You are on page 1of 35

Single Packaged

Air Conditioner
SERVICE MANUAL
MODEL: LK-C090BC00
LK-C0909C00

Air Conditioner Service Manual

TABLE OF CONTENTS
Safety Precautions ............................................................................................................................3
Model Number Nomenclature ................................................................................................. 8
General Data ............................................................................................................................. 9
Dimensions ............................................................................................................................. 10
Refrigerant Circuit diagram....................................................................................................11
Wiring Diagram....................................................................................................................... 12
Trouble Shooting Guide......................................................................................................... 14
Electric Parts Trouble Shooting Guide................................................................................. 18
Feature of Controller............................................................................................................. 25
Exploded View and Replacement Parts List........................................................................ 31
Specification of Components................................................................................................ 33

2 Single Packaged Air Conditioner

Safety Precautions

Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Be sure to read before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following
indications.

WARNING

This symbol indicates the possibility of death or serious injury.

CAUTION

This symbol indicates the possibility of injury or damage to properties only.

Meanings of symbols used in this manual are as shown below.

Be sure not to do.


Be sure to follow the instruction.

WARNING
Installation
Do not use a defective or
underrated circuit breaker. Use
this appliance on a dedicated
circuit.

For electrical work, contact the


dealer, seller, a qualified
electrician, or an Authorized
Service Center.

Always ground the product.

There is risk of fire or electric


shock.

Do not disassemble or repair the


product. There is risk of fire or
electric shock.

There is risk of fire or electric


shock.

Install the panel and the cover of


control box securely.

Always install a dedicated circuit


and breaker.

Use the correctly rated breaker


or fuse.

There is risk of fire or electric


shock.

Improper wiring or installation


may cause fire or electric shock

There is risk of fire or electric


shock.

Service Manual 3

Safety Precautions
Use the specified wires to
connect the unit.

Do not install, remove, or reinstall the unit by yourself


(customer).

Be cautious when unpacking and


installing the product.

There is risk of fire or electric


shock.

There is risk of fire, electric


shock, explosion, or injury.

Sharp edges could cause injury. Be


especially careful of the case edges
and the fins on the condenser and
evaporator.

For installation, always contact


the dealer or an Authorized
Service Center.

Do not install the product on a


defective installation stand.

Be sure the installation area


does not deteriorate with age.

There is risk of fire, electric


shock, explosion, or injury.

It may cause injury, accident, or


damage to the product.

If the base collapses, the air conditioner


could fall with it, causing property
damage, product failure, and personal
injury.

Operation
Do not let the air conditioner run for
a long time when the humidity is very
high and a door or a window is left
open.

Take care to ensure that power


cable could not be pulled out or
damaged during operation.

Do not place anything on the


power cable.

Moisture may condense and wet


or damage furniture.

There is risk of fire or electric


shock.

There is risk of fire or electric


shock.

Do not plug or unplug the power supply


plug during operation.

Do not touch(operate) the


product with wet hands.

Do not place a heater or other


appliances near the power cable.

There is risk of fire or electric


shock.

There is risk of fire or electrical


shock.

There is risk of fire and electric


shock.

4 Single Packaged Air Conditioner

Safety Precautions
Do not allow water to run into
electric parts.

Do not store or use flammable gas


or combustibles near the product.

Do not use the product in a


tightly closed space for a long
time.

It may cause There is risk of fire,


failure of the product, or electric
shock.

There is risk of fire or failure of


product.

Oxygen deficiency could occur.

Gasolin

When flammable gas leaks, turn


off the gas and open a window
for ventilation before turn the
product on.

If strange sounds, or small or smoke


comes from product. Turn the breaker
off or disconnect the power supply
cable.

Stop operation and close the window in


storm or hurricane. If possible, remove the
product from the window before the
hurricane arrives.

Do not use the telephone or turn


switches on or off. There is risk of

There is risk of electric shock or


fire.

There is risk of property damage,


failure of product, or electric
shock.

When the product is soaked


(flooded or submerged), contact
an Authorized Service Center.

Be cautious that water could not


enter the product.

explosion or fire

Do not open the panel of the product


during operation. (Do not touch the
electrostatic filter, if the unit is so
equipped.)
There is risk of physical injury,
electric shock, or product failure.

There is risk of fire or electric


shock.

There is risk of fire, electric


shock, or product damage.

Ventilate the product from time to time when


operating it together with a stove, etc.

Turn the main power off when cleaning or


maintaining the product.

There is risk of fire or electric shock.

There is risk of electric shock.

Service Manual 5

Safety Precautions
When the product is not be used for a long time,
disconnect the power supply plug or turn off the
breaker.

Take care to ensure that nobody could step on or


fall onto the unit.

There is risk of product damage or failure, or


unintended operation.

This could result in personal injury and product


damage.

CAUTION
Installation
Always check for gas (refrigerant)
pressure after installation or repair of
product.

Install the drain hose to ensure


that water is drained away
properly.

Keep level even when installing


the product.

Low refrigerant levels may cause


failure of product.

A bad connection may cause


water leakage.

To avoid vibration or water


leakage.

90

Do not install the product where the noise or


hot air from the outdoor unit could damage
the neighborhoods.

Don't use people to lift and


transport the product.

Do not install the product where it


will be exposed to sea wind (salt
spray) directly.

It may cause a problem for your


neighbors.

Avoid personal injury.

It may cause corrosion on the product. Corrosion,


particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient
operation.

Having perfect vacuum process in the factory, our units don't have drier but have filter in the refrigerant circuit.
In case of recharging R-22 gas in the field,

"DRIER" must be installed on the liquid line which is connected from discharge part of condenser to intake
part of evaporator. Because the refrigerant circuit is capable of containing water with imperfect vacuum.

6 Single Packaged Air Conditioner

Safety Precautions

Operation
Do not expose the skin directly to cool air for long
periods of time. (Don't sit in the draft.)

