You are on page 1of 711

TOMO 2: INSTRUMENTACIN

Y CONTROL
PROYECTO
EXPLOTACIN
MINA MINISTRO HALES
Outotec Chile S.A.

Contenido

22/05/2012

Pgina

Captulo 1: Filosofa de Control

Captulo 2: Listado de Equipos

Captulo 3: Mantencin
1. Descripcin General

2. Manuales de Instrumentos

3. Listado de P&ID

Outotec Chile S.A.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

TOMO 2: INSTRUMENTACIN
Y CONTROL
PROYECTO
EXPLOTACIN
MINA MINISTRO HALES
Outotec Chile S.A.

22/05/2012

1 (4)

Captulo

Filosofa de Control

En el anexo Tomo 2 Captulo 1 se adjunta la filosofa de control de las celdas, la cual


entregar al operador y al supervisor del rea, un mayor entendimiento del funcionamiento
de stas.

Outotec Chile S.A.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

TOMO 2: INSTRUMENTACIN
Y CONTROL
PROYECTO
EXPLOTACIN
MINA MINISTRO HALES
Outotec Chile S.A.

22/05/2012

2 (4)

Captulo

Listado de Instrumentos

En el anexo Tomo 2 Captulo 2 se detalla el listado completo de instrumentos que poseen


las TankCell-e160, TankCell-e300 y Sopladores.
En este listado, es posible encontrar datos tales como el Tag y el tipo de instrumento,
equipo al cual est sociado, dmetro y otras caractersticas que ayudan a identificar las
partes de la celda.

Outotec Chile S.A.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

TOMO 2: INSTRUMENTACIN
Y CONTROL
PROYECTO
EXPLOTACIN
MINA MINISTRO HALES
Outotec Chile S.A.

22/05/2012

3 (4)

Captulo

Mantencin de Instrumentos

1. Descripcin General
Se recomienda una mantencin preventiva, para prolongar la vida til de equipos e
instrumentos y as aumentar su disponibilidad. El principio de mantencin preventiva
consiste en recambiar o reparar la pieza daada antes de que el equipo falle.
Outotec Chile Ltda., puede entregar repuestos con solicitud de 6 meses de anticipacin:

Rotor

Estator

Vlvulas dardo

Elementos del sistema motoreductor.


La informacin que sigue asegurar la entrega de las piezas correctas.

Tipo
Nmero de Serie
Nmero de Pieza
Nmero de Plano

Contacto en Outotec Chile Ltda.:


Nombre
Cargo
Telfono
Direccin
E-Mail

: Sr. Eduardo Paredes Ruiz


: Gerente de Servicios
: +56 02 336 2099
: Avda. Vitacura N 2939, piso 7
: eduardo.paredes@outotec.com

Outotec Chile S.A.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

TOMO 2: INSTRUMENTACIN
Y CONTROL
PROYECTO
EXPLOTACIN
MINA MINISTRO HALES
Outotec Chile S.A.

22/05/2012

4 (4)

2. Manuales de Instrumentos
Adjunto en el anexo Tomo 2 Captulo 3 se entregan las hojas de datos y manuales de los
principales instrumentos asociados a las TankCell-e160 y TankCell-e300.
Las hojas de datos estn ordenadas en el siguiente orden:
Descripcin de Dispositivos Flujmetros Aire Flotacin.
Descripcin de Dispositivos Vlvulas de Control Aire Flotacin.
Descripcin de Dispositivos Manometros
Descripcin de Dispositivos Niveles Ultrasnicos.
Instrumentos Soplador
Los manuales estn ordenados en el siguiente orden:
Descripcin de Dispositivos Flujmetros Aire Flotacin.
Descripcin de Dispositivos Vlvulas de Control Aire Flotacin.
Descripcin de Dispositivos Niveles Ultrasnicos.

3. Listado de P&ID
Tambin se adjuntan los siguientes P&ID y planos:
TankCell-e160 (una celda)

NC5059-0022

TankCell-e160 (dos celda)

NC5059-0021

TankCell-e300

NC5059-0020

Sistema Fail Close

NC5059-0027

Soplador

NC5059-0023

Soplador Diagrama Unilineal

NC5059-0024

Outotec Chile Ltda.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

TOMO 2: INSTRUMENTACIN
Y CONTROL
PROYECTO
EXPLOTACIN
MINA MINISTRO HALES
Outotec Chile S.A.

22/05/2012

1 (1)

Anexos
Tomo 2
Captulo 1

Outotec Chile S.A.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

CORPORACION NACIONAL DEL COBRE


CODELCO CHILE
VICEPRESIDENCIA DE PROYECTOS
PROYECTO EXPLOTACION MINA MINISTRO HALES

CELDAS DE FLOTACION

Proyecto N DQ 110071

MANUAL
FILOSOFA DE CONTROL

Documento N DQ110071-C5059-MA-0030

O/C N H336073-PM014/0

REV

DESCRIPCIN

PREPAR

REVIS

APROB

FECHA

PARA INFORMACIN CLIENTE

A.T.R.

G.H.P.

G.H.P.

30-01-2012

PARA INFORMACIN CLIENTE

A.T.R.

G.H.P.

G.H.P.

22-11-2011

PARA COORDINACIN INTERNA

A.T.R.

G.H.P.

G.H.P.

20-09-2011

Outotec Chile S.A.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

CORPORACION NACIONAL DEL COBRE


PROYECTO EXPLOTACION
MINA MINISTRO HALES
CELDAS FLOTACION

FILOSOFIA DE CONTROL
DQ-110071-C5059-MA-0030
REVISION 1

INDICE
1.

Planos Asociados ....................................................................................................... 3

2.

Circuito de Flotacin ................................................................................................... 3

3.

Regulacin del Nivel de Pulpa .................................................................................... 4

4.

Panel Local de Vlvulas del tipo Dardo (Dart) ............................................................ 5

5.

Suministro de Aire de Flotacin .................................................................................. 6

6.

Distribucin y Regulacin de Aire de Flotacin ........................................................... 7

7.

Reductor..................................................................................................................... 8

Outotec Chile Ltda.


I:\MINPRO\DQ110090\C\5087\IN\DE110071-C5059-MA-0030 R1 Filosofia Control Celdas MMH.doc

Pgina 2 de 8

CORPORACION NACIONAL DEL COBRE


PROYECTO EXPLOTACION
MINA MINISTRO HALES
CELDAS FLOTACION

FILOSOFIA DE CONTROL
DQ-110071-C5059-MA-0030
REVISION 1

1. Planos Asociados
Constituyen referencias a este documento:
Nro. Documento

Descripcin

DQ110071-C5059-0020

CELDA OUTOTEC 1 TANK CELL 300 DIAGRAMA P&ID

DQ110071-C5059-0021

CELDA OUTOTEC 2 TANK CELL 160 DIAGRAMA P&ID

DQ110071-C5059-0022

CELDA OUTOTEC 1 TANK CELL 160 DIAGRAMA P&ID

DQ110071-C5059-0023

P&ID BLOWER
MANUAL DE OPERACIONES BLOWER
MANUAL DE MANTENIMIENTO REDUCTOR

DQ110071-C5059-023

PANEL LAYOUT PANEL LOCAL

2. Circuito de Flotacin
El circuito de flotacin consiste de 12 Celdas de Flotacin TankCell-300 en la etapa de
Flotacin Rougher, distribuidas en 2 bancos de 6 celdas cada uno; seguido de 14 celdas de
flotacin TankCell-160 distribuidas en 2 bancos de 4 celdas seguido de 3 celdas
correspondientes a las etapas de First Cleaner y First Cleaner Scavenger respectivamente.
Terminando con un banco de 6 Celdas de Flotacin TankCell-300 correspondiente a la
etapa Second Scavenger.
En general, cada celda de flotacin cuenta con un lazo regulador de nivel de pulpa compuesto
por un flotador ms sensor de nivel cuya seal se enva al DCS de la planta el cual comanda a
dos vlvulas dardo en paralelo en la descarga de cada celda. Las vlvulas dardos son de
dimetros fijos y estn ubicadas en el fondo de la caja de descarga de cada celda.
Tambin es regulada la adicin de aire de flotacin mediante un cuadro de control de flujo que
consiste de un transmisor de flujo msico y una vlvula de control tipo mariposa.
El concentrado de la celda es recolectado por canaletas radiales y perimetrales, las que estn
revestidas de goma. Por otro lado, el cono ajustable en altura ubicado dentro del estanque
mejora la remocin de espuma.
El estanque est recubierto interna y externamente con pintura epxica y parcialmente
reforzado en su interior con goma, las vlvulas dardo y el interior de las cajas de alimentacin
y de descarga tambin estn recubiertas con goma.

Outotec Chile Ltda.


I:\MINPRO\DQ110090\C\5087\IN\DE110071-C5059-MA-0030 R1 Filosofia Control Celdas MMH.doc

Pgina 3 de 8

CORPORACION NACIONAL DEL COBRE


PROYECTO EXPLOTACION
MINA MINISTRO HALES
CELDAS FLOTACION

FILOSOFIA DE CONTROL
DQ-110071-C5059-MA-0030
REVISION 1

3. Regulacin del Nivel de Pulpa


La regulacin del nivel de pulpa en la celda est basada en un lazo de control Proporcional +
Integral (P+I) estndar implementado en el DCS de la planta, que activa los actuadores (LY)
de las vlvulas de control (LV) tipo Dardos, ubicadas en la descarga de la celda medida.
Simultneamente se mide el nivel (LIT) de la celda a travs de un sensor de nivel ultrasnico,
que mide la posicin de un flotador en la superficie del lquido en la celda De esta manera, se
abrirn o cerrarn simultneamente estas vlvulas produciendo el efecto de vaciado o llenado
dependiendo las condiciones de operacin. Con esta medicin se puede obtener
indirectamente la banda de espuma que es la distancia entre el labio de rebose hasta el nivel
del liquido o pulpa, que es en definitiva lo que se trata de controlar.
El objetivo principal del control de nivel es estabilizar el proceso en cuanto a fluctuaciones en
la alimentacin de mineral. Tanto el set point (que determina la banda de la espuma) como
los parmetros del PI (que determinan la dinmica del lazo) deben ser fijados empricamente
en base a la experiencia con el material procesado y su comportamiento con los reactivos de
acuerdo a las caractersticas qumicas y fsicas del mineral. En la etapa de puesta en servicio
de estos equipos, se ajustan dichos parmetros logrando el perfil deseado para la operacin
del banco en su conjunto. Los valores de los parmetros del Controlador PI inicialmente
pueden ser P=0.5 ; I=10-15 s.

Outotec Chile Ltda.


I:\MINPRO\DQ110090\C\5087\IN\DE110071-C5059-MA-0030 R1 Filosofia Control Celdas MMH.doc

Pgina 4 de 8

CORPORACION NACIONAL DEL COBRE


PROYECTO EXPLOTACION
MINA MINISTRO HALES
CELDAS FLOTACION

FILOSOFIA DE CONTROL
DQ-110071-C5059-MA-0030
REVISION 1

4. Panel Local de Vlvulas del tipo Dardo (Dart)


El Panel Local de la Vlvulas Dart, es bsicamente un panel para operar (eventualmente) las
vlvulas de forma Manual por el operador en terreno y cuenta tres modos de operacin
Normal, Solicitud Local y Operacin Local.
Se presupone que el aire de instrumentacin y alimentacin elctrica es ininterrumpible para
el Panel de las vlvulas Dart, por ende se debe considerar como lgica que en caso de corte
de alimentacin al motor o detencin de la lnea de produccin, como accin de seguridad el
cierre de la vlvula dardo impidiendo el paso de material aguas abajo de la celda
correspondiente, de esta forma el Panel se mantiene en una modalidad Normal. Para pasar
este Panel a modo Operacin Local se debe solicitar al DCS mediante un pulsador (que
enva una seal sostenida) encendindose una luz en el panel indicando esta solicitud.
Mientras el DCS de la planta no habilite el Panel con una seal de retorno este se mantendr
en el estado de Solicitud Local no pudiendo operar las vlvulas de forma Local. Al
recepcionar la seal de Habilitacin Local apaga la luz de solicitud y enciende otra luz
indicando la modalidad Operacin Local, en la cual el operador en terreno puede operar las
vlvulas independientemente de forma manual en el panel, en esta modalidad el DCS puede
deshabilitar el panel en todo momento.
El Panel Local tiene como entradas y salidas, las siguientes seales:
a) Presin piloto: Presin que se entrega a los actuadores aislando el posicionador
FF H1 en modo Operacin Local.
b) Aire de Red: Alimentacin de aire de instrumentacin del Panel Local de
Vlvulas Dart.
c) Etapa 1 (A1/B1): Salida neumtica para alimentar actuador de la vlvula Dart 1
logrando su movimiento de forma Local en modo Operacin Local.
d) Etapa 2 (A2/B2): Salida neumtica para alimentar actuador de la vlvula Dart 2
logrando su movimiento de forma Local en modo Operacin Local.
e) Alimentacin de 120 VAC: Alimentacin ininterrumpida del Panel Local de
Vlvulas Dart.
f) Seal de Solicitud: Seal lgica sostenida, alambrada hacia el DCS indicando
peticin para habilitar Panel Local en modo Operacin Local.
g) Seal de Habilitacin: Seal lgica sostenida, alambrada desde el DCS al Panel
habilitar el de Operacin Local.
En resumen se tiene los Modos de Operacin del Panel:
Normal
Solicitud

Local

El control de los actuadores y el monitoreo de ambas


vlvulas Dardos lo tiene el DCS de la Planta.
El control de los actuadores y el monitoreo de ambas
vlvulas Dardos lo tiene el DCS de la Planta. Panel a
espera de habilitacin modo Operacin Local
El Panel tiene el control total del movimiento de las
vlvulas operndolas de forma manual, con
realimentacin al sistema DCS de la posicin de las
vlvulas Dart. El DCS en todo momento puede
deshabilitar esta modalidad.

Outotec Chile Ltda.


I:\MINPRO\DQ110090\C\5087\IN\DE110071-C5059-MA-0030 R1 Filosofia Control Celdas MMH.doc

Pgina 5 de 8

CORPORACION NACIONAL DEL COBRE


PROYECTO EXPLOTACION
MINA MINISTRO HALES
CELDAS FLOTACION

FILOSOFIA DE CONTROL
DQ-110071-C5059-MA-0030
REVISION 1

5. Suministro de Aire de Flotacin


El suministro de aire de flotacin cuenta con tres Sopladores en paralelo (2 funcionando y uno
en standby). Los sopladores son equipos que entregan grandes caudales de aire a una
presin relativamente baja y responden a una curva de presin vs caudal, observando la
curva caracterstica se aprecia que cuanto mayor sea la presin que el sistema requiera
menor ser el caudal de aire que el soplador es capaz de entregar y viceversa.

El panel con cuentan estos Blowers, tiene una finalidad de proteccin del equipo.
Grficamente lo que hace el panel es mover el punto de operacin del Blower dentro de la
curva alejndolo de ciertas reas identificadas como:
Surge o antibombeo: a muy bajo caudal se produce un fenmeno por el cual el
soplador no es capaz de impulsar el aire que tiene en su interior produciendo
corrientes en sentido inverso, esto genera fuertes tensiones axiales en el equipo que
puede llegar a ser destruido.
Sobrecorriente: Al aumentar el caudal, es decir cuando la contrapresin es muy baja,
aumenta consecuentemente la potencia consumida la que puede superar la mxima
que es capaz de entregar el motor.
Outotec Chile Ltda.
I:\MINPRO\DQ110090\C\5087\IN\DE110071-C5059-MA-0030 R1 Filosofia Control Celdas MMH.doc

Pgina 6 de 8

CORPORACION NACIONAL DEL COBRE


PROYECTO EXPLOTACION
MINA MINISTRO HALES
CELDAS FLOTACION

FILOSOFIA DE CONTROL
DQ-110071-C5059-MA-0030
REVISION 1

El Panel o Sistema de Seguridad anti surge y Monitoreo cuenta con un mdulo de


comunicacin ETHERNET TCP-IP, por el cual, puede entregar variada informacin al DCS
de la planta, adems mediante alambrado duro al CCM obtiene un valor de corriente de
consumo del motor del Blower (Seal 4-20mA) y enclavamientos para parada emergencia,
estatus, partir/parar, entre otros.

La funcin principal del panel de seguridad es:


Manejo de las vlvulas (Inlet y Anti Surge) para la secuencia de partida del Blower.
Apertura de la vlvula de Anti Surge en caso de bajo caudal.
Alarma y corte por bajo caudal (Surge o antibombeo)
Alarma y corte por alto caudal (Sobreconsumo o sobre corriente)
Alarmas y cortes por altas vibraciones en rodamientos.
Alarmas y cortes por altas temperaturas en rodamientos.
Alarma por filtro de entrada sucio.
Los valores de alarma y de corte, as como las condiciones pueden programarse en el panel
de control y visualizarse en el DCS mediante comunicacin. No obstante por razones de
seguridad no deben ser modificados una vez puesto en servicio por el especialista del equipo.
De igual modo ocurre con los tiempos de secuencia de movimiento de las vlvulas de succin
y Anti Surge, esta segunda est controlada por un controlador PID, cuyos parmetros se
configuran en puesta en servicio y se entregan posteriormente.

Para ms detalles del funcionamiento del Blower se pueden encontrar en el manual del
proveedor correspondiente (Continental-Industrie)

6. Distribucin y Regulacin de Aire de Flotacin


Desde la matriz principal proveniente de los sopladores, el Aire Flotacin que entra a cada
celda es regulado mediante un lazo de control Proporcional + Integral (P+I) estndar,
implementado en el DCS de la Planta, midiendo este flujo a travs de un Flujmetro por
dispersin Trmica Msico (FIT) y actuando sobre una vlvula de control automtica tipo
mariposa (FV). Adems se dispone de un manmetro de presin del Aire de Flotacin para
visualizar la presin en entrada a la celda.
La regulacin de alimentacin de aire es el mtodo ms rpido para actuar sobre el
desempeo de una Celda de Flotacin, con el cuidad que este lazo deben ser ms lentos que
el lazo de control del Blower evitando que sistema entre en resonancias. Para los valores de
los parmetro del controlador PI inicialmente considerar P=0,2; I = 50s; el SetPoint del flujo de
Aire se puede ajustar empricamente en base a la velocidad de la espuma deseada o a la
experiencia previa con mineral procesado junto con los reactivos. El proceso de ajuste de los
parmetros de control y setpoint de se realizan en la etapa de puesta en servicio del equipo.
En caso de la detencin del motor de giro de la celda, como accin de seguridad se debe
cortar la inyeccin de aire o minimizarlo al mximo de modo de no acumular carga en el Rotor
detenido en el interior de la celda.

Outotec Chile Ltda.


I:\MINPRO\DQ110090\C\5087\IN\DE110071-C5059-MA-0030 R1 Filosofia Control Celdas MMH.doc

Pgina 7 de 8

CORPORACION NACIONAL DEL COBRE


PROYECTO EXPLOTACION
MINA MINISTRO HALES
CELDAS FLOTACION

FILOSOFIA DE CONTROL
DQ-110071-C5059-MA-0030
REVISION 1

Tambin es posible utilizar un Sistema avanzado (Experto) de regulacin del aire y nivel en
base a Cmaras de Imagen de Espuma (FrothMaster ) o analizando en lnea el grado del
concentrado producido por las Celdas (Curierer ), mejorando as la eficiencia o performance
en la produccin de concentrado del conjunto de celdas.

7. Reductor

(Rev.1)

La celda cuenta con un reductor de acoplamiento directo entre el motor elctrico y el eje que
mueve el Rotor de la Celda. ste reductor cuenta con dos Indicadores y dos seales
anlogas que activan las siguientes alarmas:
Nivel de Aceite en el reductor (LI): Indicador para visualizar el nivel de aceite usado
para la lubricacin del reductor, si el indicador muestra nivel bajo la accin debe ser
de relleno de aceite.
Diferencial de presin en el Filtro (PDI): Indica que tan sucio esta el Filtro de Aceite de
la unidad, accin de cambio de filtro segn indicacin (ver catlogo del fabricante).
Presin de Aceite en el Reductor (PIT): Entrega valor de presin en el circuito de
lubricacin con alarma de baja presin (PALL), lo que indica prdida de aceite y es un
enclavamiento de detencin del respectivo motor elctrico.
Seal anloga de temperatura (TIT): Entrega valor de temperatura en el reductor,
monitoreo y alarma para temperaturas extremas, usado tambin para partidas en frio
para activar calefactor.
Para mayor informacin respecto a los rangos normales de operacin del reductor ver el
Manual de Mantenimiento del Reductor.

Outotec Chile Ltda.


I:\MINPRO\DQ110090\C\5087\IN\DE110071-C5059-MA-0030 R1 Filosofia Control Celdas MMH.doc

Pgina 8 de 8

TOMO 2: INSTRUMENTACIN
Y CONTROL
PROYECTO
EXPLOTACIN
MINA MINISTRO HALES
Outotec Chile S.A.

13/03/2012

1 (1)

Anexos
Tomo 2
Captulo 2

Outotec Chile S.A.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

CORPORACION NACIONAL DEL COBRE


CODELCO CHILE
VICEPRESIDENCIA DE PROYECTOS
PROYECTO EXPLOTACION MINA MINISTRO HALES

CELDAS DE FLOTACIN
Project No DQ110071

LISTADO
ESPECIFICACION Y LISTADO DE INSTRUMENTOS

Documento N DQ-110071-C5059-LI-0008
O/C N H336073-PM014/0

REV

DESCRIPCIN

PREPAR

REVIS

APROB

FECHA

EMITIDO COMO AS BUILD

ATR

ATR

GHP

19-01-2012

EMITIDO PARA APROBACIN CLIENTE

ATR

ATR

GHP

17-11-2011

EMITIDO PARA APROBACIN CLIENTE

ATR

ATR

GHP

15-07-2011

EMITIDO PARA INFORMACION CLIENTE

PO

GHP

GHP

14-06-2011

EMITIDO PARA COORDINACION INTERNA

GHP

06-06-2011

LISTADO DE INSTRUMENTOS
Documento N DQ-110071-C5059-LI-0008
Revisin 2
DQ- 110071

PROYECTO EXPLOTACION MINA MINISTRO HALES

CORPORACION NACIONAL DEL COBRE

LISTADO DE INSTRUMENTOS Y EQUIPOS


TAG

3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310

Servicio

LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI

1812
1799
1810
1810
1810
1782
1782
1782
1782
1812A
1812A
1812B
1812B
1812A
1812B
1812
1812
0812
1818
1829
1816
1816
1816
1783
1783
1783
1783
1818A
1818A
1818B
1818B
1818A
1818B
1818
1818
0818
1822
1874
1820
1820
1820
1784
1784
1784
1784
1822A
1822A
1822B
1822B
1822A
1822B
1822
1822
0822
1828
1875
1826
1826
1826
1785
1785
1785
1785
1828A
1828A
1828B
1828B
1828A
1828B
1828
1828
0828
1832
1878
1830
1830
1830
1786
1786
1786
1786
1832A
1832A
1832B
1832B
1832A
1832B
1832
1832
0832
1838
1883
1836
1836
1836
1787
1787
1787

Tipo

LINEA 1 CELDA ROUGHER

(1+1+1+1+1+1) TC-300

Nivel Pulpa Celda 3312-CFL-001


Presion Aire Flotacin 3312-CFL-001
Flujo Aire Flotacin 3312-CFL-001
Control Aire Flotacin 3312-CFL-001
Control Aire Flotacin 3312-CFL-001
Presin de Aceite en Reductor 3312-CFL-001
Filtro Reductor sucio 3312-CFL-001
Nivel Bajo de Aceite en Reductor 3312-CFL-001
Temperatura de Aceite en Reductor 3312-CFL-001
Descarga Celda 3312-CFL-001
Descarga Celda 3312-CFL-001
Descarga Celda 3312-CFL-001
Descarga Celda 3312-CFL-001
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-002
Presion Aire Flotacin 3312-CFL-002
Flujo Aire Flotacin 3312-CFL-002
Control Aire Flotacin 3312-CFL-002
Control Aire Flotacin 3312-CFL-002
Presin de Aceite en Reductor 3312-CFL-002
Filtro Reductor Sucio 3312-CFL-002
Nivel Bajo de Aceite en Reductor 3312-CFL-002
Temperatura de Aceite en Reductor 3312-CFL-002
Descarga Celda 3312-CFL-002
Descarga Celda 3312-CFL-002
Descarga Celda 3312-CFL-002
Descarga Celda 3312-CFL-002
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-003
Presion Aire Flotacin 3312-CFL-003
Flujo Aire Flotacin 3312-CFL-003
Control Aire Flotacin 3312-CFL-003
Control Aire Flotacin 3312-CFL-003
Presin de Aceite en Reductor 3312-CFL-003
Filtro Reductor Sucio 3312-CFL-003
Nivel Bajo de Aceite en Reductor 3312-CFL-003
Temperatura de Aceite en Reductor 3312-CFL-003
Descarga Celda 3312-CFL-003
Descarga Celda 3312-CFL-003
Descarga Celda 3312-CFL-003
Descarga Celda 3312-CFL-003
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-004
Presion Aire Flotacin 3312-CFL-004
Flujo Aire Flotacin 3312-CFL-004
Control Aire Flotacin 3312-CFL-004
Control Aire Flotacin 3312-CFL-004
Presin de Aceite en Reductor 3312-CFL-004
Filtro Reductor Sucio 3312-CFL-004
Nivel Bajo de Aceite en Reductor 3312-CFL-004
Temperatura de Aceite en Reductor 3312-CFL-004
Descarga Celda 3312-CFL-004
Descarga Celda 3312-CFL-004
Descarga Celda 3312-CFL-004
Descarga Celda 3312-CFL-004
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-005
Presion Aire Flotacin 3312-CFL-005
Flujo Aire Flotacin 3312-CFL-005
Control Aire Flotacin 3312-CFL-005
Control Aire Flotacin 3312-CFL-005
Presin de Aceite en Reductor 3312-CFL-005
Filtro Reductor Sucio 3312-CFL-005
Nivel Bajo de Aceite en Reductor 3312-CFL-005
Temperatura de Aceite en Reductor 3312-CFL-005
Descarga Celda 3312-CFL-005
Descarga Celda 3312-CFL-005
Descarga Celda 3312-CFL-005
Descarga Celda 3312-CFL-005
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-006
Presion Aire Flotacin 3312-CFL-006
Flujo Aire Flotacin 3312-CFL-006
Control Aire Flotacin 3312-CFL-006
Control Aire Flotacin 3312-CFL-006
Presin de Aceite en Reductor 3312-CFL-006
Filtro Reductor Sucio 3312-CFL-006
Nivel Bajo de Aceite en Reductor 3312-CFL-006

Transmisor de Nivel Ultrasonico


Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel

Outotec Chile SA.


DQ-110061-C5059-0008 R2 Listado de Instrumentos.xls

Lnea / Eq. Principal

3312-CFL-001
Aire Flotacin 3312-CFL-001
Aire Flotacin 3312-CFL-001
Aire Flotacin 3312-CFL-001
3310-FV-1810
Reductor Celda 3312-CFL-001
Reductor Celda 3312-CFL-001
Reductor Celda 3312-CFL-001
Reductor Celda 3312-CFL-001
3312-CFL-001
3310-LV-1812A
3312-CFL-001
3310-LV-1812B
Panel de Control Local Celda 3312-CFL-001
Panel de Control Local Celda 3312-CFL-001
Panel de Control Local Celda 3312-CFL-001
Panel de Control Local Celda 3312-CFL-001
Panel de Control Local Celda 3312-CFL-001
3312-CFL-002
Aire Flotacin 3312-CFL-002
Aire Flotacin 3312-CFL-002
Aire Flotacin 3312-CFL-002
3310-FV-1816
Reductor Celda 3312-CFL-002
Reductor Celda 3312-CFL-002
Reductor Celda 3312-CFL-002
Reductor Celda 3312-CFL-002
3312-CFL-002
3310-LV-1818A
3312-CFL-002
3310-LV-1818B
Panel de Control Local Celda 3312-CFL-002
Panel de Control Local Celda 3312-CFL-002
Panel de Control Local Celda 3312-CFL-002
Panel de Control Local Celda 3312-CFL-002
Panel de Control Local Celda 3312-CFL-002
3312-CFL-003
Aire Flotacin 3312-CFL-003
Aire Flotacin 3312-CFL-003
Aire Flotacin 3312-CFL-003
3310-FV-1820
Reductor Celda 3312-CFL-003
Reductor Celda 3312-CFL-003
Reductor Celda 3312-CFL-003
Reductor Celda 3312-CFL-003
3312-CFL-003
3310-LV-1820A
3312-CFL-003
3310-LV-1820B
Panel de Control Local Celda 3312-CFL-003
Panel de Control Local Celda 3312-CFL-003
Panel de Control Local Celda 3312-CFL-003
Panel de Control Local Celda 3312-CFL-003
Panel de Control Local Celda 3312-CFL-003
3312-CFL-004
Aire Flotacin 3312-CFL-004
Aire Flotacin 3312-CFL-004
Aire Flotacin 3312-CFL-004
3310-FV-1826
Reductor Celda 3312-CFL-004
Reductor Celda 3312-CFL-004
Reductor Celda 3312-CFL-004
Reductor Celda 3312-CFL-004
3312-CFL-004
3310-LV-1828A
3312-CFL-004
3310-LV-1828B
Panel de Control Local Celda 3312-CFL-004
Panel de Control Local Celda 3312-CFL-004
Panel de Control Local Celda 3312-CFL-004
Panel de Control Local Celda 3312-CFL-004
Panel de Control Local Celda 3312-CFL-004
3312-CFL-005
Aire Flotacin 3312-CFL-005
Aire Flotacin 3312-CFL-005
Aire Flotacin 3312-CFL-005
3310-FV-1830
Reductor Celda 3312-CFL-005
Reductor Celda 3312-CFL-005
Reductor Celda 3312-CFL-005
Reductor Celda 3312-CFL-005
3312-CFL-005
3310-LV-1832A
3312-CFL-005
3310-LV-1832B
Panel de Control Local Celda 3312-CFL-005
Panel de Control Local Celda 3312-CFL-005
Panel de Control Local Celda 3312-CFL-005
Panel de Control Local Celda 3312-CFL-005
Panel de Control Local Celda 3312-CFL-005
3312-CFL-006
Aire Flotacin 3312-CFL-006
Aire Flotacin 3312-CFL-006
Aire Flotacin 3312-CFL-006
3310-FV-1836
Reductor Celda 3312-CFL-006
Reductor Celda 3312-CFL-006
Reductor Celda 3312-CFL-006

Dim Pr in

2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF

RNG

0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

EQ ASOC

Marca

Modelo

TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0812
3310-LCP-0812
3310-LCP-0812
3310-LCP-0812
3310-LCP-0812
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0818
3310-LCP-0818
3310-LCP-0818
3310-LCP-0818
3310-LCP-0818
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0822
3310-LCP-0822
3310-LCP-0822
3310-LCP-0822
3310-LCP-0822
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0828
3310-LCP-0828
3310-LCP-0828
3310-LCP-0828
3310-LCP-0828
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0832
3310-LCP-0832
3310-LCP-0832
3310-LCP-0832
3310-LCP-0832
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300

E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC

FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12

SERIE

65F1H

IO TIP

FF H1
N/R
FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MF4035

FF H1
FF H1
N/R
N/R

P&ID

Descripcin Dispositivo

DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020

DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor

Notas

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2

Pagina 2 de 8

LISTADO DE INSTRUMENTOS
Documento N DQ-110071-C5059-LI-0008
Revisin 2
DQ- 110071

PROYECTO EXPLOTACION MINA MINISTRO HALES

CORPORACION NACIONAL DEL COBRE

LISTADO DE INSTRUMENTOS Y EQUIPOS


TAG

Servicio

Tipo

Lnea / Eq. Principal

EQ ASOC

Marca

Modelo

SERIE

3310
3310
3310
3310
3310
3310
3310
3310
3310
3310

TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP

1787
1838A
1838A
1838B
1838B
1838A
1838B
1838
1838
0838

Temperatura de Aceite en Reductor 3312-CFL-006


Descarga Celda 3312-CFL-006
Descarga Celda 3312-CFL-006
Descarga Celda 3312-CFL-006
Descarga Celda 3312-CFL-006
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close

Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local

Reductor Celda 3312-CFL-006


3312-CFL-006
3310-LV-1838A
3312-CFL-006
3310-LV-1838B
Panel de Control Local Celda 3312-CFL-006
Panel de Control Local Celda 3312-CFL-006
Panel de Control Local Celda 3312-CFL-006
Panel de Control Local Celda 3312-CFL-006
Panel de Control Local Celda 3312-CFL-006

L=100
450mm
CP25 250
450mm
CP25 250
VTS
VTS
VTS
VTS
VTS

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R

TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0838
3310-LCP-0838
3310-LCP-0838
3310-LCP-0838
3310-LCP-0838

SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS

SITRANS T
TAPON 450
ND9106FN
TAPON 450
ND9106FN
VTS
VTS
VTS
VTS
VTS

7MC1006-1DA11- T45

LINEA 2 CELDA ROUGHER

(1+1+1+1+1+1) TC-300

3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310

LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ

1862
1884
1860
1860
1860
1788
1788
1788
1788
1862A
1862A
1862B
1862B
1862A
1862B
1862
1862
0862
1868
1890
1866
1866
1866
1789
1789
1789
1789
1868A
1868A
1868B
1868B
1868A
1868B
1868
1868
0868
1872
1891
1870
1870
1870
1790
1790
1790
1790
1872A
1872A
1872B
1872B
1872A
1872B
1872
1872
0872
1879
1892
1876
1876
1876
1791
1791
1791
1791
1879A
1879A
1879B
1879B
1879A
1879B
1879
1879
0879
1882
1893
1880
1880
1880
1792
1792
1792
1792
1882A
1882A
1882B
1882B
1882A
1882B
1882

