7.7 Tapping Ranges and Tapping Methods
7.7.1 The standard tapping ranges, when taps are
7.7.3 For ratings greater than 500 kVA, on load tap
changers may be provided for variation p HV
7.7.2 Off circuit tap-changing arrangement shall be
either by means of links or by means of an
externally-operated switch with mechanical locking
device and a position indicator. Arrangement for padlocking shall be provided.
rovided, shall be as follows:
Winding tapped HV
Number of tap positions 7
+ 5 percent to -10
percent in steps of 2.5
percent for variation
of
Voltage variations
the same phase. The neutral ofthe secondary
winding shall be brought out to a separate insulated
terminal.
Alternatively, [Dyn1, see IS 2026 (Part 1)] can also be
specified. If system and application requirements
of HV voltage
from +5 percent to -15 percent in steps of 2.5 percent.
.
to case, bushing failure, faulty
connection in capacitor unit.
Fuse for externally fused capacitor;
unbalance protection for internally
.
to case, bushing failure, faulty
connection in capacitor unit.
Fuse for externally fused capacitor;
unbalance protection for internally
fast to coordinate with fast unbalance relay settings, but should not operate
ank protection schemes are provided for faults within the capacitor bank
itself. Bank protection may
include items such as a means to disconnect a faulted capacitor unit or capacitor
element(s), a means to ini-
tiate a shutdown of the bank in case of faults that may lead to a catastrophic failure,
and alarms to indicate
unbalance within the bank.