Professional Documents
Culture Documents
SCHOOL
Aiken High School
Carpe Diem Charter School
Aiken High School
Carpe Diem Charter School
Aiken High School
Carpe Diem Charter School
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
5/25/2016
6:12 AM CPS_AIKEN_KITCHEN_CME2016-085
Lead, ppb
<1
5/25/2016
6:17 AM CPS_AIKEN_NEARMAIN_CME2016-086
Lead, ppb
<1
5/25/2016
6:21 AM CPS_AIKEN_FARTHESTPOINT_CME2016-087
Lead, ppb
<1
Academy of Multilingual
Immersion Studies
5/6/2016
7:10 AM CPS_AMIS_KITCHEN_CME2016-035
Lead, ppb
<1
Academy of Multilingual
Immersion Studies
5/6/2016
7:15 AM CPS_AMIS_FARTHESTPOINT_CME2016-036
Lead, ppb
2.08
Academy of Multilingual
Immersion Studies
5/19/2016
6:00 AM CPS_AMIS_RM1105_CME2016-034
Lead, ppb
1.59
5/5/2016
6:05 AM CPS_AWL_MAIN_CME2016-022
Lead, ppb
53.6
5/5/2016
6:10 AM CPS_AWL_KITCHEN_CME2016-023
Lead, ppb
2.34
5/5/2016
6:15 AM CPS_AWL_FARTHESTPOINT_CME2016-024
Lead, ppb
<1
5/17/2016
6:23 AM CPS_AWL_MAINRETEST_CME2016-065
Lead, ppb
<1
5/12/2016
7:00 AM CPS_BONDHILL_KITCHEN_CME2016-062
Lead, ppb
<1
5/12/2016
7:15 AM CPS_BONDHILL_FARTHESTPOINTRM2200_CME2016-063
Lead, ppb
<1
5/20/2016
7:05 AM CPS_BONDHILL_RM1010_CME2016-061
Lead, ppb
<1
Carson School
5/25/2016
5:25 AM CPS_CARSON_KITCHEN_DE2016-052
Lead, ppb
<1
Carson School
5/25/2016
5:30 AM CPS_CARSON_RM2018_DE2016-053
Lead, ppb
<1
Carson School
5/25/2016
5:35 AM CPS_CARSON_RM3013_DE2016-054
Lead, ppb
<1
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
No lead detected in samples. CPS should follow
3Ts guidelines and sample at all drinking water and
cooking outlets within the school (may result in 4045 samples per school).
CPS/incorrect sampling
procedure.
Resampled.
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
Chase School
5/26/2016
6:10 AM CPS_CHASE_KITCHEN_CME2016-094
Lead, ppb
<1
Chase School
5/26/2016
6:13 AM CPS_CHASE_NEARMAIN_CME2016-094
Lead, ppb
1.13
Chase School
5/26/2016
6:17 AM CPS_CHASE_FARTHESTPOINT_CME2016-096
Lead, ppb
1.18
Cheviot School
5/4/2016
5:35 AM CPS_CHEVIOT_MAIN_DE2016-010
Lead, ppb
15.8
Cheviot School
5/4/2016
5:40 AM CPS_CHEVIOT_KITCHEN_DE2016-011
Lead, ppb
<1
Cheviot School
5/4/2016
5:45 AM CPS_CHEVIOT_RM2607_DE2016-012
Lead, ppb
5.51
Cheviot School
5/17/2016
5:20 AM CPS_CHEVIOT_MAINRETEST_DE2016-043
Lead, ppb
1.32
5/25/2016
5:43 AM CPS_CLARK_KITCHEN_CME2016-079
Lead, ppb
<1
5/25/2016
5:45 AM CPS_CLARK_NEARMAIN_CME2016-080
Lead, ppb
<1
5/25/2016
5:49 AM CPS_CLARK_FARTHESTPOINT_CME2016-081
Lead, ppb
1.54
5/12/2016
6:00 AM CPS_COLLEGEHILL_KITCHEN_DE2016-038
Lead, ppb
<1
5/12/2016
6:05 AM CPS_COLLEGEHILL_RM1235_DE2016-039
Lead, ppb
<1
5/24/2016
5:50 AM CPS_COLLEGEHILL_RM1112_DE2016-050
Lead, ppb
1.74
Covedale School
5/25/2016
5:50 AM CPS_COVEDALE_KITCHEN_DE2016-055
Lead, ppb
1.6
Covedale School
5/25/2016
6:00 AM CPS_COVEDALE_RM3125_DE2016-056
Lead, ppb
2.4
Covedale School
5/25/2016
6:10 AM CPS_COVEDALE_RM1136MUSIC_DE2016-057
Lead, ppb
5.2
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 2 of 3 sample points. Conduct a
plumbing profile to understand the material of the
fixtures at sample points. Review 3Ts guidelines to
understand options to reduce lead. CPS should
follow 3Ts guidelines and sample at all drinking
water and cooking outlets within the school (may
result in 40-45 samples per school).