Nivel Pulpa Celda 3312-CFL-007


Presion Aire Flotacin 3312-CFL-007
Flujo Aire Flotacin 3312-CFL-007
Control Aire Flotacin 3312-CFL-007
Control Aire Flotacin 3312-CFL-007
Presin de Aceite en Reductor 3312-CFL-007
Filtro Reductor Sucio 3312-CFL-007
Nivel Bajo de Aceite en Reductor 3312-CFL-007
Temperatura de Aceite en Reductor 3312-CFL-007
Descarga Celda 3312-CFL-007
Descarga Celda 3312-CFL-007
Descarga Celda 3312-CFL-007
Descarga Celda 3312-CFL-007
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-008
Presion Aire Flotacin 3312-CFL-008
Flujo Aire Flotacin 3312-CFL-008
Control Aire Flotacin 3312-CFL-008
Control Aire Flotacin 3312-CFL-008
Presin de Aceite en Reductor 3312-CFL-008
Filtro Reductor Sucio 3312-CFL-008
Nivel Bajo de Aceite en Reductor 3312-CFL-008
Temperatura de Aceite en Reductor 3312-CFL-008
Descarga Celda 3312-CFL-008
Descarga Celda 3312-CFL-008
Descarga Celda 3312-CFL-008
Descarga Celda 3312-CFL-008
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-009
Presion Aire Flotacin 3312-CFL-009
Flujo Aire Flotacin 3312-CFL-009
Control Aire Flotacin 3312-CFL-009
Control Aire Flotacin 3312-CFL-009
Presin de Aceite en Reductor 3312-CFL-009
Filtro Reductor Sucio 3312-CFL-009
Nivel Bajo de Aceite en Reductor 3312-CFL-009
Temperatura de Aceite en Reductor 3312-CFL-009
Descarga Celda 3312-CFL-009
Descarga Celda 3312-CFL-009
Descarga Celda 3312-CFL-009
Descarga Celda 3312-CFL-009
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-010
Presion Aire Flotacin 3312-CFL-010
Flujo Aire Flotacin 3312-CFL-010
Control Aire Flotacin 3312-CFL-010
Control Aire Flotacin 3312-CFL-010
Presin de Aceite en Reductor 3312-CFL-010
Filtro Reductor Sucio 3312-CFL-010
Nivel Bajo de Aceite en Reductor 3312-CFL-010
Temperatura de Aceite en Reductor 3312-CFL-010
Descarga Celda 3312-CFL-010
Descarga Celda 3312-CFL-010
Descarga Celda 3312-CFL-010
Descarga Celda 3312-CFL-010
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-011
Presion Aire Flotacin 3312-CFL-011
Flujo Aire Flotacin 3312-CFL-011
Control Aire Flotacin 3312-CFL-011
Control Aire Flotacin 3312-CFL-011
Presin de Aceite en Reductor 3312-CFL-011
Filtro Reductor Sucio 3312-CFL-011
Nivel Bajo de Aceite en Reductor 3312-CFL-011
Temperatura de Aceite en Reductor 3312-CFL-011
Descarga Celda 3312-CFL-011
Descarga Celda 3312-CFL-011
Descarga Celda 3312-CFL-011
Descarga Celda 3312-CFL-011
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local

Transmisor de Nivel Ultrasonico


Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide

3312-CFL-007
Aire Flotacin 3312-CFL-007
Aire Flotacin 3312-CFL-007
Aire Flotacin 3312-CFL-007
3310-FV-1860
Reductor Celda 3312-CFL-007
Reductor Celda 3312-CFL-007
Reductor Celda 3312-CFL-007
Reductor Celda 3312-CFL-007
3312-CFL-007
3310-LV-1862A
3312-CFL-007
3310-LV-1862B
Panel de Control Local Celda 3312-CFL-007
Panel de Control Local Celda 3312-CFL-007
Panel de Control Local Celda 3312-CFL-007
Panel de Control Local Celda 3312-CFL-007
Panel de Control Local Celda 3312-CFL-007
3312-CFL-008
Aire Flotacin 3312-CFL-008
Aire Flotacin 3312-CFL-008
Aire Flotacin 3312-CFL-008
3310-FV-1866
Reductor Celda 3312-CFL-008
Reductor Celda 3312-CFL-008
Reductor Celda 3312-CFL-008
Reductor Celda 3312-CFL-008
3312-CFL-008
3310-LV-1868A
3312-CFL-008
3310-LV-1868B
Panel de Control Local Celda 3312-CFL-008
Panel de Control Local Celda 3312-CFL-008
Panel de Control Local Celda 3312-CFL-008
Panel de Control Local Celda 3312-CFL-008
Panel de Control Local Celda 3312-CFL-008
3312-CFL-009
Aire Flotacin 3312-CFL-009
Aire Flotacin 3312-CFL-009
Aire Flotacin 3312-CFL-009
3310-FV-1870
Reductor Celda 3312-CFL-009
Reductor Celda 3312-CFL-009
Reductor Celda 3312-CFL-009
Reductor Celda 3312-CFL-009
3312-CFL-009
3310-LV-1872A
3312-CFL-009
3310-LV-1872B
Panel de Control Local Celda 3312-CFL-009
Panel de Control Local Celda 3312-CFL-009
Panel de Control Local Celda 3312-CFL-009
Panel de Control Local Celda 3312-CFL-009
Panel de Control Local Celda 3312-CFL-009
3312-CFL-010
Aire Flotacin 3312-CFL-010
Aire Flotacin 3312-CFL-010
Aire Flotacin 3312-CFL-010
3310-FV-1876
Reductor Celda 3312-CFL-010
Reductor Celda 3312-CFL-010
Reductor Celda 3312-CFL-010
Reductor Celda 3312-CFL-010
3312-CFL-010
3310-LV-1879A
3312-CFL-010
3310-LV-1879B
Panel de Control Local Celda 3312-CFL-010
Panel de Control Local Celda 3312-CFL-010
Panel de Control Local Celda 3312-CFL-010
Panel de Control Local Celda 3312-CFL-010
Panel de Control Local Celda 3312-CFL-010
3312-CFL-011
Aire Flotacin 3312-CFL-011
Aire Flotacin 3312-CFL-011
Aire Flotacin 3312-CFL-011
3310-FV-1880
Reductor Celda 3312-CFL-011
Reductor Celda 3312-CFL-011
Reductor Celda 3312-CFL-011
Reductor Celda 3312-CFL-011
3312-CFL-011
3310-LV-1882A
3312-CFL-011
3310-LV-1882B
Panel de Control Local Celda 3312-CFL-011
Panel de Control Local Celda 3312-CFL-011
Panel de Control Local Celda 3312-CFL-011

2" PNT
1/2" NPT
ph=4"
ph=4"

0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0862
3310-LCP-0862
3310-LCP-0862
3310-LCP-0862
3310-LCP-0862
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0868
3310-LCP-0868
3310-LCP-0868
3310-LCP-0868
3310-LCP-0868
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0872
3310-LCP-0872
3310-LCP-0872
3310-LCP-0872
3310-LCP-0872
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0879
3310-LCP-0879
3310-LCP-0879
3310-LCP-0879
3310-LCP-0879
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0882
3310-LCP-0882
3310-LCP-0882

E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS

Outotec Chile SA.


DQ-110061-C5059-0008 R2 Listado de Instrumentos.xls

Dim Pr in

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

RNG

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

3/4-16UNF

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R

FF H1
FF H1
VTS
VTS
DO
DI
N/R

FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS

IO TIP

FF H1

65F1H

FF H1
N/R
FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MF4035

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1
FF H1
FF H1
VTS
VTS
DO

P&ID

Descripcin Dispositivo

Notas

DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027

Ver manual del Reductor


DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS

REV 1

DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027

DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

Pagina 3 de 8

LISTADO DE INSTRUMENTOS
Documento N DQ-110071-C5059-LI-0008
Revisin 2
DQ- 110071

PROYECTO EXPLOTACION MINA MINISTRO HALES

CORPORACION NACIONAL DEL COBRE

LISTADO DE INSTRUMENTOS Y EQUIPOS


TAG

3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310

HS
- 1882
- LCP - 0882
- LIT/LE - 1889
PI
- 1894
- FIT/FE - 1886
FV
- 1886
FY
- 1886
PIT
- 1793
- PDI - 1793
LI
- 1793
TIT
- 1793
LV
- 1889A
LY
- 1889A
LV
- 1889B
LY
- 1889B
HY
- 1889A
HY
- 1889B
XZ
- 1889
HS
- 1889
- LCP - 0889

3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330

LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
PI
FIT/FE
FV
FY
PIT

2253
2249
2250
2250
2250
2231
2231
2231
2231
2253A
2253A
2253B
2253B
2253A
2253B
2253
2253
0253
2258
2304
2255
2255
2255
2232
2232
2232
2232
2258A
2258A
2258B
2258B
2258A
2258B
2258
2258
0258
2263
2310
2260
2260
2260
2233
2233
2233
2233
2263A
2263A
2263B
2263B
2263A
2263B
2263
2263
0263
2273
2322
2270
2270
2270
2234
2234
2234
2234
2273A
2273A
2273B
2273B
2273A
2273B
2273
2273
0273
2083
2061
2061
2061
2227

Servicio

Tipo

Lnea / Eq. Principal

Solicitud de habilitacin Panel Local


Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3312-CFL-012
Presion Aire Flotacin 3312-CFL-012
Flujo Aire Flotacin 3312-CFL-012
Control Aire Flotacin 3312-CFL-012
Control Aire Flotacin 3312-CFL-012
Presin de Aceite en Reductor 3312-CFL-012
Filtro Reductor Sucio 3312-CFL-012
Nivel Bajo de Aceite en Reductor 3312-CFL-012
Temperatura de Aceite en Reductor 3312-CFL-012
Descarga Celda 3312-CFL-012
Descarga Celda 3312-CFL-012
Descarga Celda 3312-CFL-012
Descarga Celda 3312-CFL-012
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close

Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local

Panel de Control Local Celda 3312-CFL-011


Panel de Control Local Celda 3312-CFL-011
3312-CFL-012
Aire Flotacin 3312-CFL-012
Aire Flotacin 3312-CFL-012
Aire Flotacin 3312-CFL-012
3310-FV-1886
Reductor Celda 3312-CFL-012
Reductor Celda 3312-CFL-012
Reductor Celda 3312-CFL-012
Reductor Celda 3312-CFL-012
3312-CFL-012
3310-LV-1889A
3312-CFL-012
3310-LV-1889B
Panel de Control Local Celda 3312-CFL-012
Panel de Control Local Celda 3312-CFL-012
Panel de Control Local Celda 3312-CFL-012
Panel de Control Local Celda 3312-CFL-012
Panel de Control Local Celda 3312-CFL-012

LINEA 1 CELDAS 1ST CLEANER


SCAVENGER

(1+1+1+1+2+1) TC-160

Nivel Pulpa Celda 3332-CFL-015


Presion Aire Flotacin 3332-CFL-015
Flujo Aire Flotacin 3332-CFL-015
Control Aire Flotacin 3332-CFL-015
Control Aire Flotacin 3332-CFL-015
Presin de Aceite en Reductor 3332-CFL-015
Filtro Reductor Sucio 3332-CFL-015
Nivel Bajo de Aceite en Reductor 3332-CFL-015
Temperatura de Aceite en Reductor 3332-CFL-015
Descarga Celda 3332-CFL-015
Descarga Celda 3332-CFL-015
Descarga Celda 3332-CFL-015
Descarga Celda 3332-CFL-015
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-016
Presion Aire Flotacin 3332-CFL-016
Flujo Aire Flotacin 3332-CFL-016
Control Aire Flotacin 3332-CFL-016
Control Aire Flotacin 3332-CFL-016
Presin de Aceite en Reductor 3332-CFL-016
Filtro Reductor Sucio 3332-CFL-016
Nivel Bajo de Aceite en Reductor 3332-CFL-016
Temperatura de Aceite en Reductor 3332-CFL-016
Descarga Celda 3332-CFL-016
Descarga Celda 3332-CFL-016
Descarga Celda 3332-CFL-016
Descarga Celda 3332-CFL-016
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-017
Presion Aire Flotacin 3332-CFL-017
Flujo Aire Flotacin 3332-CFL-017
Control Aire Flotacin 3332-CFL-017
Control Aire Flotacin 3332-CFL-017
Presin de Aceite en Reductor 3332-CFL-017
Filtro Reductor Sucio 3332-CFL-017
Nivel Bajo de Aceite en Reductor 3332-CFL-017
Temperatura de Aceite en Reductor 3332-CFL-017
Descarga Celda 3332-CFL-017
Descarga Celda 3332-CFL-017
Descarga Celda 3332-CFL-017
Descarga Celda 3332-CFL-017
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-018
Presion Aire Flotacin 3332-CFL-018
Flujo Aire Flotacin 3332-CFL-018
Control Aire Flotacin 3332-CFL-018
Control Aire Flotacin 3332-CFL-018
Presin de Aceite en Reductor 3332-CFL-018
Filtro Reductor Sucio 3332-CFL-018
Nivel Bajo de Aceite en Reductor 3332-CFL-018
Temperatura de Aceite en Reductor 3332-CFL-018
Descarga Celda 3332-CFL-018
Descarga Celda 3332-CFL-018
Descarga Celda 3332-CFL-018
Descarga Celda 3332-CFL-018
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Presion Aire Flotacin 3332-CFL-001
Flujo Aire Flotacin 3332-CFL-001
Control Aire Flotacin 3332-CFL-001
Control Aire Flotacin 3332-CFL-001
Presin de Aceite en Reductor 3332-CFL-001

Transmisor de Nivel Ultrasonico


Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin

Outotec Chile SA.


DQ-110061-C5059-0008 R2 Listado de Instrumentos.xls

3332-CFL-015
Aire Flotacin 3332-CFL-015
Aire Flotacin 3332-CFL-015
Aire Flotacin 3332-CFL-015
3330-FV-2250
Reductor Celda 3332-CFL-015
Reductor Celda 3332-CFL-015
Reductor Celda 3332-CFL-015
Reductor Celda 3332-CFL-015
3332-CFL-015
3330-LV-2253A
3332-CFL-015
3330-LV-2253B
Panel de Control Local Celda 3332-CFL-015
Panel de Control Local Celda 3332-CFL-015
Panel de Control Local Celda 3332-CFL-015
Panel de Control Local Celda 3332-CFL-015
Panel de Control Local Celda 3332-CFL-015
3332-CFL-016
Aire Flotacin 3332-CFL-016
Aire Flotacin 3332-CFL-016
Aire Flotacin 3332-CFL-016
3330-FV-2255
Reductor Celda 3332-CFL-016
Reductor Celda 3332-CFL-016
Reductor Celda 3332-CFL-016
Reductor Celda 3332-CFL-016
3332-CFL-016
3330-LV-2258A
3332-CFL-016
3330-LV-2258B
Panel de Control Local Celda 3332-CFL-016
Panel de Control Local Celda 3332-CFL-016
Panel de Control Local Celda 3332-CFL-016
Panel de Control Local Celda 3332-CFL-016
Panel de Control Local Celda 3332-CFL-016
3332-CFL-017
Aire Flotacin 3332-CFL-017
Aire Flotacin 3332-CFL-017
Aire Flotacin 3332-CFL-017
3330-FV-2260
Reductor Celda 3332-CFL-017
Reductor Celda 3332-CFL-017
Reductor Celda 3332-CFL-017
Reductor Celda 3332-CFL-017
3332-CFL-017
3330-LV-2263A
3332-CFL-017
3330-LV-2263B
Panel de Control Local Celda 3332-CFL-017
Panel de Control Local Celda 3332-CFL-017
Panel de Control Local Celda 3332-CFL-017
Panel de Control Local Celda 3332-CFL-017
Panel de Control Local Celda 3332-CFL-017
3332-CFL-018
Aire Flotacin 3332-CFL-018
Aire Flotacin 3332-CFL-018
Aire Flotacin 3332-CFL-018
3330-FV-2270
Reductor Celda 3332-CFL-018
Reductor Celda 3332-CFL-018
Reductor Celda 3332-CFL-018
Reductor Celda 3332-CFL-018
3332-CFL-018
3330-LV-2273A
3332-CFL-018
3330-LV-2273B
Panel de Control Local Celda 3332-CFL-018
Panel de Control Local Celda 3332-CFL-018
Panel de Control Local Celda 3332-CFL-018
Panel de Control Local Celda 3332-CFL-018
Panel de Control Local Celda 3332-CFL-018
Aire Flotacin 3332-CFL-001
Aire Flotacin 3332-CFL-001
Aire Flotacin 3332-CFL-001
3330-FV-2061
Reductor Celda 3332-CFL-001

Dim Pr in

VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

RNG

3/4-16UNF

N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

L=100
450mm
CP25 250
450mm
CP25 250
VTS
VTS
VTS
VTS
VTS

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R

2" PNT
1/2" NPT
ph=3"
ph=3"

0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=3"
ph=3"

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=3"
ph=3"

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=3"
ph=3"

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
1/2" NPT
ph=3"
ph=3"

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar

EQ ASOC

Marca

Modelo

3310-LCP-0882
3310-LCP-0882
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3310-LCP-0889
3310-LCP-0889
3310-LCP-0889
3310-LCP-0889
3310-LCP-0889

VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS

VTS
VTS
FMU 40

TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0253
3330-LCP-0253
3330-LCP-0253
3330-LCP-0253
3330-LCP-0253
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0258
3330-LCP-0258
3330-LCP-0258
3330-LCP-0258
3330-LCP-0258
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0263
3330-LCP-0263
3330-LCP-0263
3330-LCP-0263
3330-LCP-0263
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0273
3330-LCP-0273
3330-LCP-0273
3330-LCP-0273
3330-LCP-0273
TC-160
TC-160
TC-160
TC-160
TC-160

E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS

PROLINE T-MASS 65I


SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 450
ND9106FN
TAPON 450
ND9106FN
VTS
VTS
VTS
VTS
VTS

SERIE

65F1H

7MF4035

7MC1006-1DA11- T45

DI
N/R
FF H1
N/R
FF H1
FF H1
FF H1
N/R
N/R
FF H1
FF H1
FF H1
VTS
VTS
DO
DI
N/R

FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

IO TIP

65F80

FF H1
N/R
FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
N/R
FF H1

7MF4035

FF H1
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P

P&ID

Descripcin Dispositivo

DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027

VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS

DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021

DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor

Notas

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2

Pagina 4 de 8

LISTADO DE INSTRUMENTOS
Documento N DQ-110071-C5059-LI-0008
Revisin 2
DQ- 110071

PROYECTO EXPLOTACION MINA MINISTRO HALES

CORPORACION NACIONAL DEL COBRE

LISTADO DE INSTRUMENTOS Y EQUIPOS


TAG

Servicio

Tipo

Lnea / Eq. Principal

3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330

PDI
LI
TIT
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP

2227
2227
2227
2073
2085
2071
2071
2071
2228
2228
2228
2228
2073A
2073A
2073B
2073B
2073A
2073B
2073
2073
0073
2077
2086
2075
2075
2075
2330
2330
2330
2330
2077A
2077A
2077B
2077B
2077A
2077B
2077
2077
0077

Filtro Reductor Sucio 3332-CFL-001


Nivel Bajo de Aceite en Reductor 3332-CFL-001
Temperatura de Aceite en Reductor 3332-CFL-001
Nivel Pulpa Celda 3332-CFL-002
Presion Aire Flotacin 3332-CFL-002
Flujo Aire Flotacin 3332-CFL-002
Control Aire Flotacin 3332-CFL-002
Control Aire Flotacin 3332-CFL-002
Presin de Aceite en Reductor 3332-CFL-002
Filtro Reductor Sucio 3332-CFL-002
Nivel Bajo de Aceite en Reductor 3332-CFL-002
Temperatura de Aceite en Reductor 3332-CFL-002
Descarga Celda 3332-CFL-002
Descarga Celda 3332-CFL-002
Descarga Celda 3332-CFL-002
Descarga Celda 3332-CFL-002
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-003
Presion Aire Flotacin 3332-CFL-003
Flujo Aire Flotacin 3332-CFL-003
Control Aire Flotacin 3332-CFL-003
Control Aire Flotacin 3332-CFL-003
Presin de Aceite en Reductor 3332-CFL-003
Filtro Reductor Sucio 3332-CFL-003
Nivel Bajo de Aceite en Reductor 3332-CFL-003
Temperatura de Aceite en Reductor 3332-CFL-003
Descarga Celda 3332-CFL-003
Descarga Celda 3332-CFL-003
Descarga Celda 3332-CFL-003
Descarga Celda 3332-CFL-003
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close

Indicador diferencial de Presin


Indicador de Nivel
Transmisor de Temperatura
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local

Reductor Celda 3332-CFL-001


Reductor Celda 3332-CFL-001
Reductor Celda 3332-CFL-001
3332-CFL-002
Aire Flotacin 3332-CFL-002
Aire Flotacin 3332-CFL-002
Aire Flotacin 3332-CFL-002
3330-FV-2071
Reductor Celda 3332-CFL-002
Reductor Celda 3332-CFL-002
Reductor Celda 3332-CFL-002
Reductor Celda 3332-CFL-002
3332-CFL-002
3330-LV-2073A
3332-CFL-002
3330-LV-2073B
Panel de Control Local Celda 3332-CFL-002
Panel de Control Local Celda 3332-CFL-002
Panel de Control Local Celda 3332-CFL-002
Panel de Control Local Celda 3332-CFL-002
Panel de Control Local Celda 3332-CFL-002
3332-CFL-003
Aire Flotacin 3332-CFL-003
Aire Flotacin 3332-CFL-003
Aire Flotacin 3332-CFL-003
3330-FV-2075
Reductor Celda 3332-CFL-003
Reductor Celda 3332-CFL-003
Reductor Celda 3332-CFL-003
Reductor Celda 3332-CFL-003
3332-CFL-003
3330-LV-2077A
3332-CFL-003
3330-LV-2077B
Panel de Control Local Celda 3332-CFL-003
Panel de Control Local Celda 3332-CFL-003
Panel de Control Local Celda 3332-CFL-003
Panel de Control Local Celda 3332-CFL-003
Panel de Control Local Celda 3332-CFL-003

LINEA 1 CELDAS 2ST CLEANER


SCAVENGER

(1+1+1+1+2+1) TC-160

3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330

LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV

2278
2323
2275
2275
2275
2235
2235
2235
2235
2278A
2278A
2278B
2278B
2278A
2278B
2278
2278
0278
2283
2324
2280
2280
2280
2236
2236
2236
2236
2283A
2283A
2283B
2283B
2283A
2283B
2283
2283
0283
2268
2321
2265
2265
2265
2237
2237
2237
2237
2268A
2268A
2268B
2268B
2268A
2268B
2268
2268
0268
2288
2325
2285
2285

Nivel Pulpa Celda 3332-CFL-019


Presion Aire Flotacin 3332-CFL-019
Flujo Aire Flotacin 3332-CFL-019
Control Aire Flotacin 3332-CFL-019
Control Aire Flotacin 3332-CFL-019
Presin de Aceite en Reductor 3332-CFL-019
Filtro Reductor Sucio 3332-CFL-019
Nivel Bajo de Aceite en Reductor 3332-CFL-019
Temperatura de Aceite en Reductor 3332-CFL-019
Descarga Celda 3332-CFL-019
Descarga Celda 3332-CFL-019
Descarga Celda 3332-CFL-019
Descarga Celda 3332-CFL-019
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-020
Presion Aire Flotacin 3332-CFL-020
Flujo Aire Flotacin 3332-CFL-020
Control Aire Flotacin 3332-CFL-020
Control Aire Flotacin 3332-CFL-020
Presin de Aceite en Reductor 3332-CFL-020
Filtro Reductor Sucio 3332-CFL-020
Nivel Bajo de Aceite en Reductor 3332-CFL-020
Temperatura de Aceite en Reductor 3332-CFL-020
Descarga Celda 3332-CFL-020
Descarga Celda 3332-CFL-020
Descarga Celda 3332-CFL-020
Descarga Celda 3332-CFL-020
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-021
Presion Aire Flotacin 3332-CFL-021
Flujo Aire Flotacin 3332-CFL-021
Control Aire Flotacin 3332-CFL-021
Control Aire Flotacin 3332-CFL-021
Presin de Aceite en Reductor 3332-CFL-021
Filtro Reductor Sucio 3332-CFL-021
Nivel Bajo de Aceite en Reductor 3332-CFL-021
Temperatura de Aceite en Reductor 3332-CFL-021
Descarga Celda 3332-CFL-021
Descarga Celda 3332-CFL-021
Descarga Celda 3332-CFL-021
Descarga Celda 3332-CFL-021
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-022
Presion Aire Flotacin 3332-CFL-022
Flujo Aire Flotacin 3332-CFL-022
Control Aire Flotacin 3332-CFL-022

Transmisor de Nivel Ultrasonico


Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa

Outotec Chile SA.


DQ-110061-C5059-0008 R2 Listado de Instrumentos.xls

3332-CFL-019
Aire Flotacin 3332-CFL-019
Aire Flotacin 3332-CFL-019
Aire Flotacin 3332-CFL-019
3330-FV-2275
Reductor Celda 3332-CFL-019
Reductor Celda 3332-CFL-019
Reductor Celda 3332-CFL-019
Reductor Celda 3332-CFL-019
3332-CFL-019
3330-LV-2278A
3332-CFL-019
3330-LV-2278B
Panel de Control Local Celda 3332-CFL-019
Panel de Control Local Celda 3332-CFL-019
Panel de Control Local Celda 3332-CFL-019
Panel de Control Local Celda 3332-CFL-019
Panel de Control Local Celda 3332-CFL-019
3332-CFL-020
Aire Flotacin 3332-CFL-020
Aire Flotacin 3332-CFL-020
Aire Flotacin 3332-CFL-020
3330-FV-2280
Reductor Celda 3332-CFL-020
Reductor Celda 3332-CFL-020
Reductor Celda 3332-CFL-020
Reductor Celda 3332-CFL-020
3332-CFL-020
3330-LV-2283A
3332-CFL-020
3330-LV-2283B
Panel de Control Local Celda 3332-CFL-020
Panel de Control Local Celda 3332-CFL-020
Panel de Control Local Celda 3332-CFL-020
Panel de Control Local Celda 3332-CFL-020
Panel de Control Local Celda 3332-CFL-020
3332-CFL-021
Aire Flotacin 3332-CFL-021
Aire Flotacin 3332-CFL-021
Aire Flotacin 3332-CFL-021
3330-FV-2265
Reductor Celda 3332-CFL-021
Reductor Celda 3332-CFL-021
Reductor Celda 3332-CFL-021
Reductor Celda 3332-CFL-021
3332-CFL-021
3330-LV-2268A
3332-CFL-021
3330-LV-2268B
Panel de Control Local Celda 3332-CFL-021
Panel de Control Local Celda 3332-CFL-021
Panel de Control Local Celda 3332-CFL-021
Panel de Control Local Celda 3332-CFL-021
Panel de Control Local Celda 3332-CFL-021
3332-CFL-022
Aire Flotacin 3332-CFL-022
Aire Flotacin 3332-CFL-022
Aire Flotacin 3332-CFL-022

Dim Pr in

3/4-16UNF
L=100
2" PNT
1/2" NPT
ph=3"
ph=3"

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=3"
ph=3"

RNG

2,5+-0,3 bar
0-100C
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar

3/4-16UNF

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar

L=100
350mm
CP20 200
350mm
CP20 200
VTS
VTS
VTS
VTS
VTS

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R

2" PNT
1/2" NPT
ph=3"
ph=3"

0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=3"
ph=3"

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=3"
ph=3"

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar

3/4-16UNF

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar

L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=3"
ph=3"

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
300-2000 m3/h
0-100%

EQ ASOC

Marca

Modelo

TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0073
3330-LCP-0073
3330-LCP-0073
3330-LCP-0073
3330-LCP-0073
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0077
3330-LCP-0077
3330-LCP-0077
3330-LCP-0077
3330-LCP-0077

FINN FILTER
HYDAC
SIEMENS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
FMU 40

TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0278
3330-LCP-0278
3330-LCP-0278
3330-LCP-0278
3330-LCP-0278
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0283
3330-LCP-0283
3330-LCP-0283
3330-LCP-0283
3330-LCP-0283
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0268
3330-LCP-0268
3330-LCP-0268
3330-LCP-0268
3330-LCP-0268
TC-160
TC-160
TC-160
TC-160

E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL

PROLINE T-MASS 65I


SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

SERIE

7MC1006-1DA11- T45

65F80

IO TIP

N/R
N/R
FF H1
FF H1
N/R
FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

7MF4035

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1
FF H1
FF H1
VTS
VTS
DO
DI
N/R

VTS
VTS
VTS
VTS
VTS

FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

65F80

FF H1
N/R
FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40

P&ID

Descripcin Dispositivo

Notas

DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027

Ver manual del Reductor


Ver manual del Reductor
Ver manual del Reductor
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS

REV 2
REV 2
REV 1

DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022

DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

Pagina 5 de 8

LISTADO DE INSTRUMENTOS
Documento N DQ-110071-C5059-LI-0008
Revisin 2
DQ- 110071

PROYECTO EXPLOTACION MINA MINISTRO HALES

CORPORACION NACIONAL DEL COBRE

LISTADO DE INSTRUMENTOS Y EQUIPOS


TAG

Servicio

Tipo

Lnea / Eq. Principal

3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330

FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP

2285
2329
2329
2329
2329
2288A
2288A
2288B
2288B
2288A
2288B
2288
2288
0288
2087
2091
2091
2091
2229
2229
2229
2229
2103
2088
2101
2101
2101
2230
2230
2230
2230
2103A
2103A
2103B
2103B
2103A
2103B
2103
2103
0103
2107
2089
2105
2105
2105
2331
2331
2331
2331
2107A
2107A
2107B
2107B
2107A
2107B
2107
2107
0107

Control Aire Flotacin 3332-CFL-022


Presin de Aceite en Reductor 3332-CFL-022
Filtro Reductor Sucio 3332-CFL-022
Nivel Bajo de Aceite en Reductor 3332-CFL-022
Temperatura de Aceite en Reductor 3332-CFL-022
Descarga Celda 3332-CFL-022
Descarga Celda 3332-CFL-022
Descarga Celda 3332-CFL-022
Descarga Celda 3332-CFL-022
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Presion Aire Flotacin 3332-CFL-005
Flujo Aire Flotacin 3332-CFL-005
Control Aire Flotacin 3332-CFL-005
Control Aire Flotacin 3332-CFL-005
Presin de Aceite en Reductor 3332-CFL-005
Filtro Reductor Sucio 3332-CFL-005
Nivel Bajo de Aceite en Reductor 3332-CFL-005
Temperatura de Aceite en Reductor 3332-CFL-005
Nivel Pulpa Celda 3332-CFL-006
Presion Aire Flotacin 3332-CFL-006
Flujo Aire Flotacin 3332-CFL-006
Control Aire Flotacin 3332-CFL-006
Control Aire Flotacin 3332-CFL-006
Presin de Aceite en Reductor 3332-CFL-006
Filtro Reductor Sucio 3332-CFL-006
Nivel Bajo de Aceite en Reductor 3332-CFL-006
Temperatura de Aceite en Reductor 3332-CFL-006
Descarga Celda 3332-CFL-006
Descarga Celda 3332-CFL-006
Descarga Celda 3332-CFL-006
Descarga Celda 3332-CFL-006
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-007
Presion Aire Flotacin 3332-CFL-007
Flujo Aire Flotacin 3332-CFL-007
Control Aire Flotacin 3332-CFL-007
Control Aire Flotacin 3332-CFL-007
Presin de Aceite en Reductor 3332-CFL-007
Filtro Reductor Sucio 3332-CFL-007
Nivel Bajo de Aceite en Reductor 3332-CFL-007
Temperatura de Aceite en Reductor 3332-CFL-007
Descarga Celda 3332-CFL-007
Descarga Celda 3332-CFL-007
Descarga Celda 3332-CFL-007
Descarga Celda 3332-CFL-007
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close

Actuador Vlvula tipo Mariposa


Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local

3330-FV-2285
Reductor Celda 3332-CFL-022
Reductor Celda 3332-CFL-022
Reductor Celda 3332-CFL-022
Reductor Celda 3332-CFL-022
3332-CFL-022
3330-LV-2288A
3332-CFL-022
3330-LV-2288B
Panel de Control Local Celda 3332-CFL-022
Panel de Control Local Celda 3332-CFL-022
Panel de Control Local Celda 3332-CFL-022
Panel de Control Local Celda 3332-CFL-022
Panel de Control Local Celda 3332-CFL-022
Aire Flotacin 3332-CFL-005
Aire Flotacin 3332-CFL-005
Aire Flotacin 3332-CFL-005
3330-FV-2091
Reductor Celda 3332-CFL-005
Reductor Celda 3332-CFL-005
Reductor Celda 3332-CFL-005
Reductor Celda 3332-CFL-005
3332-CFL-006
Aire Flotacin 3332-CFL-006
Aire Flotacin 3332-CFL-006
Aire Flotacin 3332-CFL-006
3330-FV-2101
Reductor Celda 3332-CFL-006
Reductor Celda 3332-CFL-006
Reductor Celda 3332-CFL-006
Reductor Celda 3332-CFL-006
3332-CFL-006
3330-LV-2103A
3332-CFL-006
3330-LV-2103B
Panel de Control Local Celda 3332-CFL-006
Panel de Control Local Celda 3332-CFL-006
Panel de Control Local Celda 3332-CFL-006
Panel de Control Local Celda 3332-CFL-006
Panel de Control Local Celda 3332-CFL-006
3332-CFL-007
Aire Flotacin 3332-CFL-007
Aire Flotacin 3332-CFL-007
Aire Flotacin 3332-CFL-007
3330-FV-2105
Reductor Celda 3332-CFL-007
Reductor Celda 3332-CFL-007
Reductor Celda 3332-CFL-007
Reductor Celda 3332-CFL-007
3332-CFL-007
3330-LV-2107A
3332-CFL-007
3330-LV-2107B
Panel de Control Local Celda 3332-CFL-007
Panel de Control Local Celda 3332-CFL-007
Panel de Control Local Celda 3332-CFL-007
Panel de Control Local Celda 3332-CFL-007
Panel de Control Local Celda 3332-CFL-007

LINEA 1 CELDAS 2ND SCAVENGER

(1+1+1+1+1+1) TC-300

3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330

LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV

2173
2164
2170
2170
2170
2221
2221
2221
2221
2173A
2173A
2173B
2173B
2173A
2173B
2173
2173
0173
2178
2213
2175
2175
2175
2222
2222
2222
2222
2178A
2178A
2178B
2178B
2178A
2178B
2178
2178
0178
2183
2214
2180
2180

Nivel Pulpa Celda 3332-CFL-009


Presion Aire Flotacin 3332-CFL-009
Flujo Aire Flotacin 3332-CFL-009
Control Aire Flotacin 3332-CFL-009
Control Aire Flotacin 3332-CFL-009
Presin de Aceite en Reductor 3332-CFL-009
Filtro Reductor Sucio 3332-CFL-009
Nivel Bajo de Aceite en Reductor 3332-CFL-009
Temperatura de Aceite en Reductor 3332-CFL-009
Descarga Celda 3332-CFL-009
Descarga Celda 3332-CFL-009
Descarga Celda 3332-CFL-009
Descarga Celda 3332-CFL-009
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-010
Presion Aire Flotacin 3332-CFL-010
Flujo Aire Flotacin 3332-CFL-010
Control Aire Flotacin 3332-CFL-010
Control Aire Flotacin 3332-CFL-010
Presin de Aceite en Reductor 3332-CFL-010
Filtro Reductor Sucio 3332-CFL-010
Nivel Bajo de Aceite en Reductor 3332-CFL-010
Temperatura de Aceite en Reductor 3332-CFL-010
Descarga Celda 3332-CFL-010
Descarga Celda 3332-CFL-010
Descarga Celda 3332-CFL-010
Descarga Celda 3332-CFL-010
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-011
Presion Aire Flotacin 3332-CFL-011
Flujo Aire Flotacin 3332-CFL-011
Control Aire Flotacin 3332-CFL-011

Transmisor de Nivel Ultrasonico


Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa

Outotec Chile SA.


