SPECIFICATION R22 HIGH STATIC DUCTED TYPE (SINGLE SKIN)

MODEL

INDOOR UNIT
OUTDOOR UNIT

TOTAL COOLING CAPACITY


INPUT POWER
RUNNING CURRENT - 1 [3]
EER
POWER SOURCE
REFRIGERANT TYPE / CONTROL
INDOOR AIR FLOW
INDOOR FAN ESP
SOUND PRESSURE LEVEL
(MEASURED IN SOUND ROOM)
UNIT DIMENSION, INDOOR UNIT
HxWxD
OUTDOOR UNIT
INDOOR UNIT
UNIT WEIGHT
OUTDOOR UNIT
LIQUID
COPPER PIPE SIZE
GAS

MODEL

INPUT POWER
RUNNING CURRENT - 1 [3]
EER
POWER SOURCE
REFRIGERANT TYPE / CONTROL
INDOOR AIR FLOW
INDOOR FAN ESP
SOUND PRESSURE LEVEL
(MEASURED IN SOUND ROOM)
UNIT DIMENSION, INDOOR UNIT
HxWxD
OUTDOOR UNIT
INDOOR UNIT
UNIT WEIGHT
OUTDOOR UNIT
LIQUID
COPPER PIPE SIZE
GAS
INDOOR UNIT
OUTDOOR UNIT

TOTAL COOLING CAPACITY


INPUT POWER
RUNNING CURRENT - 1 [3]
EER
POWER SOURCE
REFRIGERANT TYPE / CONTROL
INDOOR AIR FLOW
INDOOR FAN ESP
SOUND PRESSURE LEVEL
(MEASURED IN SOUND ROOM)
UNIT DIMENSION, INDOOR UNIT
HxWxD
OUTDOOR UNIT
INDOOR UNIT
UNIT WEIGHT
OUTDOOR UNIT
LIQUID
COPPER PIPE SIZE
GAS

MODEL

Btu/h
W
W
A
Btu/hr/W
V/Ph/Hz

590 / 1,250
100 / 0.4

dBA

53

mm
mm
kg

INPUT POWER
RUNNING CURRENT - 1 [3]
EER
POWER SOURCE
REFRIGERANT TYPE / CONTROL
INDOOR AIR FLOW
INDOOR FAN ESP
SOUND PRESSURE LEVEL
AA(MEASURED IN SOUND ROOM)
UNIT DIMENSION, INDOOR UNIT
HxWxD
OUTDOOR UNIT
INDOOR UNIT
UNIT WEIGHT
OUTDOOR UNIT
LIQUID
COPPER PIPE SIZE
GAS

572 x 892 x 761


852 x 1,030 x 400

50

78

YSB 80B

85
9.5 / 3/8

l/s / CFM
Pa (in.wg.)

1,180 / 2,500
100 / 0.4

dBA

56

57

Btu/h
W
W
A
Btu/hr/W
V/Ph/Hz

MYSS 80C
80,000
23,447
8,760
[15.20]
9.13

kg
mm/in
mm/in

YSB 200B2
MYSS 100B x 2
200,000
58,617
20,118
[39.30]
9.94

YSB 250B2
MYSS 125B x 2
250,000
73,271
25,658
[44.50]
9.74

l/s / CFM
Pa (in.wg.)

3,021 / 6,400
265 / 1.06

3,776 / 8,000
280 / 1.12

YSB 300B2
MYSS 150C x 2
300,000
87,925
34,190
[66.40]
8.77
380-415/3/50
INDOOR TXV
4,248 / 9,000
300 / 1.20

dBA

61

63

66

Btu/h
W
W
A
Btu/hr/W
V/Ph/Hz

mm
mm
kg
mm/in
mm/in

Btu/h
W
W
A
Btu/hr/W
V/Ph/Hz
l/s / CFM
Pa (in.wg.)
dBA
mm
mm
kg
mm/in
mm/in

572 x 1,502 x 761

34.9 / 13/8

YSB 400B4
MYSS100B x 4
400,000
117,233
39,773
[77.40]
10.06

YSB 450B3
MYSS 150C X 3
450,000
131,887
50,236
[97.30]
8.96

5,664 / 12,000
310 / 1.24
66

6,372/ 13,500
350 / 1.41

85
105
12.7 /

55
88

945 x 1,894 x 980


1,291 x 1,866 x 1,199
(946 x 939 x 1,116) x 2 (946 x 939 x 1,116) x 2 (1,041 x 939 x 1,116) x 2
343
343
220
169 x 2
227 x 2
164 x 2

