PROGRAM ENERGETICS
Floor Convectors

Technical catalogue

263

55

FLOOR CONVECTORS
Natural Convection Floor Convectors TK

Floor Convectors
Application:
Floor convectors are modern heating bodies
designed for primary heating, as well as for
secondary heating, combined with other primary
heating bodies (radiators, floor heating, fan
convectors, air conditioning devices, etc.).
They are suitable for the heating of rooms with large
glazing surfaces: car showrooms, winter gardens,
apartments, business, shopping and similar
premises. In addition to their heating function, their
further important functions are the prevention of
condensation build-up on glazing, and fending-off
ingress of cold air into the room.
Natural Convection Floor Convectors TK

CONTENTS

Forced Convection Floor Convectors TKV

Natural convection floor convectors principle of


operation is natural air convection. They are designed
for secondary room heating. Their heating capacities
range from 0.3 kW to 3 kW, depending on the
convector size. They are distinguished for their silent
operation.
Forced Convection Floor Convectors TKV
TKV floor convectors principle of operation is
forced convection, i.e., natural air circulation is
boosted by means of a fan. They are suitable both
for primary and secondary heating of rooms, in
applications requiring higher heating capacities.
The heating capacity is a function of the convector
size, and ranges from 0.4 kW to 5.6 kW.

Cooling and Heating Floor Convectors TKH

Cooling and Heating Floor


Convectors TKH
The floor convector TKH draws in warm air from
the areas around the windows or hot walls, cools
it in the heat exchanger, and feeds it back into the
room. In this way, heating of room air volume due
to surface heating is reduced. In the cooling
process, a part of moisture is extracted from the
air; this dehumidification also contributes to
thermal comfort.
In the heating mode, the process is exactly
opposite. A floor convector draws in cold air from
the area behind the window. Air is heated in the
convector and fed back into the room.
Convector cooling capacities range from
0.35 kW to 0.95 kW.

CONTENTS

PROGRAM ENERGETICS
HEATING
Floor Convectors

CONTENTS

4.1.
Floor Convectors - General Information
Page
4.1.1.
Natural Convection Floor Convectors TK...........................................................................................................................................................2
4.1.1.01.
Floor Convectors TK Types and Technical Data ................................................................................................................................................5
4.1.2.
Forced Convection Floor Convectors TKV .........................................................................................................................................................8
4.1.2.01.
TKV - Application and Characteristics ...............................................................................................................................................................9
4.1.2.02.
TKV Technical Data .........................................................................................................................................................................................12
4.1.3.
Combinations of Forced and Natural Convection..........................................................................................................................................19
4.1.4.
Cooling and Heating Floor Convectors TKH....................................................................................................................................................20
4.1.4.00.
TKH - Applications and Characteristics ...........................................................................................................................................................20
4.1.4.00.
TKH Technical data ..........................................................................................................................................................................................22
4.1.5.
Accessories ............................................................................................................................................................................................................23
4.1.6.
Ordering Key ..........................................................................................................................................................................................................25
4.1.7.
Instructions for Installation ................................................................................................................................................................................27

FLOOR CONVECTORS GENERAL INFORMATION

Floor Convectors

4.1.0.00 FLOOR CONVECTORS

Application:
Floor convectors are modern heating bodies
designed for heating of business and shopping
premises, car showrooms, hotels, apartments and
other rooms. They serve either as primary heating
bodies or secondary heating bodies, combined with
primary heating bodies of other types (e.g. floor
heating, radiators, fan convectors, air conditioning
devices, etc.) They are particularly suitable for
application in all rooms with envelope walls exposed
to low exterior temperatures (large windows or glass
walls, cold walls).
Benefits:
In rooms with large glazing envelope surfaces or
cold envelope walls, it is difficult to establish
comfortable heating by means of conventional
heating bodies only. Temperature differences
between the glass surfaces and bulk air temperature
lead to cooling of air in the boundary layer along
the wall, and, in turn, to its downwards flow and
spreading across the entire room floor area, the
result being occupants discomfort. Especially when
outside temperatures drop below 10 C, it is
virtually impossible to maintain occupational
comfort in rooms with large surface windows unless
auxiliary floor convector heating is used.
Floor convectors further prevent condensation
build-up on glass, as they maintain a layer of warm
air adjacent to the glass surfaces. Floor convectors
(in particular, the TKV type) also prevent ingress of
cold outside air.
Functions:
Room heating (primary or secondary heating)
Maintenance of uniform air circulation field in
the room, and thereby, uniform distribution of
heat throughout the room
Prevention of condensation build-up on glass
surfaces
Prevention of ingress of cold outside air
through windows or doors, and thereby,
prevention of draught inside the room
Room cooling (TKH)
Operation:
Warm water from the central heating network is fed
into the floor convector heat exchanger and its heat is
transferred to air in the convector. The floor convector
draws in cold air resting close to the floor, heats the
air in the heat exchanger, and dispatches it back into
the room. In the case of heating with a TK type
convector, the heated air raises due to natural
convection.
A TKV type floor convector has a fan built in, to draw
in cold air from the region close to the floor, and,
after heating the air, to feed it back into the room, in a
pattern providing an air curtain on the glass window
surface. In this way, forced air circulation is
maintained in the room, providing faster, more
intensive and uniform heating than achievable by
natural convection (e.g. by means of radiators or
natural convection floor convectors).
Floor convector TKH has operation equal to TKV
including cooling function.

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

FLOOR CONVECTORS GENERAL INFORMATION

TKV - with forced convection

Types:
Natural convection floor convectors (type TK)
with single-, double- or triple-row heat exchanger
Forced convection floor convectors (type TKV)
with single-, double- or triple-row heat exchanger
Floor convectors with forced convection and
cooling function (type TKH) with two- or
three-row heat exchanger
Characteristics:
Large heating and cooling capacity and
high product quality
Easy connection to a single- or dual-pipe
system, like with conventional radiators
Small water content and fast heating of the room
Installation into the floor, hence no occupation
of floor area
Variety of control accessories available
Options to combine natural and forced convection
Variety of special designs available
(corner designs, rounded contours, variety of
tread-on grilles)
Nice appearance
Easy installation, operation and maintenance

TKH - with forced convection, heating and cooling function

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

4.1.0.00 FLOOR CONVECTORS

TK - with natural convection

NATURAL CONVECTION FLOOR CONVECTORS TK

Natural Convection Floor Convectors TK

4.1.1.00 FLOOR CONVECTORS

Application:
Natural convection floor convectors are applied
basically as secondary heating bodies, in
combination with other primary heating bodies
(also in combination with TKVs serving as
primary heating bodies). They are installed in the
floor, in immediate proximity to doors to outside
or windows.
Operation:
Natural convection floor convectors apply the
principle of natural circulation of air. Warm water
form the central heating network is fed into the
floor convector heat exchanger, where its heat is
transferred to the air inside the convector. The
heated air then rises into the room.

Principle of operation:

TK Natural Convection Floor Convectors


Characteristics
Suitable for secondary heating
Heating capacities ranging from 0.3 kW to 3 kW
(as a function of the convector length)
Prevention of condensation on building
envelope glazing surfaces
Silent operation
No servicing required

TK Components (Basic Design):


1 Heat exchanger
2 Longitudinal tread-on grille (with standard
011profile), anodised in the natural aluminium
3 Housing
The basic design has no water side control
components. Such elements have to be ordered
as accessories to complete the basic design, as
indicated on page 25. Special grille designs
(various profiles, roll-up grille, corner designs)
are available on order.

Sizes:
Size XX
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Housing length L 950 1250 1550 1850 2150 2450 2750 2850 3150 3450 3750 4050 4350 4650 4950
Lamellar
section length K 650 950 1250 1550 1850 2150 2450 2550 2850 3150 3450 3750 4050 4350 4650

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

NATURAL CONVECTION FLOOR CONVECTORS TK TECHNICAL DATA

Single-Row Natural Convection Floor Convector TK-XX1

105

Housing length L
Length of the part fitted with blades K

50

4.1.1.01 FLOOR CONVECTORS

200

83

42 40

160

The figure is valid for convector with connection on the right side.

Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
236
204
171
138
105

02
1250
950
341
293
245
197
149

Water flow 250 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
444
547
650
751
852
954 1054
381
469
556
643
730
816
902
318
390
463
535
608
679
749
255
312
370
428
485
542
598
192
235
277
320
363
406
448

10
3450
3150
1153
987
821
656
490

11
3750
3450
1252
1072
891
712
532

12
4050
3750
1351
1156
962
768
574

13
4350
4050
1449
1240
1031
823
616

14
4650
4350
1547
1324
1100
877
653

15
4950
4650
1646
1408
1170
930
690

Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
218
189
159
128
98

02
1250
950
315
271
227
183
138

Water flow 125 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
411
506
601
694
786
877
967
353
434
515
595
673
751
828
295
362
429
495
561
625
690
237
290
343
396
448
500
552
178
218
258
298
336
375
414

10
3450
3150
1055
904
753
603
452

11
3750
3450
1143
980
817
653
490

12
4050
3750
1231
1055
879
704
528

13
4350
4050
1317
1129
942
754
565

14
4650
4350
1402
1203
1003
803
603

15
4950
4650
1487
1276
1065
852
640

Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
202
175
147
119
91

02
1250
950
292
251
210
169
129

Water flow 50 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
379
463
545
625
702
779
853
325
398
468
537
604
669
733
272
333
391
449
506
560
614
219
267
314
360
406
450
493
165
202
237
272
307
340
373

10
3450
3150
925
796
668
536
405

11
3750
3450
996
858
719
579
438

12
4050
3750
1064
917
770
620
470

13
4350
4050
1131
975
820
660
501

14
4650
4350
1197
1033
868
700
532

15
4950
4650
1264
1090
917
740
562

14
4650
4350
1222

15
4950
4650
1306

52.4

56.0

Thermal capatities at given temperature regimen (inlet water temperature/outlet water temperature/air temperature)
Size XX
01
02
03
04
05
06
07
08
09
10
11
12
13
Housing length L
950 1250 1550 1850 2150 2450 2750 2850 3150 3450 3750 4050 4350
Fioned section lenght K
650
950 1250 1550 1850 2150 2450 2550 2850 3150 3450 3750 4050
Heating
90 C /
Q (W) 182
267
351
435
520
604
688
716
800
885
969 1053 1137
power
70 C /
Water
m (kg/h) 7.8 11.4 15.0 18.6 22.3 25.9 29.5 30.7 34.3 37.9
41.5 45.1 48.7
20 C
flow
100 C /
80 C /
20 C
75 C /
65 C /
20 C

Heating
power
Water
flow
Heating
power
Water
flow

Q (W)

226

331

436

540

645

749

854

889

993

1098

1202

1307

1411

1516

1620

m (kg/h)

9.7

14.2

18.7

23.1

27.6

32.1

36.6

38.1

42.6

47.1

51.5

56.0

60.5

65.0

69.4

Q (W)

141

207

272

337

402

468

533

555

620

685

751

816

881

946

1012

m (kg/h) 12.1

17.7

23.3

28.9

34.5

40.1

45.7

47.6

53.1

58.7

64.4

69.9

75.5

81.1

86.7

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

NATURAL CONVECTION FLOOR CONVECTORS TK TECHNICAL DATA

Double- Row Natural Convection Floor Convector TK-XX2

105

Housing length L
180

50

300

4.1.1.00 FLOOR CONVECTORS

129

173

40

Length of the part fitted with blades K

The figure is valid for convector with connection on the right side.

Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
384
332
280
226
173

02
1250
950
553
476
398
320
242

Water flow 250 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
720
885 1049 1211 1372 1531 1689
618
758
898 1036 1174 1310 1445
515
632
747
862
976 1089 1201
413
506
598
689
780
870
960
311
381
448
517
585
651
719

10
3450
3150
1846
1579
1312
1049
786

11
3750
3450
2001
1712
1424
1138
852

12
4050
3750
2154
1843
1533
1226
918

13
4350
4050
2307
1974
1642
1313
984

14
4650
4350
2458
2104
1751
1400
1049

15
4950
4650
2608
2234
1859
1486
1113

Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
370
319
268
217
165

02
1250
950
531
456
381
306
232

Water flow 125 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
688
844
995 1145 1291 1436 1577
590
723
852
980 1106 1230 1352
492
601
710
816
921 1024 1126
395
482
568
654
737
820
902
297
363
426
491
554
616
678

10
3450
3150
1716
1471
1227
983
739

11
3750
3450
1853
1589
1325
1063
800

12
4050
3750
1988
1706
1424
1142
860

13
4350
4050
2120
1820
1520
1220
919

14
4650
4350
2250
1933
1615
1297
978

15
4950
4650
2379
2045
1711
1374
1036

Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
349
300
252
203
154

02
1250
950
494
424
355
285
215

Water flow 50 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
634
767
896 1019 1137 1250 1359
544
659
769
875
978 1076 1172
454
550
642
732
818
902
984
364
441
516
588
658
727
794
274
332
389
444
498
551
603

10
3450
3150
1466
1265
1064
858
652

11
3750
3450
1567
1354
1141
922
702

12
4050
3750
1666
1441
1216
983
750

13
4350
4050
1761
1525
1289
1044
798

14
4650
4350
1853
1607
1360
1103
845

15
4950
4650
1946
1688
1431
1162
892

14
4650
4350

15
4950
4650

2084

2228

89.3

95.5

2626

2808

Thermal capatities at given temperature regimen (inlet water temperature/outlet water temperature/air temperature)
Size XX
01
02
03
04
05
06
07
08
09
10
11
12
13
Housing length L
950 1250 1550 1850 2150 2450 2750 2850 3150 3450 3750 4050 4350
Fioned section lenght K
650
950 1250 1550 1850 2150 2450 2550 2850 3150 3450 3750 4050
Heating
90 C /
Q (W) 311
455
599
743
886 1030 1174 1222 1366 1509 1653 1797 1941
power
70 C /
Water
m (kg/h) 13.3 19.5 25.7 31.8 38.0 44.1 50.3 52.4 58.5 64.7
70.8 77.0 83.2
20 C
flow
100 C /
80 C /
20 C
75 C /
65 C /
20 C

Heating
power
Water
flow
Heating
power
Water
flow

Q (W)

392

573

755

936

1116

1298

1479

1540

1721

1902

2083

2264

2446

m (kg/h) 16.8

24.6

32.4

40.1

47.8

55.6

63.4

66.0

73.8

81.5

89.3

97.0

104.8 112.5 120.3

237

346

456

565

674

784

893

930

1039

1148

1257

1367

1477

m (kg/h) 20.3

29.7

39.1

48.4

57.8

67.2

76.5

79.7

89.1

98.4

107.7 117.2

Q (W)

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

1585

1695

126.6 135.9 145.3

NATURAL CONVECTION FLOOR CONVECTORS TK TECHNICAL DATA

Three- Row Natural Convection Floor Convector TK-XX3

105

Housing length L
180

50

4.1.1.00 FLOOR CONVECTORS

400

263

216

40

Length of the part fitted with blades K

The figure is valid for convector with connection on the right side.
Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
495
429
362
293
224

02
1250
950
714
614
514
414
313

Water flow 250 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
929 1141 1350 1556 1759 1961 2159
797
977 1156 1332 1506 1678 1848
665
814
962 1108 1252 1395 1537
533
652
769
886 1001 1115 1229
401
489
577
664
750
835
920

