Miniature Temptran RTD Transmitters

TT111 only

TT111, TT211

TT211 only

Overview
Two models:
TT111: UL-recognized component for Canada and United
States.
TT211: Wider ambient rating; Factory Mutual (FM) approved
intrinsically safe and nonincendive.
Optional high-accuracy calibration to Minco RTDs for
improved accuracy; see next page and page 4-22 for
more information.

Specifications
Output: 4 to 20 mA over specified range, linear with temperature.
Calibration accuracy: 0.1% of span.
Linearity: Referenced to actual sensor temperature.
Platinum RTD input: 0.1% of span.
Nickel and nickel-iron RTD input:
0.25% of span for spans less than 100C.
0.25% of span per 100C of span for spans greater than 100C.
Adjustments: Zero and span, 5% of span. Factory set.
Ambient temperature:
TT111: 0 to 50C (32 to 122F).
TT211: -25 to 85C (-13 to 185F).
Storage: -55 to 100C (-67 to 212F).
Ambient temperature effects:
0.013% of span per C.
0.025% of span per C for spans less than 55C.
Warmup drift: 0.1% of span max., with
Vsupply = 24 VDC and Rloop = 250 .
Stable within 30 minutes.

Maximum load resistance: The maximum allowable resistance


of the signal carrying loop is:

Example: With supply voltage 24 VDC, maximum loop resistance


is 775 .
Minimum span: 27.8C (50F).
Hazardous atmospheres: All models may be used with Minco
flameproof/explosionproof connection heads. Models TT211 is
Factory Mutual approved nonincendive for use in Class I,
Division 2 areas and intrinsically safe for Class I, Division 1 areas
(requires approved barrier). Transmitter entity parameters:
Vmax = 35 volts; Imax = 150 mA; Ci = 0 F and Li = 0 mH.
Connections:
Terminal block for wires AWG 22 to AWG 14.
Physical: Polycarbonate case, epoxy potted for moisture
resistance.
Weight: 1.1 oz. (30 g).

Hazardous area requirements


For more information on how to classify a hazardous
area, methods of protection, and the various standards
and agencies (including FM, CSA, CENELEC, IECEx and
ATEX), visit www.minco.com.

Supply voltage: 8.5 to 35 VDC. Voltage effect 0.001% of span


per volt. Reverse polarity protected.
= STANDARD OPTIONS
Specifications subject to change

Page 4-2

Miniature RTD Transmitters

RTD input types

Special high-accuracy calibration

2-wire resistance thermometer:

For high system accuracy, specify transmitters with matched


calibration. Temptrans match calibrated to a sensor are always
ordered as assemblies. Common examples are shown in
Section 1.

100 at 0C
100 at 0C
100 at 0C
1000 at 0C
1000 at 0C
604 at 0C
1000 at 70F
2000 at 70F
120 at 0C

Code
PA
PB
PD, PE
PF
PW
FA
FB
FC
NA

Specification and order options:

Dimensions in inches (mm)

Model number: TT111 or TT211

PD

RTD element code from table

Output: 4 to 20 mA DC

Temperature range code starting on page 4-20


[Ex: C = 0 to 100C (32 to 212F)]

TT111PD1C = Sample part number


0.08
(2.0)
MAX.

ZERO

0.50
(12.7)

TT111

SPAN

1.0
(25.4)
0.25
(6.4)
0.149 (3.8) I.D.
THROUGH
1.5 (38.1)

MOUNTING USE #6
SCREW THROUGH OR
#8 THREAD FORMING
SCREW

0.675 (17.1)
1.09 (27.1)

Wiring Diagram
TT111
TT211
RED 1
BROWN 2
BLACK 3
ORNG 4

RESISTANCE
THERMOMETER

4 TO 20
mA LOOP

DC
SUPPLY
COPPER LEADS,
TWISTED PAIR

R1
CONTROLLER
AND/OR INDICATOR

LINE
POWER

CONTROL ROOM

= STANDARD OPTIONS
Specifications subject to change

Page 4-3

INSTRUMENTS

Element
Platinum (0.00392 TCR)
Platinum (0.00391 TCR)
Platinum (0.00385 TCR)
Platinum (0.00385 TCR)
Platinum (0.00375 TCR)
Nickel-iron (0.00518 TCR)
Nickel-iron (0.00527 TCR)
Nickel-iron (0.00527 TCR)
Nickel (0.00672 TCR)

TT246 RTD Transmitters

TT246 RTD Transmitter,


voltage output

Overview
Specify this rugged, accurate transmitter for process control
and other industrial applications.
Model TT246 outputs 1 to 5 VDC proportional to temperature.
It draws only 3 mA of quiescent current, making it ideal for
solar or battery powered systems.
2 or 3-wire RTD input
Ambient rated to 85C (185F)
Fits DIN B style connection heads
Optional high-accuracy calibration to Minco RTDs for
improved accuracy; see next page and page 4-22 for
more information.