28.6 / 11/8

61

YSB 125B
MYSS 125B
125,000
36,635
12,344
[21.40]
10.13

YSB 150B1
MYSS 150C
150,000
43,962
16,200
[31.80]
9.26

1,982 / 4,200
150 / 0.6

2,171 / 4,600
150 / 0.6

58

59

885 x 1,640 x 1,040


946 x 939 x 1,116
1,041 x 939 x 1,116
189
102
176
169
164
227
5
15.9 / /8
3
1
34.9 / 1 /8
28.6 / 1 /8

572 x 1,502 x 761


946 x 1,300 x 500
92
145
12.7 /
25.4 / 1

mm
mm

944 / 2,000

100 / 0.4

19.1 / 3/4
YSB 100B
MYSS 100B
100,000
29,308
10,334
[19.40]
9.68
380-415/3/50
R22 / INDOOR TXV
1,510 / 3,200
100 / 0.4

MYSS 72C
70,000
20,516
7,109
[13.60]
9.85

YSB 60B
YSL 61D
61,000
17,878
6,672
[10.50]
9.14

53

mm/in
mm/in

INDOOR UNIT (SINGLE SKIN)


OUTDOOR UNIT

TOTAL COOLING CAPACITY

YSB 50B
YSL 50D
50,000
14,654
5,457
[9.10]
9.16
380-415/3/50
R22 / INDOOR CAP. TUBE
755 / 1,600

YSL 40D
40,000
11,723
4,833
[7.30]
8.28

l/s / CFM
Pa (in.wg.)

INDOOR UNIT
OUTDOOR UNIT

TOTAL COOLING CAPACITY

MODEL

YSB 40B
YSL 35D
35,000
10,258
3,493
[16.40]
10.02
220-240/1/50

SPECIFICATION - R22 HIGH STATIC DUCTED TYPE (DOUBLE SKIN)

68

15.9 / 5/8

YSB 500B4
MYSS 125B x 4
500,000
146,542
51,734
[89.70]
9.66
380-415/3/50
R22 / INDOOR TXV
7,080 / 15,000
380 / 1.53

MYSS 100B

YSB 350B3
MYSS 125Bx2
350,000
102,579
36,621
[65.00]
9.56

4,956 / 10,500
285 / 1.14
66
1,546 x 2,122 x 1,199
946 x 939 x 1,116
(946 x 939 x 1,116) x 2
440
164
169 x 2

28.6 / 11/8

34.9 / 13/8

YSB 600B4
MYSS 150C x 4
600,000
175,850
67,577
[131.90]
8.88

YSB 750B5
MYSS 150C x 5
750,000
219,812
85,981
[166.90]
8.72

8,496 / 18,000
405 / 1.63
70

10,619 / 22,500
455 / 1.83
71

2,257 x 2,274 x 1,905


1,546 x 2,274 x 1,466
1,978 x 2,274 x 1,905
(946 x 939 x 1,116) x 4 (1,041 x 939 x 1,116) x 3 (946 x 939 x 1,116) x 4 (1,041 x 939 x 1,116) x 4 (1,041 x 939 x 1,116) x 5
991
1,051
513
564
227 x 3
169 x 4
227 x 4
227 x 5
164 x 4
15.9 / 5/8
34.9 / 13/8
28.6 / 11/8

1) ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING 26.7 C DB/ 19.4 C WB INDOOR AND 35C DB/ 23.9C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN SOUND ROOM

INDOOR UNIT
OUTDOOR UNIT

MODEL

NOMINAL COOLING CAPACITY


NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT- 1 [3]
EER
POWER SOURCE
REFRIGERANT TYPE/ CONTROL

Btu/hr
W
W
A
Btu/hr / W
V/Ph/Hz

YDSB 80B
MYSS 80C
80,000
23,447
8,760
[15.20]
9.13
380-415 / 3 /50
R22 / INDOOR TXV

YDSB 100B
MYSS 100B
100,000
29,308
10,334
[19.40]
9.68
380-415 / 3 /50
R22 / INDOOR TXV

YDSB 125B
MYSS 125B
125,000
36,635
12,344
[21.40]
10.13
380-415 / 3 /50
R22 / INDOOR TXV

YDSB 150B1
MYSS 150C
150,000
43,962
16,200
[31.80]
9.26
380-415 / 3 /50
R22 / INDOOR TXV

INDOOR AIR FLOW

l/s / CFM

1,180/,2500

1,510 / 3,200

1,982 / 4,200

2,171 / 4,600

INDOOR FAN ESP


SOUND PRESSURE LEVEL
(MEASURED IN SOUND ROOM)
INDOOR UNIT
UNIT DIMENSION OUTDOOR UNIT
HxWxD
INDOOR UNIT
UNIT WEIGHT
OUTDOOR UNIT
LIQUID
COPPER PIPE SIZE
GAS

