Trip Circuit Supervision In Switchgear (product-detail.html)


Posted by : Electrical India

Posted date : May 5, 2015

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 2 of 11

(/uploads/2253/Trip Circuit.png)

Trip Circuit Supervision In Switchgear


Due to operator's negligence, a catastrophic failure of critical equipment in the installation may occur
even where 'TCH Check Push Button and a TCS Lamp' are present. What is the remedy?

-K Sivakumar

A switchgear is a device or a combination of devices, primarily intended for the purpose of making,

carrying and breaking currents in electric circuits, during normal conditions as well as during abnormal
situations. Thus, in the event of an abnormality as that of a fault, detection and timely isolation of the
faulty portion of the network is the most important function of any switchgear. So, in a switchgear
installation, the trip circuit is very crucial.
What is the use, even if an installation has 'world-class' protection relays, auxiliary relays and even 'worldclass' switchgear, if the circuit breaker trip coil is faulty and/or the wiring is loose and/or the power supply
to the circuit breaker trip circuit is interrupted?
In the event that the trip circuit becomes unhealthy, either the fault remains unisolated, leading to
catastrophic damages, or leads to the tripping of an upstream switching device, thereby causing
unwanted power outage in a larger portion of the network.
The trip circuit of a switchgear may include the main protection relay, the master trip relay, relay contacts,
switchgear auxiliary contacts, fuses, links, wiring, terminal blocks etc. With so many components, the
probability of the trip circuit becoming unhealthy is quite high. Thus, it calls for a system to monitor the
integrity of the trip circuit. This is known as Trip Circuit Supervision (TCS).

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 3 of 11

Principle of operation
The trip circuit supervision, in its simplest form, may consist of a 'Trip Circuit Healthy (TCH)' indication
lamp, as shown in the figure below. To avoid any unwanted tripping of the breaker, in the event of any
short circuit in the lamp, a series resistor (R) is added in the circuit.
This arrangement offers trip circuit supervision only when the breaker is in ON condition.

Trip circuit supervision scheme, when the circuit breaker is closed...

By incorporating a simple modification, the trip circuit supervision facility can be extended to the breaker
OFF status also, as shown below:

TCS Scheme, when the circuit breaker is open or closed...

In both the above cases, the trip circuit supervision is continuous. Since this is only a local lamp indication
for the trip circuit healthiness, an operator has to continuously be monitoring the glowing of the TCH
lamp. This is not practically possible. Also, such a continuous supervision of the trip circuit, with resistors
in the circuit, might lead to unnecessary drain on the sub-station battery capacity.
Hence, the circuit can be modified such that the trip circuit healthiness can be checked only 'on demand.'
This is made possible by the addition of a 'Trip Circuit Healthy Check (TCH)' push button, with a normally
open (N.O.) contact configuration. This is shown below:

Modified circuit with the TCH push button...

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 4 of 11

But, the problem with the above scheme is that the scheme would give only a local indication. Thus, it is
suitable only for manned switchgear installations. Also, the operator has to check the healthiness of the
trip circuit, regularly, by pressing the 'TCH Push Button' and ensuring that the TCH lamp glows, while
doing so. If there is any dereliction of duty on the part of the operator, then even when the trip circuit is
faulty, the alarming situation will not come to the notice of the concerned personnel at all.
I have witnessed a couple of cases, where in such installations (as above) with a 'TCH Check Push Button
and a TCS Lamp,' there has been catastrophic failure of critical equipment in the installation, due to
operator's negligence. That is, there were failures of trip coils of important breakers in the installation, but
this did not come to the notice of any one, as no one had been following the practice to check the
healthiness of the trip circuit regularly, by pressing the TCH button.

Trip Circuit Supervision (TCS) relay...

To avoid such an eventuality and also to have a remote alarm for failure of the trip circuit healthiness, a
Trip Circuit Supervision Relay can be used.
Refer to the scheme below:

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 5 of 11

Trip circuit supervision scheme (with remote alarm), when the circuit breaker is open or closed...