CPS/incorrect sampling
procedure.
Resampled.
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
6/2/2016
6:10 AM CPS_DATERHIGH_RM0942_DE2016-082
Lead, ppb
<1
6/2/2016
6:15 AM CPS_DATERHIGH_KITCHEN_DE2016-083
Lead, ppb
1.98
6/2/2016
6:20 AM CPS_DATERHIGH_RM2603_DE20106-084
Lead, ppb
1.72
5/25/2016
6:15 AM CPS_DATERMONT_KITCHEN_DE2016-058
Lead, ppb
<1
5/25/2016
6:20 AM CPS_DATERMONT_RM0001_DE2016-059
Lead, ppb
1.59
5/25/2016
6:25 AM CPS_DATERMONT_RM2017_DE2016-060
Lead, ppb
<1
5/4/2016
6:00 AM CPS_DOUGLASS_MAIN_CME2016-016
Lead, ppb
<1
5/4/2016
6:05 AM CPS_DOUGLASS_KITCHEN_CME2016-017
Lead, ppb
<1
5/4/2016
6:10 AM CPS_DOUGLASS_FARTHESTPOINT_CME2016-018
Lead, ppb
<1
Evanston Academy
5/24/2016
6:10 AM CPS_EVANSTON_NEARMAIN_CME2016-073
Lead, ppb
<1
Evanston Academy
5/24/2016
6:15 AM CPS_EVANSTON_KITCHEN_CME2016-074
Lead, ppb
1.19
Evanston Academy
5/24/2016
6:20 AM CPS_EVANSTON_FARTHESTPOINT_CME2016-075
Lead, ppb
1.39
5/10/2016
6:35 AM CPS_FAIRVIEW_KITCHEN_DE2016-026
Lead, ppb
<1
5/10/2016
6:40 AM CPS_FAIRVIEW_RM3306_DE2016-027
Lead, ppb
<1
5/18/2016
5:45 AM CPS_FAIRVIEW_ARTRM1212_DE2016-049
Lead, ppb
<1
Fairview-Clifton German
Language School
Fairview-Clifton German
Language School
Fairview-Clifton German
Language School
5/4/2016
6:30 AM CPS_GAMBLE_KITCHEN_DE2016-017
Lead, ppb
7.55
5/4/2016
6:35 AM CPS_GAMBLE_EASTWINGBOYSRR_DE2016-018
Lead, ppb
1.42
5/17/2016
5:55 AM CPS_GAMBLE_KITCHENRETEST_DE2016-046
Lead, ppb
4.38
5/17/2016
6:00 AM CPS_GAMBLE_OFFICE1117_DE2016-047
Lead, ppb
6.19
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 2 of 3 sample points. Conduct a
plumbing profile to understand the material of the
fixtures at sample points. Review 3Ts guidelines to
understand options to reduce lead. CPS should
follow 3T guidelines and sample at all drinking
water and cooking outlets within the school (may
result in 40-45 samples per school).
CPS/incorrect sampling
procedure.
Resampled.
