You are on page 1of 74

OPERATING AND

MAINTENANCE MANUAL

MODEL :SF-960-CCT
SERIAL NO : 120338

CM Envirosystems

TABLE OF CONTENTS
PART- A Operating Instruction Manual
CHAPTER 1 Safety Instructions
1.1 Introduction
1.2 Installation Safety Notices
1.3 Operation Safety Notices
1.4 Safety warnings& symbols

CHAPTER 2 - Installation
2.1 Delivery and Uncrating of Unit
2.2 Location and Installation of Unit
2.3 Pre-requisite for installation
2.4 Preparation for Use
2.5 Input Power and other connections

CHAPTER 3 - An Introduction to Silver fog Corrosion Chamber

CHAPTER 4 Operation
4.1 Introduction
4.2 Summary of Chamber Operation
4.2.1 Solution Fog Cycle
4.2.2 High Humidity Cycle
4.2.3 Dry Cycle
4.2.4 Dwell Cycle
4.3 switches and indicators
4.4 control panel

CHAPTER 5 Controller enviCoM

CHAPTER 6 Frequently Asked Questions


CM Envirosystems

CHAPTER 7 MAINTENANCE

7.1 Preventive Maintenance Intervals


7.2Troubleshooting
7.3 Silver Fog Corrosion Test Chamber Chart
7.4 Nozzle air atomizer maintenance tips
7.5 Procedure to replace isoprene tube of peristaltic pump

CM Envirosystems

CHAPTER 1
SAFETY INSTRUCTIONS
1.1 Introduction:
Follow all CAUTION notices to prevent damage to the chamber or your
test sample. Failure to follow all CAUTION notices may void your warranty. CAUTION
may also indicate a potentially hazardous situation, which, if not avoided, may result in
minor or moderate personal injury.

1.2 Installation Safety Notices:

CAUTION: Obey all CAUTION, DANGER, and WARNING signs / labels


mounted on the equipment. Do not remove any of these signs / labels.
CAUTION: Only qualified service personnel should ever be permitted to perform any
service-related procedure on this equipment
CAUTION: Do not place the unit near combustible materials or hazardous fumes or
vapors.
CAUTION: The minimum clearance you should allow for proper ventilation around
the chamber must be at least 1mtr.
CAUTION:

This chamber must be properly connected to electrical input as

mentioned on name plate. You must verify the exact type of electrical service you have.
If there is any doubt, you must consult with a qualified electrician who is familiar with
industrial plant wiring. In addition, the input voltage should be measured while the
chamber is operating to ensure that the expected phase voltage should be of 200V and
between Neutral and Earth less than 1 volt. Operation below the phase voltage is not
recommended. An electrician who is familiar with industrial plant wiring should carry
out the above procedure.
CAUTION: This chamber is designed for operation in a conditioned laboratory
environment between 16oC (60oF) to 40oC (104oF). The performance may vary if these
conditions are not met.

CM Envirosystems

1.3 Operational Safety Notices:


CAUTION: Do not increase the specified Dead load mass placed in the workspace
as it may alter the air flow pattern as well as spray operation and also damage the work
space because it is made out of FRP.

CAUTION: The Hydro sealing of the workspace should be filled with water.

WARNING: Do not put items in the chamber that could burn or explode at high
temperatures. Though this chamber uses a taped heating element, which is embedded,
onto the workspace. This is not an explosion-proof chamber.

WARNING: The chamber door (Acrylic Dome) must remain closed while the
chamber is operating. If you need to open the dome while the chamber is operating,
wear safety goggles to prevent contact of spray solution with your eyes or switch on the
Air Purging System before opening the door.

WARNING: This chamber operates at extreme temperatures. Avoid contact with


air, objects, and surfaces that are hot to prevent severe burns. Protective gloves are
recommended.

CM Envirosystems

1.4 Safety warnings& symbols:


Obey all DANGER, WARNING, and CAUTION labels shown in
the manual and mounted on the equipment. Do not remove any labels mounted on the
equipment

Warning of hazardous area

Warning of hot surface

Warning of cold surface

Warning of dangerous electric voltage

Earth (ground) protective conductor terminal

CM Envirosystems

CHAPTER 2
INSTALLATION
2.1 Delivery and Uncrating of Unit:
Inspect equipment and shipping crate immediately upon receipt. If any
damage is apparent, you should both report it to the trucking delivery person and contact
the transportation company immediately. Make notes of any damage on the Bill Of
Lading. Retain all shipping materials for inspection. Any claims for damage must start at
the receiving point. Do not return goods to CM Envirosystems without written
authorization. When submitting a claim for shipping damage, request that the carrier
inspect the shipping container and equipment. Check packing slip carefully and make
sure all materials have been received as indicated on the packing ticket. Unless
otherwise noted, YOUR ORDER HAS BEEN SHIPPED COMPLETE

Important! Do to the vibration incurred during shipping and handling, it is possible that
mechanical connections could become loose. Check all connections to make sure they
are secure.

2.2 Location and Installation of Unit:


Your equipment has been fully operated, tested, and balanced in our plant
prior to shipment, unless notified otherwise. Follow the installation requirements below.
Do not place the unit near combustible materials or hazardous fumes or vapors
The chamber will produce highly corrosive environments and significant amount of heat
during normal operation. Locate the chamber in a room with adequate ventilation and
also ensure that air-purging system has been activated prior to door open. The chamber
must be located on a solid/floor level. Allow enough space around the chamber to permit
serviceability and the removal of the service access panels, which are located on each
side and the rear.

CM Envirosystems

2.3 Pre-requisite for installation:


1. Power Supply 230V AC,10%. 3 Phase, 50 Hz ,3 wire + Earth
2. Continuous De-Mineralized water supply with an inlet size of 8mm PU tube
Connector and pressure of 1 2 Kg/Cm2
DM Water connection should be minimum 3mtr from the water solenoid valve.

3. Clean and dry Compressed Air with an inlet size of 8mm PU tube connector
and pressure of 3 5 Kg/Cm2
4. Drain provision to connect the chamber drain.
5. Spray Solution for reservoir. (Ex: NaCl)

2.4 Preparation for Use:


1. Inspect the chamber for signs of shipping damage.
2. Read this entire manual.
3. Select a suitable location to install the chamber.
4. Verify the input voltage and phase configuration.
5. Connect to the 1 Power source.
6. Perform the following procedures as described in the Preventive maintenance
section:
a. Inspect the electrical compartment.
b. Verify the chamber performance.