10
3450
3150
2355
2016
1678
1341
1005

11
3750
3450
2548
2182
1817
1453
1089

12
4050
3750
2738
2346
1955
1564
1172

13
4350
4050
2926
2509
2091
1673
1255

14
4650
4350
3112
2669
2226
1782
1337

15
4950
4650
3299
2830
2361
1890
1420

Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
474
409
344
279
213

02
1250
950
679
584
488
392
297

Water flow 125 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
879 1073 1263 1447 1627 1802 1974
754
921 1083 1242 1396 1548 1696
629
768
903 1036 1166 1294 1419
504
615
722
829
933 1036 1137
379
461
542
622
701
778
855

10
3450
3150
2140
1841
1541
1237
932

11
3750
3450
2304
1983
1662
1335
1007

12
4050
3750
2463
2122
1781
1431
1081

13
4350
4050
2619
2258
1898
1526
1154

14
4650
4350
2771
2392
2013
1620
1227

15
4950
4650
2924
2526
2128
1714
1300

Size XX
Housing length L
Fioned section lenght K
Heating
90 C
power (W)
80 C
by the inlet
70 C
water
60 C
temperature
50 C

01
950
650
448
385
322
259
196

02
1250
950
632
541
451
362
273

Water flow 50 kg/h and air temperature 20 C


03
04
05
06
07
08
09
1550 1850 2150 2450 2750 2850 3150
1250 1550 1850 2150 2450 2550 2850
804
966 1118 1263 1400 1531 1655
689
829
961 1087 1208 1322 1432
575
692
804
911 1015 1114 1209
461
555
646
733
818
899
978
347
418
488
555
621
685
747

10
3450
3150
1773
1537
1302
1055
808

11
3750
3450
1886
1638
1391
1129
867

12
4050
3750
1994
1736
1477
1201
926

13
4350
4050
2098
1829
1561
1272
983

14
4650
4350
2197
1920
1642
1340
1039

15
4950
4650
2297
2010
1723
1409
1095

Thermal capatities at given temperature regimen (inlet water temperature/outlet water temperature/air temperature)
Size XX
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Housing length L
950 1250 1550 1850 2150 2450 2750 2850 3150 3450 3750 4050 4350 4650 4950
Fioned section lenght K
650
950 1250 1550 1850 2150 2450 2550 2850 3150 3450 3750 4050 4350 4650
Heating
90 C /
Q (W) 410
599
788
977 1166 1355 1544 1607 1796 1985 2174 2363 2552 2741 2930
power
70 C /
Water
m (kg/h) 17.6 25.7 33.8 41.9 50.0 58.1 66.2 68.9 77.0 85.1
93.2 101.3 109.4 117.5 125.6
20 C
100 C /
80 C /
20 C
75 C /
65 C /
20 C

flow
Heating
power
Water
flow
Heating
power
Water
flow

Q (W)

517

755

993

1231

1469

1707

1946

2025

2263

m (kg/h) 22.2

32.4

42.6

52.8

63.0

73.2

83.4

86.8

97.0 107.2

117.4 127.6

137.8 148.0 158.2

312

456

599

743

887

1031

1175

1222

1366

1654

1941

m (kg/h) 26.7

39.1

51.3

63.7

76.0

88.4

100.7 104.7

Q (W)

2501

1510

117.1 129.4

2740

2978

1798

141.8 154.1

3216

3454

2085

3692

2229

166.4 178.7 191.1

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

FORCED CONVECTION FLOOR CONVECTORS TKV

4.1.2.00 FLOOR CONVECTORS

Forced Convection Floor Convectors TKV


Application:
Forced convection floor convectors are designed
for primary or secondary room heating, where fast
heating and large heating capacities are required.
Type TKV floor convector heating capacities range
from 0.4 kW to 5.6 kW, as a function of the
convector size.
They are particularly suitable for application in all
rooms with envelope walls exposed to low
exterior temperatures (large windows or glass
walls, cold walls), as the occupancy comfort in a
room heavily depends on the uniform distribution
of heat in the room.

Principle of operation:

Operation:
Forced convection floor convectors apply the
principle of forced convection, i.e., air volume flow
rate is maintained both by natural circulation and by
means of a tangential fan.
A floor convector draws in air from its surrounding
floor area, heats the air in the heat exchanger, and
then returns it into the room by blowing the air
against the window surface. The jet of heated air
prevents condensation of cold glass surfaces. TKV
floor convectors further prevent cold outside air from
ingressing into the room.
Compared to natural convection floor convectors,
the TKV convectors maintain higher air circulation
velocities in the room, and thereby reduce the room
height profile temperature differences and improve
occupancy comfort.
To perform efficiently, the floor convector should be
installed as close as possible to glass surfaces.
Forced Convection Floor Convector
Characteristics:
Suitable for both primary and secondary room
heating
Large heating capacity (up to 5.6 kW with a
4,950 mm convector length)
Continuous or step fan speed setting
Low noise operation
TKV Components (Basic Design):
1 Heat exchanger
2 Tangential fan
3 Electric connection socket
4 Longitudinal tread-on grille (with the standard
011 profile), treated in the natural aluminium
colour
5 Housing
Water side and air side control accessories or
special grille designs (various profiles, roll-up
grille, corner designs) can be installed or
delivered on request.

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

FORCED CONVECTION FLOOR CONVECTORS TKV

Types and Dimensions


Single-Row Forced Convection Floor Convector TKV-1
105

Housing lenght L
160

50

Con.
Box

55

Double-Row Forced Convection Floor Convector TKV-2


Housing lenght L

105
180

50

300

129

173

40

Length of the part fitted with blades K

Con.
Box
55

Three-Row Forced Convection Floor Convector TKV-3


105

Housing lenght L
180

50

400

263

216

40

Length of the part fitted with blades K

Con.
Box

The above figures are valid for the convectors with the connection on the right side.

55

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

4.1.2.01 FLOOR CONVECTORS

200

83

42 40

Length of the part fitted with blades K

FORCED CONVECTION FLOOR CONVECTORS TKV

Components
Heat Exchanger
The heat exchanger is made of high quality materials to guarantee a long
service life. It is made of ( 15 mm copper tubes with drawn-on 83 x 50
mm aluminium lamellas. In this way, firm contact is achieved between the
lamella and the tube, and in turn, excellent heat transfer. Water
connections consist of R1/2 thread nuts. We install single-row, doublerow or three-row heat exchangers, which differ in capacities.

Tangential Fan
The tangential fan consists of a single-phase low power electric motor
(230/240 V, 50/60 Hz, max. 29 W, max. 0.23 A) and fans on both sides of
the motor. In a standard convector, two fan sets are installed. The fan is
protected against mechanical damaging by means of a protection mesh
screen.
019

Housing
The convector housing is made of galvanised steel sheet and powder
painted in black. On the purchasers request, the housing can be painted
in any RAL scale colour. The housing can be thermally insulated (DIN
4108, 4109), on request. The standard housing length is from 950 to 450 mm.
When longer units are required, the housing is assembled from several
unit parts.
If requested, the housing can be designed so as to allow levelling by
height (Code 019). The levelling requires a simple loosening of the floor
convector legs by means of a screwdriver and adjusting the height. This
design solution simplifies the installation of convectors even in the cases
of uneven floors.

Tread-on Grille

Tread-on Grille Section Shapes:

5.5

5.5

20

20

7.5

Aluminium flat
profile

Aluminium twoside slant profile

Wooden roll-up grille


profile

20

Aluminium standard
profile

20

4.1.2.01 FLOOR CONVECTORS

Heat Exchanger

Standard Tread-on Grille:


is fixed in length
has a single-slant profile
is anodised in the natural aluminium colour
At the length over 3150 mm, grille consists of two parts
Special Grille Designs, on Request:
two additional profile cross-section designs:
1. two-side slant profile or
2. flat profile
Max length of one part of the grille is 2300 mm
anodising in other colours (golden, black or brass)
roll-up grille (available with the same lamellas and anodised in the
same colours as longitudinal grilles)
Wooden roll-up grille (wood type: oak wood, ash wood, walnut wood,
mahogany)

Any special tread-on grille design shall be specified in the order, as


indicated in the ordering key section.