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
Hartwell School
5/6/2016
6:40 AM CPS_HARTWELL_KITCHEN_CME2016-032
Lead, ppb
1.19
Hartwell School
5/6/2016
6:45 AM CPS_HARTWELL_FARTHESTPOINT_CME2016-033
Lead, ppb
<1
Hartwell School
5/19/2016
6:35 AM CPS_HARTWELL_RM1202_CME2016-031
Lead, ppb
<1
Hays-Porter School
5/10/2016
5:40 AM CPS_HAYS_KITCHEN_DE2016-020
Lead, ppb
<1
Hays-Porter School
5/10/2016
5:45 AM CPS_HAYS_RM3007-DE2016-021
Lead, ppb
2.47
Hays-Porter School
5/18/2016
5:25 AM CPS_HAYS_RM1028_DE2016-048
Lead, ppb
<1
6/1/2016
5:50 AM CPS_HUGHES_KITCHEN_DE2016-073
Lead, ppb
<1
6/1/2016
5:55 AM CPS_HUGHES_RM0125_DE2016-074
Lead, ppb
<1
6/1/2016
6:00 AM CPS_HUGHES_RM3138_DE2016-075
Lead, ppb
<1
Kilgour School
4/29/2016
6:35 AM CPS_KILGOUR_MAIN_CME2016-010
Lead, ppb
<1
Kilgour School
4/29/2016
6:40 AM CPS_KILGOUR_KITCHEN_CME2016-011
Lead, ppb
<1
Kilgour School
4/29/2016
6:45 AM CPS_KILGOUR_FARTHESTPOINT_CME2016-012
Lead, ppb
<1
Midway School
5/4/2016
6:00 AM CPS_MIDWAY_MAIN_DE2016-013
Lead, ppb
19.9
Midway School
5/4/2016
6:05 AM CPS_MIDWAY_KITCHEN_DE2016-014
Lead, ppb
<1
Midway School
5/4/2016
6:10 AM CPS_MIDWAY_RM2254_DE2016-015
Lead, ppb
<1
Midway School
5/17/2016
5:30 AM CPS_MIDWAY_MAINRETEST_DE2016-044
Lead, ppb
1.54
5/12/2016
6:20 AM CPS_MTAIRY_KITCHEN_DE2016-041
Lead, ppb
6.3
5/12/2016
6:25 AM CPS_MTAIRY_RM2023_DE2016-042
Lead, ppb
<1
5/24/2016
6:05 AM CPS_MTAIRY_MUSICRM1039_DE2016-051
Lead, ppb
1.19
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 1 of 3 sample points. Conduct a
plumbing profile to understand the material of the
fixtures at sample points. Review 3Ts guidelines to
understand options to reduce lead. CPS should
follow 3Ts guidelines and sample at all drinking
water and cooking outlets within the school (may
result in 40-45 samples per school).
CPS/incorrect sampling
procedure.
Resampled.
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
4/29/2016
6:05 AM CPS_MTWASHINGTON_MAIN_CME2016-007
Lead, ppb
28.5
4/29/2016
6:10 AM CPS_MTWASHINGTON_KITCHEN_CME2016-008
Lead, ppb
1.04
4/29/2016
6:15 AM CPS_MTWASHINGTON_FARTHESTPOINT_CME2016-009
Lead, ppb
1.1
5/17/2016
6:01 AM CPS_MTWASHINGTON_MAINRETEST_CME2016-064
Lead, ppb
<1
5/12/2016
5:55 AM CPS_NORTHAVONDALE_RM1115_CME20106-055
Lead, ppb
1.02
5/12/2016
6:00 AM CPS_NORTHAVONDALE_KITCHEN_CME2016-056
Lead, ppb
<1
5/12/2016
CPS_NORTHAVONDALE_FARTHESTPOINTRM2218_CME201
6:05 AM 6-057
Lead, ppb
<1
Oyler School
5/26/2016
5:20 AM CPS_OYLER_KITCHEN_DE2016-061
Lead, ppb
2.29
Oyler School
5/26/2016
5:25 AM CPS_OYLER_EYECLINIC_DE2016-062
Lead, ppb
<1
Oyler School
5/26/2016
5:35 AM CPS_OYLER_RM3018_DE3016-063
Lead, ppb
1.3
5/10/2016
6:45 AM CPS_JOHNPPARKER_MAIN_CME2016-043
Lead, ppb
1.87
5/10/2016
6:50 AM CPS_JOHNPPARKER_KITCHEN_CME2016-044
Lead, ppb
1.64
5/10/2016
7:00 AM CPS_JOHNPPARKER_FARTHESTPOINT_CME2016-045
Lead, ppb
1.76
5/19/2016
6:15 AM CPS_PARKERRETEST_RM1023_CME2016-068
Lead, ppb
1.39
6:45 AM CPS_PARKERWOODS_KITCHEN_DE2016-070
Lead, ppb
<1
6:50 AM CPS_PARKERWOODS_ART1306_DE2016-071
Lead, ppb
<1
6:55 AM CPS_PARKERWOODS_RM3401_DE2016-072
Lead, ppb
<1
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
CPS/incorrect sampling
procedure.
