You are on page 1of 123

a schunk company

ITK Manual 13
Perfect Air-Conditioning for
Information and Telecommunications
Technology

www.wkt.com

ITK Manual 13

Weiss Klimatechnik GmbH


Weiss Klimatechnik has been synonymous with pioneering developments and high quality in air
conditioning technology all around the world for many decades. Our air conditioning units and
systems have proven their effectiveness wherever optimum air conditioning marginal conditions
for production processes and procedures are required for both personnel and machines.
Weiss Klimatechnik is a successful player in the fields of hygiene air conditioning, clean room
air conditioning and air conditioning solutions for data and telecommunications. An outstanding
level of quality, the highest possible degree of reliability, constantly increasing know-how,
readiness for innovation and, last not least, the staffs motivation and their commitment to the
company generate extraordinary levels of growth.

A Schunk Group Company


Schunk is a globally active technology corporation having

lation Business Units. Our solutions are used around the

the character of a medium-sized company with largely inde-

world in research, development, manufacturing and quality

pendent individual companies. Today, Schunk operates in its

assurance for numerous products, from the pharmaceutical

core markets carbon technology and ceramics, environmen-

industry where the stability of pharmaceuticals is tested,

tal simulation technology and climate technology, sintered

to highly technical components for the automobile industry

metal technology and ultrasonic welding technology. Schunk

and aerospace. Weiss Group is one of the most innovative

Group manages these divisions in terms of technology.

and important developers and manufacturers in these fields.

Schunk has 60 operating companies in 27 countries and


approximately 8,250 employees worldwide. In 2011, Schunk

With 25 companies, Weiss Group is represented in 14

had consolidated sales of approximately EUR 960 million.

countries worldwide. The company employs approximately


1,800 members of staff, 200 of whom are engineers and

Weiss Group is a division of Schunk Group.

scientists.

It is divided into the Air Solution and Environmental Simu3

ITK Manual 13

ICT innovations by the market leader Made in Germany


Under the umbrella and with the technology know-how

Our comprehensive know-how, long-standing experience

of Weiss Klimatechnik GmbH, Weiss Klimatechnik de-

in the industry as well as flexible service have made

velops ICT air condition systems which ensure the best

us one of the leading partners of renowned companies

possible climate conditions at the rooms of IT and tel-

at home and abroad. Our air-conditioning concepts are

ecommunications companies which are subject to high

tailor-made and future-oriented. As a result of their

thermal loads with the help of innovative technology.

performance and long service life, high efficiency as well


as cost effectiveness, they ensure optimum operational
reliability and investment security for both smaller
server units and bigger computer centres.

The ICT Team Your contacts


Management, assistance, commercial ICT
project management

Project and Order Management ICT Sales

Technical Customer
Service & Sales ICT

EI&C project
planning ICT

Stephan Lang
Head of ICT
Phone: +49 6408 846518
Mobil +49 172 6513502
E-mail: s.lang@wkt.com

Manfred Bittner
Phone: +49 6408 846404
E-mail: m.bittner@wkt.com

Martin Aumer
Regions: Baden-Wrttemberg,
Bavaria
Phone: +49 9128 9121257
Mobile phone: +49 151 16220407
E-mail: m.aumer@wkt.com

Rainer Bruning
Phone: +49 6408 846768
E-mail: r.braeuning@wkt.com

Katrin Bopp
ICT Assistant
Phone: +49 6408 846489
E-mail: k.bopp@wkt.com
Monika Nuhn
Commercial Project Management ICT
Phone: +49 6408 846465
E-mail: m.nuhn@wkt.com

Wolfgang Hoffmann
Phone: +49 6408 846542
E-mail: w.hoffmann@wkt.com
Mathias Kster
Phone: +49 6408 846724
Mobil: +49 174 1802410
E-mail: m.koester@wkt.com
Peter Rieder
Phone.: +49 6408 846157
E-mail: p.rieder@wkt.com
Manuel Senge
Phone: +49 6408 846154
E-mail: m.senge@wkt.com

Wolfgang Richter
Regions: Hesse, North RhineWestphalia, Rhineland-Palatinate,
Saarland
Phone: +49 6408 846515
Mobile phone: +49 172 6868210
E-mail: w.richter@wkt.com
Mario Schlotte
Regions: Berlin, Brandenburg,
Bremen, Hamburg,
Mecklenburg-Western Pomerania,
Lower Saxony,
Saxony, Saxony-Anhalt,
Schleswig-Holstein, Thuringia
Phone: +49 341 9845743
Mobile phone: +49 172 6868279
E-mail: m.schlotte@wkt.com

Kurt Mohr
Phone: +49 6408 846199
E-mail: k.mohr@wkt.com
Hannes Petzendorfer
Phone: +49 6408 846714
E-mail: h.petzendorfer@wkt.com

Content
Our equipment features

Unit-based solutions Cooling capacity 5 to 15 kW

12

deltaclima SMART
direct free cooling, downflow

13

deltaclima mini DX
air cooled system, up-/downflow

21

deltaclima mini CW
water cooled system, up-/downflow

25

Unit-based solutions Cooling capacity 15 to 150 kW

30

deltaclima DX
air cooled system, downflow

31

dataclima / uniclima
up-/downflow

37

deltaclima CW
water cooled system , downflow

45

deltaclima CW2 DUAL COIL


system includes two separate cooling coils, downflow

51

deltaclima FC
system with direct free cooling, downflow

57

Customer-specific solutions

64

deltaclima DX TELCO LINE


air cooled system, downflow

65

deltaclima CW TELCO LINE


water cooled system, downflow

71

deltaclima FC TELCO LINE


system with direct free cooling, downflow

77

Condensers

84

with AC-fans

85

with EC-fans (TELCO LINE)

86

Room-based solutions Cooling capacity > 150 kW

88

deltaclima CoolWall
perfect cooling for your datacenter

89

Refrigeration > 300 kW

100

deltachiller Turbo
air-/water cooled

101

Test room at the Reiskirchen site

108

The Weiss service concept

110

deltafinance financing concept

118

deltaclima Easy Configurator

122

Our features

Weiss Klimatechnik relies on energy-saving


Digital Scroll Technology
An air-conditioning systems energy consumption is largely weather dependent. At the same
time, the cooling output of a unit is usually selected for those periods of the year which are most
critical as regards temperature but which are only very short in Germany. For this reason, most
air conditioning systems are only operated at full load for a fraction of their operating period
and, as a result, they are overdimensioned.
Control system and efficiency available as an option

Switching time

The Digital Scroll technology permits stepless control in

The compressor output is controlled by the cyclic pitch

the range of between 10 to 100 % without a restriction of

control of the solenoid valve.

the scope of application. The system pressure and temperature are accurately controlled. Temperature stabilities
Control
50%
Regelung
50 %

of approximately +/- 0.5 K were measured in tests. Stable


evaporation temperatures lead to less dehumidification of
the indoor air and, as a result, they increase the sensitive

Belastet
charged

cold output. By reducing the switching frequency of the


compressor to the minimum, optimum efficiency and an increased service life of the plant are ensured. Moreover, low

relieved
Entlastet

10 s

liquefaction temperatures of up to 30 C ensure outstand-

10 s
20 s

ing energy efficiency in the course of the year.


In contrast to conventional speed controlled compressors,

Example 1: Switching time: 20 s, valve active/open:

the Digital Scroll compressor has stepless and precise

10 s, valve inactive/closed: 10 s, output: 50 %

power control which is switched on and off via a solenoid


valve as required. This does not only lead to a reduction in
the switching frequency and, as a result, to a longer service
life of the refrigerating plant. Moreover, significant energy
savings can be generated this way.

Control
40%
Regelung
40 %
Belastet
charged

relieved
Entlastet

12 s

8s
20 s

Example 2: Switching time: 20 s, valve active/open: 12 s,


valve inactive/closed: 8 s, output: 40 %

Our features

ESC Energy Save Control


In reduced outdoor temperatures, the ESC control system provides a reduced
condensation temperature. This reduces the power consumption and, as a result,
the run time of the compressors. ESC permits operation with high COP values.
Electronic expansion valve EEV

The air-cooled DX units with direct evaporation dissipate

The expansion valve reduces the losses of conventional

the heat extracted to the outside air via an air-cooled con-

thermostatic valves (up to 80 %) by 1,500 control steps.

denser installed outside the building. Depending on its size,


the climate chamber has two or three compressors which

Twin and/or triple compressors

are combined in a cooling circuit.

If e.g. 3 compressors are used in one refrigerating circuit, up


to 50% of the refrigerating capacity can be generated.

Power control of the climate cabinet is provided by switching on the individual compressors, in addition to the
optional Digital Scroll technology. The switching sequence

Evaporator

ensures that the cooling stage partial load operation always


reaches the best possible COP value.

refrigerating capacity stages:


compressor = 50 %
compressor = 80 %
compressor = 100 %

condenser

ESC Energy Save Control Advantages at a glance


Multi-stage power control
Electronic expansion valve (EEV)
Low starting current
No circulating pump, no control valve
No water-glycol
No additional water glycol exchanger areas
High redundancy
Easy and cost-effective assembly
Low investment costs

Our features

The state of the art: RadiCal


In addition to smart positioning of the fan below the air conditioning unit, the fan itself
also plays a decisive role and sets new standards.
The air conditioning units of the deltaclima series are

The EU Ecodesign Directive 327/2011 prescribes the mini-

equipped with the new fans with plastic impellers. Moreover,

mum efficiency of new fans launched on the market with an

this hybrid design permits an optimum design of the flow

electric driving power of 125 Watts or more.

configuration. This prevents stalls and turbulences in the


flow channel which, in turn, leads to higher efficiency and
extremely low noise emissions.
Moreover, the motor heat management is also designed
optimally. The stator is fully enclosed in a high-performance
plastic material. Air inlets in the rotor ensure perfect heating
of the motor, which again significantly increases efficiency.
In terms of efficiency, the fans today by far exceed the EuP
directive for electrically driven fans which will be required by
law soon.
AC radial fans RadiCal (backward curved)

Underfloor fan technology


Conventional technology

New technology

Unused space
Additional deflection losses
Increased heat exchanger surface
Increased filter area

(+A)
(+A)
(-pINT)
(-Pw)
clima
deltaclima
Double floor

Reduced internal losses


Reduced power consumption
Raw floor

Our features

Controller/Regulator with pcs+


deltaclima compact systems are equipped
with a pcs+ regulator as standard. In addition
to the usual exhaust/intake cascade regulation, the optimised software makes a whole
host of other functions possible, for example:
Setting and display of the EC fan load
Master/slave switching (up to 16 units)

Can be connected to superordinate building management

Continuous redundancy with automatic activation

systems via RS485, MOD-Bus, BACnet, Ethernet or SNMP.

Automatic reactivation of the unit with adjustable


Operating terminal

Controller

UPS operation (without heating and humidification)

LC display, 8 lines,

16 Bit, 16 MHz

Manual operation level

microprocessor

Recording of the last 10 alarms with date and time

6 buttons with LED

256 kB RAM

Alarm indications: air flow failure, filter soiling,

feedback

Battery-backed clock

temperature and moisture limit alarms, heater and

Alarm horn

Display connection

humidifier fault (if present)

Front installation

Programs saved in non-

Protection type IP65

time delay

Minimum supply air limit via cascade

22 characters

volatile flash memory

Web-Browser
In connection with the web card, the deltaclima unit can
be controlled and set remotely via the on-line user interface. To this end, we will simply integrate the deltaclima
unit into your network. Then, you will only need a PC with
a browser to view operating data and historic values or to
adjust set-point values. Your deltaclima unit is protected
against unauthorised access with two password-protected
access levels. Moreover, values can be saved and shown
graphically in a logger file over several days and, in case of
malfunctions, e-mail messages can be sent with this user
interface.

Our features

Highest quality according to VDI 6022


The equipment according to VDI 6022 is
available as a standard for our deltaclima
TELCO LINE climate units and as an option
for all other deltaclima climate units.
Housing/exterior details
Housing with removable inspection openings

on both sides

Sight glasses on both sides to control the filters


and heat exchangers

Additional display of the filter pressure regardless


of the unit control system

Additional manual operation for the interior lighting


of the unit and the fan chamber

Hygiene certificate by an independent test institute

Filter
Filter contact device for adjustable filter contact

Additional height offset to prevent moisture penetration

pressure

Adaption frame on the heat exchanger in order to

Interior lighting of the unit with a lamp with hygienically

ensure an optimum seal face between the filter and

the heat exchanger

10

of the filters
smooth surfaces

Fan
Additional lighting facility to control the fans

Hygiene
Large access for interior cleaning and revision of the unit

Smooth interior walls

Simple inspection of the condensate drip tray

Large sight opening for inspections of the interior of the

Internal sealing of the unit made of hygienically safe and

Seal with closed-pore hollow section seals

approved sealant

unit during operation

11

Unit-based solutions
cooling output 5 15 kW

12

deltaclima SMART

deltaclima SMART
The compact cooling device with direct free cooling

Energy-efficient, ready-to-plug-in and flexible


When planning and installing telecommunication stations, server rooms and container solutions for computer centres, it is important to house maximum computing capacity in the
smallest possible space which increases the thermal load. In addition, the sensitive units are
installed under critical on-site conditions where no external installation can be realised.
These critical conditions also present high challenges for the cooling equipment. For this
reason, a compact, efficient and reliable solution is needed, which produces a maximum
capacity irrespective of the outdoor temperatures while being energy and cost efficient.

13

deltaclima SMART

An intelligent solution for rooms of all sizes


Due to its compact design, the deltaclima SMART can be optimally integrated into existing
space concepts and fits into even the smallest of rooms. In addition, the only requirement is
a minimum clearance of only 50 cm each to the wall or the nearest other device. Due to this fact,
a scaling to the total capacity can be realised in even very small rooms without any problems
with the deltaclima SMART. Another benefit of the deltaclima SMART: The supply air can
either be blown into a double floor or directly from the front side of the device which creates
even more flexibility.
Simple, economic and safe
Due to its ready-to-plug-in and ready-to-operate design, the deltaclima

Furthermore, the high quality standards

SMART compact cooling device can be installed easily and at little cost. In

of our air conditioning systems ensure

addition, the device can be adjusted to changing spatial conditions without

maximum operational reliability and a low-

much effort. Due to the integrated control system, the operation of the

maintenance operation.

device can be adjusted easily to the respective on-site conditions.


All of these factors contribute to a safe investment and make the deltaclima SMART
1000 mm

1000 mm

1000 mm

the first choice for climate devices when it


comes to efficient air conditioning of sensitive systems and computer rooms.

500 mm

500 mm

A clearance to the wall or to another device of 500 mm is needed


ON ONE SIDE.

deltaclima SMART Benefits at a glance


Extremely energy efficient
Compact and space-saving design
Easy installation and start-up
Ready-to-plug-in
Automatic activation of the most energy-efficient

operating mode

Supply air via double floor or directly from the unit


Cooling capacity of up to 14 kW per unit
Space-saving scalability possible
Active exterior and circulating air cooling

14

deltaclima SMART

An intelligent technology for cool computers


The compact cooling device deltaclima SMART combines our proven cooling technology with
innovative features which create maximum variability and power output even under very challenging conditions. The core piece is a new, power-controlled cooling compressor with a digital
control system which allows the infinitely variable adaptation of the required cooling capacity.
Four operating modes for maximum efficiency
The deltaclima SMART is equipped with four individual
operating modes which are activated automatically by the
device depending on the ambient temperature. This way,
the system is always using the most energy-efficient mode
while creating maximum cooling capacity.
As a result of the intelligent control system, the benefits
of a free exterior air cooling with the effectiveness of a
circulating air cooling are combined in one unit for the first
time, thus ensuring that the system is protected from thermal loads at all times. Even during hot phases, the cooling
system will always work at low operating costs. Due to its
innovative technology the deltaclima SMART offers huge
possible energy savings.

Smart cooling in the smallest of rooms


With our deltaclima SMART compact cooling device we
offer you an extremely flexible, energy-efficient and spacesaving system which optimally fulfils the requirements
specified and which, at the same time, provide maximum
cost-effectiveness both in terms of costs of acquisition
and of operating costs.
With a variable capacity of 4 to14 kW per unit (which can
be expanded to a randomly scalable total capacity), deltaclima SMART forms the perfect solution in diverse fields
of application. On account of the ready-to-plug-in design of
the device, its installation is extremely easy and permits a
high degree of flexibility. Discover the clever way of ensuring a good climate with the deltaclima SMART!

15

deltaclima SMART

Four operating modes for maximum efficiency:


1. Mixed air cooling with exterior air

2. Free cooling with exterior air

When the exterior air temperature falls below the tempera-

Until the exterior air has the same temperature as the

ture required inside, the deltaclima SMART mixes the cooler

supply air, the device is operated in the free cooling

exterior air with the hot discharge air from the computer cen-

mode while the temperature conditioned supply air is led

tre and then blows the temperature-conditioned supply air

directly into the interior. The mechanical refrigeration

into the room. The mechanical refrigeration unit is not used.

unit is not used.

Exhaust air

Exhaust air

exterior air 5 C

discharge air 33 C

exterior air 22 C

discharge air 33 C

supply air 22 C

supply air 22 C

Exterior air < Supply air: The discharge air and the cooler

Exterior air temperature: Free cooling with supply of

exterior air are mixed to create the optimum supply air

temperature conditioned exterior air.

temperature.
3. Active cooling with exterior air

4. Active cooling with circulating air

If the temperature of the exterior air is higher than the

If the ambient temperature exceeds the temperature of

required supply air temperature, the device actively

the discharge air, the condenser and evaporator switch

cools down the warmer exterior air to the temperature

their functions to blow the actively cooled discharge air

required inside and directly discharges the discharge air

into the room. This way, maximum energy efficiency can

to the outside.

be guaranteed.

Exhaust air

Exhaust air

exterior air 22 C

discharge air 33 C

supply air 22 C

exterior air 22 C

discharge air 33 C

supply air 22 C

Exterior air temperature > supply air temperature: Active

Exterior air temperature > discharge air temperature: Active

cooling of the warmer exterior air inside the unit

cooling of discharge air to required supply air temperature.

