6MB Station Control System

Description
The unit can be supplied with
five different degrees of expansion. The basic version
6MB5240-0 is designed for
use in a single busbar feeder
with four switching devices. It
provides 8 single commands
with, and 1 single command
without error detection, all bipolar, and 16 single indications.

Siemens LSA 1.1.7 1997

Fig. 1
6MB5240-0, -1, -2 bay control
unit in 1/2 7XP20 housing

LSP1006.eps

Application
The 6MB524 bay control unit
is used for the distributed connection of the switchgear to
the SINAUT LSA substation
control and protection system.
It can be used in conjunction
with the compact 6MB513/514
control master unit or as a
distributed addition to the
6MB551 station control unit or
the 6MB552 compact remote
terminal unit. Because of its
enclosed compact housing it
is suitable for direct mounting
in the door of the low-voltage
top unit of a switchgear.
With the distributed structure
of the substation control and
protection, complicated parallel
cabling to carry the process information to a master station
is no longer required. Even the
interposing relays are eliminated. Because of the integration
of local operation into the
6MB524 bay control unit, the
local operating elements and
the remote/local changeover
switch are also obviated.
The bay control unit acquires
and processes indications and
analog measured values and
output commands. It is used
for distributed connection of indication contacts, command
outputs, current and voltage
transformers, transducers and
numerical protection relays in
medium, high and very highvoltage switchgear with a medium to large volume of commands and indications.
The 6MB524 unit is much
more powerful and has more
functions than the units previously available. It is possible
to operate it without a master
unit. The analog measured values can be acquired with a
class accuracy of 0.5 %.
All inputs and outputs of the
bay control unit connected to
the switchgear are isolated.

LSP1005.eps

6MB524 Bay control unit

Fig. 2
6MB5240-3, -4 bay control
unit in 1/1 7XP20 housing

In addition, a current transformer and two voltage transformers can be connected. As an


option, the unit can be
equipped with a transducer input. The other versions of the
unit have a graded number of
process connections, the largest being for large bays for
very high voltage (see table
on page 4). Depending on the
version, the units can be
supplied with two different
housings: the 6MB5240-0, -1
and -2 units are enclosed in a
compact standard housing
with 1/2 7XP20 format, the
6MB5240-3 and 4 units are
mounted in a standard housing with 1/1 7XP20 format.

The unit has a display and a


keypad on the front side.
This provides a user-friendly interface with which numerous
operator actions can be performed.
See Section Operation for
more details on operating the
unit (from page 3 onward).
On the front panel there is an
LED for each indication input
to show its current state. Via
the 9-way subminiature D socket of the front panel interface
it is possible to connect a testing and diagnostics PC.
Operation is menu-guided.
The operator actions which
are permissible at any point in
time are displayed in a status
line to provide the operator
with effective support.

Siemens AG 1997

6MB Station Control System


6MB524 Bay control unit
Integration into the substation control and protection
system
The 6MB524 bay control unit
is usually used in conjunction
with the compact 6MB513/
6MB514 control master unit
(Fig. 3).
The bay control unit has fibreoptic interfaces for coupling to
a master unit and for connection of two protection units.
This permits implementation
of a standard structure as
shown in Fig. 3.
If greater demands are placed
on the availability of the overall
system, a second control master unit can be used (Fig. 4).
This is also connected with
every bay control unit (Software
version V3 and higher).
The bay control unit can also
be connected to a 6MB551
station control unit or a
6MB552 compact remote terminal unit.
Design and method of
operation
The unit is controlled by a
processor module that has an
MC68360 communications
processor and a separate DSP
56002 digital signal processor.
By direct processing of the
analog measured values by
the A/D converters with a digital signal processor, a high
sampling rate of 1 kHz can be
achieved. In this way, analog
measured values can be
acquired and processed as
instantaneous values.
The unit is connected to the
switchgear via the indication,
transformer and command
module. This module contains
the command relays, the indication hybrid circuits and the
analog measured value inputs.

