Self tuning filter (STF) based reference current generation strategy for
DSTATCOM to improve power quality under non-stiff Source
J.Ramesh1, T. Aruldoss Albert Victoire 2
1

Department of Electrical and Electronics Engineering, Jawaharlal Nehru Technological University, Kakinada, Andhra Pradesh, India

ABSTRACT
The Distribution Static Compensator (DSTATCOM) is
used for compensation of load in power distribution
network. Traditional reference current generation
method will be erroneous due to non stiff sources. In this
paper, a self tuning filter based reference current
generation method which is suitable for DSTATCOM
application with non stiff source has been proposed. The
DSTATCOM control is based on the use of self tuning
filters (STF) for the current generation and on a
modulated hysteresis current controller. The use of STF
instead of filters allows extracting directly the voltage
and current fundamental components in the - axis
without phase locked loop (PLL). Also the proposed
method enables DSTATCOM to have a reduced dc-link
voltage without compromising the compensation
capability. With the reduction in the dc-link voltage, the
average switching frequency of the insulated gate bipolar
transistor switches of the DSTATCOM is also reduced.
The efficacy of the new proposed method is verified by
MATLAB simulation software.

Distribution static compensator


(DSTATCOM), Dc-link voltage, (STF), Modulated
hysteresis current controller, Non-stiff source, Selftuning filter
Keywords

I.

INTRODUCTION

The proliferation of power electronic devices, non


linear loads, and unbalanced loads has degraded the
power quality in the power distribution network [1]. To
improve the quality of power, active power filters have
been proposed [2]. The distribution static compensator
(DSTATCOM) is a shunt active filter, which injects
currents into the point of common coupling (PCC) such
that harmonic filtering, power factor correction, and load
balancing can be achieved. In practice, the load is distant
from the distribution substation and is associated with
feeder impedance. In the presence of feeder impedance,
the inverter switching distorts both the terminal voltage
and the source currents. In this situation, the source is
termed as non stiff. If the same control algorithm for the

stiff sources is used for the non -stiff sources, the


reference currents generated will be erroneous and
modified reference current generation gives, however,
better results[3], [4]. The compensation performance of
any active filter depends on the voltage rating of dc link
capacitor. In general, the dc link voltage has much
higher value than the peak value of the line-to neutral
voltages. This is done in order to ensure a proper
compensation at the peak of the source voltage. In [5],
the authors discuss the current distortion limit and loss
of control limit, which states that the dc-link voltage
should be greater than or equal to resultant 6 times the
phase voltage of the system for distortion free
compensation. When the dc-link voltage is less than this
limit, there is insufficient resultant voltage to drive the
currents through the inductances so as to track the
reference currents. Reference value of the dc-bus
capacitor voltage mainly depends upon the requirement
of reactive power compensation of the active power
filter. The primary condition for reactive power
compensation is that the magnitude of reference dc-bus
capacitor voltage should be higher than the peak of
source voltage at the PCC [6]. With the high value of
dc-link capacitor [7]-[10], the voltage source inverter
(VSI) becomes bulky and the switches used in the VSI
also need to be rated for higher value of voltage and
current. This, in turn, increases the entire cost and size of
the VSI.
In this paper, a self tuning filter based reference
current generation have been proposed which is suitable
for DSTATCOM control under non stiff source
conditions. The STF is dedicated to extract the
fundamental component directly from electrical signals
in - reference frame. In the following, the frequency
and dynamic responses of the STF are mathematically
analyzed and discussed.
The major advantages of the STF are cited under:

www.ijsret.org

160

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN 2278 0882
Volume 5, Issue 3, March 2016

Operating adequately in steady state and transient


condition;
No phase delay and unity gain at the fundamental
frequency;
No PLL required;
Easy to implement in digital or analogue control
system.
A focus is made on the STF performances by
mathematical analysis under distorted voltage
conditions. The simulation studies are carried out to
verify the proposed concept, and detailed results are
presented.

II.