16

deltaclima SMART

Technical data
Housing
Double-wall mounting with a 40 mm
insulation (fire protection class A1 according
to DIN 4102)
Greater housing rigidity, thanks to the welded
and painted design of the frame sections
Housing casing removable all round (thickness
of side and rear walls of 1.25 mm each)
Door wall thickness 1.5 mm
Immersion prime coating and powder coating,
RAL 9005 structure
Foamed-in PU gasket
Transportation with crane eyelets possible
Innovative design
Control/regulation
The electrical unit and control system are
separated from the air system side.
Inspection and maintenance work can be done
during operation as a result.
Coded plug connection for fan and sensor
system

Compl. cooling circuit with DIGITALSCROLL


compressor incl. Rotalock valves, oil sight glass
and factory-provided refrigerant filling
Refrigerant dryer with screw connections, no
soldering required when replacing the dryer
No external unit required

Fan
High-performance radial fan with optimised
efficiency, no volute casing, with backward
inclined blades, single-sided suctioning
Drive motor integrated as EC external rotor
in impeller
Fan speed is configured via EC control to suit
the individual flow rate

Filter
Cartridge-type exterior air filter F7
Filter insert outside of the housing
Filter replacement from side
(maintenance space)
Filter seal replaced during filter changing
Fiberplast frame
Filter monitoring via differential pressure
sensor

Cooling
Large-scale Cu/AI direct evaporator and
condenser with hydrophilic coating

Electronic expansion and


4-port switch valve
Optimum injection of respective refrigerant
amount
Energy saving due to exact and precise overhe
ating control
COP increase during reduced performance mode
Dehumidification switching via EEV at constant
air volume
Reversion of cooling circuit for optimum cooling
in the most energy efficient operating mode
Low internal pressure losses on air side
Low velocity for reduced pressure los
Self-filling, lockable siphon included

17

deltaclima SMART

Model

22.4 DX

Size
Framework agreement number

32.4 DX

10.6

10.6

7000001611

7000001611

2,200

3,200

Nominal volume flow Supply air


Air quantity

m/h

External pressing

Pa

50

50

Max. external pressing

Pa

250

250
0 ... 4,000

Nominal volume flow Discharge air


Air quantity

m/h

0 ... 2,800

External pressing

Pa

50

50

Max. external pressing

Pa

250

250

Cooling DX R407C and air intake 32 C / 40 % rel. humidity external air cooling1)
Type

DIGITAL-SCROLL compressor

Number of compressors

Qty.

Cooling capacity at T = 14 K

kW

10

15

Power consumption, total

kW

2.2

3.1

7.2

10.3

Max. operating current

Cooling DX R407C and air intake 36 C / 30 % rel. humidity circulating air cooling2)
Type

DIGITAL-SCROLL compressor

Number of compressors

Qty.

Cooling capacity, total

kW

10.1

14.8

Cooling capacity, sensitive

kW

10.1

14.8

Power consumption, total

kW

2.8

4.0

7.2

10.3

Max. operating current


Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit supply air1)


Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.16

0.36

1.6

1.6

Max. operating current


Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.12

0.25

1.6

1.6

Sound pressure level, discharge air nozzle

dB (A)

67

67

Sound pressure level, supply air nozzle

dB (A)

79

80

Sound pressure level, outside air nozzle

dB (A)

67

68

Sound pressure level, outgoing air nozzle

dB (A)

77

77

Freed-field sound pressure level (5 m distance)

dB (A)

55

55

Width

mm

1,000

1,000

Depth

mm

645

645

Height (above double floor)

mm

2,200

2,200

Footprint

0.6

0.6

Weight

kg

388

395

V/Ph/Hz

400/3/50

400/3/50

Max. operating current


Sound data

1) 3)

Base unit

Connection voltage

For active exterior air cooling: Discharge air temperature 36 C; exterior temperature 32 C (condenser inlet 36 C)
For active circulating air cooling: Discharge air temperature 36 C; exterior temperature 36 C (condenser inlet 36 C)
3)
For max. external pressing
We reserve the right to make technical improvements.
1)
2)

18

deltaclima SMART

Unit view

W (width)

H (height)

D (depth)

22.4 DX 10.6

Model

1,000

2,200

645

32.4 DX 10.6

1,000

2,200

645

We reserve the right to make technical improvements

19

Notes

20

deltaclima mini DX

deltaclima mini DX
The air-cooled system with innovative Energy Save Control

deltaclima mini DX operates according to the direct evaporation principle and features
the innovative Energy Save Control (ESC) designed by Weiss Klimatechnik as a standard: At
reduced outside temperatures, the power consumption of the compressors is lowered, while
their cooling output is increased at the same time.

21

deltaclima mini DX

Technical data
Housing

Fan

Double-clad wall construction with


40 mm-thick insulation (fire protection class
A1 as per DIN 4102)
High housing rigidity, thanks to welded and
painted frame profiles
Housing cladding can be removed from all
sides (side and real wall thicknesses of
1.25 mm each)
Door wall thickness: 1.5 mm
Immersion prime coated and powder coated,
RAL 9005
Foamed-in PU seal
Door wall thickness: 2 mm
Can be transported via lifting eyes
Innovative design

High-performance radial fan optimised for


efficiency, no spiral housing, features
backward-curved blades, one-sided intake
Drive motor integrated as EC external
rotor in wheel
The fan speed is set according to the
individual volume flow via the EC regulator.
The fan motor unit is installed in the base
frame and can easily be pulled out from
the front.

Controller/regulator
Electrical section and controller are sealed off
from the air-treatment section on the air side.
This allows inspection and maintenance work
to be carried out while the unit is in operation.
Mains switch accessible from the outside
Encoded plug connections for fan and sensors
Separation of power supply A and B possible

Filter
G4 cassette air circulation filter, F7 optional
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Base frame (optional)


Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)

Humidifier (optional)
Electrode steam humidifier for fully-automatic
generation and emission of mineral-free,
odourless and sterile steam
The humidifier features a microprocessor
controller and automatically adapts itself
to the existing water conductivity
(auto-adaptive).
Direct connection to all common water-supply
networks

Electric heater (optional)


Stainless-steel plain tube heating rods
Triple protection against short-circuits and
overheating via circuit breaker, safety switch
and safety thermostat

Cooling DX
Large-surface Cu/Al direct evaporator with
hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in reduced
pressure loss
Aluminium condensate pan is easy to remove
and clean
Includes self-filling, closable siphon
Cold circuit with SCROLL compressors, incl.
Rotalock valves and oil sight glass
Coolant drier with screw joints; no soldering
necessary when changing driers
Easy connection by customer

deltaclima mini DX
The benefits at a glance
Lowest possible energy costs

through EC fan technology

Can be integrated into existing


systems without any problems

Ideal for server rooms with and


without double floor

Direction of airflow: upflow or


downflow

22

deltaclima mini DX

Model

30.4 DX

Size

8.6

Nominal volume flow


Air quantity
External pressing

m3/h

3,000

Pa

20

Cooling DX R407C condensation temperature 45 C and air inlet 26 C / 45 % rel. humidity


Type

SCROLL compressor

Number of compressors

Qty.

Coldness output, total

kW

12.6

Coldness output, sensitive

kW

11.6

SHR (Sensible Heat Ratio)


Power consumption, total
Max. operating current

0.92
kW

3.2

10.3

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

G4

Fan unit
Type

EC motor, directly driven, free wheeling

Number

Qty.

Power, consumption, total

kW

0.38

Max. current consumption

2.9

Sound data
Sound output level, low-pressure side

dB (A)

71

Sound output level, high-pressure side

dB (A)

78

Housing emission

dB (A)

55

Free-field sound pressure level (2 m distance)

dB (A)

54

Width

mm

800

Depth

mm

645

Height (above double floor)

mm

1,800

Footprint

m2

0.52

Weight

kg

250

V/Ph/Hz

400/3/50

Base unit

Connection voltage
Model

30.4 DX

Options
Steam humidification
Type
Max. steam output

Electrode steam humidifier


kg/h

Max. power consumption

kW

2.3

Max. current consumption

10.0

Inches

G 3/4

mm

40

Water inlet connection


Water outlet connection
Electric heating
Type
Max. heat output
Max. current consumption

Plain tube radiator


kW

1.4

6.1

We reserve the right to make technical improvements.

23

Notes

24

deltaclima mini CW

deltaclima mini CW
The water-cooled system for maximum cooling performance with a low cost of operation

deltaclima mini CW was designed for small and medium-sized ICT rooms and can be
combined with a host of different mechanical cooling systems, such as the deltachiller
free coolers. As a result of the fans position in the base housing, the unit offers the
highest possible degree of flexibility.

25

deltaclima mini CW

Technical data
Housing

Fan

Double-clad wall construction with


40 mm-thick insulation (fire protection class
A1 as per DIN 4102)
High housing rigidity, thanks to welded and
painted frame profiles
Housing cladding can be removed from
all sides (side and rear wall thickness:
1.25 mm each)
Door wall thickness: 1.5 mm
Immersion prime coated and powder coated,
RAL 9005 structure
Foamed-in PU seal
Can be transported via lifting eyes
Innovative design

High-performance radial fan optimized for


efficiency, no spiral housing, features
backward-curved blades, one-sided intake
Drive motor integrated as EC external rotor
in wheel
The fan speed is set according to the
individual volume flow via EC regulator.
The fan motor unit is installed in the
base frame and can easily be pulled
out from the front.

Controller/Regulator
Electrical section and controller are sealed off
from the air-treatment section on the air side
This allows inspection and maintenance work
to be carried out while the unit is in operation
Mains switch accessible from the outside
Encoded plug connections for fan and sensors
Separation of power supply A and B possible

Humidifier (optional)

Filter

Electrode steam humidifier for fully automatic


generation and emission of mineral-free,
odourless and sterile steam
The humidifier features a microprocessor
controller and automatically adapts itself to
the existing water conductivity (auto-adaptive).
Direct connection to all common
water-supply networks

G4 cassette air circulation filter, F7 optional


Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Stainless-steel plain tube heating rods


Triple protection against short-circuits and
overheating via circuit breaker, safety
switch and safety thermostat

Cooling CW
Large-surface Cu/Al direct evaporator with
hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in reduced
pressure loss
Aluminium condensate pan is easy to remove
and clean
Includes self-filling, closable siphon
Cooling circuit with internal piping, including
continuous 2-port valve, optional 3-port valve
Material: Brass or red brass
Easy connection by customer

26

Base frame (optional)


Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)

Electric heater (optional)

deltaclima mini CW

Accessories and equipment option


With the following optional equipment, deltaclima mini can be optimally adapted to different
climate control and installation situations:

Intake and exhaust plenum (DX+CW)


Intake at front (DX+CW)
Multi-slat damper (DX+CW)

deltaclima mini CW The benefits at a glance

Duct connection (DX+CW)

Minimum energy costs through EC fan technology

Filter class F7 (DX+CW)

Easy integration into existing systems

Steam humidification (DX+CW)

Ideal for server rooms with and without false floor

Electrical re-heater (DX+CW)

Direction of air stream: upflow or downflow

Smoke, fire and water detectors (DX+CW)


Maximum humidity sensor (DX+CW)
Digital Scroll (DX)
3-way valve (CW)

Model

30.4 CW

Size

8.6

Nominal volume flow


Air quantity
External pressing

m3/h

3,000

Pa

20

Cooling CW Cold water 7 C / 12 C and air intake 24 C / 50 % rel. humidity


Coldness, total

kW

12.9

Coldness, sensitive

kW

10.3

Medium volume flow

m/h

2.22

Pressure loss of cooler

kPa

23.8

Pressure loss of valve

kPa

12.4

Inches

Rp 3/4

SHR (Sensible Heat Ratio)

Connection

0.80

Cooling CW Cold water 10 C / 15 C and air intake 26 C / 45 % rel. humidity


Coldness, total

kW

10.7

Coldness, sensitive

kW

10.4

Medium volume flow

m/h

1.85

Pressure loss of cooler

kPa

16.8

SHR (Sensible Heat Ratio)

Pressure loss of valve


Connection

0.97

kPa

8.6

Inches

Rp 3/4

We reserve the right to make technical improvements.

27

deltaclima mini CW

Model

30.4 CW

Size

8.6

Cooling CW Cold water 12 C / 18 C and air intake 28 C / 40 % rel. humidity


Coldness, total

kW

10.2

Coldness, sensitive

kW

10.2

Medium volume flow

m/h

1.46

Pressure loss of cooler

kPa

10.9

Pressure loss of valve

kPa

5.4

Connection

Zoll

Rp 3/4

SHR (Sensible Heat Ratio)

1.00

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

G4

Fan unit
Type

EC motor, direct driven, free wheeling

Number

Qty.

Power consumption, total

kW

0.38

Max. current consumption

2.9

Sound data
Sound output level, low-pressure side

dB (A)

71

Sound output level, high-pressure side

dB (A)

78

Housing emission

dB (A)

55

Free-field sound pressure level (2 m distance)

dB (A)

54

Width

mm

800

Depth

mm

645

Height (above double floor)

mm

1.800

Footprint

m2

0.52

Weight

kg

215

V/Ph/Hz

400/3/50

Base unit

Connection voltage
Model

30.4 CW

Options
Steam humidification
Type
Max. steam output
Max. power consumption
Max. current consumption

Electrode steam humidifier


kg/h

kW

2.3

10.0

Water intake connection

Inches

G 3/4

Water outlet connection

mm

40

Electric heater
Type
Max. heat output
Max. current consumption

We reserve the right to make technical improvements.

28

Plain tube radiator


kW

1.4

6.1

deltaclima mini DX/ CW

Unit view

W (width)

H (height)

30.4 DX 8.6

Model

800

1,800

D (depth)
645

30.4 CW 8.6

800

1,800

645

We reserve the right to make technical improvements.

29

Unit-based solutions
coldness output 15 - 150 kW

30

deltaclima DX

deltaclima DX
The air-cooled system

deltaclima DX operates according to the direct evaporation principle and features


the innovative Energy Save Control ESC designed by Weiss Klimatechnik as a standard:
With reduced outside temperatures, the power consumption of the compressors is
lowered, while their coldness output is increased at the same time. This allows redundant
compressors to be switched off.

31

deltaclima DX

Accessories and equipment options


With the following optional equipment, deltaclima DX can be optimally adapted
to different climate control and installation situations:

Intake and exhaust plenum


Intake at front
Multi-slat damper
Duct connection
Sound absorber
Filter class F7
Digital-Scroll compressor
Steam humidification
Electrical re-heater
Smoke, fire and water detectors
Maximum humidity sensor
Touch screen display

deltaclima DX The benefits at a glance


Highly efficient, all year long
Low energy consumption as with water cooling plus free cooler
Ideal for server rooms with a high thermal load
High redundancy through independent cooling circuits

32

deltaclima DX

Technical data
Housing

Electronic expansion valve

Double-clad wall construction with


40 mm-thick insulation (fire protection
class A1 as per DIN 4102)
High housing rigidity, thanks to welded and
painted frame profiles
Housing cladding can be removed from
all sides (side and rear wall thicknesses
of 1.25 mm each)
Door wall thickness: 1.5 mm
Immersion prime coated and powder coated,
RAL 9005 structure
Foamed-in PU seal
Can be transported via lifting eyes
Innovative design

Optimum injection of the respective


coolant quantity
Exact and precise overheating regulation
saves energy
COP is increased during partial-load operation
Dehumidification switching via EEV with
constant air volume

Controller/Regulator
Electrical section and controller are sealed off
from the air-treatment section on the air side
This allows inspection and maintenance work
to be carried out while the unit is in operation
Mains switch accessible from the outside
Encoded plug connections for fan and sensor
Separation of power supply A and B possible

Filter
G4 cassette air circulation filter, F7 optional
Mounted directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Cooling DX
Large-surface Cu/Al direct evaporator with
hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in reduced
pressure loss
Aluminium condensate pan is easy to
remove and clean
Includes self-filling, closable siphon
Cold circuit with SCROLL compressors,
incl. Rotalock valves and oil sight glass
Coolant drier with screw joints; no soldering
necessary when changing driers
Easy connection by customer

Fan
High-performance radial fan optimised for
efficiency, no spiral housing, features
backward-curved blades, one-sided intake
Drive motor integrated as EC external rotor
in wheel
The fan speed is set according to the
individual volume flow via EC regulator.
The fan motor unit is installed in the
base frame and can easily be pulled out
from the front.
One to two fans per unit

Base frame
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)

Humidifier (optional)
Electrode steam humidifier for fully-automatic
generation and emission of mineral-free,
odourless and sterile steam
The humidifier features a microprocessor
controller and automatically adapts itself
to the existing water conductivity
(auto-adaptive).
Direct connection to all common
water-supply network

Electric heater (optional)


Stainless-steel plain tube heating rods
Triple protection against short-circuits and
overheating via circuit breaker, safety switch
and safety thermostat
Constantly controlled

33

deltaclima DX

Model

60.4 DX

85.4 DX

125.4 DX

160.4 DX

11.9

11.9

14.9

18.9

m3/h

6,000

8,500

12,500

16,000

Pa

20

20

20

20

Size
Nominal volume flow
Air quantity
External pressing

Cooling DX R407C Condensation temperature 45 C and air intake 26 C / 45 % rel. humidity


Type

SCROLL compressor

Number of compressors

Qty.

Coldness output, total

kW

19.5

31.6

46.8

56.8

Coldness output, sensitive

kW

SHR (Sensible Heat Ratio)


Power consumption, total
Max. operating current

19.5

30.7

45.1

56.8

1.00

0.97

0.96

1.00

kW

4.5

7.8

11.7

13.5

13.1

25.6

38.4

39.3

G4

G4

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

G4

G4

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.48

0.70

1.5

1.37

1.6

4.3

4.3

8.6

Sound output level, low-pressure side

dB (A)

70

63

72

65

Sound output level, high-pressure side

dB (A)

79

74

83

75

Housing emission

dB (A)

54

48

57

50

Free-field sound pressure level


(2 m distance)

dB (A)

53

46

55

48

1,800

Max. operating current


Sound data

Base unit
Width

mm

1,100

1,100

1,400

Depth

mm

895

895

895

895

Height (above double floor)

mm

1,950

1,950

1,950

1,950

Height (below double floor)

mm

550

600

600

600

Min. height of double floor

mm

350

400

400

400

Footprint

m2

0.98

0.98

1.25

1.61

Weight (incl. base frame)

kg

455

505

585

871

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

60.4 DX

85.4 DX

125.4 DX

160.4 DX

Connection voltage
Model
Options
Steam humidification
Type
Max. steam output
Max. power consumption
Max. current consumption

Electrode steam humidifier


kg/h

15

kW

6.0

6.0

6.0

11.3

8.7

8.7

8.7

16.3

Water intake connection

Inches

G 1/2

G 1/2

G 1/2

G 1/2

Water outlet connection

mm

40

40

40

40

Electric heater
Type
Max. heat output
Max. current consumption

We reserve the right to make technical improvements.