Do not use the product for special purposes, such as preserving


foods, works of art, etc. It is a consumer air conditioner, not a
precision refrigeration system.

This could harm to


your health.

There is risk of
damage or loss
of property.

Do not block the inlet or outlet of


air flow.

Use a soft cloth to clean. Do not


use harsh detergents, solvents,
etc.

Do not touch the metal parts of the


product when removing the air filter.
They are very sharp!

It may cause product failure.

There is risk of fire, electric


shock, or damage to the plastic
parts of the product.

There is risk of personal injury.

x
Wa Thinner

Do not step on or put anything


on the product. (outdoor units)

Always insert the filter securely. Clean


the filter every four weeks or more
often if necessary.

Do not insert hands or other objects


through the air inlet or outlet while the
product is operated.

There is risk of personal injury


and failure of product.

A dirty filter reduces the efficiency of


the air conditioner and could cause
product malfunction or damage.

There are sharp and moving parts


that could cause personal injury.

Do not drink the water drained from the product.

Use a firm stool or ladder when cleaning or


maintaining the product.

It is not sanitary and could cause serious health


issues.

Be careful and avoid personal injury.

Service Manual 7

Model Number Nomenclature

Model Number Nomenclature


LK-C090BC00
1 2 3 4 5 6 7 8 9 10 11
CODE

Classification

Spelling
(English)

L: R22 & made in Changwon

Manufacturing Place &


Refrigerant
Combination
Product Type

Spelling
(English)

K: Single Packaged Type(Roof top)

Indoor/Outdoor

Spelling
(English)

-: Set or Single

Cooling only / Heat


pump / Inverter

Spelling
(English)

C: Cooling Only

Cooling Capacitor

Number

Cooling Capacitor (3~5RT: Net Cooling Capa.


6~30RT: Gross Cooling Capa.)
EX) 36,000 Btu '036'
120,000 Btu '120'

Power Configuration

Number &
Spelling

9: 380V / 60Hz / 3
B: 220V / 60Hz / 3

Air Flow Type

Spelling
(English)

For Single Packaged(Base on outdoor air discharge)


C: Convertible, H: Horizontal,

SEER Grade

Number &
Spelling

Character

5, 6, 7

10

11

Development
Sequence

Number &
Spelling

8 Single Packaged Air Conditioner

Inscription Method

Type

SEER

MICOM Control
Mechanical Cont.

10 11 12 13 14 15
0 1 2 3 4
5
A B C D E F

Development Sequence

In Case of Light
Commercial &
Commercial Unit, mark 0

General Data

General Data
Nominal ton
Models
Electrical Data ARI Net Cooling Capacity

Performance

Features

Compressor
Outdoor Coil

Voltage
M.C.A(with standard motor)
Cooling
Power Input
Cooling
Air Circulation
Nominal CFM
EER
Cooling
Sound Rating
Cooling
Wired Remote Controller
Time Delay Safety Function
Cooling Operation Mode
Heating Operation Mode(with E/Heater)
Soft Dry Operation
Timer Setting (24-Hour on/off)
Auto restart mode
Humidifier function
Test function
Defrost
Hot Start
Self-Diagnosis Function
Phase reversal error sensing
Phase loss sensing
Filter type
Type
Quantity
Type
Tube size(O.D)

(Ton)
(BTU/hr)
(W)
(Kcal/h )
(V,PH)
(Amps)
(Watt)
CFM
(BTU/hr.W)
bell

Row/FPI
Lengh
Face area
Indoor Coil

Type
Tube size(O.D)
Row/FPI
Lengh
Face area

Type
No. Used/Diameter(in.)
Drive Type
CFM
No. Motor/Motor output(Hp)
Motor RPM
Indoor Fan
Type
No. Used
Diameter/Width(in.)
Drive Type/Motor Step
No.motors
Motor output(standard/oversized)
Motor rpm(Standard/oversized)
Drain Connection Size(in.)
Dimensions
Unit (WxHxD)

(inch)
(mm)
(inch)
(mm)
(sq.ft)
(m2)
(inch)
(mm)
(inch)
(mm)
(sq.ft)
(m2)

Outdoor Fan

Weight

net

(inch)
(mm)
(kg)
(lbs)

7.5
LK-C090BC00
90,000
26,376
22,679
220V,3
43.0
10,000
3,000
9
8.5

LK-C0909C00
90,000
26,376
22,679
380V,3
26.0
10,000
3,000
9
8.5
O
O
O
O
O
O
O
O
O
O
O
O
washable & Anti-fungus
Scroll
2
High efficiency
9/32
7
3R/17FPI
54 1/8
1,375
14.3
1.33
High efficiency
3/8
9.52
3R/16FPI
33 15/32
850
8.83
0.82
Propeller
2EA/18"
Direct
3,900
2/0.4
1,130
centrifugal blower fan
1EA
13"/13"
Belt/1
1EA
1.5/3Hp
840
3/4
64 3/16 x 42 x 43 11/16
1630 x 1067 x 1109
290
639

1) Test Condition of ARI Rated Cooling Capacity :


Ambient:95F , Air entering temperature : 80F DB and 67F WB
2) ARI standard
210/240 or 360 for EER
270
for Sound
3) Filters are standard supply.

