You are on page 1of 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

Features:

ST Inverse Separate curve selection for phase

4 Element (3 Phase + EF) over current IDMT

and EF.
Design using DSP technology.

with instant trip.


Back - lit LCD display for settings.

Latching of fault current up to last 5 faults with

Display of Load current in terms of primary &


secondary.

time stamping.
Disturbance Recorder. Actual waveform of

Over current, Earth Fault, Derived EF (3Io),

current along with logical and physical status

Phase

are captured and saved in the built-in memory,

Sequence, Broken Conductor, Thermal

with date time stamping for analyzing fault

Overload,

condition & fault location.

Cold

Load

Blocking

Pickup,

Under
and

Negative

Current

Breaker

and

Fail

Inrush

Protection

functions.
Selection of Curve: Eleven selectable curves
IEC S Inverse 1 / IEC S Inverse 2 / IEC V
Inverse / IEC E Inverse / IEC LT Inverse /

Password protection for setting.


Site selectable CT secondary
Relay can be made either IDMT or Define time
Programmable

operating

time

in

instantaneous element

Definite Time / IEEE M Inverse / IEEE V

In Build Trip Circuit Supervision Function

Inverse / IEEE E Inverse / IEEE Inverse / IEEE

7 nos of Programmable output Trip Duty


contact.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 1 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

One

dedicated

changeover

contact

for

numerical relay at affordable cost. Following is


summery

Protection/ Relay Healthy.


4 nos of Programmable optically isolated

AM-810-01-04-xx-xx-xx-xx.

of

different

protection

functions

provided by relay.

status input.
4 nos of Programmable dual colour LEDs
USB (at front) and RS 485 (at rear side)
Communication Port for remote SCADA
(only

for

ADR241A i.e.

ANSI

IEC

Protection Functions

50

I >>

Instantaneous Over current


Protection (OC-Inst.)

50N

3I>>

Instantaneous Earth Fault


Protection (EF-Inst.) -Derived
EF

IE>>

Instantaneous Earth Fault


Protection (EF-Inst.) Measured EF

communicable

Relay).

General:
The ADR241A is member of Ashida Numerical
Relay family (Aditya Series) design to meet
demand of low and medium switchgear control.

50,51
50N,
51N

I>t, Ip

3Io>t, IEP Time Over current Protection


(EF-IDMT) -Derived EF
IE>t, IEP

The ADR241A is a 3 OC and 1 EF relay with


Instantaneous high set and programmable output
to simplify feeder protection wiring. The ADR241A
continuously monitors all phases and earth
current, through CT connections. The high-speed

CLP

A/D

converter.

The

micro-controller

37

I<

Undercurrent detection (low


load) function

46

I2>, I2>>

Negative Sequence Over


current function

49

Thermal Overload protection

performs powerful Numerical Algorithms to find


out RMS of current signal, and then this value is

function
50BF

use for protection and metering function. All

LCD display for metering. The Relay is having


main three functions 1) Protection 2) SelfSupervision 3) Measurement
The Relay can be supplied with different model. It
can be either Definite Time or IDMT.

CB Failure detection
protection functions

measurement is tuned to fundamental frequency.


Each input current is also displayed on 16 x 2

Time Over current Protection


(EF-IDMT) - Measured EF
Cold load pickup

micro-controller samples this current through a


16-bit

Time Over current Protection


(Phase) (OC-IDMT.)

1.1

Over current protection:

The relay is designed for Overcurrent protection


function with two independent stages. Where
Stage 1 can be programmed as IDMT or Definite
Time (DT). All major international IDMT curves
are available. Stage 2 can be programmed as
Instantaneous or Definite Time (DT). Range for

1.

Protection Functions:

stage 1 is 2% to 250% in step of 1% and stage 2

The ADR241A give maximum benefit/cost ratio.