34

Plain tube radiator, continuously regulated


kW

4.5

7.5

7.5

15

6.5

10.8

10.8

21.7

deltaclima DX

Unit view

T
B

H2

H1

Model

W (width)

H (height)

D (depth)

H1

H2

60.4 DX 11.9

1,100

2,500

895

550

1,950

85.4 DX 11.9

1,100

2,550

895

600

1,950

125.4 DX 14.9

1,400

2,550

895

600

1,950

160.4 DX 18.9

1,800

2,550

895

600

1,950

We reserve the right to make technical improvements.

35

Notes

36

dataclima uniclima

dataclima and uniclima


The universal solution with high flexibility

dataclima and uniclima the single-module compact air conditioning units. They have
been developed for use to universally cope with differing air-conditioning requirements
and meet the requirements set by VDI 6022.

37

dataclima uniclima

dataclima and uniclima Compact Air-Conditioning Units


The scope of application extends from rooms subject to extreme thermal stress for
information and communication technology down to comfort air-conditioning. Compact
construction and innovative technology ensure operating cost benefits which extend
well into the future. The optimised arrangement of mechanical and dynamic-flow
components ensure low speeds and internal pressure losses.
Maximum ease of servicing
Very little outlay is needed for starting
up, maintenance and service. All elements

dataclima uniclima The benefits at a glance

can be easily accessed in keeping with VDI

Universal scope of application

6022. Thanks to the compact housing and

Service-friendly and easy to clean as per VDI 6022

variable duct connections, the units can

Incl. Weiss Partner Package: Support from planning to

even be set up under unfavourable instal-

lation conditions. The type designations

State-of-the-art EC fan technology

reflect the field of use of the air-condition-

Nominal volume flow from 2,000 to 22,000 m3/h

ing units.

Up- and downflow execution

after-sales service

Full air-conditioning function with heating, cooling,


dataclima: Use in rooms subject to high

thermal stress

Compact, single-module construction

humidifying and de-humidifying

Filter class: F7 standard, F9 optional


uniclima: Use where comfort air-condi-

Two filter stages possible

tioning requirements apply

Highest quality as per VDI 6022


Filter

Housing profiles

Exterior air filter as bag filter in standard dimensions

Housing profiles connected with fibre-glass reinforced

Easily accessible and visible

Filter quality F7/F9, high dust storage capacity

High degree of housing rigidity

Filter frame seal replaced with filter change

Anodised aluminium profiles

Vision panel optional

Corrosion-proof

plastic corner joints complete with flame protection

Functional set-up
Refrigeration cycle and electrical equipment

Innovative design

Refrigeration cycle and electrical equipment


can be serviced during on-going operation

Fans

(without stream intervention)

Suspended fans easily removable

Clear arrangement of all components

Safe, easy handling


Easy to clean

Control and sensor


Clearly readable digital readings indicator
Filter pressure sensor autonomously for control

38

according to VDI 6022

Vision panel optional

dataclima uniclima

Technical data
Housing

Pumps, cold water (optional)

Double-shell wall construction with


45mm thick insulation producing a high
degree of housing rigidity and optimum
sound absorption
Smooth internal surfaces reduce flow losses
All-sided detachable housing lining in line
with VDI 6022
Stable, low-maintenance and flexible profile
frame structure
Optional: vision panels for fan/filter unit
allowing fans and filters to be checked
under operating conditions.
Electrical section, regulation, all-in
refrigeration components, humidifier,
PCW (Pump Cold Water) or PHW
(Pump Hot Water) valves sealed off
on the air-side from the air purification
section, thus, inspection and maintenance
possible when the unit is running.

Large-surface Cu/Al heat exchanger,


completely tubed internally,
incl. 3-way valve

Fan/Motor unit
Efficiency of optimised heavy-duty radial
fan without spiral housing, with blades bent
backwards, aspirating at one end
Drive motor as external impeller integrated
in the rotor compact design
Variable fan arrangement for maximum blow
off position diversity
Fan speed is controlled via EC or frequency
converter in keeping with individual pressure
and volume flow
Support-structured fan/motor unit easily
extractable from the front

Filter
F7/F9 filter class as cassette filter
Optional: bag filters possible with
downflow design
Filter change from the front

Refrigeration cycle

Heat exchanger
Large-surface Cu/Al heat exchanger with
2.5 mm multi-plate spacing, easy to access
for cleaning
Low passage speed thus only slight
pressure losses
Aluminium condensate tray - easily
removable and cleanable

Electrical section
Regulation system and control and power
section are in the basic appliance.
Standardised contactor/motor protection
combination for fusing the fitted component
Easily accessible main switch on the
outer housing

Humidifier
Electrode steam humidifier for automatic
generation and output of mineral-free,
odourless and sterile steam
The humidifier has a micro-processor control
and automatically adjusts to the water
conductivity present (auto-adaptive).
Direct connection to all usual water
supply grids

Electrical heating
Stainless steel smooth-bore heating rods
Threefold fusing against short circuits
and overheating by means of automatic
circuit-breaker, protective circuit-breaker
and safety thermostat constantly
controlled pump hot water (optional)
Large-surface Cu/Al heat exchanger,
completely tubed internally,
incl. 3-way valve

Scroll compressor: low-on-wear and


economical
High compressor efficiency
Future-proof, environmentally compatible
R407c refrigerant, optional R417a

39

dataclima uniclima
Type code clarification - Example
uniclima

Field of application:
uniclima: Offices, conference rooms; deltaclima: Rooms subject to high thermal stress, e.g. computer centres

75.

Scales: 75. = 7,500 m3/h

Version number: Version 3

DX / CW

Type of cooling: DX = direct evaporator; CW = cold water

D/U

Air direction through cooler: D = downflow, U = upflow

13.

Appliance width: 13. = 1,355 mm

Appliance depth: 8 = 850 mm

Kind of appliance: N = Normal

Series

35.3

55.3

75.3

90.3

120.3

160.3

220.3

m3/h

3,500

5,500

7,500

9,000

12,000

16,000

22,000

Pa

300

470

360

210

450

320

390

Nominal volume flow


Air pressure
External pressing*
*More powerful fan/motor unit on request

Cooling Refrigeration cycle, air cooled externally (tc -50 C as per Eurovent) and air intake 27 C / 46 % rel. humidity<
Cooling capacity, total

kW

13.4

18.4

29.2

34.9

45.4

54.4

73.1

Cooling capacity, sensitive

kW

11.5

17.9

26.2

31.4

41.7

52.3

71.0

Qty.

kVA

8.8

2 x 8.8

2x9

3 x 8.8

3x9

4x9

DX

DX

DX

DX

DX

DX

DX

Type
Number

Scroll compressor

Refrigerant
Electrical connected load

R407C

Part type code (DX direct evaporator)

Cooling Cold water 7 C / 12.5 C and air intake 27 C / 46 % rel. humidity*


*Other temperatures on request
Cooling capacity, total

kW

11.6

26.1

36.6

42.9

60.6

75

106

Cooling capacity, sensitive

kW

9.8

20.4

28.5

33.5

46.8

58.9

82.7

Cold water volume

m3/h

1.8

4.1

5.7

6.7

9.5

11.7

16.5

Cooler pressure loss

kPa

11.1

10

15.6

10.1

15.5

14.2

12.8

CW valve

DN

25

25

25

25

25

32

40

Valve pressure loss

kPa

Part type code (CW cold water)

16

17

31

18

33

23

27

CW

CW

CW

CW

CW

CW

CW

560

560

560

Fan/Motor Unit*
*More powerful fan/motor unit on request

Type
Quantity

EC motor, directly driven, free wheeling


pc.

mm

450

560

Motor design
Rotor diameter

External impeller

Motor control

560

560

Internal commutating unit

Motor rated output

kW

1.1

3.1

3.1

3.1

2 x 3.1

2 x 3.1

3 x 3.1

Current input, max.

2.4

4.9

4.9

4.9

2 x 4.9

2 x 4.9

3 x 4.9

Electrical connected load


Speed
Protection class
Part type code (D-downflow/U-upflow)

We reserve the right to make technical improvements.

40

kVA

1.1

3.1

3.1

3.1

2 x 3.1

2 x 3.1

3 x 3.1

1/min

1,620

1,510

1,510

1,510

1,510

1,510

1,510

IP

F 54
D

dataclima uniclima
Series

35.3

55.3

75.3

90.3

120.3

160.3

220.3

200

200

F7 filter in the intake*


*also possible as bag filter (only downflow) and as a second filter stage

Type
Number

Cassette filter
pc.

Filter class as per DIN EN 779


Recommended final pressure

F7
Pa

200

200

200

200

200

Housing dimensions
Width

mm

1,090

1,090

1,355

1,610

2,140

2,405

2,405

Depth

mm

650

850

850

850

850

1,100

1,100

Height

mm

1,950

1,950

1,950

1,950

1,950

1,950

1,950

10.6

10.8

13.8

16.8

21.8

24.11

24.11

Part type code (width, depth)


All-in basic appliance
Cooling output, total

kW

11.6

26.1

36.6

42.9

60.6

75

106

Cooling output, sensitive

kW

9.8

20.4

28.5

33.5

46.8

58.9

82.7

Cold water quantity

m3/h

1.8

4.1

5.7

6.7

9.5

11.7

16.5

Cooler pressure loss

kPa

11.1

10

15.6

10.1

15.5

14.2

12.8

CW valve

DN

25

25

25

25

25

32

40

Valve pressure losses

kPa

16

17

31

18

33

23

27

32.6

33.2

45.3

Supply voltage
Electrical connected load*
*without condenser

V/Ph/Hz
kVA

Overall type code (ex.)

Series

400/3/50
9.9

12.1

20.7

21.1

35.3 DXD
10.6 N

55.3 DXD
10.8 N

75.3 DXD
13.8 N

35.3

55.3

75.3

90.3 DXD 120.3 DXD 160.3 DXD 220.3 DXD


16.8 N
21.8 N
24.11 N
24.11 N
90.3

120.3

160.3

220.3

300

300

300

300

Options
Filter F9 in the intake*
*also possible as bag filter (only downflow) and as a second filter stage

Type
Number

Cassette filter
pc.

Filter class as per DIN EN 779


Recommended final pressure

F9
Pa

300

300

300

Max. quantity

pc.

Current input

4.7

7.4

10

11.9

15.9

21.1

29.1

Humidifying Steam generator


Type

Electrode steam humidifier

Input power

kW

3.2

6.8

8.1

10.8

14.4

19.8

Electrical connected load

kVA

3.2

6.8

8,1

10.8

14.4

19.8

Max. steam output

kg/h

4.2

6.6

10.8

14.4

19,2

26.4

1-10

1-10

1-10

1-10

1-10

Water supply
Water conductivity

bar
S/cm

125 - 900 125 - 900 125 - 900 125 - 900 125 - 900

1-10

1-10

125 - 900

125 - 900

Heating Electrical heating


Type

Smooth bore radiator

Max. number of heating rods

Qty.

Max. heating output

kW

7.5

15

15

Max. stages
Current input
Electrical connected load

12

21

21

21

30

Continuous
A

10.8

21.7

21.7

30.3

30.3

30.3

43,4

kVA

7.5

15

15

21

21

21

30
79.2

Heating Hot water 70/50


Heating output at intake temp. 15C
Hot water flow rate
Water-sided pressure loss

kW

15.9

23.9

32.4

36.2

49.2

66.5

m3/h

0.7

1.4

1.6

2.2

2.9

3.5

kPa

9.1

6.9

9.5

6.8

6.9

8.6

8.2

PWW valve

DN

15

15

15

15

25

25

25

Water-sided pressure loss - valve

kPa

11

12

16

18

27

16

17

We reserve the right to make technical improvements.

41

dataclima uniclima

Series

35.3

55.3

75.3

90.3

120.3

160.3

220.3

Heating Hot water 70/50 (VE)*


*PH = Preheater in the top-mounted box (only downflow)

Heating output at intake temp. -15C

kW

22

34.7

47.2

57.6

79

114.6

138.5

m3/h

1.5

2.1

2.5

3.5

6.1

Water-sided pressure loss

kPa

12,9

14.7

14.3

13

12

8.5

11.8

PWW valve

DN

15

15

15

15

25

25

25

Water-sided pressure loss - valve

kPa

16

20

26

38

22

26

35

Hot water flow rate

We reserve the right to make technical improvements.

Front view

Lateral view

Options
All dampers also executable as nozzles
300 to 840 mm high top-mounted and

base boxes can be supplied

150 to 650 mm high base frames can


be supplied

Max. air volume for each lateral


connection: 9,000 m3/h

Media connections: left side


(top, bottom or on the side)

Electrical connections: right side


(top, bottom or on the side)

Intake/blow-off honeycomb grid possible

Front view of unit

at the side and front, when no duct

system is needed and appliance is

directly in the room.

Left side view of unit

View of unit from top

(symmetrical arrangement of the nozzles)


(*70)

(*70)

Operating side

Maintenance envelope
min. unit depth

42

dataclima uniclima

Unit

L1

L2

L3

L4

B1

B2

H2

35.3

1.090

650

765

1.000

177

147

550

550

150 - 650

55.3

1.090

850

765

1.000

177

147

750

750

150 - 650

75.3

1.355

850

1.030

1.255

172

152

750

750

150 - 650

90.3

1.610

850

1.260

1.505

192

157

750

750

150 - 650

120.3

2.140

850

1.790

2.035

192

157

710*

750

150 - 650

160.3

2.405

1.100

2.035

2.300

212

157

(1.000) 960*

1.000

150 - 650

220.3

2.405

1.100

2.035

2.300

212

157

(1.000) 960*

1.000

150 - 650

We reserve the right to make technical improvements.

Supply connections
Lateral view from the left side

Lateral view from the right sight

Partial view from the top

PHW heater supply flow


PHW heater return flow
Humidifier supply
Humidifier discharge
PCW supply flow/refrigerant liquid line
PCW return flow/refrigerant hot gas line
Electric line inlets
Condensate discharge

43

Notes

44

deltaclima CW

deltaclima CW
The water-cooled system for maximum cooling performance with a low cost of operation

deltaclima CW was designed for IT rooms subjected to high heat loads and can be combined with a host of different mechanical cooling systems, for example the deltachiller
free coolers. By situating the fan under the floor surface, the housing provides an especially
large amount of space for large filter and heat exchanger surface.

45

deltaclima CW

Accessories and equipment options


With the following optional equipment deltaclima CW can be optimally adapted to
different climate control and installation situations:

Intake and exhaust plenum


Intake at front
Multi-slat damper
Duct connection
Sound absorber
3-way valve
Fan protection grid
Filter class F7
Steam humidification
Electrical re-heater
Smoke, fire and water detectors
Maximum humidity sensor

deltaclima CW The advantages at a glance


Minimal energy costs through reduced fan power
Especially large filter and heat exchanger surfaces
High cooling output with a small footprint
Easy integration into existing systems

46

deltaclima CW

Technical data
Housing

Fan

Double-clad wall construction with


40 mm-thick insulation (fire protection
class A1 as per DIN 4102)
High housing rigidity, thanks to welded
and painted frame profiles
Housing cladding can be removed from
all sides (side and rear wall thicknesses:
at 1.25 mm each)
Door wall thickness: 1.5 mm
Immersion prime coated and powder coated,
RAL 9005 texture
Foamed-in PU seal
Can be transported via lifting eyes
Innovative design

High-performance radial fan optimised for


efficiency, no spiral housing, features
backward-curved blades, one-sided intake
Drive motor integrated as EC external rotor
in wheel
The fan speed is set according to the
individual volume flow via EC regulator.
The fan motor unit is installed in the
base frame and can easily be pulled out
from the front.
One to four fans per unit

Controller/Regulator
Electrical section and controller are sealed off
from the air-treatment section on the air side
This allows inspection and maintenance work
to be carried out while the unit is in operation
Mains switch accessible from the outside
Encoded plug connections for fan and sensors
Separation of power supply A and B possible

Filter
G4 cassette air circulation filter, F7 optional
Installed directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Cooling CW

Base frame
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)

Humidifier (optional)
Electrode steam humidifier for fully-automatic
generation and emission of mineral-free,
odourless and sterile steam
The humidifier features a microprocessor
controller and automatically adapts itself
to the existing water conductivity
(auto-adaptive)
Direct connection to all common
water-supply networks

Electrical heater (optional)


Stainless-steel plain tube heating rods
Triple protection against short-circuits and
overheating via circuit breaker, safety switch
and safety thermostat
Continuously controlled

Large-surface Cu/Al direct evaporator with


hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in
reduced pressure loss
Aluminium condensate pan is easy to
remove and clean
Includes self-filling, closable siphon
Cooling circuit with internal piping, including
continuous 2-way valve, optional 3-way valve
Material: Brass or red brass
Easy connection by customer

47

deltaclima CW

Model

60.4 CW

110.4 CW

220.4 CW

330.4 CW

380.4 CW

11.7

11.9

18.9

26.9

31.10

m3/h

6,000

11,000

22,000

33,000

38,000

Pa

20

20

20

20

20

Size
Nominal volume flow
Air quantity
External pressing

Cooling CW Cold water 7 C / 12 C and air intake 24 C / 50 % rel. humidity


Cooling output, total

kW

26.1

42.7

84.2

128.4

198.6

Cooling output, sensitive

kW

20.8

34.9

69

104.8

152.7

0.80

0.82

0.82

0.82

0.77

Medium volume flow

m3/h

4,49

7.34

14.47

22.07

34.12

Cooler pressure loss

kPa

29,9

34.5

33.3

33.3

41.1

kPa

20.2

21

33.5

30.4

72.8

Inches

Rp 1

Rp 1 1/4

Rp 1 1/2

Rp 2

Rp 2 1/2

SHR (Sensible Heat Ratio)

Valve pressure loss


Connection

Cooling CW Cold water 10 C / 15 C and air intake 26 C / 45 % rel. humidity


Cooling output, total

kW

21.9

37.2

73.7

111.7

158.1

Cooling output, sensitive

kW

21.2

36.9

73.3

110.7

146.2

0.97

0.99

0.99

0.99

0.92

Medium volume flow

m3/h

3.77

6.4

12.67

19.21

27.2

Cooler pressure loss

kPa

21.6

26.6

25.9

25.6

27

Valve pressure loss

kPa

14.2

16

25.7

23.1

46.2

Inches

Rp 1

Rp 1 1/4

Rp 1 1/2

Rp 2

Rp 2 1/2

SHR (Sensible Heat Ratio)

Connection

Cooling CW Cold water 12 C / 18 C and air intake 28 C / 40 % rel. humidity


Cooling output, total

kW

20.8

35.2

69.8

105.8

151.5

Cooling output, sensitive

kW

20.8

35.2

69.8

105.8

151.5

1.00

1.00

1.00

1.00

1.00

SHR (Sensible Heat Ratio)


Medium volume flow

m3/h

2.99

5.06

10.02

15.2

21.76

Cooler pressure loss

kPa

14.1

17.3

16.8

16.6

17.9

Valve pressure loss


Connection

kPa

8.9

10

16.1

14.4

29.6

Inches

Rp 1

Rp 1 1/4

Rp 1 1/2

Rp 2

Rp 2 1/2

G4

G4

G4

G4

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

G4

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.57

1.26

2.74

4.08

4.68

Max. current consumption

1.6

4.3

8.6

12.9

17.2

Sound output level, low-pressure side

dB (A)

70

69

72

73

72

Sound output level, high-pressure side

dB (A)

79

80

83

84

82

Housing emission

dB (A)

55

53

56

58

56

Free-field sound pressure level (2 m distance)

dB (A)

53

52

55

56

55

Width

mm

1,100

1,100

1,800

2,600

3,100

Depth

mm

695

895

895

895

995

Height (above double floor)

mm

1,950

1,950

1,950

1,950

1,950

Height (below double floor)

mm

550

600

600

600

600

Min. double floor height

mm

350

400

400

400

400

Footprint

0.76

0.98

1.61

2.33

3.08

Weight (incl. base frame)

kg

340

385

585

843

1.100

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

Sound data

Base unit

Connection voltage

We reserve the right to make technical improvements.