2.5 Input Power and other connections:


The chamber is easily configured for operation from a 230V AC,+/-10%, 3 Phase
50 Hz ,3 Wire + Earth or as on the nameplate.
Connect the chamber plug to any 230V AC,+/-10%, 3 Phase 50/60 Hz ,3 Wire
socket.
Connect continues De -Mineralized water supply to the water inlet of the chamber.
Connect air compressor out let, to chamber air inlet

CM Envirosystems

CHAPTER 3
AN INTRODUCTION TO THE SILVERFOG CORROSION CHAMBER

Introduction:

The Silver fog corrosion chamber is designed to subject the specimen at various
corrosive test conditions like, salt chemical or water fog at saturated humidity.

Construction:
The Chamber mainly consists of three units:
a. Main Chamber.
b. Solution Reservoir
c. Control panel Unit.

The Main Chamber:


Introduction: Silver fog corrosion chambers are designed to subject the test
specimen to accelerate and highly corrosive environments without introducing other
contaminants into the test area. Chamber has a test area constructed of GRP tank,
which is impervious to the corrosive effects of the salt atmosphere. The outer body
of the chamber is made of FRP (Fiber Reinforced Plastic) with Vapor coating for a
highly resistive surface. Between the test space and the outer body Mineral wool
insulation is used to arrest the heat loss from the test space.

CM Envirosystems

Door:
Door

Pneumatic cylinder

An acrylic canopy shaped doom and fitted with a pneumatic door lift, which can be
operated using the door open and close switches provided on the control panel. The
inner surface of the dome is sloped such that the droplets do not come in direct contact
with the test specimen and slides along the surface and drains out

Test specimen space:

Test space

The test space is provided with a multi grooved shelf where the test specimen is hung
or supported within by FRP rods or using other fixtures.

CM Envirosystems

Atomizer :
ATOMIZER
WATER LINE

AIR LINE

A non-corrosive wide-angle atomizer is provided on the side of the test


space and directed towards the canopy doom, ensuring a uniform spray collection.
This unique design ensures no direct spray onto the test specimen and creates a
uniform spray .

Air Purging:
Clean and dry Compressed Air is purged into the test space ensuring all
the corrosive spray has drained out. This operation must be carried out prior to
opening the door ensuring no damage to the surrounding environment.

Drain:
A drain is provided at the bottom of the test space and connected to the
rear of the main chamber. This drain has to be piped outside during installation of the
chamber.

Solution Reservoir:
The solution reservoir is housed internally with tank capacity based on
the chamber size. The solution can be poured into the chamber by removing the
reservoir lid. This solution is introduced into the test space through the atomizing
nozzle.

Air Pressure Gauge:


Air Pressure Gauge indicates air pressure supply to the atomizer.

Air Regulator:
Air Regulator controls the pressure of the compressor air supply to the
atomizer.
CM Envirosystems

To adjust the Air Pressure:


a. Pull out the regulator knob to unlock the setting.
b. Rotate anticlockwise to decrease the pressure & clockwise to increase it.
c. Push in the regulator knob to lock the setting.

Before Start the test, connect the DM Water & Air supply:
Air Inlet

DM water Inlet

Drain

Saturator:
The saturator tank is provided with a built-in automatic water level
controller which enables the user to operate the chamber round the clock, safety is
provided if there is low water.

The immersion heater temperature is controlled

through a PID controller which is placed in the control panel.

CM Envirosystems

Humidification of chamber air is achieved by vapor injection method, which is


generated by an immersion heater in the boiler tank and which is incorporated with in the
chamber. The Steam Generator System utilizes a reservoir in which water level is been
controlled with all safety controls and water level controls.

Humidity water make up valve:


Humidity inside the chamber is generating by Steam injection method. The
steam is generated through boiler tank which is provided at rear side of the chamber.
Water in the boiler tank is maintained by float switch and water make up solenoid valve.
When the water level in the boiler tank goes low, the water make up solenoid valve
activates based on the float switch level.

Safety thermostat for


boiler

CM Envirosystems

Humidity generation
system

Wick Water make-up solenoid valve:


Humidity inside the chamber is calculated by Dry & Wet bulb
comparison method. For wet bulb we are providing wick cloth on one of the teflon
sensor, to keep the wick cloth we have provided a wick pipe. To maintain the water in
wick pipe an external Water-level adjuster is provided on the rear side of the chamber.
When water level in wick pipe goes low, water solenoid valve automatically activates
based on the float switch level.

Float switch
Wick water tank

Temperature cabinet
The positive temperature in the test space is achieved by recirculation of air
through the heating elements present in the heating cabinet. Pre-heated air of the
operating temperature is forced into the chamber through an aluminum hose to inner
space and ensuring even distribution throughout the test space. To maintain uniform
temperature in the workspace, maximum airflow is directed with the help of a ducting
provided around the fan blades.
Electrical motor
Temp cabinet

Safety thermostat for temp


cabinet

CM Envirosystems

Silver fog Corrosion Test Chambers: Working principle

The CCT Silver fog Corrosion Test Chambers are able to conduct more sophisticated
procedures such as multi-step cycles incorporating High humidity, Dry cycle,
Immersion, Spray Header or even with a refrigeration module. The CCT Silver fog
having enviCOM color touch screen controller, you can easily program complex test
cycles or run any of the pre-programmed procedures.

Solution Fog Cycle:


During the Solution fog cycle, the basic Silver fog Corrosion Test
Chambers typically operates as a conventional salt spray chamber. The corrosive
solution from the solution reservoir is pumped to the nozzles through a metering
device. Compressed air is humidified by passing through the saturator tank. The nozzle
atomizes the solution and humidified air in to a corrosive fog. Chamber heaters
maintain the programmed chamber temperature.
Typical Example: A continuous indirect spray of neutral (pH 6.5 to 7.2) saltwater
solution, which falls-out on to the specimens at a rate of 1.0 to 2.0ml/80cm/hour, in a
chamber temperature of +35C and saturator tank 45C. The test duration is variable.
The preparation of a salt solution consists normally of sodium chloride containing as a
dry compound not more than 0.1% of sodium iodide and not more than 0.3% of total
impurities. This solution is prepared by dissolving five parts by weight of salt in 95
parts by weight of distilled water. It is important to maintain this solution at a specific
gravity of from 1.023 to 1.037.
For Salt spray test AIR PRESSURE should be 1 otherwise it will affect the fog
collection.
CM Envirosystems

High Humidity Cycle:


During the high humidity cycle, the atomizer sprays saturated air and
DM water, which is held in a separate reservoir tank. The chamber heaters maintain the
programmed chamber temperature. The chamber is maintained at almost saturated
humidity

Typical Example: A chamber temperature of +38C and a relative humidity of


100%RH.The test duration is variable.

NOTE:
Connect the continuous DM water line for conducting the High
Humidity cycle.

Dry cycle:
During the dry cycle a hot air blower will purge hot air into the test
space. This creates a low humidity and dry condition inside the chamber. The chamber
heaters and the blower heater temperature are controlled.