The

ADR241A

give

all

the

advantage

is 50% to 3000% in step of 10%.

of

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 2 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

1.2

AM-810-01-04-xx-xx-xx-xx.

on IEC and IEEE standards. The inverse time

Earth Fault Protection:

The relay is designed for Earth Fault protection

delay

is

calculated

function with two independent stages. Stage 1

mathematical formula:

with

the

following

can be programmed as IDMT or Definite Time


(DT). All major international IDMT curves are

t = T*

available. Stage 2 can be programmed as

Instantaneous or Definite Time (DT). Range for

Is

+L

-1

stage 1 is 2% to 100% in step of 1% and stage 2


is 50% to 1200% in step of 10%.
Curve

1.3

C1

Derived EF Protection

The relay is internally calculated the earth fault

C2

current through software from phase current.

C3

There are two independent stages of derived

C4

earth fault (3Io) function. Stage 1 can be


programmed as IDMT or Definite Time (DT). All

C5
C6

major international IDMT curves are available.


Stage 2 can be programmed as Instantaneous or
Definite Time (DT). Range foe stage 1 is 2% to

C7
C8

100% in step of 1% and stage 2 is 50% to 1200%


in step of 10%.

1.4

Negative Sequence OC Protection

The relay is designed with two independent

Description
IEC Standard
Inverse 1
IEC Standard
Inverse 2
IEC Very
Inverse
IEC Extremely
Inverse
IEC Long
Time Inverse
Definite Time
IEEE
Moderately
Inverse
IEEE Very
Inverse

0.14

0.02

0.06

0.02

13.5

80

120

0.0515

0.02

0.114

19.61

0.491

C9

IEEE
Extremely
Inverse

28.2

C10

IEEE Inverse

5.95

C11

IEEE Short
Time Inverse

0.0239

0.02

0.121
7
0.18
0.016
9

stages for Negative sequence O/C function.


Stage 1 can be programmed as IDMT or Definite
Time (DT). All major international IDMT curves
are available. Stage 2 can be programmed as
Instantaneous or Definite Time (DT). Range for
stage 1 is 2% to 250% in step of 1% and stage 2
is 50% to 3000 in step of 10%.
The stages of over current, earth fault and
negative

sequence

O/C

function

are

programmable as per IDMT characteristic based

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 3 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

1.5

AM-810-01-04-xx-xx-xx-xx.

Timer Hold Facility / Reset


Characteristics

For stages of phase over current, earth fault


(derived and measured) and negative sequence
over current protection is provided with a timer
hold facility "tReset". It can be programmed as a
definite time.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 4 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

A possible situation arises where the reset timer

t=

AM-810-01-04-xx-xx-xx-xx.

x ln ((K- A)/(K- Th. Trip))

may be used to reduce the fault clearance time


where intermittent faults occur.

THERM AL OVERLOAD
1000.0

For example, a cable with plastic insulation


application, it is possible that the fault energy
melts the cable insulation, which then reseals

100.0

after clearance, thereby eliminating the cause for


the fault. This process repeats itself to give a
succession of fault current pulses, each of
increasing

duration

with

reducing

S
D
N
O
C
ES
IN
E
M
IT

intervals

between the pulses, until the fault becomes


permanent.

10.0
A
B
C
D
E

1.0
1.0

10.0

The range of DT time setting is 0 100 sec in


steps of 0.10 sec.
0.1

M ULTIPLE OF THERMAL THRESHOLD SETTING


Te = 10, K = 1.05
A : THERMAL STATE = 0% ,
B : THERMAL STATE = 30% ,
C : THERMAL STATE = 50% ,
D : THERM AL STATE = 70%,
E : THERMAL STATE = 90%

1.7 Under Current Protection


The relay includes undercurrent element that
can be used to prevent damage of the power
system equipment under loss of load. The
undercurrent protection function is available
only if the auxiliary contact of the CB status is
connected to the relay i.e. when CBNO contact
1.6

Thermal Overload Protection

The thermal withstand capability of the power


system equipment is affected by overheating prior
to a fault. The temperature should not exceed the
thermal withstands capability of power system
equipment. The RMS currents are measured and
analyzed to monitor the thermal state. In case of
thermal overload function the calculation of the
trip time is given by:

of CB is high.