48

deltaclima CW

Model

60.4 CW

110.4 CW

220.4 CW

330.4 CW

380.4 CW

Options
Steam humidification
Type

Electrode steam humidifier

Max. steam output

kg/h

15

15

15

Max. power consumption

kW

6.0

6.0

11.3

11.3

11.3

Max. current consumption

8,7

8,7

16,3

16.3

16.3

Water intake connection

Inch

G 1/2

G 1/3

G 1/4

G 1/5

G 1/6

Water outlet connection

mm

40

40

40

40

40

Electric heater
Type

Plaint tube radiator, continuously regulated

Max. heat output

kW

4.5

7.5

15

22.5

30

6.5

10.8

21.7

32.5

43.3

Max. current consumption

Unit view
T
B

H2

H1

W (width)

H (height)

D (depth)

H1

H2

60.4 CW 11.7

Model

1,100

2,500

695

550

1,950

110.4 CW 11.9

1,100

2,550

895

600

1,950

220.4 CW 18.9

1,800

2,550

895

600

1,950

330.4 CW 26.9

2,600

2,550

895

600

1,950

380.4 CW 31.10

3,100

2,550

995

600

1,950

We reserve the right to make technical improvements.

49

Notes

50

deltaclima CW2 DUAL COIL

deltaclima CW2 DUAL COIL


The system with two cold-water coolers

deltaclima CW2 DUAL COIL was developed specifically for the climate control of
especially critical IT and telecommunication systems. Two separate cold water coolers
provide additional security should one of the cooling circuits fail. In addition, one of these
circuits can be operated with well water instead of a free cooling battery, for example.

51

deltaclima CW2 DUAL COIL

Accessories and equipment options


deltaclima CW2 DUAL COIL can be adjusted to the respective air conditioning
and installation situation with the help of the following equipment options:

Intake and exhaust plenum


Intake at front
Multi-slat damper
Duct connection
Sound absorber
3-way valve
Fan protection grid
Filter class F7
Steam humidification
Electrical re-heater
Smoke, fire and water detectors
Maximum humidity sensor

deltaclima CW2 DUAL COIL The advantages at a glance


For critical IT and telecommunication systems
With two hydraulically separated cold water circuits
Additional energy savings during operation, e.g. with well water
Large filter and heat exchanger surfaces

52

deltaclima CW2 DUAL COIL

Technical data
Housing

Fan

Double-wall mounting with a 40 mm


insulation (fire protection class A1 according
to DIN 4102)
High housing rigidity, thanks to the welded
and painted design of the frame sections
Housing casing removable all round (thickness
of side and rear walls of 1.25 mm each)
Door wall thickness 1.5 mm
Immersion prime coating and powder coating,
RAL 9005 structure
Foamed-in PU gasket
Transportation with crane eyelets possible
Innovative design

High-performance radial fan optimised for


efficiency, no spiral housing, features
backward-curved blades, one-sided intake
Drive motor integrated as EC external
rotor in wheel
The fan speed is set according to the
individual volume flow via EC regulator
The fan motor unit is installed in the
base frame and can easily be pulled out
from the front
One to three fans per unit

Controller/Regulator
Electrical section and controller are sealed off
from the air-treatment section on the air side
This allows inspection and maintenance work
to be carried out while the unit is in operation.
Mains switch accessible from the outside
Encoded plug connections for fan and sensor
Separation of power supply A and B possible

Filter
G4 cassette air circulation filter, F7 optional
Installed directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Cooling CW
Large-surface Cu/Al direct evaporator with
hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in reduced
pressure loss
Aluminium condensate pan is easy to
remove and clean
Includes self-filling, closable siphon
Cooling circuit with internal piping, including
continuous 2-way valve, optional 3-way valve
Material: Brass or red brass
Easy connection by customer

Base frame
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm).

Humidifier (optional)
Electrode steam humidifier for fully-automatic
generation and emission of mineral-free,
odourless and sterile steam
The humidifier features a microprocessor
controller and automatically adapts itself
to the existing water conductivity
(auto-adaptive).
Direct connection to all common
water-supply networks

Electric heater (optional)


Stainless-steel plain tube heating rods
Triple protection against short-circuits
and overheating via circuit breaker, safety
switch and safety thermostat
Constantly controlled

53

deltaclima CW2 DUAL COIL

Model

90.4 CW2

180.4 CW2

280.4 CW2

11.9

18.9

26.9

m3/h

9,000

18,000

28,000

Pa

20

20

20

Size
Nominal volume flow
Air quantity
External pressing

Cooling CW Cold water 7 C / 12 C and air intake 24 C / 50 % rel. humidity


Cooling output, total

kW

31.4

63.9

101.9

Cooling output, sensitive

kW

26.2

53.3

84.4

0.83

0.83

0.83

SHR (Sensible Heat Ratio)


Medium volume flow

m3/h

5.39

10.99

17.51

Cooler pressure loss

kPa

37.1

37.2

39.5

Valve pressure loss


Connection

kPa

11.3

19.3

19.2

Inches

Rp 1 1/4

Rp 1 1/2

Rp 2

Cooling CW Cold water 10 C / 15 C and air intake 26 C / 45 % rel. humidity


Cooling output, total

kW

27.7

56.1

88.5

Cooling output, sensitive

kW

27.7

56.1

88.5

SHR (Sensible Heat Ratio)

1.00

1.00

1.00

m3/h

4.77

9.65

15.23

Cooler pressure loss

kPa

29.4

29

30.3

Valve pressure loss

kPa

8.9

14.9

14.5

Inches

Rp 1 1/4

Rp 1 1/2

Rp 2

Medium volume flow

Connection

Cooling CW Cold water 12 C / 18 C and air intake 28 C / 40 % rel. humidity


Cooling output, total

kW

24

53.1

83.9

Cooling output, sensitive

kW

24

53.1

83.9

SHR (Sensible Heat Ratio)

1.00

1.00

1.00

Medium volume flow

m3/h

3.44

7.62

12.05

Cooler pressure loss

kPa

16.2

18.8

19.7

Valve pressure loss


Connection

kPa

4.6

9.3

9.1

Inches

Rp 1 1/4

Rp 1 1/2

Rp 2

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

G4

G4

G4

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.96

1.98

3.09

Max. current consumption

4.3

8.6

12.9

Sound data
Sound output level, low-pressure side

dB (A)

64

67

70

Sound output level, high-pressure side

dB (A)

75

78

80

Housing emission

dB (A)

49

52

55

Free-field sound pressure level (2 m distance)

dB (A)

47

50

53
2,600

Base unit
Width

mm

1,100

1,800

Depth

mm

895

895

895

Height (above double floor)

mm

1,950

1,950

1,950

Height (below double floor)

mm

550

600

600

Min. double floor height

mm

350

400

400

Footprint

0.98

1.61

2.33

Weight (incl. base frame)

kg

380

605

883

V/Ph/Hz

400/3/50

400/3/50

400/3/50

Connection voltage

We reserve the right to make technical improvements.

54

deltaclima CW2 DUAL COIL

Model

90.4 CW2

180.4 CW2

280.4 CW2

Options
Steam humidification
Type

Electrode steam humidifier

Max. steam output


Max. power consumption
Max. current consumption

kg/h

15

15

kW

6.0

11.3

11.3

8.7

16.3

16.3

Water intake connection

Inches

G 1/3

G 1/4

G 1/5

Water outlet connection

mm

40

40

40

Electric heater
Type

Plain tube radiator, continuously regulated

Max. heat output


Max. current consumption

kW

7.5

15

22.5

10.8

21.7

32.5

Unit view
T
B

H2

H1

Size

W (width)

H (height)

D (depth)

H1

H2

90.4 CW2 11.9

1,100

2,550

895

600

1,950

180.4 CW2 18.9

1,800

2,550

895

600

1,950

280.4 CW2 26.9

2,600

2,550

895

600

1,950

We reserve the right to make technical improvements.

55

Notes

56

deltaclima FC

deltaclima FC
The system with direct free cooling

deltaclima FC is linked to the outside air by a special housing construction, allowing the
system to directly utilise the advantages of outdoor cooling. Automatic regulation ensures
that heat dissipation occurs in a favourable way using outside air, all year long. There are
two basic systems to choose from - deltaclima DX ESC and deltaclima CW.

57

deltaclima FC

Accessories and equipment options


With the following optional equipment, deltaclima FC can be optimally adapted
to different climate control and installation situations:

Digital-Scroll compressor (DX)


3-way valve (CW)
Fan protection grid (CW+DX)
Filter class F7 (CW+DX)
Steam humidification (CW+DX)
Electrical re-heater (CW+DX)
Smoke, fire and water detectors (CW+DX)
Maximum humidity sensor (CW+DX)

deltaclima FC The advantages at a glance


Specifically designed for IT rooms with direct access to outside air
Direct utilisation of outside air thanks to additional housing
construction
Minimal installation expenditure
Mechanical cooling can be integrated if necessary
Double supply UPS operation

58

deltaclima FC

Technical data
Housing
Double-wall mounting with a 40 mm
insulation (fire protection class A1
according to DIN 4102)
High housing rigidity, thanks to the welded
and painted design of the frame sections
Housing casing removable all round (thickness
of side and rear walls of 1.25 mm each)
Door wall thickness 1.5 mm
Immersion prime coating and powder coating,
RAL 9005 structure
Foamed in PU gasket
Transportation with crane eyelets possible
Innovative design

Controller/Regulator
Electrical section and controller are sealed off
from the air-treatment section on the air side
This allows inspection and maintenance work
to be carried out while the unit is in operation
Mains switch accessible from the outside
Encoded plug connections for fan and sensors
Separation of power supply A and B possible

Material: Brass or red brass (CW)

Electronic Expansion Valve


Optimum injection of the respective
coolant quantity
Exact and precise overheating regulation
saves energy
COP is increased during partial-load operation
Dehumidification switching via EEV with
constant air volume

Fan
High-performance radial fan optimised for
efficiency, no spiral housing, features
backward-curved blades, one-sided intake
Drive motor integrated as EC external
rotor in wheel
The fan speed is set according to the
individual volume flow via EC regulator
The fan motor unit is installed in the
base frame and can easily be pulled
out from the front
One to three fans per unit

Filter
G4 cassette air circulation filter, F7 optional
Installed directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Cooling CW+DX
Large-surface Cu/Al direct evaporator with
hydrophilic coating (CW+DX)
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work (CW+DX)
Low passage speed, which results in reduced
pressure loss (CW+DX)
Aluminium condensate pan is easy to remove
and clean (CW+DX)
Includes self-filling, closable siphon (CW+DX)
Cold circuit with SCROLL compressors, incl.
Rotalock valves and oil sight glass (CW+DX)
Refrigerant dryer with screw connections,
no soldering required when replacing
the dryer (CW+DX)
Easy connection by customer (CW+DX)
Cooling circuit with internal piping,
including continuous 2-way valve,
optional 3-way valve (CW)

Base frame
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)

Humidifier (optional)
Electrode steam humidifier for fully-automatic
generation and emission of mineral-free,
odourless and sterile steam
The humidifier features a microprocessor
controller and automatically adapts itself
to the existing water conductivity
(auto-adaptive).
Direct connection to all common
water-supply networks

Electric heating (optional)


Stainless steel smooth-bore heating rods
Threefold fusing against short circuits and
overheating by means of automatic
circuit-breaker, protective circuit-breaker
and safety thermostat
Constantly controlled

59

deltaclima DX FC

Model
Size

30.4 DX FC

85.4 DX FC

125.4 DX FC

160.4 DX FC

8.6

11.9

14.9

18.9

Nominal volume flow


Air quantity

m3/h

3,000

8,500

12,500

16,000

External pressing

Pa

150

150

150

150

Max. external pressing

Pa

150

420

170

420

Cooling DX R407C Condensation temperature 45 C and air intake 26 C / 45 % rel. humidity


Type

DIGITAL-SCROLL compressor

Number of compressors

Qty.

Cooling output, total

kW

12.6

31.6

46.8

56.8

Cooling output, sensitive

kW

11.6

30.7

45.1

56.8

SHR (Sensible Heat Ratio)


Power consumption, total
Max. operating current

0.92

0.97

0.96

1.00

kW

3.2

7.8

11.7

13.5

10.3

25.6

38.4

39.3

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.63

1.22

2.16

2.41

Max. current consumption

3.5

4.3

4.3

8.6

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

F7

F7

Sound data
Sound output level, low-pressure side

dB (A)

72

65

71

68

Sound output level, high-pressure side

dB (A)

83

75

82

78

Housing emission

dB (A)

56

50

56

53

Free-field sound pressure level (2 m distance)

dB (A)

55

48

55

51

Width

mm

800

1,100

1,400

1,800

Depth

mm

645

895

895

895

Height (above double floor)

mm

1,800

1,950

1,950

1,950

Height (below double floor)

mm

600

600

600

Min. double floor height

mm

400

400

400

Footprint

m2

0,52

0,98

1,25

1,61

Base unit

Weight (incl. base frame and FC top part)


Connection voltage

kg

300

621

720

1071

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

30.4 DX FC

85.4 DX FC

125.4 DX FC

160.4 DX FC

Model
Options
Steam humidification
Type
Max. steam output
Max. power consumption
Max. current consumption

Electrode steam humidifier


kg/h

15

kW

2.3

6.0

6.0

11.3

10.0

8.7

8.7

16.3

Water intake connection

Inches

G 3/4

G 1/2

G 1/2

G 1/2

Water outlet connection

mm

40

40

40

40

Electric heater
Type
Max. heat output
Max. current consumption

We reserve the right to make technical improvements.

60

Plain tube radiator, constantly regulated


kW

1.4

7.5

7.5

15

6.1

10,8

10.8

21.7

deltaclima DX FC

Unit view
T
B

H3

H2

H1

Size
30.4 DX FC 8.6
60.4 DX FC 11.9

W (width)

H (height)

D (depth)

H1

H2

H3

800

1,800

645

1,800

400

1,100

2,500

895

550

1,950

800

85.4 DX FC 11.9

1,100

2,550

895

600

1,950

800

125.4 DX FC 14.9

1,400

2,550

895

600

1,950

800

160.4 DX FC 18.9

1,800

2,550

895

600

1,950

800

We reserve the right to make technical improvements.

61

deltaclima CW FC
Model

30.4 CW FC

110.4 CW FC

220.4 CW FC

330.4 CW FC

8.6

11.9

18.9

26.9

m3/h

3,000

11,000

22,000

33,000

External pressing

Pa

150

150

150

150

Max. external pressing

Pa

150

200

200

200

84.2

128.4
104.8

Size
Nominal volume flow
Air quantity

Cooling CW Cold water 7 C / 12 C and air intake 24 C / 50 % rel. humidity


Cooling output, total

kW

12.9

42.7

Cooling output, sensitive

kW

10.3

34.9

69

0.80

0.82

0.82

0.82

SHR (Sensible Heat Ratio)


Medium volume flow

m3/h

2.22

7,34

14.47

22.07

Cooler pressure loss

kPa

23.8

34.5

33.,3

33.3

Valve pressure loss

kPa

12.4

21

33.5

30.4

Inches

Rp 3/4

Rp 1 1/4

Rp 1 1/2

Rp 2

Connection

Cooling CW Cold water 10 C / 15 C and air intake 26 C / 45 % rel. humidity


Cooling output, total

kW

10.7

37.2

73.7

111.7

Cooling output, sensitive

kW

10.4

36.9

73.3

110.7

0.97

0.99

0.99

0.99

SHR (Sensible Heat Ratio)


Medium volume flow

m3/h

1.85

6.4

12.67

19.21

Cooler pressure loss

kPa

16.8

26.6

25.9

25.6

Valve pressure loss

kPa

8.6

16

25.7

23.1

Inches

Rp 3/4

Rp 1 1/4

Rp 1 1/2

Rp 2

Connection

Cooling CW Cold water 12 C / 18 C and air intake 28 C / 40 % rel. humidity


Cooling output, total

kW

10.2

35.2

69.8

105.8

Cooling output, sensitive

kW

10.2

35.2

69.8

105.8

1.00

1.00

1.00

1.00

SHR (Sensible Heat Ratio)


Medium volume flow

m3/h

1.46

5.06

10.02

15.2

Cooler pressure loss

kPa

10.9

17.3

16.8

16.6

Valve pressure loss

kPa

5.4

10

16.1

14.4

Inches

Rp 3/4

Rp 1 1/4

Rp 1 1/2

Rp 2

F7

F7

Connection
Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.63

1.89

4.01

6.06

Max. current consumption

3.5

4.3

8.6

12.9

Sound output level, low-pressure side

dB (A)

72

69

72

74

Sound output level, high-pressure side

dB (A)

83

79

83

84

Housing emission

dB (A)

56

54

57

59

Free-field sound pressure level (2 m distance)

dB (A)

55

52

55

57

Width

mm

800

1,100

1.800

2,600

Depth

mm

645

895

895

895

Height (above double floor)

mm

1,800

1,950

1,950

1,950

Height (below double floor)

mm

600

600

600

Min. double floor height

mm

400

400

400

Footprint

m2

0.52

0.98

1.61

2.33

Sound data

Base unit

Weight (incl. base frame and FC top)


Connection voltage

We reserve the right to make technical improvements.