Operator station

Network control centre


Mass storage
evaluation

6MB513/514 compact control


master unit

6MB524
bay control unit

7S/7U (V3)
protection relay
(VDEW interface)

7S/7U (V3)
protection relay
(VDEW-interface)

Serial
link
Switchyard

Parallel
link

Fig. 3
6MB524 bay control unit in the SINAUT LSA substation control and protection system (standard configuration)

6MB513/514
compact
control master
unit

6MB513/514
compact
control master
unit

Connection of a further bay control or


protection unit
possible

6MB524
bay control unit

6MB524
bay control unit

7S/7U (V3)
protection relay
(VDEW-interface)

Switchyard

Serial link
Parallel link

Fig. 4
6MB524 bay control unit in the SINAUT LSA substation control and protection system (configuration
with duplicated control master unit)

Siemens LSA 1.1.7 1997

Operation
The unit is operated via the
membrane keypad and a
graphic display. The keys are
grouped together in blocks
identified by their colour in order to facilitate operations. All
the keys which are permissible in the current operating
state are also displayed in the
bottom line of the display.
Because local operation is integrated, numerous operator
actions can be performed:
Local operation for work in
the bay
Emergency operation facility if a master unit or serial
interface should fail
Display of process information (e.g. analog measured
values, indication list)
Tests and checks for the
unit
Editing of operational parameters during operation
(e.g. limit values, filtering
times, etc.)
The use of code words ensures that only authorized operators can work with the unit.
These code words can also replace the key switches familiar from the 8TK interlock system. The following authorization levels can be assigned:
Control with interlocks
(switchgear interlocking)
Control without interlocks
(S1 operation)
Unsynchronized control.
These authorization levels can,
but need not, be granted. The
local-remote changeover (S5)
takes place either automatically by selection of the feeder control display (if no code
word for interlocked switching
has been assigned) or by input
of one of the three code
words granting authorization
to switch.
The unit logs all code word inputs and operator actions in
the operation protocol.

Feeder control display

Main menu

Measured value display

Fig. 5
Examples of graphic displays

The switchgear is operated via


the keypad in several stages:
1. Switching over the switching
authority to the required
authorization level by entering
the appropriate code word
2. Selection of the switching
device in the feeder control
diagram via cursor keys. The
associated symbol blinks
3. Selection of the switching direction close or open
4. Confirmation of the switching
event with a separate key.
The command is output.

Siemens LSA 1.1.7 1997

6MB Station Control System


6MB524 Bay control unit
Volume of process data of each unit version
Unit version

Bi-polar single
commands

Single indications

Measuring inputs

Transducer
connections

6MB5240-0

8 + 11)

16

1 x I, 2 x V

/2 7XP20

6MB5240-1

12 + 11)

24

3 x I, 3 x V

/2 7XP20

6MB5240-2

16 + 21)

32

3 x I, 3 x V

/2 7XP20

6MB5240-4

1)

/1 7XP20

24 + 3

Functions
The 6MB524 bay control unit
has the following functions for
bay-related information acquisition and processing:
Indication acquisition
Single or double indications,
bit pattern indications 3 to
32 bit, transformer tap position indications, grouped indication formations. Time resolution max. 1 ms, filtering
times parameterizable for
each indication input, chatter disable possible. The indication inputs can be assigned in any way and can
be evaluated multiply, in
this way an indication required in the system several
times only needs to be routed to the unit once.
Command output
Single or double commands
with command output with
error detection and correction: the transistors for controlling the output relay are
monitored. In the event of a
fault uncontrolled command
output can be prevented.
Commands can be output
both as pulse and continuous commands (any combination possible). Synchro
check is available.
Analog value acquisition
Acquisition of instantaneous
values via a direct transformer connection with a sampling rate of 1 ms, calculation of rms values, calculation of P, Q, cos (power
factor), f, calculation of
phase-to-phase voltages
and neutral voltage from
phase voltages.
Metering
Acquisition of metered values via indication input;
calculation of metered values from analog measured
values.

1) Additional single commands, without error detection and correction


can be used, e.g. as a live contact
or for horn control.