1.8

Cold Load Pickup

Whenever a circuit breaker is turn ON relay


sense through CB auxiliary contact (CBNO) and
start internal timer known as CL timer. During this
time it takes separate set of setting, and inhibits
all other protection function for a set duration, so
that relay will not generate false trip on inrush
current.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 5 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

When the set CL time has elapsed, all of the

Normally after tripping current should be come

relevant settings revert back to their original

Zero within 100 200ms time depend upon type

values or become unblocked

of fault and breaker mechanism. After Fault Relay


start one internal timer (settable from 0.0s to 1.0

1.9

s) If fault is not cleared during this time then relay

Broken Conductor detection

The ADR241A relay incorporated a protection

declare as Breaker fail (LBB function)

element, which measures the ratio of negative to


positive phase sequence current (I2/I1). This
function is used to detect broken conductor
condition. It is based on logic of ratio of I2/I1. In

2.

Supervision Function:

2.1

Self-supervision:

normal condition, the ratio should be very low. In

The continuously keeping track on its internal

faulty condition the I2 become high while I1

hardware and the movement it detect any failure

reduces. Two stages of I2/I1 settings are

of any component, it give message on LCD

available, broken conductor alarm and broken

display, This feature is very useful to give pre

conductor trip signal. If the ratio of I2/I1 is

information to avoid any mall - operation. In such

become more than set limit relay CPU start

situation it uses some default setting and remains

internal timer (I2/I1 Time Delay). If ratio is remain

in protection mode.

high for more than set delay, relay declare as


broken conductor Trip or Alarm as per the

2.2

Trip circuit Supervision & Status:-

associated settings.
The digital opto-coupler status input assigned to
CB Status contact (CBNO & CBNC) can be used

1.10 Inrush Blocking


The inrush blocking function is considered during
transformer

energizing
nd

presence of 2

condition

based

on

to continuously monitor continuity of trip-circuit.


The general scheme is as shown in fig.
B

TCCO

harmonic. During this condition

1
6
2

over current must be blocked .hence the inrush


block function can be used to block the over
current, earth fault and negative sequence over
current stages. In general, a setting of 15% to
nd

20% for the Inrush 2

harmonic ratio can be

CB

To Relay

B1

6
2

To Relay

CB

Fig. Trip Circuit

applied.
The blocking is applicable until fundamental
current value is less than I>lift 2H setting.

Relay monitor Trip coil continuity through CB NO


during close condition and through CB NC during
Trip condition. If any discontinuity observed it

1.11 Breaker Fail Function (BF or LBB)

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 6 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

generate Alarm signal after set time delay

view via key-board.

(settable from 0.0 to 1.0 sec)

electrically erasable read only memory and

All settings are save in

remain.
3.

Measurement Function:

In normal condition this display shows all settings.

Relay Talk - V2 (RT) Software:

Via keyboard the display can be program to show

The general communication software is provided

the actual current flowing through the relay.

If

to communicate with relay, known as RT. By

current excesses set value the relay gives trip

using this software data such as event log,

command. The type of fault is displayed on LCD

disturbance records etc can be down loaded for

display.

During the fault condition the relay

measure the fault current and store in non


volatile memory. The fault current can be read

further analysis. The disturbance record data


can be saved in standard COMTRADE Format
which is understandable by numbers of relay
testing units for play back.

via keyboard on LCD display Last 5 fault


values along with tripping counter can be
Following are some of software clips
In the software you can arrange setting in different files and maintain as per feeder or bay level
The setting file can be done offline

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 7 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

All LEDs and Input / Output assignment can be done through IO Mask
Any of the Logic or physical signal can be assigned to any of the output or LED. The relay is provide with
default assignment which can be overwrite as per user requirement. The IO Mask can be save relay wise
and can be finalised offline.

Relay maintain various time stamped event which can be down load and save in file for further analysis

Similarly Disturbance record latched by relay can be download and save in RT

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 8 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

Similarly Fault data can be maintain

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM=810_01
Issue: 01 18.02.2015
Page 9 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

Ordering Information

The relay is available with nos. of different option. The option is specified by model no. It is user responsibility
to specify correct model no. while ordering.
While Ordering Specify the following Information for ADR241A Relay

Ordering information:
A

M -

E xa m p l e
A D R 2 4 1 A - A M- 8 1 0 - 0 1 - 0 4 - 2 8 - 0 3 - 0 0 - 0 2

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM-810_01
Issue: 01 18.02.2015
Page 10 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

Technical Specifications:
General specifications
Sr. No.

