Technical Manual
Type: CIMR-AUA
Models: 200 V Class: 0.4 to 110 kW (3/4 to 175 HP ND)
400 V Class: 0.4 to 630 kW (3/4 to 1000 HP ND)
600 V Class: 0.75 to 185 kW (1 to 250 HP ND)
To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
Receiving
Mechanical Installation
Electrical Installation
Parameter Details
Troubleshooting
Specifications
Parameter List
MEMOBUS/Modbus
Communications
Standards Compliance
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u Quick Reference
Easily Set Parameters for Specific Applications
Preset parameter defaults are available for setting up applications. Refer to Application Selection on
page 132.
<99> PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooo.
Perform Auto-Tuning
Automatic tuning sets motor parameters. Refer to Auto-Tuning on page 135.
Maintenance Check Using Drive Monitors
Use drive monitors to check if fans, capacitors, or other components require maintenance. Refer to Performance Life Monitors Maintenance
Monitors on page 403.
Fault Display and Troubleshooting
Refer to Drive Alarms, Faults, and Errors on page 342 and Refer to Troubleshooting without Fault Display on page 388.
Standards Compliance
Refer to European Standards on page 630 and Refer to UL and CSA Standards on page 638 <1> .
<1> CE marking applies to 200 V class and 400 V class models only.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Table of Contents
QUICK REFERENCE ....................................................................................... 3
i. PREFACE & GENERAL SAFETY.................................................................. 17
i.1
Preface ....................................................................................................................... 18
Applicable Documentation....................................................................................................... 18
Symbols................................................................................................................................... 18
Terms and Abbreviations ........................................................................................................ 19
Trademarks ............................................................................................................................. 19
i.2
1. RECEIVING .................................................................................................... 29
1.1 Section Safety............................................................................................................ 30
1.2 General Description .................................................................................................. 31
A1000 Model Selection ........................................................................................................... 31
Control Mode Selection ........................................................................................................... 32
2. MECHANICAL INSTALLATION..................................................................... 51
2.1 Section Safety............................................................................................................ 52
2.2 Mechanical Installation ............................................................................................. 54
Installation Environment .......................................................................................................... 54
Installation Orientation and Spacing........................................................................................ 54
Precautions and Instructions for Installation of Models CIMR-Ao4A0930 and 4A1200 ......... 56
Digital Operator Remote Usage .............................................................................................. 57
Exterior and Mounting Dimensions ......................................................................................... 61
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Table of Contents
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Table of Contents
Table of Contents
5.2 b: Application.....................................................................................................................162
b1: Operation Mode Selection......................................................................................................... 162
b2: DC Injection Braking and Short Circuit Braking......................................................................... 169
b3: Speed Search............................................................................................................................ 172
b4: Delay Timers ............................................................................................................................. 177
b5: PID Control................................................................................................................................ 177
b6: Dwell Function........................................................................................................................... 187
b7: Droop Control (CLV, CLV/PM) .................................................................................................. 188
b8: Energy Saving ........................................................................................................................... 189
b9: Zero Servo................................................................................................................................. 191
5.3 C: Tuning............................................................................................................................192
C1: Acceleration and Deceleration Times ....................................................................................... 192
C2: S-Curve Characteristics............................................................................................................ 194
C3: Slip Compensation.................................................................................................................... 194
C4: Torque Compensation .............................................................................................................. 197
C5: Automatic Speed Regulator (ASR) ........................................................................................... 199
C6: Carrier Frequency..................................................................................................................... 204
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Table of Contents
H2: Multi-Function Digital Outputs................................................................................................... 259
H3: Multi-Function Analog Inputs .................................................................................................... 269
H4: Multi-Function Analog Outputs ................................................................................................. 275
H5: MEMOBUS/Modbus Serial Communication ............................................................................. 276
H6: Pulse Train Input/Output........................................................................................................... 277
6. TROUBLESHOOTING.......................................................................................... 333
6.1 Section Safety....................................................................................................................334
6.2 Motor Performance Fine-Tuning ......................................................................................336
Fine-Tuning V/f Control and V/f Control with PG............................................................................. 336
Fine-Tuning Open Loop Vector Control .......................................................................................... 337
Fine-Tuning Closed Loop Vector Control ........................................................................................ 338
Fine-Tuning Open Loop Vector Control for PM Motors................................................................... 339
Fine-Tuning Advanced Open Loop Vector Control for PM Motors.................................................. 340
Fine-Tuning Closed Loop Vector Control for PM Motors ................................................................ 340
Parameters to Minimize Motor Hunting and Oscillation .................................................................. 341
Table of Contents
Alarm and Error Displays ................................................................................................................ 343
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Table of Contents
Cooling Fan Replacement: 2A0018 to 2A0081, 4A0007 to 4A0044, and 5A0006 to 5A0032 ........ 409
Cooling Fan Replacement: 2A0110, 2A0138, 4A0058, 4A0072, 5A0041, and 5A0052 ................. 411
Cooling Fan Replacement: 4A0088 and 4A0103 ............................................................................ 413
Cooling Fan Replacement: 2A0169 to 2A0415, 4A0139 to 4A0362, and 5A0062 to 5A0242 ........ 415
Cooling Fan Replacement: 4A0414 ................................................................................................ 419
Cooling Fan Replacement: 4A0515 and 4A0675 ............................................................................ 421
Cooling Fan Replacement: 4A0930 and 4A1200 ............................................................................ 425
Section Safety....................................................................................................................436
Drive Options and Peripheral Devices ............................................................................437
Connecting Peripheral Devices .......................................................................................439
Option Card Installation....................................................................................................440
Installing Option Cards .................................................................................................................... 440
Installation Procedure...................................................................................................................... 440
11
Table of Contents
Altitude Derating.............................................................................................................................. 473
B.4 b: Application.....................................................................................................................481
b1: Operation Mode Selection......................................................................................................... 481
b2: DC Injection Braking and Short Circuit Braking......................................................................... 482
b3: Speed Search............................................................................................................................ 483
b4: Timer Function .......................................................................................................................... 484
b5: PID Control................................................................................................................................ 484
b6: Dwell Function........................................................................................................................... 486
b7: Droop Control ............................................................................................................................ 486
b8: Energy Saving ........................................................................................................................... 487
b9: Zero Servo................................................................................................................................. 488
B.5 C: Tuning............................................................................................................................489
C1: Acceleration and Deceleration Times ....................................................................................... 489
C2: S-Curve Characteristics............................................................................................................ 490
C3: Slip Compensation.................................................................................................................... 490
C4: Torque Compensation .............................................................................................................. 491
C5: Automatic Speed Regulator (ASR) ........................................................................................... 492
C6: Carrier Frequency..................................................................................................................... 494
B.6 d: References.....................................................................................................................495
d1: Frequency Reference................................................................................................................ 495
d2: Frequency Upper/Lower Limits ................................................................................................. 496
d3: Jump Frequency........................................................................................................................ 496
d4: Frequency Reference Hold and Up/Down 2 Function............................................................... 497
d5: Torque Control .......................................................................................................................... 498
d6: Field Weakening and Field Forcing........................................................................................... 498
d7: Offset Frequency....................................................................................................................... 499
B.8 F: Options...........................................................................................................................505
F1: PG Speed Control Card (PG-X3/PG-B3) .................................................................................. 505
F2: Analog Input Card (AI-A3)......................................................................................................... 507
F3: Digital Input Card (DI-A3).......................................................................................................... 507
F4: Analog Monitor Card (AO-A3) ................................................................................................... 508
F5: Digital Output Card (DO-A3) ..................................................................................................... 508
F6, F7: Communication Option Card............................................................................................... 509
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Table of Contents
H2: Multi-Function Digital Outputs................................................................................................... 518
H3: Multi-Function Analog Inputs .................................................................................................... 521
H4: Analog Outputs ......................................................................................................................... 523
H5: MEMOBUS/Modbus Serial Communication ............................................................................. 524
H6: Pulse Train Input/Output........................................................................................................... 525
B.15 U: Monitors.........................................................................................................................548
U1: Operation Status Monitors ........................................................................................................ 548
U2: Fault Trace................................................................................................................................ 550
U3: Fault History.............................................................................................................................. 551
U4: Maintenance Monitors .............................................................................................................. 552
U5: PID Monitors ............................................................................................................................. 554
U6: Operation Status Monitors ........................................................................................................ 555
U8: DriveWorksEZ Monitors............................................................................................................ 556
13
Table of Contents
Yaskawa SST4 Series IPM Motor (For Constant Torque) .............................................................. 586
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Table of Contents
CSA Standards Compliance............................................................................................................ 647
Drive Motor Overload Protection ..................................................................................................... 647
Precautionary Notes on External Heatsink (IP00/Open Type Enclosure) ....................................... 649
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
15
Table of Contents
16
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
i
Preface & General Safety
This section provides safety messages pertinent to this product that, if not heeded, may result in fatality,
personal injury, or equipment damage. Yaskawa is not responsible for the consequences of ignoring
these instructions.
i.1
i.2
PREFACE...............................................................................................................18
GENERAL SAFETY...............................................................................................20
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
17
i.1 Preface
i.1
Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and
application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no
responsibility for the way its products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all
controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment
designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and
instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to
the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and
specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED.
Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its
products.
This manual is designed to ensure correct and suitable application of A1000-Series Drives. Read this manual before attempting
to install, operate, maintain, or inspect a drive and keep it in a safe, convenient location for future reference. Be sure you
understand all precautions and safety information before attempting application.
u Applicable Documentation
The following manuals are available for A1000 series drives:
A1000
CIMR-AU5A0009FAA
u Symbols
Note: Indicates a supplement or precaution that does not cause drive damage.
TERMS
18
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
i.1 Preface
u Trademarks
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
19
i.2
General Safety
General Precautions
The diagrams in this manual may be indicated without covers or safety shields to show details. Replace the covers or shields before
operating the drive and run the drive according to the instructions described in this manual.
Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to
which this manual is applicable.
The products and specifications described in this manual or the content and presentation of the manual may be changed without notice
to improve the product and/or the manual.
When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales
office and provide the manual number shown on the front cover.
If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.
WARNING
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according
to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result
in serious or fatal injury or damage to the products or to related equipment and systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
20
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u Safety Messages
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in
this manual.
WARNING
Sudden Movement Hazard
System may start unexpectedly upon application of power, resulting in death or serious injury.
Clear all personnel from the drive, motor and machine area before applying power. Secure covers, couplings, shaft keys and
machine loads before applying power to the drive.
When using DriveWorksEZ to create custom programming, the drive I/O terminal functions change from factory
settings and the drive will not perform as outlined in this manual.
Unpredictable equipment operation may result in death or serious injury.
Take special note of custom I/O programming in the drive before attempting to operate equipment.
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
21
WARNING
Crush Hazard
Do not use this drive in lifting applications without installing external safety circuitry to prevent accidental dropping
of the load.
The drive does not possess built-in load drop protection for lifting applications.
Failure to comply could result in death or serious injury from falling loads.
Install electrical and/or mechanical safety circuit mechanisms independent of drive circuitry.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Install adequate branch circuit short circuit protection per applicable codes.
Failure to comply could result in damage to the drive.
The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac
maximum (200 V Class), 480 Vac maximum (400 V Class), and 600 Vac maximum (600 V Class) when protected by
Bussmann Type FWH or FWP fuses as specified in Installing Fuses on the Input Side on page 630.
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
22
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Power Supply
Capacity (kVA)
600
Reactor
unnecessary
60
400
Drive Capacity
For specialized motors, make sure that the motor rated current is less than the rated output current for the drive.
When running more than one motor in parallel from a single drive, the capacity of the drive should be larger than [total motor
rated current 1.1].
Starting Torque
The overload rating for the drive determines the starting and accelerating characteristics of the motor. Expect lower torque
than when running from line power. To get more starting torque, use a larger drive or increase both the motor and drive capacity.
Emergency Stop
When the drive faults out, the output shuts off but the motor does not stop immediately. A mechanical brake may be required
when it is necessary to stop the motor faster than the ability of the Fast Stop function of the drive.
Options
NOTICE: The B1, B2, +1, +2, and +3 terminals are used to connect optional A1000-compatible devices only. Connecting non-Yaskawaapproved devices to these terminals may damage the drive.
Repetitive Starting/Stopping
Laundry machines, punching presses, and other applications with frequent starts and stops often approach 150% of their rated
current values. Heat stress generated from repetitive high current will shorten the life span of the IGBTs.
Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. It is beneficial to
reduce the load, increase the acceleration and deceleration times, or switch to a larger drive to help keep peak current levels
under 150%. Be sure to check the peak current levels when starting and stopping repeatedly during the initial test run, and
make adjustments accordingly.
n Installation
Enclosure Panels
Keep the drive in a clean environment by installing the drive in an enclosure panel or selecting an installation area free of
airborne dust, lint, and oil mist. Be sure to leave the required space between drives to provide for cooling, and take proper
measures so the ambient temperature remains within allowable limits and keep flammable materials away from the drive.
Yaskawa offers protective designs for drives that must be used in areas subjected to oil mist and excessive vibration. Contact
Yaskawa or your Yaskawa agent for details.
Installation Direction
NOTICE: Install the drive upright as specified in the manual. Refer to Mechanical Installation on page 54 for more information on
installation. Failure to comply may damage the drive due to improper cooling.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
23
n Settings
Motor Code
When using OLV/PM, set the proper motor code to parameter E5-01 before performing a trial run.
Upper Limits
NOTICE: The drive is capable of running the motor up to 400 Hz. Be sure to set the upper limit for the frequency of the drive to prevent the
possible danger of accidentally operating equipment at higher than rated speed. The default setting for the maximum output frequency is
60 Hz.
DC Injection Braking
NOTICE: Excessive current during DC Injection Braking and excessive duration of DC Injection Braking can cause motor overheat.
Acceleration/Deceleration Times
Acceleration and deceleration times are affected by the amount of torque generated by the motor, the load torque, and the
inertia moment. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as
long as the Stall Prevention function is in operation. Install one of the available braking options or increase the capacity of the
drive for faster acceleration and deceleration.
n General Handling
Wiring Check
NOTICE: Do not connect power supply lines to output terminals U/T1, V/T2, or W/T3. Failure to comply will destroy the drive. Be sure to
perform a final check of all sequence wiring and other connections before turning on the power and also check for short circuits on the
control terminals, which may damage the drive.
Yaskawa recommends installing a Ground Fault Circuit Interrupter (GFCI) to the power supply side. The GFCI should be
designed for use with AC drives (e.g., Type B according to IEC 60755).
Select a Molded Case Circuit Breaker (MCCB) or GFCI with a rated current 1.5 to 2 times higher than the drive rated current
to avoid nuisance trips caused by harmonics in the drive input current. Refer to Installing a Molded Case Circuit Breaker
(MCCB) or Ground Fault Circuit Interrupter (GFCI) on page 445 for more information.
NOTICE: Prevent Equipment Damage. Install a fuse and a GFCI in models CIMR-Ao4A0930 and 4A1200. Failure to comply may result in
serious damage to the facilities if the drive is defective.
Wiring
Yaskawa recommends using ring terminals on all drive models. Drive models CIMR-Ao2A0069 to 2A0415 and 4A0058 to
4A1200 require the use of use ring terminals for UL/cUL compliance. Use only the tools recommended by the terminal
manufacturer for crimping.
24
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The cooling fan of a standard motor should sufficiently cool the motor at the rated speed. As the self-cooling capability of
such a motor reduces with the speed, applying full torque at low speed will possibly damage the motor. Reduce the load torque
as the motor slows to prevent motor damage from overheat. Figure i.2 shows the allowable load characteristics for a Yaskawa
standard motor. Use a motor designed specifically for operation with a drive when 100% continuous torque is needed at low
speeds.
25% ED (or 15 min)
40% ED (or 20 min)
60% ED (or 40 min)
100
90
80
70
Torque
(%)
60
50
Continuous operation
3 6
20
60
Frequency (Hz)
Insulation Tolerance
NOTICE: Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly
long wiring distances.
High-Speed Operation
NOTICE: Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated speed.
Contact the motor or machine manufacturer.
Torque Characteristics
Torque characteristics differ compared to operating the motor directly from line power. The user should have a full
understanding of the load torque characteristics for the application.
Vibration and Shock
The drive allows selection of high carrier PWM control and low carrier PWM. Selecting high carrier PWM can help reduce
motor oscillation.
Take particular caution when adding a variable speed drive to an application running a motor from line power at a constant
speed. If resonance occurs, install shock-absorbing rubber around the base of the motor and enable the Jump frequency
selection to prevent continuous operation in the resonant frequency range.
Mechanical resonance can occur with long motor shafts and in applications such as turbines, blowers, and fans with high
inertia loads. Use Closed Loop Vector Control when these applications experience mechanical resonance problems.
Audible Noise
Noise created during run varies by the carrier frequency setting. When using a high carrier frequency, audible noise from the
motor is comparable to the motor noise generated when running from line power. Operating above the rated motor speed can
create unpleasant motor noise.
n Synchronous Motors
Contact Yaskawa or a Yaskawa agent when planning to use a synchronous motor not endorsed by Yaskawa.
Use a standard induction motor when running multiple synchronous motors simultaneously. A single drive does not have
this capability.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
25
n Specialized Motors
Multi-Pole Motor
The rated current of a multi-pole motor differs from that of a standard motor, so be sure to check the maximum current when
selecting a drive. Always stop the motor before switching between the number of motor poles. The motor will coast to stop if
a regen overvoltage (ov) fault occurs or if overcurrent (oC) protection is triggered.
Submersible Motor
The rated current of a submersible motor is greater than that of a standard motor, so select the drive capacity accordingly. Use
a motor cable large enough to avoid decreasing the maximum torque level from voltage drop caused by a long motor cable.
Explosion-Proof Motor
The motor and the drive must be tested together to be certified as explosion-proof. The drive is not designed for explosionproof areas.
When attaching an encoder to an explosion-proof motor, make sure the encoder is also explosion-proof. Use an insulating
signal converter to connect the encoder signal lines to the speed feedback option card.
Geared Motor
Make sure that the gear and the lubricant are rated for the desired speed range to avoid gear damage when operating at low
speeds or very high speeds. Consult with the manufacturer for applications that require operation outside the rated speed range
of the motor or gear box.
Single-Phase Motor
Variable speed drives are not designed to operate with single phase motors. Using capacitors to start the motor causes excessive
current to flow and can damage drive components. A split-phase start or a repulsion start can burn out the starter coils because
the internal centrifugal switch is not activated. The drive is for use with three-phase motors only.
Motor with Brake
Take caution when using the drive to operate a motor with a built-in holding brake. If the brake is connected to the output side
of the drive, it may not release at start due to low voltage levels, so be sure to install a separate power supply for the motor
brake. Note that motors with built-in brakes tend to generate a fair amount of noise when running at low speeds.
26
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
WARNING
Hot surfaces
A1000
CIMR-AU5A0009FAA
Warning Label
u Warranty Information
n Restrictions
The drive is not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or
health.
Customers who intend to use the product described in this manual for devices or systems relating to transportation, health
care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa
representatives or the nearest Yaskawa sales office.
WARNING! Injury to Personnel. This product has been manufactured under strict quality-control guidelines. However, if this product is to
be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility
where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
27
28
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
1
Receiving
This chapter explains how to inspect the drive upon receipt, and gives an overview of the different
enclosure types and components.
1.1
1.2
1.3
1.4
1.5
SECTION SAFETY.................................................................................................30
GENERAL DESCRIPTION.....................................................................................31
MODEL NUMBER AND NAMEPLATE CHECK....................................................35
DRIVE MODELS AND ENCLOSURE TYPES........................................................39
COMPONENT NAMES...........................................................................................41
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
29
1.1
Section Safety
CAUTION
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
A motor connected to a PWM drive may operate at a higher temperature than a utility-fed motor and the operating
speed range may reduce motor cooling capacity.
Ensure that the motor is suitable for drive duty and/or the motor service factor is adequate to accommodate the additional
heating with the intended operating conditions.
30
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
1.2
General Description
Model
CIMR-Ao
Rated
Output
Current
(A)
Model
CIMR-Ao
Rated
Output
Current
(A) <3>
Model
CIMR-Ao
Rated
Output
Current
(A)
Model
CIMR-Ao
Rated
Output
Current
(A) <3>
Rated
Output
Current
(A)
Model
CIMR-Ao
Rated
Output
Current
(A) <3>
0.75
2A0004
3.2 <1>
2A0004
3.5
4A0002
1.8
4A0002
2.1
2A0006
5 <1>
2A0006
2A0008
6.9 <1>
2A0008
4A0004
3.4
4A0004
2A0010
8 <1>
4A0005
4.8
2A0012
11 <1>
2A0010
9.6
4A0007
2A0018
14 <1>
2A0012
12
4A0009
7.2
2A0021
17.5 <1>
2A0018
17.5
4A0011
9.2
4A0009
8.8
5A0009
6.3
5A0006
6.1
2A0030
25 <1>
2A0021
21
4A0018
14.8
4A0011
11.1
5A0011
9.8
5A0009
10
2A0040
33 <1>
2A0030
30
4A0023
18
4A0018
17.5
5A0017
12.5
5A0011
11
15
2A0056
47 <1>
2A0040
40
4A0031
24 <1>
4A0023
23
5A0022
17
5A0017
17
20
2A0069
60 <1>
2A0056
56
4A0038
31 <1>
4A0031
31
5A0027
22
5A0022
22
25
2A0081
75 <1>
2A0069
69
4A0038
38
5A0032
27
5A0027
27
4A0044
39 <1>
5A0041
32
Motor
Power
HP
5
7.5
25-30
30
40
50
50-60
Model
CIMR-Ao
5A0003
1.7
4.1
5A0004
3.5
5A0003
2.7
5.5
4A0005
5.4
5A0006
4.1
5A0004
3.9
4A0007
6.9
4A0058
45 <1>
2A0110
85 <1>
2A0081
81
4A0044
44
5A0032
32
2A0138
115 <1>
2A0110
110
4A0072
60 <1>
4A0058
58
5A0052
41
5A0041
41
2A0169
145 <2>
2A0138
138
4A0072
72
5A0052
52
4A0088
75 <1>
5A0062
52
4A0103
91 <1>
5A0077
62
60
2A0211
180 <2>
2A0169
169
4A0088
88
5A0062
62
75
2A0250
215 <2>
2A0211
211
4A0139
112 <2>
4A0103
103
5A0099
77
5A0077
77
100
2A0312
283 <2>
2A0250
250
4A0165
150 <2>
4A0139
139
5A0125
99
5A0099
99
125
2A0360
346 <2>
2A0312
312
4A0165
165
5A0145
130
5A0125
125
125-150
4A0208
180 <2>
150
2A0415
415 <2>
2A0360
360
4A0250
216 <2>
4A0208
208
5A0192
172
5A0145
145
175
2A0415
415
200
4A0296
260 <2>
4A0250
250
5A0242
200
5A0192
192
250
4A0362
304 <2>
4A0296
296
5A0242
242
4A0414
370 <2>
4A0362
362
300
350
4A0515
450 <3>
4A0414
414
400-450
4A0515
515
400-450500
4A0675
605 <3>
500-550
4A0675
675
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Receiving
31
Model
CIMR-Ao
Rated
Output
Current
(A)
Model
CIMR-Ao
Rated
Output
Current
(A) <3>
Model
CIMR-Ao
Rated
Output
Current
(A)
Model
CIMR-Ao
Rated
Output
Current
(A) <3>
Model
CIMR-Ao
Rated
Output
Current
(A)
Model
CIMR-Ao
Rated
Output
Current
(A) <3>
650
4A0930
810 <3>
750
4A0930
930
900
4A1200
1090 <3>
1000
4A1200
1200
<1> These values assume the carrier frequency is not set higher than 8 kHz.
<2> These values assume the carrier frequency is not set higher than 5 kHz.
<3> These values assume the carrier frequency is set to 2 kHz.
Note: Current derating is required when setting the carrier frequency higher. Refer to Carrier Frequency Derating on page 468 for details.
A1-02 = 0
Basic Description
V/f control
V/f w/PG
A1-02 = 1
OLV
A1-02 = 2
CLV
A1-02 = 3
OLV/PM
A1-02 = 5
AOLV/PM
A1-02 = 6
CLV/PM
A1-02 = 7
V/f control
Open Loop
Open Loop
Closed Loop
Open Loop
Closed Loop
using motor
Vector control Vector control Vector control
Vector control Vector control
speed feedback
for PM motors for IPM motors for PM motors
Comments
Default Setting is
OLV control
(A1-02 =2)
Motor Type
IM
IM
IM
IM
PM
IPM
PM
Multi Motor
YES
Motor data
unknown
YES
High Speed
Accuracy
YES
YES
YES
YES
YES
YES
High Speed
Response
YES
YES
YES
YES
Zero Speed
Control
YES
YES
YES
Torque Control
Operation
YES
YES
YES
Torque Limit
Operation
YES
YES
YES
PG-B3 or
PG-X3
PG-B3 or
PG-X3
PG-X3
PG Option Card
32
V/f
Parameter Setting
Type of
Applications
Induction Motors
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Speed Accuracy
Induction Motors
1:40
2 to 3%
1:40
0.03%
1:200
0.2%
1:1500
0.02%
1:20
0.2%
1:100
0.2%
1:1500
0.02%
Speed deviation
when operating at
constant speed may
fluctuate with
characteristics and
motor temperature.
50 Hz
Max. frequency of a
speed reference
signal that the drive
can follow may
fluctuate with
characteristics and
motor temperature.
200% at
0 r/min
Control
Characteristics
Speed Response 3 Hz (approx.) 3 Hz (approx.)
Starting Torque
150% at 3 Hz
150% at 3 Hz
10 Hz
200% at
0.3 Hz
50 Hz
200% at
0 r/min
10 Hz
100% at
5% speed
10 Hz
200% at
0 r/min
Comments
May fluctuate with
characteristics and
motor temperature.
Stationary
Auto-Tuning
Energy
Saving
Tuning
Energy
Saving
Tuning
Rotational
Stationary
Stationary Stationary
Line to line
Line to line Line to line
resistance
resistance
resistance
Line to line Line to line Line to line
ASR
resistance
resistance
resistance
Inertia
Stationary
ApplicationSpecific
Torque Limit
Torque Control
YES
YES
YES
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
YES
Line to line
resistance Automatically
adjusts parameter
ASR
settings that concern
Inertia
electrical
characteristics of the
Encoder
motor.
offset
Back EMF
Constant
YES
YES
Allows direct
control of motor
torque for tension
control and other
such applications.
Receiving
Rotational
33
Comments
YES
YES
Zero Servo
Control
YES
YES
YES
Bi-directional speed
detection of a
coasting motor to
restart it without
stopping.
Speed Search
Energy-Saving
Control
High Slip
Braking
ApplicationSpecific
Induction Motors
Droop Function
Feed Forward
Control
Kinetic Energy
Buffering
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
(IPM motors
only)
YES
YES
Saves energy by
YES
always operating the
(IPM motors motor at its
only)
maximum
efficiency.
YES
Improves speed
accuracy when the
load changes by
compensating
effects of the system
inertia.
YES
Decelerates the
drive to allow it to
ride through a
momentary power
loss and continue
operation.
Overexcitation
Deceleration
YES
YES
YES
YES
Provides fast
deceleration without
using a braking
resistor.
Inertia Tuning,
ASR Tuning
YES
YES
Provides automatic
Speed Control and
Feed Forward
function tuning.
Overvoltage
Suppression
YES
YES
YES
YES
YES
YES
YES
Prevents
overvoltage by
increasing speed
during regeneration.
High Frequency
Injection
YES
<99> PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooo.
34
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
1.3
u Nameplate
H
G
F
E
D
IP20
IND.CONT.EQ.
7J48 B
Receiving
200/400 V Class
PASS
Assembled in USA
C
600 V Class
H
G
F
E
D
IP20
PASS
Assembled in USA
E Lot number
F Output specifications
G Input specifications
H AC drive model
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
35
CIMR - A U 2
Drive
A1000
Series
Region
Code
Japan
China
Europe
India
Asia
USA
No.
0021
No.
Customized
Specifications
No.
Enclosure
Type
Standard model
IP00/Open
Type
IP20/NEMA
Type 1
No.
Voltage Class
2 3-phase, 200-240 Vac
No.
A
K
M
N
S
A
Design
Revision
Order
Environmental
Specification <1>
Standard
Gas-resistant
Humidity- and
dust-resistant
Oil-resistant
Vibration-resistant
<1> Drives with these specifications do not guarantee complete protection for the environmental conditions indicated.
n Three-Phase 200 V
36
No.
Normal Duty
Max. Motor Capacity
kW (HP)
Rated Output
Current A
0004
0006
0008
0010
0012
0018
0021
0030
0040
0056
0069
0081
0110
0138
0169
0211
0250
0312
0360
0415
0.75 (0.75)
1.1 (1)
1.5 (2)
2.2 (3)
3.0 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
110 (175)
3.5
6.0
8.0
9.6
12
17.5
21
30
40
56
69
81
110
138
169
211
250
312
360
415
No.
Heavy Duty
Max. Motor Capacity
kW (HP)
Rated Output
Current A
0004
0006
0008
0010
0012
0018
0021
0030
0040
0056
0069
0081
0110
0138
0169
0211
0250
0312
0360
0415
0.4 (0.75)
0.75 (1)
1.1 (2)
1.5 (2)
2.2 (3)
3.0 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
3.2
5
6.9
8
11
14.0
17.5
25
33
47
60
75
85
115
145
180
215
283
346
415
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
n Three-Phase 400 V
Rated Output
Current A
2.1
4.1
5.4
6.9
8.8
11.1
17.5
23
31
38
Rated Output
Current A
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18
24
31
0044
Heavy Duty
Max. Motor Capacity
kW (HP)
0.4 (0.75)
0.75 (2)
1.5 (3)
2.2 (3)
3.0 (5)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5
(25-30)
0002
0004
0005
0007
0009
0011
0018
0023
0031
0038
0044
22 (30)
44
0058
30 (40)
58
0058
22
(25-30)
45
0072
37 (50)
72
0072
60
0088
45 (60)
88
0088
30 (40)
37
(50-60)
0103
55 (75)
103
0103
45
(50-60)
91
0139
0165
75 (100)
90 (125)
139
165
0139
0165
112
150
0208
110 (150)
208
0208
55 (75)
75 (100)
90
(125-150)
0250
0296
0362
0414
250
296
362
414
0250
0296
0362
0414
110 (150)
132 (200)
160 (250)
185 (300)
216
260
304
370
0515
132 (200)
160 (250)
185 (300)
220 (350)
250
(400-450)
515
0515
220 (350)
450
0675
355
(500-550)
675
0675
315
(400-450-500)
605
0930
500
(750)
630
(1000)
930
0930
810
1200
1200
450
(650)
560
(900)
No.
1200
No.
39
75
180
Receiving
0002
0004
0005
0007
0009
0011
0018
0023
0031
0038
Normal Duty
Max. Motor Capacity
kW (HP)
0.75 (0.75)
1.5 (2)
2.2 (3)
3.0 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
1090
Note: Refer to Drive Models and Enclosure Types on page 39 for differences regarding enclosure protection types and component descriptions.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
37
n Three-Phase 600 V
0003
0004
0006
0009
0011
0017
0022
0027
0032
0041
0052
Normal Duty
Max. Motor Capacity
kW (HP)
1.5 (2)
2.2 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
Rated Output
Current A
2.7
3.9
6.1
9
11
17
22
27
32
41
52
0062
0077
0099
0125
0145
0192
0242
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
160 (200)
185 (250)
62
77
99
125
145
192
242
No.
0003
0004
0006
0009
0011
0017
0022
0027
0032
0041
0052
Heavy Duty
Max. Motor Capacity
kW (HP)
0.75 (1)
1.5 (2)
2.2 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (25-30)
30 (40)
Rated Output
Current A
1.7
3.5
4.1
6.3
9.8
12.5
17
22
27
32
41
0062
0077
0099
0125
0145
0192
0242
37 (50-60)
45 (50-60)
55 (75)
75 (100)
90 (125)
110 (150)
160 (200)
52
62
77
99
130
172
200
No.
Note: Refer to Drive Models and Enclosure Types on page 39 for differences regarding enclosure protection types and component descriptions.
38
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
1.4
Three-Phase
200 V Class
Three-Phase
400 V Class
2A0004F
<1>
2A0006F
<1>
2A0008F
<1>
2A0010F
<1>
2A0012F
<1>
2A0018F
<1>
2A0021F
<1>
2A0030F
<1>
2A0040F
<1>
2A0056F
<1>
2A0069F
<1>
2A0081F
<1>
2A0110F
<1>
2A0138F
<1>
2A0169F
<1>
2A0211F
<1>
<2>
2A0250A
<2>
2A0312A
<2>
2A0360A
<3>
2A0415A
4A0002F
<1>
4A0004F
<1>
4A0005F
<1>
4A0007F
<1>
4A0009F
<1>
4A0011F
<1>
4A0018F
<1>
4A0023F
<1>
4A0031F
<1>
4A0038F
<1>
4A0044F
<1>
4A0058F
<1>
4A0072F
<1>
4A0088F
<1>
4A0103F
<1>
4A0139F
<1>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Receiving
Enclosure Type
Voltage Class
39
Three-Phase
400 V Class
Three-Phase
600 V Class
Enclosure <1>
IP20/NEMA Type 1
Drive Model CIMR-Ao
4A0165F
<1>
<2>
4A0208A
<2>
4A0250A
<2>
4A0296A
<2>
4A0362A
<3>
4A0414A
<3>
4A0515A
<3>
4A0675A
<3>
4A0930A
<3>
4A1200A
5A0003F
<1>
5A0004F
<1>
5A0006F
<1>
5A0009F
<1>
5A0011F
<1>
5A0017F
<1>
5A0022F
<1>
5A0027F
<1>
5A0032F
<1>
5A0041F
<1>
5A0052F
<1>
5A0062F
<1>
5A0077F
<1>
5A0099F
<1>
<2>
5A0125A
<2>
5A0145A
<2>
5A0192A
<2>
5A0242A
<1> Removing the top protective cover from a IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while retaining IP20 conformity.
<2> Customers may convert these models to IP20/NEMA Type 1 enclosures using an IP20/NEMA Type 1 Kit. Refer to IP20/NEMA Type 1 Kit
Selection on page 68 to select the appropriate kit.
<3> Contact a Yaskawa representative for IP20/NEMA Type 1 Kit availability for these models.
40
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
1.5
Component Names
This section gives an overview of the drive components described in this manual.
Note: 1. Refer to Using the Digital Operator on page 115 for a description of the operator keypad.
2. The drive may have no cooling fans or up to two cooling fans depending on the model.
A
J
K
Receiving
L
E
M
F
N
I
I Rubber bushing
J Top Protective cover
K Front cover
L USB port (type-B)
M Digital operator
N Terminal cover
O Terminal cover screw
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
41
B
C
L
M
H
O
I Front cover
J USB port (type-B)
K Front cover screw
L Digital operator
M Drive cover
N Terminal cover
O Conduit bracket front cover
42
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
I
J
E
F
L
O
Receiving
I Fan bracket
J Front cover
K USB port (type-B)
L Front cover screw
M Digital operator
N Drive cover
O Terminal cover
P Conduit bracket front cover
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
43
F
B
C
H
I
J
L
D
K
A Mounting hole
B Heatsink
C Optional 24 V DC power supply
connector cover
D Terminal board
E Fan guard
F Cooling fan
G Fan bracket
H Front cover
I USB port (type-B)
J Digital operator
K Front cover screw
L Drive cover
M Terminal cover
44
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
I
J
M
L
A Mounting hole
B Heatsink
C Optional 24 V DC power supply
connector cover
D Terminal board
E Fan guard
F Cooling fan
G Fan bracket
Receiving
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
45
N
A
J
O
A Mounting hole
B Heatsink
C Optional 24 V DC power supply
connector cover
D Terminal board
E Fan guard
F Cooling fan
G Fan bracket
H Circulation fan
I Front cover
J USB port (type-B)
K Digital operator
L Front cover screw
M Drive cover 1
N Drive cover 2
O Terminal cover
46
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
E
F
H
G
A
I
J
M
N
O
Receiving
A Mounting hole
B Heatsink
C Terminal board
D Fan guard
E Cooling fan
F Fan bracket
G Circulation Fan
H Circuit board cooling fan
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
47
G
A
H
F
B
C
M
K
N
R
S
P
Q
A Mounting hole
B Heatsink
C Terminal board
D Fan guard
E Cooling fan
F Fan unit case (L)
G Fan unit case (R)
H Circulation Fan
I Circuit board cooling fan
J Circuit board cooling fan unit case
(L)
48
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u Front Views
CIMR-Ao2A110A
CIMR-Ao2A0012F
I
I
J
D
E
D
E
A
B
L
M
F
G
H
Receiving
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
49
50
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
2
Mechanical Installation
This chapter explains how to properly mount and install the drive.
2.1
2.2
SECTION SAFETY.................................................................................................52
MECHANICAL INSTALLATION.............................................................................54
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
51
2.1
Section Safety
WARNING
Fire Hazard
Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet.
Failure to comply could result in overheating and fire.
When multiple drives are placed inside the same enclosure panel, install proper cooling to ensure air entering the enclosure
does not exceed 40 C.
Crush Hazard
Only allow qualified personnel to operate a crane or hoist to transport the drive.
Failure to comply may result in serious injury or death from falling equipment.
Use a dedicated lifter when transporting the drive by a lifter.
Failure to comply may result in serious injury or death from falling equipment.
Only use vertical suspension to temporarily lift the drive during installation to an enclosure panel. Do not use vertical
suspension to transport the drive.
Failure to comply may result in serious injury or death from falling equipment.
Use screws to securely affix the drive front cover, terminal blocks, and other drive components prior to vertical
suspension.
Failure to comply may result in serious injury or death from falling equipment.
Do not subject the drive to vibration or impact greater than 1.96 m/s2 (0.2 G) while it is suspended by the wires.
Failure to comply may result in serious injury or death from falling equipment.
Do not attempt to flip the drive over or leave the drive unattended while it is suspended by the wires.
Failure to comply may result in serious injury or death from falling equipment.
CAUTION
Crush Hazard
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
52
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
NOTICE
Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during drive installation
and project construction.
Failure to comply could result in damage to the drive. Place a temporary cover over the top during installation. Be sure to
remove the temporary cover before start-up, as the cover will reduce ventilation and cause the unit to overheat.
Observe proper electrostatic discharge (ESD) procedures when handling the drive.
Failure to comply could result in ESD damage to the drive circuitry.
Operating the motor in the low-speed range diminishes the cooling effects, increases motor temperature, and may
lead to motor damage by overheating.
Reduce the motor torque in the low-speed range whenever using a standard blower cooled motor. If 100% torque is required
continuously at low speed, consider using a special drive or vector-control motor. Select a motor that is compatible with the
required load torque and operating speed range.
The speed range for continuous operation differs according to the lubrication method and motor manufacturer.
If the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer.
Continuously operating an oil-lubricated motor in the low-speed range may result in burning.
When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to
the motor insulation voltage or use a drive-rated motor with reinforced insulation.
Failure to comply could lead to motor winding failure.
Motor vibration may increase when operating a machine in variable-speed mode, if that machine previously operated
at a constant speed.
Install vibration-proof rubber on the motor base or use the frequency jump function to skip a frequency resonating the
machine.
The motor may require more acceleration torque with drive operation than with a commercial power supply.
Set a proper V/f pattern by checking the load torque characteristics of the machine to be used with the motor.
The rated input current of submersible motors is higher than the rated input current of standard motors.
Select an appropriate drive according to its rated output current. When the distance between the motor and drive is long, use
a cable thick enough to connect the motor to the drive to prevent motor torque reduction.
The current rating differs for a motor with variable pole pitches differs from a standard motor.
Check the maximum current of the motor before selecting the drive capacity. Only switch motor poles when the motor is
stopped. Switching between motor during run will trigger overcurrent protection circuitry or result in overvoltage from
regeneration, and the motor will simply coast to stop.
When using an explosion-proof motor, it must be subject to an explosion-proof test in conjunction with the drive.
This is also applicable when an existing explosion-proof motor is to be operated with the drive. Since the drive itself is not
explosion-proof, always install it in a safe place.
Never lift the drive up while the cover is removed.
This can damage the terminal board and other components.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
53
Mechanical Installation
Equipment Hazard
2.2
Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
u Installation Environment
Install the drive in an environment matching the specifications below to help prolong the optimum performance life of the
drive.
Table 2.1 Installation Environment
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Conditions
Indoors
-10 C to +40 C (IP20/NEMA Type 1 enclosure)
-10 C to +50 C (IP00/Open Type enclosure)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20 to +60 C
Install the drive in an area free from:
oil mist and dust
metal shavings, oil, water, or other foreign materials
radioactive materials
combustible materials (e.g., wood)
harmful gases and liquids
excessive vibration
chlorides
direct sunlight.
1000 m or lower, up to 3000 m with derating. Refer to Drive Derating Data on page 468 for details.
Vibration
Orientation
Not OK
Not OK
54
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Top/Bottom Clearance
A 50 mm minimum
B 30 mm minimum
C 120 mm minimum
D Airflow direction
Figure 2.2 Correct Installation Spacing
Note: IP20/NEMA Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive for
installation.
Mechanical Installation
B
A
A 50 mm minimum
B 30 mm minimum
Top/Bottom Clearance
A
D
A
C 2 mm minimum
D 120 mm minimum
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
55
1.
2.
3.
4.
56
Remove the four eye bolts from the drive side panels and fix them securely on the top panel (Refer to Figure 2.5).
Pass wire through the holes of all four eye bolts (Refer to Figure 2.6).
Gradually take up the slack in the wires and hoist the drive after the wires are stretched tight.
Lower the drive when ready to install in the enclosure panel. Stop lowering the drive when it is near the floor then
begin lowering the drive again very slowly until the drive is placed correctly.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Mechanical Installation
Eye bolt
2
A Eye bolt
B Wires
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
57
Operator
Comm Port
S/N : J007XE273710001
1.6
15
78
90
S/N : J007XE273710001
7.9
60
44
minimum
50
Unit: mm
Yaskawa offers keypad kits that provide the functionality of the digital operator on enclosures designed for NEMA Type 1,
3R, 4, 4X, 12, or IPX6 environments. These kits are for use with digital operator models JVOP-180 and JVOP-182.
Table 2.2 Installation Environment
Keypad Kit Model
UUX000526
UUX000527
Description
Blank label on the front.
Yaskawa brand label on the front.
58
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Installation
Method
Description
Installation
Support Sets
Model
Required Tools
External/
Face-Mount
Phillips screwdriver
(#1)
EZZ020642A
Internal/
Flush-Mount
Phillips screwdriver
(#1, #2)
EZZ020642B
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project
construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation.
Remove the temporary cover before drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
External/Face-Mount
1. Cut an opening in the enclosure panel for the digital operator as shown in Figure 2.10.
2. Position the digital operator so the display faces outwards, and mount it to the enclosure panel as shown in Figure
2.9.
M3 x 6
Phillips recessed
pan head machine screw x 2
Digital Operator
Mechanical Installation
Enclosure panel
Unit: mm
2
22
26
78
22
14
Unit: mm
Internal/Flush-Mount
An internal flush-mount requires an installation support set that must be purchased separately. Contact a Yaskawa
representative to order an installation support set and mounting hardware. Figure 2.11 illustrates how to attach the Installation
Support Set A.
1.
2.
3.
Cut an opening in the enclosure panel for the digital operator as shown in Figure 2.12.
Mount the digital operator to the installation support.
Mount the installation support set and digital operator to the enclosure panel.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
59
M4 10
Phillips truss head screw 4
(for panel widths between 1 and 1.6)
M3 6
Phillips recessed
pan head machine screw 2
Unit: mm
120
89 +0.5
0
Note: Use a gasket between the enclosure panel and the digital operator in environments with a significant amount of dust or other airborne debris.
45
59 +0.5
0
Unit : mm
60
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
IP20/NEMA
Type 1
Enclosure
IP00/Open Type
Enclosure
Three-Phase
200 V Class
2A0004F
2A0006F
2A0008F
2A0010F
2A0012F
2A0018F
2A0021F
2A0030F
2A0040F
2A0056F
2A0069F
2A0081F
2A0110F
2A0138F
2A0169F
2A0211F
2A0250A <1>
2A0312A <1>
2A0360A <1>
2A0415A <2>
Three-Phase
600 V Class
Page
5A0003F
5A0004F
5A0006F
5A0009F
5A0011F
5A0017F
5A0022F
5A0027F
5A0032F
5A0041F
5A0052F
5A0062F
5A0077F
5A0099F
62
5A0125A <1>
5A0145A <1>
5A0192A <1>
5A0242A <1>
66
Mechanical Installation
Protective
Design
<1> Customers may convert these models to IP20/NEMA Type 1 enclosures using an IP20/NEMA Type 1 Kit. Refer to IP20/NEMA Type 1 Kit
Selection on page 68 to select the appropriate kit.
<2> Contact a Yaskawa representative for IP20/NEMA Type 1 Kit availability for these models.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
61
H0
t2
H2
H3
H3
H2
H1
H1
H0
4-d
W1
H4
4-d
W1
t1
t1
D1
Max.W2
Max.W2
Figure 1
D1
Figure 2
Dimensions (in)
Figure
W1
W2
H0
H1
H2
H3
H4
D1
t1
t2
Wt. (lb)
0004F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.3
0006F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.3
0008F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.5
0010F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.5
0012F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.5
0018F
5.51
11.81
6.46
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
8.2
0021F
<1>
5.51
11.81
6.46
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
8.2
0030F
5.51
11.81
6.57
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
9.3
0040F
5.51
11.81
6.57
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
9.3
0056F
7.09
13.39
7.36
6.30
11.81
11.18
0.31
1.57
0.06
2.95
0.20
M5
13.0
0069F
8.66
15.75
7.76
7.56
13.78
13.19
0.31
1.97
0.06
3.07
0.20
M6
20.1
0081F
8.66
15.75
7.76
7.56
13.78
13.19
0.31
1.97
0.06
3.07
0.20
M6
22.0
0110F
10.00
21.02
10.16
7.68
0.31
15.75
15.16
0.30
5.28
3.94
0.09
0.09
M6
50.7
0138F
10.98
24.17
10.16
8.66
0.31
17.72
17.13
0.30
6.46
3.94
0.09
0.09
M6
61.7
0169F
<1>
12.95
28.74
11.14
10.24
0.31
21.65
21.06
0.30
7.09
4.33
0.09
0.09
M6
90.4
12.95
28.74
11.14
10.24
0.31
21.65
21.06
0.30
7.09
4.33
0.09
0.09
M6
92.6
0211F
Dimensions below are the dimensions of IP00/Open Type models after customer installation of the appropriate IP20/NEMA Type 1 Kit.
0250A
0312A
0360A
17.95
37.80
12.99
12.80
0.31
27.76
26.77
0.49
10.04
5.12
0.13
0.13
M10
183.0
17.95
37.80
12.99
12.80
0.31
27.76
26.77
0.49
10.04
5.12
0.13
0.13
M10
194.0
19.84
45.98
13.78
14.57
0.31
31.50
30.43
0.51
14.49
5.12
0.18
0.18
M12
238.1
<1> Removing the top protective cover from a IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while retaining IP20 conformity.
62
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Dimensions (in)
W
W1
W2
H0
H1
H2
H3
H4
D1
t1
t2
Wt. (lb)
0002F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.5
0004F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.5
0005F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.5
0007F
5.51
11.81
6.46
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
7.9
0009F
5.51
11.81
6.46
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
8.2
0011F
Figure
5.51
11.81
6.46
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
8.2
0018F
5.51
11.81
6.57
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
9.0
0023F
5.51
11.81
6.57
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
9.0
0031F
7.09
13.39
6.57
6.30
11.81
11.18
0.31
1.57
0.06
2.17
0.20
M5
12.6
0038F
7.09
13.39
7.36
6.30
11.81
11.18
0.31
1.57
0.06
2.95
0.20
M5
13.2
0044F
8.66
15.75
7.76
7.56
13.78
13.19
0.31
1.97
0.06
3.07
0.20
M6
19.2
0058F
10.00
18.31
10.16
7.68
0.31
15.75
15.16
0.30
2.56
3.94
0.09
0.09
M6
50.7
0072F
10.98
20.28
10.16
8.66
0.31
17.72
17.13
0.30
2.56
3.94
0.09
0.09
M6
59.5
<1>
0088F
12.95
24.80
10.16
10.24
0.31
20.08
19.49
0.30
4.72
4.13
0.09
0.13
M6
86.0
0103F
<1>
12.95
24.80
10.16
10.24
0.31
20.08
19.49
0.30
4.72
4.13
0.09
0.13
M6
86.0
0139F
12.95
28.74
11.14
10.24
0.31
21.65
21.06
0.30
7.09
4.33
0.09
0.09
M6
99.2
0165F
12.95
28.74
11.14
10.24
0.31
21.65
21.06
0.30
7.09
4.33
0.09
0.09
M6
101.4
0208A
17.95
37.80
12.99
12.80
0.31
27.76
26.77
0.49
10.04
5.12
0.13
0.13
M10
191.8
0250A
19.84
45.98
13.78
14.57
0.31
31.50
30.43
0.51
14.49
5.12
0.18
0.18
M12
233.7
19.84
45.98
13.78
14.57
0.31
31.50
30.43
0.51
14.49
5.12
0.18
0.18
M12
246.9
19.84
45.98
13.78
14.57
0.31
31.50
30.43
0.51
14.49
5.12
0.18
0.18
M12
257.9
0296A
0362A
<1> Removing the top protective cover from a IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while retaining IP20 conformity.
Table 2.7 Dimensions for IP20/NEMA Type 1 Enclosure: 600 V Class
Drive Model
CIMR-Ao5A
Dimensions (in)
W
W1
W2
H0
H1
H2
H3
H4
D1
t1
t2
Wt. (lb)
0003F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.5
0004F
5.51
11.81
5.79
4.80
10.24
9.76
0.24
1.57
0.06
1.50
0.20
M5
7.5
0006F
5.51
11.81
6.46
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
8.2
0009F
5.51
11.81
6.46
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
8.2
0011F
Figure
5.51
11.81
6.57
4.80
10.24
9.76
0.24
1.57
0.06
2.17
0.20
M5
9.0
0017F
7.09
13.39
7.36
6.30
11.81
11.18
0.31
1.57
0.06
2.95
0.20
M5
13.2
0022F
7.09
13.39
7.36
6.30
11.81
11.18
0.31
1.57
0.06
2.95
0.20
M5
13.2
0027F
8.66
15.75
7.76
7.56
13.78
13.19
0.31
1.97
0.06
3.07
0.20
M6
19.2
0032F
8.66
15.75
7.76
7.56
13.78
13.19
0.31
1.97
0.06
3.07
0.20
M6
19.2
0041F
10.98
20.28
10.16
8.66
0.31
17.72
17.13
0.30
2.56
3.94
0.09
0.09
M6
59.5
10.98
20.28
10.16
8.66
0.31
17.72
17.13
0.30
2.56
3.94
0.09
0.09
M6
59.5
12.95
28.74
11.14
10.24
0.31
21.65
21.06
0.30
7.09
4.33
0.09
0.09
M6
99.2
0077F
12.95
28.74
11.14
10.24
0.31
21.65
21.06
0.30
7.09
4.33
0.09
0.09
M6
99.2
0099F
12.95
28.74
11.14
10.24
0.31
21.65
21.06
0.30
7.09
4.33
0.09
0.09
M6
99.2
<1>
0052F
0062F
Dimensions below are the dimensions of IP00/Open Type models after customer installation of the appropriate IP20/NEMA Type 1 Kit.
0125A
17.95
37.80
12.99
12.80
0.31
27.76
26.77
0.49
10.04
5.12
0.13
0.13
M10
191.8
0145A
17.95
37.80
12.99
12.80
0.31
27.76
26.77
0.49
10.04
5.12
0.13
0.13
M10
191.8
19.84
45.98
13.78
14.57
0.31
31.50
30.43
0.51
14.49
5.12
0.18
0.18
M12
233.7
19.84
45.98
13.78
14.57
0.31
31.50
30.43
0.51
14.49
5.12
0.18
0.18
M12
257.9
0192A
0242A
<1> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while
maintaining IP20 conformity.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Mechanical Installation
Dimensions below are the dimensions of IP00/Open Type models after customer installation of the appropriate IP20/NEMA Type 1 Kit.
63
W2
d6
d6
d7
d7
W1
D3
D1
D3
D2
D3
D2
d5
W2
W1 W1
d6
d5
W1
D1
D1
W
W1
d5
D2
W1
Figure 1
Figure 2
Figure 3
W
W1
W1
W2
W1
d5
W2
W2
d5
W1
W2
W1
d6
d5
W1
d6
d6
D1
D2
D2
d7
D3
D2
D3
D3
D1
D1
d7
Figure 6
Figure 5
Figure 4
W
W
W2
W4
W1
d5
d6
W3 W3
W1
W1
W2
W2
W
W1
W
d5
W3
d6
W1
d5
W4 W4
d6
D2
D3
D1
D2
D3
D2
D1
D3
D4
D1
d7
W2
W3
W3
d7
d7
W2
Figure 9
Figure 8
Figure 7
Dimensions (in)
Figure
W1
W2
W3
Diameter (in)
W4
D1
D2
D3
D4
d5
d6
d7
200 V Class
2A0004F
1.7
1.5
1.5
1.6
2.8
3.1
0.9
1.4
2A0006F
1.7
1.5
1.5
1.6
2.8
3.1
0.9
1.4
1.7
1.5
1.5
1.6
2.8
3.1
2A0010F
1.7
1.5
1.5
1.6
2.8
3.1
0.9
1.4
2A0012F
1.7
2.2
1.5
1.6
2.8
3.1
0.9
1.4
2A0008F
64
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Dimensions (in)
Figure
Diameter (in)
W1
W2
W3
W4
D1
D2
D3
D4
d5
d6
d7
2A0018F
1.7
2.2
1.5
1.6
2.8
3.1
1.4
0.9
1.7
2A0021F
1.7
2.2
1.5
1.6
2.8
3.1
1.4
0.9
1.7
1.7
2.2
1.5
1.6
2.8
3.1
1.4
0.9
1.7
2.2
1.9
3.3
2.1
1.4
0.9
1.7
2A0056F
2.2
1.9
3.3
2.1
1.4
0.9
1.7
2A0069F
1.1
3.1
2.5
3.4
2.2
1.4
0.9
1.7
2A0081F
1.1
3.1
2.5
3.4
2.2
1.4
0.9
1.7
2A0030F
2A0040F
2A0110F
3.4
3.9
1.5
0.9
3.9
1.7
1.0
2.4
1.1
2A0138F
3.9
3.9
3.5
1.6
3.9
1.7
1.0
2.0
2.4
1.1
4.4
4.3
2.2
0.6
1.2
2.6
4.7
4.3
2.1
1.6
2.0
1.4
2.4
4.4
4.3
2.2
0.6
1.2
2.6
4.7
4.3
2.1
1.6
2.0
1.4
2.4
6.9
5.1
3.6
3.3
1.0
5.4
2.0
1.6
2.0
2.4
1.4
6.9
5.1
3.6
3.3
1.0
5.4
2.0
1.6
2.0
2.4
1.4
7.5
5.1
4.1
1.2
1.1
2.8
6.2
2.8
2.0
2.0
2.4
1.7
2A0169F
2A0211F
2A0250A
2A0312A
2A0360A
7
8
9
4A0002F
1.7
1.5
1.5
1.6
2.8
3.1
0.9
1.4
4A0004F
1.7
1.5
1.5
1.6
2.8
3.1
0.9
1.4
4A0005F
1.7
1.5
1.5
1.6
2.8
3.1
0.9
1.4
4A0007F
1.7
2.2
1.5
1.6
2.8
3.1
0.9
1.4
4A0009F
1.7
2.2
1.5
1.6
2.8
3.1
0.9
1.4
4A0011F
1.7
2.2
1.5
1.6
2.8
3.1
0.9
1.4
4A0018F
1.7
2.2
1.5
1.6
2.8
3.1
0.9
1.4
4A0023F
2.2
1.9
3.3
2.1
1.4
0.9
1.7
4A0031F
4A0038F
4A0044F
4A0058F
4A0072F
4A0088F
4A0103F
4A0139F
4A0165F
4A0208A
3
6
7
8
4A0250A
4A0296A
4A0362A
2.2
1.9
3.3
2.1
1.4
0.9
1.7
1.1
3.1
2.5
3.4
2.2
1.4
0.9
1.7
1.1
3.1
2.5
3.4
2.2
1.4
0.9
1.7
3.4
3.9
1.5
0.9
3.9
1.7
1.0
2.4
1.1
2.0
3.5
3.9
1.6
0.9
3.9
1.7
1.0
2.4
1.1
2.0
3.3
4.1
0.9
3.9
2.6
1.0
2.0
2.4
1.1
3.3
4.1
0.9
3.9
2.6
1.0
2.0
2.4
1.1
4.4
4.3
2.2
0.6
1.2
2.6
4.7
4.3
2.1
1.6
2.0
1.4
2.4
4.4
4.3
2.2
0.6
1.2
2.6
4.7
4.3
2.1
1.6
2.0
1.4
2.4
6.9
5.1
3.6
3.3
1.0
5.4
2.0
1.6
2.0
2.4
1.4
7.5
5.1
4.1
1.2
1.1
2.8
6.2
2.8
2.0
2.0
2.4
1.7
7.5
5.1
4.1
1.2
1.1
2.8
6.2
2.8
2.0
2.0
2.4
1.7
7.5
5.1
4.1
1.2
1.1
2.8
6.2
2.8
2.0
2.0
2.4
1.7
Mechanical Installation
400 V Class
600 V Class
5A0003F
1.7
1.5
1.5
1.6
2.8
3.1
0.9
1.4
5A0004F
1.7
1.5
1.5
1.6
2.8
3.1
0.9
1.4
5A0006F
1.7
2.2
1.5
1.6
2.8
3.1
0.9
1.4
5A0009F
1.7
2.2
1.5
1.6
2.8
3.1
0.9
1.4
5A0011F
1.7
2.2
1.5
1.6
2.8
3.1
0.9
1.4
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
65
Dimensions (in)
Figure
5A0017F
5A0022F
5A0027F
5A0032F
5A0041F
5A0052F
5A0062F
5A0077F
5A0099F
5A0125A
5A0145A
5A0192A
5A0242A
Diameter (in)
W1
W2
W3
W4
D1
D2
D3
D4
d5
d6
d7
2.2
1.9
3.3
2.1
1.4
0.9
1.7
2.2
1.9
3.3
2.1
1.4
0.9
1.7
1.1
3.1
2.5
3.4
2.2
1.4
0.9
1.7
1.1
3.1
2.5
3.4
2.2
1.4
0.9
1.7
3.5
3.9
1.6
0.9
3.9
1.7
1.0
2.4
1.1
2.0
3.5
3.9
1.6
0.9
3.9
1.7
1.0
2.4
1.1
2.0
4.4
4.3
2.2
0.6
1.2
2.6
4.7
4.3
2.1
1.6
2.0
1.4
2.4
4.4
4.3
2.2
0.6
1.2
2.6
4.7
4.3
2.1
1.6
2.0
1.4
2.4
4.4
4.3
2.2
0.6
1.2
2.6
4.7
4.3
2.1
1.6
2.0
1.4
2.4
6.9
5.1
3.6
3.3
1.0
5.4
2.0
1.6
2.0
2.4
1.4
6.9
5.1
3.6
3.3
1.0
5.4
2.0
1.6
2.0
2.4
1.4
7.5
5.1
4.1
1.2
1.1
2.8
6.2
2.8
2.0
2.0
2.4
1.7
7.5
5.1
4.1
1.2
1.1
2.8
6.2
2.8
2.0
2.0
2.4
1.7
Note: Removing the top protective cover or bottom conduit bracket from an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection
while maintaining IP20 conformity.
4-d
t2
4-d
D1
Max W2
Max W2
W3
D1
D
Max W2
Figure 1
W1
t1
H2
t1
Figure 2
6-d
W3
t2
W1
W4
W3
8-d
H1
H2
t1
Max W2
Figure 3
66
H2
D1
Max W2
t2
H1
W3
Max W2
H2
H1
H
H1
t2
W1
Max W2
Max W2
t1
D1
Figure 4
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Dimensions (in)
Figure
0250A <1>
0312A <1>
0360A <1>
0415A
W1
W2
H1
H2
D1
t1
t2
Wt. (lb)
17.72
27.76
12.99
12.80
0.39
26.77
0.49
5.12
0.13
0.13
M10
167.6
17.72
27.76
12.99
12.80
0.39
26.77
0.49
5.12
0.13
0.13
M10
176.4
19.69
31.50
13.78
14.57
0.39
30.43
0.51
5.12
0.18
0.18
M12
216.1
19.69
31.50
13.78
14.57
0.39
30.43
0.51
5.12
0.18
0.18
M12
218.3
<1> Customers may convert these models to IP20/NEMA Type 1 enclosures using an IP20/NEMA Type 1 Kit. Refer to IP20/NEMA Type 1 Kit
Selection on page 68 to select the appropriate kit.
Table 2.10 Dimensions for IP00/Open Type Enclosure: 400 V Class
Dimensions (in)
Figure
0208A <1>
0250A <1>
0296A <1>
0362A <1>
0414A
0515A
0675A
0930A
1200A
2
3
4
W1
W2
W3
W4
H1
H2
D1
t1
t2
Wt. (lb)
17.72
27.76
12.99
12.80
0.39
26.77
0.49
5.12
0.13
0.13
M10
174.2
19.69
31.50
13.78
14.57
0.39
30.43
0.51
5.12
0.18
0.18
M12
211.6
19.69
31.50
13.78
14.57
0.39
30.43
0.51
5.12
0.18
0.18
M12
224.9
19.69
31.50
13.78
14.57
0.39
30.43
0.51
5.12
0.18
0.18
M12
235.9
19.69
37.40
14.57
14.57
0.31
36.34
0.51
5.31
0.18
0.18
M12
275.6
26.38
44.88
14.57
17.32
0.24
8.66
43.70
0.59
5.91
0.18
0.18
M12
476.2
26.38
44.88
14.57
17.32
0.24
8.66
43.70
0.59
5.91
0.18
0.18
M12
487.2
49.21
54.33
14.57
43.70
0.24
13.00
17.32
52.95
0.59
5.91
0.18
0.18
M12
1201.5
49.21
54.33
14.57
43.70
0.24
13.00
17.32
52.95
0.59
5.91
0.18
0.18
M12
1223.6
<1> Customers may convert these models to IP20/NEMA Type 1 enclosures using an IP20/NEMA Type 1 Kit. Refer to IP20/NEMA Type 1 Kit
Selection on page 68 to select the appropriate kit.
Table 2.11 Dimensions for IP00/Open Type Enclosure: 600 V Class
Drive
Model
CIMRAo5A
Dimensions (in)
W
W1
W2
W3
W4
H1
H2
D1
t1
t2
Wt. (lb)
0125A <1>
17.72
27.76
12.99
12.80
0.39
26.77
0.49
5.12
0.13
0.13
M10
174.2
0145A <1>
17.72
27.76
12.99
12.80
0.39
26.77
0.49
5.12
0.13
0.13
M10
174.2
19.69
31.50
13.78
14.57
0.39
30.43
0.51
5.12
0.18
0.18
M12
235.9
19.69
31.50
13.78
14.57
0.39
30.43
0.51
5.12
0.18
0.18
M12
235.9
0192A <1>
0242A <1>
Figure
<1> Customers may convert these models to IP20/NEMA Type 1 enclosures using an IP20/NEMA Type 1 Kit. Refer to IP20/NEMA Type 1 Kit
Selection on page 68 to select the appropriate kit.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
67
Mechanical Installation
Drive
Model
CIMRAo4A
Customers may convert IP00/Open Type models to IP20/NEMA Type 1 enclosures. Refer to Table 2.12 to select the
appropriate IP20/NEMA Type 1 Kit when performing the conversion.
Contact a Yaskawa representative for IP20/NEMA Type 1 Kit availability for IP00/Open Type models not listed.
Table 2.12 IP20/NEMA Type 1 Kit Selection
IP00/Open Type Drive Model
CIMR-Ao
2A0250A
2A0312A
2A0360A
4A0208A
4A0250A
4A0296A
4A0362A
5A0125A
5A0145A
5A0192A
5A0242A
68
Comments
100-054-503
100-054-504
100-054-503
100-054-504
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3
Electrical Installation
This chapter explains proper procedures for wiring the control circuit terminals, motor, and power
supply.
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
SECTION SAFETY.................................................................................................70
STANDARD CONNECTION DIAGRAM.................................................................72
MAIN CIRCUIT CONNECTION DIAGRAM............................................................75
TERMINAL BLOCK CONFIGURATION................................................................79
TERMINAL COVER................................................................................................81
DIGITAL OPERATOR AND FRONT COVER........................................................83
TOP PROTECTIVE COVER...................................................................................86
MAIN CIRCUIT WIRING.........................................................................................87
CONTROL CIRCUIT WIRING................................................................................98
CONTROL I/O CONNECTIONS...........................................................................105
CONNECT TO A PC.............................................................................................109
EXTERNAL INTERLOCK.....................................................................................110
WIRING CHECKLIST...........................................................................................111
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
69
3.1
Section Safety
DANGER
Electrical Shock Hazard
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or
shields before operating the drives and run the drives according to the instructions described in this manual.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
Because the leakage current exceeds 3.5 mA in models CIMR-Ao4A0414 and larger, IEC 61800-5-1 states that either the
power supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective
earthing conductor with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to comply may result
in death or serious injury.
Always use appropriate equipment for Ground Fault Circuit Interrupters (GFCIs).
The drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual current
operated protective or monitoring device is used for protection in case of direct or indirect contact, always use a type B GFCI
according to IEC 60755.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work
on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with
installation, adjustment, and maintenance of AC drives.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching
any components.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Do not install the drive to a combustible surface. Never place combustible materials on the drive.
70
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
WARNING
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
When installing dynamic braking options, perform all wiring exactly as specified in the wiring diagrams provided.
Failure to do so can result in fire. Improper wiring may damage braking components.
CAUTION
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury.
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair wires
and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Carefully review instruction manual TOBPC72060000 when connecting a dynamic braking option to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other
devices.
Failure to comply could result in damage to the drive.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
71
Electrical Installation
NOTICE
3.2
Connect the drive and peripheral devices as shown in Figure 3.1. It is possible to set and run the drive via the digital operator
without connecting digital I/O wiring. This section does not discuss drive operation; Refer to Start-Up Programming &
Operation on page 113 for instructions on operating the drive.
NOTICE: Inadequate wiring could result in damage to the drive. Install adequate branch circuit short circuit protection per applicable codes.
The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac maximum (200 V class),
480 Vac maximum (400 V class), 600 Vac maximum (600 V class).
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to the motor
insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.
NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
Note: The minimum load for the relay outputs M1-M2, M3-M4, M5-M6, and MA-MB-MC is 10 mA.
72
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Three-Phase
Power Supply R
200 to 600 V
S
50/60 Hz
(Depending on T
model capacity)
+2
Multi-function
digtial inputs
(default setting)
FU
Fuse
+1
S/L2
T/L3
S1
S2
External fault
S3
Fault reset
S4
Multi-speed step 1
S5
Multi-speed step 2
Jog speed
S7
External Baseblock
S8
W/T3
TB1
PG- X3
(option) A+
A<6>
B+
BZ+
Z-
CN5-C
CN5-B
CN5-A
Terminal board
jumpers and switches
V
Off
On
PTC
SC
AI
SP
TB2
IP
IG
DIP Switch S2
Term. Res. On/Off
a+
ab+
bz+
z-
DIP Switch S4
A3 Analog/PTC
Input Sel
+24 V <6>
PG
SD
FE
DIP Switch S1
A2 Volt/Curr. Sel
Jumper S3
H1, H2
Sink/Source Sel.
SN
Ground
Option board
connectors
S6
V
W
V/T2
<4>
Cooling fan
U/T1
Control Circuit
FW
B2
B1
Drive
R/L1
FV
Braking resistor
(option) <3>
Main Circuit
EMC
Filter
Jumper
Main
Switch
<15>
A track monitor
B track monitor
Jumper S5
AM/FM Volt./Curr.
Selection
FM AM
<7>
+V
A1
MB
MC
2 k
Multi-function
analog/pulse
train inputs
M1
M2
A3
M4
0V
M5
M6
MP
AC
<7> -V
M3
Termination resistor
(120 , 1/2 W)
DIP
Switch S2
R+
R-
FM
SIG
H2
S1
0V
<10>
S+
Safety
switch
S2
A2
AC
MEMOBUS/Modbus
comm. RS485/422
max. 115.2 kBps
Electrical Installation
MA
<14>
<11>
AM
AC
FM
+ (Output frequency)
AM
0V
+ (Output current)
E (G)
Open
Safety relay /
controller
Wire
jumper
<12>
shielded line
DM+
HC
DM
73
74
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3.3
Refer to diagrams in this section when wiring the main circuit of the drive. Connections may vary based on drive capacity.
The DC power supply for the main circuit also provides power to the control circuit.
NOTICE: Do not use the negative DC bus terminal as a ground terminal. This terminal is at high DC voltage potential. Improper wiring
connections could damage the drive.
+1
Relay
+2
R/L1
Current
sensor
U/T1
S/L2
V/T2
T/L3
W/T3
Jumper
Gate board
Control
board
Operator
Electrical Installation
+1
DC link
choke
Relay
Current
sensor
R/L1
S/L2
U/T1
+
V/T2
T/L3
W/T3
Gate board
Control
board
Operator
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
75
+1
DC link
choke
Relay
R/L1
Current
sensor
U/T1
S/L2
V/T2
T/L3
W/T3
Gate board
Control
board
Operator
+1
DC link
choke
Relay
R/L1
Current
sensor
U/T1
S/L2
V/T2
T/L3
W/T3
24 V
Power
Supply
Gate board
Control
board
Operator
76
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
+1
R/L1
DC link
choke
Relay
S/L2
Current
sensor
U/T1
V/T2
T/L3
W/T3
R1/L11
S1/L21
T1/L31
24 V
Power
Supply
Gate board
Control
board
Operator
u 12-Phase Rectification
n Removing the Jumper
WARNING! Fire Hazard. Failure to remove jumpers shorting the power supply terminals on the main circuit when operating with 12-phase
rectification may cause death or serious injury by fire.
n Application Notes
Models CIMR-Ao4A0930 and 4A1200 are shipped from the factory with jumpers short-circuiting terminals R/L1-R1/L11,
S/L2-S1/L21, and T/L3-T1/L31.
Remove M5 screws and jumpers as shown in Figure 3.7 to operate with 12-phase rectification.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
77
Electrical Installation
Models CIMR-Ao4A0930 and 4A1200 are compatible for operation with 12-phase rectification. Operation with 12-phase
rectification requires the user to separately prepare a 3-winding transformer for the power supply. Contact Yaskawa or your
nearest sales representative for transformer specifications.
Jumper
S1/L21
R1/L11
T1/L31
R/L1
T/L3
S/L2
n Connection Diagram
Braking Resistor Unit
(option)
Braking Unit
(option)
+ 3
+1
U1
V1
W1
W2 V2 U2
R/L1
S/L2
T/L3
U/T1
V/T2
Motor
W/T3
R1/L11
S1/L21
T1/L31
78
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3.4
Figure 3.9 and Figure 3.10 show the different main circuit terminal arrangements for the drive capacities.
CIMR-Ao2A0004, 0006, 0008, 0010,
0012, 0018, 0021
CIMR-Ao4A0002, 0004, 0005, 0007
0009, 0011
CIMR-Ao5A0003, 0004, 0006, 0009
CIMR-Ao2A0030, 0040
CIMR-Ao4A0018, 0023
CIMR-Ao5A0011
B1
CIMR-Ao2A0056
CIMR-Ao4A0031, 0038, 0044
CIMR-Ao5A0017, 0022, 0027, 0032
B2
_
+1
+2
B1
+1
+2
V/T2
S/L2
T/L3
+1
+2
U/T1
V/T2 W/T3
CIMR-Ao2A0110, 0138
CIMR-Ao4A0058, 0072
CIMR-Ao5A0041, 0052
+2
B2
T/L3
U/T1
V/T2
B2
B1
S/L2
Electrical Installation
B1
R/L1
B2
W/T3
R/L1
CIMR-Ao2A0069, 0081
+1
U/T1
B1
+1
W/T3
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
79
CIMR-Ao4A0088, 0103
R/L1
S/L2
T/L3
+1
+3
U/T1
V/T2
W/T3
+1
R/L1
+3
S/L2
T/L3
U/T1
V/T2
W/T3
CIMR-Ao4A0414
+1
+3
R/L1
S/L2
T/L3
CIMR-Ao4A0515, 0675
U/T1
V/T2
CIMR-Ao4A0930, 1200
U/T1
V/T2
W/T3
U/T1
V/T2
W/T3
W/T3
+1
+3
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
<1> Terminal block design differs slightly for models CIMR-Ao2A0250 to 2A0415, 4A0208 to 4A0362, and 5A0125 to
5A0242.
80
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3.5
Terminal Cover
Follow the procedure below to remove the terminal cover for wiring and to reattach the terminal cover after wiring is complete.
Loosen the terminal cover screw using a #2 Phillips screwdriver. Screw sizes vary by drive model.
Figure 3.11 Removing the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
Push in on the tab located on the bottom of the terminal cover and gently pull forward to remove the terminal cover.
Electrical Installation
2.
Figure 3.12 Removing the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
Power lines and signal wiring should pass through the opening provided. Refer to Wiring the Main Circuit Terminal on
page 97 and Wiring the Control Circuit Terminal on page 102 for details on wiring.
Reattach the terminal cover after completing the wiring to the drive and other devices.
Figure 3.13 Reattaching the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
81
Loosen the screws on the terminal cover, then pull down on the cover.
Note: The terminal cover and the number of terminal cover screws differ depending on the drive model. Refer to Component Names
on page 41 for details.
CAUTION! Do not completely remove the cover screws, just loosen them. If the cover screws are removed completely, the terminal
cover may fall off causing an injury.
Figure 3.14 Removing the Terminal Cover on an IP00/Open Type Enclosure Drive
2.
Figure 3.15 Removing the Terminal Cover on an IP00/Open Type Enclosure Drive
<1>
Figure 3.16 Reattaching the Terminal Cover on an IP00/Open Type Enclosure Drive
<1> Connect the ground wiring first, then the main circuit wiring, and finally the control circuit wiring.
82
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3.6
Detach the digital operator from the drive for remote operation or when opening the front cover to install an option card.
NOTICE: Be sure to remove the digital operator prior to opening or reattaching the front cover. Leaving the digital operator plugged into the
drive when removing the front cover can result in erroneous operation caused by a poor connection. Firmly fasten the front cover back into
place before reattaching the digital operator.
Electrical Installation
Insert the digital operator into the opening in the top cover while aligning it with the notches on the left side of the opening.
Next, press gently on the right side of the operator until it clicks into place.
Figure 3.19 Remove the Front Cover (2A0004 to 2A0081, 4A0002 to 4A0044, and 5A0003 to 5A0032)
1.
2.
3.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
83
Hook
Front cover
installation screw
Hook
Free hooks on both
sides of the cover
Figure 3.20 Remove the Front Cover (2A0010 to 2A0415 and 4A0058 to 4A1200)
4.
Unhook the left side of the front cover then swing the left side towards you as shown in Figure 3.21 until the cover
comes off.
Figure 3.21 Remove the Front Cover (2A0010 to 2A0415 and 4A0058 to 4A1200)
84
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
1.
Slide the front cover so the hooks on the top connect to the drive.
Figure 3.22 Reattach the Front Cover (2A0110 to 2A0415 and 4A0058 to 4A1200)
After connecting the hooks to the drive, press firmly on the cover to lock it into place.
Electrical Installation
2.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
85
3.7
Drive models CIMR-Ao2A0004 to 2A0081, 4A0002 to 4A0058, and 5A0003 to 5A0032 are designed to IP20/NEMA Type
1 specifications with a protective cover on the top. Removing this top protective cover or the bottom conduit bracket from an
IP20/NEMA Type 1 enclosure drive voids the NEMA Type 1 protection while maintaining IP20 conformity.
86
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3.8
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in
the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices
could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus
charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the
drive on and off more than once every 30 minutes.
600 V
Class
R/L1
S/L2
T/L3
R1-L11
S1-L21
T1-L31
U/T1
V/T2
W/T3
B1
B2
+2
+1
+3
Type
2A0004 to
2A0081
4A0002 to
4A0044
5A0003 to
5A0032
2A0110 to
2A0138
4A0058 to
4A0072
5A0041 to
5A0052
2A0169 to
2A0415
4A0088 to
4A0675
5A0062 to
5A0242
4A0930 to
4A1200
Function
Page
73
73
442
For connecting:
the drive to a DC power supply
(terminals +1 and are not EU/
CE or UL approved)
dynamic braking options
a DC link choke
446
Grounding terminal
96
Not available
Drive output
Braking resistor
Not available
DC link choke
Not available
connection
(+1, +2)
(remove the
shorting bar
DC power supply
between
input
DC power supply input (+1, )
+1 and +2)
(+1, )
Braking unit connection (+3, )
DC power
supply input
(+1, )
Not available
For 200 V class: 100 or less
For 400 V class: 10 or less
For 600 V class: 10 or less
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
87
Electrical Installation
Terminal
200 V
Class
400 V Drive Model
CIMR-Ao
Class
n Insulation Barrier
Insulation barriers are packaged with drive models CIMR-Ao4A0414 through 4A1200 to provide added protection between
terminals. Yaskawa recommends using the provided insulation barriers to ensure proper wiring. Refer to Figure 3.25 for
instructions on placement of the insulation barriers.
Insulation Barrier
88
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater
than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to
calculate the amount of voltage drop:
Line drop voltage (V) = 3 wire resistance (/km) wire length (m) current (A) 10-3
Refer to instruction manual TOBP C720600 00 for braking transistor option or braking resistor option wire gauges.
Use terminal +1 and the negative terminal when connecting a braking transistor option, regenerative converter, or a regen
unit.
NOTICE: Do not connect a braking resistor to terminals +1 or . Failure to comply may cause damage to the drive circuitry.
2A0012
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
10 <1>
14 to 10
12
14 to 10
14
14 to 10
, +1, +2
14 to 10
Terminal
B1, B2
2A0018
2A0021
14 to 10
10 <1>
14 to 10
10
12 to 10
10
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
10 <1>
14 to 10
10
12 to 10
10
12 to 10
, +1, +2
12 to 10
B1, B2
2A0030
14 to 10
10 <1>
12 to 10
10 to 6
10 to 6
, +1, +2
10 to 6
B1, B2
14 to 10
8 <1>
10 to 8
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Screw
Size
Tightening Torque
Nm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
Electrical Installation
Table 3.2 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
89
2A0040
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
8 to 6
8 to 6
, +1, +2
M4
1.2 to 1.5
(10.6 to 13.3)
B1, B2
12 to 10
8 <1>
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
6 to 4
6 to 4
M6
4 to 6
(35.4 to 53.1)
, +1, +2
6 to 4
B1, B2
10 to 6
M5
2 to 2.5
(17.7 to 22.1)
8 to 6
M6
4 to 6
(35.4 to 53.1)
4 to 3
4 to 3
M8
9 to 11
(79.7 to 97.4)
, +1, +2
4 to 3
B1, B2
8 to 6
M5
2 to 2.5
(17.7 to 22.1)
6 to 4
M6
4 to 6
(35.4 to 53.1)
3 to 2
3 to 2
M8
9 to 11
(79.7 to 97.4)
, +1, +2
3 to 2
B1, B2
M5
2 to 2.5
(17.7 to 22.1)
6 to 4
M6
4 to 6
(35.4 to 53.1)
1/0
3 to 1/0
1/0
3 to 1/0
, +1
2 to 1/0
M8
B1, B2
6 to 1/0
9 to 11
(79.7 to 97.4)
6 to 4
2/0
1 to 2/0
2/0
1 to 2/0
, +1
1/0 to 3/0
M10
18 to 23
(159 to 204)
B1, B2
4 to 2/0
M8
9 to 11
(79.7 to 97.4)
4/0
2/0 to 4/0
4/0
3/0 to 4/0
, +1
1 to 4/0
M10
+3
1/0 to 4/0
18 to 23
(159 to 204)
4 to 2
1/0 2P
1/0 to 2/0
1/0 2P
1/0 to 2/0
, +1
1 to 4/0
M10
+3
1/0 to 4/0
18 to 23
(159 to 204)
4 to 1/0
Terminal
2A0056
2A0069
2A0081
2A0110 <2>
2A0138 <2>
2A0169 <2>
2A0211 <2>
90
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Model
CIMR-Ao
2A0250 <2>
2A0312 <2>
2A0360 <2>
2A0415 <2>
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
3/0 2P
3/0 to 300
3/0 2P
3/0 to 300
M12
32 to 40
(283 to 354)
, +1
3/0 to 300
+3
2 to 300
M10
18 to 23
(159 to 204)
3 to 300
M12
32 to 40
(283 to 354)
4/0 2P
3/0 to 300
3/0 2P
3/0 to 300
M12
32 to 40
(283 to 354)
, +1
3/0 to 300
+3
3/0 to 300
M10
18 to 23
(159 to 204)
2 to 300
M12
32 to 40
(283 to 354)
250 2P
4/0 to 600
4/0 2P
4/0 to 600
M12
32 to 40
(283 to 354)
, +1
250 to 600
+3
3/0 to 600
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
350 2P
250 to 600
300 2P
300 to 600
M12
32 to 40
(283 to 354)
, +1
300 to 600
+3
3/0 to 600
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
Terminal
<1> When installing an EMC filter, additional measures must be taken to comply with IEC61800-5-1. Refer to EMC Filter Installation on page 632
for details.
<2> Drive models CIMR-Ao2A0110 to 2A0415 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Wire Range
AWG, kcmil
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
Model CIMR-Ao
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
Terminal
12
14 to 12
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
10
14 to 10
12
14 to 10
14
14 to 10
, +1, +2
14 to 10
14 to 10
10
14 to 10
B1, B2
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Screw
Size
Tightening Torque
Nm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
91
Electrical Installation
Wire Range
AWG, kcmil
10
12 to 6
10
12 to 6
, +1, +2
12 to 6
B1, B2
12 to 10
10
14 to 10
10
10 to 6
10
10 to 6
, +1, +2
12 to 6
B1, B2
12 to 10
10
12 to 10
Model CIMR-Ao
4A0018
4A0023
Terminal
Screw
Size
Tightening Torque
Nm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M5
2 to 2.5
(17.7 to 22.1)
8 to 6
10 to 6
, +1, +2
10 to 6
B1, B2
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
10 to 8
M6
4 to 6
(35.4 to 53.1)
8 to 6
8 to 6
M5
2 to 2.5
(17.7 to 22.1)
, +1, +2
B1, B2
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
10 to 6
M6
4 to 6
(35.4 to 53.1)
6 to 4
6 to 4
M6
4 to 6
(35.4 to 53.1)
, +1, +2
6 to 4
B1, B2
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
8 to 6
M6
4 to 6
(35.4 to 53.1)
6 to 4
6 to 4
, +1
6 to 1
M8
B1, B2
8 to 4
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
4A0031
4A0038
4A0044
4A0058 <1>
4A0072 <1>
4A0088 <1>
4A0103 <1>
92
8 to 6
4 to 3
4 to 3
, +1
4 to 1
B1, B2
6 to 3
3 to 1/0
3 to 1/0
, +1
3 to 1/0
+3
6 to 1/0
6 to 4
1/0
2 to 1/0
2 to 1/0
, +1
3 to 1/0
+3
4 to 1/0
6 to 4
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3/0
1/0 to 4/0
4A0139 <1>
4A0165 <1>
4A0208 <1>
4A0250 <1>
4A0296 <1>
4A0362 <1>
4A0515 <1>
<2>
Terminal
2/0
1/0 to 4/0
, +1
1/0 to 4/0
+3
3 to 4/0
4/0
3/0 to 4/0
4/0
3/0 to 4/0
,+1
1 to 4/0
+3
1/0 to 4/0
4 to 2
300
2 to 300
300
2 to 300
,+1
1 to 250
+3
3 to 3/0
4 to 300
Screw
Size
Tightening Torque
Nm (lb.in.)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M12
32 to 40
(283 to 354)
400
1 to 600
400
1/0 to 600
,+1
3/0 to 600
+3
1 to 325
2 to 350
500
2/0 to 600
500
2/0 to 600
,+1
3/0 to 600
+3
1 to 325
M10
18 to 23
(159 to 204)
2 to 350
M12
32 to 40
(283 to 354)
4/0 2P
3/0 to 600
4/0 2P
3/0 to 600
M12
32 to 40
(283 to 354)
,+1
4/0 to 600
+3
3/0 to 600
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
300 2P
4/0 to 300
300 2P
4/0 to 300
,+1
3/0 to 300
M12
+3
3/0 to 300
32 to 40
(283 to 354)
M12
32 to 40
(283 to 354)
M12
32 to 40
(283 to 354)
1 to 3/0
3/0 4P
3/0 to 300
4/0 4P
3/0 to 300
,+1
1/0 to 300
+3
1/0 to 300
1/0
1/0 to 300
300 4P
4/0 to 300
300 4P
4/0 to 300
1/0 to 300
1/0 to 300
2/0
2/0 to 300
,+1
+3
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Electrical Installation
Recomm. Gauge
AWG, kcmil
Model CIMR-Ao
93
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
4/0 4P2
3/0 to 300
Model CIMR-Ao
4A0930 <1>
4A1200 <1>
<2>
<2>
4/0 4P2
3/0 to 300
,+1
4/0 to 300
+3
4/0 to 300
3/0
3/0 to 250
300 4P2
4/0 to 300
300 4P2
4/0 to 300
250 to 300
4/0 to 300
4/0
4/0 to 250
,+1
+3
Screw
Size
Tightening Torque
Nm (lb.in.)
M12
32 to 40
(283 to 354)
M12
32 to 40
(283 to 354)
<1> Drive models CIMR-Ao4A0058 to 4A1200 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
<2> When installing an EMC filter, additional measures must be taken to comply with IEC61800-5-1. Refer to EMC Filter Installation on page 632
for details.
Wire Range
AWG, kcmil
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
Model CIMR-Ao
5A0003
5A0004
5A0006
5A0009
Terminal
B1, B2
14 to 10
10
14 to 10
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
5A0011
5A0017
5A0022
94
14 to 10
10
12 to 10
10
14 to 6
14
14 to 6
, +1, +2
14 to 6
B1, B2
14 to 10
12 to 8
10
10 to 6
10
10 to 6
, +1, +2
10 to 6
B1, B2
10 to 8
12 to 8
10 to 6
10
10 to 6
, +1, +2
10 to 6
B1, B2
10 to 8
10 to 6
Screw
Size
Tightening Torque
Nm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M5
2 to 2.5
(17.7 to 22.1)
M6
4 to 6
(35.4 to 53.1)
M5
2 to 2.5
(17.7 to 22.1)
M6
4 to 6
(35.4 to 53.1)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
6 to 4
6 to 4
M6
4 to 6
(35.4 to 53.1)
, +1, +2
6 to 4
B1, B2
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
10 to 6
M6
4 to 6
(35.4 to 53.1)
10 to 3
10 to 3
, +1, +2
6 to 1
M8
B1, B2
12 to 3
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
Model CIMR-Ao
5A0027
5A0032
5A0041
5A0052
5A0062
5A0077
5A0099
5A0125
5A0145
Terminal
10 to 3
10 to 3
, +1, +2
6 to 1
B1, B2
8 to 3
10 to 4/0
10 to 4/0
, +1, +2
4 to 4/0
B1, B2
6 to 4/0
10 to 4/0
10 to 4/0
, +1, +2
3 to 4/0
B1, B2
6 to 4/0
1/0
10 to 4/0
10 to 4/0
, +1, +2
2 to 4/0
B1, B2
4 to 4/0
2/0
1 to 300
2/0
1 to 300
, +1
2/0 to 3/0
+3
1 to 1/0
4 to 300
3/0
2/0 to 300
3/0
2/0 to 300
, +1
3/0 to 4/0
+3
1/0 to 2/0
3
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M12
32 to 40
(283 to 354)
4 to 300
300
2/0 to 600
250
2/0 to 600
, +1
2/0 to 400
+3
2/0 to 250
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
5A0192
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Electrical Installation
95
Wire Range
AWG, kcmil
400
2/0 to 600
350
2/0 to 600
, +1
2/0 to 500
+3
Model CIMR-Ao
Terminal
Screw
Size
Tightening Torque
Nm (lb.in.)
M12
32 to 40
(283 to 354)
250 to 300
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
5A0242
50 m or less
15 kHz or less
100 m or less
5 kHz or less
Note: 1. When setting carrier frequency for drives running multiple motors, calculate cable length as the total wiring distance to all connected motors.
2. The maximum cable length when using OLV/PM (A1-02 = 5) or AOLV/PM (A1-02 = 6) is 100 m.
n Ground Wiring
Follow the precautions below when wiring the ground for one drive or a series of drives.
WARNING! Electrical Shock Hazard. Make sure the protective earthing conductor complies with technical standards and local safety
regulations. Because the leakage current exceeds 3.5 mA in models CIMR-Ao4A0414 and larger, IEC 61800-5-1 states that either the
power supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing
conductor with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to comply may result in death or serious injury.
WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize
the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could
result in death or serious injury.
WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal (200 V class: ground to 100 or less; 400 V class: ground
to 10 or less; 600 V class: ground to 10 or less). Improper equipment grounding could result in death or serious injury by contacting
ungrounded electrical equipment.
NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper
equipment grounding could result in drive or equipment malfunction due to electrical interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in
abnormal operation of drive or equipment.
Refer to Figure 3.26 when using multiple drives. Do not loop the ground wire.
96
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
OK
NOT OK
Wire the main circuit terminals after the terminal board has been properly grounded.
Models CIMR-Ao2A0004 to 2A0081, 4A0002 to 4A0044, and 5A0003 to 5A0032 have a cover placed over the DC bus and
braking circuit terminals prior to shipment to help prevent miswiring. Use wire cutters to cut away covers as needed for
terminals.
B1
B2
A
B
+1
+2
U/T1
V/T2
W/T3
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
97
Electrical Installation
3.9
n Input Terminals
Table 3.6 lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.
Table 3.6 Control Circuit Input Terminals
Type
Multi-Function
Digital Inputs
Safe Disable
Inputs
98
No.
S1
S2
Multi-function input 2
(Closed: Reverse run, Open: Stop)
S3
Multi-function input 3
(External fault, N.O.)
S4
Multi-function input 4
(Fault reset)
S5
Multi-function input 5
(Multi-step speed reference 1)
S6
Multi-function input 6
(Multi-step speed reference 2)
S7
Multi-function input 7
(Jog reference)
S8
Multi-function input 8
(External baseblock)
SC
SP
105
SN
105
H1
H2
HC
Photocoupler
24 Vdc, 8 mA
Set the S3 jumper to select between sinking, sourcing mode, and
the power supply. Refer to Sinking/Sourcing Mode Switch for
Digital Inputs on page 105.
24 Vdc, 8 mA
One or both open: Output disabled
Both closed: Normal operation
Internal impedance: 3.3 k
Off time of at least 1 ms
Disconnect the wire jumpers shorting terminals H1, H2, and HC to
use the Safe Disable inputs. Set the S5 jumper to select between
sinking, sourcing mode, and the power supply as explained on page
105.
Safe disable function common
Page
248
651
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Analog Inputs /
Pulse Train
Input
No.
RP
+V
-V
A1
A2
A3
AC
Page
163
277
162
162
269
162
162
271
162
162
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
n Output Terminals
Table 3.7 lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.
Table 3.7 Control Circuit Output Terminals
No.
MA
Fault Relay
MB
Output
MC
M1
M2
Multi-Function M3
Digital Output
M4
<1>
M5
M6
MP
FM
Monitor
Output
AM
AC
Safety Monitor DM+
Output <2>
DM-
Page
259
259
32 kHz (max)
277
275
0V
Outputs status of Safe Disable function. Closed when both Safe
Disable channels are closed. Up to +48 Vdc 50 mA
653
<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching
life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
Connect a suppression diode as shown in Figure 3.28 when driving a reactive load such as a relay coil. Ensure the diode rating
is greater than the circuit voltage.
B
C
D
C Coil
D 50 mA or less
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
99
Electrical Installation
Type
MEMOBUS/Modbus
Communication <1>
No.
R+
RS+
SIG
Signal Name
Communications input (+)
Communications input (-)
Communications output (+)
Communications output (-)
Shield ground
<1> Enable the termination resistor in the last drive in a MEMOBUS/Modbus network by setting DIP switch S2 to the ON position. Refer to Control
I/O Connections on page 105 for more information on the termination resistor.
u Terminal Configuration
The control circuit terminals are arranged as shown in Figure 3.29.
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
M3 M6 M4
M1 M2 M5
MA MB MC
100
Screw
Size
M3
Tightening
Torque
Nm
(lb. in)
0.5 to 0.6
(4.4 to 5.3)
Stranded wire:
0.2 to 1.0
(24 to 16)
Solid wire:
0.2 to 1.5
(24 to 16)
0.75 (18)
Ferrule-Type Terminal
Applicable
Recomm.
wire size
wire size
mm2 (AWG)
mm2 (AWG)
0.25 to 0.5
(24 to 20)
0.5 (20)
Wire Type
Shielded wire,
etc.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
8 mm
d1
d2
mm2
(AWG)
0.25 (24)
0.34 (22)
L (mm)
d1 (mm)
d2 (mm)
Manufacturer
12.5
10.5
0.8
0.8
1.8
1.8
AI 0.5-8WH or
AI 0.5-8OG
PHOENIX CONTACT
14
1.1
2.5
Electrical Installation
0.5 (20)
Type
AI 0.25-8YE
AI 0.34-8TQ
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
101
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete. Refer to
Terminal Board Wiring Guide on page 102 for details. Prepare the ends of the control circuit wiring as shown in Figure
3.33. Refer to Wire Gauges on page 100.
NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may result in erroneous operation, damage to the
terminal block, or cause a fire.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or
equipment malfunction due to electrical interference.
Preparing wire
terminal ends
C
102
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires (preparing
wire ends as shown in Figure 3.33) and connect the shield to the ground terminal of the drive.
A Drive side
B Connect shield to ground terminal
of drive.
C Insulation
Electrical Installation
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
103
Jumper S5
Terminal AM/FM Signal
Selection
Jumper S3
Terminal H1/H2
Sink/Source Sel.
I
AM
FM
DIP Switch S4
Terminal A3 Analog/
PTC Input Sel.
DIP Switch S2
RS-422/485 Termination
Resistor
Off
PTC
On
AI
104
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
S7
S7
S8
S8
SN
SN
SC
SC
24 Vdc
24 Vdc
SP
External
24 Vdc
SP
S7
S7
S8
S8
SN
SN
SC
Electrical Installation
Mode
SC
24 Vdc
SP
External
24 Vdc
24 Vdc
SP
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
105
Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe Disable
inputs H1 and H2 as shown in Table 3.11 (Default: Source mode, internal power supply). Refer to Switches and Jumpers
on the Terminal Board on page 104 for locating jumper S3.
Table 3.12 Safe Disable Input Sink/Source/External Power Supply Selection
Mode
Jumper S3
24 Vdc
24 Vdc
HC
HC
External
24 Vdc
Sinking Mode
H1
H1
H2
H2
Jumper S3
Jumper S3
24 Vdc
24 Vdc
HC
HC
External
24 Vdc
Sourcing Mode
H1
H1
H2
H2
1.5 k
4 k
10 k
5V
8V
10 V
Note: The load resistance needed in order to get a certain high level voltage VMP can be calculated by: RL = VMP 2 / (12 VMP)
Load Impedance
MP
VMP
RL
AC
106
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Load Impedance
MP
Sink Current
AC
Description
Voltage input (-10 to +10 V)
Current input (4 to 20 mA or 0 to 20 mA): default setting
Table 3.14 Parameter H3-09 Details
No.
H3-09
Parameter Name
Description
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
Setting
Range
Default
Setting
0 to 3
Description
Analog input for the function selected in parameter H3-06
PTC input. Parameter H3-06 must be set to E (PTC input)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Electrical Installation
107
Voltage Output
Current Output
Terminal AM
FM AM
FM AM
Terminal FM
FM AM
FM AM
Parameter Name
Description
H4-07
H4-08
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
Setting
Range
Default
Setting
0 to 2
u MEMOBUS/Modbus Termination
This drive is equipped with a built-in termination resistor for the RS-422/485 communication port. DIP switch S2 enables or
disabled the termination resistor as shown in Table 3.18. The OFF position is the default. The termination resistor should be
placed to the ON position when the drive is the last in a series of slave drives. Refer to Switches and Jumpers on the Terminal
Board on page 104 to locate switch S2.
Table 3.18 MEMOBUS/Modbus Switch Settings
S2 Position
ON
OFF
Description
Internal termination resistor ON
Internal termination resistor OFF (default setting)
108
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3.11 Connect to a PC
3.11 Connect to a PC
This drive is equipped with a USB port (type-B).
The drive can connect to a USB port on a PC using a USB 2.0, AB-type cable (sold separately). After connecting the drive to
a PC, Yaskawa DriveWizard Plus software can be used to monitor drive performance and manage parameter settings. Contact
Yaskawa for more information on DriveWizard Plus.
USB Cable
(Type-AB)
(Type-B)
(Type-A)
PC
Electrical Installation
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
109
u Drive Ready
When the Drive ready signal has been set to one of the multi-function contact outputs, that output will close whenever the
drive is ready to accept a Run command or is already running. Under the following conditions the Drive ready signal will
switch off and remain off, even if a Run command is entered:
when the power supply is shut off
during a fault
when there is problem with the control power supply
when a parameter setting error makes the drive unable to run even if a Run command has been entered
when a fault such as overvoltage or undervoltage is triggered as soon as the Run command is entered
when the drive is in the Programming mode and will not accept a Run command even when entered
Output Signal
Fault
Drive Ready
Ready1
Ready2
Fault1
Parameter Setting
H2-01 = 06
Fault2
Operation
Circuit
Stop
Drive Ready
Run
Drive 1
Controller
MA
Run
S1
SC
Fault
Output
Drive Ready
Relay 1
MB
SA
Max
250 Vac
Relay 1
Relay 2
SA
Relay 2
M1
Drive Ready
Controller
MA
S1
SC
Fault
Output
MB
Relay 1
SA
Max
250 Vac
Relay 1
Fault 2
MC
Relay 2
SA
Relay 2
M1
Drive Ready
Ready 1
M2
Drive 2
Run
Fault 1
MC
Ready 2
M2
110
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Item
Page(s)
35
Make sure you have the correct braking resistors, DC link chokes, noise filters, and other peripheral devices.
437
437
Ensure that the area surrounding the drive complies with specifications.
The voltage from the power supply should be within the input voltage specification range of the drive.
224
The voltage rating for the motor should match the drive output specifications.
35
329
Confirm proper branch circuit protection as specified by national and local codes.
72
Properly wire the power supply to drive terminals R/L1, S/L2, and T/L3.
Note: Confirm the following when wiring models CIMR-Ao4A0930 and 4A1200:
Remove the jumpers shorting terminals R/L1-R1/L11, S/L2-S1/L21, and T/L3-T1/L31 when operating
with 12-phase rectification. Refer to 12-Phase Rectification on page 77 for details.
When operating without 12-phase rectification, properly wire terminals R1/L11, S1/L21, and T1/L31
in addition to terminals R/L1, S/L2, and T/L3.
75
10
96
11
Use 600 Vac vinyl-sheathed wire for the power supply and motor lines.
89
89
12
Use the correct wire gauges for the main circuit. Refer to Wire Gauges and Tightening Torque on page 89.
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is
greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following
formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 wire resistance (/km) wire length (m) current (A) 10-3
If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency set to C6-02 accordingly.
13
96
14
Tighten control circuit and grounding terminal screws. Refer to Wire Gauges and Tightening Torque on page 89.
89
Electrical Installation
96
Set up overload protection circuits when running multiple motors from a single drive.
Power supply
Drive
MC1
OL1
MC2
OL2
M1
15
M2
MCn
OLn
Mn
Note: Close MC1 MCn before operating the drive. MC1 MCn cannot be switched off during run.
16
Install a magnetic contactor when using a dynamic braking option. Properly install the resistor and ensure that overload
protection shuts off the power supply using the magnetic contactor.
17
Verify phase advancing capacitors, input noise filters, or GFCIs are NOT installed on the output side of the drive.
442
102
19
102
20
For 3-Wire sequence, set parameters for multi-function contact input terminals S1 S8, and wire control circuits.
21
22
Check for any other wiring mistakes. Only use a multimeter to check wiring.
23
Properly fasten drive control circuit terminal screws. Refer to Wire Gauges and Tightening Torque on page 89.
89
24
terminal.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
102
111
112
Item
Page(s)
25
Ensure that no frayed wires on the terminal block are touching other terminals or connections.
26
27
28
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4
Start-Up Programming & Operation
This chapter explains the functions of the digital operator and how to program the drive for initial
operation.
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
SECTION SAFETY...............................................................................................114
USING THE DIGITAL OPERATOR......................................................................115
THE DRIVE AND PROGRAMMING MODES.......................................................120
START-UP FLOWCHARTS.................................................................................126
POWERING UP THE DRIVE................................................................................131
APPLICATION SELECTION................................................................................132
AUTO-TUNING.....................................................................................................135
NO-LOAD OPERATION TEST RUN....................................................................148
TEST RUN WITH LOAD CONNECTED...............................................................150
VERIFYING PARAMETER SETTINGS AND BACKING UP CHANGES............151
TEST RUN CHECKLIST.......................................................................................153
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
113
4.1
Section Safety
DANGER
Electrical Shock Hazard
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may include drives without covers or safety shields to illustrate details. Be sure to reinstall
covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Prepare a separate holding brake.
Wire the holding brake so when a fault occurs, it is activated by an external sequence and shuts the power off or triggers an
emergency switch. Failure to comply could result in death or serious injury.
114
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.2
Use the digital operator to enter Run and Stop commands, edit parameters, and display data including fault and alarm
information.
12
11
F1
F2
ESC
3
10
RESET
RUN
5 6
LO
RE
ENTER
STOP
Display
F1
F2
ESC
3
4
Name
Function
Function Key
(F1, F2)
The functions assigned to F1 and F2 vary depending on the currently displayed menu. The
name of each function appears in the lower half of the display window.
ESC Key
RESET Key
RUN Key
Up Arrow Key
Scrolls up to display the next item, selects parameter numbers, and increments setting
values.
Scrolls down to display the previous item, selects parameter numbers, and decrements
setting values.
RUN
STOP
STOP Key
<1>
ENTER Key
10
RUN Light
Lit while the drive is operating the motor. Refer to page 117 for details.
11
LO/RE Light
Lit while the operator is selected to run the drive (LOCAL mode). Refer to page 117 for
details.
12
<2>
<1> The STOP key has highest priority. Pressing the STOP key will always cause the drive to stop the motor, even if a Run command is active at any
external Run command source. To disable the STOP key priority, set parameter o2-02 to 0.
<2> The LO/RE key can only switch between LOCAL and REMOTE when the drive is stopped. To disable the LO/RE key to prohibit switching between
LOCAL and REMOTE, set parameter o2-01 to 0.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
115
Start-Up Programming
& Operation
No.
u LCD Display
1
5
6
10
Name
DriveWorksEZ
Function Selection
4
5
Ready
Data Display
Frequency
Reference
Assignment <1>
LO/RE
Display <2>
Display
MODE
MONITR
VERIFY
PRMSET
A.TUNE
SETUP
DWEZ
DRV
PRG
Rdy
OPR
AI
COM
OP
RP
RSEQ
LSEQ
RREF
LREF
Content
Displayed when in Mode Selection.
Displayed when in Monitor Mode.
Indicates the Verify Menu.
Displayed when in Parameter Setting Mode.
Displayed during Auto-Tuning.
Displayed when in Setup Mode.
Displayed when DriveWorksEZ is set to enable. (A1-07 = 1 or 2)
Displayed when in Drive Mode.
Displayed when in Programming Mode.
Indicates the drive is ready to run.
Displays specific data and operation data.
Displayed when the frequency reference is assigned to the LCD Operator Option.
Displayed when the frequency reference is assigned to the Analog Input of the drive.
Displayed when the frequency reference is assigned to the MEMOBUS/Modbus Communication
Inputs of the drive.
Displayed when the frequency reference is assigned to an Option Unit of the drive.
Displayed when the frequency reference is assigned to the Pulse Train Input of the drive.
Displayed when the run command is supplied from a remote source.
Displayed when the run command is supplied from the operator keypad.
Displayed when the run command is supplied from a remote source.
Displayed when the run command is supplied from the operator keypad.