Siemens LSA 1.1.7 1997

48

Online parameterization
Editing of defined parameters during operation via the
keypad directly on the unit.
These parameters are: Limit
values for analog measured
values, threshold values for
analog measured value
transmission, indication filtering times, metered value
freeze intervals, command
output times, monitoring
and delay times, waiting
times in operating sequences, code words.
Synchrocheck
Connection after checking
parameterizable synchronization conditions. The bay control unit can test whether
two different network sections meet the conditions
(voltage, frequency, frequency change, phase angle) for
interconnection.
The synchro-check can be
parameterized in various versions:
With zero sum formation
for the voltages. 4 voltage
inputs are required. Can
be used with the
6MB5240-3 and -4 units.
Without zero sum formation for the voltages. 2
voltage inputs are required. Can be used with all
unit versions.
With rotation direction
monitoring and zero sum
formation. 8 voltage inputs are required. Can be
used only with unit version 6MB5240-3.
The zero sum formation is for
monitoring the measuring inputs and the A/D converter.
This monitoring is recommended. Without this zero sum formation, the safety class attained is only that of the
7VK512 (digital automatic
reclosing).

3 x I, 6 x V

Autonomous operation of
the unit (without control master unit) is possible. The
bay control unit can be started up without a master unit.
In this case the parameters
are loaded directly into the
unit. Reliable operation of
the bay control unit is
therefore guaranteed even
in the event of faults in
communication with the
master unit.
Interlocking function
The bay control unit can perform the tasks of the interlock unit. Testing of the bayspecific interlock conditions
takes place inside the bay
control unit. System interlocking is handled by the substation control and protection master unit. LSATOOLS
is used to configure the interlock conditions.
Function descriptions
For the following user functions detailed descriptions are
available in separate catalog
sheets (see also page 10, list
of Siemens catalogs for the
SINAUT LSA substation control and protection):
Control
Indication
Measuring
Metering
Network synchronization
Operation with dual station
control units
Node functions
Control and monitoring
Process information evaluation.

Housing size

Configuration
By configuration, the functions
for inputs and outputs are defined system-specifically. Configuration is performed with
the LSATOOLS parameterization system.
The parameter set is stored in
the bay control unit and not in
the master unit. In this way
the units can start up and be
operated completely autonomously.
The parameter sets can be loaded into the bay control units
centrally via the control master unit. To do this, the PC
program LSADIAG is used. In
addition, the parameter set
with LSADIAG can also be loaded into the bay control unit directly via the front panel interface. This procedure is useful
if a single bay control has to
be replaced.
When parameters are changed, those bay control units
that are not affected by these
changes remain in operation.

Technical data
Indications

Time resolution
Mean current consumption per indication input

Depends on order number:


24 to 48 V DC, threshold at 16 V
60 to 110 V DC, threshold at 43 V
220 to 250 V DC, threshold at 154 V
1 ms
<1.2 mA

Commands

Contacts per relay


Switching voltage
Make power
Break power
Continuous current

2 NO contacts
max. 250 V AC/DC
max. 1 000 W
max. 50 W
4A

Measuring inputs

Voltage inputs for direct transformer connection

20, 100, 110, 100/3, 110/3 V


(parameterizable)
<0.15 VA at rated voltage
16 2/3, 50, 60 Hz
1 A, 5 A (parameterizable); overload capability:
12 A (cont.), 15 A (15 s), 200 A (1 s)
0.5 % of rated value
<0.005 VA at rated current
-20 to +20 mA rated value,
-24 to +24 mA end value
33.2 0.1 %
0.5 % of rated value
1 Hz

The indications are arranged in


groups of four with a common potential. All indications can be parameterized for use as single or double indications.

Voltage range, switching threshold

Current consumption per voltage path


Rated frequencies
Current input for direct transformer connection
Measuring error at rated conditions
Power consumption per current path
Transformer connection
Load
Measuring error under rated conditions
Limit frequency for input signals
Power supply

Rated auxiliary voltage (-20 to +15 % each)

Meter pulse acquisition

Via indication input, additional fault input for each meter


pulse input is optional. External freeze input for one or more
meter pulse inputs possible.