Example of longitudinal grille:

10

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

Example of roll-up grille:

FORCED CONVECTION FLOOR CONVECTORS TKV

02 Thermostat valve R1/2, angular, without a


thermostat head

Control Accessories:
1. Control of the water flow rate to the
heat exchanger (water side control)
thermostat valve (designation 01 and 02)
shut-off cock (designation 03 or 04)
thermostat element (designation 05)
The basic design contains no water side control
elements. They shall be ordered as accessories to
complete the basic design, as indicated on page 17.

03 Shut-off cock R1/2, straight

04 Shut-off cock Rl/2, angular

05 Thermostat head with a remote surface mounted


sensor (up to 15 m), standard 2 m

07 Room thermostat - surface mounted

08 Continuous fan speed setting switch

2. Fan speed control (air side control)


The tangential fan operation can be controlled:
by means of a continuous speed controller
(designation 08) or
by means of a three-step speed controller MIN,
MID, MAX (designation 09)
Either of the above devices controls the electric
motor speed and thus maintains the air flow rate at
the desired value.
Room thermostat switches the fans on or off
depending on the relation between the set and
actual room temperature (designation 07)

078 Room thermostat for surface mounting with


continious fan speed setting switch, ON/OFF
switch and HEATING/COOLING switch.

09 Room thermostat for surface mounting with a


three-stage speed setting switch (MIN-MEDMAX), ON/OFF switch and
HEATING/COOLING switch.

Mandatory accessories:
The mandatory accessories of a forced convection
floor convector (TKV), to be ordered separately,
consist of:
a continuous fan speed setting switch
(designation 08) or
room thermostat for surface mounting with a
three-stage speed setting switch (MIN-MEDMAX), ON/OFF switch and HEATING/COOLING
switch (designation 09)
Room thermostat for surface mounting with
continious fan speed setting switch, ON/OFF
switch and HEATING/COOLING switch
(designation 078)

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

11

4.1.2.01 FLOOR CONVECTORS

01 Thermostat valve R1/2, straight,


without a thermostat head

FORCED CONVECTION FLOOR CONVECTORS TKV TECHNICAL DATA

Forced Convection Floor Convector Thermal Capacity


Convector length: 1600 mm
Heat exchanger lamelled section length: 1300 mm
Air temperature: 20C.
Single-Row Forced Convection Floor Convector TKV-1 with a Longitudinal Fixed Grille

4.1.2.02 FLOOR CONVECTORS

Water flow volume: 250 kg/h


Flow temperature: 90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
89.0
296
MIN
84.1
1722
MED
82.0
2339
MAX
79.8
2968
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
79.2
238
MIN
74.9
1475
MED
73.1
2005
MAX
71.3
2543
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
69.4
186
MIN
65.8
1230
MED
64.3
1670
MAX
62.7
2118
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
59.5
133
MIN
56.6
983
MED
55.4
1335
MAX
54.2
1696
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
49.7
90
MIN
47.5
739
MED
46.6
998
MAX
45.6
1271

12

Water flow volume: 125 kg/h


Flow temperature: 90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
88.0
287
MIN
78.9
1616
MED
76.2
2009
MAX
72.5
2548
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
78.4
231
MIN
70.5
1385
MED
68.2
1721
MAX
65.0
2184
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
68.8
178
MIN
62.1
1154
MED
60.2
1435
MAX
57.5
1820
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
59.1
130
MIN
53.7
924
MED
52.1
1148
MAX
50.0
1456
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
49.4
86
MIN
45.2
693
MED
44.1
860
MAX
42.5
1091

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

Water flow volume: 50 kg/h


Flow temperature: 90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
85.3
274
MIN
69.7
1186
MED
64.8
1472
MAX
59.7
1770
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
76.2
221
MIN
62.6
1016
MED
58.4
1262
MAX
54.0
1517
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
67.1
170
MIN
55.5
847
MED
52.0
1052
MAX
48.3
1264
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
57.9
124
MIN
48.4
677
MED
45.6
841
MAX
42.7
1011
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
48.6
83
MIN
41.3
508
MED
39.2
631
MAX
37.0
758

FORCED CONVECTION FLOOR CONVECTORS TKV TECHNICAL DATA

75 C / 65 C / 20 C

100 C / 80 C / 20 C

90 C / 70 C / 20 C

Single-Row Forced Convection Floor Convector TKV-1 with a Longitudinal Fixed Grille
Size XX
01
02
03
04
05
06
Housing length L
950 1250 1550 1850 2150 2450
Fioned section lenght K
650
950 1250 1550 1850 2150
Heating power Q (W) 134
215
254
335
417
498
STOP
Water flow m (kg/h) 5.7
9.2 10.9 14.4 17.9 21.3
Heating power Q (W) 664
748 1315 1399 1484 1568
MIN
Water flow m (kg/h) 28.5 32.1 56.4 60.0 63.6 67.2
Heating power Q (W) 914 1000 1814 1900 1986 2072
MED
Water flow m (kg/h) 39.2 42.9 77.7 81.4 85.1 88.8
Heating power Q (W) 1215 1302 2415 2503 2590 2678
MAX
Water flow m (kg/h) 52.1 55.8 103.5 107.3 111.0 114.8
Heating power Q (W) 162
263
307
408
509
610
STOP
Water flow m (kg/h) 6.9 11.3 13.2 17.5 21.8 26.1
Heating power Q (W) 781
885 1545 1650 1755 1859
MIN
Water flow m (kg/h) 33.5 37.9 66.2 70.7 75.2 79.7
Heating power Q (W) 1072 1179 2128 2234 2341 2448
MED
Water flow m (kg/h) 45.9 50.5 91.2 95.7 100.3 104.9
Heating power Q (W) 1424 1532 2829 2938 3046 3155
MAX
Water flow m (kg/h) 61.0 65.7 121.2 125.9 130.5 135.2
Heating power Q (W) 107
170
203
266
330
392
STOP
Water flow m (kg/h) 9.2 14.6 17.4 22.8 28.3 33.6
Heating power Q (W) 549
614 1087 1152 1218 1283
MIN
Water flow m (kg/h) 47.1 52.6 93.2 98.7 104.4 110.0
Heating power Q (W) 757
823 1503 1569 1636 1703
MED
Water flow m (kg/h) 64.9 70.5 128.8 134.5 140.2 146.0
Heating power Q (W) 1008 1075 2003 2072 2139 2207
MAX
Water flow m (kg/h) 86.4 92.1 171.7 177.6 183.3 189.2

07
2750
2450
580
24.9
1653
70.8
2158
92.5
2766
118.5
712
30.5
1965
84.2
2554
109.5
3265
139.9
456
39.1
1349
115.6
1769
151.6
2275
195.0

08
2850
2550
607
26.0
1681
72.0
2187
93.7
2795
119.8
745
31.9
1999
85.7
2590
111.0
3301
141.5
477
40.9
1371
117.5
1792
153.6
2298
197.0

09
3150
2850
688
29.5
1766
75.7
2273
97.4
2882
123.5
846
36.3
2105
90.2
2697
115.6
3408
146.1
539
46.2
1436
123.1
1858
159.3
2365
202.7

10
3450
3150
770
33.0
1851
79.3
2359
101.1
2970
127.3
947
40.6
2210
94.7
2804
120.2
3518
150.8
603
51.7
1502
128.7
1925
165.0
2433
208.5

11
3750
3450
851
36.5
1935
82.9
2445
104.8
3058
131.1
1048
44.9
2315
99.2
2911
124.8
3627
155.4
666
57.1
1567
134.3
1992
170.7
2502
214.5

12
4050
3750
932
39.9
2020
86.6
2531
108.5
3146
134.8
1148
49.2
2420
103.7
3017
129.3
3736
160.1
728
62.4
1633
140.0
2058
176.4
2570
220.3

13
4350
4050
1014
43.5
2104
90.2
2617
112.2
3233
138.6
1250
53.6
2524
108.2
3124
133.9
3844
164.7
792
67.9
1698
145.5
2125
182.1
2637
226.0