FWD/REV Pressing
8
Function Key 2
(F2)
116
FWD/REV
DATA
Pressing
F2
Pressing
F2
RESET
9
F2
FWD
REV
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Display
Function Key 1
(F1)
10
Content
JOG
Pressing
F1
HELP
Pressing
F1
Pressing
F1
HOME
Pressing
F1
ESC
Pressing
F1
Content
Display
Off
During run
Examples
<1> Refer to Figure 4.3 for the difference between flashing and flashing quickly.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Start-Up Programming
& Operation
LED
117
ON
Flashing
Flashing
quickly
ON
ON
ON
ON
/
Frequency setting
RUN LED
during stop
0 Hz
RUN
RUN
STOP
STOP
6 Hz
OFF
ON
OFF
OFF
Flashing
118
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
U1-01= 000.00Hz
0.0060.00
0.00Hz
FWD
- MODE PRG
Modified Consts
Modified
X Parameters
HELP FWD DATA
U2-02= oPr
LSEQ
U2-03= 0.00Hz LREF
JOG FWD FWD/REV
- MODE PRG
Quick Setting
<4>
<3>
A1000
XXXV, X.X/X.XkW
XX.XX/XX.XXA
<XXXXXXXXX>
- MODE PRG
Programming
<6>
Start-Up Programming
& Operation
RUN
Pressing
will start the motor.
Drive cannot operate motor.
Flashing characters are shown as 0 .
X characters are used as examples in this manual. The LCD Operator will display the actual setting values.
The Frequency Reference appears after the initial display that shows the product name.
The information that appears on the display will vary depending on the drive.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
119
4.3
The drive has a Drive Mode to operate the motor and a Programming Mode to edit parameter settings.
Drive Mode: In Drive Mode the user can operate the motor and observe U Monitor parameters. Parameter settings cannot be
edited or changed when in Drive Mode.
Programming Mode: In Programming Mode the user can edit and verify parameter settings and perform Auto-Tuning. When
the drive is in Programming Mode it will not accept a Run command unless b1-08 is set to 1.
Note: 1. If b1-08 is set to 0, the drive will only accept a Run command in Drive Mode. After editing parameters, the user must exit the Programming
Mode and enter Drive Mode before operating the motor.
2. Set b1-08 to 1 to allow motor operation from the drive while in Programming Mode.
Power Up
Contents
Frequency
Reference
(default)
Drive Mode
Monitor Display
Verify Menu
and
Operator Display
Description
This display screen allows the user to monitor and change the frequency reference while
the drive is running. Refer to The Drive and Programming Modes on page 120.
Note: The user can select the data displayed when the drive is first powered up with
parameter o1-02.
- MODE PRG
Modified Consts
Modified
X Parameters
HELP FWD DATA
- MODE PRG
Quick Setting
Setup Group
HELP FWD DATA
Lists all parameters that have been edited or changed from default settings.
Verifying Parameter Changes: Verify Menu on page 123.
Refer to
Refer to
Note: Parameters listed in the Setup Group differ depending the Application Preset
in parameter A1-06. Refer to Application Selection on page 132.
Programming
Mode
Parameter
Setting Mode
- MODE PRG
Programming
Auto-Tuning
Mode
Refer to Auto-Tuning on
120
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Contents
Operator Display
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
Frequency
Reference
Drive Mode
Description
U1-01= 000.00Hz
0.0060.00
0.00Hz
FWD
F2
right
U1-01= 006.00Hz
0.0060.00
0.00Hz
FWD
Entry Accepted
F1
left
ESC
Note: The drive will not accept a change to the frequency reference until the ENTER key is pressed after the frequency reference is entered. This
feature prevents accidental setting of the frequency reference. To have the drive accept changes to the frequency reference as soon as changes
are made without requiring the ENTER key, set o2-05 to 1.
Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz LSEQ
U1-03= 0.00A LREF
JOG FWD FWD/REV
- MODE PRG
Programming
2. Press
or
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
121
Start-Up Programming
& Operation
Figure 4.6 Setting the Frequency Reference while in the Drive Mode
Display/Result
-PRMSET- PRG
Initialization
3. Press
A1-00= 0
Select Language
FWD
-PRMSET- PRG
Basic Setup
4. Press
or
5. Press
two times.
FWD
-PRMSET- PRG
Accel/Decel
-PRMSETPRG
Accel Time 1
C1-01= 10.0Sec
(0.0~6000.0)
10.0 sec
FWD
FWD
-PRMSETPRG
Decel Time 1
6. Press
or
C1-02= 10.0Sec
(0.0~6000.0)
10.0 sec
FWD
PRG
-PRMSETDecel Time 1
7. Press
to view the current setting value (10.0 s). The leftmost digit flashes.
C1-02= 0010.0Sec
(0.0~6000.0)
10.0 sec
FWD
-PRMSETPRG
Decel Time 1
8. Press
F1
F2
, or
C1-02=0010.0Sec
(0.0~6000.0)
10.0 sec
FWD
-PRMSETPRG
Decel Time 1
9. Press
C1-02=0020.0Sec
(0.0~6000.0)
10.0 sec
FWD
10. Press
Entry Accepted
PRG
-PRMSETDecel Time 1
C1-02= 20.0Sec
(0.0~6000.0)
10.0 sec
FWD
12. Press
122
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The following example is a continuation of the steps above. Here, parameter C1-02 is accessed using the Verify Menu, and
is changed again from 10.0 s to 20.0 s.
To check the list of edited parameters:
Step
1.
Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
2.
Press
3.
Press
settings.
or
to enter the list of parameters that have been edited from their original default
or
- MODE PRG
Modified Consts
Modified
X Parameters
HELP FWD DATA
Press
C1-01=0020.0sec
(0.0~6000.0)
10.0sec
Home FWD DATA
Start-Up Programming
& Operation
4.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
123
- MODE PRG
Quick Setting
Frequency reference
appears when
powered up
<1>
Parameter Display
Control Circuit
Terminal
<2>
b1-01= 1 *1*
Analog Input
Entry Accepted
- SETUP - PRG Rdy
Run Source 1
b1-02= 1 *1*
Digital Inputs
b1-01= 0 *1*
Operator
1
FWD
Operator
<2>
124
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Control Method Selection
Frequency Reference Selection 1
Run Command Selection 1
Stopping Method Selection
Acceleration Time 1
Deceleration Time 1
Drive Duty Mode
Carrier Frequency Selection
Frequency Reference 1
Frequency Reference 2
Frequency Reference 3
Frequency Reference 4
Jog Frequency Reference
Input Voltage Setting
Maximum Output Frequency
Maximum Voltage
Base Frequency
Parameter
E1-09
E1-13
E2-01
E2-11
E5-01
E5-02
E5-03
E5-04
E5-05
E5-06
E5-07
E5-09
E5-24
H4-02
H4-05
L1-01
L3-04
Name
Minimum Output Frequency
Base Voltage
Motor Rated Current
Motor Rated Power
Motor Code Selection
Motor Rated Power
Motor Rated Current
Number of Motor Poles
Motor Stator Resistance
Motor d-Axis Inductance
Motor q-Axis Inductance
Motor Induction Voltage Constant 1
Motor Induction Voltage Constant 2
Multi-Function Analog Output Terminal FM Gain
Multi-Function Analog Output Terminal AM Gain
Motor Overload Protection Function Selection
Stall Prevention Selection during Deceleration
Switch the operation between LOCAL and REMOTE using the LO/RE key on the digital operator or via a digital input.
Note: 1. After selecting LOCAL, the LO/RE light will remain lit.
2. The drive will not allow the user to switch between LOCAL and REMOTE during run.
Display/Result
- MODE - DRV Rdy
FREF (A1/A2)
U1-01= 0.00Hz
U1-02= 0.00Hz RSEQ
U1-03= 0.00A RREF
JOG FWD FWD/REV
ALM
. The LO/RE light will light up. The drive is now in LOCAL.
2. Press
To set the drive for REMOTE operation, press the
key again.
F1
F2
LO
RE
ESC
RESET
RUN
ENTER
STOP
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Start-Up Programming
& Operation
Note: Parameter availability depends on the control mode set in A1-02; some parameters listed above may not be accessible in all control modes.
125
4.4
Start-Up Flowcharts
These flowcharts summarize steps required to start the drive. Use the flowcharts to determine the most appropriate start-up
method for a given application. The charts are quick references to help familiarize the user with start-up procedures.
Note: 1. Refer to Application Selection on page 132 to set up the drive using one of the Application Presets.
2. Function availability differs for drive models CIMR-Ao4A0930 and 4A1200. Refer to Parameter List on page 475 for details.
Flowchart
A
Subchart
A-1
A-2
A-3
126
Objective
Basic start-up procedure and motor tuning
Simple motor setup using V/f mode
High-performance operation using Open Loop Vector or Closed Loop Vector motor control
Setting up the drive to run a permanent magnet (PM) motor
Note: PM motor control modes are not available on 600 V class drives,
CIMR-Ao5oooooo.
Page
127
128
129
130
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Application Presets
A1-06 used?
YES
NO
Refer to
Application
Selection section
Control Mode
A1-02 =
To
Flowchart A-1
5: OLV/PM
6: AOLV/PM
7: CLV/PM
2: OLV
3: CLV
To
Flowchart A-3
To
Flowchart A-2
Start-Up Programming
& Operation
0: V/f
1: V/f w/PG
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
127
Is there a
PG encoder
on the motor?
YES
NO
Set or verify the V/f pattern settings E1-oo.
Set or verify the V/f pattern
settings E1-oo.
Enter the number of motor poles to E2-04 (or E4-04 for motor 2).
Energy Savings
(b8-01 = 1) or
Speed Estimation Speed Search
(b3-24 = 1) enabled
when b3-01 = 1
or L2-01 = 1,2 ?
NO
YES
Perform Rotational
Auto-Tuning for V/f Control
(T1-01 = 3)
YES
Is the motor cable longer than
50 meters?
NO
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Return to
Flowchart
A
Figure 4.9 Simple Motor Setup with Energy Savings or Speed Search
128
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
YES
NO
NO
YES
<2>
YES
Perform Stationary
Auto-Tuning 2 (T1-01 = 4)
Perform Rotating
Auto-Tuning (T1-01 = 0)
NO
Perform Stationary
Auto-Tuning 1 (T1-01 = 1)
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Is there a PG
encoder on the
motor?
NO
Should the
drive set ASR gain
automatically?
Start-Up Programming
& Operation
YES
YES
NO
NO
YES
4
Perform Inertia Tuning
(T1-01 = 8) <3>
Return to
Flowchart
A
Figure 4.10 Flowchart A2: High Performance Operation Using OLV or CLV
<1> Decouple the load from the motor to properly perform Rotational Auto-Tuning.
<2> Rotational Auto-Tuning can still be performed if the load is 30% or less, though Stationary Auto-Tuning may yield better control
performance.
<3> Make sure the motor and load can run freely (i.e., if a brake is mounted, make sure it is released).
<4> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward and the KEB Ride-Thru
function.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
129
Flowchart A3 in Figure 4.11 describes the setup procedure for running a PM motor in Open Loop Vector Control. PM motors
can be used for more energy-efficient operation in reduced or variable torque applications.
Note: 1. Although the drive sets parameters for the PG encoder during Auto-Tuning, sometimes the direction of the motor and direction of the PG
get reversed. Use parameter F1-05 to switch the direction of the PG so that it matches the motor direction.
2. Realign the Z Pulse if the PG encoder is replaced. Set T2-01 to 3 to recalibrate the drive for the new encoder.
From
Flowchart
A
YES
NO
Perform PM Stationary
Auto-Tuning (T2-01 = 1)
<1>
NO
YES
Perform PM Stationary
Auto-Tuning for Stator
Resistance (T2-01 = 2)
Run the motor without load; check the rotation direction and
operation.Verify external signal commands to the drive work as desired.
Is there a PG
encoder on the
motor?
NO
YES
YES
NO
YES
NO
Perform Back EMF Constant Tuning (T2-01 = 11) <4> <5> <6>
Return to
Flowchart
A
130
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.5
Description
200 V class: Three-phase 200 to 240 Vac 50/60 Hz
400 V class: Three-phase 380 to 480 Vac 50/60 Hz
600 V class: Three-phase 500 to 600 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3). <1>
Check for proper grounding of drive and motor.
Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.
Check control circuit terminal connections.
Open all control circuit terminals (off).
Status of the load and connected Decouple the motor from the load.
machinery
<1> Confirm the following when connecting models CIMR-Ao4A0930 and 4A1200: Remove the jumpers on R1/L11, S1/L21, and T1/L31 when using
12-phase rectification. Refer to 12-Phase Rectification on page 77 for details. When operating without 12-phase rectification, properly wire
terminals R1/L11, S1/L21, and T1/L31 in addition to terminals R/L1, S/L2, and T/L3.
n Status Display
When the power supply to the drive is turned on, the digital operator lights will appear as follows:
Name
DIGITAL OPERATOR JVOP-180
Normal
Operation
Description
ALARM
ESC
DIGITAL
OPERATOR JVOP-180
RESET
- MODE -
is lit.
LO
RE
ALARM
DRV
RUNEF3
Fault
ENTER
STOP
Ext Fault S3
FWD RESET
Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and Possible
Solutions on page 347 for more information.
and
are lit.
ESC
RESET
RUN
ENTER
STOP
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Start-Up Programming
& Operation
Status
131
4.6
Application Selection
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters
to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
An Application Preset can either be selected from the Application Selection menu in the Setup Group (Refer to Simplified
Setup Using the Setup Group on page 124) or in parameter A1-06. The following presets can be selected:
Note: 1. Application Presets can only be selected if all drive parameters are at their original default settings. It may be necessary to initialize the
drive by setting A1-03 to 2220 or 3330 prior to selecting an Application Preset.
2. Entering a value to A1-06 to enable an Application Preset will fix that value to the parameter. The value cannot be changed without first
setting A1-03 to 2220 or 3330 to initialize the drive.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter
A1-06 may automatically change the I/O terminal function from the default setting. Failure to comply may result in death or serious injury.
No.
A1-06
Parameter Name
Setting Range
0: Disabled
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC
5: Compressor
Application Presets
Default
No.
A1-02
b1-04
C1-01
C1-02
C6-01
E1-03
E1-07
E1-08
L2-01
L3-04
Name
Control Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Duty Rating
V/f Pattern Selection
Mid Output Frequency
Mid Output Frequency Voltage
Momentary Power Loss Operation Selection
Stall Prevention Selection during Deceleration
Default Setting
0: V/f Control
1: Reverse Prohibited
1.0 s
1.0 s
1: Normal Duty
0FH
30.0 Hz
50.0 V
1: Enabled
1: Enabled
No.
b1-01
b1-02
Parameter Name
Frequency Reference Selection
Run Command Selection
No.
E1-08
E2-01
b1-04
H1-05
C1-01
Acceleration Time 1
H1-06
C1-02
Deceleration Time 1
H1-07
E1-03
E1-07
L5-01
132
Parameter Name
Mid Output Frequency Voltage
Motor Rated Current
Multi-Function Digital Input Terminal S5 Function
Selection
Multi-Function Digital Input Terminal S6 Function
Selection
Multi-Function Digital Input Terminal S7 Function
Selection
Number of Auto Restart Attempts
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
No.
A1-02
C1-01
C1-02
C6-01
L3-04
Parameter Name
Control Method Selection
Acceleration Time 1
Deceleration Time 1
Duty Rating
Stall Prevention Selection during Deceleration
Default Setting
0: V/f Control
3.0 s
3.0 s
0: Heavy Duty
1: Enabled
No.
A1-02
b1-01
b1-02
C1-01
Parameter Name
Control Method Selection
Frequency Reference Selection
Run Command Selection
Acceleration Time 1
No.
C1-02
E2-01
L3-04
Parameter Name
Deceleration Time 1
Motor Rated Current
Stall Prevention Selection during Deceleration
Parameter Name
Control Method Selection
Reverse Operation Selection
Duty Selection
V/f Pattern Selection
Mid Output Frequency
Mid Output Frequency Voltage
Momentary Power Loss Operation Selection
Stall Prevention Selection during Deceleration
Default Setting
0: V/f Control
1: Reverse Prohibited
1: Normal Duty
0FH
30.0 Hz
50.0 V
1: Enabled
1: Enabled
No.
b1-01
b1-02
b1-04
Parameter Name
Frequency Reference Selection
Run Command Selection
Reverse Operation Selection
No.
E1-07
E1-08
E2-01
b3-01
H1-05
C1-01
Acceleration Time 1
H1-06
C1-02
Deceleration Time 1
H1-07
E1-03
L5-01
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Mid Output Frequency
Mid Output Frequency Voltage
Motor Rated Current
Multi-Function Digital Input Terminal S5 Function
Selection
Multi-Function Digital Input Terminal S6 Function
Selection
Multi-Function Digital Input Terminal S7 Function
Selection
Number of Auto Restart Attempts
133
Start-Up Programming
& Operation
No.
A1-02
b1-04
C6-01
E1-03
E1-07
E1-08
L2-01
L3-04
No.
A1-02
b1-04
b1-17
C6-01
C6-02
H2-03
Parameter Name
Control Method Selection
Reverse Operation Selection
Run Command at Power Up
Duty Rating
Carrier Frequency Selection
Terminals P2 Function Selection
L2-01
L8-03
L8-38
Default Setting
0: V/f Control
1: Reverse Prohibited
1: Run command issued, motor operation start
1: Normal Duty
3: 8.0 kHz
39: Watt Hour Pulse Output
2: CPU Power Active - Drive will restart if power returns prior
to control power supply shut down.
4: Operation at lower speed
2: Enabled across entire frequency range.
No.
b1-01
b1-02
b1-03
b1-04
C1-01
C1-02
C6-02
d2-01
Parameter Name
Frequency Reference Selection
Run Command Selection
Stopping Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Carrier Frequency Selection
Frequency Reference Upper Limit
No.
d2-02
E1-03
E1-04
E2-01
H3-11
H3-12
L2-01
o4-12
Parameter Name
Frequency Reference Lower Limit
V/f Pattern Selection
Max Output Frequency
Motor Rated Current
Terminal A2 Gain Setting
Terminal A2 Input Bias
Momentary Power Loss Operation Selection
kWh Monitor Initial Value Selection
No.
A1-02
b1-04
C1-01
C1-02
C6-01
E1-03
L2-01
L3-04
Parameter Name
Control Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Duty Rating
V/f Pattern Selection
Momentary Power Loss Operation Selection
Stall Prevention Selection during Deceleration
Default Setting
0: V/f Control
1: Reverse Prohibited
5.0 s
5.0 s
0: Heavy Duty
0F Hex
1: Enabled
1: Enabled
No.
b1-01
b1-02
b1-04
C1-01
C1-02
134
Parameter Name
Frequency Reference Selection
Run Command Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
No.
E1-03
E1-07
E1-08
E2-01
Parameter Name
V/f Pattern Selection
Mid Output Frequency
Mid Output Frequency Voltage
Motor Rated Current
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
4.7
Auto-Tuning
u Types of Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors and permanent magnet motors. The type of Auto-Tuning
used differs further based on the control mode and other operating conditions. Refer to the tables below to select the type of
Auto-Tuning that bests suits the application. Refer to Start-Up Flowcharts on page 126 for directions on executing AutoTuning.
Note: The drive will only show Auto-Tuning parameters that are valid for the control mode that has been set in A1-02. If the control mode is for an
induction motor, the Auto-Tuning parameters for PM motors will not be available. If the control mode is for a PM motor, the Auto-Tuning
parameters for induction motors will not be available. Inertia Tuning and ASR Gain Tuning parameters and setting options will be visible only
when the drive is set for operation with CLV or CLV/PM.
Rotational Auto-Tuning
Stationary
Auto-Tuning 1
Stationary
Auto-Tuning 2
Control Mode
V/f w/PG
OLV
Setting
T1-01 = 0
YES
YES
T1-01 = 1
YES
YES
T1-01 = 4
YES
YES
YES
YES
YES
YES
YES
YES
Stationary Auto-Tuning
for Line-to-Line
Resistance
T1-01 = 2
Rotational Auto-Tuning
for V/f Control
T1-01 = 3
V/f
CLV
Table 4.16 lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer. Also refer to pages 128 and 129 for details on Auto-Tuning processes and selections.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
135
Start-Up Programming
& Operation
Type
4.7 Auto-Tuning
Table 4.16 Auto-Tuning Input Data
Input Value
Motor rated power
Motor rated voltage
Motor rated current
Motor rated frequency
Number of motor poles
Motor rated Speed
PG Number of pulses per
revolution
Motor no-load current
Motor rated Slip
Motor iron loss
Input
Parameter
Unit
0
Standard
T1-02
T1-03
T1-04
T1-05
T1-06
T1-07
kW
Vac
A
Hz
r/min
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
T1-08
YES <1>
YES <1>
YES <1>
T1-09
T1-10
T1-11
A
Hz
W
YES
YES
YES
YES
4
Stationary 2
Automatically sets the V/f pattern and motor parameters E1-oo and E5-oo when a PM motor is used. Additionally, the
feature also sets some F1-oo parameters for speed feedback detection in Closed Loop Vector.
Table 4.17 Types of Auto-Tuning for Permanent Magnet Motors
Type
Setting
PM Motor Parameter
Settings
T2-01 = 0
PM Stationary AutoTuning
T2-01 = 1
T2-01 = 2
T2-01 = 3
T2-01 = 11
OLV/PM
Control Mode
AOLV/PM
CLV/PM
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
Table 4.18 lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer. Also refer to page 130 for details on the Auto-Tuning process and selection.
136
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
Table 4.18 Auto-Tuning Input Data
Tuning Type (T2-01)
Input
Parameter
Control Mode
A1-02
Unit
0
Motor Parameter Settings
1
Stationary
2
Stationary
Stator
Resistance
3
Z-Pulse
Offset
11
Back EMF
Constant
<5> <6>
5, 6, 7
6, 7
6, 7
5, 6, 7
<1>
<1>
<2>
<2>
<2>
<2>
<2>
T2-02
<1>
Motor Type
Motor Rated Power
Motor Rated Voltage
Motor Rated Current
Motor Rated
Frequency
Number of Motor
Poles
Motor Rated Speed
T2-03
T2-04
T2-05
T2-06
kW
Vac
A
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
T2-07
Hz
YES
YES
T2-08
YES
YES
YES
YES
T2-09
r/min
YES
YES
Stator Single-phase
Resistance
T2-10
YES
YES
YES
d-Axis Inductance
q-Axis Inductance
Induced Voltage
Constant Unit
Selection <3>
T2-11
T2-12
mH
mH
YES
YES
YES
YES
YES
YES
T2-13
mVs/
rad
(elec.)
YES
YES
YES
T2-14
mVmin
(mech.)
YES
YES
YES
Tuning Pull-in
Current
T2-15
YES
YES
PG Number of Pulses
Per Revolution
T2-16
YES <4>
YES <4>
YES <4>
Z Pulse Offset
T2-17
deg
(mech.)
YES <4>
YES <4>
YES <4>
<7>
<1>
<2>
<3>
<4>
<5>
<6>
<7>
Start-Up Programming
& Operation
Input Value
Input the motor code when using a Yaskawa motor. Select FFFF when using a motor from another manufacturer.
T2-02 is not available.
It is only necessary to input either T2-13 or T2-14. Select one and leave the other empty.
Input data is needed for CLV/PM only.
Setting 11 is valid in drive software versions S1015 and later.
Setting 11 is not available in models CIMR-Ao4A0930 and 4A1200.
Dependent upon T2-13 setting.
Inertia Tuning
ASR Gain Auto-Tuning
Setting
IM Motor PM Motor
Allows the motor to rotate at a certain speed and applies a test signal.
response to the test signal is analyzed and the necessary
T1-01 = 8 T2-01 = 8 The
adjustments are made to parameters controlling the Feed Forward and
KEB Ride-Thru functions (KEB 2, L2-29 = 1).
the same operation as Inertia Tuning, while also adjusting
T1-01 = 9 T2-01 = 9 Performs
the ASR gain according to the test signal response.
Control Mode
CLV
CLV/PM
YES
YES
YES
YES
Table 4.20 explains the data that must be entered to perform the Inertia Tuning and ASR Gain Auto-Tuning. Refer to AutoTuning for Permanent Magnet Motors on page 136 for details.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
137
4.7 Auto-Tuning
Table 4.20 Auto-Tuning Input Data
Input Value
Input Parameter
Unit
T3-01
T3-02
Hz
rad
Motor inertia
T3-03
T3-04
kgm2
Hz
YES
YES
Auto-Tuning Type
Rotational Auto-Tuning
Stationary Auto-Tuning 1
IM Motor Stationary Auto-Tuning 2
Stationary Auto-Tuning for Line-to-Line Resistance
Rotational Auto-Tuning for V/f Control
PM Motor Parameter Settings
PM Motor PM Stationary Auto-Tuning
<99>
PM Stationary Auto-Tuning for Stator Resistance
Z Pulse Offset Tuning
IM and PM Inertia Tuning
Motors
ASR Gain Auto-Tuning
Digital Input
Digital Output
Functions the same as during normal operation
Maintains the status at the start of Auto-Tuning
<99> PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
138
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
Stationary Auto-Tuning 1 and 2
Perform when using a vector control mode and Rotational Auto-Tuning cannot be performed.
Check the area around the motor to ensure that nothing will accidentally cause the motor to rotate during the Auto-Tuning
process.
Use Stationary Auto-Tuning 1 when the motor test report is not available. Use Stationary Auto-Tuning 2 when the motor
test report is available.
Stationary Auto-Tuning for Line-to-Line Resistance and PM Motor Stator Resistance
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Perform when entering motor data manually while using motor cables longer than 50 m.
If the motor cables have been replaced with cables more than 50 m long after Auto-Tuning has already been performed, use
Stationary Auto-Tuning for line-to-line resistance.
Perform both tuning methods with the machine connected to the motor, but without the load applied.
The motor will rotate during the Auto-Tuning process. Make sure the areas around the motor and connected machinery are
clear.
The drive will let the system rotate at a certain speed while superimposing a sine wave test signal. Make sure this tuning
process does not cause any problem or malfunction in the machine before using it.
Ensure the motor-mounted brake is fully released if installed.
Connected machinery should be allowed to rotate the motor.
ALARM
- MODE -
Er-03
STOP key
A During Auto-Tuning
ESC
LO
RE
ALARM
DRV
FWD RESET
B Auto-Tuning
Aborted
LO
ESC
RUN
Start-Up Programming
& Operation
A
DIGITAL OPERATOR JVOP-180
ENTER
STOP
RESET
RUN
RE
ENTER
STOP
The following example demonstrates Rotational Auto-Tuning when using OLV (A1-02 = 2) and CLV (A1-02 = 3).
Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz LSEQ
U1-03= 0.00A LREF
JOG FWD FWD/REV
- MODE - PRG
Auto-Tuning
2.
Press
or
AUTO
HELP FWD DATA
3.
Press
T1-01= 0 *0*
StandardTuning
ESC FWD DATA
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
139
4.7 Auto-Tuning
Step
Display/Result
- A.TUNE - PRG Rdy
Tuning Mode Sel
4.
Press
5.
T1-01= 0 *0*
StandardTuning
0
FWD
Entry Accepted
6.
T1-01= 0 *0*
StandardTuning
ESC FWD DATA
<1> T1-00 will appear on the display when one of the multi-function inputs has been set to switch between motor 1 and motor 2 (H1-oo = 16).
Display/Result
- A.TUNE - PRG Rdy
Mtr Rated Power
1.
Press
T1-02= 0.75kW
(0.00 ~ 650.00)
0.75kW
ESC FWD DATA
- A.TUNE - PRG Rdy
Mtr Rated Power
2.
Press
Press
kW.
4.
Press
left
F2
F1
3.
T1-02= 000.75kW
(0.00 ~ 650.00)
0.75kW
FWD
right
, and
T1-02= 000.40kW
(0.00 ~ 650.00)
0.75kW
FWD
Entry Accepted
5.
6.
- A.TUNE - PRG
Rated Voltage
T1-03= 200.0VAC
(0.0 ~ 255.0)
200.0VAC
ESC FWD DATA
- A.TUNE - PRG
Mtr Rated Slip
T1-10= X.XX Hz
(0.00 ~ 20.00)
X.XX Hz
ESC FWD DATA
Note: 1. For details on each setting, Refer to Parameter Settings during Induction Motor Auto-Tuning: T1 on page 141.
2. To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.
140
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
n Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or
serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the
motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in improper
operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.
Note: These instructions continue from Step 6 in Enter Data from the Motor Nameplate.
Step
Display/Result
- A.TUNE - DRV Rdy
Auto-Tuning
1.
2.
to confirm.
Press
to activate Auto-Tuning.
flashes. The drive begins by injecting current
into the motor for about 1 min, and then starts to rotate the motor.
Note: The first digit on the display indicates which motor is undergoing Auto-Tuning
(motor 1 or motor 2). The second digit indicates the type of Auto-Tuning being
performed.
3.
DRV
End
Tune Successful
FWD RESET
Name
Motor 1/Motor 2 Selection
Setting Range
1, 2
Default
1
Start-Up Programming
& Operation
The T1-oo parameters set the Auto-Tuning input data for induction motor tuning.
Setting 1: Motor 1
Auto-Tuning automatically sets parameters E3-oo and E4-oo for motor 2. Make sure that motor 2 is connected to the drive
for Auto-Tuning.
Name
T1-01
Setting Range
2, 3 (V/f, V/f w/PG)
0 to 2, 4 (OLV, CLV)
8, 9 (CLV)
Default
2 (V/f, V/f w/PG)
0 (OLV, CLV)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
141
4.7 Auto-Tuning
Setting 3: Rotational Auto-Tuning for V/f Control
Setting 4: Stationary Auto-Tuning 2
Setting 8: Inertia Tuning
Setting 9: ASR Gain Auto-Tuning
Name
Setting Range
T1-02
0.00 to 650.00 kW
Default
Determined by o2-04
and C6-01
Name
T1-03
Setting Range
0.0 to 255.5
V <1>
Default
200.0 V <1>
<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives. Multiply value by 2.875 for 600 V class drives.
Name
T1-04
Setting Range
10 to 200% of drive rated
current
Default
E2-01 (E4-01)
Name
Motor Base Frequency
Setting Range
0.0 to 400.0 Hz
Default
60.0 Hz
Setting Range
2 to 48
Default
4
Name
Number of Motor Poles
142
Name
Motor Base Speed
Setting Range
0 to 24000 r/min
Default
1750 r/min
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
Name
PG Number of Pulses Per Revolution
Setting Range
1 to 60000 ppr
Default
1024 ppr
Name
T1-09
Setting Range
0 A to [T1-04]
(Max: 0 to 2999.9)
Default
Note: The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place
(0.1 A) if the maximum applicable motor capacity is higher than 11 kW. Refer to Power Ratings on page 455.
Name
Motor Rated Slip
Setting Range
0.00 to 20.00 Hz
Default
No.
Name
Setting Range
T1-11
0 to 65535 W
Default
14 W
Differs depending
on motor code and
motor parameter
settings.
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
The T2-oo parameters are used to set the Auto-Tuning input data for PM motor tuning.
Selects the type of Auto-Tuning to be performed. Refer to Auto-Tuning for Permanent Magnet Motors on page 136 for
details on different types of Auto-Tuning.
No.
Name
T2-01
Setting Range
0 to 2
(OLV/PM, AOLV/PM)
0 to 3, 8, 9, 11
(CLV/PM)
Default
0
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Start-Up Programming
& Operation
Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron
loss that the drive automatically calculated the when motor capacity was entered to T1-02. Enter the motor iron loss value
listed to T1-11 if the motor test report is available.
143
4.7 Auto-Tuning
Setting 2: PM Stationary Auto-Tuning for Stator Resistance
Setting 3: Z-Pulse Offset Tuning
Setting 8: Inertia Tuning
Setting 9: ASR Gain Auto-Tuning
Setting 11: Back EMF Constant Tuning
If the drive is operating a Yaskawa PM motor from the SMRA, SSR1, or SST4 series, enter the motor code in T2-02 to
automatically set parameters T2-03 through T2-14. If the drive is operating a specialized motor or a motor designed by a
manufacturer other than Yaskawa, set T2-02 to FFFF and enter the data from the motor nameplate or the motor test report as
prompted.
Only the designated PM motor codes may be entered. The PM motor codes accepted by the drive will differ depending on the
selected control mode. Refer to E5: PM Motor Settings on page 234 for motor codes.
No.
Name
Setting Range
T2-02
0000 to FFFF
Default
Depending on A1-02
and o2-04
Name
PM Motor Type
Setting Range
0, 1
Default
1
Name
PM Motor Rated Power
Setting Range
0.00 to 650.00 kW
Default
Depending on o2-04
Name
T2-05
Setting Range
0.0 to 255.0
V <1>
Default
200.0 V <1>
<1> Values shown are specific to 200 V class drives; double the value for 400 V class drives.
144
No.
Name
T2-06
Setting Range
10% to 200% of the drive
rated current.
Default
Depending on o2-04
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
No.
T2-07
Name
PM Motor Base Frequency
Setting Range
0.0 to 400.0 Hz
Default
87.5 Hz
Name
Number of PM Motor Poles
Setting Range
2 to 48
Default
6
No.
T2-09
Name
PM Motor Base Speed
Setting Range
0 to 24000 r/min
Default
1750 r/min
Setting Range
0.000 to 65.000
Default
Depending on T2-02
Name
PM Motor d-Axis Inductance
Setting Range
0.00 to 600.00 mH
Default
Depending on T2-02
Name
PM Motor q-Axis Inductance
Setting Range
0.00 to 600.00 mH
Default
Depending on T2-02
Selects the units used for setting the induced voltage coefficient.
No.
T2-13
Name
Induced Voltage Constant Unit Selection
Setting Range
0, 1
Default
1
Setting 0: mV (r/min)
Setting 1: mV (rad/sec)
Note: If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor Induction
Voltage Constant 1) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-25 to 0.0.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Start-Up Programming
& Operation
No.
T2-10
145
4.7 Auto-Tuning
Name
PM Motor Induced Voltage Constant
Setting Range
0.1 to 2000.0
Default
Depending on T2-02
Sets the amount of pull-in current used to tune the d-Axis and q-Axis inductance. Set as a percentage of the motor rated current.
No.
T2-15
Name
Pull-In Current Level for PM Motor Tuning
Setting Range
0 to 120%
Default
30%
Enter the number of pulses from the PG encoder per motor rotation. Set the actual number of pulses for one full motor rotation.
No.
T2-16
Name
PG Number of Pulses Per Revolution for PM Motor Tuning
Setting Range
0 to 15000 ppr
Default
1024 ppr
Sets the amount of compensation or offset in 0.1 degree units to fine-tune the home position. Perform Z Pulse tuning when
the amount of offset needed for the Z Pulse is unknown or if the PG encoder is replaced.
No.
T2-17
Name
Encoder Z Pulse Offset
Setting Range
-180.0 to 180.0 deg
Default
0.0 deg
Description
8
Inertia Tuning
C5-01
C5-17 (C5-37)
C5-18 (C5-38)
YES
YES
9
Speed Control Loop (ASR)
Tuning
YES
YES
YES
YES
YES
YES
YES
YES
YES
L3-24
L3-25
n5-03
146
Name
Inertia Tuning Frequency Reference
Setting Range
0.1 to 20.0 Hz
Default
3.0 Hz
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
Name
Inertia Tuning Reference Amplitude
Setting Range
0.1 to 10.0 rad
Default
0.5 rad
Name
Motor Inertia
kgm2.
Setting Range
0.0001 to 600.00
kgm2
Default
Determined by E2-11
Capacities 5.5 to 45 kW are set in units of 0.001 kgm2. Capacities 55 kW and above
Setting Range
0.1 to 50.0 Hz
Default
10.0 Hz
Start-Up Programming
& Operation
No.
T3-04
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
147
4.8
n During Operation
Check the following items during operation:
The motor should rotate smoothly (i.e., no abnormal noise or oscillation).
The motor should accelerate and decelerate smoothly.
Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
2.
Press
F2
ESC
LO
RE
RESET
ENTER
RUN
STOP
Off
On
ALARM
3.
Press
at 6 Hz.
to give the drive a Run command. RUN will light and the motor will rotate
F2
ESC
LO
RE
RESET
ENTER
RUN
STOP
RUN
RUN
Off
On
Motor
4.
Ensure the motor is rotating in the correct direction and that no faults or alarms occur.
Forward
5.
148
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Display/Result
DRV Rdy
- MODE FREF (OPR)
U1-01= 60.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00A
LREF
JOG FWD FWD/REV
F1
6.
STOP
LO
RE
RESET
ENTER
RUN
RUN
STOP
RUN
On
Start-Up Programming
& Operation
Off
F2
ESC
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
149
4.9
150
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
o2-03
A1-03
Parameter
Name
Description
Setting
Range
Default
Setting
User Defaults
Lets the user create a set of default settings for a User Initialization.
0: Saved/Not Set
1: Set Defaults - Saves current parameter settings as the default values for a User
Initialization.
2: Clear All - Clears the currently saved user settings. After saving the user parameter set
value, the items of 1110 (User Initialization) are displayed in A1-03 (User Parameter Default
Value).
0 to 2
Initialize
Parameters
0 to 5550
Setting the Access Level for Operation only (A1-01 = 0) allows the user to access parameters A1-oo and Uo-oo only.
Other parameters are not displayed.
Setting the Access Level for User Parameters (A1-01 = 1) allows the user to access only the parameters that have been
previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific application.
No.
A1-01
A2-01
to
A2-32
A2-33
Parameter
Name
Description
Setting
Range
Default
0 to 2
4
b1-01 to
oo-oo
0, 1
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
and
Start-Up Programming
& Operation
simultaneously.
151
u Copy Function
Parameter settings can be copied to another drive to simplify parameter restoration or multiple drive setup. The drive supports
the following copy options:
LCD Operator (standard in all models)
The LCD operator used to operate the drive supports copying, importing, and verifying parameter settings. Refer to o3:
Copy Function on page 326 for details.
LED Operator
The optional LED operator also supports copying, importing, and verifying parameter settings. Refer to the manual supplied
with the LED operator for instructions.
USB Copy Unit and CopyUnitManager
The copy unit is an external option connected to the drive to copy parameter settings from one drive and save those settings
to another drive. Refer to the manual supplied with the USB Copy Unit for instructions.
The CopyUnitManager is a PC software tool. It allows the user to load parameter settings from the Copy Unit onto a PC,
or from the PC onto a Copy Unit. This is useful when managing parameters for various drives or applications. Refer to the
manual supplied with the CopyUnitManager for instructions.
DriveWizard Plus
DriveWizard Plus is a PC software tool for parameter management, monitoring, and diagnosis. DriveWizard Plus can load,
store, and copy drive parameter settings. For details, refer to Help in the DriveWizard Plus software.
152
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Checklist
Page
131
224
Check the items that correspond to the control mode being used.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing
the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary
closure on terminal S1 may cause the drive to start.
Checklist
No.
Page
Select the best V/f pattern according to the application and motor characteristics.
Perform Rotational Auto-Tuning for V/f Control if using Energy Saving functions.
135
Set up the PG feedback parameters correctly and make sure the encoder pulse counting direction is correct.
237
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02.
201
141
10
141
11
Enter the following data according to the information listed on the motor nameplate:
Motor rated power to T1-02 (kW)
Motor rated voltage to T1-03 (V)
Motor rated current to T1-04 (A)
Motor base frequency to T1-05 (Hz)
Number of motor poles to T1-06
Motor base speed to T1-07 (r/min)
141
13
Set ASR proportional gain to C5-01 and ASR integral time to C5-02. Perform ASR Tuning if possible.
201
143
143
16
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02.
201
143
18
Set ASR proportional gain to C5-01 and ASR integral time to C5-02. Perform ASR Tuning if possible.
201
19
20
Set the offset between the rotor magnetic axis and the Z-pulse of the connected encoder to E5-11.
21
The
22
To give Run command and frequency reference from the digital operator, press LO/RE key to set to LOCAL.
125
23
If the motor rotates in the opposite direction during test run, switch two of U/T1, V/T2, W/T3, or change b1-14.
131
24
In accordance with load condition, set Heavy Duty or Normal Duty mode using parameter C6-01. Normal Duty is the
default setting.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
143
153
Start-Up Programming
& Operation
Open Loop Vector Control (A1-02 = 2) or Closed Loop Vector Control (A1-02 = 3)
154
Checklist
Page
25
Set motor rated current (E2-01, E4-01, E5-03) and motor protection (L1-01) values for motor thermal protection.
26
Set the drive for REMOTE when control circuit terminals provide the Run command and frequency reference.
125
27
If the control circuit terminals should supply the frequency reference, select the correct voltage input signal level
(0 to 10 V) or the correct current input signal level (4 to 20 mA or 0 to 20 mA).
162
28
162
29
162
30
When current input is used, switch the built-in DIP switch S1 from the V-side to I-side. Set the level for current signal
used to H3-09 (set 2 for 4 to 20 mA, or 3 for 0 to 20 mA).
162
31
32
If an analog input supplies the frequency reference, make sure it produces the desired frequency reference. Make the
following adjustments if the drive does not operate as expected:
Gain adjustment: Set the maximum voltage/current signal and adjust the analog input gain (H3-03 for A1, H3-11 for A2,
H3-07 for A3) until the frequency reference value reaches the desired value.
Bias adjustment: Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for A1, H3-12 for A2,
H3-08 for A3) until the frequency reference value reaches the desired minimum value.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5
Parameter Details
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
A: INITIALIZATION..............................................................................................156
B: APPLICATION.................................................................................................162
C: TUNING............................................................................................................192
D: REFERENCE SETTINGS................................................................................209
E: MOTOR PARAMETERS..................................................................................224
F: OPTION SETTINGS.........................................................................................237
H: TERMINAL FUNCTIONS.................................................................................248
L: PROTECTION FUNCTIONS............................................................................280
N: SPECIAL ADJUSTMENTS..............................................................................313
O: OPERATOR RELATED SETTINGS................................................................323
U: MONITOR PARAMETERS..............................................................................330
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
155
5.1 A: Initialization
5.1
A: Initialization
The initialization group contains parameters associated with initial drive setup, including parameters involving the display
language, access levels, initialization, and password.
u A1: Initialization
n A1-00: Language Selection
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
No.
A1-00
Parameter Name
Language Selection
Setting Range
0 to 7
Default
0
Setting Range
0 to 2
Default
2
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
Parameter Name
Access Level Selection
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup Mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2
parameters cannot be modified.
If a digital input terminal programmed for Program lockout (H1-oo = 1B) is enabled, parameter values cannot be
modified, even if A1-01 is set to 1 or 2.
If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the
digital operator until an Enter command is issued to the drive from the serial communication.
156
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.1 A: Initialization
No.
A1-02
Parameter Name
Control Method Selection
Setting Range
0, 1, 2, 3, 5, 6, 7
Default
2
Use this mode for simple speed control and for multiple motor applications with low demands to dynamic response or speed
accuracy. This control mode is also used when the motor parameters are unknown and Auto-Tuning cannot be performed. The
speed control range is 1:40.
Setting 1: V/f Control with PG Speed Feedback
Use this mode for general-purpose applications that require high speed accuracy but do not require high dynamic response.
This control mode is also used when the motor parameters are unknown and Auto-Tuning cannot be performed. The speed
control range is 1:40.
Setting 2: Open Loop Vector Control
Use this mode for general, variable-speed applications with a speed control range of 1:200 that require precise speed control,
quick torque response, and high torque at low speed without using a speed feedback signal from the motor.
Setting 3: Closed Loop Vector Control
Use this mode for general, variable-speed applications that require precise speed control down to zero speed, quick torque
response or precise torque control, and a speed feedback signal from the motor. The speed control range is up to 1:1500.
Control Modes for Permanent Magnet Motors (SPM or IPM)
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooo.
Use this mode when running a PM motor in variable torque applications that benefit from energy efficiency. The drive can
control an SPM or IPM motor with a speed range of 1:20 in this control mode.
Use this mode to operate an IPM motor for constant torque applications. Set High Frequency Injection parameter n8-57 to 1
to achieve a speed control range as high as 1:100. Refer to n8-57: High Frequency Injection (AOLV/PM) on page 321 for
details.
Setting 7: Closed Loop Vector Control for PM
Use this mode for high-precision control of a PM motor in constant torque or variable torque applications. The speed control
range reaches 1:1500. A speed feedback signal is required.
Parameter Name
Initialize Parameters
Setting Range
0, 1110, 2220, 3330, 5550
Default
0
Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to
1: Set defaults.
Note: User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to clear
the user-defined default values.
Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.
Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence on page 255 for more information on
digital input functions.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
157
5.1 A: Initialization
Setting 3330: 3-Wire Initialization
Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse
respectively. Refer to Setting 0: 3-Wire Sequence on page 249 for more information on digital input functions.
Setting 5550: oPE04 Reset
An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is installed
in a drive that has edited parameters. Set A1-03 to 5550 to use the parameter settings saved to the terminal block memory.
Notes on Parameter Initialization
The parameters shown in Table 5.1 will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. Although
the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application preset is selected.
Table 5.1 Parameters not Changed by Drive Initialization
No.
A1-00
A1-02
C6-01
E1-03
Parameter Name
Language Selection
Control Method Selection
Duty Selection
V/f Pattern Selection
Motor Code Selection (for PM motors)
Note: PM motor control modes are not available on 600 V class drives,
CIMR-Ao5oooooo.
Communication Parameter Reset
Installation Selection
Drive/kVA Selection
E5-01
F6-08
L8-35
o2-04
Parameter Name
Password
Password Setting
Setting Range
Default
0000 to 9999
0000
The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to
unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following
parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01, A1-02,
A1-03, A1-06, and A2-01 through A2-33.
The instructions below demonstrate how to set password 1234. An explanation follows on how to enter that password to
unlock the parameters.
Table 5.2 Setting the Password for Parameter Lock
Step
1.
Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
- MODE PRG
Programming
2.
Press
or
-PRMSET- PRG
Initialization
3.
Press
A1-00= 0
Select Language
158
FWD
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.1 A: Initialization
Step
Display/Result
-PRMSET- PRG
Select Language
4.
F2
F1
left
right
A1-00=
, or
0 *0*
English
FWD
PRG
-PRMSETEnter Password
5.
6.
Press
A1- 04 =
0
(0~9999)
0
FWD
Note:
-PRMSETPRG
Select Password
A1- 05 =
04
(0~9999)
0
FWD
-PRMSETPRG
Select Password
7.
Press
A1- 05 = 0000
(0~9999)
0
FWD
-PRMSETPRG
Select Password
8.
9.
F2
F1
Use
left
Press
right
and
A1-05= 1234
(0~9999)
0
FWD
Entry Accepted
-PRMSETPRG
Select Password
A1- 05 =
04
(0~9999)
0
FWD
Step
-PRMSETPRG
Control Method
1.
2.
Press
A1-02= 2 *2*
Open LoopVector
to display A1-02.
Press
FWD
- MODE PRG
Programming
3.
Press
Table 5.4 Enter the Password to Unlock Parameters (continuing from step 3 above)
Step
Display/Result
-PRMSET- PRG
Initialization
1.
Press
A1-00= 0
Select Language
FWD
-PRMSET- PRG
Select Language
2.
F2
F1
Press
left
right
A1-00=
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
0 *0*
English
FWD
159
5.1 A: Initialization
Step
Display/Result
-PRMSETPRG
Enter Password
3.
Press
A1- 04 =
0
(0~9999)
0
FWD
-PRMSETPRG
Enter Password
4.
A1- 04 = 1234
(0~9999)
0
FWD
5.
Press
Entry Accepted
-PRMSETPRG
Enter Password
6.
A1- 04 =
0
(0~9999)
0
FWD
-PRMSETPRG
Control Method
7.
Press
A1-02= 2 *2*
Open LoopVector
FWD
-PRMSETPRG
Control Method
8.
Press
to display the value set to A1-02. If the first 0 blinks, parameter settings are unlocked.
A1-02= 2 *2*
Open LoopVector
FWD
-PRMSETPRG
Control Method
9.
10.
Use
and
to change the value if desired (though changing the control mode at this point is
not typically done).
Press
A1-02= 0 *2*
V/F Control
2
FWD
Entry Accepted
-PRMSETPRG
Control Method
11.
A1-02= 0 *0*
V/F Control
FWD
Note: 1. Parameter settings can be edited after entering the correct password.
2. Performing a 2-Wire or 3-Wire initialization resets the password to 0000.
160
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.1 A: Initialization
No.
A1-07
Parameter Name
DriveWorksEZ Function Selection
Setting Range
0 to 2
Default
0
If a digital input is programmed for DWEZ enable/disable (H1-oo = 9F), DWEZ will be enabled when the input is opened.
Parameter Name
Setting Range
A2-01 to A2-32
User Parameters 1 to 32
b1-01 to o4-13
Default
Determined by
A1-06 <1>
<1> A1-06 determines how parameters edited by the user are saved to the list of User Parameters, A2-01 through A2-32. Refer to Application
Selection on page 132 for details.
Parameter Name
Setting Range
A2-33
0, 1
Default
Determined by
A1-06
Set A2-33 to 0 to manually select the parameters listed in the User Parameter group.
Setting 1: Save list of recently edited parameters
Set A2-33 to 1 to automatically save recently edited parameters to A2-17 through A2-32. A total of 16 parameters are saved
with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. Access the User Parameters
using the Setup Mode of the digital operator.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
161
Parameter Details
To save specific parameters to A2-01 through A2-32, set parameter A1-01 to 2 to allow access to all parameters, then enter
the parameter number to one of the A2-oo parameters to assign it to the list of User Parameters. Finally, set A1-01 to 1 to
restrict access so users can only set and refer to the parameters saved as User Parameters.
5.2 b: Application
5.2
b: Application
No.
b1-01
Parameter Name
Frequency Reference Selection 1
Setting Range
0 to 4
Default
1
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in Table 5.5 for the input
used.
Table 5.5 Analog Input Settings for Frequency Reference Using Voltage Signals
Parameter Settings
Terminal
A1
A2
A3
Signal Level
0 to 10 Vdc
-10 to +10 Vdc
0 to 10 Vdc
Signal Level
Selection
H3-01 = 0
H3-01 = 1
H3-09 = 0
H3-09 = 1
H3-10 = 0
(Frequency Reference Bias)
0 to 10 Vdc
-10 to +10 Vdc
H3-05 = 0
H3-05 = 1
H3-06 = 0
(Frequency Reference Bias)
Gain
Bias
H3-02 = 0
(Frequency Reference Bias)
H3-03
H3-04
H3-11
H3-12
H3-07
H3-08
0 to 10 V
Drive
Drive
+V 10.5 V, 20 mA power supply
2k
Notes
Function Selection
4k
A1 Analog Input 1
A2 Analog Input 2
OR
-10 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
A3 Analog Input 3
-V
-V
Use the wiring example shown in Figure 5.1 for any other analog input terminals. When using input A2 make sure DIP switch
S1 is set for voltage input.
Current Input
Input terminal A2 can accept a current input signal. Refer to Table 5.6 to set terminal A2 for current input.
162
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Table 5.6 Analog Input Settings for Frequency Reference Using a Current Signal
Terminal
A2
Signal
Level
4 to 20 mA
Signal Level
Selection
H3-09 = 2
0 to 20 mA
H3-09 = 3
Parameter Settings
Function
Gain
Selection
H3-10 = 0
(Frequency Bias)
H3-11
DIP switch S1
V
Notes
Bias
H3-12
Drive
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
-V
The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs. Refer
to Multi-Step Speed Selection on page 209 for details on using this function.
Setting 2: MEMOBUS/Modbus Communications
This setting requires entering the frequency reference via the RS-485/422 serial communications port (control terminals R+,
R-, S+, S-). Refer to MEMOBUS/Modbus Configuration on page 594 for instructions.
Setting 3: Option card
Note: If the frequency reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Operator Programming
Error will be displayed on the digital operator and the drive will not run.
This setting requires a pulse train signal to terminal RP to provide the frequency reference. Follow the directions below to
verify that the pulse signal is working properly.
Verifying the Pulse Train is Working Properly
Parameter Name
Run Command Selection 1
Setting Range
0 to 3
Default
1
Setting 0: Operator
This setting requires entering the Run command via the digital operator RUN key and also illuminates the LO/RE indicator
on the digital operator.
Setting 1: Control Circuit Terminal
This setting requires entering the Run command via the digital input terminals using one of following sequences:
2-Wire sequence 1:
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
This setting requires entering the frequency reference via an option board plugged into connector CN5-A on the drive control
board. Consult the option board manual for instructions on integrating the drive with the communication system.
163
5.2 b: Application
Two inputs (FWD/Stop-REV/Stop). Set A1-03 to 2220 to initialize the drive and preset terminals S1 and S2 to these
functions. This is the default setting of the drive. Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2Wire Sequence on page 255.
2-Wire sequence 2:
Two inputs (Start/Stop-FWD/REV). Refer to Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2 on
page 256.
3-Wire sequence:
Three inputs (Start-Stop-FWD/REV). Set A1-03 to 3330 to initialize the drive and preset terminals S1, S2, and S5 to these
functions. Refer to Setting 0: 3-Wire Sequence on page 249.
Setting 2: MEMOBUS/Modbus Communications
This setting requires entering the Run command via serial communications by connecting the RS-485/422 serial
communication cable to control terminals R+, R-, S+, and S- on the removable terminal block. Refer to MEMOBUS/Modbus
Configuration on page 594 for instructions.
Setting 3: Option Card
This setting requires entering the Run command via the communication option board by plugging a communication option
board into the CN5-A port on the control PCB. Refer to the option board manual for instructions on integrating the drive into
the communication system.
Note: If b1-02 is set to 3, but an option board is not installed in CN5-A, an oPE05 operator programming error will be displayed on the digital operator
and the drive will not run.
Parameter Name
Stopping Method Selection
Setting Range
0 to 3
Default
0
When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the
active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection, Zero Speed Control,
or Short Circuit Braking, depending on the selected control mode. Refer to b2-01: DC Injection Braking Start Frequency
on page 169 for details.
Setting 1: Coast to Stop
When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to
stop. The stopping time is determined by the inertia and the friction in the driven system.
Run
command
Output
frequency
ON
OFF
Motor speed
When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time
(L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC current set in parameter b2-02
into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly faster compared
to Coast to Stop.
Note: This function is not available in the control modes for PM motors (A1-02 = 5, 6, 7).
164
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Run
command
ON
OFF
DC Injection Braking
with the current set in
b2-02
Output
frequency
Motor speed
Motor coasts
Minimum Baseblock
Time (L2-03)
DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is
removed. It can be calculated by:
DC Injection brake time
b2-04
10%
100%
(Maximum output
frequency)
Note: If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no longer
occurs.
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start
if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t
after t has expired to start the drive.
Run command
Output
frequency
ON
OFF
ON
OFF
ON
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
165
Parameter Details
5.2 b: Application
Run wait time t
Active deceleration time
Min output
frequency
Output frequency
when Stop command
was entered
100%
(Max output
frequency)
Parameter Name
Reverse Operation Selection
Setting Range
0, 1
Default
0
n b1-05: Action Selection below Minimum Output Frequency (CLV and CLV/PM)
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Sets the operation when the frequency reference is lower than the minimum output frequency set in parameter E1-09.
No.
b1-05
Parameter Name
Action Selection below Minimum Output Frequency
Setting Range
0 to 3
Default
0
The drive adjusts the motor speed following the speed reference, even if the frequency reference is below the setting of
parameter E1-09. When the Run command is removed and the motor speed is smaller than the setting of b2-01, Zero Speed
Control (not position lock) is performed for the time set in parameter b2-04 before the drive output shuts off.
Run
Command
OFF
ON
E1-09 Min.
Frequency
Frequency
reference
IM: Initial Excitation
PM: Zero Spd. Contr.
Motor
Speed
Zero Speed
Control
Zero Speed
Control
b2-01 Zero
Speed Level
b2-03
Zero Speed Time at Start
E1-09
b2-04
Zero Speed Time at Stop
The motor starts when the frequency reference exceeds the parameter E1-09 setting. When the motor is running and the
frequency reference falls below E1-09, the drive output shuts off and the motor coasts. When the motor speed falls below the
zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.
166
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Run
Command
OFF
ON
E1-09 Min.
Frequency
Frequency
reference
IM: Initial Excitation
PM: Zero Spd. Contr.
Motor
Speed
Motor
Coasts
b2-01 Zero
Speed Level
b2-03
Zero Speed Time at Start
Zero Speed
Control
b2-04
Zero Speed Time at Stop
When a Run command is active and the frequency reference is smaller than the parameter E1-09 setting, the drive runs the
motor at the speed set in E1-09. When the Run command is removed, the drive decelerates the motor. As soon as the motor
speed reaches the zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.
Run
Command
OFF
ON
E1-09 Min.
Frequency
Frequency
reference
IM: Initial Excitation
PM: Zero Spd. Contr.
Motor
Speed
Run at
E1-09
Run at
E1-09
Zero Speed
Control
b2-01 Zero
Speed Level
b2-04
Zero Speed Time at Stop
b2-03
Zero Speed Time at Start
The drive applies Zero Speed Control whenever the frequency reference setting is below the value of parameter E1-09. When
the Run command is removed, Zero Speed Control is activated for the time set in b2-04, even if it was already active before.
Run
Command
OFF
ON
Frequency
reference
Zero
IM: Initial Excitation Speed
Control
PM: Zero Spd. Contr.
Motor
Speed
Parameter Details
E1-09 Min.
Frequency
Zero Speed
Control
b2-01 Zero
Speed Level
b2-03
Zero Speed Time at Start
E1-09
b2-04
Zero Speed Time at Stop
Name
Digital Input Reading
Setting Range
0, 1
Default
1
The state of a digital input is read once. If the state has changed, the input command is immediately processed. With this setting
the drive responds more quickly to digital inputs, but a noisy signal could cause erroneous operation.
Setting 1: Read twice (2 ms scan)
The state of a digital input is read twice. The input command is processed only if the state does not change during the double
reading. This reading process is slower than the Read once process, but it is more resistant to noisy signals.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
167
5.2 b: Application
Parameter Name
LOCAL/REMOTE Run Selection
Setting Range
0, 1
Default
0
When the Run command source differs between the old source and the new source (e.g., the old source was the terminals and
the new source is serial communication), and the Run command is active at the new source as the switchover occurs, the drive
will not start or the drive will stop operation if it was previously running. The Run command must be cycled at the new source
to restart the drive.
Setting 1: Accept Run command at the new source
When the Run command is active at the new source, the drive starts or continues operation if it was previously running.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel
from rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
Parameter Name
Run Command Selection while in Programming Mode
Setting Range
0 to 2
Default
0
Setting 0: Disabled
A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
Parameter Name
Phase Order Selection
Setting Range
0, 1
Default
0
Setting Range
0 to 4
Default
0
Parameter Name
Frequency Reference Selection 2
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Parameter Name
Run Command Selection 2
Setting Range
0 to 3
Default
0
Parameter Name
Run Command at Power Up
Setting Range
0, 1
Default
0
If an external Run command is active when the drive is powered up, the drive will begin operating the motor once the internal
start up process is complete.
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin
rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to
powering up the drive. Failure to comply may cause serious injury.
Name
Setting Range
b2-01
0.0 to 10.0 Hz
Default
Determined by
A1-02
Parameter Details
The function triggered by parameter b2-01 depends on the control mode that has been selected.
V/f, V/f w/PG, and OLV (A1-02 = 0, 1, 2)
For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output
frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency
DC Injection
Braking
Time
b2-04
Figure 5.12 DC Injection Braking at Stop for V/f, V/f w/PG and OLV
Note: If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as the frequency
falls to the value set to E1-09.
For these control modes, parameter b2-01 sets the starting frequency for Short-Circuit Braking at stop. When the output
frequency falls below the setting of b2-01, Short-Circuit Braking is enabled for the time set in parameter b2-13. If DC Injection
Braking time is enabled at stop, then DC Injection Braking is performed for the time set in b2-04 after Short-Circuit Braking
is complete.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
169
5.2 b: Application
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency
Short Circuit
Braking
DC Injection
Braking
Time
b2-13
b2-04
For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at stop. When
the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter b2-04 provided
b1-05 is set to 0.
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency
Zero Speed
Control
Time
b2-04
Name
DC Injection Braking Current
Setting Range
0 to 100%
Default
50%
The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.
Increasing the current level will increase the amount of heat generated by the motor windings. Do not set this parameter higher
than the level necessary to hold the motor shaft.
Name
DC Injection Braking Time at Start
Setting Range
0.00 to 10.00 s
Default
0.00 s
Note: Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), use DC Injection or Speed Search to stop the motor
or detect motor speed before starting it. Otherwise, motor stalling and other faults can occur.
170
No.
Name
Setting Range
b2-04
0.00 to 10.00 s
Default
Determined by
A1-02
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Name
Magnetic Flux Compensation Value
Setting Range
0 to 1000%
Default
0%
When a Run command is issued, the DC current level injected into the motor changes linearly from the level set to b2-08 to
the level set to E2-03 within the time set to b2-03.
Output frequency
b2-08
E2-03
Magnetizing Current
Reference
b2-03
Time
The level of the DC current injected to the motor is limited to 80% of the drive rated current or to the motor rated current,
whichever value is smaller.
Note: 1. If b2-08 is set below 100%, it can take a relatively long time for flux to develop.
2. If b2-08 is set to 0%, the DC current level will be the DC Injection current set to b2-02.
3. As DC Injection can generate a fair amount of noise, b2-08 may need to be adjusted to keep noise levels acceptable.
Setting Range
0.00 to 25.50 s
Default
0.00 s
Note: Short Circuit Braking cannot prevent a PM motor from being rotated by an external force. Use DC Injection to prevent the load from rotating
the motor.
Name
Short Circuit Brake Time at Stop
Setting Range
0.00 to 25.50 s
Default
0.50 s
Name
Short Circuit Braking Current
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0.0 to 200.0%
Default
100.0%
171
Parameter Details
No.
b2-12
5.2 b: Application
ON
Decel time
set to b3-03
OFF
Selected
frequency
reference
Output
frequency
b3-05
When Speed Search is applied automatically with the Run command, the drive waits for the minimum baseblock time set to
L2-03 before starting Speed Search. If L2-03 is lower than the time set to parameter b3-05, then b3-05 is used as the wait time.
Decel time set
set to b3-03
Run command
OFF
ON
Selected
frequency
reference
Output
frequency
b3-02
Output current
Minimum Baseblock Time (L2-03)
Figure 5.17 Current Detection Speed Search at Start or Speed Search Command by Digital Input
Shorten the Speed Search deceleration time set to b3-03 if an oL1 fault occurs while performing Current Detection Speed
Search.
172
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Current Detection Speed Search is not available when using OLV Control for PM motors.
Increase the minimum baseblock time set to L2-03 if an overcurrent or overvoltage fault occurs when performing Speed
Search after power is restored following a momentary power loss.
This method is used by Speed Search after baseblock (e.g., a power loss where the drive CPU continued to run and the Run
command was kept active). Here, the drive estimates the motor speed by analyzing the back EMF voltage and outputs the
estimated frequency and increases the voltage using the time constant set in parameter L2-04. After that, the motor is accelerated
or decelerated to the frequency reference starting from the detected speed. If there is not enough residual voltage in the motor
windings to perform the calculations described above, the drive will automatically proceed to step 2.
AC power
supply
ON
OFF
Starts at the speed
that was detected
Output
frequency
Selected
frequency
reference
Output
current
Several miliseconds
Min. Baseblock Time
(L2-03)
b3 -05 <1>
Current Injection is performed when there is insufficient residual voltage in the motor after extended power losses, when Speed
Search is applied with the Run command (b3-01 = 1), or when an External search command is used.
This feature injects the amount of DC current set to b3-06 to the motor and detects the speed by measuring the current feedback.
The drive then outputs the detected frequency and increases the voltage using the time constant set to parameter L2-04 while
looking at the motor current.
The output frequency is reduced if the current is higher than the level in b3-02. When the current falls below b3-02, the motor
speed is assumed to be found and the drive starts to accelerate or decelerate to the frequency reference.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
173
Parameter Details
<1> After AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than
the minimum baseblock time set to L2-03, the drive will wait until the time set to b3-05 has passed after power is restored
before starting Speed Search.
5.2 b: Application
Decelerates at the Speed
Search decel time set to b3-03
Run command
OFF
Output
frequency
ON
Frequency reference
set to the drive
Starts at the speed
speed that was detected
b3-02
Output
current
1.0 s
<1> The wait time for Speed Search (b3-05) determines the lower limit.
Notes on Using Speed Estimation Speed Search
Perform Rotational Auto-Tuning for V/f Control (T1-01 = 3) prior to using Speed Estimation in V/f Control and perform
Stationary Auto-Tuning for Line-to-Line Resistance (T1-01 = 2) again if the there is a change in the cable length between
the drive and motor.
Use Current Detection to search for speeds beyond 200 Hz if the application is running multiple motors from the same drive
or if the motor is considerably smaller than the capacity of the drive.
Speed Estimation may have trouble finding the actual speed if the motor cable is very long. Use Current Detection in these
instances.
Use Current Detection instead of Speed Estimation when operating motors smaller than 1.5 kW because Speed Estimation
might not be able to detect the speed or rotation of these smaller motors, in which case Speed Estimation would stop the
motor.
Use Short Circuit Braking instead of Speed Search when using OLV/PM and AOLV/PM with a long motor cable.
Use Short Circuit Braking instead of Speed Search when attempting to find the speed of a motor coasting faster than 200
Hz in OLV/PM and AOLV/PM.
Setting
61
62
Description
External Search
Command 1
External Search
Command 2
b3-24 = 0
b3-24 = 1
Closed: Activate Current Detection Speed Search from the
maximum output frequency (E1-04).
Activate Speed Estimation
Closed: Activate Current Detection Speed Search from the Speed Search
frequency reference.
To activate Speed Search by a digital input, the input must be set together with the Run command or the Run command must
be entered after giving the Speed Search command.
Method 3. After automatic fault restart.
When the number of maximum fault restarts in parameter L5-01 is set higher than 0, the drive will automatically perform
Speed Search as specified by b3-24 following a fault.
Method 4. After momentary power loss.
This mode requires that the Power Loss Ride-Thru function is enabled during CPU operation (L2-01 = 1 or 2). Refer to L2-01:
Momentary Power Loss Operation Selection on page 287.
Method 5. After external baseblock is released.
174
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
The drive will resume the operation starting with Speed Search if the Run command is present and the output frequency is
above the minimum frequency when the Baseblock command (H1-oo = 8 or 9) is released. For this operation mode, set the
operation during an external Baseblock command to hold the output frequency (H1-13 = 0).
Parameter Name
Setting Range
b3-01
0, 1
Default
Determined by
A1-02
Setting 0: Disabled
This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed
Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Setting 1: Enabled
This setting performs Speed Search when the Run command is entered. The drive begins running the motor once Speed Search
is complete.
Name
Setting Range
b3-02
0 to 200%
Default
Determined by
A1-02
Note: When parameter A1-02 = 0 (V/f Control) the factory default setting is 120. When parameter A1-02 = 2 (Open Loop Vector) the factory default
setting is 100.
Setting Range
0.1 to 10.0 s
Default
2.0 s
Name
Setting Range
b3-04
10 to 100%
Default
Determined by
o2-04
Note: Available control modes for parameter b3-04 vary by drive model:
CIMR-Ao2A0004 to 2A0415 and 4A0002 to 4A0675: Available when A1-02 = 0, 1.
CIMR-Ao4A0930 to 4A1200: Available when A1-02 = 0.
Name
Speed Search Delay Time
Setting Range
0.0 to 100.0 s
Default
0.2 s
175
Parameter Details
No.
b3-03
5.2 b: Application
No.
Name
Setting Range
b3-06
0.0 to 2.0
Default
Determined by
o2-04
Note: Use Current Detection Speed Search if Speed Estimation is not working correctly even after adjusting b3-06.
Name
Speed Search Detection Compensation Gain
Setting Range
1.00 to 1.20
Default
1.05
Parameter Name
Setting Range
b3-14
0, 1
Default
Determined by
A1-02
Setting 0: Disabled
The drive uses the frequency reference to determine the direction of motor rotation to restart the motor.
Setting 1: Enabled
The drive detects the motor rotation direction to restart the motor.
Name
Speed Search Restart Current Level
Setting Range
0 to 200%
Default
150%
Name
Speed Search Restart Detection Time
Setting Range
0.00 to 1.00 s
Default
0.10 s
Name
Number of Speed Search Restarts
Setting Range
0 to 10
Default
3
Setting Range
0, 1
Default
0
Parameter Name
Speed Search Method Selection
176
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Name
Speed Search Wait Time
Setting Range
0.0 to 30.0 s
Default
0.5 s
Name
Start Speed Search Select
Setting Range
0, 1
Default
0
Name
Timer Function On-Delay Time
Timer Function Off-Delay Time
Setting Range
0.0 to 3000.0 s
0.0 to 3000.0 s
Default
0.0 s
0.0 s
The timer function switches on when the timer function input closes for longer than the value set to b4-01. The timer function
switches off when the timer function input is open for longer than the value set to b4-02. The following diagram illustrates
the timer function operation:
Multi-function Contact
Input: Timer Function
ON
Multi-function Contact
Output: Timer Function
ON
b4-01
On (Closed)
Off (Open)
ON
On (Closed)
Off (Open)
ON
b4-02
b4-01
b4-02
n P Control
The output of P control is the product of the deviation and the P gain so that it follows the deviation directly and linearly. With
P control, only an offset between the target and feedback remains.
n I Control
The output of I control is the integral of the deviation. It minimizes the offset between target and feedback value that typically
remains when pure P control is used. The integral time (I time) constant determines how fast the offset is eliminated.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
177
5.2 b: Application
n D Control
D control predicts the deviation signal by multiplying its derivative (slope of the deviation) with a time constant, then adds
this value to the PID input. This way the D portion of a PID controller provides a braking action to the controller response and
can reduce the tendency to oscillate and overshoot.
D control tends to amplify noise on the deviation signal, which can result in control instability. Only use D control when
absolutely necessary.
n PID Operation
To better demonstrate PID functionality, the diagram below illustrates how the PID output changes when the PID input
(deviation) jumps from 0 to a constant level.
PID input
Time
PID output
I control
PID Output
D control
P control
Time
Description
Sensors Used
Machinery speed is fed back and adjusted to meet the target value. Synchronous control is Tachometer
performed using speed data from other machinery as the target value
Maintains constant pressure using pressure feedback.
Pressure sensor
Keeps flow at a constant level by feeding back flow data.
Flow rate sensor
Thermocoupler,
Maintains a constant temperature by controlling a fan with a thermostat.
Thermistor
Settings
Set H3-02 = C
Set H3-10 = C
Set H3-06 = C
Set bit 1 in register 000F H to 1 and input the setpoint to register 0006 H
Set H6-01 = 2
Set parameter b5-18 = 1 and input the PID setpoint to b5-19
Note: A duplicate allocation of the PID setpoint input will cause an oPE alarm.
178
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Normal PID Feedback
Input the PID feedback signal from one of the sources listed below:
Table 5.9 PID Feedback Sources
Settings
Set H3-02 = B
Set H3-10 = B
Set H3-06 = B
Set H6-01 = 1
Note: A duplicate allocation of the PID feedback input will cause an oPE alarm.
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed below. The differential feedback
function is automatically enabled when a differential feedback input is assigned.
Table 5.10 PID Differential Feedback Sources
Settings
Analog Input A1
Set H3-02 = 16
Analog Input A2
Analog Input A3
Set H3-10 = 16
Set H3-06 = 16
Parameter Details
Note: A duplicate allocation of the PID differential feedback input will cause an oPE alarm.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
179
Pulse Input
PID Feedback
Pulse Input
b5-19
PID Target
Pulse Input
Option Card
Serial Comm
PID Mode
not 16
H3-02/10=B
H6-01=1
H6-01=2
H3-02/10=C
b5-18=1
Off
Z-1
PID Soft
Starter b5-17
PID Feedback
(U5-01)
not B
not 1
not 2
not C
+
Derivative
+
Time 2 or 4
b5-05
b5-01
1 or 3
Adjusted
PID Feedback
(U5-06)
b5-01 = 3/4
not 1
PID Differential
Feedback
(U5-05)
b5-01 = 1/2
H3-02/10
= 16
Frequency Reference 1 to 16
d1-01 to d1-16
Frequency
Reference
b1-01/15
PID Input
Limit
b5-35
PID Input
(U5-02)
0
1
PID Input
Characteristic
H1-oo=35 or
b5-09
-1
Proportional
Gain
b5-02
1
I-time
b5-03
1/s
Z-1
Integral Hold
H1-oo=31
PID Ouput
(U5-03)
+
+
+
+
b5-05
Derivative
Time
Z-1
+ +
2 or 4
1 or 3
Lower Limit 0
Upper Limit
Fmax x109%
-1
PID Output
Characteristic
b5-09
b5-08
PID Delay
Time
Lower Limit
Fmax x109%
Upper Limit
Fmax x109%
PID Output
Upper/Lower
Limit
b5-06 / b5-34
b5-01
Integral Reset
H1-oo=30
I - limit
b5-04
Enabled
Disabled
+
-
SFS
C1-oo
b5-07
PID Offset
PID Output
Gain
b5-10
Always 1 when
b5-01 = 3/4
RUN
On/Off
Output
Frequency
b5-11
Delay
Timer
b5-16
Sleep Function
b5-15
Sleep Level
180
+
Frequency Reference
5.2 b: Application
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Parameter Name
PID Function Setting
Setting Range
0 to 4
Default
0
The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.
Setting 2: Output frequency = PID output 2
The PID controller is enabled and the PID output builds the frequency reference. The PID feedback is D controlled.
Setting 3: Output frequency = frequency reference + PID output 1
The PID controller is enabled and the PID output is added to the frequency reference. The PID input is D controlled.
Setting 4: Output frequency = frequency reference + PID output 2
The PID controller is enabled and the PID output is added to the frequency reference. The PID feedback is D controlled.
Name
Proportional Gain Setting (P)
Setting Range
0.00 to 25.00
Default
1.00
Setting Range
0.0 to 360.0 s
Default
1.0 s
Name
Integral Limit Setting
Setting Range
0.0 to 100.0%
Default
100.0%
Note: On some applications, especially those with rapidly varying loads, the output of the PID function may show a fair amount of oscillation. Program
b5-04 to apply a limit to the integral output and suppress this oscillation.
Name
Derivative Time (D)
Setting Range
0.00 to 10.00 s
Default
0.00 s
Name
PID Output Limit
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0.0 to 100.0%
Default
100.0%
181
Parameter Details
No.
b5-03
5.2 b: Application
Name
PID Offset Adjustment
Setting Range
-100.0 to 100.0%
Default
0.0%
Name
PID Primary Delay Time Constant
Setting Range
0.00 to 10.00 s
Default
0.00 s
Note: Useful when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant frequency. Increasing
this time constant may reduce the responsiveness of the drive.
Parameter Name
PID Output Level Selection
Setting Range
0, 1
Default
0
A positive PID input causes an increase in the PID output (direct acting).
Setting 1: Reverse Output
A positive PID input causes a decrease in the PID output (reverse acting).
Name
PID Output Gain Setting
Setting Range
0.00 to 25.00
Default
1.00
Parameter Name
PID Output Reverse Selection
Setting Range
0, 1
Default
0
Negative PID output will be limited to 0 and the drive output will be stopped.
Setting 1: Reverse Enabled
Negative PID output will cause the drive to run in the opposite direction.
182
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
The following figure illustrates the working principle of feedback loss detection when the feedback signal is too low. Feedback
high detection works in the same way.
PID feedback value
PID
Feedback
Detection
Loss Level
(b5-13)
no FbL
detection
PID Feedback
Loss Detection Time
(b5-14)
time
FbL detection
PID Feedback
Loss Detection Time
(b5-14)
Parameter Name
PID Feedback Loss Detection Selection
Setting Range
0 to 5
Default
0
A digital output set for PID feedback low (H2-oo = 3E) will be triggered if the PID feedback value is below the detection
level set to b5-13 for the time set to b5-14 or longer. A digital output set for PID feedback high (H2-oo = 3F) will be
triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a
fault nor an alarm is displayed on the digital operator and the drive will continue operation. The output resets when the feedback
value leaves the loss detection range.
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a FBL - Feedback Low
alarm will be displayed and a digital output set for PID feedback low (H2-oo = 3E) will be triggered. If the PID feedback
value exceeds the level set to b5-36 for longer than the time set to b5-37, a FBH - Feedback High alarm will be displayed
and a digital output set for PID feedback high (H2-oo = 3F) will be triggered. Both events trigger an alarm output (H1oo = 10). The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection
range.
Setting 2: Feedback Loss Fault
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a FbL - Feedback Low
fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a FbH
- Feedback High fault will be displayed. Both events trigger a fault output (H1-oo = E) and cause the drive to stop the
motor.
Setting 3: Digital output only, even if PID is disabled by digital input
Same as b5-12 = 0. Detection remains active when PID is disabled by a digital input (H1-oo = 19).
Setting 4: Feedback loss alarm, even if PID is disabled by digital input
Same as b5-12 = 1. Detection remains active when PID is disabled by a digital input (H1-oo = 19).
Setting 5: Feedback loss fault, even if PID is disabled by digital input
Same as b5-12 = 2. Detection remains active when PID is disabled by a digital input (H1-oo = 19).
Name
PID Feedback Low Detection Level
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0 to 100%
Default
0%
183
Parameter Details
5.2 b: Application
Name
PID Feedback Low Detection Time
Setting Range
0.0 to 25.5 s
Default
1.0 s
Name
PID Feedback High Detection Level
Setting Range
0 to 100%
Default
100%
Name
PID Feedback High Detection Time
Setting Range
0.0 to 25.5 s
Default
1.0 s
n PID Sleep
The PID Sleep function stops the drive when the PID output or the frequency reference falls below the PID Sleep operation
level for a certain time. The drive will resume operating when the PID output or frequency reference rise above the PID Sleep
operation level for the specified time. An example of PID Sleep operation appears in the figure below.
PID Output
PID Sleep Level ( b5-15)
Sleep Delay Time
Internal Run
command
b5-16
Run
b5-16
Stop
Run command enabled
External Run
command
During Run
The PID Sleep function is active even when PID control is disabled.
The PID Sleep function stops the motor according to the stopping method set to b1-03.
The parameters necessary to control the PID Sleep function are explained below.
Name
PID Sleep Function Start Level
Setting Range
0.0 to 400.0 Hz
Default
0.0 Hz
Setting Range
0.0 to 25.5 s
Default
0.0 s
184
Name
PID Sleep Delay Time
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Name
PID Accel/Decel Time
Setting Range
0.0 to 6000.0 s
Default
0.0 s
Setting Range
0, 1
Default
0
Setting Range
0.00 to 100.00%
Default
0.00%
Parameter Name
PID Setpoint Selection
Setting 0: Disabled
Name
PID Setpoint Value
Setting Range
0 to 3
Default
1
Parameter Details
No.
b5-20
Setting 0: Hz
The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: %
The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min
The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined
Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PID
monitors U1-01 and U1-04.
Name
PID Output Lower Limit
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
-100.0 to 100.0%
Default
0.00%
185
5.2 b: Application
Name
PID Input Limit
Setting Range
0 to 1000.0%
Default
1000.0%
n b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID
feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
No.
Name
Setting Range
b5-38
1 to 60000
b5-39
0 to 3
Default
Determined by
b5-20
Determined by
b5-20
Name
Frequency Reference Monitor Content During PID
Setting Range
0, 1
Default
0
Monitor U1-01 displays the frequency reference increased or reduced for the PID output.
Setting 1: Frequency Reference
No.
b5-47
Name
Reverse Operation Selection 2 by PID Output
Setting Range
0, 1
Default
1
Negative PID output will be limited to 0 and the drive output will be stopped.
Setting 1: Reverse Enabled
Negative PID output will cause the drive to run in the opposite direction.
186
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
n Fine-Tuning PID
Follow the directions below to fine tune PID control parameters:
Table 5.11 PID Fine Tuning
Goal
Tuning Procedure
Result
Response
Suppress overshoot
Before adjustment
After adjustment
Time
Response
After adjustment
Before adjustment
Time
Before adjustment
Response
After adjustment
Time
Before adjustment
After adjustment
Parameter Details
Response
Time
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
187
5.2 b: Application
OFF
Run Command
OFF
ON
b6-01
b6-03
Output Frequency
b6-02
b6-04
Name
Dwell Reference at Start
Dwell Time at Start
Setting Range
0.0 to 400.0 Hz
0.0 to 10.0 s
Default
0.0 Hz
0.0 s
Name
Dwell Reference at Stop
Dwell Time at Stop
Setting Range
0.0 to 400.0 Hz
0.0 to 10.0 s
Default
0.0 Hz
0.0 s
Droop control automatically balances the load level between two motors driving the same load. Droop control must be activated
in one of the drives controlling these motors. The drive in which Droop control is activated shifts the load from one motor to
another by automatically reducing the speed when the torque reference rises, and automatically increasing the speed when the
torque reference falls.
Note: Disable Feed Forward (n5-01 = 0) whenever using Droop control.
Motor A runs faster than B, pulling more load
= 100% Load
= 90% Load
fref_A = constant
fref_B decrease
= 80% Load
= 90% Load
fref_A = constant
fref_B increase
= 80% Load
= 90% Load
= 100% Load
= 90% Load
188
Parameter Name
Droop Control Gain
Setting Range
0.0 to 100.0%
Default
0.0%
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Speed
Speed reference
Droop control gain
b7-01
Torque
0
100%
Parameter Name
Droop Control Delay Time
Setting Range
0.03 to 2.00 s
Default
0.05 s
Setting Range
0, 1
Default
1
Parameter Name
Droop Control Limit Selection
Setting 0: Disabled
Setting 1: Enabled
Parameter Name
Setting Range
b8-01
0, 1
Default
Determined by
A1-02
Setting 0: Disabled
Setting 1: Enabled
Name
Setting Range
b8-02
0.0 to 10.0
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Default
Determined by
A1-02
189
Parameter Details
The Energy Saving feature improves overall system operating efficiency by operating the motor at its most efficient level.
5.2 b: Application
Name
Setting Range
b8-03
0.00 to 10.00 s
Default
Determined by
A1-02 and o2-04
Name
Setting Range
b8-04
0.00 to 655.00
Default
Determined by
C6-01, E2-11, and
o2-04
Note: The default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically when AutoTuning for Energy Saving is performed (Refer to Auto-Tuning on page 135).
Name
Power Detection Filter Time
Setting Range
0 to 2000 ms
Default
20 ms
No.
b8-06
Name
Search Operation Voltage Limit
Setting Range
0 to 100%
Default
0%
No.
b8-16
Name
Energy Saving Parameter (Ki) for PM Motors
Setting Range
0.00 to 2.00
Default
1.00
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
2. This parameter is not available in models CIMR-Ao4A0930 and 4A1200.
No.
b8-16
Name
Energy Saving Parameter (Kt) for PM Motors
Setting Range
0.00 to 2.00
Default
1.00
ON
Run command
ON
OFF
Zero Servo
Operation
Note: 1. The Run command must remain on when using the Zero Servo function. Zero Servo will not hold the load in place if the Run command is
switched off.
2. When the Zero Servo command has shut off, the Zero Servo Completion digital output width also shuts off.
3. Avoid using Zero Servo to lock 100% load for long periods, as this can trigger a fault. If such loads need to be held in place for long periods,
either make sure the current is less than 50% of the drive rated current during Zero Servo, or use a larger capacity drive.
4. If the load rotates the motor when using CLV/PM, a dv4 fault may occur. To prevent this, either increase the Zero Servo gain (b9-01) or
increase the number of pulses set to F1-19 that are required to trigger dv4.
No.
b9-01
Name
Zero Servo Gain
Setting Range
0 to 100
Default
5
Name
Zero Servo Completion Width
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0 to 16383
Default
10
191
Parameter Details
When Zero Servo mode is active, the deviation between the rotor position and the zero position is displayed in monitor U6-22
(monitor value must be divided by 4 to get the deviation in actual encoder pulses).
A digital output programmed for Zero Servo complete (H2-oo = 33) is turned on when the rotor position is within the zero
position, plus or minus the Zero Servo completion width set to parameter b9-02.
5.3 C: Tuning
5.3
C: Tuning
C parameters set the characteristics for acceleration, deceleration, and S-curves. Other parameters in the C group cover settings
for slip compensation, torque compensation, and carrier frequency.
Parameter Name
Acceleration Time 1
Deceleration Time 1
Acceleration Time 2
Deceleration Time 2
Acceleration Time 3 (Motor 2 Accel Time 1)
Deceleration Time 3 (Motor 2 Decel Time 1)
Acceleration Time 4 (Motor 2 Accel Time 2)
Deceleration Time 4 (Motor 2 Accel Time 2)
Setting Range
Default
10.0 s
<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
Accel/decel times 1 are active by default if no input is set. Activate accel/decel times 2, 3, and 4 by digital inputs
(H1-oo = 7 and 1A) as explained in Table 5.12.
Table 5.12 Accel/Decel Time Selection by Digital Input
Accel/Decel Time Sel. 1
H1-oo = 7
0
1
0
1
0
0
1
1
Active Times
Acceleration
C1-01
C1-03
C1-05
C1-07
Deceleration
C1-02
C1-04
C1-06
C1-08
Figure 5.29 shows an operation example for changing accel/decel. times. The example below requires that the stopping method
be set for Ramp to stop (b1-03 = 0).
Output
frequency
Accel Time 1
(C1-01)
Decel Time 1
Decel Time 3
Decel Time 2
(C1-02)
Accel Time 3 (C1-06)
Accel Time 2 (C1-04)
(C1-05)
(C1-03)
Accel Time 4
(C1-07)
Decel Time 1
(C1-02)
Decel Time 4
(C1-08)
Decel Time 1
(C1-02)
Time
FWD (REV)
Run command
ON
OFF
ON
ON
ON
OFF
ON
ON
OFF
ON
192
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Switching Acceleration and Deceleration Times by Motor Selection
When switching between motor 1 and 2 using a digital input (H1-oo= 16), parameters C1-01 to C1-04 become accel/decel
times 1 and 2 for motor 1, while C1-05 to C1-08 become accel/decel times 1 and 2 for motor 2. Accel/decel times 1 and 2 can
be switched for each motor using a digital inputs set to H1-oo = 7 like shown in Table 5.13.
Note: 1. The motor 2 selection function cannot be used with PM motors.
2. Attempting to use the digital input setting Accel/Decel time 2 selection (H1-oo = 1A) together with motor 1/2 switching triggers an
oPE03 error, indicating contradictory multifunction input settings.
Table 5.13 Motor Switching and Accel/Decel Time Combinations
Accel/Decel Time 1 (H1-oo = 7)
Motor 1 Selected
(Terminal set to H1-oo = 16 OFF)
Accel
C1-01
C1-03
Open
Closed
Motor 2 Selected
(Terminal set to H1-oo = 16 ON)
Decel
C1-02
C1-04
Accel
C1-05
C1-07
Decel
C1-06
C1-08
The drive can switch between different acceleration and deceleration times automatically. The drive will switch from accel/
decel time 4 in C1-07 and C1-08 to the default accel/decel time in C1-01 and C1-02 (C1-05 and C1-06 for motor 2) when the
output frequency exceeds the frequency level set to parameter C1-11. When the frequency falls below this level, the accel/
decel times are switched back. Figure 5.30 shows an operation example.
Note: Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by the frequency level set to C1-11.
For example, if accel/decel time 2 is selected, the drive will use only accel/decel time 2; it will not switch from accel/decel time 4 to the selected
one.
Output Frequency
C1-11
Accel/Decel Time
Switch Frequency
C1-07
setting
C1-01
setting
C1-02
setting
C1-08
setting
Parameter Name
Setting Range
C1-11
Default
Determined by
A1-02 <1>
<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 100.0%) instead of in Hz.
Note: Setting C1-11 to 0.0 disables this function.
Parameter Name
Fast Stop Time
Setting Range
0.0 to 6000.0 s
<1>
Default
10.0 s
<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
193
Parameter Details
5.3 C: Tuning
NOTICE: Rapid deceleration can trigger an overvoltage fault. The drive output shuts off when faulted and the motor coasts. Set an
appropriate Fast Stop time to C1-09 to avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely.
Parameter Name
Accel/Decel Time Setting Units
Setting Range
0, 1
Default
1
The accel/decel times are set in 0.01 s units. The setting range will be 0.00 to 600.00 s. C1-10 cannot be set to 0 if any of the
parameters C1-01 to C1-09 are set to 600.1 seconds or more.
Setting 1: 0.1 s units
The accel/decel times are set in 0.1 s units. The setting range will be 0.0 to 6000.0 s.
Parameter Name
Setting Range
C2-01
C2-02
C2-03
C2-04
0.00 to 10.00 s
Default
Determined by
A1-02
0.20 s
0.20 s
0.00 s
C2-02
Output
frequency
C2-03
C2-04
C2-01
C2-04
C2-01
C2-02
C2-03
Setting the S-curve will increase the acceleration and deceleration times.
Actual accel time = accel time setting + (C2-01 + C2-02) / 2
Actual decel time = decel time setting + (C2-03 + C2-04) / 2
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Decrease the setting if the motor at constant speed is faster than the frequency reference.
No.
Parameter Name
Setting Range
C3-01
0.0 to 2.5
Default
Determined by
A1-02
Note: Default setting is 0.0 in V/f Control (A1-02 = 0), and 1.0 in Open Loop Vector Control (A1-02 = 2). In Closed Loop Vector Control, slip
compensation corrects inaccuracies that can result from temperature fluctuation in the rotor.
Parameter Name
Setting Range
C3-02
0 to 10000 ms
Default
Determined by
A1-02
Note: Default for V/f Control (A1-02 = 0) is 2000 ms. Default for Open Loop Vector Control (A1-02 = 2) is 200 ms.
Parameter Name
Slip Compensation Limit
Setting Range
0 to 250%
Default
200%
The slip compensation limit is constant throughout the constant torque range (frequency reference E1-06). In the constant
power range (frequency reference E1-06), it is increased based on C3-03 and the output frequency as shown in the following
diagram.
E1-04
E1-06 C3-03
C3-03
Output Frequency
E1-04
Maximum
Frequency
Parameter Details
E1-06
Base
Frequency
Parameter Name
Slip Compensation Selection during Regeneration
Setting Range
0 to 2
Default
0
Setting 0: Disabled
Slip compensation is not provided. Depending on the load and mode of operation, the actual motor speed will be lower or
higher than the frequency reference.
Setting 1: Enabled (6 Hz and above)
Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
Setting 2: Enabled (compensation provided wherever possible)
Slip compensation is enabled during regenerative operation and at frequencies as low as 2 Hz. The drive uses the motor rated
slip set to E2-02 to automatically calculate the frequency range where compensation will be disabled.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
195
5.3 C: Tuning
Parameter Name
Output Voltage Limit Operation Selection
Setting Range
0, 1
Default
0
Note: Available control modes for parameter C3-05 vary by drive model:
CIMR-Ao2A0004 to 2A0415, 4A0002 to 4A0675, and 5A0003 to 5A0242: Available when A1-02 = 0, 1
CIMR-Ao4A0930 and 4A1200: Available when A1-02 = 2, 3, 6, 7
Setting 0: Disabled
Setting 1: Enabled
No.
C3-16
Parameter Name
Output Voltage Limit Operation Start Level
Setting Range
70.0 to 90.0%
Default
85.0%
No.
C3-17
Parameter Name
Maximum Output Voltage Limit Level
Setting Range
85.0 to 100.0%
Default
90.0%
Setting Range
30.0 to 100.0%
Default
90.0%
No.
C3-18
Parameter Name
Output Voltage Limit Level
Parameter Name
Motor 2 Slip Compensation Gain
Setting Range
0.0 to 2.5
Default
Determined by E3-01
Note: Default setting is 0.0 in V/f Control (A1-02 = 0). Default setting is 1.0 in Open Loop Vector Control (A1-02 = 2) and Closed Loop Vector
Control (A1-02 = 3). In Closed Loop Vector Control, slip compensation gain acts as an adaptable gain.
Parameter Name
Motor 2 Slip Compensation Primary Delay Time
Setting Range
0 to 10000 ms
Default
Determined by A1-02
Note: The default for V/f Control (A1-02 = 0) is 2000 ms. The default for Open Loop Vector Control (A1-02 = 2) is 200 ms.
196
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Parameter Name
Motor 2 Slip Compensation Limit
Setting Range
0 to 250%
Default
200%
The slip compensation limit is constant throughout the constant torque range (frequency reference E3-06). In the constant
power range (frequency reference E3-06), it is increased based on C3-23 and the output frequency as illustrated in the
following diagram.
E3-04
E3-06 C3-23
C3-23
Output Frequency
E3-06
Base
Frequency
E3-04
Maximum
Frequency
Parameter Name
Motor 2 Slip Compensation Selection during
Regeneration
Setting Range
Default
0 to 2
Setting 0: Disabled
Setting 1: Enabled (6 Hz and above)
Setting 2: Enabled (compensation provided wherever possible)
Parameter Details
No.
Parameter Name
Setting Range
C4-01
0.00 to 2.50
Default
Determined by
A1-02
The drive calculates the motor primary voltage loss using the output current and the termination resistor value (E2-05 for IM
motors, E5-05 for PM motors) and adjusts the output voltage to compensate insufficient torque at start or when load is applied.
The effects of this voltage compensation can be increased or decreased using parameter C4-01.
Torque Compensation in OLV:
The drive controls the motor excitation current (d-Axis current) and torque producing current (q-Axis current) separately.
Torque compensation affects the torque producing current only. C4-01 works as a factor of the torque reference value that
builds the torque producing current reference.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
197
5.3 C: Tuning
Adjustment
Although this parameter rarely needs to be changed, it may be necessary to adjust the torque compensation gain in small steps
of 0.05 in the following situations:
Increase this setting when using a long motor cable.
Decrease this setting when motor oscillation occurs.
Adjust C4-01 so the output current does not exceed the drive rated current.
Note: 1. Refrain from adjusting torque compensation in Open Loop Vector Control, as it can have a negative effect on torque accuracy.
2. Refrain from adjusting this parameter in OLV/PM. Setting this value too high can cause overcompensation and motor oscillation.
Parameter Name
Setting Range
C4-02
0 to 60000 ms
Default
Determined by
A1-02
Adjustment
Although C4-02 rarely needs to be changed, adjustments may be necessary in the following situations:
Increase this setting if the motor vibrates.
Decrease this setting if the motor responds too slowly to changes in the load.
Parameter Name
Torque Compensation at Forward Start
Setting Range
0.0 to 200.0%
Default
0.0%
Parameter Name
Torque Compensation at Reverse Start
Setting Range
-200.0 to 0.0%
Default
0.0%
Parameter Name
Torque Compensation Time Constant
Setting Range
0 to 200 ms
Default
10 ms
Parameter Name
Torque Compensation Primary Delay Time 2
Setting Range
0 to 10000 ms
Default
150 ms
Note: If C4-06 is set to a relatively large value, increase the setting in n2-03 (AFR Time Constant 2) proportionally.
Parameter Name
Motor 2 Torque Compensation Gain
Setting Range
0.00 to 2.50
Default
1.00
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Frequency
reference
Limit
ASR limit
Detected speed
Change
rate
limiter
C5-01
C5-03
I
C5-05
C5-02, C5-04
Figure 5.34 Speed Control Block Diagram for V/f Control with PG
Torque limits
C5-01, C5-03
Frequency
reference
Detected speed
<1>
I
C5-02, C5-04
I
limit
Torque reference
Primary
filter
+
C5-06
(C5-10)
L7-01 to L7-04
C5-08
Figure 5.35 Speed Control Block Diagram for CLV, AOLV/PM and CLV/PM
<1> AOLV/PM estimates the speed using the motor model and does not require an encoder feedback signal.
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Perform Auto-Tuning and set up all motor data correctly prior to adjusting ASR parameters.
Use analog output signals to monitor the frequency reference after softstarter (U1-16) and the motor speed (U1-05) when
adjusting the ASR. Refer to H4: Multi-Function Analog Outputs on page 275 for details on setting up analog output
functions.
Generally when tuning the ASR, optimize the ASR gain before adjusting the integral time settings. Always make adjustments
with the load connected to the motor.
Adjusting the ASR Parameters in V/f Control with PG
In V/f Control with PG, the ASR settings change between two sets of parameters depending on the motor speed as described
in C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2 on page 201.
Perform the following steps for adjusting ASR parameters:
1.
2.
3.
4.
5.
6.
Run the motor at minimum speed and increase ASR gain 2 (C5-03) as much as possible without oscillation.
Run the motor at minimum speed and decrease ASR integral time 2 (C5-04) as much as possible without oscillation.
Check the output current monitor to make sure that the output current is less than 50% of the drive rated current. If
the value is higher than 50%, decrease C5-03 and increase C5-04.
Run the motor at maximum speed and increase ASR gain 1 (C5-01) as much as possible without oscillations.
Run the motor at maximum speed and decrease ASR integral time 1 (C5-02) as much as possible without oscillations.
If higher speed precision and faster response during acceleration or deceleration are required, enable integral control
during accel/decel by setting parameter C5-12 to 1. Change the speed and make sure no over/undershoot occurs.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
199
Parameter Details
5.3 C: Tuning
The drive is preset to use ASR settings C5-01/02 over the entire speed range in CLV, AOLV/PM, and CLV/PM. If required
by the application, a second set of ASR parameters (C5-03/04) can be automatically activated depending on the motor speed
or by using a digital input. Refer to C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2 on
page 201.
Perform the following steps for adjusting ASR parameters:
1.
2.
3.
4.
Run the motor at zero speed and increase the ASR gain (C5-01) as much as possible without oscillation.
Run the motor at zero speed and decrease the ASR integral time (C5-02) as much as possible without oscillation.
Run at the normal operating speed. Check for over/undershoot when changing speed and for any oscillation.
If problems occur in step 3, increase the integral time and reduce the gain.
Alternatively, use different ASR settings for high and low speed. Set the values from step 1 and 2 to parameters C5-03
and C5-04, then set an ASR switching frequency in parameter C5-07. Run the motor at a speed higher than C5-07
and repeat step 3 while adjusting C5-01 and C5-02.
Use Table 5.14 when making adjustments to ASR. Though the parameters listed below are for motor 1, the same changes can
be made to the corresponding motor 2 parameters when running a second motor.
Table 5.14 ASR Setup Problems and Corrective Actions
Problem
Possible Solutions
Speed reference
Motor Speed
Time
Motor Speed
Speed reference
Time
Speed reference
Motor Speed
Time
Speed reference
Motor Speed
Time
200
Check the pulse number set to F1-01 and the gear ratio in F1-12
and F1-13.
Make sure the pulse signal from the encoder is set up properly.
Check monitor U6-04 and determine if the ASR is working at
its output limit (setting of C5-05). If the ASR is at the output
limit, increase C5-05.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
No.
Parameter Name
Setting Range
C5-01
0.00 to 300.00
C5-02
0.000 to 10.000 s
C5-03
0.00 to 300.00
C5-04
0.000 to 10.000 s
Default
Determined by
A1-02
Determined by
A1-02
Determined by
A1-02
Determined by
A1-02
These parameter settings will function differently depending on the control mode.
V/f Control with PG
Parameters C5-01 and C5-02 determine the ASR characteristics at maximum speed. Parameters C5-03 and C5-04 determine
the characteristics at minimum speed.
P = C5-01
I = C5-02
P and I setting
P = C5-03
I = C5-04
E1-09
Min. output frequency
Motor speed
E1-04
Max. output frequency
In these control modes, parameters C5-03 and C5-04 define the ASR gain an integral time at zero speed. The settings in C5-01
and C5-02 are used at speeds above the setting in C5-07. C5-07 is set to 0 as the default so that C5-01 and C5-02 are used
over the entire speed range. Refer to C5-07: ASR Gain Switching Frequency on page 202.
P, I
P = C5-01
I = C5-02
Ramp
P = C5-03
I = C5-04
C5-07
(Low speed)
The gain set in C5-03 can also be activated with a digital input programmed to ASR gain switch (H1-oo = 77). When the
terminal is open, the drive uses the ASR gain level set by the pattern in the figure above. When the terminal closes, C5-03 is
used. The integral time set to C5-02 is used to change linearly between these settings. The ASR gain switch command from
a multi-function input terminal overrides the switching frequency set to C5-07.
ASR Gain Switch signal
(Digital input)
OFF
ON
Proportional gain
determined
by motor speed.
C5-02
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
201
5.3 C: Tuning
ASR Gain Tuning (C5-01, C5-03)
The higher this setting, the faster the speed response, although a setting that is too high can lead to oscillation. Increase this
setting with larger loads to minimize the speed deviation.
ASR Integral Time Tuning (C5-02, C5-04)
Determines how fast a continuous speed deviation problem is eliminated. A setting that is too long reduces the responsiveness
of the speed control. A setting that is too short can cause oscillation.
Parameter Name
ASR Limit
Setting Range
0.0 to 20.0%
Default
5.0%
Parameter Name
ASR Primary Delay Time Constant
Setting Range
0.000 to 0.500 s
Default
Determined by A1-02
Parameter Name
ASR Gain Switching Frequency
Setting Range
0.0 to 400.0 Hz
Default
0.0 Hz
Note: A multi-function input set for the ASR gain switch (H1-oo = 77) takes priority over the ASR gain switching frequency.
Switching the proportional gain and integral time in the low or high speed range can help stabilize operation and avoid resonance
problems. A good switching point is 80% of the frequency where oscillation occurs or at 80% of the target speed. Refer to
C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2 on page 201.
Parameter Name
ASR Integral Limit
Setting Range
0 to 400%
Default
400%
Parameter Name
Integral Operation during Accel/Decel
Setting Range
0, 1
Default
0
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
These parameters are set automatically when Inertia Tuning and ASR Tuning are performed in CLV and CLV/PM control
modes. Refer to Auto-Tuning on page 135 for details on Auto-Tuning or enter the data manually.
No.
Parameter Name
Setting Range
C5-17
Motor Inertia
C5-18
0.0 to 6000.0
Default
Determined by C6-01,
E5-01 and o2-04
1.0
n C5-21, C5-23 / C5-22, C5-24: Motor 2 ASR Proportional Gain 1, 2 / Integral Time 1, 2
These parameters function for motor 2 the same way that C5-01 through C5-04 function for motor 1. Refer to C5-01, C5-03/
C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2 on page 201 for details.
No.
C5-21
C5-22
C5-23
C5-24
Parameter Name
Motor 2 ASR Proportional Gain 1
Motor 2 ASR Integral Time 1
Motor 2 ASR Proportional Gain 2
Motor 2 ASR Integral Time 2
Setting Range
0.00 to 300.00
0.000 to 10.000 s
0.00 to 300.00
0.000 to 10.000 s
Default
Determined by E3-01
Determined by E3-01
Determined by E3-01
Determined by E3-01
Parameter Name
Motor 2 ASR Limit
Setting Range
0.0 to 20.0%
Default
5.0%
Parameter Name
Motor 2 ASR Primary Delay Time Constant
Setting Range
0.000 to 0.500 s
Default
0.004 s
Functions for motor 2 the same way that C5-07 functions for motor 1. Sets the frequency for motor 2 to change ASR proportional
gain 1 and 2 (C5-21, C5-23) as well as the integral time 1 and 2 (C5-22, C5-24). Refer to C5-01, C5-03/C5-02, C5-04: ASR
Proportional Gain 1, 2/ASR Integral Time 1, 2 on page 201 for details.
No.
C5-27
Parameter Name
Motor 2 ASR Gain Switching Frequency
Setting Range
0.0 to 400.0 Hz
Default
0.0 Hz
Note: A multi-function input set for the ASR gain switch (H1-oo = 77) takes priority over the ASR gain switching frequency.
Parameter Name
Motor 2 ASR Integral Limit
Setting Range
0 to 400%
Default
400%
Parameter Name
Integral Operation during Accel/Decel for Motor 2
Setting Range
0, 1
Default
0
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
203
5.3 C: Tuning
Setting 1: Enabled
Parameter Name
Setting Range
C5-37
Motor 2 Inertia
C5-38
0.0 to 6000.0
Default
Determined by C6-01 and
o2-04
1.0
Parameter Name
Duty Mode Selection
Setting Range
0, 1
Default
1 (ND)
Overload
150 %
Overload
120 %
Rated Load
100 %
Rated Load
100 %
Performance
Application
Overload capability (oL2)
Stall Prevention during
Acceleration (L3-02)
Stall Prevention during
Run (L3-06)
Default Carrier Frequency
Motor Speed
100 %
Motor Speed
100 %
150%
120%
150%
120%
2 kHz
Note: Changing the Duty Mode selection automatically changes the maximum size motor that the drive can run, sets the E2-oo parameters to
appropriate values (E4-oo for motor 2), and recalculates parameter settings determined by motor capacity (e.g., b8-04, L2-03, n5-02, L3-24,
C5-17, and C5-37).
204
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Parameter Name
Setting Range
C6-02
1 to F <1>
Default
Determined by A1-02, o2-04.
Reset when C6-01 is changed.
Settings:
C6-02
1
2
3
4
Carrier Frequency
2.0 kHz
5.0 kHz (4.0 kHz)
8.0 kHz (6.0 kHz)
10.0 kHz (8.0 kHz)
C6-02
5
6
7
8
Carrier Frequency
12.5 kHz (10.0 kHz)
15.0 kHz (12.0 kHz)
Swing PWM 1
Swing PWM 2
C6-02
9
A
Carrier Frequency
Swing PWM 3
Swing PWM 4
Note: 1. Swing PWM uses a carrier frequency of 2.0 kHz as a base, then applies a special PWM pattern to reduce the audible noise.