62

kg

265

520

790

1,138

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

deltaclima CW FC
Model

30.4 CW FC

85.4 CW FC

160.4 CW FC

250.4 CW FC

Options
Steam humidification
Type

Electrode steam humidifier

Max. steam output

kg/h

15

15

kW

2.3

6.0

11.3

11.3

Max. power consumption


Max. current consumption

10.0

8.7

16.3

16.3

Water intake connection

Inches

G 3/4

G 1/2

G 1/2

G 1/2

Water outlet connection

mm

40

40

40

40

Electric heater
Type

Plain tube radiator, continuously regulated

Max. heat output


Max. current consumption

kW

1.4

7.5

15

15

6.1

10.8

21.7

21.7

Unit view
T
B

H3

H2

H1

Size

W (width)

H (height)

T (depth)

H1

H2

H3

800

1,800

645

1,800

400

110.4 CW FC 11.9

1,100

2,550

895

600

1,950

800

220.4 CW FC 18.9

1,800

2,550

895

600

1,950

800

330.4 CW FC 26.9

2,600

2,550

895

600

1,950

800

30.4 CW FC 8.6

We reserve the right to make technical improvements.

63

Customer-specific
solutions

64

deltaclima DX TELCO LINE

deltaclima DX TELCO LINE


The air-cooled system specifically for the telecommunications industry

deltaclima DX TELCO LINE operates according to the direct evaporation principle and
features the innovative Energy-Saver Controller (ESC) designed by Weiss Klimatechnik
as standard. With reduced outside temperatures, the power consumption of the compressors is lowered, while their coldness output is increased at the same time. This allows
redundant compressors to be switched off.

65

SC

deltaclima DX TELCO LINE

Control with SAIA PCD


The deltaclima DX TELCO LINE compact
systems are equipped with a SAIA PCD
regulator as a standard. In addition to the
usual air exhaust/intake cascade regulation,
the optimised software makes a whole host
of other functions possible, for example:

Can be connected to superordinate building management


systems via RS485, BACnet, or Ethernet.
Operating terminal

Controller

5,7 TFT display

Microprocessor, Motorola

VGA 640 x 480

65536 colours

1 MB RAM

Setting and display of the EC fan load

Front installation

Battery-backed clock

Master-slave switching (up to 8 units)

Protection type: IP65

Ethernet interface

Continuous redundancy with automatic activation


Automatic reactivation of the unit with adjustable

time delay

UPS operation (without heating and humidification)


Manual operation level
Recording of alarms with date and time
Alarm indications: air flow failure, filter soiling,

temperature and humidity limit alarms, heater


and humidifier fault (if present)

Minimum supply air limit via cascade

deltaclima DX TELCO LINE


The advantages at a glance
Highly efficient, all year long
Low energy consumption, as with

water cooling plus free cooler

Ideal for computer rooms with a high heat load


High redundancy by independent cooling circuits

66

CF 5272, 66 MHz

deltaclima DX TELCO LINE

Technical data
Housing
Double-wall mounting with a 40 mm
insulation (fire protection class A1
according to DIN 4102)
High housing rigidity, thanks to the welded
and painted design of the frame sections
Housing casing removable all round (thickness
of side and rear walls of 1.25 mm each)
Door wall thickness 1.5 mm
Immersion prime coating and powder coating,
RAL 9005 structure
Foamed-in PU gasket
Transportation with crane eyelets possible
Innovative design

Control
Electrical section and controller are sealed off
from the air-treatment section on the air side
This allows inspection and maintenance work
to be carried out while the unit is in operation.
Encoded plug connections for fan and sensor
Manual operating level on unit door

Filter
Cassette air circulation filter F7
Installed directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Cooling DX
Large-surface Cu/Al direct evaporator with
hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in
reduced pressure loss
Aluminium condensate pan is easy to
remove and clean
Includes self-filling, closable siphon
Cold circuit with SCROLL compressors,
incl. Rotalock valves and oil sight glass
Refrigerant dryer with screw connections, no
soldering required when replacing the dryer
Easy connection by customer
Electronic Expansion Valve
Optimum injection of the respective
coolant quantity

Exact and precise overheating


regulation saves energy
COP is increased during partial-load operation
Dehumidification switching via EEV
with constant air volume

Fan
High-performance radial fan with optimised
efficiency, no volute casing, with backward
inclined blades, single-sided suctioning
Drive motor integrated as EC external
rotor in impeller
Fan speed is configured via EC control to suit
the individual flow rate
The fan/motor unit is installed in the
base frame and can easily be extracted
from the front.
One to two fans per unit

Base frame
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)

Exhaust plenum (optional)


Can be connected to the duct system
Positioned above the double floor
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)
Filter changed from the front
Feedthroughs for media connections

VDI 6022
Housing with removable inspection
openings on both sides
Sight glasses on both sides to control
the filters and heat exchangers
Additional filter pressure display, independent
of the unit control system
Additional manual switch for unit interior
lighting and fan chamber
Hygiene certificate by an independent
test institute

67

deltaclima DX telco line


Model TELCO LINE T = 10 K

60.4 DX

85.4 DX

125.4 DX

11.9

11.9

14.9

18.9

7000001440

7000001442

7000001445

7000001446

m3/h

4,200

8,400

12,500

16,000

Pa

20

20

20

20

Size
General contract number

160.4 DX

Nominal volume flow


Air quantity
External pressing

Cooling DX R407C Condensation temperature 50 C and air intake 32 C / 35 % rel. humidity


Type

DIGITAL-SCROLL compressor

Number of compressors

Qty.

Coldness output, total

kW

14.1

28.2

42.7

54.4

Coldness output, sensitive

kW

14.1

28.2

42.7

54.4

1.00

1.00

1.00

1.00

kW

3.6

7.2

11.3

13.7

10.3

20.6

38.4

39.3

F7

F7

SHR (Sensible Heat Ratio)


Power consumption, total
Max. operating current
Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.21

0.74

1.6

1.5

1.6

4.3

4.3

8.6

Sound output level, low-pressure side

dB (A)

62

67

72

65

Sound output level, high-pressure side

dB (A)

72

78

83

75

Housing emission

dB (A)

47

55

56

50

Free-field sound pressure level (2 m distance)

dB (A)

45

51

55

48

60.4 DX

85.4 DX

125.4 DX

160.4 DX

Max. operating current


Sound data

Model TELCO LINE T = 14 K


Size

11.9

11.9

14.9

18.9

7000001441

7000001443

7000001446

7000001448

m3/h

3,000

6,000

10,000

13,000

Pa

20

20

20

20

General contract number


Nominal volume flow
Air quantity
External pressing

Cooling DX R407C Condensation temperature 50 C and air intake 36 C / 30 % rel. humidity


Type

DIGITAL-SCROLL compressor

Number of compressors

Qty.

Coldness output, total

kW

14.1

28.2

46.3

61.1

Coldness output, sensitive

kW

SHR (Sensible Heat Ratio)


Power consumption, total
Max. operating current

14.1

28.2

46.3

61.1

1.00

1.00

1.00

1.00

kW

3.6

7.2

12

15.1

10.3

20.6

38.4

39.3

F7

F7

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.1

0.32

0.88

0.9

Max. current consumption

1.6

4.3

4.3

8.6

Sound output level, low-pressure side

dB (A)

54

60

67

61

Sound output level, high-pressure side

dB (A)

64

71

78

71

Housing emission

dB (A)

40

48

51

46

Free-field sound pressure level (2 m distance)

dB (A)

37

44

50

44

Sound data

We reserve the right to make technical improvements.

68

deltaclima DX TELCO LINE


Model

60.4 DX

85.4 DX

125.4 DX

160.4 DX

1,100

1,100

1,400

1,800

Base unit
Width

mm

Depth

mm

895

895

895

895

Height (above double floor)

mm

1,950

1,950

1,950

1,950

Height (below double floor)

mm

550

600

600

600

Min. double floor height

mm

350

400

400

400

Footprint

0.98

0.98

1.25

1.61

Weight (incl. base frame)


Connection voltage

kg

455

505

585

871

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

Unit view
T
B

H2

H1

Model

W (width)

H (height)

D (depth)

H1

H2

60.4 DX 11.9

1,100

2,500

895

550

1,950

85.4 DX 11.9

1,100

2,550

895

600

1,950

125.4 DX14.9

1,400

2,550

895

600

1,950

160.4 DX 18.9

1,800

2,550

895

600

1,950

We reserve the right to make technical improvements.

69

Notes

70

deltaclima CW TELCO LINE

deltaclima CW TELCO LINE


The water-cooled system specifically for the telecommunication industry

deltaclima CW TELCO LINE was designed for IT rooms subjected to high heat loads and
can be combined with a host of different mechanical cooling systems, for example the
deltachiller free coolers. By situating the fan under the floor surface, the housing provides
an especially large amount of space for large filter and heat exchanger surfaces.

71

deltaclima CW TELCO LINE

Control with SAIA PCD


The deltaclima CW TELCO LINE compact systems are equipped with a SAIA pcs+ regulator
as standard. In addition to the usual exhaust/
intake cascade regulation, the optimised software makes a whole host of other functions
possible, for example:

Can be connected to superordinate building management


systems via RS485, BACnet or Ethernet.
Operating display

Controller

5.7 TFT display

Microprocessor, Motorola

VGA 640 x 480

65536 colours

1 MB RAM

Setting and display of the EC fan load

Front installation

Battery-backed clock

Master/slave switching (up to 8 units)

Protection type IP65

Ethernet interface

Continuous redundancy with automatic activation


Automatic reactivation of the unit with

adjustable time delay

UPS operation (without heating and humidification)


Manual operation level
Recording of the alarms with date and time
Alarm indications: air flow failure, filter soiling,
temperature and humidity limit alarms, heater and

humidifier fault (if present)

Minimum supply air limit via cascade

deltaclima CW TELCO LINE


The advantages at a glance
Minimal energy costs through

reduced fan power

Especially large filter and heat


exchanger surfaces

High cooling output with a small footprint


Easy integration into existing systems

72

CF 5272, 66 MHz

deltaclima CW TELCO LINE

Technical data
Housing

Fan

Double-wall mounting with a


40 mm insulation (fire protection
class A1 according to DIN 4102)
High housing rigidity, thanks to the welded
and painted design of the frame sections
Housing casing removable all round (thickness
of side and rear walls of 1.25 mm each)
Door wall thickness 1.5 mm
Immersion prime coating and powder coating,
RAL 9005 structure
Foamed-in PU gasket
Transportation with crane eyelets possible
Innovative design

High-performance radial fan optimised for


efficiency, no spiral housing, features
backward-curved blades, one-sided intake
Drive motor integrated as EC external
rotor in wheel
The fan speed is set according to the
individual volume flow via the EC regulator.
The fan motor unit is installed in the
base frame and can easily be pulled out
from the front.
One to three fans per unit

Controller
Electrical section and controller are sealed off
from the air-treatment section on the air side
This allows inspection and maintenance work
to be carried out while the unit is in operation.
Encoded plug connections for fan and sensor
Manual operating level on unit door

Filter
Cassette air circulation filter F7
Installed directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Cooling CW
Large-surface Cu/Al direct evaporator with
hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in
reduced pressure loss
Aluminium condensate pan is easy to
remove and clean.
Includes self-filling, closable siphon
Cooling circuit with internal piping, including
continuous 2-way valve, optional 3-way valve
Material: Brass or red brass
Easy connection by customer

Base frame
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)

Exhaust plenum (optional)


Can be connected to the duct system
Positioned above the double floor
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)
Filter changed from the front
Feedthroughs for media connections

VDI 6022
Housing with removable inspection
openings on both sides
Sight glasses on both sides to control the
filters and heat exchangers
Additional filter pressure display, independent
of the unit control system
Additional manual switch for unit interior
lighting and fan chamber
Hygiene certificate by an independent
test institute

73

deltaclima CW TELCO LINE


Model TELCO LINE T = 10 K

330.4 CW

60.4 CW

110.4 CW

220.4 CW

11.7

11.9

18.9

26.9

7000001449

7000001451

7000001453

7000001455

m3/h

4,200

7,000

14,000

25,200

Pa

20

20

20

20

kWh

2,085

3,539

7,753

18,265

Size
General contract number
Nominal volume flow
Air quantity
External pressing
Energy consumption p.a. (Frankfurt/Main)

Cooling CW Cold water 10 C / 16 C and air intake 32 C / 35 % rel. humidity


Coldness output, total

kW

14.5

24.2

47.9

87.3

Coldness output, sensitive

kW

14.5

24.2

47.9

87.3

1.00

1.00

1.00

1.00

Medium volume flow

SHR (Sensible Heat Ratio)


m3/h

2.09

3.47

6.87

12.52

Cooler pressure loss

kPa

13.7

14.9

15.5

18

Valve pressure loss


Connection

kPa

4.4

4.7

7.6

9.8

Inches

Rp 1

Rp 1 1/4

Rp 1 1/2

Rp 2

F7

F7

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.24

0.4

0.89

2.09

Max. current consumption

1.6

4.3

8.6

12.9

Sound output level, low-pressure side

dB (A)

62

59

62

68

Sound output level, high-pressure side

dB (A)

72

70

72

78

Housing emission

dB (A)

47

43

46

52

Free-field sound pressure level (2 m distance)

dB (A)

45

42

45

51

60.4 CW

110.4 CW

220.4 CW

330.4 CW

11.7

11.9

18.9

26.9

7000001450

7000001452

7000001454

7000001456

3,000

5,000

10,000

18,000

Sound data

Series TELCO LINE T = 14 K


Size
General contract number
Nominal volume flow
Air quantity
External pressing
Energy consumption p.a. (Frankfurt/Main)

m3/h
Pa

20

20

20

20

kWh

937

1,612

3,478

7,928

Cooling CW Cold water 10 C / 16 C and air intake 36 C / 30 % rel. humidity


Coldness output, total

kW

14.1

23.4

46.5

84.6

Coldness output, sensitive

kW

14.1

23.4

46.5

84.6

SHR (Sensible Heat Ratio)

1.00

1.00

1.00

1.00

Medium volume flow

m /h

2.02

3.36

6.67

12.14

Cooler pressure loss

kPa

13

14.2

14.7

17

Valve pressure loss

kPa

4.1

4.4

7.1

9.2

Inches

Rp 1

Rp 1 1/4

Rp 1 1/2

Rp 2

F7

F7

Connection
Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.11

0.18

0.4

0.91

Max. current consumption

1.6

4.3

8.6

12.9

Sound output level, low-pressure side

dB (A)

54

52

55

60

Sound output level, high-pressure side

dB (A)

65

62

65

71

Housing emission

dB (A)

40

36

40

45

Free-field sound pressure level (2 m distance)

dB (A)

37

35

38

43

Sound data

We reserve the right to make technical improvements.

74

deltaclima CW TELCO LINE


Series TELCO LINE T = 10 K

60.4 CW

110.4 CW

220.4 CW

330.4 CW
2,600

Base unit
Width

mm

1,100

1,100

1,800

Depth

mm

695

895

895

895

Height (above double floor)

mm

1,950

1,950

1,950

1,950

Height (below double floor)

mm

550

600

600

600

Min. double floor height

mm

350

400

400

400

Footprint

0.76

0.98

1.61

2.33

Weight (incl. base frame)

kg

340

385

585

843

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

Connection voltage

Unit view
T
B

H2

H1

Model

W (width)

H (height)

D (depth)

H1

H2

60.4 CW 11.6

1,100

2,500

695

550

1,950

110.4 CW 11.9

1,100

2,550

895

600

1,950

220.4 CW 18.9

1,800

2,550

895

600

1,950

330.4 CW 26.9

2,600

2,550

895

600

1,950

We reserve the right to make technical improvements.

75

Notes

76

deltaclima FC TELCO LINE

deltaclima FC TELCO LINE


The system with direct free cooling

deltaclima FC TELCO LINE is connected to the outside air through a special


housing structure so that the system can directly use the advantages of free cooling.
The automatic control system ensures that cooling is primarily effect using outside
air throughout the year.