Typical Example: This cycle is typically after High Humidity Cycle followed by 17
hours 45 minutes of air-drying in a climate of 50%RH at +60C.

Dwell Cycle:
During the dwell cycle is an intermediate cycle where the solution spray
or other cycles have stopped and no action is taken by any of the sub-systems. The
conditions occurred in previous cycles will be usually not disturbed.

CM Envirosystems

CHAPTER 4
OPERATION
4.1 Introduction:
The CCT version uses an enviCoM color touch screen Controller which
is able to conduct more sophisticated procedures such as multi-step cycles
incorporating High humidity, Dry cycle, Immersion, Spray Header or even with a
refrigeration module. It can cycle as either a single set point controller or as a
programmable profile controller.

4.2 Summary of Chamber Operation:


Switch ON the MAINS.
Release the emergency switch.
Ensure all operational safety notices and pre-requisites have been adhered to.
Set required program in the Controller.
Load your test sample in the chamber.
RUN the program.

4.2.1 Solution Fog Cycle:


Fill the solution tank with the prepared solution as per standard requirement.
Set the required temperature in the enviCOM controller.
Set the time duration of operation in enviCOM controller
Set the required airflow in psi by using air regulator.

4.2.2 High Humidity Cycle


Set the required temperature in the controller program
Set the time duration of operation.
Set the required airflow in psi by using air regulator.
Activate the Humidity cycle event by ticking it in the controller.

CM Envirosystems

4.2.3 Dry Cycle:


Set the required temperature in the controller program
Set the time duration of operation.
Activate the Dry cycle event by ticking it in the controller.

4.2.4 Dwell Cycle:


Set the time duration of operation.
Ensure all other events are non operational.

4.3 SWITCHES AND INDICATORS


SOLUTION PUMP
AIR REGULATOR

PRESSURE GAUGE

DOOR OPEN

DOOR CLOSE

MAIN SWITCH
CHAMBER SAFETY
CONTROLLER
SATURATOR SAFETY
CONTROLLER
ENVICOM
CONTROLLER

TIME TOTALIZER

EMERGENCY SWITCH

BUZZER

CM Envirosystems

Main Switch:
The Main Switch controls power to the entire chamber. In the ON
position primary power is connected. The Main Switch is provided on the control
panel. In the OFF position (counter clockwise) primary power is disconnected. The
Main Switch can be left OFF if the chamber is not used on a daily basis.

Time Totaliser:
The Time Totaliser indicates the total usage time of the chamber.

Canopy door Operation:


The Acrylic canopy doom is assisted by pneumatically operated
cylinder with mushroom head switches. (OPEN/CLOSE) Ensure the button is
continuously kept pressed till the door is opened or closed completely. A minimum of
4Bar air pressure is required for its smooth operation.

Fault Indicator:
Fault indicator Indicates, when any error appears in the chamber.

Emergency Switch:
The Emergency cut off Switch opens the control system during
emergency. Keep the Switch closed (ON) during operating conditions.

CM Envirosystems

4.4 Control panel


Introduction: The Control panel is

designed

for easy

maintenance and accessibility. It houses all the indicating, controlling and


electrical panels. These items are accessible for maintenance and servicing
from the side of the chamber.

Control Module: Temperature conditions are controlled by PID


Controllers. Logic circuits automatically select water inlet, spray and dwell
timing modes as required.

REGULATED
POWER SUPPLY
MODULAR
CONTROLLER
PLC

CONTACTORS
MCB

SSR
RELAYS

CM Envirosystems

CHAPTER 5
CONTROLLER
1.1. enviCoM?
The enviCoM is a multi loop controller, which sets and maintains
temperature and humidity profiles. It also has the capability of storing test data, which
can be retrieved through anyone of its inbuilt communication ports.
The enviCoM comprises of a Resistive Analog Touch screen of 5.7 TFT with a 320 x
240 pixel LCD and all the inputs and outputs are managed by a PLC which also
provides Diagnostics with Pop screens and Help menus.
The enviCoM can be operated through the Ethernet port and can be configured to work
on single PC, LAN Network or even through the Internet since it is a Web Enabled
Controller.

Special Features:
Attractive Color Touch Screen
Simple self-explanatory Graphic User Interface.
Web enabled control for Internet based access.
Five inbuilt communication ports with Ethernet, USB and Rs-232
1Gbyte Compact Flash Card
Multi Zone PID control
NEMA 4X / IP66 Front panel

Display:
This operator interface uses a liquid crystal display (LCD) for displaying
text and graphics. The display utilizes a cold cathode fluorescent tube (CCFL) for
lighting the display. The CCFL tubes can be dimmed for low light conditions (Refer
Display Settings Pg). Backlight lifetime is based upon the amount of time the display is
turned on at full intensity. Turning the backlight off when the display is not in use can
extend the lifetime of your backlight.

CM Envirosystems

CAUTION:

Do not use the sharp object or fingernail when touching the screen, or apply excessive
force on it. It may cause malfunction or breakdown of the screen.

Touch screen:
This operator interface utilizes a resistive analog touch screen for user input. The unit
will only produce an audible tone (beep) when a touch on an active touch screen cell
is sensed. The touch screen is fully functional as soon as the operator interface is
initialized, and can be operated with gloved hands.

Web Server:
The various screens of the enviCoM controller can be remotely accessed using any
standard web-browser, just by enabling the server. There is no requirement to install
proprietary

software

on

your

PC.

Using your mouse, you can take control of equipment, as if you were touching the
controller.

Data Logging:
The enviCoM controller will log tags at user-programmable rates, and automatically
time/date stamp them in a Compact Flash card of 2GBytes. The information is stored
in open CSV file format, allowing you to access them with virtually any application,
such as Microsoft Excel.

Non-Volatile Memory:
The controller uses an on-board flash; the controller doesnt rely on a battery to
maintain its database. So no longer will your chamber go down for the sake of a
battery.
CM Envirosystems

Multi Communication Ports:


With standard built-in RS232, RS485, USB and an Ethernet port, the enviCoM
controller has the most powerful communications platform available today.

LOADING SCREEN

Company contact information


Database loading progress bar.

Front Panel LEDs:


There are three front panel LEDs. Shown below is the status of the LEDs

CM Envirosystems

CAUTION:

Do not turn off device while the yellow light is flickering.

MENU SCREEN

BUTTONS/INDICATORS
Monitor

FUNCTION
Displays the complete summary of control &
operation

Mimic

Displays a process mimic of the components in the


chamber.

Profile Edit

To select, recall and edit any test profile except a


running profile.

Settings

To set the control & operational parameters.