2. The value in parenthesis indicates the carrier frequency for AOLV/PM.
Remedy
<2>
Wiring Distance
Up to 50 m
1 to F (up to 15 kHz)
Up to 100 m
1 to 2 (up to 5 kHz),
7 (Swing PWM)
Note: The maximum cable length is 100 m when using OLV/PM (A1-02 = 5) or AOLV/PM (A1-02 = 6).
n C6-03, C6-04, C6-05: Carrier Frequency Upper Limit, Lower Limit, Proportional Gain
These parameters set a user-defined or a variable carrier frequency. Set C6-02 to F to set the upper and lower limits and the
carrier frequency proportional gain.
No.
Parameter Name
Setting Range
kHz <1>
C6-03
C6-04
C6-05
0 to 99 <2>
1.0 to 15.0
Default
Determined by
C6-02
<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 100.0%) instead of in Hz.
<2> The setting range is 1.0 to 5.0 for models CIMR-Ao4A0515 to 4A1200.
A carrier frequency between the fixed selectable values can be entered in parameter C6-03 when C6-02 is set to F.
In V/f Control, adjust parameter C6-04 to the same value as C6-03.
Setting a Variable Carrier Frequency (V/f Control)
In V/f Control, the carrier frequency can be set up to change linearly with the output frequency by setting the upper and lower
limits for the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05) as shown in Figure 5.39.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
205
Parameter Details
<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to the following table.
<2> The default carrier frequency in ND is Swing PWM (C6-02 = 7), using a 2 kHz base. Increasing the carrier frequency is permissible when the drive
is set for Normal Duty, however the drive rated current is reduced when the carrier frequency is increased.
5.3 C: Tuning
Carrier Frequency
C6-03
C6-04
Output
Frequency x C6-05
Output Frequency
E1-04
Max Output Frequency
Parameter Name
Carrier Frequency during Rotational Auto-Tuning
Setting Range
0, 1
Default
0
Setting 0: 5 kHz
Setting 1: Same value set to C6-03
The 2 kHz values shown for ND in Table 5.18 are equal to the drive rated current shown on the drive nameplate. Increasing
the carrier frequency above 2 kHz will reduce the ND rated output current of the drive as shown in Table 5.18.
Heavy Duty Rating (HD)
A carrier frequency setting of 8 kHz or lower is equal to the drive rated current shown on the drive nameplate. The factory
default setting for carrier frequency in HD mode is 2 kHz. Increasing the carrier frequency above 8 kHz will reduce the HD
rated output current of the drive as shown in the following tables.
Use the data in the following tables to linearly calculate output current values for carrier frequencies not listed.
Table 5.16 Three-Phase 200 V Class Carrier Frequency and Current Derating
Model
CIMR-Ao
2A0004
2A0006
2A0008
2A0010
2A0012
2A0018
2A0021
2A0030
2A0040
2A0056
2A0069
2A0081
2A0110
2A0138
206
2 kHz
3.2
5
6.9
8
11
14
17.5
25
33
47
60
75
85
115
15 kHz
2.56
4
5.5
6.4
8.8
11.2
14
20
26.4
37.6
48
53
60
81
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Model
CIMR-Ao
2A0169
2A0211
2A0250
2A0312
2A0360
2A0415
2 kHz
145
180
215
283
346
415
10 kHz
116
144
172
226
277
332
Table 5.17 Three-Phase 400 V Class Carrier Frequency and Current Derating
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
4A0018
4A0023
4A0031
4A0038
4A0044
4A0058
4A0072
4A0088
4A0103
Model
CIMR-Ao
4A0139
4A0165
4A0208
4A0250
4A0296
4A0362
4A0414
4A0515
4A0675
4A0930
4A1200
2 kHz
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18
24
31
39
45
60
75
91
2 kHz
112
150
180
216
260
304
370
450
605
810
1090
5 kHz
112
150
180
216
260
304
370
375
504
675
908
10 kHz
78
105
126
151
182
213
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
2 kHz
139
165
208
250
296
362
414
515
675
930
1200
5 kHz
112
150
180
216
260
304
370
397
528
716
938
15 kHz
1.1
2
2.9
3.3
4.3
5.5
8.9
10.8
14.4
18.6
23.4
27
36
45
55
Parameter Details
Model
CIMR-Ao
10 kHz
78
105
126
151
182
213
207
5.3 C: Tuning
Table 5.18 Carrier Frequency and Current Derating
Model
CIMR-Ao
5A0003
5A0004
5A0006
5A0009
5A0011
5A0017
5A0022
5A0027
5A0032
Model
CIMR-Ao
5A0041
5A0052
5A0062
5A0077
5A0099
Model
CIMR-Ao
5A0125
5A0145
5A0192
5A0242
208
2 kHz
1.7
3.5
4.1
6.3
9.8
12.5
17
22
27
17
17
15.1
22
22
19.5
27
27
23.9
32
15 kHz
1.3
2.1
2.9
4.5
5.6
2 kHz
32.0
41.0
52.0
62.0
77.0
99.0
10 kHz
29.4
37.3
41.9
52.0
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.4
d: Reference Settings
The figure below gives an overview of the reference input, selections, and priorities.
b1-01
(Freq. Reference Source 1)
=4
=3
=2
=1
=0
Digital Input
H1-oo = 2
Remote
MS 1
Local
Set to supply the
auxiliary frequency reference
Terminal A2
b1-15
(Freq. Reference Source 2)
H3-10 = 2
d1-02
=4
MS 2
H3-10 = 2
Terminal A3
H3-06 = 3
=3
d1-03
=2
=1
Frequency
Reference
4 through 16
=0
d1-04
d1-15
d1-16
MS 3
H3-06 = 3
MS 4
Open
NetRef
1
1 ComRef
0
Close
Frequency
Reference
MS 15
MS 16
Jog
Multi-Step Speed
Parameter Name
Setting Range
d1-01 to d1-16
Frequency Reference 1 to 16
0.00 to 400.00 Hz
<1> <2>
d1-17
0.00 to 400.00 Hz
<1> <2>
Default
0.00 Hz
<2>
6.00 Hz
<2>
<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
<2> Setting units are determined by parameter o1-03. The default is Hz (o1-03 = 0) in V/f, V/f w/PG, OLV, CLV, and OLV/PM control modes. The
default for AOLV/PM and CLV/PM control modes expresses the frequency reference as a percentage (o1-03 = 1).
To use several speed references for a multi-step speed sequence, set the H1-oo parameters to 3, 4, 5, and 32. To assign the
Jog reference to a digital input, set H1-oo to 6.
Notes on using analog inputs as Multi-Speed 1, 2, and 3:
The first frequency reference (Multi-Speed 1) comes from the source specified in b1-01. When using an analog input terminal
to supply the frequency reference, assign the frequency reference source to the control terminals (b1-01 = 1).
When an analog input is set to Auxiliary frequency 1 (H3-02, H2-06, or H2-10 = 2), the value set to this input will be used
as the Multi-Step Speed 2 instead of the value set to parameter d1-02. If no analog inputs are set for Auxiliary frequency
1, then d1-02 becomes the reference for Multi-Step Speed 2.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
209
Multi-Step
Speed
H1-oo = 3
OFF
Multi-Step
Speed 2
H1-oo = 4
OFF
Multi-Step
Speed 3
H1-oo = 5
OFF
Multi-Step
Speed 4
H1-oo = 32
OFF
Jog Reference
H1-oo = 6
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
210
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
d1-15
d1-14
d1-13
d1-12
d1-07
d1-06
d1-05
d1-01
(A1)
d1-02
(A2)
d1-01
(A3)
d1-04
d1-17
Time
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Jog Reference
ON
Parameter Name
Frequency Reference Upper Limit
Setting Range
0.0 to 110.0%
Default
100.0%
Parameter Name
Frequency Reference Lower Limit
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0.0 to 110.0%
Parameter Details
Default
0.0%
211
Operating
range
No.
d2-03
Parameter Name
Master Speed Reference Lower Limit
Setting Range
0.0 to 110.0%
Default
0.0%
Parameter Name
d3-01
Jump Frequency 1
Setting Range
0.0 to 400.0
Hz <1>
Default
0.0 Hz <1>
d3-02
Jump Frequency 2
0.0 Hz <1>
d3-03
Jump Frequency 3
0.0 Hz <1>
d3-04
1.0 Hz <1>
<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage instead of in Hz.
Figure 5.43 shows the relationship between the Jump frequency and the output frequency.
212
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Frequency
reference
decreases
Frequency
reference
increases
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Frequency 3
d3-03
Jump
Frequency 2
d3-02
Jump
Frequency 1
d3-01
Frequency
reference
No.
d4-01
Parameter Name
Frequency Reference Hold Function Selection
Setting Range
0, 1
Default
0
Acceleration hold
The hold value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off. The active
frequency reference will be the value the drive uses when it restarts.
Up/Down
The frequency reference value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off.
The drive will start from 0 Hz when it is restarted.
Up/Down 2
The frequency bias is not saved when the Stop command is entered, or 5 s after the Up/Down 2 command has been released.
The Up/Down 2 function will start with a bias of 0% when the drive is restarted.
Setting 1: Enabled
Acceleration hold
The last hold value will be saved when the Run command or the drive power is switched off and the drive will use the saved
value as the frequency reference when it restarts. Make sure to continuously enable the multi-function input terminal set for
Accel/decel ramp hold (H1-oo = A) or the hold value will be cleared when the power is switched on.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
213
Parameter Details
Determines whether the frequency reference or the frequency bias (Up/Down 2) value is saved when the Stop command is
entered or the power supply is shut down. This parameter is effective when either of the digital input functions listed below
are used:
Accel/decel ramp hold function (H1-oo= A)
Up/Down function (H1-oo = 10 and 11)
Up/Down 2 function (H1-oo = 75 and 76)
Power supply
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Frequency reference
Output frequency
d4-01 = 1
d4-01 = 0
Hold
Hold
Up/Down
The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will use
the frequency reference that was saved when it restarts.
Up/Down 2 with frequency reference from digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the Up/Down 2 bias value is
added to the frequency reference and then reset to 0. This new frequency reference is saved and will also be used to restart
the drive after the power is cycled.
Bias is added to frequency
reference and reset to 0
Output
frequency
Frequency
reference
Bias
5s
5s
Up 2 command
Figure 5.45 Up/Down 2 Example with Reference from Digital Operator and d4-01 = 1
Up/Down 2 with frequency reference from input sources other than the digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the bias value will be saved
in parameter d4-06. When restarting after the power is switched off, the drive will add the value saved in d4-06 as a bias to
the frequency reference.
214
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Output
frequency
d4-06 value
Bias
5s
5s
Up 2 command
Figure 5.46 Up/Down 2 Example with Other Reference than Digital Operator and d4-01 = 1
Note: Set the limits for Up/Down 2 properly when using d4-01 = 1 in combination with the Up/Down 2 function. Refer to d4-08: Frequency
Reference Bias Upper Limit (Up/Down 2) on page 217 and Refer to d4-09: Frequency Reference Bias Lower Limit (Up/Down 2) on page
217 for details on the limit settings.
Depending on which function is used, it is possible to clear the saved frequency reference value by:
Releasing the input programmed for Acceleration hold.
Setting an Up or Down command while no Run command is active.
Resetting parameter d4-06 to zero. Refer to d4-06: Frequency Reference Bias (Up/Down 2) on page 216 for details.
Parameter Name
Frequency Reference Bias Step (Up/Down 2)
Setting Range
0.00 to 99.99 Hz
Default
0.00 Hz
Parameter Details
While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased using the accel/decel times determined
by parameter d4-04.
Output
frequency
Bias
Up 2 command
When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for the value set in d4-03. The
frequency reference changes with the accel/decel times determined by parameter d4-04.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
215
Bias
Up 2 command
Parameter Name
Frequency Reference Bias Accel/Decel (Up/Down 2)
Setting Range
0, 1
Default
0
The drive uses accel/decel time 4 set to parameters C1-07 and C1-08.
Parameter Name
Frequency Reference Bias Operation Mode Selection
(Up/Down 2)
Setting Range
Default
0, 1
The bias is reset to 0% when inputs Up 2 and Down 2 are both on or both off. The drive will use the accel/decel time as selected
in d4-04 to accelerate or decelerate to the frequency reference value.
Parameter Name
Frequency Reference Bias (Up/Down 2)
Setting Range
-99.9 to 100.0%
Default
0.0%
The Up/Down 2 function has not been assigned to the multi-function terminals.
The frequency reference source has been changed (including LOCAL/REMOTE or External reference 1/2 switch over by
digital inputs).
216
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Analog Frequency Reference Fluctuation Limit (Up/Down 2)
Setting Range
0.1 to 100.0%
Default
1.0%
No.
d4-08
Parameter Name
Frequency Reference Bias Upper Limit (Up/Down 2)
Setting Range
0.0 to 100.0%
Default
100.0%
No.
d4-09
Parameter Name
Frequency Reference Bias Lower Limit (Up/Down 2)
Setting Range
-99.9 to 0.0%
Default
0.0%
Parameter Name
Up/Down Frequency Reference Limit Selection
Setting Range
0, 1
Parameter Details
Selects how the lower frequency limit is set when using the Up/Down function. Refer to Setting 10, 11: Up/Down
Function on page 251 for details on the Up/Down function in combination with frequency reference limits.
Default
0
The higher value between d2-02 and an analog input programmed for Frequency bias (A1, A2, A3) determines the lower
frequency reference limit.
Note: When using the External Reference 1/2 (H1-oo = 2) to switch between the Up/Down function and an analog input as the reference source,
the analog value becomes the lower reference limit when the Up/Down command is active. Set d4-10 to 1 to make the Up/Down function
independent of the analog input value.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
217
U1-09
C1-oo , C2-oo
Soft
Starter
+
+
1 d5-03
2
L7-oo
Torque
Limits
Internal Torque
Reference
Speed Limiter
Compensated torque
reference
Speed Feedback
Speed Limit Bias d5-05
The externally input torque reference is the target value for the motor output torque. If the motor torque reference and the load
torque are not in balance when in Torque Control, the motor accelerates or decelerates. To prevent operation beyond the speed
limit, compensate the external torque reference value if the motor speed reaches the limit. The compensation value is calculated
using the speed limit, speed feedback, and the speed limit bias.
If an external torque compensation value is input, it is added to the speed limit compensated torque reference value. The value
calculated is limited by the L7-oo settings, and is then used as the internal torque reference, which can be monitored in
U1-09. The L7-oo settings have highest priority. The motor cannot be operated with a higher torque than the L7-oo settings
even if the external torque reference value is increased.
n Setting the Torque Reference, Speed Limit, and Torque Compensation Values
Torque Control Reference Sources
Input Value
Signal Source
Settings
F2-01 = 0
H3-02, H3-06, or H3-10 = 13 <1>
Torque Reference
MEMOBUS Register
0004H
218
Remarks
Match the input terminal signal level settings to
the signal being used. Refer to H3: MultiFunction Analog Inputs on page 269 for details
on adjusting analog input signals.
The F3-oo settings become effective for the
option board input terminals. Match the input
terminal signal level settings to the signal being
used. Refer to H3: Multi-Function Analog
Inputs on page 269 for details on adjusting
analog input signals.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Speed Limit
Torque
Compensation
Signal Source
Settings
Remarks
d5-03 = 1
The speed limit is taken from the input The settings in C1-oo for accel/decel times and
selected as frequency reference source in C2-oo for S-curves are applied to the speed
limit value.
in parameter b1-01 or b1-15. <1>
Parameter d5-04
d5-03 = 2
0005H
register 0005H.
F6-06 = 1
Communication Option Refer to the option card manual for
Card
details about setting the torque
compensation value.
Signal selected as
frequency reference
source
<1> Sets analog input terminals A1, A2, and A3 to supply the speed limit, torque reference, or torque compensation. Setting two analog inputs for the
same function will trigger an oPE error.
The direction of the input values described above depends on the polarity of the Run command and the input value.
Table 5.21 Torque Control Signal Polarity
Forward
Reverse
Example:
The internal torque reference will be positive (forward) with a Forward run command and a positive torque reference signal.
The internal torque reference will be negative (reverse) with a Forward run command and a negative torque reference signal.
When using analog inputs, negative input values can be generated by:
Applying negative voltage input signals.
Using positive analog input signals while setting the analog input bias to negative values to make the input value negative.
When using MEMOBUS/Modbus communication or a communication option card, only positive input values can be set.
Independent of its input source, the polarity of the torque reference signal can be inverted using a digital input that is
programmed for H1-oo = 78. Use this function to input negative torque reference values when using MEMOBUS/Modbus
or a communication option card.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
219
Parameter Details
Run Command
Torque
Reference
Direction
Speed Limit
Direction
Normal
Operation
Direction
Forward
<1>
Negative (Reverse)
Negative (Reverse)
Positive (Forward)
Positive (Forward)
Negative (Reverse)
Positive (Forward)
Negative (Reverse)
Forward
Reverse
Forward
Reverse
Torque
Speed Limit
n
Bias d5-05
Speed Limit
Bias d5-05
Speed Limit
Bias d5-05
Torque
Limit
Speed
Internal
Torque
Reference
Torque
Limit
d5-05
Winder
Speed Torque
Speed Torque
Speed
Torque
n
Internal
Torque
Reference
Internal
Torque
Reference
Torque
Limit
Speed
Limit Bias
d5-05
Torque
Limit
Torque n
Limit
Speed Limit
0
Speed
Torque
Limit
Speed Limit
Bias d5-05
Internal
Torque
Reference
Internal
Torque
Reference
Speed
Limit
Torque
Speed Limit
Bias d5-05
Speed
Limit
Speed
Limit Bias
d5-05
Dn
Torque
Limit
Torque
Torque n
Limit
Speed
Speed
Torque
Limit
Application
Example
Internal
Torque
Reference
Torque
Speed
Limit
Internal
Torque
Reference
Speed
Limit Bias
d5-05
Speed Limit
Bias d5-05
Speed Limit
Speed
Limit
Torque
Speed
Speed
Torque
Limit
Speed Limit
Bias d5-05
Speed
Limit
Internal
Torque
Reference
Torque
Torque n
Limit
<1>
Torque
Torque
Limit
Torque
Limit
Unidirectional
Speed Limit
Bias
(d5-08 = 1)
Forward
Positive (Forward)
Torque
Limit
Bidirectional
Speed Limit
Bias
(d5-08 = 0)
Operating Conditions
Forward
Forward
Speed
Limit
Torque
Limit
Speed
Speed
Limit Bias
d5-05
Torque
Limit
Unwinder
Torque Speed
Torque Speed
Line Direction
Line Direction
Line Direction
Line Direction
<1> The value of delta n in the drawings depends on the ASR setting in parameters C5-oo.
220
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Run command
Operation Mode
Frequency reference
signal or d5-04
ON
OFF
Speed/Torque control
input (H1-oo = 71)
OFF
ON
ON
OFF
Speed Control
Torque Control
Speed Control
Torque Control
Speed Ref.
Speed Limit
Speed Ref.
Speed Limit
Torque Reference
d5-06
Torque Limit
d5-06
Torque Reference
Speed Control
Speed Ref.
Torque Limit
d5-06
Parameter Name
Torque Control Selection
Setting Range
0, 1
Default
0
Setting 0: Disabled
Speed Control will be active. Also use this setting when H1-oo = 71 (Speed/Torque Control Switch).
Setting 1: Enabled
Parameter Name
Torque Reference Delay Time
Setting Range
0 to 1000 ms
Default
0 ms
Parameter Name
Speed Limit Selection
Setting Range
1 or 2
Default
1
The frequency reference value at the active reference source (digital operator, External reference 1 or External reference 2)
will be used as speed limit. Note that in this case all settings for accel/decel times (C1-01 to C1-08) and S-curves (C2-01 to
C2-04) will apply for the speed limit.
Setting 2: d5-04
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
221
Parameter Name
Speed Limit
Setting Range
-120 to 120%
Default
0%
Parameter Name
Speed Limit Bias
Setting Range
0 to 120%
Default
10%
Setting Range
0 to 1000 ms
Default
0 ms
Setting Range
0, 1
Default
1
Parameter Name
Speed/Torque Control Switchover Time
Parameter Name
Unidirectional Speed Limit Bias
Setting 0: Disabled
The speed limit bias is applied in the speed limit direction and the opposite direction.
Setting 1: Enabled
The speed limit bias is applied in the opposite direction of the speed limit only.
Parameter Name
Field Weakening Level
Setting Range
0 to 100%
Default
80%
222
Parameter Name
Field Weakening Frequency Limit
Setting Range
0 to 400.0 Hz
Default
0.0 Hz
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Field Forcing Selection
Setting Range
0, 1
Default
0
Setting 0: Disabled
Setting 1: Enabled
Parameter Name
Field Forcing Limit
Setting Range
100 to 400%
Default
400%
No.
d7-01
d7-02
d7-03
Parameter Name
Offset Frequency 1
Offset Frequency 2
Offset Frequency 3
Setting Range
-100.0 to 100.0%
-100.0 to 100.0%
-100.0 to 100.0%
Default
0%
0%
0%
Multi-function
input (44) = on
Frequency
reference after
soft starter
Parameter Details
Frequency
reference
Multi-function
input (45) = on
Offset Frequency 2 [d7-02]
(Signed)
Multi-function
input (46) = on
Offset Frequency 3 [d7-03]
(Signed)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
223
5.5
E: Motor Parameters
No.
Parameter Name
E1-01
Setting Range
Default
V <1>
230 V <1>
155 to 255
<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
The input voltage setting determines the overvoltage and undervoltage detection levels, the operation levels of the braking
transistor, the KEB function, and the overvoltage suppression function.
(Approximate Values)
Voltage
200 V Class
400 V Class
600 V Class
All settings
190 V
260 V
ov Suppression /
Stall Prevention Level
(L3-17)
375 V
setting 400 V
380 V
500 V
750 V
350 V
475 V
460 V
635 V
750 V
930 V
Uv Detection Level
(L2-05)
Note: The braking transistor operation levels are valid for the drive internal braking transistor. When using an external CDBR braking chopper, refer
to the instruction manual of that unit.
Parameter Name
Setting Range
0 to
F <1>
Default
F
<2>
Choose the V/f pattern that best meets the application demands from the table below. These settings are available only in
V/f Control modes. Set the correct value to E1-03. Parameters E1-04 to E1-13 can only be monitored, not changed.
Note: 1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.
Table 5.23 Predefined V/f Patterns
Setting
0
1
2
3
224
Specification
50 Hz
60 Hz
60 Hz (with 50 Hz base)
72 Hz (with 60 Hz base)
Characteristic
Application
Constant torque
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Specification
50 Hz, Heavy Duty 2
50 Hz, Heavy Duty 1
50 Hz, Heavy Duty 1
50 Hz, Heavy Duty 2
50 Hz, mid starting torque
50 Hz, high starting torque
60 Hz, mid starting torque
60 Hz, high starting torque
90 Hz (with 60 Hz base)
120 Hz (with 60 Hz base)
180 Hz (with 60 Hz base)
Application
Variable torque
60 Hz
<1>
Characteristic
Constant output
Constant torque
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are the same as those of setting 1.
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V drives.
Table 5.24 Constant Torque Characteristics, Settings 0 to 3
60 Hz
Setting = 2
200
Voltage (V)
Voltage (V)
Setting = 1
15
15
9
Setting = 3
72 Hz
200
15
15
0 1.5 3
60
Frequency (Hz)
0 1.3 2.5
50
Frequency (Hz)
60 Hz
200
Voltage (V)
50 Hz
200
Voltage (V)
Setting = 0
0 1.5 3
50 60
Frequency (Hz)
0 1.5 3
60 72
Frequency (Hz)
Setting = 5
Voltage (V)
Voltage (V)
50 Hz
Setting = 6
35
50
9
Setting = 7
35
0 1.5
60 Hz
200
0 1.3
25
50
Frequency (Hz)
0 1.3
25
50
Frequency (Hz)
60 Hz
200
200
Voltage (V)
50 Hz
200
Voltage (V)
Setting = 4
Parameter Details
50
9
30
60
Frequency (Hz)
0 1.5
30
60
Frequency (Hz)
Setting = 9
11
0 1.3 2.5
50
Frequency (Hz)
Voltage (V)
Voltage (V)
19
50 Hz
Setting = A
24
13
0 1.3 2.5
50
Frequency (Hz)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
60 Hz
200
200
19
11
0 1.5 3
60
Frequency (Hz)
Setting = B
60 Hz
200
Voltage (V)
50 Hz
200
Voltage (V)
Setting = 8
24
15
0 1.5 3
60
Frequency (Hz)
225
Setting = D
Voltage (V)
Voltage (V)
120 Hz
Setting = E
15
15
Setting = F
17.3
10.2
0 1.5 3
60
Frequency (Hz)
0 1.5 3
60 180
Frequency (Hz)
0 1.5 3
60 120
Frequency (Hz)
60 Hz
230
15
0 1.5 3
60 90
Frequency (Hz)
180 Hz
200
200
Voltage (V)
90 Hz
200
Voltage (V)
Setting = C
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V class drives.
Table 5.28 Rated Torque Characteristics, Settings 0 to 3
60 Hz
200
Voltage (V)
200
Voltage (V)
Setting = 1
14
Setting = 2
60 Hz
14
Setting = 3
72 Hz
200
200
Voltage (V)
50 Hz
Voltage (V)
Setting = 0
14
14
0 1.3 2.5
50
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
0 1.5 3
50 60
Frequency (Hz)
0 1.5 3
60 72
Frequency (Hz)
Setting = 5
Voltage (V)
Voltage (V)
50 Hz
200
200
35
Setting = 7
6
0 1.5
60 Hz
200
35
0 1.3
25
50
Frequency (Hz)
0 1.3
25
50
Frequency (Hz)
60 Hz
200
50
Setting = 6
Voltage (V)
50 Hz
Voltage (V)
Setting = 4
30
60
Frequency (Hz)
50
7
0 1.5
30
60
Frequency (Hz)
Setting = 9
50 Hz
200
Voltage (V)
Voltage (V)
200
18
9
Setting = A
23
11
Setting = B
60 Hz
200
18
9
0 1.3 2.5
50
Frequency (Hz)
0 1.3 2.5
50
Frequency (Hz)
60 Hz
200
Voltage (V)
50 Hz
Voltage (V)
Setting = 8
0 1.5 3
60
Frequency (Hz)
23
13
60
0 1.5 3
Frequency (Hz)
226
14
120 Hz
200
Setting = E
180 Hz
Setting = F
200
14
14
0 1.5 3
60 90
Frequency (Hz)
0 1.5 3
60 120
Frequency (Hz)
0 1.5 3
60 180
Frequency (Hz)
60 Hz
230
Voltage (V)
Voltage (V)
200
Setting = D
Voltage (V)
90 Hz
Voltage (V)
Setting = C
16.1
8.1
0 1.5 3
60
Frequency (Hz)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V class drives.
Table 5.32 Rated Torque Characteristics, Settings 0 to 3
200
Setting = 1
60 Hz
Voltage (V)
Voltage (V)
Setting = 2
60 Hz
200
200
Setting = 3
72 Hz
200
Voltage (V)
50 Hz
Voltage (V)
Setting = 0
12
12
12
12
0 1.3 2.5
50
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
0 1.5 3
50 60
Frequency (Hz)
0 1.5 3
60 72
Frequency (Hz)
Setting = 5
Voltage (V)
Voltage (V)
50 Hz
35
Setting = 6
50
6
Setting = 7
60 Hz
200
35
50
6
5
0 1.5
30
60
Frequency (Hz)
0 1.3
25
50
Frequency (Hz)
0 1.3
25
50
Frequency (Hz)
60 Hz
200
200
Voltage (V)
50 Hz
200
Voltage (V)
Setting = 4
0 1.5
30
60
Frequency (Hz)
Setting = 9
Voltage (V)
Voltage (V)
50 Hz
Setting = A
15
20
9
Setting = B
60 Hz
200
15
20
11
7
0 1.5 3
60
Frequency (Hz)
0 1.3 2.5
50
Frequency (Hz)
0 1.3 2.5
50
Frequency (Hz)
60 Hz
200
200
Voltage (V)
50 Hz
200
Voltage (V)
Setting = 8
0 1.5 3
60
Frequency (Hz)
120 Hz
200
12
Setting = E
180 Hz
Setting = F
60 Hz
230
200
Voltage (V)
Voltage (V)
12
Setting = D
Voltage (V)
90 Hz
200
Voltage (V)
Setting = C
Parameter Details
12
0 1.5 3
60 90
Frequency (Hz)
0 1.5 3
60 120
Frequency (Hz)
0 1.5 3
60 180
Frequency (Hz)
13.8
6.9
0 1.5 3
60
Frequency (Hz)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When initialized, the default values for parameters E1-04 to E1-13 will be equal to Predefined V/f pattern 1.
Parameter Name
Setting Range
Default
E1-04
40.0 to 400.0 Hz
<1> <2>
E1-05
Maximum Voltage
<1>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
227
<1>
<2>
<3>
<4>
<5>
No.
Parameter Name
Setting Range
Default
E1-06
Base Frequency
0.0 to [E1-04]
<1> <2>
E1-07
0.0 to [E1-04]
<1>
E1-08
E1-09
E1-10
E1-11
0.0 to 255.0 V
<3>
0.0 to [E1-04]
0.0 to 255.0 V
<1>
<1> <2>
<3>
0.0 to [E1-04]
E1-12
0.0 to 255.0 V
<3>
E1-13
Base Voltage
0.0 to 255.0 V
<3>
<1>
0.0 Hz <5>
0.0 V
<4> <5>
0.0 V
<4>
E1-08
E1-10
E1-09
The following condition must be true when setting up the V/f pattern: E1-09 E1-07 < E1-06 E1-11 E1-04
To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
Only use E1-11, E1-12, and E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.
Parameter Name
E2-01
Setting Range
10% to 200% of the drive
rated current
Default
Determined by
C6-01 and o2-04
Note: 1. The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal
place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW. Refer to Power Ratings on page 455.
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly to
prevent this error.
228
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Setting Range
E2-02
0.00 to 20.00 Hz
Default
Determined by
C6-01 and o2-04
If Auto-Tuning cannot be performed, calculate the motor rated slip using the information written on the motor nameplate and
the formula below:
E2-02 = f - (n p)/120
(f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)
Parameter Name
E2-03
Setting Range
0 to [E2-01]
(unit: 0.01 A)
Default
Determined by
C6-01 and o2-04
Note: The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place
(0.1 A) if the maximum applicable motor capacity is higher than 11 kW. Refer to Power Ratings on page 455.
Parameter Name
Number of Motor Poles
Setting Range
2 to 48
Default
4
Sets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is automatically
calculated. Enter this value as line-to-line and not for each motor phase.
If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it manually.
When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:
E-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75 C.
B-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75 C.
F-type insulation: Multiply 0.87 times the resistance value () listed on the test report at 115 C.
No.
Parameter Name
Setting Range
E2-05
Default
Determined by
C6-01 and o2-04
Parameter Name
Setting Range
E2-06
0.0 to 40.0%
Default
Determined by
C6-01 and o2-04
Parameter Name
Motor Iron-Core Saturation Coefficient 1
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0.00 to 0.50
Default
0.50
229
Parameter Details
Parameter Name
Motor Iron-Core Saturation Coefficient 2
Setting Range
E2-07 to 0.75
Default
0.75
Parameter Name
Motor Mechanical Loss
Setting Range
0.0 to 10.0%
Default
0.0%
Default
Determined by
C6-01 and o2-04
Parameter Name
Setting Range
E2-10
0 to 65535 W
Parameter Name
Setting Range
E2-11
0.00 to 650.00 kW
Default
Determined by
o2-04
Note: The display resolution depends on the rated output power of the drive after setting the Drive Duty in parameter C6-01. Drive models CIMRAo2A0004 to 4A0515 display this value in units of 0.01 kW (two decimal places). Drive models CIMR-Ao4A0675 to 4A1200 display this
value in units of 0.1 kW (one decimal place). Refer to Nameplate on page 35 for details.
Enter the motor rated current listed on the nameplate of the motor to E2-01.
Set the Motor Rated Slip
Calculate the motor rated slip using the base speed listed on the motor nameplate. Refer to the formula below, then enter that
value to E2-02.
Motor rated slip = rated frequency [Hz] base speed [r/min] (no. of motor poles) / 120
Set the No-Load Current
Enter the no-load current at rated frequency and rated voltage to E2-03. This information is not usually listed on the nameplate.
Contact the motor manufacturer if the data cannot be found.
The default setting of the no-load current is for performance with a 4-pole Yaskawa motor.
Set the Number of Motor Poles
Only required in V/f Control with PG and Closed Loop Vector Control. Enter the number of motor poles as indicated on motor
nameplate.
230
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
E2-05 is normally set during Auto-Tuning. If Auto-Tuning cannot be performed, contact the motor manufacturer to determine
the correct resistance between motor lines. The motor test report can also be used to calculate this value using the formulas
below:
E-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75 C.
B-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75 C.
F-type insulation: Multiply 0.87 times the resistance value () listed on the test report at 115 C.
Set the Motor Leakage Inductance
The motor leakage inductance set to E2-06 determines the amount of voltage drop relative to the motor rated voltage. Enter
this value for motors with a low degree of inductance, such as high-speed motors. This information is usually not listed on the
motor nameplate. Contact the motor manufacturer if the data cannot be found.
Set the Motor Iron-Core Saturation Coefficient 1, 2
Only required in Closed Loop Vector Control. The drive compensates for the degree of mechanical loss with torque
compensation. Although E2-09 rarely needs to be changed, adjustment may be necessary in the following circumstances:
When there is a large amount of torque loss due to motor bearing friction.
When there is a large amount of torque loss in a fan or pump application.
Set the Motor Iron Loss for Torque Compensation
Only required when using V/f Control. Enter this value in watts to E2-10. The drive uses this setting to improve the precision
of torque compensation.
Setting Range
0 to 3
Default
0
Parameter Details
No.
E3-01
Note: L1-01 determines protection from motor overload (oL1) in motor 2 and motor 1.
n E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in Figure 5.53.
Note: Certain E3-oo parameters might not be visible depending on the control mode. Refer to Parameter List on page 475 for details.
No.
Parameter Name
Setting Range
Default
E3-04
40.0 to 400.0 Hz
<2>
E3-05
<1> <2>
E3-06
0.0 to [E3-04]
<2>
E3-07
0.0 to [E3-04]
<2>
E3-08
<1> <2>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
231
<1>
<2>
<3>
<4>
No.
Parameter Name
Setting Range
Default
E3-09
0.0 to [E3-04]
<2>
E3-10
<1> <2>
E3-11
0.0 to [E3-04]
0.0 Hz <4>
E3-12
E3-13
0.0 V
<3> <4>
0.0 V
<3>
Values shown here are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
Default setting is determined by the control mode selected for motor 2 (E3-01).
The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
Parameter ignored when E3-11 and E3-12 are set to 0.0.
Output (V)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
The following conditions must be true when setting up the V/f pattern: E3-09 E3-07 < E3-06 3-11 E3-04
To make the V/f pattern a straight line at a frequency lower than E3-07, set E3-09 equal to E3-07. In this case the E3-08 setting is disregarded.
Parameters E3-04 through E3-13 are reset to their default values when the drive is initialized.
Only use E3-11, E3-12, and E3-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.
Parameter Name
E4-01
Setting Range
10 to 200% of the drive rated
current.
Default
Determined by
C6-01 and o2-04
Note: 1. The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal
place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW. Refer to Power Ratings on page 455.
2. An oPE02 error will occur if the motor rated current in E4-01 is set lower than the motor no-load current in E4-03. Set E4-03 correctly to
prevent this error.
232
No.
Parameter Name
Setting Range
E4-02
0.00 to 20.00 Hz
Default
Determined by
C6-01 and o2-04
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Setting Range
E4-03
0 to [E4-01]
Default
Determined by
C6-01 and o2-04
Note: The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place
(0.1 A) if the maximum applicable motor capacity is higher than 11 kW. Refer to Power Ratings on page 455.
Parameter Name
Motor 2 Motor Poles
Setting Range
2 to 48
Default
4
Parameter Name
Setting Range
E4-05
Default
Determined by
C6-01 and o2-04
Parameter Name
Setting Range
E4-06
0.0 to 40.0%
Default
Determined by
C6-01 and o2-04
Parameter Name
Motor 2 Motor Iron-Core Saturation Coefficient 1
Setting Range
0.00 to 0.50
Default
0.50
Parameter Name
Motor 2 Motor Iron-Core Saturation Coefficient 2
Setting Range
[E4-07] to 0.75
Default
0.75
233
Parameter Details
Sets the voltage drop due to motor leakage inductance as a percentage of rated voltage of motor 2. This value is automatically
set during Auto-Tuning (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
Parameter Name
Motor 2 Mechanical Loss
Setting Range
0.0 to 10.0%
Default
0.0%
Default
Determined by
C6-01 and o2-04
Parameter Name
Setting Range
E4-10
0 to 65535 W
Parameter Name
Setting Range
E4-11
0.00 to 650.00 kW
Default
Determined by
o2-04
Note: The display resolution depends on the rated output power of the drive after setting the Drive Duty in parameter C6-01. Drive models CIMRAo2A0004 to 4A0515 display this value in units of 0.01 kW (two decimal places). Drive models CIMR-Ao4A0675 to 4A1200 display this
value in units of 0.1 kW (one decimal place). Refer to Nameplate on page 35 for details.
When using Yaskawa motors, set the motor code for the PM motor being used. The drive automatically sets several parameters
to appropriate values depending on the motor code.
Setting parameter E5-01 to FFFF allows the motor data to be manually set using the E5-oo parameters.
No.
Parameter Name
Setting Range
E5-01
0000 to FFFF
Note: 1.
2.
3.
4.
5.
Default
Determined by
A1-02, C6-01 and
o2-04
E5-oo parameters are not reset when the drive is initialized using parameter A1-03.
When E5-01 is set to a value other than FFFF, the drive will not initialize using parameter A1-03
Changing E5-01 to FFFF from value other than FFFF will not change the values of parameters E5-02 through E5-24.
Set E5-01 to FFFF when using a motor other than a Yaskawa SMRA, SSR1, or SST4 series.
Default settings are:
OLV/PM, AOLV/PM: Yaskawa SSR1 Series (1750 r/min)
CLV/PM: Yaskawa SSR4 Series (1750 r/min)
234
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors or by
entering the motor code to E5-01.
No.
Parameter Name
Setting Range
E5-02
0.10 to 650.00 kW
Default
Determined by
E5-01
Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.
No.
Parameter Name
E5-03
Setting Range
10 to 200% of drive rated
current
Default
Determined by
E5-01
Note: The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place
(0.1 A) if the maximum applicable motor capacity is higher than 11 kW. Refer to Power Ratings on page 455.
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Sets the number of motor poles. Automatically set when the value is entered to T2-08 during Auto-Tuning.
No.
Parameter Name
Setting Range
E5-04
2 to 48
Default
Determined by
E5-01
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Set the resistance for one motor phase. Do not enter the line-to-line resistance into E5-05 when measuring the resistance
manually.
No.
Parameter Name
Setting Range
E5-05
0.000 to 65.000
Default
Determined by
E5-01
Sets the d-Axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.
No.
Parameter Name
Setting Range
E5-06
0.00 to 300.00 mH
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
Default
Determined by
E5-01
235
Sets the q-Axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.
No.
Parameter Name
Setting Range
E5-07
0.00 to 600.00 mH
Default
Determined by
E5-01
Sets the induced peak voltage per phase in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an IPM
motor with derated torque (SSR1 series or equivalent) or an IPM motor with constant torque (SST4 series or equivalent).
Set the voltage constant with E5-09 or E5-24 when E5-01 is set to FFFF. This parameter is set during Auto-Tuning for PM
motors.
No.
Parameter Name
Setting Range
E5-09
Default
Determined by
E5-01
Note: Set E5-24 to 0 when setting E5-09. However, setting both E5-09 and E5-24 to 0 will trigger an alarm. An alarm will also be triggered if neither
E5-09 nor E5-24 are set to 0. When E5-01 is set to FFFF, then E5-09 = 0.0.
Sets the offset between the rotor magnetic axis and the Z Pulse of the connected encoder. This parameter is set during AutoTuning for PM motors and during Z Pulse Tuning.
No.
E5-11
Parameter Name
Encoder Z Pulse Offset
Setting Range
-180.0 to 180.0 deg
Default
0.0 deg
Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter when using an
SPM Motor (SMRA Series or equivalent).
When E5-01 is set to FFFF, use either E5-09 or E5-24 for setting the voltage constant. This parameter is set during Parameter
Auto-Tuning for PM motors.
No.
Parameter Name
Setting Range
E5-24
Default
Determined by
E5-01
Note: Set E5-24 to 0.0 when setting E5-09. However, setting both E5-09 and E5-24 to 0.0 will trigger an alarm. An alarm will also be triggered if
neither E5-09 nor E5-24 are set to 0.0. When E5-01 is set to FFFF, then E5-09 should be set to 0.0.
236
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.6
F: Option Settings
Port
Parameters
CN5-C and CN5-B (common) F1-02 to F1-04, F1-08 to F1-11, F1-14
CN5-C only
F1-01, F1-05, F1-06, F1-12, F1-13, F1-18 to F1-21
CN5-B only
F1-31 to F1-37
Parameter Name
Option Port
F1-01
CN5-C
F1-31
CN5-B
Setting Range
ppr <1>
0 to 60000
0 to 60000 ppr
Default
1024 ppr
1024 ppr
Parameter Name
Operation Selection at PG Open Circuit (PGo)
PG Open-Circuit Detection Time
Option Port
CN5-B, CN5-C
CN5-B, CN5-C
Setting Range
0 to 3
0.0 to 10.0 s
Default
1
2.0 s
Parameter Details
n F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time
An oS fault is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set in F1-09. Set the
stopping method for an oS fault in parameter F1-03.
No.
F1-03
F1-08
F1-09
Parameter Name
Operation Selection at Overspeed (oS)
Overspeed Detection Level
Overspeed Detection Delay Time
Option Port
CN5-B, CN5-C
CN5-B, CN5-C
CN5-B, CN5-C
Setting Range
0 to 3
0 to 120%
0.0 to 2.0 s
Default
1
115%
Determined by A1-02
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
237
n F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time
A speed deviation error (dEv) is triggered when the difference between the frequency reference and the speed feedback exceeds
the value set in F1-10 for longer than the time set in F1-1. The stopping method when a speed deviation fault occurs can be
selected in parameter F1-04.
No.
F1-04
F1-10
F1-11
Parameter Name
Operation Selection at Deviation (dEv)
Excessive Speed Deviation Detection Level
Excessive Speed Deviation Detection Delay Time
Option Port
CN5-B, CN5-C
CN5-B, CN5-C
CN5-B, CN5-C
Setting Range
0 to 3
0 to 50%
0.0 to 10.0 s
Default
3
10%
0.5 s
Parameter Name
PG 1 Rotation Selection
PG 2 Rotation Selection
Option Port
CN5-C
CN5-B
Setting Range
0, 1
0, 1
Default
0
0
(1 + n)
m
Example: Set F1-06 to 032 for a ratio of 1/32 between the PG card pulse input and output.
No.
Parameter Name
Option Port
Setting Range
Default
1
32
F1-06
CN5-C
1 to 132 (1 to )
F1-35
CN5-B
1 to 132 (1 to 32 )
238
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
PG 1 Gear Teeth 1
PG 1 Gear Teeth 2
PG 2 Gear Teeth 1
PG 2 Gear Teeth 2
Option Port
CN5-C
CN5-C
CN5-B
CN5-B
Setting Range
0 to 1000
0 to 1000
0 to 1000
0 to 1000
Default
0
0
0
0
Note: A gear ratio of 1 will be used if any of these parameters are set to 0.
Sets the number of times the drive will detect a dv3 situation before triggering a dv3 fault. The drive detects a dv3 condition
when the torque reference and speed reference are in opposite directions while the difference between the actual motor speed
and the speed reference is greater than 30%. Setting F1-18 to 0 disables dv3 detection.
No.
F1-18
Parameter Name
dv3 Detection Selection
Option Port
CN5-B, CN5-C
Setting Range
0 to 10
Default
10
Note: A common cause for a dv3 fault is the incorrect setting of E5-11. Make sure to enter the correct Z Pulse offset to E5-11.
Sets the number of pulses necessary to trigger a dv4 fault when there is a motor speed deviation opposite to the frequency
reference. Setting F1-19 to 0 disables dv4 detection.
No.
F1-19
Parameter Name
dv4 Detection Selection
Option Port
CN5-B, CN5-C
Setting Range
0 to 5000
Default
128
Note: 1. A common cause for a dv4 fault is the incorrect setting of E5-11. Make sure to enter the correct Z-pulse offset to E5-11.
2. Set F1-19 to 0 for applications where the direction of the load is the opposite of the speed reference.
Option Port
CN5-C
CN5-B
Setting Range
0, 1
0, 1
Default
1
1
Parameter Details
No.
F1-20
F1-36
Setting 0: Disabled
Setting 1: Enabled
Parameter Name
PG 1 Signal Selection
PG 2 Signal Selection
Option Port
CN5-C
CN5-B
Setting Range
0, 1
0, 1
Default
0
0
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
239
No.
F1-30
Parameter Name
PG Option Card Port for Motor 2 Selection
Setting Range
0, 1
Default
1
Setting 0: CN5-C
Setting 1: CN5-B
Parameter Name
Analog Input Option Card Operation Selection
Setting Range
0, 1
Default
0
Setting 0: Separate functions for each terminal (V1, V2, V3 replace terminals A1, A2, A3)
Use the H3-oo parameters described in H3-03, H3-04: Terminal A1 Gain and Bias Settings on page 270 to set the functions
and gain and bias levels for an analog reference supplied by AI-A3.
Note: Setting option card terminals for separate input functions (F2-01 = 0) while b1-01 = 3 will cause an oPE05 error.
This setting adds all three input signals on the AI-A3 option card to create the frequency reference. Set b1-01 to 3 when the
option card is the source of the frequency reference for the drive. Set the gain and bias settings for the frequency reference
supplied from AI-A3 with F2-02 and F2-03.
Parameter Name
Analog Input Option Card Gain
Analog Input Option Card Bias
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Default
100.0%
0.0%
Parameter Name
Digital Input Option Card Input Selection
Setting Range
0 to 7
Default
0
240
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Digital Input Option DI-A3 Data Length Selection
Setting Range
0 to 2
Default
2
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
Setting Range
000 to 999
000 to 999
Default
102
103
n F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set as
a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is limited to
10 V.
No.
F4-02
F4-04
F4-05
F4-06
Parameter Name
Terminal V1 Monitor Gain
Terminal V2 Monitor Gain
Terminal V1 Monitor Bias
Terminal V2 Monitor Bias
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
Default
100.0%
50.0%
0.0%
0.0%
When viewing the values set to F4-02 or F4-05 on the digital operator, a voltage equal to 100% of the parameter being viewed
(including current gain and bias settings) will be output from terminal V1 or V2. When viewing the value set to F4-05 or
F4-06, terminal V1 or V2 will output a voltage equal to 0% of the parameter being viewed (including current gain and bias
settings).
Example 1: F4-02 = 0%, F4-02 = 80%. When the parameter setting display for F4-02 is accessed using the digital operator,
terminal V1 will output a voltage of 8 V, even when the drive is stopped.
Example 2: F4-03 = 5%. When the parameter setting display for F4-03 is accessed using the digital operator, terminal V1 will
output a voltage of 0.5 V, even when the drive is stopped.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
No.
F4-01
F4-03
241
Parameter Name
Terminal V1 Signal Level
Terminal V2 Signal Level
Setting Range
0, 1
0, 1
Default
0
0
Setting 0: 0 to 10 V
Setting 1: -10 to 10 V
n F5-01 through F5-08: Digital Output Option Card Terminal Function Selection
When F5-09 = 2, the parameters listed in the table below assign functions to the output terminals on the option card.
No.
F5-01
F5-02
F5-03
F5-04
F5-05
F5-06
F5-07
F5-08
Name
Terminal P1-PC Output Selection
Terminal P2-PC Output Selection
Terminal P3-PC Output Selection
Terminal P4-PC Output Selection
Terminal P5-PC Output Selection
Terminal P6-PC Output Selection
Terminal M1-M2 Output Selection
Terminal M3-M4 Output Selection
Setting Range
0 to 192
0 to 192
0 to 192
0 to 192
0 to 192
0 to 192
0 to 192
0 to 192
Default
2: Speed agree
4: Frequency detection 1
6: Drive ready
37: During frequency output
F: Not used
F: Not used
0: During run
1: Zero speed
Parameter Name
DO-A3 Output Mode Selection
Setting Range
0 to 2
Default
0
Note: Refer to TOBP C730600 41 Yaskawa AC Drive-Option DO-A3 Installation Manual for more details on F5-09 settings.
242
CC-Link
Communication Protocol
MECHATROLINK-II
PROFIBUS-DP
CANopen
DeviceNet
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
CC-Link
F6-50 to F6-63
Communication Protocol
MECHATROLINK-II
PROFIBUS-DP
CANopen
DeviceNet
O
Parameter Name
Communications Error Operation Selection
Setting Range
0 to 3
Default
1
Parameter Name
External Fault from Comm. Option Detection Selection
Setting Range
0, 1
Default
0
Parameter Name
External Fault from Comm. Option Operation Selection
Setting Range
0 to 3
Default
1
Selects whether torque reference and torque limit values are assigned to the drive from the network.
No.
F6-06
Parameter Name
Torque Reference/Torque Limit Selection from Comm. Option
Setting Range
0, 1
Default
0
Setting Range
0, 1
Default
0
Setting 0: Enabled
Setting 1: Disabled
Parameter Name
NetRef/ComRef Function Selection
Multi-step speed input frequency references are disabled when the NetRef command is selected.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
243
Multi-step speed inputs are still active and can override the frequency reference from the communications option even when
the NetRef command is selected.
Parameter Name
Reset Communication Parameters
Setting Range
0, 1
Default
0
u CC-Link Parameters
Parameters F6-04, F6-10, F6-11, and F6-14 set the drive to operate on a CC-Link network.
Parameter Name
bUS Error Detection Time
Setting Range
0.0 to 5.0 s
Default
2.0 s
Setting Range
0 to 64
Default
0
Setting Range
0 to 4
Default
0
Parameter Name
CC-Link Node Address
Parameter Name
CC-Link Communication Speed
Settings:
F6-11
0
1
2
Communication Speed
156 kbps
625 kbps
2.5 Mbps
F6-11
3
4
Communication Speed
5 Mbps
10 Mbps
Parameter Name
CC-Link bUS Error Auto Reset
Setting Range
0, 1
Default
0
244
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set the drive to run on a PROFIBUS-DP network.
Parameter Name
PROFIBUS-DP Node Address
Setting Range
0 to 125
Default
0
Setting Range
0, 1
Default
0
Setting Range
0, 1
Default
0
Setting Range
0 to 126
Default
0
Parameter Name
PROFIBUS-DP Clear Mode Selection
Setting 0: Reset
Returns the drive status to the state prior to receiving the command.
Parameter Name
PROFIBUS-DP Data Format Selection
u CANopen Parameters
Parameters F6-35 and F6-36 set the drive to operate on a CANopen network.
Parameter Details
Parameter Name
CANopen Node ID Selection
Parameter Name
CANopen Communication Speed
Setting Range
0 to 8
Default
6
Settings:
F6-36
0
1
2
3
4
Communication Speed
Auto detection
10 kbps
20 kbps
50 kbps
125 kbps
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
F6-36
5
6
7
8
Communication Speed
250 kbps
500 kbps
800 kbps
1 Mbps
245
u DeviceNet Parameters
Parameters F6-50 through F6-63 set the drive to operate on a DeviceNet network.
Parameter Name
DeviceNet MAC Address
Setting Range
0 to 64
Default
64
Parameter Name
DeviceNet Communication Speed
Setting Range
0 to 4
Default
4
Settings:
F6-51
0
1
2
Communication Speed
125 kbps
250 kbps
500 kbps
F6-51
3
4
Communication Speed
Adjustable from Network
Auto detection
Parameter Name
DeviceNet PCA Setting
Setting Range
0 to 255
Default
21
Setting Range
0 to 255
Default
71
Parameter Name
DeviceNet PPA Setting
Parameter Name
DeviceNet Idle Mode Fault Detection
Setting Range
0, 1
Default
0
Setting 0: Enabled
Setting 1: Disabled, no fault detection
Parameter Name
DeviceNet Baud Rate Monitor
Setting Range
0 to 2 (read only)
Default
0
Settings:
F6-55
0
1
246
Communication Speed
125 kbps
250 kbps
F6-55
2
Communication Speed
500 kbps
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
DeviceNet Speed Scaling
DeviceNet Current Scaling
DeviceNet Torque Scaling
DeviceNet Power Scaling
DeviceNet Voltage Scaling
DeviceNet Time Scaling
Setting Range
-15 to 15
-15 to 15
-15 to 15
-15 to 15
-15 to 15
-15 to 15
Default
0
0
0
0
0
0
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value 2Scaling
Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive
Object 2AH, Instance 1, Attribute 7 would be 500 26 = 32000.
Parameter Name
DeviceNet Heartbeat Interval
Setting Range
0 to 10
Default
0
Setting Range
0 to 63 (read only)
Default
0
Parameter Name
DeviceNet Network MAC ID
Parameter Details
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
247
5.7
H: Terminal Functions
Setting
Range
Parameter Name
Default
H1-01
1 to 9F
H1-02
1 to 9F
H1-03
H1-04
0 to 9F
0 to 9F
H1-05
0 to 9F
H1-06
0 to 9F
H1-07
0 to 9F
H1-08
0 to 9F
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Table 5.37 Multi-Function Digital Input Terminal Settings
Setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
10
11
12
13
14
15
16
17
18
19
1A
1B
1E
248
Function
3-Wire Sequence
LOCAL/REMOTE Selection
External Reference 1/2 Selection
Multi-Step Speed Reference 1
Multi-Step Speed Reference 2
Multi-Step Speed Reference 3
Jog reference Selection
Accel/Decel Time Selection 1
Baseblock Command (N.O.)
Baseblock Command (N.C.)
Accel/Decel Ramp Hold
Drive Overheat Alarm (oH2)
Analog Terminal Input Selection
PG Encoder Disable
ASR integral reset
Through Mode
Up Command
Down Command
Forward Jog
Reverse Jog
Fault Reset
Fast Stop (N.O.)
Motor 2 Selection
Fast Stop (N.C.)
Timer Function Input
PID Disable
Accel/Decel Time Selection 2
Program Lockout
Reference Sample Hold
Page
249
249
250
250
250
250
250
250
251
251
251
251
251
251
252
252
252
253
252
253
254
254
254
254
Setting
20 to 2F
30
31
32
34
35
40
41
42
43
44
45
46
47
60
61
62
63
65
66
67
68
6A
71
72
75
76
77
78
Function
External Fault
PID Integral Reset
PID Integral Hold
Multi-Step Speed Reference 4
PID Soft Starter Cancel
PID Input Level Selection
Forward Run Command (2-Wire sequence)
Reverse Run Command (2-Wire sequence)
Run Command (2-Wire sequence 2)
FWD/REV Command (2-Wire sequence 2)
Offset Frequency 1
Offset Frequency 2
Offset Frequency 3
Node Setup
DC Injection Braking Command
External Speed Search Command 1
External Speed Search Command 2
Field Weakening
KEB Ride-Thru 1 (N.C.)
KEB Ride-Thru 1 (N.O.)
Communications Test Mode
High Slip Braking
Drive Enabled
Speed/Torque Control Switch
Zero Servo
Up 2 Command
Down 2 Command
ASR Gain Switch
External Torque Reference Polarity Inversion
Page
254
255
255
255
255
255
255
256
256
256
256
256
256
256
256
256
257
257
257
257
257
258
258
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Function
KEB Ride-Thru 2 (N.C.)
KEB Ride-Thru 2 (N.O.)
Short Circuit Braking (N.O.)
Short Circuit Braking (N.C.)
Page
Setting
258
7E
258
90 to 97
9F
Function
Forward/Reverse Detection (V/f control with
simple PG)
DriveWorksEZ Digital Input 1 to 8
DriveWorksEZ Disabled
Page
258
259
259
The digital input programmed for 3-Wire control becomes the forward/reverse directional input, S1 becomes the Run command
input, and S2 becomes the Stop command input.
The drive starts the motor when the input S1 set for the Run command closes for longer than 2 ms. The drive stops the operation
when the Stop input S2 releases for 2 ms. When the digital input programmed for a forward/reverse operation is open, the
drive is set for forward operation. When the digital input is closed, the drive is set for reverse operation.
Note: Input the Run and Stop commands via S1 and S2 when selecting a 3-Wire sequence.
Stop Switch
(N.C.)
Run Switch
(N.O.)
DRIVE
S1
S2
S5
SC
Run command
Stop command
OFF (stopped)
Forward/reverse
command
OFF (forward)
ON (reverse)
Motor speed
Stop
Forward
Reverse
Stop
Foward
This setting allows the input terminal to determine if the drive will run in LOCAL mode or REMOTE mode.
Status
Closed
Open
Description
LOCAL: Frequency reference and Run command are input from the digital operator.
REMOTE: Frequency reference and Run command are input from the selected external reference. If a digital input set to H1-oo = 2
is active, they will be read from external reference source 2 (b1-15 and b1-16). In all other cases they will be read from external reference
source 1 (b1-01 and b1-02).
Note: 1. The LO/RE key on the digital operator is disabled when one of the multi-function input terminals is set to for LOCAL/REMOTE.
2. When the drive is set to LOCAL, the LO/RE LED will light.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
249
Parameter Details
TIME
This function switches the Run command and frequency reference source between External reference 1 and 2 if the drive is
in the REMOTE mode.
Status
Open
Closed
Description
External reference 1 is used (defined by parameters b1-01 and b1-02)
External reference 2 is used (defined by parameters b1-15 and b1-16)
Note: Default drive settings do not allow switching between External reference 1 and 2 during run. Refer to b1-07: LOCAL/REMOTE Run
Selection on page 168 if this feature is required by the application.
Switches multi-step speed frequency references d1-01 to d1-08 by digital inputs. Refer to d1: Frequency Reference on page
209 for details.
Setting 6: Jog Reference Selection
The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes. Refer to d1:
Frequency Reference on page 209 for details.
Setting 7: Accel/Decel Time Selection 1
Switches between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04). Refer to C1-01 to C1-08: Accel, Decel
Times 1 to 4 on page 192 for details.
Setting 8, 9: Baseblock Command (N.O., N.C.)
When the drive receives a baseblock command, the output transistors stop switching, the motor coasts to stop, and a bb alarm
flashes on the digital operator to indicate baseblock. When baseblock ends while a Run command is active, the drive performs
Speed Search to restart the motor.
Drive Operation
Input Open
Baseblock (Interrupt output)
Normal operation
Setting 8 (N.C.)
Setting 9 (N.O.)
Input Closed
Normal operation
Baseblock (Interrupt output)
WARNING! Sudden Movement Hazard. When using a mechanical holding brake with the drive in a lifting application, close the brake when
the drive output is cut off by a baseblock command triggered by one of the input terminals. Failure to comply will result in a slipping load
from the motor suddenly coasting when the baseblock command is entered and may cause serious injury or death.
Run command
Baseblock input
Frequency
reference
OFF
ON
ON
Baseblock
release
Output frequency
Output off, motor coasts
When the digital input programmed for the Accel/decel ramp hold function closes, the drive locks (holds) the output frequency.
Acceleration or deceleration resumes when the input is reopened.
250
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Triggers an oH2 alarm when the contact closes. Drive operation is not affected because this is an alarm.
Setting C: Analog Terminal Input Selection (Terminal A1, A2, A3)
When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog
terminals.
Setting D: PG Encoder Disable
When closed, the drive disregards PG feedback from the motor when using V/f Control with PG. When the terminal is reopened,
the drive resumes using PG feedback to control motor speed.
Setting E: ASR Integral Reset
Switches between PI control and P control by resetting the integral value. Integral operation is disabled when the terminal is
closed and the drive uses P control. PI control resumes when the terminal opens.
Setting F: Through Mode
Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function in
the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/
Modbus communications.
Setting 10, 11: Up/Down Function
The Up/Down function allows the frequency reference to be set by two push buttons when one digital input is programmed
as the Up input (H1-oo= 10) to increase the frequency reference and the other digital input is programmed as the Down input
(H1-oo= 11) to decrease the frequency reference.
The Up/Down function takes priority over the frequency references from the digital operator, the analog inputs, and the pulse
input (b1-01 = 0, 1, 4). When using the Up/Down function, references provided by these sources will be disregarded.
The inputs operate as shown in the table below:
Status
Down (11)
Open
Open
Closed
Closed
Drive Operation
Hold current frequency reference
Increase frequency reference
Decrease frequency reference
Hold current frequency reference
Note: 1. An oPE03 alarm occurs when only one of the Up/Down functions is programmed to a digital input.
2. An oPE03 alarm occurs when the Up/Down function is assigned to the terminals and a different digital input is programmed for the Accel/
decel ramp hold function. For more information on alarms, Refer to Drive Alarms, Faults, and Errors on page 342.
3. The Up/Down function can only be used for External reference 1. Consider this when using Up/Down and the external reference switching
command (H1-oo = 2).
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
251
Parameter Details
Up (10)
Open
Closed
Open
Closed
Same
frequency
d4-01 = 1
Lower limit
d4-01 = 0
ON
FWD run/stop
ON
Up command
Frequency
reference
reset
ON
Down command
ON
ON
Power supply
Digital inputs programmed as Forward Jog (H1-oo = 12) and Reverse Jog (H1-oo = 13) will be Jog inputs that do not
require a Run command. Closing the terminal set for Forward Jog input will cause the drive to ramp to the Jog frequency
reference (d1-17) in the forward direction. The Reverse Jog will cause the same action in the reverse direction. The Forward
Jog and Reverse Jog command can be set independently.
Note: The Forward Jog and Reverse Jog commands override all other frequency references. However, if the drive is set to prohibit reverse rotation
(b1-04 = 1), activating Reverse Jog will have no effect. Inputting both the Forward Jog and Reverse Jog are simultaneously for 500 ms or
longer will trigger an alarm will and the drive will ramp to stop.
d1-17
Output
Frequency
d1-17
FJOG
RJOG
ON
ON
When the drive detects a fault condition, the fault output contact closes, the drive output shuts off, and the motor coasts to
stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat). After removing the Run
command, clear the fault either by pressing the RESET key on the digital operator or closing a digital input configured as a
Fault Reset (H1-oo = 14).
Note: Remove the Run command prior to resetting a fault. Fault Reset commands are ignored while the Run command is present.
The Fast Stop function operates similar to an emergency stop input to the drive. If a Fast Stop command is input while the
drive is running, the drive decelerates to a stop in the deceleration time set to C1-09 (Refer to C1-09: Fast Stop Time on page
193). The drive can only be restarted after bringing the drive to a complete stop, turning off the Fast Stop input, and switching
off the Run command.
To trigger the Fast Stop function with an N.O. switch, set H1-oo = 15.
To trigger the Fast Stop function with an N.C. switch, set H1-oo = 17.
Figure 5.60 shows an operation example of Fast Stop.
252
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Fast-Stop
H1= 17
ON
ON
ON
Decelerates at C1-09
Output Frequency
TIME
The drive has the capability to control two induction motors independently. A second motor may be selected using a multifunction digital input as shown in Figure 5.61.
Note: The motor 2 selection function cannot be used with PM motors.
Drive
Motor 1
Motor 2
When switching between motor 1 and motor 2, the parameters used to control those motors also change. Below, Table 5.38
lists the parameters that correspond to each motor:
No.
C1-oo: Acceleration/Deceleration
Time
C3-oo : Motor Slip Compensation
C4-oo: Motor Torque
Compensation
C5-oo: Speed Control (ASR)
E1-oo, E3-oo: V/f Pattern
E2-oo, E4-oo: Motor Parameters
F1-oo (PG Constant)
Note: 1.
2.
3.
4.
Parameter Details
C1-01 to C1-04
C1-05 to C1-08
C3-21 to C3-25
C4-01
C4-07
E1-oo, E2-oo
E3-oo to E4-oo
F1-01 to F1-21
When using 2 motors, the motor overload protection selection (oL1) set to L1-01 applies to both motor 1 and motor 2.
Attempting to switch between motor 1 and motor 2 during run will trigger the rUn alarm.
There is a 500 ms delay when switching between motors equipped with a PG encoder for feedback.
The motor 2 selection function cannot be used with PM motors.
If a digital output is programmed for Motor 2 selection (H1-01, H1-02, or H1-03 = 1C), the motor will be selected when
the output is closed.
Setting 18: Timer Function Input
This setting configures a digital input terminal as the input for the timer function. Use this setting combination with the timer
function output (H2-oo = 12). Refer to b4: Delay Timers on page 177 for details.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
253
Close a digital input to indefinitely disable the PID function. When the input is released, the drive resumes PID operation.
Refer to PID Block Diagram on page 180.
Setting 1A: Accel/Decel Time Selection 2
Selects accel/decel times 1 to 4 in combination with the Accel/decel time selection 1 command. Refer to C1-01 to C1-08:
Accel, Decel Times 1 to 4 on page 192 for details.
Setting 1B: Program Lockout
Parameter values cannot be changed when an input is programmed for Program Lockout and the input is open. It is still possible,
however, to view and monitor parameter settings.
Setting 1E: Reference Sample Hold
This function allows the user to sample an analog frequency reference signal being input to terminal A1, A2, or A3 and hold
the frequency reference at the sampled level. When the Analog Frequency Reference Sample/Hold function is held for at least
100 ms, the drive reads the analog input and changes the frequency reference to the newly sampled speed as illustrated in
Figure 5.62.
When the power is shut off and the sampled analog frequency reference is cleared, the frequency reference is reset to 0.
Frequency
reference
g
alo
na
sig
An
Time
OFF
Referenece
Sample Hold Input
100 ms
ON
100 ms
An oPE03 error will occur when one of the following functions is used simultaneously with the Analog frequency reference
sample/hold command:
Hold accel/decel stop (setting: A)
Up command, Down command (setting: 10, 11)
Offset frequency (setting: 44 to 46)
Up or Down functions (setting: 75, 76)
Setting 20 to 2F: External Fault
The External fault command stops the drive when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to a value between 20 and 2F. The digital
operator will display EFo where o is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal S3, EF3 will be displayed.
Select the value to be set in H1-oo from a combination of any of the following three conditions:
Signal input level from peripheral devices (N.O., N.C.)
External fault detection method
Operation after external fault detection
The following table shows the relationship between the conditions and the value set to H1-oo:
Terminal statuses, detection conditions, and stopping methods marked with an O are applicable to the corresponding settings.
Terminal Status <1>
Setting
20
21
254
N.O.
N.C.
Always
Detected
O
O
Detected
during Run
only
Stopping Method
Ramp to Stop
(fault)
Coast to Stop
(fault)
Fast Stop
(fault)
Alarm Only
(continue
running)
O
O
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
N.O.
N.C.
Stopping Method
Ramp to Stop
(fault)
O
O
O
O
Coast to Stop
(fault)
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
Alarm Only
(continue
running)
O
O
O
O
Fast Stop
(fault)
O
O
O
O
O
O
O
O
<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed.
<2> Determine whether detection for each fault should be enabled only during run or always detected.
Configuring one of the digital inputs for PID integral reset (H1-oo = 30) resets the value of the integral component in PID
control to 0 when the terminal is closed. Refer to PID Block Diagram on page 180 for more details.
Setting 31: PID Integral Hold
Configuring a digital input for Integral Hold (H1-0o = 31) locks the value of the integral component of the PID control as
long as the input is active. The PID controller resumes integral operation from the hold value as soon as the integral hold input
is released. Refer to PID Block Diagram on page 180 for more information on this function.
Setting 32: Multi-Step Speed Reference 4
A digital input configured as a PID soft starter cancel input (H1-0o = 34) enables or disables the PID soft starter and cancels
the PID accel/decel time (b5-17). Refer to PID Block Diagram on page 180.
Setting 35: PID Input Level Selection
Allows an input terminal to switch the sign of the PID input. Refer to PID Block Diagram on page 180 for details.
Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence
S1
Reverse Run
S2
SC Digital Input Common
255
Parameter Details
Selects the multi-step speeds d1-09 to d1-16 in combination with the input terminal set for Multi-Step Speed 1, 2 and 3. Refer
to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Frequency Reference on page 209.
These inputs add offset frequencies d7-01, d7-02, and d7-03 to the frequency reference. Refer to d7-01 to d7-03: Offset
Frequency 1 to 3 on page 223 for details.
Setting 47: Node Setup
If the SI-S3 option card is connected, closing this terminal sets a node address for operation on a CANopen network.
Setting 60: DC Injection Braking Command
DC Injection Braking is activated when a DC Injection Braking command is input while the drive is stopped. DC Injection
Braking is released when a Run command or a Jog command is input. Refer to b2: DC Injection Braking and Short Circuit
Braking on page 169 for details on setting up the DC Injection Braking function.
The diagram below illustrates DC Injection Braking:
DC Injection braking
command
OFF
ON
OFF
OFF
OFF
ON
DC Injection
braking
DC Injection Braking
Start Frequency
(b2-01)
Output frequency
DC Injection
braking
These input functions enable Speed Search even if parameter b3-01 = 0 (no Speed Search at start). Refer to Speed Search
Activation on page 174 for details on how to use the input signals. Refer to b3: Speed Search on page 172 for more about
Speed Search.
Note: Simultaneously assigning Speed Search 1 and Speed Search 2 to the input terminals will trigger an oPE03 error.
Enabled in V/f Control. When this input is closed, Field Weakening is performed. For details, see d6: Field Weakening and
Field Forcing.
Setting 65, 66: KEB Ride-Thru 1 (N.C.), 2 (N.O.)
Enables the KEB Ride-Thru function selected in parameter L2-29. Refer to KEB Ride-Thru Function on page 288 for more
information on this function.
DIgital Input Function
Setting 65 (N.C.)
Setting 66 (N.O.)
Drive Operation
Input Open
KEB Ride-Thru Deceleration
Normal operation
Input Closed
Normal operation
KEB Ride-Thru Deceleration
Note: Simultaneously assigning KEB Ride-Thru 1 and KEB Ride-Thru 2 to the input terminals will trigger an oPE03 error.
The drive has a built-in function to self-diagnose serial communications operation. The test involves wiring the send and
receive terminals of the RS-485/422 port together. The drive transmits data and then confirms that the communications are
received normally. Refer to Self-Diagnostics on page 625 for details on how to use this function.
256
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Closing an input programmed for this function triggers High Slip Braking (available only in V/f and V/f w/PG control modes).
After starting HSB, bring the drive to a complete stop and remove the HSB command before restarting. Refer to n3: High
Slip Braking (HSB) and Overexcitation Braking on page 314.
Setting 6A: Drive Enable
A digital input configured as a Drive enable (H1-oo = 6A) will prevent the drive from executing a Run command until
the input is closed. When the input is open, the digital operator will display dnE to indicate that the drive is disabled.
If a Run command is enabled before the terminal set for Drive enable closes, then the drive will not run until the Run
command is cycled (i.e., a new Run command is required). If the input is opened while the drive is running, the drive will stop
according to the stop method set to b1-03 (Refer to b1-03: Stopping Method Selection on page 164).
Setting 71: Speed/Torque Control Switch
Switches the drive between Torque Control and Speed Control. Torque Control is enabled when the terminal is closed, and
Speed Control is enabled when the terminal is open. Set parameter d5-01 to 0 when using this function. Refer to d5: Torque
Control on page 218 and Switching Between Torque and Speed Control on page 220.
Setting 72: Zero Servo
Activates the Zero Servo function to lock the rotor at a certain position. Refer to b9: Zero Servo on page 191 for details.
Setting 75, 76: Up 2/Down 2 Function
The Up/Down 2 function adds a bias to the frequency reference. The input programmed for 75 will increase the bias and the
input programmed for 76 will decrease the bias. Table 5.39 explains how the Up/Down 2 function works depending on the
frequency reference source and parameters d4-01, d5-03, and d4-05. Refer to d4: Frequency Reference Hold and Up/Down
2 Function on page 213 for detailed explanations of these and other Up/Down 2 related parameters.
Note: 1. The Up/Down 2 functions must be set as a pair.
2. When using the Up/Down 2 function, set appropriate bias limit values to parameters d4-08 and d4-09.
Table 5.39 Up/Down 2 Operations
d4-03
d4-05
2
Multi-Step Speed
Reference
Operation
d4-01
--
Multi-Step Speed
Reference
Value
other
than 0
--
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Frequency Saved
Not saved
Not saved
Parameter Details
Condition
Freq. Ref.
Source
5
Not saved
257
Freq. Ref.
Source
d4-03
d4-05
Other (analog
comm., etc.)
Operation
--
Other (analog
comm, etc.)
Value
other
than 0
10
d4-01
--
Frequency Saved
Not saved
Not saved
Not saved
If the bias is constant for 5 s, it is
saved to parameter d4-06. The
frequency reference cannot be
overwritten, so only the bias is
saved.
Switches the ASR gain between the values set to C5-01 and C5-03. The gain set to C5-03 is enabled when the terminal is
closed, and C5-01 is enabled when the terminal reopens. Refer to C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/
ASR Integral Time 1, 2 on page 201 for a more detailed description.
Setting 78: External Torque Reference Polarity Inversion
Reverses the direction of the torque reference when the terminal closes. Refer to d5: Torque Control on page 218 and Setting
the Torque Reference, Speed Limit, and Torque Compensation Values on page 218 for details.
Setting 7A, 7B: KEB Ride-Thru 2 (N.C., N.O.)
An input terminal set to 7A or 7B can trigger Single Drive KEB Ride-Thru during deceleration. L2-29 is disregarded if this
is enabled. Refer to KEB Ride-Thru Function on page 288 for details.
Digital Input Function
Setting 7A (N.C.)
Setting 7B (N.O.)
Drive Operation
Input Open
Single Drive KEB Ride-Thru 2
Normal operation
Input Closed
Normal operation
Single Drive KEB Ride-Thru 2
Note: Simultaneously assigning KEB Ride-Thru 1 and KEB Ride-Thru 2 to the input terminals will trigger an oPE03 error.
Setting 7C, 7D: Short Circuit Braking (N.O., N.C.) (OLV/PM, AOLV/PM)
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
Activates Short Circuit Braking in OLV control modes for PM motors. By linking all three phases of a PM motor, Short Circuit
Braking creates a braking torque to stop a rotating motor or prevent a motor from coasting due to external forces (such as the
windmill effect in fan applications). Parameter b2-18 limits the current during Short Circuit Braking.
DIgital Input Function
Setting 7C (N.O.)
Setting 7D (N.C.)
Drive Operation
Input Open
Normal operation
Short-Circuit Braking
Input Closed
Short Circuit Braking
Normal operation
Setting 7E: Forward/Reverse Detection (for V/f Control with Simple PG Feedback)
Determines the motor rotation direction for V/f Control with Simple PG feedback (A1-02 = 0 and H6-01 = 3). If the input is
open, the speed feedback signal is considered to be forward. If the input is closed, it is considered to be reverse. Refer to H6:
Pulse Train Input/Output on page 277.
258
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
These settings are for digital input functions used in DriveWorksEZ. Changing these settings is not typically required.
Setting 9F: DriveWorksEZ Disable
This function is used to enable or disable a DriveWorksEZ program in the drive. An input programmed for this function is
effective only if A1-07 = 2.
Status
Open
Closed
Description
DriveWorksEZ enabled
DriveWorksEZ disabled
Parameter Name
Terminal M1-M2 Function Selection (relay)
Terminal M3-M4 Function Selection (relay)
Terminal M5-M6 Function Selection (relay)
Setting Range
0 to 192
0 to 192
0 to 192
Default
0: During run
1: Zero Speed
2: Speed agree 1
Setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D <1>
E
F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
Function
During Run
Zero Speed
Speed Agree 1
User-Set Speed Agree 1
Frequency Detection 1
Frequency Detection 2
Drive Ready
DC Bus Undervoltage
During Baseblock (N.O.)
Frequency Reference Source
Run Command Source
Torque Detection 1 (N.O.)
Frequency Reference Loss
Page
260
260
260
261
261
262
262
262
263
263
263
263
263
263
Fault
Through Mode
Minor Fault
Fault Reset Command Active
Timer Output
Speed Agree 2
User-Set Speed Agree 2
Frequency Detection 3
Frequency Detection 4
Torque Detection 1 (N.C.)
Torque Detection 2 (N.O.)
Torque Detection 2 (N.C.)
During Reverse
During Baseblock (N.C.)
Motor 2 Selection
During regeneration
263
263
263
263
264
264
264
265
265
263
263
265
266
266
266
Setting
1E
1F
20
22
2F
30
31
32
33
37
38
39
3C
3D
3E
3F
4A
4B
4C
4D
Function
Restart Enabled
Motor Overload Alarm (oL1)
Drive Overheat Pre-Alarm (oH)
Mechanical Weakening Detection
Maintenance Period
During Torque Limit
During Speed Limit
During Speed Limit in Torque Control
Zero Servo Complete
During Frequency Output
Drive Enabled
Watt Hour Pulse Output
LOCAL/REMOTE Status
During Speed Search
PID Feedback Low
PID Feedback High
During KEB Operation
During Short Circuit Braking
During Fast Stop
oH Pre-Alarm Time Limit
Page
266
266
266
266
266
266
267
267
267
267
267
267
267
268
268
268
268
268
268
268
4E <2>
268
4F <2>
268
268
268
60
61
90
91
92
100 to 192
268
268
259
Parameter Details
Description
Drive is stopped.
A Run command is input or the drive is in deceleration or DC injection.
Run command
OFF
Baseblock
command
OFF
ON
ON
Output
frequency
During Run
OFF
ON
Terminal closes when the output frequency or motor speed (CLV, CLV/PM) falls below the minimum output frequency set
to E1-09 or b2-01.
Status
Open
Closed
Description
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
Note: In CLV and CLV/PM control modes, the zero speed level is defined by b2-01. In all other control modes, the zero speed level is the minimum
output frequency set to E1-09.
Output frequency
or
motor speed
Zero Speed
OFF
ON
Closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02) of the
current frequency reference regardless of the direction.
Status
Open
Closed
Description
Output frequency or motor speed does not match the frequency reference while the drive is running.
Output frequency or motor speed is within the range of frequency reference L4-02.
260
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
L4-02
L4-02
Speed agree 1
OFF
ON
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 300 for more details.
Setting 3: User-Set Speed Agree 1 (fref/fset Agree 1)
Closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the speed
agree width (L4-02) of the programmed speed agree level (L4-01).
Status
Open
Closed
Description
Output frequency or motor speed and frequency reference are not both within the range of L4-01 L4-02.
Output frequency or motor speed and the frequency reference are both within the range of L4-01 L4-02.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Frequency reference + L4-02
Frequency reference
L4-01 + L4-02
Frequency reference L4-02
L4-01
L4-01 L4-02
During
Forward
0 Hz
Output frequency
During Reverse
L4-01 + L4-02
Output frequency
L4-01
User Set
Speed Agree 1
Parameter Details
ON
OFF
ON
ON
OFF
ON
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 300 for more instructions.
Setting 4: Frequency Detection 1
The output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-01 plus
the detection width set in L4-02. The terminal remains open until the output frequency or motor speed fall below the level set
in L4-01.
Status
Open
Closed
Description
Output frequency or motor speed exceeded L4-01 + L4-02.
Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
261
L4-02
L4-01
L4-01
L4-02
Frequency
detection 1
ON
OFF
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 300 for more details.
Setting 5: Frequency Detection 2
The output closes when the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-01. The
terminal remains closed until the output frequency or motor speed fall below L4-01 minus the setting of L4-02.
Status
Open
Closed
Description
Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Output frequency or motor speed exceeded L4-01.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Output Frequency
or Motor Speed
L4-02
L4-01
L4-01
L4-02
Frequency
Detection 2
OFF
ON
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 300 for more details.
Setting 6: Drive Ready
The output closes when the drive is ready to operate the motor. The terminal will not close under the conditions listed below,
and any Run commands will be disregarded.
When the power is shut off
During a fault
When the internal power supply of the drive has malfunctioned
When a parameter setting error makes it impossible to run
Although stopped, an overvoltage or undervoltage situation occurs
While editing a parameter in the Programming Mode (when b1-08 = 0)
Setting 7: DC Bus Undervoltage
The output closes when the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A fault in
the DC bus circuit will also cause the terminal set for DC bus undervoltage to close.
Status
Open
Closed
262
Description
DC bus voltage is above the level set to L2-05.
DC bus voltage has fallen below the trip level set to L2-05.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Status
Open
Closed
Description
Drive is not in a baseblock state.
Baseblock is being executed.
Description
Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15).
Frequency reference is being sourced from the digital operator.
Description
Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Run command is being sourced from the digital operator.
Setting B, 17, 18, 19: Torque Detection 1 (N.O., N.C.), Torque Detection 2 (N.O., N.C.)
These digital output functions signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below. Refer to L6: Torque Detection on page
303 for details.
Status
Description
Closed
17
Open
18
Closed
19
Open
An output set for this function closes when frequency reference loss is detected. Refer to L4-05: Frequency Reference Loss
Detection Selection on page 301 for details.
Setting D: Braking Resistor Fault
An output programmed for this function closes when the dynamic braking resistor (DB) overheats or the braking transistor is
in a fault condition.
Setting E: Fault
The output closes when the drive faults (excluding CPF00 and CPF01 faults).
Setting F: Through Mode
Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function in
the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or MEMOBUS/
Modbus communications.
Setting 10: Minor Fault
The output closes when there is an attempt to reset a fault situation from the control circuit terminals, via serial communications,
or using a communications option card.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
263
Parameter Details
Setting
This setting configures a digital output terminal as the output for the timer function. Refer to b4: Delay Timers on page 177
for details.
Setting 13: Speed Agree 2 (fref /fout Agree 2)
The output closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the speed agree width (L4-04)
of the current frequency reference, regardless of the direction.
Status
Open
Closed
Description
Output frequency or motor speed does not match the frequency reference while the drive is running.
Output frequency or motor speed is within the range of frequency reference L4-04.
Output Frequency
or Motor Speed
L4-04
Speed Agree 2
OFF
ON
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 300 for more details.
Setting 14: User-Set Speed Agree 2 (fref /fset Agree 2)
The output closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within
the speed agree width (L4-04) of the programmed speed agree level (L4-03).
Status
Open
Closed
Description
Output frequency or motor speed and frequency reference are both outside the range of L4-03 L4-04.
Output frequency or motor speed and the frequency reference are both within the range of L4-03 L4-04.
Note: The detection level L4-03 is a signed value; detection works in the specified direction only.
Frequency reference + L4-04
Frequency reference
L4-03 + L4-04
Frequency reference L4-04
L4-03
L4-03 L4-04
During
Forward
Output frequency
0 Hz
Output frequency
Frequency
reference
User Set
Speed Agree 2
OFF
ON
OFF
ON
Figure 5.72 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 300 for more details.
264
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level set
in L4-03. The detection level L4-03 is a signed value; detection works in the specified direction only.
Status
Open
Closed
Description
Output frequency or motor speed exceeded L4-03 plus L4-04.
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.
Output Frequency
or Motor Speed
L4-04
L4-03
Frequency
detection 3
ON
OFF
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 300 for more details.
Setting 16: Frequency Detection 4
The output closes when the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-03. The
terminal remains closed until the output frequency or motor speed falls below L4-03 minus the setting of L4-04.
Status
Open
Closed
Description
Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03.
Output frequency or motor speed exceeded L4-03.
Note: The detection level L4-03 is a signed value; detection works in the specified direction only.
Output Frequency
or Motor Speed
Frequency
Detection 4
L4-04
Parameter Details
L4-03
5
OFF
ON
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 300 for more details.
Setting 1A: During Reverse
A digital output set for During reverse closes when the drive is running the motor in the reverse direction.
Status
Open
Closed
Description
Motor is being driven in the forward direction or stopped.
Motor is being driven in reverse.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
265
During Reverse
OFF
ON
time
The output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not switch
and no main circuit voltage is output.
Status
Open
Closed
Description
Baseblock is being executed.
Drive is not in a baseblock state.
Indicates which motor is selected when another output terminal is set to switch drive operation between two motors (H1oo = 16). Refer to Setting 16: Motor 2 Selection on page 253 for details on switching motors.
Status
Open
Closed
Description
Motor 1 is selected.
Motor 2 is selected.
An output set for Restart enabled closes when the drive attempts to restart after a fault has occurred.
The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has attempted to restart. If the drive cannot successfully restart within the number of attempts permitted
by L5-01, a fault will be triggered and the terminal set to 1E will open. Refer to L5: Fault Restart on page 301 for details on
automatic restart.
Setting 1F: Motor Overload Alarm (oL1)
The output closes when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection level.
Refer to L1-01: Motor Overload Protection Selection on page 280.
Setting 20: Drive Overheat Pre-Alarm (oH)
The output closes when the drive heatsink temperature reaches the level specified by parameter L8-02. Refer to L8-02:
Overheat Alarm Level on page 307 for details on drive overheat detection.
Setting 22: Mechanical Weakening Detection
The output closes when a mechanical weakening situation is detected. Refer to Mechanical Weakening Detection on page
304 for details.
Setting 2F: Maintenance Period
The output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as determined
by the estimated performance life span of those components. Components performance life is displayed as a percentage on
the digital operator screen. Refer to Periodic Maintenance on page 403.
Setting 30: During Torque Limit
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
266
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The output closes when the speed limit has been reached. This function can be used in CLV and CLV/PM control modes.
Status
Open
Closed
Description
The conditions described below are not present.
1. The frequency reference has reached the upper limit set in d2-01.
2. The frequency reference has fallen to the lower limit set in d2-02 or d2-03.
3. Parameter b1-05 is set to 1, 2, or 3, and the frequency reference has fallen below the minimum output frequency
(E1-09).
The motor torque and load torque are not in balance, causing the motor to accelerate. The output closes when the motor reaches
the speed limit. Refer to d5: Torque Control on page 218 and Indicating Operation at the Speed Limit on page 220 for
details.
Setting 33: Zero Servo Complete
The output closes when Zero Servo is enabled and the load is locked into position within the allowable deviation (b9-02).
Refer to b9: Zero Servo on page 191 for information on Zero Servo operation.
Setting 37: During Frequency Output
Description
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Drive is outputting frequency.
run command
baseblock
command
OFF
ON
OFF
ON
during run
OFF
during frequency
output
OFF
Parameter Details
output
frequency
ON
ON
Reflects the status of a digital input configured as a Drive enable input (H1-oo = 6A). If that digital input closes, then the
digital output set for Drive enable will also close.
Setting 39: Watt Hour Pulse Output
Outputs a pulse to indicate the watt hours. Refer to H2-06: Watt Hour Output Unit Selection on page 269 for details.
Setting 3C: LOCAL/REMOTE Status
The output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
Open
Closed
Description
REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as frequency reference
and Run command source.
LOCAL: The digital operator is used as frequency reference and Run command source.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
267
The output terminal closes while Speed Search is being performed. Refer to b3: Speed Search on page 172 for details.
Setting 3E: PID Feedback Low
The output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the
level set to b5-13 for longer than the time set to b5-14. Refer to PID Feedback Loss Detection on page 182 for details.
Setting 3F: PID Feedback High
The output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the
level set to b5-36 for longer than the time set to b5-37. Refer to PID Feedback Loss Detection on page 182 for details.
Setting 4A: During KEB Operation
The output terminal closes while KEB is being performed. Refer to KEB Ride-Thru Function on page 288 for a KEB function
description.
Setting 4B: During Short Circuit Braking
The output terminal closes while Short Circuit Braking is being executed.
Setting 4C: During Fast Stop
The output terminal closes when a Fast Stop is being executed. Refer to Setting 15, 17: Fast Stop (N.O., N.C.) on page 252.
Setting 4D: oH Pre-Alarm Time Limit
The output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat
alarm has not disappeared after 10 frequency reduction operation cycles. Refer to L8-03: Overheat Pre-Alarm Operation
Selection on page 307 for a more detailed description.
Setting 4E: Braking Transistor Fault (rr)
The output closes if the internal braking transistor reaches the overheat level.
Setting 4F: Braking Resistor Overheat (rH)
The output closes when the braking resistor exceeds the overheat level. The braking resistor may overheat due to motor
regeneration or short deceleration time setting.
Setting 60: Internal Cooling Fan Alarm
The output closes when the drive internal cooling fan has failed.
Setting 61: Rotor Position Detection Complete
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
After the Run command is given, the output terminal signals that the drive has detected the rotor position (PM motors).
Setting 90 to 92: DriveWorksEZ Digital Output 1 to 3
These settings are for output functions used in DriveWorksEZ. Normally there is no need to change these settings.
Setting 100 to 192: Functions 0 to 92 with Inverse Output
These settings have the same function as settings 0 to 92 but with inverse output. Set as 1oo, where the 1 indicates inverse
output and the last two digits specify the setting number of the function.
Examples:
For inverse output of 8: During baseblock, set 108.
For inverse output of 4A: During KEB set 14A.
268
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
H2-06
Setting Range
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default
0
Note: 1. A negative power output (i.e., regeneration) does not subtract from the total watt hours.
2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off.
H2-06
(Pulse Output Unit)
OFF
ON
OFF
0.2 s
Name
Terminal A1 Signal Level Selection
Setting Range
0 to 1
Default
0
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and bias
settings will be read as 0%.
The input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the
motor will rotate in reverse.
Parameter Details
Name
Terminal A1 Function Selection
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0 to 31
Default
0
269
Name
Terminal A1 Gain Setting
Terminal A1 Bias Setting
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Default
100.0%
0.0%
Setting Examples
Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):
A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since
the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04
above 5 Vdc.
H3-01 = 0
H3-01 = 1
Gain = 200 %
Gain = 200 %
Frequency
reference
100%
E1-04
-10 V
100 %
E1-04
-5 V
0V 5V
10 V
-100%
E1-04
Bias = 0 %
Gain = -200 %
0V
5V
10 V
Figure 5.78 Frequency Reference Setting by Analog Input with Increased Gain
Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.
H3-01 = 0
H3-01 = 1
100 %
Frequency
reference
100%
H3-01 = 0
-10 V -6.0 V
2.0 V
-25%
0
2.0 V
-25%
10 V
Analog Input
Voltage
10 V
Analog Input
Voltage
-100%
E1-04
-150%
H3-01 = 1
Figure 5.79 Frequency Reference Setting by Analog Input with Negative Bias
Name
Terminal A3 Signal Level Selection
Setting Range
0, 1
Default
0
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 0: 0 to 10 Vdc on page 269.
270
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The input level is -10 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 1: -10 to 10 Vdc on page 269.
Name
Terminal A3 Function Selection
Setting Range
0 to 31
Default
2
Name
Terminal A3 Gain Setting
Terminal A3 Bias Setting
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Default
100.0%
0.0%
Name
Terminal A2 Signal Level Selection
Setting Range
0 to 3
Default
2
Setting 0: 0 to 10 Vdc
The input level is -10 to 10 Vdc. Refer to Setting 1: -10 to 10 Vdc on page 269.
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Name
Terminal A2 Function Selection
Setting Range
0 to 31
Default
0
Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Parameter Details
Default
100.0%
0.0%
271
Name
Analog Input Filter Time Constant
Setting Range
0.00 to 2.00 s
Default
0.03 s
Name
Analog Input Terminal Enable Selection
Setting Range
1 to 7
Default
7
Name
Terminal A1 Offset
Terminal A2 Offset
Terminal A3 Offset
Setting Range
-500 to 500
-500 to 500
-500 to 500
Default
0
0
0
272
Function
Frequency Bias
Frequency Gain
Auxiliary Frequency Reference 1
Auxiliary Frequency Reference 2
Output Voltage Bias
Accel/Decel Time Gain
DC Injection Braking Current
Torque Detection Level
Stall Prevention Level During Run
Output Frequency Lower Limit Level
PID Feedback
Page
273
273
273
273
273
273
273
274
274
274
274
Setting
C
D
E
F
10
11
12
13
14
15
16
Function
PID Setpoint
Frequency Bias
Motor Temperature (PTC Input)
Through Mode
Forward Torque Limit
Reverse Torque Limit
Regenerative Torque limit
Torque Limit Using Torque Reference/Speed Limit
Torque Compensation
General Torque Limit
Differential PID Feedback
Page
274
274
274
274
274
275
275
274
275
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Function
Page
275
Through Mode
DriveWorksEZ Analog Input 1
DriveWorksEZ Analog Input 2
DriveWorksEZ Analog Input 3
274
275
The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency
reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also
when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference
by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog input
terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.
Setting 1: Frequency Gain
The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from analog
input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.
Setting 2: Auxiliary Reference 1
Sets the auxiliary frequency reference 1 when multi-step speed operation is selected. Refer to Multi-Step Speed Selection on
page 209 for details.
Setting 3: Auxiliary Reference 2
Sets the auxiliary frequency reference 2 when multi-step speed operation is selected. Refer to Multi-Step Speed Selection on
page 209 for details.
Setting 4: Output Voltage Bias
Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available
only when using V/f Control.
Setting 5: Accel/Decel Time Gain
100%
Parameter Details
Adjusts the gain level for the acceleration and deceleration times set to parameters C1-01 through C1-08.
The drive acceleration time is calculated by multiplying the gain level to C1-oo as follows:
C1-oo Accel/decel time gain = Drive accel/decel time
Acceleration/deceleration gain from 1 to 10 V
=
50%
(10 V)
Input Voltage (V)
10 (%)
20%
10%
0 1V
2V
5V
10 V
The current level used for DC Injection Braking is set as a percentage of the drive rated current.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
273
100%
Drive Rated
Current
0
(4)
10 V
(20 mA)
Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog input.
The analog input replaces the level set to L6-02. An analog input of 100% (10 V or 20 mA) sets a torque detection level equal
to 100% drive rated current/motor rated torque. Adjust the analog input gain if higher detection level settings are required.
Refer to L6: Torque Detection on page 303 for details on torque detection.
Setting 8: Stall Prevention Level
Allows an analog input signal to adjust the Stall Prevention level. Figure 5.82 shows the setting characteristics. The drive will
use the lower value of the Stall Prevention level set to L3-06 or the level coming from the selected analog input terminal.
Stall Prevention Level during Run
100%
30%
30%
100%
Figure 5.82 Stall Prevention During Run Using an Analog Input Terminal
The user can adjust the lower limit of the output frequency using an analog input signal.
Setting B: PID Feedback
Supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01. Refer to PID Feedback Input
Methods on page 178.
Setting C: PID Setpoint
Supplies the PID setpoint value and makes the frequency reference selected in parameter b1-01 no longer the PID setpoint.
PID operation to be enabled in b5-01 to use this setting. Refer to PID Setpoint Input Methods on page 178.
Setting D: Frequency Bias
The input value of an analog input set to this function will be added to the frequency reference. This function can be used with
any frequency reference source.
Setting E: Motor Temperature
In addition to motor overload fault detection oL1, it is possible to use a Positive Temperature Coefficient (PTC) thermistor
for motor insulation protection. Refer to Motor Protection Using a Positive Temperature Coefficient (PTC) Thermistor on
page 283 for a detailed explanation.
Setting F, 1F: Through Mode
When set to F or 1F, an input does not affect any drive function, but the input level can still be read out by a PLC via a
communication option or MEMOBUS/Modbus communications.
Setting 10, 11, 12, 15: Forward, Reverse, Regenerative, General Torque Limit (OLV, CLV, AOLV/PM, CLV/PM)
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
These functions set a torque limit using analog inputs for different operating conditions. Refer to L7: Torque Limit on page
305 for details.
274
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Sets the torque reference (when in Torque Control) or the torque limit (when in Speed Control). Refer to Setting the Torque
Reference, Speed Limit, and Torque Compensation Values on page 218 for details.
Setting 14: Torque Compensation
Sets a torque compensation value when using Torque Control. Refer to Setting the Torque Reference, Speed Limit, and
Torque Compensation Values on page 218 for details.
Setting 16: Differential PID Feedback
If an analog value is set for this function, the PID controller is set for differential feedback. The difference of the PID feedback
input value and the differential feedback input value builds the feedback value used to calculate the PID input. Refer to PID
Feedback Input Methods on page 178.
Setting 17: Motor Thermistor (NTC)
Used as a complement or a substitution for oL1. Refer to Motor Protection Using an NTC Thermistor Input on page 285
for details.
Setting 30, 31, 32: DriveWorksEZ Analog Inputs 1, 2, and 3
These settings are for DriveWorksEZ functions. Normally there is no need to change or apply these settings.
Setting Range
000 to 999
000 to 999
Default
102
103
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting, terminal functions as well as FM and
AM output levels can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).
Parameters H4-02 and H4-05 set the terminal FM and AM output signal level when the value of the selected monitor is at
100%. Parameters H4-03 and H4-06 set the terminal FM and AM output signal level when the value of the selected monitor
is at 0%. Both are set as a percentage, where 100% equals 10 Vdc or 20 mA analog output and 0% equals 0 V or 4 mA. The
output voltage of both terminals is limited to +/-10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and
H4-08. Figure 5.83 illustrates how gain and bias settings work.
No.
H4-02
H4-03
H4-05
H4-06
Name
Multi-Function Analog Output Terminal FM Gain
Multi-Function Analog Output Terminal FM Bias
Multi-Function Analog Output Terminal AM Gain
Multi-Function Analog Output Terminal AM Bias
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
Default
100.0%
0.0%
50.0%
0.0%
When viewing a gain setting parameter (H4-02 or H4-05) on the digital operator, the analog output will supply a voltage signal
equal to 100% of the monitor value (including changes made from bias and gain settings). When viewing a bias setting
parameter (H4-03 or H4-06), the analog output voltage will supply a signal equal to 0% monitor value.
Example 1: Set H4-02 to 50% for an output signal of 5 V at terminal FM when the monitored value is at 100%.
Example 2: Set H4-02 to 150% for an output signal of 10 V at terminal FM when the monitored value is at 76.7%.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
275
Parameter Details
No.
H4-01
H4-04
H4-07, 08 = 1
15 V
Gain = 150%
Bias = 0%
Output Voltage
10 V
10 V
Output Voltage
Gain 150%
Bias 0%
5V
Gain 100%
Bias 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
5V
-100%
-5 V
Gain 50%
Bias 0%
100%
Monitor Value
-10 V
0V
0%
Monitor Value
100%
-15 V
Figure 5.83 Analog Output Gain and Bias Setting Example 1 and 2
Example 3: Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.
H4-07, 08 = 0
Gain = 100%
Bias = 30%
H4-07, 08 = 1
10V
10 V
Gain = 100%
Bias = 0%
Output Voltage
Bias 30%
Gain 100%
Output Voltage
Bias 0%
Gain 100%
3V
0V
3V
-100%
-4 V
100%
Monitor Value
-10 V
0%
Monitor Value
100%
n H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters. Refer to Terminal AM/FM Signal
Selection on page 108 for details on setting S5.
No.
H4-07
H4-08
Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection
Setting Range
Default
0 to 2
0 to 2
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
276
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Pulse Train Input Terminal RP Function Selection
Setting Range
0 to 3
Default
0
If the pulse input is set for this function and the frequency reference source is set to pulse input (b1-01, b1-15 = 4), the drive
reads the frequency value from terminal RP.
Setting 1: PID feedback value
Using this setting, the feedback value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID
Control on page 177 for details on PID control.
Setting 2: PID setpoint value
Using this setting, the setpoint value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID
Control on page 177 for details on PID control.
Setting 3: Speed feedback (V/f Control with Simple Speed Feedback)
1.
2.
If a digital input programmed for Forward/reverse detection (H1-oo = 7E) is closed, the drive assumes reverse
rotation. If open, then the drive assumes that the motor is rotating forwards.
Using the Frequency Reference Direction
If no digital input is set to Forward/reverse detection (H1-oo = 7E), the drive uses the direction of the frequency
reference as the direction for the speed feedback detected at the pulse input.
Parameter Details
This setting can be used in V/f control to increase the speed control precision by using a motor speed feedback signal. The
drive reads the speed feedback from terminal RP, compares it to the frequency reference and compensates the motor slip using
a speed regulator (ASR, set up in the C5-oo parameters) like shown in Figure 5.85. Because input terminal RP is incapable
of detecting motor direction, a separate way of determining motor direction still needs to be set up:
Motor speed
Figure 5.85 Speed Control with ASR in V/f with Simple Speed Feedback
1.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
277
2.
3.
4.
Connect the motor speed pulse signal to the pulse input RP, set H6-01 = 3, and set the pulse signal frequency that
is equal to the maximum speed to H6-02 (pulse input scaling). Make sure the pulse input bias (H6-04) is 0% and the
gain (H6-03) is 100%.
Decide on the signal used for detecting the direction. Set H1-oo = 7F if using a digital input.
Use the ASR gain and integral time parameters described in C5: Automatic Speed Regulator (ASR) on page 199
for adjusting the responsiveness.
Note: 1. C5 parameters will appear when using V/f Control (A1-02 = 0) and when the pulse input RP function is set for simple PG feedback in V/
f Control (H6-01 = 3).
2. If running two motors from the same drive, V/f Control with simple PG feedback can be used for motor 1 only.
Name
Pulse Train Input Scaling
Setting Range
100 to 32000 Hz
Default
1440 Hz
Name
Pulse Train Input Gain
Setting Range
0.0 to 1000.0%
Default
100.0%
Name
Pulse Train Input Bias
Setting Range
-100.0 to 100.0%
Default
0.0%
Setting Range
0.00 to 2.00 s
Default
0.10 s
Name
Pulse Train Input Filter Time
Name
Setting Range
000
Default
102
<1> Set 000 when the terminal is not used or when using the terminal in the through mode.
Name
Pulse Train Monitor Scaling
Setting Range
0 to 32000 Hz
Default
1440 Hz
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0.1 to 1000.0 Hz
Default
0.5 Hz
Parameter Details
No.
H6-08
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
279
5.8
L: Protection Functions
Name
Setting Range
L1-01
0 to 6
Default
Determined by
A1-02
Note: 1. When the motor protection function is enabled (L1-01 0), an oL1 alarm can be output through one of the multi-function outputs by setting
H2-01 to 1F. The output closes when the motor overload level reaches 90% of the oL1 detection level.
2. Set L1-01 to a value between 1 and 5 when running a single motor from the drive to select a method to protect the motor from overheat.
An external thermal relay is not necessary.
Use this setting if no motor overheat protection is desired or if multiple motors are connected to a single drive. If multiple
motors are connected to a single drive, install a thermal relay for each motor as shown in Figure 5.86.
Power
supply
Drive
M1
MC1
L10
MC2
L20
M2
Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately
adjusts the electrothermal trigger point according to the motor overload characteristics, protecting the motor from overheat
throughout the entire speed range.
Overload Tolerance
Torque (%)
150
60 s
Cooling Ability
Overload Characteristics
100
90
60
50 Continuous
A
B
C
05 33
280
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Use this setting when operating a drive duty motor that allows constant torque in a speed range of 1:10. The drive will allow
the motor to run with 100% load from 10% up to 100% speed. Running at slower speeds with full load can trigger an overload
fault.
Overload Tolerance
150
Torque (%)
Overload Characteristics
60 s
100
55
50
Cooling Ability
B
C
0 110
Use this setting when operating a drive-dedicated motor that allows constant torque in a speed range of 1:100. This motor type
is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload
fault.
Overload Tolerance
150
Overload Characteristics
60 s
Torque (%)
Cooling Ability
100
90
50 Continuous
C
0 1
Parameter Details
Use this setting when operating a PM motor. PM motors for derated torque have a self-cooling design and the overload tolerance
drops as the motor slows. Electronic thermal overload is triggered in accordance with the motor overload characteristics,
providing overheat protection across the entire speed range.
Overload Tolerance
Cooling Ability
Overload Characteristics
Torque (%)
150
120
100
80
60 s
Continuous
50
0.0
10
33
100
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
281
Sets necessary protection characteristics when driving a PM with constant torque. These motors allow for a speed control from
0.2% to 100% when operating with 100% load. Slower speeds with 100% load will trigger overload.
Overload Tolerance
Cooling Ability
Overload Characteristics
150
Torque (%)
125
115
Continuous
100
83
77
67
0 0.2
150
Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately
adjusts the electrothermal trigger point according to the motor overload characteristics and protects the motor from overheat
throughout the entire speed range.
Overload Tolerance
Torque (%)
150
60 s
Cooling Ability
Overload Characteristics
100
90
60
50 Continuous
A
B
C
05 33
Name
Motor Overload Protection Time
Setting Range
0.1 to 5.0 minutes
Default
1.0 minutes
Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start.
Figure 5.87 illustrates an example of the electrothermal protection operation time using a general-purpose motor operating at
the value of E1-06, Motor Base Speed, with L1-02 set to one minute.
During normal operation, motor overload protection operates in the area between a cold start and a hot start.
Cold start: Motor protection operation time in response to an overload situation that was suddenly reached when starting a
stationary motor.
Hot start: Motor protection operation time in response to an overload situation that occurred during sustained operation at
rated current.