Minimum pulse duration >10 ms


Max. metering frequency 50 Hz
Acquisition of single and double current
pulses

Display

Semi-graphic LCD display, operating menu freely


configurable with LSATOOLS, display of feeder
control diagrams

14 lines, 21 columns

Keypad

Membrane keypad

29 keys in 6 colours, grouped in


function blocks

LEDs

Status displays
Fault display
Control LED watchdog
Status displays of the six communication channels
Indication displays

8 (yellow)
1 (red)
1 (green)
3 LEDs per channel (green, red, yellow)
1 per indication input (green)

Communication interfaces

Type (on rear of unit)

FO; FSMA connector with


Weidmller modules
Max. 5 (with software V1.0: max. 3 can be
used)
2.4 to 320 Kbaud, can be parameterized
To the master unit:
IEC 870-5, Siemens internal
To the protection units:
IEC 870-5-103 (VDEW protocol)
RS 232, automatic baudrate detection

24 to 48 V DC
60 to 125 V DC
220 to 250 V DC
Power consumption of the unit (typically, i.e. half of
6MB5240-0:
12 W
the command relays have picked up and half of the
6MB5240-1:
14 W
indication inputs have responded)
6MB5240-2:
16 W
6MB5240-3:
33 W
6MB5240-4:
25 W
Increase of the power consumption per running command
0.45 W
Increase of the power consumption per responding indication 0.22 W
Backup time during power failure
for Vaux <60 V at least 10 ms,
for Vaux 60 V 50 ms
Residual ripple of the input voltage
15 % of the rated voltage

Number
Transmission rate
Transmission protocol

Front panel interface with the PC

Siemens LSA 1.1.7 1997

6MB Station Control System


6MB524 Bay control unit
Technical data
(continued)
Mechanical design

1/2 7XP20 (6MB5240-0, -1, -2) housing


1/1 7XP20 (6MB5240-3, -4) housing
Weight of 6MB5240 -0
-1 and -2
-3
-4
Degree of protection

See dimension drawings for dimensions


approx. 6.7 kg
approx. 8.4 kg
approx. 16.1 kg
approx. 12.7 kg
IP 20 (IP 21 with additional protection
against drops of water)
Frontplate IP 51 (relevant f.i. in case of
cubicle mounting)

CE conformity, standards

This product is in conformity with the directives of the


Council of the European Communities on the approximation
of the laws of the Member States relating to the electromagnetic compatibility (EMC CounciI Directive 89/336/EEC).
The unit is designed for use in an industrial environment
acc. to the electro-magnetic compatibility (EMC) standard.

Conformity is proved by tests performed


by Siemens AG in line with article 10 of the
Council directives in accordance with the
generic standards EN 50081-2 and EN 50082-2.

Insulation tests
IEC 255-5,
DIN VDE 0435 part 303

High-voltage test (routine test), except


d.c. voltage supply input
High-voltage test (routine test), only
d.c. voltage supply input
Impulse voltage test (type test), all circuits, class III

2 kV (rms), 50 Hz (transducer input 1 kV/rms,


50 Hz)
2.8 kV DC

High-frequency test with 1 MHz interference


IEC 255-22-1, class III and VDE 0435 part 303, class III
Electrostatic discharge
IEC 255-22-2,class III and IEC 1000-4-2, class III
Radio-frequency electromagnetic field, non-modulated
report IEC 255-22-3 (report), class III
Radio-frequency electromagnetic field, amplitude modulated
ENV 5014/ENV 50204, class III, EN 1000-4-3
Radio frequency electromagnetic field, puls modulated
ENV 5014/ENV 50204, class III,EN 61000-4-3
Fast transients / bursts
IEC 255-22-4 and EN 61000-4-4, class III

2.5 kV (peak), 1 MHz, = 15 s,


400 shots/s, duration 2 s
4 kV/6 kV contact discharge, 8 kV air discharge, both polarities, 150pF, Rl =330
10 V/m, 27 to 500 MHz

EMC-Tests; immunity
(type tests)
Standards: IEC 255-22
(product norm)
EN 50082-2
(generic standard)
DIN VDE 0435 part 303

Conducted disturbances induced by radio-frequency fields,


amplitude modulated ENV 50141, class III
Power frequency magnetic field
EN 61000-4-8, class IV
EMC-Tests; emission
(type tests)
Standard: EN 50081-2
(generic standard)

Conducted interference voltage, auxiliary voltage


CISPR 11, EN 55011, limit value class A and
DIN VDE 0875 part 11, limit value class A
Interference field strength
CISPR 11, EN 55011, limit value class A and
DIN VDE 0875 part 11, limit value class A

Climatic stress test

Permissible ambient temperature

Permissible mechanical stress

Supply
A startup-tested, calibrated
complete unit is supplied.