Mode Select

To select Operation Modes, Run Modes, Power


Resumption Modes and Program Links.

Event Viewer

Complete event log of faults occurred with date and


time.

CM Envirosystems

Mode selection screen:


The Mode Selection Screen gives the user an option of various types of
Profile and Time based settings which can be set before running a test profile.
The Mode Selection Screen also has different mod like Power Resumption

Operation Mode:

BUTTONS/INDICATORS

Operation Mode Reset

FUNCTION

When this mode of operation is selected the


controller is set to a single set point and no duration
is calculated.

Operation Mode Profile

When this mode of operation is selected the


controller is set to Programmable Mode where
Multiple Test Profiles can be set with specific
duration of operation.

CM Envirosystems

Run Mode:

BUTTONS/INDICATORS
Run Mode - Delay

FUNCTION
When the ON DELAY mode is selected the no. of
hours and minutes in HH:MM format can be entered
after only which the test profile will start.

Run Mode Quick

When the QUICK RUN mode is selected the test


profile will start immediately.

Power Resumption:

BUTTONS/INDICATORS
Power Resumption- Break

FUNCTION
When this mode is selected in the event of a power
failure any active profile will be stopped when the
power is recovered.

Power Resumption- Cold

When this mode is selected in the event of a power


failure any active profile will continue from the
beginning of the profile ensuring Guaranteed Soak.

Power Resumption- Hot

When this mode is selected in the event of a power


failure any active profile will continue from the
same duration before power failure.

CM Envirosystems

Profile Edit Screen:


The Profile Edit Screen is for the user to load all the profiles into the
controllers memory. The controller can save up to 99 profiles with unique names and
set up to 999 repeat cycles. Pressing on any of the edit boxes pops up the alpha
numeric keypad.

Profile Edit Basic:


Input the profile number and the profile name in the box. The number
of repeat cycles can be set for the current profile which will loop the entire profile
from the first segment. Next press on the EDIT button to edit the entered profile or
just preview the profile by pressing the VIEW button. Press the LOAD button to
activate the profile which later can be started on the Monitor screen.

CM Envirosystems

BUTTONS/INDICATORS
Profile Number

FUNCTION
Enter the profile number you would like to edit by
pressing on the box with a maximum of 99 profiles

Profile Name

Enter the profile name with a maximum of 08


alpha/numeric characters by pressing on the box

Repeat Cycle

Enter the number of times you would like the profile


to repeat.

Edit Button

Press the EDIT button if you would like to make


changes in the profile number you have entered.

View Button

Press the VIEW button if you would like to view the


profile number you have entered.

Load Button

Press the LOAD button if you would like to load the


profile number you have entered, by which you can
start the profile on the Monitor Screen.

Profile Segment Screen:


The Profile Segment Screen is used to set the individual segments in
the selected profile number. A maximum of 50 segments can be set for a single
program.

CM Envirosystems

BUTTONS/INDICATORS
Profile Number

FUNCTION
Indicates the Profile number pre-selected on the edit
screen.

Profile Name

Indicates the Profile name pre-selected on the edit


screen.

Segment No

Indicates that, specific segment of profile

End Segment

Indicates the number of the last segment in the profile


with a maximum of 50 segments

Select segment type

Type of test to be carried out in the segment


Like SALT SPRAY,,HIGH HUMIDITY,DRY CYCLE
etc.

Temperature Edit Box

Press on the cyan box to enter the value of temperature


in Degree Celsius to be achieved or maintained in that
segment.

Saturator Temp Edit Box

Press on the cyan box to enter the value of Saturator in


deg C to be achieved or maintained in that segment.

Humidity Edit Box

Press on the cyan box to enter the value of humidity in


%RH to be achieved or maintained in that segment.

Duration in Minute Edit Box

Press on the cyan box to enter the value of duration

Select Profile Button


Copy Button

Press the button to copy that particular segment data.

Paste Button

Press the button to paste copied segment data.

Load Button

Press the button to load the profile

CM Envirosystems

Online monitoring screen


Chamber Temperature Trend Screen:
In the Temperature Trend Screen the instantaneous temperature process values will be
plotted. The Y-Axis is Temperature in C and the process values of the last 12 hours
will be plotted.

BUTTONS/INDICATORS

FUNCTION

<<

Moves to the First Page

<

Moves to the Previous Page

Live

Indicates the current trend

>

Moves to the Next Page

>>

Moves to the Last Page

IN

Zooms in to visualize shorter time span

OUT

Zoom out to visualize larger time span up to 12


hours.
Move to the Saturator Temperature Trend Screen.
Esc

CM Envirosystems

Move back to the previous screen.

Saturator Temperature Trend Screen:


In the Saturator Trend Screen the instantaneous Temperature process
values will be plotted. The Y-Axis is Temperature in deg C and the process values of
the last 12 hours will be plotted.

BUTTONS/INDICATORS

FUNCTION

<<

Moves to the First Page

<

Moves to the Previous Page

Live

Indicates the current trend

>

Moves to the Next Page

>>

Moves to the Last Page

IN

Zooms in to visualize shorter time span

OUT

Zoom out to visualize larger time span up to 12


hours.
Move to the Humidity Trend Screen.

Esc

CM Envirosystems

Move back to the previous screen.

Chamber Humidity Trend Screen:


In the Humidity Trend Screen the instantaneous Humidity process
values will be plotted. The Y-Axis is Relative Humidity in (%) percentage and the
process values of the last 12 hours will be plotted.

BUTTONS/INDICATORS

FUNCTION

<<

Moves to the First Page

<

Moves to the Previous Page

Live

Indicates the current trend

>

Moves to the Next Page

>>

Moves to the Last Page

IN

Zooms in to visualize shorter time span

OUT

Zoom out to visualize larger time span up to 12


hours.
Move back to the

Saturator Temperature Trend

Screen.
Esc

CM Envirosystems

Move back to the previous screen.

Event Viewer Screen:


The Event Viewer screen will data log all the alarms occurred during a
program run. When an alarm fault has occurred a pop up screen will appear with the
type of fault. This pop up screen can appear in any display screen and once the fault has
been cleared, it will be data logged in the event viewer screen. The format of logging
this will be date in dd/mm/yy, time in hh:mm and type of alarm / fault.

BUTTONS/INDICATORS

FUNCTION

Previous

Move to the previous page

Next

Move to the next page

Clear

To clear all the data

Esc

Return to the previous menu

CM Envirosystems

Main Settings:
The Main Settings screen is accessible after logon with the right
username and password. Press the LOGON button to select the username and enter the
password or else press the EXIT button.

Example:
Enter user name as ss and then press Enter button, then Pass word dialogue box will
open

Then Enter pass word as ss and press Enter button to access setting screen

After authentication the Main Settings screen will be accessible where factory level
settings and various other settings can be modified.