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 3 of 4 sample points. One sample
was incorrectly collected. Another sample was
collected. Conduct a plumbing profile to understand
the material of the fixtures at sample points.
Review 3Ts guidelines to understand options to
reduce lead. CPS should follow 3Ts guidelines
and sample at all drinking water and cooking
outlets within the school (may result in 40-45
samples per school).
Resampled.
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
5/12/2016
5:35 AM CPS_PLEASANTHILL_KITCHEN_DE2016-035
Lead, ppb
5.84
5/12/2016
5:40 AM CPS_PLEASANTHILL_RM2015_DE2016-036
Lead, ppb
<1
5/24/2016
5:40 AM CPS_PLEASANTHILL_ARTRM1046_DE2016-049
Lead, ppb
1.6
5/11/2016
5:55 AM CPS_PLEASANTRIDGE_RM1154_CME2016-046
Lead, ppb
<1
5/11/2016
6:00 AM CPS_PLEASANTRIDGE_KITCHEN_CME2016-047
Lead, ppb
<1
5/11/2016
6:05 AM CPS_PLEASANTRIDGE_FARTHESTPOINT_CME2016-048
Lead, ppb
<1
5/26/2016
5:45 AM CPS_PRICE_KITCHEN_DE2016-064
Lead, ppb
<1
5/26/2016
5:50 AM CPS_PRICE_RM2068_DE2016-065
Lead, ppb
<1
5/26/2016
5:55 AM CPS_PRICE_RM3016_DE2016-066
Lead, ppb
1.24
5/3/2016
5:35 AM CPS_RIVERVIEW_MAIN_CME2016-013
Lead, ppb
1.37
5/3/2016
5:40 AM CPS_RIVERVIEW_KITCHEN_CME2016-014
Lead, ppb
2.76
5/3/2016
5:45 AM CPS_RIVERVIEW_FARTHESTPOINT_CME2016-015
Lead, ppb
<1
5/26/2016
6:05 AM CPS_ROBERTS_KITCHEN_DE2016-067
Lead, ppb
<1
5/26/2016
6:15 AM CPS_ROBERTS_RM1107_DE2016-068
Lead, ppb
<1
5/26/2016
6:20 AM CPS_ROBERTS_RM3110_DE2016-069
Lead, ppb
<1
Rockdale Academy
5/10/2016
5:35 AM CPS_ROCKDALE_MAIN_CME2016-037
Lead, ppb
<1
Rockdale Academy
5/10/2016
5:40 AM CPS_ROCKDALE_KITCHEN_CME2016-038
Lead, ppb
1.46
Rockdale Academy
5/10/2016
5:45 AM CPS_ROCKDALE_FARTHESTPOINT_CME2016-039
Lead, ppb
<1
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 2 of 3 sample points. Conduct a
plumbing profile to understand the material of the
fixtures at sample points. Review 3Ts guidelines to
understand options to reduce lead. CPS should
follow 3Ts guidelines and sample at all drinking
water and cooking outlets within the school (may
result in 40-45 samples per school).
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
5/3/2016
6:35 AM CPS_ROLLHILL_MAIN_DE2016-007
Lead, ppb
2.56
5/3/2016
6:40 AM CPS_ROLLHILL_KITCHEN_DE2016-008
Lead, ppb
<1
5/3/2016
6:45 AM CPS_ROLLHILL_RM2069_DE2016-009
Lead, ppb
<1
5/6/2016
6:14 AM CPS_ROSELAWN_KITCHEN_CME2016-029
Lead, ppb
<1
5/6/2016
6:20 AM CPS_ROSELAWN_FARTHESTPOINT_CME2016-030
Lead, ppb
5/19/2016
6:15 AM CPS_ROSELAWN_RM1203_CME2016-028
Lead, ppb
2.72
Rothenberg Preparatory
Academy
5/4/2016
6:35 AM CPS_ROTHENBERG_MAIN_CME2016-019
Lead, ppb
<1
Rothenberg Preparatory
Academy
5/4/2016
6:40 AM CPS_ROTHENBERG_KITCHEN_CME2016-020
Lead, ppb
<1
Rothenberg Preparatory
Academy
5/4/2016
6:45 AM CPS_ROTHENBERG_FARTHESTPOINT_CME2016-021
Lead, ppb
1.27
4/29/2016
5:35 AM CPS_SANDS_MAIN_CME2016-004
Lead, ppb
1.18
4/29/2016
5:40 AM CPS_SANDS_KITCHEN_CME2016-005
Lead, ppb
1.67
4/29/2016
5:45 AM CPS_SANDS_FARTHESTPOINT_CME2016-006
Lead, ppb
2.05
5/11/2016
5:40 AM CPS_SAYLERPARK_KITCHEN_DE2016-030
Lead, ppb
<1
5/11/2016
5:45 AM CPS_SAYLERPARK_RM1100_DE2016-030
Lead, ppb
1.63
5/24/2016
5:00 AM CPS_SAYLERPARK_RM1056_DE2016-048
Lead, ppb
<1
5/25/2016
6:10 AM CPS_SCPA_NEARMAIN_CME2016-088
Lead, ppb
<1
5/25/2016
6:15 AM CPS_SCPA_KITCHEN_CME2016-089
Lead, ppb
<1
5/25/2016
6:20 AM CPS_SCPA_FARTHESTPOINT_CME2016-090
Lead, ppb
<1
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 1 of 3 sample points. Conduct a
plumbing profile to understand the material of the
fixtures at sample points. Review 3Ts guidelines to
understand options to reduce lead. CPS should
follow 3Ts guidelines and sample at all drinking
water and cooking outlets within the school (may
result in 40-45 samples per school).