Specifications
Output: Linear with temperature over specified range.
TT246: 1 to 5 VDC
Calibration Accuracy: 0.1% of span (0.2% of span for spans
less than 10 )
Linearity: 0.1% of span, referenced to actual sensor
temperature
Adjustments Zero and span, 5% of span, non-interacting.
Factory set.
Ambient temperature:
Operating: -40 to 85C (-40 to 185F)
Storage: -55 to 100C (-67 to 212F)

Ambient temperature effects:


0.009% of span per C
0.014% of span per C for spans less than 10
Warmup drift:
0.1% of span max., with Vsupply = 24 VDC and Rloop = 250 .
Stable within 15 minutes.
Supply voltage:
TT246: 7.5 to 35 VDC
Voltage effect 0.001% of span per volt.
Reverse polarity protected.
Supply current: 3mA max. with no load.
Maximum load resistance: The maximum allowable resistance
of the signal carrying loop is:

Example: With supply voltage 24 VDC, maximum loop


resistance is 700 .
Minimum span: 10C (18F).
Minimum output current: 2.2 mA.
Maximum output current: 28 mA.
Leadwire compensation: (3-wire RTD) 0.05% of span per
up to 25 in each leg.
Hazardous atmospheres: May be used with Minco explosionproof connection heads.
Connections: Terminal block for wires AWG 22 to AWG 14.
Physical: Polycarbonate case, epoxy potted for moisture
resistance.
Weight: 2.0 oz. (57 g).

= STANDARD OPTIONS
Specifications subject to change

Page 4-4

RTD input types

Special high-accuracy calibration

Element
Platinum (0.00392 TCR)
Platinum (0.00391 TCR)
Platinum (0.00385 TCR)
Platinum (0.00385 TCR)
Platinum (0.00375 TCR)
Copper (0.00427 TCR)
Nickel-iron (0.00518 TCR)
Nickel-iron (0.00527 TCR)
Nickel-iron (0.00527 TCR)
Nickel (0.00672 TCR)

100 at 0C
100 at 0C
100 at 0C
1000 at 0C
1000 at 0C
10 at 25C
604 at 0C
1000 at 70F
2000 at 70F
120 at 0C

Code
PA
PB
PD, PE
PF
PW
CA
FA
FB
FC
NA

For high system accuracy, specify transmitters with matched


calibration. Temptrans match calibrated to a sensor are
always ordered as assemblies.

Specification and order options:


TT246 Model Number:
PB
RTD element code from table
1
K

Temperature range code starting on page 4-20


[Ex: K = 0 to 200C (32 to 392F)]

TT246PB1K = Sample part number

Dimensions in inches (mm)

2
1

0.188 (4.8) DIA. [2]


3

3
2

SIGNAL
(TT246 HAS
THREE
SIGNAL
TERMINALS)

0.26 (6.6) DIA.

1.30
(33.0)

SPAN

ZERO
SENSOR

0.65
(16.5)
0.320 (8.1) DIA. [2]
A
1.725 (43.8)
DIAMETER

LED

0.725
(18.42)
1.10 (27.9)
SECTION A-A

Wiring Diagram

= STANDARD OPTIONS
Specifications subject to change

Page 4-5

INSTRUMENTS

2 or 3-wire resistance thermometer:

TT205 Thermocouple Transmitters

TT205
Thermocouple Transmitter

Overview
Model TT205 interfaces with thermocouples for use in process
control and other industrial applications.
Model TT205 offers superior performance in an economical
and small package.
Thermocouple input
Fits DIN B style connection heads

Maximum load resistance: The maximum allowable resistance


of the signal carrying loop is:

Example: With supply voltage 24 VDC, maximum loop


resistance is 700 .
Minimum output current: 1.5 mA.
Maximum output current: 28 mA.

Specifications

Burnout: Downscale burnout standard; upscale optional.

Output: 4 to 20 mA over specified range.

Connections: Terminal block for wires AWG 22 to AWG 14.

Accuracy: 0.2% of span.

Physical: Polycarbonate case, epoxy potted for moisture


resistance.

Linearity: Voltage linear.


The output signal is voltage linear (not
temperature linear) and is intended for use with
instruments which compensate for the nonlinear
signal output of the thermocouples sensor.

Weight: 1.8 oz. (52 g).

Adjustments: Zero and span, 5% of span,


non-interacting. Factory set.
Warmup drift: 0.2% of span max., with
Vsupply = 24 VDC and Rloop = 250 .
Stable within 15 minutes.
Supply voltage: 8.5 to 35 VDC
Voltage effect 0.001% of span per volt.
Reverse polarity protected.