CM Envirosystems

Main Settings screen

Buttons/Indicators
Temperature

Function
Press this button to change factory settings of basic
temperature control, calibration and limit values.

Saturator

Press this button to change factory settings of basic


Saturator Temp control, calibration and limit values.

Humidity

Press this button to change factory settings of basic


humidity control, calibration and limit values.

Extra settings

Press this button to change factory settings of various


other control, limit and time related values

HMI settings

Press this button to change the Date & time,


Language, Display contrasted.,

Print Settings

Press this button to enter online printer settings

IO Monitors

Press this button to see IO & OP in plc

Logout

Press this button to logout from the current Main


Settings screen.

Esc
CM Envirosystems

Return to the previous menu without logout

Temperature PID Settings


Screen 01:
The first section consists of temperature Controlling Values, the second section, Set
Point Parameters, the third section, Input Parameters and the fourth section Output
Parameters

BUTTONS/INDICATORS
Dry Bulb Temp PV

FUNCTION
The Dry Bulb Temperature Process Value indicates the
value in C which is connected by the dry RTD Pt-100
sensor.

Dry Bulb Temp SV

The Dry Bulb Temperature Set Value indicates the


current set point active in C

Low Limit

The controller has programmable low setpoint limit


values to restrict the setting range of the setpoint. Set
the limits so that the setpoint value cannot be set
outside the safe operating area of the process.

High Limit

The controller has programmable high setpoint limit


values to restrict the setting range of the setpoint. Set
the limits so that the setpoint value cannot be set
outside the safe operating area of the process

CM Envirosystems

Offset Correction

This value offsets the temperature value by the entered


amount. Offset only applies to temperature sensor.

O/P Power

Displays the output power set by the Output Low


Limit and the Output High Limit.
Move to the next page

Esc

Return to the previous menu

Screen 02:
This screen section consists of the PID Parameters, Auto Tune and Activation of the
Zone PIDs.

Conti,,

CM Envirosystems

BUTTONS/INDICATORS

FUNCTION
This determines the control action for the PID loop.
Programmed for direct action (cooling), the DLC

Control Action

output power will increase if the Process value is above


the Setpoint value. Programmed for reverse action
(heating), the output power decreases when the Process
Value is above the Setpoint Value.
The dampening time, entered as a time constant in
seconds, dampens (filters) the calculated output power.
Increasing the value increases the dampening effect.

Dampening Time

Generally, dampening times in the range of onetwentieth to one-fiftieth of the controllers integral time
(or process time constant) is effective. Dampening
times longer than these may cause controller instability
due to the added lag effect.
The cycle time, entered in seconds, is the combined
time of an on and off cycle of a time proportioning
control output. With time proportional output, the
percentage of control power is converted into output on

Cycle Time

time of the cycle time value. (If the controller


calculates that 65% power is required and has a cycle
time of 10 seconds, the output will be on for 6.5
seconds and off for 3.5 seconds.) For best control, a
cycle time equal to one-tenth of the process time
constant, or less, is recommended.
These parameters may be used to control low limit
power due to process disturbances or set point changes.

Power Low Limit

Enter the safe output low power limits for the process.
At 0%, both OP1 and OP2 are off; at 100%, OP1 is on
for heating ; and at -100%, OP2 is on for cooling.

CM Envirosystems

Proportional band, entered as percent of full input range,


is the band from the set point where the controller
adjusts the percent output power based on how close the
process value is to the set point. For temperature inputs,
P Band

the input range is fixed per the entered RTD type.


The proportional band should be set to obtain the best
response to a process disturbance while minimizing
overshoot. A proportional band of 0.0% forces the
controller into On/Off
Control with its characteristic cycling at set point.
Integral time is defined as the time, in seconds; it takes
the output power due to integral action alone to equal
the output power due to proportional action alone during
a constant process error. As long as the error exists,

I Time

integral action repeats the proportional action each


integral time. Integral action shifts the centre point
position of the proportional band to eliminate error in
the steady state. The higher the integral time, the slower
the response. The optimal integral time is best
determined during PID Tuning. If time is set to zero, the
previous Integral output power value is maintained.

D Time

Derivative time, entered as seconds per repeat, is the


time that the controller looks ahead at the ramping
error to see what the proportional contribution will be
and it matches that value every Derivative time. As
long as the ramping error exists, the Derivative action
is repeated by Proportional action every derivative
time. Increasing the derivative time helps to stabilize
the response, but too high of a derivative time, coupled
with noisy signal processes, may cause the output to
fluctuate too greatly, yielding poor control. Setting the
time to zero disables Derivative Action.

CM Envirosystems

Press the Red button to start the Auto Tune feature.


Auto-Tune is a user-initiated function where the
controller automatically determines the Proportional
Band, Integral Time, Derivative Time, Digital Filter,
Start Auto Tune

Control Output Dampening Time, and Relative Gain


(Heat/Cool)

values

based

upon

the

process

characteristics. The Auto-Tune operation cycles the


controlling output(s) at a control point three-quarters
of the distance between the present process value and
the set point. The nature of these oscillations
determines the settings for the controllers parameters.
Auto-Tune Phase

The controller will oscillate the controlling output for


four cycles. The cycling phase can be monitored from
the Auto-Tune Phase. The time to complete the AutoTune cycles is process dependent. The controller
should automatically stop Auto-Tune and store the
calculated values when the four cycles are complete If
the controller remains in Auto- Tune unusually long,
there may be a process problem. Auto-Tune may be
stopped by entering 0 in Auto-Tune Start.

Auto-Tune Code

The Auto Tuning Code sets the PID profile typically as


per the different codes from 0 to 2.

Activate Zone PID

Press the Red button to activate the Zone PID feature.


In this feature different PIDs can be set for a specific
temperature range.
Move to the previous page

Esc

CM Envirosystems

Go back to menu

Saturator PID Settings:


Screen 01:
The first section consists of wet bulb temperature (Saturator) Controlling Values, the
second section, Set Point Parameters, the third section, Input Parameters and the fourth
section Output Parameters

BUTTONS/INDICATORS
Wet Bulb Temp PV

FUNCTION
The Wet Bulb Temperature Process Value indicates the
value in C which is connected by the wet RTD Pt-100
sensor.

Wet Bulb Temp SV

The Wet Bulb Temperature Set Value indicates the


current set point active in C

Low Limit

The controller has programmable low set point limit


values to restrict the setting range of the set point. Set
the limits so that the set point value cannot be set
outside the safe operating area of the process.