77

deltaclima FC TELCO LINE

Accessories and equipment options


With the following equipment options, deltaclima FC TELCO LINE can be optimally
adapted to different climate control and installation situations:

FC

Digital-Scroll compressor (DX)

Steam humidifier (CW+DX)

3-way valve (CW)

Electrical re-heater (CW+DX)

Fan protection grid (CW+DX)

Smoke, fire and water detectors (CW+DX)

Filter class F7 (CW+DX)

Maximum humidity sensor (CW+DX)

deltaclima FC TELCO LINE The advantages at a glance


Specifically designed for IT rooms with direct access

to the outside air

Direct use of outside air through additional housing structure


Low installation efforts
Mechanical cooling can be integrated as needed
Double supply USP operation

Control with SAIA PCD


The deltaclima FC TELCO LINE compact
systems are equipped with a SAIA PCD control
system as a standard. In addition to the usual
exhaust/intake cascade regulation, the optimised software makes a whole host of other
functions possible, for example:

Can be connected to superordinate building management


systems via RS485, BACnet or Ethernet.
BeOperating console

Controller

5.7 TFT display

Microprocessor, Motorola

VGA 640 x 480

65536 colours

1 MB RAM

Setting and display of the EC fan load

Front installation

Battery-backed, clock

Master/slave switching (up to 8 units)

Protection class IP65

Ethernet interface

Continuous redundancy with automatic activation


Automatic reactivation of the unit with

adjustable time delay

UPS operation (without heating and humidification)


Manual operation level
Recording of alarms with date and time
Alarm indications: air flow failure, filter soiling,
temperature and humidity limit alarms, heater and

humidifier fault (if present)

Minimum supply air limit via cascade

78

CF 5272, 66 MHz

deltaclima FC TELCO LINE

Technical data
Housing

Cooling CW

Double-wall mounting with a 40 mm


insulation (fire protection class A1
according to DIN 4102)
High housing rigidity, thanks to the welded
and painted design of the frame sections
Housing casing removable all round (thickness
of side and rear walls of 1.25 mm each)
Door wall thickness 1.5 mm
Immersion prime coating and powder coating,
RAL 9005 structure
Foamed-in PU gasket
Transportation with crane eyelets possible
Innovative design

Large-surface Cu/Al direct evaporator with


hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work.
Low passage speed, which results in
reduced pressure loss
Aluminium condensate pan is easy to
remove and clean
Includes self-filling, closable siphon
Cooling circuit with internal piping, including
continuous 2-way valve, optional 3-way valve
Material: Brass or red brass
Easy connection by customer

Controller/Regulator

Electronic expansion valve

Electrical section and controller are sealed off


from the air-treatment section on the air side
This allows inspection and maintenance work
to be carried out while the unit is in operation
Mains switch accessible from the outside
Encoded plug connections for fan and sensors
Separation of power supply A and B possible

Optimum injection of the respective


coolant quantity
Exact and precise overheating
regulation saves energy
COP is increased during partial-load operation
Dehumidification switching via EEV with
constant air volume

Filter

Fan

G4 cassette air circulation filter, F7 optional


Installed directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

High-performance radial fan optimised for


efficiency, no spiral housing, features
backward-curved blades, one-sided intake
Drive motor integrated as EC external
rotor in wheel
The fan speed is set according to the
individual volume flow via the EC regulator.
The fan motor unit is installed in the
base frame and can easily be pulled out
from the front.
One to three fans per unit

Cooling DX
Large-surface Cu/Al direct evaporator with
hydrophilic coating
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in
reduced pressure loss
Aluminium condensate pan is easy to
remove and clean
Includes self-filling, closable siphon
Cold circuit with SCROLL compressors,
incl. Rotalock valves and oil sight glass
Refrigerant dryer with screw connections, no
soldering required when replacing the dryer
Easy connection by customer

Base frame
Vibration-insulated unit feet
Height can be adjusted individually
(adjustment range: 50 mm)

79

deltaclima DX FC TELCO LINE


Model TELCO LINE T = 10 K
Size

60.4 DX FC

85.4 DX FC

125.4 DX FC

160.4 DX FC

11.9

11.9

14.9

18.9

General contract number - Unit

7000001440 7000001442 7000001445 7000001446

General contract number Top part

7000001465 7000001466 7000001467 7000001468

Nominal volume flow


Air quantity

m3/h

4,200

8,400

22,500

16,000

External pressing

Pa

150

150

150

150

Max. external pressing

Pa

240

420

170

420

Cooling DX R407C Condensation temperature 50 C and air intake 32 C / 35 % rel. humidity


Type

DIGITAL-SCROLL Compressor

Number of compressors

Qty.

Coldness output, total

kW

14.1

28.2

42.7

54.4

Coldness output, sensitive

kW

14.1

28.2

42.7

54.4

SHR (Sensible Heat Ratio)

1.00

1.00

1.00

1.00

Power consumption, total

kW

3.6

7.2

11.3

13.7

Max. current consumption

10.3

20.6

38.4

39.3

F7

F7

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.4

1.18

2.14

2.38

Max. current consumption

1.6

4.3

4.3

8.6

Sound output level, low-pressure side

dB (A)

57

65

71

68

Sound output level, high-pressure side

dB (A)

68

75

82

78

Housing emission

dB (A)

43

49

56

53

Free-field sound pressure level (2 m distance)

dB (A)

40

48

54

51

60.4 DX FC

110.4 DX FC

220.4 DX FC

330.4 DX FC

11.9

11.9

14.9

18.9

Sound data

Model TELCO LINE T = 14 K


Size
General contract number - Unit

7000001441 7000001443 7000001446 7000001448

General contract number Top part

7000001465 7000001466 7000001467 7000001468

Nominal volume flow


Air quantity

m3/h

3,000

6,000

10,000

13,000

External pressing

Pa

150

150

150

150

Max. external pressing

Pa

310

540

380

500

Cooling DX R407C Condensation temperature 50 C and air intake 36 C / 30 % rel. humidity


Type

DIGITAL-SCROLL compressor

Number of compressors

Qty.

Coldness output, total

kW

14.1

28.2

46.3

61.1

Coldness output, sensitive

kW

14.1

28.2

46.3

61.1

1.00

1.00

1.00

1.00

SHR (Sensible Heat Ratio)


Power consumption, total

kW

3.6

7.2

12

15.1

Max. current consumption

10.3

20.6

38.4

39.3

F7

F7

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type
Qty.

Power consumption, total

kW

0.27

0.68

1.35

1.66

Max. current consumption

1.6

4.3

4.3

8.6

We reserve the right to make technical improvements.

80

EC motor, direct driven, free-wheeling

Number

deltaclima DX FC TELCO LINE


Sound data
Sound output level, low-pressure side

dB (A)

53

62

67

66

Sound output level, high-pressure side

dB (A)

64

71

78

75

Housing emission

dB (A)

39

47

51

51

Free-field sound pressure level (2 m distance)

dB (A)

36

45

50

49

Width

mm

1,100

1,100

1,400

1,800

Depth

mm

895

895

895

895

Height (above double floor)

mm

1,950

1,950

1,950

1,950

Height (below double floor)

mm

550

600

600

600

Min. double floor height

mm

350

400

400

400

Footprint

m2

0.98

0.98

1.25

1.61

Base unit

Weight (incl. base frame and FC top)


Connection voltage

kg

560

621

720

1,071

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

Unit view
T
B

H3

H2

H1

Size
60.4 DX FC 11.9

W (width)

H (height)

D (depth)

H1

H2

H3

1,100

2,500

895

550

1,950

800

85.4 DX FC 11.9

1,100

2.550

895

600

1,950

800

125.4 DX FC 14.9

1,400

2,550

895

600

1,950

800

160.4 DX FC 18.9

1,800

2,550

895

600

1,950

800

We reserve the right to make technical improvements.

81

deltaclima CW FC TELCO LINE


Model TELCO LINE T = 10 K
Size

60.4 CW FC

110.4 CW FC

220.4 CW FC

330.4 CW FC

11.7

11.9

18.9

26.9

General contract number - unit

7000001449 7000001451 7000001453 7000001455

General contract number - top

7000001469 7000001470 7000001471 7000001472

Nominal volume flow


Air quantity

m3/h

4,200

7,000

14,000

25,200

External pressing

Pa

150

150

150

150

Max. external pressing

Pa

230

530

510

440

Cooling CW Cold water 10 C / 16 C and air intake 32 C / 35 % rel. humidity


Coldness, total

kW

14.5

24.2

47.9

87.3

Coldness, sensitive

kW

14,5

24,2

47,9

87,3

1.00

1.00

1.00

1.00
12.52

SHR (Sensible Heat Ratio)


Medium volume flow

m/h

2.09

3.47

6.87

Pressure loss of cooler

kPa

13,7

14,9

15,5

18

Pressure loss of valve

kPa

4.4

4.7

7.6

9.8

Connection

Inch

Rp 1

Rp 1 1/4

Rp 1 1/2

Rp 2

F7

F7

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type

EC motor, direct driven, free-wheeling

Number

Qty.

Power consumption, total

kW

0.44

0.78

1.65

3.38

Max. current consumption

1.6

4.3

8.6

12.9

Sound output level, low-pressure side

dB (A)

57

61

65

69

Sound output level, high-pressure side

dB (A)

69

72

75

79

Housing emission

dB (A)

43

46

50

54

Free-field sound pressure level (2 m distance)

dB (A)

40

45

48

52

60.4 DX FC

110.4 DX FC

220.4 DX FC

330.4 DX FC

11.7

11.9

18.9

26.9

Sound data

Model TELCO LINE T = 14 K


Size
General contract number - unit

7000001450 7000001452 7000001454 7000001456

General contract number - top

7000001469 7000001470 7000001471 7000001472

Nominal volume flow


Air quantity

m3/h

3,000

5,000

10,000

18,000

External pressing

Pa

150

150

150

150

Max. external pressing

Pa

290

580

570

550

Cooling CW Cold water 10 C / 16 C and air intake 36 C / 30 % rel. humidity


Coldness, total

kW

14.1

23.4

46.5

84.6

Coldness, sensitive

kW

14,1

23,4

46,5

84,6

1.00

1.00

1.00

1.00

2.02

3.36

6.67

12.14

SHR (Sensible Heat Ratio)


Medium volume flow

m/h

Pressure loss of cooler

kPa

13

14,2

14,7

17

Pressure loss of valve

kPa

4.1

4.4

7.1

9.2

Connection

Inch

Rp 1

Rp 1 1/4

Rp 1 1/2

Rp 2

F7

F7

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

F7

F7

Fan unit
Type
Qty.

Power consumption, total

kW

0.28

0.49

1.03

1.95

Max. current consumption

1.6

4.3

8.6

12.9

We reserve the right to make technical improvements.

82

EC motor, direct driven, free-wheeling

Number

deltaclima CW FC TELCO LINE


Sound data
Sound output level, low-pressure side

dB (A)

53

61

64

66

Sound output level, high-pressure side

dB (A)

64

69

73

75

Housing emission

dB (A)

40

45

49

51

Free-field sound pressure level (2 m distance)

dB (A)

36

41

47

49

Width

mm

1,100

1,100

1,800

2,600

Depth

mm

695

895

895

895

Height (above double floor)

mm

1,950

1,950

1,950

1,950

Height (below double floor)

mm

550

600

600

600

Min. double floor height

mm

350

400

400

400

Footprint

m2

0.76

0.98

1.61

2.33

Base unit

Weight (incl. base frame and FC top)


Connection voltage

kg

460

520

790

1,138

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

Unit view
T
B

H3

H2

H1

Size

W (width)

H (height)

D (depth)

H1

H2

H3

60.4 CW FC 11.7

1.100

2.500

695

550

1.950

800

110.4 CW FC 11.9

1.100

2.550

895

600

1.950

800

220.4 CW FC 18.9

1.800

2.550

895

600

1.950

800

330.4 CW FC 26.9

2.600

2.550

895

600

1.950

800

We reserve the right to make technical improvements.

83

Condensers

84

Condensers

Condensers with AC fan technology


Condenser model

KLDR 2.2

KLDR 3.2

KLDR 4.2

KLDR 5.2

KLDR 6.2

KLDR 7.2
160.4 DX

Condensation temperature 50 C and air intake 35 C / 34 % rel. humidity


Unity types

30.4 DX

60.4 DX

85.4 DX

125.4 DX

30.4 DX

60.4 DX

85.4 DX

125.4 DX

160.4 DX

Type

Axial blower condenser

Number of fans

Qty.

Max. air quantity

m3/h

7,000

8,300

14,000

17,600

18,600

27,900

Condenser output

kW

19.1

29.5

38.2

53.6

70.1

105.2

Max. power consumption

kW

0.68

0.60

1.36

1.20

1.20

1.80

Max. current consumption

3.0

2.6

6.0

5.2

5.2

7.9

Max. free field sound press


level (5 m distance)

dB (A)

51

47

54

50

50

52

Width (A+C)

mm

1,025

1,175

1,775

2,075

2,775

4,025

Depth, vertical (B1)*

mm

750

900

1,500

1,800

2,500

3,750

Depth, horizontal (B2)*

mm

842

1,130

842

1,130

1,130

1,130

Depth, horizontal (B3)

mm

740

740

740

740

740

740

Depth, horizontal (B4)*

mm

470

470

470

470

470

470

Height, vertical (D)

mm

1,100

1,140

1,100

1,140

1,140

1,140

Height, horizontal (E)

mm

840

1,130

840

1,130

1,130

1,130

Height, horizontal (F)

mm

1,160

1,450

1,160

1,450

1,450

1,450

Weight

kg

95

140

150

210

275

395

V/Ph/Hz

230/1/50

230/1/50

230/1/50

230/1/50

230/1/50

230/1/50

Connection voltage

*Mounting holes
We reserve the right to make technical improvements.

Execution (V) vertically blowing

Execution (H) horizontally blowing

Execution (H) horizontally blowing

85

Condensers

Condensers with AC fan technology (TELCO LINE)


Extra Quiet Model
Air intake 36 C / 34 % rel. humidity
Condenser model
Unit types
General contract number

KLDR

KLDR

KLDR

KLDR

0651C1

0651C1

0651B3

0651C3

60.4 DX

85.4 DX

125.4 DX

160.4 DX

7000001444

7000000764

7000000765

7000000762

Type
Number of fans

Qty.

Max. volume flow

m/h

6,980

6,980

17,510

18,450

Condenser output

kW

26

26

64.6

76.3

Max. input power

kW

0.4

0.4

0.75

0.75

1.75

1.75

3.6

3.6

dB (A)

49

49

49

49

Width (A+C)

mm

1,475

1,475

3,545

4,155

Depth, vertical (B1)

mm

1,145

1,145

1,145

1,145

Max. current consumption


Max. free field sound pressure level
(5 m distance)

Depth, horizontal (B2)

mm

Height, vertical (D)

mm

950

950

950

950

Height, horizontal (E)

mm

Weight

kg

123

123

302

345

V/Ph/Hz

30/1/50

30/1/50

230/1/50

230/1/50

Connection voltage

We reserve the right to make technical improvements.

86

Axial blower condenser

Notes

87

Room-based solutions,
cooling capacity > 150 kW

88

deltaclima CoolWall

deltaclima CoolWall
Greater performance, lower energy consumption, greater flexibility, lower space requirement

The requirements which computer centres need to meet are continually growing.
Increasing quantities of data and ever expanding capacities mean that computer rooms
need continually expanding cooling capacities. This leads to an increase in energy costs
and, frequently, associated shortages of space. The required cooling capacity is no longer
achieved in extreme cases.

89

deltaclima CoolWall

Perfect air-conditioning for your computer centre


The deltaclima CoolWall from Weiss Klimatechnik GmbH represents an intelligent
solution for computer rooms of all sizes. The flexible, high-output and energy-saving
system is recommended for both new installations and as a retrofitting solution.
A reliable principle
The deltaclima CoolWall works in the same manner as an

deltaclima CoolWall increases flexibly relative to the grow-

air-conditioning cabinet, with fans for air conveyance and a

ing cooling demands of computer rooms. This ensures the

heat exchanger to cool the air. Whereas any air-conditioner

achievement of much enhanced scalability when compared

unit can only exploit the heat exchange surface in the

to conventional precision air-conditioners.

device itself, the deltaclima CoolWall utilises the complete


height and width of the computer room to cool the air. The
entire IT room thus becomes an air-cooling unit.

Criteria

Adequate output for every need

Cooling capacity > 300 kW

The considerably expanded cooling surface and flexible air

Low space

flow layout with fans in the double floor practically doubles

Cold chamber concept

the specific cooling capacity when compared to precision

Innovative system

air-conditioner units. Consequently, the output of the

Micro-scalability

90

deltaclima

deltaclima
CoolWall

deltaclima CoolWall

A sensible investment for your company


Save energy
Cooling of the computer room can be precisely controlled
through the design of the heat exchanger and number of
fans. The drastic reduction in internal pressure losses is
achieved as a consequence, resulting in a considerable drop
in energy consumption when compared to air-conditioning
cabinets. And the larger the cooling capacity required, the
greater the saving achieved. Investment costs are, in any
case, lower than the new installation of precision air-conditioner units.
Create the space you need
The complete dispensing with air-conditioning cabinets
means that considerably more space is available, and capacities can also be expanded without difficulty in existing
space concepts. The outlay for the installation of the deltaclima CoolWall is roughly equivalent to that of conventional air-conditioner units.
The deltaclima CoolWall principle

required air flow is established behind the cooling wall.

The deltaclima CoolWall consists of a wall with a cooling

They force and filter the hot air out of the computer room

and filter module encompassing a separate control and

through the cooling wall, conveying the cold air through the

special energy-saving EC fans. The fans ensure that the

double floor back to the racks. In the contrary layout, the


air flow selectively expels hot air through the double floor
and feeds in cold air through the cooling wall.
The generous heat exchange surfaces mean that higher
water temperatures can also be used. This enables the
extended exploitation of external air during operation with
indirect free cooling.
The deltaclima CoolWall can be integrated in the existing
cold water mains network without difficulty.

Die deltaclima CoolWall The advantages at a glance


Extremely high cooling capacity
Extremely low energy requirement
Extremely space-saving
Extremely flexible room layout
Extremely favourable scalability
Extremely investment-friendly

91

deltaclima CoolWall

Same area, twice the capacity


An exemplary calculation based on a computer room with an area of 960 m was made to
compare the performance of precision air-conditioner units with the deltaclima CoolWall.
Seven precision air-conditioner units with service access

The result

and, alternatively, a deltaclima CoolWall and 42 fans in

The larger heat exchange surface enabled the deltaclima

the double floor were installed along the front wall on an

CoolWall to achieve practically twice the specific cooling

installation surface of 20 m x 2 m in a computer room with

capacity in the same area when compared with conventional

a width of 20 m, a length of 50 m and a height of 2.6 m

precision air-conditioner units. The deltaclima CoolWall can

(above the double floor). The heat exchangers are fed with

dissipate around 1.9 kW per m area, while the precision air-

cooling water with a supply temperature of 10 C and a

conditioner units can only barely manage 1 kW. It simultane-

return temperature of 15 C. The air intake temperature

ously saves energy and considerably reduces running costs:

in the heat exchangers is 30 C. The cooling capacity was


calculated with the same temperature difference for both
examples, while it was assumed that an air-conditioner
unit is installed for plant operation (i.e. only six units were
included in the calculation).

Conventional circulating air cooling unit version

deltaclima CoolWall version


50 m

50 m

cold aisle

20 m

warm room

cold aisle

20 m

warm room

cold aisle

2m

Specific capacities dissipated: 936 kW/960 m = 1 kW/m

Temperature air intake


Cooling water temperature
Cooling capacities
Heat exchange surface
Fans
Air output at same air speed
Computer room area
Specific cooling capacity

We reserve the right to make technical improvements.

