant, basic quantity
Circulating air volume per speed
Sound pressure level per speed

Power supply

Nominal current consumption

1)

LRA

Operating medium

25
Fresh air, max. 80% relative humidity

mm/mm

1250 / 125

1250 / 125

height

mm

825

825

width

mm

450

450

depth

mm

380

380

kg

35.0

35.0

Exhaust air hose, length / diameter


Dimensions

21
Fresh air, max. 80% relative humidity

Weight
Serial number
Ref. No.
1) Room temperature WB 35C/DB 24C

630...

568...

631...

569...

1615290

1615291

1615350

1615351

2) Distance 1m

Customer Service and


Guarantee
For the guarantee to be valid, the purchaser or his customer must completely fill out the guarantee certificate
enclosed with all units and send it back to REMKO GmbH
& Co. KG.

The units are repeatedly tested at the production site to


ensure that they are working properly. If a malfunction
occurs that cannot be eliminated by the operating personnel, please contact your dealer or contact person.

Environment and Recycling


Important information about recycling!

Only authorised personnel may come into contact with


the cold cycle. This ensures that refrigerant does not
escape into the environment when the unit is being repaired.
Both the refrigerant and the system parts are subject to
special requirements for disposal. The refrigerant in use
is a safety refrigerant. This means that, should damage
occur, the quantities released will not cause injury to the
respiratory systems of people and animals.
Do not touch the liquid refrigerant as it can freeze the
skin!

Proper use
Operation/handling which does not comply with
these instructions is prohibited!
In cases of non-compliance, we assume no liability
and the guarantee becomes null and void.

12

The manufacturer assumes no liability for damage resulting from non-compliance with manufacturer specifications and legal requirements, or if modifications are
made to the units.

Exploded View
8

24

27

26
6

28

29

25
33

11
14

34

13

15

12

16
19
18

30

17
7

20
31

3
2

10

23

22

21

Spare Part List


No. Description

RKL290 S-Line

1
2
3
4
5

Cover, front
Recessed grip

No. Description

Ref. No.
RKL350 S-Line

1107000 1107043 1107000 1107043


1107001 1107044 1107001 1107044
1107002 1107002 1107002 1107002

Control panel cover


Air outlet grille
Plate fins
Adjustable lever
(plate fins)
Cover, rear

Air filter (circulation)

1107007 1107046 1107007 1107046

9
10

Unit bottom
Transport wheel

1107003 1107003 1107003 1107003


1107004 1107004 1107004 1107004
1107005 1107005 1107005 1107005
1107006 1107045 1107006 1107045
1107008 1107008 1107008 1107008
1107009 1107009 1107009 1107009

11

Fan housing (circulation) 1107010 1107010 1107010 1107010

12
13
14
15
16
17
18

Fan wheel (exhaust)


Fan motor (exhaust)
Collection tray
Condenser
Water pump cpl.
Floater (reservoir)
Microswitch 1 (tank)

1107011 1107011 1107011 1107011


1107012 1107012 1107013 1107013
1107014 1107014 1107014 1107014
1107015 1107015 1107015 1107015
1107016 1107016 1107016 1107016
1107017 1107017 1107017 1107017
1107018 1107018 1107018 1107018

When orderig parts please indicate ref. no and machine no. (see type plate).
We reserve the right to make changes to dimensions and design in the interest
of technical progress.

Ref. No.
RKL 290 S-Line

19
20
21
22
23
24
25
26
27
28
29
30
31
32
33

Microswitch 2 (tank)
Evaporator
Compressor cpl.
Control panel foil
Control panel circuit board
Control board
Fan motor (circulation)
Evaporator housing
Fan housing (circulation)
Fan wheel (circulation)
Fin motor
Filter (exhaust)
Power supply with plug
Capacitor compressor
Capacitor fan motor
(circulation)
34 Capacitor fan motor
(exhaust)
Infrared remote control
Exhaust air hose cpl.

RKL 350 S-Line

1107019 1107019 1107019

1107019

1107020 1107020 1107020

1107020

1107021 1107021 1107022

1107022

1107023 1107023 1107023

1107023

1107024 1107024 1107024

1107024

1107025 1107025 1107025

1107025

1107026 1107027 1107026

1107027

1107028 1107028 1107028

1107028

1107029 1107029 1107029

1107029

1107030 1107030 1107030

1107030

1107031 1107031 1107031

1107031

1107032 1107047 1107032

1107047

1107033 1107033 1107033

1107033

1107034 1107034 1107036

1107036

1107037 1107037 1107038

1107038

1107039 1107039 1107040

1107040

1613135 1613135 1613135

1613135

1107042 1107048 1107042

1107048

Accessoires
variable wall lead-through 1613118 1613118 1613118 1613118

13

Installation Diagram of the Wall-Lead Through


Back pressure flap
Safety guard
Sealing cap

Telescope
pipe

min. 400 mm

Installation instructions
1. Create a core hole in the outer wall (maximum wall
thickness 480 mm) with a diameter of at least 135
mm.
Keep an eye out for possible supply lines in this
area!
2. Insert the telescope pipe in the wall lead-through
that you created so that the outer pipe (100 mm diameter) is on the inner side of the wall.
To prevent cold bridges, insulate the telescope pipe
with a suitable insulation material.
3. Place bricks around the telescope pipe in the core
hole so that it is aligned with both sides of the wall.

14

4. Attach the safety guard to the outer side of the wall


with 4 screws.
Mount the safety guard paying attention to the position of the rain drainage.
5. Insert the back pressure flap inside and attach it with
4 screws as well.
The oben label on the back pressure flap must be
visible from inside!
6. Close the opening on the back pressure flap with the
sealing cap when taking the device out of operation,
e.g. before winter, to prevent air circulation.

REMKO GmbH & Co. KG


Air-conditioning and heating
technology
D-32791 Lage Im Seelenkamp 12
D-32777 Lage P.O. Box 1827
Phone +49 5232 606-0
Fax
+49 5232 606-260
E-mail info@remko.de
Internet www.remko.de