14
4650
4350
1095
46.9
2189
93.8
2703
115.8
3321
142.3
1351
57.9
2630
112.7
3231
138.5
3953
169.4
855
73.3
1764
151.2
2191
187.8
2705
231.9

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

15
4950
4650
1177
50.4
2274
97.5
2789
119.5
3409
146.1
1452
62.2
2735
117.2
3337
143.0
4062
174.1
918
78.7
1830
156.9
2258
193.5
2773
237.7

13

4.1.2.02 FLOOR CONVECTORS

Forced Convection Floor Convector Thermal capatities at given temperature regimen


(inlet water temperature/outlet water temperature/air temperature)

FORCED CONVECTION FLOOR CONVECTORS TKV TECHNICAL DATA

Forced Convection Floor Convector Thermal Capacity


Convector length: 1600 mm
Heat exchanger lamelled section length: 1300 mm
Air temperature: 20C.
Double- Row Forced Convection Floor Convector TKV-2 with a Longitudinal Fixed Grille

4.1.2.02 FLOOR CONVECTORS

Water flow volume: 250 kg/h


Flow temperature: 90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
88.2
530
MIN
82.0
2331
MED
78.8
3256
MAX
76.3
4007
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
78.5
425
MIN
73.1
1999
MED
70.4
2791
MAX
68.2
3437
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
68.9
329
MIN
64.3
1664
MED
62.0
2325
MAX
60.2
2863
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
59.2
239
MIN
55.4
1330
MED
53.6
1859
MAX
52.1
2290
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
49.5
160
MIN
46.6
1001
MED
45.2
1394
MAX
44.1
1717

14

Water flow volume: 125 kg/h


Flow temperature:90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
86.5
511
MIN
75.4
2126
MED
71.2
2746
MAX
66.0
3498
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
77.2
410
MIN
67.5
1822
MED
63.9
2354
MAX
59.4
2997
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
67.8
317
MIN
59.6
1518
MED
56.5
1962
MAX
52.9
2498
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
58.4
231
MIN
51.7
1215
MED
49.2
1568
MAX
46.3
1998
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
48.9
154
MIN
43.8
911
MED
41.9
1177
MAX
39.7
1499

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

Water flow volume: 50 kg/h


Flow temperature: 90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
81.8
478
MIN
62.1
1630
MED
57.4
1900
MAX
50.5
2307
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
73.4
384
MIN
56.1
1397
MED
52.1
1628
MAX
46.1
1978
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
64.9
299
MIN
50.0
1164
MED
46.7
1357
MAX
41.7
1648
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
56.2
219
MIN
44.0
931
MED
41.4
1085
MAX
37.4
1319
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
47.5
146
MIN
38.0
698
MED
36.0
814
MAX
33.0
989

FORCED CONVECTION FLOOR CONVECTORS TKV TECHNICAL DATA

75 C / 65 C / 20 C

100 C / 80 C / 20 C

90 C / 70 C / 20 C

Double- Row Forced Convection Floor Convector TKV-2 with a Longitudinal Fixed Grille
Size XX
01
02
03
04
05
06
07
Housing length L
950 1250 1550 1850 2150 2450 2750
Fioned section lenght K
650
950 1250 1550 1850 2150 2450
Heating power Q (W) 242
385
458
602
745
889 1032
STOP
Water flow m (kg/h) 10,4 16,5 19,6 25,8 31,9 38,1 44,2
Heating power Q (W) 1012 1161 2000 2149 2298 2447 2596
MIN
Water flow m (kg/h) 43,4 49,8 85,7 92,1 98,5 104,9 111,3
Heating power Q (W) 1365 1516 2706 2856 3007 3158 3309
MED
Water flow m (kg/h) 58,5 65,0 116,0 122,4 128,9 135,3 141,8
Heating power Q (W) 1878 2031 3731 3884 4037 4190 4344
MAX
Water flow m (kg/h) 80,5 87,0 159,9 166,5 173,0 179,6 186,2
Heating power Q (W) 295
476
558
739
920 1101 1281
STOP
Water flow m (kg/h) 12,6 20,4 23,9 31,7 39,4 47,2 54,9
Heating power Q (W) 1194 1382 2358 2546 2733 2921 3109
MIN
Water flow m (kg/h) 51,2 59,2 101,1 109,1 117,1 125,2 133,2
Heating power Q (W) 1606 1796 3182 3371 3561 3752 3942
MED
Water flow m (kg/h) 68,8 77,0 136,4 144,5 152,6 160,8 168,9
Heating power Q (W) 2205 2398 4378 4571 4764 4957 5151
MAX
Water flow m (kg/h) 94,5 102,8 187,6 195,9 204,2 212,4 220,8
Heating power Q (W) 192
300
363
473
582
691
800
STOP
Water flow m (kg/h) 16,5 25,7 31,1 40,5 49,9 59,2 68,6
Heating power Q (W) 833
946 1648 1761 1874 1988 2101
MIN
Water flow m (kg/h) 71,4 81,1 141,3 150,9 160,6 170,4 180,1
Heating power Q (W) 1127 1242 2236 2350 2465 2579 2694
MED
Water flow m (kg/h) 96,6 106,5 191,7 201,4 211,3 221,1 230,9
Heating power Q (W) 1554 1671 3089 3206 3322 3439 3556
MAX
Water flow m (kg/h) 133,2 143,2 264,8 274,8 284,7 294,8 304,8

08
2850
2550
1080
46,3
2645
113,4
3359
144,0
4395
188,4
1342
57,5
3171
135,9
4005
171,6
5215
223,5
836
71,7
2138
183,3
2732
234,2
3595
308,1

09
3150
2850
1224
52,5
2794
119,7
3510
150,4
4548
194,9
1523
65,3
3358
143,9
4195
179,8
5408
231,8
946
81,1
2252
193,0
2847
244,0
3711
318,1

10
3450
3150
1367
58,6
2943
126,1
3661
156,9
4701
201,5
1703
73,0
3546
152,0
4385
187,9
5601
240,0
1055
90,4
2365
202,7
2962
253,9
3827
328,0

11
3750
3450
1511
64,8
3092
132,5
3812
163,4
4854
208,0
1885
80,8
3734
160,0
4576
196,1
5793
248,3
1164
99,8
2478
212,4
3077
263,7
3944
338,1

12
4050
3750
1654
70,9
3241
138,9
3963
169,8
5008
214,6
2065
88,5
3922
168,1
4766
204,3
5987
256,6
1273
109,1
2592
222,2
3192
273,6
4061
348,1

13
4350
4050
1798
77,1
3390
145,3
4114
176,3
5161
221,2
2247
96,3
4110
176,1
4956
212,4
6180
264,9
1383
118,5
2705
231,9
3307
283,5
4177
358,0

14
4650
4350
1941
83,2
3539
151,7
4265
182,8
5314
227,7
2427
104,0
4297
184,2
5147
220,6
6373
273,1
1491
127,8
2818
241,5
3422
293,3
4294
368,1

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

15
4950
4650
2058
88,2
3688
158,1
4416
189,3
5467
234,3
2608
111,8
4485
192,2
5337
228,7
6566
281,4
1601
137,2
2932
251,3
3536
303,1
4410
378,0

15

4.1.2.02 FLOOR CONVECTORS

Forced Convection Floor Convector Thermal capatities at given temperature regimen


(inlet water temperature/outlet water temperature/air temperature)

FORCED CONVECTION FLOOR CONVECTORS TKV TECHNICAL DATA

Forced Convection Floor Convector Thermal Capacity


Convector length: 1600 mm
Heat exchanger lamelled section length: 1300 mm
Air temperature: 20C.
Three- Row Forced Convection Floor Convector TKV-3 with a Longitudinal Fixed Grille

