PAC-L Series

Packaged Air Conditioners


Range 5 TR to 30 TR
( 18 kW to 105 kW )

Bulletin # 071/2010 (NEW)

SKM Packaged Airconditioning Units


PAC-L Series - R22

Contents
Capacity Ratings ................................08
Fan Performance .................................10
Electrical Data......................................11
Typical Wiring Diagram........................12
Dimensional Data ..............................14
Recommended Clearances ...............17
Installation & Commissioning ...............19
Guide Specifications............................20

Legend ................ .................................02


Nomenclature....................................... 02
Introduction....
.............................02
General Features ...............................03
Main Component Features .................03
Optional Features ................................04
Microprocessor Control.......................05
Engineering Specifications.................06

Introduction
New SKM PAC-L Series Packaged Air
Conditioners are designed and manufactured
to meet the requirements of Gulfs severe
climatic conditions and are built specifically
for ducted systems which will enable them
to be installed easily on roof tops or on the
ground.
The PAC-L series Packaged Air Conditioners
are compact, quiet, most efficient and self
contained units are ideal for commercial and
top end residential applications.

Legend
The following legends are used throughout this manual:
cfm ........ Cubic feet per minute
Hz ......... Hertz
kW ........ Kilowatts
kg .......... Kilogram
lbs ......... Pounds
l/s .......... Liters per second
Pa ......... Pascal
in. wg .... Inch water gauge

AFR ...... Air Flow Rate


MBh ...... BTUH x 1000
Ph ......... Phase
PI .......... Power Input of Compressor
BPF....... By Pass Factor
TR ......... Tons of Refrigeration
V ........... Volts

S K M PA C - L S e r i e s a r e a v a i l a b l e
in 12 different sizes from 5.0 to 30 TR
(18 to 105 kW) in 60 Hz at nominal AHRI
conditions. PAC-L units are designed, rated
and manufactured in accordance with AHRI
210/240 and 340/360 standards.
The PAC-L series units from SKM are
completely assembled, leak tested, vacuumed,
internally wired and fully charged with R-22
refrigerant at factory. Each unit is fully factory
tested before dispatch and is ready for
installation. All that is required on the site is to
connect ducts, drain lines, main power supply
and field wiring to the thermostat. This greatly
reduces the installation works and cost.
SKM PAC-L series packaged air conditioners
are designed to operate in a wide ambient
temperature range between 50F (10C)
to 125F (52C).

Nomenclature

SKM Airconditioning Equipment,

PAC

L - 6

1 060 R

Power Supply Code

R:
E:
T:

380V/3Ph/60Hz
460V/3Ph/60Hz
220-230V/3Ph/60Hz

Compressor Nominal Capacity in MBh


1: Single circuit
2: Double circuit

Built in the Gulf...for the World

6 = 60Hz
Packaged Air
Conditioner

L - Series

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
General Features

Condenser Coils

The PAC-L Series Packaged Air Conditioners are yet another


new unique series from SKM incorporates many salient features
which, together, provides a heavy duty, robust, long lasting
commercial unit meant for high end residential and commercial
applications. The PAC-L series models combine high efficiency
condenser and cooling coil, evaporator blower and heavy duty
motor in addition to premium safety and operational controls.

Condenser coils are manufactured from cross fin Waffle Louvre


and Hi-X seamless copper tubes mechanically bonded to
aluminium fins to ensure optimum heat transfer. All coils are
tested against leakage by air pressure 450psig (3100 kPa)
under water. An integral subcooling circuit is incorporated in the
lower section of the condenser to increase system capacity. The
additional condenser surface provides more cooling using less
energy at no additional cost.

The complete PAC-L packaged unit provides an extremely


rugged, long life, energy efficient, self contained packaged air
conditioner that will provide cooling with higher efficiency over
a long and extended life.
What makes PAC-L series yet another model in the top class
range of SKM products is the use of:

High efficiency totally sealed scroll hermetic compressors.


Totally enclosed, Class F insulated, minimum IP55 protected
condenser and evaporator fan motors.
Heavy duty condenser and evaporator coils optimised in
design for long-life maintenance free operation.
Cabinet construction specifically designed for Gulf
climates.
Electrical panel with many features, as standard.
Typically, much heavier gauge tubing and thicker fins for
ruggedness and long life.

Main Component Features

Condenser Fans
Condenser fans are propeller type with aluminium alloy blades
and are directly driven by electric motors. Motors are internally
protected for overloads and Totally Enclosed Air Over (TEAO),
six pole with Class F insulation and minimum IP55 protection.
The TEAO and Class F insulation features ensure long life and
are unique to SKM. The condenser fans are individually statically
and dynamically balanced at the factory. Complete fan assembly
is mounted downward on the strong and acrylic coated fan guard
for the smaller units.
For larger units fan,
assembly is separate
and provided with
suitable acrylic coated
fan guard. Motors are
wired to the control panel
to control the operation of
these motors along with
the compressors.

The common standard features of all PAC-L series packaged


units include the following:

Figure 1

Condenser Fan Motor


arrangement for Models
PAC-L 61060-62180

Compressors
Compressors used in PAC-L packaged unit series are
hermetically sealed, compact scroll with the following features:

High Efficiency.
Quite operation, Low Sound levels.
Better debris handling.
Self compensating of wear (wears-in vs. wears-out).
70% fewer moving parts than comparably sized reciprocating
compressors
Internal motor protection / Advanced scroll temperature
protection.
Suction gas motor cooling.
Suction screen.
Disc type check valve.
Centrifugal oil pumps with filter and magnet.
Brazed fittings or Rotalock options.

Condenser Fan Motor


Figure 2 : arrangement for Models
PAC-L 62200-62360

Evaporator
Evaporator coils are manufactured from Hi-x tubes mechanically
bonded to aluminium cross wave fins to ensure optimum heat
transfer. All evaporator coils are tested against leakage by air
pressure of 300 psig (2068 kPa) under water. Coils conform to
AHRI-410.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
Evaporator

Optional Features

Evaporator coils are manufactured from Hi-x tubes mechanically


bonded to aluminium cross wave fins to ensure optimum heat
transfer. All evaporator coils are tested against leakage by air
pressure under water. Coils conform to AHRI-410 (300 psig
(1720 KPa)).

As with all SKM air conditioning units, the PAC-L Series


Packaged Units are available with multitude of optional features
available on request:

Voltage Monitoring Modules

(VMM)

Provide protection to the PAC-L Series in the event of :

Evaporator Fan & Drive


Evaporator fans are forward curved centrifugal double inlet, double
width, statically and dynamically balanced. Bearings used in the
fans are self aligning and lubricated for life. Evaporator fans are
belt driven and use V belts with an adjustable variable pitch
motor pulley resulting in an accurate fan air flow adjustment.

Phase burn-out
Phase reversal
Under / over voltage on the incoming line voltage.

High & Low Pressure Gauges

(SDG)

Fans are driven by Totally Enclosed, IP55 Protected, 4 pole


Class F insulated electric motors. The motors are factory wired to
the control panel where the motor starters are located to control
the operation of the motors. The motors conform to relevant IEC
standards.

Unit mounted for each compressor to monitor the high and


lo-side operating pressure.

Casing and Structure

Liquid Line Sight Glass

The unit casing used in PAC-L series is made of hot dip


galvanized (zinc coated) steel sheets, conforming to JIS-G
3302 and ASTMA525, which is phosphatized and baked after an
electrostatic powder coat of approx. 60 microns. This finish and
coating can pass a 1000 hour in 5% salt spray testing at 95F
(35C) and 95% relative humidity as per ASTM B117.

For monitoring refrigerant charge and to provide visual indication


of moisture presence in the system.

The evaporator section is insulated from all the sides with 1 thick
fiber glass insulation with extremely tough and durable black
composite surface. The insulation cum sound liner meets the fire
requirements of NFPA90A & 90B and is secured with mechanical
fasteners in addition to water resistant adhesive.

1" (25mm) / 2" (50mm) Flat Filter Section

(FFS)

For heavy filtration need a section can be provided without or


with aluminium cleanable filter (1AF/2AF).

(RSG)

Electric Heating

(HC@)

The following electric heaters are available as optional accessories


on request. Components include electric heater elements,
magnetic contactors, thermal safety cut-out (manual & auto)
and airflow switch.

MODEL
PACL

HEATER (kW) STAGES

61060
61070

Control Panel
The PAC-L packaged Air Conditioners are provided with IP-54
control panel enclosure comprising all starting, operating and
safety controls.

61090
62105
62120

62180

Condensor & Evaporator Fan motor contactor and overload


relays.

24Volts low voltage fused transformer for user supplied and


installed room thermostat.

Compressor short cycling protection.

Control disconnect switch for each circuit.

Power and control circuit terminal blocks.

High pressure protector.

Low pressure protector.

61105

The following are the standard components used in all PAC-L


series units.
Individual compressor motor contactors.

4.5

62150
62215

18

24

62240
62300
62360

Table 1

Pump Down Facility with solenoid valve

(PDS)

For providing means to pump down circuit refrigerant gas into


condenser. This step reduces the amount of charge on the low
side in order to prevent off cycle migration.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
Low Voltage Thermostat

(COTS/CHTS)

(1 or 2 stages as per model) for wall mounting and for either


cooling (COTS) or cooling/heating (CHTS) operation (not required
with MCP Option).

Shut-off Valve

(SFV)

Shut-off valves are available as an option for models PAC-L


61060 - 62105 (Shut-Off Valves are not standard in these models).

Extra Shut-off Valve

(XFV)

To fully isolate refrigerant filter drier; an additional shut-off valve


can be incorporated in the liquid line.