Pa (in.wg)

100 (0.4)

100 (0.4)

150 (0.6)

150 (0.6)

dBA

56

57

58

59

mm
mm
kg

648 x 1,502 x 813


946 x 1,300 x 500
112
145
12. 7 / 1/2
25.4 / 1

648 x 1,502 x 813


946 x 939 x 1,116
116
164
15.9 / 5/8
28.6 / 1 1/8

963 x 1,640 x 1061


946 x 939 x 1,116
161
169
15.9 / 5/8
34.9 / 1 3/8

963 x 1,640 x 1061


1,041 x 939 x 1,116
209
227
15.9 / 5/8
34.9 / 1 3/8

INDOOR UNIT
OUTDOOR UNIT

MODEL

NOMINAL COOLING CAPACITY


NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT- 1 [3]
EER
POWER SOURCE
REFRIGERANT TYPE/ CONTROL

mm/in
mm/in

Btu/hr
W
W
A
Btu/hr / W
V/Ph/Hz

YDSB 200B2
MYSS 100B X2
200,000
58,617
20,118
[39.30]
9.94
380-415 / 3 /50
R22 / INDOOR TXV

YDSB 250B2
MYSS 125B X2
250,000
73,271
25,658
[44.50]
9.74
380-415 / 3 /50
R22 / INDOOR TXV

YDSB 300B3
MYSS 100B X3
300,000
87,925
30,832
[59.80]
9.73
380-415 / 3 /50
R22 / INDOOR TXV

YDSB 350B3
MYSS 125B X2
350,000
102,579
36,621
[65.00]
9.56
380-415 / 3 /50
R22 / INDOOR TXV

MYSS 100B

INDOOR AIR FLOW

l/s / CFM

3,021 / 6,400

3,776 / 8,000

4,248 / 9,000

4,956/ 10,500

INDOOR FAN ESP


SOUND PRESSURE LEVEL
(MEASURED IN SOUND ROOM)
INDOOR UNIT
UNIT DIMENSION HxWxD
OUTDOOR UNIT
INDOOR UNIT
UNIT WEIGHT
OUTDOOR UNIT
LIQUID
COPPER PIPE SIZE
GAS

Pa (in.wg)

265 (1.06)

280 ( 1.12)

300 (1.20)

285 (1.14)

dBA

58

60

63

mm
mm
kg

967 x 1,904 x 1078


(949 x 939 x 1,116) x 2
208
164 x 2
15.9 / 5/8
28.6 / 1 1/8

1,318 x 1,904 x 1,304


( 946 x 939 x 1,116 ) x 2
278
169 x 2
15.9 / 5/8
34.9 / 1 3/8

1,318 x 1,904 x 1,304


( 946 x 939 x 1,116) x 3
298
164 x 3
15.9 / 5/8
28.6 / 1 1/8

INDOOR UNIT
OUTDOOR UNIT

mm/in
mm/in

63
1,592 x 2,122 x 1,338
( 946 x 939 x 1,116 ) x 2
946 x 939 x 1,116
352
169 x 2
164
15.9 / 5/8
34.9 / 1 3/8
28.6 / 1 1/8

Btu/hr
W
W
A
Btu/hr / W
V/Ph/Hz

YDSB 400B4
MYSS 100B X4
400,000
117,233
39,773
[77.40]
10.06
380-415 / 3 /50
R22 / INDOOR TXV

YDSB 500B4
MYSS 125B X4
500,000
146,542
51,734
[89.70]
9.66
380-415 / 3 /50
R22 / INDOOR TXV

INDOOR AIR FLOW

l/s / CFM

5,664 / 12,000

7,080 / 15,000

INDOOR FAN ESP


SOUND PRESSURE LEVEL
(MEASURED IN SOUND ROOM)
INDOOR UNIT
UNIT DIMENSION HxWxD
OUTDOOR UNIT
INDOOR UNIT
UNIT WEIGHT
OUTDOOR UNIT
LIQUID
COPPER PIPE SIZE
GAS

Pa (in.wg)

310 ( 1.24)