Specification

Particulars

I.

Current Input

: Suitable for 1 Amp / 5 Amp site selectable.

II.

Aux. Supply

: 24 230 V AC/DC ( 20%).

III.

VA burden on CTs

: Less than 0.2 VA.

IV.

VA burden on Aux.

: Less than 10 Watts

V.

Pick up

: Within 1.1 times of set value

VI.

Reset Value

: 95% to 90% of pick up.

VII.

Operating Time

: 10 selectable IDMT curve C1 to C5 and C7 to C11 define time C6

VIII.

Output Contact

: Instantaneous Time < 55ms on 2 times current of setting.


: 7 NO Trip duty contact for Alarm and Trip, 1 C/O for Protection / Relay
Healthy
IX.

Contact Rating

: Continuous: 5A
: Make & carry for 0.5 sec : 30A
: Make carry for 3 sec : 15A

X.

Opto isolated input

: 4 Nos. Of user programmable Status input


Rated voltage : 24 - 230V AC/DC

XI.

Continuous carrying
capacity

: 2 x of rated for CT.

XII.

Thermal With stand for CT

: 40 x of rated CT for 3.0 sec.

XIII.

Operating temperature range

: -10 C to +65 C

XIV.

Relative Humidity

: Humidity (RH) 95% maximum

XV.

Storage temperature range

: -20 C to +80 C.

Relay Setting
GENERAL SETTING
Sr. No

Parameter

Setting / Ranges

1.

Password

0000 9999 in steps of 1

2.

New Password

0000 9999 in steps of 1

3.

Unit ID

001 250 in steps of 1

4.

Com Port

USB/ RS485

5.

Set Parity

None/ Even/ Odd

6.

Set Baud Rate

9600 57600

7.

Frequency

50/ 60 Hz in steps of 10

8.

CT Secondary

1A/ 5A

9.

CT Primary

10 5000 in steps of 10

10.

Trip Ckt Supervision

Enable/ Disable

11.

Tsup Delay

00.0 1.00 Sec in steps of 0.1

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM-810_01
Issue: 01 18.02.2015
Page 11 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

12.

Breaker Fail

Byp/ Int/ Ext

13.

BF Delay

00.0 1.00 Sec in steps of 0.1

14.

I_BF

5% - 100% in steps of 1%

15.

BF Reset

CB Open/ CB Open + I<

AM-810-01-04-xx-xx-xx-xx.

OVER CURRENT SETTING


Sr. No

Parameter

Setting / Ranges

1.

Ip>

Enable/ Disable

2.

Ip>

2% - 250% in steps of 1%

3.

TMS

0.025 1.200 in steps of 0.005

4.

Curve

IEC S Inverse 1 / IEC S Inverse 2 / IEC V Inverse / IEC E Inverse /


IEC LT Inverse / DT / IEEE M Inverse / IEEE V Inverse / IEEE E
Inverse / IEEE Inverse / IEEE ST Inverse

5.

DT Delay

0.00 100.0 Sec in steps of 0.10 Sec

6.

tRESET

DT

7.

tRESET Delay

0.00 100 Sec in steps of 0.10 Sec

nd

8.

9.

Ip>>

Enable/ Disable

10.

Ip>>

50% - 3000% in steps of 10%

11.

Delay

00.0 100 Sec in steps of 0.10 Sec

12.

nd

Hrm Restrain

Hrm Restrain

Enable/ Disable

Enable/ Disable

EARTH FAULT SETTING


Sr. No

Parameter

Setting / Ranges

1.

Ie>

Enable/ Disable

2.

Ie>

2% - 100% in steps of 1%

3.

TMS

0.025 1.200 in steps of 0.005

4.

Curve

IEC S Inverse 1 / IEC S Inverse 2 / IEC V Inverse / IEC E Inverse /


IEC LT Inverse / DT / IEEE M Inverse / IEEE V Inverse / IEEE E
Inverse / IEEE Inverse / IEEE ST Inverse

5.

