Professional Documents
Culture Documents
Special thanks to the Bonneville Power Adminstration for permitting us to distribute this tool to energy professionals worldwide,
as well as Christopher B. Milan, PE, CEM Mechanical & Civil Engineer, B.P.A. for developing these calculators.
See the complete line of energy saving drives from Cerus by clicking on the photo below:
If you have any questions regarding these tools, please click to email Chris Milan at bpa.gov
This, and other handy calculators can be found at http://www.cerusind.com/calculators.asp
Click here for extensive analysis tools at DOE web site
Page 2 of 14
Revision No. 1
Page 3 of 14
Revision No. 1
104.4
89.6
80.0
75.7
62.8
51.1
40.7
40.0
32.0
25.0
20.0
16.4
20.0
17.0
102.93
100.00
100.0
60.0
120.00
120.0
80.00
79.50
60.00
59.75
43.46
40.00
30.38
20.27
20.00
12.89
5.37
4.75
0.0
0
20
40
60
% of Design CFM
80
100
120
8.00
0.00
0
20
40
60
80
100
120
The power curves above are used in the energy savings analysis. Curves developed from data obtained by measuring the operating characteristics of various fan systems and from
information provided in "Flow Control", a Westinghouse publication, Bulletin B-851, F/86/Rev-CMS 8121. Curves are representative, not precise,
final economic analysis should be based on actual power (kW) measurements of the fan system.
Page 4 of 14
Revision No. 1
hp
%
%
KW
www.cerusind.com
1-800-3543787
Facility Information
Enter Hours per year fan operates:
Enter Energy Charge:
80
0.05
hrs/yr
$/kwh
Duty Cycle
Power Analysis
Savings Analysis
Existing System
Enter
Enter Percent of Design Percent of
Capacity (CFM)
Time at this Existing System
Percent of
Capacity
Design (KW)
0.0%
10.0%
20.0%
30.0%
40.0%
50.0%
60.0%
70.0%
80.0%
90.0%
100.0%
5.0%
5.0%
10.0%
10.0%
10.0%
10.0%
10.0%
10.0%
10.0%
10.0%
10.0%
Totals:
Do Not
Enter Data
Below
ASD System
Percent of
Design (kW)
for ASD
System
Existing System
Power (kW)
20.00
20.64
21.57
23.32
26.44
31.45
38.92
49.36
63.33
81.37
104.01
14.04
14.49
15.14
16.37
18.56
22.08
27.32
34.66
44.47
57.13
73.03
5.90
4.75
5.37
8.00
12.89
20.27
30.38
43.46
59.75
79.50
102.93
2,584.31 Kwh/yrexisting
100.0%
Annual Energy
Savings (Kwh/yr)
4.14
3.33
3.77
5.62
9.05
14.23
21.33
30.51
41.95
55.82
72.27
39.60
44.64
90.99
86.03
76.09
62.84
47.97
33.18
20.13
10.52
6.04
2,066.29 Kwh/yrasd
$
$
$
$
$
$
$
$
$
$
$
1.98
2.23
4.55
4.30
3.80
3.14
2.40
1.66
1.01
0.53
0.30
518.03 $
25.90
Sample Duty Cycles (these can be used as a guide if the duty cycle is not known)
Sample Duty Cycle - HIGH FAN LOADING
Sample Duty Cycle - LOW FAN LOADING
60
70
60
60
50
40
30
20
20
20
10
0
50
75
Percent of Design Capacity
(cfm)
55
50
40
30
20
25
15
10
0
90
5
30
50
70
Percent of Design
Capacity (cfm)
90
Summary
Energy Savings:
Cost Savings:
Enter Materials Cost:
518.03 KWH/yr
25.90
-
$
$
years
This calculator was developed by Chris Milan at the Bonneville Power Administration (BPA) and is intended to be used as an estimation of potential energy savings and simple payback
for ASD installations. Final economic decisions should be based upon more extensive analysis tools than what is provided here.
If you have any questions or comments, please email Chris Milan at the following:
More extensive analysis tools are available at the following DOE web site:
cbmilan@bpa.gov
http://www.eere.energy.gov/industry
Page 5 of 14
Revision No. 1
Applications
Performance Characteristics
Radial-Blade Fans
Axial Fans
The fan blades tilt back, away from the direction of rotation.
The main difference between fans in this category is the
shape and construction of the blades. The Backward-Inclined
Flat blades tend to be more rugged and allow some
particulate to pass through but these blades are not very
aerodynamic and therefore are the least efficient. The
Backward-Inclined Curved blades are more efficient but their
orientation with the air stream can allow moisture and
particulate to collect on the blades which reduces fan
performance and may cause excessive vibrations. The
efficiency ranges from 75 to 85%. The Backward-Inclined
Airfoil blade resembles the wing of an aircraft and is the most
efficient fan type with efficiencies over 90%.