Factory Installed Option


Microprocessor Based Control

(MCP)

The controller consists of modules with on board display and user


interface terminals. The controller has compact dimensions and
can manage package unit with cooling / heating circuits. The
controller has the following features.

Built in anti recycle timer to prevent compressor short


cycling.
Auto, lead/lag of the compressor.
Common alarm available through the dry contact.
Remote start/stop of the unit.
Cooling and heating functions are available.

Alternative Condenser Material


Made of copper tubes and alternative fin material and/or
protective coats.

For Copper Fins specify (FC)


For Precoated Aluminum Fins, specify (FAP)
For Aluminum Fins with Aeris Coat Protection, specify
(FAA)
For Copper Fins with Aeris Coat Protection, specify (FCA)

Following parameters can be displayed on the controller LCD:

Return or space air temperature.

High pressure, low pressure alarms.

Alternative Evaporator Material


Made of copper tubes and alternative fin material and/or
protective coats.

For Copper Fins specify (FC)


For Precoated Aluminum Fins, specify (FAP)
For Aluminum Fins with Aeris Coat Protection, specify
(FAA)
For Copper Fins with Aeris Coat Protection, specify (FCA)
Figure 3

Condenser Coil Guard

(CGP)

Wire mesh guard, in painted finish, for condenser coils.


Recommended on ground level installation where coil needs to
be protected against vandalism.

Double Skin Insulation

(DSI)

For Evaporator section with Foam board insulation.

External Overload Protection

Remote Terminal:
It is sophisticated graphic LCD for the panel mounting, installation
on the unit, or remote wall mounting, for the complete control
of the unit. This terminal has an excellent feature for servicing and
setting up the unit. It can interface easily through RS485 terminal
and require external temperature sensor to control the unit.

(EOP)

For those electrical specification requires additional overload


protection for the compressors.

Figure 4

Air Conditioning Equipment . Built in the Gulf... for the World

Figure 5

SKM Packaged Airconditioning Units


PAC-L Series - R22
ENGINEERING SPECIFICATIONS
Model PAC - L
Cooling Capacity (1)
Cooling Capacity (2)
Cooling Capacity (3)
Capacity Steps
Compressor

Condenser

Coil

61070

61090

61105

62105

62120

MBh

60.7

74.4

90.4

105.8

106.7

122.4

kW

17.8

21.8

26.5

31.0

31.3

35.9

MBh

54.8

67.0

81.1

94.9

95.7

110.4

kW

16.1

19.6

23.8

27.8

28.0

32.3

MBh

53.7

65.7

79.3

92.9

93.6

108.1

kW

15.7

19.3

23.2

27.2

27.4

31.7

100-0

100-0

100-0
100-0
Hermetic Scroll

100-50-0

100-50-0

1
1
Waffle louver fins and Hi-X tubes

ft

19.4

19.4

26.7

26.7

26.7

40.0

1.8

1.8

2.5
2.5
Propeller Direct Drive

2.5

3.7

560 / 1

560 / 1

560 / 2

560 / 2

560 / 2

560 / 2

cfm

4740

4740

8400

8400

8400

8400

l/s

2237

2237
3964
3964
3964
Totally enclosed, Class-F insulation, 6-pole, IP55 Protected

3964

kW / #

0.37 / 1

0.37/1

ft

4.6

6.4

0.43

0.60

AT-10/10
1

AT-10/10
1

AT-12/12
1

cfm

2000

2400

3000

l/s

944

1133

kW

0.55

0.75

1.1

1.1

1.1

1.5

lbs

11.0

11.5

14.7

15.4

17.3

22.6

kg

5.0

5.2

6.7

7.0

7.8

10.2

lbs

687

701

820

893

985

1071

kg

312

318

372

405

447

486

Type
Qty.
Type
Face Area
Type

Fan

Code/Qty
Air Flow

Motor

Coil

Evaporator

61060

Type
Size / Qty.
Type
Face Area
Type
Code

Fan

Blower Qty.
Air Flow

Motor

Type
Size

Refrigerant Operating Charge


(R-22)
Operating Weight Approximate

0.37 / 2
0.37 / 2
Cross Wave Fin, and Hi-X Tubes

0.37 / 2

0.37 / 2

7.5

9.7

0.70

0.90

AT-12/12
1

AT-12/12
1

AT-15/15
1

3000

3000

4000

1416
1416
1416
Totally Enclosed, Class F insulated, IP55 Protected

1888

7.5

7.5

0.70
0.70
Centrifugal DIDW Belt Drive

Table 2

Notes:
(1) The capacity ratings are based on AHRI standard 210/240 & 340/360.Evaporator entering air conditions of 80F/67F
(27C/19.5C)drybulb/wetbulb and condenser entering air temperature of 95F (35C) drybulb.
(2) Evaporator entering air conditions of 80F/67F (27C/19.5C) drybulb/wetbulb and condenser entering air temperature of
115F(46C) drybulb.
(3) Evaporator entering air conditions of 80F/67F (27C/19.5C) drybulb/wetbulb and condenser entering air temperature of
118.4F(48C) drybulb.
* Capacity for all conditions are gross capacity which does not include the effect of Evaporator Fan Motor Heat.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
ENGINEERING SPECIFICATIONS
Model PAC - L
Cooling Capacity (1)
Cooling Capacity (2)
Cooling Capacity (3)
Capacity Steps
Compressor

Condenser

Coil

62180

62215

62240

62300

62360

MBh

151.8

179.7

215.1

240.4

303.4

357.5

kW

44.5

52.7

63.0

70.4

88.9

104.7

MBh

137.1

160.6

192.5

216.5

271.3

318.7

kW

40.2

47.1

56.4

63.4

79.5

93.4

MBh

134.3

157.4

188.6

212.1

265.7

311.8

kW

39.3

46.1

55.3

62.1

77.9

91.4

100-50-0

100-50-0

100-50-0
100-50-0
Hermetic Scroll

100-50-0

100-50-0

2
2
Waffle louver fins and Hi-X tubes

ft

40.0

40.0

40.0

54.7

54.7

54.7

3.7

3.7

3.7
5.1
Propeller Direct Drive

5.1

5.1

628 / 2

628 / 2

723 / 2

729 / 2

823/2

823 / 2

cfm

11640

11640

16680

18740

24140

23620

l/s

5493

5493
7872
8844
11392
Totally enclosed, Class-F insulation, 6-pole, IP55 Protected

11147

kW / #

0.45 / 2

0.45 / 2

ft

9.7

12.5

0.90

1.16

AT-15/15

AT-12/12 SC2

AT-12/12 SC2

cfm

4000

5700

l/s

1888

2690

kW
lbs
kg
lbs
kg

Type
Qty.
Type
Face Area
Type

Fan

Code/Qty
Air Flow

Motor

Coil
Evaporator

62150

Type
Size / Qty.
Type
Face Area

1.5/2

1.5 / 2

21.7

21.7

2.01

2.01

AT-15/15 SC2

AT-15/15 SC2

AT-15/15 SC2

6600

8000

8000

10000

3775

4719

1.5
23.5
10.7

3115
3775
Totally Enclosed, Class F insulated, IP55 Protected
2.2
2.2
3.0
24.7
28.5
34.1
11.2
12.9
15.5

3.0
36.1
16.4

4.0
46.9
21.3

1234

1306

1520

1625

1807

2052

560

592

689

737

820

931

Type
Fan

Code
Blower Qty.
Air Flow

Motor

Type
Size

Refrigerant Operating Charge


(R-22)
Operating Weight Approximate

1.1 / 2
1.5/2
Cross Wave Fin, and Hi-X Tubes
16.0

21.7

1.49
2.01
Centrifugal DIDW Belt Drive

Table 3

Notes:
(1)

The capacity ratings are based on AHRI standard 210/240 & 340/360.Evaporator entering air conditions of 80F/67F
(27C/19.5C)drybulb/wetbulb and condenser entering air temperature of 95F (35C) drybulb.

(2) Evaporator entering air conditions of 80F/67F (27C/19.5C) drybulb/wetbulb and condenser entering air temperature of
115F(46C) drybulb.
(3) Evaporator entering air conditions of 80F/67F (27C/19.5C) drybulb/wetbulb and condenser entering air temperature of
118.4F(48C) drybulb.
* Capacity for all conditions are gross capacity which does not include the effect of Evaporator Fan Motor Heat.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
CAPACITY RATINGS - 60 HZ
Condenser Entering Air Temperature