= STANDARD OPTIONS
Specifications subject to change

Page 4-6

TT205

TT205 Dimensions in inches (mm)

Ambient temperature:
Operating: -10 to 60C (14 to 140F).
Storage: -55 to 100C (-67 to 212F).

0.50
(12.7)
1

SPAN

Ambient temperature effects: 0.036% of span per C.

1.0
(25.4)

Cold junction compensation drift: 0.05C per C.

0.25
(6.4)
0.149 (3.8) I.D.
THROUGH
1.5 (38.1)

Specification and order options

Model Number:
TT190: Round
TT205: Rectangular
TC junction type:
E = Chromel-Constantan
J = Iron-Constantan
K = Chromel-Alumel
T = Copper-Constantan

U = Ungrounded junction (required)

Output: 4 to 20 mA DC

AN

Temperature range code starting on page 4-20


[Ex: AN = -17.8 to 148.9C (0 to 300F)]

0.675 (17.1)

MOUNTING USE #6
SCREW THROUGH OR
#8 THREAD FORMING
SCREW

1.09 (27.1)

INSTRUMENTS

Minimum span: 150C (270F).

TT205

0.08
(2.0)
MAX.

ZERO

Wiring Diagram
TT205
1
2
3
4

THERMOCOUPLE

4 TO 20
mA LOOP

DC
SUPPLY
COPPER LEADS,
TWISTED PAIR

R1
CONTROLLER
AND/OR INDICATOR

LINE
POWER

CONTROL ROOM

TT205JU1AN = Sample part number

= STANDARD OPTIONS
Specifications subject to change

Page 4-7

TT273 Field Rangeable RTD


Temperature Transmitter

Overview
Model TT273 is a 2-wire temperature transmitter for 2 or 3-lead
100 platinum RTDs. The transmitter converts the RTD
temperature into a linearized 4 to 20 mA DC current signal.
Because this current signal is immune to leadwire and electrical
noise, the TT273 lets you obtain accurate temperature readings
from RTDs thousands of feet away. An ordinary twisted pair of
wires carries both the temperature signal and power for the
transmitters electronics.

TT273 RTD
Temperature Transmitter

Ambient temperature effects:


0.018% of span/C (0.01% of span/F).

An LED conveniently indicates the status of the control loop.


The brightness is directly proportional to the loop current. A
very bright LED indicates an open RTD; a dark LED signals a
shorted RTD or loss of current loop power.

Warmup drift: 0.1% of span max., assuming


Vsupply = 24 VDC and Rloop = 250 .
Stable within 15 minutes.

4 to 20 mA current signal

Supply voltage:
Non-Isolated: 10 to 45 volts DC with no load.
Isolated: 13 to 45 volts DC with no load.
Reverse polarity protected.

Fits standard 35 mm DIN rail


Field-calibrate to your temperature range
Optional high-accuracy calibration to Minco RTDs for
improved accuracy; see next page and page 5-22 for more
information

Input/output isolation (optional): 600 VRMS, 1 minute.

Voltage effect: 0.001% of span per volt.


Lead wire compensation: (3-wire RTD)
0.05% of span per , up to 25 in each leg.

Optional Input/Output isolation to 600 VRMS


Maximum load resistance: The maximum allowable resistance
of the signal-carrying loop is given by this formula:

Specifications

Non-Isolated:

Output: 4 to 20 mA DC over specified range.


Calibration accuracy: 0.2% of span.
Linearity: 0.2% of span, reference to actual sensor temperature.
Adjustments:
Zero: -50 to 150C (-58 to 302F).
Span: 50 to 600C (90 to 1080F).
Ambient temperature:
Operating: -40 to 85C (-40 to 185F).
Storage: -55 to 100C (-67 to 212F).

Isolated:
Maximum output current: 28 mA.
Connections: Terminal block accepts wires from AWG 22 to
AWG 14.
Physical: Polycarbonate, DIN rail enclosure.
Weight: 4.2 oz. (119 g).
= STANDARD OPTIONS
Specifications subject to change

Page 4-12

RTD input types


2 or 3-wire 100 platinum RTD.

TT273

Model number

Code

PD

RTD element code from table

Platinum (0.00392 TCR)

100 at 0C

PA

Output: 4 to 20 mA DC

Platinum (0.00391 TCR)

100 at 0C

PB

Platinum (0.00385 TCR)

100 at 0C

PD, PE

Element

Special high-accuracy calibration


For high system accuracy, specify transmitters with matched
calibration. Temptrans match calibrated to a sensor are always
ordered as assemblies. Common examples are shown in
Section 1.