CONVENTIONAL TOPOLOGIES OF
DSTATCOM

2.1 System configuration


In this section, the conventional topologies of the
DSTATCOM are discussed in detail. Fig. 1 shows the
power circuit of the neutral clamped VSI topology-based
DSTATCOM which is considered the conventional
topology in this study. Even though this topology
requires two dc storage devices, each leg of the VSI can
be controlled independently and tracking is smooth with
less number of switches when compared to other VSI
topologies [11]. In this figure, vsa, vsb, and vsc are source
voltages. Similarly, v ta, v tb, and vtc are the terminal
voltages at the PCC. The source currents in three phases
are represented by isa, isb, and isc and load currents are
represented by ila, ilb, and ilc. The shunt active filter
currents are denoted by ifa, ifb, ifc, and io represents the
current in the neutral leg. Ls and Rs represent the feeder
inductance and resistance, respectively.
The interfacing inductance and resistance are presented
by Lf and Rf, respectively. The load constituted of both
linear and nonlinear loads are as shown in this figure.
The dc-link capacitors and voltages across them are
represented by Cdc1 = Cdc2 = C dc and Vdc1 = Vdc2 = V dc,
respectively. The current through the dc link is
represented by the idc. In this topology, the voltage
across each dc-link capacitance is chosen as 1.6 times
the peak value of the source voltages as given in [12].

Figure 1: Neutral clamped VSI topology based


DSTATCOM
2.2 Design of VSI parameters
The parameters of the VSI need to be designed with
utmost care for better tracking performance. The
principal parameters that ought to be taken into account
while designing conventional VSI are dc-link voltage
Vdc, dc storage capacitor Cdc, interfacing inductance Lf ,
and switching frequency fsw.
A detailed design
procedure of VSI parameters is given in [13]; based on
the following equations, the parameters of the
conventional VSI topology are selected. The dc-link
capacitor value is given by

2 X X / 2nT
1.8Vm 2 1.4Vm 2

Cdc

(1)

Where Vm is the peak value of the source voltage, X is


the kVA rating of the system, n is the number of cycles,
and T is the time period of each cycle. The interfacing
inductance is given by

Lf

1.6Vm
4hf sw m ax

(2)

Where

k1 2m 2 1
f sw max
k 2 4m 2

(3)

Where k1 and k2 are proportionality constants, fswmax is


the maximum switching frequency of the switch, fswmin is
minimum switching frequency of the switch, and m is
given by

www.ijsret.org

161

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN 2278 0882
Volume 5, Issue 3, March 2016

(4)

1 f sw max / f sw max

Consider a three-phase system with 230-V line-toneutral voltage. The hysteresis band h is taken as 0.5 A.
From (2), the interfacing inductance Lf is computed to be
26 mH. The base kVA rating of the system is taken as 15
kVA. Using (1), Cdc is computed and found to be 3300
F. The system parameters are given in Table I for the
conventional VSI topology.

2.3 Generation
currents

of

conventional

reference

In this paper, for conventional topology the reference


currents are generated using instantaneous symmetrical
component theory [14] and are given as

fa

fb

ila i

ilb i

sa

sb

v vtc vta
Plavg Ploss (5)
ilb tb

i * fc ilc i * sc ila

vtc vta vtb


Plavg Ploss

tk

i * fb ilb i * sb ilb

v tb1 v tcl v ta1


Plavg Ploss

i * fc ilc i * sc ilc

v tc1 v tal v tb1


Plavg Ploss

1
(6)

Where

(v

tk 1

) 2 , tan / 3

k a ,b ,c

The aforesaid algorithm gives balanced source currents


after compensation regardless of unbalanced and
distorted supply.