Service Manual 9

Dimensions

Dimensions
LK-C090*C**
Unit Dimensions(Figure 1B)
Unit : Inch(mm)
UNITS

7.5RT

A
B
C
D
E
F
G

42(1,067)
43 11/16(1,109)
64 3/16(1,630)
41 12/16(1,061)
7 5/16(185)
2 6/16(60)
2 15/16(70)

CLEARANCE 36"

CLEARANCE 18"
(HORIZONTAL)
CLEARANCE 32"
(DOWN FLOW)

100
Drain Connection Hole 3/4"

1115

Figure 1A
CLEARANCE 34"

F
A

E
Center line of hole
G
D
1" Dia. hole control wires
1 1/2" Dia. hole power wires
1

1 /2 "

B
C

Figure 1B

Dia. hole other purpose

CLEARANCE 48"

Horizontal Application Unit(Figure 1C)


Rear view showing duct opening for horizontal air flow.
Unit : Inch(mm)

14 13/16(377)
9 4/16(235)
10 15/16(278)
2 7/16(62)
9 6/16(136)
22 9/16(700)
20 4/16(514)

RETURN

7.5RT

A
B
C
D
E
F
G

SUPPLY

UNITS

Figure 1C

(266)
(235)

RETURN

SUPPLY

(352)

27 9/16(700)
20 4/16(514)

(159)

A
B

3 13/16(97)

10 8/16

7.5RT

9 4/16

UNITS

Unit : Inch(mm)

13 14/16

Unit : Inch(mm)

Top view

6 4/16

Down flow application unit (Figure 1D)

313/16(97)

Figure 1D

10 Single Packaged Air Conditioner

Refrigerant Circuit Diagram

Refrigerant Circuit Diagram


Service Valve

Low Pressure Switch

Service Valve
Suction Line
Comp A

Comp B
Capilliary
Outdoor Coil

High Pressure Switch

Indoor Coil

Circuit A
Circuit B

: Refrigerant Flow

Service Manual 11

Wiring Diagram

Wiring Diagram
LK-C090BC00
CAUTION

USING ELECTRIC
HEATER(OPTION)

The unit can sense phase reversal error & phase loss
with micro processor. If there's a phase problem on
the unit, the micro processor stop the unit and show
error message on the LCD wired remote controller.
Comply with the service manual and check power connection.
But all electrical work shall only be done by qualified
personel in consideration of the current safety
regulation.

TS

EH
R
(U)
T
S
(V) (W)

3
3WIRE
220V
60Hz
POWER
SUPPLY

TS

EH

BK

T2(V)

WH

T3(W)

RD

RD

BK
WH

BK
T1(U)

COMP
(A)

BK
WH
RD

IN
MOTOR

BK
WH
RD

MAGNETIC CONTACTOR
MOTOR,INDOOR

BK
WH
RD
WH
BK

BK

MAGNETIC CONTACTOR(A)

(B)
(A)
CN_COMP

Ry

BK

WH

WH

(OUT IN)

(5A 250V)

WH

T3(W)

RD

THERMISTOR
IN(A)

BK
WH
RD

4 3
TERMINAL
BLOCK

HIGH PRESSURE
SWICH(B-Cycle)
HIGH PRESSURE
SWICH(A-Cycle)

1
TERMINAL
BLOCK

BL
WH

BK

CN_REMO

WH

CN_ZON

LOW PRESSURE
SWICH(A-Cycle)

THERMISTOR
OUT AIR

RD
BL

CN_L/P

LOW PRESSURE
SWICH(B-Cycle)

RD

CN_CC

MAGNETIC CONTACTOR(D)

YL

CN_H/P

WH

THERMISTOR
IN(B)

CN_TEMP_OUT

BK

T2(V)

THERMISTOR
RETUTN AIR
(OPTION)

CN_A_CYCLE

(OUT IN)

T1(U)

CN_THMO

COMP
(B)

CN_RETURN_AIR CN_B_CYCLE

CN_BYPASS

FUSE

WH

MAIN PCB ASM

Ry

WH

TERMINAL BLOCK

R
(U)
(T1)

Ry

YL

S
(V)
(T2)

T(W)

CN_HUMID

BK
BK
WH
WH
RD
RD

CN_PHASE

R(U)
S(V)

CN_ECONO

3
3WIRE
220V
60Hz
POWER
SUPPLY

OUT1 OUT2)
CN_FAN

Ry

T
(W)
(T3)

(IN

Ry

BR

Ry

250V/3.15A
CN_POWER
N

Ry

BR

FUSE

CN_HEATER

Ry

BK

BR
YL

BK

BK

YL

YL

BR
OR

BR
OR

BK

BK

BK

BK

RD

TERMINAL
BLOCK

CAPACITOR

BR
RD
YL

FIRE
ALARM

2
4

HUMIDIFIER

CANNOT BE USED WHEN


USING THERMOSTAT

3854A20290G

12 Single Packaged Air Conditioner

TERMINAL 3
BLOCK
3WIRE
T(W)
220V
S(V)
60Hz
POWER
R(U)
SUPPLY

REMOVE JUMP WIRE WHEN


CONNECTING FIRE ALARM
SYSTEM

POWER RELAY
(AC 24V)

BR
OR

WH

MOTOR
OUT
(B-1)

BR
OR

CAPACITOR

POWER RELAY2
MOTOR,OUTDOOR1

MOTOR
OUT
(A-1)

YL

YL

REMOTE
CONTROLLER

FIRE ALARM
(AC 24V)

FIELD
INSTALLATION

NOTE
FIELD WIRING
FACTORY WIRING

BK:BLACK
RD:RED
BR:BROWN WH:WHITE
OR:ORANGE YL:YELLOW
BL:BLUE

Safety Precautions

LK-C0909C00
CAUTION

USING ELECTRIC
HEATER(OPTION)

The unit can sense phase reversal error & phase loss
with micro processor. If there's a phase problem on
the unit, the micro processor stop the unit and show
error message on the LCD wired remote controller.
Comply with the service manual and check power connection.
But all electrical work shall only be done by qualified
personel in consideration of the current safety
regulation.