Input/Output:
N = Non-isolated
I = Isolated
Factory
preset temp. range:
(-25/50)
(4 mA/20 mA temperature)
Range is user adjustable.
Refer to the Zero and Span specifications.
Temperature scale:
C
F = Fahrenheit
C = Celsius
TT273PD1N(-25/50)C = Sample part number

Dimensions in inches (mm)


SLIDING
CATCH

2.95
(74.9)

35 mm DIN
RAIL MOUNT

PWR
ZERO
SPAN

DIP SWITCH
RANGE SELECTION

0.886
(22.5)

3.875
(98.4)

Wiring diagram
TT273
PWR

SPAN

ZERO

RESISTANCE
THERMOMETER

DC
SUPPLY
4 TO 20
mA LOOP

COPPER LEADS,
TWISTED PAIR

R1
CONTROLLER
AND/OR INDICATOR

LINE POWER

CONTROL ROOM

= STANDARD OPTIONS
Specifications subject to change

Page 4-13

INSTRUMENTS

Specification and order options

TT274 Field Rangeable Thermocouple


Temperature Transmitter

Overview
Model TT274 is a 2-wire temperature transmitter for types J
and K thermocouples. The transmitter converts the thermocouples millivolt signal to a 4 to 20 mA DC current signal. Because
this current signal is immune to leadwire and electrical noise,
the TT274 lets you obtain accurate temperature readings from
thermocouples thousands of feet away. An ordinary twisted
pair of wires carries both the temperature signal and power for
the transmitters electronics.
With the isolation option, the mV input signal from the thermocouple is electrically isolated from the 4 to 20 mA output,
allowing use of grounded thermocouples with multiple TT274s
operating from the same power supply.
An LED conveniently indicates the status of the control loop.
The brightness is directly proportional to the loop current. A
dark LED signals an open sensor or loss of current loop power.
4 to 20 mA current signal
Fits standard 35 mm DIN rail
Field-calibrate to your thermocouple type and temperature
range
Optional Input/Output isolation to 600 VRMS

Specifications

TT274 Thermocouple
Temperature Transmitter

Ambient temperature:
Operating: -40 to 85C (-40 to 185F).
Storage: -55 to 100C (-67 to 212F).
Ambient temperature effects: 0.036% of span/C (0.02% of
span/F).
Cold junction compensation drift: 0.03C/C for -25 to 70C
ambients. 0.06C/C for -40 to -25C and 70 to 85C ambients.
Warmup drift: 0.1% of span max., assuming
Vsupply = 24 VDC and Rloop = 250 .
Stable within 15 minutes.
Input/output isolation (optional): 600 VRMS, 1 minute.
Supply voltage:
Non-Isolated: 10 to 45 volts DC with no load.
Isolated: 13 to 45 volts DC with no load.
Reverse polarity protected.
Voltage effect: 0.001% of span per volt.

Input: Type J or K thermocouple (field selectable).


Output: 4 to 20 mA DC over specified range.

Maximum load resistance: The maximum allowable resistance


of the signal-carrying loop is given by this formula:

Accuracy: 0.2% of span.


Linearity: Voltage linear.
The output signal of the TT274 is voltage linear
(not temperature linear) and is intended for use with
instruments which compensate for the nonlinear signal
output of the thermocouple sensor.
Adjustments:
Zero:
-50C to 150C (-58F to 302F).
Span:
Type J: 125 to 850C (225 to 1530F).
Type K: 150 to 1200C (270 to 2160F).

Non-Isolated:

Isolated:
Maximum output current: 28 mA.
Connections: Terminal block accepts wires from AWG 22 to
AWG 14.
Physical: Polycarbonate, DIN rail enclosure.
Weight: 4.2 oz. (119 g).
= STANDARD OPTIONS
Specifications subject to change

Page 4-14

TT274

Model number

T/C element code


J = Type J thermocouple
K = Type K thermocouple

Output: 4 to 20 mA DC

INSTRUMENTS

Specification and order options

Input/Output:
N = Non-isolated
I = Isolated
(-25/200) Factory preset temp. range:
(4 mA/20 mA temperature)
Range is user adjustable.
Refer to the Zero and Span specifications.
Temperature
scale:
C
F = Fahrenheit
C = Celsius
TT274K1N(-25/200)C = Sample part number
N

Dimensions in inches (mm)


SLIDING
CATCH

2.95
(74.9)

35 mm DIN
RAIL MOUNT

PWR
ZERO
SPAN

DIP SWITCH
RANGE SELECTION

0.886
(22.5)

3.875
(98.4)

Wiring diagram
TT274
PWR

SPAN

ZERO

THERMOCOUPLE

DC
SUPPLY
4 TO 20
mA LOOP

COPPER LEADS,
TWISTED PAIR

R1
CONTROLLER
AND/OR INDICATOR

LINE POWER

CONTROL ROOM

Specifications subject to change

Page 4-15