These fans are typically the most rugged of all types and can
range from Paddle-Wheel design to Flat Blades with corrosion
resistance coatings. These fans usually operate at lower
volumes but higher pressures than other fan types. The wide
openings between the blades allow larger material to pass
through and also minimizes vibrations when operating during
conditions when the flow and pressure drops. The
construction of these fans allows them to be modified to meet
specific applications and to be repaired at minimum costs.
Typical ranges of fan efficiencies for Flat Blades is 55 to 65%
and 60 to 75% for the Radial Tip.
The fan performance curve for this group of fans indicates that
they are capable of providing high flow rates at lower
pressures than other fan types. These fans will typically have
a unique BHP curve that requires maximum power at zero flow
rate. The horsepower and static pressure will increase and
decrease as flow increases until finally reaching a minimum
value at maximum flow rate. These variations in flow and
pressure result in different flow rates at the same operating
pressure, causing instability and control problems. Operating
within this region should be avoided.
These fans are the fans of choice for moving material or air in
harsh operating environments. They are used to convey
everything from air filled with particulate to wood chips, rock or
metal scrap
Reference: "Improving Fan System Performance" Industrial Technologies and Best Practices Web Site at: http://www.oit.doe.gov
Page 6 of 14
Revision No. 1
120.0
80.0
100.0
104.0
100.0
99.8
81.4
63.3
60.0
49.4
40.0
38.9
31.5
26.4
20.0
20.0
21.6
20.6
23.3
0.0
0
20
40
60
80
% of Design CFM
100
120
% o f D e s i g n In pu t Po w e r (k W )
84.6
80.0
73.8
66.7
60.0
52.6
55.8
57.4
58.5
59.9
62.3
47.3
40.0
20.0
120.0
0.0
106.7
100.0
20
40
60
% of Design CFM
80
100
120
91.9
80.0
81.2
73.9
60.0
56.1
59.8
62.2
64.0
66.0
69.1
50.3
40.0
20.0
0.0
20
40
60
80
100
120
% of Design CFM
Page 7 of 14
Revision No. 1
120.0
105.9
105.2
100.0
102.1
100.0
96.3
80.0
90.0
90.6
76.9
64.6
60.0
53.8
44.5
40.0
36.7
30.4
88.7
80.0
80.2
71.5
70.0
63.6
60.0
57.2
53.3
52.6
50.0
40.0
30.0
25.6
20.4
20.0
22.3
20.0
10.0
0.0
0.0
0
20
40
60
% of Design CFM
80
100
120
20
40
60
% of Design CFM
80
100
120
The power curves above are used in the energy savings analysis. Curves developed from data obtained by measuring the operating characteristics of
various fan systems and from information provided in "Flow Control", a Westinghouse publication, Bulletin B-851, F/86/Rev-CMS 8121. Curves are
representative, not precise, final economic analysis should be based on actual power(kW) measurements of the fan system.
Page 8 of 14
Revision No. 1
50.00
95.00
90.00
35.34
8760
0.05
hp
%
%
KW
hrs/yr
$/kwh
Duty Cycle
Power Analysis
Savings Analysis
Existing System
Enter
Percent of
Design
Capacity
(CFM)
Enter Percent
of Time at
this Capacity
25.0%
50.0%
70.0%
90.0%
15.0%
55.0%
25.0%
5.0%
Totals:
7 Measured kW
Existing
System
Percent of
Design (KW)
54.90
71.53
88.71
102.08
ASD System
Annual Energy Cost
Savings ($/yr)
6.42
20.27
43.46
79.50
231,719.64 Kwh/yrexisting
100.0%
Annual Energy
Savings (Kwh/Yr)
Percent of
Design (KW)
for ASD
System
Do Not
Existing
Enter Data System Power
Below
(KW)
19.40
25.28
31.35
36.07
2.27
7.16
15.36
28.09
22,511.26
87,270.91
35,022.55
3,494.89
0.00
0.00
0.00
0.00
0.00
0.00
0.00
83,420.05 Kwh/yrasd
$
$
$
$
1,125.56
4,363.55
1,751.13
174.74
148,299.60 $
7,414.98
Sample Duty Cycles (use these as a guide if the duty cycle is not known)
Sample Duty Cycle - HIGH FAN LOADING
Sample Duty Cycle - LOW FAN LOADING
70
60
50
40
30
20
20
10
60
20
55
60
50
40
30
20
25
15
10
0
50
75
Percent of Design Capacity
(cfm)
30
90
50
Percent of Design
Capacity (cfm)70
90
Summary
Energy Savings: (Note 1)
Cost Savings:
Enter Materials Cost:
$
$
148,299.60 KWH/yr
7,414.98
950.00
$
$
100,000.00
100,950.00
13.61 years
This calculator was developed by Chris Milan at the Bonneville Power Administration (BPA) and is intended to be used as an indication of the potential energy savings
and simple payback for ASD installations. If you have any questions or suggestions for improvements, please contact Chris Milan at cbmilan@bpa.gov. More extensive
analysis tools are available at: http://www.eere.energy.gov/industry.