92

cold aisle

2m

Specific capacities dissipated: 1,844 kW/960 m = 1.92 kW/m

Conventional circulating air cooling unit

deltaclima CoolWall

30 C / 30 % r. h.

30 C / 30 % r. h.

10 C / 15 C

10 C / 15 C

6 x 156 kW = 936 kW

1,844 kW

6 x 3.84 m = 23 m

2.5 x 18 m = 45 m

18 x

42 x

6 x 33,000 m/h = 198,000 m/h

390,000 m/h

48 x 20 m = 960 m

48 x 20 m = 960 m

0.98 kW/m

1.92 kW/m

deltaclima CoolWall

Perfect for any room architecture


The deltaclima CoolWall not only represents a space-saving solution because an air-conditioning
cabinet is no longer required. Its installation is also completely flexible and, consequently, can
be adapted to suit any room architecture. Different layouts can, in principle, be realised in all
conceivable variants and dimensions.
The cooling surfaces of the deltaclima CoolWall consist of
modular components in two sizes (2,400 mm x 1,200 mm
and 2,400 mm x 1,800 mm). This means that the entire wall
surface of every computer room can be fitted, regardless of
the room size.

Single-sided installation

Double-sided installation

Rack

Rack

cold aisle

cold aisle

Rack

Rack

warm room

warm room

Rack

Rack

cold aisle

cold aisle

Rack

Rack

The computer room is supplied via a deltaclima CoolWall

The computer room is supplied via two deltaclima

at the end wall.

CoolWall units at both end walls.

Central installation

Corner installation

Rack

Rack

cold aisle

cold aisle

cold aisle

Rack

Rack

Rack

warm room

warm room

Rack

warm room
Rack

Rack

Rack

cold aisle

cold aisle

cold aisle

Rack

Rack

Rack

Two computer rooms are supplied simultaneously via two

A computer room can also be supplied by two deltaclima

deltaclima CoolWall units separated from each other.

CoolWall units located in the corners if the end wall on


its own is too narrow.

93

deltaclima CoolWall

Energy comparison
Initial situation:

Operating conditions:

Development of computer centre areas of

Return air: 29 C / 30 % r. h.

Water: VL 18 C (well water, system separation)

approximately 200 m each

Thermal load per module approx. 1.5 kW/m = 320 kW

External pressing: 50 Pa

Connection to the cold water supply via two supply lines

Filter class: G4

4 pipelines in double floor

Redundancy: 2N+2

2 climate racks on opposite sides

Sequence operation
Emergency operation

Version 4 x 2 conventional circulating

Version 3 x 2 deltaclima CoolWall

air cooling unit

11 m

11 m

2,5 m

2,5 m

If the system is designed for a conventional circulating air

If the CoolWall is designed for the same useful cooling

cooling unit, an expansion is no longer possible.

capacity, 23% of the energy costs as against circulating


air cooling units can be saved.

Version 4 x 2 deltaclima CoolWall

Version 5 x 2 deltaclima CoolWall

11 m

11 m

2,5 m

2,5 m

With the medium CoolWall equipment 35% of the energy

With the maximum CoolWall equipment, 54% of the energy

costs as against circulating air cooling units can be saved.

costs as against circulating air cooling units can be saved.

94

deltaclima CoolWall

Series

Conventional circulating air cooling


unit (CAC)

deltaclima
CoolWall
300.4 CW
[version 3 x 2]

deltaclima
CoolWall
300.4 CW
[version 4 x 2]

deltaclima
CoolWall
300.4 CW
[version 5 x 2]

redundancy

Qty.

[4 x 2 version]

deltaclima

6+2

8+2

units in operation

Qty.

CoolWall

10

fans per unit

Qty.

300.4 CW

cooling capacity

kW

[3 x 2 version]

deltaclima

40,9

32,5

cooling capacity, total

kW

CoolWall

328,2

327,2

325,0

airflow

m/h

300.4 CW

21.500

17.800

17.800

airflow, total

m/h

[4 x 2 version]

deltaclima

142.400

178.000

power consumption

kW

CoolWall

1,95

1,24

0,70

power consumption, total

kW

300.4 CW

11,70

9,92

7,00

net cooling capacty, total

kW

[5 x 2 version]

317

317

318

kW/m

1,59

1,59

1,59

1,59

net cooling capacity, specific


energy consumption
energy costs (0,15/kWh)

kW/year

133.152

102.492

86.899

61.320

/year

19.973,00

15.374,00

13.035,00

9.198,00

savings per room

/year

4.599,00

6.938,00

10.854,00

savings per room

%/year

23%

35%

54%

We reserve the right to make technical improvements.

Total Cost of Ownership (TCO)


350.000

300.000

Costs (EUR)

250.000

200.000

150.000

100.000

50.000

0
0

10

time (year)

conventional circulating
air cooling unit
[version 4 x 2]

WEISS deltaclima
CoolWall 300.4 CW
[version 3 x 2]

WEISS deltaclima
CoolWall 300.4 CW
[version 4 x 2]

WEISS deltaclima
CoolWall 300.4 CW
[version 5 x 2]

95

deltaclima CoolWall

Flexibility over the entire surface


When it comes to cooling servers, the deltaclima CoolWall is available in
two versions: the warm room and cold room concept.

The warm room concept involves the introduction of cooled

Air conveyance is reversed in the cold room concept. The air

air into the double floor and its conveyance via the perforat-

is fed into the room through the cooling wall and suctioned

ed double floor plates to the rack suction points. The cooling

into the server. It absorbs the heat present here and returns

air flows through the server cabinet at a temperature of e.g.

to the circuit via the double floor. At this, the complete room

between 20 and 26 C, absorbs the heat present and returns

appears as a compensation room and the IT staff is work-

to the circuit via the cooling wall.

ing in cooled environment.

96

deltaclima CoolWall

Technical data
Housing

Fan

Greater housing rigidity, thanks to the welded


and painted design of the frame profiles
Housing casing removable all round (side and
rear panel thickness 1.25 mm in each case)
Side visible in computer centre is perforated
Electrophoretic dip priming and powder
coating, RAL 9005
Can be transported with the crane eyelets
Innovative design
Simple on-site dry construction wall
installation
Controller/regulator
Can be connected to superordinate building
management systems via BACnet,
SNMP or Ethernet.

The fan motor unit is simply suspended


in the double floor grid
High-performance radial fan with optimised
efficiency, no volute casing, with backward
inclined blades, single-sided suctioning
Drive motor integrated as EC external
rotor in impeller
Fan speed is configured via EC control to suit
the individual flow
Replacement possible from above
All electrical connections with plug connector

Accessories and equipment options


Side wall panelling
3-way valve
Cold aisle control

Filter
G4 cassette air circulation filter
Installed directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential
pressure sensor

Cooling
Room height cooling segments with
large-surfaced Cu/AI heat exchanger
Slat spacing is greater than 2 mm, allowing
easy access for cleaning work
Low passage speed, which results in
reduced pressure loss
Condensate pan is easy to clean
Cold circuit with internal piping, including
continuous 2-way valve, optional 3-way valve
Material: Brass and/or red brass
Easy connection by customer

97

deltaclima CoolWall

Series

180.4 CW

300.4 CW

12.3

18.3

m/h

18.000

30.000

Pa

20

20
121,1

Size
Nominal volume flow
Air quantity
External pressing

Cooling CW Cold water 10 C / 15 C and air intake 26 C / 45 % rel. humidity


Cooling output, total

kW

73

Cooling output, sensitive

kW

68

113

0.93

0.93

SHR (Sensible Heat Ratio)


Medium volume flow

m/h

12.55

20.84

Cooler pressure loss

kPa

29.9

28.2

Valve pressure loss

kPa

9.8

27.1

Connection

Inch

Rp 2

Rp 2 1/2

Cooling CW Cold water 12 C / 18 C and air intake 28 C / 40 % rel. humidity


Cooling output, total

kW

69.9

116.1

Cooling output, sensitive

kW

69.9

116.1

1.00

1.00

m/h

10.04

16.67

SHR (Sensible Heat Ratio)


Medium volume flow
Cooler pressure loss

kPa

19.8

18.7

Valve pressure loss

kPa

6.3

17.4

Connection

Inch

Rp 2

Rp 2 1/2

Cooling CW Cold water 10 C / 15 C and air intake 30 C / 30 % rel. humidity


Cooling output, total

kW

93.8

155.8

Cooling output, sensitive

kW

93.8

155.8

1.00

1.00

Medium volume flow

m/h

16.13

26.79

Cooler pressure loss

kPa

46.5

43.9

Valve pressure loss

kPa

16.3

44.9

Connection

Inch

Rp 2

Rp 2 1/2

SHR (Sensible Heat Ratio)

Filter at intake
Type

Cassette filter

Filter class as per DIN EN 779

G4

G4

Fan unit impeller 630 mm


Type

EC motor, directly driven, free wheeling

Number*

Qty.

Power consumption, total

kW

1.6

2.92
12.9

Max. current consumption

8.6

Weight per fan unit

kg

59

59

Min. double floor height

mm

550

550

Sound data
Sound output level, low-pressure side

dB (A)

73

77

Sound output level, high-pressure side

dB (A)

78

82

**Number of fans can be selected.


We reserve the right to make technical improvements.

98

deltaclima CoolWall

Model

180.4 CW

300.4 CW

Fan unit Impeller 450 mm


Type

EC motor, directly driven, free wheeling

Number*

Qty.

Power consumption, total

kW

1.8

3
12.5

Max. current consumption

7.5

Weight per fan unit

kg

39

39

Min. double floor height

mm

500

500

Sound data
Sound output level, low-pressure side

dB (A)

80

82

Sound output level, high-pressure side

dB (A)

86

88

Width

mm

1,200

1,800

Depth

mm

350

350

Height (above double floor)

mm

2,400

2,400

Footprint

0.42

0.63

Weight

kg

200

300

V/Ph/Hz

400/3/50

400/3/50

Base unit

Connection voltage

**Number of fans can be selected.

Unit view

T
B

Series

W (width)

H (height)

D (depth)

180.4 CW

1.200

2.400

350

300.4 CW

1.800

2.400

350

We reserve the right to make technical improvements.

99

Cooling capacity > 300 kW

100

deltachiller Turbo

deltachiller Turbo
The efficient cooling technology for servers and IT

With the deltachiller Turbo Weiss provides an innovative cooling system which
universally fulfils the customers diverse requirements. The Turbo is impressive,
in particular, on account of its high reliability, individual scalability and welcome
cost effectiveness. Its intelligent design enables it, in particular, to cool the IT
and server technology.

101

deltachiller Turbo

Perfect cooling with innovative technology


The deltachiller Turbo offers the right output level for every field of application. The modular
structure of the compressor ensures a high scalability. It can optionally be executed with air or
water cooling and, as a result, it can be installed indoors or outdoors. The stepless control of
the refrigeration technology dynamically adjusts to the respective current output requirements
during on-going operation. Moreover, the deltachiller Turbo can excellently be integrated into
existing systems.
Innovations for practical use

mediate readiness for operation. All of these components

The deltachiller Turbo is impressive because of is higher

make the deltachiller Turbo a profitable investment in

level of innovation. Each individual system is planned,

every respect: as regards cost effectiveness, efficiency and

coordinated and designed by Weiss in accordance with the

operational safety as well as in terms of energy savings and

customers specifications. As a result, every deltachiller

environmental friendliness.

Turbo is exactly dimensioned and controlled with regard to


the specific requirements.

Comprehensive success in terms of quality

The development is based on an understanding of the op-

The Weiss deltachiller Turbo stands for performance,

erational procedures, production processes and, ultimately,

economy and safety. The innovative technology Made in

the cooling requirement in the respective applications.

Germany results from profound engineering skills, a high


level of vertical integration and far-reaching guarantees

The deltachiller Turbo is convincing on account of short

combined with outstanding service. It is designed specifi-

delivery times, simple installation or replacement and im-

cally for use in IT/server environments.

Economical and safe operation


The sophisticated technology of the deltachiller Turbo ensures the economical and safe
operation of the system. It protects the environment and helps to ensure compliance with
statutory energy saving provisions.
Electromagnetically shielded from the IT

Stepless power control

The Weiss Turbo technology is designed for use in IT and

The deltachiller Turbo is impressive on account of its ideal

server environments. The electromagnetic energy gener-

power control. It autonomously adjusts its output to the

ated during refrigeration is filtered efficiently. As a result,

respectively current cooling requirement via an industry-ad-

the machine complies with the high EMC standards and, as a

justed PLC control system with freely programmable regula-

result, it can be installed in all critical and sensitive areas.

tion. In this context, the stepless speed control constantly


maintains a cos phi of 0.98 even in partial load operation.

Stability through minimum starting current

To this end, the intelligent control system can switch off

The deltachiller Turbo works with a low starting current

individual compressor in line with the requirements.

of less than 5 A, this keeps the electrical supply network


stable. As a result, high inrush currents and voltage spikes

At the same time, the control system reduces the starts

are additionally prevented in emergency operation.

of the compressor motors, which tangibly increases their


service life. As a result, reactive current compensation is
not required for refrigerating machines.

102

deltachiller Turbo

Superior in every respect


Operating noises are undesirable, in particular, if the system is installed indoors. For this
reason, the deltachiller Turbo is equipped
with a magnetically suspended and touch-free
compressor technology. This way, noteworthy
mechanical vibrations are not created. As a
result, the sound level is extremely low and
additional constructional measures for sound
protection can usually be dispensed with in
their entirety.
Project-specific plant manager
The integrated control system having the form of an
industry-adjusted control unit ensuring the efficient operation of the refrigerating unit forms the core of the deltachiller Turbo.
deltachiller Turbo (water-cooled unit)
A superior control unit in a separate control cabinet is
required for interconnected operation on the part of the
refrigerating machine. The cold manager has the task of
controlling the optimum operating point for group-focused
and partial load-optimised refrigerating machine operation
for the best possible energy efficiency. To this end, it calcu-

As an option, controlling of the overall system can be taken

lates the optimum values on the basis of the internal control

over. In this case, system segments, such as re-cooling,

algorithms and adjusts the operating conditions to these.

pumps for the cold- and cooling-water-side media circulation or the free cooling function can be integrated into
performance optimisation and the overall system works
even more energy efficiently with a project-specific plant
manager.
Oil free is carefree
A special feature of the deltachiller Turbo is its oil-free operation. This form of operation entails several advantages.
Of course, it reduces the maintenance effort required, which
saves times and money. This is due to the simple fact that
oil does not have to be provided and, as a result, disposed
of. Moreover, compared with refrigerating systems using oil,
such as e.g. screw compressor units, the annual efficiency
is better without an oil pump. And, finally, the strict rules of
the German Water Resources Act do not apply if the system
is oil-free.

Detailed view of the deltachiller Turbo compressor


(air-cooled unit)

103

deltachiller Turbo

Modular maintenance during operation

Protection against power outages

A modular structure was consciously selected for the del-

On request, Weiss can equip the deltachiller Turbo for

tachiller Turbo: This saves time and money. The modular

operation using an uninterruptible power supply to be

design on the basis of marketable components ensures

provided by the customer. This ensures the refrigeration

direct availability, short delivery times and a trouble-free

supply even in the event of a potential power outage. The

installation. Moreover, there is no need to build an exces-

Turbo automatically switches to emergency operation and

sive stock of spare parts.

maintains all functions. The refrigeration supply remains


stable and in line with the individual design of the plant or

Furthermore, this design permits the compressors to be

with the capacity of the upstream UPS system at all times.

replaced while the system is in operation without interfering in the refrigeration cycle. This ensures the refrigeration

Refrigerant monitoring

supply at all times. The operating and/or industrial process-

Pursuant to EN 842, leakage and leak tests are required

es are not affected in any way.

by law up to four times per year depending on the filling


quantity of the refrigerant. Weiss uses leakage detection

Ready for even the highest temperatures

systems in the deltachiller Turbo. They are used to detect

The intelligently designed heat exchanges and the oil-

leakages early on and reduce the costs for the required

free turbo compressor work absolutely reliably even at

tests.

maximum operating temperatures. The intrinsically safe


design ensures safe operation since the maximum operat-

Leakage detection systems are prescribed for all refriger-

ing pressures of the heat exchangers cannot be exceeded.

ants with filling levels >25 kg, OPD>0 and GWP>0, on

As a result, the deltachiller Turbo is significantly more

principle. Even though these systems are not required for

leak-proof. It fulfils all valid EU guidelines and is ready for

smaller filling quantities, they significantly extend the

operation without safety valves.

prescribed testing intervals.

Overview of a heat pump

The deltachiller Turbo as a heat pump


As a special feature of the deltachiller Turbo, it can be
operated as a heat pump: In this form of operation, it
produces heat instead of refrigerating.

Compressor

The system optionally withdraws energy from the soil,

directly via a closed heating circuit.


Therefore, as a heat pump, the deltachiller Turbo
provides an interesting alternative to the usual heating
systems, e.g. in order to heat buildings, industrial facilities or swimming pools.

104

expansion element
(throttle)

energy drain

thermal energy created in the process can be recovered

condenser

condenser. In addition to the so-called dissipation circuit,

evaporator

into useful thermal energy through the optional double

Energy source

the ground water or the outside air and, e.g., converts it

deltachiller Turbo

Technical data
Model

WT_.3

Cooling capacity with 20 % Antifrogen N


Cooling capacity

kW

250

400

16/10 C

20/14 C

16/10 C

20/14 C

16/10 C

20/14 C

250

280

400

460

550

620

493

552

684

755
130

Heat exchanger
Condenser output

550

40/45 C
kW

310

339

Volume flow

m/h

56

63

91

103

127

Pressure drop

kPa

48

56

30

36

53

55

Connection

DN

80

80

125

125

125

125

16 C

20 C

16 C

20 C

16 C

20 C

Free cooling capacity upon ingress of water


Outside temperature 10 C

kW

270

340

Outside temperature 5 C

kW

325

Number of compressors

Qty.

Refrigerating circuit

Qty.

420

540
650

Refrigerating circuit
Type

TURBO compressor

Refrigerant
Connection voltage
Compressor power consumption, total
Operating current, max.

R134a
V/Ph/Hz

400/3/50

kW

60

59

93

92

134

135

95

94

150

149

212

213

4.8

4.8

4.3

5.0

4.1

4.6

COP
Cold water circuit
Water quantity

m/h

36

40

57

66

79

89

Pressure loss

kPa

43

49

26

31

40

45

Connection

DN

80

80

125

125

125

125

Qty.