DQ-110061-C5059-0008 R2 Listado de Instrumentos.xls

3332-CFL-009
Aire Flotacin 3332-CFL-009
Aire Flotacin 3332-CFL-009
Aire Flotacin 3332-CFL-009
3330-FV-2170
Reductor Celda 3332-CFL-009
Reductor Celda 3332-CFL-009
Reductor Celda 3332-CFL-009
Reductor Celda 3332-CFL-009
3332-CFL-009
3330-LV-2173A
3332-CFL-009
3330-LV-2173B
Panel de Control Local Celda 3332-CFL-009
Panel de Control Local Celda 3332-CFL-009
Panel de Control Local Celda 3332-CFL-009
Panel de Control Local Celda 3332-CFL-009
Panel de Control Local Celda 3332-CFL-009
3332-CFL-010
Aire Flotacin 3332-CFL-010
Aire Flotacin 3332-CFL-010
Aire Flotacin 3332-CFL-010
3330-FV-2175
Reductor Celda 3332-CFL-010
Reductor Celda 3332-CFL-010
Reductor Celda 3332-CFL-010
Reductor Celda 3332-CFL-010
3332-CFL-010
3330-LV-2178A
3332-CFL-010
3330-LV-2178B
Panel de Control Local Celda 3332-CFL-010
Panel de Control Local Celda 3332-CFL-010
Panel de Control Local Celda 3332-CFL-010
Panel de Control Local Celda 3332-CFL-010
Panel de Control Local Celda 3332-CFL-010
3332-CFL-011
Aire Flotacin 3332-CFL-011
Aire Flotacin 3332-CFL-011
Aire Flotacin 3332-CFL-011

Dim Pr in

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
1/2" NPT
ph=3"
ph=3"

3/4-16UNF
L=100
2" PNT
1/2" NPT
ph=3"
ph=3"

3/4-16UNF
L=100
525mm
CPY25 388
525mm
CPY25 388
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=3"
ph=3"

RNG

0-100%
0,5 bar
2,5+-0,3 bar
0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar
0-100C
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar

3/4-16UNF

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
300-2000 m3/h
0-100%
0-100%
0,5 bar
2,5+-0,3 bar

L=100
350mm
CP20 200
350mm
CP20 200
VTS
VTS
VTS
VTS
VTS

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R

2" PNT
1/2" NPT
ph=4"
ph=4"

0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

3/4-16UNF

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%

EQ ASOC

Marca

Modelo

TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0288
3330-LCP-0288
3330-LCP-0288
3330-LCP-0288
3330-LCP-0288
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0103
3330-LCP-0103
3330-LCP-0103
3330-LCP-0103
3330-LCP-0103
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
TC-160
3330-LCP-0107
3330-LCP-0107
3330-LCP-0107
3330-LCP-0107
3330-LCP-0107

BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

SERIE 92/6A FFHH


SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3330-LCP-0173
3330-LCP-0173
3330-LCP-0173
3330-LCP-0173
3330-LCP-0173
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3330-LCP-0178
3330-LCP-0178
3330-LCP-0178
3330-LCP-0178
3330-LCP-0178
TC-300
TC-300
TC-300
TC-300

E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL

SERIE

IO TIP

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

7MF4035

7MC1006-1DA11- T45

65F80

FF H1
FF H1
N/R
N/R
FF H1
FF H1
N/R
FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F80

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T

7MF4035

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1
FF H1
FF H1
VTS
VTS
DO
DI
N/R

VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40
PROLINE T-MASS 65I
SERIE 40

65F1H

FF H1
N/R
FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

P&ID

Descripcin Dispositivo

DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0021
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0022
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027

DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS

DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020

DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013

Notas

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

Pagina 6 de 8

LISTADO DE INSTRUMENTOS
Documento N DQ-110071-C5059-LI-0008
Revisin 2
DQ- 110071

PROYECTO EXPLOTACION MINA MINISTRO HALES

CORPORACION NACIONAL DEL COBRE

LISTADO DE INSTRUMENTOS Y EQUIPOS


TAG

FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP
LIT/LE
PI
FIT/FE
FV
FY
PIT
PDI
LI
TIT
LV
LY
LV
LY
HY
HY
XZ
HS
LCP

2180
2223
2223
2223
2223
2183A
2183A
2183B
2183B
2183A
2183B
2183
2183
0183
2188
2215
2185
2185
2185
2224
2224
2224
2224
2188A
2188A
2188B
2188B
2188A
2188B
2188
2188
0188
2193
2216
2190
2190
2190
2225
2225
2225
2225
2193A
2193A
2193B
2193B
2193A
2193B
2193
2193
0193
2198
2217
2195
2195
2195
2226
2226
2226
2226
2198A
2198A
2198B
2198B
2198A
2198B
2198
2198
0198

Servicio

Tipo

Lnea / Eq. Principal

Control Aire Flotacin 3332-CFL-011


Presin de Aceite en Reductor 3332-CFL-011
Filtro Reductor Sucio 3332-CFL-011
Nivel Bajo de Aceite en Reductor 3332-CFL-011
Temperatura de Aceite en Reductor 3332-CFL-011
Descarga Celda 3332-CFL-011
Descarga Celda 3332-CFL-011
Descarga Celda 3332-CFL-011
Descarga Celda 3332-CFL-011
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-012
Presion Aire Flotacin 3332-CFL-012
Flujo Aire Flotacin 3332-CFL-012
Control Aire Flotacin 3332-CFL-012
Control Aire Flotacin 3332-CFL-012
Presin de Aceite en Reductor 3332-CFL-012
Filtro Reductor Sucio 3332-CFL-012
Nivel Bajo de Aceite en Reductor 3332-CFL-012
Temperatura de Aceite en Reductor 3332-CFL-012
Descarga Celda 3332-CFL-012
Descarga Celda 3332-CFL-012
Descarga Celda 3332-CFL-012
Descarga Celda 3332-CFL-012
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-013
Presion Aire Flotacin 3332-CFL-013
Flujo Aire Flotacin 3332-CFL-013
Control Aire Flotacin 3332-CFL-013
Control Aire Flotacin 3332-CFL-013
Presin de Aceite en Reductor 3312-CFL-001
Filtro Reductor Sucio 3332-CFL-013
Nivel Bajo de Aceite en Reductor 3332-CFL-013
Temperatura de Aceite en Reductor 3332-CFL-013
Descarga Celda 3332-CFL-013
Descarga Celda 3332-CFL-013
Descarga Celda 3332-CFL-013
Descarga Celda 3332-CFL-013
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close
Nivel Pulpa Celda 3332-CFL-014
Presion Aire Flotacin 3332-CFL-014
Flujo Aire Flotacin 3332-CFL-014
Control Aire Flotacin 3332-CFL-014
Control Aire Flotacin 3332-CFL-014
Presin de Aceite en Reductor 3332-CFL-014
Filtro Reductor Sucio 3332-CFL-014
Nivel Bajo de Aceite en Reductor 3332-CFL-014
Temperatura de Aceite en Reductor 3332-CFL-014
Descarga Celda 3332-CFL-014
Descarga Celda 3332-CFL-014
Descarga Celda 3332-CFL-014
Descarga Celda 3332-CFL-014
Vlvula de accionamiento manual Dardo A
Vlvula de accionamiento manual Dardo B
Habilitacin de Panel a Local
Solicitud de habilitacin Panel Local
Panel de Control Local / Sistema Fail Close

Actuador Vlvula tipo Mariposa


Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local
Transmisor de Nivel Ultrasonico
Manometro
Flujometro Termico Masico
Vlvula Control tipo Mariposa
Actuador Vlvula tipo Mariposa
Switch de Presin
Indicador diferencial de Presin
Indicador de Nivel
Transmisor de Temperatura
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Control Tipo Dardo
Actuador/Posicionador Vlvula tipo Dardo
Vlvula Manual
Vlvula Manual
Vlvula Solenoide
Botonera/Selector
Panel Control Local

3330-FV-2180
Reductor Celda 3332-CFL-011
Reductor Celda 3332-CFL-011
Reductor Celda 3332-CFL-011
Reductor Celda 3332-CFL-011
3332-CFL-011
3330-LV-2183A
3332-CFL-011
3330-LV-2183B
Panel de Control Local Celda 3332-CFL-011
Panel de Control Local Celda 3332-CFL-011
Panel de Control Local Celda 3332-CFL-011
Panel de Control Local Celda 3332-CFL-011
Panel de Control Local Celda 3332-CFL-011
3332-CFL-012
Aire Flotacin 3332-CFL-012
Aire Flotacin 3332-CFL-012
Aire Flotacin 3332-CFL-012
3330-FV-2185
Reductor Celda 3332-CFL-012
Reductor Celda 3332-CFL-012
Reductor Celda 3332-CFL-012
Reductor Celda 3332-CFL-012
3332-CFL-012
3330-LV-2188A
3332-CFL-012
3330-LV-2188B
Panel de Control Local Celda 3332-CFL-012
Panel de Control Local Celda 3332-CFL-012
Panel de Control Local Celda 3332-CFL-012
Panel de Control Local Celda 3332-CFL-012
Panel de Control Local Celda 3332-CFL-012
3332-CFL-013
Aire Flotacin 3332-CFL-013
Aire Flotacin 3332-CFL-013
Aire Flotacin 3332-CFL-013
3330-FV-2190
Reductor Celda 3332-CFL-013
Reductor Celda 3332-CFL-013
Reductor Celda 3332-CFL-013
Reductor Celda 3332-CFL-013
3332-CFL-013
3330-LV-2193A
3332-CFL-013
3330-LV-2193B
Panel de Control Local Celda 3332-CFL-013
Panel de Control Local Celda 3332-CFL-013
Panel de Control Local Celda 3332-CFL-013
Panel de Control Local Celda 3332-CFL-013
Panel de Control Local Celda 3332-CFL-013
3332-CFL-014
Aire Flotacin 3332-CFL-014
Aire Flotacin 3332-CFL-014
Aire Flotacin 3332-CFL-014
3330-FV-2195
Reductor Celda 3332-CFL-014
Reductor Celda 3332-CFL-014
Reductor Celda 3332-CFL-014
Reductor Celda 3332-CFL-014
3332-CFL-014
3330-LV-2198A
3332-CFL-014
3330-LV-2198B
Panel de Control Local Celda 3332-CFL-014
Panel de Control Local Celda 3332-CFL-014
Panel de Control Local Celda 3332-CFL-014
Panel de Control Local Celda 3332-CFL-014
Panel de Control Local Celda 3332-CFL-014

3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330
3330

BLOWERS

3313-SOP-001

3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310

IT
- 3832
- PDSH - 3831
PIT
- 3831
TI
- 3882
PI
- 3880
FV
- 3883
FY
- 3883
HV
- 3889
HY
- 3889
TE
- 3884A
TE
- 3884B
TE
- 3885
TE
- 3886
TE
- 3887
TE
- 3888A
TE
- 3888B
VT
- 3888A
VT
- 3888B
LG
- 3888A
LG
- 3888B

Consumo de Corriente Motor Blower


Cambio de Filtro Entrada de Aire Blow er
Presin de Salida Blower
Temperatura de Salida Blower
Presin de Salida Blower
Control Anti Surge
Control Anti Surge
Valvula secuencia partida
Valvula secuencia partida
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Vibraciones descanso blower
Vibraciones descanso blower
Nivel Aceite lubricacin Blower
Nivel Aceite lubricacin Blower

Transductor de Corrriente en CCM


Swith Diferencial de Presin
Transmisor de Presin
Termometro
Manometro
Vlvula Control Tipo Mariposa
Actuador/Posicionador Vlvula Mariposa
Vlvula Control ON/OFF
Actuador/Posicionador Vlvula ON/OFF
RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
Transductor de Vibraciones
Transductor de Vibraciones
Indicador de Nivel de Aceite
Indicador de Nivel de Aceite

BLOWERS

3313-SOP-002

3310
3310
3310
3310
3310
3310
3310
3310
3310

IT
- 3836
- PDSH - 3835
PIT
- 3891
TI
- 3892
PI
- 3892
FV
- 3893
FY
- 3893
HV
- 3899
HY
- 3899

Consumo de Corriente Motor Blower


Cambio de Filtro Entrada de Aire Blow er
Presin de Salida Blower
Temperatura de Salida Blower
Presin de Salida Blower
Control Anti Surge
Control Anti Surge
Valvula secuencia partida
Valvula secuencia partida

Transductor de Corrriente en CCM


Swith Diferencial de Presin
Transmisor de Presin
Termometro
Manometro
Vlvula Control Tipo Mariposa
Actuador/Posicionador Vlvula Mariposa
Vlvula Control ON/OFF
Actuador/Posicionador Vlvula ON/OFF

Outotec Chile SA.


DQ-110061-C5059-0008 R2 Listado de Instrumentos.xls

Dim Pr in

RNG

EQ ASOC

Marca

Modelo

BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS
E+ H
VTS
E+ H
BRAY CONTROL
BRAY LINE
SIEMENS
FINN FILTER
HYDAC
SIEMENS
LOURDES
METSO
LOURDES
METSO
VTS
VTS
VTS
VTS
VTS

SERIE 92/6A FFHH


SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40

SERIE

IO TIP

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R

CCM
Inlet Blower 3313-SOP-001
Outlet Blower 3313-SOP-001
Outlet Blower 3313-SOP-001
Outlet Blower 3313-SOP-001
Outlet Blower 3313-SOP-001
3313-FV-3883
Inlet Blower 3313-SOP-001
3313-HV-3889
Motor Blower 3313-SOP-001
Motor Blower 3313-SOP-001
Motor Blower 3313-SOP-001
Motor Blower 3313-SOP-001
Motor Blower 3313-SOP-001
Blower 3313-SOP-001
Blower 3313-SOP-001
Blower 3313-SOP-001
Blower 3313-SOP-001
Blower 3313-SOP-001
Blower 3313-SOP-001

400mm
VTS
VTS
VTS
1/2" NPT
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

0-20A
VTS
VTS
VTS
VTS
0-100%
0-100%
0-100%
0-100%
0-200C
0-200C
0-200C
0-200C
0-200C
0-200C
0-200C
VTS
VTS
VTS
VTS

3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001
3313-SOP-001

VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

4-20mA + HART DQ-110071-C-5059-0023


DQ-110071-C-5059-0023
FF H1
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
N/R
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
24VDC
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023

N/R
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

CCM
Inlet Blower 3313-SOP-002
Outlet Blower 3313-SOP-002
Outlet Blower 3313-SOP-002
Outlet Blower 3313-SOP-002
Outlet Blower 3313-SOP-002
3313-FV-3883
Inlet Blower 3313-SOP-002
3313-HV-3889

400mm
VTS
VTS
VTS
1/2" NPT
VTS
VTS
VTS
VTS

0-20A
VTS
VTS
VTS
VTS
0-100%
0-100%
0-100%
0-100%

3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002

VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

4-20mA + HART DQ-110071-C-5059-0023


DQ-110071-C-5059-0023
FF H1
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
N/R
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
24VDC
DQ-110071-C-5059-0023

N/R
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

3/4-16UNF
L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

65F1H

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

PROLINE T-MASS 65I


SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS
DQ110071-C5059-0015
DQ110071-C5059-0014
DQ110071-C5059-0012
DQ110071-C5059-0013
DQ110071-C5059-0013
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
Ver manual del Reductor
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
DQ-110071-20-IN-DS-0402
VTS
VTS
VTS
VTS
VTS

L=100
425mm
CP25 250
425mm
CP25 250
VTS
VTS
VTS
VTS
VTS

L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

PROLINE T-MASS 65I


SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 600
ND9106FN
TAPON 600
ND9106FN
VTS
VTS
VTS
VTS
VTS
FMU 40

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

Descripcin Dispositivo

3/4-16UNF

3/4-16UNF

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

7MC1006-1DA11- T45

P&ID

0-100C
0-100%
0-100%
0-100%
0-100%
N/R
N/R
N/R
N/R
N/R
0-500mm
48kPa
400-2800 m3/h
0-100%
0-100%
0-4 bar
2,5+-0,3 bar

L=100
600mm
CPY25 450
600mm
CPY25 450
VTS
VTS
VTS
VTS
VTS
2" PNT
1/2" NPT
ph=4"
ph=4"

FF H1
FF H1
N/R
N/R
FF H1

DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0020
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027
DQ-110071-C-5059-0027

TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3330-LCP-0183
3330-LCP-0183
3330-LCP-0183
3330-LCP-0183
3330-LCP-0183
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3330-LCP-0188
3330-LCP-0188
3330-LCP-0188
3330-LCP-0188
3330-LCP-0188
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3330-LCP-0193
3330-LCP-0193
3330-LCP-0193
3330-LCP-0193
3330-LCP-0193
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
TC-300
3330-LCP-0198
3330-LCP-0198
3330-LCP-0198
3330-LCP-0198
3330-LCP-0198

3/4-16UNF

0-100%
0-4 bar
2,5+-0,3 bar

PROLINE T-MASS 65I


SERIE 40
SERIE 92/6A FFHH
SITRANS P
FPC,V25,VM-F6
FSA 127-2,4/-/12
SITRANS T
TAPON 450
ND9106FN
TAPON 450
ND9106FN
VTS
VTS
VTS
VTS
VTS

7MF4035

FF H1

7MF4035

FF H1

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1

65F1H

FF H1
VTS
VTS
DO
DI
N/R
FF H1
N/R
FF H1

7MF4035

FF H1

7MF4035

7MC1006-1DA11- T45

FF H1
FF H1
N/R
N/R
FF H1
FF H1
FF H1
VTS
VTS
DO
DI
N/R

Notas

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

REV 2
REV 2
REV 2
REV 1

A suministrar por Cliente


A suministrar por Cliente

A suministrar por Cliente


A suministrar por Cliente

Pagina 7 de 8

LISTADO DE INSTRUMENTOS
Documento N DQ-110071-C5059-LI-0008
Revisin 2
DQ- 110071

PROYECTO EXPLOTACION MINA MINISTRO HALES

CORPORACION NACIONAL DEL COBRE

LISTADO DE INSTRUMENTOS Y EQUIPOS


TAG

TE
TE
TE
TE
TE
TE
TE
VT
VT
LG
LG

3894A
3894B
3895
3896
3897
3898A
3898B
3898A
3898B
3898A
3898B

Servicio

Tipo

Lnea / Eq. Principal

EQ ASOC

Marca

Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Vibraciones descanso blower
Vibraciones descanso blower
Nivel Aceite lubricacin Blower
Nivel Aceite lubricacin Blower

RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
Transductor de Vibraciones
Transductor de Vibraciones
Indicador de Nivel de Aceite
Indicador de Nivel de Aceite

Motor Blower 3313-SOP-002


Motor Blower 3313-SOP-002
Motor Blower 3313-SOP-002
Motor Blower 3313-SOP-002
Motor Blower 3313-SOP-002
Blower 3313-SOP-002
Blower 3313-SOP-002
Blower 3313-SOP-002
Blower 3313-SOP-002
Blower 3313-SOP-002
Blower 3313-SOP-002

VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

0-200C
0-200C
0-200C
0-200C
0-200C
0-200C
0-200C
VTS
VTS
VTS
VTS

3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002
3313-SOP-002

VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023

VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

CCM
Inlet Blower 3313-SOP-003
Outlet Blower 3313-SOP-003
Outlet Blower 3313-SOP-003
Outlet Blower 3313-SOP-003
Outlet Blower 3313-SOP-003
3313-FV-3883
Inlet Blower 3313-SOP-003
3313-HV-3889
Motor Blower 3313-SOP-003
Motor Blower 3313-SOP-003
Motor Blower 3313-SOP-003
Motor Blower 3313-SOP-003
Motor Blower 3313-SOP-003
Blower 3313-SOP-003
Blower 3313-SOP-003
Blower 3313-SOP-003
Blower 3313-SOP-003
Blower 3313-SOP-003
Blower 3313-SOP-003

400mm
VTS
VTS
VTS
1/2" NPT
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

0-20A
VTS
VTS
VTS
VTS
0-100%
0-100%
0-100%
0-100%
0-200C
0-200C
0-200C
0-200C
0-200C
0-200C
0-200C
VTS
VTS
VTS
VTS

3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003
3313-SOP-003

VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

4-20mA + HART DQ-110071-C-5059-0023


DQ-110071-C-5059-0023
FF H1
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
N/R
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
24VDC
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
4-20mA + HART DQ-110071-C-5059-0023
DQ-110071-C-5059-0023
DQ-110071-C-5059-0023

N/R
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS
VTS

3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310

BLOWERS

3313-SOP-003

3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310
3310

IT
- 3839
- PDSH - 3838
PIT
- 3901
TI
- 3902
PI
- 3900
FV
- 3903
FY
- 3903
HV
- 3909
HY
- 3909
TE
- 3904A
TE
- 3904B
TE
- 3905
TE
- 3906
TE
- 3907
TE
- 3908A
TE
- 3908B
VT
- 3908A
VT
- 3908B
LG
- 3908A
LG
- 3908B

Consumo de Corriente Motor Blower


Cambio de Filtro Entrada de Aire Blow er
Presin de Salida Blower
Temperatura de Salida Blower
Presin de Salida Blower
Control Anti Surge
Control Anti Surge
Valvula secuencia partida
Valvula secuencia partida
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Temperatura descansos
Vibraciones descanso blower
Vibraciones descanso blower
Nivel Aceite lubricacin Blower
Nivel Aceite lubricacin Blower

Transductor de Corrriente en CCM


Swith Diferencial de Presin
Transmisor de Presin
Termometro
Manometro
Vlvula Control Tipo Mariposa
Actuador/Posicionador Vlvula Mariposa
Vlvula Control ON/OFF
Actuador/Posicionador Vlvula ON/OFF
RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
RTD PT100
Transductor de Vibraciones
Transductor de Vibraciones
Indicador de Nivel de Aceite
Indicador de Nivel de Aceite

NOTAS :

VENDOR TO SPECIFY
NOT REQUIRED

VTS
N/R

LIF
FIT
FV
PI

PI
FIT
LV
LE
FV
LIT

Dim Pr in

RNG

Modelo

SERIE

IO TIP

P&ID

Descripcin Dispositivo

Notas

A suministrar por Cliente


A suministrar por Cliente

0
32
32
32

35
0
60
0
35
0

2x 4" + 21 x 6"

160

Outotec Chile SA.


DQ-110061-C5059-0008 R2 Listado de Instrumentos.xls

Pagina 8 de 8

TOMO 2: INSTRUMENTACIN
Y CONTROL
PROYECTO
EXPLOTACIN
MINA MINISTRO HALES
Outotec Chile S.A.

22/05/2012

1 (1)

Anexos
Tomo 2
Captulo 3

Outotec Chile S.A.


Avda. Vitacura 2939 Piso 7 y Piso 9
Edificio Millenium, Las Condes
7550011, Santiago, Chile
Tel. +56 2 336 2000, Fax +56 2 336 2041
www.outotec.com

CORPORACION NACIONAL DEL COBRE


CODELCO CHILE
VICEPRESIDENCIA DE PROYECTOS
PROYECTO EXPLOTACION MINA MINISTRO HALES

CELDAS DE FLOTACIN
Project No DQ110071

DESCRIPCIN DE DISPOSITIVOS
FLUJOMETROS AIRE FLOTACION

Documento N DQ-110071-C5059-0012
O/C N H336073-PM014/0

REV

DESCRIPCIN

PREPAR

REVIS

APROB

FECHA

EMITIDO COMO CERTIFICADO

ATR

ATR

GHP

10-08-2011

EMITIDO PARA INFORMACION CLIENTE

ATR

ATR

GHP

25-07-2011

EMITIDO PARA COMPRA

ATR

ATR

GHP

13-06-2011

EMITIDO PARA COORDINACIN INTERNA

ATR

ATR

GHP

08-06-2011

1 INSTRUCCIONES AL PROVEEDOR
2
3
4
5
6
7
8
9 LISTA DE EQUIPOS INCLUIDOS
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
REV REV DESCRIPTION

TAG
3310-FIT/FE-1810
3310-FIT/FE-1816
3310-FIT/FE-1820
3310-FIT/FE-1826
3310-FIT/FE-1830
3310-FIT/FE-1836
3310-FIT/FE-1860
3310-FIT/FE-1866
3310-FIT/FE-1870
3310-FIT/FE-1876
3310-FIT/FE-1880
3310-FIT/FE-1886
3330-FIT/FE-1850
3330-FIT/FE-2255
3330-FIT/FE-2260
3330-FIT/FE-2270
3330-FIT/FE-2061
3330-FIT/FE-2071
3330-FIT/FE-2075
3330-FIT/FE-2275
3330-FIT/FE-2280
3330-FIT/FE-2265
3330-FIT/FE-2285
3330-FIT/FE-2091
3330-FIT/FE-2101
3330-FIT/FE-2105
3330-FIT/FE-2170
3330-FIT/FE-2175
3330-FIT/FE-2180
3330-FIT/FE-2185
3330-FIT/FE-2190
3330-FIT/FE-2195

DATE

BY

SERVICIO
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin
Flujo Aire Flotacin

APP

REMARKS

3312-CFL-001
3312-CFL-002
3312-CFL-003
3312-CFL-004
3312-CFL-005
3312-CFL-006
3312-CFL-007
3312-CFL-008
3312-CFL-009
3312-CFL-010
3312-CFL-011
3312-CFL-012
3332-CFL-015
3332-CFL-016
3332-CFL-017
3332-CFL-018
3332-CFL-001
3332-CFL-002
3332-CFL-003
3332-CFL-019
3332-CFL-020
3332-CFL-021
3332-CFL-022
3332-CFL-005
3332-CFL-006
3332-CFL-007
3332-CFL-009
3332-CFL-010
3332-CFL-011
3332-CFL-012
3332-CFL-013
3332-CFL-014

PROJECT NUMBER
DE110071
DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1810
Flujo Aire Flotacin 3312-CFL-001

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1816
Flujo Aire Flotacin 3312-CFL-002

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1820
Flujo Aire Flotacin 3312-CFL-003

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1826
Flujo Aire Flotacin 3312-CFL-004

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1830
Flujo Aire Flotacin 3312-CFL-005

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1836
Flujo Aire Flotacin 3312-CFL-006

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1860
Flujo Aire Flotacin 3312-CFL-007

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1866
Flujo Aire Flotacin 3312-CFL-008

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1870
Flujo Aire Flotacin 3312-CFL-009

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1876
Flujo Aire Flotacin 3312-CFL-010

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1880
Flujo Aire Flotacin 3312-CFL-011

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FIT/FE-1886
Flujo Aire Flotacin 3312-CFL-012

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
4 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
800 mm
303 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F1H-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-1850
Flujo Aire Flotacin 3332-CFL-015

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2255
Flujo Aire Flotacin 3332-CFL-016

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2260
Flujo Aire Flotacin 3332-CFL-017

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2270
Flujo Aire Flotacin 3332-CFL-018

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2061
Flujo Aire Flotacin 3332-CFL-001

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0021

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2071
Flujo Aire Flotacin 3332-CFL-002

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0021

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2075
Flujo Aire Flotacin 3332-CFL-003

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2275
Flujo Aire Flotacin 3332-CFL-019

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2280
Flujo Aire Flotacin 3332-CFL-020

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2265
Flujo Aire Flotacin 3332-CFL-021

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2285
Flujo Aire Flotacin 3332-CFL-022

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2091
Flujo Aire Flotacin 3332-CFL-005

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0021

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2101
Flujo Aire Flotacin 3332-CFL-006

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0021

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2105
Flujo Aire Flotacin 3332-CFL-007

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0022

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2170
Flujo Aire Flotacin 3332-CFL-009

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2175
Flujo Aire Flotacin 3332-CFL-010

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2180
Flujo Aire Flotacin 3332-CFL-011

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2185
Flujo Aire Flotacin 3332-CFL-012

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2190
Flujo Aire Flotacin 3332-CFL-013

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
FLOWMETER BODY

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FIT/FE-2195
Flujo Aire Flotacin 3332-CFL-014

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23

Body type
End conn nominal size
End conn term type
Seal type
Mounting hardware
Body wetted material
End termination material
Gasket/Seal material

FLANGED
3 INCH
DIRECT MOUNT
F TYPE
N/R
SS 316
SS 316
VITON

61
62
63
64
65
66
67
68
69
70
71
72

PERFORMANCE CHARACTERISTICS
Max press at design temp

24
25
26
27
28
29
30

Sensor type
Sensor wetted material
Fill fluid material

73
74
75
76
77
78
79

Min working temperature


Flow rate accuracy rating
Density accuracy rating
Min velocity URL
Density LRL
Min req back press
Pressure drop at flow URL

31
32
33
34
35
36

Housing type
Enclosure type no/class
Signal termination type
Cert/Approval Type
Enclosure material

80
81
82
83
84
85

Min ambient working temp


Contacts AC rating
Contacts DC rating
Max sensor to receiver lg

Rating
Style

ANSI 16.5
SCH 40

SENSING ELEMENT
THERMAL FLOWMETER
SS 316
N/R

CONNECTION HEAD
POWDER COATED
NEMA 4X/IP67
1/2 INCH NPT
STANDART
CAST ALUMINIUM

37
38
39 TRANSMITTER OR COMPUTER
40
41
42
43
44
45

Housing type
Measurement compensation
Output signal type
Enclosure type no/class
Span-zero adjustment
Characteristic curve

COMPACK HOUSING
REQUIRED
DIGITAL, SEE ITEM 46
NEMA 4X/IP67
REQUIRED
LINEAR RESPECT TO FLOW

46
47
48
49
50
51
52

Digital communication std


Signal power source
Failsafe style
Integral indicator style
Signal termination type
Cert/Approval Type
Mounting location/type

FIELD BUS FUNDATION


120 VAC
N/R
TWO LINES
BLOCK
FF
FIELD

53
54
55
56
57
58
59
110
111

Calibration type
Failure/Diagnostic action
Enclosure material

STANDART
N/R
CAST ALUMINIUM

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

50 Hz

Location
Area Class
P&ID
TOTALIZER INDICATOR

FIELD
NON HAZARDOUS AREA
DQ-110071-C-5059-0020

Totalizer type
Enclosure type no/class
Signal power source
Contacts arrangement
Totalizer reset style
Integral inedicator style
Cert/Approval type
Mounting location/type
Enclosure material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

At

60 C

-20 C
Max
<0,5% AT FULL SCALE
N/R
400 m3/h
Max
2,24 kg/m3
Max
100 kPa
300 kPa
At
-20 C
8 mm
8 mm

100 C

3000 m3/h

25 C

Max
At
At

60 C
12 mm
12 mm

N/R

ACCESSORIES

86 Connecting cable length


87 Isolation manifold
88 Remote indicator style

N/R
N/R
N/R

89 Calibrarion adapter
90
91
92
93
94 SPECIAL REQUIREMENTS

N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
NON AGENCY APROVED METER
REQUIRED
NOT REQUIRED

PHYSICAL DATA
28 kg
640 mm
299 mm
600 mm
1/2 inch
BY MANUFACTURER
INPUT OR TEST
LRV
URV

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Flow rate analog output


Mass flow rate analog output
Meas analog output
Measurement - Scale

MANUFACTURER

MODEL NUMBER

120 FLOW TUBE & TRANSMITTER


121
122
123
124 NOTES

ENDRESS + HAUSER

t-mass 65F80-AK2AG1AABABK

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

100 kPa

400 m3/h

3000 m3/h

Style

THREADED / NPT

OUTPUT OR SCALE
LRV
URV
1%

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0012

INSTRUMENT DATA SHEET


FLOWMETER
Device Specification

ACTION

CORPORACION NACIONAL DEL COBRE


CODELCO CHILE
VICEPRESIDENCIA DE PROYECTOS
PROYECTO EXPLOTACION MINA MINISTRO HALES

CELDAS DE FLOTACIN
Project No DQ110071

DESCRIPCIN DE DISPOSITIVOS
VALVULAS DE CONTROL AIRE FLOTACION

Documento N C5059-013
O/C N H336073-PM014/0

REV

DESCRIPCIN

PREPAR

REVIS

APROB

FECHA

EMITIDO COMO SUMINISTRADO

ATR

ATR

GHP

14-11-2011

EMITIDO COMO CERTIFICADO

ATR

ATR

GHP

10-08-2011

EMITIDO PARA INFORMACION CLIENTE

ATR

ATR

GHP

25-07-2011

EMITIDO PARA COMPRA

ATR

ATR

GHP

13-06-2011

EMITIDO PARA COORDINACIN INTERNA

ATR

ATR

GHP

08-06-2011

1 INSTRUCCIONES AL PROVEEDOR
2
3
4
5
6
7
8
9 LISTA DE EQUIPOS INCLUIDOS
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
REV REV DESCRIPTION

TAG
3310-FV-1810
3310-FV-1816
3310-FV-1820
3310-FV-1826
3310-FV-1830
3310-FV-1836
3310-FV-1860
3310-FV-1866
3310-FV-1870
3310-FV-1876
3310-FV-1880
3310-FV-1886
3330-FV-2250
3330-FV-2255
3330-FV-2260
3330-FV-2270
3330-FV-2061
3330-FV-2071
3330-FV-2075
3330-FV-2275
3330-FV-2280
3330-FV-2265
3330-FV-2285
3330-FV-2091
3330-FV-2101
3330-FV-2105
3330-FV-2170
3330-FV-2175
3330-FV-2180
3330-FV-2185
3330-FV-2190
3330-FV-2195

DATE

SERVICIO
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire
Control Aire

BY

APP

REMARKS

Flotacin 3312-CFL-001
Flotacin 3312-CFL-002
Flotacin 3312-CFL-003
Flotacin 3312-CFL-004
Flotacin 3312-CFL-005
Flotacin 3312-CFL-006
Flotacin 3312-CFL-007
Flotacin 3312-CFL-008
Flotacin 3312-CFL-009
Flotacin 3312-CFL-010
Flotacin 3312-CFL-011
Flotacin 3312-CFL-012
Flotacin 3332-CFL-015
Flotacin 3332-CFL-016
Flotacin 3332-CFL-017
Flotacin 3332-CFL-018
Flotacin 3332-CFL-001
Flotacin 3332-CFL-002
Flotacin 3332-CFL-003
Flotacin 3332-CFL-019
Flotacin 3332-CFL-020
Flotacin 3332-CFL-021
Flotacin 3332-CFL-022
Flotacin 3332-CFL-005
Flotacin 3332-CFL-006
Flotacin 3332-CFL-007
Flotacin 3332-CFL-009
Flotacin 3332-CFL-010
Flotacin 3332-CFL-011
Flotacin 3332-CFL-012
Flotacin 3332-CFL-013
Flotacin 3332-CFL-014

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

14.11.11
10.08.11

ATR
ATR

GHP
GHP

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1810
Control Aire Flotacin 3312-CFL-001

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1816
Control Aire Flotacin 3312-CFL-002

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1820
Control Aire Flotacin 3312-CFL-003

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1826
Control Aire Flotacin 3312-CFL-004

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1830
Control Aire Flotacin 3312-CFL-005

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1836
Control Aire Flotacin 3312-CFL-006

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1860
Control Aire Flotacin 3312-CFL-007

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1866
Control Aire Flotacin 3312-CFL-008

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1870
Control Aire Flotacin 3312-CFL-009

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1876
Control Aire Flotacin 3312-CFL-010

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1880
Control Aire Flotacin 3312-CFL-011

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-FV-1886
Control Aire Flotacin 3312-CFL-012

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
4 INCH
Rating
4 INCH
Rating
Style
LUG
PTFE
ANSI B16,10
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
3,7 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

25
50
300
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2250
Control Aire Flotacin 3332-CFL-015

