You are on page 1of 2

GS5-H1

Installation & General Inspection

Details

Date
Huawei Representative
TNL Representative
Site ID-GIS Code
Site Type (Shelter (Indoor/ Outdoor,Nano),
Civil, Mobility Shared)
Site Type (AC/Non-AC)

25/7/16
Mohd Zaid
Ravinder Thapa
GS5

Site on SDH,CEN
(ALU,Cisco,Hauwei,ZTE),MW,SDH L2 POI
Node Name
Vendor & Model
MSAN Uplink Port Details
MSAN Uplink Connectivity Type (Ethernet/
Fiber)
Software
Source A in VDc
Source B in VDc
Earthing Value in Ohm
Amps Rating of MCB's

Nanoshelter
AC
CEN - ALU
H1
Huawei MA5600T
0/9/0- & 0/10/0
Fiber
MA5600V800R016C00SPC101
53.9
54.0
1.3 ohm
63A

Sr No

Item

Slot

Serial Numbers

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

H801CITD
H80DCCPE
H80DCCPE
H80DCCPE
H80DCCPE
H80DCCPE
H80DCCPE
H808ASPB
H806VPGA
H802SCUN
H802SCUN
H806VPGA
H808ASPB
H80DCCPE
H80DCCPE
H80DCCPE
H80DCCPE
H80DCCPE
H80DCCPE

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

020LKLD0FB000290
023ANU10FA003940
023ANU10FA002703
023ANU10FA002789
023ANU10FA001652
023ANU10FA003771
023ANU10FA002720
020STCDMF9601650
022PRY10FA000906
021VDEDMFA602560
021VDEDMFA601782
022PRY10FA000951
020STCDMF9601464
023ANU10FA002653
023ANU10FA003702
023ANU10FA003746
023ANU10FA003827

Criteria

Description

Status

Remarks

Pass/Fail

Applicable for NEW RACk


only

Pass

H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W
H/W

installed shall be verified from NOC thru EMS


installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS
installed shall be verified from NOC thru EMS

Pass/Fail
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass

Physical Verification
19

Proper Installation/Mounting of Rack

OK

20

Proper Installation/Mounting of MSAN


Shelf

OK

21

Sufficient Space for Air Circulation

OK

22

No Physical Damage to MSAN


Shelf/Cards

OK

Pass

23

No Physical Damage to MSAN Cards

OK

Pass

24

Proper laying of Power Cables


Terminating of power cables to Dual
Power Supply
Earth Cable is properly Grounded
Proper Laying of Fiber/ Ethernet
Cables

OK

Pass

28
29

25
26
27

30
31
32

OK

Pass
Applicable for New Rack
only and if Space avialbale

Air-flow from bottom to TOP for MA5600T and from


Left to right for MA5603T

Cabinet to DCDB only

Pass

Pass

OK

Pass

OK

Pass

Proper Laying of Subscribers Cables

OK

Pass

All Cards are screw tight


Check the Labelling of Shelf, Power
Cables, Grounding Cables & Uplink
Connectivity Cables
All Alarms LEDs/ Lamps are in
healthy condition.
Unused Slots are close with Blank
pannel

OK

Pass

OK

Pass

OK

Should be Green

OK

Pass
Pass

Optical Power Level of Uplinking


Fiber Patch Cord

Uplink Port

Tx (db)

Rx(db)

Limit (db)

Pass/Fail

33

0/9/0

1/1/7

-6.110112

-6.187043

should be greater than -19

Pass

34

0/10/0

1/1/8

-5.800442

-5.412111

should be greater than -19

Pass

Mohd Zaid
Huawei Representative Signature

Ravinder Thapa
TNL Field Representative Signature

GS5-H1
S.No. Test Description

Criteria

AT Observation

Pass/Fail

ok
ok
ok
ok
ok
ok
ok
ok
ok
ok
ok
ok
Detail

pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass

1798

10.108.2.153

pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27

SW Reset-Verify of correct SW start up after reset


SSH-Verify Telnet is disabled in case of ALU. Only SSH is enabled
Uplink Description-Uplink Port descritpion should be there
No incremental CRC Errors on the link
No link should sync on half duplex
System date & time should be correct
No uplink alarms should be present
Alarm should come in case of Line card is removed
FAN/FAN Tray failure should come in case of FAN Tray removed
Alarm should come in case controller card is removed.
All unused Uplink Should be Shutdown
Idle session time out should be configured
TYPE
HSI VLAN
IPTV VLAN
Voice VLAN
Mgmt. VLAN ID
Mgmt. IP
Mgmt. Subnet Mask
Signaling VLAN ID
Signaling IP
Signaling Subnet
Signaling Gateway
Media VLAN ID
Media IP
Media Subnet
Media Gateway