High Limit

The controller has programmable high set point limit


values to restrict the setting range of the set point. Set
the limits so that the set point value cannot be set
outside the safe operating area of the process

CM Envirosystems

Rounding

Rounding selections other than 1 because the process


value to round to the nearest rounding increment
selected. (For example, rounding of 5 causes 122 to
round to 120 and 123 to round to 125.) Rounding
starts at the least significant digit of the process value.
If the signal is
Inherently jittery, the process value may be rounded to
a value higher than 1.

Offset Correction

This value offsets the temperature value by the


entered amount. Offset only applies to temperature
sensor.

O/P Power

Displays the output power set by the Output Low


Limit and the Output High Limit.
Move to the next page

Esc

Return to the previous menu

Screen 02:
This screen section consists of the PID Parameters and Auto Tune.

CM Envirosystems

BUTTONS/INDICATORS

FUNCTION

Control Action

This determines the control action for the PID loop.


Programmed for direct action (cooling), the DLC
output power will increase if the Process value is
above the Setpoint value. Programmed for reverse
action (heating), the output power decreases when the
Process Value is above the Setpoint Value.

Dampening Time

The dampening time, entered as a time constant in


seconds, dampens (filters) the calculated output power.
Increasing the value increases the dampening effect.
Generally, dampening times in the range of onetwentieth to one-fiftieth of the controllers integral
time

(or

process

time

constant)

is

effective.

Dampening times longer than these may cause


controller instability due to the added lag effect.
Cycle Time

The cycle time, entered in seconds, is the combined


time of an on and off cycle of a time proportioning
control output. With time proportional output, the
percentage of control power is converted into output
on time of the cycle time value. (If the controller
calculates that 65% power is required and has a cycle
time of 10 seconds, the output will be on for 6.5
seconds and off for 3.5 seconds.) For best control, a
cycle time equal to one-tenth of the process time
constant, or less, is recommended.

Power Low Limit

These parameters may be used to control low limit


power due to process disturbances or set point
changes. Enter the safe output low power limits for
the process. At 0%, both OP1 and OP2 are off; at
100%, OP1 is on for heating ; and at -100%, OP2 is
on for cooling.

CM Envirosystems

Power High Limit

These parameters may be used to control high limit


power due to process disturbances or set point changes.
Enter the safe output low power limits for the process.
At 0%, both OP1 and OP2 are off; at 100%, OP1 is on
for heating ; and at -100%, OP2 is on for cooling.

P Band

Proportional band, entered as percent of full input


range, is the band from the set point where the
controller adjusts the percent output power based on
how close the process value is to the set point. For
temperature inputs, the input range is fixed per the
entered RTD type.
The proportional band should be set to obtain the best
response to a process disturbance while minimizing
overshoot. A proportional band of 0.0% forces the
controller into On/Off
Control with its characteristic cycling at set point.

I Time

Integral time is defined as the time, in seconds; it takes


the output power due to integral action alone to equal
the output power due to proportional action alone
during a constant process error. As long as the error
exists, integral action repeats the proportional action
each integral time. Integral action shifts the centre
point position of the proportional band to eliminate
error in the steady state. The higher the integral time,
the slower the response. The optimal integral time is
best determined during PID Tuning. If time is set to
zero, the previous Integral output power value is
maintained.

CM Envirosystems

Derivative time, entered as seconds per repeat, is the


time that the controller looks ahead at the ramping
error to see what the proportional contribution will be
and it matches that value every Derivative time. As
D Time

long as the ramping error exists, the Derivative action


is repeated by Proportional action every derivative
time. Increasing the derivative time helps to stabilize
the response, but too high of a derivative time, coupled
with noisy signal processes, may cause the output to
fluctuate too greatly, yielding poor control. Setting the
time to zero disables Derivative Action.
Press the Red button to start the Auto Tune feature.
Auto-Tune is a user-initiated function where the
controller automatically determines the Proportional
Band, Integral Time, Derivative Time, Digital Filter,
Control Ouput Dampening Time, and Relative Gain

Start Auto Tune

(Heat/Cool)

values

based

upon

the

process

characteristics. The Auto-Tune operation cycles the


controlling output(s) at a control point three-quarters of
the distance between the present process value and the
setpoint. The nature of these oscillations determines the
settings for the controllers parameters.
The controller will oscillate the controlling output for
four cycles. The cycling phase can be monitored from
the Auto-Tune Phase. The time to complete the AutoAuto-Tune Phase

Tune cycles is process dependent. The controller


should automatically stop Auto-Tune and store the
calculated values when the four cycles are complete
If the controller remains in Auto- Tune unusually
long, there may be a process problem. Auto-Tune
may be stopped by entering 0 in Auto-Tune Start.

CM Envirosystems

Auto-Tune Code

The Auto Tuning Code sets the PID profile typically


as per the different codes from 0 to 2.
Move to the previous page

Esc

Go back to menu

PID Control:
Introduction:
In PID Control, the controller processes the input and then calculates a
control output power value by use of a modified Proportional Band, Integral Time,
and Derivative Time control algorithm. The system is controlled with the new output
power value to keep the process at the setpoint. The Control Action for PID Control
can be set to reverse for heating (output on when below the setpoint) or direct for
cooling (output on when above the setpoint) applications. For heat and cool systems,
the heat (OP1) and cool (OP2) outputs can be used together in the PID Control. The
PID parameters can be Auto-Tune or Manual Tune to the process.

A Typical PID Response Curve:

CM Envirosystems

Auto Tune:
Auto-Tune is a user-initiated function where the controller automatically
determines the Proportional Band, Integral Time, Derivative Time, Digital Filter,
Control Output Dampening Time, and Relative Gain (Heat/Cool) values based upon the
process characteristics. The Auto-Tune operation cycles the controlling output(s) at a
control point three-quarters of the distance between the present process value and the
set point. The nature of these oscillations determines the settings for the controllers
parameters. Auto-Tune may be initiated at start-up, from setpoint or at any other
process point. However, insure normal process conditions (example: minimize unusual
external load disturbances) as they will have an effect on the PID calculations. AutoTune cannot be initiated while running a profile.
The controller will oscillate the controlling output(s) for four cycles. The cycling phase
can be monitored from the Auto-Tune Phase. The time to complete the Auto-Tune
cycles is process dependent. The controller should automatically stop Auto-Tune and
store the calculated values when the four cycles are complete. If the controller remains
in Auto- Tune unusually long, there may be a process problem. Auto-Tune may be
stopped by entering 0 in Auto-Tune Start.

Auto Tune Code:


The Auto Tuning Code sets the PID profile typically as per the different codes from 0 to
2

CM Envirosystems

Manual PID Adjustments:


In some applications, it may be necessary to fine tune the Auto-Tune
calculated PID parameters. To do this, a chart recorder or data logging device is
needed to provide a visual means of analyzing the process. Compare the actual
process response to the PID response figures with a step change to the process. Make
changes to the PID parameters in no more than 20% increments from the starting
value and allow the process sufficient time to stabilize before evaluating the effects of
the new parameter settings. In some unusual cases, the Auto-Tune function may not
yield acceptable control results or induced oscillations may cause system problems. In
these applications, Manual Tuning is an alternative.