DT Delay

0.00 100.0 Sec in steps of 0.10 Sec

6.

tRESET

DT

7.

tRESET Delay

0.00 100 Sec in steps of 0.10 Sec

nd

8.

9.

Ie>>

Enable/ Disable

10.

Ie>>

50% - 1200% in steps of 10%

11.

Delay

0.00 100.0 Sec in steps of 0.10 Sec

12.

nd

Hrm Restrain

Hrm restrain

Enable/ Disable

Enable/ Disable

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM-810_01
Issue: 01 18.02.2015
Page 12 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

DERIVED EARTH FAULT (3IO) SETTING


Sr. No

Parameter

Setting / Ranges

1.

3Io>

Enable/ Disable

2.

3Io>

2% - 100% in steps of 1%

3.

TMS

0.025 1.200 in steps of 0.005

4.

Curve

IEC S Inverse 1 / IEC S Inverse 2 / IEC V Inverse / IEC E Inverse /


IEC LT Inverse / DT / IEEE M Inverse / IEEE V Inverse / IEEE E
Inverse / IEEE Inverse / IEEE ST Inverse

5.

DT Delay

0.00 100.0 Sec in steps of 0.10 Sec

6.

tRESET

DT

7.

tRESET Delay

0.00 100 Sec in steps of 0.10 Sec

nd

8.

9.

3Io>>

Enable/ Disable

10.

3Io>>

50% - 1200% in steps of 10%

11.

Delay

0.00 100.0 Sec in steps of 0.10 Sec

12.

nd

Hrm Restrain

Hrm restrain

Enable/ Disable

Enable/ Disable

COLD LOAD PICKUP SETTING


Sr. No

Parameter

Setting / Ranges

1.

Cold load Pickup

Enable/ disable

2.

CL Timer

0.00 100.0 Sec in steps of 0.10 Sec

3.

CLIp>

Enable/ disable

4.

CLIp>

2% - 250% in steps of 1%

5.

TMS

0.025 1.200 in steps of 0.005

6.

Curve

IEC S Inverse 1 / IEC S Inverse 2 / IEC V Inverse / IEC E Inverse /


IEC LT Inverse / DT / IEEE M Inverse / IEEE V Inverse / IEEE E
Inverse / IEEE Inverse / IEEE ST Inverse

7.

DT Delay

0.00 100.0 Sec in steps of 0.10 Sec

8.

CLIp>>

Enable/ Disable

9.

CLIp>>

50% - 3000% in steps of 10%

10.

Delay

00.0 100 Sec in steps of 0.10 Sec

11.

CLIe>

Enable/ Disable

12.

CLIe>

2% - 100% in steps of 1%

13.

TMS

0.025 1.200 in steps of 0.005

14.

Curve

IEC S Inverse 1 / IEC S Inverse 2 / IEC V Inverse / IEC E Inverse /


IEC LT Inverse / DT / IEEE M Inverse / IEEE V Inverse / IEEE E
Inverse / IEEE Inverse / IEEE ST Inverse

15.

DT Delay

0.00 100.0 Sec in steps of 0.10 Sec

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM-810_01
Issue: 01 18.02.2015
Page 13 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

AM-810-01-04-xx-xx-xx-xx.

16.

CLIe>>

Enable/ Disable

17.

CLIe>>

50% - 1200% in steps of 10%

18.

Delay

0.00 100.0 Sec in steps of 0.10 Sec

19.

CL3Io>

Enable/ Disable

20.

CL3Io>

2% - 100% in steps of 1%

21.

TMS

0.025 1.200 in steps of 0.005

22.

Curve

IEC S Inverse 1 / IEC S Inverse 2 / IEC V Inverse / IEC E Inverse /


IEC LT Inverse / DT / IEEE M Inverse / IEEE V Inverse / IEEE E
Inverse / IEEE Inverse / IEEE ST Inverse

23.

DT Delay

0.00 100.0 Sec in steps of 0.10 Sec

24.

CL3Io>>

Enable/ Disable

25.

CL3Io>>

50% - 1200% in steps of 10%

26.