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
5/10/2016
6:30 AM CPS_SHRODER_MAIN_CME2016-040
Lead, ppb
<1
5/10/2016
6:35 AM CPS_SHRODER_KITCHEN_CME2016-041
Lead, ppb
1.2
5/10/2016
6:40 AM CPS_SHRODER_FARTHESTPOINT_CME2016-042
Lead, ppb
<1
5/19/2016
7:00 AM CPS_SHRODERRETEST_RM0430_CME2016-069
Lead, ppb
<1
5/11/2016
6:25 AM CPS_SILVERTON_KITCHEN_CME2016-050
Lead, ppb
3.82
5/11/2016
6:35 AM CPS_SILVERTON_FARTHESTPOINT_CME2016-051
Lead, ppb
<1
5/19/2016
6:15 AM CPS_SILVERTON_RM1135_CME2016-049
Lead, ppb
<1
5/5/2016
6:35 AM CPS_SAVONDALE_MAIN_CME2016-025
Lead, ppb
60.1
5/5/2016
6:40 AM CPS_SAVONDALE_KITCHEN_CME2016-026
Lead, ppb
1.12
5/5/2016
6:45 AM CPS_SAVONDALE_FARTHESTPOINT_CME2016-027
Lead, ppb
<1
5/17/2016
6:45 AM CPS_SOUTHAVONDALE_MAINRETEST_CME2016-066
Lead, ppb
<1
5/25/2016
6:40 AM CPS_SPENCER_KITCHEN_CME2016-091
Lead, ppb
11.6
5/25/2016
6:45 AM CPS_SPENCER_NEARRM111_CME2016-092
Lead, ppb
2.54
5/25/2016
6:50 AM CPS_SPENCER_NEARRM208_CME3016-093
Lead, ppb
8.03
5/25/2016
6:20 AM CPS_TAFT_FARTHESTPOINT_CME2016-082
Lead, ppb
3.17
5/25/2016
6:28 AM CPS_TAFT_NEARMAIN_CME2016-083
Lead, ppb
<1
5/25/2016
6:30 AM CPS_TAFT_KITCHEN_CME2016-084
Lead, ppb
<1
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 1 of 4 sample points. Conduct a
plumbing profile to understand the material of the
fixtures at sample points. Review 3Ts guidelines to
understand options to reduce lead. CPS should
follow 3Ts guidelines and sample at all drinking
water and cooking outlets within the school (may
result in 40-45 samples per school).
CPS/incorrect sampling
procedure.
Resampled.