Siemens LSA 1.1.7 1997

10 V/m, 900 MHz, repetition frequency


200 Hz, duty-cycle 50 %
2 kV, 5/50 ns, 5 kHz, burst length = 15 ms,
repetition rate 300 ms, both polarities,
Rl = 50 , duration 1 min
10 V, 150 kHz to 80 MHz, AM 80 %, 1 kHz,

30 A/m, continuous, 300 A/m for 3 s, 50 Hz


150 kHz to 30 MHz

30 to 1000 MHz

-5 to +55 C

during service

10 to 60 Hz, 0.035 mm amplitude


60 to 150 Hz, 0.5 g acceleration
5 to 8 Hz, 7.5 mm amplitude
8 to 150 Hz, 2 g acceleration

during transport
Connection method (electrical)

10 V/m, 80 to 1000 MHz, AM 80 %, 1 kHz,

during service
(recommended)
during storage
during transport

Permissible humidity

Mechanical test stress


IEC 255-21-1, IEC 68-2

5 kV (peak), 1.2/50 s, 0.5 J,


3 positive and 3 negative shots
at intervals of 5 s

Indication and command contacts via Weidmller


module blocks

-25 to +55 C
-25 to +70 C
yearly average of 75 % relative humidity,
on 30 days per year, up to 95 % relative
humidity, condensation not permissible

Selection and ordering data

Order-No.

6MB5240-0 bay control unit


(Contains one indication, transformer and command module)
Compact bay control unit (control input/output unit)
in 1/2 7XP20 housing for use in medium-voltage switchgear
Volume of process data:
8 single commands (4 with, 4 without common potential) plus one single command without
error detection and correction; 16 single indications, in groups of 4 with common potential;
Number of fibre-optic connections
2
3

6MB5240 0C 0 0

A
B

Auxiliary voltages (power supply)


24 to 48 V DC
60 to 125 V DC
220 to 250 V DC

2
4
5

Auxiliary voltages (indication inputs)


24 to 48 V DC
60 to 125 V DC
220 to 250 V DC

2
4
5

Number of current and voltage inputs for direct transformer connection


1 current input, 2 voltage inputs

Number of transducer inputs


without transducer input
with one transducer input

6MB5240-1 bay control unit


(Contains two indication, transformer and command modules, one with fewer signals)
Compact bay control unit (control input/output unit)
in 1/2 7XP20 housing for use in medium-voltage switchgear
Volume of process data:
12 single commands (4 with, 8 without common potential) plus one single command without
detection and correction 24 single indications, in groups of 4 with common potential
Number of fibre-optic connections
2
3
Auxiliary voltages (power supply)
24 to 48 V DC
60 to 125 V DC
220 to 250 V DC
Auxiliary voltages (indication inputs)
24 to 48 V DC
60 to 125 V DC
220 to 250 V DC
Number of current and voltage inputs for direct transformer connection
3 current input, 3 voltage inputs
Number of transducer inputs
without transducer input
with one transducer input
with two transducer inputs

A
B

6MB5240 1C 0 0

A
B

2
4
5

2
4
5

A
B
C

Siemens LSA 1.1.7 1997

6MB Station Control System


6MB524 Bay control unit

Selection and ordering data (continued)

Order-No.

6MB5240-2 bay control unit


(Contains two indication, transformer and command modules)
Compact bay control unit (control input/output unit)
in 1/2 7XP20 housing for use in high-voltage switchgear
Volume of process data:
16 single commands (4 with, 4 without common potential) plus 2 single commands without
error detection and correction; 32 single indications, in groups of 4 with common potential;
Number of fibre-optic connections
2
3
5

6MB5240 2C 0 0

A
B
D

Auxiliary voltages (power supply)


24 to 48 V DC
60 to 125 V DC
220 to 250 V DC

2
4
5

Auxiliary voltages (indication inputs)


24 to 48 V DC
60 to 125 V DC
220 to 250 V DC

2
4
5

Number of current and voltage inputs for direct transformer connection


3 current input, 3 voltage inputs

Number of transducer inputs


without transducer input
with one transducer input
with two transducer inputs

6MB5240-4 bay control unit


(Contains 3 indication, transformer and command modules)
Compact bay control unit (control input/output unit)
in 1/1 7XP20 housing for use in high-voltage switchgear
Volume of process data:
24 single commands (4 with, 4 without common potential) plus 3 single commands without
error detection and correction, 48 single indications, in groups of 4 with common potential
Number of fibre-optic connections
3
5
Auxiliary voltages (power supply)
24 to 48 V DC
60 to 125 V DC
220 to 250 V DC
Auxiliary voltages (indication inputs)
24 to 48 V DC
60 to 125 V DC
220 to 250 V DC
Number of current and voltage inputs for direct transformer connection
3 current input, 6 voltage inputs
Number of transducer inputs
without transducer input
with two transducer inputs