AFR
cfm
l/s
(BPF)
1260
595
0.1
2000

F
62
67
72
62

C MBh
16.7 50.7
19.4 55.4
22.2 59.8
16.7 55.5

kW
14.9
16.2
17.5
16.3

MBh
41.1
34.8
28.2
51.9

61060

944
0.14
2521
1190
0.16
1769
835
0.1
2400

67
72
62
67
72
62
67
72
62

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

60.7
65.7
57.5
63
68.2
64.7
70.4
75.8
68.2

17.8
19.2
16.8
18.5
20
19
20.6
22.2
20

61070

1133
0.12
3538
1670
0.16
2064
974
0.1
3000

67
72
62
67
72
62
67
72
62

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

74.4
80.3
72.1
78.8
85.2
77.5
84.4
90.8
82.9

61090

1416
0.13
4128
1948
0.16
2064
974
0.04
3000

67
72
62
67
72
62
67
72
62

61105

1416
0.07
4128
1948
0.1
2064
974
0.04
3000

62105

62120

Model
PACL

EWB

95F (35C)
Total Capacity Sen Capacity

105F (41C)
Total Capacity Sen Capacity

kW
12
10.2
8.3
15.2

PI
kW
4.1
4.2
4.3
4.2

MBh
48.5
53.1
57.3
53

kW
14.2
15.5
16.8
15.5

MBh
40.1
33.8
27.3
50.8

42.8
33.5
57.5
47.8
36.7
54.7
45.8
36.6
63.9

12.5
9.8
16.8
14
10.7
16
13.4
10.7
18.7

4.3
4.4
4.2
4.3
4.4
5.1
5.2
5.4
5.2

58.1
62.9
54.9
60.2
65.2
61.7
67.3
72.5
65.1

17
18.4
16.1
17.6
19.1
18.1
19.7
21.3
19.1

21.8
23.5
21.1
23.1
25
22.7
24.7
26.6
24.3

52.7
41.1
72.1
63.6
48.1
64.7
54.4
43.6
78.4

15.4
12
21.1
18.7
14.1
19
15.9
12.8
23

5.3
5.5
5.3
5.5
5.7
5.6
5.8
6
5.8

71.1
76.7
68.7
75.1
81.1
74
80.6
86.9
79

19.4 90.4
22.2 97.2
16.7 86.8
19.4 94.6
22.2 101.7
16.7 89.1
19.4 96.9
22.2 104.4
16.7 97