12

12

16

16

kW

1.9

1.9

1.8

1.8

1.9

1.9

2.9

2.9

2.8

2.8

2.9

2.9

Sound power level +/- 3 dB

dB (A)

86

86

89

89

89

89

Free field sound power level (1 m distance)

dB (A)

68

68

71

71

71

71

dB (A)

89

89

91

91

92

92

dB (A)

61

61

63

63

64

64

Heat exchanger blowers


Type
Number
Connection voltage
Power consumption per blower
Operating current, max., per blower

Axial blowers
V/Ph/Hz

400/3/50

Sound data refrigerating machine

Sound data heat exchanger


Sound power level
Free field sound power level (10 m distance)
Base unit refrigeration
Length

mm

2,600

2,600

3,700

3,700

3,700

3,700

Depth

mm

990

990

1,130

1,130

1,130

1,130

Height

mm

1,950

1,950

2,000

2,000

2,000

2,000

Weight

kg

2,050

2,050

3,015

3,015

3,015

3,015

Heat exchanger
Length

mm

5,565

5,565

7,935

7,935

2 x 5,565

2 x 5,565

Depth

mm

2,300

2,300

2,300

2,300

2 x 2,300

2 x 2,300

Height

mm

2,850

2,850

2,850

2,850

2 x 2,850

2 x 2,850

Weight

kg

2,600

2,600

3,540

3,540

2 x 2,600

2 x 2,600

We reserve the right to make technical improvements.

105

deltachiller Turbo

Model

WT_.3

Cooling capacity with 20 % Antifrogen N


Cooling capacity

kW

850

900

16/10 C

20/14 C

16/10 C

20/14 C

16/10 C

20/14 C

850

960

900

1.030

1.100

1.250

Heat exchanger capacity


Condenser capacity

1.100

40/45 C
kW

1.058

1.168

1.105

1.234

1.359

1.509
280

Volume flow

m/h

197

217

205

229

252

Pressure drop

kPa

49

59

34

41

49

59

Connection

DN

150

150

200

200

200

200

16 C

20 C

16 C

20 C

16 C

Free cooling capacity upon ingress of water

810

810

20 C

Outside temperature 10 C

kW

Outside temperature 5 C

kW

975

Number of compressors

Qty.

Refrigerating circuit

Qty.

975

1.370
1.260

Refrigerating circuit
Type

TURBO compressor

Refrigerant
Connection voltage
Compressor power consumption, total
Operating current, max.

R134a
V/Ph/Hz

400/3/50

kW

208

208

205

204

259

259

329

329

329

327

410

410

4.1

4.6

4.4

5.1

4.2

4.8
179.3

COP
Cold water circuit
Water quantity

m/h

121.7

137.7

128.9

147.8

157.5

Pressure loss

kPa

34

40

29

34

38

44

Connection

DN

125

125

150

150

150

150

Qty.

24

24

24

24

48

48

kW

1.9

1.9

1.9

1.9

1.8

1.8

2.9

2.9

2.9

2.9

2.8

2.8

Sound power level +/- 3 dB

dB (A)

90

90

91

91

91

91

Free field sound power level (1 m distance)

dB (A)

71

71

72

72

72

72

Sound power level

dB (A)

94

94

94

94

96

96

Free field sound power level (10 m distance)

dB (A)

66

66

66

66

68

68

Heat exchanger blower


Type
Number
Connection voltage
Power consumption per blower
Operating current, max., per blower

Axial blowers
V/Ph/Hz

400/3/50

Sound data refrigerating machine

Sound data heat exchanger

Base unit refrigeration


Length

mm

4,270

4,270

4,270

4,270

4,270

4,270

Depth

mm

1,461

1,461

2,210

2,210

2,210

2,210

Height

mm

2,400

2,400

2,050

2,050

2,050

2,050

Weight

kg

4,695

4,695

5,865

5,865

5,865

5,865

mm

3 x 5,565

3 x 5,565

3 x 5,565

3 x 5,565

4 x 7,935

4 x 7,935

Heat exchanger
Length
Depth

mm

3 x 2,300

3 x 2,300

3 x 2,300

3 x 2,300

4 x 2,300

4 x 2,300

Height

mm

3 x 2,850

3 x 2,850

3 x 2,850

3 x 2,850

4 x 2,850

4 x 2,850

Weight

kg

3 x 2,600

3 x 2,600

3 x 2,600

3 x 2,600

4 x 3,540

4 x 3,540

We reserve the right to make technical improvements.

106

Notes

107

Test room at
the Reiskirchen site

108

Prfraum am Standort Reiskirchen

We leave nothing to chance


the Weiss Development Centre
If you start implementation right away in complex technical tasks, you are often held up by
rework at your own expense. That is why it is better to test and check first and then to start
off. At the Weiss Development Centre, state-of-the art technologies and comprehensive
engineering expertise is available for you to this end.
As a result, we can develop individual solutions based on

measuring and test equipment give you added security

international standards for each and every individual case.

for the trouble-free execution of your projects on time.

The far-reaching Weiss competence in the development of

In this process, you have access to the pool of solutions

own products and plants, the comprehensive potential of

which Weiss has successfully developed and implemented

experience gathered in all fields of application of process

worldwide. And there is certainly a host of these solutions

air-conditioning technology and generously equipped

available for you.

At a glance What the development service can do for you:


Clear definition of tasks and aims
Joint establishment of admissible tolerances
Planning all required steps and measures
Coordination of all development phases
Quality-related advice as regards questions of tolerance and function
Process capability analyses and optimisations, e.g.:

Sound emissions

Simulation of ambient conditions (temperature, humidity, UV ...)

EMC testing

Output measurements, e.g. of refrigerating, heating and humidification capacity

Energy consumption

Flow simulations

Statistical and computer-assisted recording and analysis of measured values


Project-accompanying qualification tests to support process reliability
Practical simulation of diverse conditions
Provision of all the required test equipment
Provision of conference rooms, presentation media and means of communication

109

The Weiss Service Concept

110

The Weiss Service Concept

On a partnership basis, effective and global:


Service which pays off
True service means knowing your customers requirements and being committed to actively
finding sustainable solutions to your customers benefit. And Weiss fulfils this requirement
of a true partnership with its holistic service concepts which focuses on the operational
reliability and cost effectiveness of the systems. As our customer, you will benefit from the
comprehensive after-sales service as well as the customer-specific qualification and training
offer, in addition to planning and implementation. To this end, our personal contacts and service
teams who are familiar with your specific requirements in detail and are committed to finding
individual and effective solutions are available for your worldwide.
Weiss Klimatechnik GmbH offers service concepts for the

and processes as well as their monitoring and maintenance.

following fields of competence: refrigeration, air-conditioning

Our strengths focus on individual industry-specific solutions

systems, ventilation and hygiene engineering. They comprise

for the fields of information and telecommunications tech-

planning, the implementation and modernisation of plants

nology, Mediclean and clean room technology.

111

The Weiss Service Concept

Available worldwide from a single source

In this context, the essential service aspects are quality,

As a group of companies operating worldwide Weiss has

quality assurance and personal support. These are our main

a global service network with highly-qualified members

objectives with the help of which we ensure the functional-

of staff. In addition to the comprehensive presence in

ity and efficiency as well as your systems cost and energy

Germany, Weiss also has service centres in Europe, Asia

efficiency in the long run.

and the USA. In this way, we ensure personal contact and


an in-depth dialogue with our customers and can tailor all

Our services at a glance

measures to be taken specifically to the underlying system


requirements. As a result, our customers get all services
from a single source and in the quality they are used to
from Weiss.
Individual
customer
advice

With individual service for an optimum result


Weiss uses high-quality technologies to ensure the lasting

Assembly/
start-up

optimum performance of your system and, in this process,


it makes sure that they are used in a manner tailored
specifically to the customers requirements. After all, the

Maintenance/
inspection/
service

Training courses/
workshops

individual dimensioning, proper handling and reliable operation of plants and processes create the preconditions for
the full utilisation of the performance potential and energy
efficiency of our technology. And this is exactly what the

Hygiene
testing as per
VDI 6022/DIN
1964 Part 4

Provision of
spare parts

services by Weiss aim to do.


Clean room
certification/requalification

Unit and plant


monitoring
EnEv German
Energy Saving
Ordinance

112

Energy use
optimisation

The Weiss Service Concept

We increase efficiency and you can


save energy and costs
Plant optimisation is used to improve and ensure the performance, energy efficiency and
operational reliability in the long run. To this end, Weiss optimises its own systems which
have been used for some time as well as other manufacturers products. As a result, we offer
our customers individual service concepts which are specifically tailored to their individual
circumstances and requirements. Continuous quality assurance forms part of these service
concepts. It comprises the continuous monitoring, maintenance in keeping with applicable
intervals and modernisation in line with the requirements.
Any plant optimisation is based on detailed stock taking.

Usually, we identify tremendous savings potential which

In this process, we check the air conditioning and process

can, in part, be achieved with relatively small interventions.

technology in terms of their balance of activities, operational

The drive technology as well as the control technology as

reliability and energy efficiency. On this basis, we provide

regards power, refrigerating machines and volume flow form

concrete optimisation recommendations, retrofit decisive

major starting points for plant optimisation.

components and assume the task of fine tuning the interactions between these.

113

The Weiss Service Concept

We are motivated by cost effectiveness


The drive accounts for the biggest share in the total energy demand.
As a result, it also provides the biggest saving potential. Retrofitting,
for example with the help of frequency converters is comparatively
easy, while the effect of such modernisations is tremendous: Directly
driven EC motors or directly driven motors with frequency converters
are much more effective than the V-belt drives which have been used
for a long time. Efficiency can be improved from approximately 35% to
up to 60%.
Intelligent power and cost control
The intelligent control technology by Weiss can dynamically control
the volume flow. It adjusts the air quantity and the cooling output to
changing room conditions in line with the respective demand. To this
end, our service teams rely on presence sensors as well as air quality
and room temperature sensors. Switching from outside air to circulating air operation compensates even extreme weather conditions.
Moreover, just one filter stage is sufficient because the volume flow is
continuously adjusted to the filter soiling level. This contributes to a
reduction in on-going costs and maintenance expenses.
Naturally on the safe side
With the individual service provided by Weiss, environmental protection and cost effectiveness go hand in hand. As a result, ecologically
sensible investments also pay off in terms of cost effectiveness at all
times.
Energy inspections are prescribed at certain intervals any way and
Weiss is authorised to carry out such inspections pursuant to the German Energy Saving Ordinance. In this capacity, we recommend sensible
measures for improving energy efficiency properties and also issue the
energy performance certificates. As a result, you automatically fulfil
the statutory requirements as per EnEV (Energy Saving Ordinance)
and the Renewable Energy Heat Act. At the same time, you will reduce
your energy demand in the short run and will, in particular, generate
significant savings in operating costs in the long run in view of increasing energy prices.
Furthermore, we are pleased to advise you on possible subsidies from
public funds and, specifically, as regards investment grants by the
Federal Office of Economics and Export Control (BAFA). This generates
concrete savings, the required operational reliability and legal security
as well as an image improvement, which is difficult to quantify. As a
result, plant optimisation by Weiss gives you comprehensive competitive advantages.

114

The Weiss Service Concept

You can rely on us


The services provided by Weiss comprise consultancy, advice and production as well as
installation, support and training. As a result, our customers receive all services as regards
refrigerating, air conditioning, ventilation and control engineering from one source worldwide
reliably, quickly as well as flexibly..
Assembly and commissioning

Technical Inspection Board (TV) according to DIN ISO

Proper assembly and commissioning comprises units and

9001, Weiss has the required certificate verifying its status

systems from the Dataclima, Teleclima and Uniclima seg-

as a specialist company. We coordinate the desired scope

ments as well as sophisticated particle measurements in

of maintenance with our customers on an individual basis

the Mediclean segment. Moreover, Weiss also provides clas-

according to VDMA 24186.

sification measurements in the clean room segment.


Control system conversion
Maintenance and service

Analogous control systems have become somewhat obso-

The regular maintenance of plants ensures their reliable

lete which is also why spare parts are no longer available.

and cost-effective operation and extends their service life.

As it is, switching to a digital control system is a better

Work on the pipeline system and on the refrigerating units

alternative. To this end, we offer you our PC-assisted con-

of air-conditioning systems has to be carried out by special-

trol technology. The system ensures the availability of the

ist companies in accordance with Art. 19-i of the German

ventilation and air-conditioning technology systems and

Water Resources Act. As a company certified by the German

saves energy in the long run.

115

The Weiss Service Concept

Data transmission/control centre technology


Weiss data transmission systems guarantee the reliable detection of malfunctions of your systems and the
transmission of the information to our control station. Our
service technicians are excellently prepared when they are
deployed on a repair assignment. This reduces expensive
unnecessary trips to the site to an absolute minimum. We
would be pleased to present our data transmission systems
to you in a personal meeting at your premises.

Spare parts management


Moreover, Weiss also supports its customers as regards
spare parts management. By keeping a comprehensive
stock we ensure the prompt availability of all wear and
spare parts. Moreover, building your own, manageable stock
on site can be sensible. Weiss provides competent advice
as to the cases in which this is recommendable. In order to
ensure the highest possible cost effectiveness and planning security we consider the respective individual space
requirements, in addition to the technical aspects.
Clean room technology
Weiss offers the mandatory verification of flawless operation required by law as a rule, specifically, for state-of-theart production under clean room conditions, whether in
pharmaceuticals production, biotechnology or chip production. In this process, our clean room technology experts will
carry out all the required tasks ranging from the analysis
of critical points to monitoring.

116

The Weiss Service Concept

Hygiene
The VID guideline 6022 governing hygiene requirements
for ventilation and air-conditioning systems applies to
all air-conditioned commercial rooms in which people are
present. This also includes the mandatory regular hygiene
examinations as per Art. 3 of the German Workplaces Ordinance. Weiss carries out these inspections in a quick, simple
and legally secure manner in accordance with the latest
standards and issues the corresponding certificates.

Customer training courses and workshops


Upon request, your operating staff can be trained by competent experts in all fields of refrigerating and air-conditioning technology. Furthermore, we offer training courses
regarding control technology and engineering as well as
hygiene training courses as per VDI 6022 (type A+B).
These training courses can be carried out at our corporate
training centre or on site at your facility. In addition to
the transfer of theoretical knowledge, the content of the
workshops is extended with the help of case studies and
practical approaches to solving problems.
The content and the duration of the training courses are
tailored to your wishes and requirements. We, of course,
advice you on all questions and would be pleased to submit
a corresponding offer to you.

Weiss Service-Hotline
Check our offer on a non-obligation basis.
We are pleased to advise you.
Just contact our service hotline at:
+49 64 08 / 84 74

117

Deltafinance
financing concept

118

Deltafinance financing concept

Offer one:

To make sure your


plans for the future
do not become a thing
of the past today

Financing at particularly
favourable terms

In difficult economic times, companies


investment and financing scopes become
increasingly tight. Increasing borrowing
costs, restricted credit lines there are many
reasons why planned investments are postponed (albeit not cancelled) to such a degree
that this can result in tangible competitive
disadvantages.

In cooperation with our financing partner,


we can support you in implementing your
air conditioning technology with particularly favourable financing
The advantages are obvious:
The monthly expenses are significantly lower than

under the current interest rate level on the market.

A start-up investment by your company is


In order to enable you to carry out technologically as

not required.

well as strategically required measures promptly we offer you alternative tailor-made, reliable and effective -

As a result, you can implement planned modernisations

financing solutions for the WKT air conditioning systems

or new equipment projects in the field of IT air condi-

for IT and telecommunication systems in cooperation

tioning without delay.

with a renowned financing partner.


This gives you access to state-of-the-art air conditioning technology and reliable financing expertise from one
source. You can further expand the efficiency of IT and
telecommunications at your company and, as a result,
you are certainly perfectly prepared for the future.

119

Deltafinance financing concept

Offer two:

Financing through cost


reductions resulting
from energy savings

You can expect


impressive advantages:
WKT air conditioning
systems WKT financing

With WKT Klimatechnik energy consumption


and, as a result, costs required for air conditioning of computer centres and telecommunications facilities can be lowered dramatically. Under this model, financing is effected
as refunding through the energy savings
generated.

We offer you concepts tailored to your


needs to enable you to benefit from
progressive IT air-conditioning technology
to the highest degree possible today for
future-oriented financing with maximum
investment security.
No start-up investment and equity burden

The advantages of this calculation model:

No impact on the balance sheet and positive

Implement your project now and finance it

later simply finance retroactively through

No deterioration in liquidity parameters and

savings in on-going costs.

effect on ratings
debt equity ratio

In this case, a start-up investment is not

Secure calculation basis without the risk of a

required either. There is no burden on your

equity right from the start.

Individual contract design also as per international

change in interest rates

accounting
This forms an extraordinarily convenient possibility
of creating an ideal climate for competitive IT and

With us you can secure your own position on the

telecommunications facilities.

market and make sure you do not forego any


competitive advantages. We are, of course, pleased
to advise you in a personal meeting..

120

Notes

121

deltaclima
Easy Configurator

122

deltaclima Easy Configurator

deltaclima Easy Configurator

DX unit
DX direct selection

CW unit
CW direct selection

new unit

shopping basket

CW technical data

DX technical data

contact

Please contact us directly.


This program enables you to simply and conveniently select and put together your precision air-conditioning unit. There are two ways
of doing this:
Direct selection:

The selected units are displayed in the shopping basket

Top left in the blue segment

and sent to the competent contact with your inquiry.

you can see the direct selection.

You will receive a prompt confirmation.

Click on the CW units (CW = water-cooled system)

or DX units (DX = air-cooled system)

deltaclima Easy Configurator


is a program by Weiss Klimatechnik which gives you all

New unit:

the necessary technical details and a total price for you

You can select the cooling output and refrigerant here.

planned system. The deltaclima Easy Configurator enables

The programme recommends one or several units.

you to save time and effort and as a result - money.

In both cases, you can select between the


pre-fixed and customised versions.
pre-fixed means that the units are fully configured

within tried and tested equipment: Fixed price.

Fixed equipment.

customized means that you as the customer can


select your personal equipment and options on the

basis of a defined unit.

Passion for Climate


Greizer Strae 41 49
35447 Reiskirchen-Lindenstruth
Germany
Phone: +49 6408 84-6500
Telefax: +49 6408 84-8720
ict@wkt.com
www.wkt.com

WKT-D 0/17 0,5M 04/13 N Glo Bec

Weiss Klimatechnik GmbH