282
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
10
7
3
Cold start
1
0.4
Hot start
0.1
0
100
150
200
Multi-function input
MA
MB
DIP Switch S4
PTC
Fault output
MC
M1
M2
AI
Multi-function
digital outputs
Parameter Details
A3 (0-10 V)
M3
M4
M5
M6
PTC
thermistor
AC
The PTC must exhibit the characteristics shown in Figure 5.89 in one motor phase. The motor overload protection of the drive
expects 3 of these PTCs to be connected in a series.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
283
Class F
150 C
Resistance ( )
Tr
Tr - 5K (oH3 Alarm Level)
Tr
Temperature
Set up overheat detection using a PTC using parameters L1-03, L1-04, and L1-05 as explained in the following sections.
Name
Motor Overheat Alarm Operation Selection (PTC input)
Setting Range
0 to 3
Default
3
The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop
The drive stops the motor using the Fast Stop time set in parameter C1-09.
Setting 3: Alarm only
The operation is continued and an oH3 alarm is displayed on the digital operator.
Name
Motor Overheat Fault Operation Selection (PTC input)
Setting Range
0 to 2
Default
1
The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to Stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop
The drive stops the motor using the Fast Stop time set in parameter C1-09.
284
Name
Motor Temperature Input Filter Time (PTC input)
Setting Range
0.00 to 10.00 s
Default
0.20 s
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Continuous Electrothermal Operation Selection
Setting Range
0, 1
Default
1
Setting 0: Disabled
Setting 1: Enabled
+V
(+10.5 V, 20 mA)
Voltage Divider
2 kW
A2 (0-10 V)
NTC Thermistor
DIP Switch S1
V
Parameter Details
AC
20,000
15,000
10677
10,000
5,000
0
2733
716
-50
50
100
Temperature ( C)
150
L1-15 to L1-20 can determine the overheat protection settings using the NTC thermistor input. Parameter descriptions are
listed below.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
285
No.
L1-15
Name
Motor 1 Thermistor Selection (NTC)
Setting Range
0, 1
Default
0
Setting Range
50 to 200 C
Default
120
Setting Range
0, 1
Default
0
Setting Range
50 to 200 C
Default
120
Setting Range
0 to 3
Default
3
Setting Range
0 to 3
Default
1
Setting 0: Disabled
Setting 1: Enabled
Sets the temperature that will trigger an overheat fault (oH5) for motor1.
No.
L1-16
Name
Motor 1 Overheat Temperature
No.
L1-17
Name
Motor 2 Thermistor Selection (NTC)
Setting 0: Disabled
Setting 1: Enabled
Sets the temperature that will trigger an overheat fault (oH5) for motor 2.
No.
L1-18
Name
Motor 2 Overheat Temperature
Name
Operation Time at Thermistor Disconnect (NTC)
The drive stops the motor using the deceleration time set in parameter C1-02.
Setting 1: Coast to stop
The drive output is switched off and the motor coasts to a stop.
Setting 2: Fast stop
The drive stops the motor using the Fast stop time set in parameter C1-09.
Setting 3: Alarm only
The operation is continued and a THo alarm is displayed on the digital operator.
286
Name
Operation at Motor Overheat
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The drive stops the motor using the deceleration time set in parameter C1-02.
Setting 1: Coast to stop
The drive output is switched off and the motor coasts to a stop.
Setting 2: Fast stop
The drive stops the motor using the Fast stop time set in parameter C1-09.
Setting 3: Alarm only
The operation is continued and an oH5 alarm is displayed on the digital operator.
Name
Momentary Power Loss Operation Selection
Setting Range
0 to 5
Default
0
If power is not restored within 15 ms, a Uv1 fault will result and the motor coasts to stop.
Setting 1: Recover within L2-02
When a momentary power loss occurs, the drive output will be shut off. If the power returns within the time set to parameter
L2-02, the drive will perform Speed Search and attempt to resume operation. If the power does not return within this time, it
will trigger a Uv1 fault.
Setting 2: Recover as long as CPU has power
When a momentary power loss occurs, the drive output will be shut off. If the power returns and the drive control circuit has
power, the drive will attempt to perform Speed Search and resume the operation. This will not trigger a Uv1 fault.
Setting 3: Kinetic Energy Backup (KEB) Ride-Thru operation within L2-02
The drive decelerates using regenerative energy from the motor until the power returns and then restarts. If the motor comes
to a stop before the power returns, the drive loses control power and the drive output shuts off. A Uv1 fault is not triggered.
The type of KEB operation is determined by the L2-29 setting.
Setting 5: Ramp to stop with KEB deceleration
The drive ramps to stop using the regenerative energy from the motor. Even if the power is restored, the drive will continue
to decelerate until the motor comes to a complete stop. The type of KEB operation is determined by the L2-29 setting. If an
input terminal set for KEB 1 (H1-oo = 65, 66) is triggered while the drive is decelerating, it will accelerate back up to speed
when the input is released.
Notes on Settings 1 through 5
Uv will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is not
output at this time.
A Momentary Power Loss Unit is available to allow for a longer momentary power loss ride through time in models
CIMR-Ao2A0004 to 2A0056 and 4A0002 to 4A0031. This option makes it possible to continue running the drive after up
to two seconds of power loss.
When using a magnetic contactor between the motor and the drive, keep the magnetic contactor closed as long as the drive
performs KEB operation or attempts to restart with Speed Search.
Keep the Run command active during KEB operation or the drive cannot accelerate back to the frequency reference when
the power returns.
When L2-01 is set to 3, 4, or 5, KEB Ride-Thru will be executed as specified in L2-29.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
287
Parameter Details
The drive decelerates using regenerative energy from the motor until the time set in L2-02 has expired. It then tries to accelerate
back to the frequency reference. If the power does not return within the time set to L2-02, it will trigger a Uv1 fault and the
drive output will shut off. The type of KEB operation is determined by the L2-29 setting.
After KEB Ride-Thru begins, the drive uses regenerative energy from the motor to keep the DC bus voltage at the level set
to L2-11 while adjusting the rate of deceleration based on the time set to L2-06. The user must set L2-06 properly to prevent
Uv1 and ov faults.
Note: Shorten the KEB deceleration time (L2-06) if undervoltage (Uv1) occurs in the DC bus. Increase the KEB deceleration time if overvoltage
(ov) occurs.
The drive uses information about the inertia of the connected machinery to determine the deceleration rate necessary to keep
the DC bus voltage at the level set in parameter L2-11. The resulting deceleration time is calculated based on the system inertia
and cannot be adjusted.
System KEB Ride-Thru 1 (L2-29 = 2)
The drive decelerates at the KEB deceleration time set to L2-06. L2-06 is the time required to decelerate from the current
frequency reference to 0. Using this setting, multiple drives can decelerate while keeping the speed ratio constant between
those drives. This function requires a braking resistor and disregards the voltage level in the DC bus.
System KEB Ride-Thru 2 (L2-29 = 3)
The drive decelerates based on the KEB deceleration time set to L2-06 while monitoring the DC bus voltage. If the voltage
level rises, the drive briefly holds the frequency before continuing to decelerate.
When using a digital input to trigger KEB operation and the device controlling the input acts relatively slow, set a minimum
KEB operation time in parameter L2-10. In the example below, the DC bus voltage triggers KEB operation and a digital input
triggers the Hold command.
Main Power Supply
0V
Power loss
L2-10
DC bus voltage
L2-11 (Desired DC Bus Voltage)
L2-05 (Uv Detection Level)
0V
Input holds KEB operation,
even though voltage has
returned
Output Frequency
KEB deceleration is
triggered by DC bus voltage
0 Hz
288
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Here, L2-01 = 3 and the input terminals have not been set for KEB Ride-Thru (H1-oo does not equal 65, 66, 7A, 7B). After
decelerating for the time set in parameter L2-02, the drive ends KEB operation and attempts to accelerate back to the frequency
reference. A Uv1 fault occurs and the drive output shuts off if the power does not return within the time set to L2-02.
Power Loss longer than L2-02
Power Loss
Power Loss
0V
0V
DC Bus Voltage
L2-11 (Desired DC
Bus Voltage)
0V
L2-02
(Power Loss
Ride-Thru Time)
Output Frequency
L2-02
(Power Loss
Ride-Thru Time)
KEB Deceleration
0 Hz
0 Hz
Here, L2-01 = 3 and an input terminal is set to issue KEB Ride-Thru (H1-oo = 65, 66, 7A, 7B). After decelerating for the
time set in parameter L2-02, the drive checks the DC bus voltage and the status of the digital input. If the DC bus voltage is
still below the level set in L2-11 or if the KEB digital input is still active, KEB deceleration continues. If the voltage level has
risen above the value set to L2-11, then normal operation is resumed.
Note: If L2-10 is set to a longer time than L2-02, the drive checks the DC bus voltage level and the status of the terminal assigned to KEB Ride-Thru
after the time set to L2-02 passes. The drive will then try to restart.
Power loss shorter than L2-02
Power Loss
0V
Power Loss
0V
L2-10
L2-10
Parameter Details
DC bus voltage
0V
0V
L2-02
(Power Loss
Ride-Thru Time)
L2-02
(Power Loss
Ride-Thru Time)
Output Frequency
KEB deceleration is
triggered by DC bus voltage
0 Hz
KEB deceleration is
triggered by DC bus voltage
0 Hz
KEB Ride-Thru Operation as Long as CPU Has Power, KEB Input Not Used
Here, L2-01 = 4 and the input terminals have not been set for KEB Ride-Thru (H1-oo does not equal 65, 66, 7A, 7B). After
decelerating for the time set to parameter L2-10, the drive checks the DC bus voltage level. Deceleration continues if the DC
bus voltage is lower than the level set in L2-11. Normal operation resumes when the DC bus voltage rises above the value of
L2-11.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
289
Power Loss
Power Loss
0V
0V
DC Bus Voltage
L2-11 (Desired DC Bus Voltage)
L2-10
(Min. KEB Operation
Time)
Output Frequency
L2-10
(Min. KEB
Op. Time)
KEB Deceleration
KEB Deceleration
0 Hz
0 Hz
KEB Ride-Thru Operation as Long as CPU Has Power, KEB Input Used
Here, L2-01 = 3 and an input terminal is set to issue KEB Ride-Thru (H1-oo = 65, 66, 7A, 7B). After decelerating for the
time set to parameter L2-10, the drive checks the DC bus voltage and the status of the digital input. Deceleration continues if
the DC bus voltage is still below the level set in L2-11 or if the digital input assigned to KEB Ride-Thru is still active. Normal
operation resumes when the DC bus voltage rises above the value of L2-11 and the terminal that initiated KEB Rid-Thru is
released.
Power loss shorter than L2-10
Power Loss
Power Loss
0V
0V
L2-10 (Min.
KEB
Operation
Time)
Output Frequency
KEB deceleration is
triggered by DC bus voltage
0 Hz
KEB deceleration is
triggered by DC bus voltage
0 Hz
L2-01 = 5
KEB operation ends when the motor has come to a stop, even if the power returns and the digital input terminal that initiated
KEB Ride-Thru is cleared.
290
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B1
B2
L1
R/L1
U/T1
L2
S/L2
V/T2
L3
T/L3
W/T3
UV Detection
Relay
S6 - KEB command 1 or 2
S1 - Start command
SC
Name
C1-09
C2-03
S-Curve at Deceleration
Start
L2-05
Undervoltage Detection
Level
L2-06
L2-07
L2-08
L2-10
Setting Instructions
Increase if an overvoltage fault occurs during KEB deceleration.
Decrease if an undervoltage fault occurs during KEB deceleration.
Shorten if undervoltage occurs immediately after KEB Ride-Thru is
triggered.
Lengthen this setting if overvoltage occurs immediately after KEB
operation starts.
Increase if an undervoltage fault occurs at KEB operation start to let the
drive detect power loss more quickly.
Increase if an overvoltage fault occurs during KEB deceleration
Decrease if an undervoltage fault occurs during KEB deceleration
Adjust to the desired acceleration time. If set to 0, standard acceleration
times are used (C1-01, C1-03, C1-05, C1-07).
Increase if an undervoltage fault occurs immediately after KEB
operation starts.
Decrease if an overvoltage fault occurs immediately after KEB
operation starts.
Increase when a digital input is set for KEB Ride-Thru and an
undervoltage fault occurs after power was lost because the device
controlling the input does not react quickly enough.
If the DC bus voltage overshoots after KEB Ride-Thru begins (and
no input terminal is set to KEB Ride-Thru), increase L2-10 to longer
than the overshoot.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
NO
NO
NO YES YES
291
Parameter Details
Parameter
L2-11
L3-20
L3-21
L3-24
L3-25
Name
Setting Instructions
Set to approximately 1.22 times the input voltage for Single Drive
Desired DC Bus Voltage KEB Ride-Thru 2.
during KEB
Set to approximately 1.4 times the input voltage for Single Drive KEB
Ride-Thru 1 and System KEB Ride-Thru modes.
Increase this setting in steps of 0.1 if overvoltage or undervoltage
Main Circuit Adjustment occurs at the beginning of deceleration
Gain
Reduce if torque ripple occurs during deceleration while executing
KEB Ride-Thru.
Reduce L3-21 in steps of 0.05 if there is a fairly large speed or current
ripple.
Accel/Decel Rate
Decreasing this setting too much can cause a slow DC bus voltage
Calculation Gain
control response, and may lead to problems with overvoltage or
undervoltage.
Motor Acceleration Time Set the motor acceleration time as described on page 299.
Load Inertia Ratio
Set the load/inertia ratio as described on page 299.
NO YES NO
NO
NO YES NO
NO
NO YES NO
NO YES NO
NO
NO
No.
Name
Setting Range
L2-02
0.0 to 25.5 s
Default
Determined by C6-01
and o2-04
Name
Setting Range
L2-03
0.1 to 5.0 s
Default
Determined by C6-01
and o2-04
Name
Setting Range
L2-04
0.0 to 5.0 s
Default
Determined by
C6-01 and o2-04
Name
Setting Range
L2-05
Default
Determined by
A1-02, C6-01, E1-01
and o2-04 <2>
<1> Values are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<2> The default setting for 400 V class drives depends on whether the drive input voltage is over 400 V or under 400 V.
Note: 1. Install an AC reactor option on the input side of the power supply when setting L2-05 below the default value to prevent damage to drive
circuitry.
292
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
L2-06
Setting Range
0.00 to 6000.0
s <1>
Default
0.00 s
<1> Setting range is determined by the accel/decel time units set in C1-10. If the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes
0.00 to 600.00 s.
Name
Setting Range
Default
L2-07
0.00 s
<1> Setting range is determined by the accel/decel time units set in C1-10. If the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes
0.00 to 600.00 s.
Name
Frequency Gain at KEB Start
Setting Range
0 to 300%
Default
100%
Determines the duration of KEB Ride-Thru operation after it is triggered. Refer to KEB Ride-Thru End Detection on page
289.
No.
L2-10
Name
KEB Detection Time
Setting Range
0 to 2000 ms
Default
50 ms
Name
Setting Range
L2-11
Default
Determined by
E1-01
<1> Values are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
No.
L2-29
Name
KEB Method Selection
Setting Range
0 to 3
Default
0
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
293
Parameter Details
Name
Setting Range
0 to
2 <1>
Default
1
Setting 0: Disabled
No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to speed
fast enough, causing an overload fault.
Setting 1: Enabled
Enables Stall Prevention during acceleration. Operation varies depending on the control mode.
V/f Control, V/f Control with PG, and Open Loop Vector Control:
Acceleration is reduced when the output current value exceeds 85% of the level set to parameter L3-02 for a longer than the
time set to L3-27. The acceleration stops when the current exceeds L3-02. Acceleration continues when the current falls
below L3-02 for longer than the time set to L3-27.
The Stall Prevention level is automatically reduced in the constant power range. Refer to L3-03: Stall Prevention Limit
during Acceleration on page 295.
Output current
L3-02
L3-02
-15%
Time
Output frequency
294
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Output current
L3-02
15 % of L3-02
Time
Output frequency
L3-27
L3-27
Time
Deceleration
using L3-22
Figure 5.99 Stall Prevention During Acceleration for Permanent Magnet Motors
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooo.
The drive disregards the selected acceleration time and attempts to accelerate in the minimum time. The acceleration rate is
adjusted so the current does not exceed the value set to parameter L3-02.
Name
Setting Range
0 to 150%
<1>
Default
<1>
Lower L3-02 if stalling occurs when using a motor that is relatively small compared to the drive.
Also set parameter L3-03 when operating the motor in the constant power range.
Name
Stall Prevention Limit during Acceleration
Setting Range
0 to 100%
Default
50%
L3-02
L3-03
Output frequency
E1-06
Base frequency
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
295
Parameter Details
<1> The upper limit and default value is determined by the duty rating and the carrier frequency derating selection (C6-01 and L8-38 respectively).
Name
Deceleration Time at Stall Prevention During Acceleration
Setting Range
0 to 6000.0 s
Default
0.0 s
Name
L3-04
Setting Range
0 to
5 <1> <2>
Default
1
<1> Settings 3 through 5 are not available in OLV/PM. Settings 2 through 5 are not available in AOLV/PM and CLV/PM.
<2> Setting 3 is not available for models CIMR-Ao4A0930 and 4A1200.
Setting 0: Disabled
The drive decelerates according to the set deceleration time. With high inertia loads or rapid deceleration, an overvoltage fault
may occur. If an overvoltage fault occurs, use dynamic braking options or switch to another L3-04 selection.
Setting 1: General-purpose Stall Prevention
The drive tries to decelerate within the set deceleration time. The drive pauses deceleration when the DC bus voltage exceeds
the Stall Prevention level and then continues deceleration when the DC bus voltage drops below that level. Stall Prevention
may be triggered repeatedly to avoid an overvoltage fault. The DC bus voltage level for Stall Prevention depends on the input
voltage setting E1-01.
Drive Input Voltage
200 V Class
400 V Class
600 V Class
Note: 1. Do not use this setting in combination with a Dynamic Braking Resistor or other dynamic braking options. If Stall Prevention during
deceleration is enabled, it will be triggered before the braking resistor option can operate.
2. This method may lengthen the total deceleration time compared to the set value. If this is not appropriate for the application consider using
a dynamic braking option.
Time
specified deceleration time
The drive adjusts the deceleration rate so the DC bus voltage is kept at the level set to parameter L3-17. This produces the
shortest possible deceleration time while protecting the motor from stalling. The selected deceleration time is disregarded and
the achievable deceleration time cannot be smaller than 1/10 of the set deceleration time.
This function uses the following parameters for adjusting the deceleration rate:
DC bus voltage gain (L3-20)
Deceleration rate calculations gain (L3-21)
Inertia calculations for motor acceleration time (L3-24)
296
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Enables the Stall Prevention function while using a dynamic braking resistor. Overvoltage problems in the DC bus can occur
if Stall Prevention during deceleration is disabled (L3-04) in OLV and a dynamic braking option is installed. Set L3-04 to 3
to remedy this situation.
Setting 4: Overexcitation Deceleration 1
Overexcitation Deceleration 1 (increasing the motor flux) is faster than deceleration with no Stall Prevention (L3-04 = 0).
Setting 4 changes the selected decel time and functions to provide protection from an overvoltage trip. Refer to Overexcitation
Deceleration (Induction Motors) on page 315 for details.
Setting 5: Overexcitation Deceleration 2
Overexcitation Deceleration 2 slows down the motor while trying to maintain the DC bus voltage at the level set to parameter
L3-17. This function shortens the achievable deceleration time more than by using Overexcitation Deceleration 1. Setting 5
will shorten/lengthen the decel time to maintain the L3-17 bus level. Refer to Overexcitation Deceleration (Induction
Motors) on page 315 for details.
Name
Stall Prevention Selection During Run
Setting Range
0 to 2
Default
1
Setting 0: Disabled
Drive runs at the set frequency reference. A heavy load may cause the motor to stall and trip the drive with an oC or oL fault.
Setting 1: Decelerate using C1-02
Name
L3-06
Setting Range
30 to 150
<1>
Default
<1>
<1> The upper limit and default for this setting is determined by C6-01 and L8-38.
Name
Automatic Reduction Selection for Stall Prevention During Run
Setting Range
0, 1
Default
0
Setting 0: Disabled
The level set in L3-06 is used throughout the entire speed range.
Setting 1: Enabled
The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
297
Parameter Details
If the current exceeds the Stall Prevention level set in parameter L3-06, the drive will decelerate at decel time 1 (C1-02). When
the current level drops below the value of L3-06 minus 2% for 100 ms, the drive accelerates back to the frequency reference
at the active acceleration time.
Name
Overvoltage Suppression Function Selection
Setting Range
0, 1
Default
0
Setting 0: Disabled
The regenerative torque limit and the output frequency are not adjusted. A regenerative load may trip the drive with an
overvoltage fault. Use this setting if dynamic braking options are installed.
Setting 1: Enabled
When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by decreasing the regenerative
torque limit and increasing the output frequency.
n L3-17: Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention
Sets the target DC bus voltage level used by the overvoltage suppression function (L3-11 = 1), Intelligent Stall Prevention
during deceleration (L3-04 = 2).
No.
L3-17
Name
Target DC Bus Voltage for Overvoltage Suppression
and Stall Prevention
Setting Range
150 to 400 Vdc <1>
Default
370 Vdc
<1> <2>
<1> Values are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but set the
value below 1040 Vdc (overvoltage protection level).
<2> This value is initialized when E1-01 is changed.
Name
Setting Range
L3-20
0.00 to 5.00
Default
Determined by
A1-02
Adjustment for Single Drive KEB 2 (L2-29 = 1) and Intelligent Stall Prevention During Deceleration
Increase this setting slowly in steps of 0.1 if overvoltage or undervoltage occurs at the beginning of deceleration.
Decrease this setting if there is a fair amount of speed or torque ripple.
Adjustment for Overvoltage Suppression
Increase this setting slowly in steps of 0.1 if overvoltage suppression is enabled (L3-11 = 1) and a sudden increase in a
regenerative load causes an overvoltage fault.
298
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
L3-21
0.10 to 10.00
<1>
<1> This value is reset to its default value when the control mode is changed (A1-02). The value shown here is for OLV.
Adjustment for Single Drive KEB 2 (L2-29 = 1) and Intelligent Stall Prevention During Deceleration
Reduce L3-21 in steps of 0.05 if there is a fairly large speed or current ripple.
Small reductions of L3-21 can help solve problems with overvoltage and overcurrent.
Decreasing this setting too much can cause slow DC bus voltage control response and may also lengthen deceleration times
beyond optimal levels.
Adjustment for Overvoltage Suppression
Increase this setting in steps of 0.1 if overvoltage occurs as a result of a regenerative load when overvoltage suppression is
enabled (L3-11 = 1).
Decrease L3-21 in steps of 0.05 if there is a fairly large speed ripple when overvoltage suppression is enabled.
Name
Setting Range
L3-24
0.001 to 10.000 s
Default
Determined by o2-04, C6-01,
E2-11, and E5-01 <1>
<1> Parameter L3-24 is defaulted for a Yaskawa standard 4-pole motor. During Auto-Tuning, L3-24 will be initialized to a Yaskawa standard 4-pole
motor if parameter E2-11 is changed. This value also changes based on the motor code set to E5-01 when using OLV/PM.
Parameter Details
In CLV/PM, use the Inertia Auto-Tuning function to let the drive automatically adjust this parameter. Refer to AutoTuning on page 135.
Manual Parameter Setup
60
2
P Motor[kW] 103
n rated [r/min]
Name
Load Inertia Ratio
Setting Range
1.0 to 1000.0
Default
1.0
When set incorrectly, a fairly large current ripple can result during Single Drive KEB 2 (L2-29 = 1). This may cause overvoltage
suppression (L3-11 = 1) or other faults such as ov, Uv1, and oC.
Automatic Parameter Setup
In CLV for induction motors or PM motors, use the Inertia Auto-Tuning function to let the drive automatically adjust this
parameter. Refer to Auto-Tuning on page 135.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
299
Machine Inertia
Motor Inertia
Name
Additional DC Bus Capacitors
Setting Range
0 to 65000 F
Default
0 F
Name
Stall Prevention Detection Time
Setting Range
0 to 5000 ms
Default
50 ms
Name
Speed Agreement Detection Level
Setting Range
0.0 to 400.0 Hz
L4-02
0.0 to 20.0 Hz
Default
0.0 Hz
Determined by
A1-02
Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection on page 259, Settings 2, 3, 4, and 5.
n L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-)
Parameter L4-03 sets the detection level for the digital output functions Speed agree 2, User-set speed agree 2, Frequency
detection 3, and Frequency detection 4.
Parameter L4-04 sets the hysteresis level for these functions.
No.
L4-03
Name
Speed Agreement Detection Level (+/-)
Setting Range
-400.0 to 400.0 Hz
L4-04
0.0 to 20.0 Hz
Default
0.0 Hz
Determined by
A1-02
Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection on page 259, Settings 13, 14, 15, and
16.
300
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Analog
frequency
reference
10%
400 ms
Loss of
Reference
output
OFF
ON
time
Set H2-01, H2-02, or H2-03 to C for a digital output to trigger when frequency reference loss occurs. Refer to Setting C:
Frequency Reference Loss on page 263 for details on setting the output function.
Parameter L4-05 selects the operation when a frequency reference loss is detected.
No.
L4-05
Name
Frequency Reference Loss Detection Selection
Setting Range
0, 1
Default
0
Setting 0: Stop
Drive follows the frequency reference (which is no longer present) and stops the motor.
Setting 1: Continue operation with reduced frequency reference
The drive will continue operation at the frequency reference value set to parameter L4-06. When the external frequency
reference value is restored, the operation is continued with the frequency reference.
Name
Frequency Reference at Reference Loss
Setting Range
0.0 to 100.0%
Default
80.0%
Parameter Details
Name
Speed Agreement Detection Selection
Setting Range
0, 1
Default
0
The drive can attempt to restart itself following the faults listed below.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
301
Name
Ground Fault
Output Open Phase
Overcurrent
Drive Overheat
Motor Overload
Fault
oL4
ov
PF
rH
rr
Name
Overtorque 2
DC Bus Overvoltage
Input Phase Loss
Braking Resistor Fault
Braking Transistor Fault
oL2
Drive Overload
Uv1
oL3
Overtorque 1
STo
<1> When L2-01 is set to 1 through 4 (continue operation during momentary power loss)
Name
Number of Auto Restart Attempts
Setting Range
0 to 10 Times
Default
0 Times
Name
Auto Restart Fault Output Operation Selection
Setting Range
0, 1
Default
0
Name
Fault Reset Interval Time
Setting Range
0.5 to 600.0 s
Default
10.0 s
Setting Range
0, 1
Default
0
Name
Fault Reset Operation Selection
The drive will continuously attempt to restart. If it restarts successfully, the restart counter is increased. This operation is
repeated each time a fault occurs until the counter reaches the value set to L5-01.
Setting 1: Count restart attempts
The drive will attempt to restart using the time interval set to parameter L5-04. A record is kept of the number of attempts to
restart to the drive, regardless of whether those attempts were successful. When the number of attempted restarts exceeds the
value set to L5-01, the drive stops attempting to restart.
302
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Description
Torque detection 1, N.O. (output closes when overload or underload is detected)
Torque detection 1, N.C. (output opens when overload or underload is detected)
Torque detection 2, N.O. (output closes when overload or underload is detected)
Torque detection 2, N.C. (output opens when overload or underload is detected)
Figure 5.103 and Figure 5.104 illustrate the functions of overtorque and undertorque detection.
Motor current / torque
10 % hysteresis
10 % hysteresis
L6-02/05
L6-03/06
Torque detection 1 (NO)
or
Torque detection 2 (NO)
L6-03/06
ON
ON
10 % hysteresis
L6-02/05
L6-03/06
ON
Parameter Details
L6-03/06
Torque detection 1 (NO)
or
Torque detection 2 (NO)
ON
Name
Torque Detection Selection 1
Torque Detection Selection 2
Setting Range
0 to 8
0 to 8
Default
0
0
Setting 0: Disabled
Setting 1: oL3, oL4 at speed agree (Alarm)
Overtorque detection is active only when the output speed is equal to the frequency reference (i.e., no detection during
acceleration and deceleration). The operation continues after detecting overtorque and triggering an oL3/oL4 alarm.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
303
Overtorque detection works as long as the Run command is active. The operation continues after detecting overtorque and
triggering an oL3/oL4 alarm.
Setting 3: oL3, oL4 at speed agree (Fault)
Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation stops and triggers an oL3/oL4 fault.
Setting 4: oL3, oL4 at run (Fault)
Overtorque detection works as long as a Run command is active. The operation stops and triggers an oL3/oL4 fault.
Setting 5: UL3, UL4 at speed agree (Alarm)
Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation continues after detecting overtorque and triggering a UL3/UL4 alarm.
Setting 6: UL3, UL4 at Run (Alarm)
Undertorque detection works as long as the Run command is active. The operation continues after detecting overtorque and
triggering a UL3/UL4 alarm.
Setting 7: UL3, UL4 at Speed Agree (Fault)
Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation stops and triggers a UL3/UL4 fault.
Setting 8: UL3, UL4 at run (Fault)
Undertorque detection works as long as a Run command is active. The operation stops and triggers a UL3/UL4 fault.
Name
Torque Detection Level 1
Torque Detection Level 2
Setting Range
0 to 300%
0 to 300%
Default
150%
150%
Note: The torque detection level 1 (L6-02) can also be supplied by an analog input terminal set to H3-oo = 7. Here, the analog value has priority
and the setting in L6-02 is disregarded. Torque detection level 2 (L6-05) cannot be set by an analog input.
Name
Torque Detection Time 1
Torque Detection Time 2
Setting Range
0.0 to 10.0 s
0.0 to 10.0 s
Default
0.1 s
0.1 s
304
Name
Mechanical Weakening Detection Operation
Setting Range
0 to 8
Default
0
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Detection when the speed is above L6-09 (signed). Operation continues and triggers an oL5 alarm after detection.
Setting 2: Continue running if the speed is greater than L6-09 (Alarm)
Detection when the speed is above L6-09 (unsigned). Operation continues and triggers an oL5 alarm after detection.
Setting 3: Stop when motor speed is greater than L6-09 (Signed)
Detection when the speed is above L6-09 (signed). Operation stops and triggers an oL5 fault after detection.
Setting 4: Stop when Motor Speed is Greater than L6-09
Detection when the speed is above L6-09 (unsigned). Operation stops and triggers an oL5 fault after detection.
Setting 5: Continue running if the speed is less than L6-09 (Signed) (Alarm)
Detection when the speed is below L6-09 (signed). Operation continues and triggers an oL5 alarm after detection.
Setting 6: Continue running if the speed is less than L6-09 (Alarm)
Detection when the speed is below L6-09 (unsigned). Operation continues and triggers an oL5 alarm after detection.
Setting 7: Stop when Motor Speed is less than L6-09 (Signed)
Detection when the speed is below L6-09 (signed). Operation stops and triggers an oL5 fault after detection.
Setting 8: Stop when motor speed is less than L6-09
Detection when the speed is below L6-09 (unsigned). Operation stops and triggers an oL5 fault after detection.
Name
Mechanical Weakening Detection Speed Level
Setting Range
-110.0 to 110.0%
Default
110%
Name
Mechanical Weakening Detection Time
Setting Range
0.0 to 10.0 s
Default
0.1 s
Name
Mechanical Weakening Detection Start Time
Setting Range
0 to 65535 h
Default
0h
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
305
Parameter Details
Sets the time permitted for the situation selected in parameter L6-08 to arise before detecting mechanical weakening.
Quadrant 2
Quadrant 1
Quadrant 3
Quadrant 4
Name
Forward Torque Limit
Reverse Torque Limit
Forward Regenerative Torque Limit
Reverse Regenerative Torque Limit
Setting Range
0 to 300%
0 to 300%
0 to 300%
0 to 300%
Default
200%
200%
200%
200%
Note: If the multi-function analog input is programmed for 10: Forward torque limit, 11: Reverse torque limit, 12: Regenerative torque limit,
or 15: General torque limit, the drive uses the lowest value from L7-01 through L7-04, or analog input torque limit.
Name
Torque Limit Integral Time Constant
Setting Range
5 to 10000 ms
Default
200 ms
Name
Torque Limit Control Method Selection during Accel/Decel
Setting Range
0, 1
Default
0
The torque limit function works with P control during accel and decel, and switches to I control at constant speed. Use this
setting when accelerating or decelerating to the desired speed has priority over the torque limit during speed changes.
Setting 1: Integral control
The torque limit function always uses I control. Use this setting when a highly accurate torque limit is required, even during
speed changes. Using this function may increase the acceleration time, or prevent the motor speed from reaching the frequency
reference if the torque limit is reached first.
306
Name
Torque Limit Process at Start
Setting Range
0, 1
Default
1
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Torque limit is created at start without a delay time. Disable L7-16 to maximize the response time when the application requires
sudden acceleration or deceleration at start.
Setting 1: Enabled
No.
L8-01
Name
Internal Dynamic Braking Resistor Protection Selection
(ERF type)
Setting Range
0, 1
Default
Determined by
C6-01 and o2-04
Setting 0: Disabled
Disables braking resistor protection. Use this setting for any dynamic braking option other than the Yaskawa ERF-type resistor.
Setting 1: Enabled
Name
Setting Range
L8-02
50 to 150 C
Default
Determined by
C6-01 and o2-04
Setting Range
0 to 4
Default
3
Parameter Details
No.
L8-03
Name
Overheat Pre-Alarm Operation Selection
If an overheat alarm occurs, the drive decelerates to stop using the currently selected deceleration time. If a digital output is
programmed for fault (H2-oo = E), this output will be triggered.
Setting 1: Coast to stop
If an overheat alarm occurs, the drive switches off the output and the motor coasts to stop. If a digital output is programmed
for fault (H2-oo = E), this output will be triggered.
Setting 2: Fast Stop
If an overheat alarm occurs, the drive decelerates to stop using the Fast Stop time (C1-09). If a digital output is programmed
for fault (H2-oo = E), this output will be triggered.
Setting 3: Alarm only
If an overheat alarm occurs, an alarm is output and the drive continues operation.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
307
If an overheat alarm occurs, the operation continues with the speed reduced to the level set to parameter L8-19. If the oH alarm
is still present after 10 s, the speed is reduced again. The amount of speed reduction depends on how often the alarm repeats.
If the oH alarm disappears while the drive is operating at a reduced speed, the drive will switch to the previous speed in 10 s
increments until reaching base frequency. Figure 5.106 explains the operation with reduced speed during an oH alarm. A
digital output programmed for 4D is switched when the oH alarm is still active after ten reduction cycles.
Output frequency
10 s
10 s
10 s
10 s
10 s
10 s
10 s
fref
fref (L8-19)
fref (L8-19)2
fref (L8-19)
oH
Alarm
oH
Alarm
Reset oH
Alarm
Reset oH
Alarm
oH
Alarm
etc.
oH
Alarm
fref (L8-19)4
time
oH alarm number
Digital ouput (4D)
Name
Frequency Reduction Rate During Overheat Pre-Alarm
Setting Range
0.1 to 0.9
Default
0.8
Setting Range
0, 1
Default
1
Name
Input Phase Loss Protection Selection
Setting 0: Disabled
Setting 1: Enabled
Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage
imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
The drive is decelerating.
No Run command is active.
Output current is less than or equal to 30% of the drive rated current.
308
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Output Phase Loss Protection Selection
Setting Range
0 to 2
Default
1
Setting 0: Disabled
Setting 1: Fault when one phase is lost
An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.
Setting 2: Fault when two phases are lost
An output phase loss fault (LF) is triggered when two output phases are lost. The output shuts off and the motor coasts to stop.
Name
Output Ground Fault Detection Selection
Setting Range
0, 1
Default
1
Setting 0: Disabled
A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.
Name
Heatsink Cooling Fan Operation Selection
Setting Range
0, 1
Default
0
The fan is switched on when a Run command is active and switched off with the delay set to parameter L8-11 after releasing
the Run command. This setting extends the fan lifetime.
Setting 1: Run always
Name
Heatsink Cooling Fan Off-Delay Time
Setting Range
0 to 300 s
Default
60 s
Name
Ambient Temperature Setting
Setting Range
-10 to 50 C
Default
40 C
No.
L8-15
Name
oL2 Characteristics Selection at Low Speed
Setting Range
0, 1
Default
1
The overload protection level is not reduced. Frequently operating the drive with high output current at low speed can lead to
premature drive faults.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
309
The overload protection level (oL2 fault detection level) is automatically reduced at speeds below 6 Hz. At zero speed, the
overload is derated by 50%.
No.
L8-18
Name
Software Current Limit Selection
Setting Range
0, 1
Default
0
The drive may trip on an oC fault if the load is too heavy or the acceleration is too short.
Setting 1: Software CLA enabled
When the Software CLA current level is reached, the drive reduces the output voltage to reduce the current. Normal operation
continues when the current level drops below the Software CLA level.
Adjusts the overcurrent detection level in OLV/PM, AOLV/PM, or CLV/PM. A setting of 100% is equal to the motor rated
current. When the drive rated current is considerably higher than the motor rated current, use this parameter to decrease the
overcurrent level and prevent motor demagnetization from high current.
Overcurrent detection uses the lower value between the overcurrent level for the drive and the motor rated current multiplied
by L8-27.
No.
L8-27
Name
Overcurrent Detection Gain
Setting Range
0.0 to 300.0%
Default
300.0%
Enables or disables output current unbalance detection in OLV/PM, AOLV/PM, or CLV/PM. Current unbalance can heat a
PM motor and demagnetize the magnets. The current unbalance detection function monitors output current and triggers the
LF2 fault to prevent such motor damage.
No.
L8-29
Name
Current Unbalance Detection (LF2)
Setting Range
0, 1
Default
1
Setting 0: Disabled
The LF2 fault is triggered if an output current unbalance is detected. Drive output shuts off and the motor coasts to stop.
n L8-32: Main Contactor and Cooling Fan Power Supply Failure Selection
Determines drive operation when a FAn fault occurs.
No.
L8-32
Name
Main Contactor and Cooling Fan Power Supply Failure Selection
Setting Range
0 to 4
Default
1
The drive stops the motor using the deceleration time set in parameter C1-02.
Setting 1: Coast to stop
The drive output is switched off and the motor coasts to a stop.
Setting 2: Fast stop
The drive stops the motor using the Fast stop time set in parameter C1-09.
310
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
The operation is continued and a FAn alarm is displayed on the digital operator.
Setting 4: Operation with reduced speed
The operation is continued, but the speed is reduced to the level set in parameter L8-19.
Note: FAn is detected as an error when Settings 0 or 2 are selected; it is detected as an alarm when Settings 3 or 4 are selected.
No.
Name
Setting Range
Default
L8-35
0 to 3
<1>
For an Open Type enclosure drive installed with at a minimum of 30 mm space to the next drive or a cabinet wall.
Setting 1: Side-by-Side mounting
For drives mounted according to Yaskawa Side-by-Side specifications (requires 2 mm between drives).
Setting 2: IP20/NEMA Type 1 enclosure
For finless drives or a standard drive mounted with the heatsink outside the cabinet or enclosure panel.
No.
Name
Setting Range
L8-38
0 to 2
Default
Determined by
A1-02, C6-01 and
o2-04
Setting 0: Disabled
The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive
returns to the normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.
Setting 2: Enabled for entire frequency range
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
Selects the operation of the carrier frequency reduction function. Reduces the carrier frequency when the output current exceeds
a certain level. This temporarily increases the overload capability (oL2 detection), allowing the drive to run through transient
load peaks without tripping.
311
Name
Setting Range
L8-40
0.00 to 2.00 s
Default
Determined by
A1-02
Name
High Current Alarm Selection
Setting Range
0, 1
Default
0
Setting 0: Disabled
No alarm is detected.
Setting 1: Enabled
An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an alarm
(H2-oo = 10) will close.
No.
L8-55
Name
Internal Braking Transistor Protection
Setting Range
0, 1
Default
0
Setting 0: Disabled
Disable braking transistor protection when not using the internal braking transistor, including the following instances:
When using a regen converter such as DC5.
When using a regen unit such as RC5.
When using external braking transistor options like CDBR units.
When using the drive in common DC bus applications and the internal braking chopper is not installed.
Enabling L8-55 under such conditions can incorrectly trigger a braking transistor fault (rr).
Setting 1: Enabled
Enable L8-55 when connecting a braking resistor or a braking resistor unit to the drive built-in braking transistor.
Models CIMR-Ao2A0004 to 2A0138, 4A0002 to 4A0072, and 5A0003 to 5A0052 come with a built-in braking transistor.
No.
L8-78
Name
Power Unit Output Phase Loss Protection
Setting Range
0, 1
Default
1
Setting 0: Disabled
Setting 1: Enabled
312
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
5.9
n: Special Adjustments
These parameters control a variety of specialized adjustments and functions, including Hunting Prevention, AFR Control,
High Slip Braking, resistance between motor lines, and PM motor control functions.
No.
n1-01
Name
Hunting Prevention Selection
Setting Range
0, 1
Default
1
Setting Range
0.00 to 2.50
Default
1.00
Setting 0: Disabled
Setting 1: Enabled
Name
Hunting Prevention Gain Setting
Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases.
If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases.
Name
Setting Range
n1-03
0 to 500 ms
Default
Determined by
o2-04
Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
Increase this value for applications with a large load inertia. A higher setting leads to slower response, which can result in
oscillation at lower frequencies.
Lower this setting if oscillation occurs at low speed.
No.
n1-05
Name
Hunting Prevention Gain while in Reverse
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0.00 to 2.50
Default
0.00
313
Parameter Details
Determines the responsiveness of the Hunting Prevention function (affects the primary delay time for Hunting Prevention).
Name
AFR Gain
Setting Range
0.00 to 10.00
Default
1.00
Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
If hunting occurs, increase the setting value in steps of 0.05 while checking the response.
If response is low, decrease the setting value in steps of 0.05 while checking the response.
Name
AFR Time Constant 1
AFR Time Constant 2
Setting Range
0 to 2000 ms
0 to 2000 ms
Default
50 ms
750 ms
Note: Setting parameter n2-02 higher than n2-03 will trigger an oPE08 error.
Although these parameters rarely need to be changed, they may require adjustment in the following situations:
If hunting occurs, increase n2-02. If response is low, decrease it.
Increase n2-03 if overvoltage occurs with high inertia loads at the end of acceleration or with sudden load changes.
If setting n2-02 to a higher value, increase C4-02 (Torque Compensation Delay Time Constant 1) proportionally.
If setting n2-03 to a higher value, increase C4-06 (Torque Compensation Delay Time Constant 2) proportionally.
The set deceleration time is ignored during HSB. Use Overexcitation Deceleration 1 (L3-04 = 4) or a dynamic braking option
to stop the motor within a specified time.
Braking time varies based on the load inertia and motor characteristics.
Enabling HSB and KEB Ride-Thru simultaneously will trigger an oPE03 error.
HSB must be triggered by a digital input set to H1-oo = 68. After the HSB command is given, the drive will not restart
until the motor is completely stopped and the Run command is cycled.
Use parameters n3-01 through n3-04 to adjust HSB.
314
Name
High Slip Braking Deceleration Frequency Width
Setting Range
1 to 20%
Default
5%
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
n3-02
100 to 200%
Default
Determined by
C6-01 and L8-38
Name
High Slip Braking Dwell Time at Stop
Setting Range
0.0 to 10.0 s
Default
1.0 s
Name
High Slip Braking Overload Time
Setting Range
30 to 1200 s
Default
40 s
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
315
Parameter Details
Name
Overexcitation Deceleration Gain
Setting Range
1.00 to 1.40
Default
1.10
The optimum setting for n3-13 depends on the motor flux saturation characteristics.
Gradually increase the gain to 1.25 to 1.30 to improve the braking power of Overexcitation Deceleration.
Lower n3-13 when flux saturation characteristics cause overcurrent. A high setting sometimes causes overcurrent (oC),
motor overload (oL1), or drive overload (oL2). Lowering n3-21 can also help remedy these problems.
Name
High Frequency Injection During Overexcitation Deceleration
Setting Range
0, 1
Default
0
Setting 0: Disabled
Setting 1: Enabled
Name
High Slip Suppression Current Level
Setting Range
0 to 150%
Default
100%
Name
Overexcitation Operation Selection
Setting Range
0 to 2
Default
0
316
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Enabling Feed Forward improves the responsiveness of the drive to speed reference changes in applications where a high
speed control proportional gain setting (ASR gain, C5-01, C5-03) would lead to problems with overshoot, undershoot, or
oscillation. Figure 5.107 gives an example of overshoot reduction by Feed Forward. Parameters related to this function and
the function principle are illustrated in Figure 5.108. Feed Forward can only be used in CLV, CLV/PM, or AOLV/PM (A1-02
= 4, 6, or 7).
900
750
Suppresses
overshoot at the
end of acceleration
1050
Overshoot
0.5
1050
900
750
0.5
Time (s)
Time (s)
U1-20
Feed Forward
Control
n5-02/03
+
Frequency
Reference
ASR P and I
C5-01/02/03/04
Speed
Feedback
U6-25
Torque reference
U1-09
ASR Output
Name
Feed Forward Control Selection
Setting Range
0, 1
Default
0
Setting 0: Disabled
Setting 1: Enabled
Parameter Name
Setting Range
n5-02
0.001 to 10.000 s
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
Frequency
reference after
Soft Starter
Default
Determined by
C6-01, E5-01 and
o2-04
317
The motor acceleration time can be calculated by one of the following formulas:
n5-02 =
Where:
JMotor is the motor inertia in kgm/s2.
nrated is the rated speed of the motor in r/min.
Trated is the rated torque of the motor in Nm.
JMotor nrated
30 Trated
or
n5-02 =
4 JMotor frated
p Trated
Where:
JMotor is the motor inertia in kgm/s2.
frated is the rated frequency of the motor in Hz.
p is the number of motor poles (not pole pairs).
Trated is the rated torque of the motor in Nm.
Take the following steps when measuring the motor acceleration time:
1.
2.
3.
4.
5.
6.
7.
8.
Parameter Name
Feed Forward Control Gain
Setting Range
0.00 to 100.00
Default
1.00
Set this value automatically with Inertia Auto-Tuning. If Inertia Auto Tuning cannot be performed, determine the value for
parameter n5-03 using the following steps:
1.
2.
3.
4.
5.
6.
7.
Reverse the parameter settings above and calculate the set value for parameter n5-03 using the formula below.
Set the frequency reference equal to a value in the upper speed range of the machine (fref_Test).
While monitoring the motor speed in U1-05, start the motor in the forward direction and measure the time it takes to
reach the rated speed (taccel).
n5-03 =
318
taccel TLim_Test
n5-02
frated
fref_Test 100
-1
Where:
taccel is the measured acceleration time in s.
frated is the rated frequency of the motor in Hz.
TLim_Test is torque limit setting during the test.
fref_Test is the frequency reference during the test in Hz.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Online Tuning Selection
Setting Range
0 to 2
Default
0
Setting 0: Disabled
Setting 1: Line-to-line resistance tuning
This setting enables line-to-line resistance online tuning. This procedure is effective for speed values up to 6 Hz and improves
the overload capacity in the low speed range by adjusting the value set for the motor resistance.
Setting 2: Voltage correction
The drive adjusts the output voltage during run to improve overload tolerance and minimize the effects of high temperatures
on speed accuracy.
Note: This setting can only be selected when the Energy Saving function is disabled (b8-01 = 0).
Name
Online Tuning Gain
Setting Range
0.10 to 5.00
Default
1.00
These parameters adjust the control performance in the vector control modes for permanent magnet motors.
Parameter Details
Sets the current used for the initial rotor position estimation as a percentage of the motor rated current.
No.
n8-01
Name
Initial Rotor Position Estimation Current
Setting Range
0 to 100%
Default
50%
Sets the current that is applied to pull the rotor into position after the initial rotor position estimations are complete. The value
is set as a percentage of the motor rated current. Increase this setting to increase the starting torque.
No.
n8-02
Name
Pole Attraction Current
Setting Range
0 to 150%
Default
80%
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
319
Name
Initial Rotor Position Detection Selection
Setting Range
0 to 2
Default
1
Setting 0: Pull in
High frequency is injected to detect the rotor position. Some noise may be generated from the motor at start.
Setting 2: Pulse injection
A pulse signal is injected into the motor to detect the rotor position.
Sets the gain for internal speed feedback detection control. Although this parameter rarely needs to be changed, adjustment
may be necessary under the following conditions:
Increase this setting if motor oscillation or hunting occurs.
Decrease this setting in increments of 0.05 to decrease drive responsiveness.
No.
n8-45
Name
Speed Feedback Detection Control Gain
Setting Range
0.00 to 10.00
Default
0.80
Sets the time constant for pull-in current to match the actual current.
Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions:
Increase this setting when it takes too long for the reference value of the pull-in current to match the target value.
Decrease this setting if motor oscillation occurs.
No.
n8-47
Name
Pull-In Current Compensation Time Constant
Setting Range
0.0 to 100.0 s
Default
5.0 s
Sets the d-Axis current during no-load operation at a constant speed. Set as a percentage of the motor rated current.
Increase this setting when hunting occurs or the motor speed is unstable while running at a constant speed.
Slightly reduce this value if there is too much current when driving a light load at a constant speed.
No.
n8-48
Name
Pull-In Current
Setting Range
20 to 200%
Default
30%
Sets the d-Axis current reference when running with high load at constant speed. When using an IPM motor, this parameter
uses the reluctance torque to increase the efficiency and reduce energy consumption. Set this parameter to 0 when using an
SPM motor.
Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions:
Lower the setting if motor operation is unstable when driving heavy loads.
If motor parameters (E5-oo) have been changed, this value will be reset to 0 and will require readjustment.
320
No.
Name
Setting Range
n8-49
-200.0 to 0.0%
Default
Determined by
E5-01
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Sets the pull-in current during acceleration and deceleration as a percentage of the motor rated current (E5-03).
Adjustment may be necessary under the following conditions:
Increase this setting when a large amount of starting torque is required.
Lower this setting if there is excessive current during acceleration.
No.
n8-51
Name
Acceleration/Deceleration Pull-In Current
Setting Range
0 to 200%
Default
50%
Name
Voltage Error Compensation Time Constant
Setting Range
0.00 to 10.00
Default
1.00
Sets the ratio between motor inertia and the inertia of the connected machinery. If this value is set too low, the motor may not
start very smoothly and trigger an STo (Motor Step-Out) fault.
Increase this setting for large inertia loads or to improve speed control response. A high setting with low inertia load may
cause oscillation.
Name
Load Inertia
Setting Range
0 to 3
Default
0
The inertia ratio between the motor and the load is lower than 1:10.
Setting 1: Between 1:10 and 1:30
The inertia ratio between the motor and the load is between 1:10 and 1:30. Set n8-55 to 1 if an STo fault occurs as a result of
impact load or sudden acceleration/deceleration when n8-55 = 0.
Setting 2: Between 1:30 and 1:50
The inertia ratio between the motor and the load is between 1:30 and 1:50. Set n8-55 to 2 if an STo fault occurs as a result of
impact load or sudden acceleration/deceleration when n8-55 = 1.
Setting 3: Beyond 1:50
The inertia ratio between the motor and the load is higher than 1:50. Set n8-55 to 3 if an STo fault occurs as a result of impact
load or sudden acceleration/deceleration when n8-55 = 2.
Name
High Frequency Injection
Setting Range
0, 1
Default
0
Setting 0: Disabled
Disable n8-57 with SPM motors. The speed control range will be limited to approximately 1:20.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
321
Parameter Details
No.
n8-55
Enable n8-57 with IPM motors. This allows precise speed detection in a speed control range of approximately 1:100.
Note: 1. This function generates some audible noise in the motor up to a certain speed.
2. Set E1-09 to 0.0 when using zero speed control.
Name
Setting Range
0.0 to 230.0
Vac <1>
Default
200 Vac <1>
<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives. Multiply value by 2.875 for 600 V class drives.
Sets the gain for internal speed feedback detection control when overvoltage suppression is active. Although this setting rarely
needs to be changed, adjustment may be necessary under the following conditions:
Increase this setting if motor oscillation or hunting occurs when ov suppression is active.
Decrease this setting in increments of 0.05 to decrease the drive responsiveness during ov suppression.
No.
n8-65
Name
Speed Feedback Detection Control Gain during ov Suppression
(OLV/PM)
Setting Range
Default
0.00 to 10.00
1.50
No.
n8-69
Name
Speed Calculation Gain
Setting Range
0.00 to 20.00
Default
1.00
No.
n8-84
322
Name
Polarity Judge Current
Setting Range
0 to 150%
Default
100%
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
o1-01
Setting Range
104 to 813
U1-04 (Control Mode) to
U8-13 (DWEZ Custom
Monitor 3) <1>
Default
106 (U1-06)
Name
User Monitor Selection after Power Up
Setting Range
1 to 5
Default
1
Name
Setting Range
o1-03
0 to 3
Default
Determined by
A1-02
Set the value used for the maximum frequency reference to o1-10. Set the placement of the decimal point in this number to
o1-11.
For example, to have the maximum output frequency displayed as 100.00, set o1-10 = 1000 and o1-11 = 2 (i.e., 1000 with
2 decimal points).
Note: 1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
U1-01: frequency reference
U1-02: output frequency
U1-05: motor speed
U1-16: output frequency after softstarter (accel/decel ramp generator)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
323
Parameter Details
Determines the units used for the frequency reference when setting parameters that create the V/f pattern: E1-04, E1-06, E1-09,
E1-11, and E2-04. For motor 2, this includes parameters E3-04, E3-06, E3-07, E3-09, and E3-11. Enabled only in vector
control modes (CLV, AOLV/PM, CLV/PM).
No.
o1-04
Name
V/f Pattern Display Unit
Setting Range
0, 1
Default
0
Default
Determined by
o1-03
Setting 0: Hertz
Setting 1: r/min
Note: For motor 2, o1-04 can only be set to 0 for Hertz.
Name
Setting Range
o1-10
1 to 60000
Name
Setting Range
o1-11
0 to 3
Default
Determined by
o1-03
Name
LO/RE Key Function Selection
Setting Range
0, 1
Default
1
Setting 0: Disabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL is
selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections
thoroughly before making any setting changes to o2-01 and b1-07. Table 5.43 lists the setting combinations for o2-01 and b1-07.
324
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
o2-01
0
b1-07
0
1
0
1
1
Name
STOP Key Function Selection
Setting Range
0, 1
Default
1
Setting 0: Disabled
Setting 1: Enabled
The STOP key will terminate drive operation even if the Run command source is not assigned to the digital operator. Cycle
the Run command to restart the drive if the drive has been stopped by pressing the STOP key.
Name
User Parameter Default Value
Setting Range
0 to 2
Default
0
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the
ENTER key saves the values and returns the display to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for User Initialize are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values and
returns the display to 0.
No.
Name
Setting Range
o2-04
Default
Determined by
drive capacity
Name
Frequency Reference Setting Method Selection
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0, 1
Default
0
325
Parameter Details
The ENTER key must be pressed every time the frequency reference is changed using the digital operator for the drive to
accept the change.
Setting 1: ENTER key not required
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital operator.
The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after remaining unchanged
for 5 seconds.
Name
Digital Operator Disconnection Operation
Setting Range
0, 1
Default
1
The operation stops and triggers an oPr fault. The motor coasts to stop.
No.
o2-07
Name
Motor Direction at Power Up when Using Operator
Setting Range
0, 1
Default
0
Setting 0: Forward
Setting 1: Reverse
Name
Copy Function Selection
Setting Range
0 to 3
Default
0
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
326
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Copy Allowed Selection
Setting Range
0, 1
Default
0
Setting 0: Disabled
Setting 1: Enabled
No.
o4-01
Name
Cumulative Operation Time Setting
Setting Range
0 to 9999 h
Default
0h
Name
Cumulative Operation Time Selection
Setting Range
0, 1
Default
0
The drive logs the time it is connected to a power supply, regardless of whether the motor is running.
Setting 1: Run time
The drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)
and when there is voltage output.
Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03
also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after
replacing the cooling fan.
Note: 1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. 300
will be displayed in monitor U4-03.
2. The cooling fan may require maintenance at an earlier date in harsher environments.
No.
o4-03
Name
Cooling Fan Operation Time Setting
Setting Range
0 to 9999 h
Default
0h
No.
o4-05
Name
Capacitor Maintenance Setting
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Setting Range
0 to 150%
Parameter Details
Default
0%
327
No.
o4-07
Name
DC Bus Pre-charge Relay Maintenance Setting
Setting Range
0 to 150%
Default
0%
No.
o4-09
Name
IGBT Maintenance Setting
Setting Range
0 to 150%
Default
0%
Name
U2, U3 Initialization
Setting Range
0, 1
Default
0
Setting 0: No action
The drive keeps the previously saved record concerning fault trace and fault history.
Setting 1: Reset fault data
Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and
returns the display to 0.
Name
kWh Monitor Initialization
Setting Range
0, 1
Default
0
Setting 0: No Action
Resets the kWh counter. The monitors U4-10 and U4-11 will display 0 after they are initialized. Setting o4-12 to 1 and
pressing the ENTER erases kWh data and returns the display to 0.
Name
Number of Run Commands Counter Initialization
Setting Range
0, 1
Default
0
Setting 0: No Action
Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the
counter value and returns the display to 0.
328
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u q: DriveWorksEZ Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
u T: Motor Tuning
Parameter Details
Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.
Refer to Auto-Tuning on page 135 for details on Auto-Tuning parameters.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
329
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
331
332
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
6
Troubleshooting
This chapter provides descriptions of the drive faults, alarms, errors, related displays, and guidance for
troubleshooting. This chapter can also serve as a reference guide for tuning the drive during a trial run.
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
SECTION SAFETY...............................................................................................334
MOTOR PERFORMANCE FINE-TUNING...........................................................336
DRIVE ALARMS, FAULTS, AND ERRORS........................................................342
FAULT DETECTION.............................................................................................347
ALARM DETECTION...........................................................................................365
OPERATOR PROGRAMMING ERRORS............................................................374
AUTO-TUNING FAULT DETECTION..................................................................379
COPY FUNCTION RELATED DISPLAYS...........................................................384
DIAGNOSING AND RESETTING FAULTS.........................................................386
TROUBLESHOOTING WITHOUT FAULT DISPLAY..........................................388
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
333
6.1
Section Safety
DANGER
Electrical Shock Hazard
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may illustrate drives without covers or safety shields to display details. Be sure to reinstall covers
or shields before operating the drives and run the drives according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not touch terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the drive
input power is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before
touching any components.
After blowing a fuse or tripping a GFCI, do not attempt to restart the drive or operate peripheral devices until five
minutes pass and CHARGE lamp is OFF.
Failure to comply could result in death, serious injury, and damage to the drive.
Check wiring and peripheral device ratings to identify the cause of trips.
Contact your supplier if the cause cannot be identified.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation,
adjustment and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry, or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work
on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming drive input power before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
334
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
NOTICE
Troubleshooting
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires
and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Carefully review instruction manual TOBPC72060000 when connecting a dynamic braking option to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for modification of the product made by the user.
Check all the wiring after installing the drive and connecting other devices to ensure that all connections are correct.
Failure to comply could result in damage to the drive.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
335
6.2
This section offers helpful information for counteracting oscillation, hunting, and other problems that occur while performing
a trial run. Refer to the section below that corresponds to the motor control method used.
Note: This section describes commonly edited parameters that may be set incorrectly. Consult Yaskawa for more information on detailed settings
and for fine-tuning the drive.
Parameter No.
Corrective Action
Increase
the setting when motor hunting and oscillation occur
Hunting Prevention Gain with a light
load.
(n1-02)
Reduce the setting if hunting occurs when using a motor with a
relatively low inductance, such as a high-frequency motor or a
motor with a larger frame size.
Default
Suggested
Setting
1.00
0.10 to 2.00
1 (2 kHz)
1 to max. setting
200 ms
100 to 1000 ms
1.00
0.50 to 1.50
Motor noise
Carrier Frequency
Motor hunting and
oscillation at speeds up Selection (C6-02)
to 40 Hz
Torque Compensation
Primary Delay Time
(C4-02)
Reduce the setting if motor torque and speed response are too
slow.
Increase the setting if motor hunting and oscillation occur.
Torque Compensation
Gain (C4-01)
Depends on
o2-04, Drive Default setting
Model
5 V
Selection
0.0
(no slip
compensation)
0.5 to 1.5
<1> ASR in V/f Control with PG only controls the output frequency, and does not allow the same high gain settings as CLV control.
<2> Refer to C5: Automatic Speed Regulator (ASR) on page 199 for details on ASR.
336
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Torque Compensation
Primary Delay Time
Constant 1 (C4-02)
Slip Compensation
Primary Delay Time
Constant (C3-02)
Corrective Action
Default
Suggested
Setting
1.00
0.50 to 2.00
50 ms
50 to 2000 ms
750 ms
750 to 2000 ms
150 ms
150 to 750 ms
20 ms
20 to 100 ms
200 ms
100 to 500 ms
1.0
0.5 to 1.5
Motor noise
Motor hunting and
oscillation occur at
speeds below 10 Hz
Carrier Frequency
Selection (C6-02)
Troubleshooting
Problem
When using OLV, leave the torque compensation gain (C4-01) at its default setting of 1.00.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
337
Parameter No.
Motor noise
Control motor hunting Carrier Frequency
and oscillation occur at Selection (C6-02)
speeds below 3 Hz
Overshoot or undershoot
when the speed changes
with high inertia load
Suggested
Setting
20.00
10.00 to 50.00
0.500 s
0.300 to 1.000 s
Switch the drive between two different ASR proportional gain and
integral time settings based on the output frequency.
0.0 Hz
0.004 s
0.004 to 0.020 s
ASR Proportional Gain 1 Gradually increase the ASR gain setting in increments of 5 if
motor torque and speed response are too slow.
(C5-01)
Reduce
the setting if motor hunting and oscillation occur.
ASR Proportional Gain 2
(C5-03)
Only adjust parameter C5-03 when C5-05 > 0.
<1>
Perform ASR Auto-Tuning if possible.
ASR Integral Time 1
Reduce the setting if motor torque and speed response are too
(C5-02)
slow.
ASR Integral Time 2
Increase
the setting if motor hunting and oscillation occur.
(C5-04)
<1>
Only adjust parameter C5-04 when C5-05 > 0.
Default
Corrective Action
<1> Refer to C5: Automatic Speed Regulator (ASR) on page 199 for details on ASR.
338
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Undesirable motor
performance
Parameter No.
Motor parameters
(E1-oo, E5-oo)
DC Injection Braking
Current (b2-02), DC
Oscillation at start or the Injection Time at Start
motor stalls
(b2-03)
Load Inertia Ratio
(n8-55)
Corrective Action
Check the settings for base and maximum frequency in the
E1-oo parameters.
Check E5-oo parameters and set motor data correctly. Do
not enter line-to-line data where single-phase data is required,
and vice versa.
Perform Auto-Tuning.
Adjust parameter n8-55 to meet the load inertia ratio of the
machine.
Increase the speed feedback detection gain (n8-45).
Default
Suggested
Setting
0
0.8
50%
Increase in steps
of 5%
b2-03 = 0.5 s
b2-02 = 50%
b2-02 if
b2-03 = 0.0 s Increase
needed
Pull-In Current
Compensation Time
Constant (n8-47)
5.0 s
Reduce in
increments
of 0.2 s
30%
Increase in
increments of 5%
Hunting or oscillation
occur
Speed feedback
Detection Gain (n8-45)
0.8
Increase in
increments 0.05
Induced Voltage
Constant
(E5-09 or E5-24)
Stalling or oscillation
occur when load is
applied during constant
speed
Troubleshooting
Problem
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
339
Parameter No.
Corrective Action
ASR Proportional Gain 1 Gradually increase the setting in increments of 5 if motor torque
and speed response are too slow.
(C5-01)
ASR Proportional Gain 2 Reduce the setting if motor hunting and oscillation occur.
(C5-03)
Only adjust parameter C5-03 when C5-05 > 0.
Reduce the setting if motor torque and speed response are too
ASR Integral Time 1
slow.
(C5-02)
ASR Integral Time 2
Increase the setting if motor hunting and oscillation occur.
(C5-04)
Only adjust parameter C5-04 when C5-05 > 0.
Default
Suggested
Setting
10.00
5.00 to 30.00
0.500 s
0.300 to
1.000 s <1>
<1>
Switch the drive between two different ASR proportional gain and
integral time settings based on the output frequency.
0.0%
0.0 to
Max r/min
Increase the setting if the load is less rigid and subject to oscillation.
0.010 s
0.016 to
0.035 s <1>
Motor parameters
(E1-oo, E5-oo)
Default
Suggested
Setting
20.00
10.00 to
50.00 <1>
0.500 s
0.300 to
1.000 s <1>
<1> Optimal settings will differ between no-load and loaded operation.
Parameter No.
Corrective Action
ASR Proportional Gain 1 Gradually increase the setting in increments of 5 if motor torque
and speed response are too slow.
(C5-01)
ASR Proportional Gain 2 Reduce the setting if motor hunting and oscillation occur.
(C5-03)
Perform ASR Gain Auto-Tuning if possible
Reduce the setting if torque and speed response are too slow.
Increase the setting if motor hunting and oscillation occur.
Switch the drive between two different ASR proportional gain and
integral time settings based on the output frequency.
0.0%
0.0 to
Max r/min
Increase the setting if the load is less rigid and subject to oscillation.
0.016 s
0.004 to
0.020 s <1>
<1> Optimal settings will differ between no-load and loaded operation.
340
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Application
Prevents motor speed loss by maintaining the output frequency when working with heavy loads or when there
is powerful backlash on the machine side.
Balances the load between two motors driving the same load when A1-02 is set to 3 or 7.
Adjusting accel and decel times will affect the torque presented to the motor during acceleration or
deceleration.
Prevents shock at the beginning and end of acceleration and deceleration.
Skips over the resonant frequencies of connected machinery.
Prevents fluctuation in the analog input signal due to noise.
Stall Prevention
(L3-01 through L3-06, L3-11)
Prevents motor speed loss and overvoltage when the load is too heavy or during sudden acceleration/
deceleration.
Adjustment is not normally necessary because Stall Prevention is enabled as a default. Set L3-04 to 0 to
disable Stall Prevention during deceleration when using a braking resistor.
Torque Limits
(L7-01 through L7-04, L7-06, L7-07)
Increases response for acceleration/deceleration and reduces overshooting when there is low machine rigidity
and ASR gain cannot be increased. Set the inertia ratio between the load and motor and the acceleration time
of the motor running alone.
Troubleshooting
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
341
6.3
Faults
Operation Errors
Tuning Errors
342
Drive Response
When the drive detects a fault:
The digital operator displays text indicating the specific fault and the ALM indicator LED remains lit until the fault is reset.
The fault interrupts drive output and the motor coasts to a stop.
Some faults allow the user to select the stopping method when the fault occurs.
Fault output terminals MA-MC will close, and MB-MC will open.
The drive will remain inoperable until the fault is cleared. Refer to Fault Reset Methods on page 387.
When the drive detects an alarm or a minor fault:
The digital operator displays text indicating the specific alarm or minor fault, and the ALM indicator LED flashes.
The drive continues running the motor, although some alarms allow the user to select a stopping method when the alarm
occurs.
A multi-function contact output set to be tripped by a minor fault (H2- oo = 10) closes. If the output is set to be tripped
by an alarm, the contact will not close.
The digital operator displays text indicating a specific alarm and the ALM indicator LED flashes.
Remove the cause of the problem to reset a minor fault or alarm.
An operation error occurs when parameter settings conflict or do not match hardware settings (such as with an option card).
When the drive detects an operation error:
The digital operator displays text indicating the specific error.
Multi-function contact outputs do not operate.
The drive will not operate the motor until the error has been reset. Correct the settings that caused the operation error to clear
the error.
Tuning errors occur while performing Auto-Tuning.
When the drive detects a tuning error:
The digital operator displays text indicating the specific error.
Multi-function contact outputs do not operate.
Motor coasts to stop.
Remove the cause of the error and repeat the Auto-Tuning process.
Copy Function Errors occur when using the digital operator or the USB Copy Unit to copy, read, or verify parameter settings.
The digital operator displays text indicating the specific error.
Multi-function contact outputs do not operate.
Pressing any key on the digital operator will clear the fault. Investigate the cause of the problem (such as model incompatibility)
and try again.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
<1>
,
,
<2>
to
,
to
<3>
<4>
347
bUS
347
CE
MEMOBUS/Modbus Communication
Error
347
Control Fault
347
348
348
CPF02
348
CPF03
348
CPF06
348
348
348
CPF22
Hybrid IC Error
CPF23
CPF24
Digital Operator
Display
<3>
Name
Page
LF2
Current Imbalance
353
LF3
353
nSE
353
oC
Overcurrent
353
oFA00
354
oFA01
354
to
355
355
to
355
to
355
oFb00
355
349
oFb01
355
349
oFb02
355
349
oFb03,
oFb11
355
CPF26 to
CPF34
CPF40 to Control Circuit Error
CPF45
349
,
to
355
oFC00
355
dEv
349
oFC01
356
dv1
349
oFC02
356
dv2
350
356
dv3
Inversion Detection
350
dv4
350
dv7
350
oH
Heatsink Overheat
356
DriveWorksEZ Fault
350
oH1
Heatsink Overheat
356
E5
351
oH3
357
EF0
351
oH4
357
oH5
357
oL1
Motor Overload
357
oL2
Drive Overload
358
oL3
Overtorque Detection 1
358
oL4
Overtorque Detection 2
358
oL5
359
oL7
359
dWFL
to
Page
boL
CF
,
Name
EF1 to
EF8
External Fault
(input terminal S1 to S8)
351
Err
351
FAn
351
FbH
352
FbL
352
GF
Ground Fault
352
LF
353
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
,
to
<3>
356
343
Troubleshooting
Digital Operator
Display
Page
Digital Operator
Display
Name
Page
oPr
359
STo
Pull-Out Detection
362
oS
Overspeed
(for Control Mode with PG)
359
SvE
Zero-Servo Fault
362
ov
Overvoltage
359
THo
Thermistor Disconnect
362
PF
360
UL3
Undertorque Detection 1
362
PG Disconnect
(for Control Mode with PG)
PG Hardware Fault
(when using PG-X3)
UL4
Undertorque Detection 2
362
361
UL5
363
UnbC
Current Unbalance
363
rF
361
Uv1
Undervoltage
363
rH
361
Uv2
363
rr
361
Uv3
364
SC
361
Uv4
364
SEr
362
voF
364
PGo
PGoH
<4>
Name
<3>
<3>
361
<3>
<1> Displayed as
when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show
.
<2> Displayed as
when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show
.
<3> Detected in models CIMR-Ao4A0903 and 4A1200.
<4> Available in drive software versions 1015 and later.
Name
SI-T Station Number Setting
Error (CC-Link, CANopen,
MECHATROLINK-II)
Drive Baseblock
YES
365
No output
Page
FbH
YES
367
FbL
YES
368
Input <3>
YES
368
HbbF
Input <3>
YES
368
HCA
Current Alarm
YES
368
LT-1
output
Cooling Fan Maintenance Time No <1>
369
LT-2
No output
369
LT-3
No output
369
output
IGBT Maintenance Time (50%) No <1>
369
Hbb
365
Name
Minor Fault
Output
(H2-oo =
10)
YES
365
YES
365
YES
365
YES
366
CrST
Cannot Reset
YES
366
dEv
YES
366
LT-4
dnE
Drive Disabled
YES
367
oH
Heatsink Overheat
YES
369
344
Page
Digital Operator
Display
to
Minor Fault
Output
(H2-oo =
10)
<1>
<1>
YES
350
oH2
Drive Overheat
YES
369
E5
YES
351
oH3
Motor Overheat
YES
370
EF
YES
367
EF0
YES
367
oH5
YES
370
YES
367
oL3
Overtorque 1
YES
370
oL4
Overtorque 2
YES
370
<2>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Minor Fault
Output
(H2-oo =
10)
Page
YES
372
THo
Thermistor Disconnect
YES
372
371
TrPC
YES
372
371
UL3
Undertorque 1
YES
372
UL4
Undertorque 2
YES
372
UL5
Mechanical Weakening
Detection 2
YES
363
Minor Fault
Output
(H2-oo =
10)
Page
YES
370
oS
Mechanical Weakening
Detection 1
Overspeed
(for Control Mode with PG)
YES
371
ov
Overvoltage
YES
Digital Operator
Display
oL5
Name
Digital Operator
Display
SE
<2>
371
371
Uv
Undervoltage
YES
372
372
voF
YES
373
n Operation Errors
Table 6.11 Operation Error Displays
Digital Operator
Display
Name
Page
Digital Operator
Display
Name
Page
374
oPE09
376
oPE02
374
oPE10
377
oPE03
374
oPE11
377
oPE04
375
oPE13
377
oPE05
375
oPE15
377
oPE06
375
oPE16
377
oPE07
375
oPE18
377
oPE08
376
Troubleshooting
oPE01
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
345
n Auto-Tuning Errors
Table 6.12 Auto-Tuning Error Displays
Digital Operator
Display
Name
Page
Digital Operator
Display
Name
Page
End1
379
Er-09
Acceleration Error
381
End2
379
Er-10
381
End3
379
Er-11
381
381
End4
Er-12
379
Er-13
382
382
End5
379
Er-14
End6
379
Er-15
382
Inertia ID Error
382
End7
380
Er-16
Er-01
380
Er-17
382
Er-02
Alarm
380
Er-18
382
PM Inductance Error
382
Er-03
380
Er-19
Er-04
380
Er-20
382
Er-21
383
Er-05
380
Er-08
381
346
Name
Page
Digital Operator
Display
Name
Page
CoPy
384
rdEr
385
CPEr
384
rEAd
385
CPyE
384
vAEr
385
vFyE
385
vrFy
385
CSEr
384
dFPS
384
End
Task complete
384
iFEr
Communication error
384
ndAT
385
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
6.4
Fault Detection
Fault Name
Braking Transistor Overload Fault
The braking transistor reached its overload level.
Possible Solution
Select the correct braking resistor.
Fault Name
Option Communication Error
bUS
Cause
No signal was received from the PLC
Possible Solution
Replace the option card if there are no problems with the wiring and the error continues to occur.
The option card is not properly connected to The connector pins on the option card do not line up properly with the connector pins on the drive.
the drive
Reinstall the option card.
Fault Name
MEMOBUS/Modbus Communication Error
CE
Control data was not received for the CE detection time set to H5-09.
Cause
Possible Solution
Check for faulty wiring.
Faulty communications wiring or an existing Correct the wiring.
short circuit
Check for disconnected cables and short circuits and repair as needed.
Check the various options available to minimize the effects of noise.
Counteract noise in the control circuit, main circuit, and ground wiring.
Use only recommended cables or other shielded line. Ground the shield on the controller side or the
Communication data error occurred due to
drive input power side.
noise
Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if
required.
Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive
power supply input.
Digital Operator Display
CF
Cause
Motor parameters are set improperly
Torque limit is too low
Fault Name
Control Fault
The torque limit was reached continuously for three seconds or longer while ramping to stop in OLV
Control.
Possible Solution
Check the motor parameter settings and repeat Auto-Tuning.
Set the torque limit to the most appropriate setting (L7-01 through L7-04).
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
347
Troubleshooting
Fault Name
Control Circuit Error
Possible Solution
Fault Name
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
Possible Solution
Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Fault Name
Control Board Connection Error
Connection error between the control board and the drive
Possible Solution
Turn off the power and check the connection between the control board and the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Check the various options available to minimize the effects of noise.
Counteract noise in the control circuit, main circuit, and ground wiring.
Use only recommended cables or other shielded line. Ground the shield on the controller side or the
drive input power side.
Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if
required.
Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive
power supply input.
Fault Name
EEPROM Memory Data Error
Error in the data saved to EEPROM
Cause
Possible Solution
Turn off the power and check the connection between the control board and the drive.
There is an error in EEPROM control circuit If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
The power supply was switched off while
Reinitialize the drive using parameter A1-03.
parameters were being saved to the drive
Digital Operator Display
CPF07
CPF08
Cause
There is a faulty connection between the
terminal board and the control board
Fault Name
Terminal Board Connection Error
Possible Solution
Turn off the power and check the connection between the control board and the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
or
Cause
348
Fault Name
Control Circuit Error
Possible Solution
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Hardware is damaged
Digital Operator Display
CPF22
Fault Name
Hybrid IC Failure
Cause
Possible Solution
Fault Name
Control Board Connection Error
Connection error between the control board and the drive
Possible Solution
Turn off the power and check the connection between the control board and the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Fault Name
Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).
Possible Solution
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Possible Solution
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Hardware is damaged
Digital Operator Display
dEv
Fault Name
Speed Deviation (for Control Mode with PG)
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for
longer than the time set to F1-11.
Cause
Possible Solution
Fault Name
Z Pulse Fault
The motor turned one full rotation without the Z Pulse being detected.
Possible Solution
Cause
PG encoder is disconnected, improperly
Make sure the PG encoder is properly connected and all shielded lines are properly grounded.
wired, or the PG option card or PG encoder are
If the problem continues after cycling power, replace the PG option card or the PG encoder.
damaged
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
349
Troubleshooting
to
to
Fault Name
Control Circuit Error
CPU error
Fault Name
Z Pulse Noise Fault Detection
dv2
The Z Pulse is out of phase by more than 5 degrees for the number of times specified in parameter F1-17.
Cause
Possible Solution
Noise interference along the PG cable
Separate the PG cable lines from the source of the noise.
PG cable is not wired properly
Rewire the PG encoder and properly ground all shielded lines.
PG option card or the PG encoder are damaged If the problem continues after cycling power, replace the PG option card or the PG encoder.
Digital Operator Display
Fault Name
Inversion Detection
dv3
The torque reference and acceleration are in opposite directions and the speed reference and actual motor
speed differ by more than 30% for the number of times set to F1-18.
Cause
Possible Solution
Set
the
value
for
to
E5-11
as
specified
on
the motor nameplate. Readjust the Z Pulse offset when
The Z Pulse offset is not set properly to E5-11 replacing the PG encoder or changing the application
to rotate the motor in reverse.
An external force on the load side caused the Make sure the motor is rotating in the proper direction.
motor to move
Identify and fix any problems on the load side causing the motor to rotate in the opposite direction.
Noise interference along the PG cable
affecting the A or B pulse
Properly rewire the PG encoder and connect all lines including shielded line.
PG encoder is disconnected, improperly
wired, or the PG option card or PG encoder are
damaged
Rotational direction for the PG encoder set to Properly connect the motor lines for each phase (U, V, W).
F1-05 is the opposite of the motor line order
Digital Operator Display
dv4
Fault Name
Inversion Prevention Detection
Pulses indicate that the motor is rotating in the opposite direction of the speed reference. Set the number
of pulses to trigger inverse detection to F1-19.
Note: Set F1-19 to 0 to disable inverse detection in applications where the motor may rotate in the
opposite direction of the speed reference.
Cause
Possible Solution
Set the value for to E5-11 as specified on the motor nameplate.
The Z Pulse offset is not set properly to E5-11 If the problem continues after cycling power, replace the PG option card or the PG encoder. Readjust
the Z Pulse offset when replacing the PG encoder or changing the application to rotate the motor in
reverse.
Noise interference along the PG cable
affecting the A or B pulse
dv7
Cause
Disconnection in the motor coil winding
Loose output terminals
Fault Name
Polarity Judge Timeout
Possible Solution
Measure the motor line-to-line resistance and replace the motor if the motor coil winding is
disconnected.
Check for loose terminals. Apply the tightening torque specified in this manual to fasten the terminals.
Refer to Wire Gauges and Tightening Torque on page 89 for details.
350
Fault Name
DriveWorksEZ Fault
Possible Solution
Correct the cause of the fault.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Fault Name
SI-T3 Watchdog Timer Error
The watchdog timed out.
Possible Solution
Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and
proceed to phase 3. Refer to the SI-T3 Option Technical Manual for more details on troubleshooting.
Fault Name
Option Card External Fault
An external fault condition is present.
Cause
Possible Solution
Remove
the
cause
of
the
external
fault.
An external fault was received from the PLC
and F6-03 is set to a value other than 3.
Remove the external fault input from the PLC.
Problem with the PLC program
Check the PLC program and correct problems.
Digital Operator Display
EF1
Fault Name
External Fault (input terminal S1)
Troubleshooting
EEPROM
Hardware problem
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
351
Fault Name
Internal Fan Fault
Fan or magnetic contactor failure
Cause
Possible Solution
Fault Name
Excessive PID Feedback
FbH
Cause
Parameters are set inappropriately
Incorrect PID feedback wiring
There is a problem with the feedback sensor
Digital Operator Display
FbL
Cause
Parameters are set inappropriately
Incorrect PID feedback wiring
There is a problem with the feedback sensor
PID feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set b5-12
to 2 or 5 to enable fault detection.
Possible Solution
Check b5-36 and b5-37 settings.
Correct the wiring.
Check the sensor on the control side.
Replace the sensor if damaged.
Fault Name
PID Feedback Loss
This fault occurs when PID feedback loss detection is programmed to trigger a fault (b5-12 = 2) and the
PID feedback level is below the detection level set to b5-13 for longer than the time set to b5-14.
Possible Solution
Check b5-13 and b5-14 settings.
Correct the wiring.
Check the sensor on the control side.
Replace the sensor if damaged.
Fault Name
Ground Fault
GF
A current short to ground exceeded 50% of rated current on the output side of the drive.
Setting L8-09 to 1 enables ground fault detection.
Cause
Possible Solution
Check the insulation resistance of the motor.
Motor insulation is damaged
Replace the motor.
Check the motor cable.
Remove the short circuit and reapply power to the drive
A damaged motor cable is creating a short
circuit
Check the resistance between the cable and the ground terminal .
Replace the cable.
Reduce the carrier frequency.
Excessive leakage current at the drive output
Reduce the amount of stray capacitance.
The set value exceeds the allowable setting range while the drive automatically adjusts the current
offset. This only happens when attempting to restart a PM motor that is coasting to stop.
The drive started to run during a current offset Set b3-01 to 1 to enable Speed Search at Start.
fault or while coasting to a stop
Perform Speed Search 1 or 2 (H1-oo = 61 or 62) via one of the external terminals.
Note: Speed Searches 1 and 2 are the same when using OLV/PM.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
Hardware problem
representative for instructions on replacing the control board.
352
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Fault Name
Output Phase Loss
Phase loss on the output side of the drive.
Setting L8-07 to 1 or 2 enables Phase Loss Detection.
Possible Solution
Check for wiring errors and properly connect the output cable.
Correct the wiring.
Check the resistance between motor lines.
Replace the motor if the winding is damaged.
Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges
and Tightening Torque on page 89 for details.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
The drive cannot operate a single phase motor.
LF
Cause
The output cable is disconnected
The motor winding is damaged
Fault Name
Terminal wires are loose on the output side of Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and
the drive
Tightening Torque on page 89 for details.
The output circuit is damaged
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Measure the line-to-line resistance for each motor phase. Ensure all values match.
Replace the motor.
LF3
<1>
Cause
The gate drive board in the power unit is
damaged.
Fault Name
Power Unit Output Phase Loss 3
Phase loss occurred on the output side
Setting L8-78 to 1 enables Power Unit Output Phase Loss Protection
Possible Solution
Cycle the power supply. Refer to Diagnosing and Resetting Faults on page 386 for details. If the fault
continues to occur, replace the gate drive board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the gate drive board.
Fault Name
Node Setup Error
A terminal assigned to the node setup function closed during run.
Possible Solution
Stop the drive when using the node setup function.
Fault Name
Overcurrent
Drive sensors detected an output current greater than the specified overcurrent level.
Possible Solution
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
353
Enter
the correct motor code to E5-01.
The wrong motor code has been entered for
OLV/PM (Yaskawa motors only) or the motor Set E5-01 to FFFF if using a non-Yaskawa PM motor. Set the correct motor data to the E5-oo
data are wrong
parameters or perform Auto-Tuning.
Check the control mode.
The motor control method and motor do not For IM motors, set A1-02 to 0, 1, 2, or 3.
match
For PM motors, set A1-02 to 5, 6, or 7.
The rated output current of the drive is too
Use a larger drive.
small
Digital Operator Display
oFA00
Fault Name
Option Card Connection Error at Option Port CN5-A
Option compatibility error
Possible Solution
Cause
The option card installed into port CN5-A is Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.
incompatible with the drive
A PG option card is connected to option port PG option cards are supported by option ports CN5-B and CN5-C only. Connect the PG option card to
CN5-A
the correct option port.
Digital Operator Display
oFA01
Cause
354
Fault Name
Option Card Fault at Option Port CN5-A
Option not properly connected
Possible Solution
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Fault Name
to
oFA03 to oFA06
oFA10, oFA11
to
oFA12 to oFA17
oFA30 to oFA43
to
Cause
Possible Solution
Fault Name
Option Card Fault at Option Port CN5-B
Option compatibility error
Cause
The option card installed into port CN5-B is
incompatible with the drive
Possible Solution
Make sure the drive supports the option card to be installed. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more
than one communication option.
Fault Name
Option Card Fault at Option Port CN5-B
Option not properly connected
Possible Solution
Turn off the power and reconnect the option card.
The option card connection to port CN5-B is Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
Try to use the card in a different option port (in case of a PG option, use port CN5-C). If the option
faulty
card works properly in a different option port, CN5-B is damaged, and the drive requires replacement.
If the error persists (oFA01 or oFC01 occur), replace the option card.
Digital Operator Display
oFb02
Cause
An option card of the same type is already
installed in option port CN5-A
An input option card is already installed in
option port CN5-A
Fault Name
Option Card Fault at Option Port CN5-B
Same type of option card is currently connected
Possible Solution
Except for PG options, only one of each option card type can only be installed simultaneously. Make sure
only one type of option card is connected.
Install a communication option, a digital input option, or an analog input option. More than one of the
same type of card cannot be installed simultaneously.
oFb03 to oFb11
to
oFb12 to oFb17
Cause
Fault Name
Option card error occurred at Option Port CN5-B
Possible Solution
Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Fault Name
Option Card Connection Error at Option Port CN5-C
Option compatibility error
Possible Solution
Confirm that the drive supports the option card to be installed. Contact Yaskawa for assistance.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
Cause
355
Communication option cards are only supported by option port CN5-A. It is not possible to install more
than one communication option.
Fault Name
Option Card Fault at Option Port CN5-C
Option not properly connected
Cause
Possible Solution
Turn the power off and reconnect the option card.
The option card connection to port CN5-C is Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
Try to use the card in a different option port (in case of a PG option, use port CN5-B). If the option
faulty.
card works properly in a different option port, CN5-C is damaged, and the drive requires replacement.
If the error persists (oFA01 or oFb01 occur), replace the option card.
Digital Operator Display
oFC02
Cause
Fault Name
Option Card Fault at Option Port CN5-C
Same type of option card is currently connected
Possible Solution
Except for PG options, only one of each option card type can only be installed simultaneously. Make sure
only one type of option card is connected.
Install a communication option, a digital input option, or an analog input option. More than one of the
same type of card cannot be installed simultaneously.
A maximum of two PG option boards can be used simultaneously. Remove the PG option board installed
into option port CN5-A.
oFC03 to oFC11
to
oFC12 to oFC17
Fault Name
Option Card Error Occurred at Option Port CN5-C
Cause
Possible Solution
Cause
Surrounding temperature is too high
356
Possible Solution
Check the temperature surrounding the drive. Verify temperature is within drive specifications.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.
Measure the output current.
Decrease the load.
Lower the carrier frequency (C6-02).
Replace the cooling fan. Refer to Cooling Fan Replacement: 2A0018 to 2A0081, 4A0007 to 4A0044,
and 5A0006 to 5A0032 on page 409.
After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.
Fault Name
Overheat 1 (Heatsink Overheat)
The heatsink temperature exceeded the drive overheat level. Overheat level is determined by drive
capacity (o2-04).
Possible Solution
Check the temperature surrounding the drive.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Fault Name
Motor Overheat Alarm (PTC Input)
The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the alarm detection level.
Detection requires setting multi-function analog inputs H3-02, H3-06, or H3-10 to E.
Possible Solution
Check the size of the load, the accel/decel times, and the cycle times.
Decrease the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
Check the motor rated current.
Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
Ensure the motor cooling system is operating normally.
Repair or replace the motor cooling system.
Fault Name
Motor Overheat Fault (PTC Input)
The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the fault detection level.
Detection requires setting multi-function analog inputs H3-02, H3-06, or H3-10 to E.
Possible Solution
Check the size of the load, the accel/decel times, and the cycle times.
Decrease the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
<1>
Cause
Motor has overheated
Fault Name
Motor Overheat (NTC Input)
The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2)
Possible Solution
Reduce the load.
Check the ambient temperature.
Troubleshooting
Fault Name
Motor Overload
The electronic motor overload protection tripped
Possible Solution
Reduce the load.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
357
Output current fluctuation due to input phase Check the power supply for phase loss.
loss
Digital Operator Display
Fault Name
Drive Overload
oL2
The thermal sensor of the drive triggered overload protection.
Cause
Possible Solution
Load is too heavy
Reduce the load.
Acceleration or deceleration time is too short Increase the settings for the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
The output voltage is too high
Do not lower E1-08 and E1-10 excessively. This reduces load tolerance at low speeds.
Drive capacity is too small
Overload occurred when operating at low
speeds
Excessive torque compensation
Parameters related to Speed Search are set
incorrectly
Output current fluctuation due to input phase Check the power supply for phase loss.
loss
Digital Operator Display
oL3
Fault Name
Overtorque Detection 1
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time
(L6-03).
Possible Solution
Cause
Parameter settings are not appropriate for the Check L6-02 and L6-03 settings.
load
Fault on the machine side (e.g., machine is
Check the status of the load. Remove the cause of the fault.
locked up)
Digital Operator Display
oL4
Fault Name
Overtorque Detection 2
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable
time (L6-06).
Possible Solution
Cause
Parameter settings are not appropriate for the Check the settings of parameters L6-05 and L6-06.
load
358
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Fault Name
Mechanical Weakening Detection 1
Overtorque occurred, matching the conditions specified in L6-08.
Possible Solution
Cause
Overtorque triggered mechanical weakening Identify the cause of mechanical weakening.
detection level set to L6-08
Digital Operator Display
oL7
Cause
Excessive load inertia
Motor is driven by the load
Something on the load side is restricting
deceleration
Fault Name
High Slip Braking oL
The output frequency stayed constant for longer than the time set to n3-04 during High Slip Braking.
Possible Solution
Reduce deceleration times in parameters C1-02, C1-04, C1-06, and C1-08 for applications that do not
use High Slip Braking.
Use a braking resistor to shorten deceleration time.
The overload time during High Slip Braking Increase parameter n3-04 (High-slip Braking Overload Time).
is too short
Install a thermal relay and increase the setting of n3-04 to maximum value.
Digital Operator Display
oPr
Fault Name
External Digital Operator Connection Fault
The external operator has been disconnected from the drive.
Note: An oPr fault will occur when all of the following conditions are true:
Output is interrupted when the operator is disconnected (o2-06 = 1).
The Run command is assigned to the operator (b1-02 = 0 and LOCAL has been selected).
Cause
Possible Solution
Check the connection between the operator and the drive.
External operator is not properly connected to Replace the cable if damaged.
the drive
Turn off the drive input power and disconnect the operator. Reconnect the operator and reapply drive
input power.
oS
Cause
Overshoot is occurring
Incorrect speed feedback scaling if terminal
RP is used as speed feedback input in V/f
control
Incorrect number of PG pulses has been set
Inappropriate parameter settings
Fault Name
Overspeed (for Control Mode with PG)
The motor speed feedback exceeded the F1-08 setting.
Possible Solution
Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control
Integral Time 1).
If using Closed Loop Vector mode, enable Feed Forward and perform Inertia Auto-Tuning.
Set H6-02 to the value of the speed feedback signal frequency when the motor runs at the maximum
speed.
Adjust the input signal using parameters H6-03 through H6-05.
Check and correct parameter F1-01.
Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).
Fault Name
Overvoltage
Voltage in the DC bus has exceeded the overvoltage detection level.
ov
For 200 V class drives: approximately 410 V
For 400 V class drives: approximately 820 V (740 V when E1-01 is less than 400)
For 600 V class drives: approximately 1040 V
Cause
Possible Solution
Increase the deceleration time (C1-02, C1-04, C1-06, C1-08).
Deceleration time is too short and regenerative Install a dynamic braking resistor or a dynamic braking resistor unit.
energy is flowing from the motor into the drive Set L3-04 to 1 to enable stall prevention during deceleration. Stall Prevention is enabled as the default
setting.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
359
Note: Voltage surge can result from a thyristor convertor and phase advancing capacitor using the
same input power supply.
Check the motor wiring for ground faults.
Correct grounding shorts and reapply power.
Check the settings for Speed Search-related parameters.
Enable Speed Search restart function (b3-19 greater than or equal to 1 to 10).
Adjust the current level during Speed Search and the deceleration time (b3-02 and b3-03 respectively).
Perform Stationary Auto-Tuning for line-to-line resistance and then set b3-14 to 1 to enable Speed
Estimation Speed Search.
The braking transistor or braking resistor are Check braking transistor and braking resistor wiring for errors.
wired incorrectly
Properly rewire the braking resistor device.
PG cable is disconnected
PG cable wiring is wrong
Noise interference along the PG encoder
wiring
Check the load inertia settings when using KEB, overvoltage suppression, or Stall Prevention during
deceleration.
Adjust the load inertia ratio in L3-25 to better match the load.
360
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Fault Name
PG Disconnect (for any control modes using a PG option card)
No PG pulses are received for longer than the time set to F1-14.
Possible Solution
Reconnect the cable.
Correct the wiring.
Check the power line to the PG encoder.
Ensure the motor brake releases properly.
Fault Name
PG Hardware Fault (detected when using a PG-X3 option card)
PG cable is not connected properly.
Possible Solution
Reconnect the cable and check the setting of F1-20.
Fault Name
Braking Resistor Fault
The resistance of the braking resistor is too low.
Possible Solution
Select a braking resistor option that it fits the drive braking transistor specification.
A regenerative converter, regenerative unit, or Set L8-55 to 0 to disable the braking transistor protection selection.
braking unit is being used
rH
Fault Name
Braking Resistor Overheat
Braking resistor protection was triggered.
Fault detection is enabled when L8-01 = 1 (disabled as a default).
Cause
Possible Solution
Check the load, deceleration time, and speed.
Reduce the load inertia.
Increase the deceleration times (C1-02, C1-04, C1-06, C1-08, C1-09).
Replace the dynamic braking option with a larger device that can handle the power that is discharged.
Recalculate braking load and braking power. Reduce the braking load by adjusting braking resistor
settings.
the braking operation duty cycle. Braking resistor protection for ERF-type braking resistors
The braking operation duty cycle is too high Check
(L8-01 = 1) allows a braking duty cycle of maximum 3%.
Check the specifications and conditions for the braking resistor device.
Select the optimal braking resistor.
Note: The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more
frequently than its rating permits will trip the alarm even when the braking resistor surface is not very hot.
Fault Name
Dynamic Braking Transistor
The built-in dynamic braking transistor failed.
Possible Solution
Cycle power to the drive and check for reoccurrence of the fault.
Replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
<1>
Fault Name
IGBT Short Circuit or Ground Fault
Cause
IGBT fault
IGBT short circuit detection circuit fault
Possible Solution
Check motor wiring.
Turn off the power supply, then turn it on. If the problem continues, contact your Yaskawa
representative or the nearest Yaskawa sales office.
361
Troubleshooting
Fault Name
Too Many Speed Search Restarts
SEr
The number of Speed Search restarts exceeded the value set to b3-19.
Cause
Possible Solution
Reduce the detection compensation gain during Speed Search (b3-10).
Parameters related to Speed Search are set to Increase the current level when attempting Speed Search (b3-17).
the wrong values
Increase the detection time during Speed Search (b3-18).
Repeat Auto-Tuning.
The motor is coasting in the opposite direction Set b3-14 to 1 to enable Bi-Directional Speed Search.
of the Run command
Digital Operator Display
Fault Name
THo
Cause
The motor thermistor is not connected
properly.
Fault Name
Zero Servo Fault
Position deviation during zero servo.
Possible Solution
Set the torque limit to an appropriate value using parameters L7-01 to L7-04.
Reduce the amount of load torque.
Check the PG signal for noise interference.
Fault Name
Thermistor Disconnect
The thermistor that detects motor temperature has become disconnected.
Possible Solution
Check the thermistor wiring.
Fault Name
Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the
allowable time (L6-03).
Possible Solution
Cause
Parameter settings are not appropriate for the Check the settings of parameters L6-02 and L6-03.
load
There is a fault on the machine side
Check the load for any problems.
Digital Operator Display
UL4
362
Fault Name
Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the
allowable time (L6-06).
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Possible Solution
Fault Name
Mechanical Weakening Detection 2
The operation conditions matched the conditions set to L6-08.
Possible Solution
Cause
Undertorque was detected and matched the
conditions for mechanical loss detection set to Check the load side for any problems.
L6-08
Digital Operator Display
UnbC
<1>
Fault Name
Current Unbalance
Current flow has become unbalanced.
Cause
Possible Solution
Check wiring
Check for damaged transistors.
Check for short circuits or grounding problems on the connected motor.
Uv1
Cause
Fault Name
DC Bus Undervoltage
Voltage in the DC bus fell below the undervoltage detection level (L2-05).
For 200 V class drives: approximately 190 V
For 400 V class drives: approximately 380 V (350 V when E1-01 is less than 400)
For 600 V class drives: approximately 475 V
The fault is output only if L2-01 is set to 0 or 1 and the DC bus voltage has fallen below the level set to
L2-05 for longer than the time set to L2-02.
Possible Solution
The main circuit drive input power is wired incorrectly.
Correct the wiring.
Fault Name
Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.
Possible Solution
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
363
Troubleshooting
Fault Name
Undervoltage 3 (Soft-Charge Bypass Circuit Fault)
The soft-charge bypass circuit failed.
Possible Solution
Cycle power to the drive and see if the fault reoccurs.
If the problem continues, replace either the control board or the entire drive. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
Check monitor U4-06 for the performance life of the soft-charge bypass.
Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or a Yaskawa representative.
Fault Name
Gate Drive Board Undervoltage
Uv4
<1>
Voltage drop in the gate drive board circuit
Cause
Possible Solution
Cycle power to the drive and see if the fault reoccurs. Refer to Diagnosing and Resetting Faults on
Not enough power is being supplied to the gate page 386 for details.
drive board.
If the problem continues, replace either the gate drive board or the entire drive. For instructions on
replacing the gate drive board, contact Yaskawa or a Yaskawa representative.
<1> Detected in models CIMR-Ao4A0903 and 4A1200.
Digital Operator Display
voF
Cause
Hardware is damaged
364
Fault Name
Output Voltage Detection Fault
Problem detected with the voltage on the output side of the drive.
Possible Solution
Replace the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or a Yaskawa representative.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
6.5
Alarm Detection
Cause
External baseblock signal was entered via
one of the multi-function input terminals Check external sequence and baseblock signal input timing.
(S1 to S8).
Digital Operator Display
boL
Cause
The proper braking resistor has not been
installed.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
365
Troubleshooting
Possible Solutions
Check
for
wiring
errors.
Communications wiring is faulty, there is a
short circuit, or something is not connected Correct the wiring.
properly.
Check for disconnected cables and short circuits. Repair as needed.
Programming error on the master side.
Check communications at start-up and correct programming errors.
Perform a self-diagnostics check.
Communications circuitry is damaged.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing
the control board, contact Yaskawa or your nearest sales representative.
a termination resistor at both ends of a communication line. Set the internal termination resistor switch
Termination resistor setting is incorrect. Install
correctly on slave drives. Place DIP switch S2 to the ON position.
Digital Operator Display
CE
Cause
Check the H5 parameter settings and the protocol setting in the controller.
Ensure settings are compatible.
Communications cable is disconnected or Check the connector to make sure the cable has a signal.
damaged.
Replace the communications cable.
Digital Operator Display
CrST
Cause
Possible Solutions
Ensure
that
a
Run
command
cannot
be
entered
from the external terminals or option during fault reset.
Fault reset was being executed when a Run
command was entered.
Turn off the Run command.
Digital Operator Display
dEv
Cause
Load is too heavy
Acceleration and deceleration times are set Increase the acceleration and deceleration times (C1-01 through C1-08).
too short.
The load is locked up.
Check the machine.
Check the settings of parameters F1-10 and F1-11
Parameter settings are inappropriate.
.
Set H6-02 to value of the speed feedback signal frequency when the motor runs at the maximum speed.
Incorrect speed feedback scaling when
using terminal RP as speed feedback input Adjust the speed feedback signal using parameters H6-03 through H6-05.
Make sure the speed feedback signal frequency does not exceed the maximum input frequency of terminal
in V/f Control.
RP.
The motor brake engaged.
Ensure the brake releases properly.
366
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Cause
Possible Solutions
Cause
Possible Solutions
An external fault was received from the
PLC with F6-03 set to 3, which allows the Remove the cause of the external fault.
drive to continue running after an external Remove the external fault input from the PLC.
fault occurs.
There is a problem with the PLC program. Check the PLC program and correct problems.
EF1
EF2
EF3
EF4
EF5
EF6
EF7
EF8
Cause
An external device has tripped an alarm
function.
Wiring is incorrect.
Multi-function contact inputs are set
incorrectly.
Digital Operator Display
FbH
Cause
Troubleshooting
Remove the cause of the external fault and reset the multi-function input value.
Ensure the signal lines have been connected properly to the terminals assigned for external fault detection
(H1-oo = 20 to 2F).
Reconnect the signal line.
Check if the unused terminals have been set for H1-oo = 20 to 2F (External Fault).
Change the terminal settings.
Minor Fault Name
Excessive PID Feedback
The PID feedback input is higher than the level set to b5-36 for longer than the time set to b5-37, and b5-12
is set to 1 or 4.
Possible Solutions
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
367
Cause
Parameter settings for b5-13 and b5-14 are Check parameters b5-13 and b5-14.
incorrect.
PID feedback wiring is faulty.
Correct the wiring.
Feedback sensor has malfunctioned.
Check the sensor and replace it if damaged.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Feedback input circuit is damaged.
Yaskawa or your nearest sales representative.
Digital Operator Display
Hbb
Cause
Both Safe Disable Inputs H1 and H2 are
open.
Internally, both Safe Disable channels are Replace either the control board or the entire drive. For instructions on replacing the control board, contact
broken.
Yaskawa or your nearest sales representative.
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
Digital Operator Display
either the control board or the entire drive. For instructions on replacing the control board, contact
One of the Safe Disable channels is faulty. Replace
Yaskawa or your nearest sales representative.
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
Digital Operator Display
368
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
LT-2
Cause
The main circuit and control circuit
capacitors have reached 90% of their
expected performance lives.
Digital Operator Display
LT-3
The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note: An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
Possible Solutions
Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.
Minor Fault Name
Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.
Note: An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
Cause
Possible Solutions
The DC bus soft charge relay has reached Replace either the control board or the entire drive. For instructions on replacing the control board, contact
90% of expected performance life.
Yaskawa or your nearest sales representative.
Digital Operator Display
LT-4
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
369
Troubleshooting
Note: An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
Cause
Possible Solutions
IGBTs have reached 50% of their expected Check the load, carrier frequency, and output frequency.
performance life.
Search for the device that tripped the overheat warning. Remove the cause of the problem.
Minor Fault Name
Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02,
H3-06 or H3-10 = E).
Possible Solutions
Repair the PTC input wiring.
Note: Refrain from lowering E1-08 and E1-10 excessively to prevent a reduction in load tolerance at
low speeds.
Check the motor-rated current.
Enter motor-rated current on motor nameplate (E2-01).
Ensure the motor cooling system is operating normally.
Repair or replace the motor cooling system.
<1>
Cause
Motor has overheated.
Cause
Overtorque occurred, triggering the
mechanical weakening level set to L6-08. Check for the cause of mechanical weakening.
370
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
ov
Cause
Surge voltage present in the drive input
power.
PG cable is disconnected.
PG cable wiring is wrong.
Noise interference along PG encoder
wiring.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
371
THo
Cause
The motor thermistor is not connected
properly.
Cause
IGBTs have reached 90% of their expected Replace the drive.
performance life.
Digital Operator Display
UL3
Cause
Inappropriate parameter settings.
Load has dropped or decreased
significantly.
Digital Operator Display
UL4
Cause
Inappropriate parameter settings.
The load has dropped or decreased
significantly.
Digital Operator Display
Uv
Cause
Phase loss in the drive input power.
372
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
Hardware is damaged.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
373
6.6
Error Name
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Possible Solutions
Correct the value set to o2-04.
Error Name
Parameter Range Setting Error
oPE02
Use U1-18 to find parameters set outside the range.
Cause
Possible Solutions
Parameters were set outside the possible setting range.
Set parameters to the proper values.
Note: When multiple errors occur simultaneously, other errors are given precedence over oPE02.
Digital Operator Display
Error Name
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01
to H1-08.
oPE03
Cause
The same function is assigned to two multi-function inputs.
Excludes Not used and External Fault.
Possible Solutions
Ensure all multi-function inputs are assigned to different functions.
Re-enter the multi-function settings to ensure this does not occur.
The Up command was set but the Down command was not, or vice versa
(settings 10 vs. 11).
Properly set the functions that required for use in combination with other
The Up 2 command was set but the Down 2 command was not, or vice versa functions.
(settings 75 vs. 76).
Run/Stop command for a 2-wire sequence was set (H1-oo = 42), but
Forward/Reverse command (H1-oo = 43) was not.