26.5
28.5
25.4
27.7
29.8
26.1
28.4
30.6
28.4

64.5
50.1
86.8
75.2
56.9
72.7
61.5
49.8
89.1

18.9
14.7
25.4
22
16.7
21.3
18
14.6
26.1

5.9
6.1
5.9
6.1
6.2
6.8
7
7.1
7

67
72
62
67
72
62
67
72
62

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

105.8
114
102.4
111.9
120.7
90
97.9
105.3
98

31
33.4
30
32.8
35.4
26.4
28.7
30.9
28.7

73.7
57.9
102.4
86.7
66.2
73.2
61.9
50.1
89.5

21.6
17
30
25.4
19.4
21.4
18.2
14.7
26.2

1416
0.07
4128
1948
0.1
2674
1262
0.1
4000

67
72
62
67
72
62
67
72
62

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

106.7
114.9
103.5
112.9
121.7
103.6
113
122.1
111.8

31.3
33.7
30.3
33.1
35.7
30.4
33.1
35.8
32.8

74.1
58.2
103.5
87
66.5
85.3
72
58.1
104.7

1888
0.13
5347
2523
0.16

67
72
62
67
72

19.4
22.2
16.7
19.4
22.2

122.4
132.4
116.8
128.1
138.7

35.9
38.8
34.2
37.5
40.6

86.4
67.5
116.8
99.3
75.9

Total Capacity

115F (46C)
Sen Capacity

kW
11.7
9.9
8
14.9

PI
kW
4.6
4.7
4.8
4.7

MBh
45.9
50.2
54.3
50

kW
13.4
14.7
15.9
14.7

MBh
38.9
32.7
26.2
49.6

41.8
32.5
54.9
46.8
35.7
53.4
44.6
35.5
62.6

12.3
9.5
16.1
13.7
10.5
15.6
13.1
10.4
18.4

4.8
4.9
4.7
4.9
5
5.8
6
6.1
5.9

54.8
59.4
51.7
56.8
61.6
58.1
63.5
68.5
61.3

16.1
17.4
15.2
16.6
18.1
17
18.6
20.1
18

20.8
22.5
20.1
22
23.8
21.7
23.6
25.5
23.2

51.5
39.9
68.7
62.4
46.8
63.1
52.9
42.2
76.8

15.1
11.7
20.1
18.3
13.7
18.5
15.5
12.4
22.5

6.1
6.2
6
6.2
6.4
6.4
6.5
6.6
6.5

67
72.2
64.6
70.7
69.4
75.8
81.9
74

86.3
93
82.6
90.2
97.3
84.9
92.6
99.8
92.3

25.3
27.2
24.2
26.4
28.5
24.9
27.1
29.2
27

62.9
48.7
82.6
73.7
55.5
70.8
59.7
48.1
87.1

18.4
14.3
24.2
21.6
16.3
20.8
17.5
14.1
25.5

6.6
6.7
6.5
6.7
6.8
7.7
7.8
8
7.8

7.1
7.3
7.1
7.2
7.4
7.1
7.3
7.4
7.3

100.9
108.9
97.4
106.6
115.2
85.8
93.4
100.6
93.2

29.6
31.9
28.5
31.2
33.8
25.2
27.4
29.5
27.3

71.9
56.1
97.4
84.7
64.4
71.2
60.1
48.4
87.5

21.1
16.4
28.5
24.8
18.9
20.9
17.6
14.2
25.6

21.7
17.1
30.3
25.5
19.5
25
21.1
17
30.7

7.5
7.7
7.4
7.6
7.8
8.3
8.5
8.7
8.5

101.7
109.7
98.4
107.5
115.9
99
108.3
117
106.8

29.8
32.1
28.8
31.5
34
29
31.7
34.3
31.3

72.2
56.4
98.4
85
64.7
83.2
70
56.2
102.6

25.3
19.8
34.2
29.1
22.2

8.7
8.9
8.6
8.9
9.1

117
126.7
111.4
122.3
132.6

34.3
37.1
32.7
35.9
38.9

84.4
65.7
111.4
97.3
73.9

Total Capacity

118.4F (48C)
Sen Capacity

kW
11.4
9.6
7.7
14.5

PI
kW
5.1
5.3
5.4
5.2

MBh
45
49.2
53.2
49

kW
13.2
14.4
15.6
14.4

MBh
38.5
32.3
25.8
49

40.6
31.4
51.7
45.6
34.6
51.8
43.1
34.1
61.1

11.9
9.2
15.2
13.4
10.1
15.2
12.6
10
17.9

5.4
5.5
5.3
5.4
5.6
6.6
6.7
6.8
6.7

53.7
58.3
50.6
55.6
60.4
56.9
62.3
67.2
60

15.7
17.1
14.8
16.3
17.7
16.7
18.3
19.7
17.6

19.6
21.2
18.9
20.7
20.3
22.2
24
21.7

50
38.5
64.6
60.8
61.1
51
40.5
74

14.6
11.3
18.9
17.8
17.9
14.9
11.9
21.7

6.8
6.9
6.7
6.9
7.1
7.2
7.3
7.2

65.7
70.7
63.3
69.2
67.8
74.2
80.2
72.3

81.1
87.7
77.3
84.8
92
79.7
87.1
94.1
86.5

23.8
25.7
22.7
24.9
27
23.3
25.5
27.6
25.4

61
47
77.3
71.8
53.8
68.4
57.5
46
84.6

17.9
13.8
22.7
21
15.8
20.1
16.8
13.5
24.8

7.3
7.3
7.2
7.3
7.3
8.6
8.8
8.9
8.7

8
8.2
7.9
8.1
8.4
8.1
8.2
8.4
8.2

94.9
102.7
91.3
100.2
80.6
88
94.9
87.5

27.8
30.1
26.8
29.4
23.6
25.8
27.8
25.6

69.6
54
91.3
82.5
68.9
57.8
46.3
85.1

20.4
15.8
26.8
24.2
20.2
17
13.6
24.9

21.2
16.5
28.8
24.9
19
24.4
20.5
16.5
30.1

8.4
8.6
8.3
8.5
8.8
9.4
9.6
9.8
9.6

95.7
103.3
92.2
100.9
93.5
102.3
110.6
100.6

28
30.3
27
29.6
27.4
30
32.4
29.5

69.9
54.2
92.2
82.7
80.8
67.7
54
100.1

24.7
19.2
32.7
28.5
21.7

9.8
10.1
9.7
9.9
10.2

110.4
119.6
104.9
115.3
125.2

32.3
35.1
30.7
33.8
36.7

82
63.4
104.9
94.9
71.6

Total Capacity

125F (52C)
Sen Capacity

kW
11.3
9.5
7.6
14.4

PI
kW
5.3
5.4
5.5
5.4

MBh
43.2
47.3
51.3
47

kW
12.7
13.9
15
13.8

MBh
37.7
31.5
25.1
47

kW
11.1
9.2
7.4
13.8

PI
kW
5.7
5.8
5.9
5.8

40.2
31
50.6
45.2
34.2
51.3
42.7
33.6
60

11.8
9.1
14.8
13.2
10
15
12.5
9.9
17.6

5.6
5.7
5.5
5.6
5.8
6.8
6.9
7
6.9

51.7
56.1
48.6
53.5
58.2
54.6
59.9
64.6
57.6

15.1
16.5
14.2
15.7
17.1
16
17.5
18.9
16.9

39.5
30.4
48.6
44.4
33.5
50.3
41.7
32.8
57.6

11.6
8.9
14.2
13
9.8
14.8
12.2
9.6
16.9

5.9
6
5.8
5.9
6.1
7.2
7.3
7.4
7.3

19.2
20.7
18.5
20.3
19.9
21.7
23.5
21.2

49.5
38
63.3
60.3
60.5
50.4
39.9
72.3

14.5
11.1
18.5
17.7
17.7
14.8
11.7
21.2

7
7.1
7
7.1
7.4
7.5
7.5
7.4

63.1
68
60.7
66.4
64.8
71.1
77.2
69.2

18.5
19.9
17.8
19.4
19
20.9
22.6
20.3

48.5
37.1
60.7
59.3
59.2
49.2
38.8
69.2

14.2
10.9
17.8
17.4
17.4
14.4
11.4
20.3

7.4
7.5
7.3
7.4
7.9
7.9
7.9
7.9

79.3
86
75.5
83
77.9
85.3
92.3
84.6

23.3
25.2
22.1
24.3
22.8
25
27
24.8

60.4
46.4
75.5
71.2
67.7
56.8
45.3
83.9

17.7
13.6
22.1
20.9
19.8
16.6
13.3
24.6

7.5
7.5
7.5
7.5
8.9
9.1
9.2
9

76.1
82.9
72.3
79.7
74.7
81.9
88.8
81.1

22.3
24.3
21.2
23.4
21.9
24
26
23.8

59.3
45.4
72.3
70
66.2
55.4
44.1
81.1

17.4
13.3
21.2
20.5
19.4
16.2
12.9
23.8

7.9
7.8
7.9
7.8
9.5
9.6
9.7
9.6

8.9
9.2
8.8
9.1
9.1
9.2
9.3
9.2

92.9
100.7
89.3
98.1
78.9
86.2
93
85.6

27.2
29.5
26.2
28.8
23.1
25.3
27.3
25.1

68.9
53.3
89.3
81.7
68.1
57.1
45.6
84.3

20.2
15.6
26.2
24
20
16.7
13.4
24.7

9.2
9.5
9.1
9.4
9.4
9.5
9.7
9.5

89.3
96.9
85.5
94.3
75.6
82.7
89.4
82

26.2
28.4
25.1
27.6
22.2
24.2
26.2
24

67.5
52.1
85.5
80.4
66.6
55.7
44.3
82

19.8
15.3
25.1
23.6
19.5
16.3
13
24

9.8
10
9.7
9.9
10
10.1
10.2
10.1

20.5
15.9
27
24.2
23.7
19.8
15.8
29.3

9.4
9.6
9.3
9.5
10.5
10.7
10.9
10.7

93.6
101.1
90.2
98.7
91.6
100.3
108.5
98.5

27.4
29.6
26.4
28.9
26.9
29.4
31.8
28.9

69.2
53.5
90.2
81.9
80
66.9
53.3
98.5

20.3
15.7
26.4
24
23.4
19.6
15.6
28.9

9.7
9.9
9.6
9.8
10.8
11.1
11.3
11

89.8
97.1
86.3
94.6
88
96.4
104.6
94.5

26.3
28.5
25.3
27.7
25.8
28.3
30.6
27.7

67.7
52.2
86.3
80.5
78.4
65.4
51.9
94.5

19.9
15.3
25.3
23.6
23
19.2
15.2
27.7

10.2
10.5
10.2
10.4
11.5
11.8
12
11.7

24
18.6
30.7
27.8
21

10.9
11.2
10.8
11.1
11.4

108.1
117.3
102.7
112.9
122.8

31.7
34.4
30.1
33.1
36

81.2
62.6
102.7
94
70.9

23.8
18.4
30.1
27.6
20.8

11.3
11.6
11.1
11.4
11.8

104
113.1
98.5
108.6
118.4

30.5
33.2
28.9
31.8
34.7

79.7
61.3
98.5
92.5
69.5

23.4
18
28.9
27.1
20.4

12
12.2
11.8
12.1
12.4

Table 4

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
CAPACITY RATINGS - 60 HZ
Condenser Entering Air Temperature

