1 (8)
0-003-2237-0 (EN)
APPLICATION EXAMPLE
Carbon Wall
Occupancy
dioxide Module Sensor
Sensor
Two Electrical
Reheat Stages,
Relays
and Damper
Fan
Figure 1
FUNCTIONS
The TAC Xenta 102-AX VAV controller
is a component of a single path VAV air
delivery system (Figure 1).
The controller has an integrated static
air velocity transducer and a motorized
bidirectional actuator. Other features:
CO2 monitoring;
reheat control;
damper control;
heating/cooling changeover;
occupancy/light control.
3-stage heating
Pulse Width Modulation (up to 999 s)
Increase/decrease (floating)
nvoSetPtOffset
nvoStatOccBtn
nvoUnvInput4
UnivIn4 Sense 1
nvoAuxTemp2
nvoCO2sensor
nvoUnvInput3
UnivIn3 Sense 1
nvoLocalOccLatch
nvoUnvInput2
UnivIn2 Sense 1
VAV Controller 1
nvoAuxTemp1
nvoEmergCmd
nvoUnvInput1
nviRelStPt
nviActuatorState
nviUnvOutput1
UnivOut1 Object 1
nviUnvOutput2
UnivOut2 Object 1
nviUnvOutput3
UnivOut3 Object 1
nvoActualValue
UnivIn1 Sense 1
Damper Actuator 1
nvoAirFlow
nvoAirPressure
Airflow sense
Air flow calibration and essential configuration can be made directly from the
wall module (I/STAT) and the hand-held
M/STAT.
Plug-In
When the controller is connected to a
LonMaker LNS 3 network, a software
Plug-In is provided to simplify the
setting and monitoring of the controller
functions, for example the Network
Variables and the Configuration
Parameters.
0-003-2237-0 (EN)
nviStPointOffset
nvoBoxFlow
nviOccCmd
nvoEffectSetPt
nviAirFlowReset
nvoFanLoad
nviApplicMode
nvoFlowControlPt
nviBoxFlow
nvoHeat1Load
nviOutsideTemp
nvoHeat2Load
nviCO2
nvoHighSpaceTemp
nviOccLocalLatch
nvoLowStaticPres
nviDuctInTemp
nvoOAirFlowRatio
nviEmergCmd
nvoOccpncyStatus
nviEnergyHoldOff
nvoSpaceTemp
nviManOverride
nvoTerminalLoad
nviRemoteOccBtn
nvoUnitStatus
nviSetPoint
nvoMotorPositn
nviSpaceTemp X/STAT
2 (8)
Figure 2
Warmup
Max. Flow
Cooling
Max. Flow
Air Flow
Heating Min. Flow
+100%
Standby mode
The standby mode is to raise the active
cooling setpoint/lower the heating setpoint when the zone is temporarily
unoccupied.
Bypass mode
When the TAC Xenta VAV controller is
in unoccupied scheduled times of the
day or week, a push-button Bypass, or
manual override from the local wall
module (for example I/STAT or S/STAT)
can activate the Bypass mode to the
occupied setpoints for an adjustable
override period.
If the button is pressed again before the
defined override period expires, the unit
will return operation to unoccupied
setpoints unless the local hardware
input or the network input are calling for
occupancy.
Unoccupied mode
Unoccupied is to prevent the zone from
overheating/overcooling after-hours.
Morning Warmup
Adjusting the temperature, before a set
time, so that the correct comfort temperature is reached as required.
Night Purge
Using cool night air to ventilate the
building in Unoccupied mode.
Emergency pressurization/depressurization
Optional pressurization control supporting smoke control systems for the entire
area served.
Heat Stages: 5 4 3 2 1
1 Warmup
0%
2 Fan
3 Heat 1
-50%
4 Heat 2
5 Heat 3
-100% Heating
Band
+50%
Terminal Load
0%
Cooling
Band
Offset
Cooling
Setpoint
Offset
Heating
Setpoint
Figure 3
Air flow
100%
max.
min.
0%
low limit
high limit
CO2 level
(ppm)
Figure 4
Pre-cooling
Lowering the temperature during the
night to anticipate and lessen the cooling
demand during the day.
Accessories
G and G0:
Min. cross-sectional area 0,75 and
1,5 mm (AWG 18 and 14).
I/STAT
C1 and C2:
TP/FT-10 allows the user to wire the
control devices with virtually no
topology restrictions.
The max. wire distance in one
segment depends on the type of wire
and the topology.
M/STAT
TTS100WJ
0-003-2237-0 (EN)
OPERATING
MODES (CONTD.)