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2255
Control Aire Flotacin 3332-CFL-016

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2260
Control Aire Flotacin 3332-CFL-017

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2270
Control Aire Flotacin 3332-CFL-018

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2061
Control Aire Flotacin 3332-CFL-001

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0021
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2071
Control Aire Flotacin 3332-CFL-002

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0021
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2075
Control Aire Flotacin 3332-CFL-003

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2275
Control Aire Flotacin 3332-CFL-019

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2280
Control Aire Flotacin 3332-CFL-020

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2265
Control Aire Flotacin 3332-CFL-021

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2285
Control Aire Flotacin 3332-CFL-022

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2091
Control Aire Flotacin 3332-CFL-005

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0021
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2101
Control Aire Flotacin 3332-CFL-006

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0021
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2105
Control Aire Flotacin 3332-CFL-007

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2170
Control Aire Flotacin 3332-CFL-009

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2175
Control Aire Flotacin 3332-CFL-010

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2180
Control Aire Flotacin 3332-CFL-011

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2185
Control Aire Flotacin 3332-CFL-012

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2190
Control Aire Flotacin 3332-CFL-013

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
VALVE BODY AND BONNET

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-FV-2195
Control Aire Flotacin 3332-CFL-014

7
8
9
10
60

12
13
14
15
16
17
18
19
20

Body type
Bonnet style
Inlet conn nominal size
Outlet conn nominal size
End conn termn type
Flange facing finish
Shaft seal type
Face-to-face standard
Yoke boss diameter

BUTTERFLY, CONTROL VALVE


HIGH PERFORMANCE
3 INCH
Rating
3 INCH
Rating
Style
LUG
RTFE
ANSI B16,34
VTS

61
62
63
64
65
66
67
68
69

Enclosure type no/class


Digital comunication std
Signal power source
Presure gauges
Cert/Approval type
Mounting location/type
Enclosure material

21
22
23
24
25
26
27
28
29
30
31

Body and bonnet material


Lining material
Body/Bonnet bolting matl
Packing flg bolting matl
Gasket material
Packing material

SS 316
VTS
N/R
N/R
N/R
N/R

VALVE TRIM
Closure member type
Trim style

Configuration type
Input signal type
Enclosure type no/class
Signal power source
Digital comunication std
Cert/Approval type
Presure gauges
By-pass manifold
Enclosure material

DISK
VTS

70
71
72
73
74
75
76
77
78
79
80

32
33
34
35
36
37
38
39

Inherent characteristic
Real ring type
Flow direction force
Shaft diameter
Closure member material
Seal ring material
Shaft material
Flow ring material

EQUAL PERCENTAGE
RPTFE
BIDIRECTIONAL
2,8 INCH
Rated Travel
N/R
RPTFE
SS 316
N/R

81
82
83
84
85
86
87
88

Max pressure at design temp


Min working temperature
Max pressure drop
Rated flow coef type
Rated factor Fl
Rated seat leakage class

40
41
42
43
44
45

Guide/Retained material
Guide bushing material
Hard facing/coating

VTS
SS 316
VTS

89
90
91
92
93
94

Air set filter style


Air set gauges
Mounting hardware
Tubing nominal size / matl

46
47
48
49
50
51
52

Actuator type
Effective area
Bench set LRL
Max supply capability
Handwheel type/position
Mounting orientation
Casing/cylinder material

150

90

ACTUATOR

53 Diaphragm/O ring matl


54 Yoke material
55
56 SIGNAL TRANSDUCER
57
58
59
110
111

ANSI

Input signal type


Output signal type
Accuracy rating
CALIBRATION AND TEST
TAG NO/FUNCTIONAL IDENT

Location
FIELD
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
SIGNAL TRANSDUCER continued

POSITIONER OR CONTROLLER

Max

100 psi

700
-30
120
3,7

kPa
C
kPa
Coef

At
Max

50 C
100 C

N/R
VTS

Xt
Smr

ACCESSORIES
EXTERNAL
N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

RPTFE
N/R

102
103
104
105

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance

FF H1
FF H1
0.5% OR BETTER

106 Signal conn nominal size


107 Mfr reference dwg
108

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
N/R
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Bench set-Travel
Positioner Input-Travel
Transducer input-output
Test pressure

MANUFACTURER

MODEL NUMBER

120
121
122
123
124

BRAY CONTROL
BRAY LINE
BRAY LINE

SERIE 40
SERIE 92
6A FFHH

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

LINEAL
FF H1
NEMA 4X
VTS
FF H1
N/R
90 psi
N/R
ALUMINIUM

PERFORMANCE CHARACTERISTICS

NEUMATIC, DOUBLE ACTING


VTS
VTS
URL
VTS
VTS
SIDE / OVER
ALUMINIUM

VALVE
VALVE ACTUATOR/POSICIONATOR
VALVE POSICIONATOR

NEMA 4X
N/R
N/R
N/R
N/R
FIELD
ALUMINIUM

17
50
250
60

kg
mm
mm
mm

1/2 inch
BY MANUFACTURER

Style

Threaded / NPT

INPUT OR TEST
LVR
URV

OUTPUT OR SCALE
LRV
URV

ACTION

NOTES
VTS = VENDOR TO SPECIFY
N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

1
0

SEGN SUMINISTRADO
PARA CERTIFICAR

14.11.11
10.08.11

ATR
ATR

GHP
GHP

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

REMARKS

PROJECT NUMBER
DE110071
DOCUMENT NUMBER
C5059-0013

INSTRUMENT DATA SHEET


BUTTERFLY VALVE CONTROL ASSEMBLY
Device Specification

CORPORACION NACIONAL DEL COBRE


CODELCO CHILE
VICEPRESIDENCIA DE PROYECTOS
PROYECTO EXPLOTACION MINA MINISTRO HALES

CELDAS DE FLOTACIN
Project No DQ110071

DESCRIPCIN DE DISPOSITIVOS
NIVELES ULTRASONICOS

Documento N C5059-015
O/C N H336073-PM014/0

REV

DESCRIPCIN

PREPAR

REVIS

APROB

FECHA

EMITIDO COMO PLANO CERTIFICADO

ATR

ATR

GHP

10-08-2011

EMITIDO PARA APROBACION CLIENTE

ATR

ATR

GHP

25-07-2011

EMITIDO PARA COMPRA

ATR

ATR

GHP

13-06-2011

EMITIDO PARA COORDINACIN INTERNA

ATR

ATR

GHP

08-06-2011

1 INSTRUCCIONES AL PROVEEDOR
2
3
4
5
6
7
8
9 LISTA DE EQUIPOS INCLUIDOS
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
REV REV DESCRIPTION

TAG
3310-LIT/LE-1812
3310-LIT/LE-1818
3310-LIT/LE-1822
3310-LIT/LE-1828
3310-LIT/LE-1832
3310-LIT/LE-1838
3310-LIT/LE-1862
3310-LIT/LE-1868
3310-LIT/LE-1872
3310-LIT/LE-1879
3310-LIT/LE-1882
3310-LIT/LE-1889
3330-LIT/LE-2253
3330-LIT/LE-2258
3330-LIT/LE-2263
3330-LIT/LE-2273
3330-LIT/LE-2073
3330-LIT/LE-2077
3330-LIT/LE-2278
3330-LIT/LE-2283
3330-LIT/LE-2268
3330-LIT/LE-2288
3330-LIT/LE-2103
3330-LIT/LE-2107
3330-LIT/LE-2173
3330-LIT/LE-2178
3330-LIT/LE-2183
3330-LIT/LE-2188
3330-LIT/LE-2193
3330-LIT/LE-2198

DATE

BY

SERVICIO
Nivel Pulpa Celda 3312-CFL-001
Nivel Pulpa Celda 3312-CFL-002
Nivel Pulpa Celda 3312-CFL-003
Nivel Pulpa Celda 3312-CFL-004
Nivel Pulpa Celda 3312-CFL-005
Nivel Pulpa Celda 3312-CFL-006
Nivel Pulpa Celda 3312-CFL-007
Nivel Pulpa Celda 3312-CFL-008
Nivel Pulpa Celda 3312-CFL-009
Nivel Pulpa Celda 3312-CFL-010
Nivel Pulpa Celda 3312-CFL-011
Nivel Pulpa Celda 3312-CFL-012
Nivel Pulpa Celda 3332-CFL-015
Nivel Pulpa Celda 3332-CFL-016
Nivel Pulpa Celda 3332-CFL-017
Nivel Pulpa Celda 3332-CFL-018
Nivel Pulpa Celda 3332-CFL-002
Nivel Pulpa Celda 3332-CFL-003
Nivel Pulpa Celda 3332-CFL-019
Nivel Pulpa Celda 3332-CFL-020
Nivel Pulpa Celda 3332-CFL-021
Nivel Pulpa Celda 3332-CFL-022
Nivel Pulpa Celda 3332-CFL-006
Nivel Pulpa Celda 3332-CFL-007
Nivel Pulpa Celda 3332-CFL-009
Nivel Pulpa Celda 3332-CFL-010
Nivel Pulpa Celda 3332-CFL-011
Nivel Pulpa Celda 3332-CFL-012
Nivel Pulpa Celda 3332-CFL-013
Nivel Pulpa Celda 3332-CFL-014

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1812
Nivel Pulpa Celda 3312-CFL-001

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1818
Nivel Pulpa Celda 3312-CFL-002

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1822
Nivel Pulpa Celda 3312-CFL-003

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1828
Nivel Pulpa Celda 3312-CFL-004

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1832
Nivel Pulpa Celda 3312-CFL-005

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1838
Nivel Pulpa Celda 3312-CFL-006

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1862
Nivel Pulpa Celda 3312-CFL-007

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1868
Nivel Pulpa Celda 3312-CFL-008

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1872
Nivel Pulpa Celda 3312-CFL-009

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1879
Nivel Pulpa Celda 3312-CFL-010

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1882
Nivel Pulpa Celda 3312-CFL-011

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3312/ FLOTACION PRIMARIA
3310-LIT/LE-1889
Nivel Pulpa Celda 3312-CFL-012

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2253
Nivel Pulpa Celda 3332-CFL-015

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2258
Nivel Pulpa Celda 3332-CFL-016

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2263
Nivel Pulpa Celda 3332-CFL-017

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2273
Nivel Pulpa Celda 3332-CFL-018

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2073
Nivel Pulpa Celda 3332-CFL-002

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0021
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2077
Nivel Pulpa Celda 3332-CFL-003

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2278
Nivel Pulpa Celda 3332-CFL-019

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2283
Nivel Pulpa Celda 3332-CFL-020

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2268
Nivel Pulpa Celda 3332-CFL-021

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2288
Nivel Pulpa Celda 3332-CFL-022

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2103
Nivel Pulpa Celda 3332-CFL-006

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0021
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2107
Nivel Pulpa Celda 3332-CFL-007

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0022
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2173
Nivel Pulpa Celda 3332-CFL-009

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2178
Nivel Pulpa Celda 3332-CFL-010

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2183
Nivel Pulpa Celda 3332-CFL-011

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2188
Nivel Pulpa Celda 3332-CFL-012

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2193
Nivel Pulpa Celda 3332-CFL-013

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
Area Name
TAG
Service
PROCESS CONNECTION

PROYECTO EXPLOTACION MINA MINISTRO HALES


3332/ AREA FLOTACION
3330-LIT/LE-2198
Nivel Pulpa Celda 3332-CFL-014

7
8
9
10
60

Location
Field
Area Class
NON HAZARDOUS
P&ID
DQ-110071-C-5059-0020
PERFORMANCE CHARACTERISTICS

12
13
14
15
16
17
18
19

Body/Fitting type
Process conn nominal size
Process conn termn type
Wetted material
Flange material
Seal/O ring material

COMPACT TRANSMITER
1 1/2 INCH
Rating
THREADED
Style
PVDF
N/R
N/R

61
62
63
64
65
66
67
68

Max press at design temp


Min working temperature
Accuracy rating
Level lower range limit
Min measurement span
Beam angle
Min ambient working temp
Contacts ac rating

20
21
22
23
24
25

Detector type
Detector style
Insertion length
Integral cable length

26
27
28
29
30
31
32

Type
Enclosure type no/class
Cert/Approval type
Mounting location/type
Enclosure material

NPT

SENSING ELEMENT
INTEGRATED WITH TRANSMITTER
NON CONTACT
VTS
VTS

69 Contacts dc rating
70 Max sensor to receiver lg
71
72
73
74

INTEGRATED WITH TRANSMITTER


NEMA 4X/IP68
N/R
FIELD
PVDF

75
76
77
78
79
80
81

33 Housing type
34 Measurement compensation
35 Output signal type

INTEGRATED
REQUIRED, TEMPERATURE COMPENSATED
DIGITAL, SEE ITEM 39

82
83
84 ACCESSORIES

36
37
38
39
40
41
42
43
44
45

NEMA 4X/IP68
N/R
LINEAR RESPECT MEASURED LEVEL
FIELDBUS FOUNDATION H1
N/R
N/R
Quantity
N/R
DIGITAL, LCD INTEGRATED
GENERAL PORPOSE
FIELD

85
86
87
88
89
90
91
92
93
94

CONNECTION HEAD

TRANSMITTER w/wo SWITCHES

Enclosure type no/class


Control sequence
Characteristic curve
Digital communication std
Signal power source
Contact arrangement
Failsafe style
Integral indicator style
Cert/Approval type
Mounting location/type

46 Failure/Diagnostic action
47 Signal processing
48 Enclosure material
49
50
51
52

VTS
N/R
ALUMINIUM F12

53
54
55
56
57
58
59
110 CALIBRATION AND TEST
111 TAG NO/FUNCTIONAL IDENT

Connecting cables length


Enclosure heater
Mounting hardware

<10
N/R
N/R

At
Max

30 C
50 C

URL
Max

500 mm
400 mm

Max
At max

50 C

At max
1000 mm

N/R
N/R
N/R

SPECIAL REQUIREMENTS

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Signal conn nominal size
Mfr reference dwg

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-123/122-0001
GENERAL PORPOSE
N/R
N/R

PHYSICAL DATA

MEAS/SIGNAL/TEST

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Level analog Output


Level scale
Note 1
Level Setpoint 1 Output

MANUFACTURER

MODEL NUMBER

120 LEVEL TRANSMITTER


121
122
123
124 NOTES

Endress+Hauser

FMU40-ANF2A4

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

0,5

100 kPa
-40 C
%
0 mm
200 mm

-40 C

2,6 kg
VTS
300 mm
N/R
1/2 INCH
BY MANUFACTURER

Style

INPUT OR TEST
LRV
URV

OUTPUT OR SCALE
LRV
URV

0m
0m

500mm
500mm

Threaded / NPT

0%

ACTION

100%

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96
Note 1
Este Instrumento entrega como valor medido la distancia entre el nivel de rebalse (Labio Launder) de la Celda hasta el nivel de la pulpa Mediante un dispositivo tipo Flotador.
El nivel de la espuma es obtenido indirectamente conociendo la altura de la celda.

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10,08,11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0015

INSTRUMENT DATA SHEET


NON CONTACT ULTRASONIC LEVEL
Device Specification

CORPORACION NACIONAL DEL COBRE


CODELCO CHILE
VICEPRESIDENCIA DE PROYECTOS
PROYECTO EXPLOTACION MINA MINISTRO HALES

CELDAS DE FLOTACIN
Project No DQ110071

DESCRIPCIN DE DISPOSITIVOS
MANOMETROS

Documento N C5059-014
O/C N H336073-PM014/0

REV

DESCRIPCIN

PREPAR

REVIS

APROB

FECHA

EMTIDO COMO CERTIFICADO

ATR

ATR

GHP

10-08-2011

EMITIDO PARA INFORMACION CLIENTE

ATR

ATR

GHP

25-07-2011

EMITIDO PARA COMPRA

ATR

ATR

GHP

13-06-2011

EMITIDO PARA COORDINACIN INTERNA

ATR

ATR

GHP

08-06-2011

1 INSTRUCCIONES AL PROVEEDOR
2
3
4
5
6
7
8
9 LISTA DE EQUIPOS INCLUIDOS
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
REV REV DESCRIPTION

TAG
3310-PI-1799
3310-PI-1829
3310-PI-1874
3310-PI-1875
3310-PI-1878
3310-PI-1883
3310-PI-1884
3310-PI-1890
3310-PI-1891
3310-PI-1892
3310-PI-1893
3310-PI-1894
3330-PI-2249
3330-PI-2304
3330-PI-2310
3330-PI-2322
3330-PI-2083
3330-PI-2085
3330-PI-2086
3330-PI-2323
3330-PI-2324
3330-PI-2321
3330-PI-2325
3330-PI-2087
3330-PI-2088
3330-PI-2089
3330-PI-2164
3330-PI-2213
3330-PI-2214
3330-PI-2215
3330-PI-2216
3330-PI-2217

DATE

SERVICIO
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire
Presion Aire

BY

APP

REMARKS

Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin
Flotacin

3312-CFL-001
3312-CFL-002
3312-CFL-003
3312-CFL-004
3312-CFL-005
3312-CFL-006
3312-CFL-007
3312-CFL-008
3312-CFL-009
3312-CFL-010
3312-CFL-011
3312-CFL-012
3332-CFL-015
3332-CFL-016
3332-CFL-017
3332-CFL-018
3332-CFL-001
3332-CFL-002
3332-CFL-003
3332-CFL-019
3332-CFL-020
3332-CFL-021
3332-CFL-022
3332-CFL-005
3332-CFL-006
3332-CFL-007
3332-CFL-009
3332-CFL-010
3332-CFL-011
3332-CFL-012
3332-CFL-013
3332-CFL-014

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1799
Service
Presion Aire Flotacin 3312-CFL-001
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1829
Service
Presion Aire Flotacin 3312-CFL-002
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1874
Service
Presion Aire Flotacin 3312-CFL-003
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1875
Service
Presion Aire Flotacin 3312-CFL-004
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1878
Service
Presion Aire Flotacin 3312-CFL-005
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1883
Service
Presion Aire Flotacin 3312-CFL-006
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1884
Service
Presion Aire Flotacin 3312-CFL-007
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1890
Service
Presion Aire Flotacin 3312-CFL-008
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1891
Service
Presion Aire Flotacin 3312-CFL-009
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1892
Service
Presion Aire Flotacin 3312-CFL-010
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1893
Service
Presion Aire Flotacin 3312-CFL-011
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3312/ FLOTACION PRIMARIA
TAG
3310-PI-1894
Service
Presion Aire Flotacin 3312-CFL-012
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2249
Service
Presion Aire Flotacin 3332-CFL-015
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2304
Service
Presion Aire Flotacin 3332-CFL-016
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2310
Service
Presion Aire Flotacin 3332-CFL-017
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2322
Service
Presion Aire Flotacin 3332-CFL-018
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2083
Service
Presion Aire Flotacin 3332-CFL-001
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0021

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2085
Service
Presion Aire Flotacin 3332-CFL-002
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0021

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2086
Service
Presion Aire Flotacin 3332-CFL-003
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2323
Service
Presion Aire Flotacin 3332-CFL-019
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2324
Service
Presion Aire Flotacin 3332-CFL-020
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2321
Service
Presion Aire Flotacin 3332-CFL-021
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2325
Service
Presion Aire Flotacin 3332-CFL-022
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2087
Service
Presion Aire Flotacin 3332-CFL-005
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0021

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2088
Service
Presion Aire Flotacin 3332-CFL-006
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0021

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2089
Service
Presion Aire Flotacin 3332-CFL-007
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0022

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2164
Service
Presion Aire Flotacin 3332-CFL-009
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2213
Service
Presion Aire Flotacin 3332-CFL-010
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2214
Service
Presion Aire Flotacin 3332-CFL-011
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2215
Service
Presion Aire Flotacin 3332-CFL-012
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2216
Service
Presion Aire Flotacin 3332-CFL-013
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

1 GENERAL

6 GENERAL

2
3
4
5
11

Project Name
PROYECTO EXPLOTACION MINA MINISTRO HALES
Area Name
3332/ AREA FLOTACION
TAG
3330-PI-2217
Service
Presion Aire Flotacin 3332-CFL-014
PROCESS CONNECTION AND CASE

7
8
9
10
60

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Case type
Case style
Gauge size
Process conn nominal size
Process conn location
Case pressure relief type
Ring style
Mounting type
Case material
Ring material
Exterior treatment-color
Window material
Stem material
Seal/O ring material
Liquid fill material

61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77

29
30
31
32
33
34
35
36
37
38
39

Elastic element type


Movement style
Nominal accuracy grade
Joint type
Element material
Movement material

ANGULAR
0,5 %
VTS
VTS
TEFLON COATED STAINLESS STEEL

DIAL AND POINTER


Dial scale type
Pointer adjustment

ANGULAR
REQUIRED

40
41
42
43
44
45

Graduations and color


Scale range type
Dial material

kPa AND PSI / BLACK /WHITE BACKGROUND


LINEAR
ALUMINIUM

HIGH SIDE SEAL


Seal type

THREADED

46
47
48
49
50
51
52

Process conn nominal size


Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material

1/2
INCH
THREADED
N/R
N/R
1/2
INCH
N/R
SS304

53
54
55
56
57
58
59
110
111

Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
SS316
VTS
VTS
SS304
SILICONE OIL

CIRCULAR
NEMA 4X
4 INCH
1/2
INCH
FIELD
VTS
VTS
VTS
SS316 / PHENOLIC
SS316
VTS
ACRILIC
VTS
VTS
VTS

Style

THREADED / NPT

PRESSURE ELEMENT AND MOVEMENT

ANSI 150
NPTM

Lenght

FIELD
NON HAZARDOUS
DQ-110071-C-5059-0020

Seal type
Process conn nominal size
Process conn termn type
Diaphragm extension lg
Flushing conn quantity
Instrument conn nom size
Capillary/Fitting dia
Diaphragm material
Capillary-armor matl
Bolting material
Upper housing material
Lower housing/Flange matl
Gasket/O ring material
Fill fluid material

N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R
N/R

PERFORMANCE CHARACTERISTICS
Max press at design temp

INCH

Rating
Style

INCH
Lenght

100 kPa

At

80 C

-15 C
0,5 % FSD
0 kPa

Max

50 C

URL
At

65 kPa

Max

35 C

78
79
80
81
82
83
84
85
86
87
88

Min working temperature


Accuracy rating
Diff pressure LRL
Fill fluid sp gr
Ambient temperature error
Min ambient working temp

89
90
91
92
93
94

Pressure limit valve matl


Restrictor style
Pressure snubber matl
Pulsation dampener matl
Scale overlays
SPECIAL REQUIREMENTS

N/R
N/R
N/R
N/R
N/R

95
96
97
98
99
100
101

Custom tag
Reference specification
Compilance standard
Calibration report
Software configuration

REQUIRED AS INDICATED ON ITEM 4


H336073-0000-75-122/123-0001
ASME
REQUIRED
NOT REQUIRED

102
103
104
105
106
107
108

Estimated weigth
Face-to-face dimension
Overall height
Removal clearance
Mfr reference dwg

VTS
VTS
-15 C

ACCESSORIES

PHYSICAL DATA
VTS
VTS
VTS
VTS
VTS

MEAS/SIGNAL/TEST

INPUT OR TEST
LVR
URV

112
113
114
115
116
117
118 COMPONENTS AND IDENTIFICATIONS
119 COMPONENT TYPE

Pressure / scale

0 kPa

MANUFACTURER

MODEL NUMBER

120 PRESSURE GAUGE


121
122
123
124 NOTES

WIKA

VTS

125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
REV

CALIBRATION AND TEST


TAG NO/FUNCTIONAL IDENT

Rating
Style

Location
Area Class
P&ID
LOW SIDE SEAL

OUTPUT OR SCALE
LRV
URV

100 kPa

VTS = VENDOR TO SPECIFY


N/R = NOT REQUIRED
ALL PARTS MUST SATISFY TECHNICAL SPECIFICATION AS INDICATED ON ITEM 96

REV DESCRIPTION

DATE

BY

APP

REMARKS

PROJECT NUMBER
DE110071

PARA CERTIFICACION

10.08.11

ATR

GHP

DOCUMENT NUMBER

C
B
A

PARA INFORMACION CLIENTE


PARA COMPRA
PARA COORDINACIN

25.07.11
16.06.11
08.06.11

ATR
ATR
ATR

GHP
GHP
GHP

C5059-0014

INSTRUMENT DATA SHEET


MANOMETRO
Device Specification

ACTION

CORPORACION NACIONAL DEL COBRE


CODELCO CHILE
VICEPRESIDENCIA DE PROYECTOS
PROYECTO EXPLOTACION MINA MINISTRO HALES

CELDAS DE FLOTACIN
Project No DQ110071

HOJA DE DATOS DE INSTRUMENTOS


EQUIPO BLOWER

Documento N DQ-110071-C5059-025
O/C N H336073-PM014/0

REV

DESCRIPCIN

PREPAR

REVIS

APROB

FECHA

EMITIDO COMO PLANO CERTIFICADO

ATR

ATR

GHP

14-11-2011

EMITIDO PARA INFORMACION CLIENTE

ATR

ATR

GHP

10-10-2011

EMITIDO PARA COORDINACION INTERNA

ATR

ATR

GHP

20-09-2011

ACCESSORIES
TECHNICAL
DATA SHEET
BLOWER BEARING
VIBRATION SENSOR
VIB 30/10
4-20 mA Velocity Transducer
for PLC interface

ACCESSORIES
TECHNICAL
DATA SHEET
BEARING
TEMPERATURE
SENSOR , PT 100


Parameter Setting
10399720-2650534

53208013

t-mass 65 F

Purchase order number

Transmitter/Sensor

833211-30 / Endress+Hauser Flowtec AG

DN100 / 4"

Order N/Manufacturer

Nominal diameter

65F1H-AK2AG1AABABK

Order code

Tag N

EA0AF802000
Serial N

The below parameters are set according to your order.


Please refer to the Operating Manual for any parameters not mentioned.

Device software
Communication type
ITK version
Device revision

V3.00.01
FOUNDATION Fieldbus
5.0.1
Dev.01/DD.01 [ID 1065 (hex)]

Operation
Language

English

Gas mixture
Gas type 1
% fraction 1

Air
100 %

Process parameters
Process pressure
Reference temperature
Reference pressure

1.0132 bar a
0 C
1.013 bar a

Units
Unit mass flow
Unit corrected volume flow
Unit temperature

kg/hr
Nm/hr
C

User interface
Assign line 1
Assign line 2

Mass flow
Totalizer 1

21.10.2011
Date
Endress+Hauser Flowtec AG
Kgenstrasse 7 / Rue de l'Europe 35
CH-4153 Reinach / F-68700 Cernay
Page 1 / 2


Parameter Setting
10399720-2650534

Totalizer 1
Assign totalizer 1

Mass flow

Totalizer 2
Assign totalizer 2

Mass flow

21.10.2011
Date
Endress+Hauser Flowtec AG
Kgenstrasse 7 / Rue de l'Europe 35
CH-4153 Reinach / F-68700 Cernay
Page 2 / 2


Flow Calibration with Adjustment
15023808-2650534

53208013

FCP-16 (Air)

Purchase order number

Calibration rig

833211-30 / Endress+Hauser Flowtec AG

3750.0 kg/hr

Order N/Manufacturer

Calibrated full scale

65F1H-AK2AG1AABABK

Calibration Interface

Order code

Calibrated output

t-mass 65 F DN100 / 4" (98 mm)

0.968 bar a

Transmitter/Sensor

Ambient pressure

EA0AF802000

28.8 %

Serial N

Ambient relative humidity

24.1 C

Tag N

Ambient temperature

Flow

Flow

target
[kg/hr]

[%]

Flow

meas.
[kg/hr]

Pressure Temp.**
[bar a]

[C]

100%)

Measured error % o.r.

o.r.*
[%]

Tolerance limit: 1.5% o.r.


7.5

9.8
32.0
91.5
-

368.462
1201.54
3430.62
-

369.486
1203.35
3423.42
-

0.966
0.951
0.815
-

24.0
23.7
19.8
-

0.28
0.15
-0.21
-

5
2.5
0
-2.5
-5
-7.5
0

*o.r.: of rate
**Calculated value

10

20

30

40

50

60

70

80

90

100 [%]
Flow

For detailed data concerning output specifications of the unit under test, see Technical Information (TI), chapter Performance characteristics.
Traceability to the national standard for all test instruments used for the calibration is guaranteed.
Endress+Hauser Flowtec operates ISO/IEC 17025 accredited calibration facilities in Reinach (CH), Cernay (FR), Greenwood (USA),
Aurangabad (IN) and Suzhou (CN).

&

25.10.2011

A. Wicky

Date of calibration

Operator

Endress+Hauser Flowtec AG
Kgenstrasse 7 / Rue de l'Europe 35
CH-4153 Reinach / F-68700 Cernay

Certified acc. to
ISO 9001

Page 1 / 1

Operating Instructions

Proline t-mass 65
FOUNDATION Fieldbus
Thermal Mass Flow Measuring System

BA00134D/06/EN/13.10
71128089
Valid as of version
V 3.00.XX (Device software)

Proline t-mass 65 FOUNDATION Fieldbus

Table of contents

Table of contents
1

Safety instructions . . . . . . . . . . . . . . . . 5

1.1
1.2
1.3
1.4
1.5

Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation, commissioning and operation . . . . . . . .
Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . .
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on safety conventions and icons . . . . . . . . . . .

Identification . . . . . . . . . . . . . . . . . . . . 7

2.1

2.2
2.3
2.4

Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1.1 Nameplate of the transmitter . . . . . . . . . . . . 7
2.1.2 Nameplate of the sensor . . . . . . . . . . . . . . . 8
2.1.3 Nameplate for connections . . . . . . . . . . . . . 9
Certificates and approvals . . . . . . . . . . . . . . . . . . . 10
FOUNDATION Fieldbus device certification . . . . . 10
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 10

Installation . . . . . . . . . . . . . . . . . . . . . 11

3.1

3.4

Incoming acceptance, transport and storage . . . . . .


3.1.1 Incoming acceptance . . . . . . . . . . . . . . . . .
3.1.2 Transport . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation conditions . . . . . . . . . . . . . . . . . . . . . .
3.2.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . .
3.2.2 System pressure and pulsating flow . . . . . .
3.2.3 Pipework requirements . . . . . . . . . . . . . . .
3.2.4 Orientation . . . . . . . . . . . . . . . . . . . . . . . .
3.2.5 Inlet and outlet runs . . . . . . . . . . . . . . . . .
3.2.6 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.7 Thermal insulation . . . . . . . . . . . . . . . . . .
3.2.8 Vibrations . . . . . . . . . . . . . . . . . . . . . . . . .
Installation instructions . . . . . . . . . . . . . . . . . . . . .
3.3.1 Mounting the insertion sensor . . . . . . . . . .
3.3.2 Removing the insertion sensor . . . . . . . . . .
3.3.3 Mounting the flanged sensor . . . . . . . . . . .
3.3.4 Turning the transmitter housing . . . . . . . .
3.3.5 Turning the local display . . . . . . . . . . . . . .
3.3.6 Installing the wall-mount
transmitter housing . . . . . . . . . . . . . . . . . .
Post-installation check . . . . . . . . . . . . . . . . . . . . . .

Wiring . . . . . . . . . . . . . . . . . . . . . . . . 27

4.1

FOUNDATION Fieldbus cable specification . . . . . .


4.1.1 Cable type . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Maximum overall cable length . . . . . . . . . .
4.1.3 Maximum spur length . . . . . . . . . . . . . . . .
4.1.4 Number of field devices . . . . . . . . . . . . . . .
4.1.5 Shielding and grounding . . . . . . . . . . . .
4.1.6 Bus termination . . . . . . . . . . . . . . . . . . . . .
4.1.7 Further information . . . . . . . . . . . . . . . . . .
Connecting the remote version . . . . . . . . . . . . . . .
4.2.1 Connecting connecting cable for sensor/
transmitter . . . . . . . . . . . . . . . . . . . . . . . .
4.2.2 Cable specification, connecting cable . . . . .
Connecting the measuring unit . . . . . . . . . . . . . . .

3.2

3.3

4.2

4.3

Endress+Hauser

5
5
6
6
6

11
11
11
11
12
12
12
13
14
15
18
18
18
19
19
22
22
23
23
24
26

27
27
28
28
28
28
29
29
30
30
30
31

4.4
4.5

4.3.1 Transmitter connection . . . . . . . . . . . . . . .


4.3.2 Terminal assignment . . . . . . . . . . . . . . . . .
Degree of protection . . . . . . . . . . . . . . . . . . . . . . .
Post-connection check . . . . . . . . . . . . . . . . . . . . . .

Operation . . . . . . . . . . . . . . . . . . . . . . 36

5.1
5.2
5.3

Quick operation guide . . . . . . . . . . . . . . . . . . . . . .


Display and operating elements . . . . . . . . . . . . . . .
Brief operating instructions to the function matrix .
5.3.1 General notes . . . . . . . . . . . . . . . . . . . . . .
5.3.2 Enabling the programming mode . . . . . . . .
5.3.3 Disabling the programming mode . . . . . . . .
Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1 Type of error . . . . . . . . . . . . . . . . . . . . . . .
5.4.2 Error message type . . . . . . . . . . . . . . . . . . .
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.1 FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.2 Operating via FOUNDATION Fieldbus
configuration programs . . . . . . . . . . . . . . .
5.5.3 Current device description files . . . . . . . . .
FOUNDATION Fieldbus hardware settings . . . . . .
5.6.1 Switching hardware write protection
on and off . . . . . . . . . . . . . . . . . . . . . . . . .

5.4

5.5

5.6

31
34
34
35

36
37
38
39
39
39
40
40
40
41
41
41
42
43
43

Commissioning . . . . . . . . . . . . . . . . . . 44

6.1
6.2
6.3

Function check . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching on the measuring device . . . . . . . . . . . .
Commissioning with FOUNDATION Fieldbus . . . .
6.3.1 Commissioning . . . . . . . . . . . . . . . . . . . . .
6.3.2 Gas compensation input . . . . . . . . . . . . . . .
Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4.1 Quick Setup "Commissioning" . . . . . . . . . .
6.4.2 Quick Setup "Sensor" . . . . . . . . . . . . . . . . .
6.4.3 "Gas" Quick Setup menu . . . . . . . . . . . . . .
6.4.4 "Pressure" Quick Setup menu . . . . . . . . . . .
6.4.5 "Heat Flow" Quick Setup menu . . . . . . . . .
6.4.6 Data backup/transmission . . . . . . . . . . . . .
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5.1 Zero point adjustment . . . . . . . . . . . . . . . .
Data storage device (HistoROM) . . . . . . . . . . . . . .
6.6.1 HistoROM/S-DAT (sensor-DAT) . . . . . . . .
6.6.2 HistoROM/T-DAT (transmitter-DAT) . . . .