Page 9 of 14
[Revision No. 1]
Outlet
Dampers
Adjustable
Speed-Drives
Inlet Guide Vanes are installed across the opening of the fan inlet. By opening and
closing, they vary the amount of air entering the fan and change the profile of the
entering airstream. As the air passes through the vanes it begins to swirl in the
same rotation as the fan impeller, this pre-spinning of the air reduces the momentum
that the fan blades can impact on the entering air and therefore reduces the velocity
and pressure of the discharged air. As the vanes continue to close, this swirling
action increases and continues to decrease the pressure and flow the fan delivers to
the system. The fan horsepower is proportional to the flow and pressure, therefore
the horsepower requirement also decreases. Because the inlet vane opening
affects all three of these fan characteristics, a new fan performance curve is created
whenever the vane position is changed. Inlet control does not affect the system
curve, as vane positions change the fan performance curve rides up and down the
system curve.
Outlet dampers do not change the characteristics of the entering airstream. Outlet
dampers control flowrate by restricting the amount of air being discharged. This
restriction allows the air flow rate to be varied the same way a discharge throttle
valve adjusts the volume of flow out of a pump. The resistance of flow through the
system increases as the flow(cfm) of air increases. This relationship is shown
graphically by plotting the flow and corresponding resistance(pressure) to generate
the system resistance curve. When the system curve and fan performance curve are
shown on the same graph, the intersection of these two curves defines a unique
point of operation. When the fan is installed in this particular system and operates at
this flow rate, it will produce this pressure. The fan can only operate as shown by it's
performance curve, for a given pressure it will provide a unique flow or vice versa.
Inlet dampers can be oriented to provide the same affect as inlet guide vanes but
usually are not as effective at inducing the appropriate swirl. The blades typically
operate in parallel with each other. If the inlet dampers are installed too far from the
fan inlet or are not oriented properly, they only serve to restrict the entering airflow.
With outlet damper control, any new operating point is achieved by adjusting the
characteristics of the system curve, not the fan performance curve. For example, in
order to reduce the fan flow rate, as the outlet dampers begin to close, the system's
resistance(pressure) increases and shifts the system curve upward until it intersects
the fan performance curve to define a new operating point of increased pressure
and reduced flow.
Inlet Dampers are usually a better choice of flow control than Outlet Dampers
because when properly installed, they allow the fan horsepower to be reduced as
the flow is reduced. Inlet Guide Vanes usually provide more accurate control of fan
performance than Inlet Dampers. Inlet Guide Vanes are an efficient method for
controlling flow rates down to approximately 70% of capacity. This would
correspond to a vane position of approximately 50% closed. If the desired fan flow
rate requires that the vanes be closed more than 50%, adjustable speed drives
usually provide more efficient controllability by reducing the fan speed rather than
continuing to restrict the fan inlet with the guide vanes.
Dampers are an efficient method of fully open/closed flow control such as exhaust
air or outside air intakes. Outlet dampers are the least efficient method of variable
flow control. In order for the fan to compensate for this increase in system pressure
when the dampers begin to close, it has to move to the left up along the
performance curve to the higher operating pressure. For the majority of fans, as you
continue to restrict flow and increase pressure, the fan operates in the least efficient
and unstable region of the fan performance curve. Operating at higher system
pressures than necessary to reduce the flow rate not only wastes energy but
increases the air leakage throughout the system. Depending upon the variation in
flow rates required by the system, inlet guide vanes or adjustable speed drives may
provide more energy efficient flow control.
ASDs are an excellent choice of flow control if the system allows the fan or pump to
operate at reduced flow rates and loads for a significant portion of the operating time.
The ASDs provide quick and accurate adjustments to flow rate and pressure as
required to maintain set point. Another advantage of ASD control is their soft starting
capabilities which reduces the high in-rush currents at start-up. Operating at reduced
speeds can increase the equipment life, reduce vibrations and noise. For fan
applications were the flow rate does not vary significantly, inlet guide vanes may be a
better choice of control. ASDs are not 100% efficient, therefore operating the motor at
full speed with the ASD will increase the input power due to the inefficiency of the
drive. ASDs typically require that they be placed in a clean, conditioned environment
which could result in high installation costs.