Delay

0.00 100.0 Sec in steps of 0.10 Sec

NEGATIVE SEQUENCE OC SETTING


Sr. No

Parameter

Setting / Ranges

1.

I2>

Enable/ Disable

2.

I2>

2% - 250% in steps of 1%

3.

TMS

0.025 1.200 in steps of 0.005

4.

Curve

IEC S Inverse 1 / IEC S Inverse 2 / IEC V Inverse / IEC E Inverse /


IEC LT Inverse / DT / IEEE M Inverse / IEEE V Inverse / IEEE E
Inverse / IEEE Inverse / IEEE ST Inverse

5.

DT Delay

0.00 100.0 Sec in steps of 0.10 Sec

6.

tRESET

DT

7.

tRESET Delay

0.00 100 Sec in steps of 0.10 Sec

nd

8.

9.

I2>>

Enable/ Disable

10.

I2>>

50% - 3000% in steps of 10%

11.

Delay

00.0 100 in steps of 0.10 Sec

12.

nd

Hrm Restrain

Hrm Restrain

Enable/ Disable

Enable/ Disable

BROKEN CONDUCTOR SETTING


Sr. No

Parameter

Setting / Ranges

1.

BC Alarm

Disabled / Enabled

2.

I2/I1 Set-1

20% - 100% in steps of 1%

3.

I2/I1 Time Dly-1

0.00 100.0 Sec in steps of 0.10 Sec

4.

BC Trip

Disabled / Enabled

5.

I2/I1 Set-2

20% - 100% in steps of 1%

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM-810_01
Issue: 01 18.02.2015
Page 14 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

6.

I2/I1 Time Dly-2

AM-810-01-04-xx-xx-xx-xx.

0.00 100.0 Sec in steps of 0.10 Sec

THERMAL OVERLOAD:
Sr. No

Parameter

Setting / Ranges

1.

Thermal Alarm

Enable/ Disabled

2.

Thermal Alarm

50% - 100% in steps of 1%

3.

Thermal Trip

Enable/ Disabled

4.

IFLA

20% - 250% in steps of 1%

5.

Time constant

001 - 200 Min in steps of 1 Min

6.

1 to 1.50 in steps of 0.01

UNDER CURRENT PROTECTION:


Sr. No

Parameter

Setting / Ranges

1.

UI<

Enabled / Disabled

2.

UI<

2% - 100% in steps of 1%

3.

UI< Delay

0.20 100.0 Sec in steps of 0.10 Sec

INRUSH BLOCKING
Sr. No
1.

Parameter
2nd Harmonic
nd

2.

Harm Thresh

3.

I>lift 2H

Settings / Ranges
Enabled / Disabled
5 % - 70% in steps of 1%
200% - 3000% in steps of 1%

DATE AND TIME SETTING


Sr. No

Parameter

Settings / Ranges

1.

SET Hours

00 to 23 Hrs in step 1.

2.

SET Minutes

00 to 59 Mins in step 1.

3.

SET Seconds

00 to 59Sec. in step 1.

4.

SET Date

01 to 31 Days in step of 1.

5.

SET Month

01 to 12 Months in step of 1.

6.

SET Year

00 to 99 Years in step of 1.

I/O CONFIGURATION SETTING


Sr. No

Parameter

Setting / Ranges

1.

Relay

1 = Assign ; 0 = Not Assign

2.

LED G

1 = Assign ; 0 = Not Assign

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM-810_01
Issue: 01 18.02.2015
Page 15 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

3.

LED R

1 = Assign ; 0 = Not Assign

4.

AND Logic

1 = Assign ; 0 = Not Assign

5.

Status

1 = Assign ; 0 = Not Assign

AM-810-01-04-xx-xx-xx-xx.

LATCH I/O
Sr. No

Parameter

Setting / Ranges

1.

Contact HR/SR

1= HR

/ 0 = SR

2.

LED G HR/SR

1= HR

/ 0 = SR

3.

LED R HR/SR

1= HR

/ 0 = SR

ANDEQ TIME
Sr. No

Parameter

Setting / Ranges

1.