380 (1.53)

dBA

64

MODEL

NOMINAL COOLING CAPACITY


NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT- 1 [3]
EER
POWER SOURCE
REFRIGERANT TYPE/ CONTROL

mm
mm
kg

( 946 x 939 x 1,116) x 4


364
164 x 4
15.9 / 5/8
28.6 / 1 1/8

mm/in
mm/in

65
1,585 x 2,320 x 1,622

(946 x 939 x 1,116) x 4


386
169 x 4
15.9 / 5/8
34.9 / 1 3/8

1) ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING 26.7 C DB/ 19.4 C WB INDOOR AND 35C DB/ 23.9C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASURED IN SOUND ROOM

www.york.com.my
Group Associated (C&L) Sdn Bhd (109719-M)
Head Office: Tel: 03-7718 8388 Fax: 03-7727 4371
Email: sales_enquiry@york.com.my, customer_service@york.com.my
Branches:

Penang Tel: 04-331 1670


Perak
Tel: 05-548 2307
Sarawak Tel: 082-333 299

Service Centre:

Alor Setar

Johor
Tel: 07-557 7788
Pahang
Melaka Tel: 06-288 1133
Sabah
Negeri Sembilan Tel: 06-768 8969

Tel: 09-567 6778


Tel: 088-722 194

Kota Bharu
Authorized dealer:

are marketed by:


and
Group Associated (C&L) Sdn Bhd (109719-M)
Catalogue No: YSB-1112-C

HighDucted
Static
Split

System
Features

The Trusted Quality And


Name In Air-Conditioning
This unprecedented innovation is brought to you by
YORK - the trusted name in air-conditioning for quality
and reliable after-sales-service. With a nationwide
service network. YORK is ever ready to take you to a new
dimension in cooling comfort.
100% coil leak test by helium testing method and every
components being used in YORK unit are tested, at R&D
test lab, which is registered under ISO standard and
recognised by Sirim.

Wide Product Range

Copper tubes were tested at burst pressure, where it is at


least 3 times the refrigerant operating pressure.

YORK ducted split is offering very wide range of product


lineup which is applicable from residential, to light
commercial or even commercial use.

Every unit receives a 100% unit run test before leaving


the production line in the facrtory, which is registered
under ISO standard and recognised by Sirim.

Products Overview

Modular Combination

YORK ducted split product is connectable to 9 different


capacities of outdoor units. The individual indoor units
capacity can ranking up to 750 kBtu/hr ( for single skin)
and 500kBtu/hr ( for double skin)

With the choices of vertical and horizontal air throw make


it versatile to various architectual design.

Fire-resistant Polyethylene is used at every possible


condensate panel to prevent all forms of water or
moisture penetration. Polyethlene, which is also a type a
Closed Cell Foam Insulation (CCF) has offered the
following advantages:
Durable external surface that resists dirt tough and
resilient.
Higher degree of puncture resistance when compared
to fiberglass.
Easily cleaned surface (if necessary) to further resist
microbial growth.

Changeable Drive Package

Components

Cabinet Construction
YSL 35-61D
YSB 40B/50B

YSB 200B2

YSB 400B4/450B4/500B4

YDSB 80B/100B

YDSB 300B3

MYSS 72-80C

YSB 60B/80B/100B

YSB 250B2/300B2

YSB 600B4

YDSB 125B/150B1

Both indoor and outdoor are coated with weatherproofed


electro galvanized mild steel casing, with an epoxy
polyester powder coated for severe external conditions.
Service panel is available at the convenience side for both
indoor and outdoor.

Indoor Air Throw Direction

Non-standard external static pressure & airflow


requirement can be sized by changing the factory fitted
drive package. (for belt drive model only)

YDSB 350B3
MYSS 100-125B

Easy To Reach Access Valve

Discharge line and suction line access valve is accessible


without opening the unit casing.

Excellent Thermal barrier


YSB 125B/150B

YSB 300B3/350B3

Indoor Unit (Single Skin Ducted Type)

YSB 750B5

YDSB 200B2/250B2

YDSB 400B4/500B4

Indoor Unit (Double Skin Ducted Type)

MYSS 150C

Outdoor Unit

Insulation

(applicable to double skin ducted type)


All the frameworks are insulated with 1 inch double
skin PU insulation panel to create a thermal barrier
between the internal and external surfaces.
The Polyurethane foam (PU) create the optimum
insulation performance and rigidity.

Compressor:
Each high efficiency scroll type compressor is
hermetically sealed, quiet running and supported
on rubber mounts to minimize vibration.
Indoor Fan:
A dynamically balanced forward curved fan with a
field changeable pulley package, in order to match the
designed supply air requirements (For belt-driven
model only)

Safety Fearures

High pressure and low pressure protection


Phase sequencer is used to detect for any wrong
phase and phase loss during installation and operation.
Compressor & motor current overload protection.
Minimum compressor's running time to ensure oil return.