You are on page 1of 31

Custom Air Handler Solutions

Custom Units to Meet Your Unique Design Needs

Engineered for flexibility and performance

Contents
Horizontal Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Horizontal with Standard Economizer Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Stacked Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Dual Path Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Heat Recovery Wheel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Fixed Plate Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Multizone Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dedicated Exhaust Energy Recovery Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Redundant Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Short Economizer with Exhaust Air Dampers in Return Fan Section . . . . . . . . . . . . . . . . . . . . 10
Short Economizer with Exhaust Air Dampers in Return Fan Section Side Return . . . . . . . . . 11
Side Return Fan Opening Version II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Side-by-side Energy Recovery Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dual Wheel Energy Recovery Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Plate Heat Recovery Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dual Duct AHU with Final Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Energy Wheel On Skyline Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Dual Direct Drive Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Double Wheel AHU with UV Lights: 3 Fans, Two Exhaust Air Paths . . . . . . . . . . . . . . . . . . . . . 19
Side-by-side Wheel (over 25 kCFM) and Mis-Matched Air Paths . . . . . . . . . . . . . . . . . . . . . . . 20
Stacked ERV with Mismatched Heights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Dual Path Energy Recovery Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Total Wheel + Plate with Two 22 Fan Arrays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Triple Stacked Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Humidifier & Evaporative Cooling Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Split Outside Air Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Bypass Damper on Cooling Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Side-Car Energy Recovery Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

DG 19008-2

Design Guide DG 19008-2-001


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Horizontal Configuration

Supercedes: ED 19008-1

Figure 1: Unit Components

Outdoor Air 75F / 70F

Supply Air 70F / 55F

Add temp boxes on all


standard configurations

Cooling Coil

Dampers

55F / 55F
Filter Section

Return Air

Supply Fan

80F / 67F
Heating Coil

NOTE: Default temperatures are typical and in F, enter your own data by selecting from the drop-down list or highlighting the contents and typing in your custom data.

Standard template in the software program. Temperature boxes are editable.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-002


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Horizontal with Standard Economizer Configuration

Supercedes: ED 19008-1

Figure 1: Unit Components

Exhaust Air

Outdoor Air 75F

Cooling Coil

Dampers

55F / 55F
Return Fan

Supply Fan

Heating Coil

Supply Air
Return Air

58F / 55F

80F / 67F
NOTE: Default temperatures are typical and in F, enter your own data by selecting from the drop-down list or highlighting the contents and typing in your custom data.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-003


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Stacked Configuration

Supercedes: ED 19008-1

Figure 1: Unit Components

Supply Air 58F / 55F

Outdoor Air
75F
Supply Fan

Dampers
Cooling Coil

Return Air

Filter Section

55F / 55F

80F / 67F
Heating Coil

OFF

NOTE: Default temperatures are typical and in F, enter your own data by selecting from the drop-down list or highlighting the contents and typing in your custom data.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-004


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Dual Path Configuration

Supercedes: ED 19008-1

Figure 1: Unit Components

70F / 55F

Damper

Outdoor Air

Heating
Coil
Filter
Section
Cooling
Coil

90F / 78F

Heating
Coil

Damper

Return Air

Filter
Section

80F / 67F

Supply Fan

Supply Air

Cooling
Coil

70F / 55F

OFF

NOTE: Default temperatures are typical and in F, enter your own data by selecting from the drop-down list or highlighting the contents and typing in your custom data.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-005


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Heat Recovery Wheel Configuration

Supercedes: ED 19008-1

Figure 1: Unit Components

Return Air 80F / 67F


Bypass Damper

Exhaust Air

Filter
Section

Exhaust Fan
Recirculation
Bypass
Energy
Recovery
Wheel

83F / 70F

Filter
Section

Outdoor Air
95F / 78F

Supply Fan

Cooling
Coil
Heating
Coil
Bypass Damper

70F / 55F

Supply Air
70F / 55F

NOTE: Default temperatures are typical and in F, enter your own data by selecting from the drop-down list or highlighting the contents and typing in your custom data.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-006


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Fixed Plate Configuration

Supercedes: ED 19008-1

Figure 1: Unit Components

Supply Air
70F / 55F
Heating
Coil

Exhaust Air

Cooling
Coil

Exhaust Fan

Supply Fan

Plate
Damper

Damper
Filter
Section

Outdoor Air
95F / 78F

Filter
Section

Return Air
80F / 67F

NOTE: Default temperatures are typical and in F, enter your own data by selecting from the drop-down list or highlighting the contents and typing in your custom data.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-007