System should come up with MA5600V800R016C00 version


User should not able to do Telnet
Uplink Must persent as per CRF UPLINK
Value of CRC should be 0
Uplink should sync on Full Duplex
Time should be correct and need to be Record
Need to verify from EMS , and EMS should not show any alarm on Uplink port
Need to verify from EMS , and EMS should show alarm if Board Removed
Need to verify from EMS , and EMS should show alarm if Board Removed
Need to verify from EMS , and EMS should show alarm if Board Removed
Must be shoutdown
10 Min

28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47

ADSL & VDSL2 Vectoring Services Speed testing= PPPoE mode


ADSL & VDSL2 Vectoring Services Speed testing=Bridge mode
ADSL & VDSL2 Vectoring Services Speed testing=Static user
Rate Limit Testing= 2, 4, & 8 Mb
Rate Limit Testing=16Mb
Rate Limit Testing=32Mb
Rate Limit Testing=40Mb
Rate Limit Testing=Mb
IPTV Services Testing with Snooping Setting (SD TV & HD TV)
WIFI Hot Spot Service Testing
Port Binding test
Basic Voice Call testing=Local OG
Basic Voice Call testing= Local IG
Basic Voice Call testing=Centrex - OG & IC
Basic Voice Call testing=Reverse Centrex - OG & IC
Basic Voice Call testing=Intra MSAN to MSAN -IC & OG
Basic Voice Call testing=Intra MSAN to SIP/FTTH-IC & OG
Three Party Conference Call
Call Transfer
Call Waiting
External Alarm
External Alarms verfication-Type of Alarms=High Temperature
External Alarms verfication-Type of Alarms=PP Fail
External Alarms verfication-Type of Alarms=Low Battery
External Alarms verfication-Type of Alarms=AC Main Fails
External Alarms verfication-Type of Alarms=Fire
External Alarms verfication-Type of Alarms=Door Open
External Alarms verfication-Type of Alarms=DG fail to Start
Service Assurance
Controller Card Redundancy via Command Line
Controller Card Redundancy via Manual Cards Jackout -JackIn
Power Card Redundancy via Manual Cards Jackout -JackIn
Power Source Redundancy
Chassis Power Restoration time
Dual Uplink Redundancy Via Command Line
Dual Uplink Redundancy Via Manual Patch Cord Jackout -JackIn
Monitoring
Visibility of Node in EMS

Subscriber should connect in PPPoe Mode


Subscriber should connect in Bridge Mode
Subscriber should work on Static IP
Subscriber should to get 2, 4 & 8 Mb
Subscriber should to get 16
Subscriber should to get 32
Subscriber should to get 40
Subscriber should to get 80
IPTV should run normal
Wifi Should work
Port Binding should work
outgoing should work
incoming should work
incoming should work & outgoing should work
Incoming should work & outgoing should work
Incoming should work & outgoing should work
Incoming should work & outgoing should work
Confrence should work
Call Transfer should work
Call waiting should work

ok
ok
ok
ok
ok
ok
ok
ok
iptv not available
ok
ok
ok
ok
ok
ok
ok
ok
ok
ok

pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass
pass

simulated Alarm should be reported to EMS


simulated Alarm should be reported to EMS
simulated Alarm should be reported to EMS
simulated Alarm should be reported to EMS
simulated Alarm should be reported to EMS
simulated Alarm should be reported to EMS
simulated Alarm should be reported to EMS

ok
ok
ok
ok
ok
ok
ok

pass
pass
pass
pass
pass
pass
pass

Service should not impact; <= 2 RTO


Service should not impact; <= 2 RTO
Service should not impact; <= 2 RTO
Service should not impact; <= 2 RTO
Service should not impact; <= 2 RTO
Service should not impact; <= 2 RTO
Service should not impact; <= 2 RTO

ok
ok
ok
ok
ok
ok
ok
Status
ok

pass
pass
pass
pass
pass
pass
pass

48
49
50
51
52
53
54
55
56
57
58
59
60
61
62

Mohd Zaid
Huawei Representative Signature

2018
33
3980
10.226.145.162
as per CRF detail

255.255.255.248
33
10.107.2.154

255.255.255.248
10.107.2.153

32
10.108.2.154

255.255.255.248

Node Should be Visible in EMS

Ravinder Thapa
TNL Field Representative Signature

pass