4.1.2.02 FLOOR CONVECTORS

Water flow volume: 250 kg/h


Flow temperature: 90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
87.5
729
MIN
80.1
2888
MED
76.0
4083
MAX
73.6
4783
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
77.8
642
MIN
71.3
2538
MED
67.9
3529
MAX
66.0
4083
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
68.5
438
MIN
63.0
2042
MED
59.9
2946
MAX
58.9
3238
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
58.9
321
MIN
54.3
1663
MED
51.9
2363
MAX
50.2
2858
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
49.3
204
MIN
45.8
1225
MED
44.0
1750
MAX
42.9
2071

16

Water flow volume: 125 kg/h


Flow temperature: 90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
85.2
700
MIN
72.7
2523
MED
67.1
3340
MAX
59.9
4390
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
76.1
569
MIN
64.9
2202
MED
60.1
2902
MAX
55.1
3631
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
66.9
452
MIN
57.4
1838
MED
53.3
2435
MAX
48.6
3121
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
57.8
321
MIN
50.1
1444
MED
46.9
1910
MAX
43.1
2465
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
48.5
219
MIN
42.6
1079
MED
40.0
1458
MAX
37.5
1823

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

Water flow volume: 50 kg/h


Flow temperature: 90 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
78.8
653
MIN
55.2
2030
MED
50.6
2298
MAX
42.8
2753
Flow temperature: 80 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
70.8
537
MIN
50.2
1738
MED
46.4
1960
MAX
39.0
2392
Flow temperature: 70 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
63.0
408
MIN
45.2
1447
MED
42.0
1633
MAX
35.9
1989
Flow temperature: 60 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
54.8
303
MIN
40.2
1155
MED
37.6
1307
MAX
33.2
1563
Flow temperature: 50 C
Fan
Water-outlet
Heating
speed
temperature
power Q (W)
STOP
46.5
204
MIN
35.0
875
MED
33.1
986
MAX
29.5
1196

FORCED CONVECTION FLOOR CONVECTORS TKV TECHNICAL DATA

75 C / 65 C / 20 C

100 C / 80 C / 20 C

90 C / 70 C / 20 C

Three- Row Forced Convection Floor Convector TKV-3 with a Longitudinal Fixed Grille
Size XX
01
02
03
04
05
06
Housing length L
950 1250 1550 1850 2150 2450
Fioned section lenght K
650
950 1250 1550 1850 2150
Heating power Q (W) 337
525
641
829 1017 1205
STOP
Water flow m (kg/h) 14,4 22,5 27,5 35,5 43,6 51,6
Heating power Q (W) 1258 1452 2482 2677 2871 3065
MIN
Water flow m (kg/h) 53,9 62,2 106,4 114,7 123,0 131,4
Heating power Q (W) 1883 2081 3733 3931 4129 4327
MED
Water flow m (kg/h) 80,7 89,2 160,0 168,5 177,0 185,4
Heating power Q (W) 2359 2559 4684 4884 5084 5285
MAX
Water flow m (kg/h) 101,1 109,7 200,7 209,3 217,9 226,5
Heating power Q (W) 410
647
779 1016 1253 1490
STOP
Water flow m (kg/h) 17,6 27,7 33,4 43,5 53,7 63,9
Heating power Q (W) 1485 1730 2928 3173 3418 3662
MIN
Water flow m (kg/h) 63,6 74,1 125,5 136,0 146,5 156,9
Heating power Q (W) 2215 2464 4388 4637 4887 5136
MED
Water flow m (kg/h) 94,9 105,6 188,1 198,7 209,4 220,1
Heating power Q (W) 2770 3022 5498 5750 6002 6255
MAX
Water flow m (kg/h) 118,7 129,5 235,6 246,4 257,2 268,1
Heating power Q (W) 268
411
510
653
796
939
STOP
Water flow m (kg/h) 23,0 35,2 43,7 56,0 68,2 80,5
Heating power Q (W) 1035 1182 2043 2192 2339 2487
MIN
Water flow m (kg/h) 88,7 101,3 175,1 187,9 200,5 213,2
Heating power Q (W) 1555 1706 3085 3236 3387 3537
MED
Water flow m (kg/h) 133,3 146,2 264,4 277,4 290,3 303,2
Heating power Q (W) 1952 2104 3878 4030 4182 4335
MAX
Water flow m (kg/h) 167,3 180,3 332,4 345,4 358,5 371,6

07
2750
2450
1393
59,7
3260
139,7
4524
193,9
5485
235,1
1726
74,0
3908
167,5
5385
230,8
6507
278,9
1082
92,7
2635
225,9
3687
316,0
4487
384,6

08
2850
2550
1455
62,4
3324
142,5
4590
196,7
5552
237,9
1805
77,4
3989
171,0
5468
234,3
6592
282,5
1129
96,8
2684
230,1
3737
320,3
4538
389,0

09
3150
2850
1643
70,4
3519
150,8
4788
205,2
5752
246,5
2042
87,5
4234
181,5
5717
245,0
6844
293,3
1272
109,0
2832
242,7
3888
333,3
4690
402,0

10
3450
3150
1831
78,5
3713
159,1
4986
213,7
5952
255,1
2278
97,6
7779
333,4
5967
255,7
7096
304,1
1415
121,3
2980
255,4
4039
346,2
4842
415,0

11
3750
3450
2019
86,5
3907
167,4
5184
222,2
6153
263,7
2515
107,8
4723
202,4
6216
266,4
7349
315,0
1558
133,5
3127
268,0
4189
359,1
4995
428,1

12
4050
3750
2207
94,6
4102
175,8
5382
230,7
6353
272,3
2752
117,9
4969
213,0
6466
277,1
7601
325,8
1701
145,8
3276
280,8
4340
372,0
5147
441,2

13
4350
4050
2395
102,6
4296
184,1
5580
239,1
6553
280,8
2989
128,1
5214
223,5
6715
287,8
7853
336,6
1844
158,1
3423
293,4
4490
384,9
5299
454,2

14
4650
4350
2583
110,7
4490
192,4
5778
247,6
6754
289,5
3226
138,3
5458
233,9
6965
298,5
8106
347,4
1987
170,3
3571
306,1
4641
397,8
5452
467,3

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

15
4950
4650
2771
118,8
4685
200,8
5976
256,1
6954
298,0
3463
148,4
5704
244,5
7214
309,2
8358
358,2
2130
182,6
3719
318,8
4792
410,7
5604
480,3

17

4.1.2.02 FLOOR CONVECTORS

Forced Convection Floor Convector Thermal capatities at given temperature regimen


(inlet water temperature/outlet water temperature/air temperature)

FORCED CONVECTION FLOOR CONVECTORS TKV TECHNICAL DATA

Water Pressure Drop in the Convector dp (kPa)

50

Flow m (kg/h)
125
250

Calculation of pressure drop dp (Pa) dependent on water flow m (kg/h)

TKV-1

0,08

0,33

1,12

dp = 0.0146 m2 + 0.8472 m (Pa)

TKV-2

0,13

0,58

1,99

dp = 0.0265 m2 + 1.3526 m (Pa)

TKV-3

0,21

0,94

3,31

dp = 0.0457 m2 + 1.8256 m (Pa)

Noise Level:
Velocity
MIN
MED
MAX

Sound pressure Lpa (dB)


21,9
35,9
45,6

Noise Level Measurement:


The measurements were carried out in an anechoic chamber, 109 m3 in
volume, with reflecting floor.The anechoic chamber is constructed in
conformance with the ISO 3745 standard.
Sound pressure was measured with the microphone positioned at a distance
1 m directly above the floor convector.

Connection Diagrams:
Connection Diagram for Accessory 09
L
N
PE

(x)
(x)
(x)

L
N
PE
230 V, 50Hz
3 G 1,5 mm

(x)
(x)
(x)

Connection Diagram for Accessories 07 and 08

Room Thermostat

230 V, 50 Hz

Accessory 09

3 G 1,5 mm2
1 2

(x)
Fan
QLK 45

5678

Connection box

230 V

(x)
(x)
(x)

Connection Diagram for Accessory 078


L
N
PE

Room Thermostat

,50Hz

Accessory 078

3 G 1,5 mm2

HEAT/COOL

5 6 7 8

(x)
(x)

1 2 3 4

(x)

ON-OFF J

Floor convector TKV


Fan
QLK 45

Connection box
NL
11 11 22 22

5678

2 x 0,75 mm2

Note: Connections marked with (x) are to be carried out by customer.