In the above arrangement, when the breaker is ON, and if the trip circuit is healthy, the current path will
be:
+ ve, Fuse, R, Coil A of the TCS relay, 52a contact, Trip Coil (TC), Link & -ve.
Coil A of the TCS relay will energise and the normally open (N.O.) contact of this coil, wired in the path of
Coil C of the TCS relay, will close. Thus, Coil C of the TCS relay will energise and open its normally closed
(N.C.) contact that may be wired to the Trip Circuit Failure Alarm.
And, when the breaker is OFF, and if the trip circuit is healthy, the current path will be:
+ ve, Fuse, R, Coil A of the TCS relay, R, Coil B of the TCS relay, Trip Coil (TC), Link & -ve.
Now, both Coil A & Coil B of the TCS Relay will energise and the normally open (N.O.) contacts of these
two coils wired in the path of Coil C of the TCS relay, will close. Thus, Coil C of the TCS relay will energise
and open its normally closed (N.C.) contact that may be wired to the Trip Circuit Failure Alarm.
Thus, when the trip circuit is healthy, no trip circuit failure alarm will be initiated. When the trip circuit is
unhealthy, whether the breaker is in ON condition or in OFF condition, an alarm will be initiated.
Again, to avoid any unwanted tripping in the event of an inadvertent short circuit in any of the trip circuit
supervision circuit components, resistors are added in series with coils A & B. Generally, these resistors
are mounted separately, external to the relay. A very important point to note is that the trip circuit failure
alarm supply should be independent of the tripping supply so that the trip circuit failure indication/alarm
will be obtained, even in the case of failure of the tripping supply.
Such Trip Circuit Supervision (TCS) relays are intended for a continuous supervision of circuit breaker trip
circuit, and to give an alarm for loss of auxiliary supply, faults on the trip-coil or its wires independent of
the breaker position, faults on the breaker auxiliary contacts and faults in the supervision relay itself.
Numerical trip circuit supervision relay

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 6 of 11

The trip circuit supervision relay SPER 1C1 from ABB...


As in the case of any other protection relay and auxiliary relays, technology has evolved today there are
numerical trip circuit supervision relays available in the market place. The numerical TCS relay is designed
for the supervision of trip circuits and other important control and monitoring circuits.

Fig. 1: A block diagram of a TCS relay...

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 7 of 11

Block diagram of the relay is shown in Fig. 1. The supervision function is based on a low-level (~ 3 mA)
current injection principle. The injected current is sensed by two opto-couplers (one each wired across
relay terminals 13-15 and across 12-11. The supervision function in the two steady states of circuit
breaker-trip circuit (pre-close and post-close) can be seen from figures 2 & 3.

Fig. 2: Pre-close supervison...

Fig. 3: Post-close supervison...

The relay monitors the trip coil circuit continuously in breaker ON as well as in OFF conditions and gives
alarm in case of the following faults:

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 8 of 11

Open circuit of trip coil or trip coil circuit


Failure of trip coil supply
Under-voltage condition of trip coil supply
Failure of auxiliary supply
Failure of circuit breaker mechanism to complete a trip operation

And, in most of the modern 'Numerical Protection Relays,' the trip circuit supervision function is in-built.
Thus, there is no need for any external Trip Circuit Supervision (TCS )relay, either electro-mechanical or
numerical.
Conclusion
It is hoped that the importance and criticality of the trip circuit supervision in electrical switchgear
installations is well understood. It is wished that the practice of frequent, continuous, regular monitoring
of the trip circuit healthiness is followed in all electrical switchgear installations.

The Author is Manager at Megawin Switchgear Pvt.Ltd.

1 Comment

Electrical India

Recommend 3

Share

Login

Sort by Best

Join the discussion


Pakhi Tiwari 8 months ago

Thanks. I learn lot of thing. Thank you. i am part of global sparenparts private limited.
Reply Share

Subscribe d Add Disqus to your site Add Disqus Add

(http://www.megger.com)

Privacy

(http://www.motwane.com/)

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 9 of 11

(http://www.finolex.com)

(http://www.leoni.com)

(http://www.desmaindia.com)

(http://www.guptapower.com)

(https://www.omicronenergy.com/)

(http://www.havells.com)

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear

11/7/2016

Electrical

Page 10 of 11

(https://www.mersen.com)

(http://www.wire-india.com/)

(http://www.deif.com)

(http://www.cpri.com)

(http://www.igus.in)

Our Magazines

http://www.electricalindia.in/blog/post/id/5460/trip-circuit-supervision-in-switchgear