GENERATION OF NEW REFERNCE


CURRENT
WITH
NON
STIFF
SOURCE

3.1 Self tuning filter


Hong-sock Song studied the integration in the
synchronous reference frame [15]. The equation that he
has established for instantaneous signals is given under

Vxy (t ) e jt e jtU xy (t )dt

Where

v ta1 v tal v tc1


Plavg Ploss

III.

v vtb vtc
Plavg Ploss
ila ta

i * fa ila i * sa ila

, tan / 3

k a ,b ,c

Here, Plavg is the average load power, Ploss denotes the


switching losses in actual compensator and it is
generated using a capacitor voltage PI controller. The
term Plavg is obtained using a moving average filter of
one cycle window of time T in seconds. The term is
the desired phase angle between the source voltage and
current. In this paper, the load currents are unbalanced
and distorted; these currents flow through the feeder
impedance and make the voltage at PCC unbalanced and
distorted. However, if the voltages are unbalanced and
distorted, it is not at all feasible to get balanced and
sinusoidal currents after compensation using (5). To
eliminate this limitation of the algorithm, fundamental
positive sequence voltages v+ta1 (t), v+tb1 (t) and v+tc1 (t)
of the distorted terminal voltages are extracted. Now, the
voltages vta(t), vtb(t), and vtc(t) in (5) are replaced by
v+ta1(t), v+tb1(t), andv+tc1(t), respectively. Therefore, the
expressions for reference compensator currents become

(7)

Where U xy and Vxy are the instantaneous signals which


can be expressed by the transfer function after Laplace
transformation

Figure 2: Self-tuning filter

H ( s)

Vxy (t )
U xy ( s)

s j
s2 2

(8)
Here the constant K is introduced in the following
transfer function H(s), to obtain a STF with a cut-off

www.ijsret.org

162

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN 2278 0882
Volume 5, Issue 3, March 2016

frequency o, so the earlier transfer function H(s)


becomes

H ( s)

Vxy (t )
U xy ( s)

( s K ) jo
2
( s K ) 2 o

(9)
By introducing the constant K in H(s), the transfer
function magnitude is limited and mostly equal to one
for =o. Furthermore, the phase delay is equal to zero
for the frequency o. Input signals U xy(s) and the output
signals V xy(s) are modified by the following expressions

x ( s )

K o
K (s K )
x (s)
x ( s)
2
2
2
( s K ) o
( s K ) 2 o
(10)

x ( s )

K o
K (s K )
x (s)
x ( s)
2
2
2
(s K ) o
(s K ) 2 o

(11)
Where x (s) and x (s) can be either a current or a
voltage signal, respectively before and after filtering
Eqs. (10) and (11) can be expressed as follows:

K
x (s) x (s) o x (s)
s
s

K
x ( s) x ( s) x ( s) o x ( s)
s
s
x ( s)

This three-phase signal can be transformed into the twophase - reference frame by using the Concordia
transformation
1
2
3
2

1 x
a
2 x

3 b
x
2 c

(17)
From (14)-(16) and (17) we obtained the following
expressions
3
X 1 sin(t 1 )
2

x (t )

3 n
X h sin(ht h )
2 h2

(18)
x (t )

3
3
X 1 cos(t 1 )
X h cos(ht h )
2
2 h2

(19)
By replacing Eqs. (18) and (19) after Laplace
transformation into Eqs. (10) and (11) by taking the
inverse Laplace transformation, the following
instantaneous expressions for the STF outputs are
obtained
3.3 Harmonic Isolator

(12)
The load currents, iLa, iLb and iLc of the three-phase
system are transformed into the - axis as follows

(13)

The block diagram of the STF tuned at the pulsation o


is depicted in Fig.2. One can notice that no displacement
is introduced by this filter at the system pulsation.

i
i

3.2 Dynamic response of the STF under Distorted


conditions

xa (t ) X 1 sin(t 1 ) X h sin(ht h )
(14)

2 n
2

xb (t ) X 1 sin t 1 X h sin ht h
3 h2
3

(15)

2 n
2

xc (t ) X 1 sin t 1 X h sin ht h
3 h2
3

(16)

1
2

3
0

1
2
3
2

1 i
La
2 i

3 Lb

i
2 Lc

(20)

Figure 3: STF-based harmonic isolator

A three-phase distorted electrical signal x(t) can be


expressed in Fourier series by Eqs. (14)- (16) as follows
h2

1
2

3
0

x
x

As known, the currents in the - axis can be


respectively decayed into DC and AC components by

~
i i i
~
i i i

(21)