18

4 x 0,75 mm2

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

MIN
MED
MAX
Floor convector TKV

Conection box

NL
11 11 22 22

(x) (x)

Accessory 08

5 6 7 8

(x) (x) (x)

Speed regulator

100%
OFF
N L1 3 4

(x)

Accessory 07

1 2 3 4

(x)

ON-OFF J

Room thermostat

230 V, 50Hz
3 G 1,5 mm

N L1

4.1.2.02 FLOOR CONVECTORS

Maximum operating pressure is 25 bar.

Fan
QLK 45

COMBINATIONS OF NATURAL AND FORCED CONVECTION FLOOR CONVECTORS

Combinations of Natural and Forced Convection Floor Convectors


As a standard case, the combination of TK and TKV convectors is based on heat exchangers with the same numbers of rows. Combinations of convectors having
heat exchangers with different numbers of rows are also possible (as indicated in the drawing below).

Installation
The drawing below illustrates the installation of an individual fan to the desired location along a long assembly.

Con.
Box

Corner Designs
If the convector assembly axis is broken, special corner elements are installed in the corners. The heat exchangers of adjacent linear sections are interconnected
by means of flexible or copper tubes, so that the tubes are not fitted with lamellas in the corners.
Corner 90

Corner 135

Rounded Lines

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

19

4.1.3.00 FLOOR CONVECTORS

Con.
Box

COOLING AND HEATING FLOOR CONVECTOR TKH

Cooling and Heating Floor Fan Convectors TKH

4.1.4.00 FLOOR CONVECTORS

Application:
Cooling floor fan convectors are designed for
secondary cooling, during the cooling season, in
rooms where cooling is required close to the heat
source (e.g., solar radiation through windows) to
prevent room temperature raising. They are
suitable for all rooms with large hot envelope
surfaces (large windows, glazing, etc.). They are
applied in buildings in which, due to the
construction characteristics, ceiling cooling is
not feasible. During the heating season, the
convectors can be applied for room heating.
TKH (Basic Design) Components:
1. Heat exchanger
2. Tangential fan (with IP 44 protection)
3. Electric connection socket
4. Longitudinal tread-on grille
5. Condensate drip tray
6. Housing

Special grille designs can be installed or supplied


on request.
Operation:
Cooling floor fan convectors apply forced
convection, i.e. the volume air flow rate is achieved
by a tangential fan. The floor convector draws in
warm air from the areas around windows or hot
walls, , cools it in the heat exchanger, and feeds it
back into the room. In this way, heating of room air
volume due to surface heating is reduced. In the
cooling process, a part of moisture is extracted
from the air; this dehumidification also contributes
to thermal comfort.
In the heating mode, the process is exactly
opposite. A floor convector draws in cold air from
the area behind the window. Air is heated in the
convector and fed back into the room.
Types:
Two different types are available. The TKH-2 model
is fitted with a double-row heat exchanger, and the
TKH-3 model, with a three-row heat exchanger.
Control Accessories:
Water side controls and special design grilles are
installed or fitted on special orders. Other
accessories are equal to the ones for the TKV type.

Dimensions:
Type
TKH-2
TKH-3

20

L of housing (mm)
1600
1600

L of heat exchanger (mm)


1250
1250

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

Width (mm)
300
400

Height (mm)
150
150

COOLING AND HEATING FLOOR CONVECTOR TKH

Types and dimensions


Double- Row Forced Convection Floor Convector TKH-2
1600

150

1250

170

80

15

40

128

300

4.1.4.00 FLOOR CONVECTORS

Con.
Box

Three- Row Forced Convection Floor Convector TKH-3


1600

150

1250

170

68.5 18

45.5

215

400

Con.
Box

The above figures are valid for the convectors with the connection on the right side.

Connection diagram:
Connection diagrams are the same as those for the TKV (see page 18).

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

21

COOLING AND HEATING FLOOR CONVECTOR TKH TECHNICAL DATA

Forced Convection Floor Convector Thermal Capacity


Convector length: 1600 mm
Heat exchanger lamelled section length: 1250 mm
Air temperature: 20C.

4.1.4.02 FLOOR CONVECTORS

Two- Row floor convector TKH-2 with a longitudinal fixed grille: see TKV-2 specifications (page 13 and 15)
Three- Row floor convector TKH-3 with a longitudinal fixed grille: see TKV-3 specifications (page 14 and 17)
Cooling and pressure characteristics for TKH-2 and TKH-3:
Measurements carried out in accordance with the EUROVENT 6/3 norm.
KH - 2
Ti-Tv = 12-7C
Water-flow 103 kg/h
Fan speed
min
med
max

Ti-Tv
7/12C
7/12C
7/12C

Q Total cooling (W)


347
427
576

QL Cooling latent (W)


155
188
244

QS hladilna senzibilna (W) Air-humidity


192
60%
239
60%
332
60%

Room temperature (C)


27
27
27

Flow
250kg/h
250kg/h
250kg/h

Q Total cooling (W)


456
588
863

QL Cooling latent (W)


208
252
330

QS Cooling sensible
248
336
533

Air-humidity
60%
60%
60%

Room temperature (C)


27
27
27

Ti-Tv
7/12C
7/12C
7/12C

Q Total cooling (W)


507
595
776

QL Cooling latent (W)


228
249
270

QS Cooling sensible
279
346
506

Air-humidity
60%
60%
60%

Room temperature (C)


27
27
27

Flow
250kg/h
250kg/h
250kg/h

Q Total cooling (W)


497
645
965

QL Cooling latent (W)


190
240
348

QS Cooling sensible
307
405
617

Air-humidity
60%
60%
60%

Room temperature (C)


27
27
27

Water-flow 250 kg/h


Fan speed
min
med
max

TKH - 3
Ti-Tv = 12-7C
Water-flow 135 kg/h
Fan speed
min
med
max

Water-flow 250 kg/h


Fan speed
min
med
max

Water pressure drop in the convector dp (kPa):


see TKV-2 specifications (also applying to TKH-2) and TKV-3 specifications (also applying to TKH-3) on page 18

Noise Level:
Velocity
MIN
MED
MAX

22

Sound pressure Lpa (dB)


26,6
34,6
49,4

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

Noise Level Measurement:


The measurements were carried out in an anechoic chamber, 109 m3 in
volume, with reflecting floor.The anechoic chamber is constructed in
conformance with the ISO 3745 standard.
Sound pressure was measured with the microphone positioned at a distance
1 m directly above the floor convector.

ACCESSORIES
CODE

CONTROL ACCESSORIES
Water side control (control of the warm water flow rate into the convector)

01

Thermostat valve R1/2, straight, without a thermostat head

02

Thermostat valve R1/2, angular, without a thermostat head

03

Shut-off cock R1/2, straight

04

Shut-off cock R1/2, angular

05

Thermostat head with a remote surface-mounted sensor (up to 15 m). It serves to open and close the thermostat valve without a thermostat head.

07

Room thermostat, surface-mounted. Setting range +10 C to +30 C.

08

Continuous fan speed control switch.

078

Room thermostat for surface mounting with continious fan speed setting switch, ON/OFF switch and HEATING/COOLING switch

09

Room thermostat for surface mounting with a three-stage speed setting switch (MIN-MED-MAX), ON/OFF switch and HEATING/COOLING switch.