Drive Enable is set to multi-function input S1 or S2 (H1-01 = 6A or
H1-02 = 6A).
Two of the following functions are set simultaneously:
Up/Down Command (10 vs. 11)
Up 2/Down 2 Command (75 vs. 76)
Hold Accel/Decel Stop (A)
Analog Frequency Reference Sample/Hold (1E)
Offset Frequency 1, 2, 3 Calculations (44, 45, 46)
The Up/Down command (10, 11) and PID control (b5-01) are enabled
simultaneously.
374
Properly set the functions that required for use in combination with other
functions.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Error Name
oPE04
Cause
The drive, control board, or terminal board have been replaced and the
parameter settings between the control board and the terminal board no
longer match.
Initialization Required
Possible Solutions
Set A1-03 to 555o to load the parameter settings stored in the terminal board
to the drive. Initialize parameters after drive replacement by setting A1-03
to 1110 or 2220.
Error Name
Set H6-01 to 0.
Troubleshooting
oPE05
Cause
Frequency reference is assigned to an option card (b1-01 = 3) and an input
option card is not connected to the drive.
The Run command is assigned to an option card (b1-02 = 3) and an input
option card is not connected to the drive.
Frequency reference is assigned to the pulse train input (b1-01 = 4) and
terminal RP is not set for frequency reference input (H6-01 > 0)
Although the digital card input is set for BCD special for a 5-digit input
(F3-01 = 6), the data length is set for 8-bit or 12-bit (F3-03 = 0, 1).
The following values have been set while an AI-A3 option card is installed:
The source of frequency reference setting is assigned to an option card
(b1-01 = 3).
The action for the analog card is set for separate terminal input
(F2-01 = 0).
6
Error Name
Control Method Selection Error
Correct the setting for the control method.
Possible Solutions
Connect a PG option card.
Correct the value set to A1-02.
Error Name
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02,
H3-06, or H3-10 and PID functions conflict.
Possible Solutions
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
375
Error Name
Parameter Selection Error
oPE08
A function has been set that cannot be used in the motor control method
selected.
Cause
Possible Solutions
Attempted to use a function that is not valid for the selected control mode. Check the motor control method and the functions available.
In OLV, n2-02 is longer than n2-03
Adjust parameter values so n2-02 is shorter than n2-03.
In OLV, C4-02 is longer than C4-06
Adjust parameter values so C4-02 is shorter than C4-06.
Set the correct motor code in accordance with the motor being used
(E5-01).
In OLV/PM, parameters E5-02 to E5-07 are set to 0.
When using a special-purpose motor, set E5-oo in accordance with the
test report provided.
The following settings have occurred in OLV/PM:
Set E5-09 or E5-24 to the correct value, and set the other to 0.
E5-03 does not equal 0
Set the motor rated current for PM to 0 (E5-03).
E5-09 and E5-24 are both equal to 0, or neither equals 0
b1-14 (Phase Order Selection) is set to 1 (Switch phase order) when using a Correct the parameter settings.
PG option card.
In AOLV/PM High Frequency Injection is disabled (n8-57 = 0) and the
minimum frequency (E1-09) is set lower than 1/20 of the base frequency
setting.
Note:
Use U1-18 to find parameters that are set outside the specified setting range. When multiple errors occur simultaneously, other errors are
given precedence over oPE08.
Digital Operator Display
oPE09
Cause
The following simultaneous contradictory settings have occurred:
b5-15 is not set to 0.0 (PID Sleep Function Operation Level)
The stopping method is set to either DC Injection Braking or coast to stop
with a timer (b1-03 = 2 or 3).
b5-01 is set to 1 or 2, enabling PID control, but the lower limit for the
frequency reference (d2-02) is not set to 0 while reverse output is enabled
(b5-11 = 1).
b5-01 is set to 3 or 4, enabling PID control, but the lower limit for the
frequency reference (d2-01) is not 0.
376
Error Name
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is
enabled (b5-01 = 1 to 4).
Possible Solutions
Set b5-15 to a value other than 0.0.
Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
oPE10
Cause
V/f pattern setting error.
Digital Operator Display
oPE11
Error Name
V/f Data Setting Error
One of the following setting errors has occurred:
E1-04 E1-06
E1-06 E1-07
E1-07 E1-09
or E1-09 E1-11
E3-04 E3-06
E3-06 E3-07
E3-07 E3-09
or E3-09 E3-11
Possible Solutions
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.
For motor 2, correct E3-04, E3-06, E3-07, E3-09, and E3-11.
Error Name
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Possible Solutions
Cause
The following simultaneous contradictory settings have occurred: C6-05 >
6 and C6-04 > C6-03 (carrier frequency lower limit is greater than the upper
limit).
Correct the parameter settings.
If C6-05 6, the drive operates at C6-03.
The upper and lower limits between C6-02 and C6-05 are contradictory.
Digital Operator Display
Error Name
Error Name
oPE15
Error Name
oPE16
Cause
In AOLV/PM, the automatically calculated energy saving coefficients are
out of the allowable range.
Digital Operator Display
oPE18
Cause
Troubleshooting
Cause
Torque Control is enabled (d5-01 = 1) while the Speed/Torque Control
switch function is assigned to a digital input (H1-oo = 71).
Either d5-01 is set to 1 to enable Torque Control, or the Speed/Torque Control
switch is assigned to a digital input H1-oo = 71, while at the same time:
Feed Forward is enabled (n5-01 = 1), or
Correct the parameter settings.
Droop Control is enabled (b7-01 0), or
Intelligent Stall Prevention or Intelligent Stall Prevention 2 is enabled
(L3-04 = 2 or 5), or
A digital input is set for the power KEB 1 or KEB 2 (H1-oo = 7A or 7B)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
377
378
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
6.7
When the Auto-Tuning faults shown below are detected, the fault is displayed on the digital operator and the motor coasts to
a stop. Auto-Tuning faults do not trigger a multi-function terminal set for fault or alarm output.
An Endo error indicates that although Auto-Tuning has successfully completed, there is some discrepancy in the calculations.
If an Endo error occurs, check for the cause of the error using the table below, and perform Auto-Tuning again after fixing
the problem. Start the application if no problem can be diagnosed despite the existence of the Endo error.
Error Name
Excessive
V/f
Setting
(detected
only
during
Rotational
Auto-Tuning and displayed after Auto-Tuning is
End1
complete)
Cause
Possible Solutions
The torque reference exceeded 20% during Prior to Auto-Tuning, verify the information on the motor nameplate.
Auto-Tuning.
Enter proper values from motor nameplate to parameters T1-03 to T1-05 and repeat Auto-Tuning.
The results from Auto-Tuning the no-load If possible, disconnect the motor from the load and perform Auto-Tuning. If the load cannot be uncoupled,
current exceeded 80%.
use the current Auto-Tuning results.
Digital Operator Display
End2
Cause
Motor data entered during Auto-Tuning
was incorrect.
Error Name
Motor Iron-Core Saturation Coefficient (detected only during Rotational Auto-Tuning and displayed after
Auto-Tuning is complete)
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.
Error Name
Troubleshooting
End3
Cause
The correct current rating printed on the
motor nameplate was not entered into
T1-04.
Error Name
Cause
Possible Solutions
Make
sure
the
data
entered
for
Auto-Tuning
is correct.
The calculated slip is outside the allowable
range.
If possible, perform Rotational Auto-Tuning. If not possible, perform Stationary Auto-Tuning 2.
Digital Operator Display
End5
Cause
The calculated resistance value is outside
the allowable range.
Error Name
Error Name
Leakage Inductance Alarm
Cause
Possible Solutions
The calculated leakage inductance value is Double-check the data entered for the Auto-Tuning process.
outside the allowable range.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
379
Error Name
No-Load Current Alarm
Cause
Possible Solutions
Error Name
Motor Data Error
Possible Solutions
Check that the motor data entered to T1 parameters matches motor nameplate input before Auto-Tuning.
Restart Auto-Tuning and enter the correct information.
Error Name
Minor Fault
Possible Solutions
Exit the Auto-Tuning menu, check the alarm code, remove the alarm cause, and repeat Auto-Tuning.
Error Name
STOP Button Input
Possible Solutions
Auto-Tuning did not complete properly. Restart Auto-Tuning.
Error Name
Line-to-Line Resistance Error
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.
Error Name
No-Load Current Error
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.
Results from Auto-Tuning are outside the Check and correct faulty motor wiring.
parameter setting range or the tuning
Perform Rotational Auto-Tuning.
process took too long.
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make
The load was too high during Rotational
sure the load is lower than 30%.
Auto-tuning.
If a mechanical brake is installed, make sure it is fully lifted during tuning.
380
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Error Name
Rated Slip Error
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.
Results from Auto-Tuning are outside the Check and correct faulty motor wiring.
parameter setting range or the tuning
Perform Rotational Auto-Tuning.
process took too long.
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make
The load was too high during rotational
sure the load is lower than 30%.
Auto-tuning.
If a mechanical brake is installed, make sure it is fully lifted during tuning.
Digital Operator Display
Er-09
Cause
The motor did not accelerate for the
specified acceleration time.
Torque limit when motoring is too low
(L7-01 and L7-02).
The load was too high during Rotational
Auto-Tuning.
Error Name
Acceleration Error
Possible Solutions
Increase the acceleration time (C1-01).
Disconnect the machine from the motor if possible.
Check L7-01 and L7-02 settings.
Increase the setting.
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make
sure the load is lower than 30%.
If a mechanical brake is installed, make sure it is fully lifted during tuning.
Error Name
Motor Direction Error
Cause
The encoder signal lines are not properly
connected to the drive.
Possible Solutions
Check and correct wiring to the PG encoder.
Check the motor speed monitor U1-05 while manually turning the motor forward. If the sign displayed is
negative, change the setting of parameter F1-05.
Error Name
Motor Speed Fault
Possible Solutions
Increase the acceleration time (C1-01).
Disconnect the machine from the motor if possible.
Error Name
Current Detection Error
Cause
Possible Solutions
One of the motor phases is missing:
Check motor wiring and correct any problems.
(U/T1, V/T2, W/T3).
The current exceeded the current rating of Check motor wiring for a short between motor lines.
the drive.
Close any magnetic contactors used between motors.
Replace the control board or the entire drive. For instructions on replacing the control board, contact
The current is too low.
Yaskawa or your nearest sales representative.
Attempted Auto-Tuning without motor
Connect the motor and restart Auto-Tuning.
connected to the drive.
Replace the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa
Current detection signal error.
or your nearest sales representative.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
381
Troubleshooting
Er-11
Error Name
Leakage Inductance Error
Cause
Possible Solutions
Error Name
Motor Speed Error 2
Cause
The motor speed exceeded twice the
amplitude of speed reference during Inertia Reduce the ASR gain set to C5-01.
Tuning.
Digital Operator Display
Er-15
Possible Solutions
Error Name
Torque Saturation Error
Cause
Possible Solutions
The output torque reached the torque limit Increase the torque limits in L7-01 through L7-04 within reasonable limits.
set in L7-01 through L7-04 during Inertia Reduce the test signal amplitude in T3-01 and restart Auto-Tuning. If necessary, reduce the test signal
Tuning.
frequency (T3-02) and restart Auto-Tuning.
Digital Operator Display
Er-16
Cause
The inertia identified by the drive was
abnormally small or abnormally large
during Inertia Tuning.
Error Name
Inertia Detection Error
Possible Solutions
Reduce the test signal amplitude in T3-01 and restart Auto-Tuning. If necessary, reduce the test signal
frequency (T3-02) and restart Auto-Tuning.
Check the basic motor inertia value entered to T3-03.
Error Name
Reverse Prohibited Error
Cause
Possible Solutions
Drive is prohibited from rotating the motor Inertia Auto-Tuning cannot be performed if the drive is restricted from rotating in reverse.
in reverse while attempting to perform
Assuming it is acceptable for the application to rotate in reverse, set b1-04 to 0 and then pertorm Inertia
Inertia Tuning.
Tuning.
Digital Operator Display
Er-18
Error Name
Induction Voltage Error
Cause
Possible Solutions
The result of Back EMF Constant Tuning
(induced voltage) exceeds the allowable Double-check the data entered to the T2-oo parameters and restart Auto-Tuning.
setting range.
Digital Operator Display
Er-19
Error Name
PM Inductance Error
Cause
Possible Solutions
The induced voltage constant attempted to
set a value to E5-08 or E5-09 that is outside Double-check the data entered to the T2-oo parameters and restart Auto-Tuning.
the allowable range.
Digital Operator Display
Er-20
Error Name
Stator Resistance Error
Cause
Possible Solutions
Stator resistance tuning attempted to set a
value to E5-06 that is outside the allowable Double-check the data entered to the T2-oo parameters and restart Auto-Tuning.
setting range.
382
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
Cause
Motor was coasting when Auto-Tuning
was performed.
Either the motor or the PG encoder on the
motor are not properly wired.
The direction for the PG encoder is set
incorrectly, or the number of pulses set for
the PG encoder is wrong.
PG encoder is damaged.
Error Name
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
383
6.8
Task
Writing Parameter Settings (flashing)
Possible Solutions
This is not an error.
Task
Control Mode Mismatch
Cause
Possible Solutions
Verify
the
control
mode
for
the
parameters
to be loaded onto the drive and the control mode on
Control mode of the parameters to be loaded onto
drive to which those parameters will be written.
the drive and the control mode set to the drive do
not match.
Set the same control mode using parameter A1-02 and retry.
Digital Operator Display
CPyE
Cause
Failed writing parameters
Task
Error Writing Data
Possible Solutions
Attempt to write parameters again.
Task
Copy Unit Error
Possible Solutions
Replace the operator or the USB Copy Unit.
Hardware fault
Digital Operator Display
dFPS
Task
Drive Model Mismatch
Cause
Possible Solutions
The drives used in the copy and write process are
not the same model.
Verify the model number of the drive from which the parameters were copied and the model of
the drive to which those parameters will be written.
The drive from which the parameters were
copied is a different model.
Make sure the two drives are the same model and have the same software version.
The drive to be written to is a different model.
Digital Operator Display
End
Task
Task Complete
Cause
Finished reading, writing, or verifying parameters. This is not an error.
Digital Operator Display
iFEr
Task
Communication Error
Cause
A communication error occurred between the drive Check the cable connection.
and the operator or the USB copy unit.
384
Possible Solutions
Possible Solutions
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Use the cable originally packaged with the USB Copy Unit.
Task
Model, Voltage Class, Capacity Mismatch
Cause
Possible Solutions
Task
Error Reading Data
Cause
Possible Solutions
Failed while attempting to read parameter settings Press and hold the READ key on the USB Copy Unit for at least one second to have the unit read
from the drive.
parameters from the drive.
Digital Operator Display
rEAd
Cause
Displayed while the parameter settings are being
read onto the USB Copy Unit.
Task
Reading Parameter Settings (flashing)
Possible Solutions
This is not an error.
Task
Voltage Class, Capacity Mismatch
Cause
Possible Solutions
The drive from which the parameters were copied
and the drive on which the Verify mode is being Make sure electrical specifications and capacities are the same for both drives.
performed have different electrical specifications
or are a different capacity.
Digital Operator Display
Parameter settings in the drive and those saved to the copy function are not the same
Possible Solutions
To synchronize parameters, either write the parameters saved on the USB Copy Unit or digital
operator onto the drive, or Read the parameter settings on the drive onto the USB Copy Unit.
Troubleshooting
vFyE
Cause
Indicates that parameter settings that have been
Read and loaded onto the Copy Unit or Digital
Operator are different.
Task
Task
Comparing Parameter Settings (flashing)
Cause
The Verify mode has confirmed that parameters
settings on the drive and parameters read to the copy This is not an error.
device are identical.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Possible Solutions
385
6.9
When a fault occurs and the drive stops, follow the instructions below to remove whatever conditions triggered the fault, then
restart the drive.
Note: An oC/SC fault will be displayed in the event of an IGBT failure. It may not be possible to reset this fault until the IGBT problem is corrected.
1.
2.
3.
Note: 1. To find out what faults were triggered, check the fault history in U2-02. Information on drive status when the fault occurred
such as the frequency, current, and voltage can be found in U2-03 through U2-20. Refer to Viewing Fault Trace Data After
Fault on page 386 for information on how to view fault data.
2. When the fault continues to be displayed after cycling power, remove the cause of the fault and reset.
Look at the digital operator for information on the fault that occurred.
Refer to Fault Displays, Causes, and Possible Solutions on page 347.
Reset the fault. Refer to Fault Reset Methods on page 387.
Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
2. Press
3. Press
or
and
to scroll to monitor U2-02. The fault code shown in U2-02
4. Press
is the fault that occurred most recently.
Press
to view drive status information when fault occurred.
5. Parameters U2-03 through U2-20 help determine the cause of a fault.
Parameters to be monitored differ depending on the control mode.
386
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Procedure
- MODE -
DRV
oC
Overcurrent
FWD RESET
F1
RESET
LO
RE
RESET
ENTER
RUN
F2
ESC
STOP
Drive
Fault Reset Switch
ON
OFF
Turn off the main power supply if the above methods do not reset the fault. Reapply power after the
digital operator display has turned off.
Troubleshooting
Note: If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command before attempting to clear
a fault situation.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
387
u Common Problems
Common Problems
Cannot Change Parameter Settings
Motor Does Not Rotate
Motor Does Not Rotate Properly after Pressing RUN Button Motor Rotates in the Opposite Direction from the Run
or after Entering External Run Command
Command
Motor Rotates in One Direction Only
Motor is Too Hot
Drive Does Not Allow Selection of Rotational Auto-Tuning
oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Motor Stalls During Acceleration or With Large Loads
Drive Frequency Reference Differs from the Controller Frequency Reference Command
Excessive Motor Oscillation and Erratic Rotation
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled
Noise From Drive or Motor Cables When the Drive is Powered On
Ground Fault Circuit Interrupter (GFCI) Trips During Run
Unexpected Noise from Connected Machinery
Connected Machinery Vibrates When Motor Rotates
Oscillation or Hunting
PID Output Fault
Insufficient Starting Torque
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)
Output Frequency is not as High as Frequency Reference
Buzzing Sound from Motor at 2 kHz
Unstable Motor Speed when Using PM or IPM
Motor Does Not Restart after Power Loss
Page
388
389
390
390
390
391
391
391
392
392
392
393
393
393
393
394
394
394
394
394
395
395
Possible Solutions
Stop the drive and switch over to the Programming Mode.
Most parameters cannot be edited during run.
The Access Level is set to restrict access to parameter Set the Access Level to allow parameters to be edited (A1-01 = 2).
settings.
See what mode the operator is currently set for.
The operator is not in the Parameter Setup Mode
Parameters cannot be edited when in the Setup Mode (STUP). Switch modes so that PAr
(the screen will display PAr).
appears on the screen. Refer to The Drive and Programming Modes on page 120.
A multi-function contact input terminal is set to allow When the terminal is open, parameters cannot be edited.
or restrict parameter editing
Turn on the multi-function contact input set to 1B.
(H1-01 through H1-08 = 1B).
388
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Possible Solutions
If the password entered to A1-04 does not match the password saved to A1-05, then drive
settings cannot be changed.
Reset the password.
If you cannot remember the password:
STOP
Scroll to A1-04. Press
and
simultaneously. Parameter A1-05 will appear.
Set a new password to parameter A1-05.
Check the drive input power voltage by looking at the DC bus voltage (U1-07).
Check all main circuit wiring.
u Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External
Run Command
Possible Solutions
Check if the DRV light on the digital operator is lit.
The drive is not in the Drive Mode. Enter the Drive Mode to begin operating the motor. Refer to The Drive and Programming Modes on page
120.
Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the
source, the LO/RE button LED must be on. If the source is REMOTE, it must be off.
Take the following steps to solve the problem:
was pushed.
Push
.
If o2-01 is set to 0, then the LO/RE button will be disabled.
Auto-Tuning has just completed.
When Auto-Tuning completes, the drive is switched back to the Programming Mode. The Run command will
not be accepted unless the drive is in the Drive Mode.
Use the digital operator to enter the Drive Mode. Refer to The Drive and Programming Modes on page 120.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
389
Troubleshooting
Possible Solutions
STOP
Pressing
will decelerate the drive to stop.
was pressed when the drive Switch off the Run command and then re-enter a new Run command.
was started from a REMOTE source.
STOP
Set o2-02 to 0 to disable
.
Motor starting torque is too low.
Refer to Motor Performance Fine-Tuning on page 336.
Frequency reference value is too low
or the drive does not accept the value Enter a value that is above the minimum output frequency determined by E1-09.
entered.
If the drive is supposed to be set up for a 2-wire sequence, then ensure parameters H1-03 through H1-08 are not
The sequence Start/Stop sequence is set to 0.
set up incorrectly.
If the drive is supposed to be set up for a 3-wire sequence, then one of the parameters H1-03 through H1-08 must
be set to 0. Terminal S1 will become the Start, terminal S2 will become the Stop input.
STOP
Possible Solutions
2
1.
2.
The motor is running at almost 0 Hz and the Speed
Search estimated the speed to be in the opposite
direction.
Disable bi-directional search (b3-14 = 0) so that Speed Search is performed only in the
specified direction.
Note: Check the motor specifications for the forward and reverse directions. The motor specifications will vary depending on the manufacturer of
the motor.
Possible Solutions
Check parameter b1-04.
Set parameter b1-04 to 0 to allow the motor to rotate in reverse.
Make sure that one of the input terminals S3 to S8 used for the 3-Wire sequence has been set
for reverse.
390
Possible Solutions
If the load is too heavy for the motor, the motor will overheat as it exceeds its rated torque value
for an extended period of time.
Keep in mind that the motor also has a short-term overload rating in addition to the possible
solutions provided below:
Reduce the load.
Increase the acceleration and deceleration times.
Check the values set for the motor protection (L1-01, L1-02) as well as the motor rated current
(E2-01).
Increase motor capacity.
Check the ambient temperature.
Cool the area until it is within the specified temperature range.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Possible Solutions
Perform Auto-Tuning.
Calculate the motor value and reset the motor parameters.
Change the motor control method to V/f Control (A1-02 = 0).
When the motor cable is long, high voltage surges occur between the motor coils and drive
switching.
Normally, surges can reach up to three times the drive input power supply voltage.
Use a motor with a voltage tolerance higher than the max voltage surge.
Use an inverter-duty motor rated for use with AC drives when using the motor on drives rated
higher than 200 V class.
Install an AC reactor on the output side of the drive. The carrier frequency should be set to 2
kHz when installing an AC reactor.
Check the motor fan.
Increase the carrier frequency to lower the current harmonic distortion and lower the motor
temperature.
Possible Solutions
Check if the desired tuning mode is available for the selected control mode. Refer to AutoThe desired Auto-Tuning mode is not available for the
Tuning on page 135.
selected control mode.
Change the motor control method by setting A1-02.
u oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Cause
Motor rated current and the motor no-load current
setting in the drive are incorrect.
Possible Solutions
The user is trying to set the motor rated current in E2-01 to a value lower than the no-load
current set in E2-03.
Make sure that value set in E2-01 is higher than E2-03.
If it is necessary to set E2-01 lower than E2-03, first lower the value set to E2-03, then change
the setting in E2-01 as needed.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
391
Troubleshooting
Cause
Torque limit has been reached or current suppression
keeps the drive from accelerating.
The Stall Prevention level during run has been set too
low.
Possible Solutions
Perform Auto-Tuning.
Calculate motor data and reset motor parameters.
Switch to V/f Control (A1-02 = 0).
Check the multi-function analog input settings. Multi-function analog input terminal A1, A2,
or A3 is set for frequency gain (H3-02, H3-10, or H3-06 is set to 1), but there is no voltage
or current input provided.
Make sure H3-02, H3-10, and H3-06 are set to the proper values.
See if the analog input value is set to the right value (U1-13 to U1-15).
Check the Stall Prevention level during acceleration (L3-02).
If L3-02 is set too low, acceleration may be taking too long.
Increase L3-02.
Check the Stall Prevention level during run (L3-06).
If L3-06 is set too low, speed will drop as the drive outputs torque.
Increase the setting value.
The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line
resistance.
Be aware that V/f Control is comparatively limited when it comes to producing torque at low
speeds.
Consider switching to Open Loop Vector Control.
u Drive Frequency Reference Differs from the Controller Frequency Reference Command
Cause
The analog input gain and bias for the frequency
reference input are set to incorrect values.
Possible Solutions
Check the gain and bias settings for the analog inputs that are used to set the frequency reference.
Check parameters H3-03 and H3-04 for input A1, check parameters H3-11 and H3-12 for input
A2, and check parameters H3-07 and H3-08 for input A3.
Set these parameters to the appropriate values.
If more than one of multi-function analog inputs A1 to A3 is set for frequency reference bias
(H3-02, H3-10, or H3-06 is set to 0), then the sum of all signals builds the frequency reference.
Make sure that H3-02, H3-10, and H3-06 are set appropriately.
Check the input level set for terminals A1 to A3 (U1-13 to U1-15).
Possible Solutions
Check drive input power voltage to ensure that it provides stable power.
Enable Hunting Prevention (n1-01 = 1).
Increase the AFR gain (n2-01) or the AFR time constant (n2-02).
392
Possible Solutions
Check the Stall Prevention level during deceleration (L3-04).
If a dynamic braking option has been installed, disable Stall Prevention during deceleration
(L3-04 = 0).
Set deceleration to more appropriate time (C1-02, C1-04, C1-06, C1-08).
Assuming parameter settings are normal and that no overvoltage occurs when there is
insufficient torque, it is likely that the demand on the motor has exceeded the motor capacity.
Use a larger motor.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Possible Solutions
Check the settings for the torque limit (L7-01 through L7-04).
If the torque limit is enabled, deceleration might take longer than expected because the drive
cannot output more torque than the limit setting. Ensure the torque limit is set to a high enough
value.
Increase the torque limit setting.
If multi-function analog input terminal A1, A2, or A3 is set to torque limit (H3-02, H3-10, or
H3-06 equals 10, 11, 12, or 15), ensure that the analog input levels are set to the correct levels.
Ensure H3-02, H3-10, and H3-06 are set to the right levels.
Ensure the analog input is set to the correct value (U1-13 to U1-15).
Load exceeded the internal torque limit determined by Switch to a larger capacity drive.
the drive rated current.
Possible Solutions
Possible Solutions
Check the wiring and rating of peripheral devices.
Increase the GFCI sensitivity or use GFCI with a higher threshold.
Lower the carrier frequency (C6-02).
Reduce the length of the cable used between the drive and the motor.
Install a noise filter or reactor on the output side of the drive. Set the carrier frequency to 2 kHz when connecting
a reactor.
Possible Solutions
Adjust the carrier frequency using parameters C6-02 through C6-05.
Adjust the parameters used for the Jump frequency function (d3-01 through d3-04) to skip the
problem-causing bandwidth.
Place the motor on a rubber pad to reduce vibration.
Note: The drive may have trouble assessing the status of the load due to white noise generated from using Swing PWM (C6-02 = 7 to A).
n Oscillation or Hunting
Cause
Insufficient tuning.
Gain is too low when using PID control.
The frequency reference is assigned to an external
source and the signal is noisy.
Possible Solutions
Perform Auto-Tuning.
Refer to Motor Performance Fine-Tuning on page 336.
Refer to b5: PID Control on page 177 for details.
Ensure that noise is not affecting the signal lines.
Separate main circuit wiring and control circuit wiring.
Use twisted-pair cables or shielded wiring for the control circuit.
Increase the analog input time filter constant (H3-13).
Perform Auto-Tuning.
Reduce the length of the cable.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
393
Possible Solutions
Check the multi-function analog input terminal settings.
Set multi-function analog input terminal A1, A2, or A3 for PID feedback (H3-02, H3-10, or
H3-06 = B).
A signal input to the terminal selection for PID feedback is needed.
Check the connection of the feedback signal.
Check the various PID-related parameter settings.
No PID feedback input to the terminal causes the value detected to be 0, causing a PID fault
and the drive to operate at max frequency.
PID control keeps the difference between target and detection values at 0. Set the input level
for the values relative to one another.
Use analog input gains H3-03 and H3-11 to adjust PID target and feedback signal scaling.
u Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection
Braking)
Cause
DC Injection Braking is set too low and the drive
cannot decelerate properly.
Possible Solutions
Adjust the DC Injection braking settings.
Increase the current level for DC Injection Braking (b2-02).
Increase the DC Injection Braking time at stop (b2-04).
The stopping method is set so that the drive coasts to Set b1-03 (Stopping Method Selection) to 0 or 2.
stop.
Possible Solutions
Adjust the parameters used for the Jump frequency function (d3-01, d3-02, d3-03).
Frequency reference is set within the range of the Jump
Enabling the Jump frequency prevents the drive from outputting the frequencies specified in
frequency.
the Jump range.
Set the maximum output frequency and the upper limit for the frequency reference to more
appropriate values (E1-04, d2-01).
Upper limit for the frequency reference has been
exceeded.
The following calculation yields the upper value for the output frequency:
E1-04 x d2-01 / 100
Large load triggered Stall Prevention function during Reduce the load.
acceleration.
Adjust the Stall Prevention level during acceleration (L3-02).
Possible Solutions
If the output current rises too high at low speeds, the carrier frequency is automatically reduced
and causes a whining or buzzing sound.
Exceeded 110% of the rated output current of the drive If the sound is coming from the motor, disable carrier frequency derating (L8-38 = 0).
while operating at low speeds.
Disabling the automatic carrier frequency derating increases the chances of an overload fault
(oL2). Switch to a larger capacity motor if oL2 faults occur too frequently.
394
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Possible Solutions
Refer to Motor Performance Fine-Tuning on page 336 for details.
Check the speed control range and adjust the speed accordingly.
Refer to Motor Performance Fine-Tuning on page 336 for details.
Increase the S-curve time at the start of acceleration (C2-01).
Enter the correct motor code for the PM motor being used into E5-01.
For special-purpose motors, enter the correct data to all E5 parameters according to the test
report provided for the motor.
Troubleshooting
Cause
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
395
396
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
7
Periodic Inspection & Maintenance
This chapter describes the periodic inspection and maintenance of the drive to ensure that it receives
the proper care to maintain overall performance.
7.1
7.2
7.3
7.4
7.5
7.6
SECTION SAFETY...............................................................................................398
INSPECTION........................................................................................................400
PERIODIC MAINTENANCE.................................................................................403
DRIVE COOLING FANS.......................................................................................405
REPLACING THE AIR FILTER............................................................................430
DRIVE REPLACEMENT.......................................................................................432
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
397
7.1
Section Safety
DANGER
Electrical Shock Hazard
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or
shields before operating the drives and run the drives according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with
installation, adjustment, and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work
on the drive.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching
any components.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
398
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
WARNING
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Follow cooling fan replacement instructions. The cooling fan cannot operate properly when it is installed incorrectly
and could seriously damage the drive.
Follow the instructions in this manual to replace the cooling fan, making sure that the label is on top before inserting the
cooling fan into the drive. To ensure maximum useful product life, replace both cooling fans when performing maintenance.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair wires
and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation,
adjustment and maintenance of AC drives.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other
devices.
Failure to comply could result in damage to the drive.
Comply with proper wiring practices.
The motor may run in reverse if the phase order is backward.
Connect motor input terminals U, V and W to drive output terminals U/T1, V/T2, and W/T3. The phase order for the drive
and motor should match.
Frequently switching the drive power supply to stop and start the motor can damage the drive.
To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power
supply off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the
motor.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
399
NOTICE
7.2 Inspection
7.2
Inspection
Power electronics have limited life and may exhibit changes in characteristics or performance deterioration after years of use
under normal conditions. To help avoid such problems, it is important to perform preventive maintenance and periodic
inspection on the drive.
Drives contain a variety of power electronics such as power transistors, semiconductors, capacitors, resistors, fans, and relays.
The electronics in the drive serve a critical role in maintaining proper motor control.
Follow the inspection lists provided in this chapter as a part of a regular maintenance program.
Note: The drive will require more frequent inspection if it is placed in harsh environments, such as:
High ambient temperatures
Frequent starting and stopping
Fluctuations in the AC supply or load
Excessive vibrations or shock loading
Dust, metal dust, salt, sulfuric acid, chlorine atmospheres
Poor storage conditions.
Perform the first equipment inspection one to two years after installation.
Inspection Points
Corrective Action
Check the load coupling.
Inspect for abnormal oscillation or noise coming from Measure motor vibration.
the motor.
Tighten all loose components.
Environment
Load
400
Checked
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
7.2 Inspection
n Periodic Inspection
WARNING! Electrical Shock Hazard. Do not inspect, connect, or disconnect any wiring while the power is on. Failure to comply can result
in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even
after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching
any components.
Table 7.2 Periodic Inspection Checklist
Inspection Area
Inspection Points
Corrective Action
Main Circuit Periodic Inspection
Inspect equipment for discoloration from overheating Replace damaged components as required.
or deterioration.
The drive has few serviceable parts and may require
Inspect for damaged or deformed parts.
complete drive replacement.
Inspect for dirt, foreign particles, or dust collection on
components.
Conductors and
Wiring
Terminals
General
Checked
Operation Check
General
Circuit Boards
If
terminals are integral to a circuit board, then
Make sure all terminals have been properly tightened. board
or drive replacement may be required.
Fix any loose connections.
If an antistatic cloth or vacuum plunger cannot be
used, replace the board.
Check for any odor, discoloration, and rust. Make sure Do not use any solvents to clean the board.
connections are properly fastened and that no dust or oil Use dry air to clear away foreign matter. Use a
mist has accumulated on the surface of the board.
pressure of 39.2 104 to 58.8 104 Pa
(4 - 6 kgcm2) (57 to 85 psi).
The drive has few serviceable parts and may require
complete drive replacement.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
401
7.2 Inspection
Inspection Area
Inspection Points
Corrective Action
Cooling System Periodic Inspection
Cooling Fan,
Circulation Fan,
Control Board
Cooling Fan
Heatsink
Air Duct
Digital Operator
402
Checked
Replace as required.
Refer to Drive Cooling Fans on page 405 for
information on cleaning or replacing the fan.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
7.3
Periodic Maintenance
The drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance warning
and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to check predicted
maintenance periods for the components listed below.
Cooling Fan, Circulation Fan, Control Board Cooling Fan
Electrolytic Capacitors
Inrush Prevention Circuit
IGBTs
For replacement parts, contact the distributor where the drive was purchased or contact Yaskawa directly.
u Replacement Parts
Table 7.3 contains the estimated performance life of components that require replacement during the life of the drive. Only
use Yaskawa replacement parts for the appropriate drive model and revision.
Table 7.3 Estimated Performance Life
Component
Cooling Fan, Circulation Fan
Electrolytic Capacitors
10 years <1>
<1> The drive has few serviceable parts and may require complete drive replacement.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing parts
to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use.
Usage conditions for estimated performance life:
Ambient temperature: Yearly average of 40 C (IP00/Open Type enclosure)
Load factor: 80% maximum
Operation time: 24 hours a day
U4-03
U4-04
U4-05
U4-06
U4-07
Component
Cooling Fan
Circulation Fan
Control Board Cooling
Fan
DC Bus Capacitors
Inrush (pre-charge)
Relay
IGBT
Contents
Displays the accumulated operation time of the fan, from 0 to 99999 hours. This value is automatically reset
to 0 once it reaches 99999.
Displays the accumulated fan operation time as a percentage of the specified maintenance period.
Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period.
Displays the number of times the drive is powered up as a percentage of the performance life of the inrush
circuit.
Displays the percentage of the maintenance period reached by the IGBTs.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
403
Function
Corrective Action
The cooling fans have reached 90% of their designated Replace the cooling fan.
life time.
Contact a Yaskawa representative or the
The DC bus capacitors have reached 90% of their
nearest Yaskawa sales office on
designated life time.
possible drive replacement.
<1>
LT-1
<1>
LT-2
<1>
LT-3
<1>
LT-4
<2>
TrPC
<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2-oo = 2F). The alarm
will also trigger a digital output that is programmed for alarm indication (H2-oo = 10).
<2> This alarm message will always be output, even if the Maintenance Monitor function is not assigned to any of the digital outputs (H2-oo = 2F).
The alarm will also trigger a digital output that is programmed for alarm indication (H2-oo = 10).
404
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
7.4
NOTICE: Follow cooling fan replacement instructions. The cooling fan cannot operate properly when installed incorrectly and could seriously
damage the drive. To ensure maximum useful product life, replace all cooling fans when performing maintenance.
Contact a Yaskawa representative or the nearest Yaskawa sales office to order replacement cooling fans as required.
For drives with multiple cooling fans, replace all the fans when performing maintenance to ensure maximum product
performance life.
Cooling Fans
Circulation Fans
Page
2A0004
2A0006
2A0008
2A0010
2A0012
2A0018
2A0021
2A0030
2A0040
2A0056
2A0069
2A0081
2A0110
2A0138
2A0169
2A0211
2A0250
2A0312
2A0360
2A0415
1
1
2
2
2
2
2
2
2
2
2
2
2
3
3
1
1
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
4A0018
4A0023
4A0031
4A0038
4A0044
4A0058
4A0072
4A0088
4A0103
1
1
1
2
2
2
2
2
2
2
2
2
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
409
411
415
409
411
413
405
406
Model CIMR-Ao
4A0139
4A0165
4A0208
4A0250
4A0296
4A0362
4A0414
4A0515
4A0675
4A0930
4A1200
Cooling Fans
2
2
2
3
3
3
3
3
3
6
6
Circulation Fans
1
1
2
2
4
4
2
2
4
4
Page
5A0003
5A0004
5A0006
5A0009
5A0011
5A0017
5A0022
5A0027
5A0032
5A0041
5A0052
5A0062
5A0077
5A0099
5A0125
5A0145
5A0192
5A0242
1
1
2
2
2
2
2
2
2
2
2
2
2
2
3
3
415
419
421
425
409
411
415
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
2A0110 to 2A0138
4A0058 to 4A0103
5A0041 to 5A0052
2A0169 to 2A0415
4A0139 to 4A0362
5A0062 to 5A0242
A
B
C
D
E
G
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
407
408
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u Cooling Fan Replacement: 2A0018 to 2A0081, 4A0007 to 4A0044, and 5A0006 to 5A0032
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious
personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the
power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any
components.
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power
to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled down.
NOTICE: Follow cooling fan replacement instructions. Improper fan replacement could cause damage to equipment. Make sure the fan is
facing upwards when installing the replacement fan into the drive. Replace all fans when performing maintenance to help ensure maximum
useful product life.
Depress the right and left sides of the fan cover tabs and pull upward. Remove the fan cover from the top of the drive.
The following figure illustrates a drive with a single cooling fan.
Figure 7.3 Remove the Cooling Fan Finger Guard: 2A0018 to 2A0081, 4A0007 to 4A0044, and 5A0006 to 5A0032
Remove the cooling fan cartridge. Disconnect the pluggable connector and remove the fan.
2.
Figure 7.4 Remove the Cooling Fan: 2A0018 to 2A0081, 4A0007 to 4A0044, and 5A0006 to 5A0032
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
409
1.
Install the replacement cooling fan into the drive, ensuring the alignment pins line up as shown in the figure below.
B
C
Figure 7.5 Install the Cooling Fan: 2A0018 to 2A0081, 4A0007 to 4A0044, and 5A0006 to 5A0032
2.
Properly connect the fan power lines, then place the cable back into the recess of the drive.
A
A Back
B Front
Figure 7.6 Connect the Cooling Fan Power Supply Connectors: 2A0018 to 2A0081, 4A0007 to 4A0044,
and 5A0006 to 5A0032
3.
While pressing in on the hooks on the left and right sides of the fan finger guard, guide the fan finger guard until it
clicks back into place.
Figure 7.7 Reattach the Fan Finger Guard: 2A0018 to 2A0081, 4A0007 to 4A0044, and 5A0006 to 5A0032
4.
410
Turn on the power supply and set o4-03 to 0 to reset the Maintenance Monitor cooling fan operation time.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u Cooling Fan Replacement: 2A0110, 2A0138, 4A0058, 4A0072, 5A0041, and 5A0052
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious
personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the
power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any
components.
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power
to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled down.
NOTICE: Follow cooling fan and circulation fan replacement instructions. Improper fan replacement may cause damage to equipment. When
installing the replacement fan into the drive, make sure the fan is facing upwards. Replace all fans when performing maintenance to help
ensure maximum useful product life.
While pressing in on the hooks located on the left and right sides of the fan finger guard, free the fan finger guard
leading by lifting the back end first.
Figure 7.8 Remove the Cooling Fan Finger Guard: 2A0110, 2A0138, 4A0058, 4A0072, 5A0041, and 5A0052
2.
Lift out the back end of the fan finger guard first. Unplug the replay connector and free the fan finger guard from the
drive.
Figure 7.9 Remove the Cooling Fan: 2A0110, 2A0138, 4A0058, 4A0072, 5A0041, and 5A0052
1.
2.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
411
A Back
B Front
Figure 7.10 Cooling Fan Power Supply Connectors: 2A0110, 2A0138, 4A0058, 4A0072, 5A0041, and 5A0052
3.
Figure 7.11 Install the Cooling Fan: 2A0110, 2A0138, 4A0058, 4A0072, 5A0041, and 5A0052
4.
Tilt up the back end of the fan finger guard and slide the fan finger guard into the opening near the front of the drive,
then guide the fan finger guard into place.
Insertion area
Front of drive
Back of drive
Cross-Section
Fan finger guard
Hook
Back of drive
Hook
Front of drive
Figure 7.12 Reattach the Fan Cover: 2A0110, 2A0138, 4A0058, 4A0072, 5A0041, and 5A0052
5.
Press in on the hooks of the left and right sides of the fan cover and guide the fan finger guard until it clicks into place.
Figure 7.13 Reattach the Fan Finger Guard: 2A0110, 2A0138, 4A0058, 4A0072, 5A0041, and 5A0052
6.
412
Turn on the power supply and set o4-03 to 0 to reset the Maintenance Monitor cooling fan operation time.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
While pressing in on the hooks located on the left and right sides of the fan finger guard, free the fan finger guard by
lifting the back end first.
Figure 7.14 Remove the Cooling Fan Finger Guard: 4A0088 and 4A0103
Lift up directly on the cooling fan as shown in Figure 7.15. Unplug the relay connector and release the fan from the
drive.
2.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
413
1.
Install the replacement fan into the drive. Align the pins as shown in Figure 7.16.
2.
Properly connect the fan power lines then replace the power supply connectors and cables into the recess of the drive.
A
A Back
B Front
Figure 7.17 Cooling Fan Power Supply Connectors: 4A0088 and 4A0103
3.
Angle the fan finger guard as shown in Figure 7.18 and insert the connector tabs into the corresponding holes on the
drive.
Holes for connector tabs.
Hook
Four tabs
Back of Drive
Hook
Front of Drive
Figure 7.18 Reattach the Fan Finger Guard: 4A0088 and 4A0103
4.
414
While pressing in on the hooks of the left and right sides of the fan finger guard, guide the fan finger guard until it clicks
back into place.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Figure 7.19 Reattach the Fan Finger Guard: 4A0088 and 4A0103
5.
Turn on the power supply and set o4-03 to 0 to reset the Maintenance Monitor cooling fan operation time.
u Cooling Fan Replacement: 2A0169 to 2A0415, 4A0139 to 4A0362, and 5A0062 to 5A0242
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious
personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the
power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any
components.
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power
to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled down.
NOTICE: Follow cooling fan and circulation fan replacement instructions. Improper fan replacement may cause damage to equipment. When
installing the replacement fan into the drive, make sure the fan is facing upwards. Replace all fans when performing maintenance to help
ensure maximum useful product life.
2A0360, 2A0415,
4A0250, 4A0296, 4A0362
5A0192, 5A0242
C
E
A Fan unit
B Fan relay cable
C Fan connector (CN6)
3.
Remove the screws holding the fan unit in place and slide the fan unit out of the drive.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
415
Figure 7.21 Remove the Fan Unit: 2A0169 to 2A0415, 4A0139 to 4A0362, and 5A0062 to 5A0242
4.
Note: Do not pinch the fan cable between parts when reassembling the fan unit.
2A0360, 2A0415,
4A0362,
5A0192, 5A0242
4A0250, 4A0296
B
C
A Fan guard
B Cable cover
C Cooling fan
D Circulation fan
Figure 7.22 Fan Unit Disassembly: 2A0169 to 2A0415, 4A0139 to 4A0362, and 5A0062 to 5A0242
n Cooling Fan Wiring: 2A0169, 2A0211, 4A0139, 4A0165, and 5A0062 to 5A0099
1.
Position the protective tube so the fan connector sits in the center of the protective tube.
Protective tube
2.
416
Place the fan connector covered by the tube as shown in Figure 7.23.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4A0165
Fan B2
Fan B1
Figure 7.23 Cooling Fan Wiring: 2A0169, 2A0211, 4A0139, 4A0165, and 5A0062 to 5A0099
3.
Make sure that the protective tube does not stick out beyond the fan guard.
Position the protective tube so the fan connector sits in the center of the protective tube.
Protective tube
2.
Insert the connector for fan B2 and guide the lead wire for fan B2 so the cable hook holds it in place.
Insert the connector for fan B1.
Fan B1
Cable hook
Fan B2
Figure 7.24 Cooling Fan Wiring: 2A0250, 2A0312, 4A0208, 5A0125, and 5A0145
3.
Make sure that the protective tube does not stick out beyond the fan guard.
n Cooling Fan Wiring: 2A0360, 2A0415, 4A0250 to 4A0362, 5A0192, and 5A0242
1.
Position the protective tube so the fan connector sits in the center of the protective tube.
Protective tube
2.
3.
In the space between fans 1 and 2, place the fan connector for fan B2 in front of the fan connector for fan B1.
Place the connector for fan B3 between fans B2 and B3.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
417
Fan B3
Fan B1
Fan B2
Figure 7.25 Cooling Fan Wiring: 2A0360, 2A0415, 4A0250 to 4A0362, 5A0192, and 5A0242
4.
5.
Note: Do not pinch the fan cable between parts when reassembling the fan unit.
Reverse the procedure described above to reinstall the cooling fan unit.
Figure 7.26 Install the Cooling Fan Unit: 2A0169 to 2A0415 and 4A0139 to 4A0362, and 5A0062 to 5A0242
2.
3.
418
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
E
F
B
C
G
A Fan unit
B Circulation fan unit
C Circulation fan
D Circulation fan relay cable
Remove the circulation fan relay cable from the hook. Remove the fan connector (CN7).
Remove the screws holding the fan units in place and slide the fan units out of the drive.
Periodic Inspection &
Maintenance
3.
4.
7
Figure 7.28 Remove the Fan Unit: 4A0414
5.
Remove the fan guard and circulation fan casing. Replace the cooling fans.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
419
A Fan guard
B Cooling fan
C Fan unit case
Position the protective tube so the fan connector sits in the center of the protective tube.
Protective tube
2.
Place the fan connector covered by the tube as shown in Figure 7.30.
Cooling Fan B1
Connector
for fan B1
Connector
for fan B2
Connector
for fan B3
3.
420
Reverse the procedure described above to reinstall the cooling fan unit.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
2.
3.
7
E
A Fan unit
B Fan relay connector
C Circuit board cooling fan
D Circuit board cooling fan case
E Hook
F Circuit board cooling fan
connector
G Circuit board cooling fan cable
3.
Loosen all nine screws and slide the panel to the right.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
421
Slide Panel
Screw
4.
Remove the slide panel, fan unit, and circuit board cooling fan unit.
5.
Note: Do not pinch the fan cable between parts when reassembling the fan unit.
A Cooling fan
6.
422
Turn the fan unit over and replace the circulation fans.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
A Circulation fan 1
B Circulation fan 2
7.
Place the cooling fan connectors and guide the lead wires so they are held in place by the cable hooks.
Cooling Fan B2
Cooling Fan B1
Relay Connector
Relay Connector
Relay Connector
Cooling Fan B3
7
Cooling Fan B4
Cooling Fan B5
2.
Guide the lead wires so that they are held in place by the cable hooks and place the circulation fan connectors between
the fan and the fan unit.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
423
Cooling Fan B2
Cooling Fan B1
Relay Connector
Cooling Fan B5
Cooling Fan B4
3.
Position the protective tube so the fan connector sits in the center of the protective tube. (Circuit board cooling fans
only)
Protective tube
4.
Guide the lead wires through the provided hooks so the wires are held in place.
Circuit Board Cooling Fan B6
Circuit Board Cooling Fan B7
Relay Connector
Relay Connector
5.
Reverse the procedure described above to reinstall the cooling fan unit.
Figure 7.41 Install the Cooling Fan Unit: 4A0515 and 4A0675
2.
3.
424
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
2.
Remove the connectors for the cooling fan relay and the circuit board cooling fan.
D
B
A
H
F
G H
E
F
3.
Loosen screws A (4 count) and B (18 count) and slide the panel to the right.
Note: The fan unit can be removed by loosening these screws; they do not need to be removed.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
425
Screw B
Slide Panel
Slide Panel
Screw A
Screw A
Screw B
Screw A
Screw B
4.
Remove the slide panel, fan units, and circuit board cooling fan unit.
5.
426
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
A
C
A Cooling fan
B Fan unit case
6.
Place the cooling fan connectors and guide the lead wires so that they are held in place by the cable hooks.
Fun Unit Case (L)
Cooling Fan B2
Relay Connector
Cooling Fan B3
Relay
Relay Connector
Connector
Cooling Fan B4
Cooling Fan B5
Hook
Relay Connector
Cooling Fan B6
Relay Connector
Relay
Connector
7.
Turn the fan unit over and replace the circulation fans.
7
A Circulation fan 1
B Circulation fan 2
8.
Place the cooling fan connectors and guide the lead wires so that they are held in place by the cable hooks.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
427
Circulation Fan B8
Relay Connector
Circulation Fan B7
Hook
Circulation Fan B9
Hook
9.
Note: Figure 7.49 shows the right side circuit board cooling fan.
A
10.Position the protective tube so the fan connector sits in the center of the protective tube. (Circuit board cooling fans
only)
Protective tube
11.Guide the lead wires through the provided hooks so the wires are held in place.
Circuit Board Cooling Fan B6
Circuit Board Cooling Fan B7
Relay Connector
Relay Connector
428
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Reverse the procedure described above to reinstall the cooling fan unit.
Note: Properly connect the relay connectors to the fan unit connectors.
Figure 7.51 Install the Cooling Fan Unit: 4A0930 and 4A1200
2.
3.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
429
7.5
C Blind cover
3.
Loosen the screws holding the filter case in place. Do not remove the screws.
430
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
4.
Hold the bottom of the filter case and slide it out from the drive.
B
A
A Opening
B Filter case
5.
A Air filter
B Filter case
Figure 7.55 Remove the Air Filter
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
431
7.6
Drive Replacement
u Serviceable Parts
The drive contains some serviceable parts. The following parts can be replaced over the life span of the drive:
Terminal board I/O PCBs
Cooling fan(s)
Front cover
Replace the drive if the main power circuitry is damaged. Contact your local Yaskawa representative before replacing parts
if the drive is still under warranty. Yaskawa reserves the right to replace or repair the drive according to Yaskawa warranty
policy.
u Terminal Board
The drive has a modular I/O terminal block that facilitates quick drive replacement. The terminal board contains on-board
memory that stores all drive parameter settings and allows the parameters to be saved and transferred to the replacement drive.
To transfer the terminal board, disconnect the terminal board from the damaged drive then reconnect it to the replacement
drive. Once transferred, there is no need to manually reprogram the replacement drive.
Note: If the damaged drive and the new replacement drive are have different capacities, the data stored in the terminal board cannot be transferred
to the new drive and an oPE01 error will appear on the display. The terminal board can still be used, but parameter setting from the old drive
cannot be transferred. The replacement drive must be initialized and manually programmed.
C
D
432
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
1.
2.
Loosen the screws holding the terminal board in place. Remove the screw securing the bottom cover and remove the
bottom cover from the drive.
Note: IP00/Open Type enclosure drives do not have a bottom cover or conduit.
7
Figure 7.58 Unscrew the Terminal Board and Remove the Bottom Cover
3.
Slide the terminal board as illustrated by the arrows to remove it from the drive along with the bottom cover.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
433
4.
5.
Disconnect all option cards and options, making sure they are intact before reusing.
Replace the drive and wire the main circuit.
After wiring the main circuit, connect the terminal block to the drive as shown in Figure 7.61. Use the installation screw
to fasten the terminal block into place.
2.
3.
4.
434
Reconnect options for the new drive the same way the options were connected in the old drive. Connect option boards
to the same option ports in the new drive that were used in the old drive.
Replace the terminal cover.
After powering on the drive, all parameter settings are transferred from the terminal board to the drive memory. If an
oPE04 error occurs, load the parameter settings saved on the terminal board to the new drive by setting parameter
A1-03 to 5550. Reset the Maintenance Monitor function timers by setting parameters o4-01 through o4-12 to 0, and
parameter o4-13 to 1.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
8
Peripheral Devices & Options
This chapter explains the installation of peripheral devices and options available for the drive.
8.1
8.2
8.3
8.4
8.5
SECTION SAFETY...............................................................................................436
DRIVE OPTIONS AND PERIPHERAL DEVICES................................................437
CONNECTING PERIPHERAL DEVICES.............................................................439
OPTION CARD INSTALLATION..........................................................................440
INSTALLING PERIPHERAL DEVICES................................................................442
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
435
8.1
Section Safety
DANGER
Electrical Shock Hazard
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or
shields before operating the drives and run the drives according to the instructions described in this manual.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation,
adjustment and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work
on the drive.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
436
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
8.2
The following table of peripheral devices lists the names of the various accessories and options available for Yaskawa drives.
Contact Yaskawa or your Yaskawa agent to order these peripheral devices.
Peripheral Device Selection: Refer to the Yaskawa catalog for selection and part numbers.
Peripheral Device Installation: Refer to the corresponding option manual for installation instructions.
Table 8.1 Available Peripheral Devices
Option
Model Number
DC link choke
AC Reactor
Braking Resistor
Description
Power Options
Improves the power factor by suppressing harmonic distortion from the power supply.
Protects the drive when operating from a large power supply and improves the power factor by
suppressing harmonic distortion. Highly recommended for power supplies that exceed 600 kVA.
For use with systems that require dynamic braking with up to 3% ED. If higher ED is required,
use a Braking Resistor Unit.
Note: Not rated for 600 V class drive models.
Input/Output Option Cards
Allows high precision, high resolution analog reference input
Input channels: 3
Voltage input: -10 to 10 Vdc (20 k), 13- bit signed
Current input: 4 to 20 mA or 0 to 20 mA (250 k), 12-bit
Analog Input
AI-A3
Analog Monitor
AO-A3
Digital Input
DI-A3
Digital Output
DO-A3
PG-X3
PG-B3
EtherNet/IP
Modbus TCP/IP
DeviceNet
PROFIBUS-DP
MECHATROLINK-II
SI-EN3
SI-EM3
SI-N3
SI-P3
SI-T3
CC-Link <1>
SI-C3
CANopen <1>
SI-S3
LED Operator
Remote Operator Cable
USB Copy Unit
Interface Options
JVOP-182
5-digit LED operator; max. cable length for remote usage: 3 m
UWR000051, 1 m cable RJ-45, 8-pin straight through, UTP CAT5e, extension cable (1 m or 2 m) to connect the digital
UWR000052, 2 m cable operator for remote operation.
Allows the user to copy and verify parameter settings between drives.
JVOP-181
Functions as an adapter to connect the drive to a USB port on a PC.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
437
Model Number
Description
EZZ020800A/B/C/D
Mechanical Options
Installation kit for mounting the drive with the heatsink outside of the panel (Side-by-Side
mounting possible)
100-054-503
100-054-504
24 V Power Supply
PS-A10L, PS-A10H
Others
Supplies the drive controller with 24 Vdc power during main power loss.
Use PS-A10H for 600 V class drive models.
DriveWizard 2010
Contact Yaskawa
PC Software Tools
PC tool for drive setup and parameter management
DriveWorksEZ
Contact Yaskawa
<1> Limited support. Contact a Yaskawa representative or the nearest Yaskawa sales office for assistance.
438
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
8.3
Figure 8.1 illustrates how to configure the drive and motor to operate with various peripheral devices.
Refer to the specific manual for the devices shown below for more detailed installation instructions.
Engineering Software Tools
DriveWizard Plus
DriveWorksEZ
LOCK
JVOP-181
ERR
COM
ad
Re
rify
Ve
YASKAWA
py
Co
USB Cable
(Type-AB)
PC
Surge
Absorber
+2
+1
DC Link Choke
AC Reactor
Braking Resistor
or Braking Resistor Unit
Ground
Input Side
Noise Filter
24 V control
power supply
unit
Motor
Ground
Note: If the drive is set to trigger a fault output when the fault restart function is activated (L5-02 = 1), then a sequence to interrupt power when a
fault occurs will turn off the power to the drive while the drive attempts to restart. The default setting for L5-02 is 0 (fault output active during
restart).
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
439
8.4
This section provides instructions on installing the option cards listed in Table 8.1.
Port/Connector
CN5-A
PG-X3, PG-B3
CN5-B, C
DO-A3, AO-A3
CN5-A, B, C
2 <2>
1
<1> Option cards AI-A3 and DI-A3 cannot set the frequency reference when installed to ports CN5-B or CN5-C. It is still possible, however, to view
the input status using U1-21, U1-22, U1-23 (for AI-A3), and U1-17 (for DI-A3).
<2> Use port CN5-C when connecting one PG option card. Use ports CN5-B and CN5-C when connecting two PG option cards.
u Installation Procedure
DANGER! Electircal Shock Hazard. Disconnect all power to the drive and wait at least the amount of time specified on the drive front cover
safety label. After all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing
to prevent electric shock. The internal capacitor remains charged even after the power supply is turned off.
WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death
or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives and Option Cards.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option card, drive, and circuit
boards. Failure to comply may result in ESD damage to circuitry.
NOTICE: Damage to Equipment. Tighten all terminal screws to the specified tightening torque. Failure to comply may cause the application
to operate incorrectly or damage the drive.
Use the procedure described below when installing option cards to the drive.
1.
2.
Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the operator and
front cover. Refer to Digital Operator and Front Cover on page 83.
Insert the CN5 connector on the option card into the matching CN5 connector on the drive, then fasten it into place
using one of the screws included with the option card.
A
E
F
B
C
G
J
A Connector CN5-C
B Connector CN5-B
C Connector CN5-A
D Drive grounding terminal (FE)
E Insert connector CN5 here
F Option card
G Mounting screw
H Ground wire
I Use wire cutters to create an
opening for cable lines
J Front cover
K Digital operator
L Terminal cover
440
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
3.
Connect the ground wire to the ground terminal using one of the screws.
Some option cards come with ground wires of different lengths for connecting the card to the drive. Select the ground
wire with the most appropriate length.
Note: There are only two screw holes on the drive for ground terminals. When connecting three option cards, two ground wires will need
to share the same ground terminal.
4.
Wire the option card to the terminal block on the option card.
Refer to the option card manual for wiring instructions.
When installing option cards to models CIMR-Ao2A0004 to 2A0040, CIMR-Ao4A0002 to 4A0023,
and CIMR-Ao5A0003 to 5A0011, it may be necessary to route the cables connected to the option through the top
cover to the outside. In this case, cut out the perforated openings on the left side of the drive top cover, being careful
not to leave any sharp edges that may damage the cable.
Models CIMR-Ao2A0056 to 2A0415, CIMR-Ao4A0031 to 4A1200, and CIMR-Ao5A0017 to 5A0242 have enough
space to keep all wiring inside the unit.
5.
Note: 1. Leave enough space when wiring to easily reattach the front cover. Make sure no wires get caught between the front cover
and the drive.
2. Any exposed wiring will void the wall-mount enclosure rating.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
441
8.5
This section describes the proper steps and precautions to take when installing or connecting various peripheral devices to the
drive.
NOTICE: Use a class 2 power supply when connecting to the control terminals. Improper application of peripheral devices could result in
drive performance degradation due to improper power supply. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control,
Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies.
Drive
Braking Resistor
B2
442
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B1
Thermal Relay
Trip Contact
Drive
B2
MC
R
S
T
R/L1
S/L2
T/L3
200/400/600 V
THRX OFF
ON
MC
Drive
SA
MC
THRX
1 2
Braking Resistor Unit
(Close: Overheat)
SA
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
443
1
Thermal Overload
Protector Trip Contact
Drive
Thermal Relay
Trip Contact
Figure 8.8 Connecting a Braking Unit (CDBR type) and Braking Resistor Unit (LKEB type)
(CIMR-Ao2A0169 to 2A0415, 4A0088 to 4A1200)
+3
2 Braking
Resistor
Unit
B
1
P
+ +0
Level Detector
Drive
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
2 Braking
Resistor
Unit
B
1
P
MASTER
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
+0
2 Braking
Resistor
Unit
B
1
P
+0
MASTER
MASTER
SLAVE
+15
5
2
Braking Unit 1
3
SLAVE
SLAVE
Braking Unit 3
Braking Unit 2
444
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u Installing a Molded Case Circuit Breaker (MCCB) or Ground Fault Circuit Interrupter
(GFCI)
Install an MCCB or GFCI for line protection between the power supply and the main circuit power supply input terminals
R/L1, S/L2, and T/L3. This protects the main circuit and devices wired to the main circuit while also providing overload
protection.
NOTICE: Prevent Equipment Damage. Install a fuse and a GFCI to models CIMR-Ao4A0930 and 4A1200, Failure to comply may result in
damage to the power supply in the event of a short circuit.
MCCB or GFCI
MC
MC
SA
R/L1
S/L2
T/L3
MB
MC
MC
A Power supply
B Drive
Note: Choose a GFCI designed specifically for an AC drive. The operation time should be at least 0.1 s with sensitivity amperage of at least 200 mA
per drive. The output waveform of the drive may cause an increase in leakage current. This may in turn cause the leakage breaker to malfunction.
Increase the sensitivity amperage or lower the carrier frequency to correct the problem.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
445
Drive outputs generate high-frequency leakage current as a result of high-speed switching. Install a GFCI on the input side of
the drive to switch off potentially harmful leakage current.
Factors in determining leakage current:
Size of the AC drive
AC drive carrier frequency
Motor cable type and length
EMI/RFI filter
If the GFCI trips spuriously, consider changing these items or use a GFCI with a higher trip level.
n Connecting an AC Reactor
C
A
R/L1
S/L2
T/L3
A Power supply
B MCCB
C AC reactor
D Drive
Figure 8.11 Connecting an AC Reactor
R/L1
S/L2
T/L3
+1
+2
A Power supply
B MCCB
C Drive
D DC link choke
Figure 8.12 Connecting a DC Link Choke
446
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
MCCB
R/L1
S/L2
T/L3
E
MCCB
A Power supply
B Input-side noise filter
(model LNFD-oo)
C Drive
D Other control device
A Power supply
B Drive
MCCB
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
D
M
Radiated Noise: Electromagnetic waves radiated from the drive and cables create noise throughout the radio bandwidth
that can affect surrounding devices.
Induced Noise: Noise generated by electromagnetic induction can affect the signal line and may cause the controller to
malfunction.
Preventing Induced Noise
Use a noise filter on the output side or use shielded cables. Lay the cables at least 30 cm away from the signal line to prevent
induced noise.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
447
MCCB
C
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
E
G
F
E Separate at least 30 cm
F Controller
G Signal line
A Power supply
B Drive
C Shielded motor cable
D Motor
The drive, input lines, and output lines generate radio frequency noise. Use noise filters on input and output sides and install
the drive in a metal enclosure panel to reduce radio frequency noise.
Note: The cable running between the drive and motor should be as short as possible.
A
C
B
MCCB
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
A Metal enclosure
B Power supply
C Noise filter
D Drive
G
M
E Noise filter
F Shielded motor cable
G Motor
Manufacturer: Bussmann
Model
448
2A0004
FWH-70B
70
2A0006
FWH-70B
70
2A0008
FWH-70B
70
2A0010
FWH-70B
70
2A0012
FWH-70B
70
2A0018
FWH-90B
90
2A0021
FWH-90B
90
2A0030
FWH-100B
100
2A0040
FWH-200B
200
2A0056
FWH-200B
200
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Manufacturer: Bussmann
Model
2A0069
FWH-200B
200
2A0081
FWH-300A
300
2A0110
FWH-300A
300
2A0138
FWH-350A
350
2A0169
FWH-400A
400
2A0211
FWH-400A
400
2A0250
FWH-600A
600
2A0312
FWH-700A
700
2A0360
FWH-800A
800
2A0415
FWH-1000A
1000
4A0002
FWH-40B
40
4A0004
FWH-50B
50
4A0005
FWH-70B
70
4A0007
FWH-70B
70
4A0009
FWH-90B
90
4A0011
FWH-90B
90
4A0018
FWH-80B
80
4A0023
FWH-100B
100
4A0031
FWH-125B
125
4A0038
FWH-200B
200
4A0044
FWH-250A
250
4A0058
FWH-250A
250
4A0072
FWH-250A
250
4A0088
FWH-250A
250
4A0103
FWH-250A
250
4A0139
FWH-350A
350
4A0165
FWH-400A
400
4A0208
FWH-500A
500
4A250
FWH-600A
600
4A0296
FWH-700A
700
4A0362
FWH-800A
800
4A0414
FWH-800A
800
4A0515
FWH-1000A
1000
4A0675
FWH-1200A
1200
4A0930
FWH-1200A
1200
4A1200
FWH-1600A
1600
FWP-50B
50
5A0004
FWP-50B
50
5A0006
FWP-60B
60
5A0009
FWP-60B
60
5A0011
FWP-70B
70
5A0017
FWP-100B
100
5A0022
FWP-100B
100
5A0027
FWP-125A
125
5A0032
FWP-125A
125
5A0041
FWP-175A
175
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
449
Manufacturer: Bussmann
Model
5A0052
FWP-175A
175
5A0062
FWP-250A
250
5A0077
FWP-250A
250
5A0099
FWP-250A
250
5A0125
FWP-350A
350
5A0145
FWP-350A
350
5A0192
FWP-600A
600
5A0242
FWP-600A
600
Generally, thermal relays are applied on general-purpose motors. When general-purpose motors are driven by AC drives, the
motor current is approximately 5% to 10% greater than if driven by a commercial power supply. In addition, the cooling
capacity of a motor with a shaft-driven fan decreases when operating at low speeds. Even if the load current is within the motor
rated value, motor overheating may occur. A thermal relay cannot effectively protect the motor due to the reduction of cooling
at low speeds. For this reason, apply the UL recognized electronic thermal overload protection function built into the drive
whenever possible.
UL recognized electronic thermal overload function of the drive: Speed-dependent heat characteristics are simulated using
data from standard motors and force-ventilated motors. The motor is protected from overload using this function.
Using a Single Drive to Operate Multiple Motors
Turn off the electronic thermal overload function. Please refer to the appropriate product instruction manual to determine
which parameter disables this function.
Note: The UL recognized electronic thermal overload function cannot be applied when operating multiple motors with a single drive.
When a high carrier frequency and long motor cables are used, nuisance tripping of the thermal relay may occur due to increased
leakage current. To avoid this, reduce the carrier frequency or increase the tripping level of the thermal overload relay.
450
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Current waveforms generated by high carrier frequency PWM drives tend to increase the temperature in overload relays. It
may be necessary to increase the trip level setting when encountering nuisance triggering of the relay.
WARNING! Fire Hazard. Confirm an actual motor overload condition is not present prior to increasing the thermal oL trip setting. Check
local electrical codes before making adjustments to motor thermal overload settings. Failure to comply could result in death or serious injury.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
451
452
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Appendix: A
Specifications
A.1
A.2
A.3
A.4
A.5
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
453
Overload Tolerance
0: Heavy Duty
1: Normal Duty
(default)
120% rated output current for 60 s varies by model 2 kHz, Swing PWM
2 kHz
<1> Refer to Power Ratings on page 455 for information on rating changes based on drive model.
TERMS
HD and ND: HD refers to applications requiring constant torque output, while ND refers to applications with
variable torque needs. The drive allows the user to select HD or ND torque depending on the application. Fans,
pumps, and blowers should use ND (C6-01 = 1), and other applications generally use HD (C6-01 = 0).
Swing PWM: Swing PWM equivalent to a 2 kHz audible noise. This function turns the motor noise into a less
obtrusive white noise.
Note: Differences between HD ratings and ND ratings for the drive include rated input and output current, overload capacity, carrier frequency, and
current limit. The default setting is for ND (C6-01 = 1).
454
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Input
<2>
Specification
ND Rating
HD Rating
ND Rating
HD Rating
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
Rated Output Capacity
(kVA) <4>
ND Rating
HD Rating
ND Rating
<5>
<5>
HD Rating
0004
0.75
0.75
3.9
2.9
0006
1
1
7.3
5.8
0008
2
2
8.8
7
0010
3
2
10.8
7.5
0012
3
3
13.9
11
0018
5
3
18.5
15.6
0021
7.5
5
24
18.9
0030
10
7.5
37
28
2.2
1.3
3.1
2.2
4.1
3.1
1.3
2.3
1.2
1.9
<6>
<6>
3.5
3.2
<6>
2.6
-15 to 10%
5%
5.8
7.8
4.1
5.8
9.5
7.8
14
9.5
18
14
3.7
6.7
11.4
4.6
4.2
5.3
<6>
<6>
<6>
<6>
9.6
12
6.9
11
<6>
<6>
<6>
<6>
6.7
9.5
<6>
<6>
17.5
21
30
14
17.5
<6>
<6>
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
25
<6>
Specifications
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating..
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
455
Input
<2>
Specification
ND Rating
HD Rating
ND Rating
HD Rating
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
Rated Output Capacity
(kVA) <4>
ND Rating
HD Rating
ND Rating
<5>
<5>
HD Rating
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
0040
15
10
52
37
0056
20
15
68
52
0069
25
20
80
68
0081
30
25
96
80
0110
40
30
111
82
0138
50
40
136
111
0169
60
50
164
136
0211
75
60
200
164
27
18
36
27
44
36
-15 to 10%
5%
52
51
44
37
15.2
21
26
31
12.6
17.9
<6>
<6>
<6>
<6>
<6>
<6>
<7>
40
56
69
81
110
138
169
211
33
47
60
75
85
115
145
180
<6>
<6>
<6>
23
<6>
29
<6>
42
32
<6>
62
51
75
62
91
75
53
64
80
44
<6>
55
<6>
69
<7>
User adjustable
between 1 and
10 kHz
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
456
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Input
Specification
<1>
<2>
0250
100
75
271
200
ND Rating
HD Rating
ND Rating
HD Rating
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
ND Rating
Rated Output Capacity (kVA)
0360
150
125
394
324
0415
175
150
471
394
<5>
<4>
HD Rating
ND Rating
0312
125
100
324
271
124
91
148
124
180
148
215
180
95
119
137
158
82
108
132
158
250
312
360
415
215
283
346
415
<6>
<5>
HD Rating
<6>
<6>
<6>
<6>
<6>
<5>
<5>
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Specifications
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
457
Specification
ND Rating
Maximum Applicable Motor
Capacity (HP) <1>
HD Rating
ND Rating
Input Current (A) <2>
HD Rating
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
Rated Output Capacity
(kVA) <4>
Rated Output Current
(A)
0002
0.75
0.75
2.1
1.8
0004
2
2
4.3
3.2
0005
3
3
5.9
4.4
0007
3
3
8.1
6
0009
5
5
9.4
8.2
-15 to 10%
5%
10.0
14.5
8.1
10.0
4.3
2.3
6.1
4.3
8.1
6.1
ND Rating <5>
HD Rating
1.6
3.1
4.1
5.3
6.7
1.4
2.6
3.7
4.2
<5>
2.1
4.1
5.4
6.9
HD Rating
Output
0018
10
7.5
20
15
0023
15
10
24
20
0031
20
15
38
29
2.3
1.4
ND Rating
0011
7.5
5
14
10.4
1.8
<6>
3.4
<6>
4.8
<6>
5.5
<6>
19.4
14.6
28.4
19.2
37.5
28.4
8.5
13.3
17.5
24
5.5
11.3
13.7
18.3
8.8
11.1
17.5
23
31
9.2
14.8
7.2
<6>
<6>
<6>
18
<6>
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
24
<6>
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,
and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
458
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Input
<2>
ND Rating
HD Rating
ND Rating
HD Rating
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
Rated Output Capacity
(kVA) <4>
Rated Output Current
(A)
Output
Specification
0038
25
20
44
39
0044
30
25-30
52
44
0058
40
25-30
58
43
0072
50
40
71
58
0088
60
50-60
86
71
0103
75
50-60
105
86
-15 to 10%
5%
64.9
78.6
53.0
64.9
54.9
46.6
53.0
39.3
ND Rating <5>
HD Rating
29
34
44
55
67
24
30
34
48
57
<5>
38
44
58
72
88
91
HD Rating
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
0165
125
100
170
142
46.6
37.5
ND Rating
0139
100
75
142
105
31
<6>
39
<6>
45
<6>
60
<6>
75
<6>
96.0
78.6
130
96.0
156
130
78
106
126
69
85
114
103
139
165
112
150
<6>
<6>
<7>
User adjustable
between 1 and
10 kHz
Specifications
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,
and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
459
0250
200
0296
250
0362
300
0414
350
0515
400-450
HD Rating
125-150
150
200
250
300
ND Rating
207
248
300
346
HD Rating
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
170
207
248
300
Input
<2>
Specification
0208
150
ND Rating
<5>
HD Rating
ND Rating
<5>
HD Rating
Overload Tolerance
Carrier Frequency
0930
750
1200
1000
350
0675
500-550
400-450500
650
900
410
465
657
922
1158
346
410
584
830
1031
189
155
227
189
274
227
316
274
-15 to 10%
5%
375
316
159
191
226
276
316
392
514
709
915
137
165
198
232
282
343
461
617
831
208
250
296
362
414
515
675
930
1200
180
216
260
304
370
450
605
810
1090
<6>
<6>
<6>
<6>
<6>
<6>
<6>
<6>
<5>
<5>
425
375
601
534
843
759
1059
943
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
2 kHz
0.95 [input
voltage]
400 Hz (user-adjustable)
150 Hz (useradjustable)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,
and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
460
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Input
<2>
ND Rating
HD Rating
ND Rating
HD Rating
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
Rated Output Capacity
(kVA) <3>
Rated Output Current
(A)
Output
Specification
ND Rating
<4>
HD Rating
ND Rating
<4>
HD Rating
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
0003
2
1
3.6
1.9
0004
3
2
5.1
3.6
0006
5
3
8.3
5.1
0009
7.5
5
12
8.3
0011
10
7.5
16
12
0017
15
10
23
16
0022
20
15
31
23
0027
25
20
38
31
0032
30
25
45
38
35
26
43
35
51
43
22
27
32
4.1
2.2
5.8
4.1
9.5
5.8
2.7
3.9
6.1
1.7
3.5
4.1
<5>
<5>
<5>
2.7
3.9
6.1
1.7
3.5
4.1
6.3
<5>
<5>
<5>
<5>
<5>
11
9.8
<5>
17
12
17
22
27
<5>
<5>
<5>
<5>
11
17
22
27
32
9.8
12.5
17
22
<5>
<5>
<5>
<5>
27
<5>
Specifications
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
461
Specification
Input
<1>
<2>
ND Rating
HD Rating
ND Rating
HD Rating
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
ND Rating
Rated Output Capacity (kVA)
HD Rating
ND Rating
<4>
<3>
<4>
HD Rating
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
0041
40
25-30
44
33
0052
50
40
54
44
0062
60
50-60
66
54
0077
75
50-60
80
66
0099
100
75
108
80
50
38
62
50
41
52
62
32
41
52
91
75
123
91
77
99
62
77
<5>
<5>
<5>
<5>
<6>
41
52
62
77
99
32
41
52
62
<5>
<5>
<5>
77
<5>
<6>
User
adjustable
between 2 and
8 kHz
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be increased to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
462
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Input
Specification
<1>
<2>
ND Rating
HD Rating
ND Rating
HD Rating
Rated Voltage
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
ND Rating
Input Power (kVA)
HD Rating
ND Rating
Rated Output Capacity (kVA)
<4>
<3>
HD Rating
ND Rating
<4>
HD Rating
0125
125
100
129
108
0145
150
125
158
129
0192
200
150
228
158
0242
250
200
263
228
147
123
301
261
124
144
191
241
99
129
171
199
125
145
192
242
99
130
172
200
<4>
<4>
<4>
<4>
<4>
<4>
<4>
<4>
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Specifications
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be increased to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
463
Control Method
Specification
The following control methods can be set using drive parameters:
V/f Control (V/f)
V/f Control with PG (V/f w/PG)
Open Loop Vector Control (OLV)
Closed Loop Vector Control (CLV)
Open Loop Vector Control for PM (OLV/PM)
Advanced Open Loop Vector Control for PM (AOLV/PM)
Closed Loop Vector Control for PM (CLV/PM)
Note: PM motor control modes are not available on 600 V class drives,
CIMR-Ao5Aoooooo.
0.01 to 400 Hz
Digital input: within 0.01% of the max output frequency (-10 to +40 C)
Analog input: within 0.1% of the max output frequency (25 C 10 C)
inputs: 0.01 Hz
Frequency Setting Resolution Digital
Analog inputs: 1/2048 of the maximum output frequency setting (11 bit plus sign)
Control
Characteristics
<2>
<2>
Torque Limit
Accel/Decel Time
Braking Torque
Braking Transistor
V/f Characteristics
464
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Protection
Functions
Specification
Electronic thermal overload relay
Drive stops when output current exceeds 200% of Heavy Duty Rating
Drive stops after 60 s at 150% of rated Heavy Duty output current <6>
200 V class: Stops when DC bus voltage exceeds approx. 410 V
400 V class: Stops when DC bus voltage exceeds approx. 820 V
600 V class: Stops when DC bus voltage exceeds approx. 1040 V
200 V class: Stops when DC bus voltage falls below approx. 190 V
400 V class: Stops when DC bus voltage falls below approx. 380 V
600 V class: Stops when DC bus voltage falls below approx. 475 V
Environment
Protection Design
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
465
Specifications
Ground Protection
Normal Duty
Heavy Duty
Rated Amps
(A)
Heatsink Loss
(W)
Interior Unit
Loss (W)
Rated Amps
(A) <3>
Heatsink Loss
(W)
Interior Unit
Loss (W)
2A0004
3.2
<1>
14.8
44
59
3.5
18.4
47
66
2A0006
5.0
<1>
24
48
72
6.0
31
51
82
6.9
<1>
35
49
84
8.0
43
52
95
2A0010
8.0
<1>
43
52
95
9.6
57
58
115
2A0012
11.0
<1>
64
58
122
12.0
77
64
141
14.0
<1>
77
60
137
17.5
101
67
168
17.5
<1>
101
67
168
21
138
83
222
2A0008
2A0018
2A0021
2A0030
25 <1>
194
92
287
30
262
117
379
2A0040
33 <1>
214
105
319
40
293
145
437
2A0056
47 <1>
280
130
410
56
371
175
546
2A0069
60 <1>
395
163
558
69
491
205
696
2A0081
75 <1>
460
221
681
81
527
257
785
2A0110
85 <1>
510
211
721
110
719
286
1005
2A0138
115 <1>
662
250
912
138
842
312
1154
2A0169
145 <1>
816
306
1122
169
1014
380
1394
2A0211
180 <2>
976
378
1354
211
1218
473
1691
2A0250
215 <2>
1514
466
1980
250
1764
594
2358
2A0312
283 <2>
1936
588
2524
312
2020
665
2686
2A0360
346 <2>
2564
783
3347
360
2698
894
3591
2A0415
415 <3>
2672
954
3626
415
2672
954
3626
Rated Amps
(A)
Heatsink Loss
(W)
Interior Unit
Loss (W)
Rated Amps
(A) <3>
Heatsink Loss
(W)
Interior Unit
Loss (W)
4A0002
1.8
<1>
15.9
45
61
2.1
20
48
68
4A0004
3.4
<1>
25
46
70
4.1
32
49
81
4.8
<1>
37
49
87
5.4
45
53
97
4A0007
5.5
<1>
48
53
101
6.9
62
59
121
4A0009
7.2
<1>
53
55
108
8.8
66
60
126
9.2
<1>
4A0005
4A0011
466
Normal Duty
Heavy Duty
4A0018
4A0023
69
61
130
11.1
89
73
162
14.8
<1>
135
86
221
17.5
177
108
285
18.0
<1>
150
97
247
23
216
138
354
4A0031
24 <1>
208
115
323
31
295
161
455
4A0038
31 <1>
263
141
403
38
340
182
521
4A0044
39 <1>
330
179
509
44
390
209
599
4A0058
45 <1>
349
170
518
58
471
215
686
4A0072
60 <1>
484
217
701
72
605
265
870
4A0088
75 <1>
563
254
817
88
684
308
993
4A0103
91 <1>
723
299
1022
103
848
357
1205
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Normal Duty
Heavy Duty
Rated Amps
(A)
Heatsink Loss
(W)
Interior Unit
Loss (W)
Rated Amps
(A) <3>
4A0139
112 <1>
908
416
1325
139
1215
534
1749
4A0165
150 <2>
1340
580
1920
165
1557
668
2224
4A0208
180 <2>
1771
541
2313
208
1800
607
2408
4A0250
216 <2>
2360
715
3075
250
2379
803
3182
4A0296
260 <2>
2391
787
3178
296
2448
905
3353
4A0362
304 <2>
3075
985
4060
362
3168
1130
4298
4A0414
370 <2>
3578
1164
4742
414
3443
1295
4738
4A0515
450 <3>
3972
1386
5358
515
4850
1668
6518
4A0675
605 <3>
4191
1685
5875
675
4861
2037
6898
4A0930
810 <3>
6912
2455
9367
930
8476
2952
11428
4A1200
1090 <3>
7626
3155
10781
1200
8572
3612
12184
Heatsink Loss
(W)
Interior Unit
Loss (W)
Normal Duty
Heavy Duty
Heatsink Loss
(W)
Interior Unit
Loss (W)
Rated Amps
(A) <1>
Heatsink Loss
(W)
Interior Unit
Loss (W)
5A0003
1.7 <2>
28.9
19.8
48.7
2.7
21.5
23.3
44.8
5A0004
3.5 <2>
54.3
27.6
81.9
3.9
27.5
33.6
61.1
5A0006
4.1 <2>
53.0
27.0
80.0
6.1
28.1
43.7
71.8
5A0009
6.3 <2>
78.7
36.4
115.1
9.0
43.4
68.9
112.3
5A0011
9.8 <2>
110.9
49.5
160.3
11
56.1
88.0
144.0
5A0017
12.5 <2>
144.7
67.5
212.2
17
96.6
146.7
243.2
5A0022
17 <2>
203.8
81.1
284.8
22
99.4
178.3
277.7
5A0027
22 <2>
267.2
113.8
381.1
27
132.1
227.2
359.3
5A0032
27 <3>
332.9
132.2
465.1
32
141.6
279.9
421.5
5A0041
32 <3>
405.9
127.6
533.5
41
330.8
136.2
467.0
5A0052
41 <3>
527.2
161.4
688.5
52
427.8
166.2
594.0
5A0062
52 <3>
1271.5
335.0
1606.5
62
791.2
279.0
1070.2
5A0077
62 <3>
1457.0
379.5
1836.5
77
959.1
329.4
1288.6
5A0099
77 <2>
1267.0
352.0
1619.0
99
1253.2
411.7
1664.9
5A0125
99 <1>
1328
422
1750
125
1641
537
2178
5A0145
130 <1>
1638
508
2146
145
1860
603
2463
5A0192
172 <1>
2114
648
2762
192
2420
769
3189
5A0242
200 <1>
2526
896
3422
242
3100
1131
4231
Specifications
Rated Amps
(A)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
467
2A0004 to 2A0069
Heavy Duty
2A0081 to 2A0138
80% of HD
70% of HD
2 kHz
8 kHz
15 kHz
Normal Duty
2A0169 to 2A0415
Heavy Duty
80% of HD
2 kHz
5 kHz
10 kHz
Normal Duty
4A0002 to
4A0103
Heavy Duty
60% of HD
2 kHz
8 kHz
15 kHz
468
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Normal Duty
4A0139 to 4A0362
Heavy Duty
70% of HD
2 kHz
5 kHz
10 kHz
2 kHz
5 kHz
Normal Duty
Heavy Duty
83% of HD
2 kHz
5 kHz
Specifications
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
469
Normal Duty
Heavy Duty
62.5% of HD
2 kHz
5 kHz
Normal Duty
5A0003 to 5A0032
Heavy Duty
60% of HD
2 kHz
15 kHz
8 kHz
Normal Duty
Heavy Duty
88% of HD
2 kHz
8 kHz
10 kHz
470
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Normal Duty
Heavy Duty
84% of HD
2 kHz
8 kHz
10 kHz
5A0099
Heavy Duty
70% of HD
2 kHz
5 kHz
8 kHz
Normal Duty
Heavy Duty
Specifications
93% of HD
2 kHz
3 kHz
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
471
Normal Duty
Heavy Duty
83% of HD
2 kHz
3 kHz
u Temperature Derating
To ensure the maximum performance life, the drive output current must be derated as shown in Figure A.14 when the drive
is installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure reliable
drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.
n Parameter Settings
No.
L8-12
Name
Description
Ambient
Adjust the drive overload (oL2) protection level when the drive is installed
Temperature Setting in an environment that exceeds its ambient temperature rating.
L8-35
Installation Method
Selection
0: IP00/Open-Chassis Enclosure
1: Side-by-Side Mounting
2: IP20/NEMA Type 1 Enclosure
3: Finless Drive or External Heatsink Installation
Range
Def.
-10 to 50
40 C
0 to 3
<1>
IP00/Open-Chassis Enclosure
Drive operation between -10 C and 50 C allows 100% continuous current without derating.
Side-by-Side Mounting
Drive operation between -10 C and 30 C allows 100% continuous current without derating. Operation between 30 C and
50 C requires output current derating.
IP20/NEMA Type 1 Enclosure
Drive operation between -10 C and 40 C allows 100% continuous current without derating. Operation between 40 C and
50 C requires output current derating.
External Heatsink Installation, Finless Drive
Drive operation between -10 C and 40 C allows 100% continuous current without derating. Operation between 40 C and
50 C requires output current derating.
472
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Drive Rating
(%)
100
85
70
55
0
-10
30
40
50
L8-12
(Ambient temp: C)
u Altitude Derating
Specifications
The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive
rated voltage and the rated output current must be derated for 1% per 100 m.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
473
474
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Appendix: B
Parameter List
This appendix contains a full listing of all parameters and settings available in the drive.
B.1
B.2
B.3
B.4
B.5
B.6
B.7
B.8
B.9
B.10
B.11
B.12
B.13
B.14
B.15
B.16
B.17
B.18
B.19
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
475
Symbol
All Modes
V/f
V/f w PG
Description
Parameter is available in all control modes.
Parameter is available when operating the drive with V/f Control.
Parameter is available when operating the drive with V/f with PG Control.
OLV
Parameter is available when operating the drive with Open Loop Vector.
CLV
Parameter is available when operating the drive with Closed Loop Vector.
OLV/PM
AOLV/PM
CLV/PM
Parameter is available when operating the drive with Open Loop Vector for PM motors. <99>
Parameter is available when operating the drive with Advanced Open Loop Vector for PM motors. <99>
Parameter is available when operating the drive with Closed Loop Vector for PM motors. <99>
Parameter is NOT available when operating the drive in the control mode.
Parameter can be changed during run.
Motor 2
<99>
476
OLV/PM
Refers to a second motor when the drive is operating two motors. Switch between these motors using the multifunction input terminals.
AOLV/PM
CLV/PM
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooo.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Initialization Parameters
Page
Parameter
Group
479
H2 <1>
518
Name
Page
A2
User Parameters
480
H3 <1>
521
b1
481
H4
523
482
H5
524
Speed Search
483
H6
525
b4
Timer Function
484
Motor Protection
526
b5
PID Control
484
L1 <1>
L2
527
b6
Dwell Function
486
Stall Prevention
529
b7
b8
Droop Control
Energy Saving
486
487
L3 <1>
L4
L5
Speed Detection
Fault Restart
530
531
b9
C1
Zero Servo
Acceleration and Deceleration Times
488
489
L6
L7
Torque Detection
Torque Limit
531
533
C2
S-Curve Characteristics
490
L8 <1>
Drive Protection
533
Slip Compensation
490
n1
Hunting Prevention
536
C4
Torque Compensation
491
n2
536
C5
492
n3
536
Carrier Frequency
494
n5
537
Online Tuning
538
538
540
b2
b3 <1>
C3 <1>
C6 <1>
d1
Frequency Reference
495
n6
d2
496
d3
Jump Frequency
Frequency Reference Hold and Up/Down 2
Function
Torque Control
Field Weakening and Field Forcing
Offset Frequency
V/f Pattern for Motor 1
496
n8 <1>
o1
497
o2
540
498
498
499
500
o3
o4
q
r
Copy Function
Maintenance Monitor Settings
DriveWorksEZ Parameters
DriveWorksEZ Connection Parameters
541
541
543
543
E2 <1>
E3
Motor 1 Parameters
501
T1
544
502
T2
PM Motor Auto-Tuning
545
E4 <1>
Motor 2 Parameters
503
T3
547
E5
PM Motor Settings
504
U1 <1>
548
Fault Trace
550
Fault History
551
Maintenance Monitors
552
PID Monitors
Operation Status Monitors
DriveWorksEZ Monitors
554
555
556
d4
d5
d6
d7
E1
F1
505
U2 <1>
F2
507
U3
507
U4 <1>
508
508
509
513
U5
U6
U8
F3
F4
F5
F6, F7
H1
<1> Specifications differ for models CIMR-Ao4A0930 and 4A1200. Refer to Parameter Differences for Models CIMR-Ao4A0930 and 4A1200 on
page 478 for details.
Parameter List
Parameter
Group
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
477
478
Name
Differences
b3
Speed Search
Depends on b3-04 setting. Refer to b3: Speed Search on page 483 for details.
C3
Slip Compensation
Depends on C3-05 setting. Refer to C3: Slip Compensation on page 490 for details.
C3-16 to C3-18 are available.
C6
Carrier Frequency
Defaults and setting ranges differ for C6-02, C6-03, and C6-04. Refer to C6: Carrier Frequency on page
494 for details.
C6-09 is not available.
E2
Motor 1 Parameters
Setting units differ for E2-05. Refer to E2: Motor 1 Parameters on page 501 for details.
E4
Motor 2 Parameters
Setting units differ for E4-05. Refer to E4: Motor 2 Parameters on page 503 for details.
H2
Multi-Function Digital
Outputs
H3
Multi-Function Digital
Inputs
H3-oo = 17 is available.
L1
Motor Protection
L1-15 to L1-20 are available. Refer to L1: Motor Protection on page 526 for details.
L3
Stall Prevention
L8
Drive Protection
n8
U1
Setting units differ for U1-03. Refer to U1: Operation Status Monitors on page 548 for details.
U1-29 is available.
U2
Fault Trace
Setting units differ for U2-05. Refer to U2: Fault Trace on page 550 for details.
U2-27 and U2-28 are available.
U4
Maintenance Monitors
Setting units differ for U4-13. Refer to U4: Maintenance Monitors on page 552 for details.
U4-32, U4-37, U4-38, and U4-39 are available.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u A1: Initialization
No.
(Addr.
Hex)
Name
Description
Values
Page
All Modes
A1-00
(100)
Language Selection
<1>
A1-01
(101)
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
Default: 0
Range: 0 to 7
156
All Modes
<2>
0: View and set A1-01 and A1-04. Uo-ooparameters can also be viewed. Default: 2
1: User Parameters (access to a set of parameters selected by the user, A2-01 Range: 0 to 2
to A2-32)
2: Advanced Access (access to view and set all parameters)
156
All Modes
A1-02
(102)
<1>
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
Default: 2
Range: 0 to 3;
5 to7
157
Note: PM motor control modes are not available on 600 V class drives,
CIMR-Ao5oooooo.
All Modes
A1-03
(103)
Initialize Parameters
0: No initialization
Default: 0
1110: User Initialize (parameter values must be stored using parameter o2-03) Range: 0 to 3330;
2220: 2-Wire initialization
5550
3330: 3-Wire initialization
5550: oPE04 error reset
157
All Modes
A1-04
(104)
Password
Default: 0000
When the value set into A1-04 does not match the value set into A1-05,
Min.: 0000
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-33 cannot Max.: 9999
be changed.
Password Setting
Default: 0000
When the value set into A1-04 does not match the value set into A1-05,
Min.: 0000
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-33 cannot Max.: 9999
be changed.
158
All Modes
A1-05
(105)
158
A1-06
(127)
Application Preset
A1-07
(128)
DriveWorksEZ Function
Selection
Default: 0
Range: 0 to 5
160
Default: 0
Range: 0 to 2
161
All Modes
0: DWEZ Disabled
1: DWEZ Enabled
2: Digital input (enabled when H1-oo = 9F)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter List
All Modes
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
479
Description
Values
All Modes
Default: <1>
Recently edited parameters are listed here. The user can also select parameters Range: b1-01 to
to appear here for quicker access.
o4-13
Page
161
All Modes
A2-33
(126)
0: Parameters A2-01 to A2-32 are reserved for the user to create a list of User Default: 1 <2>
Parameters.
Range: 0, 1
1: Save history of recently viewed parameters. Recently edited parameters will
be saved to A2-17 through A2-32 for quicker access.
161
<1> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<2> Default setting value is dependent on parameter A1-06. Default is 0 when A1-06 = 0, and 1 when A1-06 0.
480
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.4 b: Application
B.4 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID
control, the Dwell function, Energy Savings, and a variety of other application-related settings.
Name
Description
Values
Page
All Modes
b1-01
(180)
Frequency Reference
Selection 1
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse input (terminal RP)
Default: 1
Range: 0 to 4
162
Default: 1
Range: 0 to 3
163
Default: 0
Range: 0 to 3 <1>
164
Default: 0
Range: 0, 1
166
Default: 0
Range: 0 to 3
166
All Modes
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
b1-02
(181)
Run Command
Selection 1
b1-03
(182)
0: Ramp to stop
Stopping Method Selection 1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
b1-04
(183)
All Modes
All Modes
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
b1-05
(184)
b1-06
(185)
0: Input status is read once and processed immediately (for quicker response) Default: 1
Range: 0, 1
1: Input is read twice and processed only if the status is the same in both
readings (robust against noisy signals)
b1-07
(186)
LOCAL/REMOTE Run
Selection
0: An external Run command must be cycled at the new source in order to be Default: 0
Range: 0, 1
activated.
1: An external Run command at the new source is accepted immediately.
b1-08
(187)
Run Command Selection in 0: Run command is not accepted while in Programming Mode.
Programming Mode
1: Run command is accepted while in Programming Mode.
2: Prohibit entering Programming Mode during run.
All Modes
167
All Modes
168
All Modes
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
168
Default: 0
Range: 0, 1
168
Default: 0
Range: 0 to 4
168
CLV
0: Standard
1: Switch phase order (reverses the direction of the motor)
All Modes
b1-15
(1C4)
Frequency Reference
Selection 2
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter List
b1-14
(1C3)
Default: 0
Range: 0 to 2
481
B.4 b: Application
No.
(Addr.
Hex)
Name
Description
Values
Page
All Modes
b1-16
(1C5)
Run Command
Selection 2
Default: 0
Range: 0 to 3
b1-17
(1C6)
Default: 0
Run Command at Power Up 0: Disregarded. A new Run command must be issued after power up.
1: Allowed. Motor will start immediately after power up if a Run command Range: 0, 1
is already enabled.
169
All Modes
169
Name
b2-01
(189)
Default: <1>
Sets the frequency at which DC Injection Braking starts when Ramp to stop Min.: 0.0 Hz
Max.: 10.0 Hz
(b1-03 = 0) is selected.
b2-02
(18A)
DC Injection Braking
Current
Default: 50%
Min.: 0
Sets the DC Injection Braking current as a percentage of the drive rated current. Max.: 100
b2-03
(18B)
Default: 0.00 s
DC Injection Braking Time
OLV/PM
AOLV/PM
CLV/PM
Min.: 0.00
at Start
Sets DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) Max.: 10.00
time at start. Disabled when set to 0.00 seconds.
b2-04
(18C)
Default: <1>
DC Injection Braking Time
OLV/PM
AOLV/PM
CLV/PM
Min.: 0.00 s
at Stop
Sets DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) Max.: 10.00 s
time at stop.
b2-08
(190)
Magnetic Flux
Compensation Value
b2-12
(1BA)
b2-13
(1BB)
b2-18
(177)
Description
Values
Page
All Modes
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
V/f
V/f w PG
OLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
CLV
CLV
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
170
CLV
Sets the time for Short Circuit Braking operation at start. <2>
OLV/PM
170
CLV
169
<2>
170
Default: 0%
Min.: 0
Max.: 1000
171
Default: 0.00 s
Min.: 0.00
Max.: 25.50
171
Default: 0.50 s
Min.: 0.00
Max.: 25.50
171
CLV
Default: 100.0%
Min.: 0.0
Determines the current level for Short Circuit Braking. Set as a percentage of Max.: 200.0
the motor rated current.
171
482
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.4 b: Application
Name
b3-01
(191)
b3-02
(192)
b3-03
(193)
b3-04
(194)
b3-05
(195)
b3-06
(196)
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Page
CLV
Default: <1>
Range: 0, 1
175
Default: <1>
Min.: 0%
Sets the current level at which the speed is assumed to be detected and Speed Max.: 200%
Search is ended. Set as a percentage of the drive rated current.
175
0: Disabled
1: Enabled
CLV
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: 2.0 s
Min.: 0.1
Max.: 10.0
175
CLV
Determines how much to lower the V/f ratio during Speed Search.
Default: <2>
Output voltage during Speed Search equals the V/f setting multiplied by b3-04. Min.: 10%
Note: Available control mode for parameter b3-04 varies by drive model: Max.: 100%
CIMR-Ao2A0004 to 2A0415, 4A0002 to 4A0675, and 5A0003
to 5A0242: Available when A1-02 = 0, 1
CIMR-Ao4A0930 and 4A1200: Available when A1-02 = 0
175
All Modes
Default: 0.2 s
When using an external contactor on the output side, b3-05 delays executing Min.: 0.0
Speed Search after a momentary power loss to allow time for the contactor to Max.: 100.0
close.
V/f w PG
OLV
AOLV/PM
CLV/PM
CLV
Sets the current injected to the motor at the beginning of Speed Estimation
Speed Search. Set as a coefficient for the motor rated current.
V/f
V/f w PG
OLV
Default: <2>
Min.: 0.0
Max.: 2.0
CLV
Default: 1.05
Sets the gain which is applied to the speed detected by Speed Estimation Speed Min.: 1.00
Max.: 1.20
Search before the motor is reaccelerated. Increase this setting if ov occurs
when performing Speed Search after a relatively long period of baseblock.
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
b3-10
(19A)
b3-14
(19E)
b3-17
(1F0)
b3-18
(1F1)
b3-19
(1F2)
b3-24
(1C0)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
Default: <1>
Range: 0, 1
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
CLV
CLV
Sets the number of times the drive can attempt to restart when performing
Speed Search.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
176
CLV
176
CLV
Default: 150%
Min.: 0
Sets the Speed Search restart current level as a percentage of the drive rated Max.: 200
current.
OLV/PM
175
176
Default: 0.10 s
Min.: 0.00
Max.: 1.00
176
Default: 3
Min.: 0
Max.: 10
176
Default: 0
Range: 0, 1
176
CLV
0: Current Detection
1: Speed Estimation
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
483
Parameter List
V/f
OLV/PM
175
B.4 b: Application
No.
(Addr
Hex.)
b3-25
(1C8)
b3-27
(1C9)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
Default: 0.5 s
Min.: 0.0
Sets the time the drive must wait between each Speed Search restart attempt. Max.: 30.0
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Page
177
CLV
Default: 0
Range: 0, 1
177
Name
b4-01
(1A3)
b4-02
(1A4)
Description
All Modes
Sets the on-delay and off-delay times for a digital timer output
(H2-oo=12).
The output is triggered by a digital input programmed to
H1-oo=18).
Values
Page
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
177
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
177
Name
Description
Values
Page
All Modes
b5-01
(1A5)
b5-02
(1A6)
0: Disabled
1: Enabled (PID output becomes output frequency reference, deviation D
Default: 0
controlled)
Range: 0 to 4
2: Enabled (PID output becomes output frequency reference, feedback D
controlled)
3: Enabled (PID output added to frequency reference, deviation D controlled)
4: Enabled (PID output added to frequency reference, feedback D controlled)
All Modes
Default: 1.00
Min.: 0.00
Max.: 25.00
181
Default: 1.0 s
Min.: 0.0
Max.: 360.0
181
b5-03
(1A7)
b5-04
(1A8)
All Modes
Default: 100.0%
Sets the maximum output possible from the integrator as a percentage of the Min.: 0.0
Max.: 100.0
maximum output frequency.
b5-05
(1A9)
b5-06
(1AA)
Sets the maximum output possible from the entire PID controller as a
percentage of the maximum output frequency.
b5-07
(1AB)
b5-08
(1AC)
484
All Modes
All Modes
All Modes
All Modes
All Modes
Sets a low pass filter time constant on the output of the PID controller.
181
181
Default: 0.00 s
Min.: 0.00
Max.: 10.00
181
Default: 100.0%
Min.: 0.0
Max.: 100.0
181
Default: 0.0%
Min.: -100.0
Max.: 100.0
182
Default: 0.00 s
Min.: 0.00
Max.: 10.00
182
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.4 b: Application
No.
(Addr.
Hex)
Name
Description
All Modes
b5-09
(1AD)
b5-10
(1AE)
All Modes
Values
Page
Default: 0
Range: 0, 1
182
Default: 1.00
Min.: 0.00
Max.: 25.00
182
Default: 0
Range: 0, 1
182
All Modes
b5-11
(1AF)
b5-12
(1B0)
b5-13
(1B1)
b5-14
(1B2)
b5-15
(1B3)
b5-16
(1B4)
b5-17
(1B5)
b5-18
(1DC)
b5-19
(1DD)
Sets the PID feedback loss detection level as a percentage of the maximum
output frequency.
All Modes
0: Disabled
1: Enabled
183
Default: 0%
Min.: 0
Max.: 100
183
Default: 1.0 s
Min.: 0.0
Max.: 25.5
184
Default: <1>
Min.: 0.0 Hz
Max.: 400.0 Hz
Default: 0.0 s
Min.: 0.0
Max.: 25.5
Default: 0.0 s
Min.: 0.0
Max.: 6000.0
Default: 0
Range: 0, 1
All Modes
Default: 0.00%
Sets the PID target value when b5-18 = 1. Set as a percentage of the maximum Min.: 0.00
Max.: 100.00
output frequency.
184
184
185
185
185
All Modes
b5-20
(1E2)
b5-34
(19F)
All Modes
Default: 0.00%
Sets the minimum output possible from the PID controller as a percentage of Min.: -100.00
Max.: 100.00
the maximum output frequency.
185
b5-35
(1A0)
All Modes
Default: 1000.0%
Limits the PID control input (deviation signal) as a percentage of the maximum Min.: 0.0
Max.: 1000.0
output frequency. Acts as a bipolar limit.
186
b5-36
(1A1)
All Modes
Default: 100%
Sets the PID feedback high detection level as a percentage of the maximum Min.: 0
Max.: 100
output frequency.
184
b5-37
(1A2)
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Default: 1
Range: 0 to 3
Default: 1.0 s
Min.: 0.0
Max.: 25.5
185
184
485
Parameter List
0: 0.01 Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must entered)
3: User-set (set scaling to b5-38 and b5-39)
B.4 b: Application
No.
(Addr.
Hex)
b5-38
(1FE)
Name
Description
Values
All Modes
Default: <2>
Sets the display value of U5-01 and U5-04 when the maximum frequency is Min.: 1
Max.: 60000
output.
Page
186
All Modes
b5-39
(1FF)
0: No decimal places
PID Setpoint Display Digits 1: One decimal place
2: Two decimal places
3: Three decimal places
b5-40
(17F)
0: Display the frequency reference (U1-01) after PID compensation has been Default: 0
Frequency Reference
Monitor Content during PID added.
Range: 0, 1
1: Display the frequency reference (U1-01) before PID compensation has been
added.
Default: <2>
Range: 0 to 3
186
All Modes
186
All Modes
b5-47 <3>
(17D)
Default: 1
Range: 0, 1
186
Name
b6-01
(1B6)
b6-02
(1B7)
b6-03
(1B8)
b6-04
(1B9)
Description
Values
Default: 0.0 Hz
Min.: 0.0
Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain Max.: 400.0
that frequency at start.
Default: 0.0 s
Min.: 0.0
Max.: 10.0
All Modes
Default: 0.0 Hz
All Modes
Min.: 0.0
Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain Max.: 400.0
that frequency at stop.