Then, the STF extracts the fundamental components at


the pulsation o directly from the currents in the -
axis. Then, the - harmonic components of the load
currents are computed by subtracting the STF input
signals from the corresponding outputs as shown in
Fig.3. The resulting signals are the AC components,

www.ijsret.org

163

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN 2278 0882
Volume 5, Issue 3, March 2016

~
~
i and i , which correspond to the harmonic components
[16] of the load currents iLa, iLb and iLc in the stationary
reference frame. For the source voltage, the three phase
voltages vsa, vsb and vsc are transformed to the -
reference frame as follows:

1
v
2

v
3

0

1
2
3
2

i*

v
v v
2

(22)

Then, we applied self-tuning filtering to these -


voltage components. This filter allows suppressing of
any harmonic component of the distorted mains voltages
and consequently leads to improve the performance of
the harmonic isolator. After computation of the
fundamental component v
and the harmonic

currents i we calculate the p and q powers as follows

p i v i v

~
i* i

v ~
q
v v2
2

(26)

v
pc
v v2
2

v
v v2
2

(27)

pc
(28)

The references currents are obtained from Eqs. (27) and


(28). Accordingly, a small amount of active power is
captivated from or released to the DC capacitor so as to
control the DC bus voltage [17] and [18]. Then, the filter
reference currents in the abc coordinates are defined
by
i

i
i

q i v i v

~p pc

With substitution of (24) into (25) and (26), we obtained

~
i* i

1 v
sa
2 v

3 sb

v
2 sc

*
fa
*
fb
*
fc

(23)

2 1
3 2
1

0

3 i

2 i
3

(29)

Where
3.4 Modulated Hysteresis Current Controller

p p ~
p, q q q~
With p , q fundamental components, ~
p , q~ alternative
components and the power components,

~p

and

q~ related to the same - voltages and currents are as


follows

p v
~
q~ v

v ~
i

v i

(24)

After adding the active power required for regulating DC


bus voltage, pc, to the alternative component of the
p , the current references in
instantaneous real power, ~

the - reference frame, i


are calculated by

i*

v
v
~p pc 2 2 q~
2
v v
v v
2

(25)

Now the current controller has to be considered. With


linear controllers using pulse width modulation (PWM)
techniques, a constant switching frequency can be
obtained and a well-defined harmonic spectrum can also
be obtained, but with limited number of dynamic
properties. Compared with linear controllers, non-linear
ones based on hysteresis strategies allows faster dynamic
response and better robustness with respect to the
variation of the non-linear load [19]. Nonetheless, with
non-linear current controllers, the switching frequency is
not constant and this technique generates a large side
harmonics band around the switching frequency. To fix
the switching frequency, one solution could consist in
using a variable hysteresis bandwidth. This solution
which implies the knowledge of the system model and
its parameters with enough precision is difficult to
implement experimentally. Here, we implemented a nonlinear current controller, so-called modulated hysteresis
current controller [20]. Fig.4. presents the modulated

www.ijsret.org

164

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN 2278 0882
Volume 5, Issue 3, March 2016

hysteresis current controller. The major principle of this


controller consists in adding to the error

3.5. DC bus voltage control


A DC bus controller is required to control the DC bus
voltage vdc and to compensate for the DSTATCOM
losses. The measured DC bus voltage vdc is compared
with its reference value v dc. The error is applied to a
proportional integral (PI) controller. So, the
compensating device can control the DC capacitor
voltage without any external power supply.

Figure 4: Modulated hysteresis current controller

IV.

Signal X (X = i - i f ) a triangular carrier signal (Tr) with


amplitude (Atr) and period (T). The carrier frequency is
selected which is equal to the desired switching
frequency for the voltage inverter. The resulting signal
(H) constitutes then the new reference of a traditional
hysteresis controller with a bandwidth of 2Bh. The
outputs of the hysteresis block are the switching pattern
of the voltage source inverter.