CODE
010

CORNER DESIGNS
Floor convector corner design with housing and grille, without heat exchanger

CODE
011

4.1.5.00 FLOOR CONVECTORS

Air side control (fan operation control)

Standard tread-on grille design:


Longitudinal fixed grille - profile

TREAD-ON GRILLE
Anodised:
Standard:

D - anodised in the natural aluminium colour (C0)


(included in the basic design price)

On purchasers request: A- golden (C3), B-black (C35), C- brass colour (C4)


012

Longitudinal fixed grille - profile

Anodised:
Standard:

D - anodised in the natural aluminium colour (C0)

On purchasers request: A- golden (C3), B-black (C35), C- brass colour (C4)


013

Longitudinal fixed grille - profile

Anodised:
A- golden (C3), B-black (C35), C- brass colour (C4),
D- natural aluminium colour (C0)

014

Rolo-up grille - profile

Anodised:
A- golden (C3), B-black (C35), C- brass colour (C4),
D- natural aluminium colour (C0)

Wooden roll-up grille - profile

Wood type:
1 - oak, 2 - ash, 3 - walnut, 4 - mahogany

015

Rolo-up grille - profile

Anodised:
A- golden (C3), B-black (C35), C- brass colour (C4),
D- natural aluminium colour (C0)

016

Rolo-up grille - profile

014W

CODE

HOUSING

017

Housing thermal insulation

018

Protection cover (protection of the convector against soiling or damaging during installation and up to its commissioning)

019

Convector level adjusting screws

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

23

4.1.5.00 FLOOR CONVECTORS

ACCESSORIES - CONTROLS

Valves and Shut-off Cocks


Valves 01, 02, 03 and 04 are suitable for the
installation onto steel tubes. On purchasers
request, valves suitable for the installation on
copper tubes are available. Such a request shall
be specifically indicated in the order.

01 Thermostat valve R1/2, straight,


without a thermostat head

02 Thermostat valve R1/2, angular, without a


thermostat head

03 Shut-off cock R1/2, straight

04 Shut-off cock Rl/2, angular

05 Thermostat head with a remote surface mounted


sensor (up to 15 m), standard 2 m

07 Room thermostat - surface mounted

Appropriate Control Accessories


for natural convection floor convectors TK:
accessories 01 to 05.
for forced convection floor convectors TKV:
accessories 01 to 05, 07, 08, 09.
for cooling and heating floor fan convectors
TKH: accessories 01 to 05, 07, 08, 09

078 Room thermostat for surface mounting with


continious fan speed setting switch, ON/OFF
switch and HEATING/COOLING switch.

09 Room thermostat for surface mounting with a


three-stage speed setting switch (MIN-MEDMAX), ON/OFF switch and
HEATING/COOLING switch (designation 09).

08 Continuous fan speed setting switch

24

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

ORDERING KEY

Natural Convection Floor Convector


Ordering Key:

TK - XX1 / 01, 02, 03, 04, 05 / 010, 011D, ...016D, 017, 018, 019
Code 019: convector level adjusting screws
Code 018: protection cover

4.1.6.00 FLOOR CONVECTORS

Code 017: housing thermal insulation


Codes 011 to 016: Floor grille designs in
specified colour or wood type (see page 23)

Code 010: corner design


Codes 01 to 05: control accessories
1 Single-row convector
2 Double-row
3 Three-row
Size (01 to 15)
TK Natural Convection Floor Convector
Forced Convection Floor Convector
Ordering Key:

TKV - 1 / 01, 02, 03 ... / 010, 011D, ...016D, 017, 018, 019
Code 019: convector level adjusting screws
Code 018: protection cover
Code 017: housing thermal insulation
Codes 011 to 016: Floor grille designs in
specified colour or wood type (see page 23)

Code 010: corner design


Codes 01 to 09: control accessories
1 Single-row convector
2 Double-row
3 Three-row
TKV Forced Convection Floor Convector
Mandatory accessories:
The mandatory accessories of a forced convection
floor convector (TKV), to be ordered separately,
consist of either a continuous fan speed setting
switch (designation 08) or a room thermostat for
surface mounting with a three-step speed setting
switch (MIN-MED-MAX), ON/OFF switch and
HEATING/COOLING switch, (designation 09).
Packing:
Each convector is individually packed.

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

25

ORDERING KEY

Cooling and Heating Floor Convector TKH


Ordering Key:

TKH - 2 / 01, 02, 03 ... /011D, ...016D, 017, 018, 019


Code 019: convector level adjusting screws
Code 018: protection cover

4.1.6.00 FLOOR CONVECTORS

Code 017: housing thermal insulation


Codes 011 to 016: Floor grille designs in
specified colour or wood type (see page 23)

Codes 01 to 08, 09: control accessories


2 Double-row convector
3 Three-row

TKH Cooling and Heating Floor Convector


Mandatory accessories:
The mandatory accessories of a forced convection
floor convector for cooling and heating (TKH), to
be ordered separately, consist of either a
continuous fan speed setting switch (designation
08) or a room thermostat for surface mounting
with a three-step speed setting switch (MIN-MEDMAX), ON/OFF switch and HEATING/COOLING
switch, (designation 09).
Packing:
Each convector is individually packed.

26

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

Instructions for Proper Installation of


Floor Convectors
When installing in concrete, make sure to insert
spacers, which serve to prevent housing
deformations.
Protect internal parts against soiling with concrete
or other dirt, by means of a cover (available under
product code 018), inserted under spacers. Remove
the cover only when the convector is ready for
operation. Likewise, handle the grille with care,
protecting it against soiling (with concrete, lime,
paints,...) and damaging (scratches, corrosion,...).

Dimensions:
Type

single-row

200

192

double-row

300

292

three-row

400

392

Levelling:

Levelling bolt

Instructions for Startup and Operation:


1. Make sure the convector internals are clean
and dry.
2. De-aerate the connected heat exchanger and
inspect the piping connections for any leakage.
3. Connection to electric mains shall be carried
out by a qualified person.
4. Check the operation of fans at all speeds.
5. In case of a convector controlled by a room
thermostat, set the desired temperature.
6. The grille is dimensioned for normal
loading,.i.e. human weight; if higher loads are
anticipated, the convector shall be fitted with
an additional "bridge".
When connecting the piping, make sure not to
damage soldered joints on the water heat
exchanger connections.
When connecting floor convectors in permanent
installation, a device to separate all phases from
the mains shall be provided, with the open contact
clearance of 3 mm.
Any intervention beyond the standard connection
is considered an intervention into the device and
shall only be attempted with prior approval by the
manufacturer.
Caution:
Do not install the floor convectors in the floor of
wet environment, for example, of bathrooms,
toilets, swimming pool area or in wet basements.
Maintenance:
Clean the grille by means of a damp cloth.
Periodically clean the internals of the floor
convector with a vacuum cleaner.
In case of water ingress into the floor fan
convector, make sure to disconnect electric power
supply.
Levelling:
In a case of uneven surfaces at the place of
installation, we recommend the application of
levelling bolts (accessory 019), which allow the
convector to be adjusted in height by up to 15
mm.

The right for technical changes reserved.


TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

27

4.1.7.00 FLOOR CONVECTORS

FLOOR CONVECTORS INSTALLATION

The right for technical changes reserved.

28

TECHNICAL CATALOGUE IMP Klima d.o.o., Air conditioning systems production

Production: IMP Klima; Design: D. T. M.; Layout: Epromak; Print: Tiskarna Ljubljana, d.d.; March 2004

42

200

180

129

300

40

150

atmosphere

120

150

for people
40

We provide

a pleasant

120

180

IMP KLIMA
Air conditioning systems production

40

Fax numbers
+386 5 374 30 82
Foreign sales department:
+386 5 374 71 88
Marketing:
+386 5 374 30 83

216

Telephone numbers
+386 5 374 30 00
Foreign sales department:
+386 5 374 30 04, 374 30 19, 374 30 21
Marketing:
+386 5 374 30 23

400

Godovi~ 150
5275 Godovi~
SLOVENIA

180

E-mail
impklima@imp-klima.si
Internet
http://www.imp-klima.si

IMP Klima for pleasant and healthy air-conditioning