TS

EH
R
(U)

3
3WIRE
380V
60Hz
POWER
SUPPLY

T
S
(V) (W)

TS

EH

T1(U)

BK

T2(V)

WH

T3(W)

RD

RD

BK
WH

BK

COMP
(A)

BK
WH
RD

IN
MOTOR

BK
WH
RD

MAGNETIC CONTACTOR
MOTOR,INDOOR

BK
WH
RD
WH
BK

BK

MAGNETIC CONTACTOR(A)

Ry

(B)
(A)
CN_COMP

WH

TERMINAL BLOCK

Ry

BK

WH

WH

(OUT IN)

(5A 250V)

WH

T3(W)

RD

THERMISTOR
IN(A)

BK
WH
RD

4 3
TERMINAL
BLOCK

HIGH PRESSURE
SWICH(B-Cycle)
HIGH PRESSURE
SWICH(A-Cycle)

2
1
TERMINAL
BLOCK

BL
WH

BK

CN_REMO

WH

CN_ZON

LOW PRESSURE
SWICH(A-Cycle)

THERMISTOR
OUT AIR

RD
BL

CN_L/P

LOW PRESSURE
SWICH(B-Cycle)

RD

CN_CC

MAGNETIC CONTACTOR(D)

YL

CN_H/P

WH

THERMISTOR
IN(B)

CN_TEMP_OUT

T2(V)

THERMISTOR
RETUTN AIR
(OPTION)

CN_A_CYCLE

(OUT IN)

BK

CN_THMO

COMP
(B)

T1(U)

CN_RETURN_AIR CN_B_CYCLE

FUSE

CN_BYPASS

WH

MAIN PCB ASM

Ry

YL

R
(U)
(T1)

S
(V)
(T2)

T(W)

CN_HUMID

BK
BK
WH
WH
RD
RD
BK
BK

CN_PHASE

R(U)
S(V)

CN_ECONO

3
4WIRE
380
60Hz
POWER
SUPPLY

OUT1 OUT2)
CN_FAN

Ry

T
(W)
(T3)

(IN

Ry

BR

Ry

250V/3.15A
CN_POWER
N

Ry

BR

FUSE

CN_HEATER

Ry

BK

BR
YL

BK

MOTOR
OUT
(B-1)

YL

BR
OR

BR
OR

BK

BK

BR
RD
YL

WH

YL

TERMINAL
BLOCK

CAPACITOR

FIRE
ALARM

2
4

HUMIDIFIER

CANNOT BE USED WHEN


USING THERMOSTAT

3854A20290H

TERMINAL
BLOCK
3
N
4WIRE
T(W)
380V
S(V)
60Hz
POWER
R(U)
SUPPLY

REMOVE JUMP WIRE WHEN


CONNECTING FIRE ALARM
SYSTEM

POWER RELAY
(AC 24V)

BK

RD
CAPACITOR

BK

BR
OR

POWER RELAY2
MOTOR,OUTDOOR1

BR
OR

BK

YL

MOTOR
OUT
(A-1)

YL

REMOTE
CONTROLLER

FIRE ALARM
(AC 24V)

FIELD
INSTALLATION

NOTE
FIELD WIRING
FACTORY WIRING

BK:BLACK
RD:RED
BR:BROWN WH:WHITE
OR:ORANGE YL:YELLOW
BL:BLUE

Service Manual 13

Troubleshooting Guide

Troubleshooting Guide
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING

MINIMUM

MAXIMUM

220V

198V

242V

380V

342V

418V

1. No cooling and heating operation performed


1) Both the blower and the compressor do not work
WHAT TROUBLED
Other parts except the
unit

COMPLAINTS

HOW TO CHECK

REMEDY

Electric supply interrupted


Defective power wiring
Cut off power fuse

Measure power sypply


with a tester in case that
the same power source is
supplied to other
equipment except the unit,
what and where troubled
can be discovered by
checking the operation of
other equipment.

Too low voltage

Measure it with a tester.

Check the power source.


Use a thick cable if
necessary.

Magnetic Contactor for


compressor & fan motor

Control point is on
condition of "OFF" due to
trouble.

Make short-circuit, then


measure it with tester.

Replace it if necessary.

Operating switch

Troubled or defective
contactor

Check it with the eyes or


tester.

Repair or replace it.

Repair a switch box


and relative instrument.
Replacement of fuse
Request a power
supplier to repair.

2) Only Indoor blowers do not work


WHAT TROUBLED
Motor

Electric wiring

COMPLAINTS
Over heated
Wiring short
Cut- OFF of wiring
Short circuited on
operation

14 Single Packaged Air Conditioner

HOW TO CHECK

REMEDY

Check it with tester

Repair or replace it.

Check it with a tester.

Rewiring or Repair.

Troubleshooting Guide

3) Only outdoor fan does not work


WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

Motor

Over-heated
Wire short

Check how it is insulated.

Repair or replace it.

Electric Wiring

Cut off of wiring

Check it with a tester.

Rewiring or repair.

Short circuited on
operation
Capacitor

Defected

Check it with tester.

Replace it.

4) Only compressor does not work


WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

Magnetic switch for


compressor motor

Defective contact,
magnetic coil troubled.

Check it with the eyes on


with a tester.

Repair or replace it.

Compressor motor

Troubled over-heated
(layer short)

Check how it is insulated.

Replace or repair the


compressor.

High pressure switch

Troubled or defective
contact or operating

Check it with a tester.

Replace it if
necessary.

Electric circuit

Defective connection or
disconnection of the circuit
for compressor.

Check it with a tester.

Rewiring or push
reset button.

Service Manual 15

Troubleshooting Guide

2. The Units discontinue after the operation started


WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

Outdoor coil

Coil is dirty *1

Checking

Wash it by means of
something like chemical
washing.

In-condensable gas
blended.

Air intruded into the


refrigerant pipe line *1

In the event that


difference between the
saturating temperature
corresponding to high
pressure and the
temperature of air
discharged from the
outdoor coil is more than
15C, incondensable gas
may be blended.

Extract air by vacuum


pump, then replenish
(charge) the refrigerant.

Improper adjustment

Check it with a pressure


gauge.

Read just it to normal


operating pressure.
(Note)
Don't alternate the
specified adjusting
pressure. If the adjusted
pressure exceed the
specified range, it will
cause a great accident.