Extra Settings:
Screen 01:

CM Envirosystems

BUTTONS/INDICATORS

FUNCTION

Temp Hold Back Value During This will hold the temperature SV till the PV Hold
Ramp

back value should match with SV during the


temperature ramp up/down.

Temp Hold Back Value For This will hold the temperature SV till the PV Hold
Seg Change

back value should match with SV during the segment


change.

Temp

Hold

During Soak

Back

Values This will hold the temperature SV till the PV Hold


back value should match with SV during the soak
period.

Move to the previous page


Esc

CM Envirosystems

Return to the previous menu

HMI Settings:
HMI Settings Menu Screen:

BUTTONS/INDICATORS

FUNCTION

Date & Time

Press this button to change the current date and time

Touch Cal

Press this button to calibrate the touch of the screen

Language

Press this button to change the Language settings in


the controller

CF Card

Press this button to check the status and format the


Compact Flash Card loaded in the HMI

Display

Pres this button to change the screen display settings

Internet Protocol

Press this button to edit the IP settings to interface


the controller to the web based browser.

Esc

CM Envirosystems

Go back to previous menu

Clock & Date Setup:


Press on the white edit box to change the Current Clock in HH:MM:SS
format and Date in DD/MM/YY format

Touch Calibration Screen:


The screen can be calibrated for touch by accessing this screen. Press the
squares which are displayed around the screen precisely.
Use this touch calibration only if any misalignment of touch problems occurs during
regular operation.

CM Envirosystems

Language Selection Screen:


Select the language options available by pressing the white edit box.

Compact Flash Memory Card Screen:


The controller is provided with a Compact Flash card of 1Gbytes and
this screen provides information of its status and an option of formatting the flash card
by pressing the white edit box is provided.

CM Envirosystems

Display Settings:
In the display settings screen the screen contrast and brightness can be
increased or decreased.

Network Settings
The Network settings screen displays the current IP settings for the
controller and the network settings can be edited to allow this controller to be accessed
by a single PC, LAN or via Internet using the Ethernet adapter.
Kindly ask your service provider or network administrator to provide an active
connection with Static IP to access this controller through the internet.
A PC with a standard web browser like Internet Explorer could be used to communicate
with this controller. Enter the IP address of the controller on the web address bar to
display the screen and click the screen just as the touch screen on your PC.

CM Envirosystems

BUTTONS/INDICATORS
HMI IP Address

FUNCTION
Displays the current IP address assigned to the
controller

HMI Subnet Mask

Displays the current Subnet Mask assigned to the


controller

HMI Gateway

Displays the current Gateway assigned to the


controller

Edit Network Settings

Press this button to edit the network settings in the


edit box below the button.

New IP Address

Enter the new IP Address which usually consists of


four group of numbers separated by periods such as
192.168.1.10

New Subnet Mask

Enter the new Subnet Mask which usually consists of

New Gateway

Enter the new Gateway which is usually

Cancel

Press this button to cancel the new settings and use


the existing old settings displayed in the box above
this button.

Apply

Press this button to apply the new settings entered in


the box at the side of this button.

Esc

CM Envirosystems

Return to previous menu

Printer Settings:
A serial printer can be connected directly to the controller to data log
basic test profile information like Profile Number, Time, Date, Process Value, Set Value
etc.

BUTTONS/INDICATORS
Data logging Time Interval

FUNCTION
Press the Cyan edit box to enter the time in seconds
between each print interval.

Test Print

Press this button to test the connected printer.

Start

Press this button to start printing.

Stop

Press this button to stop printing

I/O Monitor
By Pressing I/O Monitor screen in Main settings it will display the
Input & Output details in PLC.

CM Envirosystems

Fault Indication:
Chamber over Temperature:
If chamber temperature exits the chamber safety controller limit, it will show pop-up
screen below as shown.

By pressing Help it will display the HELP screen as shown in below.


By Pressing OK it will close the POP-UP Screen.

CM Envirosystems

Saturator over Temperature:


If saturator temperature exits the saturator safety controller limit, it will show pop-up
screen below as shown.

By pressing Help it will display the HELP screen as shown in below.


By Pressing OK it will close the POP-UP Screen.

CM Envirosystems

Solution Low Level Indicator:


If solution reaches low level in Reservoir tank, Float switch give the indication as
Solution low level, it will show pop-up screen below as shown.

By pressing Help it will display the HELP screen as shown in below.


By Pressing OK it will close the POP-UP Screen.

CM Envirosystems

Saturator Low Water:


If water level reaches minimum level in Bubbling tower, float switch will give the
indication as low saturator water level, it will show pop-up screen below as shown.

By pressing Help it will display the HELP screen as shown in below.


By Pressing OK it will close the POP-UP Screen.

CM Envirosystems

Air Supply:
If Air supply less than 4 kg/cm2 , Air pressure switch will cut the contact & give the
fault indication as shown in below screen.

By pressing Help it will display the HELP screen as shown in below.


By Pressing OK it will close the POP-UP Screen.

CM Envirosystems

Wick tank low water:


If water level reaches minimum level in wick tank, float switch will give the indication
as low water level in wick tank, it will show pop-up screen below as shown.

By pressing Help it will display the HELP screen as shown in below.


By Pressing OK it will close the POP-UP Screen.

CM Envirosystems

Air Supply:
If water level reaches minimum level in boiler tank, float switch will give the indication
as low water level in boiler tank, it will show pop-up screen below as shown.

By pressing Help it will display the HELP screen as shown in below.


By Pressing OK it will close the POP-UP Screen.

CM Envirosystems

Communication:
Types of Interface:

Ethernet:
Used for connecting the controller to the PC, for remote access or through LAN and
Internet.
Ethernet communications can be established at either 10 BASE-T or 100 BASE-TX.
The controllers RJ45 jack is wired as a NIC (Network Interface Card). For example,
when wiring to a hub or switch use a straight-through cable, but when connecting to
another NIC such as a router for LAN use a crossover cable.
The Ethernet connector contains two LEDs. A yellow LED in the upper right, and a
bi-colour green/amber LED in the upper left. The LEDs represent the following
statuses:

CM Envirosystems

RS232:
Used for connecting the serial printer for online data logging of basic test profile
parameters.
The controllers RS232 port is used with a RJ12 cable end and the printer end a
standard DB9 with a twist in the cable. The cable connections are as follows:

CM Envirosystems

RS485:
The controller has one RS422/485 port. This port can be configured to act as either
RS422 or RS485.