6.4

6.5
6.6

44
44
45
45
50
52
52
54
55
57
58
60
61
61
62
62
62

Maintenance . . . . . . . . . . . . . . . . . . . . 63

7.1
7.2
7.3
7.4
7.5
7.6

External cleaning . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer cleaning . . . . . . . . . . . . . . . . . . . . . . . .
Replacing seals . . . . . . . . . . . . . . . . . . . . . . . . . . . .
In-situ calibration . . . . . . . . . . . . . . . . . . . . . . . . . .
Recalibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accessories . . . . . . . . . . . . . . . . . . . . . 65

8.1
8.2

Device-specific accessories . . . . . . . . . . . . . . . . . . . 65
Measuring principle-specific accessories . . . . . . . . . 65

63
63
63
64
64
64

Proline t-mass 65 FOUNDATION Fieldbus

Table of contents

8.3

Service-specific accessories . . . . . . . . . . . . . . . . . . 66

Trouble-shooting . . . . . . . . . . . . . . . . . 67

9.1
9.2

9.5
9.6
9.7

Troubleshooting instructions . . . . . . . . . . . . . . . . .
System/process error messages . . . . . . . . . . . . . .
9.2.1 List of system error messages . . . . . . . . . .
9.2.2 List of process error messages . . . . . . . . . . .
Process errors without messages . . . . . . . . . . . . . .
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.4.1 Removing and installing printed
circuit boards . . . . . . . . . . . . . . . . . . . . . . .
9.4.2 Replacing the device fuse . . . . . . . . . . . . . .
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software history . . . . . . . . . . . . . . . . . . . . . . . . . .

10

Technical data . . . . . . . . . . . . . . . . . . . 87

10.1

Technical data at a glance . . . . . . . . . . . . . . . . . . .


10.1.1 Applications . . . . . . . . . . . . . . . . . . . . . . . .
10.1.2 Function and system design . . . . . . . . . . . .
10.1.3 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1.4 Output . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1.5 Power supply . . . . . . . . . . . . . . . . . . . . . . .
10.1.6 Performance characteristics . . . . . . . . . . . .
10.1.7 Operating conditions: Installation . . . . . . . .
10.1.8 Operating conditions: Environment . . . . . .
10.1.9 Operating conditions: Process . . . . . . . . . .
10.1.10 Mechanical construction . . . . . . . . . . . . . .
10.1.11 Human interface . . . . . . . . . . . . . . . . . . . .
10.1.12 Certificates and approvals . . . . . . . . . . . . .
10.1.13 Ordering information . . . . . . . . . . . . . . . .
10.1.14 Accessories . . . . . . . . . . . . . . . . . . . . . . . .
10.1.15 Documentation . . . . . . . . . . . . . . . . . . . .

9.3
9.4

67
71
72
77
77
79
80
85
86
86
86

87
87
87
87
88
90
90
91
91
92
93
95
95
97
97
97

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Safety instructions

Safety instructions

1.1

Designated use

The measuring device described in these Operating Instructions is to be used only for measuring the
mass flow rate of gases (e. g. kg, Nm3 scf). At the same time, the system also measures gas
temperature. The measuring device can be configured to measure a standard range of pure gases or
gas mixtures.
Examples:
Air
Oxygen
Nitrogen
Carbon Dioxide
Argon, etc.
The use with corrosive, saturated or unclean gases should be treated with caution (contact your
Endress+Hauser sales representative). The use with unstable gases or gases not deemed to be
suitable by Endress+Hauser must be avoided. The measuring device is not designed to be used with
liquids or fluids in the liquid phase.
Resulting from incorrect use or from use other than that designated, the operational safety of the
measuring devices can be jeopardized. The manufacturer accepts no liability for damages being
produced from this.

1.2

Installation, commissioning and operation

Note the following points:


Installation, connection to the electricity supply, commissioning and maintenance of the device
must be carried out by trained, qualified specialists authorised to perform such work by the
facility's owner operator.
The specialist must have read and understood these Operating Instructions and must follow the
instructions they contain.
The device must be operated by persons authorised and trained by the facility's owner-operator.
Strict compliance with the instructions in the Operating Instruction is mandatory.
Endress+Hauser is willing to assist in clarifying the chemical resistance properties of parts wetted
by special fluids, including fluids used for cleaning. However small changes in temperature,
concentration or the degree of contamination in the process can result in changes of the chemical
resistance properties. Therefore, Endress+Hauser can not guarantee or accept liability for the
chemical resistance properties of the fluid wetted materials in a specific application. The user is
responsible for the choice of fluid wetted materials in regards to their in-process resistance to
corrosion.
If carrying out welding work on the piping, the welding unit should not be grounded by means
of the measuring device.
The installer must ensure that the measuring system is correctly wired in accordance with the
wiring diagrams. The transmitter must be earthed unless special protection measures have been
taken e.g. galvanically isolated power supply SELV or PELV! (SELV = Safe Extra Low Voltage;
PELV = Protective Extra Low Voltage)
Invariably, local regulations governing the opening and repair of electrical devices apply.

Endress+Hauser

Safety instructions

Proline t-mass 65 FOUNDATION Fieldbus

1.3

Operational safety

Note the following points:


Measuring systems for use in hazardous environments are accompanied by separate "Ex
documentation", which is an integral part of these Operating Instructions. Strict compliance with
the installation instructions and ratings as stated in this supplementary documentation is
mandatory. The symbol on the front of this supplementary Ex documentation indicates the
approval and the certification body (e.g. 0 Europe, 2 USA, 1 Canada).
When hot fluid passes through the measuring tube, the surface temperature of the housing
increases. In the case of the sensor, in particular, users should expect temperatures that can be
close to the fluid temperature. If the temperature of the fluid is high, implement sufficient
measures to prevent burning or scalding.
The measuring device complies with the general safety requirements in accordance with
EN 61010-1, the EMC requirements of IEC/EN 61326, and NAMUR recommendation NE 21,
NE 43 and NE 53.
The separate document on the Pressure Equipment Directive must be observed for devices used
in Category II or III installations in accordance with the Pressure Equipment Directive.
The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser distributor will supply you with current information and updates to these
Operating Instructions.

1.4

Return

Do not return a measuring device if you are not absolutely certain that all traces of hazardous
substances have been removed, e.g. substances which have penetrated crevices or diffused
through plastic.
Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be
charged to the owner-operator.
Please note the measures on 86

1.5

Notes on safety conventions and icons

The devices are designed to meet state-of-the-art safety requirements, have been tested, and left the
factory in a condition in which they are safe to operate. The devices comply with the applicable
standards and regulations in accordance with EN 61010-1 "Protection Measures for Electrical
Equipment for Measurement, Control, Regulation and Laboratory Procedures". They can, however,
be a source of danger if used incorrectly or for other than the designated use.
Consequently, always pay particular attention to the safety instructions indicated in these Operating
Instructions by the following icons:

#
"
!

Warning!
"Warning" indicates an action or procedure which, if not performed correctly, can result in injury
or a safety hazard. Comply strictly with the instructions and proceed with care.
Caution!
"Caution" indicates an action or procedure which, if not performed correctly, can result in incorrect
operation or destruction of the device. Comply strictly with the instructions.
Note!
"Note" indicates an action or procedure which, if not performed correctly, can have an indirect
effect on operation or trigger an unexpected response on the part of the device.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Identification

Identification

2.1

Device designation

The "t-mass 65" flow measuring system consists of the following components:
t-mass 65 transmitter
t-mass F, t-mass I sensors
Two versions are available:
Compact version: transmitter and sensor form a single mechanical unit.
Remote version: transmitter and sensor are installed separately

2.1.1

Nameplate of the transmitter

7 8

Proline t-mass 65
1

Order Code: 65F25-XXXXXXXXXXXX


Ser.No.:
12345678901
TAG No.: ABCDEFGHJKLMNPQRST

20-55VAC/16-62VDC
50-60Hz

FOUNDATION Fieldbus
DEVICE ID 452B481042-21000191000

IP67/NEMA/Type4X

14VA/8W

4
5

20C (4F) < Tamb < +60C (+140F)


R

N12895

FOUNDATION

6
A0011350

Fig. 1:
1
2
3
4
5
6
7
8

Endress+Hauser

Nameplate specifications for the "t-mass 65" transmitter (example)


Order code, serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits
Power supply, frequency, power consumption
Available inputs/outputs:
Reserved for information on special products
Please refer to operating instructions / documentation
Reserved for certificates, approvals and for additional information on device version
Ambient temperature range
Degree of protection

Identification

Proline t-mass 65 FOUNDATION Fieldbus

2.1.2

Nameplate of the sensor

Proline t-mass F
1
2
3
4
5
6
7
8

Order Code: 65F50-XXXXXXXXXXXX


Ser.No.:
12345678901
TAG-No.:
ABCDEFGHIJKLMNOPQRST

IP67 / NEMA/Type 4X

10

DN50 DIN/EN PN40


P:
T:
Materials:
Seal:

-0.5...40bar / -7.25...+580 psi gauge


-40C...+100C / -40F...+212F
316/316L/1.4404/Alloy C-22 (2.4602)
EPDM / PEEK

3.1
i

-20C(-4F) <Tamb< +60C(+140F)

N12895

11
a0005512

Fig. 2:
1
2
3
4
5
6
7
8
9
10
11

Nameplate specifications for the "t-mass F" sensor (example)


Order code, serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits
Nominal diameter device
Pressure range
Temperature range
Material of measuring tubes
Seal material
Reserved for information on special products
Please refer to operating instructions / documentation
Ambient temperature range
Degree of protection
Reserved for additional information on device version (approvals, certificates)

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Nameplate for connections

Supply /
Versorgung /
Tension d'alimentation

12345678912

26 = FF +
27 = FF

L1 / L+
N / LPE

FOUNDATION Fieldbus

2
3

26(+) / 27(-)

Ser.No.:

active
passive
normally open contact
normally closed contact

24(+) / 25(-)

A:
P:
NO:
NC:

22(+) / 23(-)

See operating manual


Betriebsanleitung beachten
Observer manuel d'instruction

20(+) / 21(-)

2.1.3

Identification

6
7
8
9

Exworks / ab Werk / rglages usine


Device SW: XX.XX.XX
Communication: XXXXXXXXXX
Drivers: ID XXXX (HEX)
Date: DD. MMM. YYYY

Update 1

Update 2

319475-00XX

10
a0002083

Fig. 3:
1
2
3
4

5
6
7
8
9
10

Endress+Hauser

Nameplate specifications for Proline transmitter (example)


Serial number
Possible configuration of current output
Possible configuration of relay contacts
Terminal assignment, cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L for DC
Signals present at inputs and outputs, possible configuration and terminal assignment (20 to 27),
see also "Electrical values of inputs/outputs", 87
Version of device software currently installed
Installed communication type
Information on current communication software
Date of installation
Current updates to data specified in points 6 to 9

Identification

Proline t-mass 65 FOUNDATION Fieldbus

2.2

Certificates and approvals

The devices are designed in accordance with good engineering practice to meet state-of-the-art
safety requirements, have been tested, and left the factory in a condition in which they are safe to
operate. The devices comply with the applicable standards and regulations in accordance with
EN 61010-1 "Protection Measures for Electrical Equipment for Measurement, Control, Regulation
and Laboratory Procedures" and with the EMC requirements of IEC/EN 61326.
The measuring system described in these Operating Instructions thus complies with the statutory
requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by
affixing to it the CE mark.
The measuring system meets the EMC requirements of the Australian Communications and Media
Authority (ACMA).

2.3

FOUNDATION Fieldbus device certification

The flowmeter has passed all the test procedures implemented and has been certified and registered
by the Fieldbus FOUNDATION. The flowmeter thus meets all the requirements of the specifications
listed below:
Certified to FOUNDATION fieldbus specification
The flowmeter meets all the specifications of the FOUNDATION Fieldbus-H1.
Interoperability Test Kit (ITK), revision 5.0: The device can also be operated in conjunction with
other-make certified devices.
Physical Layer Conformance Test by Fieldbus Foundation

2.4

Registered trademarks

KALREZ and VITON


Registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA
AMS
Registered trademark of Emmerson Process Management, St. Louis, USA
HART
Registered trademark of HART Communication Foundation, Austin, USA
HistoROM, S-DAT, T-DAT, F-CHIP, FieldCare, Fieldcheck, Applicator, t-mass
Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH

10

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Installation

Installation

3.1

Incoming acceptance, transport and storage

3.1.1

Incoming acceptance

On receipt of the goods, check the following points:


Check the packaging and the contents for damage.
Check the shipment, make sure nothing is missing and that the scope of supply matches your
order.

3.1.2

Transport

The following instructions apply to unpacking and to transporting the device to its final location:
Transport the devices in the containers in which they are delivered.
The covers or caps fitted to the process connections prevent mechanical damage to the
transducers during transportation and storage. Consequently, do not remove these covers or caps
until immediately before installation.
Do not lift measuring devices of nominal diameters > DN 40 (> 1") by the transmitter housing
or the connection housing in the case of the remote version ( 4). Use webbing slings slung
round the two process connections. Do not use chains, as they could damage the housing.

Warning!
Risk of injury if the measuring device slips. The center of gravity of the assembled measuring device
might be higher than the points around which the slings are slung.
At all times, therefore, make sure that the device does not unexpectedly turn around its axis or slip.

a0004294

Fig. 4:

3.1.3

Instructions for transporting sensors with > DN 40 (> 1")

Storage

Note the following points:


Pack the measuring device in such a way as to protect it reliably against impact for storage (and
transportation). The original packaging provides optimum protection.
The permissible storage temperature is 40 to +80 C (40 F to +176 F).
Preferably +20 C (+68 F).
Do not remove the protective covers or caps on the process connections until you are ready to
install the device.
The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
Devices delivered with special sealing or bagging for oxygen service must remain sealed or bagged
until ready for installation.

Endress+Hauser

11

Installation

Proline t-mass 65 FOUNDATION Fieldbus

3.2

Installation conditions

Note the following points:


The thermal dispersion principle is very sensitive to disturbed flow conditions.
Observe the recommended inlet and outlet requirements.
Good engineering practice is necessary for the associated pipe work and installation.
Ensure correct alignment and orientation of the sensor.
Take measures to reduce or avoid condensation (e.g. install a condensation trap, thermal
insulation, etc.).
The maximum permitted ambient temperatures and the medium temperature range ( 92)
must be observed.
Install the transmitter in a shaded location or use a protective sun shield.
For mechanical reasons, and in order to protect the pipe, it is advisable to support heavy sensors.

3.2.1

Dimensions

The dimensions and installation lengths of the sensor and transmitter can be found in the "Technical
Information" for the device in question. This document can be downloaded as a PDF file from
www.endress.com. A list of the "Technical Information" documents available is provided in the
"Documentation" section on 97.

3.2.2

System pressure and pulsating flow

Reciprocating pumps and some compressor systems can create strong changes in process pressure
that can induce spurious internal flow patterns and therefore cause additional measurement error.
These pressure pulses must be reduced by the appropriate measures:
Use of expansion tanks
Use of inlet expanders
Relocate the flowmeter further downstream
In compressed air systems, it is recommended to mount the flowmeter after the filter, dryer and
buffer devices to avoid pulsations and oil/dirt contamination. Do not mount the flowmeter directly
after the compressor outlet.

12

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

3.2.3

Installation

Pipework requirements

Good engineering practice should be followed at all times:


Correct preparation, welding and finishing techniques
Correctly sized gaskets
Correctly aligned flanges and gaskets
Connecting pipe work should match the internal diameter of the flowmeter.
Maximum pipe diameter mismatch should not exceed:
1 mm (0.04 inch) for diameters < DN 200 (8")
3 mm (0.12 inch) for diameters DN 200 (8")
For further information please refer to ISO 14511.

a0005103

Correctly aligned flanges and gaskets

a0005104

Pipe diameter one is not equal pipe


diameter two

"

Endress+Hauser

a0005105

Incorrectly sized gaskets

a0005106

Incorrectly aligned flanges and gaskets

Caution!
New installations should be free of metallic and abrasive particles to prevent damage to the sensing
elements on start-up.

13

Installation

Proline t-mass 65 FOUNDATION Fieldbus

3.2.4

Orientation

Make sure that the direction arrow on the sensor matches the direction of gas flow through the pipe.
Flanged sensor

Insertion sensor

Vertical orientation
compact

remote

compact

remote

m, n

A0013785

Horizontal orientation, transmitter head up


compact/remote

n
A0013786

Horizontal orientation, transmitter head down


compact/remote

o
A0013787

Inclined orientation, transmitter head down


compact/remote

p
A0009897

= Recommended orientation
= Orientation recommended in certain situations
m In the case of saturated or unclean gases, upward flow in a vertical pipe section is preferred to minimize
condensation/contamination.
n Not recommended if the vibrations are too high or if the installation is unstable.
o Only suitable for clean/dry gases. Do not mount the sensor from the bottom, on horizontal pipes, if build-up or
condensate are likely to be present. Mount the sensor in a position as indicated below
p If the gas is very damp or saturated with water (e. g. Bio Gas), mount in inclined orientation (max. 135).

14

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

3.2.5

Installation

Inlet and outlet runs

The thermal dispersion principle is sensitive to disturbed flow conditions.


As a general rule, the thermal flowmeter should always be installed as far away as possible from any
flow disturbances. For further information please refer to ISO 14511.

Note!
Where two or more flow disturbances are located upstream of the meter, the longest indicated
inlet length should prevail. For example if a control valve and a bend are mounted upstream of
the flowmeter, the recommended inlet length should be according to the control valve (50 DN).
For very light gases such as Helium and Hydrogen all upstream distances should be doubled.
The minimum recommendations for inlet and outlet runs (without flow conditioner) are:
Flanged sensor
1

2
15 x DN

3
15 x DN

2 x DN

a0007523

2 x DN

a0007524

5
20 x DN

15 x DN

2 x DN

2 x DN

a0007525

6
35 x DN

a0007526

50 x DN

2 x DN

2 x DN

a0007527

a0007528

1 = Reduction, 2 = Expansion, 3 = 90 elbow or T-piece, 4 = 2 90 elbow, 5 = 2 90 elbow (3-dimensional),


6 = Control valve

Insertion sensor
1

2
20 x DN

3
20 x DN

5 x DN

a0007529

4
5 x DN

a0007532

5 x DN

a0007530

5
25 x DN

20 x DN

5 x DN

a0007531

6
40 x DN

5 x DN

50 x DN

5 x DN

a0007564

a0007534

1 = Reduction, 2 = Expansion, 3 = 90 elbow or T-piece, 4 = 2 90 elbow, 5 = 2 90 elbow (3-dimensional),


6 = Control valve or pressure regulator

Endress+Hauser

Note!
A specially designed perforated plate flow conditioner can be installed if it is not possible to observe
the inlet runs required ( 16).

15

Installation

Proline t-mass 65 FOUNDATION Fieldbus

Outlet runs with pressure measuring points


The pressure measuring point should be installed downstream of the measuring device, so that there
is no potential influence of the pressure transmitter process connection on the flow entering the
measuring point.

PT

2...5 x DN
a0005114

Fig. 5:

Installing a pressure measuring point (PT = pressure transmitter)

Perforated plate flow conditioner


It is recommended to install a perforated plate flow conditioner if the recommended inlet runs are
not available. See accessories 65.

5 DN

2 DN

5 DN

8 DN

5 DN

2
a0005115

Fig. 6:

The figure above illustrates the minimum recommended inlet and outlet runs expressed in multiples of the pipe
diameter using a flow conditioner.

1 = Flow conditioner with the flanged sensor, 2 = Flow conditioner with the insertion sensor

Flow conditioner for use with insertion sensors


The well known "Mitsubishi" design is recommended for this application DN 80 mm (3") to
DN 300 mm (12"). The flow conditioner must be installed at a distance of 8 DN upstream of the
sensor. A further 5 pipe diameters inlet run is required upstream of the actual conditioner itself.

16

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Installation

Flow conditoner for use with flanged sensors


This is a special Endress+Hauser version designed specially for use with the t-mass F sensor (sizes
DN 25 to 100 / 1" to 4"). The mounting hole patterns and sizing are of a multi-variant design which
means that one plate will fit different flange pressure classes e.g. Cl. 150 and Cl. 300.
The flow conditioner and gaskets are fitted between two pipe flange and the flow meter
flange 7 .
Use only bolts which match to tehflange bolt hole and this will ensure that the correct positioning
of the plate can be found. The alignment notch must also be pointing in the same plane as the
transmitter.
Incorrect installation of the flow conditioner will have a small effect on the measurement accuracy.
4

1
a0005116

Fig. 7:

Flow conditioner mounting arrangement (example)

1 = perforated plate flow conditioner, 2 = aeal/gasket, 3 = alignment notch, 4 = alignment in the same plane as the
transmitter

Endress+Hauser

Note!
For optimum performance, it is advised that the t-mass F sensor and flow conditioner are ordered
at the same time such that they are calibrated together. To retrospectively fit a flow conditioner
will have a small effect on the measurement performance.
The use of other types of flow conditioners, other than the Endress+Hauser flow conditioner, with
the t-mass F sensor will have an impact on the measurement performance due to the effects of
flow profile and pressure drop.
Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by the
customer.

17

Installation

Proline t-mass 65 FOUNDATION Fieldbus

3.2.6

Heating

Some applications require suitable measures to avoid heat loss (condensation). Heating can be
electric, e. g. with heated elements, or by means of hot water, steam pipes or insulation.

"

Caution!
Risk of electronics overheating! Consequently, make sure that the adapter between sensor and
transmitter and the connection housing of the remote version always remain free of insulating
material.

3.2.7

Thermal insulation

When the gas is very damp or saturated with water (e. g. bio gas), the piping and flowmeter body
should be insulated to prevent water droplets condensing on the measuring sensor.

a0005122

Fig. 8:
a
b

Maximum thermal insulation for t-mass 65F and 65I


Maximum insulation height for the flanged sensor
Maximum insulation height for the insertion sensor

3.2.8

"

18

Vibrations

Caution!
Excessive vibration can result in mechanical damage to the measuring device and its mounting.
Observe the vibration spezification in the technical data section 91

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Installation

3.3

Installation instructions

3.3.1

Mounting the insertion sensor

The sensor can be mounted into a welding socket or a retractable mounting set. If a retractable
mounting set is being used, then refer to the supplementary documentation delivered with the
mounting set.
Mounting the welding socket
This instruction describes mounting of the Endress+Hauser welding socket. If an existing or
customer-specific mounting set is being used, then go to the next section "Insertion depth
calculation and adjustment".

!
"
#

Note!
Take the orientation and inlet and outlet runs into account before mounting the welding
socket 14 ff.
The welding socket is made of stainless steel 1.4404 (316/316L). Use appropriate welding
technique.
Caution!
When mounting the fitting to a thin wall duct, use a suitable support bracket for the sensor and weld
the welding socket to a base plate to spread the load. Otherwise, the mounting may be unstable and
the duct wall can be damaged.
Warning!
These instructions are only applicable to installation in an un-pressurized line, without gas present
and at safe temperatures.
1.

Drill or cut hole of 31.0 mm 0.5 mm (1.22" 0.019") in the pipe.

2.

Deburr the hole.

3.

Fit the edge of the welding socket into hole, align it vertically and weld it on 9.

90

90

A0010098

Fig. 9:

Positioning the welding socket on the pipe (or duct)

Insertion depth calculation and adjustment


To obtain the best measurement results, it is important that the sensor is inserted at the right
insertion depth in the pipe/duct. A millimeter and inch scale is provided along the entire length of
the sensor tube. This makes it possible to align the sensor at the right depth.
4.

Endress+Hauser

Calculate the insertion depth:


with the help of the Quick Setup "Sensor" 54 or
using the following dimensions and formulae

19

Installation

Proline t-mass 65 FOUNDATION Fieldbus

230
220
210

200
190

230

220

210
8

180

210

190

200
190

180

180

230
220

200

A0005118

Fig. 10:
A
B
C

Dimensions needed to calculate the insertion depth

Pipes: internal diameter


Ducts: internal dimension
Wall thickness
Dimension from pipe/duct to the compression fitting

Note!
For detailed remarks on calculation refer to Technical Information TI00069D.
Calculated insertion depth (SI units)= 0.3 A + B + C + 2 mm
Calculated insertion depth (US units) = 0.3 A + B + C + 0.079 inch
Note down the calculated value.

4
2

230

220
210
8

200
190
180

3
A0010001

Fig. 11:

5.

Aligning the sensor to the calculated insertion depth

Insert the sensor into the socket (1) and tighten the lower nut of compression fitting (2) first
by hand and then tighten it 1 revolutions using a wrench (42 mm).

"

Caution!
NPT thread: use a thread sealing tape or paste
G 1 A thread: the sealing ring supplied must be installed

20

6.

Tighten the upper nut of compression fitting (3) such that the sensor can still be adjusted.

7.

Read off the calculated insertion depth from the scale and adjust the sensor so that the value
aligns with the upper end of the compression fitting (4).

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Installation

Aligning the sensor with the flow direction

903

907
A0005117

Fig. 12:

8.

Aligning the sensor with the flow direction

Check and ensure that the sensor is aligned vertically at a 90 angle on the pipe/duct.
Turn the sensor so that the arrow marking matches the direction of flow.

Note!
To ensure optimum exposure of the measuring transducers to the flowing gas stream, the sensor
must not be rotated more than 7 degrees from this alignment.

A0010114

Fig. 13:

9.

Securing the position of the sensor

Tighten the compression fitting (1) by hand to secure the position of the sensor. Then, using
an open-ended wrench, tighten another 1 revolutions in a clockwise direction.

10. Fix the two securing screws (2) (Allen key 3 mm; 1/8").

Warning!
Observe torque: 4 Nm (2.95 lbf ft)

11. Check that the sensor and transmitter do not turn.


12. Check the measuring point for leaks at the maximum operating pressure.

Endress+Hauser

21

Installation

Proline t-mass 65 FOUNDATION Fieldbus

3.3.2

Removing the insertion sensor

Warning!
Do not remove the measuring device when it is pressurized! Stop the gas flow and unpressurize
the process pipe.
In the case of toxic, explosive or flammable gases, the pipe in which the measuring device is
installed must be purged with an inert gas to remove all traces of the gas used.
Make sure that the process cannot be resumed while removal work is in progress.
Allow the system and device to cool to a safe temperature (i.e. <50 C, <120 F).

3
1
A0011016

Fig. 14:

Removing the insertion sensor

1.

Release the securing screws (1).

2.

Release the upper nut of compression fitting using a wrench, turning in a counterclockwise
direction (2).

"

Caution!
In the case of vertical installation, do not drop the measuring device into the pipe.

3.

Unscrew the lower nut of compression fitting (3) and remove the sensor.

3.3.3

Mounting the flanged sensor

The arrow on the sensor must match with the actual direction of flow through the pipe.

A0013663

Fig. 15:

22

Mounting in direction of flow

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

3.3.4

Installation

Turning the transmitter housing

Turning the aluminium field housing

Warning!
The rotating mechanism for devices for hazardous areas Zone 1 (ATEX/IEC Ex) or Class I Div. 1
(FM/CSA) is different to that described here. The procedure for turning these housings is described
in the Ex-specific documentation 97.
1.

Loosen the two securing screws.

"

Caution!
Special screw! Do not loosen screw completely or replace with another screw.
Use only original parts from Endress+Hauser.
2.

Turn the bayonet catch as far as it will go.

3.

Carefully lift the transmitter housing as far as it will go.

4.

Turn the transmitter housing to the desired position (max. 2 90 in either direction).

5.

Lower the housing into position and re-engage the bayonet catch.

6.

Retighten the two securing screws.

5
1

6
a0004302

Fig. 16:

3.3.5

Turning the transmitter housing (aluminium field housing)

Turning the local display

1.

Unscrew cover of the electronics compartment from the transmitter housing.

2.

Press the side latches on the display module and remove the module from the electronics
compartment cover plate.

3.

Rotate the display to the desired position (4 45 in both directions), and reset it onto the
electronics compartment cover plate.

4.

Screw the cover of the electronics compartment firmly back onto the transmitter housing.

4 x 45

A0003236

Fig. 17:

Endress+Hauser

Turning the local display (field housing)

23

Installation

Proline t-mass 65 FOUNDATION Fieldbus

3.3.6

Installing the wall-mount transmitter housing

There are various ways of installing the wall-mount transmitter housing:


Mounted directly on the wall
Installation in control panel 25 (separate mounting set, accessories 65)
Pipe mounting 25 (separate mounting set, accessories 65)

"

Caution!
Make sure that ambient temperature does not go beyond the permissible range of
20 C to +60 C (4 F to +140 F), optional 40 C to +60 C (40 F to +140 F).
Install the device in a shaded location. Avoid direct sunlight on the display.
Always install the wall-mount housing in such a way that the cable entries are pointing down.
Mounted directly on the wall
1.

Drill the holes as illustrated in the diagram.

2.

Remove the cover of the connection compartment (a).

3.

Push the two securing screws (b) through the appropriate bores (c) in the housing.
Securing screws (M6): max. 6.5 mm (0.25 inch)
Screw head: max. 10.5 mm (0.4 inch)

4.

Secure the transmitter housing to the wall as indicated.

5.

Screw the cover of the connection compartment (a) firmly onto the housing.

35 (1.38)

c
81.5 (3.2)

a
90 (3.54)

192 (7.56)

mm (inch)
a0001130

Fig. 18:

24

Mounted directly on the wall

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Installation

Installation in control panel


1.

Prepare the opening in the panel as illustrated in the diagram.

2.

Slide the housing into the opening in the panel from the front.

3.

Screw the fasteners onto the wall-mount housing.

4.

Screw threaded rods into holders and tighten until


the housing is solidly seated on the panel wall. Afterwards, tighten the locking nuts.
Additional support is not necessary.

210 (8.27)

+0.5 (+0.019)
0.5 (0.019)

245 (9.65)

mm (inch)

+0.5 (+0.019)
0.5 (0.019)

~110 (~4.33)
a0001131

Fig. 19:

Panel installation (wall-mount housing)

Pipe mounting
The assembly should be performed by following the instructions in the diagram.

"

Caution!
If a warm pipe is used for installation, make sure that the housing temperature does not exceed the
max. permitted value of +60 C (+140 F).

2070
( 0.792.75)

~155 (~ 6.1)
mm (inch)
a0001132

Fig. 20:

Endress+Hauser

Pipe mounting (wall-mount housing)

25

Installation

Proline t-mass 65 FOUNDATION Fieldbus

3.4

Post-installation check

Perform the following checks after installing the measuring device in the pipe:

26

Device condition and specifications

Notes

Is the device damaged (visual inspection)?

Does the device correspond to specifications at the measurement point, including


process temperature and pressure, ambient temperature, measuring range, etc.?
Check the name plate.

Installation

Notes

Correct alignment of pipe/gasket/flowmeter body?

13

Professional installation (correct pipe internal diameter, correctly sized gaskets)?

13

Is the position chosen for the sensor correct, in other words suitable for sensor
type, fluid properties and fluid temperature?

14

Is there sufficient upstream and downstream pipe sensor?

15

Correct installation of flow conditioner (if fitted)?

16

Does the arrow on the sensor match the direction of flow through the pipe?

14

Correct sensor depth (insertion sensor only)?

19

Process environment / process conditions

Notes

Is the measuring device protected against moisture and direct sunlight?

Is the measuring device protected against overheating?

18

Is the measuring device protected against excessive vibration?

18, 91

Check gas conditions (e. g. purity, dryness, cleanliness)

Select suitable orientation


14

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

#
!

Wiring

Wiring

Warning!
When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to
these Operating Instructions. Please do not hesitate to contact your Endress+Hauser representative
if you have any questions.
Note!
The device does not have an internal power isolation switch. Therefore provide an isolation switch
or circuit breaker which can be used to disconnect the power supply to the device.

4.1

FOUNDATION Fieldbus cable specification

4.1.1

Cable type

Twin-core cable is recommended for connecting the flowmeter to the FOUNDATION Fieldbus H1.
By analogy with IEC 61158-2 (MBP) protocol four different cable types (A, B, C, D) can be used
with the FOUNDATION Fieldbus Protocol, only two of which (cable types A and B) are shielded.
Cable types A or B are particularly preferable for new installations. Only these types have cable
shielding that guarantees adequate protection from electromagnetic interference and thus the
most reliable data transfer. With cable type B more than one fieldbus (with the same degree of
protection) may be operated in a cable. No other circuits are permissible in the same cable.
Practical experience has shown that cable types C and D should not be used due to the lack of
shielding, since the freedom from interference generally does not meet the requirements
described in the standard.
The electrical data of the fieldbus cable has not been specified but determines important
characteristics of the design of the fieldbus, such as distances bridged, number of participants,
electromagnetic compatibility, etc.
Type A

Type B

Cable structure

twisted pair, shielded

one or more twisted pairs, fully


shielded

Wire size

0.8 mm2 (AWG 18)

0.32 mm2 (AWG 22)

Loop resistance (DC)

44 W/km

112 W/km

Impedance at 31.25 kHz

100 W 20%

100 W 30%

Attenuation at 39 kHz

3 dB/km

5 dB/km

Capacitive asymmetry

2 nF/km

2 nF/km

Envelope delay distortion


(7.9 to 39 kHz)

1.7 ms/km

Shield coverage

90%

Max. cable length (inc. spurs >1 m)

1900 m (6233 ft)

*
1200 m (3937 ft)

* not specified

Suitable fieldbus cables (Type A) from various manufacturers for the non-hazardous area are listed
below:
Siemens: 6XV1 830-5BH10
Belden: 3076F
Kerpen: CeL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL

Endress+Hauser

27

Wiring

Proline t-mass 65 FOUNDATION Fieldbus

4.1.2

Maximum overall cable length

The maximum network expansion depends on the type of ignition protection and the cable
specifications. The overall cable length is made up of the length of the main cable and the length of
all spurs (>1 m/3.28 ft). Note the following points:
The maximum permissible overall cable length depends on the cable type used ( 27).
If repeaters are used the maximum permissible cable length is doubled. A maximum of three
repeaters are permitted between user and master.

4.1.3

Maximum spur length

The line between distribution box and field unit is described as a spur.
In the case of non Ex-rated applications the max. length of a spur depends on the number of spurs
(>1 m/3.28 ft):

Number of spurs

1 to 12

13 to 14

15 to 18

19 to 24

25 to 32

Max. length per spur

120 m (393 ft)

90 m (295 ft)

60 m (196 ft)

30 m (98 ft)

1 m (3.28 ft)

4.1.4

Number of field devices

According to IEC 61158-2 (MBP) a maximum of 32 field devices may be connected per fieldbus
segment. However, this number may be restricted in certain circumstances (type of ignition
protection, bus power option, current consumption of field device).
A maximum of four field devices can be connected to a spur.

4.1.5

Shielding and grounding

The optimum electromagnetic compatibility of the fieldbus system is guaranteed only when system
components and in particular lines are shielded and the shielding provides the most complete
coverage possible. Shield coverage of 90% is ideal.
Shielding should be connected as often as possible with the reference ground. The national
regulations and guidelines governing the installation of electrical equipment also apply where
relevant!
Where there are large differences in potential between the individual grounding points, only one
point of the shielding is connected directly with the reference ground. In systems without potential
equalization, cable shielding of fieldbus systems should therefore only be grounded on one side, for
example at the fieldbus supply unit or at safety barriers.

"

28

Caution!
If the cable shielding is grounded at more than one point in systems without potential equalization,
network frequency equalization currents can occur that damage the bus cable or the bus shielding
and substantially affect signal transmission.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

4.1.6

Wiring

Bus termination

The start and end of each fieldbus segment are always to be terminated with a bus terminator. With
various junction boxes (not Ex-rated) the bus termination can be activated via a switch. If this is not
the case a separate bus terminator must be installed. Note the following points in addition:
In the case of a branched bus segment the device furthest from the segment connector represents
the end of the bus.
If the fieldbus is extended with a repeater then the extension must also be terminated at both
ends.