A shortage of refrigerant
amount. * 2

Check pressure

Replenish the
refrigerant. Repair the
spot where it is leaked.

Reverse rotation of fan


Obstacle

Confirm the wind blowing


out upward.

Air short circuit *1

Check it with eyes.

If reversed, connect
interchanged wires to
each terminal.
Power wirings.

High pressure switch

Refrigerant

Outdoor Fan

Note: Use an appropriate measuring instrument for readjustment.


*1: High-pressure switch moves.
*2: Low- pressure switch moves.

16 Single Packaged Air Conditioner

Troubleshooting Guide

3. The unit is working, but not cooling and heating sufficiently


(Both blower and compressor are working)
WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

Load

Much Cooling or Heating


load

Heat load increased.


Window or door has many
cracks or gaps.

Do necessary disposal
respectively.

Air flow

Obstacle disturbs Intake


of uniform airflow.

Checking

Correct it.

Short air volume

Reverse rotation of
blower.

Checking

Correct it.

Refrigerant

Shortage in the charged


refrigerant.

Coil inlet pipe is frosted

Recharge it.
(Repair the leakage spot).

Air passage

Improper or foreign bodies

Checking

Correct or clear the


foreign bodies.

Air filter

Clogged with dust

Checking

Cleaning

4. All the functions are performed as specified, but very noisy and vibrant
WHAT TROUBLED
Compressor

Blower

COMPLAINTS

HOW TO CHECK

REMEDY

Liquid refrigerant flooding


back from the evaporator.

Check for refrigerant over-charge.


Check to see if the intake air temperature is
extremely cold.
Check for insufficient air flow quantity.

Faulty Discharge valve


and suction valve.

Checking

Replace the
compressor

Fan broken.

Checking

Repair or replace it.


Clear the foreign bodies.

Foreign matters intruded.


Screws

Looseness or fail-off of
screws

Checking

Correct

Electric troubles
(Magnetic contactor)

Defective contact.
Defective contact point.
Rusting and foreign
matters in the iron core
contact face. Defective
contact of the
operating switch.

Checking

Repair and clean or


replace it.

Others

Improper installation

Checking

Correct it.

Service Manual 17

Electronic parts Troubleshooting Guide

Electronic parts Troubleshooting Guide


Possible trouble 1
Is the input voltage of
Main PCB AC220V?

: The unit does not operate.


NO

1. Check the Fuse.


2. Check the wiring of AC220V.

YES

Is the output voltage


of IC03D(7812 ) on the
main PCB DC5V?

NO

1. Exchange IC03D(7805) on
the main PCB.

YES

Is the output voltage


of IC01A(7036) on the
main PCB DC5V?

NO

1. Exchange IC01A(7036) on
the main PCB.

YES

OSC01B vibration?

NO

1. Exchange OSC01B.
2. Check the pattern around
OSC01B on the main PCB.

YES

1. Exchange main PCB ASS'Y

Possible trouble 2

Is the power ON?

: The remote-controller does not operate.

NO

1. Check the FUSE.


2. Check the input voltage of
Main PCB ASS'Y.

YES

Is the input voltage


of remote-controller
DC12V?

NO

YES

1. Exchange remote-controller
2. Check or exchange the Main
PCB ASS'Y.

18 Single Packaged Air Conditioner

1. Check or exchange the IC03D


on the Main PCB.
2. Check or exchange the
Connector (RED, BROWN)
of the remote controller.

Electronic parts Troubleshooting Guide

Possible trouble 3

: Key input of remote-controller does not respond.

Is the connection between


MAIN PCB and remote-controller
correct?

NO

1. Check or repair Connector wiring.


2. Exchange the Connector.

YES

Is any key on the remote-controller


keeping pressed?

YES

1. Replace the pressed key.


2. Exchange the Knob or Key.

YES

1. Remove cause of Check.

NO

Is there Check(F**) on
the remote controller LCD?
NO

Is the input power voltage of


remote-controller DC12V?

NO

1. Check 220V Power on the


MAIN PCB.

YES

Is there OSC01B vibration


on the remote-controller
PCB?

NO

1. Exchange OSC01B
2. Check the pattern around OSC01B
on the remote-controller PCB.

YES

Do Keys have troubles?

YES

1. Check Keys.
2. Repair or exchange Key.

NO

Exchange remote-controller.

Possible trouble 4
Are there trouble in
LCD parts?

: LCD display on the remote-controller shows some trouble.


YES

1. Check crack, damage of LCD.


2. Check LCD pattern.

NO

Is there trouble in the


remote-controller PCB
ASS'Y?
NO

YES

1. Check or repair all IC with


dust or moisture on the PCB.
2. Exchange remote-controller
PCB.

Exchange remote-controller.

Service Manual 19

Electronic parts Troubleshooting Guide

Possible trouble 5
Is the unit operating?

: No cooling operation performed.


NO

1. Press power ON/OFF button.

YES

Is the cooling mode?

NO

1. Press cooling operation key.


2. After reenergizing power supply,
press power "ON/OFF" button.

NO

1. Set following.
'Set Temp. < Room Temp.'

YES

Set Temp. < Room Temp.?

YES

Is the output
voltage of IC03D on the MAIN
PCB DC5V?

NO

1. Check or exchange IC03D


on the MAIN PCB.

YES

Is the output
voltage of IC01M's 11,12(COMP B)PIN
on the MAIN PCB DC0V?

NO

1. Check or exchange IC01M.


2. Check 3-minutes time delay.

YES

Is the voltage
between A/B(COMP B) of CN-COMP
and NEUTRAL 220V?

NO

1. Check or exchange RY4/RY5(COMP B).

YES

Is the magnetic contactor


for compressor ON?

NO

YES

1. Check Compressor and


Capacitor for Compressor.
NOTE: 3 model has not capacitor for compressor.

20 Single Packaged Air Conditioner

1. Check the wiring of Magnetic


contactor.
2. Exchange Magnetic contactor.