Siemens LSA 1.1.7 1997

A
B
C

6MB5240 4C 0 0

B
D

2
4
5

2
4
5

A
C

Selection and ordering data (continued)

Order-No.

6MB5240-3 bay control unit


(Contains 5 indication, transformer and command modules)
Compact bay control unit (control input/output unit)
in 1/1 7XP20 housing for use in high-voltage switchgear
Volume of process data:
40 single commands (4 with, 4 without common potential) plus five single commands without
error detection and correction; 80 single indications, in groups of 4 with common potential;
Number of fibre-optic connections
5

6MB5240 3C 0 0

Auxiliary voltages (power supply)


24 to 48 V DC
60 to 125 V DC
220 to 250 V DC
Auxiliary voltages (indication inputs)
24 to 48 V DC
60 to 125 V DC
220 to 250 V DC
Number of current and voltage inputs for direct transformer connection
6 current input, 6 voltage inputs
Number of transducer inputs
without transducer input
with two transducer inputs
with five transducer inputs

2
4
5

2
4
5

A
C
F

Technical Specification
6MB524 bay control unit (input/output unit) for SINAUT LSA
Order-No.: 6MB5240-NAANN-NAAN
1/2 7XP20 flush-mounting housing for 6MB5240-0/ -1/ -2
1/1 7XP20 flush-mounting housing for 6MB5240-3/ -4
Generalities
Input/Output unit for installation in medium and high-voltage
switchgear
Compact unit with all required functions for application in a bay
Integrated operation via large display and keypad
Adaptable to individual requirements
Coupling to the central unit via interference-free fibre-optic
cables
Due to the distributed connection of switchgear to the control
system elimination of costly parallel cabling
All interfaces to the switchgear are interposed.
Features
Compact design
Flexible and user-friendly parameterization by means of
LSATOOLS
Interference-free FO
Integrated operation
High measuring accuracy.

Scope of functions
Flexible quantity-listing from 8 to 40 commands,
16 to 80 indications, time-stamped
Acquisition of instantaneous measured values with a sampling
rate of up to 1 kHz
High measuring accuracy of 0.5% for direct transformer
connection and transducer input
Synchro-check
Integrated measured value processing, f.i. P, Q, power factor
calculation
Switch interlocking
Processing of meter pulse
Stand-alone operation
Convenient diagnosis
On-line parameterization for selected parameters
Integrated relay for direct control of the substation
Emergency control via display and keypad also possible in case
of connection failure to the master unit
Operation authorization by code words
Protection relays directly connectable (up to 4 relays).

Siemens LSA 1.1.7 1997

6MB Station Control System


6MB524 Bay control unit

Index of Siemens catalogs for SINAUT LSA substation control and protection

6MB Station control system

6MB Telecontrol system

User functions

Supporting
PC applications

Switchgear cubicle

10

Siemens LSA 1.1.7 1997

Title of catalog

Expected
publishing
date

Catalog
abbreviations

Order No.

6MB522 Input/output unit


6MB523 Input/output unit
6MB511/6MB512 Substation control master unit
7SW511/7SW512 Relay data concentrator
6MB520/6MB521 Input/output units
6MB513/514 Compact control master unit and
relay data concentrator
6MB524 Bay control unit
6MB525 Mini bay unit