4.1.7

Further information

General information and further notes on connections can be found on the website
(www.fieldbus.org) of the Fieldbus Foundation or in the Operating Instructions "FOUNDATION
Fieldbus Overview" (acquired at: www.endress.com Download).

Endress+Hauser

29

Wiring

Proline t-mass 65 FOUNDATION Fieldbus

4.2

Connecting the remote version

4.2.1

Connecting connecting cable for sensor/transmitter

Warning!
After removing the electronics cover, there is a risk of electric shock as shock protection is
removed! Switch off the measuring device before removing internal covers.
Risk of electric shock. Connect the protective earth to the ground terminal on the housing before
the power supply is applied.
1.

Remove the connection compartment cover by loosening the fixing screws on the transmitter
and sensor housing.

2.

Feed the connecting cable through the appropriate cable entry.

3.

Establish the connections between sensor and transmitter in accordance with the wiring
diagram: ( 21 or see wiring diagram in screw cap; wire cross-section: max. 2.5 mm /
AWG 13).

4.

Screw the connection compartment cover back onto the sensor and transmitter housing.
A

B
p cover tight w
Kee ircuits are ali hile
ve
c

over tight whi


ep c
Ke ircuits are alive le
c

t unter Spannu
ng
Nich ffnen

vri
pas ou r lappa
Ne sous tension reil

6
GND 10V COMMS
+
+
41 42 43 44

41 42 43 44
+
+
GND 6 COMMS
10V
a0005123

Fig. 21:
A
B
C
D

Connecting the remote version

Wallmount housing; Non-hazardous area and zone 2 (ATEX II3G, FM/CSA) see separate "Ex documentation"
Field housing; Zone 1 (ATEX II2GD, IECEx, FM/CSA) see separate "Ex documentation"
Remote sensor insertion
Remote sensor flanged

Wire colors (when supplied by Endress+Hauser):


Terminal no. 41 = white; 42 = brown; 43 = green; 44 = yellow

4.2.2

Cable specification, connecting cable

The specifications of the cable connecting the transmitter and the sensor of the remote version are
as follows:
2 2 0.5 mm (AWG 20) PVC cable with common shield (2 twisted pairs)
Conductor resistance: 40 /km ( 131.2 /1000 ft)
Operating voltage: 250 V
Temperature range: 40 to +105 C (40 to +221 F)
Overall nominal diameter: 8.5 mm (0.335")
Maximum cable length: 100 m (328 feet)

!
30

Note!
The cable must be installed securely to prevent movement
The cable should be of sufficient diameter to provide adequate sealing of the cable gland 90.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

4.3

Wiring

Connecting the measuring unit

Field instruments can be connected to the FOUNDATION Fieldbus in two ways:


Connection via conventional cable gland 31
Connection using prefabricated fieldbus connector (option) 33

4.3.1

Transmitter connection

Warning!
Risk of electric shock. Switch off the power supply before opening the device. Do not install or
wire the device while it is connected to the power supply. Failure to comply with this precaution
can result in irreparable damage to the electronics.
Risk of electric shock. Connect the protective earth to the ground terminal on the housing before
the power supply is applied unless special protection measures have been taken
(e.g. galvanically isolated power supply SELV or PELV).
Compare the specifications on the nameplate with the local supply voltage and frequency. The
national regulations governing the installation of electrical equipment also apply.
1.

Unscrew the connection compartment cover (f) from the transmitter housing.

2.
3.

Feed the power supply cable (a) and the signal cable (b) through the appropriate cable entries.
Perform wiring:
Wiring diagram (aluminium housing) 22
Wiring diagram (wall-mount housing) 23
Terminal assignment 34

4.

Screw the cover of the connection compartment (f) back onto the transmitter housing.

Connecting the aluminum field housing

27
+ 26
25
+ 24
23
+ 22
21
+ 20

N (L-) 2
L1 (L+) 1

b
d

c
a
a0004582

Fig. 22:
a

b
c
d
e
f
g

Endress+Hauser

Connecting the transmitter (aluminum field housing). Wire cross-section: max. 2.5 mm(AWG 13)

Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC


Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L for DC
Signal cable: Terminals Nos. 20-27 34
Ground terminal for protective earth
Ground terminal for signal cable shield
Service adapter for connecting service interface FXA193 (FieldCheck, FieldCare)
Cover of the connection compartment
Securing clamp

31

Wiring

Proline t-mass 65 FOUNDATION Fieldbus

Connecting the wall-mount housing

N (L-)
L1 (L+)

+ + + +
20 21 22 23 24 25 26 27

1 2

f
a

d
a0001135

Fig. 23:
a

b
c
d
e
f

32

Connecting the transmitter (wall-mount housing); wire cross-section: max. 2.5 mm (AWG 13)

Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC


Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L for DC
Signal cable: Terminals Nos. 20-27 34
Ground terminal for protective earth
Ground terminal for signal cable shield
Service adapter for connecting service interface FXA 193 (FieldCheck, FieldCare)
Cover of the connection compartment

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Wiring

Fieldbus connector
The connection technology of FOUNDATION Fieldbus allows measuring devices to be connected
to the fieldbus via uniform mechanical connections such as T-boxes, junction boxes, etc.
This connection technology using prefabricated distribution modules and plug-in connectors offers
significant advantages over conventional wiring:
Field devices can be removed, replaced or added at any time during normal operation.
Communication is not interrupted.
This simplifies installation and maintenance significantly.
Existing cable infrastructures can be used and expanded instantly, e.g. when constructing new
star distributors using 4-channel or 8-channel junction boxes.
The device can therefore be supplied with a ready-mounted fieldbus connector. Fieldbus connectors
for retrofitting can be ordered from Endress+Hauser as a spare part. 65
A

B
C

Esc

D
C

26.5 mm
(1.040")
2.2

2.3

2.1

2.4

190 mm

7/8-16 UNC

M 20.5

2
a0006390

Fig. 24:

Connector for connecting to the FOUNDATION Fieldbus

A
B
C
D

Wall-mount housing
Field housing
Protective cap for connector
Fieldbus connector

1
2
2.1
2.2
2.3
2.4

Protective cap for connector


Fieldbus connector (pin assignment/color codes)
Brown wire: FF + (terminal 26)
Blue wire: FF (terminal 27)
Not assigned
Green/yellow: ground (notes on connection 28, 29)

Technical data, connector:


Degree of protection IP 67
Ambient temperature range: 40 to +150 C (40 to +302 F)

Endress+Hauser

33

Wiring

Proline t-mass 65 FOUNDATION Fieldbus

4.3.2

Terminal assignment

Note!
The electrical characteristic quantities are listed in the "Technical data" section.
Terminal No. (inputs/outputs)
Order version

20 (+) / 21 ()

22 (+) / 23 ()

24 (+) / 25 ()

26 = FF +
27 = FF

65***-***********G

FOUNDATION
Fieldbus Ex i

65***-***********K

FOUNDATION
Fieldbus

With integrated reverse polarity protection

4.4

Degree of protection

The devices fulfill all the requirements for IP 67 (NEMA 4X).


Compliance with the following points is mandatory following installation in the field or servicing,
in order to ensure that IP 67 (NEMA 4X) protection is maintained:
The housing seals must be clean and undamaged when inserted into their grooves. The seals must
be dried, cleaned or replaced if necessary.
All threaded fasteners and screw covers must be firmly tightened.
The cables used for connection must be of the specified outside diameter (Cable entry 90)
Firmly tighten the cable entries (point a 25).
The cables must loop down before they enter the cable entries ("water trap") (point b 25).
This arrangement prevents moisture penetrating the entry. Always install the measuring device
in such a way that the cable entries do not point up.
Remove all unused cable entries and insert plugs instead.
Do not remove the grommet from the cable entry.

b
a0001914

Fig. 25:

34

Installation instructions, cable entries

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

4.5

Wiring

Post-connection check

Perform the following checks after completing electrical installation of the measuring device:

Endress+Hauser

Device condition and specifications

Notes

Are cables or the device damaged (visual inspection)?

Electrical connection

Notes

Does the supply voltage match the specifications on the nameplate?

85 to 260 V AC (45 to 65 Hz)


20 to 55 V AC (45 to 65 Hz)
16 to 62 V DC

Do the cables comply with the specifications?

27

Do the cables have adequate strain relief?

Is the cable type route completely isolated?


Without loops and crossovers?

Are the power supply and signal cables correctly connected?

See the wiring diagram inside


the cover of the terminal
compartment

Are all screw terminals firmly tightened?

Are all cable entries installed, firmly tightened and correctly sealed?
Cables looped as "water traps"?

34

Are all housing covers installed and firmly tightened?

Electrical connection of FOUNDATION Fieldbus-H1

Notes

Are all the connecting components (T-boxes, junction boxes, connectors, etc.)
connected with each other correctly?

Has each fieldbus segment been terminated at both ends with a bus terminator?

Has the max. length of the fieldbus cable been observed in accordance with the
FOUNDATION Fieldbus specifications?

28

Has the max. length of the spurs been observed in accordance with the
FOUNDATION Fieldbus specifications?

28

Is the fieldbus cable fully shielded (90%) and correctly grounded?

28

35

Operation

Proline t-mass 65 FOUNDATION Fieldbus

Operation

5.1

Quick operation guide

The user has a number of options for configuring and commissioning the device:
1.

Local display (option) 37


The local display enables you to read all important variables directly at the measuring point,
configure device-specific parameters in the field and perform commissioning.

2.

Operating programs 41
FOUNDATION Fieldbus functions and device-specific parameters are configured primarily via
the fieldbus interface. You can obtain special configuration and operating programs from
various manufacturers for these purposes.

3.

Jumpers for diverse hardware settings 43


Jumpers on the I/O board provide the means of setting the following hardware parameters for
the FOUNDATION Fieldbus:
Enabling/disabling the simulation mode in the function blocks (e.g. AI, DO function block)
Switching the hardware write protection on and off

2B

2A

FXA193

Esc

Esc

3
1
XXX.XXX.XX

Esc

a0006391

Fig. 26:
1
2A
2B

36

FOUNDATION Fieldbus operating options

Local display for device operation in the field (option)


Configuration/operating programs for operating via the FOUNDATION Fieldbus (FF functions, device parameters)
Configuration/operating program for operating via the FXA193
service interface
(e.g. ToF Tool - Fieldtool Package)
Jumper/miniature switches for hardware settings (write protection, simulation mode)

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

5.2

Operation

Display and operating elements

The local display enables you to read all important parameters directly at the measuring point and
configure the device using the function matrix.
The display consists of two lines; this is where measured values and/or status variables (process/
system error messages, bar graph, etc.) are displayed. You can change the assignment of display lines
to different variables to suit your needs and preferences ( see the "Description of Device
Functions" manual).

48.25 xx/yy
3702.6 x
Esc

3
a0011430

Fig. 27:
1

Display and operating elements

Liquid crystal display


The backlit, two-line liquid crystal display shows measured values, dialog texts, fault messages and notice messages.
The display as it appears when normal measuring is in progress is known as the HOME position (operating mode).
Upper display line: shows primary measured values, e.g. mass flow in [kg/h] or in [%].
Lower display line: shows additional measured variables and status variables, e.g. totalizer reading in [kg], bar
graph, measuring point designation.
O/S keys
Enter numerical values, select parameters
Select different function groups within the function matrix
Press the X keys simultaneously to trigger the following functions:
Exit the function matrix step by step HOME position
Press and hold down O/S keys ( X) for longer than 3 seconds Return directly to HOME position
Cancel data entry
F Enter key
HOME position Entry into the function matrix
Save the numerical values you input or settings you change

Icons
The icons which appear in the field on the left make it easier to read and recognize measured
variables, device status, and error messages.
Icon

Meaning

Icon

Meaning

System error

Process error

Fault message
(with effect on outputs)

Notice message
(without effect on outputs)

Low flow cut off or extended flow function is active

Endress+Hauser

37

Operation

Proline t-mass 65 FOUNDATION Fieldbus

5.3

Brief operating instructions to the function matrix

Note!
See the general notes 39.
Function descriptions see the "Description of Device Functions" manual
1.

HOME position F Entry into the function matrix

2.

Select a function group (e.g. CURRENT OUTPUT 1)

3.

Select a function (e.g. TIME CONSTANT)


Change parameter / enter numerical values:
OS Select or enter enable code, parameters, numerical values
F Save your entries

4.

Exit the function matrix:


Press and hold down Esc key (X) for longer than 3 seconds HOME position
Repeatedly press Esc key (X) Return step by step to HOME position

Esc

p
m

Esc

>3s

Esc

o
E

Esc

E
E
E
E

a0001142

Fig. 28:

38

Selecting functions and configuring parameters (function matrix)

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

5.3.1

Operation

General notes

The Quick Setup menu contains the default settings that are adequate for commissioning.
Complex measuring operations on the other hand necessitate additional functions that you can
configure as necessary and customise to suit your process parameters. The function matrix,
therefore, comprises a multiplicity of additional functions which, for the sake of clarity, are arranged
in a number of function groups.
Comply with the following instructions when configuring functions:
You select functions as described already. 38
You can switch off certain functions (OFF). If you do so, related functions in other function groups
will no longer be displayed.
Certain functions prompt you to confirm your data entries. Press P to select "SURE ( YES )" and
press F to confirm. This saves your setting or starts a function, as applicable.
Return to the HOME position is automatic if no key is pressed for 5 minutes.
Programming mode is disabled automatically if you do not press a key within 60 seconds
following automatic return to the HOME position.

"
!

Caution!
All functions are described in detail, as is the function matrix itself, in the "Description of Device
Functions" manual, which is a separate part of these Operating Instructions.
Note!
The transmitter continues to measure while data entry is in progress, i.e. the current measured
values are output via the signal outputs in the normal way.
If the power supply fails, all preset and parameterised values remain safely stored in the EEPROM.
However, some functions may be affected (i. e. data/values not saved) if the power supply is
interupted during editing or operation of those functions. More details are contained in the
"Description of Device Functions" manual, BA00135D/06.

5.3.2

Enabling the programming mode

The function matrix can be disabled. Disabling the function matrix rules out the possibility of
inadvertent changes to device functions, numerical values or factory settings. A numerical code
(factory setting = 65) has to be entered before settings can be changed.
If you use a code number of your choice, you exclude the possibility of unauthorised persons
accessing data ( see the "Description of Device Functions" manual).
Comply with the following instructions when entering codes:
If programming is disabled and the P operating elements are pressed in any function, a prompt
for the code automatically appears on the display.
If "0" is entered as the customer's code, programming is always enabled.
Your Endress+Hauser representative can be of assistance if you mislay your personal code.

"

Caution!
Changing certain parameters such as all sensor characteristics, for example, influences numerous
functions of the entire measuring system, particularly measuring accuracy.
There is no need to change these parameters under normal circumstances and consequently, they
are protected by a special code known only to the Endress+Hauser representative. Please contact
Endress+Hauser if you have any questions.

5.3.3

Disabling the programming mode

Programming mode is disabled if you do not press an operating element within 60 seconds following
automatic return to the HOME position.
You can also disable programming in the "ACCESS CODE" function by entering any number (other
than the customer's code).

Endress+Hauser

39

Operation

Proline t-mass 65 FOUNDATION Fieldbus

5.4

Error messages

5.4.1

Type of error

Errors that occur during commissioning or measuring are displayed immediately. If two or more
system or process errors occur, the error with the highest priority is the one shown on the display.
The measuring system distinguishes between two types of error:
System error: This group includes all device errors, e.g. communication errors, hardware errors,
etc. 72
Process error: This group includes all application errors, e.g. flow limit, etc. 77

XXXXXXXXXX
#000 00:00:05

3
a0000991

Fig. 29:
1
2
3
4
5

Error messages on the display (example)

Error type: P = process error, S = system error


Error message type: $ = fault message, ! = notice message, definition
Error designation: e.g. FLOW LIMIT = maximum flow limit exceeded
Error number: e.g. #422
Duration of most recent error occurrence (in hours, minutes and seconds)

5.4.2

Error message type

The measuring device always assigns system and process errors which occur to two types of error
messages (fault or notice messages), resulting in different weightings 71.
Serious system errors, e.g. module defects, are always identified and classed as "fault messages" by
the measuring device.
Notice message (!)
The error in question has no effect on measurement currently in progress.
Displayed as Exclamation mark (!), type of error (S: system error, P: process error)
Presentation on the FOUNDATION Fieldbus Notice messages are transmitted to subsequent
Function Blocks or higher-level process control systems by means of the status "UNCERTAIN" of
the output value OUT (AI Block).
Fault message ( $)
The error in question interrupts or stops measurement currently in progress.
Displayed as Lightning flash ( $ ), type of error (S: system error, P: process error)
Presentation on the FOUNDATION Fieldbus Fault messages are transmitted to subsequent
Function Blocks or higher-level process control systems by means of the status "BAD" of the
output value OUT (AI Block).

40

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Operation

5.5

Communication

5.5.1

FieldCare

FieldCare is Endress+Hausers FDT-based plant Asset Management Tool and allows the
configuration and diagnosis of intelligent field devices. By using status information, you also have a
simple but effective tool for monitoring devices. The Proline flow measuring devices are accessed
via a service interface or via the service interface FXA193.

5.5.2

Operating via FOUNDATION Fieldbus configuration programs

The user can obtain special configuration and operating programs offered by the different
manufacturers for use in configuration. These can be used for configuring both the FOUNDATION
Fieldbus functions and all the device-specific parameters. The predefined Function Blocks allow
uniform access to all the network and fieldbus device data.
A step-by-step description of the procedure for commissioning the FF functions is given on 45,
along with the configuration of device-specific parameters.
General information on FOUNDATION Fieldbus is provided in the Operating Instructions
"FOUNDATION Fieldbus Overview" (BA013S) acquired at: www.endress.com Download.
System files
You will need the following files for commissioning and network configuration:
Commissioning Device description (Device Description: *.sym, *.ffo)
Network configuration CFF file (Common File Format: *.cff)
You can obtain these files as follows:
Free of charge via the Internet www.endress.com
From Endress+Hauser stating the order number (No. 56003896)
Via the Fieldbus Foundation Organization www.fieldbus.org

Note!
Ensure you use the correct system files for linking the field devices into the host system. Appropriate
version information can be called up via the following functions/parameters:
Local display:
HOME COMMUNICATION FOUND. FIELDBUS DEVICE REVISION
HOME COMMUNICATION FOUND. FIELDBUS DD REVISION
FOUNDATION Fieldbus interface
Resource Block Parameter DEV_REV
Resource Block Parameter DD_REV
Example (with local display):
Display in the DEVICE REVISION function 01
Display in the DD REVISION function 01
Device description file (DD) required 0101.sym / 0101.ffo

Endress+Hauser

41

Operation

Proline t-mass 65 FOUNDATION Fieldbus

5.5.3

Current device description files

The following table illustrates the suitable device description file for the operating tool in question
and then indicates where these can be obtained.
HART protocol:
Valid for software:

3.00.XX

Function "Device software"

Device data FOUNDATION


Manufacturer ID:
Device ID:

17hex (ENDRESS+HAUSER)
1065hex

Function "Manufacturer ID"


Function "Device ID"

FOUNDATION Fieldbus
version data:

Device Revison 6/ DD Revision 1

Software release:

12.2010

Operating program

How to acquire:

Device Description (DD) and


Capability File (CFF)

www.endress.com Download
www.fieldbus.org

Device driver for FF host


systems:

How to acquire:

ABB (FieldController 800)

see FF standard device driver

Allen Bradley (Control Logix)

see FF standard device driver

Emerson (Delta V)

www.easydeltav.com

Endress+Hauser (ControlCare)

see FF standard device driver

Honeywell (Experion PKS)

see FF standard device driver

SMAR (System 302)

see FF standard device driver

Yokogawa
(CENTUM CS 3000)

www.yokogawa.com

Device drivers for additional Sources for obtaining updates:


FF operating programs:
Handheld terminal 375

www.fieldcommunicator.com

Note!
The device drivers can be added and updated via the update function of the handheld
terminal 375.

42

Tester/simulator:

Sources for obtaining device descriptions:

Fieldcheck

Update by means of FieldCare with the Flow Device FXA193/291 DTM in the
Fieldflash Module

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Operation

5.6

FOUNDATION Fieldbus hardware settings

5.6.1

Switching hardware write protection on and off

A jumper on the I/O board provides the means of switching hardware write protection on or off.

Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
1.

Switch off power supply.

2.

Remove the I/O board 80

3.

Configure hardware write protection and simulation mode appropriately using the jumpers
(see graphic).

4.

Installation of the I/O board is the reverse of the removal procedure.

LED

1
1.1
2
1.2
2.1
2.2
A0004731

Fig. 30:
1
1.1
1.2

Jumper for enabling/disabling write protection:


Write protection disabled (factory setting) = it is possible to write-access the device functions via the FF interface
Write protection enabled = it is not possible to write-access the device functions via the FF interface

2
2.1

Jumper for simulation mode:


Simulation mode enabled (factory setting) = simulation in the Analog Input Function Block and in the Discrete
Output Function Block is possible
Simulation mode disabled = simulation in the Analog Input Function Block and in the Discrete Output Function
Block is not possible

2.2
LED

Endress+Hauser

Hardware configuration (I/O board)

(light emitting diode):


Continuously lit Ready (no communication via FF active)
Not lit Not ready
Flashes slowly Ready (communication via FF active)
Flashes quickly Device error present (error message type "fault message") 67

43

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

Commissioning

6.1

Function check

Make sure that all final checks have been completed before you start up your measuring point:
Checklist for "Post-installation check" 26
Checklist for "Post-connection check" 35

6.2

Switching on the measuring device

Once the post-connection checks have been successfully completed, it is time to switch on the
supply voltage. The device is now operational.
The measuring device performs a number of power on self-tests. As this procedure progresses the
following sequence of messages appears on the local display:
t-mass 65
START-UP

Start-up message

t-mass 65
FOUND. FIELDBUS

Show the input/output modules

DEVICE SOFTWARE
V XX.XX.XX

Current software version

SYSTEM OK
OPERATION

Beginning of normal measuring mode

Normal measuring mode commences as soon as start-up completes.


Various measured values and/or status variables appear on the display (HOME position).

44

Note!
If start-up fails, an error message indicating the cause is displayed.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

6.3

Commissioning

Commissioning with FOUNDATION Fieldbus

Note the following points:


The files required for commissioning and network configuration can be obtained as described on
41
The device is identified by the FOUNDATION Fieldbus in the host or configuration system via
the device ID (DEVICE_ID). The DEVICE_ID is a combination of the manufacturer ID, device
type and device serial number. It is unique and can never be duplicated.
The DEVICE_ID is composed as follows:
452B48 1065 - XXXXXXXXXXX
Device serial number(11-digit)
Device type (t-mass 65)
Endress+Hausser

6.3.1

Commissioning

The following description allows step-by-step commissioning of the measuring device and all the
necessary configuration for the FOUNDATION Fieldbus:
1.

Switch on the measuring device.

2.

Note the DEVICE_ID on the device nameplate 7.

3.

Open the configuration program.

4.

Load the device description file or CFF file into the host system or into the configuration
program. Ensure you use the correct system files. Refer to the example on 47.
The first time it is connected the device reports as follows:
EH_TMASS_65_ xxxxxxxxxxx (tag name PD-TAG)
452B481042- xxxxxxxxxxx (Device_ID)
Block structure:

Display text (xxx = serial number)

Endress+Hauser

Base index

Description

RESOURCE_ xxxxxxxxxxx

400

Resource Block

TRANSDUCER_FLOW_xxxxxxxxxxx

1400

"Flow" Transducer Block

TRANSDUCER_DIAG_xxxxxxxxxxx

1600

"Diagnosis" Transducer Block

TRANSDUCER_DISP_xxxxxxxxxxx

1800

"Display" Transducer Block

TRANSDUCER_TOT_xxxxxxxxxxx

1900

"Totalizer" Transducer Block

TRANSDUCER_GAS_xxxxxxxxxxx

2700

"Heat Flow" Transducer Block

ANALOG_INPUT_1_xxxxxxxxxxx

500

Analog Input function block 1

ANALOG_INPUT_2_xxxxxxxxxxx

550

Analog Input function block 2

ANALOG_INPUT_3_xxxxxxxxxxx

600

Analog Input function block 3

ANALOG_INPUT_4_xxxxxxxxxxx

650

Analog Input function block 4

ANALOG_INPUT_5_xxxxxxxxxxx

700

Analog Input function block 5

ANALOG_OUTPUT_xxxxxxxxxxx

2300

Analog Output function block (DO)

DISCRETE_OUTPUT_xxxxxxxxxxx

900

Discrete Output function block (DO)

PID_xxxxxxxxxxx

1000

PID function block (PID)

ARITHMETIC_xxxxxxxxxxx

1100

Arithmetic function block (ARTH)

INPUT_SELECTOR_xxxxxxxxxxx

1150

Input Selector function block (ISEL)

SIGNAL_CHARACT_xxxxxxxxxxx

1200

Signal Characterizer function block (CHAR)

INTEGRATOR_xxxxxxxxxxx

1250

Integrator function block (INTG)

45

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

Note!
The device is supplied with the bus address "250" and is thus in the address range reserved for
readdressing field devices, between 248 and 251. This means that the LAS (Link Active Scheduler)
automatically assigns the device a free bus address in the initialization phase.
5.

Identify the field device using the DEVICE_ID that you noted down and assign the desired field
device tag name (PD_TAG) to the fieldbus device in question.
Factory setting: EH_TMASS_65_xxxxxxxxxxx

Configuration of the "Resource Block" (base index 400)


6.

Open the Resource Block.

7.

On delivery write protection is disabled so that you can access the write parameters via FF.
Check this status via the parameter WRITE_LOCK:
Write protection activated = LOCKED
Write protection deactivated = NOT LOCKED
Deactivate the write protection if necessary 43.

8.

Enter the desired block name (optional).


Factory setting: RESOURCE_ xxxxxxxxxxx

9.

Set the operating mode in the parameter group MODE_BLK (parameter TARGET) to AUTO.

Configuration of the "Transducer Blocks"


The individual Transducer Blocks comprise various parameter groups ordered by device-specific
functions:
Transducer Block

Base index

Description

"Flow" Transducer Block

1400

Flow measurement

"Diagnosis" Transducer Block

1600

Diagnostic functions

"Display" Transducer Block

1800

Local display functions

"Totalizer" Transducer Block

1900

Totalizer 1 to 2

"Heat Flow" Transducer Block

2700

Heat flow measurement

The following description provides an example for the "Flow" Transducer Block (base index: 1400).
10. Enter the desired block name (optional).
Factory setting: TRANSDUCER_FLOW_xxxxxxxxxxx
11. Open the "Flow" Transducer Block.
12. Now configure the device-specific parameters relevant for your application.

Note!
Changes to the device parameters can only be made after entering a valid access code in the
parameter "Access Code".
The selection of the system units in the "Flow" Transducer Block has no effect on the output
value OUT (AI Block). Units of the process variables which are transmitted via the
FF-interface must be specified separately in the Analog Input function block via the
XD_SCALE and OUT_SCALE parameter group.

13. Set the "Flow" and "Totalizer" Transducer Blocks to AUTO in the MODE_BLK parameter
group (TARGET parameter). Only then is it ensured that the process variables can be processed
correctly by the downstream AI function block.

46

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Commissioning

Configuration of the "Analog Input function blocks"


The device has five Analog Input function blocks that can be assigned to the various process
variables. The following description provides an example for the Analog Input function block 1 (base
index: 500).
14. Enter the desired name for the Analog Input function block (optional).
Factory setting: ANALOG_INPUT_1xxxxxxxxxxx
15. Open the Analog Input function block 1.
16. Set the operating mode in the parameter group MODE_BLK (parameter TARGET) to OOS, i.e.
block Out Of Service.
17. Using the parameter CHANNEL select the process variable that is to be used as the input value
for the function block algorithm (scaling and limit value monitoring functions). The following
settings are possible:
Process variable

Channel parameter

Mass flow

Corrected volume flow

Temperature

Totalizer 1

Totalizer 2

Heat flow

53

18. In the parameter group XD_SCALE select the desired engineering unit and the block input
range (e.g. measurement range of the flow application) for the process variable in question (see
the example below).

"

Caution!
Make sure that the selected unit is suitable for the measurement variable of the selected
process variable. Otherwise the parameter BLOCK_ERROR will display the error message
"Block Configuration Error" and the block operating mode cannot be set to AUTO.

19. In the L_TYPE parameter, select the mode of linearization for the input variable (Direct,
Indirect, Indirect Sq Root) "Description of Device Functions" manual

"

Caution!
Note that with the type of linearization "Direct" the configuration of the parameter group
OUT_SCALE must agree with the configuration of the parameter group XD_SCALE.
Otherwise the block operating mode cannot be set to AUTO. Such incorrect configuration is
indicated in the parameter BLOCK_ERROR via the "Block Configuration Error" message.
Example:
The measurement range of the sensor is 0 to 30 m3/h.
The output range to the automation system should be 0 to 30 m3/h also.
The following settings should be made:
Analog Input function block/parameter CHANNEL (selection of input value),
selection: 2 Volume flow
Parameter L_TYPE Direct
Parameter group XD_SCALE
XD_SCALE 0% = 0
XD_SCALE 100% = 30
XD_SCALE UNIT = m3/h
Parameter group OUT_SCALE
OUT_SCALE 0% = 0
OUT_SCALE 100% = 30
OUT_SCALE UNIT = m3/h

Endress+Hauser

47

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

20. Use the following parameters to define the limit values for alarm and warning messages:
HI_HI_LIM Limit value for the upper alarm
HI_LIM Limit value for the upper warning
LO_LIM Limit value for the lower warning
LO_LO_LIM Limit value for the lower alarm
The limit values entered must be within the value range specified in the parameter group
OUT_SCALE.
21. In addition to the actual limit values you must also specify the action taken if a limit value is
exceeded using so-called "alarm priorities" (parameters HI_HI_PRI, HI_PRI, LO_PR,
LO_LO_PRI) See the "Description of Device Functions" manual. Reporting to the fieldbus
host system only takes place if the alarm priority is higher than 2.
22. System configuration/connection of function blocks:
A concluding "overall system configuration" is essential so that the operating mode of the
Analog Input function block can be set to AUTO and so that the field device is integrated into
the system application. To do this, configuration software is used to connect the function
blocks to the desired control strategy - generally graphically - and then the sequence of the
individual process control functions is specified.
23. After specifying the active LAS, download all the data and parameters into the field device.
24. Set the operating mode in the parameter group MODE_BLK (parameter TARGET) to AUTO.
This is only possible under two conditions, however.
The function blocks are correctly connected with each other.
The Resource Block is in operating mode AUTO.

48

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Commissioning

Configuration of the "Analog Output function block" (base index 2300)


The measuring device has an Analog Output function block that can be assigned to the various
process variables.

Note!
The process value transmitted to the Analog Output function block by the density measuring device
must be greater than 0, in order to avoid the status BAD or UNCERTAIN.
The following example shows how the value of a gas analysor measuring device for operating
"Mole % gas 1" parameter can be read in via the Analog Output function block.
Firstly, a connection must be established between the Analog Output function block and the
"Mole % gas 1" parameter in the "Flow" Transducer Block. In addition, the value "39"
(Mole Fraction) must be assigned to the CHANNEL parameter.
25. Enter the desired name for the Analog Output function block (optional). Factory setting:
ANALOG_OUTPUT_xxxxxxxxxxx
26. Open the Analog Output function block.
27. Set the operating mode in the MODE_BLK parameter group (TARGET parameter) to OOS, i.e.
block Out Of Service.
28. Using the CHANNEL parameter, select "Mole Fraction" which is to be used as the input value
for the Transducer Block algorithm (scaling function).
The following settings are possible:
Process variable

Channel parameter

Pressure

17

Mole Fraction

39

29. In the PV_SCALE parameter group, select the desired engineering unit and the block input
range (measuring range of the gasanalysor application) for the relevant process variable (see the
following example).

"

Caution!
Make sure that the selected unit is suitable for the measurement variable of the selected
process variable. Otherwise, the BLOCK_ERROR parameter will display the error message
"Block Configuration Error", and the block operating mode cannot be set to AUTO.
Example:
The measuring range of the density application is 0 to 30 %.
The output range to the automation system should be 0 to 30 % also.
The following settings are required:
- Analog Output function block / CHANNEL parameter (output value option),
option 39 = Mole Fraction
- SHED_OPTIONS parameter e.g. Normal Shed Normal Return
- PV_SCALE parameter group
- PV_SCALE 0% = 0
- PV_SCALE 100% = 30
- PV_SCALE UNIT = %
- OUT_SCALE parameter group
- OUT_SCALE 0% = 0
- OUT_SCALE 100% = 30
- OUT_SCALE UNIT = %

30. Set the operating mode in the MODE_BLK parameter group (TARGET parameter) to AUTO.

Endress+Hauser

49

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

31. System configuration/connection of function blocks:


A concluding "overall system configuration" is essential so that the operating mode of the
Analog Output function block can be set to AUTO and so that the device is integrated into the
system application. To do this, configuration software is used to connect the function blocks to
the desired control strategy - mainly graphically - and the sequence of the individual process
control functions is then specified.

6.3.2

Gas compensation input

The flowmeter can read a output signal from a gas analyzer and automatically update the the first
two gas components (e.g. GAS TYPE 1 and 2) in the programmed gas mixture. This provides a more
accurate measurement in case of varying compositions. For example: varying methane and carbon
dioxide components in a bio gas application.
FOUNDATION Fieldbus

1
4
2

5
6

A0015244

Fig. 31:
1
2
3
4
5
6

Gas mixture compensation using a gas analyzer

Gas analyzer
Gas detector
Gas analyzer output
t-mass
Power supply
Input/Output

Performing the Quick Setup

50

1.

GAS GROUP
use the O or S key to select the required GAS GROUP and continue with F
set the ANALYZER INPUT to ON if a gas compensation input is being used (see "Description
of Device Functions" manual BA00135D/06)
select the NUMBER OF GASES in the group from 1 to 8
select the GAS TYPE from the choose list
enter the MOLE % for each GAS TYPE (only if NUMBER OF GASES is 2 and more)
The error message CHECK VALUES appears if the total mixture % does not equal 100%. Go
back and check the mixture settings.

2.

SAVE CHANGES?
Select YES to save changes to the GAS GROUP and activate them. Press F to continue or
Select CANCEL to save the entered settings in buffer memory but not activate them for
measurement. If this function is selected, then it will be necessary to come back to this gas
group and save it at a later stage.
Select DISCARD to clear the last changes and return to CONFIGURE GROUP to make new
settings.
Exit the function using ESC (X keys simultaneously)

3.

ANOTHER GAS GROUP?