AFR
cfm
l/s
(BPF)
2674
1262
0.04
4000

F
62
67
72
62

C
16.7
19.4
22.2
16.7

MBh
126.9
137.6
147.8
139.6

kW
37.2
40.3
43.3
40.9

MBh
99.7
84.9
69.3
123

62150

1888
0.07
5347
2523
0.1
3438
1622
0.04
5700

67
72
62
67
72
62
67
72
62

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

151.8
163.4
147.1
160.3
172.8
148.1
161.1
173.2
165

44.5
47.9
43.1
47
50.7
43.4
47.2
50.8
48.4

62180

2690
0.08
6875
3244
0.1
4400
2076
0.04
6600

67
72
62
67
72
62
67
72
62

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

179.7
193.2
169.9
185.1
199
180.7
196.7
211.8
197.1

62215

3115
0.07
8800
4153
0.1
5958
2812
0.1
8000

67
72
62
67
72
62
67
72
62

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

62240

3775
0.12
11917
5624
0.16
5958
2812
0.04
8000

67
72
62
67
72
62
67
72
62

62300

3775
0.06
11917
5624
0.1
5958
2812
0.04
10000

62360

4719
0.08
11917
5624
0.1

Model
PACL

EWB

95F (35C)
Total Capacity
Sen Capacity

105F (41C)
Sen Capacity
Total Capacity

kW
29.2
24.9
20.3
36

PI
kW
10.2
10.5
10.7
10.5

MBh
121.4
131.8
141.7
133.3

kW
35.6
38.6
41.5
39.1

MBh
97
82.4
67
120.2

102.3
81
143.9
117.9
91.1
121
102.4
82.7
159.4

30
23.8
42.2
34.6
26.7
35.5
30
24.2
46.7

10.8
11.1
10.7
11
11.3
12.1
12.5
12.8
12.6

145.2
156.4
140.3
153.1
165.1
140.8
153.3
165.1
156.4

42.6
45.9
41.1
44.9
48.4
41.3
44.9
48.4
45.8

52.7
56.6
49.8
54.3
58.3
53
57.7
62.1
57.8

130.9
101.3
169.9
143.9
109.6
150.8
127.1
102.1
188.6

38.4
29.7
49.8
42.2
32.1
44.2
37.2
29.9
55.3

13
13.3
12.8
13.2
13.5
14.2
14.5
14.8
14.5

170.9
184.5
161
176
171.9
187.5
202.2
187.2

215.1
231.9
206.4
225.5
209.8
228.3
245.7
220.6

63
68
60.5
66.1
61.5
66.9
72
64.7

155.2
120.7
206.4
180
180.7
150.9
120
210.6

45.5
35.4
60.5
52.8
53
44.2
35.2
61.7

14.9
15.3
14.7
15.1
15.7
16.1
16.5
15.9

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

240.4
258.8
232.9
254
273.5
261.7
283.8
304.2
279.8

70.5
75.8
68.3
74.5
80.2
76.7
83.2
89.2
82

173
134.2
232.9
210.4
157.9
212.1
179.3
144.8
248

50.7
39.3
68.3
61.7
46.3
62.2
52.6
42.4
72.7

67
72
62
67
72
62
67
72
62

19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7

303.4
324.9
299.3
324.5
347
315.4
338.9
328.4

88.9
95.2
87.7
95.1
101.7
92.4
99.3
96.3

205.9
162.2
299.3
250.7
190.7
192.9
158.1
295.9

67
72
62
67
72

19.4
22.2
16.7
19.4
22.2

357.5
384.8
338.7
369
397.3

104.8
112.8
99.3
108.2
116.5

245.4
193.2
325.3
267.2
207.1

Total Capacity

115F (46C)
Sen Capacity

kW
28.4
24.1
19.6
35.2

PI
kW
11.6
11.9
12.1
11.9

MBh
114.4
124.5
134.2
125.5

kW
33.5
36.5
39.3
36.8

MBh
93.8
79.3
64.1
116.9

99.8
78.6
140.3
115.2
88.6
117.6
99.1
79.6
155.9

29.2
23
41.1
33.8
26
34.5
29
23.3
45.7

12.2
12.5
12.1
12.4
12.8
13.7
14
14.2
14

137.1
147.8
132.1
144.4
155.6
131.8
143.9
155.6
146.3

40.2
43.3
38.7
42.3
45.6
38.6
42.2
45.6
42.9

50.1
54.1
47.2
51.6
50.4
55
59.3
54.9

127.6
98.4
161
140.6
146.8
123.3
98.6
184.5

37.4
28.8
47.2
41.2
43
36.1
28.9
54.1

14.3
14.4
14.1
14.3
16
16.3
16.6
16.3

160.6
174.5
150.6
165.6
161.2
176.4
190.7
175.4

204.7
221.1
195.9
214.5
200.4
218.3
235.1
210.5

60
64.8
57.4
62.9
58.7
64
68.9
61.7

151.4
117.1
195.9
176.1
176.6
147
116.3
206.4

44.4
34.3
57.4
51.6
51.8
43.1
34.1
60.5

16.7
17.2
16.5
17
17.6
18
18.4
17.8

16.3
16.7
16.2
16.6
17
21.4
22
22.6
21.9

229.6
247.2
222
242.2
248.5
270
290.1
265.3

67.3
72.5
65.1
71
72.8
79.1
85
77.8

169
130.4
222
206.3
206
173.6
139.5
241.7

49.5
38.2
65.1
60.5
60.4
50.9
40.9
70.8

60.3
47.5
87.7
73.5
55.9
56.6
46.3
86.7

22.6
23.2
22.5
23.2
23.8
26.2
26.8
26.5

288.6
310.1
283.8
308.9
331.9
275.9
300.2
323.2
311.4

84.6
90.9
83.2
90.5
97.3
80.9
88
94.7
91.3

200.1
157
283.8
245
185.8
218.9
186.3
152
288.7

71.9
56.6
95.3
78.3
60.7

27.3
28.1
26.8
27.6
28.4

339.8
366.4
321.1
350.6
378.2

99.6
107.4
94.1
102.8
110.9

238.7
186.8
318
260.2
200.8

Total Capacity

118.4F (48C)
Sen Capacity

kW
27.5
23.2
18.8
34.3

PI
kW
13.2
13.4
13.6
13.4

MBh
112
122.1
131.6
122.9

kW
32.8
35.8
38.6
36

MBh
92.7
78.3
63.2
115.8

96.6
75.6
132.1
112
85.5
113.6
95.3
76.2
146.3

28.3
22.2
38.7
32.8
25.1
33.3
27.9
22.3
42.9

13.7
14
13.6
13.9
14.3
15.2
15.4
15.4
15.4

134.3
144.9
129.4
141.5
152.4
128.8
140.9
152.5
143

39.4
42.5
37.9
41.5
44.7
37.8
41.3
44.7
41.9

47.1
51.1
44.1
48.5
47.2
51.7
55.9
51.4

123.8
95.1
150.6
136.9
142
118.8
94.5
175.4

36.3
27.9
44.1
40.1
41.6
34.8
27.7
51.4

15.4
15.4
15.4
15.4
17.8
18.1
18.5
18.1

157.4
171.2
147.3
162.3
157.6
172.8
187
171.6

192.5
208.5
183.6
201.6
188.8
206.1
222.1
198.2

56.4
61.1
53.8
59.1
55.3
60.4
65.1
58.1

146.8
112.9
183.6
171.5
171.6
142.3
111.8
198.2

43
33.1
53.8
50.3
50.3
41.7
32.8
58.1

18.5
19.2
18.3
18.9
19.6
20
20.4
19.8

18.3
18.7
18.1
18.6
24.1
24.7
25.2
24.6

216.5
233.2
208.7
227.9
232.7
253.7
273.5
248.4

63.5
68.3
61.2
66.8
68.2
74.4
80.2
72.8

164.2
125.8
208.7
201.3
198.8
166.9
133.4
234.5

48.1
36.9
61.2
59
58.3
48.9
39.1
68.7

58.7
46
83.2
71.8
54.5
64.1
54.6
44.5
84.6

25.2
25.8
25.1
25.7
26.5
28.9
29.5
30.1
29.8

271.3
292.8
265.8
290.7
258.1
281.7
304.1
291.1

79.5
85.8
77.9
85.2
75.6
82.6
89.1
85.3

193.5
151.1
265.8
238.6
210.4
178.5
144.8
280.1

70
54.8
93.2
76.3
58.9

30.6
31.3
30.1
30.9
31.7

318.7
344.6
300
328.8
355.6

93.4
101
87.9
96.4
104.2

230.7
179.5
300
252.2
193.5

125F (52C)
Sen Capacity

kW
27.2
22.9
18.5
33.9

MBh
107.6
117.5
126.8
118.1

kW
31.6
34.4
37.2
34.6

MBh
90.7
76.4
61.4
113.8

kW
26.6
22.4
18
33.3

PI
kW
14.6
14.8
15
14.8

95.6
74.6
129.4
111
84.5
112.3
94.1
75.1
143

28
21.9
37.9
32.5
24.8
32.9
27.6
22
41.9

14.2
14.5
14.1
14.3
14.7
15.7
15.8
15.8
15.8

129.2
139.3
124.2
135.9
146.3
123.4
135.4
147
137.2

37.9
40.8
36.4
39.8
42.9
36.2
39.7
43.1
40.2

93.7
72.7
124.2
109
82.5
109.9
91.9
73.1
137.2

27.5
21.3
36.4
31.9
24.2
32.2
26.9
21.4
40.2

15
15.3
14.9
15.2
15.6
16.6
16.6
16.6
16.6

46.1
50.2
43.2
47.6
46.2
50.6
54.8
50.3

122.6
94.1
147.3
135.7
140.5
117.3
93.2
171.6

35.9
27.6
43.2
39.8
41.2
34.4
27.3
50.3

15.8
15.7
15.8
15.8
18.4
18.7
19
18.7

151.4
141.3
156.1
151.1
166.1
180.2
164.5

44.4
41.4
45.8
44.3
48.7
52.8
48.2

120.4
141.3
133.6
137.6
114.7
90.8
164.5

35.3
41.4
39.1
40.3
33.6
26.6
48.2

16.6
16.6
16.5
19.5
19.7
20
19.7

188.6
179.5
197.4
185
202
217.7
194.1

55.3
52.6
57.9
54.2
59.2
63.8
56.9

145.3
179.5
170.1
170
140.7
110.3
194.1

42.6
52.6
49.9
49.8
41.3
32.3
56.9

19.1
18.8
19.4
20.3
20.6
21.1
20.5

181.3
172.2
189.9
177.7
194.2
209.4
186.3

53.1
50.5
55.7
52.1
56.9
61.4
54.6

142.7
172.2
167.5
166.9
137.8
107.5
186.3

41.8
50.5
49.1
48.9
40.4
31.5
54.6

20.1
19.8
20.4
21.5
21.8
22.2
21.6

20.3
20.8
20.1
20.6
26.9
27.3
27.8
27.2

212.1
228.4
204.3
223.1
227.5
248.4
268.1
242.9

62.2
67
59.9
65.4
66.7
72.8
78.6
71.2

162.6
124.3
204.3
199.7
196.5
164.7
131.5
232.2

47.6
36.4
59.9
58.5
57.6
48.3
38.5
68

20.9
21.5
20.7
21.3
27.7
28.2
28.6
28.1

203.8
219.4
196
214
217.8
238.5
257.9
232.5

59.7
64.3
57.4
62.7
63.8
69.9
75.6
68.2

159.6
121.4
196
196.5
192.1
160.7
127.9
227.8

46.8
35.6
57.4
57.6
56.3
47.1
37.5
66.8

22.1
22.6
21.8
22.4
29.3
29.6
30
29.5

56.7
44.3
77.9
69.9
61.7
52.3
42.4
82.1

27.7
28.3
27.6
28.3
32.4
33
33.6
33.3

265.7
287.1
259.9
284.7
252.1
275.6
297.8
284.4

77.9
84.1
76.2
83.5
73.9
80.8
87.3
83.4

191.4
149.1
259.9
236.5
207.7
175.9
142.4
277.3

56.1
43.7
76.2
69.3
60.9
51.6
41.7
81.3

28.5
29.1
28.4
29
33.6
34.2
34.7
34.4

255.1
276.2
248.9
273.4
241.2
264.4
286.2
272.1

74.8
81
73
80.1
70.7
77.5
83.9
79.7

187.4
145.5
248.9
232.4
202.6
171.2
138.1
272.1

54.9
42.6
73
68.1
59.4
50.2
40.5
79.7

29.9
30.5
29.8
30.4
35.7
36.2
36.6
36.4

67.6
52.6
87.9
73.9
56.7

34
34.5
33.5
34.2
34.8

311.8
337.5
293.1
321.7
348.3

91.4
98.9
85.9
94.3
102.1

228.1
177.1
293.1
249.7
191.1

66.9
51.9
85.9
73.2
56

35
35.5
34.6
35.2
35.7

299.2
324.5
280.5
308.7
335

87.7
95.1
82.2
90.5
98.2

223.4
172.8
280.5
244.9
186.8

65.5
50.6
82.2
71.8
54.8

36.8
37
36.5
36.9
37.1

Table 5

Notes:
1.
2.
3.
4.

Total Capacity

PI
kW
13.7
13.9
14.1
13.9

See page 3 for Legend.


Ratings are based on 80F (27C) DB evaporator entering air dry bulb temperature.
Direct Interpolation is permissible. Do not extrapolate.
SKM Computer Selections are available for quick and accurate selections.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
FAN PERFORMANCE - 60 HZ
PACL

61060

61070

61090

61105

62105

62120

62150

62180

62215

62240

62300

62360

Airflow Rate

Internal Static
Pressure

RPM

External Static Pressure in.wg (Pa)


0.2 (50)

0.4 (100)

0.5 (125)

0.6 (150)

0.8 (200)

1.0 (250)

1.25 (312)