LONMARK OBJECTS
AND NETWORK VARIABLES
VAV Controller
Object Type: # 8010
mode
00 HVAC_AUTO
01 HVAC_HEAT
02 HVAC_MRNG_WRMUP
03 HVAC_COOL
04 HVAC_NIGHT_PURGE
06 HVAC_OFF
nv1
nviSpaceTemp
SNVT_temp_p
nv3
nvoSpaceTemp
SNVT_temp_p
nv2
nviSetPoint
SNVT_temp_p
nv4
nvoUnitStatus
SNVT_hvac_status
06 HVAC_OFF
09 HVAC_FAN_ONLY
FF HVAC_NUL
00 OC_OCCUPIED
01 OC_UNOCCUPIED
02 OC_BYPASS
03 OC_STANDBY
FF OC_NUL
00 EMERG_NORMAL
01 EMERG_PRESSURIZE
02 EMERG_DEPRESSURIZE
03 EMERG_PURGE
04 EMERG_SHUTDOWN
FF EMERG_NUL
09 HVAC_FAN_ONLY
FF HVAC_NUL
nv5
nviApplicMode
SNVT_hvac_mode
nv16
nvoEffectSetPt
SNVT_temp_p
nv6
nviManOverride
SNVT_hvac_overid
nv17
nvoFlowControlPt
SNVT_flow
nv7
nviStPointOffset
SNVT_temp_p
nv18
nvoBoxFlow
SNVT_flow
nv8
nviOccCmd
SNVT_occupancy
nv19
nvoTerminalLoad
SNVT_lev_percent
nv9
nviEmergCmd
SNVT_hvac_emerg
nv10
nviBoxFlow
SNVT_flow
nv11
nviEnergyHoldOff
SNVT_switch
nv13
nviCO2
SNVT_ppm
nv15
nviDuctInTemp
SNVT_temp_p
Configuration Properties
nciMinDelTempSnd
nciSpacTempHiLim
nciSpacTempHiHys
nciSpacTempLoLim
nciSpacTempLoHys
nciOvrBehavSpTem
nciOvrDefltSpTem
nciOvrValueSpTem
nciSetPnts
nciSetpntOffRnge
nciMaxFlow
nciMinFlow
nciMaxFlowWarmup
nciMinFlowWarmup
nciMinFlowHeat
nciMinFlowStand
nciUnoccuAirFlow
nciAirFlowFanOff
nciAirFlowFanOn
nciSetPnts.occupied_cool
.standby_cool
.unoccupied_cool
.occupied_heat
.standby_heat
.unoccupied_heat
nciOveridDuratn
nciCoolingBand
nciHeatingBand
nciCO2HiLimitCIn
nciCO2LoLimitCIn
nciCO2ThrshldCIn
nciCO2ThrshldOff
nciCO2ThrshldOn
nciOccupiedOA
nciUnoccupiedOA
nciFanTypeVAV
nciFanEnaWarmup
nciResponseRate
nciVAVSelctnCntl
nciHeatEnaWarmup
nciLoStaPriority
nciDelayReprtLoS
nciHiTempPriority
nciDelayReprtHiT
nciHomeLEDTmOut
nciSrvcModeTmOut
nciPasswordVaule
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_override
SNVT_temp_p
SNVT_temp_p
SNVT_temp_setpt
SNVT_temp_p
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
heat_output_primary Heat1Load
heat_output_secondryHeat2Load
cool_output
CoolLoad
econ_output
VavLoad
fan_output
FanLoad
in_alarm
SNVT_elapsed_tm
SNVT_temp_p
SNVT_temp_p
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_flow
SNVT_flow
UNVT_fan_type
UNVT_no_yes
UNVT_response_rt
UNVT_vav_selectn
UNVT_no_yes
SNVT_count
SNVT_time_sec
SNVT_count
SNVT_time_sec
SNVT_time_sec
SNVT_time_sec
UNVT_password
nviRemoteOccBtn
SNVT_switch
nv25
nvoOccpncyStatus
SNVT_occupancy
nv22
nviOutsideTemp
SNVT_temp_p
vn26
nvoMotorPosition
SNVT_lev_percent
nv23
nviOccLocalLatch
SNVT_occupancy
vn27
nvoFanLoad
SNVT_lev_percent
nv24
nviAirFlowReset
SNVT_lev_percent
nv28
nvoHeat1Load
SNVT_lev_percent
nv29
nvoHeat2Load
SNVT_lev_percent
nv30
nvoOAirflowRatio
SNVT_lev_percent
nv31
nvoLowStaticPress
SNVT_count
nv32
nvoHighSpaceTemp
SNVT_count
Hardware Input/Output
M/STAT, I/STAT
Figure 5
Damper Actuator
Object Type: # 8110
Mandatory Network Variables
nv1
nviRelStpt
SNVT_lev_percent
nv2
nviActuatorState
SNVT_switch
nv3
nvoActualValue
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
SNVT_time_sec
SNVT_time_sec
UNVT_output_type