Advantages/
Disadvantages
Operating
Characteristics
Reference: "Improving Fan System Performance" Industrial Technologies and Best Practices Web Site at: http://www.oit.doe.gov
Page 10 of 14
Revision No. 1
120.00
104.45
100.00
120.00
89.64
80.00
75.69
62.77
60.00
51.06
40.00
40.75
32.01
25.03
20.00
16.40
17.04
19.98
0.00
102.79
100.00
80.00
79.40
60.00
59.53
43.19
40.00
30.37
20.00
21.07
14.32
15.30
13.05
0.00
0
20
40
60
80
100
120
10
20
30
40
50
60
70
80
90
100
110
120
104.88
100
96.29
86.46
80
75.81
64.76
60
53.72
43.12
40
33.38
24.92
20
13.51
18.16
0
0
Page 11 of 14
20
40
60
% of Design Flow (gpm)
80
100
120
Revision No. 1
100.00
95.00
55.00
43.19
hp
%
%
KW
www.cerusind.com
1-800-3543787
Facility Information
Enter Hours per year pump operates:
Enter Energy Charge:
4000
0.05
hrs/yr
$/kwh
Existing Pump Flow Control Method
1 Throttling Valve
2 Eddy Current Clutch
3 Mechanical (Torque Converter)
Duty Cycle
Power Analysis
Savings Analy
Existing System
Enter Percent
Enter
of Design
Percent of
Capacity
Time at this
(GPM)
Capacity
5.0%
5.0%
10.0%
10.0%
10.0%
10.0%
10.0%
10.0%
10.0%
10.0%
10.0%
Totals:
100.0%
0.0%
10.0%
20.0%
30.0%
40.0%
50.0%
60.0%
70.0%
80.0%
90.0%
100.0%
Existing
System
Percent of
Design (KW)
Do Not
Enter Data
Below
ASD System
Existing
System Power
(kW)
55.21
61.39
67.19
72.61
77.65
82.31
86.59
90.49
94.01
97.15
99.91
Percent of
Design (kW)
for ASD
System
27.45
19.12
14.32
13.05
15.30
21.07
30.37
43.19
59.53
79.40
102.79
11.85
8.26
6.19
5.64
6.61
9.10
13.12
18.65
25.71
34.29
44.40
23.85
26.52
29.02
31.36
33.54
35.55
37.40
39.08
40.60
41.96
43.15
142,738.45 Kwh/yr
69,503.14 Kwh/yr
existing
Annual Energy
Savings (Kwh/yr)
2,398.30
3,651.08
9,133.28
10,289.94
10,772.16
10,579.93
9,713.26
8,172.14
5,956.57
3,066.55
-497.91
73,235.31
asd
Sample Duty Cycles (these can be used as a guide if the duty cycle is not known)
Sample Duty Cycle - HIGH PUMP LOADING
70
60
60
50
60
55
50
40
40
30
25
30
20
20
20
20
15
10
10
0
0
50
75
Percent of Design Capacity
(gpm)
90
30
Percent 50
of Design Capacity (gpm)
70
Summary
Energy Savings:
Cost Savings:
Materials Cost:
$
$
73,235.31 KWH/yr
3,661.77
-
Labor Cost:
Total Cost:
Simple Payback:
$
$
This calculator was developed by Chris Milan at the Bonneville Power Administration (BPA) and is intended to be used as an estimation of potential energy s
simple payback for ASD installations. Final economic decisions should be based upon more extensive analysis tools than what is provided here.
If you have any questions or comments, please email Chris Milan at the following:
cbmilan@bpa.gov
Page 12 of 14
Revision No. 1
ity Information
Savings Analysis
119.92
182.55
456.66
514.50
538.61
529.00
485.66
408.61
297.83
153.33
-24.90
$
3,661.77
60
55
50
40
30
25
20
15
10
5
0
30
Percent 50
of Design Capacity (gpm)
70
90
Summary
years
tion (BPA) and is intended to be used as an estimation of potential energy savings and
upon more extensive analysis tools than what is provided here.
cbmilan@bpa.gov
Page 13 of 14
Revision No. 1
% of Design (kW)
105
100
125.00
100.00
97.15
94.01
99.91
90.49
86.59
% of Design (kW)
82.31
77.65
75.00
95
72.61
67.19
90
50.00
85
25.00
80
10
20
30
40
50
60
70
80
90
100
110
0.00
10
20
30
40
50
60
70
80
90
100
110
The power curves above are used in the energy savings analysis. Curves developed from data obtained by measuring the operating
characteristics of various pumps and from information provided in "Flow Control", a Westinghouse publication, Bulliten B-851, F/86/RevCMS 8121. Curves are representative, not precise, final economic analysis should be based on actual power (kW) measurements of the
pumping system.
Page 14 of 14
Revision No. 1