Electronic parts Troubleshooting Guide

Possible trouble 6

Is the heater operation?

: No heater operation performed.


NO

1. Select heater operation mode.

YES

Is the heater LCD "ON"?

NO

1. Reconnecting power supply.


Press Heater Key.

NO

1. Set following.
'Set temp. > Room temp.'

YES

Set temp. > Room temp.?

YES

Is the output
voltage of IC03D on the
MAIN PCB DC5V?

NO

1. Check or exchange IC03D,


IC02D on the MAIN PCB.

YES

Is the output
voltage of IC02M's 15, 16PIN on the
MAIN PCB 0V?

NO

1. Check or exchange IC02M.

YES

Is the voltage
between A/B(Heat B) of CN-HEAT
and NEUTRAL 220V?

NO

1. Check or exchange RY13/RY14(Heat A, B).

YES

Is the magnetic contactor for


heater ON?

NO

1. Check the wiring of Magnetic


contactor.
2. Exchange Magnetic contactor.

YES

Check or exchange E/Heater.

Service Manual 21

Electronic parts Troubleshooting Guide

Possible trouble 7

Is the indoor fan operation?

: No humidifier operation performed.


NO

1. Press cooling or fan operation


or heater operation key.

YES

Is the HUMID LCD "ON"?

NO

1. Press humidifier Key.

YES

Is the output
voltage of IC03D on the
MAIN PCB DC5V?

NO

1. Check or exchange IC03D.


IC02D on the MAIN PCB.

YES

Is the output
voltage of IC01M's 10PIN on
the MAIN PCB 0V?

NO

1. Check or exchange IC01M.

YES

Is the voltage
between 1PIN of CN-HUMID and
NEUTRAL 220V?

NO

1. Check or exchange RY3.

YES

Is the magnetic
contactor for humidifier ON?

NO

YES

Check the humidifier.

22 Single Packaged Air Conditioner

1. Check the wiring or Magnetic


contactor.
2. Exchange Magnetic contactor.

Electronic parts Troubleshooting Guide

Possible trouble 8
Is the unit operating?

: Indoor motor does not operate.


NO

1. Press power ON/OFF button.


2. Reconnect the power supply.

YES

Is the output
voltage of IC02M's 14PIN on
the MAIN PCB 0V?

NO

1. Check or exchange IC01M.

YES

Is the voltage
between 1PIN(IN) of CN-FAN(IN) and
NEUTRAL 220V?

NO

1. Check or exchange RY10.

YES

Is the "Power relay" for


indoor motor ON?

NO

1. Check the wiring of


"Power relay".
2. Exchange "Power relay".

YES

Check the indoor motor.

Possible trouble 9
Is it cooling operation?

: Outdoor motor does not operate.


NO

1. Press power "ON/OFF" button.


2. Select cooling operation.

YES

Is the compressor operating?

NO

YES

Is the output
voltage of IC02M's 13/12(OUT FAN B)
on the MAIN PCB 0V?

NO

1. Set following.
Set temp. < Room temp.
2. Wait, if the unit has operating
with 3-minute time delay.

1. Check or exchange IC02M.

YES

Is the voltage
between OUT A/B of CN-FAN and
NEUTRAL 220V?

NO

1. Check or exchange
RY11/RY12(OUT FAN B).

YES

Is the "Power relay" for


outdoor motor ON?

NO

1. Check the wiring of


"Power relay".
2. Exchange "Power relay".

YES

Check the outdoor motor A/B.

Service Manual 23

Features of Controller

Features of Controller
1. Main Controller Circuit Diagram

24 Single Packaged Air Conditioner

(L)

(N)

FUSE

RY13

HEAT(A)

IN

FAN(IN)

HEAT(B)

A CN_HAETER

R17K
D11K
A

R08K

D06D
IC02K
CN_FAN

FAN_OUT
(B)

D07D
FAN_OUT
(A)

IC03K

IC01K

IC01D

S/TRANS

RY3
HYMID

IC02D

C03D

C09D

ZD02D
CN_HUMID

COMP(B)

C03D1

L01D

COMP(A)

4WAY(B)

CN_COMP

D03D

COMP(B)

C01J

R03D

C05D

OUT

BP(B)

4WAY(A)

CN_BYPASS

IN

JP03

JP06

JP05

JP04

BP(A)

RY6

ZNR01J

CN_POWER

JP07
BP(B)

CN_B_CYCLE

JP02

C07D

OUT
IN

JP10

JP09

JP08

CN_A_CYCLE

BP(A)

JP12

PWB:6870A20012A
ASM:6871A10041

CN_RETURN_AIR

CN_SUB

CN_THMO

1 2

CN_TEMP_OUT

60
5

D02D

55
10

R11D

50
15

NF01J

RY14

JP18

JP17

SWITCH

JP14

L02K

D09K

CN_CC

(B)

(A)

CN_H/P (WH)

TEST_SW

45
20

LED4
LED3
LED2
LED1

40
25

NTC01D

RY4

R18K
RY10

D08D

C02A

L01K

JP15

35
30

C01D

RY11

(B)

(A)

CN_REMO

OSC01B

D01D

RY5

CN_PHASE
RY12

COMP(A)
RY9

JP11
MICOM

JP01
4WAY(A)

RY8

4WAY(B)

RY7

CN_ZONE
IC01A

D30CI

D11D

Features of Controller

2. Feature of Main Controller

ZD01F

Service Manual 25

CN_L/P(YL)

OP_J1

Features of Controller

3. Feature of Remote-Controller PCB ASS'Y

4. Feature of Remote-Controller LCD

AUTO SWING

OPERATION

SET TEMP
Room Temp

HI
MED
LO

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door
ZONE
1 2 3 4

Time
Timer

Operation unit

On Off
Set no. Time 01

03

SUB FUNCTION

Program set
05

26 Single Packaged Air Conditioner

07

09

11

13

15

17

19

21

23

Features of Controller

5. Error Mode & Corrective Method


Error mode

Cause of error

Sensing condition of error

CH01

OPEN/SHORT of Voltage of sensing: Over 4.8V


room temp.
Voltage of sensing: Less than
sensor
0.5V

CH02

OPEN/SHORT of Voltage of sensing: Over 4.8V


indoor pipe temp. Voltage of sensing: Less than
0.5V
sensor
Communication
Error

Method of SVC

Remark

Room
1. Check the voltage of "CO1H"
temp.(25C)
on the remote controller.
= DC 2.5V
2. Check the temp. sensor of
remtote controller.
1. Check the voltage between PIN 3 Pipe temp.(25C)
and 4 of CN-A cycle/CN-B cycle.
= DC 2.2V
2. Check the temp. sensor of
indoor pipe.