cfm

l/s

in.wg

Pa

RPM

KW

RPM

KW

RPM

KW

RPM

KW

RPM

KW

RPM

KW

RPM

KW

1260

595

0.19

48.16

715

0.15

775

0.18

833

0.20

940

0.25

1039

0.30

1152

0.37

2000

944

0.43

107.66

769

0.34

858

0.39

902

0.42

945

0.45

1029

0.52

1110

0.58

1206

0.67

2521

1190

0.65

161.89

913

0.62

985

0.69

1021

0.72

1057

0.76

1126

0.83

1195

0.91

1278

1.01

1769

835

0.19

48.18

628

0.21

730

0.26

780

0.28

829

0.31

924

0.37

1014

0.43

1120

0.51

2400

1133

0.33

81.76

775

0.46

853

0.52

891

0.55

929

0.58

1004

0.65

1077

0.72

1167

0.82

3538

1670

0.65

161.85

1063

1.33

1117

1.42

1144

1.46

1170

1.51

1223

1.60

1275

1.69

1340

1.81

2064

974

0.19

48.19

609

0.27

659

0.30

707

0.34

799

0.42

885

0.50

983

0.61

3000

1416

0.37

92.27

639

0.51

712

0.59

748

0.64

784

0.68

856

0.77

925

0.87

1010

1.00

4128

1948

0.65

161.87

818

1.20

871

1.30

898

1.36

924

1.41

977

1.53

1030

1.64

1096

1.80

2064

974

0.23

56.22

522

0.21

625

0.28

675

0.32

723

0.35

814

0.43

898

0.51

995

0.62

3000

1416

0.43

107.65

662

0.53

734

0.62

771

0.66

806

0.71

877

0.80

946

0.90

1030

1.03

4128

1948

0.76

188.85

847

1.25

900

1.36

927

1.42

953

1.47

1006

1.59

1059

1.71

1124

1.87

2064

974

0.23

56.22

522

0.21

625

0.28

675

0.32

723

0.35

814

0.43

898

0.51

995

0.62

3000

1416

0.43

107.65

662

0.53

734

0.62

771

0.66

806

0.71

877

0.80

946

0.90

1030

1.03

4128

1948

0.76

188.85

847

1.25

900

1.36

927

1.42

953

1.47

1006

1.59

1059

1.71

1124

1.87

2674

1262

0.19

48.20

511

0.32

553

0.37

594

0.42

671

0.52

742

0.63

823

0.77

4000

1888

0.39

97.08

541

0.63

604

0.74

634

0.79

665

0.85

724

0.98

782

1.11

852

1.28

5347

2523

0.65

161.86

675

1.37

723

1.50

746

1.57

769

1.64

816

1.78

861

1.94

918

2.13

2674

1262

0.23

56.23

437

0.25

525

0.34

566

0.38

607

0.43

682

0.53

752

0.64

833

0.79

4000

1888

0.45

113.26

562

0.67

624

0.77

654

0.83

684

0.89

743

1.02

800

1.15

869

1.33

5347

2523

0.76

188.84

701

1.44

748

1.58

771

1.65

795

1.72

841

1.87

886

2.02

942

2.22

3438

1622

0.2

49.23

647

0.46

704

0.53

758

0.60

858

0.75

948

0.92

1051

1.13

5700

2690

0.48

118.81

703

1.07

783

1.25

822

1.34

862

1.44

938

1.64

1013

1.86

1102

2.14

6875

3244

0.66

165.32

807

1.75

874

1.96

907

2.06

940

2.17

1006

2.40

1070

2.64

1149

2.95

4400

2076

0.2

49.21

643

0.63

693

0.71

742

0.79

836

0.96

924

1.14

1027

1.38

6600

3115

0.4

99.60

706

1.37

776

1.55

811

1.65

846

1.75

915

1.96

983

2.18

1066

2.47

8800

4153

0.66

165.32

888

2.98

941

3.22

967

3.35

994

3.47

1046

3.72

1098

3.99

1163

4.33

5958

2812

0.17

41.18

527

0.78

568

0.87

609

0.98

687

1.20

761

1.44

846

1.76

8000

3775

0.28

68.63

530

1.24

597

1.45

629

1.57

661

1.69

725

1.94

787

2.21

861

2.57

11917

5624

0.56

138.35

721

3.61

767

3.91

790

4.07

812

4.22

857

4.54

903

4.87

958

5.31

5958

2812

0.2

49.21

540

0.81

582

0.91

622

1.01

700

1.24

772

1.48

857

1.80

8000

3775

0.33

82.01

548

1.29

614

1.51

647

1.63

679

1.75

742

2.01

803

2.29

877

2.65

11917

5624

0.66

165.33

746

3.77

792

4.08

814

4.23

837

4.39

881

4.71

958

5.31

980

5.48

5958

2812

0.2

49.21

540

0.81

582

0.91

622

1.01

700

1.24

772

1.48

857

1.80

10000

4719

0.49

121.37

648

2.33

701

2.60

728

2.73

754

2.87

806

3.16

857

3.47

920

3.87

11917

5624

0.66

165.33

746

3.77

792

4.08

814

4.23

837

4.39

881

4.71

958

5.31

980

5.48

Range
50 Hz
709
to
937
718
to
950

641
to
814

544
to
691

716
to
910

548
to
696

645
to
819
Table 6

Areas shaded in blue indicate factory setting of rpm.


Areas shaded in grey indicate operating range outside the standard motor. Shift to larger motor size in this area.
Internal static pressure is based on pressure drops through evaporator coil and fan casing.
The shown rpm range is with standard pulleys combination.

10

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
ELECTRICAL DATA

POWER SUPPLY 380V/3PH/60HZ


Model
PACL
61060
61070
61090
61105
62105
62120
62150
62180
62215
62240
62300
62360

Unit Characteristic
MFA
32
32
40
50
40
50
50
63
80
80
125
160

MCA
18
20
25
29
26
32
37
42
53
61
76
93

Compressor
QTY
1
1
1
1
2
2
2
2
2
2
2
1+ 1

MCC
15
15
17
23
13
15
15
17
23
26
34
50+40

RLA
11
12
15
18
9
11
13
15
18
20
27
38+29

Condenser Fan motor


LRA
75
70
100
123
54
75
70
100
123
140
145
196+139

QTY
1
1
2
2
2
2
2
2
2
2
2
2

FLA
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
2.4
3.2
3.2
3.2

LRA
4.0
4.0
4.0
4.0
4.0
4.0
4.4
4.4
11.0
16.0
16.0
16.0

Evaporator Fan Motor


FLA
1.6
1.9
2.6
2.6
2.6
3.4
3.4
4.9
4.9
6.7
6.7
8.4

LRA
6.0
7.5
10.3
10.3
10.3
15.3
15.3
22.8
22.8
31.3
31.3
44
Table 7

POWER SUPPLY 460V/3PH/60HZ


Model
PACL
61060
61070
61090
61105
62105
62120
62150
62180
62215
62240
62300
62360

Unit Characteristic
MFA
25
32
40
40
32
40
50
50
63
80
100
125

MCA
16
18
22
25
24
27
32
37
46
52
64
80

Compressor
QTY
1
1
1
1
2
2
2
2
2
2
2
1+1

MCC
12
14
17
23
11
12
14
17
23
24
29
39+35

RLA
9
11
13
15
8
9
11
13
15
17
22
31+25

Condenser Fan motor


LRA
60
75
100
95
50
60
75
100
95
114
125
179+150

QTY
1
1
2
2
2
2
2
2
2
2
2
2

FLA
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
2.4
3.2
3.2
3.2

LRA
5.0
5.0
5.0
5.0
5.0
5.0
6.0
6.0
13.0
18.0
18.0
18.0

Evaporator Fan Motor


FLA
1.6
1.7
2.3
2.3
2.3
3.4
3.4
4.5
4.5
6.2
6.2
7.8

LRA
7.0
8.7
12.0
12.0
12.0
18.0
18.0
26.3
26.3
36.5
36.5
51.0
Table 8

Air Conditioning Equipment . Built in the Gulf... for the World

11

SKM Packaged Airconditioning Units


PAC-L Series - R22
ELECTRICAL DATA

POWER SUPPLY 220V/3PH/60HZ

Unit Characteristic

Model
PACL

MFA
50
63
80
80
63
80
100
100
125
160
200
250

61060
61070
61090
61105
62105
62120
62150
62180
62215
62240
62300
62360

Compressor

MCA
30
34
43
49
48
53
64
74
90
103
131
162

QTY
1
1
1
1
2
2
2
2
2
2
2
1+1

MCC
24
29
35
45
22
24
29
35
45
47
66
82+75

Condenser Fan motor

RLA
18
21
25
30
16
18
22
25
30
34
46
63+53

LRA
124
156
164
195
91
124
156
164
195
225
245
340+300

QTY
1
1
2
2
2
2
2
2
2
2
2
2

FLA
2.5
2.5
2.5
2.5
2.5
2.5
3.3
3.3
6.0
7.0
7.0
7.0

Evaporator Fan Motor

LRA
10.0
10.0
10.0
10.0
10.0
10.0
13.0
13.0
28.0
32.0
32.0
32.0

FLA
2.8
3.4
4.5
4.5
4.5
5.9
5.9
8.3
8.3
11.5
11.5
14.7

LRA
10.4
13
17.8
17.8
17.8
26.5
26.5
39.5
39.5
54.2
54.2
76.2
Table 9

Voltage imbalance between phases to be <2%

Legend
MCC Maximum Continuous Current corresponding to the cutout
amps of internal motor protector.
MCA Minimum Circuit Amps for wire sizing
MFA Maximum Fuse Amps for Fuse sizing
RLA Rated Load Amps
FLA Full Load Amps
LRA Locked Rotor Amps

Typical Wiring Diagram


**

L1
L2
L3
N

POWER SUPPLY (V/Ph/Hz)

PTB

L EGEN D
C1

C2

C3

OL2

OL3

**

CONTACTOR

PROVIDE OVERCURRENT, EARTH FAULT PROTECTION,


SHORT CIRCUIT AND DISCONNECT
AS REQUIRED
BY
CCH MEANS
CRANK
CASE HEATER
LOCAL & NATIONAL ELECTRIC CODE.

CF
T1

T3

L E GCFM
EN D

T2

EFM

CFM

CF2

2A

4A

CSCONTROL CONTROL
SWITCH
FUSE

CFM

CONDENSER
FAN MOTOR
EFM
EVAPORATOR
FAN MOTOR

CS
EFM
FCS
HPS

C1

TH (BY OTHERS)

CS

Y
C1

C3

FAN CYCLING SWITCH

LPS

LOW PRESSURE SWITCH

HIGH PRESSURE SWITCH

OVERLOAD RELAY
PTB
POWER TERMINAL BLOCK

PTB

POWER TERMINAL BLOCK

TFR

TFR
TRANSFORMER
TRANSFORMER

TH

THTHERMOSTAT
THERMOSTAT
TIME DELAY RELAY

TDR
TIME DELAY RELAY
FIELD WIRING AND
FIELD SUPPLIED
-----FIELDDEVICES
WIRING AND

HPS

FIELD SUPPLIED DEVICES

24V

220V

CCH

EVAPORATOR
FANPRESSURE
MOTOR
HPS
HIGH
SWITCH

OL

MODEL: PACL-61060 & 61070

OL2
LPS

OL3
CR2

CR1

N
E

12

FAN CYCLING SWITCH

CONTROL SWITCH

OLLOW PRESSURE
OVERLOAD
SWITCH RELAY

-----CR1

COMPRESSOR MOTOR

FCS

LPS

TDR
TFR

CRANK CASE HEATER

CF

CM
CF1

CONDENSER FAN MOTOR

CMCONTACTOR
COMPRESSOR MOTOR

CCH

CM

CONTROL FUSE

CONTROL CIRCUIT

CR2

C3

TDR

WIRING DIAGRAM SHOWN IN


* TYPICAL
SUITABLE FOR 380V/3Ph/60Hz ONLY.