ANDEQ A Op Time

0001 3600 Sec in steps of 1Sec.

2.

ANDEQ A Rst Time

0001 3600 Sec in steps of 1Sec.

3.

ANDEQ B Op Time

0001 3600 Sec in steps of 1Sec.

4.

ANDEQ B Rst Time

0001 3600 Sec in steps of 1Sec.

5.

ANDEQ C Op Time

0001 3600 Sec in steps of 1Sec.

6.

ANDEQ C Rst Time

0001 3600 Sec in steps of 1Sec.

7.

ANDEQ D Op Time

0001 3600 Sec in steps of 1Sec.

8.

ANDEQ D Rst Time

0001 3600 Sec in steps of 1Sec.

Drawing References
XVI.

: For Cabinet Type

- MAC01926

: For Back Terminal Connections

- APR06822

: For Electrical Connection Diagram

- APR06823

Conformance to Standards:
Sr. No.
I.

Specification

Particulars

High Voltage Test

: IEC 60255-5.
: At 2.5kV 50Hz between all terminal connected together and Earth for
1 minutes

II.

Impulse Voltage Test

: IEC60255-5.
: Test voltage: 5KV (peak) 1.2 / 50us,
: Energy : 0.5 J,
: Polarity : + ve and Ve
: Nos. of impulses : 3 positive and 3 negative impulse
: Duration between Impulses : 5 sec.

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM-810_01
Issue: 01 18.02.2015
Page 16 / 17

Type: ADR241A

ASHIDA Numerical 3OC + EF Protection Relay

III.

High Frequency test

AM-810-01-04-xx-xx-xx-xx.

: IEC 60255-22-1,
: Frequency : 1MHz Damped Oscillatory
: Longitudinal : 5 KV (peak)
: Duration: sec duration 2 sec.
Between input current Terminal

IV.

Electro static Discharge

: IEC 60255-22-2 Class III and IEC 61000-4-2 class III.


: Contact discharge : 6kV,
: Air discharge: 8KV
: Polarity: both +ve and Ve polarities.

V.

Fast transient
interference/bursts

: IEC 60255-22-4 and IEC 61000-4-4, class III


: Amplitude 2Kv, pulse shape 5/50ns.
: Burst duration = 15ms.
: Repetition rate 300ms;
: Both polarities; Ri = 50; duration 1 min.

VI.

Vibration Test

: IEC 60255-21-1 class 1


: Frequency Range = 10Hz 150Hz ,
2

: Acceleration. = 1gn (9.8 m/s )


: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.
VII.

Shock Test

: IEC 60255-21-2 class 1


2

: Acceleration. = 15gn (15 x 9.8 m/s )


: Half sine pulse width 11ms
Number of shocks per axis 3 per direction.
VIII.

Serge Immunity Test

: IEC 60255-22-5 / BS EN 61000-4-5 : 1995


: Differential Mode = 2kV
: Common Mode = 4kV
: 1.2/50uS , 5 surges of each polarity

IX.

Conducted Emission Test

: BS EN 55011 : 1998
: Frequency 0.15MHz 30MHz

X.

Radiated Emission Test

: BS EN 55011 : 1998
: Frequency 30MHz 1GHz

XI.

Power Frequency
Magnetic Test

: BS EN 61000-4-8 : 1994.

XII.

Conducted Disturbance
induced by Radio
Frequency field

: IEC 60255-22-6 / BS EN 61000-4-6: 1996.

Radiated Electromagnetic
Field Disturbance Test

: IEC 60255-22-3 / BS EN 61000-4-3 : 1995

XIII.

: Freq. 50 Hz, Field 100 A/m for 1 min. 1000 A/m for 3 sec.,
: Freq. 150kHz 80MHz, Amplitude 10 V, Modulation 80% AM @ 1KHz

: Freq. 80 MHz1000 MHz, Amplitude 10V/m, Modulation 80% AM @ 1KHz

Datasheet Change Log for ADR241A_AM-810


Issue No.
01

Date
18.02.2015

Description /Changes
First Prototype specification

Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21,
Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com

Ref.:ADR241A_AM-810_01
Issue: 01 18.02.2015
Page 17 / 17