CH03

Communication interruption
between remote controller and
Main PCB for 2 minutes.

1. Check the connecting wire


between main PCB remote
controller.
2. Check the input voltage of
remote-controller.
3. Check the wiring of
remote-controller.

Input voltage of
remote-controller
= DC 12V

CH04

OPEN/SHORT of Voltage of sensing: Over 4.8V


Voltage of sensing: Less than
outdoor pipe
0.5V
sensor

1. Check the voltage between PIN


1 and 2 of CN-A cycle/CN-B
cycle ON the main PCB.
2. Check the temp. sensor of
remtote controller.

Pipe
temp.(25C)
= DC 2.5V

CH05

OPEN/SHORT of Voltage of sensing: Over 4.8V


Voltage of sensing: Less than
outdoor room
0.5V
temp. sensor

1. Check the voltage between


PIN 1 and 3 of CN-TEMP
OUT on the main PCB.
2. Check the temp. sensor of
outdoor room.

Room
temp.(25C)
= DC 2.2V

CH16

OPEN of
A_Cycle_Low
Pressure Switch

1. Check Low Pressure Switch


2. Check Refrigerant pressure

CH17

OPEN of
B_Cycle_Low
Pressure Switch

Sensing the numer of Low pressure


S/W open after power_On
First time within 1 minute
- 3 time during 30 minutes after first
time sensing
- 6 time until 30 minutes after first
time sensing

CH18

OPEN of
A_Cycle_High
Pressure Switch

1. Check High Pressure Switch


2. Check Refrigerant pressure

CH19

OPEN of
B_Cycle_High
Pressure Switch

Sensing the numer of high pressure


S/W open after power_On
First time within 1 minute
- 3 time during 30 minutes after first
time sensing
- 6 time until 30 minutes after first
time sensing

CH21

Phase Reversal
Error

Sensing the Reversal Phase

1. Check Power Connection

CH22

Phase Loss

Sensing the Phase Missing

1. Check Power Connection

1. Check Low Pressure Switch


2. Check Refrigerant pressure

1. Check High Pressure Switch


2. Check Refrigerant pressure

Service Manual 27

Features of Controller

6. Principal part list of controller


Model

Main PCB ASM

Remote
controller

Pipe
Sensor A

Pipe
Sensor A/B

Outdoor Room
Sensor

Remark

LK-C090*H**

6871A10041A

6711A20043Y

6323AQ2333T

6323AQ2333U

6323AQ3214H

Cooling Only

7. Principal part list of Main PCB ASM


No
1
2
3
4
5

Part No
0IMCRTO020C
6920AQ9033F
6212A90001E
6900AQ9028N
6102AQ9075A

Part Name
MICOM(Main)
Relay
Resonator
Fuse
Varistor

Remarks
MICOM

28 Single Packaged Air Conditioner

8. Principal part list of Remote Controller


No
1
2
3
4

Part No
Part Name
Remark
OIMCRTO006K MICOM(Remote Controller) MICOM
6304A30001K LCD
6
6871A10072G Remote C PCB ASM
Cooling Only

Features of Controller

9. Explanation of principal function


Flow Chart
START(Power supply)
YES

1. Initialize "micom".
2. A/D convert.
3. Main PCB: Waiting cooling operation.
4. Remote controller: Waiting input.
Dehumidification Mode?
A

NO

Heater operation mode?

YES
YES

Power ON?

YES

NO

Dehumidification operating

NO

Set Temp. > Indoor Temp.

YES

YES

NO

Cooling Mode?

Stop condition?
Heater operating

YES

YES

Go to A

NO

Set Temp. < Indoor Temp.

YES

NO

YES

Stop condition?

YES
YES

Go to A

Time delay mode

NO

Fan only operating

Cooling operating

NO

Stop condition?

YES

Go to A

NO

Stop condition?

YES

Go to A

Service Manual 29

Exploded View and Replacement Parts List

Exploded View and Replacement Parts List


Exploded View

145610
349600

435312

342800
359012

W4400
145610
346810

354210
559010

552111
546810
549610
137210

137213-2
354210
330870

554160
554030

249950
152302

W6920

W0CZZ
566001
268714
263230
554031

137213-1

237204

267110

30 Single Packaged Air Conditioner

Exploded View and Replacement Parts List

Replacement Parts List


LOCATION
No.