This port can be configured to communicate with a 2 wire communication device as


follows:

CM Envirosystems

This port can be configured to communicate with modular controllers as follows:

USB:
The USB is used to transfer data from the Compact Flash card. In order to establish
connection a driver must be installed on your computer. This driver is installed with
Crimson and is located in the folder C:\Program Files\Red Lion Controls\Crimson
2.0\Device\ after Crimson is installed. Once the driver is installed, connect the controller
with a USB Type B and the PC with a standard USB.

CAUTION:

WARNING - Do not connect or disconnect cables while power is applied unless area is
known to be non-hazardous. Usb port is for system set-up and diagnostics and is not
intended for permanent connection.

CM Envirosystems

RS232:
This RS232 port is connected to the PLC, which controls the input and outputs of the
chamber.

Compact Flash:
Compact Flash socket is a Type II socket that can accept either Type I or II cards. The
Compact Flash provided in the controller is 1Gbytes and cards with a minimum of 4
Mbytes and a maximum of 2 Gbytes with the controllers Compact Flash socket can be
used. The Compact Flash is used for configuration transfers and data logging.
A card reader attached to a PC can read information stored on a Compact Flash card
by the controller.

WARNING

Do not remove or insert the Compact Flash card while power is applied. Refer to
Front Panel LEDs.

CM Envirosystems

CHAPTER 6
FREQUENTLY ASKED QUESTION

The solution tank reservoir requires manual feeding; so how many hours can I
run the chamber uninterrupted?
The solution tank capacity of the Silver fog 250 is 60L, Silver fog
450 is 80L and Silver fog 1000 is 80L. The solution consumption would vary based
on the type of test carried out.

Can I use ordinary water or Tap water to run the chamber?


Ordinary or Tap water cannot be used to run the chamber because this
will damage the saturator and clog the internal systems. Also as per standard test
procedure only DM water is to be used to get correct and accurate results.

Im not going to use the chamber for a while. Is there anything I should do to
prepare it for storage?
Perform ALL the steps in the Preventive Maintenance Schedule before placing the
chamber into storage. This will ensure that the chamber will be ready to operate when
it is taken out of storage. If the chamber has a problem and is still under warranty,
these problems should be resolved before being placed into storage, since the warranty
period starts from the date of shipment. The chamber should be stored in a
conditioned environment. Do not store it outside or where it will be subjected to dirt
or excessive moisture.

I havent used the chamber for a while. Is there anything I should do to

prepare it for operation?


Perform ALL the steps in the Preventive Maintenance Schedule before placing the
chamber back into service. This will ensure that nothing has been damaged.

CM Envirosystems

CHAPTER 7
MAINTENANCE
! WARNING: Maintenance must be performed by properly trained personnel only.

7.1 Preventive Maintenance Intervals


Daily or As Needed
Clean chamber interior and exterior.
Listen for abnormal noise or vibration.
Clean the bottom of the inner Tank before loading the components.
Take care of the sensors while loading the components
Air regulator drain valve to be purged.

Every 3 Months
Check Electrical Loose Connection

Every 6 Months
Inspect the electrical compartment.
Drain the humidity system.
Clean the nozzle.
Verify the calibration of the controller.

How to Clean the Chamber Interior and Exterior?


Wipe or vacuum out all debris.
Clean surfaces with a damp cloth or mild detergent. Avoid cleaners that are
abrasive or leave a residue. Do NOT use steel wool.
Clean the exterior painted surfaces with a damp cloth or mild detergent. If you are
using a detergent, test a small inconspicuous area to make sure it does not damage
the finish.

CM Envirosystems

Cleaning the Atomizer

Remove the atomizer head and flush out with forced air.

Maintenance of the Air Regulator:

Flush out the moisture of the air regulator by pressing the drain knob.

7.2 Trouble Shooting


PROBLEM

PROBABLE CAUSE

CORRECTIVE
ACTION

Chamber over
temperature

SSR direct
Controller calls
continuous O/P

Replace SSR
Set Controller PID Or
Check Control O/P

Saturator Over
Temperature

SSR direct
Controller calls
continuous O/P

Replace SSR
Set Controller PID Or
Check Control O/P

Dry Heater Over


Temperature

SSR direct
Controller calls
continuous O/P

Replace SSR
Set Controller PID Or
Check Control O/P

DM Water Low Level

I/L S.Valve failed

Check & Replace

Solution Low Level

Flow switch Failed


No DM Water inlet
Relay is not Working

Check & Replace


Check DM Water I/L or
Storage Tank .
Check & Replaced

Relay not Working


Solution Low Level

Check & Replaced


Check & Replaced

Float is not working


Relay not Working
Solution Low Level

CM Envirosystems

Check & Replaced


Check & Replaced
Check & Replaced

PROBLEM

Humidity Desired not


achieving

The Controller Heat blip


is Constantly ON

PROBABLE CAUSE

CORRECTIVE
ACTION

Water is not connected


to the unit

Connect the continuous


water supply

Wet heater burnt due to


low water
Water control solenoid
not energized

Replace the wet heater

Solid
State
Relay
defective
The sensor is open
circuited/defective.
The over temperature
safety has failed, open
circuited.
A heating element has
failed.
The
controller's
Thermocouple
temperature sensor has
failed.

Check coil - replace if


burned
Check solenoid circuit
repair circuit
Replace the SSR
Replace
Replace

Replace
Replace
thermocouple

the

7.3 Silver Fog Corrosion Test Chamber Chart


MODEL

Internal Dimension
in mm

External Dimension
in mm

Solution
Reservoir (L)

Silver Fog 250

800W x 500D x 550H

1800w x 800D x 1200H

60

Silver Fog 450

850W x 700D x 800H

2000w x 950D x 1450H

80

Silver Fog
1000

1600W x 700D x 800H

2650w x 950D x1550H

80

CM Envirosystems

7.4 Air atomizing spray nozzle:

MAINTENANCE TIPS:

1.

Disassemble the spray nozzle as shown above.

2.

Change gasket to ensure proper sealing.

3.

Remove the atomizer head and flush out with forced air.

4.

Clean fluid cap using needle.

CM Envirosystems

7.5 Procedure to replace isoprene tube of peristaltic pump

Open the protective cover of peristaltic


pump

Press the button of tube holder down

Lift the tube from the roller and


the holders

Remove the tube from both ends

Replace with the new isoprene tube

CM Envirosystems

Put the new tube in the same position as


before and assemble in the holder

Place the new tube in to drive by


pressing the button as shown

Close the protective cover of peristaltic


pump

Note: Recommended to replace isoprene tube for every 350 hrs of test run

CM Envirosystems

You might also like