Agenda
Fundamentals and the Operation of the Pumped
Documentation
System Overview
Liebert MC
Intelligent, high
efficiency condensers
System Components
Digital scroll compressors match cooling to IT load
Staged evaporator coil reduces compressor power and
Fixed
Fixed
Digital
Digital
Efficiency
(COP)
Sound Power
(dBA)
Refrigerant Charge
(lb)
Footprint
(ft2)
Weight
(lb)
Fin/Tube
Liebert MC
+/-
31
47
+ 52%
77.3
73
- 4.3 dBA
22
- 73%
39.8
33.6
- 15%
670
400
- 40%
Liebert DSE
Indoor Unit
Liebert MC
Condensers
DX Operation Mode
Cooling
Mode
Outdoor
Temp
Cooling
PUE
Full
Compressor
95
1.28
Condenser: 3.9 kW
Pump 1: 0 kW
Pump 2: 0 kW
Refrigerant
Pump
Electronic
expansion valve
Evaporator
Condenser
Compressor
Evaporator: 3.2 kW
Compressor 1: 8.5 kW
Compressor 2: 8.5 kW
7
Cooling
Mode
Full
Compressor
Partial
EconoPhase
Outdoor
Temp
Cooling
PUE
95
1.28
65
1.17
Condenser: 3.9 kW
Pump 1: 0.6 kW
Pump 2: 0 kW
Refrigerant
Pump
Electronic
expansion valve
Evaporator
Condenser
Compressor
Evaporator: 3.2 kW
Compressor 1: 0 kW
Compressor 2: 8.5 kW
8
Cooling
Mode
Full
Compressor
Partial
EconoPhase
Full
EconoPhase
Outdoor
Temp
Cooling
PUE
95
1.28
65
1.17
45
1.09
Condenser: 3.9 kW
Pump 1: 0.6 kW
Pump 2: 0.6 kW
Refrigerant
Pump
Electronic
expansion valve
Evaporator
Condenser
Compressor
Evaporator: 3.2 kW
Compressor 1: 0 kW
Compressor 2: 0 kW
9
Annual free-cooling hours increase at higher return air conditions and lower unit loads:
Percentage of Annual Hours with 100% Free-Cooling Available
Location
San Francisco, CA
42%
70%
Chicago, IL
55%
62%
Charlotte, NC
36%
45%
10
11
EconoPhase
Unit Status
Refrigerant
Temperature
Pump
Head
Liebert MC Condenser
Condenser
Fan Speed
Liebert MC
Unit Status
Ambient
Temperature
Head
Pressure
Room
Humidity
Room
Temperature
Evaporator
Fan Speed
Liebert
iCOM
12
13
14
DA080 (1)
88
84
3.2
10.5
85
77
3.0
9.1
Model
DA085 (1)
DA125
100
146
94
146
3.1
3.8
10.1
17.5
92
83
2.7
8.7
130
130
3.4
12.2
DA150
170
170
3.2
13.0
DA165
181
181
3.1
12.8
153
153
2.9
12.0
163
163
2.8
11.7
Length (A)
100"
100"
144"
144"
144"
Width (B)
35"
35"
47"
47"
47"
*Add minimum 18" height for separate filter plenum, plus floorstand height
Height (C)
76"
76"
76"
76"
76"
18
700
600
500
2012 Temperatures
400
2013 Temperatures
300
200
100
Unit #1
Econ Hrs
4,018Hrs
Unit #2
Econ Hrs
5,354Hrs
0
Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct
1.40
Power History
300
1.30
250
1.25
Cooling PUE
1.35
KW
350
200
1.20
1.15
Avg O/A Temp
Cooling PUE
100
1.10
50
0
29-Aug-12
1.05
18-Oct-12
7-Dec-12
26-Jan-13
17-Mar-13
6-May-13
25-Jun-13
14-Aug-13
3-Oct-13
22-Nov-13
1.00
11-Jan-14
prefer ASHRAE
Recommended Conditions
(41.9 F. Dew Point to 60%
RH)
DSE is an indirect system
21
22
centers.
23
24
25
26
27
Source:
http://www.energy.ca.gov/title24/2008standards/special_case_appliance/ref
rigerant_economizer/2015-0609_Emerson_Proposal_to_Include_Refrigerant_Economizers_in_T24.pdf
28
29
30
31
32
Refrigerant Economizers
Approved as Alt. Comp. Pkg. for Title 24
Source: http://docketpublic.energy.ca.gov/PublicDocuments/15-MISC03/TN206117_20150916T095116_Resolution_of_the_Energy_Commi
ssion_re_Refrigerant_Economizers.pdf
33
Questions?
34