SNVT_state
SNVT_time_sec
SNVT_time_sec
Hardware Output
Motor_desired_position
Motor_position
4 (8)
Figure 6
nvoUnvInput1
SNVT_lev_percent
nv1
nvoUnvInput2
SNVT_lev_percent
nv1
Configuration Properties
nciMaxRngeUI1
nciMinRngeUI1
nciDeltaSndUI1
nciGainUI1
nciOffsetUI1
nciOvrBehavUI1
nciOvrDefltUI1
nciOvrValueUI1
nciUniIn1Selctn
nciEmContctDebTm
nciOvrDefltEmCon
nciOvrValueEmCon
nciDelTemSndAux1
nciOffsetTemAux1
nciOvrDefltTAux1
nciOvrValueTAux1
Configuration Properties
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_muldiv
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
UNVT_select_UI
SNVT_elapsed_tm
SNVT_hvac_emerg
SNVT_hvac_emerg
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
nciMaxRngeUI2
nciMinRngeUI2
nciDeltaSndUI2
nciGainUI2
nciOffsetUI2
nciOvrBehavUI2
nciOvrDefltUI2
nciOvrValueUI2
nciUniIn2Selctn
nciOccLatchDebTm
nciOccLatchPeriod
nciOcLatchNormOp
nciOvrDefltOccLt
nciOvrValueOccLt
nvoEmergCmd
SNVT_hvac_emerg
nv3
nvoAuxTemp1
SNVT_temp_p
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_muldiv
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
UNVT_select_UI
SNVT_elapsed_tm
SNVT_elapsed_tm
SNVT_occupancy
SNVT_occupancy
SNVT_occupancy
nvoLocalOccLatch
SNVT_occupancy
nv2
Hardware Input
Hardware Input
Analog_value[]
Analog_value[]
nv1
Configuration Properties
Configuration Properties
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_muldiv
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
UNVY_select_UI
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
nciMaxRngeUI4
nciMinRngeUI4
nciDeltaSndUI4
nciGainUI4
nciOffsetUI4
nciOvrBehavUI4
nciOvrDefltUI4
nciOvrValueUI4
nciUniIn4Selctn
nciSStatBtnDebTm
nciOvrDefltOccBt
nciOvrValueOccBt
nciOvrDefltSPOfs
nciOvrValueSPOfs
nv3
nv2
nvoCO2sensor
SNVT_ppm
nv3
nvoAuxTemp2
SNVT_temp_p
nvoSetPtOffset
SNVT_temp_p
nvoStatOccBtn
SNVT_switch
Hardware Input
Hardware Input
Analog_value[]
Analog_value[]
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_muldiv
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
UNVT_select_UI
SNVT_elapsed_tm
SNVT_switch
SNVT_switch
SNVT_temp_p
SNVT_temp_p
nvoUnvInput4
SNVT_lev_percent
nv1
nciMaxRngeUI3
nciMinRngeUI3
nciDeltaSndUI3
nciGainUI3
nciOffsetUI3
nciOvrBehavUI3
nciOvrDefltUI3
nciOvrValueUI3
nciUniIn3Selctn
nciDelCO2SndUI3
nciOffsetCO2UI3
nciOvrDefltCO2
nciOvrValueCO2
nciDelTemSndAux2
nciOffsetTemAux2
nciOvrDefltTAux2
nciOvrValueTAux2
Figure 8
Figure 7
Figure 9
5 (8)
Figure 10
0-003-2237-0 (EN)
AirFlow_Input_Object
Object Type # 1
nv1
nvoAirFlow
SNVT_flow
nv2
nvoAirPressure
SNVT_press_p
nv1
nviUnvOutput1
SNVT_lev_percent
Configuration Properties
nciMaxRngeUO1
nciMinRngeUO1
nciOvrBehavUO1
nciOvrDefltUO1
nciOvrValueUO1
nciDelayStartUO1
nciDelayStopUO1
nciOutputTypUO1
nciDirectionUO1
nciInvertUO1
nciMinPulseUO1
nciDriveTimeUO1
Configuration Properties
nciDuctArea
nciPickupFactor
nciBoxConstant
nciLoBoxVelPress
nciAirFlowCoeff
nciMinDelFloSnd1
nciOvrBehavFlow1
nciOvrDefltFlow1
nciOvrValueFlow1
nciCalHiPress1
nciCalLoPress1
nciCalHiCount1
nciCalLoCount1