DESCRIPTION

137210
145610
145610
152302
237204
249950
261704
263230
263230
263230
267110
268714
330870
342800
346810
349600

PANEL ASSEMBLY,FRONT(INDOOR)
PULLEY ASSEMBLY
PULLEY ASSEMBLY
FILTER(MECH),A/C
PANEL,FRONT
CONTROL BOX ASSEMBLY,SINGLE
TRANSFORMER,POWER
THERMISTOR ASSEMBLY
THERMISTOR ASSEMBLY
THERMISTOR ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY,MAIN
DRAIN PAN ASSEMBLY
BEARING
MOTOR ASSEMBLY,INDOOR
BRACKET ASSEMBLY

354210

EVAPORATOR ASSEMBLY,FIRST

359012
435312
546810
549610
552111

FAN,SIDE
GRILLE,DISCHARGE
MOTOR ASSEMBLY,OUTDOOR
MOUNT ASSEMBLY,MOTOR(OUTDOOR)
TUBE ASSEMBLY,CAPILLARY

554031

554160
559010
566000
566000
566001
566001
738281
137213-1
137213-2
W0CZZ
W4400
W6920

CONDENSER ASSEMBLY,FIRST

COMPRESSOR SET
FAN ASSEMBLY,PROPELLER
SWITCH,PRESSURE
SWITCH,PRESSURE
SWITCH,MAGNET
SWITCH,MAGNET
MANUAL,SERVICE
PANEL ASSEMBLY,SIDE
PANEL ASSEMBLY,SIDE
CAPACITOR,DRAWING
BELT,V
RELAY

PART No.
LK-C090BC00

LK-C0909C00

3721A10115A
4561A30001L
3A00217R
5230A20003S
3720A20088D
4995A10132A
6170A90004A
6323AQ2333T
6323AQ2333U
6323AQ3214H
6711A20043Y
6871A10041A
3087A10021A
4A00131A
4681A20018A
4811A30006A
5421A10049B
5421A10049A
5835A20001A
3530A20007J
4680AP2610G
3A00434H
5211A23021A
5403A10033G
5403A10033H
5403A10033C
5403A10033D
2520UNAR2AA
1A00195G
6600A20004E
6600A20004C
6600B000041
6600B000032
3828A30101E
3721A10117A
3721A10116A
2H00841J
4400A30001P
6920AP3400A

3721A10115A
4561A30001L
3A00217R
5230A20003S
3720A20088D
4995A10132B
6170A90004A
6323AQ2333T
6323AQ2333U
6323AQ3214H
6711A20043Y
6871A10041A
3087A10021A
4A00131A
4681A20018C
4811A30006A
5421A10049B
5421A10049A
5835A20001A
3530A20007J
4680AP2610G
3A00434H
5211A23021A
5403A10033G
5403A10033H
5403A10033C
5403A10033D
2520UNAU1BA
1A00195G
6600A20004E
6600A20004C
6600B000041
6600B000032
3828A30101E
3721A10117A
3721A10116A
2H00841J
4400A30001P
6920AP3400A

5851A20004A
6600L000007
6600L000006

5851A20004A
6600L000007
6600L000006

REMARKS

Blower Side
Indoor Motor Side

Pipe Senser A-cycle


Pipe Senser B-cycle
Outdoor Temp.senser

Upper
Lower

Upper , Bare Fin


Lower , Bare Fin
Upper , Gold Fin
Lower , Gold Fin

High Pressure Switch


Low Pressure Switch
Compressor
Indoor Motor

Outdoor Motor
Outdoor Motor

Optional parts
558511
566000
566000

DRIER ASSEMBLY
SWITCH PRESSURE
SWITCH PRESSURE

High pressure gauge


Low pressure gauge

Service Manual 31

Exploded View and Replacement Parts List

Specification of Components
MODEL

COMP

INDOOR MOTOR

OUTDOOR MOTOR

OUTDOOR FAN
INDOOR BLOWER
MOTOR PULLEY
BLOWER PULLEY

V-BELT

LOWER PRESSURE SWITCH

HIGH PRESSURE SWITCH

CAPACITOR for ODM


FILTER

CAPILLIARY TUBE
CONTACTOR for COMP.
CONTROl for IDM
RELAY for ODM
*RLA
**LRA

LK-C090BC00
P/No
Model name
*RLA
**LRA
Q'ty
P/No
Output(HP)
Shaft
RPM
P/No
Output(HP)
Shaft
RPM
Q'ty
P/No
Diameter
P/No
Diameter*width
P/No
Type
P/No
Type
Outside Dia
P/No
Type
Length
P/No
Spec.
Rated Voltage
Maker
P/No
Spec.
Rated Voltage
Maker
P/No
Spec.
P/No
Size
Q'ty
P/No
Size
Q'ty
P/No
Spec.
P/No
Spec.
P/No
Spec.

: RATED LOAD AMPER


: LOCK LOAD AMPER

32 Single Packaged Air Conditioner

2520UNAR2AA
SR049RAA
16
108
2
4681A20018A
1.5
22
840
4680AP2610G
0.4
12.0
1130
2
1A00195G
460(mm)
5835A20001A
320*320(mm)
3A00217R
VARIABLE
4561A30001L
B TYPE
170(mm)
4400A30001P
48A
1219(mm)
6600A20004C
OFF:2.0kgf/ON:3.5kgf
DC 24V
SAGINOMIYA
6600A20004E
OFF: 33kgf/ON: 24kgf
DC 24V
SAGINOMIYA
2H00841J
6F/370V
5230A20003S
330*728(mm)
1
5211A23021A
I.D 1.6*800(mm)
10
6600B000041
32A, 220V CONTROL
6600B000032
220V, 22A
6920AP3400A
220V, 25A

LK-C0909C00
2520UNAU1BA
SR049UAA
9
57
2
4681A20018C
1.5
22
840
4680AP2610G
0.4
12.0
1130
2
1A00195G
460(mm)
5835A20001A
320*320(mm)
3A00217R
VARIABLE
4561A30001L
B TYPE
170(mm)
4400A30001P
48A
1219(mm)
6600A20004C
OFF: 2.0kgf/ON:3.5kgf
DC 24V
SAGINOMIYA
6600A20004E
OFF: 33kgf/ON: 24kgf
DC 24V
SAGINOMIYA
2H00841J
6F/370V
5230A20003S
330*728(mm)
1
5211A23021A
I.D 1.6*800(mm)
10
6600B000041
32A, 220V CONTROL
6600B000032
220V, 22A
6920AP3400A
220V, 25A

Memo

Service Manual 33

Memo

34 Single Packaged Air Conditioner

P/No.: 3828A30101E

June, 2004
Printed in Korea