Default: 0.0 s
Min.: 0.0
Max.: 10.0
Page
188
188
188
188
Name
b7-01
(1CA)
b7-02
(1CB)
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: 0.0%
Min.: 0.0
Sets the speed reduction gain applied at a torque reference of 100%. Set as a Max.: 100.0
percentage of motor base speed.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
<1>
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: Disabled
1: Enabled
Page
CLV
CLV
Values
188
Default: 0.05 s
Min.: 0.03
Max.: 2.00
189
Default: 1
Range: 0, 1
189
CLV
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.4 b: Application
Name
b8-01
(1CC)
b8-02
(1CD)
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: Disabled
1: Enabled
b8-04
(1CF)
b8-05
(1D0)
b8-06
(1D1)
b8-16
(1F8)
<5>
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
189
Default: <1>
Min.: 0.0
Max.: 10.0
189
Default: <2>
Min.: 0.00 s
Max.: 10.00 s
190
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Default: <1>
Range: 0, 1
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the limit for the voltage search operation as a percentage of the motor
rated voltage.
V/f
V/f w PG
OLV
OLV/PM
V/f
AOLV/PM
CLV/PM
Page
CLV
Values
190
Default: 20 ms
Min.: 0
Max.: 2000
190
Default: 0%
Min.: 0
Max.: 100
190
CLV
190
b8-17
(1F9)
<5>
V/f
V/f w PG
OLV
OLV/PM
V/f
AOLV/PM
CLV/PM
CLV
190
<1>
<2>
<3>
<4>
<5>
Parameter List
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
487
B.4 b: Application
Name
b9-01
(1DA)
b9-02
(1DB)
488
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the position loop gain for the Zero Servo function.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the range to trigger an output terminal set for Zero Servo Complete
during Zero Servo operation.
Values
Page
Default: 5
Min.: 0
Max.: 100
191
Default: 10
Min.: 0
Max.: 16383
191
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.5 C: Tuning
B.5 C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, slip compensation, torque compensation,
and carrier frequency selections.
Name
Description
All Modes
Acceleration Time 1
C1-02
(201)
Deceleration Time 1
C1-03
(202)
Acceleration Time 2
Deceleration Time 2
C1-04
(203)
C1-05
(204)
C1-06
(205)
C1-07
(206)
C1-08
(207)
Values
All Modes
Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>
All Modes
All Modes
Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>
All Modes
Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>
All Modes
C1-09
(208)
C1-10
(209)
C1-11
(20A)
Accel/Decel Time
Switching Frequency
All Modes
Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>
Page
192
192
192
192
192
192
192
192
Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>
193
Default: 1
Range: 0, 1
194
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
193
Parameter List
<1> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
489
B.5 C: Tuning
Name
C2-01
(20B)
S-Curve Characteristic at
Accel Start
C2-02
(20C)
S-Curve Characteristic at
Accel End
C2-03
(20D)
S-Curve Characteristic at
Decel Start
C2-04
(20E)
S-Curve Characteristic at
Decel End
Description
Values
All Modes
Run Command
Output Frequency
OFF
C2-02
C2-03
C2-01
C2-04
Time
Default: 0.20 s
Min.: 0.00
Max.: 10.00
Default: 0.20 s
Min.: 0.00
Max.: 10.00
Default: 0.20 s
Min.: 0.00
Max.: 10.00
Default: 0.00 s
Min.: 0.00
Max.: 10.00
Page
<1>
194
194
194
194
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the gain for the motor slip compensation function used for motor 1.
C3-02
(210)
C3-03
(211)
C3-04
(212)
Slip Compensation
Selection during
Regeneration
C3-05
(213)
C3-16
(261)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Adjusts the slip compensation function delay time used for motor 1.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Default: <1>
Min.: 0.0
Max.: 2.5
194
Default: <1>
Min.: 0 ms
Max.: 10000 ms
195
CLV
Default: 200%
Min.: 0
Sets an upper limit for the slip compensation function as a percentage of motor Max.: 250
rated slip for motor 1 (E2-02).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
Note: Available control mode for parameter C3-05 varies by drive model:
CIMR-Ao2A0004 to 2A0415, 4A0002 to 4A0675, and 5A0003
to 5A0242: Available when A1-02 = 0,1.
CIMR-Ao4A0930 and 4A1200: Available when A1-02 = 2, 3, 6,
7.
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
Default: 0
Range: 0 to 2
195
Default: 0
Range: 0, 1
196
Default: 85.0%
Min.: 70.0
Max.: 90.0
196
CLV
0: Disabled.
1: Enabled. Automatically decreases motor flux when output voltage
saturation is reached.
OLV/PM
195
CLV
0: Disabled.
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.
OLV/PM
Page
CLV
Sets the output voltage limit operation start level (percentage modulation)
when C3-05 is enabled.
Note: This parameter is only available in models CIMR-Ao4A0930 and
4A1200.
490
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.5 C: Tuning
No.
(Addr.
Hex)
C3-17
(262)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Page
CLV
Default: 90.0%
Min.: 85.0
Max.: 100.0
196
Default: 90.0%
Min.: 30.0
Max.: 100.0
196
Default: <2>
Min.: 0.0
Max.: 2.5
196
Default: <2>
Min.: 0 ms
Max.: 10000 ms
196
Default: 200%
Min.: 0
Max.: 250
197
Default: 0
Range: 0 to 2
197
C3-18
(263)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Output Voltage Limit Level Sets the maximum percentage of output voltage reduction when C3-05 is
enabled.
Note: This parameter is only available in models CIMR-Ao4A0930 and
4A1200.
C3-21
(33E)
C3-22
(241)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
CLV
C3-23
(242)
C3-24
(243)
V/f
V/f w PG
OLV
CLV
C4-01
(215)
C4-02
(216)
Name
Torque Compensation
Primary Delay Time 1
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the gain for the automatic torque (voltage) boost function and helps to
produce better starting torque. Used for motor 1.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
C4-03
(217)
Torque Compensation at
Forward Start
C4-04
(218)
Torque Compensation at
Reverse Start
C4-05
(219)
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
CLV
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Values
Page
Default: <1>
Min.: 0.00
Max.: 2.50
197
Default: <2>
Min.: 0 ms
Max.: 60000 ms
198
Default: 0.0%
Min.: 0.0
Max.: 200.0
198
Default: 0.0%
Min.: -200.0
Max.: 0.0
198
Default: 10 ms
Min.: 0
Max.: 200
198
491
Parameter List
No.
(Addr.
Hex)
B.5 C: Tuning
No.
(Addr.
Hex)
C4-06
(21A)
C4-07
(341)
Name
Torque Compensation
Primary Delay Time 2
Motor 2 Torque
Compensation Gain
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Values
Page
Default: 150 ms
Min.: 0
Max.: 10000
198
Default: 1.00
Min.: 0.00
Max.: 2.50
198
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the speed control gain 2 of the speed control loop (ASR).
C5-04
(21E)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
ASR Limit
C5-06
(220)
C5-07
(221)
C5-08
(222)
C5-12
(386)
C5-17
(276)
492
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the upper limit for the speed control loop (ASR) as a percentage of the
maximum output frequency (E1-04).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the filter time constant for the time from the speed loop to the torque
command output.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Motor Inertia
Default: <1>
Min.: 0.00
Max.: 300.00
Page
<2>
Default: <1>
Min.: 0.000 s
Max.: 10.000 s
201
Default: <1>
Min.: 0.00
Max.: 300.00
201
<2>
Default: <1>
Min.: 0.000 s
Max.: 10.000 s
201
Default: 5.0%
Min.: 0.0
Max.: 20.0
202
Default: <1>
Min.: 0.000 s
Max.: 0.500 s
202
Default: 0.0 Hz
Min.: 0.0
Sets the frequency for switching between proportional gain 1, 2 and integral Max.: 400.0
time 1, 2.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
202
Default: 400%
Min.: 0
Max.: 400
202
Default: 0
Range: 0, 1
202
CLV
201
CLV
Sets the ASR integral upper limit as a percentage of rated load torque.
Integral Operation during
Accel/Decel
Values
CLV
202
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.5 C: Tuning
C5-18
(277)
C5-21
(356)
C5-22
(357)
C5-23
(358)
C5-24
(359)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: 1.0
Min.: 0.0
Sets the ratio between the motor and load inertia. This value is automatically Max.: 6000.0
set during ASR or Inertia Auto-Tuning.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the proportional gain of the speed control loop (ASR) for motor 2.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the integral time of the speed control loop (ASR) for motor 2.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the speed control gain 2 of the speed control loop (ASR) for motor 2.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the integral time 2 of the speed control loop (ASR) for motor 2.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
C5-26
(35B)
C5-27
(35C)
Sets the upper limit for the speed control loop (ASR) for motor 2 as a
percentage of the maximum output frequency (E3-04).
V/f
C5-32
(361)
C5-37
(278)
C5-38
(279)
<1>
<2>
<3>
<4>
<5>
Motor 2 Inertia
Page
CLV
C5-25
(35A)
C5-28
(35D)
Values
V/f w PG
OLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Default: <5>
Min.: 0.00
Max.: 300.00
202
<2>
Default: <5>
Min.: 0.000 s
Max.: 10.000 s
203
Default: <5>
Min.: 0.00
Max.: 300.00 <2>
203
Default: <5>
Min.: 0.000 s
Max.: 10.000 s
203
Default: 5.0%
Min.: 0.0
Max.: 20.0
203
Default: <5>
Min.: 0.000 s
Max.: 0.500 s
203
CLV
Default: 0.0 Hz
Min.: 0.0
Sets the frequency for motor 2 used to switch between proportional gain 1 and Max.: 400.0
2, and between the integral time 1 and 2.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the ASR integral upper limit for motor 2 as a percentage of rated load
torque.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: 400%
Min.: 0
Max.: 400
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
203
203
CLV
203
CLV
0: Disabled. Integral functions for motor 2 are enabled only during constant Default: 0
Range: 0, 1
speed.
1: Enabled. Integral functions are always enabled for motor 2, during accel/
decel and during constant speed.
OLV/PM
203
CLV
Sets the ratio between the motor 2 and machine inertia. This value is
automatically set during ASR or Inertia Auto-Tuning.
Default: 1.0
Min.: 0.0
Max.: 6000.0
204
204
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter List
No.
(Addr.
Hex)
493
B.5 C: Tuning
Name
Description
Values
All Modes
Page
Default: 1
Range: 0, 1
204
Default: <1>
Range: 1 to 9;
A, F
205
All Modes
C6-02
(224)
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
Carrier Frequency Selection 7: Swing PWM1 (Audible sound 1)
8: Swing PWM2 (Audible sound 2)
9: Swing PWM3 (Audible sound 3)
A: Swing PWM4 (Audible sound 4)
B to E: No setting possible
F: User-defined (determined by C6-03 through C6-05)
Note: The available settings are 1, 2, and F for models CIMR-Ao4A0930
and 4A1200.
C6-03
(225)
C6-04
(226)
Default: <2>
Min.: 1.0 kHz
Note: C6-04 and C6-05 are available only in V/f and V/f w/PG control Max.: 15.0 kHz
modes.
Default: <2>
Determines the upper and lower limits for the carrier frequency.
Min.: 1.0 kHz
In OLV, C6-03 determines the upper limit of the carrier frequency.
Max.: 15.0 kHz
All Modes
205
205
Carrier Frequency
C6-03
C6-05
(227)
C6-04
Carrier Frequency
Proportional Gain
Output Frequency
(C6-05) K
E1-04
Max Output
Frequency
Output
Frequency
Default: <2>
Min.: 0
Max.: 99
205
Default: 0
Range: 0, 1
206
Note: The setting range is 1.0 to 5.0 kHz for models CIMR-Ao4A0930
and 4A1200.
C6-09
(22B)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
<1> Default setting value is dependent on parameters A1-02, Control Method Selection, C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.
494
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.6 d: References
B.6 d: References
Reference parameters set the various frequency reference values during operation.
d1-01
(280)
d1-02
(281)
d1-03
(282)
d1-04
(283)
d1-05
(284)
d1-06
(285)
d1-07
(286)
d1-08
(287)
d1-09
(288)
d1-10
(28B)
d1-11
(28C)
d1-12
(28D)
d1-13
(28E)
Name
Description
All Modes
Frequency Reference 1
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 2
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 3
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 4
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 5
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 6
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 7
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 8
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 9
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 10
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 11
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 12
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 13
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Values
Page
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
Parameter List
No.
(Addr.
Hex)
<2>
495
B.6 d: References
No.
(Addr.
Hex)
d1-14
(28F)
d1-15
(290)
d1-16
(291)
d1-17
(292)
Name
Description
All Modes
Frequency Reference 14
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 15
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes
Frequency Reference 16
Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
Values
Page
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00 <1>
209
<2>
<2>
<2>
Default: 6.00 Hz
Min.: 0.00
Sets the Jog frequency reference. Setting units are determined by parameter
Max.: 400.00 <1>
o1-03.
All Modes
209
<2>
<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
<2> The setting range is 0.0 to 66.0 in AOLV/PM.
Name
Description
All Modes
d2-01
(289)
d2-02
(28A)
d2-03
(293)
All Modes
All Modes
Sets the lower limit for frequency references from analog inputs as a
percentage of the maximum output frequency.
Setting
Page
Default: 100.0%
Min.: 0.0
Max.: 110.0
211
Default: 0.0%
Min.: 0.0
Max.: 110.0
211
Default: 0.0%
Min.: 0.0
Max.: 110.0
212
Name
Description
Values
Page
All Modes
d3-01
(294)
Jump Frequency 1
212
All Modes
d3-02
(295)
Jump Frequency 2
212
All Modes
d3-03
(296)
496
Jump Frequency 3
212
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.6 d: References
No.
(Addr.
Hex)
d3-04
(297)
Name
Description
Values
All Modes
Default: <1>
Sets the dead-band width around each selected prohibited frequency reference Min.: 0.0
Max.: 20.0
point.
Page
212
Name
d4-01
(298)
Description
Values
Page
All Modes
d4-03
(2AA)
d4-04
(2AB)
Default: 0
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency that Range: 0, 1
was saved.
All Modes
Sets the bias added to the frequency reference when the Up 2 and Down 2
digital inputs are enabled (H1-oo = 75, 76).
All Modes
213
Default: 0.00 Hz
Min.: 0.00
Max.: 99.99
215
Default: 0
Range: 0, 1
216
All Modes
d4-05
(2AC)
d4-06
(2AD)
Default: 0.0%
The Up/Down 2 bias value is saved in d4-06 when the frequency reference is Min.: -99.9
not input by the digital operator. Set as a percentage of the maximum output Max.: 100.0
frequency.
d4-07
(2AE)
Limits how much the frequency reference is allowed to change while an input Default: 1.0%
Analog Frequency
Reference Fluctuation Limit terminal set for Up 2 or Down 2 is enabled. If the frequency reference changes Min.: 0.1
for more than the set value, then the bias value is held and the drive accelerates Max.: 100.0
(Up/Down 2)
or decelerates to the frequency reference. Set as a percentage of the maximum
output frequency.
216
All Modes
216
All Modes
d4-08
(2AF)
d4-09
(2B0)
All Modes
Default: 0.0%
Sets the upper limit for the bias and the value that can be saved in d4-06. Set Min.: 0.0
Max.: 100.0
as a percentage of the maximum output frequency.
217
All Modes
Default: 0.0%
Sets the lower limit for the bias and the value that can be saved in d4-06. Set Min.: -99.9
Max.: 0.0
as a percentage of the maximum output frequency.
217
Up/Down Frequency
Reference Limit Selection
All Modes
Default: 0
Range: 0, 1
217
Parameter List
d4-10
(2B6)
217
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
497
B.6 d: References
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
d5-01
(29A)
Default: 0
0: Speed Control
Range: 0, 1
1: Torque Control
Set to 0 when using a digital input to switch between Speed and Torque Control
(H1-oo = 71).
d5-02
(29B)
Default: 0 ms
Min.: 0
Sets a delay time for the torque reference signal. Used to suppress effects by Max.: 1000
noisy or fluctuating torque reference signals.
d5-03
(29C)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
d5-04
(29D)
Speed Limit
OLV
Default: 1
Range: 1, 2
V/f w PG
OLV
CLV/PM
V/f
V/f w PG
OLV
Speed/Torque Control
Switchover Time
d5-08
(2B5)
V/f
AOLV/PM
CLV/PM
V/f w PG
OLV
AOLV/PM
CLV/PM
222
CLV
Default: 0 ms
Sets the delay time for switching between Speed and Torque Control using an Min.: 0
input terminal (H1-oo = 71). Reference values are held during this switch Max.: 1000
delay time.
OLV/PM
d5-06
(29F)
222
CLV
Default: 10%
Sets the speed limit bias as a percentage of the maximum output frequency. Min.: 0
The bias is applied to the specified speed limit and can adjust the margin for Max.: 120
the speed limit.
AOLV/PM
221
CLV
CLV/PM
OLV/PM
221
CLV
Default: 0%
Sets the speed limit during Torque Control as a percentage of the maximum Min.: -120
output frequency. Enabled when d5-03 = 2. A negative setting sets a limit in Max.: 120
the opposite direction of the Run command.
V/f
d5-05
(29E)
V/f w PG
AOLV/PM
221
CLV
Page
222
CLV
Default: 1
Range: 0, 1
222
d6-01
(2A0)
d6-02
(2A1)
d6-03
(2A2)
498
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
Default: 80%
Sets the drive output voltage for the Field Weakening function as a percentage Min.: 0
of the maximum output voltage.
Max.: 100
Enabled when a multi-function input is set for Field Weakening (H1-oo =
63).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: Disabled
1: Enabled
222
CLV
0.0 Hz
Field Weakening Frequency Sets the lower limit of the frequency range where Field Weakening control is Default:
Min.: 0.0
valid.
Limit
The Field Weakening command is valid only at frequencies above this setting Max.: 400.0
and only when the output frequency matches the frequency reference (speed
agree).
V/f
Page
222
CLV
Default: 0
Range: 0, 1
223
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.6 d: References
No.
(Addr
Hex.)
Name
Description
V/f
d6-06
(2A5)
V/f w PG
OLV
Values
CLV
Default: 400%
Sets the upper limit of the excitation current command during magnetic field Min.: 100
forcing. A setting of 100% is equal to motor no-load current. Disabled only Max.: 400
during DC Injection Braking.
OLV/PM
AOLV/PM
Page
CLV/PM
223
Name
Description
Setting
Page
Offset Frequency 1
All Modes
Default: 0.0%
Added to the frequency reference when the digital input Frequency offset 1 Min.: -100.0
Max.: 100.0
(H1-oo = 44) is switched on.
223
d7-02
(2B3)
Offset Frequency 2
All Modes
Default: 0.0%
Added to the frequency reference when the digital input Frequency offset 2 Min.: -100.0
Max.: 100.0
(H1-oo = 45) is switched on.
223
d7-03
(2B4)
Offset Frequency 3
All Modes
Default: 0.0%
Added to the frequency reference when the digital input Frequency offset 3 Min.: -100.0
Max.: 100.0
(H1-oo = 46) is switched on.
223
Parameter List
d7-01
(2B2)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
499
Name
Description
Values
Page
All Modes
E1-03
(302)
E1-04
(303)
Maximum Output
Frequency
E1-05
(304)
Maximum Voltage
E1-06
(305)
Base Frequency
E1-07
(306)
E1-08
(307)
E1-10
(309)
<9>
E1-12
(30B)
<9>
E1-13
(30C)
500
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
<1>
224
CLV
Default: F <2>
Range: 0 to 9;
A to F <3>
224
Default: <4>
Min.: 40.0
Max.: 400.0
227
<5>
<6>
227
227
Default: <4>
Min.: 0.0
Max.: E1-04
227
E1-08
Default: <4>
Min.: 0.0 V
Max.: 255.0 V <1>
227
E1-10
Default: <4>
Min.: 0.0
Max.: E1-04
E1-09
(308)
E1-11
(30A)
Default: 230 V
WARNING! Electrical Shock Hazard. Drive input voltage (not motor Min.: 155
voltage) must be set in E1-01 for the protective features of the drive to Max.: 255 <1>
function properly. Failure to do so may result in equipment damage
and/or death or personal injury.
E1-09
<5>
<6>
227
<7>
E1-11, E1-12, and E1-13 are available only in the following control modes:
Middle Output Frequency 2
V/f Control, V/f with PG, Open Loop Vector, Closed Loop Vector.
Default: <4>
Min.: 0.0 V
Max.: 255.0 V <1>
Default: 0.0 Hz
Min.: 0.0
Max.: E1-04 <7>
Default: 0.0 V
Min.: 0.0
Max.: 255.0 V <1>
227
Base Voltage
227
227
227
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
Parameter setting value is not reset to the default value when the drive is initialized.
The setting value is F in OLV modes.
Default setting is dependent on parameters A1-02, Control Model Selection, C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
Default setting is dependent on parameter E5-01, Motor Code Selection.
In OLV/PM, setting range varies according to the motor code entered to E5-01. The setting range is 0.0 to 400.0 Hz when E5-01 is set to FFFF.
The setting range is 0.0 to 66.0 in AOLV/PM.
When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
Name
Description
Default: <1>
Min.: 10% of drive
OLV/PM
AOLV/PM
CLV/PM
rated current
Sets the motor nameplate full load current in amps. Automatically set during Max.: 200% of
Auto-Tuning.
drive rated current
V/f
E2-01
(30E)
Values
V/f w PG
OLV
Page
CLV
228
<2>
E2-02
(30F)
E2-03
(310)
E2-04
(311)
E2-05
(312)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Default: <1>
Min.: 0.00 Hz
Max.: 20.00 Hz
228
Default: <1>
Min.: 0 A
<2>
Sets the no-load current for the motor. Automatically set during Auto-Tuning. Max.: E2-01
229
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
Motor Line-to-Line
Resistance
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: 4
Min.: 2
Max.: 48
229
Default: <1>
Min.: 0.000
Max.: 65.000
229
CLV
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
CLV
Default: <1>
Min.: 0.0%
Sets the voltage drop due to motor leakage inductance as a percentage of motor Max.: 40.0%
rated voltage. Automatically set during Auto-Tuning.
E2-07
(314)
E2-08
(315)
E2-09
(316)
E2-10
(317)
V/f
V/f w PG
OLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
CLV
Sets the motor mechanical loss as a percentage of motor rated power (kW).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
229
Default: 0.50
Min.: E2-07
Max.: 0.50
229
Default: 0.75
Min.: E2-07
Max.: 0.75
230
Default: 0.0%
Min.: 0.0
Max.: 10.0
230
Default: <1>
Min.: 0 W
Max.: 65535 W
230
501
Parameter List
V/f
E2-06
(313)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Page
CLV
Default: <1>
Min.: 0.00 kW
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set Max.: 650.00 kW
during Auto-Tuning.
230
<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.
Name
E3-01
(319)
E3-04
(31A)
E3-05
(31B)
E3-06
(31C)
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
V/f
V/f w PG
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
E3-12
E3-08
(31E)
E3-09
(31F)
E3-10
(320)
<3>
E3-12
(346)
<3>
E3-13
(347)
<1>
<2>
<3>
<4>
<5>
502
E3-13
E3-08
E3-10
Default: 0
Range: 0 to 3
231
Default: <1>
Min.: 40.0
Max.: 400.0
231
231
231
Default: <1>
Min: 0.0
Max: E3-04
231
Default: <1>
Min: 0.0 V
Max: 255.0 V <2>
231
Default: <1>
Min.: 0.0
Max.: E3-04
231
Default: <1>
Min: 0.0 V
Max: 255.0 V <2>
Note: E3-07 and E3-08 are only available in the following control modes:
Default: 0.0
V/f, V/f w/PG and OLV.
Min.: 0.0
Max.: E3-04 <4>
Default: 0.0 V
Min.: 0.0
Max.: 255.0 <2>
E3-09
Page
CLV
E3-07
(31D)
E3-11
(345)
Values
231
231
231
231
Default setting is dependent on E3-01, Motor 2 Control Mode Selection. The value shown here is for V/f Control (0).
Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
Ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0.
The setting range is 0.0 to 66.0 in AOLV/PM.
When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
Default: <1>
Min.: 10% of drive
OLV/PM
AOLV/PM
CLV/PM
rated current
Sets the full load current for motor 2. Automatically set during Auto-Tuning. Max.: 200% of
drive rated current
V/f
E4-01
(321)
Values
V/f w PG
OLV
Page
CLV
232
<2>
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Default: <1>
Min.: 0.00 Hz
Max.: 20.00 Hz <2>
E4-02
(322)
E4-03
(323)
Default: <1>
Min.: 0 A
<2>
Sets the no-load current for motor 2. Automatically set during Auto-Tuning. Max.: E4-01
E4-04
(324)
Default: 4
Min.: 2
Sets the number of poles of motor 2. Automatically set during Auto-Tuning. Max.: 48
E4-05
(325)
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Motor 2 Line-to-Line
Resistance
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
232
CLV
233
CLV
233
CLV
Default: <1>
Min.: 0.000
Max.: 65.000
233
Default: <1>
Min: 0.0%
Max: 40.0%
233
233
OLV
AOLV/PM
CLV/PM
CLV
E4-07
(343)
Default: 0.50
Min.: 0.00
Set to the motor iron saturation coefficient at 50% of magnetic flux for motor Max.: 0.50
2. Automatically set during Auto-Tuning.
E4-08
(344)
Default: 0.75
Min.: E4-07
Set to the motor iron saturation coefficient at 75% of magnetic flux for motor Max.: 0.75
2. This value is automatically set during Auto-Tuning.
E4-09
(33F)
E4-10
(340)
E4-11
(327)
Sets the voltage drop for motor 2 due to motor leakage inductance as a
percentage of rated voltage. Automatically set during Auto-Tuning.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
CLV
Sets the motor mechanical loss for motor 2 as a percentage of motor rated
power (kW).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
233
Default: 0.0%
Min.: 0.0
Max.: 10.0
233
Default: <1>
Min.: 0 W
Max.: 65535 W
234
CLV
Default: <1>
Min.: 0.00 kW
Sets the motor rated capacity in kW. Automatically set during Auto-Tuning. Max.: 650.00 kW
234
<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
503
Parameter List
V/f
OLV/PM
E4-06
(326)
E5-01
(329)
<2>
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Page
CLV
Enter the Yaskawa motor code for the PM motor being used. Various motor Default: <5> <6>
parameters are automatically set based on the value of this parameter. Settings Min.: 0000
that were changed manually will be overwritten by the defaults of the selected Max.: FFFF <1>
motor code.
234
E5-04
(32C)
<2>
E5-05
(32D)
<2>
E5-06
(32E)
<2>
E5-07
(32F)
<2>
E5-09
(331)
<2>
E5-11
(333)
E5-24
(353)
<2>
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Default: <3>
Min.: 0.10 kW
Max.: 650.00 kW
235
Default: <3>
Min: 10% of drive
rated current
Max: 200% of drive
rated current <4>
235
Default: <3>
Min.: 2
Max.: 48
235
Default: <3>
Min.: 0.000
Max.: 65.000
235
Default: <3>
Min.: 0.00 mH
Max.: 300.00 mH
235
Default: <3>
Min.: 0.00 mH
Max.: 600.00 mH
236
Default: <3>
Min.: 0.0 mV/
Sets the induced phase peak voltage in units of 0.1 mV/(rad/s) [electrical
(rad/s)
angle]. Set this parameter when using a Yaskawa SSR1-Series PM motor with Max.: 2000.0 mV/
derated torque, or a Yaskawa SST4-Series motor with constant torque.
(rad/s)
Set E5-24 to 0 when setting this parameter.
236
E5-03
(32B)
<2>
V/f
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
Sets the offset between the rotor magnetic axis and the Z Pulse of an
incremental encoder during Z Pulse offset tuning.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
236
CLV
Default: <3>
Min.: 0.0 mV/
(r/min)
Sets the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min)
[mechanical angle]. Set this parameter when using a Yaskawa SMRA-Series Max.: 6500.0 mV/
(r/min)
SPM motor.
236
<1>
<2>
<3>
<4>
504
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.8 F: Options
B.8 F: Options
F parameters program the drive for PG feedback from the motor and to function with option cards.
F1-01
(380)
F1-02
(381)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
Operation Selection at PG
Open Circuit (PGo)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Page
237
CLV
Default: 1
Range: 0 to 4
237
Default: 1
Range: 0 to 3
237
Default: 3
Range: 0 to 3
238
Default: <1>
Range: 0, 1
238
Note: Due to potential damage to the motor and machinery, only use the
Alarm only and No alarm display settings under special
circumstances.
F1-04
(383)
F1-05
(384)
F1-06
(385)
F1-08
(387)
Operation Selection at
Overspeed (oS)
Operation Selection at
Deviation
PG 1 Rotation Selection
V/f w PG
OLV
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Pulse A leads
1: Pulse B leads
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the division ratio for the pulse monitor used of the PG option card installed Default: 1
Min.: 1
to port CN5-C.
Max.: 132
By setting xyz, the division ratio becomes = [(1 + x) / yz].
If only using the A pulse for one-track input, the input ratio will be 1:1
regardless of F1-06 setting.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Default: 115%
Min.: 0
Max.: 120
238
237
505
Parameter List
F1-03
(382)
V/f
OLV/PM
B.8 F: Options
No.
(Addr.
Hex)
Name
F1-09
(388)
F1-10
(389)
Default: 10%
Excessive Speed Deviation
OLV/PM
AOLV/PM
CLV/PM
Min.: 0
Detection Level
Sets the speed deviation detection level as a percentage of the maximum output Max.: 50
frequency.
F1-11
(38A)
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
V/f
F1-12
(38B)
PG 1 Gear Teeth 1
F1-13
(38C)
PG 1 Gear Teeth 2
F1-14
(38D)
PG Open-Circuit Detection
Time
F1-18
(3AD)
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
F1-32
(3B1)
F1-33
(3B2)
506
PG 2 Gear Teeth 1
238
CLV
CLV
238
238
Default: 0
Min.: 0
Sets the gear ratio between the motor shaft and the encoder (PG). A gear ratio Max.: 1000
of 1 will be used if F1-12 or F1-13 are set to 0.
238
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Disabled
n: Number of dv3 occurrences that must be detected to trigger a dv3 fault.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: Disabled
n: Number of pulses that the A and B pulse are reversed that triggers dv4
detection.
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
239
Default: 128
Min.: 0
Max.: 5000
239
Default: 1
Range: 0, 1
239
Default: 0
Range: 0, 1
239
Default: 1
Range: 0, 1
240
237
Default: 0
Range: 0, 1
238
Default: 0
Min.: 0
Max.: 1000
238
CLV
CLV
CLV
0: Pulse A leads
1: Pulse B leads
OLV/PM
Default: 10
Min.: 0
Max.: 10
CLV
237
CLV
0: A pulse detection
1: AB pulse detection
OLV/PM
Default: 2.0 s
Min.: 0.0
Max.: 10.0
CLV
Sets the number of pulses for a PG option card connected to port CN5-B.
PG 2 Rotation Selection
237
CLV
Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if F1-12 or F1-13 are set to 0.
V/f
F1-31
(3B0)
Page
Default: 0
Min.: 0
Max.: 1000
Default: <1>
Min.: 0.0 s
Max.: 2.0 s
Default: 0.5 s
Min.: 0.0
Sets the time in seconds for a speed deviation situation to trigger a fault (dEv). Max.: 10.0
F1-20
(3B4)
F1-30
(3AA)
OLV
V/f
PG 1 Signal Selection
V/f w PG
OLV/PM
F1-19
(3AE)
F1-21
(3BC)
CLV
Values
CLV
Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if F1-33 or F1-34 are set to 0.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.8 F: Options
No.
(Addr.
Hex)
F1-34
(3B3)
Name
PG 2 Gear Teeth 2
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: 0
Min.: 0
Sets the gear ratio between the motor shaft and the encoder (PG). A gear ratio Max.: 1000
of 1 will be used if F1-33 or F1-34 are set to 0.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
238
CLV
F1-36
(3B5)
Page
CLV
F1-35
(3BE)
F1-37
(3BD)
Values
Default: 1
Min.: 1
Max.: 132
238
Default: 1
Range: 0, 1
239
Default: 0
Range: 0, 1
239
CLV
CLV
0: A pulse detection
1: AB pulse detection
Name
Description
Values
Page
All Modes
F2-01
(38F)
F2-02
(368)
F2-03
(369)
0: Option card input terminals V1, V2, and V3 replace drive input terminals Default: 0
A1, A2, and A3.
Range: 0, 1
1: Input signals to terminals V1, V2, and V3 are added together to create the
frequency reference.
All Modes
Sets the gain for the input signal to the analog card.
Sets the bias for the input signal to the analog card.
All Modes
240
Default: 100.0%
Min.: -999.9
Max.: 999.9
240
Default: 0.0%
Min.: -999.9
Max.: 999.9
240
Name
Description
Values
Page
F3-01
(390)
240
All Modes
F3-03
(3B9)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Default: 2
Range: 0 to 2
Parameter List
All Modes
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
Default: 0
4: BCD, 0.1 Hz units
Range: 0 to 7
5: BCD, 0.01 Hz units
6: BCD customized setting (5-digit), 0.02 Hz units
7: Binary input
When the digital operator units are set to be displayed in Hertz or user-set units
(o1-03 = 2 or 3), the units for F3-01 are determined by parameter o1-03.
241
507
B.8 F: Options
Name
Description
Values
Page
All Modes
F4-01
(391)
F4-02
(392)
Terminal V1 Monitor
Selection
Sets the monitor signal for output from terminal V1. Set this parameter to the Default: 102
Range: 000 to 999
last three digits of the desired Uo-oo monitor. Some U parameters are
available only in certain control modes.
All Modes
Terminal V1 Monitor Gain Sets the gain for voltage output via terminal V1.
Default: 100.0%
Min.: -999.9
Max.: 999.9
241
241
All Modes
F4-03
(393)
F4-04
(394)
Terminal V2 Monitor
Selection
Sets the monitor signal for output from terminal V2. Set this parameter to the Default: 103
Range: 000 to 999
last three digits of the desired Uo-oo monitor. Some U parameters are
available only in certain control modes.
241
All Modes
Default: 50.0%
Min.: -999.9
Max.: 999.9
241
All Modes
Default: 0.0%
Min.: -999.9
Max.: 999.9
241
Default: 0.0%
Min.: -999.9
Max.: 999.9
241
Default: 0
Range: 0, 1
242
Default: 0
Range: 0, 1
242
Terminal V2 Monitor Gain Sets the gain for voltage output via terminal V2.
F4-05
(395)
Sets the amount of bias added to the voltage output via terminal V1.
F4-06
(396)
Sets the amount of bias added to the voltage output via terminal V2.
F4-07
(397)
0: 0 to 10 V
1: -10 to 10 V
F4-08
(398)
0: 0 to 10 V
1: -10 to 10 V
All Modes
All Modes
All Modes
F5-02
(39A)
F5-03
(39B)
F5-04
(39C)
F5-05
(39D)
F5-06
(39E)
F5-07
(39F)
F5-08
(3A0)
F5-09
(3A1)
Name
Description
All Modes
Sets the function for contact output terminals M1-M2, M3-M4, and
photocoupler output terminals P1 through P6.
Values
Page
Default: 2
Range: 0 to 192
242
Default: 4
Range: 0 to 192
Default: 6
Range: 0 to 192
Default: 37
Range: 0 to 192
Default: F
Range: 0 to 192
Default: F
Range: 0 to 192
Default: 0
Range: 0 to 192
Default: 1
Range: 0 to 192
242
242
242
242
242
242
242
All Modes
508
Default: 0
0: Output terminals are each assigned separate output functions.
Range: 0 to 2
1: Binary code output.
2: Use output terminal functions selected by parameters F5-01 through F5-08.
242
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.8 F: Options
Name
Description
Values
Page
All Modes
F6-01
(3A2)
Communications Error
Operation Selection
F6-02
(3A3)
F6-03
(3A4)
External Fault from Comm. 0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
Option Operation Selection 1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
F6-04
(3A5)
F6-06
(3A7)
Torque Reference/Torque
AOLV/PM
CLV/PM
Limit Selection from Comm. OLV/PM
0: Disabled. Torque reference/limit from option board disabled.
Option
1: Enabled. Torque reference/limit from option board enabled.
All Modes
Default: 1
Range: 0 to 3
243
Default: 0
Range: 0, 1
243
Default: 1
Range: 0 to 3
243
Default: 2.0 s
Min.: 0.0
Max.: 5.0
244
Default: 0
Range: 0, 1
243
Default: 0
Range: 0, 1
243
All Modes
All Modes
Sets the delay time for error detection if a bus error occurs.
V/f
F6-07
(3A8)
F6-08
(36A)
<1>
F6-10
(3B6)
V/f w PG
OLV
CLV
All Modes
Multi-Step Speed Enable/
Disable Selection when
0: Multi-step reference disabled (same as F7)
NefRef/ComRef is Selected 1: Multi-step reference enabled (same as V7)
All Modes
Reset Communication
Parameters
0: Communication-related parameters (F6-oo) are not reset when the drive Default: 0
is initialized using A1-03.
Range: 0, 1
1: Reset all communication-related parameters (F6-oo) when the drive is
initialized using A1-03.
Default: 0
All Modes
Min.: 0
Sets the node address if a CC-Link option is installed.
Max.: 64
244
244
All Modes
F6-11
(3B7)
CC-Link Communication
Speed
F6-14
(3BB)
F6-20
(36B)
MECHATROLINK Station
Sets the station address when the MECHATROLINK-II option has been
Address
installed.
F6-21
(36C)
MECHATROLINK Frame
Size
F6-22
(36D)
MECHATROLINK Link
Speed
F6-23
(36E)
MECHATROLINK
Monitor Selection (E)
All Modes
0: Disabled
1: Enabled
All Modes
All Modes
0: 32 byte
1: 17 byte
All Modes
0: 10 Mbps
1: 4 Mbps
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Default: 0
Range: 0 to 4
244
Default: 0
Range: 0, 1
244
Default: 21
Min.: 20
Max.: 3F
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Min.: 0
Max.: FFFF
Parameter List
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
509
B.8 F: Options
No.
(Addr.
Hex)
Name
Description
Values
Page
Default: 0
Min.: 0
Max.: FFFF
F6-25
(3C9)
Default: 1
Range: 0 to 3
F6-26
(3CA)
MECHATROLINK bUS
Errors Detected
Default: 2
Min.: 2
Max.: 10
F6-30
(3CB)
PROFIBUS-DP Node
Address
Default: 0
Min.: 0
Max.: 125
245
F6-31
(3CC)
F6-32
(3CD)
PROFIBUS-DP Data
Format Selection
F6-35
(3D0)
CANopen Node ID
Selection
F6-24
(36F)
MECHATROLINK
Monitor Selection (F)
All Modes
All Modes
All Modes
0: PPO Type
1: Conventional
All Modes
245
Default: 0
Range: 0, 1
245
Default: 0
Min.: 0
Max.: 126
245
Default: 6
Range: 0 to 8
245
Default: 64
Min.: 0
Max.: 64
246
Default: 4
Range: 0 to 4
246
All Modes
F6-36
(3D1)
CANopen Communication
Speed
F6-50
(3C1)
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
All Modes
F6-51
(3C2)
0: 125 kbps
DeviceNet Communication 1: 250 kbps
Speed
2: 500 kbps
3: Adjustable from network
4: Detect automatically
All Modes
F6-52
(3C3)
F6-53
(3C4)
F6-54
(3C5)
Sets the format of the data set from the DeviceNet master to the drive.
All Modes
Sets the format of the data set from the drive to the DeviceNet master.
All Modes
Default: 21
Min.: 0
Max.: 255
Default: 71
Min.: 0
Max.: 255
246
246
Default: 0
Range: 0, 1
246
Default: 0
Range: 0 to 2
246
Default: 0
Min.: -15
Max.: 15
247
All Modes
F6-55
(3C6)
F6-56
(3D7)
510
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.8 F: Options
No.
(Addr.
Hex)
Name
F6-57
(3D8)
F6-58
(3D9)
F6-59
(3DA)
F6-60
(3DB)
F6-61
(3DC)
F6-62
(3DD)
DeviceNet Heartbeat
Interval
F6-63
(3DE)
Reserved
IP Address 1
F7-02
(3E6)
IP Address 2
F7-03
(3E7)
IP Address 3
F7-04
(3E8)
IP Address 4
F7-05
(3E9)
Subnet Mask 1
F7-06
(3EA)
Subnet Mask 2
F7-07
(3EB)
Subnet Mask 3
F7-08
(3EC)
Subnet Mask 4
F7-09
(3ED)
Gateway Address 1
F7-10
(3EE)
Gateway Address 2
F7-11
(3EF)
Gateway Address 3
F7-12
(3E0)
Gateway Address 4
<2>
<2>
<2>
All Modes
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: 0
Max.: 10
Default: 63
Min.: 0
Max.: 63
Page
247
247
247
247
247
247
247
All Modes
F7-01
(3E5)
<2>
All Modes
Sets the scaling factor for the output current monitor in DeviceNet.
Values
All Modes
Sets the second most significant octet of network static Subnet Mask.
All Modes
Sets the third most significant octet of network static Subnet Mask.
All Modes
Sets the fourth most significant octet of network static Subnet Mask.
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Default: 192
Range: 0 to 255
Default: 168
Range: 0 to 255
Default: 1
Range: 0 to 255
Default: 20
Range: 0 to 255
Default: 255
Range: 0 to 255
Default: 255
Range: 0 to 255
Default: 255
Range: 0 to 255
Default: 0
Range: 0 to 255
Default: 192
Range: 0 to 255
Default: 168
Range: 0 to 255
Default: 1
Range: 0 to 255
Default: 1
Range: 0 to 255
Parameter List
F6-64 to
F6-71
(3DF to
3C8)
Description
511
B.8 F: Options
No.
(Addr.
Hex)
Name
Description
Values
Page
All Modes
F7-13
(3F1)
Default: 2
Range: 0 to 2
Default: 1
Range: 0 to 2
Default: 10
Range: 10, 100
All Modes
F7-14
(3F2)
F7-15
(3F3)
Communication Speed
Selection
F7-16
(3F4)
Communication Loss
Timeout
Default: 0
Sets the timeout value for communication loss detection in tenths of a second. Min.: 0
A value of 0 disables the connection timeout.
Max.: 300
Example: An entered value of 100 represents 10.0 seconds.
F7-17
(3F5)
Default: 0
Min.: -15
Max.: 15
F7-18
(3F6)
All Modes
Default: 0
EtherNet/IP Current Scaling
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID Min.: -15
Factor
Max.: 15
2AH Object.
F7-19
(3F7)
Default: 0
Min.: -15
Max.: 15
F7-20
(3F8)
Default: 0
Min.: -15
Max.: 15
F7-21
(3F9)
All Modes
Default: 0
EtherNet/IP Voltage Scaling
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH Min.: -15
Factor
Max.: 15
Object.
F7-22
(3FA)
Default: 0
Min.: -15
Max.: 15
All Modes
All Modes
All Modes
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH
Object.
All Modes
All Modes
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.
All Modes
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
All Modes
F7-23 to
F7-32
(3FB to
374)
F7-33 to
F7-42
(375 to
37E)
All Modes
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Cycle power for setting changes to take effect.
<3> If F7-13 is set to 0, all IP addresses (F7-01 to F7-04) must be unique.
512
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
All Modes
H1-01
(438)
H1-02
(439)
H1-03
(400)
H1-04
(401)
H1-05
(402)
H1-06
(403)
H1-07
(404)
H1-08
(405)
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
Values
Page
248
248
Default: 24
Min.: 0
Max.: 9F
248
Default: 14
Min.: 0
Max.: 9F
248
248
248
248
Default: 8
Min.: 0
Max.: 9F
248
<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).
H1 Multi-Function Digital Input Selections
Function
Description
Page
All Modes
3-Wire sequence
Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)
Terminals S1 and S2 are automatically set up for the Run command and Stop command.
LOCAL/REMOTE selection
Open: REMOTE (parameter settings determine the source of the frequency Reference 1 or 2
(b1-01, b1-02 or b1-15, b1-16)
Closed: LOCAL, digital operator is run and reference source
Open: Run command and frequency reference source 1 (determined by b1-01 and b1-02)
Closed: Run command and frequency reference source 2 (determined by b1-15 and b1-16)
249
All Modes
249
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
250
513
Parameter List
H1-oo
Setting
Function
Description
Page
250
All Modes
When input terminals are set to Multi-Step Speed References 1 through 3, switching
combinations of those terminals will create a multi-step speed sequence using the frequency
references set in d1-01 through d1-08.
When input terminals are set to Multi-Step Speed References 1 through 3, switching
combinations of those terminals will create a multi-step speed sequence using the frequency
references set in d1-01 through d1-08.
When input terminals are set to Multi-Step Speed References 1 through 3, switching
combinations of those terminals will create a multi-step speed sequence using the frequency
references set in d1-01 through d1-08.
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference
sources.
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2 (set
in C1-03, C1-04).
All Modes
250
All Modes
250
All Modes
250
All Modes
All Modes
250
250
250
250
251
All Modes
PG encoder disable
Through mode
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
251
251
CLV
Open: PI control
Closed: Integral reset
251
All Modes
Select this setting when using the terminal in a pass-through mode. The terminal does not
trigger a drive function but can be used as digital input for the controller the drive is connected
to.
251
All Modes
10
Up command
The drive accelerates when the Up command terminal closes, and decelerates when the Down
command closes. When both terminals are closed or both are open, the drive holds the
frequency reference. The Up and Down commands must always be used in conjunction with
one another.
251
All Modes
514
11
Down command
12
Forward Jog
The drive accelerates when the Up command terminal closes, and decelerates when the Down
command closes. When both terminals are closed or both are open, the drive holds the
frequency reference. The Up and Down commands must always be used in conjunction with
one another.
All Modes
251
252
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Function
13
Reverse Jog
14
Fault reset
15
Description
All Modes
Closed: Resets faults if the cause is cleared and the Run command is removed.
All Modes
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Page
252
252
252
CLV
16
Motor 2 selection
17
18
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the
timer function output (H2-oo = 12).
19
PID disable
1A
Used in conjunction with an input terminal set for Accel/decel time selection 1
(H1-oo = 7), and allows the drive to switch between accel/decel times 3 and 4.
1B
Program lockout
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to
the digital operator).
Closed: Parameters can be edited and saved.
1E
253
252
All Modes
253
All Modes
254
All Modes
254
All Modes
All Modes
Closed: Samples the analog frequency reference and operates the drive at that speed.
254
254
All Modes
External fault
30
31
32
Multi-Step Speed
Reference 4
34
All Modes
254
255
All Modes
255
All Modes
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2, and 3. Use
parameters d1-09 to d1-16 to set reference values.
255
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
255
515
Parameter List
20 to 2F
Function
35
40
Description
All Modes
Page
255
Open: Stop
Closed: Forward run
255
41
Open: Stop
Closed: Reverse run
255
42
Run command
(2-Wire sequence 2)
Open: Stop
Closed: Run
256
43
FWD/REV command
(2-Wire sequence 2)
44
Offset frequency 1
45
Offset frequency 2
46
Offset frequency 3
47
Node setup
60
Open: Forward
Closed: Reverse
256
Note: Determines motor direction, but does not issue a Run command. Cannot be set
together with settings 40 or 41.
All Modes
V/f w PG
OLV
AOLV/PM
CLV/PM
256
256
256
256
CLV
256
62
63
Field weakening
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Closed: Activates Current Detection Speed Search from the maximum output frequency
(E1-04).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
256
CLV
256
Closed: Activates Current Detection Speed Search from the frequency reference.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
256
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
65
66
67
68
All Modes
256
256
Tests the MEMOBUS/Modbus RS-485/422 interface. Displays PASS if the test completes
successfully.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
256
CLV
257
Closed: Activates High Slip Braking to stop the drive during a Run command.
516
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Function
Description
Page
Open: Drive disabled. If this input is opened during run, the drive will stop as specified by
b1-03.
Closed: Ready for operation.
257
All Modes
6A
Drive enable
71
72
Zero servo
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
257
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
257
75
Up 2 command
Used to control the bias added to the frequency reference by the Up/Down 2 function. The
Up 2 and Down 2 commands must always be used in conjunction with one another.
76
Down 2 command
Used to control the bias added to the frequency reference by the Up/Down 2 function. The
Up 2 and Down 2 commands must always be used in conjunction with one another.
257
All Modes
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
77
78
7A
Open: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB
Ride-Thru 2.
7B
Closed: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB
Ride-Thru 2.
7C
V/f w PG
OLV
257
258
CLV
258
All Modes
258
All Modes
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
258
CLV
258
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
258
90 to 97
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Forward/reverse detection
(V/f Control with Simple PG
feedback)
DriveWorksEZ
digital inputs 1 to 8
All Modes
258
259
All Modes
9F
DriveWorksEZ disable
259
Parameter List
7E
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
517
Name
Terminal M1-M2 function
selection (relay)
Terminal M3-M4 function
selection (relay)
Terminal M5-M6 function
selection (relay)
Description
All Modes
Values
Page
Default: 0
Range: 0 to 192
Default: 1
Range: 0 to 192
Default: 2
Range: 0 to 192
259
Default: 0
Range: 0 to 4
269
259
259
All Modes
H2-06
(437)
Outputs a 200 ms pulse signal when the watt-hour counter increases by the
units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function
Description
All Modes
During run
Zero speed
Speed agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the hysteresis set to
L4-02).
Frequency detection 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined
by L4-02.
Frequency detection 2
Drive ready
DC bus undervoltage
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-15).
Closed: Digital operator supplies the frequency reference.
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
Page
260
All Modes
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
All Modes
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02).
260
260
All Modes
261
All Modes
261
All Modes
Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis determined
by L4-02.
All Modes
Closed: Power up is complete and the drive is ready to accept a Run command.
All Modes
Closed: Drive has entered the baseblock state (no output voltage).
262
262
262
263
All Modes
263
All Modes
518
All Modes
263
263
263
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Function
Description
Page
All Modes
263
Fault
Through mode
10
Minor fault
11
12
Timer output
13
Speed agree 2
14
15
Frequency detection 3
16
Frequency detection 4
17
All Modes
263
Set this value when using the terminal in the pass-through mode.
All Modes
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.
263
263
All Modes
18
19
1A
During reverse
1B
1C
Motor 2 selection
Closed: A command has been entered to clear a fault via the input terminals or from the serial
network.
All Modes
263
264
Closed: When drive output frequency equals the frequency reference L4-04.
All Modes
Closed: When the drive output frequency is equal to the value in L4-03 L4-04.
All Modes
Closed: When the drive output frequency is less than or equal to the value in L4-03 L4-04.
All Modes
Closed: When the output frequency is greater than or equal to the value in L4-03 L4-04.
264
264
265
265
All Modes
263
Open: Drive has entered the baseblock state (no output voltage).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
263
265
266
CLV
266
During regeneration
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
266
1E
Restart enabled
1F
20
22
Mechanical weakening
detection
2F
Maintenance period
All Modes
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
All Modes
266
266
266
B
266
All Modes
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require
maintenance.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter List
266
519
Function
During torque limit
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Page
CLV
266
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
267
33
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
267
Closed: Speed limit has been reached while using Torque Control.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
267
37
38
Drive enabled
39
3C
LOCAL/REMOTE status
3D
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being
performed).
All Modes
Closed: Multi-function input set for Drive enable is closed (H1-oo = 6A)
All Modes
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
267
267
267
All Modes
267
Open: REMOTE
Closed: LOCAL
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
268
3F
4A
4B
All Modes
268
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
268
268
CLV
268
4D
4E
All Modes
Closed: A Fast Stop command has been entered from the operator or input terminals.
All Modes
268
268
All Modes
268
4F
Braking resistor overheat (oH) Closed: The dynamic braking resistor has overheated.
268
520
All Modes
268
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
90 to 92
Function
Rotor position detection
complete
DriveWorksEZ
digital outputs 1 to 3
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Page
CLV
268
Closed: Drive has successfully detected the rotor position of the PM motor.
All Modes
268
0 to 92 with inverse
100 to 192 Function
Inverts the output switching of the multi-function output functions.
output
Set the last two digits of 1oo to reverse the output signal of that specific function.
268
Name
H3-01
(410)
H3-02
(434)
Terminal A1 Function
Selection
H3-03
(411)
H3-04
(412)
H3-05
(413)
H3-06
(414)
Terminal A3 Function
Selection
H3-07
(415)
H3-08
(416)
Description
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.
Values
Default: 0
Range: 0, 1
269
Default: 0
Range: 0 to 31
269
Default: 100.0%
Min.: -999.9
Max.: 999.9
270
All Modes
Default: 0.0%
Sets the level of the input value selected in H3-02 when 0 V is input at terminal Min.: -999.9
Max.: 999.9
A1.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Sets the level of the input value selected in H3-06 when 10 V is input at
terminal A3.
Page
270
Default: 0
Range: 0, 1
270
Default: 2
Range: 0 to 31
270
Default: 100.0%
Min.: -999.9
Max.: 999.9
271
All Modes
Default: 0.0%
Sets the level of the input value selected in H3-06 when 0 V is input at terminal Min.: -999.9
Max.: 999.9
A3.
271
All Modes
H3-09
(417)
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Default: 2
Range: 0 to 3
271
Default: 0
Range: 0 to 31
271
H3-10
(418)
Terminal A2 Function
Selection
H3-11
(419)
H3-12
(41A)
H3-13
(41B)
All Modes
All Modes
Default: 100.0%
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input Min.: -999.9
Max.: 999.9
at terminal A2.
All Modes
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is
input at terminal A2.
Default: 0.0%
Min.: -999.9
Max.: 999.9
All Modes
Default: 0.03 s
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used Min.: 0.00
Max.: 2.00
for noise filtering.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
271
271
272
521
Parameter List
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage
input signal.
Name
Description
Values
Page
All Modes
H3-14
(41C)
H3-16
(2F0)
Terminal A1 Offset
H3-17
(2F1)
Terminal A2 Offset
H3-18
(2F2)
Terminal A3 Offset
Determines which analog input terminals will be enabled when a digital input
programmed for Analog input enable (H1-oo = C) is activated.
1: Terminal A1 only
Default: 7
2: Terminal A2 only
Range: 1 to 7
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
All Modes
Default: 0
Min.: -500
Max.: 500
Default: 0
Min.: -500
Max.: 500
Default: 0
Min.: -500
Max.: 500
272
273
273
273
Function
Description
All Modes
Frequency bias
Frequency gain
Page
273
All Modes
All Modes
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
273
273
273
CLV
273
All Modes
273
10 V = 100%
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
273
Overtorque/undertorque
detection level
All Modes
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
274
CLV
274
522
PID feedback
PID setpoint
Frequency bias
All Modes
274
274
10 V = 100%
All Modes
274
10 V = 100%
All Modes
274
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Function
Description
Through mode
10
Page
All Modes
274
10 V = 100%
All Modes
274
Set this value when using the terminal in the pass-through mode.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
274
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
274
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
274
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
275
Torque compensation
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
275
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
274
All Modes
275
10 V = 100%
All Modes
17
10 V = -9 C
0 V = 234 C
275
Through mode
DriveWorksEZ
analog input 1 to 3
All Modes
274
Set this value when using the terminal in the pass-through mode.
All Modes
275
Name
Description
Values
Page
Default: 102
Range: 000 to 999
275
Default: 100.0%
Min.: -999.9
Max.: 999.9
275
H4-01
(41D)
H4-02
(41E)
H4-03
(41F)
Multi-Function Analog
Output Terminal FM Gain
Multi-Function Analog
Output Terminal FM Bias
Sets the signal level at terminal FM that is equal to 100% of the selected
monitor value.
All Modes
Default: 0.0%
Sets the signal level at terminal FM that is equal to 0% of the selected monitor Min.: -999.9
Max.: 999.9
value.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
275
523
Parameter List
All Modes
Multi-Function Analog
Output Terminal FM
Monitor Selection
Name
Description
Values
Page
Default: 103
Range: 000 to 999
275
Default: 50.0%
Min.: -999.9
Max.: 999.9
275
All Modes
H4-04
(420)
H4-05
(421)
H4-06
(422)
Multi-Function Analog
Output Terminal AM
Monitor Selection
Multi-Function Analog
Output Terminal AM Gain
Multi-Function Analog
Output Terminal AM Bias
Sets the signal level at terminal AM that is equal to 100% of the selected
monitor value.
All Modes
Default: 0.0%
Sets the signal level at terminal AM that is equal to 0% of the selected monitor Min.: -999.9
Max.: 999.9
value.
275
All Modes
H4-07
(423)
Multi-Function Analog
Output Terminal FM Signal 0: 0 to 10 V
1: -10 to 10 V
Level Selection
2: 4 to 20 mA
H4-08
(424)
Multi-Function Analog
Output Terminal AM Signal 0: 0 to 10 V
1: -10 to 10 V
Level Selection
2: 4 to 20 mA
Default: 0
Range: 0 to 2
276
Default: 0
Range: 0 to 2
276
All Modes
Name
Description
All Modes
Values
Page
Default: 1F (Hex)
Min.: 0
Max.: FF
598
Default: 3
Range: 0 to 8
598
Default: 0
Range: 0 to 2
598
Default: 0
Range: 0 to 3
598
Default: 0
Range: 0, 1
599
Default: 5 ms
Min.: 5
Max.: 65
599
Default: 1
Range: 0, 1
599
All Modes
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
H5-02
(426)
Communication Speed
Selection
H5-03
(427)
Communication Parity
Selection
H5-04
(428)
0: Ramp to stop
Stopping Method after
Communication Error (CE) 1: Coast to stop
2: Fast Stop
3: Alarm only
H5-05
(429)
Communication Fault
Detection Selection
H5-06
(42A)
H5-07
(42B)
All Modes
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
All Modes
All Modes
524
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault
will occur.
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
All Modes
H5-09
(435)
CE Detection Time
H5-10
(436)
H5-11
(43C)
Communications ENTER
Function Selection
H5-12
(43D)
0: 0.1 V units
1: 1 V units
Values
Page
Default: 2.0 s
Min.: 0.0
Max.: 10.0
599
Default: 0
Range: 0, 1
599
All Modes
Default: 0
Range: 0, 1
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
600
600
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
Name
Description
Values
Page
All Modes
0: Frequency reference
Pulse Train Input Terminal 1: PID feedback value
Default: 0
RP Function Selection
Range: 0 to 3
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1
in V/f Control)
277
H6-02
(42D)
All Modes
Default: 1440 Hz
Sets the terminal RP input signal frequency that is equal to 100% of the value Min.: 1000
Max.: 32000
selected in H6-01.
278
H6-03
(42E)
All Modes
Default: 100.0%
Sets the level of the value selected in H6-01 when a frequency with the value Min.: 0.0
Max.: 1000.0
set in H6-02 is input.
278
H6-04
(42F)
H6-05
(430)
H6-06
(431)
H6-07
(432)
H6-08
(43F)
All Modes
Pulse Train Input Filter Time Sets the pulse train input filter time constant.
Default: 0.0%
Min.: -100.0
Max.: 100.0
278
Default: 0.10 s
Min.: 0.00
Max.: 2.00
278
Default: 102
Range: 000 to 809
278
All Modes
Select the pulse train monitor output function (value of the o-oo part of
Uo-oo).
For example, enter 501 for U5-01.
All Modes
Default: 1440 Hz
Pulse Train Monitor Scaling Sets the terminal MP output signal frequency when the monitor value is 100%. Min.: 0
To have the pulse train monitor output equal the output frequency, set H6-06 Max.: 32000
to 2 and H6-07 to 0.
278
All Modes
Default: 0.5 Hz
Pulse Train Input Minimum
Min.: 0.1
Sets
the
minimum
frequency
for
the
pulse
train
input
to
be
detected.
Enabled
Frequency
Max.: 1000.0
when H6-01 = 0, 1, or 2.
278
Parameter List
H6-01
(42C)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
525
Name
Description
Values
Page
All Modes
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
Default: <1>
4: PM motor with variable torque
Range: 0 to 6
5: PM motor with constant torque control
6: General purpose motor (50 Hz)
The drive may not be able to provide protection when using multiple motors,
even if overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal
relays to each motor.
L1-01
(480)
L1-02
(481)
L1-03
(482)
Sets operation when the motor temperature analog input (H3-02, H3-06, or
H3-10 = E) exceeds the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only (oH3 will flash)
L1-04
(483)
Sets stopping method when the motor temperature analog input (H3-02,
H3-06, or H3-10 = E) exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
L1-05
(484)
L1-13
(46D)
Continuous Electrothermal
Operation Selection
280
282
Default: 3
Range: 0 to 3
284
Default: 1
Range: 0 to 2
284
Default: 0.20 s
Min.: 0.00
Max.: 10.00
284
Default: 1
Range: 0, 1
285
Default: 0
Note: This parameter is only available in models CIMR-Ao4A0930 and Range: 0, 1
4A1200.
286
All Modes
All Modes
All Modes
Adjusts the filter for the motor temperature analog input (H3-02, H3-06, or
H3-10 = E).
All Modes
0: Disabled
1: Enabled
All Modes
L1-15
(440)
Motor 1 Thermistor
Selection (NTC)
L1-16
(441)
Motor 1 Overheat
Temperature
0: Disabled
1: Enabled
All Modes
Default: 120 C
Min.: 50
Note: This parameter is only available in models CIMR-Ao4A0930 and Max.: 200
4A1200.
Sets the temperature for motor 1 that triggers an overheat fault (oH5).
286
All Modes
L1-17
(442)
526
Motor 2 Thermistor
Selection (NTC)
0: Disabled
1: Enabled
Note: This parameter is only available in models CIMR-Ao4A0930 and
4A1200.
Default: 0
Range: 0, 1
286
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
L1-18
(443)
Motor 2 Overheat
Temperature
Description
Values
Page
All Modes
Default: 120 C
Min.: 50
Note: This parameter is only available in models CIMR-Ao4A0930 and Max.: 200
4A1200.
Sets the temperature for motor 1 that triggers an overheat fault (oH5).
286
All Modes
L1-19
(444)
Operation at Thermistor
Disconnect (THo) (NTC)
286
L1-20
(445)
Default: 1
Range: 0 to 3
286
Name
Description
Values
Page
All Modes
L2-01
(485)
L2-02
(486)
Sets the Power Loss Ride-Thru time. Enabled only when L2-01 = 1 or 3.
Default: <1>
Min.: 0.0 s
Max.: 25.5 s
287
292
All Modes
<1>
Sets the minimum wait time for residual motor voltage decay before the drive Default:
Min.:
0.1
s
output reenergizes after performing Power Loss Ride-Thru.
Increasing the time set to L2-03 may help if overcurrent or overvoltage occur Max.: 5.0 s
during Speed Search or during DC Injection Braking.
L2-03
(487)
L2-04
(488)
Default: <1>
Min.: 0.0 s
Sets the time for the output voltage to return to the preset V/f pattern during Max.: 5.0 s
Speed Search.
L2-05
(489)
Undervoltage Detection
Level (Uv1)
L2-06
(48A)
All Modes
Default: 0.00 s
Sets the time required to decelerate from the speed when KEB was activated Min.: 0.00 <4>
Max.: 6000.0
to zero speed.
293
L2-07
(48B)
All Modes
Default: 0.00 s
Sets the time to accelerate to the frequency reference when momentary power Min.: 0.00 <4>
Max.: 6000.0
loss is over. If set to 0.0, the active acceleration time is used.
293
V/f w PG
OLV
AOLV/PM
CLV/PM
CLV
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
292
292
527
Parameter List
V/f
OLV/PM
292
Name
L2-08
(48C)
L2-10
(48E)
L2-11
(461)
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Page
CLV
Sets the desired value of the DC bus voltage during KEB Ride-Thru.
Default: 100%
Min.: 0
Max.: 300
293
Default: 50 ms
Min.: 0
Max.: 2000
293
Default: <2>
[E1-01] 1.22
Min.: 150 Vdc
Max.: 400 Vdc <5>
293
Default: 0
Range: 0 to 3
293
All Modes
L2-29
(475)
<1>
<2>
<3>
<4>
Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
Default setting is dependent on parameter E1-01, Input voltage Setting.
Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but
set the value below 1040 Vdc (overvoltage protection level).
528
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
L3-01
(48F)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Page
CLV
0: Disabled.
1: General purpose. Acceleration is paused as long as the current is above the Default: 1
Range: 0 to 2
L3-02 setting.
2: Intelligent. Accelerate in the shortest possible time without exceeding the
L3-02 level.
294
L3-03
(491)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets Stall Prevention lower limit during acceleration when operating in the
constant power range. Set as a percentage of drive rated current.
Default: <1>
Min.: 0%
Max.: 150%
<1>
Default: 50%
Min.: 0
Max.: 100
295
295
All Modes
L3-04
(492)
296
L3-05
(493)
L3-06
(494)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Disabled. Drive runs at a set frequency. A heavy load may cause speed loss. Default: 1
1: Decel time 1. Uses the deceleration time set to C1-02 while Stall Prevention Range: 0 to 2
is performed.
2: Decel time 2. Uses the deceleration time set to C1-04 while Stall Prevention
is performed.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
297
CLV
Default: <1>
Min.: 30%
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive rated current. Max.: 150%
<1>
297
All Modes
L3-11
(4C7)
Overvoltage Suppression
Function Selection
Default: 0
Range: 0, 1
L3-17
(462)
L3-20
(465)
L3-21
(466)
Accel/Decel Rate
Calculation Gain
298
298
Default: <4>
Min.: 0.00
Max.: 5.00
298
Default: 1.00
Sets the proportional gain used to calculate the deceleration rate during KEB Min.: 0.10
Ride-Thru, ov suppression function, and Stall Prevention during deceleration Max.: 10.00
(L3-04 = 2).
299
All Modes
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
529
Parameter List
Name
Deceleration Time at Stall
Prevention during
Acceleration
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the deceleration time used for Stall Prevention during acceleration in
OLV/PM.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Default: 0.0 s
Min.: 0.0
Max.: 6000
Automatic Reduction
Selection for Stall
Prevention during Run
L3-24
(46E)
L3-25
(46F)
L3-26
(455)
Additional DC Bus
Capacitors
L3-27
(456)
<1>
<2>
<3>
<4>
<5>
<6>
<7>
<8>
0: Sets the Stall Prevention level set in L3-04 that is used throughout the entire Default: 0
Range: 0, 1
frequency range.
1: Automatic Stall Prevention level reduction in the constant output range. The
lower limit value is 40% of L3-06.
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
When DC bus capacitors have been added externally, be sure to add those
values to the internal capacitor table for proper DC bus calculations.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
296
CLV
L3-23
(4FD)
V/f
Page
CLV
Sets the time the current must exceed the Stall Prevention level to activate
Stall Prevention.
297
299
Default: 1.0
Min.: 1.0
Max.: 1000.0
299
Default: 0 F
Min: 0
Max: 65000
300
Default: 50 ms
Min.: 0
Max.: 5000
300
Upper limit is dependent on parameters C6-01, Drive Duty Selection, and L8-38, Frequency Reduction Selection.
The setting range is 0 to 2 in OLV/PM control mode. The setting range is 0 and 1 in CLV or AOLV/PM control modes.
Default setting is dependent on parameter E1-01, Input voltage Setting.
Default setting is determined by parameter A1-02, Control Mode Setting.
Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
Default setting is dependent on parameter E5-01, Motor Code Selection.
Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but
set the value below 1040 Vdc (overvoltage protection level).
Name
Description
Values
Page
L4-01
(499)
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
300
L4-02
(49A)
Default: <1>
Min.: 0.0
Max.: 20.0
300
L4-03
(49B)
Default: 0.0 Hz
Min.: -400.0
Max.: 400.0
300
L4-04
(49C)
Default: <1>
Min.: 0.0
Max.: 20.0
300
L4-05
(49D)
Default: 0
Range: 0, 1
301
530
All Modes
All Modes
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
Values
All Modes
Default: 80%
Sets the percentage of the frequency reference that the drive should run with Min.: 0.0
Max.: 100.0
when the frequency reference is lost.
L4-06
(4C2)
Frequency Reference at
Reference Loss
L4-07
(470)
All Modes
Default: 0
Range: 0, 1
Page
301
301
Name
L5-01
(49E)
L5-02
(49F)
L5-04
(46C)
L5-05
(467)
Description
Values
All Modes
Default: 0
Sets the number of times the drive may attempt to restart after the following Min.: 0
Max.: 10
faults occur: GF, LF, oC, ov, PF, rH, rr, oL1, oL2, oL3, oL4, STo, Uv1.
All Modes
Page
302
Default: 0
Range: 0, 1
302
Default: 10.0 s
Min.: 0.5
Max.: 600.0
302
All Modes
302
Name
Description
Values
Page
All Modes
Torque Detection
Selection 1
L6-02
(4A2)
Torque Detection
Level 1
L6-03
(4A3)
Torque Detection
Time 1
All Modes
Default: 0.1 s
Min.: 0.0
Max.: 10.0
303
304
304
Parameter List
L6-01
(4A1)
0: Disabled
1: oL3 detection only active during speed agree, operation continues after
detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3
Default: 0
fault
4: oL3 detection always active during run, output shuts down on an oL3 fault Range: 0 to 8
5: UL3 detection only active during speed agree, operation continues after
detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3
fault
8: UL3 detection always active during run, output shuts down on an oL3 fault
Default: 150%
All Modes
Min.: 0
Sets the overtorque and undertorque detection level.
Max.: 300
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
531
Name
Description
Values
Page
All Modes
L6-04
(4A4)
Torque Detection
Selection 2
L6-05
(4A5)
Torque Detection
Level 2
L6-06
(4A6)
Torque Detection
Time 2
0: Disabled
1: oL4 detection only active during speed agree, operation continues after
detection
2: oL4 detection always active during run, operation continues after detection
3: oL4 detection only active during speed agree, output shuts down on an oL4
Default: 0
fault
4: oL4 detection always active during run, output shuts down on an oL4 fault Range: 0 to 8
5: UL4 detection only active during speed agree, operation continues after
detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4
fault
8: UL4 detection always active during run, output shuts down on an oL4 fault
All Modes
303
Default: 150%
Min.: 0
Max.: 300
304
Default: 0.1 s
Min.: 0.0
Max.: 10.0
304
All Modes
L6-08
(468)
Mechanical Weakening
Detection Operation
L6-09
(469)
Mechanical Weakening
Detection Speed Level
All Modes
Default: 110.0%
Sets the speed that triggers Mechanical Weakening Detection. When L6-08 is Min.: -110.0
set for an unsigned value, the absolute value is used if the setting is negative. Max.: 110.0
305
L6-10
(46A)
Mechanical Weakening
Detection Time
All Modes
Default: 0.1 s
Sets the time mechanical weakening has to be detected before an alarm or fault Min.: 0.0
Max.: 10.0
is triggered.
305
L6-11
(46B)
Mechanical Weakening
Detection Start Time
532
All Modes
Default: 0 h
Min.: 0
Max.: 65535
304
305
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
L7-01
(4A7)
L7-02
(4A8)
L7-03
(4A9)
Forward Regenerative
Torque Limit
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
Sets the torque limit value as a percentage of the motor rated torque. Four
individual quadrants can be set.
Output Torque
Positive Torque
L7-01
L7-04
Motor
r/min
Regeneration
REV
FWD
Regeneration
L7-04
(4AA)
Reverse Regenerative
Torque Limit
L7-06
(4AC)
L7-07
(4C9)
L7-02
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
L7-03
Negative Torque
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: 200%
Min.: 0
Max.: 300
Default: 200%
Min.: 0
Max.: 300
Default: 200%
Min.: 0
Max.: 300
Page
306
306
306
Default: 200%
Min.: 0
Max.: 300
306
Default: 200 ms
Min: 5
Max: 10000
306
CLV
0: Proportional control (changes to integral control at constant speed). Use this Default: 0
setting when acceleration to the desired speed should take precedence over the Range: 0, 1
torque limit.
1: Integral control. Set L7-07 to 1 if the torque limit should take precedence.
306
Name
Description
Values
Page
All Modes
L8-01
(4AD)
L8-02
(4AE)
Default: 0
Range: 0, 1
Default: <1>
All Modes
An overheat alarm occurs when heatsink temperature exceeds the L8-02 level. Min.: 50 C
Max.: 150 C
307
307
All Modes
L8-03
(4AF)
Overheat Pre-Alarm
Operation Selection
L8-05
(4B1)
Input Phase Loss Protection Selects the detection of input current phase loss, power supply voltage
imbalance, or main circuit electrolytic capacitor deterioration.
Selection
0: Disabled
1: Enabled
L8-07
(4B3)
307
Default: 1
Range: 0, 1
308
Default: 1
Range: 0 to 2
308
All Modes
L8-09
(4B5)
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
All Modes
0: Disabled
1: Enabled
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter List
All Modes
B
<1>
Default:
Range: 0, 1
309
533
Name
Description
Values
Page
All Modes
L8-10
(4B6)
Default: 0
0: During run only. Fan operates only during run for L8-11 seconds after stop. Range: 0, 1
1: Fan always on. Cooling fan operates whenever the drive is powered up.
309
L8-11
(4B7)
Default: 60 s
Sets a delay time to shut off the cooling fan after the Run command is removed Min.: 0
Max.: 300
when L8-10 = 0.
309
L8-12
(4B8)
Ambient Temperature
Setting
L8-15
(4BB)
oL2 Characteristics
Selection at Low Speeds
L8-18
(4BE)
L8-19
(4BF)
All Modes
Default: 40 C
Min.: -10
Max.: 50
309
Default: 1
Range: 0, 1
309
Default: 0
Range: 0, 1
310
All Modes
Default: 0.8
Frequency Reduction Rate
0.1
during Overheat Pre-Alarm Specifies the frequency reference reduction gain at overheat pre-alarm when Min.:
Max.: 0.9
L8-03 = 4.
308
All Modes
Enter the ambient temperature. This value adjusts the oL2 detection level.
All Modes
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Disabled
1: Enabled
V/f
V/f w PG
OLV
CLV
L8-27
(4DD)
Default: 300.0%
OLV/PM
AOLV/PM
CLV/PM
Overcurrent Detection Gain Sets the gain for overcurrent detection as a percentage of the motor rated
Min.: 0.0
current. Overcurrent is detected using the lower value between the overcurrent Max.: 300.0
level of the drive or the value set to L8-27.
L8-29
(4DF)
Current Unbalance
Detection (LF2)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
310
CLV
Default: 1
Range: 0, 1
0: Disabled
1: Enabled
310
All Modes
L8-32
(4E2)
Determines drive response when a fault occurs with the internal cooling fan.
Main Contactor and Cooling 0: Ramp to stop
Default: 1
Fan Power Supply Failure 1: Coast to stop
Range: 0 to 4
Selection
2: Fast stop (Decelerate to stop using the deceleration time set to C1-09)
3: Alarm only (FAn will flash)
4: Continue operation at reduced speed as set to L8-19.
All Modes
L8-35
(4EC)
L8-38
(4EF)
Installation Method
Selection
Carrier Frequency
Reduction
0: IP00/Open-Chassis enclosure
1: Side-by-Side mounting
2: IP20/NEMA Type 1 enclosure
3: Finless model drive or external heatsink installation
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
L8-40
(4F1)
Carrier Frequency
Reduction Off Delay Time
L8-41
(4F2)
V/f w PG
OLV
<1> <2>
<3>
Default: <4>
Range: 0 to 2
AOLV/PM
311
CLV
Default: <5>
Sets the time that the drive continues running with reduced carrier frequency Min.: 0.00 s
after the carrier reduction condition is gone. Setting 0.00 s disables the carrier Max.: 2.00 s
frequency reduction time.
OLV/PM
311
Range: 0 to 3
CLV
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the entire speed range
V/f
Default:
310
CLV/PM
312
All Modes
534
Default: 0
0: Disabled
1: Enabled. An alarm is triggered at output currents above 150% of drive rated Range: 0, 1
current.
312
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
Values
Page
All Modes
L8-55
(45F)
312
All Modes
L8-78
(2CC)
Default: 1
Range: 0, 1
312
Parameter List
<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is determined by the drive model:
Setting 2: Model code CIMR-Ao2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242
Setting 0: Model code CIMR-Ao2A0250 to 2A0415 and 4A0208 to 4A1200
<4> Default setting is dependent on parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
535
Name
Hunting Prevention
Selection
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
n1-02
(581)
n1-03
(582)
n1-05
(530)
Default: 1
Range: 0, 1
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
313
CLV
Default: 1.00
Min.: 0.00
If the motor vibrates while lightly loaded, increase the gain by 0.1 until
vibration ceases. If the motor stalls, decrease the gain by 0.1 until the stalling Max.: 2.50
ceases.
OLV/PM
Page
CLV
0: Disabled
1: Enabled
V/f
Values
CLV
313
Default: <1>
Min.: 0 ms
Max.: 500 ms
313
Default: 0.00
Min.: 0.00
Sets the gain used for Hunting Prevention. If set to 0, the gain set to n1-02 is Max.: 2.50
used for operation in reverse.
313
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Name
n2-01
(584)
n2-02
(585)
n2-03
(586)
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
Default: 1.00
Sets the internal speed feedback detection control gain in the automatic
Min.: 0.00
frequency regulator (AFR).
Max.: 10.00
If hunting occurs, increase the set value. If response is low, decrease the set
value.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the time constant used for speed feedback detection control (AFR).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Page
Default: 50 ms
Min.: 0
Max.: 2000
314
314
CLV
Default: 750 ms
Min.: 0
Sets the AFR time constant to be used during Speed Search and during regen. Max.: 2000
314
Name
n3-01
(588)
High-Slip Braking
Deceleration Frequency
Width
n3-02
(589)
536
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Page
CLV
Default: 5%
Min.: 1
Max.: 20
314
Default: <1>
Min.: 100%
Sets the current limit during HSB as a percentage of the motor rated current. Max.: 200%
315
Sets the output frequency reduction step width for when the drive stops the
motor using HSB. Set as a percentage of the maximum output frequency.
Increase this setting if overvoltage occurs during HSB.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
Default: 1.0 s
Sets the time the drive will run with minimum frequency (E1-09) at the end Min.: 0.0
of deceleration.
Max.: 10.0
If this time is set too low, the machine inertia can cause the motor to rotate
slightly after HSB.
n3-03
(58A)
n3-04
(58B)
Default: 40 s
High-Slip Braking Overload
Sets the time required for an HSB overload fault (oL7) to occur when the drive Min.: 30
Time
output frequency does not change during an HSB stop. This parameter does Max.: 1200
not typically require adjustment.
n3-13
(531)
Overexcitation Deceleration
OLV/PM
AOLV/PM
CLV/PM
Gain
Sets the gain applied to the V/f pattern during Overexcitation Deceleration
(L3-04 = 4).
n3-14
(532)
V/f
n3-21
(579)
n3-23
(57B)
High-Slip Suppression
Current Level
Overexcitation Operation
Selection
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
315
Default: 1.10
Min.: 1.00
Max.: 1.40
316
Default: 0
Range: 0, 1
316
Default: 100%
Min.: 0
Max.: 150
316
Default: 0
Range: 0 to 2
316
CLV
CLV
Sets output current level at which the drive will start reducing the
overexcitation gain in order to prevent a too high motor slip during
Overexcitation Deceleration. Set as a percentage of the drive rated current.
OLV/PM
315
CLV
0: Disabled
1: Enabled
OLV/PM
Page
CLV
<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and L8-38, Frequency Reduction Selection.
n5-01
(5B0)
n5-02
(5B1)
n5-03
(5B2)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
Default: 0
Range: 0, 1
Default: 1.00
Min.: 0.00
Sets the ratio between motor and load inertia. Lower this setting if overshoot Max.: 100.00
occurs at the end of acceleration.
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
317
CLV
OLV/PM
Page
CLV
0: Disabled
1: Enabled
OLV/PM
Values
317
CLV
318
Parameter List
No.
(Addr.
Hex)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
537
n6-01
(570)
n6-05
(5C7)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
Page
CLV
Default: 0
Range: 0 to 2
319
Default: 1.00
Min.: 0.10
Decrease this setting for motors with a relatively large rotor time constant. If Max.: 5.00
overload occurs, increase this setting slowly in increments of 0.10.
319
0: Disabled
1: Line-to-line resistance tuning
2: Voltage correction. Setting not possible when Energy Saving is enabled
(b8-01).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Name
Description
V/f
n8-01
(540)
n8-02
(541)
n8-35
(562)
n8-45
(538)
n8-47
(53A)
Pull-In Current
Compensation Time
Constant
n8-49
(53C)
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
538
Acceleration/Deceleration
Pull-In Current
CLV
OLV
Default: 1
Range: 0 to 2
319
Default: 0.80
Min.: 0.00
Max.: 10.00
320
CLV
Default: 5.0 s
Sets the time constant to make the pull-in current reference and actual current Min.: 0.0
value agree. Decrease the value if the motor begins to oscillate, and increase Max.: 100.0
the value if it takes too long for the current reference to equal the output current.
OLV/PM
AOLV/PM
V/f w PG
CLV/PM
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f w PG
OLV
CLV/PM
320
CLV
Default: 50%
Min.: 0
Sets the d-Axis current reference during acceleration/deceleration as a
percentage of the motor rated current. Set to a high value when more starting Max.: 200
torque is needed.
AOLV/PM
320
CLV
Default: <1>
Min.: -200.0%
Sets the d-Axis current reference when running a high load at constant speed. Max.: 0.0%
Set as a percentage of the motor rated current.
OLV/PM
320
CLV
Default: 30%
Defines the d-Axis current reference during no-load operation at a constant Min.: 20
speed. Set as a percentage of the motor rated current. Increase this setting if Max.: 200
hunting occurs while running at constant speed.
OLV/PM
319
CLV
0: Pull-in
1: High frequency injection
2: Pulse injection
OLV/PM
319
CLV
Default: 80%
Min.: 0
Sets the current during initial polar attraction as a percentage of the motor rated Max.: 150
current. Enter a high value when attempting to increase starting torque.
OLV/PM
Page
CLV
CLV/PM
V/f
V/f
n8-51
(53E)
AOLV/PM
OLV/PM
V/f
Pull-In Current
OLV
Default: 50%
Sets the current used for initial rotor position estimation as a percentage of the Min.: 0
motor rated current (E5-03). If the motor nameplate lists an Si value, that Max.: 100
value should be entered here.
OLV/PM
V/f
n8-48
(53B)
V/f w PG
Values
321
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
V/f
n8-54
(56D)
n8-55
(56E)
n8-57
(574)
Load Inertia
n8-65
(65C)
<3>
n8-84
(2D3)
<3>
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: 0
Min.: 0
Max.: 3
CLV
OLV
OLV/PM
AOLV/PM
CLV/PM
Min.: 0.0
Max.: 230.0 <2>
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
322
CLV
Default: 1.00
Sets the proportional gain for PLL control of an extended observer. There is Min.: 0.00
normally no need to change this parameter from the default value.
Max.: 20.00
Note: This parameter is not available in models CIMR-Ao4A0930 and
4A1200.
OLV/PM
V/f
322
CLV
Default: 1.50
Min.: 0.00
Sets the gain used for internal speed feedback detection during ov suppression. Max.: 10.00
OLV/PM
321
Default: 200.0 V
<2>
Prevents output voltage saturation. Should be set just below the voltage
provided by the input power supply.
V/f w PG
321
CLV
Default: 0
0: Disabled. Disable when using an SPM motor.
Range: 0, 1
1: Enabled. Use this setting to enhance the speed control range when using an
IPM motor.
V/f
321
CLV
Page
CLV
Default: 1.00 s
Voltage Error Compensation
Min.: 0.00
Adjusts
the
value
when
hunting
occurs
at
low
speed.
If
hunting
occurs
with
Time Constant
sudden load changes, increase n8-54 in increments of 0.1. Reduce this setting Max.: 10.00
if oscillation occurs at start.
n8-62
(57D)
n8-69
(65D)
V/f w PG
Values
322
CLV
Sets the current to determine polarity for the initial polarity calculation as a
percentage of the motor rated current.
100% = Motor rated current
Default: 100%
Min.: 0
Max.: 150
322
Parameter List
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
539
Name
Description
All Modes
Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: Uo-oo.
Values
Page
Default: 106
(Monitor U1-06)
Range: 104 to 809
323
Default: 1
Range: 1 to 5
323
All Modes
o1-02
(501)
o1-03
(502)
o1-04
(503)
o1-10
(520)
o1-11
(521)
Sets the units the drive should use to display the frequency reference and motor
speed monitors.
Default: <1>
0: 0.01 Hz
Range: 0 to 3
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04,
or E5-04)
3: User-selected units (set by o1-10 and o1-11)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
323
CLV
0: Hz
1: r/min
All Modes
Default: <1>
Range: 0, 1
324
Default: <2>
Range: 1 to 60000
324
324
Name
o2-01
(505)
o2-02
(506)
Description
Values
Page
All Modes
Default: 1
0: Disabled
Range: 0, 1
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
All Modes
324
Default: 1
Range: 0, 1
325
Default: 0
Range: 0 to 2
325
All Modes
o2-03
(507)
o2-04
(508)
540
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
Default:
All Modes
Determined by
Enter the drive model. Setting required only if installing a new control board. drive capacity
325
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
Values
Page
All Modes
o2-05
(509)
Frequency Reference
Setting Method Selection
o2-06
(50A)
o2-07
(527)
Default: 0
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using Range: 0, 1
the up and down arrow keys only.
All Modes
325
Default: 1
Range: 0, 1
326
Default: 0
Range: 0, 1
326
All Modes
o2-09
(50D)
0: Forward
1: Reverse
This parameter requires assigning drive operation to the digital operator.
Factory use.
Values
Page
Name
Description
All Modes
o3-01
(515)
o3-02
(516)
0: No action
Default: 0
1: Read parameters from the drive, saving them onto the digital operator.
Range: 0 to 3
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data saved
on the operator.
All Modes
Default: 0
Range: 0, 1
326
327
Description
Values
o4-01
(50B)
Default: 0 h
Cumulative Operation Time All Modes
Min.: 0
Setting
Sets the value for the cumulative operation time of the drive in units of 10 h. Max.: 9999
o4-02
(50C)
o4-03
(50E)
o4-05
(51D)
Capacitor Maintenance
Setting
o4-07
(523)
o4-09
(525)
Page
327
All Modes
327
327
Default: 0%
Min.: 0
Max.: 150
327
Default: 0%
Min.: 0
Max.: 150
328
All Modes
Default: 0%
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 for IGBT Min.: 0
Max.: 150
replacement times.
328
All Modes
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to
check when the capacitors may need to be replaced.
All Modes
Sets the value of the Maintenance Monitor for the soft charge bypass relay.
See U4-06 to check when the bypass relay may need to be replaced.
All Modes
o4-11
(510)
U2, U3 Initialization
0: U2-oo and U3-oo monitor data is not reset when the drive is initialized Default: 0
(A1-03).
Range: 0, 1
1: U2-oo and U3-oo monitor data is reset when the drive is initialized
(A1-03).
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter List
No.
(Addr.
Hex)
328
541
Name
Description
Values
Page
All Modes
o4-12
(512)
Default: 0
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized
Range: 0, 1
(A1-03).
1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03).
o4-13
(528)
Number of Run Commands 0: Number of Run commands counter is not reset when the drive is initialized Default: 0
(A1-03).
Counter Initialization
Range: 0, 1
1: Number of Run commands counter is reset when the drive is initialized
(A1-03).
328
All Modes
542
328
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Description
All Modes
DriveWorksEZ Parameters
Values
Page
329
Values
Page
Default: 0
Min.: 0
Max.: FFFF
329
Parameter List
No.
(Addr.
Name
Description
Hex)
r1-01 to DriveWorksEZ Connection
All Modes
r1-40
Parameters
1
to
20
(upper/
DriveWorksEZ
Connection Parameters 1 to 20 (upper/lower)
(1840 to lower)
1867)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
543
T1-01
(701)
<1>
T1-02
(702)
Name
Auto-Tuning Mode
Selection
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
Default: 1
Range: 1, 2
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
T1-05
(705)
T1-06
(706)
T1-07
(707)
T1-08
(708)
544
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the rated frequency of the motor as specified on the motor nameplate.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the rated speed of the motor as specified on the motor nameplate.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Default: <3>
Min.: 0.00 kW
Max.: 650.00 kW
Min: 0.0
Max: 255.0 <4>
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
142
Default: <3>
Min.: 10% of drive
rated current
Max.: 200% of
drive rated current
142
Default: 60.0 Hz
Min.: 0.0
Max.: 400.0
142
Default: 4
Min.: 2
Max.: 48
142
142
CLV
142
Default: 200.0 V
<4>
T1-04
(704)
T1-09
(709)
V/f
141
CLV
141
CLV
0: Rotational Auto-Tuning
1: Stationary Auto-Tuning 1
Default: 0
2: Stationary Auto-Tuning for Line-to-Line Resistance
0 to 4; 8, 9
3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and Range:
<2>
Speed Estimation Speed Search)
4: Stationary Auto-Tuning 2
8: Inertia Tuning (perform Rotational Auto-Tuning prior to Inertia Tuning)
9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain
Auto-Tuning)
OLV/PM
Page
CLV
Values
142
CLV
Default:
Sets the no-load current for the motor. After setting the motor capacity to T1-02 Min.: 0 A
and the motor rated current to T1-04, this parameter will automatically display Max.: T1-04
the no-load current for a standard 4-pole Yaskawa motor. Enter the no-load
current as indicated on the motor test report.
143
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
T1-11
(70B)
<1>
<2>
<3>
<4>
<5>
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
Page
CLV
Values
Default:
Min.: 0.00 Hz
Max.: 20.00 Hz
143
CLV
OLV/PM
AOLV/PM
CLV/PM
Default: 14 W <5>
Sets the iron loss for determining the Energy Saving coefficient.
Min.: 0
The value is set to E2-10 (motor iron loss) set when the power is cycled. If Max.: 65535
T1-02 is changed, a default value appropriate for the motor capacity that was
entered will appear.
143
The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
Default setting is determined by parameter A1-02, Control Method Setting.
Default setting is dependent on parameter o2-04, Drive Model Selection.
Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
Default setting value differs depending on the motor code value and motor parameter settings.
T2-01
(750)
T2-02
(751)
T2-03
(752)
T2-04
(730)
Name
PM Motor Auto-Tuning
Mode Selection
PM Motor Type
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
Default: 1
Range: 0, 1
144
CLV
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
144
CLV
0: IPM motor
1: SPM motor. Parameter T2-17 will not be displayed with this setting.
OLV/PM
143
CLV
<3>
Enter the motor code when using a Yaskawa PM motor. After entering the Default:
Min:
0000
motor code, the drive automatically sets parameters T2-03 through T2-14.
When using a motor without a supported motor code or a non-Yaskawa motor, Max: FFFF
set FFFF and adjust the other T2 parameters according to the motor nameplate
or the motor test report.
OLV/PM
Page
Parameter List
No.
(Addr.
Hex)
<4>
Default:
Min.: 0.00 kW
Max.: 650.00 kW
144
545
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
T2-06
(733)
T2-07
(753)
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Page
Default: 200.0 V
<5>
Values
Min.: 0.0
Max.: 255.0 <5>
144
Default: <4>
Min.: 10% of drive
rated current
Max.: 200% of
drive rated current
144
Default: 87.5 Hz
Min.: 0.0
Max.: 400.0
145
CLV
T2-08
(734)
Default: 6
Min.: 2
Enter the number of motor poles for the PM motor as indicated on the motor Max.: 48
nameplate.
145
T2-09
(731)
Default: 1750
r/min
Min.: 0
Enter the base speed for the PM motor as indicated on the motor nameplate. Max.: 24000
145
T2-10
(754)
T2-11
(735)
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
Enter the rotor resistance for the PM motor as indicated on the motor
nameplate.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Enter the d-axis inductance for the PM motor as indicated on the motor
nameplate.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Default: <6>
Min.: 0.000
Max.: 65.000
145
Default: <6>
Min.: 0.00 mH
Max.: 600.00 mH
145
Default: <6>
Min.: 0.00 mH
Max.: 600.00 mH
145
T2-12
(736)
T2-13
(755)
T2-14
(737)
Default: <6>
Min.: 0.1
Max.: 2000.0
146
T2-15
(756)
Default: 30%
Pull-In Current Level for PM OLV/PM
AOLV/PM
CLV/PM
Min.: 0
Motor Tuning
Sets the amount of pull-in current to use for Auto-Tuning as a percentage of Max.: 120
the motor rated current. Increase this setting for high inertia loads.
146
T2-16
(738)
T2-17
(757)
Enter the q-axis inductance for the PM motor as indicated on the motor
nameplate.
V/f
546
OLV
CLV
Default: 1
0: mV/(r/min). E5-09 will automatically be set to 0.0, and E5-24 will be used. Range: 0, 1
1: mV/(rad/sec). E5-24 will automatically be set to 0.0, and E5-09 will be used.
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
V/f
<1>
<2>
<3>
<4>
<5>
V/f w PG
OLV/PM
V/f w PG
OLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
145
CLV
Sets the offset between encoder offset and the rotor magnetic axis.
146
146
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Values
CLV
Default: 3.0 Hz
Min.: 0.1
Sets the frequency of the test signal used during Inertia Tuning and ASR Gain Max.: 20.0
Auto-Tuning. Reduce this value if the inertia is large or if a fault occurs.
T3-02
(761)
T3-03
(762)
Motor Inertia
<1>
<1>
<1>
T3-04
(763)
<1>
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
AOLV/PM
CLV/PM
146
CLV
CLV
Sets the motor inertia. Default setting is the inertia of a Yaskawa motor.
OLV/PM
Page
147
147
CLV
Default: 10.0 Hz
Min.: 0.1
Sets the response frequency of the mechanical system connected to the motor. Max.: 50.0
Oscillation may result if set too high.
147
Parameter List
<1> Displayed only when performing Inertia Tuning or ASR Gain Auto-Tuning (T1-01 = 8 or T2-01 = 9).
<2> Default setting is dependent on parameter E5-01, Motor Code Selection.
<3> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
547
B.15 U: Monitors
B.15 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
Name
U1-01
(40)
Frequency Reference
U1-02
(41)
Output Frequency
Analog Output
Level
Description
All Modes
Unit
10 V: Max frequency
0.01 Hz
10 V: Max frequency
0.01 Hz
10 V: Drive rated
current
<1> <2>
No signal output
available
All Modes
U1-03
(42)
Output Current
U1-04
(43)
Control Method
U1-05
(44)
Motor Speed
U1-06
(45)
U1-07
(46)
DC Bus Voltage
U1-08
(47)
Output Power
U1-09
(48)
Torque Reference
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
10 V: Max frequency
0.01 Hz
Displays the motor speed feedback. Display units are determined by o1-03.
All Modes
10 V: 200 Vrms
10 V: 400 V
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
<3>
<3>
0.1 Vac
1 Vdc
<4>
10 V: Motor rated
torque
0.1%
No signal output
available
All Modes
U1 - 10= 00000000
1 Digital input 1
1
U1-10
(49)
1
Input Terminal Status
1
1
1
1
1
548
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.15 U: Monitors
No.
(Addr.
Hex)
Name
Analog Output
Level
Description
Unit
All Modes
U1 - 11= 00000000
1 Multi-Function
Digital Output
U1-11
(4A)
(terminal M1-M2)
1 Multi-Function
Digital Output
1
0
1
(terminal M3-M4)
Multi-Function
Digital Output
(terminal M5-M6)
Not Used
Fault Relay
(terminal MA-MC closed
MA-MC open)
No signal output
available
No signal output
available
All Modes
U1 - 12= 00000000
U1-12
(4B)
Drive Status
1 During run
1 During zero-speed
1 During REV
fault reset
1 During
signal input
1 During speed agree
1 Drive ready
alarm
1 During
detection
1 During fault detection
U1-13
(4E)
U1-14
(4F)
U1-15
(50)
U1-16
(53)
All Modes
10 V: 100%
0.1%
10 V: 100%
0.1%
10 V: 100%
0.1%
All Modes
Displays output frequency with ramp time and S-curves. Units determined 10 V: Max frequency
by o1-03.
0.01 Hz
All Modes
U1-17
(58)
U1-18
(61)
Displays the reference value input from the DI-A3 option card.
No signal output
Display will appear in hexadecimal as determined by the digital card input available
selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bit
All Modes
No signal output
Displays the parameter number that caused the oPEoo or Err (EEPROM available
write error) error.
Parameter List
All Modes
U1 - 19= 00000000
U1-19
(66)
MEMOBUS/Modbus
Error Code
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
1 CRC Error
1 Data Length Error
0 Not Used
1 Parity Error
1 Overrun Error
1 Framing Error
1 Timed Out
0 Not Used
No signal output
available
549
B.15 U: Monitors
No.
(Addr.
Hex)
Name
Description
Analog Output
Level
Unit
U1-21
(77)
10 V: 100%
0.1%
U1-22
(72A)
10 V: 100%
0.1%
U1-23
(72B)
10 V: 100%
0.1%
U1-24
(7D)
Determined by H6-02
1 Hz
U1-25
(4D)
U1-26
(5B)
All Modes
FLASH ID
All Modes
ROM ID
No signal output
available
No signal output
available
No signal output
available
All Modes
U1-29
(7AA)
PWM ID
Note: This parameter is only available in models CIMR-Ao4A0930
and 4A1200.
<1> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND/HD selection in parameter C6-01. This value has two decimal places (0.01 kW) if the drive is set for a
maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 kW) if the maximum applicable motor capacity is
higher than 11 kW.
Name
Description
U2-01
(80)
Current Fault
U2-02
(81)
Previous Fault
U2-03
(82)
Frequency Reference at
Previous Fault
U2-04
(83)
Output Frequency at
Previous Fault
U2-05
(84)
U2-06
(85)
U2-07
(86)
Output Voltage at
Previous Fault
U2-08
(87)
DC Bus Voltage at
Previous Fault
U2-09
(88)
550
All Modes
All Modes
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
All Modes
Analog Output
Level
Unit
No signal output
available
No signal output
available
No signal output
available
0.01 Hz
No signal output
available
0.01 Hz
No signal output
available
<1> <2>
No signal output
available
0.01 Hz
No signal output
available
0.1 Vac
No signal output
available
1 Vdc
No signal output
available
0.1 kW
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.15 U: Monitors
No.
(Addr.
Hex)
Name
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
U2-10
(89)
Torque Reference at
Previous Fault
U2-11
(8A)
U2-12
(8B)
Analog Output
Level
Unit
No signal output
available
0.1%
No signal output
available
No signal output
available
U2-13
(8C)
U2-14
(8D)
Cumulative Operation
Time at Previous Fault
U2-15
(7E0)
Displays the speed reference for the soft starter at the previous fault.
U2-16
(7E1)
U2-17
(7E2)
U2-19
(7EC)
Rotor Deviation at
Previous Fault
U2-20
(8E)
Heatsink Temperature at
Previous Fault
U2-27
(7FA)
Motor Temperature at
Previous Fault (NTC)
All Modes
No signal output
available
1h
No signal output
available
0.01 Hz
No signal output
available
0.10%
No signal output
available
0.10%
No signal output
Displays the degree of rotor deviation when the most recent fault occurred available
(same status will appear as shown in U6-10).
0.1 deg
All Modes
All Modes
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Displays the q-axis current for the motor at the previous fault.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Displays the d-axis current for the motor at the previous fault.
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV
CLV/PM
All Modes
Displays the temperature of the heatsink when the most recent fault
occurred.
No signal output
available
1 C
All Modes
Displays the temperature of the motor when the most recent fault occurred. No signal output
available
Note: This parameter is only available in models CIMR-Ao4A0930
and 4A1200.
1 C
<1> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
U3-05 to
U3-10
(804 to
809)
Name
Description
Analog Output
Level
Unit
Parameter List
No.
(Addr.
Hex)
U3-01 to
U3-04
(90 to 93
(800 to
803))
All Modes
No signal output
available
All Modes
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
551
B.15 U: Monitors
No.
(Addr.
Hex)
U3-11 to
U3-14
(94 to 97
(80A to
80D))
U3-15 to
U3-20
(80E to
813)
Name
Description
Analog Output
Level
Unit
All Modes
Cumulative Operation
Time at 1st to 4th Most
Recent Fault
Displays the cumulative operation time when the first to the fourth most
recent faults occurred.
Cumulative Operation
Time at 5th to 10th Most
Recent Fault
Displays the cumulative operation time when the fifth to the tenth most
recent faults occurred.
All Modes
No signal output
available
1h
No signal output
available
1h
Name
Description
Analog Output
Level
Unit
All Modes
Displays the cumulative operation time of the drive. The value for the
cumulative operation time counter can be reset in parameter o4-01. Use No signal output
parameter o4-02 to determine if the operation time should start as soon as available
the power is switched on or only while the Run command is present. The
maximum number displayed is 99999, after which the value is reset to 0.
U4-01
(4C)
Cumulative Operation
Time
U4-02
(75)
Number of Run
Commands
No signal output
Displays the number of times the Run command is entered. Reset the
number of Run commands using parameter o4-13. This value will reset to available
0 and start counting again after reaching 65535.
U4-03
(67)
Displays the cumulative operation time of the cooling fan. The default value No signal output
for the fan operation time is reset in parameter o4-03. This value will reset available
to 0 and start counting again after reaching 99999.
U4-04
(7E)
Cooling Fan Maintenance Displays main cooling fan usage time as a percentage of its expected
performance life. Parameter o4-03 can be used to reset this monitor.
U4-05
(7C)
Capacitor Maintenance
U4-06
(7D6)
Soft Charge Bypass Relay Displays the soft charge bypass relay maintenance time as a percentage of No signal output
Maintenance
its estimated performance life. Parameter o4-07 can be used to reset this available
monitor.
U4-07
(7D7)
IGBT Maintenance
U4-08
(68)
Heatsink Temperature
U4-09
(5E)
LED Check
U4-10
(5C)
U4-11
(5D)
U4-13
(7CF)
1h
All Modes
1 Time
All Modes
All Modes
1h
No signal output
available
1%
No signal output
Displays main circuit capacitor usage time as a percentage of their expected available
performance life. Parameter o4-05 can be used to reset this monitor.
1%
All Modes
All Modes
552
All Modes
Lights all segments of the LED to verify that the display is working
properly.
All Modes
No signal output
available
1%
10 V: 100 C
1 C
No signal output
available
No signal output
available
1 kWh
Monitors the drive output power. The value is shown as a 9-digit number
displayed across two monitor parameters, U4-10 and U4-11.
Example:
No signal output
12345678.9 kWh is displayed as:
available
U4-10: 678.9 kWh
U4-11: 12345 MWh
All Modes
1%
No signal output
available
1 MWh
0.01 A
<1> <2>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.15 U: Monitors
No.
(Addr.
Hex)
Name
Description
All Modes
U4-14
(7D0)
U4-16
(7D8)
Displays the output frequency when the current value shown in U4-13
occurred.
Analog Output
Level
No signal output
available
Unit
0.01 Hz
All Modes
10 V: 100%
0.1%
All Modes
U4-18
(7DA)
Frequency Reference
Source Selection
U4-19
(7DB)
U4-20
(7DC)
No signal output
available
No signal output
available
0.01%
Option Frequency
Reference
No signal output
available
All Modes
U4-21
(7DD)
U4-22
(7DE)
MEMOBUS/Modbus
Communications
Reference
No signal output
Displays the drive control data set by MEMOBUS/Modbus
available
communications register no. 0001H as a four-digit hexadecimal number.
U4-23
(7DF)
Communication Option
Card Reference
No signal output
Displays drive control data set by an option card as a four-digit hexadecimal available
number.
U4-32
(7FB)
All Modes
Parameter List
All Modes
All Modes
B
1 C
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
553
B.15 U: Monitors
No.
(Addr.
Hex)
Name
Description
Analog Output
Level
Unit
All Modes
U4-37
(1044)
oH Alarm Location
Monitor
U4-38
(1045)
Displays the module where the FAn alarm occurred as a binary number.
U4-39
(1046)
Displays the module where the voF alarm occurred as a binary number.
No signal output
available
No signal output
available
No signal output
available
All Modes
<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<2> The unit is 1 A in models CIMR-Ao4A0930 and 4A1200.
Name
U5-01
(57)
PID Feedback
U5-02
(63)
PID Input
U5-03
(64)
PID Output
U5-04
(65)
PID Setpoint
Description
All Modes
Analog Output
Level
Unit
10 V: 100%
0.01%
10 V: 100%
0.01%
10 V: 100%
0.01%
10 V: 100%
0.01%
U5-05
(7D2)
PID Differential Feedback Displays the 2nd PID feedback value if differential feedback is used (H3- 10 V: 100%
oo = 16).
0.01%
U5-06
(7D3)
Displays the amount of PID input (deviation between PID setpoint and
feedback).
All Modes
All Modes
V/f
U5-21
(872)
<1>
U5-22
(873)
<1>
V/f w PG
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
V/f
Automatically Calculated
Energy Saving Coefficient Displays the energy saving coefficient Ki value.
Ki Value
Note: This parameter is not available in models CIMR-Ao4A0930
and 4A1200.
V/f
V/f w PG
OLV
OLV/PM
V/f
AOLV/PM
CLV/PM
0.01%
No signal output
available
0.01
No signal output
available
0.01
CLV
Automatically Calculated
Energy Saving Coefficient Displays the energy saving coefficient Kt value.
Kt Value
Note: This parameter is not available in models CIMR-Ao4A0930
and 4A1200.