LSA 1.1.1
LSA 1.1.2
LSA 1.1.3

E50001K5701A111A47600
E50001K5701A121A27600
E50001K5701A131A27600

LSA 1.1.4
LSA 1.1.6

E50001K5701A141A17600
E50001K5701A161A17600

LSA 1.1.7
LSA 1.1.8

E50001K5701A171A27600
E50001K5701A181A17600

LSA 1.2.1
LSA 1.2.2
LSA 1.2.3
LSA 1.2.4

E50001K5701A211A27600
E50001K5701A221A17600
E50001K5701A231A17600
E50001K5701A241A17600

planned

LSA 1.2.5

E50001K5701A251A17600

planned

LSA 1.2.6

E50001K5701A261A17600

LSA 1.4.1

E50001K5701A411A17600

LSA 1.4.2

E50001K5701A421A17600

LSA 1.4.3

E50001K5701A431A17600

LSA 1.4.4

E50001K5701A441A17600

LSA 1.4.5

E50001K5701A451A17600

LSA 1.4.6

E50001K5701A461A17600

LSA 1.4.7
LSA 1.4.8

E50001K5701A471A17600
E50001K5701A481A17600

LSA 1.4.9

E50001K5701A491A17600

LSATOOLS

planned

LSA 1.5.1

E50001K5701A511A17600

LSADIAG
LSACONTROL
LSATEST
LSAPROCESS

planned

LSA 1.5.2
LSA 1.5.3
LSA 1.5.4
LSA 1.5.5

E50001K5701A521A17600
E50001K5701A531A17600
E50001K5701A541A17600
E50001K5701A551A17600

LSA 1.6.1

E50001K5701A611A17600

6MB551 Station control unit


6MB552 Compact remote terminal unit
6MB55300 Minicompact remote terminal unit
6MB55301 Minicompact remote terminal unit
for cable shield communication (RTC)
6MB5540 Remote terminal unit
SINAUT LSA COMPACT
6MB5515 Station control unit
Control in SINAUT LSA substation
control and protection
Status indications in SINAUT LSA substation
control and protection
Analog values in SINAUT LSA substation
control and protection
Metering in SINAUT LSA substation
control and protection
Voltage control with the I/O units 6MB520
and 6MB521
Network synchronization with I/O units 6MB520
and 6MB521
Operation with two control master units
Node functions
System management with the
SINAUT Substation Control and Protection System
Engineering and
parameterization system
Testing and diagnostics system
Control and monitoring
Communication diagnostics
Process information analysis
LSA678 Standard cubicle

MWB module 0
Indications inputs

V1

Commands

Transducer
input (20 mA,
optional) Single
command
(without
error
detection)

Direct
V2 transformer
inputs
I1
V+
V

FO interfaces
to master unit(s)
and for cascading
of protection relays
(parameterizable)
3rd interface
is optional

Power
supply

Fig. 6
Connection diagram of the 6MB5240-0 bay control unit

Siemens LSA 1.1.7 1997

11

6MB Station Control System


6MB524 Bay control unit

MWB module 0
Indications inputs

MWB module 1

MWB module 0

Indications inputs

Commands

Commands

Transducer
input 1
(20 mA,
optional)

V1

V3

Direct
V2 transformer
inputs

Direct
I2 transformer
inputs

I1

I3

V+
V

Power
supply

Fig. 7
Connection diagram of the 6MB5240-1 bay control unit

12

Transducer
input 2
(20 mA, optional)

Siemens LSA 1.1.7 1997

Single
command
(without
error
detection)

FO interfaces
to master unit(s)
and for cascading
of protection relays
(parameterizable)
3rd interface
is optional

MWB module 0
Indications inputs

MWB module 1
Indications inputs

Commands

Single command 2
(without
error
detection)

Transducer
input 1
(20 mA,
optional)

V1

V3

Direct
V2 transformer
inputs

Direct
I2 transformer
inputs

I1

I3

MWB module 0
Commands

Single command 1
(without
error
detection)

FO interfaces
to master unit(s)
and for cascading
of protection relays
(parameterizable)

V+
V
Power
supply

Transducer
input 2
(20 mA, optional)

Interfaces 3 to
5 are optional

Fig. 8
Connection diagram of the 6MB5240-2 bay control unit

Siemens LSA 1.1.7 1997

13

6MB Station Control System


6MB524 Bay control unit

MWB module 0
Indications inputs

MWB module 1
Indications inputs

Commands

Single command 2
(without
error
detection)

Transducer
input 1
(20 mA,
optional)

V1

V3

Direct
V2 transformer
inputs

Direct
V4 transformer
inputs

I1

I2

V+
V
Power
supply

Fig. 9
Connection diagram of the 6MB5240-4 (part 1) bay control unit

14

Siemens LSA 1.1.7 1997

Transducer
input 2
(20 mA, optional)