TYPICAL WIRING DIAGRAM SHOWN IN


SUITABLE FOR 380V/3Ph/60Hz ONLY.

FOR 220V/3Ph/60Hz & 460V/3Ph/50Hz


PLEASE CONSULT SKM.

TDR

FOR 220V/3Ph/60Hz & 460V/3Ph/50Hz


PLEASE CONSULT SKM.

C1

C2

OVERCURRENT, EARTH FAULT PROTECTION,


** PROVIDE
SHORT CIRCUIT AND DISCONNECT MEANS AS REQUIRED BY
LOCAL & NATIONAL ELECTRIC CODE.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
Typical Wiring Diagram
PAC-L Models: 61090 & 61105
**

POWER SUPPLY (V/Ph/Hz)

PTB

L1
L2
L3
N

C1

C2

T1

T3

C3

OL2

T2

OL3

CFM1

CM

C4

CF1

CF2

2A

4A

OL4

EFM

CFM2

MODEL: PACL- 61090 & 61105

C1

CS
TH (BY OTHERS)

C1

Y
C4

CR1

HPS

FCS

24V

CCH

220V

TFR

LPS
OL2

OL3

OL4
CR2

CR1

C4

CR2

TDR

C1

TDR

C2

C3

N
E

CONTROL CIRCUIT

PAC-L Models: 62105, 62120, 62150, 62180, 62215, 62240 & 62300
POWER SUPPLY (V/Ph/Hz)

PTB

L1
L2
L3
N

**
C1

C2

T1

T3

T1

T3
T2

T2

CM1

C3

C4

C5

OL3

OL4

OL5

PROVID
SHORT
LOCAL

EFM

CFM2

CFM1

CM2

L EGEN D
C

CONTACTOR

CCH

CRANK CASE HEATER

CF

CONTROL FUSE

CFM

CONDENSER FAN MOTOR

CM

COMPRESSOR MOTOR

CS

CONTROL SWITCH

EFM

EVAPORATOR FAN MOTOR

FCS

FAN CYCLING SWITCH

HPS

HIGH PRESSURE SWITCH

LPS

LOW PRESSURE SWITCH

CF2

CF1

10A

2A

C1

C2

Y1

C1

CS2

CS1

TH (BY OTHERS)

C2

OL

OVERLOAD RELAY

PTB

POWER TERMINAL BLOCK

TFR

TRANSFORMER

Y2

C5

C5

TFR

TH

THERMOSTAT

TDR

TIME DELAY RELAY

------

FIELD WIRING AND

CR1
HPS2
M

24V

220V

CCH2

HPS1
CCH1

**

FCS

FIELD SUPPLIED DEVICES


LPS2

LPS1

OL3

WIRING DIAGRAM SHOWN IN


* TYPICAL
SUITABLE FOR 380V/3Ph/60Hz ONLY.

OL4

OL5

CR2

CR1

CR2

CR3

C5

TDR1

TDR1

CR3

C1

TDR2

TDR2

FOR 220V/3Ph/60Hz & 460V/3Ph/50Hz


M PLEASE CONSULT SKM.
C2

C3

C4

N
E

CONTROL CIRCUIT

OVERCURRENT, EARTH FAULT PROTECTION,


** PROVIDE
SHORT CIRCUIT AND DISCONNECT MEANS AS REQUIRED BY
LOCAL & NATIONAL ELECTRIC CODE.

Air Conditioning Equipment . Built in the Gulf... for the World

13

SKM Packaged Airconditioning Units


PAC-L Series - R22
Typical Wiring Diagram
PAC-L Models: 62360
** L1
L2

POWER SUPPLY (V/Ph/Hz)

PTB

L3
N
C1

C2

T2

T1

MPM1
CF1
2A

T2 T1 S2 S1 M1 M2

T2

T1

MPM2

T3

C4

C5

OL3

OL4

OL5

T3

T2 T1 S2 S1 M1 M2

CM1

C3

CM2

TO
CONTROL
CIRCUIT

CFM1

CFM2

EFM

TO
CONTROL
CIRCUIT

CF2
10A

MODEL: PACL- 62360


C1

C2

CS1

TH (BY OTHERS)

Y1

CS2

C1

C2

Y2

C5

C5

M1

M1

CR1
M2

M2

HPS1

HPS2

24V

100VA

220V

CCH2

CCH1

TFR
M

LPS1

FCS

LPS2
OL3

OL4

OL5

TDR1

TDR2

CR2

CR1

CR2

C5

CR3

CR3

C1

TDR1

C2

TDR2

C3

C4

N
E

CONTROL CIRCUIT

Dimensional Data
PAC-L Models: 61060 & 61070
10
[254]

10
[254]

2
[51]

A1

A3

4
3
AIR IN

A4
DRAIN
2 x FPT 3/4 [19]

42.5
[1079]

30
[762]

22
[559]

4.2
[106]

44.25
[1124]

61070

50.6
[1285]

38.6
[979]

24
[610]

5.8
[148]

47.9
[1216]

1
[25]

AIR IN

A
=

13.03
[331]

ACCESS PANEL
FOR COMPRESSOR
POWER SOURCE
HOLE 1[25]
CONTROL CIRCUIT
HOLE 0.75 [19]

10.8
[275]

RIGGING HOLES
0.79 [20] x 4Nos.
ACCESS PANEL
ON BOTH SIDES

H
B
5.5
[140]

R/A

5
[126]

Air Conditioning Equipment . Built in the Gulf... for the World

3.94
[100]

S/A

1
44.25
[1124]
40.31
[1024]

61060

22
[559]

AIR OUT

14

1.2
[30]

59
[1499]

C 11.38
[289]

A2
4-0.79 [20] HOLES
FOR ANCHOR BOLTS

DIMENSIONS

MODEL
PACL-

SKM Packaged Airconditioning Units


PAC-L Series - R22
Dimensional Data
PAC-L Models: 61090, 61105 & 62105
10
[254]

2
[51]

A1

10
[254]

A3

LEGEND
1 CONTROL PANEL
2 COMPRESSOR

3 CONDENSER FAN
4 CONDENSER COIL
5 EVAPORATOR COIL

6 EVAPORATOR FAN
7 EVAPORATOR FAN MOTOR
ALL DIMENSIONS ARE IN INCHES [MM]
A2

DRAIN
2 x FPT 3/4 [19]
28
[711]
6

AIR OUT

1
[25]

1.2
[30]

67.5
[1714]

S/A

8
[203]

50.6
[1285]
38.6
[980]
15.55
[395]

4
[102]

7.6 13.43
[341]

4-0.79 [20] HOLES


FOR ANCHOR BOLTS

MODEL:PACL- 62105 WITH TWO COMPRESSOR

A4

55.7
[1414]

AIR IN

13.8
[351]

ACCESS PANEL
FOR COMPRESSOR

RIGGING HOLES
0.79 [20] x 4Nos.

3.94
[100]

5.5
[140]

R/A

28
[711]

5
5
[126]

[1227]

52.25
[1327]
48.31

[192]

ACCESS PANEL
ON BOTH SIDES
CONTROL CIRCUIT
HOLE 0.75 [19]

POWER SOURCE
HOLE 1[25]

PAC-L Models: 62120 & 62150


10
[254]
A1

4-0.79 [20] HOLES


FOR ANCHOR BOLTS

10
[254]
A3

4
LEGEND
1 CONT RO L PANEL
2 COMPRESSOR
3 CONDENSER FAN

4 CONDENSER COIL
5 EVAPO RATOR COIL
6 EVAPO RATO R FAN
7 EVAPO RATOR FAN MO TOR
ALL DIMENSIO NS ARE IN INCHES [M M]

3
A4

8.5

[216]

2
RIGGING HOLES
[20]
0.79
x 4Nos.

7
ACCESS PANEL
ON BOTH SIDES

13.8
[351]

25
[635]
5.5
[140]

R/A

5
5
[126]

52.25
[1327]
48.31
[1227]

S/A

AIR IN

15.9
[404]

AIR OUT

75
[1905]
56
[1423]
18.5
[471]

56.1
[1425]

30
[762]

DRAIN
2 x FPT 1[25]
1
[25]

3.94
[100]

77
[1956]

1.2
[30]

A2

Air Conditioning Equipment . Built in the Gulf... for the World

15

SKM Packaged Airconditioning Units


PAC-L Series - R22
Dimensional Data
PAC-L Models: 62180 - 62360
MODEL: PACL- 62180 to 62360
10
[254]
A1

10
[254]

4-0.79 [20] HOLES


FOR ANCHOR BOLTS

A3

POWER
SOURCE

CONTROL
CIRCUIT

* MO DEL WITH DOWNWARD CONDENSER FAN

DETAIL AT `A'

ALL DIM ENSIO NS ARE IN INCHES [M M]

MODEL
PACL1

75
75
60
[1905] [1905] [1524]

30
[762]

28
[711]

13.43
[341]

43.7
57.6
[1109] [1464]

7.5
[191]

62215

75
75
64
[1905] [1905] [1626]

36
[914]

28
[711]

13.43
[341]

43.7
63.6
[1109] [1616]

7.5
[191]

62240

101.6
88
78
40
[2581] [2235] [1981] [1016]

38.6
[981]

15.91
[404]

52.3
71.1
[1328] [1806]

8.5
[216]

62300

101.6
88
78
40
[2581] [2235] [1981] [1016]