554
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
B.15 U: Monitors
Description
All Modes
Analog Output
Level
Unit
U6-01
(51)
10 V: Motor secondary
rated current
0.1%
U6-02
(52)
0.1%
U6-03
(54)
U6-04
(55)
ASR Input
U6-05
(59)
U6-06
(5A)
V/f
U6-07
(5F)
ASR Output
V/f w PG
OLV
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
CLV
Displays the input and output values when using ASR control.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
10 V: Max frequency
10 V: Motor secondary
rated current
0.01%
CLV
0.1 Vac
0.1 Vac
0.1%
0.1%
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Displays the output value for current control relative to motor secondary
current (q-Axis).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
U6-08
(60)
U6-09
(7C0)
Advance Phase
Compensation ()
U6-10
(7C1)
U6-13
(7CA)
U6-14
(7CB)
U6-18
(7CD)
U6-19
(7E5)
U6-20
(7D4)
U6-21
(7D5)
Offset Frequency
U6-22
(62)
Displays the output value for current control relative to motor secondary
current (d-Axis).
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
10 V: 180 deg
-10 V: -180 deg
0.1 deg
10 V: 180 deg
Displays the amount of deviation between the actual d-Axis / q-Axis and -10 V: -180 deg
the -Axis / -Axis used for motor control.
0.1 deg
V/f w PG
AOLV/PM
OLV
CLV
CLV/PM
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
All Modes
All Modes
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
10 V: 180 deg
-10 V: -180 deg
0.1 deg
10 V: 180 deg
-10 V: -180 deg
0.1 deg
10 V: 65536
1 pulse
10 V: 65536
1 pulse
10 V: Max frequency
0.1%
0.1%
CLV
Displays how far the rotor has moved from its last position in PG pulses
(multiplied by 4).
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
555
Parameter List
No.
(Addr.
Hex)
B.15 U: Monitors
No.
(Addr.
Hex)
Name
U6-25
(6B)
U6-26
(6C)
Description
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Analog Output
Level
Unit
10 V: Motor secondary
rated current
0.01%
10 V: Motor secondary
rated current
0.01%
<1> Values shown are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the values by 2.875 for 600 V class drives.
556
Name
Description
Analog Output
Level
Unit
All Modes
DriveWorksEZ Custom
Monitor 1 to 10
DriveWorksEZ Version
Control Monitor 1 to 3
All Modes
10 V: 100%
No signal output
available
0.01%
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
b2-01
b2-04
b3-01
b3-02
b3-14
b5-15
b6-01
Setting Range
Resolution
0.0 to 10.0
OLV (2)
CLV (3)
0.1 Hz
0.5
0.5
0.5
0.5
0.00 to 10.00
0.01 s
0.50
0.50
0.50
0.50
0 to 1
0 to 200
1%
120
100
0 to 1
0.0 to
400.0 <1>
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 to
400.0 <1>
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 to
400.0 <1>
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 to 10.0
0.1
0.7
1.0
0.00 to 10.00
0.01 s
0.50 <2>
0.01 <2>
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.00 to 10.00
0.01 s
0.20
0.20
0.20
0.20
b8-01
b8-02
b8-03
C1-11
C2-01
C3-01
0.0 to 2.5
0.1
0.0
1.0
1.0
C3-02
0 to 10000
1 ms
2000
200
C4-01
0.00 to 2.50
0.01
1.00
1.00
1.00
C4-02
0 to 10000
1 ms
200 <3>
200 <3>
20
C5-01
0.00 to 300.00
0.01
0.20
20.00
C5-02
0.000 to 10.000
0.001 s
0.200
0.500
C5-03
0.00 to 300.00
0.01
0.02
20.00
C5-04
0.000 to 10.000
0.001 s
0.050
0.500
C5-06
0.000 to 0.500
0.001 s
0.004
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
7 <4>
7 <4>
7 <4>
0.0 to
400.0 <1>
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
400.0 <1>
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
1.0 Hz
C5-07
C6-02
d3-01
Jump Frequency 1
0 to 1
0.0 to
400.0 <1>
1 to F
d3-02
Jump Frequency 2
0.0 to
d3-03
Jump Frequency 3
d3-04
0.1
1.0 Hz
1.0 Hz
1.0 Hz
d5-02
0 to 1000
1 ms
E1-04
40.0 to 400.0
0.1 Hz
60.0
60.0
60.0
60.0
E1-05
Maximum Voltage
0.1 V
575 <7>
575 <7>
575
575
E1-06
Base Frequency
0.0 to 400.0
0.1 Hz
60.0
60.0
60.0
60.0
E1-07
0.0 to 400.0
0.1 Hz
3.0
3.0
3.0
3.0
0.1 V
15.0 <7>
15.0 <7>
15.0
15.0
0.1 Hz
1.5
1.5
0.5
0.0
0.1 V
9.0
9.0
2.0
0.0
0 to 60000
1 ppr
600
600
600
600
0 to 1
0.0 to 2.0
0.1 s
1.0
0.0
0.0 to
255.0 <6>
E1-08
E1-09
E1-10
F1-01
F1-05
PG 1 Rotation Selection
F1-09
L1-01
0 to 4
L3-20
0.00 to 5.00
0.01
1.00
1.00
0.30
0.30
L3-21
0.10 to 10.00
0.01
1.00
1.00
1.00
1.00
0.0 to
0.0 to 400.0
0.0 to
255.0 <6>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter List
b6-03
557
Name
Setting Range
400.0 <1>
Resolution
OLV (2)
CLV (3)
0.0 Hz
L4-01
L4-02
L4-03
L4-04
0.0 to 20.0
0.1 Hz
2.0
2.0
2.0
2.0
L8-38
0 to 2
<4>
<4>
<4>
<4>
L8-40
0.00 to 2.00
0.01 s
0.50
0.50
0.50
0.50
o1-03
0 to 3
o1-04
0 to 1
0.0 to
0.0 to 20.0
-400.0 to
400.0 <8>
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.1 Hz
2.0
2.0
2.0
2.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 100.0%) instead of in Hz.
<2> This setting value depends on a Maximum Applicable Motor Capacity in models CIMR-Ao2A0250 to 2A0415, CIMR-Ao4A0139 to 4A1200,
and CIMR-Ao5A0099 to 5A0242: 2.00 in Open Loop Vector Control, 0.05 in Closed Loop Vector Control.
<3> This setting value depends on a Maximum Applicable Motor Capacity: 1000 s in models CIMR-Ao2A0138 to 2A0415, CIMR-Ao4A0139 to
4A1200, and CIMR-Ao5A0099 to 5A0242
<4> Default setting is dependent on parameter C6-01, Drive Duty Selection.
<5> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 40.0%) instead of in Hz.
<6> Values shown are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the values by 2.875 for 600 V class drives.
<7> This setting value depends on a Maximum Applicable Motor Capacity and V/f pattern selection in parameter E1-03.
<8> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (-100.0 to 100.0%) instead of in Hz.
Table B.4 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
No.
Name
Setting Range
Resolution
AOLV/PM (6)
CLV/PM (7)
0.5% <1>
0.0 to 10.0
0.1 Hz
0.5 Hz
1.0% <1>
0.00 to 10.00
0.01 s
0.00
0.00
0.00
0 to 1
0 to 200
1%
0 to 1
0.1
0.0 Hz
0.0%
0.0%
b6-01
0.1
0.0 Hz
0.0%
0.0%
b6-03
0.1
0.0 Hz
0.0%
0.0%
b8-01
b8-02
b8-03
b2-01
b2-04
b3-01
b3-02
b3-14
b5-15
C1-11
C2-01
C3-01
0 to 1
0.0 to 10.0
0.1
0.00 to 10.00
0.01 s
Hz <2>
0.1
0.0 Hz
0.0%
0.0%
0.00 to 10.00
0.01 s
1.00
0.20
0.20
0.0 to 2.5
0.1
C3-02
0 to 10000
1 ms
C4-01
0.00 to 2.50
0.01
0.00
C4-02
0 to 10000
1 ms
100
C5-01
0.00 to 300.00
0.01
10.00
20.00
C5-02
0.000 to 10.000
0.001 s
0.500
0.500
C5-03
0.00 to 300.00
0.01
10.00
20.00
C5-04
0.000 to 10.000
0.001 s
0.500
0.500
C5-06
0.000 to 0.500
0.001 s
0.016
0.004
0.1
0.0 Hz
0.0%
0.0%
0.0 to 400.0
Hz <2>
C5-07
C6-02
d3-01
Jump Frequency 1
0.0 to 400.0
Hz <2>
0.1
0.0 Hz
0.0%
0.0%
d3-02
Jump Frequency 2
0.1
0.0 Hz
0.0%
0.0%
d3-03
Jump Frequency 3
Hz <2>
0.1
0.0 Hz
0.0%
0.0%
0.1
1.0 Hz
1.0%
1.0%
d3-04
558
0.0 to 400.0
1 to F
0.0 to 400.0
0.0 to
20.0 <3>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Torque Reference Delay Time
E1-04
E1-05
Maximum Voltage
Setting Range
Resolution
0 to 1000
40.0 to 400.0
0.0 to
377.1 <5>
AOLV/PM (6)
1 ms
0.1 Hz
<4>
<4>
<4>
0.1 V
<4>
<4>
<4>
<4>
<4>
E1-06
Base Frequency
0.0 to 400.0
0.1 Hz
<4>
E1-07
0.0 to 400.0
0.1 Hz
E1-08
E1-09
E1-10
F1-01
F1-05
PG 1 Rotation Selection
377.1 <5>
CLV/PM (7)
0.1 V
0.0 to 400.0
0.1 Hz
<4>
<4>
0.0
0.1 V
0 to 60000
1 ppr
1024
1024
1024
0 to 1
0.0 to 2.0
0.1 s
0.0
0.0
0 to 4
0.0 to
F1-09
L1-01
L3-20
0.00 to 5.00
0.01
0.65
0.65
0.65
L3-21
0.10 to 10.00
0.01
1.00
1.00
1.00
L4-01
L4-02
L4-03
0.0 to 400.0
Hz <2>
0.0 to 20.0
0.0 to 400.0
0.1
0.0 Hz
0.0%
0.0%
0.1 Hz
2.0 Hz
4.0% <1>
4.0% <1>
0.1
0.0 Hz
0.0%
0.0%
4.0% <1>
Hz <6>
L4-04
0.0 to 20.0
0.1 Hz
2.0 Hz
4.0% <1>
L8-38
0 to 2
L8-40
0.00 to 2.00
0.01 s
0.00
0.00
0.00
o1-03
0 to 3
o1-04
0 to 1
Parameter List
<1>
<2>
<3>
<4>
<5>
<6>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
559
Name
Setting Range
Resolution
OLV (2)
CLV (3)
C3-21
0.0 to 2.5
0.1
0.0
1.0
1.0
C3-22
0 to 10000
1 ms
2000
200
C5-21
0.00 to 300.00
0.01
0.20
20.00
C5-22
0.000 to 10.000
0.001 s
0.200
0.500
C5-23
0.00 to 300.00
0.01
0.02
20.00
C5-24
0.000 to 10.000
0.001 s
0.050
0.500
7 <1>
7 <1>
7 <1>
7 <1>
C5-26
1 to F
E3-04
40.0 to 400.0
0.1 Hz
60.0
60.0
60.0
60.0
0.0 to 255.0
0.1 V
200.0
200.0
200.0
200.0
Voltage <2>
E3-05
E3-06
0.0 to 400.0
0.1 Hz
60.0
60.0
60.0
60.0
E3-07
0.0 to 400.0
0.1 Hz
3.0
3.0
3.0
0.0
0.0 to 255.0
0.1 V
15.0
15.0
11.0
0.0
Voltage <2>
E3-08
E3-09
0.0 to 400.0
0.1 Hz
1.5
1.5
0.5
0.0
E3-10
0.0 to 255.0
0.1 V
9.0
9.0
2.0
0.0
<1> Default setting is determined by parameters o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
560
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Unit
V/f Control
F
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
E1-03
<1>
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
60.0
<2>
E1-05 <3>
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
230.0
230.0
230.0
<2>
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
<2>
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
0.0
E1-08 <3>
15.0
15.0
15.0
15.0
35.0
50.0
35.0
50.0
19.0
24.0
19.0
24.0
15.0
15.0
15.0
17.3
13.8
0.0
<99>
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
0.0
<2>
E1-10 <3>
9.0
9.0
9.0
9.0
8.0
9.0
8.0
9.0
11.0
13.0
11.0
15.0
9.0
9.0
9.0
10.2
2.9
0.0
<1>
<2>
<3>
<99>
This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
Default setting is dependent on parameter E5-01, Motor Code Selection.
Values shown here are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooo.
Table B.7 E1-03 V/f Pattern Settings for Drive Capacity: CIMR-Ao2A0030 to 2A0211;
CIMR-Ao4A0018 to 4A0103; CIMR-Ao5A0011 to 5A0077
No.
Unit
V/f Control
F
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
E1-03
<1>
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
60.0
<2>
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
230.0
230.0
230.0
<2>
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
<2>
E1-05
<3>
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
0.0
E1-08 <3>
14.0
14.0
14.0
14.0
35.0
50.0
35.0
50.0
18.0
23.0
18.0
23.0
14.0
14.0
14.0
16.1
12.7
0.0
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
0.0
<2>
E1-10 <3>
7.0
7.0
7.0
7.0
6.0
7.0
6.0
7.0
9.0
11.0
9.0
13.0
7.0
7.0
7.0
8.1
2.3
0.0
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<2> Default setting is dependent on parameter E5-01, Motor Code Selection.
<3> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
No.
Unit
V/f Control
E1-03
<1>
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
60.0
<2>
E1-05 <3>
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
230.0
230.0
230.0
<2>
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
<2>
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
0.0
E1-08 <3>
12.0
12.0
12.0
12.0
35.0
50.0
35.0
50.0
15.0
20.0
15.0
20.0
12.0
12.0
12.0
13.8
12.7
0.0
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
0.0
<2>
E1-10 <3>
6.0
6.0
6.0
6.0
5.0
6.0
5.0
6.0
7.0
9.0
7.0
11.0
6.0
6.0
6.0
6.9
2.3
0.0
Parameter List
Table B.8 E1-03 V/f Pattern Settings for Drive Capacity: CIMR-Ao2A0250 to 2A0415;
CIMR-Ao4A0139 to 4A1200; CIMR-Ao5A0099 to 5A0242
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<2> Default setting is dependent on parameter E5-01, Motor Code Selection.
<3> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
561
Name
Unit
Model CIMR-Ao
Default Settings
2A0004
HD
2A0006
ND
HD
2A0008
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW
(HP)
0.4
(0.75)
0.75
(0.75)
0.75
(1)
1.1
(1)
1.1
(2)
1.5
(2)
1.5
(2)
2.2
(3)
100
100
100
100
100
100
100
100
62
ND
HD
2A0010
63
ND
HD
64
ND
65
b3-04
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
288.2
223.7
223.7
196.6
196.6
169.4
169.4
156.8
kgm2
0.0015
0.0028
0.0028
0.0068
0.0068
0.0068
0.0068
0.0088
1.9
3.3
3.3
4.9
4.9
6.2
6.2
8.5
Hz
2.9
2.5
2.5
2.6
2.6
2.6
2.6
2.9
1.2
1.8
1.8
2.3
2.3
2.8
2.8
9.842
5.156
5.156
3.577
3.577
1.997
1.997
1.601
18.2
13.8
13.8
18.5
18.5
18.5
18.5
18.4
14
26
26
38
38
53
53
77
562
E5-01
Hex.
1202
1202
1203
1203
FFFF
FFFF
1205
1205
L2-02
0.1
0.1
0.2
0.2
0.3
0.3
0.3
0.3
L2-03
0.2
0.3
0.3
0.4
0.4
0.4
0.4
0.5
L2-04
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L3-24
0.178
0.142
0.142
0.142
0.142
0.166
0.166
0.145
L8-02
115
115
115
115
115
115
115
115
L8-35
L8-38
n1-03
n5-02
ms
10
10
10
10
10
10
10
10
0.178
0.142
0.142
0.142
0.142
0.166
0.166
0.145
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Unit
Model CIMR-Ao
Default Settings
2A0012
HD
2A0018
ND
HD
2A0021
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW
(HP)
2.2
(3)
3.0
(3)
3.0
(3)
3.7
(5)
3.7
(5)
5.5
(7.5)
5.5
(7.5)
7.5
(10)
100
100
100
100
100
100
100
100
66
ND
HD
2A0030
67
ND
HD
68
ND
6A
b3-04
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
156.8
136.4
136.4
122.9
122.9
94.75
94.75
72.69
kgm2
0.0088
0.0158
0.0158
0.0158
0.0158
0.0255
0.026
0.037
C6-02
8.5
11.4
11.4
14
14
19.6
19.6
26.6
Hz
2.9
2.7
2.7
2.73
2.73
1.5
1.5
1.3
3.7
3.7
4.5
4.5
5.1
5.1
1.601
1.034
1.034
0.771
0.771
0.399
0.399
0.288
18.4
19
19
19.6
19.6
18.2
18.2
15.5
77
91
91
112
112
172
172
262
E5-01
Hex.
1206
1206
FFFF
FFFF
1208
1208
120A
120A
L2-02
0.5
0.5
L2-03
0.5
0.5
0.5
0.6
0.6
0.7
0.7
0.8
L2-04
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L3-24
0.145
0.145
0.145
0.154
0.154
0.168
0.168
0.175
L8-02
125
125
110
110
110
110
120
120
L8-35
L8-38
n1-03
n5-02
10
10
10
10
10
10
10
10
0.145
0.145
0.145
0.154
0.154
0.168
0.168
0.175
Parameter List
ms
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
563
Name
Unit
Model CIMR-Ao
Default Settings
2A0040
HD
2A0056
ND
HD
2A0069
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW
(HP)
7.5
(10)
11
(15)
11
(15)
15
(20)
15
(20)
18.5
(25)
18.5
(25)
22
(30)
100
100
100
100
100
100
100
100
6B
ND
HD
2A0081
6D
ND
HD
6E
ND
6F
b3-04
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
72.69
70.44
70.44
63.13
63.13
57.87
57.87
51.79
kgm2
0.037
0.053
0.053
0.076
0.076
0.138
0.138
0.165
C6-02
26.6
39.7
39.7
53
53
65.8
65.8
77.2
Hz
1.3
1.7
1.7
1.6
1.6
1.67
1.67
1.7
11.2
11.2
15.2
15.2
15.7
15.7
18.5
0.288
0.23
0.23
0.138
0.138
0.101
0.101
0.079
15.5
19.5
19.5
17.2
17.2
15.7
20.1
19.5
262
245
245
272
272
505
505
538
564
E5-01
Hex.
120B
120B
120D
120D
120E
120E
120F
120F
L2-02
L2-03
0.8
0.9
0.9
L2-04
0.3
0.3
0.3
0.6
0.6
0.6
0.6
0.6
L3-24
0.175
0.265
0.265
0.244
0.244
0.317
0.317
0.355
L8-02
125
125
120
120
120
120
125
125
L8-35
L8-38
n1-03
n5-02
ms
10
10
10
10
10
10
10
10
0.175
0.265
0.265
0.244
0.244
0.317
0.317
0.355
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Unit
Model CIMR-Ao
Default Settings
2A0110
HD
2A0138
ND
HD
2A0169
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW
(HP)
22
(30)
30
(40)
30
(40)
37
(50)
37
(50)
45
(60)
45
(60)
55
(75)
100
80
80
80
80
80
80
80
70
ND
HD
2A0211
72
ND
HD
73
ND
74
b3-04
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
2.00
b8-04
51.79
46.27
46.27
38.16
38.16
35.78
35.78
31.35
kgm2
0.165
0.220
0.220
0.273
0.273
0.333
0.333
0.490
C6-02
77.2
105
105
131
131
160
160
190
Hz
1.7
1.8
1.8
1.33
1.33
1.6
1.6
1.43
18.5
21.9
21.9
38.2
38.2
44
44
45.6
0.079
0.064
0.064
0.039
0.039
0.03
0.03
0.022
19.5
20.8
20.8
18.8
18.8
20.2
20.2
20.5
538
699
699
823
823
852
852
960
E5-01
Hex.
1210
1210
1212
1212
1213
1213
1214
1214
L2-02
L2-03
1.1
1.1
1.1
1.1
1.2
1.2
1.3
L2-04
0.6
0.6
0.6
0.6
0.6
L3-24
0.355
0.323
0.323
0.32
0.32
0.387
0.387
0.317
L8-02
130
130
130
130
130
130
125
125
L8-35
L8-38
n1-03
n5-02
10
10
10
10
10
10
10
10
0.355
0.323
0.323
0.32
0.32
0.387
0.387
0.317
Parameter List
ms
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
565
Name
Unit
Model CIMR-Ao
Default Settings
2A0250
HD
2A0312
ND
HD
2A0360
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW
(HP)
22
(75)
30
(100)
30
(100)
37
(125)
37
(125)
45
(150)
45
(150)
55
(175)
80
80
80
80
80
80
80
80
75
ND
HD
2A0415
76
ND
HD
77
ND
78
b3-04
b3-06
0.5
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b8-03
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
31.35
23.1
23.1
20.65
20.65
18.12
18.12
18.12
kgm2
0.49
0.90
0.90
1.10
1.10
1.90
1.90
1.90
C6-02
190
260
260
260
260
260
260
260
Hz
1.43
1.39
1.39
1.39
1.39
1.39
1.39
1.39
45.6
72
72
72
72
72
72
72
0.022
0.023
0.023
0.023
0.023
0.023
0.023
0.023
20.5
20
20
20
20
20
20
20
960
1200
1200
1200
1200
1200
1200
1200
566
E5-01
Hex.
1215
1215
1216
1216
FFFF
FFFF
FFFF
FFFF
L2-02
L2-03
1.3
1.5
1.5
1.5
1.5
1.7
1.7
1.7
L2-04
L3-24
0.317
0.533
0.533
0.592
0.592
0.646
0.646
0.646
L8-02
115
115
120
120
120
120
120
120
L8-35
L8-38
n1-03
n5-02
ms
10
10
10
10
100
100
100
100
0.317
0.533
0.533
0.592
0.592
0.646
0.646
0.646
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Unit
Model CIMR-Ao
Default Settings
4A0002
HD
4A0004
ND
HD
4A0005
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW (HP)
0.4
(0.75)
0.75
(0.75)
0.75
(2)
1.5
(2)
1.5
(3)
2.2
(3)
2.2
(3)
3.0
(3)
92
ND
HD
4A0007
93
ND
HD
94
ND
95
b3-04
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
576.4
447.4
447.4
338.8
338.8
313.6
313.6
265.7
kgm2
0.0015
0.0028
0.0028
0.0068
0.0068
0.0088
0.0088
0.0158
1.6
1.6
3.1
3.1
4.2
4.2
5.7
Hz
2.9
2.6
2.6
2.5
2.5
2.7
0.6
0.8
0.8
1.4
1.4
1.5
1.5
1.9
38.198
22.459
22.459
10.1
10.1
6.495
6.495
4.360
18.2
14.3
14.3
18.3
18.3
18.7
18.7
19
14
26
26
53
53
77
77
105
Hex.
1232
1232
1233
1233
1235
1235
1236
1236
0.1
0.1
0.2
0.2
0.3
0.3
0.5
0.5
L2-03
0.2
0.3
0.3
0.4
0.4
0.5
0.5
0.5
L2-04
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L3-24
0.178
0.142
0.142
0.166
0.166
0.145
0.145
0.145
L8-02
110
110
110
110
110
110
110
110
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.178
0.142
0.142
0.166
0.166
0.145
0.145
0.145
L2-02
Parameter List
E5-01
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
567
Name
Unit
Model CIMR-Ao
Default Settings
4A0009
HD
4A0011
ND
HD
4A0018
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW (HP)
3.0
(5)
3.7
(5)
3.7
(5)
5.5
(7.5)
5.5
(7.5)
7.5
(10)
7.5
(10)
11
(15)
96
ND
HD
4A0023
97
ND
HD
99
ND
9A
b3-04
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
265.7
245.8
245.8
189.5
189.5
145.38
145.38
140.88
kgm2
0.0158
0.0158
0.0158
0.0255
0.026
0.037
0.037
0.053
5.7
9.8
9.8
13.3
13.3
19.9
Hz
2.7
2.7
2.7
1.5
1.5
1.3
1.3
1.7
1.9
2.3
2.3
2.6
2.6
5.6
4.360
3.333
3.333
1.595
1.595
1.152
1.152
0.922
19
19.3
19.3
18.2
18.2
15.5
15.5
19.6
105
130
130
193
193
263
263
385
568
E5-01
Hex.
FFFF
FFFF
1238
1238
123A
123A
123B
123B
L2-02
0.5
0.5
0.5
0.5
0.8
0.8
L2-03
0.5
0.6
0.6
0.7
0.7
0.8
0.8
0.9
L2-04
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L3-24
0.145
0.154
0.154
0.168
0.168
0.175
0.175
0.265
L8-02
110
110
110
110
110
110
115
115
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.145
0.154
0.154
0.168
0.168
0.175
0.175
0.265
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Unit
Model CIMR-Ao
Default Settings
4A0031
HD
4A0038
ND
HD
4A0044
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW
(HP)
11
(15)
15
(20)
15
(20)
18.5
(25)
18.5
(25-30)
22
(30)
22
(25-30)
30
(40)
100
100
100
100
100
100
100
100
9C
ND
HD
4A0058
9D
ND
HD
9E
ND
9F
b3-04
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
140.88
126.26
126.26
115.74
115.74
103.58
103.58
92.54
kgm2
0.053
0.076
0.076
0.138
0.138
0.165
0.165
0.220
C6-02
19.9
26.5
26.5
32.9
32.9
38.6
38.6
52.3
Hz
1.7
1.6
1.6
1.67
1.67
1.7
1.7
1.8
5.6
7.6
7.6
7.8
7.8
9.2
9.2
10.9
0.922
0.55
0.55
0.403
0.403
0.316
0.316
0.269
19.6
17.2
17.2
20.1
20.1
23.5
23.5
20.7
385
440
440
508
508
586
586
750
E5-01
Hex.
123D
123D
123E
123E
123F
123F
1240
1240
L2-02
L2-03
0.9
1.1
L2-04
0.3
0.6
0.6
0.6
0.6
0.6
0.6
0.6
L3-24
0.265
0.244
0.244
0.317
0.317
0.355
0.355
0.323
L8-02
120
120
120
120
115
115
120
120
L8-35
L8-38
n1-03
n5-02
10
10
10
10
10
10
10
10
0.265
0.244
0.244
0.317
0.317
0.355
0.355
0.323
Parameter List
ms
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
569
Name
Unit
Model CIMR-Ao
Default Settings
4A0072
HD
4A0088
ND
HD
4A0103
C6-01
o2-04
Hex.
E2-11 (E4-11)
kW
(HP)
30
(40)
37
(50)
37
(50-60)
45
(60)
45
(50-60)
55
(75)
55
(75)
75
(100)
100
100
100
100
100
80
80
60
A1
ND
HD
4A0139
A2
ND
HD
A3
ND
A4
b3-04
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.7
b8-03
0.50
0.50
0.50
0.50
0.50
2.00
2.00
2.00
b8-04
92.54
76.32
76.32
71.56
71.56
67.2
67.2
46.2
kgm2
0.220
0.273
0.273
0.333
0.333
0.490
0.490
0.90
E2-01 (E4-01)
C6-02
52.3
65.6
65.6
79.7
79.7
95
95
130
E2-02 (E4-02)
Hz
1.8
1.33
1.33
1.6
1.6
1.46
1.46
1.39
E2-03 (E4-03)
10.9
19.1
19.1
22
22
24
24
36
E2-05 (E4-05)
0.269
0.155
0.155
0.122
0.122
0.088
0.088
0.092
E2-06 (E4-06)
20.7
18.8
18.8
19.9
19.9
20
20
20
E2-10 (E4-10)
750
925
925
1125
1125
1260
1260
1600
1245
570
E5-01
Hex.
1242
1242
1243
1243
1244
1244
1245
L2-02
L2-03
1.1
1.1
1.1
1.2
1.2
1.2
1.2
1.3
L2-04
0.6
0.6
0.6
0.6
0.6
L3-24
0.323
0.32
0.32
0.387
0.387
0.317
0.317
0.533
L8-02
120
120
110
110
120
120
130
130
L8-35
L8-38
n1-03
n5-02
ms
10
10
10
10
10
10
30
30
0.323
0.32
0.32
0.387
0.387
0.317
0.317
0.533
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Unit
Model CIMR-Ao
C6-01
o2-04
Hex.
E2-11 (E4-11)
kW
(HP)
Default Settings
4A0165
HD
4A0208
ND
HD
A5
75
(100)
4A0250
ND
HD
A6
90
(125)
90
(125150)
4A0296
ND
HD
A7
110
(150)
110
(150)
ND
A8
132
(200)
132
(200)
160
(250)
b3-04
60
60
60
60
60
60
60
60
b3-06
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b8-03
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
46.2
38.91
38.91
36.23
36.23
32.79
32.79
30.13
kgm2
0.90
1.10
1.10
1.90
1.90
2.10
2.10
3.30
E2-01 (E4-01)
130
156
156
190
190
223
223
270
E2-02 (E4-02)
Hz
1.39
1.4
1.4
1.4
1.4
1.38
1.38
1.35
E2-03 (E4-03)
36
40
40
49
49
58
58
70
E2-05 (E4-05)
0.092
0.056
0.056
0.046
0.046
0.035
0.035
0.029
E2-06 (E4-06)
20
20
20
20
20
20
20
20
E2-10 (E4-10)
1600
1760
1760
2150
2150
2350
2350
2850
1249
E5-01
Hex.
1246
1246
1247
1247
1248
1248
1249
L2-02
L2-03
1.3
1.5
1.5
1.7
1.7
1.7
1.7
1.8
L2-04
L3-24
0.533
0.592
0.592
0.646
0.646
0.673
0.673
0.777
L8-02
130
130
120
120
120
120
125
125
L8-35
L8-38
n1-03
n5-02
30
30
30
30
30
30
30
30
0.533
0.592
0.592
0.646
0.646
0.673
0.673
0.777
Parameter List
ms
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
571
Name
Unit
Model CIMR-Ao
C6-01
o2-04
Hex.
E2-11 (E4-11)
kW
(HP)
Default Settings
4A0362
HD
4A0414
ND
HD
A9
160
(250)
4A0515
ND
HD
AA
185
(300)
185
(300)
ND
AC
220
(350)
220
(350)
250
(400
-450)
b3-04
60
60
60
60
60
60
b3-06
0.7
0.7
0.7
0.7
0.7
0.7
b8-03
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
30.13
30.57
30.57
27.13
27.13
21.76
kgm2
3.30
3.60
3.60
4.10
4.10
6.50
E2-01 (E4-01)
270
310
310
370
370
500
E2-02 (E4-02)
Hz
1.35
1.3
1.3
1.3
1.3
1.25
E2-03 (E4-03)
70
81
81
96
96
130
E2-05 (E4-05)
0.029
0.025
0.025
0.02
0.02
0.014
E2-06 (E4-06)
20
20
20
20
20
20
E2-10 (E4-10)
2850
3200
3200
3700
3700
4700
FFFF
C5-17 (C5-37)
C6-02
572
Motor Inertia
E5-01
Hex.
124A
124A
FFFF
FFFF
FFFF
L2-02
L2-03
1.8
1.9
1.9
2.1
L2-04
L3-24
0.777
0.864
0.864
0.91
0.91
1.392
L8-02
130
130
140
140
140
140
L8-35
L8-38
n1-03
n5-02
ms
30
30
100
100
100
100
0.777
0.864
0.864
0.91
0.91
1.392
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Unit
Model CIMR-Ao
C6-01
o2-04
Hex.
E2-11 (E4-11)
kW
(HP)
Default Settings
4A0675
HD
4A0930
ND
HD
AE
315
(400
-450
-500)
4A1200
ND
HD
B0
355
(500
-550)
450
(650)
ND
B2
500
(750)
560
(900)
630
(1000)
b3-04
60
60
60
60
60
60
b3-06
0.7
0.7
0.7
0.7
0.7
0.7
b8-03
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
C5-17 (C5-37)
C6-02
Motor Inertia
Carrier Frequency Selection
21.76
23.84
21.4
20.26
18.12
17.06
kgm2
11.00
12.00
13.00
14.00
18.00
18.00
7
1200
E2-01 (E4-01)
500
650
800
900
1090
E2-02 (E4-02)
Hz
1.25
0.9
0.8
0.7
E2-03 (E4-03)
130
130
160
180
218
240
E2-05 (E4-05)
0.014
0.012
0.01
0.009
0.007
0.006
E2-06 (E4-06)
20
20
20
20
20
20
E2-10 (E4-10)
4700
5560
7050
7833
9870
11123
Hex.
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
L2-03
2.1
2.3
2.8
3.1
4.6
L2-04
2.6
3.8
4.5
L3-24
1.392
1.667
2.222
2.857
3.333
L8-02
140
140
140
140
140
140
L8-35
L8-38
n1-03
ms
100
100
100
100
100
100
n5-02
1.392
1.667
2.222
2.857
3.333
Parameter List
E5-01
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
573
Name
Unit
Model CIMR-Ao
C6-01
o2-04
Hex
.
E2-11
(E4-11)
kW
(HP
)
0.75
(1)
1.5
(2)
1.5
(2)
2.2
(3)
2.2
(3)
3.7
(5)
3.7
(5)
5.5
(7.5)
5.5
(7.5)
7.5
(10)
b3-04
100
100
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
541.9
494.4
494.4
415.3
415.3
320.2
320.2
239.95
239.95
199.86
0.0028
0.0068
0.0068
0.0088
0.0088
0.0158
0.0158
0.0255
0.026
0.037
C5-17
(C5-37)
C6-02
Motor Inertia
kgm
Default Settings
5A0003
5A0004
5A0006
5A0009
5A0011
HD
ND
HD
ND
HD
ND
HD
ND
HD
ND
C3
C4
C5
C7
C9
E2-01
(E4-01)
1.7
2.7
2.7
3.9
3.9
6.1
6.1
11
E2-02
(E4-02)
Hz
2.5
2.5
2.5
3.0
3.0
2.7
2.7
1.5
1.5
1.3
E2-03
(E4-03)
0.8
0.8
0.8
1.2
1.2
1.8
1.8
2.7
2.7
3.3
E2-05
(E4-05)
Motor Line-to-Line
Resistance
21.9
13.72
13.72
8.825
8.825
4.936
4.936
2.601
2.601
1.446
E2-06
(E4-06)
18.3
18.3
18.3
18.7
18.7
19.3
19.3
18.2
18.2
15.5
E2-10
(E4-10)
53
53
53
77
77
130
130
193
193
263
L2-02
0.2
0.2
0.3
0.3
0.5
0.5
0.5
0.5
0.8
0.8
L2-03
0.5
0.5
0.5
0.5
0.5
0.8
0.8
0.8
0.8
L2-04
0.5
0.5
0.5
0.5
0.5
0.6
0.6
0.7
0.7
0.8
L3-24
0.142
0.166
0.166
0.145
0.145
0.154
0.154
0.168
0.168
0.175
L8-02
110
110
110
110
110
110
110
110
115
115
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
10
10
n5-02
0.142
0.166
0.166
0.145
0.145
0.154
0.154
0.168
0.168
0.175
574
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Unit
Model CIMR-Ao
Default Settings
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW
(HP)
7.5
(10)
11
(15)
11
(15)
15
(20)
15
(20)
18.5
(25)
18.5 (
25)
22
(30)
5A0017
5A0022
5A0027
5A0032
HD
ND
HD
ND
HD
ND
HD
CA
CC
CD
ND
1
CE
b3-04
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
200
172
172
154
154
140
140
129
kgm2
0.037
0.053
0.053
0.076
0.076
0.138
0.138
0.165
11
17
17
22
22
27
27
32
Hz
1.3
1.7
1.7
1.6
1.6
1.67
1.67
1.7
3.3
5.1
5.1
6.6
6.6
8.1
8.1
9.6
1.45
1.17
1.17
0.9
0.9
0.66
0.66
0.52
15.5
19.6
19.6
17.2
17.2
20.1
20.1
23.5
263
385
385
440
440
508
508
586
L2-02
L2-03
1.2
1.2
1.2
1.2
1.2
L2-04
0.8
0.9
0.9
L3-24
0.18
0.27
0.27
0.24
0.24
0.32
0.32
0.36
L8-02
120
120
120
120
115
115
115
115
L8-35
L8-38
n1-03
n5-02
10
10
10
10
10
10
10
10
0.18
0.27
0.27
0.24
0.24
0.32
0.32
0.36
Parameter List
ms
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
575
Name
Unit
Model CIMR-Ao
Default Settings
C6-01
o2-04
Hex.
E2-11 (E4-11)
kW
(HP)
22
(25-30)
5A0041
5A0052
5A0062
HD
ND
HD
ND
HD
CF
D1
30
(40)
30
(40)
ND
1
D2
37
(50)
37
(50-60)
45
(60)
b3-04
100
80
80
80
80
80
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
128.65
115.57
115.57
97.01
97.01
90.07
kgm2
0.165
0.220
0.220
0.273
0.273
0.333
E2-01 (E4-01)
32
41
41
52
52
62
E2-02 (E4-02)
Hz
1.7
1.8
1.8
1.33
1.33
1.6
E2-03 (E4-03)
9.6
12.3
12.3
15.6
15.6
18.8
E2-05 (E4-05)
0.516
0.438
0.438
0.267
0.267
0.21
E2-06 (E4-06)
23.5
20.7
20.7
18.8
18.8
19.9
E2-10 (E4-10)
586
750
750
925
925
1125
L2-02
L2-03
1.2
1.2
1.2
1.2
1.2
1.5
L2-04
1.1
1.1
1.2
1.2
1.3
L3-24
0.355
0.323
0.323
0.32
0.32
0.387
L8-02
110
110
110
110
110
110
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
n5-02
0.355
0.323
0.323
0.32
0.32
0.387
C5-17 (C5-37)
C6-02
576
Motor Inertia
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Unit
Model CIMR-Ao
C6-01
o2-04
Hex.
E2-11 (E4-11)
kW (HP)
Default Settings
5A0077
5A0099
HD
ND
HD
D3
45
(50-60)
ND
1
D4
55
(75)
55
(75)
75
(100)
b3-04
80
80
80
80
b3-06
0.5
0.5
0.5
0.5
b8-03
0.5
b8-04
90.07
80.87
80.87
70.07
kgm2
0.333
0.490
0.49
0.90
E2-01 (E4-01)
62
77
77
99
E2-02 (E4-02)
Hz
1.6
1.46
1.46
1.39
E2-03 (E4-03)
18.8
23.1
23.1
29.7
E2-05 (E4-05)
0.21
0.15
0.15
0.099
E2-06 (E4-06)
19.9
20
20
20
E2-10 (E4-10)
1600
C5-17 (C5-37)
C6-02
Motor Inertia
1125
1260
1260
L2-02
L2-03
1.5
1.8
1.8
1.8
L2-04
1.3
1.5
1.5
1.6
L3-24
0.387
0.317
0.317
0.533
L8-02
110
110
110
110
L8-35
L8-38
n1-03
n5-02
10
10
30
30
0.387
0.317
0.317
0.533
Parameter List
ms
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
577
Name
Unit
Model CIMR-Ao
Default Settings
C6-01
o2-04
Hex.
E2-11
(E4-11)
kW
(HP)
75
(100)
90
(125)
90
(125)
110
(150)
110
(150)
160
(200)
160
(200)
185
(250)
5A0125
5A0145
5A0192
5A0242
HD
ND
HD
ND
HD
ND
HD
D3
D4
D5
ND
1
D6
b3-04
80
80
80
80
80
80
80
80
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
70.07
61.50
61.50
58.67
58.67
49.90
49.90
42.90
kgm2
0.90
1.10
1.10
1.90
1.90
2.10
3.30
4.10
E2-01
(E4-01)
99
125
130
145
172
192
200
242
E2-02
(E4-02)
Hz
1.39
1.39
1.39
1.40
1.40
1.35
1.35
1.35
E2-03
(E4-03)
29.7
37.5
37.5
43.2
43.2
57.6
57.6
57.6
E2-05
(E4-05)
0.099
0.079
0.079
0.060
0.060
0.037
0.037
0.037
E2-06
(E4-06)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
E2-10
(E4-10)
1600
2150
2150
2150
2150
2850
2850
2850
L2-02
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-03
1.8
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-04
1.6
1.7
1.7
1.8
1.8
2.0
2.0
2.0
L3-24
0.533
0.592
0.592
0.646
0.646
0.673
0.777
0.864
L8-02
110
110
110
110
110
110
110
110
L8-35
L8-38
n1-03
n5-02
C5-17
(C5-37)
C6-02
578
Motor Inertia
ms
30
30
30
30
30
30
30
30
0.533
0.592
0.592
0.646
0.646
0.673
0.777
0.864
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
E5-01
Name
Unit
Default Settings
0002
0003
0005
0006
0008
Voltage Class
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
Rated Speed
r/min
1800
1800
1800
1800
1800
E5-02
kW
0.4
0.75
1.5
2.2
3.7
E5-03
2.1
4.0
6.9
10.8
17.4
E5-04
E5-05
2.47
1.02
0.679
0.291
0.169
E5-06
mH
12.7
4.8
3.9
3.6
2.5
E5-07
mH
12.7
4.8
3.9
3.6
2.5
E5-09
mVs
/rad
E5-24
mV/
(r/min)
62.0
64.1
73.4
69.6
72.2
E1-04
Hz
120
120
120
120
120
E1-05
Maximum Voltage
200.0
200.0
200.0
200.0
200.0
E1-06
Base Frequency
Hz
120
120
120
120
120
E1-09
Hz
kgm2
0.0007
0.0014
0.0021
0.0032
0.0046
C5-17
Motor Inertia
L3-24
0.064
0.066
0.049
0.051
0.044
n5-02
0.064
0.066
0.049
0.051
0.044
n8-49
Table B.13 200 V, 3600 r/min Type Yaskawa SMRA Series SPM Motor Settings
E5-01
Name
Unit
Default Settings
0103
0105
0106
0108
Voltage Class
200
200
200
200
Rated Power
kW
0.75
1.5
2.2
3.7
Rated Speed
r/min
3600
3600
3600
3600
E5-02
kW
0.75
1.5
2.2
3.7
E5-03
4.1
8.0
10.5
16.5
E5-04
E5-05
0.538
0.20
0.15
0.097
E5-06
mH
3.2
1.3
1.1
1.1
E5-07
mH
3.2
1.3
1.1
1.1
E5-09
mVs
/rad
E5-24
mV/
(r/min)
32.4
32.7
36.7
39.7
E1-04
Hz
240
240
240
240
E1-05
Maximum Voltage
200.0
200.0
200.0
200.0
E1-06
Base Frequency
Hz
240
240
240
240
E1-09
Hz
12
12
12
12
C5-17
Motor Inertia
kgm2
0.0007
0.0014
0.0021
0.0032
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter List
No.
579
Name
Unit
Default Settings
L3-24
0.137
0.132
0.132
0.122
n5-02
0.137
0.132
0.132
0.122
n8-49
Name
Motor Code
Selection
Unit
Default Settings
1202
1203
1205
1206
1208
120A
120B
120D
120E
120F
1210
1212
1213
1214
1215
1216
Voltage Class
Rated Power
kW
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
30
37
45
55
Rated Speed
75
r/min
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
Motor Rated
Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15.0
18.00
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
Motor Rated
Current
1.77
3.13
5.73
8.44
13.96
20.63
28.13
41.4
55.4
68.2
80.6
105.2
131.3
153.1
185.4
257.3
E5-04
Number of Motor
Poles
E5-05
Motor Stator
Resistance (r1)
8.233
2.284
1.470
0.827
0.455
0.246
0.198
0.094
0.066
0.051
0.037
0.030
0.020
0.014
0.012
0.006
E5-06
Motor d-Axis
Inductance (Ld)
mH
54.84
23.02
17.22
8.61
7.20
4.86
4.15
3.40
2.45
2.18
1.71
1.35
0.99
0.83
0.79
0.44
E5-07
Motor q-Axis
Inductance (Lq)
mH
64.10
29.89
20.41
13.50
10.02
7.43
5.91
3.91
3.11
2.55
2.05
1.82
1.28
1.01
0.97
0.56
E5-09
Motor Induction
Voltage Constant
1 (Ke)
mVs
/rad
223.7
220.3
240.8
238.0
238.7
239.6
258.2
239.3
248.1
253.6
250.0
280.9
264.2
280.4
311.9
268.0
E5-24
Motor Induction
Voltage Constant
2 (Ke)
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum
Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Minimum Output
Frequency
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.0011
0.0017
0.0023
0.0043
0.0083
0.014
0.017
0.027
0.046
0.55
0.064
0.116
0.140
0.259
0.31
0.42
L3-24
Motor
Acceleration
Time for Inertia
Calculations
0.092
0.076
0.052
0.066
0.075
0.083
0.077
0.084
0.102
0.101
0.098
0.130
0.127
0.193
0.191
0.187
n5-02
Motor
Acceleration
Time
0.092
0.076
0.052
0.066
0.075
0.083
0.077
0.084
0.102
0.101
0.098
0.130
0.127
0.193
0.191
0.187
n8-49
-7.6
-11.5
-9.1
-19.0
-18.7
-23.4
-18.5
-10.9
-16.5
-11.3
-12.8
-16.8
-15.6
-10.7
-9.6
-13.3
E5-01
580
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Unit
Default Settings
1232
1233
1235
1236
1238
123A
123B
123D
123E
123F
Voltage Class
Rated Power
kW
400
400
400
400
400
400
400
400
400
400
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Rated Speed
18
r/min
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
E5-03
0.89
1.56
2.81
4.27
7.08
10.31
13.65
20.7
27.5
33.4
E5-04
E5-05
25.370
9.136
6.010
3.297
1.798
0.982
0.786
0.349
0.272
0.207
E5-06
mH
169.00
92.08
67.71
34.40
32.93
22.7
16.49
13.17
10.30
8.72
E5-07
mH
197.50
119.56
81.71
54.00
37.70
26.80
23.46
15.60
12.77
11.22
E5-09
mVs
/rad
392.6
440.6
478.3
466.3
478.8
478.1
520.0
481.5
498.8
509.5
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
kgm2
0.0011
0.0017
0.0023
0.0043
0.0083
0.014
0.017
0.027
0.046
0.055
C5-17
Motor Inertia
L3-24
0.092
0.076
0.052
0.066
0.075
0.083
0.077
0.084
0.102
0.101
n5-02
0.092
0.076
0.052
0.066
0.075
0.083
0.077
0.084
0.102
0.101
n8-49
-8.6
-11.5
-10.3
-19.8
-8.5
-11.0
-18.6
-12.5
-15.5
-17.9
Name
Unit
No.
E5-01
Default Settings
1240
1242
1243
1244
1245
1246
1247
1248
1249
124A
Voltage Class
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
22
30
37
45
55
75
90
110
132
160
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
160.00
E5-03
39.8
52.0
65.8
77.5
92.7
126.6
160.4
183.3
222.9
267.7
E5-04
E5-05
0.148
0.235
0.079
0.054
0.049
0.029
0.019
0.017
0.012
0.008
E5-06
mH
6.81
5.4
4.08
3.36
3.16
2.12
1.54
1.44
1.21
0.97
E5-07
mH
8.47
7.26
5.12
3.94
3.88
2.61
2.06
2.21
1.46
1.28
E5-09
mVs
/rad
503.9
561.7
528.5
558.1
623.8
594.5
524.1
583.7
563.6
601.2
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.064
0.116
0.140
0.259
0.31
0.42
0.56
0.83
0.96
1.61
L3-24
0.098
0.130
0.127
0.193
0.191
0.187
0.208
0.254
0.243
0.338
n5-02
0.098
0.130
0.127
0.193
0.191
0.187
0.208
0.254
0.243
0.338
n8-49
-15.1
-16.8
-14.1
-8.8
-9.6
-10.3
-17.0
-21.7
-10.9
-13.2
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
581
Parameter List
No.
Name
Motor Code Selection
E5-01
Unit
Default Settings
1302
1303
1305
1306
1308
130A
130B
130D
130E
130F
1310
1312
1313
1314
1315
Voltage Class
Rated Power
kW
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
30
37
45
Rated Speed
55
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15.00
18.00
22.00
30.00
37.00
45.00
55.00
E5-03
1.88
3.13
5.63
8.33
14.17
20.63
27.71
39.6
55.5
65.6
75.1
105.2
126.0
153.1
186.5
E5-04
E5-05
3.190
1.940
1.206
0.665
0.341
0.252
0.184
0.099
0.075
0.057
0.041
0.034
0.023
0.015
0.012
E5-06
Motor d-Axis
Inductance (Ld)
mH
32.15
26.12
14.72
12.27
8.27
6.49
6.91
4.07
3.29
2.53
1.98
1.75
1.48
1.04
0.87
E5-07
Motor q-Axis
Inductance (Lq)
mH
41.74
34.30
20.15
14.77
9.81
7.74
7.66
4.65
3.84
3.01
2.60
2.17
1.70
1.31
1.10
E5-09
Motor Induction
Voltage Constant 1 (Ke)
mVs
/rad
264.3
269.6
284.3
287.1
284.5
298.0
335.0
303.9
311.2
300.9
327.7
354.2
369.6
351.6
374.7
E5-24
Motor Induction
mV/
Voltage Constant 2 (Ke) (r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Minimum Output
Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.0017
0.0023
0.0043
0.0083
0.0136
0.017
0.027
0.046
0.055
0.064
0.116
0.140
0.259
0.312
0.42
L3-24
Motor Acceleration
Time for Inertia
Calculations
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
0.085
0.080
0.122
0.108
0.161
0.160
0.175
n5-02
Motor Acceleration
Time
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
0.085
0.080
0.122
0.108
0.161
0.160
0.175
n8-49
-6.6
-10.9
-13.5
-9.0
-9.5
-10.1
-6.0
-9.3
-10.7
-13.2
-15.7
-11.5
-7.0
-11.8
-10.2
582
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Unit
Default Settings
1332
1333
1335
1336
1338
133A
133B
133D
133E
133F
Voltage Class
Rated Power
kW
400
400
400
400
400
400
400
400
400
400
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Rated Speed
18
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
E5-03
0.94
1.56
2.81
4.27
6.98
10.21
13.85
19.5
27.4
32.9
E5-04
E5-05
12.760
7.421
4.825
2.656
1.353
0.999
0.713
0.393
0.295
0.223
E5-06
mH
128.60
85.11
58.87
46.42
31.73
26.20
27.06
15.51
12.65
9.87
E5-07
mH
166.96
113.19
80.59
60.32
40.45
30.94
33.45
19.63
15.87
12.40
E5-09
mVs
/rad
528.6
544.2
568.5
572.8
562.9
587.6
670.1
612.7
624.6
610.4
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
kgm2
0.0017
0.0023
0.0043
0.0083
0.0136
0.017
0.027
0.046
0.055
0.064
C5-17
Motor Inertia
L3-24
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
0.085
0.080
n5-02
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
0.085
0.080
n8-49
-6.6
-9.2
-13.5
-12.1
-13.7
-10.1
-12.2
-15.5
-15.1
-16.0
Name
Unit
No.
E5-01
Default Settings
1340
1342
1343
1344
1345
1346
1347
1348
1349
Voltage Class
400
400
400
400
400
400
400
400
400
Rated Power
kW
22
30
37
45
55
75
90
110
132
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
E5-03
37.6
52.5
63.2
76.4
96.1
124.0
153.1
186.5
226.0
E5-04
E5-05
0.164
0.137
0.093
0.059
0.048
0.028
0.024
0.015
0.011
E5-06
mH
7.90
7.01
5.93
4.17
3.11
2.32
2.20
1.45
1.23
E5-07
mH
10.38
8.68
6.79
5.22
4.55
2.97
3.23
1.88
1.67
E5-09
mVs
/rad
655.4
708.4
739.2
703.0
747.1
639.3
708.0
640.7
677.0
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.116
0.140
0.259
0.312
0.42
0.56
0.83
0.96
1.61
L3-24
0.122
0.108
0.161
0.160
0.175
0.171
0.213
0.201
0.281
n5-02
0.122
0.108
0.161
0.160
0.175
0.171
0.213
0.201
0.281
n8-49
-15.7
-11.5
-6.8
-11.5
-14.8
-15.8
-19.6
-14.9
-15.1
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
583
Parameter List
No.
Name
Motor Code Selection
E5-01
Unit
Default Settings
1402
1403
1405
1406
1408
140A
140B
Voltage Class
Rated Power
kW
Rated Speed
140D
140E
200
200
200
200
200
200
0.4
0.75
1.5
2.2
3.7
5.5
140F
1410
1412
1413
1414
200
200
200
200
200
200
200
200
7.5
11.0
15
18.00
22.00
30.00
37.00
45.00
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
E5-03
1.88
3.02
6.00
8.85
14.27
20.21
26.67
39.9
55.6
63.5
74.4
104.2
129.6
154.2
E5-04
E5-05
4.832
2.704
1.114
0.511
0.412
0.303
0.165
0.113
0.084
0.066
0.048
0.035
0.023
0.016
E5-06
mH
48.68
32.31
19.22
12.15
7.94
11.13
6.59
4.96
3.83
3.33
2.38
2.04
1.53
1.16
E5-07
mH
63.21
40.24
24.38
15.35
11.86
14.06
8.55
6.12
4.65
4.5
3.15
2.86
2.27
1.54
E5-09
mVs
/rad
320.4
327.1
364.4
344.4
357.5
430.8
391.5
384.4
372.1
421.3
410.9
436.1
428.8
433.3
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
kgm2
0.0017
0.0023
0.0083
0.0136
0.0171
0.027
0.046
0.055
0.064
0.116
0.14
0.259
0.312
0.418
C5-17
Motor Inertia
L3-24
0.062
0.044
0.080
0.090
0.067
0.072
0.088
0.073
0.062
0.091
0.092
0.125
0.122
0.135
n5-02
0.062
0.044
0.080
0.090
0.067
0.072
0.088
0.073
0.062
0.091
0.092
0.125
0.122
0.135
n8-49
-8.8
-9.9
-9.3
-10.0
-17.7
-12.3
-15.3
-13.9
-14.4
-17.9
-15.9
-17.9
-20.1
-13.7
584
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Unit
Default Settings
1432
1433
1435
1436
1438
143A
143B
143D
143E
Voltage Class
Rated Power
kW
400
400
400
400
400
400
400
400
400
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Rated Speed
15
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
E5-03
0.94
1.51
3.00
4.43
7.08
10.10
13.33
19.9
27.8
E5-04
E5-05
19.320
10.800
4.456
2.044
1.483
1.215
0.660
0.443
0.331
E5-06
mH
194.70
129.20
76.88
48.60
37.58
44.54
26.36
19.10
15.09
E5-07
mH
252.84
160.90
97.52
61.40
47.65
56.26
34.20
24.67
18.56
E5-09
mVs
/rad
640.9
654.1
728.8
688.9
702.0
861.5
783.0
762.2
749.6
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
kgm2
0.0017
0.0023
0.0083
0.0136
0.0171
0.027
0.046
0.055
0.064
C5-17
Motor Inertia
L3-24
0.062
0.044
0.080
0.090
0.067
0.072
0.088
0.073
0.062
n5-02
0.062
0.044
0.080
0.090
0.067
0.072
0.088
0.073
0.062
n8-49
-8.8
-9.9
-9.3
-10.0
-12.8
-12.3
-15.3
-16.7
-14.9
No.
E5-01
Name
Unit
Default Settings
143F
1440
1442
1443
1444
1445
1446
1447
1448
Voltage Class
400
400
400
400
400
400
400
400
400
Rated Power
kW
18
22
30
37
45
55
75
90
110
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
18.50
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
E5-03
31.8
37.2
52.1
64.8
76.6
92.0
127.1
150.5
185.4
E5-04
E5-05
0.264
0.192
0.140
0.093
0.063
0.051
0.033
0.027
0.015
E5-06
mH
13.32
9.52
8.16
6.13
4.63
3.96
3.03
2.60
1.89
E5-07
mH
18.00
12.60
11.40
9.10
6.15
5.00
5.14
3.28
2.33
E5-09
mVs
/rad
842.7
821.8
872.3
857.7
866.6
854.0
823.1
853.4
829.2
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.116
0.140
0.259
0.312
0.418
0.56
0.83
0.96
1.61
L3-24
0.091
0.092
0.125
0.122
0.135
0.147
0.161
0.154
0.212
n5-02
0.091
0.092
0.125
0.122
0.135
0.147
0.161
0.154
0.212
n8-49
-17.9
-15.9
-17.7
-20.1
-13.8
-12.5
-28.8
-13.3
-11.6
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
585
Parameter List
No.
E5-01
Name
Unit
Default Settings
2202
2203
2205
2206
2208
220A
220B
220D
220E
220F
2210
2212
2213
2214
2215
2216
Voltage Class
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
30
37
45
55
75
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
1.77
3.54
6.56
8.96
14.79
20.94
29.58
41.1
54.2
68.2
78.6
104.2
129.2
153.1
205.2
260.4
E5-04
E5-05
2.247
1.132
0.774
0.479
0.242
0.275
0.161
0.111
0.071
0.049
0.040
0.030
0.020
0.013
0.009
0.006
E5-06
mH
22.32
12.38
8.90
7.39
5.06
5.82
3.86
3.59
2.67
1.98
1.69
1.31
0.88
0.77
0.55
0.40
E5-07
mH
32.50
15.72
11.96
9.63
6.42
6.74
4.66
4.32
3.1
2.41
2.12
1.61
1.14
1.04
0.69
0.50
E5-09
mVs
/rad
215.2
203.9
219.3
230.6
235.1
251.7
235.7
252.0
253.7
244.6
256.3
283.1
266.3
260
261.5
259.3
E5-24
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Minimum Output
Frequency
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.0016
0.0022
0.0042
0.0081
0.0133
0.013
0.017
0.027
0.044
0.054
0.063
0.113
0.137
0.252
0.30
0.41
L3-24
0.134
0.099
0.094
0.124
0.121
0.081
0.075
0.082
0.099
0.098
0.096
0.127
0.124
0.188
0.186
0.184
n5-02
0.134
0.099
0.094
0.124
0.121
0.081
0.075
0.082
0.099
0.098
0.096
0.127
0.124
0.188
0.186
0.184
n8-49
-9.3
-6.4
-10.0
-9.9
-9.7
-8.4
-11.5
-13.1
-10.9
-14.3
-15.1
-11.3
-14.1
-18.8
-11.4
-12.2
586
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Unit
Default Settings
2232
2233
2235
2236
2238
223A
223B
223D
223E
223F
2240
2242
Voltage Class
Rated Power
kW
400
400
400
400
400
400
400
400
400
400
400
400
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
Rated Speed
30
r/min
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
22.00
30.00
E5-03
0.92
1.77
3.33
4.48
7.50
10.42
14.27
20.5
26.4
34.2
38.8
52.2
E5-04
E5-05
8.935
4.570
3.096
1.906
0.972
1.103
0.630
0.429
0.275
0.196
0.160
0.120
E5-06
mH
80.14
48.04
35.60
30.31
20.03
23.41
14.86
14.34
9.99
7.92
6.82
5.24
E5-07
mH
110.76
64.88
47.84
38.36
24.97
28.70
17.25
17.25
12.37
9.64
8.51
6.44
E5-09
mVs
/rad
416.5
399.4
438.5
475.5
463.7
485.8
470.4
513.4
505.3
489.2
509.5
566.2
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Minimum Output
Frequency
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.0016
0.0022
0.0042
0.0081
0.0133
0.013
0.017
0.027
0.044
0.054
0.063
0.113
L3-24
0.134
0.099
0.094
0.124
0.121
0.081
0.075
0.082
0.099
0.098
0.096
0.127
n5-02
0.134
0.099
0.094
0.124
0.121
0.081
0.075
0.082
0.099
0.098
0.096
0.127
n8-49
-7.5
-8.5
-9.8
-8.2
-9.1
-13.1
-9.2
-12.4
-15.1
-14.3
-15.3
-11.3
No.
E5-01
Name
Unit
Default Settings
2243
2244
2245
2246
2247
2248
2249
224A
224C
224D
224E
Voltage Class
400
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
37
45
55
75
90.00
110
132
160
200
220
300
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
37.00
45.00
55.00
75.00
90.00
110.00
132.00
160.00
200.00
250.00
300.00
E5-03
65.4
77.6
99.3
130.2
153.1
184.4
229.2
269.8
346.9
421.9
520.8
E5-04
E5-05
0.077
0.052
0.036
0.023
0.019
0.017
0.012
0.008
0.005
0.004
0.002
E5-06
mH
3.57
2.98
1.59
1.59
1.51
1.43
1.13
0.96
0.65
0.67
0.40
E5-07
mH
4.65
3.75
2.78
1.97
1.76
1.92
1.54
1.26
0.88
0.74
0.52
E5-09
mVs
/rad
531.6
530.6
515.2
515.2
538.3
590.9
548.2
603.9
556.8
593.1
495.4
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Minimum Output
Frequency
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.137
0.252
0.30
0.41
0.55
0.82
0.96
1.60
1.95
2.82
3.70
L3-24
0.124
0.188
0.186
0.184
0.205
0.250
0.244
0.336
0.327
0.379
0.414
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
587
Parameter List
No.
Name
Unit
n5-02
s
%
n8-49
Default Settings
0.124
0.188
0.186
0.184
0.205
0.250
0.244
0.336
0.327
0.379
0.414
-14.5
-13.2
-22.6
-11.9
-8.6
-14.8
-17.5
-12.5
-14.7
-5.1
-16.3
Table B.22 200 V, 1450 r/min Type Yaskawa SST4 Series IPM Motor
No.
E5-01
Name
Unit
Default Settings
2302
2303
2305
2306
2308
230A
230B
230D
230E
230F
2310
2312
2313
2314
2315
2316
Voltage Class
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
30
37
45
55
75
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15.0
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
1.77
3.33
5.94
9.48
14.17
20.42
27.92
39.6
54.2
68.3
75.2
102.0
131.3
160.4
191.7
257.3
E5-04
E5-05
3.154
1.835
0.681
0.308
0.405
0.278
0.180
0.098
0.073
0.055
0.048
0.034
0.023
0.016
0.012
0.007
E5-06
Motor d-Axis
Inductance (Ld)
mH
28.46
19.46
10.00
6.88
8.15
5.77
6.32
3.34
2.94
2.23
2.08
1.67
1.39
0.94
0.82
0.56
E5-07
Motor q-Axis
Inductance (Lq)
mH
39.29
25.89
15.20
9.25
10.76
8.60
8.80
4.61
3.65
2.85
2.66
2.04
1.73
1.22
1.06
0.76
E5-09
Motor Induction
Voltage Constant 1 (Ke)
mVs
/rad
268.8
256.9
271.9
260.2
286.8
314.9
300.8
292.3
305.1
297.6
355.8
355.4
324.0
302.4
337.2
323.4
E5-24
Motor Induction
mV/
Voltage Constant 2 (Ke) (r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Minimum Output
Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.0016
0.0022
0.0081
0.0133
0.0133
0.017
0.027
0.044
0.054
0.063
0.113
0.137
0.252
0.304
0.41
0.55
L3-24
Motor Acceleration
Time for Inertia
Calculations
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
0.083
0.079
0.118
0.105
0.157
0.156
0.172
0.169
n5-02
Motor Acceleration
Time
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
0.083
0.079
0.118
0.105
0.157
0.156
0.172
0.169
n8-49
-7.5
-9.4
-13.9
-10.0
-15.0
-17.9
-22.7
-20.5
-14.6
-16.4
-11.8
-10.5
-14.5
-17.4
-13.9
-17.5
588
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Unit
Default Settings
2332
2333
2335
2336
2338
233A
233B
233D
233E
233F
2340
Voltage Class
Rated Power
kW
400
400
400
400
400
400
400
400
400
400
400
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
Rated Speed
22
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
22.00
E5-03
0.91
1.67
3.02
4.74
7.08
10.21
13.96
20.5
27.1
34.2
37.6
E5-04
E5-05
12.616
7.340
2.724
1.232
1.509
1.112
0.720
0.393
0.291
0.220
0.192
E5-06
mH
113.84
77.84
40.00
27.52
31.73
23.09
25.28
13.36
11.77
8.94
8.32
E5-07
mH
157.16
103.56
60.80
37.00
40.88
34.39
35.20
18.44
14.60
11.40
10.64
E5-09
mVs
/rad
490.8
513.8
543.7
520.3
580.8
602.7
601.5
584.6
610.3
595.2
711.6
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
kgm2
0.0016
0.0022
0.0081
0.0133
0.0133
0.017
0.027
0.044
0.054
0.063
0.113
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
0.083
0.079
0.118
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
0.083
0.079
0.118
-9.5
-9.4
-13.7
-10.0
-12.9
-19.9
-22.8
-19.8
-14.5
-16.1
-11.8
C5-17
Motor Inertia
L3-24
n5-02
n8-49
No.
E5-01
Name
Unit
Default Settings
2342
2343
2344
2345
2346
2347
2348
2349
234A
234C
234D
Voltage Class
400
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
30
37
45
55
75
90
110
132
160
200
250
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
160.00
200.00
250.00
E5-03
50.9
65.4
80.2
96.1
129.2
153.1
191.7
226.0
268.8
331.3
422.9
E5-04
E5-05
0.136
0.091
0.064
0.048
0.028
0.024
0.015
0.011
0.007
0.006
0.003
E5-06
mH
6.68
5.30
3.76
3.09
2.24
2.20
1.34
1.23
0.92
0.84
0.61
E5-07
mH
8.16
6.80
4.88
4.75
3.03
3.23
2.16
1.67
1.30
1.25
0.89
E5-09
mVs
/rad
710.8
652.7
604.8
669.1
646.8
708.0
637.8
677.0
661.7
687.1
655.9
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.137
0.252
0.304
0.41
0.55
0.82
0.96
1.60
1.95
2.82
3.70
L3-24
0.105
0.157
0.156
0.172
0.169
0.210
0.201
0.279
0.281
0.325
0.341
n5-02
0.105
0.157
0.156
0.172
0.169
0.210
0.201
0.279
0.281
0.325
0.341
n8-49
-10.5
-15.6
-17.4
-21.7
-17.3
-19.6
-24.1
-15.1
-17.0
-19.8
-19.3
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
589
Parameter List
No.
Name
Unit
Default Settings
2402
2403
2405
2406
2408
240A
240B
240D
240E
240F
2410
2412
2413
2414
2415
2416
Voltage Class
Rated Power
kW
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
30
37
45
55
Rated Speed
75
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
1.77
3.44
5.94
9.17
14.79
20.21
27.40
39.0
55.9
65.4
77.0
103.5
126.0
153.1
188.5
260.4
E5-04
E5-05
2.680
1.520
1.071
0.542
0.362
0.295
0.162
0.115
0.083
0.065
0.052
0.035
0.026
0.019
0.013
0.009
E5-06
mH
30.55
15.29
17.48
11.98
8.60
9.54
5.31
4.44
3.50
2.92
2.55
2.03
1.59
1.24
0.98
0.70
E5-07
mH
42.71
24.28
22.51
15.51
10.69
13.84
8.26
5.68
4.23
3.79
3.22
2.46
1.92
1.64
1.37
0.97
E5-09
mVs
/rad
313.1
313.1
345.3
342.9
363.8
384.3
379.9
370.2
364.5
404.5
445.1
444.4
447.3
470.8
422.4
418.3
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
2.9
2.9
2.9
2.9
2.9
E1-09
C5-17
Motor Inertia
L3-24
n5-02
n8-49
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
0.027
0.044
0.054
0.063
0.113
0.137
0.252
0.304
0.410
0.55
0.82
0.080
0.081
0.078
0.088
0.066
0.070
0.085
0.071
0.061
0.089
0.090
0.122
0.119
0.132
0.145
0.159
0.080
0.081
0.078
0.088
0.066
0.070
0.085
0.071
0.061
0.089
0.090
0.122
0.119
0.132
0.145
0.159
-8.4
-11.0
-10.7
-10.7
-9.4
-22.5
-22.2
-16.7
-13.7
-15.2
-10.9
-9.8
-9.3
-11.5
-17.7
-17.1
kgm2
Table B.25 400 V, 1150 r/min Type Yaskawa SST4 Series IPM Motor
No.
E5-01
590
Name
Unit
Default Settings
2432
2433
2435
2436
2438
243A
243B
243D
243E
243F
2440
Voltage Class
400
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
22.00
E5-03
0.89
1.72
3.02
4.58
7.40
10.21
13.75
19.5
27.7
32.7
39.2
E5-04
E5-05
10.720
6.080
4.336
2.143
1.428
1.199
0.648
0.460
0.325
0.260
0.209
E5-06
mH
122.20
61.16
70.24
46.20
33.87
41.67
21.24
17.76
12.83
11.68
10.09
E5-07
mH
170.80
97.12
90.04
60.28
42.98
69.15
33.04
22.72
17.19
15.16
16.25
E5-09
mVs
/rad
626.1
626.1
703.1
727.6
699.0
861.5
759.7
740.4
716.6
809.1
786.2
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
C5-17
Motor Inertia
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
kgm2
0.0022
0.0042
0.0081
0.0133
0.0168
0.027
0.044
0.054
0.063
0.113
0.137
L3-24
0.080
0.081
0.078
0.088
0.066
0.070
0.085
0.071
0.061
0.089
0.090
n5-02
0.080
0.081
0.078
0.088
0.066
0.070
0.085
0.071
0.061
0.089
0.090
n8-49
-8.4
-11.0
-9.9
-9.0
-11.4
-23.2
-22.1
-16.7
-20.2
-15.2
-27.7
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Motor Code Selection
E5-01
Unit
Default Settings
2442
2443
2444
2445
2446
2447
2448
2449
244A
244C
Voltage Class
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
30
37
45
55
75
90k
110
132
160
200
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
160.00
200.00
E5-03
51.8
63.0
76.6
93.1
128.1
153.1
186.5
221.9
269.8
336.5
E5-04
E5-05
0.140
0.106
0.076
0.051
0.032
0.026
0.015
0.012
0.009
0.007
E5-06
mH
8.12
6.43
4.96
3.99
2.97
2.44
1.87
1.49
1.41
1.22
E5-07
mH
9.84
7.71
6.56
5.39
3.90
3.23
2.46
2.08
1.88
1.51
E5-09
mVs
/rad
888.8
857.7
941.6
853.8
829.6
835.6
833.4
848.6
889.1
915.0
E5-24
mV/
(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
kgm2
0.252
0.304
0.410
0.55
0.82
0.96
1.60
1.95
2.82
3.70
Motor Inertia
L3-24
0.122
0.119
0.132
0.145
0.159
0.155
0.211
0.214
0.256
0.268
n5-02
0.122
0.119
0.132
0.145
0.159
0.155
0.211
0.214
0.256
0.268
n8-49
-9.8
-10.2
-11.5
-16.0
-15.7
-15.7
-14.7
-16.5
-14.1
-10.4
Parameter List
C5-17
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
591
592
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Appendix: C
MEMOBUS/Modbus Communications
C.1
C.2
C.3
C.4
C.5
C.6
C.7
C.8
C.9
C.10
C.11
C.12
MEMOBUS/MODBUS CONFIGURATION...........................................................594
COMMUNICATION SPECIFICATIONS................................................................595
CONNECTING TO A NETWORK.........................................................................596
MEMOBUS/MODBUS SETUP PARAMETERS...................................................598
DRIVE OPERATIONS BY MEMOBUS/MODBUS................................................601
COMMUNICATIONS TIMING...............................................................................602
MESSAGE FORMAT............................................................................................603
MESSAGE EXAMPLES.......................................................................................605
MEMOBUS/MODBUS DATA TABLE..................................................................607
ENTER COMMAND..............................................................................................623
COMMUNICATION ERRORS..............................................................................624
SELF-DIAGNOSTICS...........................................................................................625
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
593
Slave (Drive)
594
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Communication
Parameters
RS-422, RS-485
Asynchronous (Start-stop synchronization)
Communication Speeds
1.2; 2.4; 4.8; 9.6; 19.2; 38.4; 57.6; 76.8; 115.2 kbps
Available
Data length
8-bit (fixed)
Parity
Select even, odd, or none
Stop bit
1-bit (fixed)
MEMOBUS/Modbus (using RTU mode only)
255 drives
MEMOBUS/Modbus
Communications
Protocol
Max Number of Slaves
Specifications
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
595
1.
With the power shut off, connect the communications cable to the drive and the master. Use terminals TB5 for
MEMOBUS/Modbus.
IG R+ R- S+ SS
S+
R
R+
IG
(TB5)
Send ()
Send (+)
Receive ()
Receive (+)
Shield Ground
2.
3.
4.
5.
6.
7.
Check or set the termination resistor selection at all slaves. Use the description in Network Termination on page
597 for slaves that are A1000 drives.
Switch the power on.
Set the parameters needed for serial communications (H5-01 through H5-12) using the digital operator.
Shut the power off and wait until the display on the digital operator goes out completely.
Turn the power back on.
The drive is now ready to begin communicating with the master.
n RS-485 Interface
PLC
R
R+
S
S+
IG
S
S+
R
R+
IG
S2
S
S+
R
R+
IG
S2
S
S+
R
R+
IG
S2
Drive
OFF
Drive
OFF
Drive
ON
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
n RS-422 Interface
PLC
R
R+
S
S+
IG
S
S+
R
R+
IG
S2
S
S+
R
R+
IG
S2
S
S+
R
R+
IG
S2
Drive
OFF
Drive
OFF
Drive
ON
u Network Termination
MEMOBUS/Modbus
Communications
The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in termination resistor that
can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the termination resistor
by setting DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not located at the network
line end.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
597
No.
Name
H5-01
Setting Range
0 to
FFH <1>
Default
1FH
Each slave drive must be assigned a unique slave address for serial communications to work. Setting H5-01 to any value
besides 0 assigns the drive its address in the network. Slave addresses do not need to be assigned in sequential order, but no
two drives may share the same address.
No.
H5-02
H5-02
0
1
2
3
4
Name
Communication Speed Selection
Communication Speed
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
Setting Range
0 to 5
H5-02
5
6
7
8
Default
3
Communication Speed
38400 bps
57600 bps
76800 bps
115200 bps
No.
H5-03
Name
Communication Parity Selection
Setting Range
0 to 2
Default
0
Setting Range
0 to 3
Default
3
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
Name
Stopping Method after CE
598
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Name
Communication Fault Detection Selection
Setting Range
0 or 1
Default
1
Setting 0: Disabled
If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered and
the drive will operate as determined by parameter H5-04.
Name
Drive Transmit Wait Time
Setting Range
5 to 65 ms
PLCDrive
DrivePLC
PLCDrive
Command message
Response message
Command message
24 bit length
Default
5 ms
Time
H5-06 setting
Name
RTS Control Selection
Setting Range
0 or 1
Default
1
Use this setting when using RS-485 signals for communications or when using the RS-422 signals for point-to-point
communications.
Setting 1: Enabled. RTS switches while sending.
Name
CE Detection Time
Setting Range
0.0 to 10.0 s
Default
2.0 s
MEMOBUS/Modbus
Communications
Name
Unit Selection for MEMOBUS/Modbus Register 0025H
Setting Range
0 or 1
Default
0
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
599
Name
Communications Enter Function Selection
Setting Range
0 or 1
Default
1
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
Name
Run Command Method Selection
Setting Range
0 or 1
Default
0
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive in the forward direction. Setting bit 1 will start and
stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive. Setting bit 1 changes the direction.
600
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Parameter
b1-01
b1-02
b1-15
b1-16
Name
Frequency Reference Selection 1
Run Command Selection 1
Frequency Reference Selection 2
Run Command Selection 2
Required Setting
2
2
2
2
MEMOBUS/Modbus
Communications
Refer to b1-01: Frequency Reference Selection 1 on page 162 and Refer to b1-02: Run Command Selection 1 on page
163 for details on external reference parameter selections. Refer to Setting 2: External Reference 1/2 Selection on page
250 for instructions on selecting external references 1 and 2.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
601
Command Type
1
Example
Control command (Run, Stop)
Set inputs/outputs
Read monitors and parameter values
Write parameters
H5-11 = 0: 50 ms
H5-11 = 1: 200ms <1>
200 ms to 2 s, depending on the number
of parameters that were changed <1>
5s
<1> If the drive receives command type 1 data during the minimum wait time, it will perform the command and then respond. However, if it receives
a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.
PLCDrive
DrivePLC
PLCDrive
Command message
Response message
Command message
24 bit length
Time
Master Send
Wait Time
A timer should be set in the master to check how long it takes for the slave drive(s) to respond to the master. If no response
is received within a certain amount of time, the master should try resending the message.
DrivePLC
PLCDrive
Command message
Response message
Command message
24 bit length
Time
H5-06
setting
602
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
SLAVE ADDRESS
FUNCTION CODE
DATA
ERROR CHECK
u Slave Address
The slave address in the message defines the note the message is sent to. Use addresses between 0 and FF (hex). If a message
with slave address 0 is sent (broadcast), the command from the master will be received by all slaves. The slaves do not provide
a response to a broadcast type message.
u Function Code
The three types of function codes are shown in the table below.
Function
Code
03H
08H
10H
Function Name
Read MEMOBUS/Modbus registers
Loopback test
Write to multiple MEMOBUS/Modbus registers
u Data
Configure consecutive data by combining the MEMOBUS/Modbus register address (test code in case of a loopback test) and
the data the register contains. The data length changes depending on the command details.
A drive MEMOBUS/Modbus register always has a data length of two bytes. Data written into drive registers must also always
have a length of two bytes. Register data read out from the drive will always consist of two bytes.
u Error Check
The drive uses a CRC-16 (cyclic redundancy check, checksum method) for checking data validity. Use the procedure described
below when calculating the CRC-16 checksum for command data or when verifying response data.
When the drive receives data, it calculates the CRC-16 checksum from the data and compares it to the CRC-16 value received
within the message. Both must match before a command is processed.
An initial value of FFFFH (i.e., all 16 bits equal 1) must be used for CRC-16 calculations in the MEMOBUS/Modbus protocol.
Calculate the CRC-16 checksum using the following steps:
1.
2.
3.
4.
5.
6.
7.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
603
MEMOBUS/Modbus
Communications
n Command Data
Description
Initial Value (FFFFH)
Address 02H
XOR w initial value
Shift 1
XOR w A001H
XOR result
Shift 2
XOR w A001H
XOR result
Shift 3
Shift 4
XOR w A001H
XOR result
Shift 5
Shift 6
XOR w A001H
XOR result
Shift 7
Shift 8
XOR w A001H
XOR result
Calculation
1111 1111 1111 1111
0000 0000 0000 0010
1111 1111 1111 1101
0111 1111 1111 1110
1010 0000 0000 0001
1101 1111 1111 1111
0110 1111 1111 1111
1010 0000 0000 0001
1100 1111 1111 1110
0110 0111 1111 1111
0011 0011 1111 1111
1010 0000 0000 0001
1001 0011 1111 1110
0100 1001 1111 1111
0010 0100 1111 1111
1010 0000 0000 0001
1000 0100 1111 1110
0100 0010 0111 1111
0010 0001 0011 1111
1010 0000 0000 0001
1000 0001 0011 1110
Overflow
0
1
0
1
0
1
Description
Function Code 03H
XOR w result
Shift 1
XOR w A001H
XOR result
Shift 2
XOR w A001H
XOR result
Shift 3
Shift 4
XOR w A001H
XOR result
Shift 5
Shift 6
XOR w A001H
XOR result
Shift 7
XOR w A001H
XOR result
Shift 8
XOR w A001H
XOR result
Calculation
0000 0000 0000 0011
1000 0001 0011 1101
0100 0000 1001 1110
1010 0000 0000 0001
1110 0000 1001 1111
0111 0000 0100 1111
1010 0000 0000 0001
1101 0000 0100 1110
0110 1000 0010 0111
0011 0100 0001 0011
1010 0000 0000 0001
1001 0100 0001 0010
0100 1010 0000 1001
0010 0101 0000 0100
1010 0000 0000 0001
1000 0101 0000 0101
0100 0010 1000 0010
1010 0000 0000 0001
1110 0010 1000 0011
0111 0001 0100 0001
1010 0000 0000 0001
1101 0001 0100 0000
1101 0001 0100 0000
CRC-16
D140H
Continue from here with next data.
Overflow
0
1
0
1
n Response Data
Perform a CRC-16 calculation on the response message data as described above as a validation check. The result should match
the CRC-16 checksum received within the response message.
604
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Upper
Lower
Upper
Lower
Upper
Lower
Upper
Lower
00H
00H
00H
00H
01H
F4H
AFH
82H
u Loopback Test
Function code 08H performs a loopback test that returns a response message with exactly the same content as the command
message. The response message can be used to check communications between the master and slave. User-defined test code
and data values can also be set.
The following table shows a message example when performing a loopback test with the slave 1 drive.
Response Message (normal)
Slave Address
01H
Function Code
08H
Upper
00H
Test Code
Lower
00H
Upper
A5H
Data
Lower
37H
Upper
DAH
CRC-16
Lower
8DH
MEMOBUS/Modbus
Communications
Command Message
Slave Address
01H
Function Code
08H
Upper
00H
Test Code
Lower
00H
Upper
A5H
Data
Lower
37H
Upper
DAH
CRC-16
Lower
8DH
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
605
00H
02H
04H
00H
01H
02H
58H
63H
39H
Upper
Lower
Upper
Lower
00H
02H
10H
08H
Note: Double the number of the data quantity for the number of bytes in the command message.
606
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
u Command Data
It is possible to both read and write command data.
Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers.
Contents
Reserved
Operation Commands and Multi-function Inputs
H5-12 = 0: Forward Run Command (0 = Stop, 1 = Forward Run)
bit 0
H5-12 = 1: Run Command (0 = Stop, 1 = Run)
H5-12 = 0: Reverse Run Command (0 = Stop, 1 = Reverse Run)
bit 1
H5-12 = 1: Forward/Reverse (0 = Forward, 1 = Reverse)
bit 2
bit 3
bit 4
0001H
bit 5
0002H
0003H
0004H
0005H
0006H
0007H
0008H
0009H
000AH
000BH to 000EH
bit 6
Multi-Function Input 3
bit 7
Multi-Function Input 4
bit 8
Multi-Function Input 5
bit 9
Multi-Function Input 6
bit A
Multi-Function Input 7
bit B
Multi-Function Input 8
bit C to F
Reserved
Frequency Reference Units are determined by parameter o1-03.
V/f Gain
Torque Reference/Torque Limit, 0.1% units, signed (Usable only if Torque Control is enabled)
Torque Compensation, 0.1% units, signed (Usable only if Torque Control is enabled)
PID Target, 0.01% units, signed
Analog Output Terminal FM Setting (10 V / 4000 H)
Analog Output Terminal AM Setting (10 V / 4000 H)
Settings for Multi-Function Digital Outputs
bit 0
Multi-Function Contact Output (terminal M1-M2)
bit 1
Multi-Function Contact (terminal M3-M4)
bit 2
Multi-Function Contact (terminal M5-M6)
bit 3 to 5
Reserved
bit 6
Enables the function in bit 7
bit 7
Fault Contact Output (terminal MA/MB-MC)
bit 8 to F
Reserved
Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000
Reserved
MEMOBUS/Modbus
Communications
Register No.
0000H
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
607
0010H to 001AH
001BH
001CH
001DH
Contents
Control Selection Setting
bit 0
Reserved
bit 1
PID Setpoint Input
bit 2
Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)
bit 3
Torque compensation input (enables the setting from MEMOBUS/Modbus)
bit 4 to B
Reserved
bit C
Enable Terminal S5 Input for Broadcast Data
bit D
Enable Terminal S6 Input for Broadcast Data
bit E
Enable Terminal S7 Input for Broadcast Data
bit F
Enable Terminal S8 Input for Broadcast Data
Reserved
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
Digital Output Option DO-A3 Output (Binary)
001EH to 001FH
Reserved
000FH
u Monitor Data
Monitor data can be read only.
Register No.
0020H
0021H
Contents
Drive Status 1
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to bit D
bit E
bit F
Fault Contents 1
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
608
During Run
During Reverse
Drive Ready
Fault
Data Setting Error
Multi-Function Contact Output (terminal M1-M2)
Multi-Function Contact (terminal M3-M4)
Multi-Function Contact (terminal M5-M6)
Reserved
ComRef status
ComCtrl status
Overcurrent (oC), Ground fault (GF)
Overvoltage (ov)
Drive Overload (oL2)
Overheat 1 (oH1), Drive Overheat Warning (oH2)
Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH)
Reserved
PID Feedback Loss (FbL / FbH)
EF to EF8: External Fault
CPFoo: Hardware Fault (includes oFx)
Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/
UL4)
PG Disconnected (PGo), PG Hardware Fault (PGoH), Overspeed (oS), Excessive Speed Deviation
(dEv)
Main Circuit Undervoltage (Uv)
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)
Output Phase Loss (LF), Input Phase Loss (PF)
MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
Operator Connection Fault (oPr)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Contents
0022H
0023H
Frequency Reference
0024H
0029H
002AH
002BH
Fault Contents 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
Alarm Contents 1
bit 0, 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Input Terminal Status
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to bit F
Reserved
Upper or lower limit error
Data conformity error
Writing to EEPROM
Reserved
<1>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
MEMOBUS/Modbus
Communications
0025H
0026H
0027H
0028H
609
002CH
002DH
002EH
002FH
0030H
0031H
0032H
0033H
0034H
0035H
0036H, 0037H
0038H
0039H
003AH
003BH, 003CH
003DH
003EH
003FH
0040H to 004AH
610
Contents
Drive Status 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
During Run
Zero Speed
Speed Agree
User Speed Agree
Frequency Detection 1
Frequency Detection 2
Drive Ready
During Undervoltage
During Baseblock
Frequency Reference from Operator Keypad
Run Command from Operator Keypad
Over/Undertorque 1, 2
Frequency Reference Loss
bit D
During Fault Restart
bit E
Fault
bit F
Communication Timeout
Output Terminal Status
bit 0
Multi-Function Contact Output (terminal M1-M2)
bit 1
Multi-Function Contact (terminal M3-M4)
bit 2
Multi-Function Contact (terminal M5-M6)
bit 3 to 6
Reserved
bit 7
Fault Contact Output (terminal MA/MB-MC)
bit 8 to F
Reserved
Reserved
Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
Reserved
DC Bus Voltage, 1 Vdc units
Torque Reference (U1-09), 1% units
Reserved
Product Code 1 [ASCII], Product Type (A0 for A1000)
Product Code 2 [ASCII], Region Code
Reserved
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
PID Input, 0.1% units, signed, 100% / max. output frequency
PID Output, 0.1% units, signed, 100% / max. output frequency
Reserved
Communications Error Contents <3>
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to bit F
Reserved
Output Frequency
r/min <4>
0.01% units
Used for various monitors U1-oo. Refer to U: Monitors on page 548 for parameter details.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
004CH to 007EH
007FH
0080H to 0097H
0098H
0099H
009AH
009BH
009CH to 00AAH
00ABH
00ACH
00ADH
00AEH, 00AFH
During Run
During Zero Speed
During Reverse Run
During Fault Reset Signal Input
During Speed Agree
Drive Ready
Alarm
Fault
bit 8
bit 9
bit A
bit B
bit E
bit F
Used for various monitors U1-oo, U4-oo, U5-oo and U6-oo. Refer to U: Monitors on page 548 for parameter details.
Alarm Code, Refer to Alarm Register Contents on page 622 for alarm codes.
Used for monitors U2-oo, U3-oo. Refer to U: Monitors on page 548 for parameter details and Refer to Fault Trace
Contents on page 620 for register value descriptions.
High Word of Accumulated Operation Time Monitor, 10 h units (U4-01)
Low Word of Accumulated Operation Time Monitor, 1 h units (U4-01)
High Word of Cooling Fan Operation Time Monitor (U4-03)
Low Word of Cooling Fan Operation Time Monitor (U4-03)
Reserved
Drive Rated Current
<2>
Reserved
Register contains ASCII code of the option card.
DI-A3 = 0x01
DO-A3 = 0x02
AI-A3 = 0x03
AO-A3 = 0x04
PG-B3 = 0x11
PG-X3 = 0x12
Communication Option: Register contains ASCII code of 1st and 3rd digit of the option card type
number.
Example: Register value is 5343H for SC if a SI-C3 option card is installed.
00B0H
00B1H
00B2H
00B3H
Reserved
Option Code Connected to CN5-B
Option Code Connected to CN5-C
00B4H
Reserved
00B5H
00B6H
00B7H
00B8H
00B9H to 00BEH
00BFH
Frequency Reference
MEMOBUS/Modbus
Communications
004BH
Contents
Drive status (U1-12)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
<4>
0.01% units
Reserved
Lists the last two digits of operation error code oPEoo.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
611
00C0H
00C1H
00C2H
612
Contents
Fault Contents 3
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Fault Contents 4
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Fault Contents 5
bit 0
bit 1
bit 2, 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B to E
bit F
Undervoltage (Uv1)
Control Power Supply Undervoltage (Uv2)
Soft Charge Circuit Fault (Uv3)
IGBT Short Circuit (SC)
Ground Fault (GF)
Overcurrent (oC)
Overvoltage (ov)
Heatsink Overheat (oH)
Heatsink Overheat (oH1)
Motor Overload (oL1)
Drive Overload (oL2)
Overtorque Detection 1 (oL3)
Overtorque Detection 2 (oL4)
Dynamic Braking Transistor Fault (rr)
Braking Resistor Overheat (rH)
External Fault at input terminal S3 (EF3)
External Fault at input terminal S4 (EF4)
External Fault at input terminal S5 (EF5)
External Fault at input terminal S6 (EF6)
External Fault at input terminal S7 (EF7)
External Fault at input terminal S8 (EF8)
Cooling Fan Error (FAn)
Overspeed (os)
Excessive Speed Deviation (dEv)
PG Disconnected (PGo)
Input Phase Loss (PF)
Output Phase Loss (LF)
Motor Overheat (PTC input) (oH3)
Digital Operator Connection Fault (oPr)
EEPROM Write Error (Err)
Motor Overheat Fault (PTC input) (oH4)
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Reserved
Control Fault (CF)
Zero Servo Fault (SvE)
Option External Fault (EF0)
PID Feedback Loss (FbL)
Undertorque Detection 1 (UL3)
Undertorque Detection 2 (UL4)
High Slip Braking Overload (oL7)
Reserved
Hardware Fault (includes oFx)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
00C3H
00C4H
00C5H
00C6H
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6, 7
bit 8
bit 9 to B
bit C
bit D
bit E
bit F
Fault Contents 8
bit 0
bit 1
bit 2
bit 3 to 9
bit A
bit B to D
bit E
bit F
Fault Contents 9
bit 0
bit 1 to F
Reserved
Reserved
Z Pulse Fall Detection (dv1)
Z Pulse Noise Fault Detection (dv2)
Inversion Detection (dv3)
Inversion Prevention Detection (dv4)
Current Imbalance (LF2)
Pullout Detection (STo)
PG Hardware Fault (PGoH)
SI-T3 Watchdog Error (E5)
Reserved
Too many speed search restarts (SEr)
Reserved
PID Feedback Loss (FbH)
External Fault 1, input terminal S1 (EF1)
External Fault 2, input terminal S2 (EF2)
Mechanical Weakening Detection 1 (oL5)
Mechanical Weakening Detection 2 (UL5)
Current Offset Fault (CoF)
Reserved
DriveWorksEZ Fault (dWFL)
Reserved
Output Voltage Detection Fault (voF)
Braking Resistor Fault (rF)
Braking Transistor Overload Fault (boL)
Motor Overheat (NTC Input) (oH5)
Reserved
Node Setup Fault (nSE)
Thermistor Disconnect (THo)
Reserved
Polarity Judge Timeout (dv7)
Reserved
Power Unit Output Phase Loss 3 (LF3)
Current Unbalance (UnbC)
Gate Drive Board Undervoltage (Uv4)
Reserved
MEMOBUS/Modbus
Communications
00C7H
Contents
Fault Contents 6
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B to F
Fault Contents 7
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
613
00C8H
00C9H
00CAH
614
Contents
Alarm Contents 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Alarm Contents 3
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Alarm Contents 4
bit 0
bit 1
bit 2 to 5
bit 6
bit 7
bit 9
bit A
bit B to F
Undervoltage (Uv)
Overvoltage (ov)
Heatsink Overheat (oH)
Drive Overheat (oH2)
Overtorque 1 (oL3)
Overtorque 2 (oL4)
Run Commands Input Error (EF)
Drive Baseblock (bb)
External Fault 3, input terminal S3 (EF3)
External Fault 4, input terminal S4 (EF4)
External Fault 5, input terminal S5 (EF5)
External Fault 6, input terminal S6 (EF6)
External Fault 7, input terminal S7 (EF7)
External Fault 8, input terminal S8 (EF8)
Cooling Fan Error (FAn)
Overspeed (oS)
Excessive Speed Deviation (dEv)
PG Disconnected (PGo)
Digital Operator Connection Fault (oPr)
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Serial Communication Transmission Error (CALL)
Motor Overload (oL1)
Drive Overload (oL2)
Reserved
Option Card External fault (EF0)
Motor 2 Switch command input during run (rUn)
Reserved
Serial Communication Transmission Error (CALL)
Undertorque Detection 1 (UL3)
Undertorque Detection 2 (UL4)
MEMOBUS/Modbus Test Mode Fault (SE)
Reserved
Motor Overheat 1 (PTC Input) (oH3)
Reserved
PID Feedback Loss (FbL)
PID Feedback Loss (FbH)
Drive Disabled (dnE)
PG Disconnected (PGo)
Reserved
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
00CBH
Contents
Alarm Contents 5
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
00CCH
00CDH to 00CFH
00D0H
bit D
bit E, F
Alarm Contents 6
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5 to 6
bit 7
bit 8
bit 9 to B
bit C
bit D to F
Reserved
CPF Contents 1
bit 0, 1
bit 2
bit 3
bit 4, 5
bit 6
bit 7
bit 8
bit 9, A
bit B
bit C
bit D
bit E
bit F
Reserved
A/D Conversion Error (CPF02)
PWM Data Fault (CPF03)
Reserved
EEPROM Memory Data Error (CPF06)
Terminal Board Connection Error (CPF07)
EEPROM Serial Communications Fault (CPF08)
Reserved
RAM Fault (CPF11)
FLASH Memory Fault (CPF12)
Watchdog Circuit Exception (CPF13)
Control Circuit Fault (CPF14)
Reserved
MEMOBUS/Modbus
Communications
Register No.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
615
00D1H
00D2H
00D3H to 00D7H
00D8H
00D9H
00DAH to 00DBH
616
Contents
CPF Contents 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
bit 0
bit 1
bit 2
bit 3
bit 4 to 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
oFA0x Contents (CN5-A)
oFA0x Contents (CN5-A)
bit 0
bit 1
bit 2
bit 3, 4
bit 5
bit 6
bit 7 to F
oFA1x Contents (CN5-A)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
00DBH
00DCH
00DDH
bit D
bit E, F
oFb0x Contents (CN5-B)
bit 0
bit 1
bit 2
bit 3, 4
bit 5
bit 6
bit 7 to F
oFb1x Contents (CN5-B)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved
MEMOBUS/Modbus
Communications
00DEH to 00DFH
Contents
oFA3x Contents (CN5-A)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
617
00E0H
00E1H
00E2H
00E3H, 00E4H
618
Contents
oFb3x Contents (CN5-B)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
oFC0x Contents (CN5-C)
bit 0
bit 1
bit 2
bit 3, 4
bit 5
bit 6
bit 7 to F
oFC1x Contents (CN5-C)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
00E5H
00E6H to 00FFH
Contents
oFC3x Contents (CN5-C)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
Reserved
<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW. Refer to Power Ratings on page 455.
<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04, E4-04, or E5-05 depending on the motor being used.
<5> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
u Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
0001H
0002H
Contents
Digital Input Command
bit 0
bit 1
bit 2, 3
bit 4
bit 5
bit 6 to B
bit C
bit D
bit E
bit F
Frequency Reference
MEMOBUS/Modbus
Communications
Register No.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
619
620
Fault Name
Undervoltage (Uv1)
Control Power Supply Undervoltage (Uv2)
Soft Charge Circuit Fault (Uv3)
Fault Code
0037H
0038H
003BH
0041H
0042H
0043H
0044H
0045H
0046H
0047H
0048H
0049H
004DH
004EH
004FH
0050H
0052H
0053H
005BH <1>
005FH
0060H
0061H
0083H
0084H
0087H
0088H
0089H
008CH
008DH
008EH
008FH
0091H
0092H
0093H
0094H
0095H
0096H
0097H
0098H
0099H
009AH
009BH
009CH
009DH
009EH
Fault Name
Pullout Detection (Sto)
PG Hardware Fault (PGoH)
Too Many Speed Search Restarts (SEr)
PID Feedback Loss (FbH)
External Fault 1, Input Terminal S1 (EF1)
External Fault 2, Input Terminal S2 (EF2)
Mechanical Weakening Detection 1 (oL5)
Mechanical Weakening Detection 2 (UL5)
Current Offset Fault (CoF)
PLC Detection Error 1 (PE1)
PLC Detection Error 2 (PE2)
DriveWorksEZ Fault (dWFL)
Output Voltage Detection Fault (voF)
Braking Resistor Transistor Fault (rF)
Braking Transistor Overload Fault (boL)
Motor Overheat (NTC Input) ( oH5)
Node Setup Fault (nSE)
Thermistor Disconnect (THo)
Polarity Judge Timeout (dv7)
Power Unit Output Phase Loss 3 (LF3)
Current Unbalance (UnbC)
Power Supply Module Undervoltage (Uv4)
A/D Conversion Error (CPF02)
PWM Data Fault (CPF03)
EEPROM Memory Data Error (CPF06)
Terminal Board Connection Error (CPF07)
EEPROM Serial Communication Fault (CPF08)
RAM Fault (CPF11)
Flash Memory Circuit Exception (CPF12)
Watchdog Circuit Exception (CPF13)
Control Circuit Fault (CPF14)
Clock Fault (CPF16)
Timing Fault (CPF17)
Control Circuit Fault (CPF18)
Control Circuit Fault (CPF19)
Hardware Fault at Power Up (CPF20)
Hardware Fault at Communication Start Up (CPF21)
A/D Conversion Fault (CPF22)
PWM Feedback Fault (CPF23)
Drive Unit Signal Fault (CPF24)
Terminal Board is Not Properly Connected. (CPF25)
ASIC BB Circuit Error (CPF26)
ASIC PWM Setting Register Error (CPF27)
ASIC PWM Pattern Error (CPF28)
ASIC On-delay Error (CPF29)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Fault Name
ASIC BBON Error (CPF30)
ASIC Code Error (CPF31)
ASIC Start-up Error (CPF32)
Watch-dog Error (CPF33)
ASIC Power/Clock Error (CPF34)
External A/D Converter Error (CPF35)
Control Circuit Error (CPF40)
Control Circuit Error (CPF41)
Control Circuit Error (CPF42)
Control Circuit Error (CPF43)
Control Circuit Error (CPF44)
Control Circuit Error (CPF45)
Option Compatibility Error (oFA00)
Option Not Properly Connected (oFA01)
0103H
0106H
0107H
0111H
0112H
0113H
0114H
0115H
0116H
0117H
0118H
0131H
0132H
0133H
0134H
0135H
0136H
0137H
0138H
0139H
013AH
013BH
Fault Code
013CH
013DH
013EH
0201H
0202H
0205H
0206H
0210H
0211H
0212H
0213H
0214H
0215H
0216H
0217H
0231H
0232H
0233H
0234H
0235H
0236H
0237H
0238H
0239H
023AH
023BH
023CH
023DH
023EH
0300H
0301H
0302H
0305H
0306H
Fault Name
Drive Timeout Waiting for Response (oFA41)
Control Response Selection 2 Error (oFA42)
Control Response Selection Error (oFA43)
Option Connection Error (oFb01)
Same Type of Option Card Already Connected
(oFb02)
A/D Conversion Error (oFb05)
Option Response Error (oFb06)
Option RAM Fault (oFb10)
Option Operation Mode Fault (SLMOD) (oFb11)
Drive Receive CRC Error (oFb12)
Drive Receive Frame Error (oFb13)
Drive Receive Abort Error (oFb14)
Option Receive CRC Error (oFb15)
Option Receive Frame Error (oFb16)
Option Receive Abort Error (oFb17)
Comm. ID Error (oFb30)
Model Code Error (oFb31)
Sumcheck Error (oFb32)
Comm. option Timeout Waiting for Response (oFb33)
MEMOBUS Timeout (oFb34)
Drive Timeout Waiting for Response (oFb35)
CI Check Error (oFb36)
Drive Timeout Waiting for Response (oFb37)
Control Command Selection Error (oFb38)
Drive Timeout Waiting for Response (oFb39)
Control Response Selection 1 Error (oFb40)
Drive Timeout Waiting for Response (oFb41)
Control Response Selection 2 Error (oFb42)
Control Response Selection Error (oFb43)
Option Compatibility Error (oFC00)
Option Not Properly Connected (oFC01)
Same Type of Option Card Already Connected
(oFC02)
A/D Conversion Error (oFC05)
Option Response Error (oFC06)
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
621
Fault Name
Undervoltage (Uv)
Overvoltage (ov)
Heatsink Overheat (oH)
Drive Overheat (oH2)
Overtorque 1 (oL3)
Overtorque 2 (oL4)
Run commands input error (EF)
Drive Baseblock (bb)
External Fault 3, input terminal S3 (EF3)
External Fault 4, input terminal S4 (EF4)
Fault Code
0022H
0027H
0028H
002AH
002BH
0031H
0032H
0033H
0034H
0035H
Fault Name
Motor Overheat (oH3)
PID Feedback Loss (FbL)
PID Feedback Loss (FbH)
Drive Disabled (dnE)
PG Disconnected (PGo)
SI-T3 Watchdog Error (E5)
SI-T3 Station Address Setting Error (AEr)
SI-T3 Comm. Cycle Setting Error (CyC)
High Current Alarm (HCA)
Cooling Fan Maintenance Time (LT-1)
0036H
0038H
0039H
003AH
003BH
003CH
003DH
003EH
003FH
0040H
0041H
0042H
0043H
0044H
0045H
0048H
0049H
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
622
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Description
Simultaneously writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM. Parameter
changes remain after cycling power.
Writes data in the RAM only. Parameter changes are lost when the drive is shut off.
Note: The EEPROM can only be written to 100,000 times, so it is recommended to limit the number of times writing to the EEPROM. The Enter
command registers are write-only and if these registers are read, the register address will be invalid (Error code: 02H). An Enter command is
not required when reference or broadcast data are sent to the drive.
MEMOBUS/Modbus
Communications
H5-11 Settings
H5-11 = 0
Drive being replaced
G7, F7
How parameter settings are enabled When the Enter command is received from the master.
Upper/lower limit check is performed, taking the settings
Upper/lower limit check
of related parameters into account.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
623
Error Code
01H
02H
03H
21H
22H
23H
24H
624
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
C.12 Self-Diagnostics
C.12 Self-Diagnostics
The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosis
function, use the following procedure.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or
serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply
is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least
one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
1.
2.
3.
4.
5.
6.
7.
MEMOBUS/Modbus
Communications
When a fault occurs, the drive will display CE on the keypad display.
8. Turn off the power supply.
9. Remove the wire jumpers from terminal R+, R-, S+, S-, and S6-SC. Reset jumper S3 to its original position and set
terminal S6 to its original function.
10.Return to normal operation.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
625
C.12 Self-Diagnostics
626
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Appendix: D
Standards Compliance
This appendix explains the guidelines and criteria for maintaining CE and UL standards.
D.1
D.2
D.3
D.4
SECTION SAFETY...............................................................................................628
EUROPEAN STANDARDS..................................................................................630
UL AND CSA STANDARDS................................................................................638
SAFE DISABLE INPUT FUNCTION....................................................................651
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
627
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or
shields before operating the drives and run the drives according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching
any components.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work
on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
628
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
NOTICE
Standards Compliance
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded wire for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires
and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Carefully review instruction manual TOBPC72060000 when connecting a braking option to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting other devices.
Failure to comply could result in damage to the drive.
D
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
629
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in business
and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics
manufacturers, and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
Low Voltage Directive: 2006/95/EC
EMC Guidelines: 2004/108/EC
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying
the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE
standards. After setting up the device, verify that conditions meet European standards.
Note: 600 V class drives (models CIMR-Ao5oooooo) are not compliant with European Standards.
n Area of Use
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC664.