SIMULATION RESULTS

The simulation results for both the conventional and the


proposed topologies are presented in this section for a
lucid understanding and for a comparison between both
the topologies. The load currents and terminal (PCC)
voltages before compensation are shown in Fig. 6. The
load currents are unbalanced and distorted; the terminal
voltages are also unbalanced and distorted because of the
flow of these load currents through the feeder impedance
in the system. The Simulink model of DSTATCOM as
shown in fig .5. Simulation parameters as shown in
Appendix A

Fig. 5: Simulink model of DSTATCOM

www.ijsret.org

165

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN 2278 0882
Volume 5, Issue 3, March 2016

(a)
Fig. 8: Compensator filter currents

(b)
Fig 6: (a) Load currents before compensation (b)
Terminal voltage before compensation

Fig. 9: DC capacitor voltages (top and bottom)

4.1 Simulation results using conventional topology


The source currents after compensation are balanced and
sinusoidal as shown in the fig.7.These currents still
contain the switching frequency of the compensator. The
three-phase compensator currents are depicted in Fig. 8.
The dc-link voltages across the top and bottom dc-link
capacitors are shown in Fig. 9; using PI controller, the
voltage across both capacitors are maintained constant to
the reference value of 320 V as shown in the figure. The
terminal voltages contain the switching frequency
components of the inverter and are shown in Fig. 10.

Fig. 10: Terminal voltages after compensation


4.2. Simulation results using proposed topology
The source currents after compensation using proposed
topology are shown in Fig.11. The compensator currents
are displayed in Fig.12, which are identical to the
currents using the conventional topology. The dc-link
voltages across the top and bottom dc-link capacitors are
shown in Fig.13. The terminal voltages after
compensations are shown in Fig.14, which are free from
the switching frequency components of the inverter.

Fig. 7: source currents after compensation

www.ijsret.org

166

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN 2278 0882
Volume 5, Issue 3, March 2016

conditions. A self tuning filter based reference current


computation method suitable for DSTATCOM has been
suggested. This has the capability of compensating the
load at a lower dc-link voltage under non-stiff source.
Self-tuning filters have been introduced in the proposed
method instead of filters for both system voltages and
load currents. The use of this filter gives the satisfactory
performances since it perfectly extracts the harmonic
currents under distorted conditions. For the current
controller, we implemented the modulated hysteresis
current controller to obtain a fixed switching frequency
for the IGBTs. The simulation results have demonstrated
and comforted the major advantages of using STF and
modulated hysteresis current controller in the
DSTATCOM control. In conclusion, the proposed
control for DSTATCOM is very effectual in installation
on an actual power system under non stiff source
conditions.

Fig. 11: source currents after compensation

APPENDIX- A
Fig. 12: Compensator filter currents
System voltages: 230 V(L-L), 50 Hz; load: (1) Linear
load impedance Z la =34+j47.5 ,Z lb = 81+j39.6 ,Z lc
= 31.5 + j 70.9 ;Load (2) Nonlinear loads: Three phase
full bridge rectifier load feeding a R-L load of 150 300mH; VSI papameters: C dc=3300F, V dcref
=320V,Lf=26 mH, Rf=0.1 ; PI controller gains: K p=2,
K i=0.5; Hysteresis Band width 0.5 A

REFERENCES
Fig. 13: DC capacitor voltages (top and bottom)

Fig. 14: Terminal voltages after compensation

V.