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
6/1/2016
6:15 AM CPS_TAFTHIGH_KITCHEN_DE2016-076
Lead, ppb
<1
6/1/2016
6:20 AM CPS_TAFTHIGH_RM1040_DE2016-077
Lead, ppb
1.2
6/1/2016
6:25 AM CPS_TAFTHIGH_RM2026_DE2016-078
Lead, ppb
<1
5/3/2016
6:10 AM CPS_TAYLOR_MAIN_DE2016-004
Lead, ppb
10.3
5/3/2016
6:15 AM CPS_TAYLOR_KTICHEN_DE2016-005
Lead, ppb
<1
5/3/2016
6:20 AM CPS_TAYLOR_RM311_DE2016-006
Lead, ppb
<1
5/17/2016
5:15 AM CPS_TAYLOR_MAINRETEST_CME2016-067
Lead, ppb
<1
5/10/2016
6:00 AM CPS_VIRTUALHS_MAINTSHOP_DE2016-022
Lead, ppb
<1
5/10/2016
6:05 AM CPS_VIRTUALHS_OFFICEWKRM_DE2016-023
Lead, ppb
<1
5/10/2016
6:10 AM CPS_VIRTUALHS_ABLE/GEDKITCHEN_DE2016-024
Lead, ppb
2.7
5/24/2016
5:45 AM CPS_WALNUTHILLS_NEARMAIN_CME2016-070
Lead, ppb
<1
5/24/2016
5:50 AM CPS_WALNUTHILLS_KITCHEN_CME2016-071
Lead, ppb
1.32
5/24/2016
5:55 AM CPS_WALNUTHILLS_FARTHESTPOINT_CME2016-072
Lead, ppb
<1
6/2/2016
5:50 AM CPS_WESTERNHILLS_RM0204_DE2016-079
Lead, ppb
4.72
6/2/2016
5:55 AM CPS_WESTERNHILLS_KITCHEN_DE2016-080
Lead, ppb
<1
6/2/2016
6:00 AM CPS_WESTERNHILLS_RM3143_DE2016-081
Lead, ppb
<1
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 1 of 3 sample points. Conduct a
plumbing profile to understand the material of the
fixtures at sample points. Review 3Ts guidelines to
understand options to reduce lead. CPS should
follow 3Ts guidelines and sample at all drinking
water and cooking outlets within the school (may
result in 40-45 samples per school).
CPS/incorrect sampling
procedure.
Resampled.
SAMPLE
DATE
SAMPLE
TIME
SAMPLE NAME
PARAMETER
CODE
COMMENTS REGARDING
AMOUNT SAMPLING PROCESS
Westwood School
5/3/2016
5:40 AM CPS_WESTWOOD_KITCHEN_DE2016-002
Lead, ppb
Westwood School
5/3/2016
Lead, ppb
<1
Westwood School
5/12/2016
5:45 AM CPS_WESTWOOD_RM3048_DE2016-003
CPS_WESTWOOD_FARTHESTPOINTRM20223_CME20166:45 AM 060
Lead, ppb
<1
Westwood School
5/17/2016
5:45 AM CPS_WESTWOOD_RM1002_DE2016-045
Lead, ppb
<1
5/26/2016
5/26/2016
6:33 AM CPS_WINTONHILLS_NEARMAIN_CME2016-097
6:40 AM CPS_WINTONHILLS_KITCHEN_CME2016-098
Lead, ppb
Lead, ppb
<1
<1
5/26/2016
6:42 AM CPS_WINTONHILLS_FARTHESTPOINT_CME2016-099
Lead, ppb
<1
5/25/2016
6:50 AM CPS_WITHROW_NEARMAIN_CME2016-076
Lead, ppb
<1
5/25/2016
7:00 AM CPS_WITHROW_KITCHEN_CME2019-077
Lead, ppb
1.37
5/25/2016
7:10 AM CPS_WITHROW_FARTHESTPOINT_CME2016-078
Lead, ppb
<1
5/18/2016
6:55 AM CPS_WOODFORD_WORKROOM1213_CME2016-052
Lead, ppb
<1
5/11/2016
7:00 AM CPS_WOODFORD_KITCHEN_CME206-053
Lead, ppb
<1
5/11/2016
7:05 AM CPS_WOODFORD_FARTHESTPOINT_CME2016-054
Lead, ppb
<1
5:35 AM CPS_WOODWARD_KITCHEN_CME2016-059
Lead, ppb
<1
6:45 AM CPS_WOODWARD_RM20223_CME2016-060
Lead, ppb
<1
6:45 AM CPS_WOODWARD_RM10112_CME2016-058
Lead, ppb
<1
Greater Cincinnati Water Works - Lead Testing Results for Cincinnati Public Schools
GCWW
COMMENTS/REVIEW/RECOMMENDATIONS
Lead detected at 1 of 4 sample points. Conduct a
plumbing profile to understand the material of the
fixtures at sample points. Review 3Ts guidelines to
understand options to reduce lead. CPS should
follow 3Ts guidelines and sample at all drinking
water and cooking outlets within the school (may
result in 40-45 samples per school).
10