MWB module 0
Commands

Single command 1
(without
error
detection)

FO interfaces
to master unit(s)
and for cascading
of protection relays
(parameterizable)

MWB module 4
Indications inputs Commands

Single command 3
(without
error
detection)

V5
Direct
V6 transformer
inputs
I3

Fig. 10
Connection diagram of the 6MB5240-4 (part 2) bay control unit

Siemens LSA 1.1.7 1997

15

6MB Station Control System


6MB524 Bay control unit

MWB module 0
Indications inputs

MWB module 1
Indications inputs Commands

Single command 2
(without
error
detection)

Transducer
input 1
(20 mA,
optional)

V1

V3

Direct
V2 transformer
inputs

Direct
I2 transformer
inputs

I1

I3

V+
V
Power
supply

Fig. 11
Connection diagram of the 6MB5240-3 (part 1) bay control unit

16

Siemens LSA 1.1.7 1997

Transducer
input 2
(20 mA, optional)

MWB module 0
Commands

Single command 1
(without
error
detection)

FO interfaces
to master unit(s)
and for cascading
of protection relays
(parameterizable)

MWB module 2
Indications inputs

Commands

MWB module 3
Indications inputs

Single command 3
(without
error
detection)

Commands

Single command 4
(without
error
detection)

V4

V6

Direct
V5 transformer
inputs

Direct
V7 transformer
inputs

I4

I5

Transducer
input 3
(20 mA, optional)

Transducer
input 4
(20 mA, optional)

Fig. 12
Connection diagram of the 6MB5240-3 (part 2) bay control unit

Siemens LSA 1.1.7 1997

17

6MB Station Control System


6MB524 Bay control unit

MWB module 4
Indications inputs Commands

Single command 5
(without
error
detection)

V8
Direct
V9 transformer
inputs
I6

Transducer
input 5
(20 mA, optional)

Fig. 13
Connection diagram of the 6MB5240-3 (part 3) bay control unit

18

Siemens LSA 1.1.7 1997

Dimensions drawings in mm

Assembly plate

Diam. 5 or M4

Diam. 6

Modular
FO module
terminal block

Modular
terminal block

Rear view

Side view

Panel cutout

Fig. 14
6MB5240-0, -1, -2 bay control unit in 1/2 7XP20 housing

Assembly plate

Modular terminal block


Rear view

Diam. 5
Diam. 6

FO module

Modular terminal block


Side view

Fig. 15
6MB5240-3, -4 bay control unit in 1/1 7XP20 housing

Panel cutout

Siemens LSA 1.1.7 1997

19

Conditions of Sale and Delivery


Export Regulations, Trademarks, Dimensions
Conditions of Sale and Delivery
Subject to the
General Conditions of Supply
and Delivery
for Products and Services of
the Electrical and Electronic
Industry and to any other
conditions agreed upon with
the recipients of catalogs.

The technical data, dimensions


and weights are subject to
change unless otherwise stated
on the individual pages of this
catalog.
The illustrations are
for reference only.

Export Regulations
In accordance with the present
provisions of the German Export
List and the US Commercial
Control List, export licences are
not required for the products
listed in this catalog.

We reserve the right to adjust


the prices and shall charge the
prices applying on the date of
delivery.

A En 1.91a

Trademarks
An export licence may however
be required due to countryspecific application and final
destination of the products.
Relevant are the export criteria
stated in the delivery note and
the invoice regarding a possible
export and reexport licence.
Subject to change without notice.

All product designations used


are trademarks or product
names of Siemens AG or of
other suppliers.
Dimensions
All dimensions in this catalog
are given in mm.

Siemens online
The Power Transmission and
Distribution Group can also be
found in the Internet at:
http://www.ev.siemens.de

Responsible for
Technical contents: Dr. Markus Wache,
Siemens AG, EV S V2, Nrnberg
General editing: Claudia Khn-Sutiono,
Siemens AG, EV BK T, Erlangen
Bereich
Energiebertragung und -verteilung
Geschftsgebiet Sekundrsysteme
P. O. Box 48 06
D-90026 Nrnberg

Siemens Aktiengesellschaft

Order No.: E50001-K5701-A171-A2-7600


Printed in Germany