38.6
[981]

15.91
[404]

52.3
71.1
[1328] [1806]

8.5
[216]

62360

101.6
88
78
40
[2581] [2235] [1981] [1016]

38.6
[981]

15.91
[404]

52.3
71.1
[1328] [1806]

8.5
[216]

A4

2
[51]

DRAIN
2 x FPT 1[25]
1
[25]

D
6

A
=

S/A

W
1.2
[30]

*62180

A2

DIMENSIONS
L

AIR IN
R/A

2
RIGGING HOLES
0.79 [20] x 4Nos.

ACCESS PANEL
ON BOTH SIDES

13.8
[351]

5.5
[140]

3.94
[100]

5
[126]

48.31
[1227]

57.96
[1472]

Loading Points & Weights


TOTAL
WEIGHT

MODEL
PACL -

166
[75]

687
[312]

62150

169
[77]

170
[77]

701
[318]

62180

379
[172]

372
[169]

286
[130]

269
[122]

1306
[592]

248
[112]

189
[86]

182
[83]

820
[372]

62215

447
[203]

438
[199]

325
[147]

310
[141]

1520
[689]

219
[99]

274
[124]

202
[92]

198
[90]

893
[405]

62240

476
[216]

467
[212]

350
[159]

332
[151]

1625
[737]

62105

260
[118]

286
[130]

224
[102]

215
[98]

985
[447]

62300

507
[230]

501
[227]

406
[184]

393
[178]

1807
[820]

62120

271
[123]

302
[137]

253
[115]

245
[111]

1071
[486]

62360

575
[261]

566
[257]

464
[210]

447
[203]

2052
[931]

MODEL
PACL -

LOAD AT EACH POINT Lbs [kg]


A2
A3
A4
A1

61060

163
[74]

196
[89]

162
[73]

61070

166
[75]

196
[89]

61090

201
[91]

61105

LOAD AT EACH POINT Lbs [kg]


A1
A2
A3
A4
286
271
340
337
[154]
[153]
[130]
[123]

A1-A4 ARE LOADING POINTS 0.79 [20]

16

Air Conditioning Equipment . Built in the Gulf... for the World

TOTAL
WEIGHT
1234
[560]

SKM Packaged Airconditioning Units


PAC-L Series - R22
Recommended Clearances
A

MODEL
PACL- 61060

44
[1118]

PACL- 61070
PACL- 61090, 61105 &
62105

52
[1321]

34
[864]

42
[1067]

72
[1829]

SPACING FOR AIR FLOW

SPACING FOR SERVICE


A

88
[2235]

[762]

DUCT

DUCT

30
[762]

30
[762]

30

DUCT

ALL DIMENSIONS ARE IN INCHES[MM]

PACL- 61060/61070

A
PACL- 61060/61070

DUCT

30
[762]

[762]

30

[762]

DUCT

30

DUCT

A
PACL- 61090 to 62105

SINGLE UNIT

A
PACL- 61090 to 62105
MULTIPLE UNIT

Air Conditioning Equipment . Built in the Gulf... for the World

17

SKM Packaged Airconditioning Units


PAC-L Series - R22
Recommended Clearances
A

SPACING FOR AIR FLOW

SPACING FOR SERVICE


30
[762]

DUCT

DUCT

30
[762]

DUCT

30
[762]

PACL- 62120/62150

MODEL

60
[1524]

PACL- 62120 /62150


PACL- 62180

52
[1321]

PACL- 62215

PACL- 62120/62150

64
[1626]

88
[2438]

68
[1727]

82
[2083]

PACL- 62240/62300/62360

30
[762]

DIMENSIONS ARE IN INCHES [MM]

DUCT

DUCT

DUCT

30
[762]

30
[762]

PACL- 62180 to 62360

SINGLE UNIT
PACL- 62180 to 62360

MULTIPLE UNIT

18

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22
Installation and Commissioning

Install the unit in such a location which is flat and strong enough to support its weight.

Provide a trap of over 2" (50mm) in the drain piping for water seal.

All field wiring must comply with applicable local and national codes.

Connect supply and return ducts as shown.

Service spacing should be provided as shown in the figure. If any obstacles are around the unit, distributed air is short-circuited
so that the unit stops frequently and access to the unit is difficult for inspection and aftersales services.
INSTALLATION & COMMISSIONING
CO NTR O L
P AN EL BO X

3000

No obstacle

SPACING FOR AIRFLOW

POWER
SO U R CE
C O NTR O L
C IR CU IT

A IR IN

SPACING FOR SERVICE

S .A IR
A IR IN

R .AIR

PACL- 61090, 61105 & 62105

C O NTR O L
P AN EL BO X
AIR O U T

3000

No obstacle

PACL- 61060/61070

POWER
SO U RCE
CO N TRO L
CIR C U IT
AIR O U T

A IR IN

S. AIR

No obstacle

AIR IN

3000

A IR IN
AIR OUT

C O NTR O L
P ANE L B O X

AIR IN

CO NT RO L
CIR CU IT

R.A IR

AIR OUT
PO W E R
S O U R CE

AIR IN

S.AIR

R.AIR

AIR IN

PACL- 62120 & 62150


3000

No obstacle

AIR OUT

CONTROL
PANEL BOX

AIR IN
AIR IN

C O NTR O L
C IR CU IT

AIR OUT
PO W E R
S O U R CE

AIR IN

S.AIR

S.AIR

R.AIR

PACL- 62180 to 62360

Air Conditioning Equipment . Built in the Gulf... for the World

19

SKM Packaged Airconditioning Units


PAC-L Series - R22
GUIDE SPECIFICATIONS
GENERAL

EVAPORATOR FAN(S) & MOTOR

Packaged Air Conditioners shall be composed of


compressor(s), condenser & evaporator coils with fans, refrigerant
piping, electrical components & enclosing cabinet in one piece.
These units shall be factory assembled, internally wired, fully
refrigerant charged with R22, tested under strict quality standards
& are suitable for outdoor installation on rooftop or ground level
with ducted system. These units shall be capable to operate
from 50 F (10C) to 125 F (52C) ambient temperature without
failure & shall be rated in accordance with AHRI-340/360 and
AHRI- 210/240 standards. Capacity as per attached schedule.

Fans of evaporators shall be forward curved, double inlet double


width (DIDW), centrifugal type, statically & dynamically balanced,
mounted on a single heavy duty shaft with permanently lubricated
bearings & driven by V belt with an adjustable variable pitch
motor pulley. Motor shall be Totally Enclosed Fan Cooled (TEFC),
4 poles, class-F insulated, minimum IP55 protection & wired to
unit control panel.

COMPRESSOR(S)
Compressor shall be hermetically sealed, compact high efficiency
and low noise scroll type. These compressors are refrigerant gas
cooled, furnished with advanced scroll temperature protection
or internal motor protection.

REFRIGERANT PIPING
Refrigerant circuit piping shall be fabricated from ACR
grade copper including shut-off valve, filter drier & thermostatic
expansion valve. Suction line shall be insulated with
(12 mm) wall thickness enclosed cell pipe insulation
with maximum k factor 0.28 Btu.in/ft2 hf (0.040 W / m k).

CASING
CONDENSER COIL(S)
Condenser coils shall be air cooled with integral sub cooler,
constructed of special inner grooved seamless copper tubes
3/8 OD mechanically expanded into waffle louver aluminum
cross . These coils shall be tested against leakage by air pressure
of 450 psig (3100 kPa) under water, cleaned & dehydrated at
the factory.

CONDENSER FAN(S) & MOTOR(S)


Condenser Fans shall be direct driven propeller type discharging
air vertically upward, equipped with statically & dynamically
balanced aluminum alloy blades, inherent corrosion resistant
shaft & PVC coated steel wire fan guard. Condenser fan
motor(s) shall be Totally Enclosed Air Over (TEAO), 6 poles
with class-F insulation, minimum IP55 protection & wired to
unit control panel.

FILTER SECTION
Flat Filter Section incorporating 1 (25mm) or 2 (50mm)
thick filter having an average arrestance efficiency of 54% as
per ASHRAE Standard 52.1 or equivalent can be provided, if
desired.

CONTROL PANEL

EVAPORATOR COIL
Evaporator coil shall be constructed of inner grooved copper
tubes 3/8 OD mechanically bonded to aluminum (copper) crosswave fins. Coil consists of headers of seamless copper tubing,
thermostatic expansion valve(s) & multi-circuited distributor(s).
These coils shall be tested against leakage by air pressure of
300 psig (2068 kPa) under water, cleaned & dehydrated at the
factory. Coil shall conform to AHRI-410.

20

Casing shall be made of hot dip galvanized (zinc coated),


phosphatized steel sheets which are then electrostatically
polyester powder coated to provide an extremely tough, scratch
resistance & excellent anti-corrosive protection. Casing shall
pass1000 hours in 5% salt spray testing at 95F (35C) &
95% relative humidity as per ASTM B117. Evaporator section
shall be sealed with vinyl gaskets & completely insulated
faced with black glass tissue (BGT) heavy density, fire retardant,
permanent odorless fiberglass insulation of minimum
1 (25 mm) thickness and 32 kg/m3 density having maximum
k factor 0.23 Btu.in/ft2 hf. (0.033 W / m k). Unit casing shall be
provided with access panels for easy service and maintenance
of all unit parts.

The panel shall be factory wired and conforms to IP54


requirements. Control Panel shall contain individual electrical
components, contactors, overload relays, transformer,
anti-recycling time delay relay, control circuit disconnect switch,
power & control circuit terminal blocks & High / low pressure
switch.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Packaged Airconditioning Units


PAC-L Series - R22