CONCLUSION

This paper has discussed in detail the control and


performances of a DSTATCOM under non-stiff source

[1] M. Bollen, Understanding Power Quality Problems:


Voltage Sags and Interruptions. New York: IEEE Press,
1999.
[2] A. Sahoo and T. Thyagarajan, Modelling of facts
and custom power devices in distribution network to
improve power quality, in Proc. Int. Conf. Power Syst.,
2009, pp. 17.
[3] M. K. Mishra, A. Ghosh, and A. Joshi, Load
compensation for systems with non-stiff source using
state feedback, Electro Power Syst. Res., vol. 67, no. 1,
pp. 3544, 2003.
[4] A. Ghosh and G. Ledwich, Load compensating
DSTATCOM in weak ac systems, IEEE Trans. Power
Del., vol. 18, no. 4, pp. 13021309, Oct. 2003.
[5] B. T. Ooi, J. C. Salmon, J. W. Dixon, and A. B.
Kulkarni, A three phase controlled-current PWM
converter with leading power factor, IEEE Trans. Ind.
Appl., vol. IA-23, no. 1, pp. 7884, Jan. 1987.

www.ijsret.org

167

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN 2278 0882
Volume 5, Issue 3, March 2016

[6] Y. Ye, M. Kazerani, and V. Quintana, Modelling


control and implementation of three-phase PWM
converters, IEEE Trans. Power Electron.,vol. 18, no. 3,
pp. 857864, May 2003.
[7] G. S. Perantzakis, F. H. Xepapas, and S. N. Manias,
A novel four-level voltage source inverterInfluence of
switching strategies on the distribution of power losses,
IEEE Trans. Power Electron., vol. 22, no. 1,pp. 149
159, Jan. 2007.
[8] M. Routimo, M. Salo, and H. Tuusa, Comparison of
voltage-source and current-source shunt active power
filters, IEEE Trans. Power Electron., vol. 22, no. 2, pp.
636643, Mar. 2007.
[9] J. Liang, T. Green, C. Feng, and G. Weiss, Increasing
voltage utilization in split-link four-wire inverters, IEEE
Trans. Power Electron., vol. 24, no. 6, pp. 15621569,
Jun. 2009.
[10] V. George and Mahesh K. Mishra, Design and
analysis of user-defined constant switching frequency
current-control-based four-leg Dstatcom, IEEE Trans.
Power Electron., vol. 24, no. 9, pp. 21482158, Sep.
2009.
[11] H. Akagi and R. Kondo, A transformer less hybrid
active filter using a three-level pulse width modulation
(PWM) converter for a medium voltage motor drive,
IEEE Trans. Power Electron., vol. 25, no. 6,pp. 1365
1374, Jun. 2010.
[12] V. George and Mahesh K. Mishra, DSTATCOM
topologies for three phase high power applications, Int.
J. Power Electron., vol. 2, no. 2, pp. 107124, 2010.
[13] M. K. Mishra and K. Karthikeyan, Design and
analysis of voltage source inverter for active
compensators to compensate unbalanced and non-linear
loads, in Proc. Int. Power Eng. Conf., 2007, pp. 649
654.
[14] M. K. Mishra and B. Kalayan Kumar, A
DSTATCOM topology with reduced DC link voltage
rating for load compensation with non stiff source, IEEE
Trans. Power Electron., vol. 27, no. 3,pp. 12011211,
Mar. 2012.
[15] M.Abdusalam and Sharam Karimi, New digital
reference current generation for shunt active power filter
under distorted voltage conditions. Electric power
system research 79 (2009) 759-765.
[16] B. Singh, K. Al-Haddad, A. Chandra, A review of
active filters for power quality improvement, IEEE
Transactions on Industrial Electronics 46 ,960971,Oct
1999.
[17] S.A. Gonzalez, R. Garcia-Retegui, M. Benedetti,
Harmonic computation technique suitable for active
power filters, IEEE Transactions on Industrial
Electronics 54 27913279, Oct 2007.

[18] G.W. Chang, C.M. Yeh, Optimisation-based


strategy for shunt active power filter control under nonideal supply voltages, IEE Proceedings Electric Power
Applications 152 182190, Mar 2005.
[19] M.Montero, E.R. Cadaval, F. Gonzalez,
Comparison of control strategies for shunt active power
filters in three-phase four-wire systems, IEEE
Transactions on Power Electronics 22, 229236,Jan
2007.
[20] M.P. Kazmierkowski, L. Malesani, Current control
techniques for three-phase voltage source PWM
converters: a survey, IEEE Transactions on Industrial
Electronics 45 691703, 1998.