nciGainPress1
OffsetPress1
FactAirfloCal
SNVT_area
UNVT_pickup_fact
UNVT_box_const
SNVT_press_p
SNVT_lev_percent
SNVT_flow
SNVT_override
SNVT_flow
SNVT_flow
SNVT_press_p
SNVT_press_p
SNVT_count
SNVT_count
SNVT_muldiv
UNVT_press_10th
UNVT_airflow_cal
Optional Network
Variables
Configuration
Properties
Hardware Input
Hardware Output
air_pressure
Flow
Off_Time_UO1
On_Time_UO1
Output_pin_1
Configuration Properties
SNVT_lev_percent
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
SNVT_time_sec
SNVT_time_sec
UNVT_output_type
SNVT_state
UNVT_invert
SNVT_time_sec
SNVT_time_sec
nciMaxRngeUO3
SNVT_lev_percent
SNVT_lev_percent
nciMinRngeUO3
SNVT_override
nciOvrBehavUO3
SNVT_lev_percent
nciOvrDefltUO3
SNVT_lev_percent
nciOvrValueUO3
SNVT_time_sec
nciDelayStartUO3
SNVT_time_sec
nciDelayStopUO3
UNVT_output_type
nciOutputTypUO3
SNVT_state
nciDirectionUO3
UNVT_invert
nciInvertUO3
Optional Network
Variables
SNVT_time_sec
nciMinPulseUO2
Configuration
Properties
SNVT_time_sec
nciDriveTimeUO3
Optional Network
Variables
Configuration
Properties
Manufacturer Network Variables
Hardware Output
0-003-2237-0 (EN)
nviUnvOutput3
SNVT_lev_percent
Configuration Properties
Figure 12
Off_Time_UO2
On_Time_UO2
Output_pin_2
if DO
nviUnvOutput2
SNVT_lev_percent
nciMaxRngeUO2
nciMinRngeUO2
nciOvrBehavUO2
nciOvrDefltUO2
nciOvrValueUO2
nciDelayStartUO2
nciDelayStopUO2
nciOutputTypeUO2
nciDirectionUO2
nciInvertUO2
nciMinPulseUO2
nciDriveTimeUO2
if PWM
Figure 11
nv1
SNVT_lev_percent
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
SNVT_time_sec
SNVT_time_sec
UNVT_output_type
SNVT_state
UNVT_invert
SNVT_time_sec
SNVT_time_sec
Hardware Output
if PWM
Off_Time_UO3
On_Time_UO3
Output_pin_3
if DO
Figure 13
6 (8)
if PWM
if DO
Figure 14
Node Object
Object Type: # 0
Mandatory Network Variables
nv1
nviRequest
SNVT_obj_request
nv2
nvoStatus
SNVT_obj_status
nviTimeSet
SNVT_time_stamp
nv4
nv8
nvoAlarm
SNVT_alarm
nvoFileDirectory
SNVT_address
Configuration Properties
nciProgramVersion
nciApplicVersion
nciLocation
JobNumber
nciOEMtype
nciNetworkConfig
nciMinSendTime
nciRcvHrtBt
nciSndHrtBt
nciAssignedAddr
UNVT_progm_versn
UNVT_aplic_versn
SNVT_str_asc
SNVT_str_asc
SNVT_str_asc
SNVT_config_src
SNVT_time_sec
SNVT_time_sec
SNVT_time_sec
SNVT_count
nviRawHwOutValus
UNVT_rawHwOut
nv10
nvoRawHwValues
UNVT_rawHwValues
Hardware Input/Output
All Inputs and Outputs
Figure 15
7 (8)
0-003-2237-0 (EN)
HARDWARE INTERFACE
TB
Term.
no.
Label
no.
Designation
Description
1
2
12
13
G
G0
1
2
3
14
15
16
V1
V2
V3
1
2
10
11
C1
C2
1
2
3
7
8
9
STAT-DATA
STAT-PWR
STAT-GND
1
2
3
4
1
2
3
4
U1
U2
U3
U4
5
6
5
6
Not used
Measurement neutral
DIMENSIONS
mm (in.):
197
(7.75)
63
(2.50)
159
(6.25)
Figure 16
Trademarks and registered trademarks are the property of their respective owners.
TAC Vista, TAC Menta, TAC Xenta and TAC I-Talk are registered trademarks of TAC AB. LonMark and LonWorks are registered trademarks of the Echelon Corporation.
Windows is a registered trademark of Microsoft.
tac-global.com
0-003-2237-0 (EN)
8 (8)