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Multizone Configuration

Supercedes: ED 19008-1

Figure 1: Unit Components

Multizone
Hot Air

Outdoor Air

120F / 68F

75F / 70F

Heating
Coil
Dampers

Damper

Damper

Cooling
Coil

Filter
Section

Return Air
80F / 67F

Supply Fan

Multizone
Cold Air
55F / 55F

NOTE: Default temperatures are typical and in F, enter your own data by selecting from the drop-down list or highlighting the contents and typing in your custom data.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-008


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Dedicated Exhaust Energy Recovery Unit

Supercedes: ED 19008-1

The dedicated exhaust energy recovery unit provides more energy recovery, and often at a lower cost than typical
solutions. It is well suited for LEED buildings and schools because of its ability to economically handle large
ventilation rates.
Figure 1: Unit Components

Side View

Advantages
Recover energy from Class I & II air streams
- Class I air is defined by Standard 62.1 as normal return air with no odors or health issues
- Class II air has some odor, but no health risks (ie: bathroom or cafeteria exhaust) The percentage of class 2
air that may be re-designated as class 1 is limited to no more than 10% by ASHRAE standard 62.
A single air handler for both exhaust air streams
A lower first cost than multiple smaller ERUs for each restroom
Damper and wall arrangement prevents Class II from recirculating to the building
Will work for VAV and CAV type systems
Bypass dampers can be added to the energy recovery wheel to save fan energy in economizer mode

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-009

Custom Air Handler Solutions


Redundant Fans

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

Redundant fans provide 100% back-up for supply and return fans. This can be used to enhance reliability as well
as simplify scheduling of maintenance and service work.
Other features that are shown on this unit include:
1 . Bypass dampers on the energy recovery wheel to save fan energy when in economizer mode.
2 . Return air bypass damper to allow for up to 100% recirculated air in night mode.
Figure 1: Unit Components

Side View

Advantages
Complete flexibility in fan selection allows fans to be identical as well as the option to mix fans for different
operating conditions
Smaller footprint than two units or storing backup fans and parts nearby

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-010

Custom Air Handler Solutions


Short Economizer with Exhaust Air Dampers in Return Fan Section

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

A shorter AHU can be selected by providing exhaust air dampers in the return fan section.
Figure 1: Unit Components and Dimensions

Side View

Plan View

Advantages
Shorter footprint and lower cost than traditional air side economizers
Flexible damper location for exhaust and OA dampers to accommodate installation requirements. (Either side,
top or end)
Installations in cold climates should use a blender and possibly look at splitting the outside air dampers to
encourage better mixing. Check on freeze protection offerings

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-011

Custom Air Handler Solutions


Short Economizer with Exhaust Air Dampers in Return Fan Section
Side Return

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

A shorter AHU can be selected by providing exhaust air dampers in the return fan section.
Side return opening allows for unit to better match building limitations for the return air path
Exhaust air damper is located on the left hand end of the AHU
Damper locations can be customized to any side or size in order to accommodate installation requirements.
The designer should remember to pay attention to air mixing in climates with cold or hot & humid conditions
Figure 1: Unit Components and Dimensions

Side View

Plan View

Advantages
Shorter footprint and smaller unit size than a traditional air side economizers
The smaller size can provide a lower cost depending on the damper size requirements of the unit

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-012


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Side Return Fan Opening Version II

Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Plan View

Advantages & Notes


L-shape fit best in mechanical room
Eliminated fan array needed to shorten unit

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-013

Custom Air Handler Solutions


Side-by-side Energy Recovery Units

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

A side-by-side arrangement can simplify layout of energy recovery units


Figure 1: Unit Components

Side View
Plan View

Advantages
Exhaust and supply air streams do not have to evenly match dimensions. Wheel performance will change
Large units may not fit in an over/under arrangement
Flexible wheel selection and placement can help the designer to optimize performance

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-014


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Dual Wheel Energy Recovery Unit

Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Side View

Advantages
A dual wheel AHU combines a total energy wheel with a sensible wheel that provides very good 100% outside
air performance.
The addition of the sensible wheel gives a higher effectiveness and reheats the supply air from saturated to a
more neutral relative humidity
These are often supplied on geothermal WSHP projects because they can significantly lower the outside air
loads and results in a smaller geothermal loop

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-015

Custom Air Handler Solutions


Plate Heat Recovery Unit

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Side View

Plate AHU Energy Recovery


Supply air stream
Return air stream
Exhaust air stream
Sensible recovery from exhaust air
Economizer air stream
Stacked arrangement

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-019


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Dual Duct AHU with Final Filters

Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Side View

Advantages & Notes


Replacement units for healthcare that now need final filters

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-020


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Energy Wheel On Skyline Unit

Supercedes: ED 19008-1

Figure 1: Energy Wheel on Skyline

Side View

Advantages
Low profile unit with energy recovery
Rooftop application frees interior space for customer use
Only use the horizontally mounted wheel if very low height is required. A vertically mounted wheel is available
in a side-by-side that will be a lower cost and smaller footprint.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-021


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Dual Direct Drive Fans

Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Plan View

Advantages & Notes


Better redundancy, footprint, turndown, etc.
Possible on large and small units

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-022


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Double Wheel AHU with UV Lights: 3 Fans, Two Exhaust Air Paths

Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Side View
The two separate exhaust air streams allow isolation of flows and optimization of separate fan systems.
The dual wheels provide a very efficient treatment of outside air that can lower first cost expenses for
compressor cooling, heating and possible geothermal loop costs.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-023

Custom Air Handler Solutions


Side-by-side Wheel (over 25 kCFM) and Mis-Matched Air Paths

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Plan View

Advantages & Notes


Single supply air path is larger than Outside Air path
Dual plenum fans
Bypass dampers on wheel

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-024


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Stacked ERV with Mismatched Heights

Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Side View

Advantages & Notes


Split level of stacked section does not have to match single height section
Reduces height and cost of total unit
Differences can be larger, but usually not huge

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-025


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Dual Path Energy Recovery Unit

Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Side View

Advantages & Notes


Dual path provides an exhaust airflow only path and a second path for return or exhaust airflow.
It is possible to draw exhaust air from both exhaust air streams in this case if the negative static of the supply
fan is less than the exhaust at the recirculation damper.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-026


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Total Wheel + Plate with Two 22 Fan Arrays

Figure 1: Unit Components

Side View

Advantages & Notes


22 fan array provides redundancy and a smaller footprint
Plate and coil wrap-around provides treatment of outside airflow
Plate has zero cross leakage

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Supercedes: ED 19008-1

Design Guide DG 19008-2-027


Group: Air Handling Units

Custom Air Handler Solutions

Date: November 2012

Triple Stacked Unit

Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Side View

Advantages & Notes


Third level simplified duct tie-in for contractor

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-028

Custom Air Handler Solutions


Humidifier & Evaporative Cooling Section

Figure 1: Unit Components

Advantages & Notes


Nortec model MH direct humidification for Data Centers
Evaporative cooling for the Western US
Simple section in Vision AHU
Stainless basin
Controller included

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

Design Guide DG 19008-2-029

Custom Air Handler Solutions


Split Outside Air Dampers

Figure 1: Unit Components and Dimensions

Advantages
Lower cost air measuring with smaller OA damper
LEED and Std 189 jobs may require all OA be measured

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

Design Guide DG 19008-2-030

Custom Air Handler Solutions


Bypass Damper on Cooling Coil

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Advantages
Bypass damper can save the fan energy for the air pressure drop of the coil. Typically
.75"-1.00" of static can be reduced off of the fan for all economizer hours and heating
hours.
Can be provided as a single height unit or as a multiple height unit for larger units that
may have interference issues.

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

Design Guide DG 19008-2-031

Custom Air Handler Solutions


Side-Car Energy Recovery Wheel

Group: Air Handling Units


Date: November 2012
Supercedes: ED 19008-1

Figure 1: Unit Components and Dimensions

Advantages
Provides a more square footprint where a long AHU might not work
Can match a smaller wheel with a a larger AHU to handle smaller percentages of OA
with a larger return air AHU

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

2013 Daikin Applied McQuay 1-800-432-1342 www.DaikinMcQuay.com

DG 19008-2

You might also like