Manufacturer: Bussmann
Model
630
2A0004
FWH-70B
70
2A0006
FWH-70B
70
2A0008
FWH-70B
70
2A0010
FWH-70B
70
2A0012
FWH-70B
70
2A0018
FWH-90B
90
2A0021
FWH-90B
90
2A0030
FWH-100B
100
2A0040
FWH-200B
200
2A0056
FWH-200B
200
2A0069
FWH-200B
200
2A0081
FWH-300A
300
2A0110
FWH-300A
300
2A0138
FWH-350A
350
2A0169
FWH-400A
400
2A0211
FWH-400A
400
2A0250
FWH-600A
600
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Manufacturer: Bussmann
Model
FWH-700A
700
2A0360
FWH-800A
800
2A0415
FWH-1000A
1000
FWH-40B
40
4A0004
FWH-50B
50
4A0005
FWH-70B
70
4A0007
FWH-70B
70
4A0009
FWH-90B
90
4A0011
FWH-90B
90
4A0018
FWH-80B
80
4A0023
FWH-100B
100
4A0031
FWH-125B
125
4A0038
FWH-200B
200
4A0044
FWH-250A
250
4A0058
FWH-250A
250
4A0072
FWH-250A
250
4A0088
FWH-250A
250
4A0103
FWH-250A
250
4A0139
FWH-350A
350
4A0165
FWH-400A
400
4A0208
FWH-500A
500
4A0250
FWH-600A
600
4A0296
FWH-700A
700
4A0362
FWH-800A
800
4A0414
FWH-800A
800
4A0515
FWH-1000A
1000
4A0675
FWH-1200A
1200
4A0930
FWH-1200A
1200
4A1200
FWH-1600A
1600
5A0003 <1>
FWP-50B
50
5A0004 <1>
FWP-50B
50
5A0006 <1>
FWP-60B
60
5A0009 <1>
FWP-60B
60
5A0011 <1>
FWP-70B
70
5A0017 <1>
FWP-100B
100
5A0022 <1>
FWP-100B
100
5A0027 <1>
FWP-125A
125
5A0032 <1>
FWP-125A
125
5A0041 <1>
FWP-175A
175
5A0052 <1>
FWP-175A
175
5A0062 <1>
FWP-250A
250
5A0077 <1>
FWP-250A
250
5A0099 <1>
FWP-250A
250
5A0125 <1>
FWP-350A
350
5A0145 <1>
FWP-350A
350
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Standards Compliance
D
631
Manufacturer: Bussmann
Model
5A0192 <1>
FWP-600A
600
5A0242 <1>
FWP-600A
600
<1> 600 V class drives are not compliant with European Standards.
n Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your Yaskawa representative for instructions.
Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive
also comply with EMC guidelines.
1.
2.
3.
4.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
Place the drive and EMC noise filter in the same enclosure.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
B
A
U/T1
C
U
V/T2
W/T3
A Drive
B 10 m max cable length between
drive and motor
C Motor
D Metal conduit
E Ground wire should be as short as
possible.
5.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
WARNING! Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models CIMR-Ao4A0414 to 4A1200, IEC
61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing
conductor, or a protective earthing conductor with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to
comply may result in death or serious injury.
632
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Connect a DC link choke to minimize harmonic distortion. Refer to DC Link Chokes for EN 61000-3-2
Compliance on page 637.
Standards Compliance
6.
D
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
633
D
B
J
B
I
H
G
A Make sure the ground wire is
grounded
B Grounding surface (remove any
paint or sealant)
C Metal plate
D Enclosure panel
E Drive
F Motor cable (braided shield cable,
max. 10 m)
G Motor
H Cable shield ground
I Cable clamp
J Ground plate (scrape off any
visible paint)
K EMC noise filter
Figure D.4 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)
634
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
n EMC Filters
Install the drive with the EMC filters listed below to comply with the EN61800-3 requirements.
Table D.2 EN61800-3 Filters
Filter Data (Manufacturer: Schaffner)
Model CIMR-Ao
Type
Weight (lb)
Dimensions
[W x D x H] (in)
Y x X (in)
Figure
FS5972-10-07
10
2.6
4.5 12.3
FS5972-18-07
18
2.9
4.5 12.3
2A0008
2A0010
2A0012
2A0018
2A0021
FS5972-35-07
35
4.6
6.9 13.2
FS5972-60-07
60
8.8
8.1 15.4
FS5972-100-35
100
7.5
2.6 10.0
FS5972-170-40
170
13.2
4.0 14.4
FS5972-250-37
250
25.8
3.5 19.6
FS5972-410-99
410
23.1
9.3 4.7
FS5972-600-99
600
24.3
9.3 4.7
2A0030
2A0040
2A0056
2A0069
2A0081
2A0110
2A0138
2A0169
2A0211
2A0250
2A0312
2A0360
2A0415
FS5972-10-07
10
2.4
4.5 12.3
FS5972-18-07
18
3.7
4.5 12.3
4A0007
4A0009
4A0011
4A0018
4A0023
FS5972-35-07
35
4.6
6.9 13.2
FS5972-60-07
60
8.8
8.0 15.4
FS5972-100-35
100
7.5
2.6 10.0
FS5972-170-35
170
10.4
4.0 14.4
FS5972-250-37
250
25.8
3.5 19.6
4A0031
4A0038
4A0044
4A0058
4A0072
4A0088
4A0103
4A0139
4A0208
Standards Compliance
4A0165
D
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
635
Type
Weight (lb)
Dimensions
[W x D x H] (in)
Y x X (in)
FS5972-410-99
400
23.1
9.3 4.7
FS5972-600-99
600
24.3
9.3 4.7
4A0675
FS5972-800-99
800
69.4
10.8 8.3
4A0930
FS5972-600-99 <1>
600
24.3
9.3 4.7
4A1200
FS5972-800-99 <1>
800
69.4
10.8 8.3
Figure
4A0250
4A0296
4A0362
4A0414
4A0515
Y
W
H
X
W
Y
D
D
Figure 2
Figure 1
W
Figure 3
636
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
DC Link Chokes
Model
200 V Three-Phase Units
Rating
UZDA-B
5.4 A
8 mH
UZDA-B
3.2 A
28 mH
Standards Compliance
Note: Contact Yaskawa for information about DC link chokes for other models.
D
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
637
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described
below must be met to maintain compliance when using this drive in combination with other equipment:
n Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
2A0012
2A0018
638
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
Terminal
B1, B2
14 to 10
10 <1>
14 to 10
12
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
10 <1>
14 to 10
10
12 to 10
10
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
10 <1>
14 to 10
Screw
Size
Tightening Torque
Nm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
2A0021
2A0030
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
10
12 to 10
10
12 to 10
, +1, +2
12 to 10
B1, B2
14 to 10
10 <1>
12 to 10
10 to 6
10 to 6
, +1, +2
10 to 6
Terminal
B1, B2
2A0040
Screw
Size
Tightening Torque
Nm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M6
4 to 6
(35.4 to 53.1)
14 to 10
8 <1>
10 to 8
8 to 6
8 to 6
, +1, +2
B1, B2
12 to 10
8 <1>
10 to 8
6 to 4
6 to 4
, +1, +2
6 to 4
B1, B2
10 to 6
M5
2 to 2.5
(17.7 to 22.1)
8 to 6
M6
4 to 6
(35.4 to 53.1)
4 to 3
4 to 3
M8
9 to 11
(79.7 to 97.4)
, +1, +2
4 to 3
B1, B2
8 to 6
M5
2 to 2.5
(17.7 to 22.1)
6 to 4
M6
4 to 6
(35.4 to 53.1)
3 to 2
3 to 2
M8
9 to 11
(79.7 to 97.4)
, +1, +2
3 to 2
B1, B2
M5
2 to 2.5
(17.7 to 22.1)
6 to 4
M6
4 to 6
(35.4 to 53.1)
1/0
3 to 1/0
1/0
3 to 1/0
, +1
2 to 1/0
M8
B1, B2
6 to 1/0
9 to 11
(79.7 to 97.4)
6 to 4
2/0
1 to 2/0
2/0
1 to 2/0
, +1
1/0 to 3/0
M10
18 to 23
(159 to 204)
B1, B2
4 to 2/0
M8
9 to 11
(79.7 to 97.4)
4/0
2/0 to 4/0
4/0
3/0 to 4/0
, +1
1 to 4/0
M10
+3
1/0 to 4/0
18 to 23
(159 to 204)
4 to 2
2A0056
2A0069
2A0081
2A0110 <2>
2A0138 <2>
2A0169 <2>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Standards Compliance
Model
CIMR-Ao
D
639
2A0211 <2>
2A0250 <2>
2A0312 <2>
2A0360 <2>
2A0415 <2>
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
1/0 2P
1/0 to 2/0
Terminal
Screw
Size
Tightening Torque
Nm (lb.in.)
M10
18 to 23
(159 to 204)
M12
32 to 40
(283 to 354)
1/0 2P
1/0 to 2/0
, +1
1 to 4/0
+3
1/0 to 4/0
4 to 1/0
3/0 2P
3/0 to 300
3/0 2P
3/0 to 300
, +1
3/0 to 300
+3
2 to 300
M10
18 to 23
(159 to 204)
3 to 300
M12
32 to 40
(283 to 354)
4/0 2P
3/0 to 300
3/0 2P
3/0 to 300
M12
32 to 40
(283 to 354)
, +1
3/0 to 300
+3
3/0 to 300
M10
18 to 23
(159 to 204)
2 to 300
M12
32 to 40
(283 to 354)
250 2P
4/0 to 600
4/0 2P
4/0 to 600
M12
32 to 40
(283 to 354)
, +1
250 to 600
+3
3/0 to 600
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
350 2P
250 to 600
300 2P
300 to 600
M12
32 to 40
(283 to 354)
, +1
300 to 600
+3
3/0 to 600
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
<1> When installing an EMC filter, additional measures must be taken to comply with IEC61800-5-1. Refer to EMC Filter Installation on page 632
for details.
<2> Drive models CIMR-Ao2A0110 to 2A0415 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
640
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
14
14 to 10
14
4A0002
4A0004
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
4A0005
4A0007
4A0009
4A0011
Terminal
12
14 to 12
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
10
14 to 10
12
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
4A0018
4A0023
14 to 10
10
14 to 10
10
12 to 6
10
12 to 6
, +1, +2
12 to 6
B1, B2
12 to 10
10
14 to 10
10
10 to 6
10
10 to 6
, +1, +2
12 to 6
B1, B2
12 to 10
10
12 to 10
Screw
Size
Tightening Torque
Nm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M5
2 to 2.5
(17.7 to 22.1)
8 to 6
10 to 6
, +1, +2
10 to 6
B1, B2
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
10 to 8
M6
4 to 6
(35.4 to 53.1)
8 to 6
8 to 6
M5
2 to 2.5
(17.7 to 22.1)
, +1, +2
B1, B2
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
10 to 6
M6
4 to 6
(35.4 to 53.1)
6 to 4
6 to 4
M6
4 to 6
(35.4 to 53.1)
, +1, +2
6 to 4
B1, B2
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
8 to 6
M6
4 to 6
(35.4 to 53.1)
6 to 4
6 to 4
, +1
6 to 1
M8
B1, B2
8 to 4
9 to 11
(79.7 to 97.4)
8 to 6
4A0031
4A0038
4A0044
4A0058 <1>
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Standards Compliance
Recomm. Gauge
AWG, kcmil
Model CIMR-Ao
D
641
Wire Range
AWG, kcmil
4 to 3
4 to 3
, +1
4 to 1
B1, B2
6 to 3
3 to 1/0
3 to 1/0
, +1
3 to 1/0
+3
6 to 1/0
6 to 4
1/0
2 to 1/0
2 to 1/0
, +1
3 to 1/0
+3
4 to 1/0
Model CIMR-Ao
4A0072 <1>
4A0088 <1>
4A0103 <1>
4A0139 <1>
4A0165 <1>
4A0208 <1>
4A0250 <1>
4A0296 <1>
4A0362 <1>
642
Terminal
6 to 4
3/0
1/0 to 4/0
2/0
1/0 to 4/0
, +1
1/0 to 4/0
+3
3 to 4/0
4/0
3/0 to 4/0
4/0
3/0 to 4/0
,+1
1 to 4/0
+3
1/0 to 4/0
4 to 2
300
2 to 300
300
2 to 300
,+1
1 to 250
+3
3 to 3/0
4 to 300
Screw
Size
Tightening Torque
Nm (lb.in.)
M8
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M12
32 to 40
(283 to 354)
400
1 to 600
400
1/0 to 600
,+1
3/0 to 600
+3
1 to 325
2 to 350
500
2/0 to 600
500
2/0 to 600
,+1
3/0 to 600
+3
1 to 325
M10
18 to 23
(159 to 204)
2 to 350
M12
32 to 40
(283 to 354)
4/0 2P
3/0 to 600
4/0 2P
3/0 to 600
M12
32 to 40
(283 to 354)
,+1
4/0 to 600
+3
3/0 to 600
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Wire Range
AWG, kcmil
300 2P
4/0 to 300
Model CIMR-Ao
4A0414 <1>
<2>
Terminal
300 2P
4/0 to 300
,+1
3/0 to 300
+3
3/0 to 300
1 to 3/0
3/0 4P
3/0 to 300
4/0 4P
3/0 to 300
1/0 to 300
,+1
+3
4A0675 <1>
4A0930 <1>
4A1200 <1>
<2>
<2>
<2>
1/0 to 300
1/0
1/0 to 300
300 4P
4/0 to 300
300 4P
4/0 to 300
,+1
1/0 to 300
+3
1/0 to 300
2/0
2/0 to 300
4/0 4P2
3/0 to 300
4/0 4P2
3/0 to 300
,+1
4/0 to 300
+3
4/0 to 300
3/0
3/0 to 250
300 4P2
4/0 to 300
300 4P2
4/0 to 300
250 to 300
4/0 to 300
4/0
4/0 to 250
,+1
+3
Screw
Size
Tightening Torque
Nm (lb.in.)
M12
32 to 40
(283 to 354)
M12
32 to 40
(283 to 354)
M12
32 to 40
(283 to 354)
M12
32 to 40
(283 to 354)
M12
32 to 40
(283 to 354)
Standards Compliance
<1> Drive models CIMR-Ao4A0058 to 4A1200 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
<2> When installing an EMC filter, additional measures must be taken to comply with IEC61800-5-1. Refer to EMC Filter Installation on page 632
for details.
D
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
643
Wire Range
AWG, kcmil
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
14 to 10
Model CIMR-Ao
5A0003
5A0004
5A0006
5A0009
Terminal
10
14 to 10
14
14 to 10
14
14 to 10
, +1, +2
14 to 10
B1, B2
5A0011
5A0017
5A0022
5A0027
5A0032
5A0041
5A0052
5A0062
644
Screw
Size
Tightening Torque
Nm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M5
2 to 2.5
(17.7 to 22.1)
M6
4 to 6
(35.4 to 53.1)
M5
2 to 2.5
(17.7 to 22.1)
M6
4 to 6
(35.4 to 53.1)
M6
4 to 6
(35.4 to 53.1)
14 to 10
10
12 to 10
10
14 to 6
14
14 to 6
, +1, +2
14 to 6
B1, B2
14 to 10
12 to 8
10
10 to 6
10
10 to 6
, +1, +2
10 to 6
B1, B2
10 to 8
12 to 8
10 to 6
10
10 to 6
, +1, +2
10 to 6
B1, B2
10 to 8
10 to 6
6 to 4
6 to 4
, +1, +2
6 to 4
B1, B2
10 to 8
M5
2 to 2.5
(17.7 to 22.1)
10 to 6
M6
4 to 6
(35.4 to 53.1)
10 to 3
10 to 3
, +1, +2
6 to 1
M8
B1, B2
12 to 3
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
M10
18 to 23
(159 to 204)
10 to 3
10 to 3
, +1, +2
6 to 1
B1, B2
8 to 3
10 to 4/0
10 to 4/0
, +1, +2
4 to 4/0
B1, B2
6 to 4/0
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Wire Range
AWG, kcmil
10 to 4/0
10 to 4/0
, +1, +2
3 to 4/0
B1, B2
6 to 4/0
1/0
10 to 4/0
10 to 4/0
, +1, +2
2 to 4/0
B1, B2
4 to 4/0
2/0
1 to 300
2/0
1 to 300
, +1
2/0 to 3/0
+3
1 to 1/0
Model CIMR-Ao
5A0077
5A0099
5A0125
5A0145
Terminal
Screw
Size
Tightening Torque
Nm (lb.in.)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M12
32 to 40
(283 to 354)
4 to 300
3/0
2/0 to 300
3/0
2/0 to 300
, +1
3/0 to 4/0
+3
1/0 to 2/0
4 to 300
300
2/0 to 600
250
2/0 to 600
, +1
2/0 to 400
+3
2/0 to 250
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
400
2/0 to 600
350
2/0 to 600
M12
32 to 40
(283 to 354)
, +1
2/0 to 500
+3
250 to 300
M10
18 to 23
(159 to 204)
1 to 350
M12
32 to 40
(283 to 354)
5A0192
5A0242
Standards Compliance
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL approval requires the use of crimp terminals
when wiring the drive main circuit terminals on models CIMR-Ao2A0110 to 2A0415 and 4A0058 to 4A1200. Use only
crimping tools as specified by the crimp terminal manufacturer. Yaskawa recommends crimp terminals made by JST and
Tokyo DIP (or equivalent) for the insulation cap.
Table D.7 matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals, tools, and insulation
caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive
model. Place orders with a Yaskawa representative or the Yaskawa sales department.
The closed-loop crimp terminal sizes and values listed in Table D.7 are Yaskawa recommendations. Refer to local codes for
proper selections.
Table D.7 Closed-Loop Crimp Terminal Size
Tool
Die Jaw
Insulation
Cap
Model No.
Code <1>
YA-4
AD-900
TP-003
100-054-028
R5.5-4
YA-4
AD-900
TP-005
100-054-029
R5.5-5
YA-4
AD-900
TP-005
100-054-030
Wire Gauge
Terminal
Screws
Crimp Terminal
Model Number
Machine No.
2 mm2
14 AWG
M4
R2-4
M4
M5
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
D
645
Tool
Die Jaw
Insulation
Cap
Model No.
Code <1>
YA-4
AD-901
TP-008
100-054-031
R8-5
YA-4
AD-901
TP-008
100-054-032
R8-8
YA-4
AD-901
TP-008
100-061-111
M4
14-NK4
YA-4
AD-902
TP-014
100-054-033
M5
R14-5
YA-4
AD-902
TP-014
100-054-034
M6
R14-6
YA-5
AD-952
TP-014
100-051-261
M8
R14-8
YA-5
AD-952
TP-014
100-054-035
M10
R14-10
YA-5
AD-952
TP-014
100-061-112
M6
R22-6
YA-5
AD-953
TP-022
100-051-262
Terminal
Screws
Crimp Terminal
Model Number
Machine No.
M4
8-4
M5
M8
8 mm2
8 AWG
14 mm2
6 AWG
22 mm2
4 AWG
M8
R22-8
YA-5
AD-953
TP-022
100-051-263
M10
R22-10
YA-5
AD-953
TP-022
100-061-113
30 / 38
3 / 2 AWG
M8
R38-8
YA-5
AD-954
TP-038
100-051-264
M10
R38-10
YA-5
AD-954
TP-038
100-061-114
mm2
M8
R60-8
YA-5
AD-955
TP-060
100-051-265
M10
R60-10
YF-1, YET-300-1
TD-321, TD-311
TP-060
100-051-266
M10
38-L10
YF-1, YET-150-1
TD-224, TD-212
TP-038
100-051-556
M10
80-10
YF-1, YET-300-1
TD-323, TD-312
TP-080
100-051-267
M10
80-L10
YF-1, YET-150-1
TD-227, TD-214
TP-080
100-051-557
M12
80-L12
YF-1, YET-300-1
TD-323, TD-312
TP-080
100-051-558
M10
R100-10
YF-1, YET-300-1
YF-1, YET-150-1
TD-324, TD-312
TD-228, TD-214
TP-100
100-051-269
M10
100-L10
YF-1, YET-150-1
TD-228, TD-214
TP-100
100-051-559
M12
100-L12
YF-1, YET-300-1
TD-324, TD-312
TP-100
100-051-560
150
250 / 300 kcmil
M10
R150-10
YF-1. YET-150-1
TD-229, TD-215
TP-150
100-051-272
M12
R150-12
YF-1, YET-300-1
TD-325, TD-313
TP-150
100-051-273
250 kcmil 2P
250 kcmil 4P
300 kcmil 2P
300 kcmil 4P
M10
150-L10
YF-1, YET-150-1
TD-229, TD-215
TP-150
100-051-561
M12
150-L12
YF-1, YET-300-1
TD-325, TD-313
TP-150
100-051-562
200 mm2
350 kcmil
400 kcmil
M10
200-10
YF-1, YET-300-1
TD-327, TD-314
TP-200
100-051-563
M12
R200-12
YF-1, YET-300-1
TD-327, TD-314
TP-200
100-051-275
M12
200-L12
YF-1, YET-300-1
TD-327, TD-314
TP-200
100-051-564
M10
325-10
YF-1, YET-300-1
TD-328, TD-315
TP-325
100-051-565
M12
325-12
YF-1, YET-300-1
TD-328, TD-315
TP-325
100-051-277
mm2
50 / 60
1 AWG
1/0 AWG
1/0 AWG 2P
1 AWG 2P
2 AWG 2P
mm2
80
2/0 / 3/0 AWG
2/0 AWG 2P
3/0 AWG 2P
3/0 AWG 4P
100 mm2
4/0 AWG
4/0 AWG 2P
4/0 AWG 4P
mm2
350 kcmil 2P
400 kcmil 2P
325 mm2
500 kcmil
600 / 650 kcmil
500 kcmil 2P
600 kcmil 2P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 C 600 Vac UL-approved vinyl-sheathed insulation.
Provide fuse branch circuit protection using the fuses listed in Installing Fuses on the Input Side on page 630.
646
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Terminal Signal
P1, P2, PC, DM+, DM-
Digital inputs
Analog inputs / outputs
Standards Compliance
D
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
647
Description
Disabled the internal motor overload protection of the drive.
Selects protection characteristics for a standard self-cooled motor with limited cooling capabilities
Standard fan-cooled motor (default)
when running below the rated speed. The motor overload detection level (oL1) is automatically
reduced when running below the motor rated speed.
Selects protection characteristics for a motor with self-cooling capability within a speed range of
Drive duty motor with a speed range of 1:10 10:1. The motor overload detection level (oL1) is automatically reduced when running below
1/10 of the motor rated speed.
Selects protection characteristics for a motor capable of cooling itself at any speed including zero
Vector motor with a speed range of 1:100 speed (externally cooled motor). The motor overload detection level (oL1) is constant over the
entire speed range.
Permanent Magnet motor with variable
Selects protection characteristics for a variable torque PM motor. The motor overload detection
torque
level (oL1) is automatically reduced when running below the motor rated speed.
Permanent Magnet motor with constant
Selects protection characteristics for a constant torque PM motor. The motor overload detection
torque
level (oL1) is constant over the whole speed range.
Selects protection characteristics for a standard self-cooled motor with limited cooling capabilities
Standard fan-cooled motor (50 Hz)
when running below the rated speed. The motor overload detection level (oL1) is automatically
reduced when running below the motor rated speed.
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection
(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Enable motor overload protection (L1-01 = 1 to 5) when connecting the drive to a single motor, unless another motor overload
preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts off the output
of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated while the drive
is powered up.
Cold Start
1
0.4
Hot Start
0.1
0
100
150
200
648
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Code Number
100-061-273
100-061-274
Model
ECAT31875-11
ECAT31876-11
100-061-275
ECAT31877-11
100-061-277
ECAT31726-11
100-061-278
ECAT31698-11
100-061-273
100-061-274
ECAT31875-11
ECAT31876-11
100-061-276
ECAT31878-11
100-061-275
ECAT31877-11
100-061-277
ECAT31726-11
100-061-278
ECAT31698-11
100-061-279
ECAT31740-11
100-061-280
ECAT31746-11
100-061-281 <1>
ECAT31741-11
100-061-274
ECAT31876-11
100-061-275
ECAT31877-11
Figure
Figure D.9
Figure D.10
Figure D.9
100-061-277
ECAT31726-11
100-061-278
ECAT31698-11
Note: Model CIMR-Ao4A1200 is UL compliant when the air entering the drive-installed panel or cabinet is 45 C or cooler. For more information,
contact your nearest Yaskawa representative or our sales office.
Standards Compliance
D
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
649
C
E
D
D Installation screws
E Capacitor cover
Figure D.9 Capacitor Cover
A
B
C
E
D
D Installation screws
E Capacitor cover
650
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Two Safe Disable inputs and one EDM output according to ISO138491 Cat. 3 PLd, IEC61508
SIL2. <1>
Time from input open to drive output stop is less than 1 ms.
PFD = 5.15E-5
PFH = 1.2E-9
Performance Level
The Safe Disable inputs satisfy all requirements of Performance Level (PL) d according to
ISO13849-1 (DC from EDM considered). <1>
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
u Precautions
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849
Cat. 3, IEC/EN61508 SIL2, Insulation coordination: class 1.
DANGER! Sudden Movement Hazard. Improper use of the Safe Disable function can result in serious injury or even death. Make sure the
whole system or machinery in which the Safe Disable function is used complies with safety requirements. When implementing the Safe
Disable function into the safety system of a machine, perform a thorough risk assessment for the entire system to assure compliance with
relevant safety norms.
DANGER! Sudden Movement Hazard. When using a PM motor, even if the drive output is shut off by the Safe Disable function, a breakdown
of two output transistors can cause current to flow through the motor winding, resulting in a rotor movement for a maximum angle of 180
degrees (electrically). Make sure such a situation would have no effect on the safety of the application when using the Safe Disable function.
DANGER! Sudden Movement Hazard. The Safe Disable function can switch off the drive output, but does not cut the drive power supply
and cannot electrically isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or
installations on the drive input side as well as the drive output side.
WARNING! Sudden Movement Hazard. When using the Safe Disable inputs, make sure to remove the wire links between terminals H1,
H2, and HC that were installed prior to shipment. Failing to do so will keep the Safe Disable circuit from operating properly and can cause
injury or even death.
NOTICE: All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating normally,
there is a risk of serious personal injury.
NOTICE: Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should be
permitted to wire, inspect, and maintain the Safe Disable input.
NOTICE: From the moment terminal inputs H1 and H2 have opened, it takes up to 1 ms for drive output to shut off completely. The sequence
set up to trigger terminals H1 and H2 should make sure that both terminals remain open for at least 1 ms in order to properly interrupt drive
output.
NOTICE: The Safe Disable Monitor (output terminals DM+ and DM-) should not be used for any other purpose than to monitor the Safe
Disable status or to discover a malfunction in the Safe Disable inputs. The monitor output is not considered a safe output.
NOTICE: When utilizing the Safe Disable function, use only the EMC filters recommended in EMC Filters on page 635.
The Safe Disable circuit consists of two independent input channels that can block the output transistors and provide a
monitoring channel to indicate the status of those input channels.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Standards Compliance
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849
Cat. 3, IEC/EN61508 SIL2, Insulation coordination: class 1.
D
651
HC
Feedback
Safety
Outputs
H1
Control
Circuit
Jumper S3
Setting:
SINK
Gate Block 1
N Power Module P
H2
Gate Block 2
DM+
>=1
DMDrive
Output
Frequency
Run Command
Run
Stop
H1, H2 Input
Drive Output
Normal operation
Whenever either one Safe Disable input or both inputs open, the motor torque is shut off by switching off the drive output. If
the motor was running before the Safe Disable inputs opened, then the motor will coast to stop, regardless of the stopping
method set in parameter b1-03.
Notice that the Safe Torque Off state can only be achieved using the Safe Disable function. Removing the Run command
stops the drive and shuts the output off (baseblock), but does not create a Safe Torque Off status.
Note: To avoid an uncontrolled stop during normal operation, make sure that the Safe Disable inputs are opened first when the motor has completely
stopped.
The Safe Disable function can only be deactivated when a Run command is not active.
652
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Table D.11 explains the drive output and Safe Disable monitor state depending on the Safe Disable inputs.
Table D.11 Safety Input and EDM Terminal Status
Safe Disable Input Status
Input 1, H1-HC
Input 2, H2-HC
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
Safely disabled,
Safe Torque Off
Safely disabled,
Safe Torque Off
HbbF (flashes)
ON
ON
Safely disabled,
Safe Torque Off
HbbF (flashes)
ON
ON
Baseblock,
ready for operation
Normal display
With the Safe Disable monitor output (terminals DM+ and DM-), the drive provides a safety status feedback signal. This signal
should be read by the device that controls the Safe Disable inputs (PLC or a safety relay) in order to prohibit leaving the Safe
Torque Off status in case the safety circuit malfunctions. Refer to the instruction manual of the safety device for details on
this function.
Digital Operator Display
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849
Cat. 3, IEC/EN61508 SIL2, Insulation coordination: class 1.
Standards Compliance
When both Safe Disable inputs are open, Hbb will flash in the digital operator display.
If one Safe Disable channel is on while the other is off, HbbF will flash in the display to indicate that there is a problem in
the safety circuit or in the drive. This display should not appear under normal conditions if the Safe Disable circuit is utilized
properly. Refer to Alarm Codes, Causes, and Possible Solutions on page 365 to resolve possible errors.
D
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
653
654
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Appendix: E
Quick Reference Sheet
This section provides tables to keep record of the drive specifications, motor specifications, and drive
settings. Fill in the table data after commissioning the application and have them ready when contacting
Yaskawa for technical assistance.
E.1
E.2
E.3
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
655
E.1
u Drive Specifications
Normal Duty Amps / Heavy Duty Amps
AC drive model
MODEL :
Input specifications
Output specifications
INPUT
OUTPUT
MASS
O/N
S/N
Lot number
Serial number
CIMR-AU5A0009FAA
REV : A
: AC3PH 500-600V 50/60Hz 12.0A/8.3A
IND.CONT.EQ.
: AC3PH 0-600V 0-400Hz 9.0A/6.3A
7J48 B
: 3.5kg
PRG : 1010
:
:
FILE NO : E131457
TYPE 1 ENCLOSURE
IP20
Software version
PASS
MADE IN JAPAN
Enclosure type
Items
Model
Serial Number
Software Version (PRG)
Options used
Date of Usage
Description
CIMR-A
u Motor Specifications
n Induction Motor
Items
Manufacturer
Model
Motor Rated Power (T1-02)
Motor Rated Voltage (T1-03)
Description
kW
V
Items
Motor Rated Current (T1-04)
Motor Base Frequency (T1-05)
Number of Motor Poles (T1-06)
Motor Base Speed (T1-07)
Description
A
Hz
Items
Induction Voltage Constant
Induction Voltage Constant
PM Motor Rated Current
(T2-06)
PM Motor Base Frequency
(T2-07)
Number of PM Motor Poles
(T2-08)
PM Motor Base Speed (T2-09)
Description
mVs/rad
mV/(r/min)
Items
Description
r/min
Description
kW
V
q-Axis Inductance
mH
x-Axis Inductance
mH
A
Hz
r/min
656
Description
Resolution
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
E.2
Use the following tables to keep records of the most important parameters. Have these data available when contacting Yaskawa
technical support.
u Basic Setup
Item
Control Mode
Normal/Heavy Duty Selection
Frequency Reference Source
Run Command Source
Setting Value
Memo
Setting Value
Memo
A1-02 =
C6-01 =
b1-01 =
b1-02 =
E1-03 =
E1-04 =
E1-05 =
E1-06 =
E1-07 =
E1-08 =
E1-09 =
E1-10 =
u Motor Setup
Induction
Permanent
Magnet
Item
Motor Rated Current
Motor Rated Slip
Motor No-Load Current
No. of Motor Poles
Line-to-Line Resistance
Motor Leakage
Inductance
Motor Code Selection
Motor Rated Power
Motor Rated Current
No. of Motor Poles
Motor Stator Resistance
Motor d-Axis Inductance
Motor q-Axis Inductance
Induction Volt. Const. 1
Encoder Z-pulse Offset
Induction Volt. Const. 2
Setting Value
E2-01 =
E2-02 =
E2-03 =
E2-04 =
E2-05 =
Memo
E2-06 =
E5-01 =
E5-02 =
E5-03 =
E5-04 =
E5-05 =
E5-06 =
E5-07 =
E5-09 =
E5-11 =
E5-24 =
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Motor Type
657
Input Used
S1
S2
S3
S4
S5
S6
S7
S8
Setting Value
and Function Name
H1-01 =
H1-02 =
H1-03 =
H1-04 =
H1-05 =
H1-06 =
H1-07 =
H1-08 =
Memo
Input Used
RP
A1
A2
A3
Setting Value
and Function Name
H6-01 =
H3-02 =
H3-10 =
H3-06 =
Memo
Output Used
M1-M2
M3-M4
M5-M6
Setting Value
and Function Name
H2-01 =
H2-02 =
H2-03 =
Memo
Setting Value
and Function Name
H4-01 =
H4-04 =
H6-06 =
Memo
u Monitor Outputs
Terminal
FM
AM
MP
658
Output Used
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
E.3
Use the Verify Menu to see which parameters have been changed from their original default settings
below the parameter number indicates that the parameter setting can be changed during run.
Parameter names in bold face type are included in the Setup Group of parameters.
A1-00
A1-01
A1-02
A1-03
A1-04
A1-05
A1-06
A1-07
A2-01 to
A2-32
A2-33
b1-01
b1-02
b1-03
b1-04
b1-05
b1-06
b1-07
Name
Language Selection
Access Level Selection
Control Method Selection
Initialize Parameters
Password
Password Setting
Application Preset
DriveWorksEZ Function Selection
User Parameters, 1 to 32
User Parameter Automatic Selection
Frequency Reference Selection 1
Run Command Selection 1
Stopping Method Selection
Reverse Operation Selection
Action Selection below Minimum Output
Frequency
b1-08
b1-14
b1-15
b1-16
b1-17
b2-01
b2-02
b2-03
b2-04
b2-08
b2-12
b2-13
b2-18
b3-01
b3-02
b3-03
b3-04
b3-05
b3-06
b3-10
b3-14
b3-17
b3-18
User
Setting
No.
b3-19
b3-24
b3-25
b3-27
b4-01
b4-02
b5-01
b5-02
b5-03
b5-04
b5-05
b5-06
b5-07
b5-08
b5-09
b5-10
b5-11
b5-12
b5-13
b5-14
b5-15
b5-16
b5-17
b5-18
b5-19
b5-20
b5-34
b5-35
b5-36
b5-37
b5-38
b5-39
b5-40
Name
User
Setting
No.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
659
Name
Dwell Time at Start
Dwell Reference at Stop
Dwell Time at Stop
Droop Control Gain
C1-07
C1-08
C5-22
Deceleration Time 4 (Motor 2 Decel Time 2)
C1-10
C1-11
C2-01
C2-02
C2-03
C2-04
C3-01
660
C5-03
Fast-Stop Time
C3-03
C3-04
C3-05
C5-02
C5-05
C5-06
C5-07
C5-08
C5-12
C5-17
C5-18
C5-21
Acceleration Time 2
C4-06
C4-07
C5-01
C5-23
C5-24
C5-25
C5-26
C5-27
C5-28
C5-32
C5-37
C5-38
C6-01
C6-02
C6-03
User
Setting
C5-04
Deceleration Time 2
Name
C4-03
C4-04
C4-05
Deceleration Time 1
C1-09
C3-02
C4-02
C1-06
C3-23
C4-01
C1-05
C3-22
b8-05
b8-06
C1-04
C3-21
C3-24
C1-03
No.
b8-04
C1-02
User
Setting
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
C6-04
C6-05
C6-09
d1-01
d1-02
d1-03
d1-04
d1-05
d1-06
d1-07
d1-08
d1-09
d1-10
d1-11
d1-12
d1-13
d1-14
d1-15
d1-16
d1-17
Frequency Reference 1
Frequency Reference 2
Frequency Reference 3
Frequency Reference 4
Frequency Reference 5
Frequency Reference 6
Frequency Reference 7
Frequency Reference 8
Frequency Reference 9
Frequency Reference 10
Frequency Reference 11
Frequency Reference 12
Frequency Reference 13
Frequency Reference 14
Frequency Reference 15
Frequency Reference 16
Jog Frequency Reference
d2-01
d2-02
d2-03
d3-01
d3-02
d3-03
d3-04
d4-01
d4-03
d4-04
User
Setting
No.
Name
d4-05
d4-06
d4-07
d4-08
d4-09
d4-10
d5-01
d5-02
d5-03
d5-04
d5-05
d5-06
d5-08
d6-01
d6-02
d6-03
d6-06
d7-01
d7-02
d7-03
Offset Frequency 1
Offset Frequency 2
Offset Frequency 3
E1-01
E1-03
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
E1-13
E2-01
E2-02
E2-03
E2-04
E2-05
E2-06
E2-07
E2-08
E2-09
E2-10
E2-11
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
User
Setting
No.
661
Name
E3-01
E3-04
E3-05
E3-06
E3-07
E3-08
E3-09
E3-10
E3-11
E3-12
E3-13
E4-01
E4-02
E4-03
E4-04
E4-05
E4-06
E4-07
E4-08
E4-09
E4-10
E4-11
E5-01
E5-02
E5-03
E5-04
E5-05
E5-06
E5-07
E5-09
E5-11
E5-24
F1-01
F1-02
F1-03
F1-04
F1-05
F1-06
F1-08
F1-09
F1-10
F1-11
F1-12
F1-13
F1-14
F1-18
F1-19
F1-20
F1-21
F1-30
662
User
Setting
No.
F1-31
F1-32
F1-33
F1-34
F1-35
F1-36
F1-37
F2-01
F2-02
F2-03
Name
PG 2 Pulses Per Revolution
PG 2 Rotation Selection
PG 2 Gear Teeth 1
PG 2 Gear Teeth 2
PG 2 Division Rate for PG Pulse Monitor
PG Option Card Disconnect Detection 2
PG2 Signal Selection
Analog Input Option Card Operation Selection
Analog Input Option Card Gain
Analog Input Option Card Bias
F3-01
F3-03
F4-01
F4-02
F4-03
F4-04
F4-05
F4-06
F4-07
F4-08
F5-01
F5-02
F5-03
F5-04
F5-05
F5-06
F5-07
F5-08
F5-09
F6-01
F6-02
F6-03
F6-04
F6-06
F6-07
F6-08
F6-10
F6-11
F6-14
F6-20
F6-21
User
Setting
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
F6-22
F6-23
F6-24
F6-25
F6-26
F6-30
F6-31
F6-32
F6-35
F6-36
F6-50
F6-51
F6-52
F6-53
F6-54
F6-55
F6-56
F6-57
F6-58
F6-59
F6-60
F6-61
F6-62
F6-63
H1-01
H1-02
H1-03
H1-04
H1-05
H1-06
H1-07
H1-08
H2-01
H2-02
H2-03
H2-06
H3-01
H3-02
H3-03
H3-04
H3-05
H3-06
User
Setting
No.
H3-07
H3-08
H3-09
H3-10
H3-11
H3-12
H3-13
H3-14
H4-01
H4-02
H4-03
Name
Terminal A3 Gain Setting
Terminal A3 Bias Setting
Terminal A2 Signal Level Selection
Terminal A2 Function Selection
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Analog Input Filter Time Constant
Analog Input Terminal Enable Selection
Multi-Function Analog Output Terminal FM
Monitor Selection
Multi-Function Analog Output Terminal FM
Gain
Multi-Function Analog Output Terminal FM Bias
H4-04
H4-05
H4-06
H4-07
H4-08
H5-01
H5-02
H5-03
H5-04
H5-05
H5-06
H5-07
H5-09
H5-10
H5-11
H5-12
H6-01
H6-02
H6-03
H6-04
H6-05
H6-06
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
User
Setting
No.
663
Name
Pulse Train Monitor Scaling
L1-04
L1-05
L1-13
L2-01
L2-02
L2-03
L2-04
L2-05
L2-06
L2-07
L2-08
L2-10
L2-11
L2-29
L3-01
L3-02
L3-03
L3-04
L3-05
L3-06
L3-11
L1-03
L3-17
L3-20
L3-21
L3-24
L3-25
L3-26
L3-27
L4-01
L4-02
L4-03
L4-04
L4-05
L4-06
L4-07
L5-01
L5-02
L5-04
L3-22
L3-23
664
User
Setting
No.
Name
L5-05
L6-01
L6-02
L6-03
L6-04
L6-05
L6-06
L6-08
L6-09
L6-10
L6-11
L7-01
L7-02
L7-03
L7-04
L7-06
L7-07
L8-01
L8-02
L8-03
L8-05
L8-07
L8-09
L8-10
L8-11
L8-12
L8-15
L8-18
L8-19
L8-27
L8-29
L8-32
L8-35
L8-38
L8-40
L8-41
L8-55
n1-01
n1-02
n1-03
n1-05
n2-01
n2-02
n2-03
n3-01
n3-02
User
Setting
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
n3-03
n3-04
n3-13
n3-14
n3-21
n3-23
n5-01
n5-02
n5-03
n6-01
n6-05
n8-01
n8-02
n8-35
n8-45
n8-47
n8-48
n8-49
n8-51
n8-54
n8-55
n8-57
n8-62
n8-65
n8-69 <1>
Name
High-Slip Braking Dwell Time at Stop
High-Slip Braking Overload Time
Overexcitation Deceleration Gain
High Frequency Injection during Overexcitation
Deceleration
High-Slip Suppression Current Level
Overexcitation Operation Selection
Feed Forward Control Selection
Motor Acceleration Time
Feed Forward Control Gain
Online Tuning Selection
Online Tuning Gain
Initial Rotor Position Estimation Current
Pole Attraction Current
Initial Rotor Position Detection Selection
Speed Feedback Detection Control Gain
Pull-In Current Compensation Time Constant
Pull-In Current
d-Axis Current for High Efficiency Control
Acceleration/Deceleration Pull-In Current
Voltage Error Compensation Time Constant
Load Inertia
High Frequency Injection
Output Voltage Limit
Speed Feedback Detection Control Gain during ov
Suppression
Speed Calculation Gain
User
Setting
No.
Name
o4-02
o4-03
o4-05
o4-07
o4-09
o4-11
o4-12
o4-13
q1-01 to
q6-07
r1-01 to
r1-40
T1-00
T1-01
T1-02
T1-03
T1-04
T1-05
T1-06
T1-07
T1-08
T1-09
T1-10
T1-11
T2-01 <1>
T2-02
T2-03
T2-04
T2-05
T2-06
T2-07
T2-08
T2-09
T2-10
T2-11
T2-12
T2-13
T2-14
T2-15
T2-16
T2-17
T3-01
T3-02
T3-03
T3-04
User
Setting
DriveWorksEZ Parameters
DWEZ Connection Parameter 1 to 20 (upper/
lower)
Motor 1/Motor 2 Selection
Auto-Tuning Mode Selection
No.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
665
666
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Index
A3 ..............................................................................99
-.................................................................................87 AC .............................................................................99
-V ..............................................................................99 Accel/Decel Rate Calculation Gain ..................................... 299
Accel/Decel Time.................................................... 341, 464
+
Accel/Decel Time Setting Units ......................................... 194
+1 ..............................................................................87 Accel/Decel Time Switching Frequency ............................... 193
+2 ..............................................................................87 Acceleration/Deceleration Pull-In Current ............................. 321
+3 ..............................................................................87 Acceleration Error ......................................................... 381
+V..............................................................................99 Acceleration Time ......................................................... 192
Acceleration Time Pull-In Current ...................................... 538
Numerics
Access Level Selection.............................................. 151, 156
1800 r/min Type Yaskawa SMRA Series SPM Motor Settings ..... 579
AC Reactor ................................................................. 437
200 V, 1150 r/min Type Yaskawa SSR1 Series IPM Motor......... 584
Action Selection below Minimum Output Frequency ................ 166
200 V, 1150 r/min Type Yaskawa SST4 Series IPM Motor ......... 590
Additional DC Bus Capacitors........................................... 300
200 V, 1450 r/min Type Yaskawa SSR1 Series Motor............... 582
Adjusted Slip Calculation Error ......................................... 379
200 V, 1450 r/min Type Yaskawa SST4 Series IPM Motor ......... 588
Adjusting the ASR Parameters........................................... 199
200 V, 1750 r/min Type Yaskawa SSR1 Series IPM Motor......... 580
AEr........................................................................... 365
200 V, 1750 r/min Type Yaskawa SST4 Series IPM Motor ......... 586
AFR.......................................................................... 314
24 V Power Supply ........................................................ 438
AFR Gain ................................................................... 337
2-Wire Initialization ....................................................... 157
AFR Time Constant 1 ..................................................... 337
3600 r/min Type Yaskawa SMRA Series SPM Motor Settings ..... 579
AFR Time Constant 2 ..................................................... 337
3-Wire Initialization ....................................................... 158
AI-A3........................................................................ 437
3-Wire Sequence........................................................... 158
AI-A3 Settings ............................................................. 240
3-Wire Sequence Wiring Diagram ...................................... 249
Air Filter Replacement .................................................... 430
400 V, 1150 r/min Type Yaskawa SSR1 Series IPM Motor......... 585
Alarm Outputs for Maintenance Monitors ............................. 404
400 V, 1150 r/min Type Yaskawa SST4 Series IPM Motor ... 590,
Alarm Register 007FH Contents......................................... 622
591
Alarms and Errors ............................................................ 3
400 V, 1450 r/min Type Yaskawa SSR1 Series IPM Motor......... 583
Allowable Frequency Fluctuation ... 455, 456, 457, 458, 459, 460,
400 V, 1450 r/min Type Yaskawa SST4 Series IPM Motor ......... 589
461,
462,
463
400 V, 1750 r/min Type Yaskawa SSR1 Series IPM Motor......... 581
Allowable Voltage Fluctuation ... 455, 456, 457, 458, 459, 460, 461,
400 V, 1750 r/min Type Yaskawa SST4 Series IPM Motor ......... 587 462,
463
5th Most Recent Fault..................................................... 551 ALM LED Light ........................................................... 115
Altitude........................................................................54
A
A/D Conversion Error..................................................... 348 AM.............................................................................99
A1 ..............................................................................99 Ambient Temperature .......................................................54
A1000 Models................................................................31 Ambient Temperature and Installation Method Derating ............ 473
A1-01 ........................................................................ 151 Ambient Temperature Setting................................ 309, 472, 534
A1-02 ........................................................................ 392 Analog Filter Time Constant ............................................. 341
A1-02 (Motor 1 Control Mode) Dependent Parameters .............. 557 Analog Frequency Reference Fluctuation Limit....................... 217
A1-03 ........................................................................ 151 Analog Frequency Reference Sample/Hold............................ 254
A1-04 ........................................................................ 389 Analog Input Card Settings............................................... 240
A1-04, A1-05: Password and Password Setting ....................... 158 Analog Input Filter Time Constant ...................................... 272
A1-05 ........................................................................ 389 Analog Input Option Card Bias .......................................... 240
A2 ..............................................................................99 Analog Input Option Card Gain ......................................... 240
A2-01 ........................................................................ 151 Analog Input Option Card Operation Selection ....................... 240
A2-32 ........................................................................ 151 Analog Inputs / Pulse Train Input .........................................99
A2-33 ........................................................................ 151 Analog Input Terminal Enable Selection ............................... 272
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
667
Index
Analog Monitor Card Settings ................................................ 241
AO-A3............................................................................ 437
AO-A3 Settings ................................................................. 241
Application Presets ............................................................. 132
Application Selection ............................................................. 3
ASR............................................................................... 199
ASR Gain Auto-Tuning........................................................ 137
ASR Gain Switching Frequency.............................................. 201
ASR Integral Limit ............................................................. 202
ASR Integral Time.............................................................. 201
ASR Limit ....................................................................... 202
ASR Primary Delay Time Constant .......................................... 202
ASR Proportional Gain ........................................................ 201
ASR Response Frequency ..................................................... 147
Attachment for External Heatsink ...................................... 438, 450
Automatic Reduction Selection for Stall Prevention during Run ... 297,
530
Automatic Speed Regulator ................................................... 199
Auto Restart Fault Output Operation Selection............................. 302
Auto Restart Operation Selection............................................. 531
Auto-Tuning ............................................................ 3, 138, 141
Auto-Tuning Codes............................................................. 379
Auto-Tuning Errors............................................................. 346
Auto-Tuning Fault Codes...................................................... 139
Auto-Tuning Fault Detection.................................................. 379
Auto-Tuning Fault Solutions .................................................. 379
Auto-Tuning for Induction Motors ........................................... 135
Auto-Tuning for Permanent Magnet Motors................................ 136
Auto-Tuning Input Data ........................................... 136, 137, 138
Auto-Tuning Interruption and Fault Codes.................................. 139
Auto-Tuning Mode Selection ........................................... 141, 544
B
B1 ...................................................................................87
b1-01.............................................................................. 389
b1-02.............................................................................. 389
b1-04.............................................................................. 390
B2 ...................................................................................87
b2-02.............................................................................. 394
b2-04.............................................................................. 394
b5-09.............................................................................. 394
b6-01 through b6-04............................................................ 341
Backing Up Parameter Values ................................................ 151
Baseblock ........................................................................ 365
Base Frequency ................................................................. 228
Base Voltage .................................................................... 228
Basic Auto-Tuning Preparations.............................................. 138
Basic Start-up and Motor Tuning............................................. 127
bb.................................................................................. 365
Bi-Directional Speed Search Selection ...................................... 176
boL.......................................................................... 347, 365
Braking circuit protective cover ................................................97
Braking Resistor .......................................................... 437, 442
Braking Resistor Fault ......................................................... 361
Braking Resistor Overheat..................................................... 361
Braking Resistor Overheat Protection ....................................... 465
Braking Resistor Overload Protection ....................................... 443
Braking Torque ................................................................. 464
Braking Transistor .............................................................. 464
Braking Transistor Overload Fault ..................................... 347, 365
668
C
C1-01 ............................................................................. 123
C2-01 through C2-04........................................................... 341
C3-01 ....................................................................... 336, 337
C3-02 ............................................................................. 337
C4-01 ............................................................................. 336
C4-02 ....................................................................... 336, 337
C4-06 ............................................................................. 337
C6-01 ............................................................................. 336
C6-02 ........................................................... 111, 336, 337, 393
C6-05 ............................................................................. 393
Cable Length Between Drive and Motor ......................................96
CALL............................................................................. 365
Cannot Change Parameter Settings........................................... 388
Cannot Reset .................................................................... 366
CANopen Communication Speed ............................................ 245
CANopen Node ID Selection ................................................. 245
CANopen Parameters .................................................... 242, 245
Capacitor Maintenance......................................................... 552
Capacitor Maintenance Setting ......................................... 327, 541
Capacitor Maintenance Time.................................................. 369
Carrier Frequency......... 204, 455, 456, 457, 458, 459, 460, 461, 462, 463
Carrier Frequency and Current Derating .............................. 206, 208
Carrier Frequency Derating .....................................................32
Carrier Frequency during Rotational Auto-Tuning ........................ 206
Carrier Frequency Lower Limit............................................... 205
Carrier Frequency Proportional Gain ........................................ 205
Carrier Frequency Reduction.................................................. 534
Carrier Frequency Reduction Off-Delay Time ............................. 312
Carrier Frequency Reduction Selection...................................... 311
Carrier Frequency Selection.........................................96, 336, 337
Carrier Frequency Setting Error .............................................. 377
Carrier Frequency Upper Limit ............................................... 205
CC-Link bUS Error Auto Reset............................................... 244
CC-Link Communication Speed.............................................. 244
CC-Link Node Address ........................................................ 244
CC-Link Parameters...................................................... 242, 244
CE........................................................................... 347, 366
CE Detection Time ............................................................. 599
CE Low Voltage Directive Compliance ..................................... 630
CE mark.......................................................................... 630
CF ................................................................................. 347
Changing Parameter Settings or Values ..................................... 121
Circulation Fan............................................................... 47, 48
Closed-Loop Crimp Terminal Size.............................................89
Closed Loop Vector control .....................................................32
Closed Loop Vector Control for PM Motors..................................32
Coast to stop ..................................................................... 164
Coast to Stop with Timer ...................................................... 165
Comm. option card connection error (CN5-A) ............................. 355
Command Messages from Master to Drive ................................. 602
Communication Error .......................................................... 384
Communication Fault Detection Selection .................................. 599
Communication Option Card.................................................. 242
Communication Option Card Reference..................................... 553
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Index
Communication Option Station Number Setting Error (CC-Link, CANopen,
MECHATROLINK-II)......................................................... 365
Communication Parity Selection ............................................. 598
Communications Enter Function Selection ................................. 600
Communications Error Operation Selection ................................ 243
Communication Speed Selection ............................................. 598
Communications Timing ...................................................... 602
Comparing Parameter Settings................................................ 385
Component Names ...............................................................41
Compressor Application ....................................................... 134
Conduit bracket .............................................................. 41, 43
Conduit Bracket Dimensions for IP20/NEMA Type 1 ......................64
Conduit bracket front cover .....................................................41
Connected Machinery Vibrates When Motor Rotates ..................... 393
Connecting a DC Link Choke................................................. 446
Connecting an AC Reactor .................................................... 446
Connecting a Noise Filter...................................................... 447
Connecting a Suppression Diode ...............................................99
Connecting a Surge Absorber ................................................. 446
Connecting Braking Units in Parallel ........................................ 444
Connecting Peripheral Devices ............................................... 439
Connecting to a PC (USB)..................................................... 109
Connection of a Motor PTC ................................................... 283
Continuous Electrothermal Operation Selection ..................... 285, 526
Control Board Connection Error........................................ 348, 349
Control Circuit Error ..................................................... 348, 349
Control Circuit Input Terminals ................................................98
Control Circuit Output Terminals ..............................................99
Control Circuit Terminal Block Functions ....................................98
Control Fault .................................................................... 347
Control Method Selection ..................................................... 157
Control Method Selection Error .............................................. 375
Control Mode.............................................................. 157, 548
Control Mode Dependent Parameter Default Values ...................... 557
Control Mode Mismatch ....................................................... 384
Control Modes and their Features ..............................................32
Control Mode Selection..........................................................32
Control Power Supply Voltage Fault......................................... 363
Conveyor Application.......................................................... 133
Cooling Fan.............................................41, 42, 44, 45, 46, 47, 48
Cooling fan ........................................................................43
Cooling Fan Maintenance ..................................................... 552
Cooling Fan Maintenance Setting (Operation Time) ...................... 541
Cooling Fan Maintenance Time .............................................. 369
Cooling Fan Operation Time.................................................. 552
Cooling Fan Operation Time Setting......................................... 327
Cooling Fan Replacement ..................................................... 356
CoPy .............................................................................. 384
Copy Allowed Selection ....................................................... 327
Copy Function................................................................... 152
Copy Function Errors .......................................................... 342
Copy Function Selection....................................................... 326
Copy Unit Error ................................................................. 384
CopyUnitManager .............................................................. 152
CPEr .............................................................................. 384
CPF02 ............................................................................ 348
CPF03 ............................................................................ 348
CPF06 ............................................................................ 348
CPF07 ............................................................................ 348
CPF08 ............................................................................ 348
D
d2-01.............................................................................. 394
d3-01.............................................................................. 393
d3-01 through d3-04............................................................ 341
d3-04.............................................................................. 393
Daily Inspection................................................................. 400
d-Axis ACR Output ............................................................ 555
d-Axis Current for High Efficiency Control ................................ 320
DC bus circuit protective cover .................................................97
DC Bus Overvoltage ........................................................... 371
DC Bus Pre-Charge Relay Maintenance Setting ........................... 328
DC Bus Undervoltage .......................................................... 363
DC Bus Voltage................................................................. 548
DC Bus Voltage Adjustment Gain ........................................... 298
DC Bus Voltage at Previous Fault............................................ 550
DC Bus Voltage Setpoint during KEB....................................... 293
DC Injection Braking at Stop ................................................. 394
DC Injection Braking Current........................................... 170, 394
DC Injection Braking Input Timing Diagram............................... 256
DC Injection Braking Start Frequency....................................... 164
DC Injection Braking Time at Start .......................................... 164
DC Injection Braking Time at Stop .......................................... 170
DC Injection Braking to Stop ................................................. 164
DC link choke ................................................................... 437
DC Link Chokes for EN 61000-3-2 Compliance........................... 633
D Control ........................................................................ 178
Deceleration Rate Calculation Gain.......................................... 529
Deceleration Time .............................................................. 192
Deceleration Time at Stall Prevention during Acceleration......... 295, 530
Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01) ....... 325
Delay Timers .................................................................... 177
Derivative Time (D) ............................................................ 181
Desired DC Bus Voltage during KEB ....................................... 528
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
669
Index
dEv.......................................................................... 349, 366
DeviceNet Baud Rate Monitor................................................ 246
DeviceNet Communication Speed............................................ 246
DeviceNet Heartbeat Interval ................................................. 247
DeviceNet Idle Mode Fault Detection ....................................... 246
DeviceNet MAC Address...................................................... 246
DeviceNet Network MAC ID ................................................. 247
DeviceNet Parameters.................................................... 242, 246
DeviceNet PCA Setting ........................................................ 246
DeviceNet PPA Setting ........................................................ 246
DeviceNet Scaling Factors .................................................... 247
dFPS .............................................................................. 384
DI-A3............................................................................. 437
DI-A3 Settings .................................................................. 240
Diagnosing and Resetting Faults ............................................. 353
Digital Input Card Settings .................................................... 240
Digital Input Option Card Input Selection .................................. 240
Digital Input Option DI-A3 Data Length Selection ........................ 241
Digital Input Reading .......................................................... 167
Digital Operator ..............................41, 42, 43, 44, 45, 46, 47, 48, 41
Digital Operator Dimensions....................................................58
Digital Operator Display Selection..................................... 323, 540
Digital Operator Installation Methods and Required Tools .................59
Digital Operator Keypad Functions .......................................... 324
Digital Operator Menu and Screen Structure ............................... 119
Digital Operator Remote Installation ..........................................58
digital operator remote usage ...................................................57
Digital Output Card Settings .................................................. 242
Digital Output Option Card Terminal Function Selection ................ 242
Dimensions for IP00/Open Type Enclosure: 200 V Class ..................67
Dimensions for IP00/Open Type Enclosure: 400 V Class ..................67
Dimensions for IP00/Open Type Enclosure: 600V Class ...................67
Dimensions for IP20/NEMA Type 1 Enclosure: 200 V Class..............62
Dimensions for IP20/NEMA Type 1 Enclosure: 400 V Class..............63
Dimensions for IP20/NEMA Type 1 Enclosure: 600 V Class..............63
DIP Switch S1.....................................................................49
DIP Switch S1 Settings ........................................................ 107
DIP Switch S2.....................................................................49
DIP Switch S4 Settings ........................................................ 107
DM-.................................................................................99
DM+ ................................................................................99
dnE................................................................................ 367
DO-A3............................................................................ 437
DO-A3 Output Mode Selection............................................... 242
DO-A3 Settings ................................................................. 242
Down Arrow Key ............................................................... 115
Drive/kVA Selection ........................................................... 540
Drive Capacity Setting Fault .................................................. 374
Drive Cooling Fans ............................................................. 402
Drive Cover.............................................42, 43, 44, 45, 46, 47, 48
Drive Derating Data ..............................................................54
Drive Disabled .................................................................. 367
Drive Does Not Allow Selection of Rotational Auto-Tuning ............ 391
Drive Duty Mode Selection ...................................................... 3
Drive Mode ................................................................ 120, 121
Drive Model Mismatch ........................................................ 384
Drive Models and Types.........................................................61
Drive Model Selection ......................................................... 325
Drive Mode Unit Monitor Selection ................................... 323, 540
Drive Operation Status at Previous Fault.................................... 551
670
E
E (G)................................................................................99
E1-03 ............................................................................. 391
E1-04 ....................................................................... 391, 394
E1-08 ....................................................................... 336, 337
E1-09 ............................................................................. 389
E1-10 ....................................................................... 336, 337
E2-01 ....................................................................... 336, 647
E2-02 ............................................................................. 336
E2-03 ....................................................................... 336, 380
E3-01 (Motor 2 Control Mode) Dependent Parameters ................... 560
E5 ................................................................................. 351
EEPROM Memory Data Error................................................ 348
EEPROM Write Error.......................................................... 351
EF ................................................................................. 367
EF0 ......................................................................... 351, 367
EF1 ......................................................................... 351, 367
EF2 ......................................................................... 351, 367
EF3 ......................................................................... 351, 367
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Index
EF4 ......................................................................... 351, 367
EF5 ......................................................................... 351, 367
EF6 ......................................................................... 351, 367
EF7 ......................................................................... 351, 367
EF8 ......................................................................... 351, 367
Electromotive Force Parameter Tuning...................................... 136
EMC Filter and Drive Installation for CE Compliance.................... 634
EMC Filter Installation...........................................................91
EMC Filters...................................................................... 632
EMC Guidelines ................................................................ 630
EMC Guidelines Compliance ................................................. 632
EN61800-3 Filters .............................................................. 635
Enclosure Types ..................................................................39
Encoder Z-Pulse Offset .................................................. 146, 236
End................................................................................ 384
End1 .............................................................................. 379
End2 .............................................................................. 379
End3 .............................................................................. 379
End4 .............................................................................. 379
End5 .............................................................................. 379
End6 .............................................................................. 379
End7 .............................................................................. 380
Energy Saving................................................................... 189
Energy Saving Coefficient Value............................................. 190
Energy Saving Control Filter Time Constant ............................... 190
Energy Saving Control Selection ............................................. 189
Energy Saving Gain ............................................................ 189
Energy Savings Constants Error .............................................. 377
Enter Command................................................................. 600
Enter command necessary ..................................................... 600
Enter command not necessary ................................................ 600
Enter Command Settings when Upgrading the Drive...................... 623
Enter Command Types......................................................... 623
Enter Data from the Motor Nameplate....................................... 140
ENTER Key ..................................................................... 115
Er-01.............................................................................. 380
Er-02.............................................................................. 380
Er-03.............................................................................. 380
Er-04.............................................................................. 380
Er-05.............................................................................. 380
Er-08.............................................................................. 381
Er-09.............................................................................. 381
Er-10.............................................................................. 381
Er-11.............................................................................. 381
Er-12.............................................................................. 381
Er-13.............................................................................. 382
Er-14.............................................................................. 382
Er-15.............................................................................. 382
Er-16.............................................................................. 382
Er-17.............................................................................. 382
Er-18.............................................................................. 382
Er-19.............................................................................. 382
Er-20.............................................................................. 382
Er-21.............................................................................. 383
Err................................................................................. 351
Error Reading Data ............................................................. 385
Errors and Displays When Using the Copy Function...................... 346
Error Writing Data.............................................................. 384
European Standards ............................................................... 3
Excessive Motor Oscillation and Erratic Rotation ......................... 392
F
FAn ............................................................................... 352
FAn Alarm Location Monitor................................................. 554
Fan Bracket ...............................................................44, 45, 46
Fan bracket ........................................................................43
Fan Cover ..................................................................... 41, 42
Fan Finger Guard ............................................................ 41, 42
Fan Guard........................................................44, 45, 46, 47, 48
Fast Stop Sequence ............................................................. 253
Fast Stop Time .................................................................. 193
Fault Causes and Solutions .................................................... 347
Fault Detection .................................................................. 347
Fault Displays ................................................................... 347
Fault History............................................................... 330, 386
Fault Relay Output................................................................99
Fault Reset Interval Time................................................ 302, 531
Fault Reset Methods............................................................ 342
Fault Reset Operation Selection ........................................ 302, 531
Fault Restart ..................................................................... 266
Faults ....................................................................... 342, 343
Fault Trace................................................................. 330, 386
FbH ......................................................................... 352, 367
FbL ......................................................................... 352, 368
Feed Forward Control .................................................... 317, 341
Feed Forward Control Diagram............................................... 317
Feed Forward Control Gain ................................................... 318
Feed Forward Control Selection .............................................. 317
Ferrule Dimensions............................................................. 101
Ferrule Terminal Types and Sizes ............................................ 101
Ferrule-Type Wire Terminals ................................................. 101
Field Forcing .................................................................... 222
Field Forcing Limit ............................................................. 223
Field Forcing Selection ........................................................ 223
Field Weakening ................................................................ 222
Field Weakening Frequency Limit ........................................... 222
Field Weakening Level ........................................................ 222
Fine-Tuning Advanced Open Loop Vector Control for PM Motors..... 340
Fine-Tuning Closed Loop Vector Control................................... 338
Fine-Tuning Closed Loop Vector Control for PM Motors................ 340
Fine-Tuning Open Loop Vector Control .................................... 337
Fine-Tuning Open Loop Vector Control for PM Motors.................. 339
Fine-Tuning V/f Control and V/f Control with PG ........................ 336
FJOG/RJOG Operation ........................................................ 252
FM ..................................................................................99
Forward/Reverse Run Command Input Error............................... 367
Forward Regenerative Torque Limit ................................... 306, 533
Forward Torque Limit.................................................... 306, 533
Frequency Accuracy (Temperature Fluctuation) ........................... 464
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
671
Index
Frequency Control Range...................................................... 464
Frequency Detection 1 Time Chart........................................... 262
Frequency Detection 2 Time Chart........................................... 262
Frequency Detection 3 Example with a Positive L3-04 Value ........... 265
Frequency Detection 4 Example with Positive L3-04 Value ............. 265
Frequency Gain at KEB Start ................................................. 293
Frequency Reduction Rate during Overheat Pre-Alarm............. 308, 534
Frequency Reference ..................................................... 209, 548
Frequency Reference at Previous Fault ...................................... 550
Frequency Reference at Reference Loss............................... 301, 531
Frequency Reference Bias ..................................................... 215
Frequency Reference Bias (Up/Down 2) .................................... 555
Frequency Reference Bias Accel/Decel ..................................... 216
Frequency Reference Bias Lower Limit ..................................... 215
Frequency Reference Bias Operation Mode Selection .................... 216
Frequency Reference Bias Step............................................... 215
Frequency Reference Bias Upper Limit ..................................... 215
Frequency Reference from MEMOBUS/Modbus Comm. ................ 553
Frequency Reference Hold .................................................... 213
Frequency Reference Hold Function Selection ............................. 213
Frequency Reference Loss Detection Selection ...................... 263, 530
Frequency Reference Lower Limit ........................................... 211
Frequency Reference Monitor Content During PID ....................... 186
Frequency Reference Selection ............................................... 481
Frequency Reference Selection 1....................................... 162, 389
Frequency Reference Selection 2............................................. 168
Frequency Reference Setting / Decimal Display ........................... 540
Frequency Reference Setting and User-Set Display ....................... 540
Frequency Reference Setting Hierarchy ..................................... 209
Frequency Reference Setting Method Selection...................... 325, 541
Frequency Reference Source Selection ...................................... 553
Frequency Reference Upper Limit ........................................... 211
Frequency Setting Resolution ................................................. 464
Frequency Setting Signal ...................................................... 464
Front Cover ........................................ 41, 42, 43, 44, 45, 46, 47, 48
Front Cover Screw......................................... 42, 44, 45, 46, 47, 48
Function Code................................................................... 603
Functions for Terminals S1 to S8............................................. 248
Fuse ............................................................................... 448
Fuse Selection ............................................................. 448, 630
HbbF.............................................................................. 368
HC ..................................................................................98
HCA .............................................................................. 368
HD ................................................................................ 204
HD and ND ...................................................................... 454
Heatsink ............................................ 41, 42, 43, 44, 45, 46, 47, 48
Heatsink Cooling Fan Off-Delay Time ...................................... 309
Heatsink Cooling Fan Operation Delay Time .............................. 534
Heatsink Cooling Fan Operation Selection............................ 309, 534
Heatsink Overheat ........................................................ 356, 369
Heatsink Temperature.......................................................... 552
Heavy Duty ...................................................................... 204
Heavy Duty Ratings ............................................................ 204
High Current Alarm Selection ................................................ 312
High Frequency Injection...................................................... 157
High Frequency Injection during Overexcitation Deceleration .......... 316
High Performance Operation Using OLV or CLV ......................... 129
High Slip Braking .............................................................. 314
High Slip Braking Current Limit ............................................. 315
High-Slip Braking Current Limit ............................................. 536
High Slip Braking Deceleration Frequency Width......................... 314
High-Slip Braking Deceleration Frequency Width......................... 536
High Slip Braking Dwell Time at Stop ...................................... 315
High-Slip Braking Dwell Time at Stop ...................................... 537
High-slip Braking oL........................................................... 359
High Slip Braking Overload Time............................................ 315
High-Slip Braking Overload Time ........................................... 537
High Slip Suppression Current Level ........................................ 316
High-Slip Suppression Current Level........................................ 537
HSB............................................................................... 257
Humidity ...........................................................................54
Hunting Prevention ............................................................. 313
Hunting Prevention Gain ...................................................... 336
Hunting Prevention Gain Setting ....................................... 313, 536
Hunting Prevention Gain while in Reverse ........................... 313, 536
Hunting Prevention Selection ........................................... 313, 536
Hunting Prevention Time Constant .................................... 313, 536
HVAC Fan Application ........................................................ 134
Hybrid IC Failure ............................................................... 349
H
H1 ...................................................................................98
H1 Multi-Function Digital Input Selections................................. 513
H2 ...................................................................................98
H3-02 ................................................................. 392, 393, 394
H3-09 ............................................................................. 107
H3-10 ....................................................................... 393, 394
H3-11 ............................................................................. 394
H3-13 ....................................................................... 341, 393
H3 Multi-Function Analog Input Settings................................... 522
Hbb ............................................................................... 368
672
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Index
Initial Operation................................................................. 126
Initial Rotor Position Detection Selection ................................... 319
Initial Rotor Position Estimation Current.................................... 319
Input Current .................... 455, 456, 457, 458, 459, 460, 461, 462, 463
Input Fuses................................................................. 448, 630
Input Phase Loss ................................................................ 360
Input Phase Loss Protection Selection ................................. 308, 533
Input Power...................... 455, 456, 457, 458, 459, 460, 461, 462, 463
Input Pulse Monitor ............................................................ 550
Input Terminals ................................................................. 125
Input Terminal Status .......................................................... 548
Input Terminal Status at Previous Fault ..................................... 551
Input Voltage Setting........................................................... 224
Inrush Prevention Circuit Fault ............................................... 364
Inrush Prevention Relay Maintenance Setting .............................. 541
Inspection .................................................................. 400, 401
Installation Area ..................................................................54
Installation Environment.........................................................54
Installation Method Selection ................................................. 311
Installation Orientation...........................................................54
Installation Orientation and Spacing ...........................................54
Installation Spacing...............................................................55
Installing a Braking Resistor\: ERF type .................................... 442
Installing a Braking Resistor Unit\: LKEB type ............................ 442
Installing a Braking Unit\: CDBR Type ..................................... 443
Installing a GFCI................................................................ 445
Installing a Magnetic Contactor ................................................24
Installing a Molded Case Circuit Breaker (MCCB)..........................24
Installing a Motor Thermal Overload (oL) Relay on the Drive Output
..................................................................................... 450
Installing Other Types of Braking Resistors ................................ 443
Installing Peripheral Devices.................................................. 442
Installing the Cooling Fan ..................................................... 410
Integral Limit Setting........................................................... 181
Integral Operation during Accel/Decel ...................................... 202
Integral Operation during Accel/Decel for Motor 2........................ 203
Integral Time Setting (I) ....................................................... 181
Interlock Circuit Example ..................................................... 110
Internal Dynamic Braking Resistor Protection Selection (ERF type)...307,
533
Inversion Detection............................................................. 350
Inversion Prevention Detection ............................................... 350
IP00/Open Type Enclosure ......................................................39
IP20/NEMA Type 1 Enclosure .................................................39
IP20/NEMA Type 1 Kit ....................................................... 438
IP20/NEMA Type 1 Kit Selection..............................................68
J
Jog Frequency Reference ...................................................... 209
Jump Frequency........................................................... 212, 341
Jump Frequency Width ........................................................ 212
L
L3-01 through L3-06 ........................................................... 341
L3-02 ....................................................................... 392, 394
L3-04 ............................................................................. 392
L3-06 ............................................................................. 392
L3-11 ............................................................................. 341
L7-01 through L7-04 ..................................................... 341, 393
L7-06 ............................................................................. 341
L7-07 ............................................................................. 341
L8-12 ............................................................................. 472
L8-35 ............................................................................. 472
L8-38 ............................................................................. 394
Language Selection............................................................. 156
LCD Display .................................................................... 116
Leakage Inductance Alarm .................................................... 379
Leakage Inductance Error ..................................................... 382
LED Check ...................................................................... 552
LED Operator ................................................................... 437
LF ................................................................................. 353
LF2 ............................................................................... 353
LF3 ............................................................................... 353
Line-to-Line Motor Resistance Online Tuning ............................. 538
Line-to-Line Resistance Error................................................. 380
LO/RE ................................................................ 117, 125, 148
LO/RE (LOCAL/REMOTE) Key Function Selection ..................... 168
LO/RE LED ..................................................................... 117
LO/RE Light..................................................................... 115
LO/RE Selection Key .......................................................... 115
Load Current .................................................................... 538
Load Inertia................................................................ 321, 539
Load Inertia Ratio................................................... 203, 299, 530
LOCAL........................................................................... 125
LOCAL/REMOTE Key Function Selection ................................ 540
LOCAL/REMOTE Run Selection............................................ 168
Loopback Test................................................................... 605
Loss of Reference Function ................................................... 301
Low Voltage Directive ......................................................... 630
Low Voltage Wiring for Control Circuit Terminals ....................... 647
LT-1 .............................................................................. 369
LT-2 .............................................................................. 369
LT-3 .............................................................................. 369
LT-4 .............................................................................. 369
673
Index
M2 ..................................................................................99
M3 ..................................................................................99
M4 ..................................................................................99
M5 ..................................................................................99
M6 ..................................................................................99
MA..................................................................................99
Magnetic Flux Compensation Value ......................................... 171
Main Circuit Connection Diagram ........................................ 75, 97
Main Circuit Terminal ...........................................................49
Main Circuit Terminal and Motor Wiring.....................................96
Main Circuit Terminal Block Configuration ..................................79
Main Circuit Terminal Functions...............................................87
Main Circuit Terminal Wiring ..................................................49
Main Circuit Wiring ..............................................................87
Main Power Circuit Voltage Adjustment Gain ............................. 529
Maintenance ............................................................... 266, 404
Maintenance Alarms ........................................................... 404
Maintenance Monitors ......................................................... 330
Maintenance Monitor Settings ................................................ 327
Master Speed Reference Lower Limit ....................................... 212
Maximum Applicable Motor Capacity ....455, 456, 457, 458, 459, 460,
461,
462,
463
Maximum Output Frequency....227, 455, 456, 457, 458, 459, 460, 461,
462,
463
Maximum Output Voltage..... 455, 456, 457, 458, 459, 460, 461, 462, 463
Maximum Voltage.............................................................. 227
MB ..................................................................................99
MC ..................................................................................99
Mechanical Weakening Detection............................................ 266
Mechanical Weakening Detection 1 ................................... 359, 370
Mechanical Weakening Detection 2 ......................................... 363
Mechanical Weakening Detection Operation ......................... 304, 532
Mechanical Weakening Detection Speed Level ...................... 305, 532
Mechanical Weakening Detection Start Time ........................ 305, 532
Mechanical Weakening Detection Time............................... 305, 532
MECHATROLINK-II Parameters ........................................... 242
MEMOBUS/Modbus Comm. Test Mode Complete ....................... 371
MEMOBUS/Modbus Communication Error.......................... 347, 366
MEMOBUS/Modbus Communications Reference......................... 553
MEMOBUS/Modbus Communication Test Mode Error .................. 372
MEMOBUS/Modbus Data Table............................................. 607
MEMOBUS/Modbus Error Code ............................................ 549
MEMOBUS/Modbus Error Codes ........................................... 624
MEMOBUS/Modbus Setup Parameters ..................................... 598
MEMOBUS/Modbus Specifications ......................................... 595
MEMOBUS/Modbus Switch Settings ....................................... 108
MEMOBUS/Modbus Termination .............................................49
Menu Structure for Digital Operator ......................................... 119
Message Format................................................................. 603
Middle Output Frequency ..................................................... 228
Middle Output Frequency 2 ................................................... 228
Middle Output Frequency Voltage ........................................... 228
Middle Output Frequency Voltage 2 ......................................... 228
Mid Output Voltage A ......................................................... 336
Minimum KEB Time........................................................... 293
Minimum Output Frequency .................................................. 228
Minimum Output Frequency Voltage........................................ 228
Minimum Output Voltage ..................................................... 336
Minimum Wait Time for Sending Messages................................ 602
Minor Alarms ................................................................... 343
674
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Index
Motor d-Axis Current at Previous Fault ..................................... 551
Motor d-Axis Inductance ...................................................... 235
Motor Direction at Power Up when Using Operator................. 326, 541
Motor Direction Error .......................................................... 381
Motor Does Not Rotate ........................................................ 389
Motor Excitation Current (ld) ................................................. 555
Motor Hunting and Oscillation Control Parameters ....................... 341
Motor Induction Voltage Constant 1 ......................................... 236
Motor Induction Voltage Constant 2 ......................................... 236
Motor Inertia .............................................................. 147, 203
Motor Iron-Core Saturation Coefficient ..................................... 379
Motor Iron-Core Saturation Coefficient 1 ................................... 229
Motor Iron-Core Saturation Coefficient 2 ................................... 230
Motor Iron Loss ........................................................... 143, 545
Motor Iron Loss for Torque Compensation ................................. 230
Motor is Too Hot ............................................................... 390
Motor Leakage Inductance .................................................... 229
Motor Line-to-Line Resistance ............................................... 229
Motor Mechanical Loss ........................................................ 230
Motor No-Load Current.................................................. 143, 229
Motor Overheat ................................................................. 370
Motor Overheat (NTC Input) ........................................... 357, 370
Motor Overheat Alarm (PTC Input).......................................... 357
Motor Overheat Alarm Operation Selection .......................... 284, 526
Motor Overheat Fault (PTC Input) ........................................... 357
Motor Overheat Fault Operation Selection............................ 284, 526
Motor Overload ................................................................. 357
Motor Overload Estimate (oL1) .............................................. 553
Motor Overload Protection Selection ............................ 266, 526, 648
Motor Overload Protection Time ................................. 282, 526, 648
Motor Parameters ............................................................... 224
Motor Performance Fine-Tuning ............................................. 336
Motor PG Feedback Line Driver Interface .................................. 437
Motor PG Feedback Open Collector Interface.............................. 437
Motor Poles...................................................................... 140
Motor Produces Insufficient Torque ......................................... 394
Motor Protection ................................................................ 280
Motor Protection Using a Positive Temperature Coefficient Thermistor
..................................................................................... 274
Motor PTC Characteristics .................................................... 284
Motor Pull Out or Step Out Detection ....................................... 362
Motor q-Axis Current at Previous Fault ..................................... 551
Motor q-Axis Inductance ...................................................... 236
Motor Rated Current ............................. 140, 142, 228, 235, 544, 647
Motor Rated Power ........................................... 142, 230, 235, 544
Motor Rated Slip.......................................................... 143, 228
Motor Rated Voltage ............................................... 140, 142, 544
Motor Rotates After the Drive Output is Shut Off ......................... 394
Motor Rotates Faster Than the Frequency Reference...................... 392
Motor Rotates in One Direction Only........................................ 390
Motor Secondary Current (Iq) ................................................ 555
Motor Selection ................................................................. 253
Motor Selection 1/2............................................................. 544
Motor Speed ..................................................................... 548
Motor Speed at Previous Fault ................................................ 550
Motor Speed Error 2............................................................ 382
Motor Speed Fault .............................................................. 381
Motor Stalls During Acceleration or With Large Loads .................. 391
Motor Stator Resistance........................................................ 235
Motor Switch during Run...................................................... 372
N
n1-02.............................................................................. 336
n2-01.............................................................................. 337
n2-02.............................................................................. 337
n2-03.............................................................................. 337
Nameplate..........................................................................35
ND ................................................................................ 204
ndAT.............................................................................. 385
NetRef/ComRef Function Selection.......................................... 243
Network Termination .......................................................... 596
Noise From the Drive or Motor Cables When the Drive is Powered On
..................................................................................... 393
No-Load Current Alarm ....................................................... 380
No-Load Current Error......................................................... 380
No-Load Operation ............................................................. 148
No-Load Operation Test Run ................................................. 148
Normal Duty..................................................................... 204
Normal Duty Ratings........................................................... 204
Notes on Inertia Tuning and ASR Gain Auto-Tuning ..................... 139
Notes on Rotational Auto-Tuning ............................................ 138
Notes on Stationary Auto-Tuning ............................................ 138
nSE ............................................................................... 353
Number of Auto Restart Attempts...................................... 302, 531
Number of Motor Poles ...................................... 142, 229, 235, 544
Number of PM Motor Poles ................................................... 145
Number of Run Commands ................................................... 552
Number of Run Commands Counter Initialization......................... 328
Number of Speed Search Restarts ............................................ 176
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
675
Index
O
o2-01.............................................................................. 389
o2-03.............................................................................. 151
o2-04.............................................................................. 336
oC ................................................................................. 353
oFA00 ............................................................................ 354
oFA01 ............................................................................ 354
oFA03 to oFA06 ................................................................ 355
oFA10 ............................................................................ 355
oFA11 ............................................................................ 355
oFA12 to oFA17 ................................................................ 355
oFA30 to oFA43 ................................................................ 355
oFb00 ............................................................................. 355
oFb01 ............................................................................. 355
oFb02 ............................................................................. 355
oFb03 to oFb11 ................................................................. 355
oFb12 to oFb17 ................................................................. 355
oFC00 ............................................................................ 355
oFC01 ............................................................................ 356
oFC02 ............................................................................ 356
oFC03 to oFC11 ................................................................ 356
oFC12 to oFC17 ................................................................ 356
Offset Frequency.......................................................... 223, 555
oH ........................................................................... 356, 369
oH1 ............................................................................... 356
oH2 ............................................................................... 369
oH3 ......................................................................... 357, 370
oH4 ............................................................................... 357
oH5 ......................................................................... 357, 370
oH Alarm Location Monitor .................................................. 554
oL1................................................................................ 357
oL2.......................................................................... 358, 394
oL2 Characteristics Selection at Low Speeds......................... 309, 534
oL3.......................................................................... 358, 370
oL4.......................................................................... 358, 370
oL5.......................................................................... 359, 370
oL7................................................................................ 359
Online Tuning Gain ............................................................ 319
Online Tuning Selection ....................................................... 319
oPE ............................................................................... 374
oPE01 ............................................................................ 374
oPE02 ............................................................................ 374
oPE03 ............................................................................ 374
oPE04 ............................................................................ 375
oPE05 ............................................................................ 375
oPE06 ............................................................................ 375
oPE07 ............................................................................ 375
oPE08 ............................................................................ 376
oPE09 ............................................................................ 376
oPE10 ............................................................................ 377
oPE11 ............................................................................ 377
oPE13 ............................................................................ 377
oPE15 ............................................................................ 377
oPE16 ............................................................................ 377
oPE18 ............................................................................ 377
oPE Fault Parameter............................................................ 549
Open Loop Vector Control ....................................32, 337, 392, 394
Open Loop Vector Control for IPM Motors ..................................32
Open Loop Vector Control for PM Motors ...................................32
676
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Index
ov............................................................................ 359, 371
Overcurrent ...................................................................... 353
Overcurrent Detection Gain ............................................. 310, 534
Overexcitation Deceleration................................................... 297
Overexcitation Deceleration Gain ...................................... 316, 537
Overexcitation Operation Selection .................................... 316, 537
Overheat 1 (Heatsink Overheat) .............................................. 356
Overheat Alarm Level.................................................... 266, 533
Overheat Pre-Alarm Operation Selection ............................. 268, 533
Overload Protection ............................................................ 465
Overload Tolerance............. 455, 456, 457, 458, 459, 460, 461, 462, 463
Overspeed (for Control Mode with PG) ............................... 359, 371
Overspeed Detection Delay Time ............................................ 237
Overspeed Detection Level.................................................... 237
Overtorque 1..................................................................... 370
Overtorque 2..................................................................... 370
Overtorque Detection 1 ........................................................ 358
Overtorque Detection 2 ........................................................ 358
Overtorque Detection Operation.............................................. 303
Overvoltage...................................................................... 359
Overvoltage Protection......................................................... 465
Overvoltage Suppression Function ........................................... 298
Overvoltage Suppression Function Selection ............................... 298
ov Suppression Function Selection........................................... 529
P
Parameter Access Level........................................................ 151
Parameter Range Setting Error................................................ 374
Parameter Selection Error ..................................................... 376
Parameter Settings .............................................................. 121
Parameters for KEB Ride-Thru ............................................... 291
Parameters that Change with the Motor Code Selection .................. 579
Parameters to Minimize Motor Hunting and Oscillation .................. 341
PASS ............................................................................. 371
Password ................................................................... 151, 158
Password Setting................................................................ 158
Password Settings............................................................... 151
P Control ......................................................................... 177
Peak Hold Current .............................................................. 552
Peak Hold Output Frequency ................................................. 553
Performance Life ............................................................ 403, 3
Performance Life Monitors Maintenance Monitors........................... 3
Periodic Inspection ............................................................. 401
Periodic Maintenance .......................................................... 266
Permanent Magnet Motor Control............................................... 3
PF ................................................................................. 360
PG 1 Division Rate for PG Pulse Monitor .................................. 238
PG 1 Gear Teeth 1 .............................................................. 239
PG 1 Gear Teeth 2 .............................................................. 239
PG 1 Pulses Per Revolution ................................................... 237
PG 1 Rotation Selection ....................................................... 238
PG 1 Signal Selection .......................................................... 239
PG 2 Division Rate for PG Pulse Monitor .................................. 238
PG 2 Gear Teeth 1 .............................................................. 239
PG 2 Gear Teeth 2 .............................................................. 239
PG 2 Pulses Per Revolution ................................................... 237
PG 2 Rotation Selection ....................................................... 238
PG 2 Signal Selection .......................................................... 239
PG-B3 ............................................................................ 437
PG-B3 Settings.................................................................. 237
PG Disconnect (for any control modes using a PG option card) ......... 361
PG Disconnect (for Control Mode with PG) ................................ 371
PG Hardware Fault (detected when using a PG-X3 option card) ... 361,
371
PG Number of Pulses Per Revolution........................................ 143
PG Number of Pulses Per Revolution for PM Motor Tuning............. 146
PGo ......................................................................... 361, 371
PGoH ....................................................................... 361, 371
PG Open-Circuit Detection Time............................................. 237
PG Option Card Disconnection Detection 1 ................................ 239
PG Option Card Disconnection Detection 2 ................................ 239
PG Option Card Port for Motor 2 Selection................................. 240
PG Speed Control Card Settings.............................................. 237
PG-X3 ............................................................................ 437
PG-X3 Settings.................................................................. 237
Phase Order Selection .......................................................... 168
PID Accel/Decel Time ......................................................... 185
PID Block Diagram............................................................. 180
PID Control...................................................................... 177
PID Feedback ................................................................... 554
PID Feedback High Detection Level......................................... 184
PID Feedback High Detection Time ......................................... 184
PID Feedback Input Methods ................................................. 178
PID Feedback Loss ....................................................... 352, 368
PID Feedback Loss Detection Selection..................................... 183
PID Feedback Low Detection Level ......................................... 183
PID Feedback Low Detection Time.......................................... 184
PID Fine Tuning ................................................................ 187
PID Function Setting ........................................................... 181
PID Input (feedback) ........................................................... 554
PID Input Limit ................................................................. 186
PID Monitors .................................................................... 330
PID Offset Adjustment......................................................... 182
PID Output....................................................................... 554
PID Output Fault................................................................ 394
PID Output Gain Setting....................................................... 182
PID Output Level Selection ................................................... 182
PID Output Limit ............................................................... 181
PID Output Lower Limit....................................................... 185
PID Output Reverse Selection ................................................ 182
PID Primary Delay Time Constant ........................................... 182
PID Setpoint ..................................................................... 554
PID Setpoint Display Digits................................................... 186
PID Setpoint Input Methods................................................... 178
PID Setpoint Scaling ........................................................... 185
PID Setpoint Selection ......................................................... 185
PID Setpoint User Display .................................................... 186
PID Setpoint Value ............................................................. 185
PID Sleep ........................................................................ 184
PID Sleep Delay Time ......................................................... 184
PID Sleep Function Start Level ............................................... 184
PM Inductance Error ........................................................... 382
PM Motor Auto-Tuning Mode Selection .................................... 143
PM Motor Base Frequency .................................................... 145
PM Motor Base Speed ......................................................... 145
PM Motor Code ................................................................. 235
PM Motor Code Selection ..................................................... 144
PM Motor Control Tuning..................................................... 319
PM Motor d-Axis Inductance ................................................. 145
PM Motor Induced Voltage Constant ........................................ 146
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
677
Index
PM Motor Parameter Settings................................................. 136
PM Motor q-Axis Inductance ................................................. 145
PM Motor Rated Current ...................................................... 144
PM Motor Rated Power........................................................ 144
PM Motor Rated Voltage ...................................................... 144
PM Motor Settings ............................................................. 144
PM Motor Stator Resistance .................................................. 145
PM Motor Type ................................................................. 144
PM Stationary Auto-Tuning................................................... 136
PM Stationary Auto-Tuning for Stator Resistance ......................... 136
Polarity Judge Timeout ........................................................ 350
Pole Attraction Current ........................................................ 319
Power Detection Filter Time .................................................. 190
Powering Up the Drive......................................................... 131
Power Ratings (Three-Phase 200 V Class)...................... 455, 456, 457
Power Ratings (Three-Phase 400 V Class)...................... 458, 459, 460
Power Ratings (Three-Phase 600 V Class)...................... 461, 462, 463
Power Unit Output Phase Loss 3 ............................................. 353
Predefined V/f Patterns ........................................................ 224
Preface..............................................................................18
Preparing the Ends of Shielded Cables ...................................... 103
Preset Reference Timing Diagram ........................................... 211
Previous Fault ................................................................... 550
PROFIBUS-DP Clear Mode Selection ...................................... 245
PROFIBUS-DP Data Format Selection...................................... 245
PROFIBUS-DP Node Address ............................................... 245
PROFIBUS-DP Parameters ............................................. 242, 245
Programming Mode ...................................................... 120, 121
Proportional Gain Setting (P) ................................................. 181
Protective Cover ..................................................................56
Protective Covers, Reattaching .................................................82
Protective Covers, Removing .............................................. 81, 82
Protective cover to prevent miswiring .........................................49
PTC ............................................................................... 274
Pull-In Current ............................................................ 320, 538
Pull-In Current Compensation Time Constant.............................. 538
Pull-In Current during Accel/Decel for PM................................. 362
Pull-In Current Level for PM Motor Tuning................................ 146
Pulse Monitor Selection Error ................................................ 377
Pulse Output Connection Using External Voltage Supply ................ 107
Pulse Output Connection Using Internal Voltage Supply ................. 106
Pulse Train Input/Output....................................................... 258
Pulse Train Input Bias.......................................................... 278
Pulse Train Input Filter Time ................................................. 278
Pulse Train Input Gain ......................................................... 278
Pulse Train Input Minimum Frequency...................................... 278
Pulse Train Input Scaling ...................................................... 278
Pulse Train Input Terminal RP Function Selection ........................ 277
Pulse Train Monitor Scaling .................................................. 278
Pulse Train Monitor Selection ................................................ 278
Q
q-axis ACR Output ............................................................. 555
R
R-.................................................................................. 100
R/L1 ................................................................................87
R+ ................................................................................. 100
R1-L11 .............................................................................87
Radiated and Radio Frequency Noise........................................ 448
678
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Index
RUN Key ........................................................................ 115 Slip Compensation Primary Delay Time .............................. 195, 337
RUN LED........................................................................ 117 Slip Compensation Selection during Regeneration ........................ 195
RUN Light ....................................................................... 115 SN...................................................................................98
Soft Charge Bypass Relay Maintenance..................................... 552
S
Soft Charge Bypass Relay Maintenance Time.............................. 369
S- .................................................................................. 100 Soft CLA Selection ............................................................. 534
S/L2.................................................................................87 Soft Starter Speed Reference at Previous Fault............................. 551
S+ ................................................................................. 100 Software Current Limit Selection ............................................ 310
S1 ...................................................................................98 Software No. (Flash) ........................................................... 550
S1-L21..............................................................................87 Software No. (PWM)........................................................... 550
S2 ...................................................................................98 Software No. (ROM) ........................................................... 550
S3 ...................................................................................98 Software version ..................................................................35
S4 ...................................................................................98 Space Between Drives (Side-by-Side Mounting) ............................55
S5 ...................................................................................98 Speed/Torque Control Switchover Time .................................... 222
S6 ...................................................................................98 Speed Agree 1 Time Chart .................................................... 261
S7 ...................................................................................98 Speed Agree 2 Time Chart .................................................... 264
S8 ...................................................................................98 Speed Agreement Detection Level ..................................... 300, 530
Safe Disable Circuit ............................................................ 651 Speed Agreement Detection Level (+/-) ............................... 300, 530
Safe Disable Function Wiring Example (SINK Mode).................... 652 Speed Agreement Detection Selection....................................... 301
Safe Disable Input Function................................................... 651 Speed Agreement Detection Width .................................... 300, 530
Safe Disable Inputs ...............................................................98 Speed Agreement Detection Width (+/-) .............................. 300, 530
Safe Disable Monitor Output Function and Digital Operator Display
Speed Control Accuracy ....................................................... 464
..................................................................................... 653
Speed Control Integral Time 1 ................................................ 371
Safe Disable Signal Input...................................................... 368
Speed Control Loop Auto-Tuning............................................ 137
Safety Hazard Definitions .......................................................20
Speed Control Proportional Gain 1........................................... 371
Safety Information................................................................20
Speed Control Range ........................................................... 464
Safety Input and EDM Terminal Status ..................................... 653
Speed Deviation (for Control Mode with PG) .............................. 349
Safety Monitor Output ...........................................................99
Speed Deviation (when using a PG option card) ........................... 366
Safety Standard ................................................................. 465
Speed Estimation Type Speed Search........................................ 173
SC .............................................................................98, 361
Speed Feedback Detection Contol (AFR) Tuning.......................... 314
S-Curve Characteristics .................................................. 194, 341
Speed Feedback Detection Control (AFR) Gain ..................... 314, 536
SE ................................................................................. 372
Speed Feedback Detection Control (AFR) Time Constant 1 ....... 314, 536
Search Operation Voltage Limit .............................................. 190
Speed Feedback Detection Control (AFR) Time Constant 2 ....... 314, 536
Self-diagnosing function of the serial communication interface circuits
Speed Feedback Detection Control Gain .............................. 320, 538
..................................................................................... 625
Speed Feedback Detection Control Gain during ov Suppression ........ 322
SEr ................................................................................ 362
Speed Limit...................................................................... 222
Serial Communications Cable Connection Terminals (TB5) ............. 596
Speed Limitation................................................................ 220
Serial Communication Terminals............................................. 100
Speed Limit Bias.......................................................... 220, 222
Serial Communication Transmission Error ................................. 365
Speed Limit Selection .......................................................... 221
Serviceable Parts................................................................ 432
Speed Response ................................................................. 464
Setup Group ..................................................................... 120
Speed Search .................................................................... 164
Setup Group Parameters ....................................................... 125
Speed Search Deactivation Current .......................................... 175
Setup Mode ...................................................................... 121
Speed Search Deceleration Time ............................................. 175
Shielded Twisted-Pair Cables ................................................. 103
Speed Search Delay Time ..................................................... 175
Short Circuit Brake Time at Start............................................. 171
Speed Search Detection Compensation Gain ............................... 176
Short Circuit Brake Time at Stop............................................. 171
Speed Search Method Selection .............................................. 176
Short Circuit Braking Current................................................. 171
Speed Search Restart Current Level.......................................... 176
Side-by-Side Installation.........................................................55
Speed Search Restart Detection Time........................................ 176
Side-by-Side Mounting ........................................................ 472
Speed Search Selection at Start ............................................... 175
Side-by-Side Setup ...............................................................55
Speed Search Wait Time....................................................... 177
Simple Motor Setup Using V/f Control...................................... 128
Stall Prevention ........................................................... 294, 341
Simplified Setup Using the Setup Group .................................... 121
Stall Prevention Detection Time.............................................. 300
Single Drive KEB Ride-Thru 1 ............................................... 288
Stall Prevention Level during Acceleration ........................... 295, 529
Single Drive KEB Ride-Thru 2 ............................................... 288
Stall Prevention Level during Run ..................................... 297, 529
Sink/source jumper S3 ...........................................................49
Stall Prevention Limit during Acceleration ........................... 294, 529
Sinking/Sourcing Mode Switch for Digital Inputs ...........................49
Stall Prevention Selection during Acceleration....................... 294, 529
Slave Address ................................................................... 603
Stall Prevention Selection during Deceleration....................... 296, 529
Slip Compensation.............................................................. 194
Stall Prevention Selection during Run ................................. 297, 529
Slip Compensation Gain ................................................. 194, 337
Standard Connection Diagram ..................................................72
Slip Compensation Limit ...................................................... 195
Starting Torque.................................................................. 464
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
679
Index
Start-Up Flowcharts ............................................................ 126
Stationary Auto-Tuning........................................................ 139
Stationary Auto-Tuning 1...................................................... 135
Stationary Auto-Tuning 2...................................................... 135
Stationary Auto-Tuning for Line-to-Line Resistance ...................... 135
Stator Resistance Error......................................................... 382
Status Display ................................................................... 131
STo ............................................................................... 362
STOP button Input.............................................................. 380
STOP Key ....................................................................... 115
STOP Key Function Selection .......................................... 325, 540
Stopping Method after Communication Error .............................. 598
Stopping Method Selection.................................................... 164
Storage Temperature .............................................................54
Surrounding Area .................................................................54
SvE ............................................................................... 362
Swing PWM ............................................................... 205, 454
Switching Between LOCAL and REMOTE ................................ 125
Switching Between Torque and Speed Control............................. 220
System KEB Ride-Thru 1 ..................................................... 288
System KEB Ride-Thru 2 ..................................................... 288
T
T/L3.................................................................................87
T1-03 ............................................................................. 140
T1-04 ............................................................................. 140
T1-05 ............................................................................. 140
T1-06 ............................................................................. 140
T1-07 ....................................................................... 140, 141
T1-L31 .............................................................................87
Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention
..................................................................................... 298
Task Complete .................................................................. 384
Temperature Derating ............................................................55
Terminal A1 Bias Setting...................................................... 270
Terminal A1 Function Selection.............................................. 269
Terminal A1 Gain Setting ..................................................... 270
Terminal A1 Signal Level Selection ......................................... 269
Terminal A2 Bias Setting...................................................... 271
Terminal A2 Function Selection.............................................. 271
Terminal A2 Gain Setting ..................................................... 271
Terminal A2 Signal Level Selection ......................................... 271
Terminal A3 Bias Setting...................................................... 271
Terminal A3 Function Selection.............................................. 271
Terminal A3 Gain Setting ..................................................... 271
Terminal A3 Signal Level Selection ......................................... 270
Terminal Block Configuration ..................................................79
Terminal Board .........................41, 42, 43, 44, 45, 46, 47, 48, 49, 432
Terminal Board Connection Error............................................ 348
Terminal Board Connector ......................................................49
Terminal Connections for Communication Self-Diagnostics............. 625
Terminal Cover ...............................41, 42, 43, 44, 45, 46, 47, 48, 81
Terminal Cover Screw ...........................................................41
Terminal M1-M2 Function Selection ........................................ 259
Terminal M1-M2 Output Selection .......................................... 242
Terminal M3-M4 Output Selection .......................................... 242
Terminal P1-PC Output Selection ............................................ 242
Terminal P2-PC Output Selection ............................................ 242
Terminal P3-PC Output Selection ............................................ 242
Terminal P4-PC Output Selection ............................................ 242
680
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
Index
Types of Auto-Tuning for Induction Motors................................ 135 V/f Control.........................................................................32
Types of Auto-Tuning for Permanent Magnet Motors .................... 136 V/f Control Mode Tuning ..................................................... 336
V/f Control Mode Tuning Parameters ....................................... 336
U
V/f control using motor speed feedback .......................................32
U/T1 ................................................................................87 V/f Control with Simple Speed Feedback ................................... 277
U1-01 ....................................................................... 389, 391 V/f Data Setting Error.......................................................... 377
U1-07 ............................................................................. 389 V/f Gain During Speed Search................................................ 175
U1-09 ............................................................................. 389 V/f Pattern Defaults ............................................................ 561
U2, U3 Initialization............................................................ 328 V/f Pattern Display Unit ....................................................... 324
U2, U3 Initial Value Selection ................................................ 541 V/f Pattern for Motor 1......................................................... 224
U2-02 ............................................................................. 386 V/f Pattern for Motor 2......................................................... 231
U2-03 through U2-17 .......................................................... 386 V/f Pattern Selection ..................................................... 224, 391
U4-05 ............................................................................. 373 V/T2 ................................................................................87
UL3 ......................................................................... 362, 372 vAEr .............................................................................. 385
UL4 ......................................................................... 362, 372 VERIFY.......................................................................... 326
UL5 ............................................................................... 363 Verifying Parameter Changes ................................................. 120
UL and CSA Standards ........................................................... 3 Verify Menu ..................................................................... 120
UL Standards Compliance.......................................................89 vFyE .............................................................................. 385
UnbC ............................................................................. 363 voF .......................................................................... 364, 373
Undertorque Detection 1................................................. 362, 372 voH Alarm Location Monitor ................................................. 554
Undertorque Detection 2................................................. 362, 372 Voltage Class, Capacity Mismatch .......................................... 385
Undertorque Detection Operation ............................................ 303 Voltage drop calculation formula...............................................89
Undervoltage .................................................................... 372 Voltage Error Compensation Time Constant ............................... 321
Undervoltage 3 .................................................................. 364 vrFy ............................................................................... 385
Undervoltage 3 (Soft-Charge Bypass Circuit Fault) ....................... 364
Undervoltage Detection Level (Uv1) .................................. 292, 527 W
Undervoltage Protection ....................................................... 465 W/T3................................................................................87
Unexpected Noise from Connected Machinery............................. 393 Warranty Information ............................................................27
Unidirectional Speed Limit Bias.............................................. 222 Water Supply Pump Application ............................................. 132
Unit Code ........................................................................ 325 Watt Hour Output Example ................................................... 269
Unit Selection for MEMOBUS/Modbus Register 0025H................. 599 Watt Hour Output Unit Selection............................................. 267
Unstable Motor Speed when Using PM ..................................... 395 Watt Loss 200 V Class Three Phase Models................................ 466
Up/Down 2 Function ........................................................... 213 Watt Loss 400 V Class Three Phase Models................................ 466
Up/Down 2 Operations......................................................... 257 Watt Loss Three-Phase 600 V Class Models............................... 467
Up/Down Command Operation............................................... 252 Wire Gauge, Three Phase 200 V Class ..................................89, 638
Up/Down Frequency Reference Limit Selection ........................... 217 Wire Gauge, Three Phase 400 V Class ..................................91, 641
Up Arrow Key................................................................... 115 Wire Gauge, Three Phase 600 V Class ..................................94, 644
USB Copy Unit ........................................................... 152, 437 Wire Gauges.......................................................................89
USB port (type-B) .......................... 41, 42, 43, 44, 45, 46, 47, 48, 109 Wiring Checklist ................................................................ 111
User Defaults .................................................................... 151 Wiring Diagram for 2-Wire Sequence ....................................... 255
User Monitor Selection after Power Up ............................... 323, 540 Wiring Distance................................................................. 205
User Parameter Automatic Selection............................. 151, 161, 480 Wiring the Control Circuit Terminal ...........................................81
User Parameter Default Value .......................................... 325, 540 WRITE ........................................................................... 326
User Parameters................................................................. 151 Writing Parameter Settings .................................................... 384
User Parameters 1 to 32............................................ 151, 161, 480 Writing to Multiple Registers ................................................. 606
User-Set Display Units Decimal Display.................................... 324
Z
User-Set Display Units Maximum Value.................................... 324
User Set Speed Agree 1 Time Chart ......................................... 261 Zero Servo ....................................................................... 191
User Set Speed Agree 2 Example with a Positive L3-04 Value .......... 264 Zero Servo Completion Width ................................................ 191
Using Braking Units in Parallel............................................... 444 Zero Servo Fault ................................................................ 362
Using the Pulse Train Output ................................................. 106 Zero Servo Gain................................................................. 191
Using the Safe Disable Function.............................................. 651 Zero-Speed Time Chart ........................................................ 260
Uv ................................................................................. 372 Z Pulse Correction Error....................................................... 383
Uv1 ............................................................................... 363 Z Pulse Fault .................................................................... 349
Uv2 ............................................................................... 363 Z Pulse Noise Fault Detection ................................................ 350
Uv3 ............................................................................... 364 Z Pulse Offset Tuning.......................................................... 136
Uv4 ............................................................................... 364
V
V/f Characteristics .............................................................. 464
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
681
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
Date of Publication
682
Revision
Number
Section
November 2010
All
July 2010
All
March 2010
Revised Content
Addition: Larger drive capacities added along with corresponding
data.
Three-Phase 600V: CIMR-Ao5A0125 to 5A0242
Revision: Reviewed and corrected documentation.
Addition: Larger drive capacities added along with corresponding
data.
Three-Phase 400V: CIMR-Ao4A0930 and 4A1200
Three-Phase 600V: CIMR-Ao5A0041 to 5A0099
Revision: Reviewed and corrected documentation.
Added software revision S1015
First Edition. This manual supports drive software versions
VSA90504o and VSA901014.
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
YASKAWA ELECTRIC SIEP C710616 41C YASKAWA AC Drive A1000 Technical Manual
683
YASKAWA AC Drive-A1000
High Performance Vector Control Drive
Technical Manual
YASKAWA AMERICA, INC.
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan
Phone: 81-3-5402-4502 Fax: 81-3-5402-4580
http://www.yaskawa.co.jp
No. 18 Xizang Zhong Road, 17F, Harbour Ring Plaza, Shanghai, 200001, China
Phone: 86-21-5385-2200 Fax: 86-21-5385-3299
http://www.yaskawa.com.cn
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
2010 YASKAWA ELECTRIC CORPORATION. All rights reserved.