Select YES to continue to the CONFIGURE GROUP function. Use the O or S key key to
select another group and proceed as per above instructions.
Select NO to exit to the Quick Setup.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Commissioning

The following points should be observed or checked for correctness:


Check in the function GAS whether ANALYZER INPUT is ON (Function GAS 55)
Check the actual % value of the main gas component being transmitted from the analyzer:
PROCESS PARAMETER MOLE % GAS 1.
A gas group must consist of at least 2 gas types (e.g. methane 60%, carbon dioxide 40%).
The first gas fraction (GAS 1) transmitted from the gas analyzer will be adjusted dynamically and
the additional gas fractions will be computed as fixed percentages of the whole.

Endress+Hauser

Note!
You can find more detailed information on the GAS GROUP programming in the separate
"Description of Device Functions" manual BA00135D/06 see chapter GAS.

51

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

6.4

Quick Setup

All important device parameters for standard operation can be configured quickly and easily by
means of the Quick Setup menu, especially for devices that have been delivered with factory default
settings

Note!
If the measuring device has been ordered with customer-specific settings then the Quick Setup is
not necessary. Check that the parameterization protocol on the CD delivered with the device
matches your required data.

6.4.1

Quick Setup "Commissioning"


XXX.XXX.XX

Esc

++

Quick Setup

QS
Commission

E+

Language

HOME-POSITION

Pre-setting

Selection pre-settings
Actual settings

Delivery settings

Selection system units

Pressure

Temperature

Mass flow

Corr. Vol. Flow

Heat Flow

Density

Unit
Pressure

Unit
Temperature

Unit
Mass Flow

Unit
Corr. Vol. Flow

Unit Calorific
Value Mass

Unit
Density

Reference
Temperature

Unit Calorific
Val. Corr. Vol.

Reference
Pressure

Unit
Heat Flow

Quit

Unit
Quantity Heat
Yes

Yes

Configure another system unit ?

No

Automatic configuration of display ?

No

Automatic parameterization of the display

u
Sensor

Gas

Carry out another Quick Setup


Pressure

Heat Flow

No

Carry out the selected Quick Setup

A0014984-en

Fig. 32:

QUICK SETUP COMMISSIONING- menu for straightforward configuration of the major device functions

Note!
The display returns to the QUICK SETUP cell if you press the ESC key combination (Q) during
programming of a parameter anywhere in the menu.
QUICK SETUP - COMMISSION
Use the O or S key at the prompt "QS-COMMISSION NO" and the device access code entry appears. Enter the device access
code "65" and press F; programming is enabled. The prompt "QS-COMMISSION NO" appears. Use the O or S key to
change NO to YES and press F.
LANGUAGE
Use the O or S key to select the required language and continue with F.

52

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Commissioning

PRE-SETTING.
m Select ACTUAL SETTINGS to continue programming the device and go to the next level or select DELIVERY SETTINGS
to reset the device. The device restarts and returns to the Home position.
- ACTUAL SETTINGS are the actual programmed parameters in the device
- DELIVERY SETTINGS are the programmed parameters (factory settings plus customer
specific settings) originally delivered with the device
SYSTEM UNITS.
Select required system unit function and carry out parameterization or select QUIT to return to the QUICK SETUP function
if no further programming is required.
n Only units not yet configured in the current setup are available for selection in each cycle.
o The YES option remains visible until all the units have been configured.
NO is the only option displayed when no further units are available.

Automatic configuration of the display


t The "automatic parameterization of the display" option contains the following basic settings/factory settings:
- YES: main line = MASS FLOW, additional line = TOTALIZER 1
- NO: The existing (selected) settings remain.
Carry out another Quick Setup?
u Select additional Quick Setups to complete commissioning or select NO to exit.

Endress+Hauser

53

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

6.4.2

Quick Setup "Sensor"

It is essential that the insertion sensor is setup according to the actual pipe or duct and then installed
at the calculated insertion depth. This Quick Setup guides you systematically through the procedure
to setup the sensor.

Note!
The QUICK SETUP SENSOR function is not available for flanged type sensors.

XXX.XXX.XX

++

QUICK SETUP

QS
SENSOR

E+

Esc

UNIT
LENGTH

HOME-POSITION

m Selection Pipe Type


PIPE
TYPE
CIRCULAR

RECTANGULAR

PIPE
STANDARD

INTERNAL
HEIGHT

NOMINAL
DIAMETER

INTERNAL
WIDTH

OUTER
DIAMETER

WALL
THICKNESS

WALL
THICKNESS

MOUNTING

INTERNAL
DIAMETER

MOUNTING SET
LENGTH

INSERTION
DEPH
A0009910-en

PIPE TYPE
m CIRCULAR
in case that the pipe is of a standard type, then parameterize functions PIPE STANDARD and NOMINAL
DIAMETER
In case that the pipe is a non-standard type, then select OTHERS in the function PIPE STANDARD and
parameterize the functions WALL THICKNESS and OUTER DIAMETER.
The function INTERNAL DIAMETER displays the calculated internal diameter and is read only.
RECTANGULAR
Enter the INTERNAL HEIGHT, INTERNAL WIDTH and WALL THICKNESS of the duct
Select the MOUNTING orientation of the sensor: HORIZONTAL or VERTICAL
MOUNTING SET LENGTH
n Enter the measured length of the mounting set (including the compression fitting) 19.
INSERTION DEPTH
o This function calculates the insertion depth value for the mounting of the sensor 19.
This function is read only.
Press F to save settings and return to QUICK SETUP SENSOR group.

54

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Commissioning

6.4.3

"Gas" Quick Setup menu

The device can be setup with 1 or 2 individual gas groups in memory. This means that up to 2
different gas flow streams (e.g. nitrogen and argon) can be measured in a single pipe with one
flowmeter.
In the case of 2 gas groups being used, a digital input can be assigned to switch between the gas
groups or, alternatively, the switch can be done manually via a function in the device software.

XXX.XXX.XX

++

QUICK SETUP

E+

QS
GAS

Esc

SELECT
GROUP

HOME-POSITION

Selection of Gas Group

GAS GROUP 1

QUIT

GAS GROUP 2

ANALYZER
INPUT

ANALYZER
INPUT

NUMBER OF
GASES

NUMBER OF
GASES

GAS TYPE 1

GAS TYPE 1

DESCRIPTION 1

MOLE % GAS 1

MOLE % GAS 1

DESCRIPTION 2

CORRECTION
FACTOR 1

GAS TYPE
28

GAS TYPE
28

CORRECTION
FACTOR 2

REFERENCE
DENSITY 1

MOLE % GAS
28

MOLE % GAS
28

REFERENCE
DENSITY 2

CHECK
VALUES

CHECK
VALUES

Selection
SAVE CHANGES?

CANCEL

Configure Another Group?

DISCARD

YES

YES

NO

A0009907-en

Programming a gas group


The device allows flexible change of the gas group parameters, independent of the original factory
setup and calibration
A gas group can be programmed as:
one single gas or
one gas mixture (of up to 8 components)
A single gas can be:
selected from a list of standard gases or
setup for other suitable types of gases, such as Ozone, using manual correction factors and the
option called SPECIAL GAS. This requires application evaluation at the factory - consult your
Endress+Hauser representative prior to using this function.

Endress+Hauser

55

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

Setting or viewing the active gas group


Go to the function SELECT GROUP and simply select 1 or 2 and then exit using ESC (+/- keys
simultaneously). No save function is necessary.

Note!
This Quick Setup Gas function is not available if an in-situ calibration function has been performed
on the device as the in-situ calibration curve refers to the sensor power at each recorded flow point.
Therefore, the programmed gas settings become redundant. 64
Performing the Quick Setup

56

1.

GAS GROUP
Use the O or S key to select the required GAS GROUP and continue with F.
select the NUMBER OF GASES in the group from 1 to 8
select the GAS TYPE from the choose list.
enter the MOLE % for each GAS TYPE (only if NUMBER OF GASES is 2 and more).
The error message CHECK VALUES appears if the total mixture % does not equal 100%. Go
back and check the mixture settings.

2.

SAVE CHANGES?
Select YES to save changes to the GAS GROUP and activate them. Press F to continue or
Select CANCEL to save the entered settings in buffer memory but not activate them for
measurement. If this function is selected, then it will be necessary to come back to this gas
group and save it at a later stage.
Select DISCARD to clear the last changes and return to CONFIGURE GROUP to make new
settings.

3.

ANOTHER GAS GROUP?


Select YES to continue to the CONFIGURE GROUP function. Use the O or S key to select
another group and proceed as per above instructions.
Select NO to exit to the Quick Setup.

Note!
You can find more detailed information on the GAS GROUP programming in the separate
"Description of Device Functions" manual BA00135D/06 see chapter GAS 1/2.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

6.4.4

Commissioning

"Pressure" Quick Setup menu

Use this Quick Setup to program the individual process pressure for each gas group. If only one gas
group is being used, then only the function PROCESS PRESSURE 1 needs to be programmed,
PROCESS PRESSURE 2 can remain with default settings.

XXX.XXX.XX

Esc

++

QUICK SETUP

E+

QS
PRESSURE

HOME-POSITION

PROCESS
PRESSURE 1
PROCESS
PRESSURE 2

A0009908-en

Endress+Hauser

Note!
The device operates with absolute pressure only. Convert any gauge pressures to absolute
pressure.
If a pressure compensating input is being used, then the input signal value overrides the manually
programmed value. The pressure input value applies to both gas groups. i.e. 2 independent
pressure values are no longer possible.
This Quick Setup Gas function is not available if an in-situ calibration function has been
performed on the device as the in-situ calibration curve refers to the sensor power at each
recorded flow point. Therefore, the programmed pressure settings become redundant 64.

57

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

6.4.5

"Heat Flow" Quick Setup menu

The device can calculate and output the heat of combustion of common fuel gases such as methane,
natural gas, propane, butane, ethane and hydrogen.
Use this Quick Setup menu to program the method used to calculate the heating value or calorific
value (CV). The device can be configured to give two independent heating value outputs and
totalized values. For example, the pipeline has either natural gas or propane running at separate
times and the heating value is required for both gases.

XXX.XXX.XX

++

QUICK SETUP

E+

Esc

QS
HEAT FLOW

CALORIFIC
VALUE TYPE

HOME-POSITION
Selection CALCULATION MODE 1

AUTO NET

AUTO GROSS

MANUAL
CALORIFIC
VALUE 1

Selection CALCULATION MODE 2

AUTO NET

AUTO GROSS

MANUAL
CALORIFIC
VALUE 2

REF. COMBUST.
TEMPERATURE
A0009909-en

Calculation mode 1 and 2


The heating value for CALCULATION MODE 1 corresponds to the settings in the function
GAS GROUP 1.
The heating value for CALCULATION MODE 2 corresponds to the settings in the function
GAS GROUP 2.

Note!
If only one gas group is used, then leave mode 2 as default settings.
The units of measure are selected in the system units section 52.
Auto Gross
The gross heating value (or higher heating value) is the total heat obtained by complete combustion
at constant pressure of a volume of gas in air, including the heat released by the water vapor in the
combustion products (gas, air and combustion products taken at reference cumbustion temperature
and standard pressure).
Auto Net
The net heating value (or lower heating value) is determined by subtracting the heat of vaporization
of the water vapor from the higher heating value. This treats any water formed as water vapor. The
energy required to vaporize the water therefore is not realized as heat.

58

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Commissioning

Manual
This function allows entry of a user-specific heating value if the required value is different to the
following table.
Gas

Formula

Net/lower heating value

Gross/upper heating value

[Mj/kg]

MBtu/lb

[Mj/kg]

MBtu/lb

Hydrogen

H2

119.91

51.56

141.78

60.97

Ammonia

NH3

18.59

7.99

22.48

9.67

Carbon Monoxide

CO

10.1

4.34

10.1

4.34

Hydrogen Sulphide

H2S

15.2

6.54

19.49

8.38

Methane

CH4

50.02

21.51

55.52

23.87

Ethane

C2H6

47.5

20.43

51.93

22.33

Propane

C3H8

46.32

19.92

50.32

21.64

Butane

C4H10

45.71

19.66

49.51

21.29

Ethylene

C2H4

47.16

20.28

50.31

21.63

* According to ISO 6976:1995(E) and GPA Standard 2172-96

Reference combustion temperature


The following reference temperatures are used:
Country

Endress+Hauser

reference combustion temperature

Austria, Belgium, Denmark, Germany, Italy, Luxembourg,


The Netherlands, Poland, Russia, Sweden, Switzerland

25 C

Brazil, China

20 C

France, Japan

0 C

Australia, Canada, Czech Republic, Hungary, India, Ireland, Malaysia,


Mexico, South Africa, Great Britain

15 C

Slovakia

25 C

USA, Venezuela

60 F

59

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

6.4.6

Data backup/transmission

Using the T-DAT SAVE/LOAD function, you can transfer data (device parameters and settings)
between the T-DAT (exchangeable memory) and the EEPROM (device storage unit).
This is required in the following instances:
Creating a backup: current data are transferred from an EEPROM to the T-DAT.
Replacing a transmitter: current data are copied from an EEPROM to the T-DAT and then
transferred to the EEPROM of the new transmitter.
Duplicating data: current data are copied from an EEPROM to the T-DAT and then transferred to
EEPROMs of identical measuring points.

Note!
For information on installing and removing the T-DAT 79

XXX.XXX.XX

Esc

Quick Setup

HOME
POSITION

T-DAT
SAVE/LOAD

LOAD

F
Restart of the
measuring device

CANCEL

F
YES

SAVE

NO

YES

NO

Input is
saved

a0001221-en

Fig. 33:

Data backup/transmission with T-DAT SAVE/LOAD function

Information on the LOAD and SAVE options available


LOAD:
Data are transferred from the T-DAT to the EEPROM.

Note!
Any settings already saved on the EEPROM are deleted.
This option is only available, if the T-DAT contains valid data.
This option can only be executed if the software version of the T-DAT is the same or newer than
that of the EEPROM. Otherwise, the error message "TRANSM. SW-DAT" appears after restarting
and the LOAD function is then no longer available.
SAVE:
Data are transferred from the EEPROM to the T-DAT

60

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Commissioning

6.5

Adjustment

6.5.1

Zero point adjustment

Calibration takes place under reference operating conditions. ( 90).


Consequently, the zero point adjustment is generally not necessary!
At zero flow conditions, the output of most thermal mass flow devices has a strong dependency on
the process pressure. The effect on the true zero point of the device, by the static line pressure, is
dependant on the gas type and the application demands and in many cases the use of the low flow
cut-off function is adequate to zero the device output.
However, with some gases and /or a combination of high static line pressures, the zero point may
need to be adjusted under process conditions to restore the very low measurement capability of the
device.
Therefore, the zero point adjustment is advisable in the following special cases:
To achieve highest measuring accuracy with very small flow rates.
Under process or operating conditions where the gas properties (heat capacity and thermal
conductivity) will change e.g. Hydrogen and Helium.
Preconditions for a zero point adjustment
Note the following before you perform a zero point adjustment:
A zero point adjustment can be performed only with gases that contain no solid contents or
condensate.
The adjustment is performed with the process gas at zero flow and at operating pressure. This can
be achieved, for example, with shut-off valves upstream and/or downstream of the sensor.
Normal operation valves 1 and 2 open
Zero point adjustment with pump pressure Valve 1 open / valve 2 closed
Zero point adjustment without pump pressure Valve 1 closed / valve 2 open

a0003601

Fig. 34:

Endress+Hauser

Zero point adjustment and shut-off valves

Note!
You can view the currently valid zero point value using the ZERO POINT function in the SENSOR
DATA group (see the "Description of Device Functions" manual, BA00135D/06).

61

Commissioning

Proline t-mass 65 FOUNDATION Fieldbus

Performing a zero point adjustment


1.

Operate the system until operating conditions have settled.

2.

Stop the flow (v = 0 m/s).

3.

Check the shut-off valves for leaks.

4.

Check that operating pressure is correct.

5.

Using the local display, select the ZEROPOINT ADJUSTMENT function in the function matrix:
PROCESS PARAMETER ZERO POINT ADJUST

6.

When you press O or S you are automatically prompted to enter the access code if the
function matrix is still disabled. Enter the code (factory setting = 65).

7.

Use O or S to select START and press F to confirm. The zero point adjustment now starts
and is completed within a few seconds.

Note!
If the flow in the pipe is unstable, the following error message may appear on the display "ZERO
ADJUST FAIL". The zero point adjustment has failed. The preconditions need to be stabilised
before attempting a new adjustment.

8.

Back to the HOME position:


Press and hold down Esc key (X) for longer than three seconds or
Repeatedly press and release the Esc key (X).

Resetting a zero point adjustment


The currently stored zero point can be reset to the original factory value by using the RESET option
within ZERO POINT ADJUST.
Use O or S to select RESET and press F to confirm. The zero point adjustment is now reset.

6.6

Data storage device (HistoROM)

At Endress+Hauser, the term HistoROM refers to various types of data storage modules on which
process and measuring device data are stored. By plugging and unplugging such modules, device
configurations can be duplicated onto other measuring devices to cite just one example.

6.6.1

HistoROM/S-DAT (sensor-DAT)

The HistoROM/S-DAT is an exchangeable data storage device in which all sensor relevant
parameters are stored, i.e., pipe type, diameter, serial number, flow conditoner, zero point.

6.6.2

HistoROM/T-DAT (transmitter-DAT)

The HistoROM/T-DAT is an exchangeable data storage device in which all transmitter parameters
and settings are stored.
Storing of specific parameter settings from the EEPROM to the HistoROM/T-DAT and vice versa
has to be carried out by the user (= manual save function). Please refer to 60 for a description
of the related function (T-DAT SAVE/LOAD) and the exact procedure for managing data).

62

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Maintenance

Maintenance

Generally, the flowmeter requires no special maintenance work, particularly if the gas is clean and
dry.

Warning!
Hazardous area approvals may demand that the device be returned to an Endress+Hauser
production centre ( 86) for service or that work can only be carried out by a qualified
Endress+Hauser service person. Consult your Endress+Hauser service representative for more
information.

7.1

External cleaning

When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the
surface of the housing and the seals.

7.2

Pipe cleaning

The sensor is capable of withstanding clean in place (CIP) processes using heated liquids or steam
(SIP), within the maximum specified temperature limits. However the sensor measurement will be
adversely affected during the cleaning cycle and a settling down period will be required after the
cycle to allow the process and sensor temperatures to re-stabilise.

!
"

Note!
The POSITIVE ZERO RETURN function maybe activated to set the current output to zero flow
during such cycles. See "Description of Device Functions" manual for more information.
Caution!
Do not use a pipe cleaning pig.

7.3

Transducer cleaning

For gases that do carry impurities, it is recommended that the sensor be routinely inspected and
cleaned to minimise any potential measuring errors due to contamination or build-ups. The
frequency of inspection and cleaning will depend upon the application and expected measurement
performance.
Cleaning is performed by applying a non-filming or oil-free type cleaning fluid to a soft brush or cloth
and gently wiping over the surface until all build-ups and contaminants are removed.

"

Caution!
Use care not to bend the sensing elements of the transducer during cleaning.
Do not use abrasive materials or fluids corrosive to the sensor materials and seals.
Sensor-specific information:
t-mass F sensor:
Removal of the transducer requires specialist knowledge, tools and parts. The process seal also
may need to be tested and re-qualified. This procedure must be carried out by an Endress+Hauser
production centre.
t-mass I sensor:
Cleaning of this sensor is straight forward. Safely remove it from the process and clean it as per
above instructions. 19

Endress+Hauser

63

Maintenance

Proline t-mass 65 FOUNDATION Fieldbus

7.4

Replacing seals

Under normal circumstances, fluid wetted seals of the sensor do not require replacement.
Replacement is necessary only in special circumstances, for example if aggressive or corrosive fluids
are incompatible with the seal material.
Sensor-specific information:
t-mass F sensor:
The sensor contains o-rings seals and a bushing. In case of failure, the device must be returned to
an Endress+Hauser production centre for inspection and repair. 86
t-mass I sensor:
The transducer is welded to the insertion tube and has no exchangeable seals. The compression
fitting contains wetted seals (ferrules) and a bonded seal is used on the G 1 A thread version.

"

Caution!
Do not reuse gaskets after removing sensors.
Use only original parts from Endress+Hauser. The compression fitting and gasket seals are
deliverable as spare parts. The seal ring can be replaced easily on site

7.5

In-situ calibration

The t-mass flowmeters are designed to support in-situ calibration using a reference meter signal,
thus saving time and cost by reducing the need for factory re-calibration.
Pre-requirements for in-situ calibration with adjustment:
1.

Stable gas composition (operation with one gas group only; without gas analyzer input)

2.

Stable pressure and temperature (without pressure compensation input)

3.

Mass flow reference


a. mass flow reference meter, mounted in the measurement or bypass pipe, providing a mA
signal to t-mass or
b. manual entry of known mass flow reference values. For example, the display value from
the reference meter or a derived value from a pump curve)

4.

Ability to control the flow range over a minimum of 5 control points

This function is activated using the service access code.


Please discuss your specific requirements with your Endress+Hauser service representative.

7.6

Recalibration

For thermal meters, the interval between calibrations is dependent on the application since
calibration drift is predominantly caused by contamination of the sensor surface.
If the gas is not clean (i.e. contains particulates), then gentle cleaning of the sensor elements can be
effective at regular intervals. The cleaning interval will depend upon the nature and extent of the
contamination.
Determination of recalibration intervals:
If the measurement is critical, then a calibration audit should be undertaken by performing
recalibration checks once per year for a period of 2 years. Increase that period to twice per year
if the application gas is not clean and dry. Depending on the results of the audit, the next
recalibration check interval can be increased or decreased accordingly.
For non-critical applications and or where the gas is clean and dry, a recalibration interval of every
2 to 3 years is recommended.

64

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Accessories

Accessories

Various accessories, which can be ordered separately from Endress+Hauser, are available for the
transmitter and the sensor. Detailed information on the order code in question can be obtained from
your Endress+Hauser representative.

8.1

Device-specific accessories

Accessory

Description

Order code

Mounting boss

Mounting boss for the t-mass insertion sensor


G 1 A thread
1" NPT female thread

DK6MB - ***

Cable remote

Connecting cable for the remote version sensor and transmitter


(per m (ft), up to 100m (328ft) max.)

DK6CA - **

Transmitter t-mass 65

Transmitter for replacement or for stock. Use the order code to


define the following specifications:
Approvals
Degree of protection / version
Cable entries
Display / power supply / operation
Software
Outputs / inputs

65XXX-XXXXXX******

Inputs/outputs

Flexible I/O board conversion kit with appropriate


plug-in sub I/O modules for converting the input/output
configuration.

DK6UI-***

8.2

Measuring principle-specific accessories

Accessory

Description

Order code

Mounting set for


transmitter

Mounting set for remote version. Suitable for:

DK6WM - *

Wall mounting
Pipe mounting
Installation in control panel
Mounting set for aluminium field housing:
Suitable for pipe mounting (" to 3")

Flow conditioner

Hot tap

Perforated plate flow conditioner:


t-mass F sensor (DN25 to 100, 1"to 4")
t-mass I sensor (DN80 to 300, 3" to 12")
Mounting set with ball valve and safety chain. Insertion or
extraction of sensor under process pressure (max. 4 bar, 58 psi).
Mounting set with ball valve and spindle retractor. Insertion or
extraction of sensor under process pressure (max. 16 bar,
235 psi).

Graphic data manager


Memograph M

Endress+Hauser

DK6ST-***
DK7ST-***
Please refer to the
product page of the
Endress+Hauser Internet
page:
www.endress.com

The graphic data manager Memograph M provides information on RSG40 - ************


all the relevant process variables. Measured values are recorded
correctly, limit values are monitored and measuring points
analyzed. The data are stored in the 256 MB internal memory and
also on an SD card or USB stick.
Memograph M boasts a modular design, intuitive operation and a
comprehensive security concept. The ReadWin 2000 PC
software is part of the standard package and is used for configuring,
visualizing and archiving the data captured.
The mathematics channels which are optionally available facilitate
continuous monitoring, e.g. of specific energy consumption, boiler
efficiency and other parameters which are necessary for efficient
energy management.

65

Accessories

Proline t-mass 65 FOUNDATION Fieldbus

8.3

Service-specific accessories

Accessory

Description

Order code

Applicator

Software for selecting and sizing Endress+Hauser measuring


devices:
Calculation of all the necessary data for identifying the
optimum flowmeter: e.g. nominal diameter, pressure loss,
accuracy or process connections
Graphic illustration of the calculation results

DKA80 - *

Administration, documentation and access to all project-related


data and parameters over the entire life cycle of a project.
Applicator is available:
Via the Internet: https://wapps.endress.com/applicator
On CD-ROM for local PC installation.

66

Fieldcheck

Tester/simulator for testing flowmeters in the field.


50098801
When used in conjunction with the "FieldCare" software package,
test results can be imported into a database, printed and used for
official certification.
Contact your Endress+Hauser representative for more
information.

FieldCare

FieldCare is Endress+Hauser's FDT based Plant Asset


Management Tool. It can configure all intelligent field devices in
your plant and supports you in managing them. By using status
information, it also provides a simple but effective means of
checking their health.

Please refer to the


product page of the
Endress+Hauser Internet
page:
www.endress.com

FXA193

The FXA193 service interface connects the device to the PC for


configuration via FieldCare.

FXA193 *

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Trouble-shooting

Trouble-shooting

9.1

Troubleshooting instructions

Always start troubleshooting with the checklist below, if faults occur after startup or during
operation. The routine takes you directly to the cause of the problem and the appropriate remedial
measures.

"

Caution!
In the event of a serious fault, a flowmeter might have to be returned to the manufacturer for repair.
The necessary procedures must be carried out before you return the device to Endress+Hauser
86
Always enclose a duly completed "Declaration of contamination" form. You will find a preprinted
blank of this form at the back of this manual.
Check the display
No display visible. No
connection to the FF host
system

1. Check the supply voltage Terminals 1, 2


2. Check device fuse 85
20 to 260 V AC and 20 to 64 V DC: 2 A slow-blow / 250 V
3. Measuring electronics defective Order spare parts 79

No display visible.
Connection to the FF host
system established
however.
Display texts are in a
foreign language.

1. Check whether the ribbon-cable connector of the display module is correctly plugged
into the amplifier board 80
2. Display module defective Order spare parts 79
3. Measuring electronics defective Order spare parts 79
Switch off power supply. Then press the OS keys simultaneously to switch the device back
on. The display text will appear in English (default) and is displayed at maximum contrast.

No connection can be
Measuring electronics board defective Order spare parts 79
established with the FF host
system, even though
measured value reading is
visible.

Error messages on display


Errors which occur during commissioning or measuring operation are displayed immediately. Error messages consist of a
variety of icons. The meanings of these icons are as follows (example):

Error type: S = system error, P = process error


Error message type: $ = fault message, ! = notice message
EMPTY PIPE = type of error, e.g. measuring tube is only partly filled or completely empty
03:00:05 = duration of error occurrence (in hours, minutes and seconds)
#401 = error number

Caution!
" Also observe
the information on 40
The measuring system interprets simulations and positive zero return as system errors, but displays them as notice
message only.
Error number:
No. 001 399
No. 501 699

System error (device error) has occurred 72

Error number:
No. 401 - 499

Process error (application error) has occurred 77

Endress+Hauser

67

Trouble-shooting

Proline t-mass 65 FOUNDATION Fieldbus

Faulty connection to the fieldbus host system


No connection can be made between the fieldbus host system and the measuring device.
Check the following points:
Supply voltage
Transmitter

Check the supply voltage Terminals 1/2

Device fuse

Check device fuse 85


20 to 260 V AC and 20 to 64 V DC: 2 A slow-blow / 250 V

Fieldbus connection

FOUNDATION Fieldbus: check the data cable


Terminal 26 = FF +
Terminal 27 = FF

Fieldbus connector
(Option)

Check pin assignment/wiring 33


Check connection between connector/fieldbus port.
Is the coupling ring tightened correctly?

Fieldbus voltage

Check that a min. bus voltage of 9 V DC is present at Terminals 26/27. Permissible range:
9 to 32 V DC

Network structure

Check permissible fieldbus length and number of spurs. 33

Basic current

Is there a basic current of min. 12 mA?

Bus address

Check bus address: make sure there are no double assignments

Bus termination

Is the FOUNDATION Fieldbus-H1 network correctly terminated?


Each bus segment must always be terminated with a bus terminator at both ends (start and
finish). Otherwise there may be interference in communication.

Current consumption,
permitted feed current

Check the current consumption of the bus segment:


The current consumption of the bus segment in question (= total of basic currents of all bus
users) must not exceed the max. permissible feed current of the bus power supply.

Device Description (DD)

Instal the DD if you cannot access the manufacturer-specific parameters.


Note!
!
Ensure you use the correct system files for linking the field devices into the host system.
Appropriate version information can be called up in the device via the following functions/
parameters:
Local display:
HOME COMMUNICATION FOUND. FIELDBUS DEVICE REVISION
HOME COMMUNICATION FOUND. FIELDBUS DD REVISION
FF configuration program:
Resource Block Parameter DEV_REV
Resource Block Parameter DD_REV
Example (with local display):
Displayed in the DEVICE REVISION function 01
Displayed in the DD REVISION function 01
Device description file (DD) required 0101.sym / 0101.ffo

68

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Trouble-shooting

Problems with configuration of function blocks


Transducer Blocks:
Check whether the operating mode of the Resource Block is in AUTO mode Parameter
The operating mode cannot group MODE_BLK / parameter TARGET.
be set to AUTO.
Analog Input function
There may be several reasons for this. Check the following in sequence:
block:
1. Check whether the operating mode of the Analog Input function block is in AUTO
The operating mode cannot
mode Parameter group MODE_BLK / parameter TARGET.
be set to AUTO.
If not and the mode cannot be set to AUTO, first check the following.
2. Make sure that the CHANNEL parameter (process variable selection) is already
configured in the Analog Input function block 45. CHANNEL = 0 (Uninitialized)
is not valid.
3. Make sure that the XD_SCALE parameter group (input range, unit) is already
configured in the Analog Input function block 47 (incl. configuration example)

"Make sureCaution!
that the selected unit is suitable for the process variable selected in the
CHANNEL parameter. Otherwise the parameter BLOCK_ERROR will display the error
message "Block Configuration Error". In this status the block operating mode cannot be
set to AUTO.
4. Make sure that the L_TYPE parameter (type of linearization) is already configured in
the Analog Input function block 47.

"Make sureCaution!
that with the type of linearization "Direct" the scaling of the parameter
group OUT_SCALE is identical to that of the parameter group XD_SCALE. If set
incorrectly the parameter BLOCK_ERROR will display the error message "Block
Configuration Error". In this status the block operating mode cannot be set to AUTO.
Configuration example 47
5. Check whether the operating mode of the Resource Block is set to AUTO
MODE_BLK parameter group/TARGET parameter.
6. Make sure that the function blocks are correctly interconnected and that this system
configuration has been sent to the fieldbus station 47.
Analog Input function
block:
The operating mode is set
to AUTO but the status of
the AI output value OUT is
"BAD" or "UNCERTAIN".

1. Check whether the operating mode of the Transducer Blocks is set to AUTO
MODE_BLK parameter group / TARGET parameter. The following Transducer Blocks
have to be set to AUTO by using the various CHANNEL parameters:
Flow" Transducer Block (base index: 1400):
CHANNEL 1 (mass flow)
CHANNEL 2 (calculated volume flow)
CHANNEL 3 (temperature)
CHANNEL 53 (heat flow)
"Totalizer" Transducer Block (base index: 1900):
CHANNEL 7 (Totalizer 1)
CHANNEL 8 (Totalizer 2)
2. Check whether an error is pending in the "Flow" (base index: 1400) or "Totalizer"
(base index: 1900) Transducer Blocks "Diagnosis" Transducer Block (base index:
1600) "Diag. - Act.Sys.Condition" parameter.
Error messages 71

Endress+Hauser

69

Trouble-shooting

Proline t-mass 65 FOUNDATION Fieldbus

Parameters cannot be
1.
modified or no write access
2.
to parameters.

Parameters that only display values or settings cannot be modified!


Hardware write protection is enabled Deactivate the write protection 43

Note!
You can use the parameter WRITE_LOCK in the Resource Block to check whether
hardware write protection is activated or deactivated:
LOCKED = write protection enabled (activated)
UNLOCKED = no write protection (deactivated)

Transducer Block:
The manufacturer-specific
parameters are not visible.

3.

The block operating mode is wrong. Certain parameters can only be modified in mode
OOS (Out of Service) or MAN (MANual) Set the operating mode of the block to
the required mode Parameter group MODE_BLK.

4.

The value entered is outside the specified input range for the parameter in question:
Enter suitable value
Increase input range if necessary

5.

Transducer Blocks: The programming level is not enabled Enable by entering the
code in the "Access Code" parameter or by means of the service code in the service
parameters.

The device description file (Device Description, DD) has not been loaded into the host
system or the configuration program Load the file into the configuration system.
Reference sources of the DD 42
Note!
!
Ensure you use the correct system files for linking the field devices into the host system.
Appropriate version information can be called up in the device via the following functions/
parameters:
Local display:
HOME COMMUNICATION FOUND. FIELDBUS DEVICE REVISION
HOME COMMUNICATION FOUND. FIELDBUS DD REVISION
FF configuration program:
Resource Block Parameter DEV_REV
Resource Block Parameter DD_REV
Example (with local display):
Display in the DEVICE REVISION function 01
Display in the DD REVISION function 01
Required Device Description files (DD) 0101.sym / 0101.ffo

Analog Input function


block:
The output value OUT is
not updated despite having
a valid "GOOD" status.

Simulation is active Deactivate simulation via parameter group SIMULATE.

Error messages
Error messages in the FF configuration program 71
Error messages on the local display 71

Other error (without error message)


Some other error has
occurred.

70

Diagnosis and rectification 77

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

9.2

Trouble-shooting

System/process error messages

General notes
The flowmeter assigns current system and process errors to two error message types in accordance
with a predefined algorithm and classifies them accordingly:
"Fault message" error message type:
A message of this type immediately interrupts or stops measurement.
Presentation on the FOUNDATION Fieldbus Fault messages are transmitted to downstream
function blocks or higher-level process control systems by means of the status "BAD" of the AI
output parameter OUT.
Local display A flashing lightning symbol ($) is displayed
"Notice message" error message type:
Measurement continues despite this message.
Presentation on the FOUNDATION Fieldbus Notice messages are transmitted to downstream
function blocks or higher-level process control systems by means of the status "UNCERTAIN" of
the AI output parameter OUT.
Local display A flashing exclamation mark (!) is displayed.
Critical system errors, e.g. module defects, are always identified and classed as "fault messages" by
the measuring device. Simulations in the "Flow" Transducer Block and positive zero return, on the
other hand, are identified as "notice messages" only.
Error messages in the FF configuration programs See Table
System and process errors are recognized and reported in the Transducer Blocks. Such errors are
displayed via the following parameters specified in the FOUNDATION Fieldbus specification:
BLOCK_ERR
Transducer Error
In the "Diagnosis" Transducer Block (base index: 1600), detailed reasons for errors and device status
messages are displayed by means of the "Diag. - Act.Sys.Condition" parameter (manufacturerspecific) Table.
Error messages on the local display See Table
You will find more details on how error messages are presented on 40.

Endress+Hauser

71

Trouble-shooting

Proline t-mass 65 FOUNDATION Fieldbus

9.2.1

No.

Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)

List of system error messages

Transducer Block
error messages

Analog Input function block


error messages

Cause/remedy
(Spare parts 79

* With FF, error messages are displayed in the "Diagnosis" Transducer Block (base index: 1600) by means of the "Diag. Act.Sys.Condition" parameter
(manufacturer-specific).
S = System error
$ = Fault message (with an effect on operation)
! = Notice message (without an effect on operation)
No. # 0xx Hardware error
001

Device status message (FF):


ROM/RAM failure
Err. No. 001
Local display:
S: CRITICAL FAIL.
$: # 001

011

Device status message (FF):


Amplifier EEPROM failure
Err. No. 011
Local display:
S: AMP HW EEPROM
$: # 011

012

Device status message (FF):


Amplifier EEPROM data
inconsistent
Err. No. 012

BLOCK_ERR = Device needs


maintenance now

Transducer_Error = Electronics OUT. SUBSTATUS = Device


failure
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
BLOCK_ERR = Device needs
maintenance now
Transducer_Error = Data
integrity error

Device status message (FF):


S-DAT failure / S-DAT not
inserted
Err. No. 031

BLOCK_ERR = Device needs


maintenance now
Transducer_Error = Data
integrity error

Device status message (FF):


S-DAT data inconsistent
Err. No. 032
Local display:
S: SENSOR SW DAT
$: # 032

72

Remedy:
Replace the amplifier board.

OUT. QUALITY = BAD

Cause:
Measuring amplifier has faulty EEPROM

OUT. SUBSTATUS = Device


Failure

Remedy:
Replace the amplifier board.

OUT. QUALITY = BAD


OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)

BLOCK_ERR = Device needs


maintenance now

OUT. QUALITY = BAD

Transducer_Error = Electronics OUT. SUBSTATUS = Device


failure
Failure

Local display:
S: SENSOR HW DAT
$: # 031

032

Cause:
ROM/RAM error. Error when accessing the
program memory (ROM) or random access
memory (RAM) of the processor.

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)

Local display:
S: AMP SW EEPROM
$: # 012

031

OUT. QUALITY = BAD

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)

BLOCK_ERR = Device needs


maintenance now
Transducer_Error = Data
integrity error

OUT. QUALITY = BAD


OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)

Cause:
Error when accessing data of the measuring
amplifier EEPROM
Remedy:
Perform a "warm restart" (start the measuring
system without disconnecting mains power).
FF: "Diagnosis" Transducer Block (base index:
1600) "Sys. Reset" parameter RESTART
SYSTEM
Local display: SUPERVISION
SYSTEM OPERATION SYSTEM RESET
( RESTART SYSTEM)
Cause:
1. S DAT is not correctly plugged into the
amplifier board (or is missing).
2. S-DAT is defective.
Remedy:
1. Check whether the S-DAT is correctly plugged
into the amplifier board,
2. Replace the S-DAT if it is defective.
Check whether the new replacement DAT is
compatible with the existing electronics.
Check the:
- Spare part set number
- Hardware revision code
3. Replace measuring electronics boards if
necessary.
4. Plug the S-DAT into the amplifier board.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

No.

035

Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)
Device status message (FF):
Sensor EEPROM failure
Err. No. 035
Local display:
S: SEN HW-ROM/RAM
$: # 035

036

Device status message (FF):


Sensor EEPROM failure
Err. No. 036
Local display:
S: SEN SW-ROM/RAM
$: # 036

041

Device status message (FF):


T-DAT failure
Err. No. 041
Local display:
S: TRANSM. HW-DAT
$: # 041

042

Device status message (FF):


T-DAT data inconsistent
Err. No. 042
Local display:
S: TRANSM. SW-DAT
$: # 042

Transducer Block
error messages
BLOCK_ERR = Device needs
maintenance now
Transducer_Error = Data
integrity error

Trouble-shooting

Analog Input function block


error messages

Cause/remedy
(Spare parts 79

OUT. QUALITY = BAD

Cause:
Sensor: Defective ROM/RAM.

OUT. SUBSTATUS = Device


Failure

Remedy:
Replace the remote amplifier board.

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)
BLOCK_ERR = Device needs
maintenance now
Transducer_Error = Data
integrity error

OUT. QUALITY = BAD


OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)

BLOCK_ERR = Device needs


maintenance now

OUT. QUALITY = BAD

Transducer_Error = Electronics OUT. SUBSTATUS = Device


failure
Failure

BLOCK_ERR = Device needs


maintenance now
Transducer_Error = Data
integrity error

Cause:
1. T DAT is not correctly plugged into the
amplifier board (or is missing).
2. T-DAT is faulty.

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)

Remedy:

OUT. QUALITY = BAD

2. Replace the T-DAT if faulty.


Check whether the new replacement DAT is
compatible with the existing electronics.
Check the:
- Spare part set number
- Hardware revision code

OUT. SUBSTATUS = Device


Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)

1. Check whether the T-DAT is correctly plugged


into the amplifier board.

3. Replace measuring electronics boards if


necessary.
4. Plug the T-DAT into the amplifier board.

No. # 1xx Software error


070

Device status message (FF):


Sensor Defect
Err. No. 070
Local display:
S: SENSOR DEFECT
$: # 071

072

Device status message (FF):


A to D Reference Error
Err. No. 072
Local display:
S: A/D REF. ERROR .
$: # 072

Endress+Hauser

BLOCK_ERR = Device needs


maintenance now
Transducer_Error =
Mechanical failure

OUT. QUALITY = BAD


OUT. SUBSTATUS = Device
Failure

Cause:
Flow sensor are likely to be defect, measurement is
no longer possible.
Remedy:
Contact your Endress+Hauser representative

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)
BLOCK_ERR = Device needs
maintenance now

OUT. QUALITY = BAD

Transducer_Error = Electronics OUT. SUBSTATUS = Device


failure
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)

Cause:
Measuring amplifier analougue to digital converter
circuitry faulty.
Remedy:
Replace the remote amplifier board.

Hinweis!
Ensure that the S-DATs and T-DAT are transferred
from old circuit board to the new one.

73

Trouble-shooting

No.

121

Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)
Device status message (FF):
Software compatibility
problem amplifier
I/O module
Err. No. 121

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block
error messages
BLOCK_ERR = Device needs
maintenance now

Analog Input function block


error messages

Cause/remedy
(Spare parts 79

OUT. QUALITY = BAD

Cause:
Due to different software versions, I/O board and
amplifier board are only partially compatible
(possibly restricted functionality).

Transducer_Error = I/O failure OUT. SUBSTATUS = Device


(input/output error)
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)

Local display:
S: A/C COMPATIB.
!: # 121

Note!
The indication on the display as notice message
appears only for 30 seconds (with listing in
"Previous system condition" function).
This Situation in which the software versions
differ can occur if only one electronics board has
been exchanged; the extended software
functionality is not available. The previousiy
existing software functionality is still available
and measurement operation is possible..
Remedy:
Module with lower software version must either be
updated by FieldCare using the required
(recommended) software version, or the module
must be replaced.

No. # 2xx Error in DAT / no communication


205

Device status message (FF):


Save to T-DAT failed
Err. No. 205
Local display:
S: LOAD T-DAT
!: # 205

206

Device status message (FF):


Restore from T-DAT failed
Err. No. 206
Local display:
S: SAVE T-DAT
!: # 206

251

Device status message (FF):


Communication failure
amplifier
Err. No. 251

BLOCK_ERR = Device needs


maintenance now

Transducer_Error = Electronics OUT. SUBSTATUS = Device


failure
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
BLOCK_ERR = Device needs
maintenance now

Device status message (FF):


Communication failure
amplifier
Err. No. 261
Local display:
S: COMMUNICAT. I/O
$: # 261

74

OUT. QUALITY = BAD

Transducer_Error = Electronics OUT. SUBSTATUS = Device


failure
Failure

BLOCK_ERR = Device needs


maintenance now

Cause:
Data backup (downloading) to
TDAT failed, or error when accessing (uploading)
the calibration values stored in the TDAT.
Remedy:
1. Check whether the T-DAT is correctly plugged
into the amplifier board.
2. Replace the T-DAT if it is defective
Before replacing the DAT, check that the new,
replacement DAT is compatible with the
measuring electronics. Check the:
Spare part set number
Hardware revision code

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)

3. Replace measuring electronics boards if


necessary .

OUT. QUALITY = BAD

Cause:
Internal communication fault on the amplifier
board.

Transducer_Error = Electronics OUT. SUBSTATUS = Device


failure
Failure

Local display
S: COMMUNICAT. AMP
$: # 251
261

OUT. QUALITY = BAD

Remedy:
Replace the amplifier board.

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)
BLOCK_ERR = Device needs
maintenance now

OUT. QUALITY = BAD

Transducer_Error = I/O failure OUT. SUBSTATUS = Device


(communication problems)
Failure

Cause:
Communication error. No data reception between
amplifier and I/O board or faulty internal data
transfer.

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

No.

Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)

Transducer Block
error messages

Trouble-shooting

Analog Input function block


error messages

Cause/remedy
(Spare parts 79

OUT. QUALITY = BAD

Cause:
The measured sensor differential temperature is
below lirnit vaiue.

No. # 3xx System limits exceeded


372

Device status message (FF):


Diff. Temp. is below limit
Err. No. 372
Local display:
S: DIFF.TEMP.LOW
$: # 372

381

Device status message (FF):


Fluid temperature min.
Err. No. 381
Local display:
S: FLUIDTEMP.MIN.
$: # 381

382

Device status message (FF):


Fluid temperature max.
Err. No. 382
Local display:
S: FLUIDTEMP.MAX.
$: # 382

BLOCK_ERR = Device needs


maintenance now
Transducer_Error = General
failure

OUT. SUBSTATUS = Device


Failure
BLOCK_ERR = Input Failure

BLOCK_ERR = Device needs


maintenance now
Transducer_Error = General
failure

BLOCK_ERR = Device needs


maintenance now
Transducer_Error = General
failure

OUT. QUALITY = BAD


OUT. SUBSTATUS = Sensor
Failure

OUT. QUALITY = BAD


OUT. SUBSTATUS = Sensor
Failure

Remedy:
Reduce the flow rate or consider replaclng the
instrurnent with a suitabie size for the application if
possible.
Cause:
The temperature Sensor on the measuring tube is
probably defective.
Remedy:
Check the following eiectrical connections before
you contact your Endress+Hauser service
organization:
Verify that the sensor signal cable connector is
correctly plugged into the arnplifier board.
80
Remote version:
Check sensor and transrnitter terminal
connections No. 9 and 10 30

No. # 5xx Application error


501

502

Device status message (FF):


Download device software
active
Err. No. 501

BLOCK_ERR = Device needs


maintenance now
Transducer_Error = General
Error

OUT. QUALITY = UNCERTAIN


OUT. SUBSTATUS = Non specific

Cause:
New amplifier or communication (I/O module)
software version is loaded.
Currently no other functions are possible.

Local display:
S: SW.-UPDATE ACT.
!: # 501

BLOCK_ERR = Input Failure


(faulty input value from
Transducer Blocks)

Remedy:
Wait until the procedure is finished. The device
will restart automatically.

Device status message (FF):


BLOCK_ERR = Device needs
Up-/Download device software
maintenance now
active
Transducer_Error = General
Err. No. 502
Error
Local display:
S: UP-/DOWNLO. ACT.
!: # 502

OUT. QUALITY = UNCERTAIN

Cause:
Uploading or downloading the device data via
operating program. Currently no other functions
are possible.

OUT. SUBSTATUS = Non specific


BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)

Remedy:
Wait until the procedure is finished.

OUT. QUALITY = UNCERTAIN

Cause:
Positive zero return is active.

No. # 6xx Simulation mode active


601

Device status message (FF):


Positive zero return active
Err. No. 601
Local display:
S: POS. ZERO-RETURN
!: # 601

Endress+Hauser

OUT. SUBSTATUS = Non specific

Note!
This message has the highest display priority!
Remedy:
Deactivate positive zero return:
FF: "Flow" Transducer Block (base index: 1100)
"System - Positive Zero Return" parameter
OFF
Local display: BASIC FUNCTIONS
SYSTEM PARAMETERS CONFIGURATIONS
POS. ZERO RETURN ( OFF)

75

Trouble-shooting

No.

691

Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)
Device status message (FF):
Simulation failsafe active
Err. No. 691

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block
error messages
BLOCK_ERR = Simulation
active

Local display:
S: SIM. FAILSAFE
!: # 691

692

Device status message (FF):


Simulation volume flow
active
Err. No. 692

Device status message (FF):


Simulation Volume flow
active
Err. No. 698

Cause/remedy
(Spare parts 79

OUT. QUALITY = UNCERTAIN

Cause:
Simulation of response to error (outputs) is active.

OUT. SUBSTATUS = Non specific

Remedy:
Switch off simulation:
FF: "Diagnosis" Transducer Block (base index:
1600) "Sys. Sim.Failsafe Mode" parameter
OFF
Local display: SUPERVISION
SYSTEM OPERATION SIM. FAILSAFE
MODE ( OFF)

BLOCK_ERR = Simulation active

BLOCK_ERR = Simulation
active

OUT. QUALITY = UNCERTAIN

Cause:
Simulation of the measured value is active.

OUT. SUBSTATUS = Non specific

Remedy:
Switch off simulation:
FF: "Flow" Transducer Block (base index: 1400)
"Simulation - Measurand" parameter OFF
Local display: SUPERVISION
SYSTEM OPERATION SIM.
MEASURAND ( OFF)

BLOCK_ERR = Simulation active

Local display:
S: SIM. MEASURAND
!: # 692

698

Analog Input function block


error messages

BLOCK_ERR = Simulation
active

OUT. QUALITY = UNCERTAIN


OUT. SUBSTATUS = Non specific

Cause:
The measuring device is being checked on site via
the test and simulation device.

Local display:
S: DEV.TEST ACT.
!: # 698

76

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

9.2.2

No.

Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)

Trouble-shooting

List of process error messages

Transducer Block
error messages

Analog Input function block


error messages

Cause/remedy

* With FF, error messages are displayed in the "Diagnosis" Transducer Block (base index: 1600) by means of the "Diag. Act.Sys.Condition" parameter
(manufacturer-specific).
P = Process error
$ = Fault message (with an effect on operation)
! = Notice message (without an effect on operation)
422

Device status message (FF):


Massflow exceeded max limit
Err. No. 422

OUT. QUALITY = UNCERTAIN


OUT. SUBSTATUS = Non specific

Local display:
P: FLOW LIMIT
$: # 422
433

Device status message (FF):


Zero point adjustment is not
possible
Err. No. 731

Remedy:
Reduce the flow rate or replace the instrument
with a suitable size for the application.
Transducer_Error =
Configuration error

OUT. QUALITY = UNCERTAIN


OUT. SUBSTATUS =
Configuration error

Local display:
P: ADJ. ZERO FAIL
$: # 731

9.3
Symptoms

Cause:
The measured flow has exceeded the maximum
limit.

Cause:
The zero point adjustment is not possible or has
been cancelled.
Remedy:
Make sure that Zero point adjustment is carried out
at "zero flow" only (v = 0 m/s) 61

Process errors without messages

Rectification

Note!
!
You may have to change or correct certain settings of the function matrix in order to rectify faults. The functions outlined below, such as DISPLAY DAMPING, for
example, are described in detail in the "Description of Device Functions" manual.
Displayed measured value fluctuates
even though flow is steady.

Device displays flow with no actual


flow present.

1.

Increase value of the TIME CONSTANT setting CURRENT OUTPUT function group.

2.

Increase value of the DISPLAY DAMPING setting USER INTERFACE function group.

3.

The inlet and outlet lengths must be observed. See installation conditions 15

4.

Consider the use of a flow conditioner. See installation conditions 16

5.

Relocate the meter to a point where there is less flow disturbance

1.

The low flow cut off value is programmed too low. Increase value of the ON VALUE LOW FLOW CUT OFF setting
PROCESS PARAMETERS function group (Factory setting = 1% of 20mA value).

2.

Check for leaks in the pipe line downsteam of the sensor.

3.

Reduce or eliminate pressure pulsations in the line.

Device displays flow with no actual


Start the ZERO POINT ADJUST function PROCESS PARAMETERS function group.
flow present - but with high static line See Zero Point Adjust function 61
pressure and thermally conductive
Note!
gases present (e.g. Hydrogen, Helium, Process preconditions are required before starting this function.
etc.). Line pressure is typically > 5 bar /
75 psi

Device displays zero flow but flow is


present.

Endress+Hauser

1.

The INSTALLATION FACTOR may have a wrong setting = 0 PROCESS PARAMETERS function group (factory
setting = 1.0).

2.

The LOW FLOW CUT OFF setting may be too high. Adjust the function ON VALUE LOW FLOW CUT OFF to a
lower value PROCESS PARAMTERS function group (factory setting 1% of calibrated 20mA value).

3.

The ZERO POINT ADJUST function may have been incorrectly carried out with flow present. RESET the zero point
adjustment if necessary PROCESS PARAMETERS function group.

77

Trouble-shooting

Proline t-mass 65 FOUNDATION Fieldbus

Symptoms

Rectification

Device displays incorrect flow value.

1.

Check the basic parameters of the device (Quick Setup 52)


Especially:
Gas
Process pressure
Reference presssure and reference temperature
Flow units
Output assignment

2.

Check the installation conditions (Post-installation check 26)


1. The inlet and outlet lengths must be observed 15.
2. Consider the use of a flow conditioner if the necessary inlet requirements cannot be met 16.
3. t-mass F: Check for diameter mismatch between the flanges and check the gasket alignment 13.
t-mass I: Check the sensor orientation and insertion depth. 19.
4. If the above actions do not resolve the problem, consider adjusting the INSTALLATION FACTOR so that the
displayed flow rate matches the expected flow rate PROCESS PARAMETERS function group (factory setting
1.0).

3.

The flow rate maybe too high (i.e. above sensor calibration range)
1. Check the sensor measuring range using the Endress+Hauser Applicator program.
2. Check if the inverted plus sign "+" is shown on the display? If yes, reduce the velocity if possible.

4.

The flow rate maybe too low


1. Check the sensor measuring range using the E+H Applicator program.
2. Increase the velocity if possible.

5.

Check the condition of the transducer


1. Are the measuring elements bent? If yes, replacement is necessary.
2. Are build-ups present? If yes, clean the sensors (Transducer cleaning 63).
3. Has corrosion occured? If yes, replacement is necessary.

6.

Check if the gas is wet? Is condensate present on the sensors?


If yes:
1. For horizontal pipes: Mount the sensor at 135 14
2. Install a condensate trap or filter upstream of the flowmeter

7.

Check if heating devices are used upstream of the flowmeter causing possible temperature profile effects ?
If yes:
1. Relocate the flowmeter further downstream or
2. Install a flow conditioner upstream of the flowmeter

The fault cannot be rectified or some


other fault not described above has
occurred.
In these instances, please contact your
Endress+Hauser representative.

The following options are available for tackling problems of this nature:
Request the services of an Endress+Hauser service technician
If you contact our service representative to have a service technician sent out, please be ready with the following
information:
Brief description of the fault
Nameplate specifications : Order code and serial number 7
Returning devices to Endress+Hauser
The procedures on must be carried out before you return a flowmeter requiring repair or calibration to Endress+Hauser.
6
Always enclose a duly completed "Declaration of contamination" form with the flowmeter. You will find a preprinted
"Declaration of contamination" at the back of this manual.
Replace transmitter electronics
Components in the measuring electronics defective order replacement 79

78

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

9.4

Trouble-shooting

Spare parts

The previous sections contain a detailed trouble-shooting guide. 67


The measuring device, moreover, provides additional support in the form of continuous selfdiagnosis and error messages.
Fault rectification can entail replacing defective components with tested spare parts. The illustration
below shows the available scope of spare parts.

Note!
You can order spare parts directly from your Endress+Hauser representative by providing the serial
number printed on the transmitter's nameplate. 7
Spare parts are shipped as sets comprising the following parts:
Spare part
Additional parts, small items (threaded fasteners, etc.)
Mounting instructions
Packaging

4
5

A0014983

Fig. 35:
1
2
3
4
5
6

Endress+Hauser

Spare parts for transmitter 65 (field and wall-mount housings)

Power unit board (85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC)


Amplifier board
I/O board (COM module)
HistoROM/S-DAT (sensor data memory)
HistoROM/T-DAT (transmitter data memory)
Display module

79

Trouble-shooting

Proline t-mass 65 FOUNDATION Fieldbus

9.4.1

Removing and installing printed circuit boards

Field housing

"

Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
Risk of damaging electronic components (ESD protection). Static electricity can damage electronic
components or impair their operability. Use a workplace with a grounded working surface
purposely built for electrostatically sensitive devices!
If you cannot guarantee that the dielectric strength of the device can be maintained during the
following steps, then an appropriate inspection test must be carried out in accordance with the
manufacturers specifications.
When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement
to these Operating Instructions.
Caution!
Use only original Endress+Hauser parts.
Installation and removal 36
1.

Unscrew cover of the electronics compartment from the transmitter housing.

2.

Remove the screws (1.1) and remove the cover (1) from the electronics compartment.

3.

Disconnect the display ribbon cable (1.2) from the amplifier board.

4.

Remove power supply board (3) and I/O board (5):


Insert a thin pin into the hole (2) provided for the purpose and pull the board clear of its holder.
Remove amplifier board (4):
Disconnect the plug of the sensor signal cable (4.1) including HistoROM/S-DAT (4.2) and
HistoROM/T-DAT (4.3) from the board.
Insert a thin pin into the hole (2) provided for the purpose and pull the board clear of its
holder.

5.

6.

80

Installation is the reverse of the removal procedure.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Trouble-shooting

4
2
5
4.1
4.2
4.3

1.1

1.2
A0014977

Fig. 36:
1
1.1
1.2
2
3
4
4.1
4.2
4.3
5

Endress+Hauser

Field housing: removing and installing printed circuit boards

Electronics compartment cover with local display


Screws of electronics compartment cover
Ribbon cable (display module)
Aperture for installing/removing boards
Power unit board
Amplifier board
Signal cable (sensor)
HistoROM/S-DAT (sensor data memory)
HistoROM/T-DAT (transmitter data memory)
I/O board

81

Trouble-shooting

Proline t-mass 65 FOUNDATION Fieldbus

Wall-mount housing

"

Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
Risk of damaging electronic components (ESD protection). Static electricity can damage electronic
components or impair their operability. Use a workplace with a grounded working surface
purposely built for electrostatically sensitive devices!
If you cannot guarantee that the dielectric strength of the device can be maintained during the
following steps, then an appropriate inspection test must be carried out in accordance with the
manufacturers specifications.
When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement
to these Operating Instructions.
Caution!
Use only original Endress+Hauser parts.
Installation and removal 37

82

1.

Remove the screws and open the hinged cover (1) of the housing.

2.

Loosen the screws securing the electronics module (2). Then push up electronics module and
pull it as far as possible out of the wall-mount housing.

3.

Disconnect the sensor signal cable plug (7.1) including HistoROM/S-DAT (7.2) and
HistoROM/T-DAT (7.3) from amplifier board (7).

4.

Remove the cover (4) from the electronics compartment by removing the screws.

5.

Disconnect the ribbon cable plug (3) of the display module from amplifier board (7).

6.

Remove the boards (6, 7, 8):


Insert a thin pin into the hole (5) provided for the purpose and pull the board clear of its holder.

7.

Installation is the reverse of the removal procedure.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Trouble-shooting

2
6
4

3
7
5
8

7.1

7.2
7.3

A0014978

Fig. 37:
1
2
3
4
5
6
7
7.1
7.2
7.3
8

Endress+Hauser

Field housing: removing and installing printed circuit boards

Housing cover
Electronics module
Ribbon cable (display module)
Screws of electronics compartment cover
Aperture for installing/removing boards
Power unit board
Amplifier board
Signal cable (sensor)
HistoROM/S-DAT (sensor data memory)
HistoROM/T-DAT (transmitter data memory)
I/O board

83

Trouble-shooting

Proline t-mass 65 FOUNDATION Fieldbus

Electronics housing sensor remote version

"

Warning!
Risk of damaging electronic components (ESD protection). Static electricity can damage electronic
components or impair their operability. Use a workplace with a grounded working surface
purposely built for electrostatically sensitive devices!
If you cannot guarantee that the dielectric strength of the device can be maintained during the
following steps, then an appropriate inspection test must be carried out in accordance with the
manufacturers specifications.
When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement
to these Operating Instructions.
Caution!
Use only original Endress+Hauser parts.
Removal and installation 38
1.

Remove the safety screw (1) and remove the cover (2) from the electronics compartment.

2.

Disconnect the sensor cable plug (3).

3.

Disconnect the remote cable from the terminal block (4).

4.

Remove the two screws (5) from the printed circuit board

5.

Remove printed circuit board (6)

6.

Installation is the reverse of the removal procedure.

5
3

a0005131

Fig. 38:

Electronics compartment of the sensor housing remote version: removing and installing printed circuit board

Wire colors (when supplied by Endress+Hauser):


Terminal no. 41 = white; 42 = brown; 43 = green; 44 = yellow

84

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

9.4.2

Trouble-shooting

Replacing the device fuse

Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
The main fuse is on the power unit board.
The procedure for replacing the fuse is as follows:

"

1.

Switch off power supply.

2.

Remove the power unit board 80

3.

Remove the protection cap (1) and replace the device fuse (2).
Only use the following fuse type:
Power supply 20 to 55 V AC / 16 to 62 V DC 2.0 A slow-blow / 250 V; 5.2 20 mm
Power supply 85 to 260 V AC 0.8 A slow-blow / 250 V; 5.2 20 mm
Ex-rated devices see the Ex documentation.

4.

Installation is the reverse of the removal procedure.

Caution!
Use only original Endress+Hauser parts.

2
1
a0001148

Fig. 39:
1
2

Endress+Hauser

Replacing the device fuse on the power unit board

Protective cap
Device fuse

85

Trouble-shooting

Proline t-mass 65 FOUNDATION Fieldbus

9.5

"

Return

Caution!
Do not return a measuring device if you are not absolutely certain that all traces of hazardous
substances have been removed, e.g. substances which have penetrated crevices or diffused through
plastic.
Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be charged
to the owner-operator.
The following steps must be taken before returning a flow measuring device to Endress+Hauser,
e.g. for repair or calibration:
Always enclose a duly completed "Declaration of contamination" form. Only then can
Endress+Hauser transport, examine and repair a returned device.
Enclose special handling instructions if necessary, for example a safety data sheet as per
EC REACH Regulation No. 1907/2006.
Remove all residues. Pay special attention to the grooves for seals and crevices which could
contain residues. This is particularly important if the substance is hazardous to health, e.g.
flammable, toxic, caustic, carcinogenic, etc.

Note!
You will find a preprinted "Declaration of contamination" form at the back of these Operating
Instructions.

9.6

Disposal

Observe the regulations applicable in your country!

9.7

86

Software history

Note!
Up or downloading a software version normally requires a special service software.

Date

Software version

Changes to software

Operating Instructions

12.2010

3.00.XX

Original software

71128089/13.10

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Technical data

10

Technical data

10.1

Technical data at a glance

10.1.1

Applications

The measuring device described in these Operating Instructions is to be used only for measuring the
mass flow rate of gases (e. g. kg, Nm3 scf). At the same time, the system also measures gas
temperature. The measuring device can be configured to measure a standard range of pure gases or
gas mixtures.
Examples:
Air
Oxygen
Nitrogen
Carbon Dioxide
Argon, etc.
The use with corrosive, saturated or unclean gases should be treated with caution (contact your
Endress+Hauser sales representative). The use with unstable gases or gases not deemed to be
suitable by Endress+Hauser must be avoided. The measuring device is not designed to be used with
liquids or fluids in the liquid phase.
Resulting from incorrect use or from use other than that designated, the operational safety of the
measuring devices can be jeopardized. The manufacturer accepts no liability for damages being
produced from this.

10.1.2

Function and system design

Measuring principle

Mass flow measurement by the thermal dispersion principle.

Measuring system

The t-mass 65 flow measuring system consists of the following components:


t-mass 65 transmitter
t-mass F, t-mass I sensor
Two versions are available:
Compact version: transmitter and sensor form a single mechanical unit.
Remote version: transmitter and sensor are installed separately.

10.1.3

Input

Measured variable

Mass flow
Gas temperature
Gas heat flow

Measuring range

The measuring range is dependent upon:


Gas
Pressure
Temperature
Cross-sectional area of pipe or duct
Use of flow conditioner (t-mass F sensor)
Please refer to Applicator, the Endress+Hauser sizing and selection software, for calculation of the
measuring range.

Endress+Hauser

87

Technical data

Proline t-mass 65 FOUNDATION Fieldbus

10.1.4
Output signal

Output

Physical data transmission (Physical Layer Type):


Fieldbus interface in accordance with IEC 61158-2
Corresponds to device version type 512 of the FOUNDATION Fieldbus specification:
type 512 standard data transfer (9 mA, symmetrical), separate supply to field device (4-wire),
intrinsically safe version of the FF interface, FISCO
With integrated reverse polarity protection

Signal on alarm

Status messages as per FOUNDATION Fieldbus specification

Link Master (LM)


support

Yes

Link Master

Selectable

Basic Device

Factory setting

Device basic current

12 mA

Device starting current

<12 mA

Device error current (FDE)

0 mA

Device (lift off)


min. voltage

9 V (H1-segment)

Permissible fieldbus supply


voltage

9 to 32 V

Integrated reverse polarity


protection

Yes

ITK Version

5.0

Number of VCRs (total)

48

Number of link objects in VFD

40

Device capacitance

In accordance with IEC 60079-27, FISCO/FNICO

Galvanic isolation

All circuits for inputs, outputs and power supply are galvanically isolated from each other.

Data transmission rate

31.25 kbit/s, voltage mode

Signal coding

Manchester II

88

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Bus times

Block information,
execution time

Output data

Min. idle time between two telegrams:


MIN_INTER_PDU_DELAY = 6 octet time (transfer time per octet)

Block

Base index

Execution time [ms]

Functionality

Resource Block

400

Enhanced

"Flow" Transducer Block

1400

Vendor specific

"Diagnosis" Transducer Block

1600

Vendor specific

"Display" Transducer Block

1800

Vendor specific

"Totalizer" Transducer Block

1900

Vendor specific

"Heat Flow" Transducer Block

2700

Vendor specific

Analog Input Function Block 1

500

20

Standard

Analog Input Function Block 2

550

20

Standard

Analog Input Function Block 3

600

20

Standard

Analog Input Function Block 4

650

20

Standard

Analog Input Function Block 5

700

20

Standard

Analog Output Function Block (AO)

2300

20

Standard

Discrete Output Function Block (DO)

900

20

Standard

PID Function Block (PID)

1000

50

Standard

Arithmetic Function Block (ARTH)

1100

20

Standard

Input Selector Function Block (ISEL)

1150

20

Standard

Signal Characterizer Function Block (CHAR)

1200

20

Standard

Integrator Function Block (INTG)

1250

25

Standard

Transducer Blocks / Analog Input Function Blocks


Block

Process variable

Channel parameter
(AI Block)

"Flow" Transducer Block

Mass flow

Calculated volume flow

Temperature

Heat flow

53

Totalizer 1

Totalizer 2

"Totalizer" Transducer Block

Endress+Hauser

Technical data

89

Technical data

Proline t-mass 65 FOUNDATION Fieldbus

10.1.5

Power supply

Electrical connections

27

Supply voltage

85 to 260 V AC, 45 to 65 Hz
20 to 55 V AC, 45 to 65 Hz
16 to 62 V DC

Cable entry

Power supply and signal cables (inputs/outputs):


Cable entry M20 1.5 (8 to 12 mm (0.31 to 0.47 inch))
Threads for cable entries, " NPT, G "
Connecting cable for remote version:
Cable entry M20 1.5 (8 to 12 mm (0.31 to 0.47 inch))
Threads for cable entries, " NPT, G "

Cable specifications
(remote version)

30

Power consumption

AC: 85 to 260 V = 18.2 W ; 20 to 55 V = 14 W ; (including sensor)


DC: 8 W (including sensor)

Power supply failure

Lasting min. 1 power cycle:


EEPROM/HistoROM T-DAT saves measuring system data if power supply fails.
HistoROM S-DAT is an exchangeable data storage chip with sensor specific data: (pipe type,
nominal diameter, serial number, flow conditioner, zero point, etc).
Totalizer stops at the last value determined

Potential equalisation

No measures necessary.
For devices in hazardous areas please refer to the additional Ex documentation.

10.1.6

Performance characteristics

Calibration reference
conditions

Accredited according to ISO/IEC 17025


Traceable to National Standards
Calibration gas: air
Temperature controlled to 24 C 0.5 C (75.2 F 0.9 F) at atmospheric pressure
Humidity controlled < 40% RH

Maximum measured error

t-mass 65F:
1.5 % of reading for 100 % to 10 % of full scale (at reference conditions)
0.15 % of full scale for 10 % to 1 % of full scale (at reference conditions)
t-mass 65I:
1.0% of reading
0.5% of full scale (at reference conditions)

Repeatability

0.4 % of reading for velocities above 1.0 m/s (3.3 ft/s)

Influence of medium pressure


(Pressure co-efficient)

Air: 0.35% per bar (0.02% per psi) of process pressure change
Other gases: on request

Response time

Typically less than 2 seconds for 63 % of a given step change (in either direction).

90

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

10.1.7

Technical data

Operating conditions: Installation

Installation instructions

12

Inlet and outlet runs

15

Length of connecting cable

Max. 100 m (328 feet), remote version

System pressure

12

10.1.8
Ambient temperature

Operating conditions: Environment

Standard: 20 to +60 C (4 to +140 F)


Optional: 40 to +60 C (-40 to +140F)

Note!
Install the device in a shady location. Avoid direct sunlight, particularly in warm climatic regions.
(A protective sun cover is available on request)
At ambient temperatures below 20 C (4 F) the readability of the display may be impaired.

Storage temperature

40 to +80 C (40 to +176 F), recommended +20 C (+68 F)

Degree of protection

Standard: IP 67 (NEMA 4X) for transmitter and sensor

Shock resistance

According to IEC 60068-2-31

Vibration resistance

Acceleration up to 1 g, 10 to 150 Hz, following IEC 60068-2-6

Electromagnetic compatibility
(EMC)

To IEC/EN 61326 and NAMUR recommendation NE 21

Endress+Hauser

91

Technical data

Proline t-mass 65 FOUNDATION Fieldbus

10.1.9
Medium temperature range

Operating conditions: Process

Sensor
t-mass F:
40 C to +100 C (40 F to +212 F)
t-mass I:
40 C to +130 C (40 F to +266 F)
Seals t-mass F
O-rings:
Viton FKM 20C+100C (4F+212F)
Kalrez 20C+100C (4F+212F)
EPDM 40C+100C (40F+212F)
Bushing:
PEEK, PVDF 40C+100C (40F+212F)
Seals t-mass I
Bonded seals:
Kalrez 20C+130C (4F+266F)
EPDM 40C+130C (40F+266F)
Nitrile 35C+130C (31F+266F)
Ferrule:
PEEK, PVDF 40C+130C (40F+266F)

Pressure loss

Negligible (without flow conditioner).


Refer to Applicator for the precise calculation 66

Medium pressure range


(nominal pressure)

t-mass F:
0.5 to 40 bar gauge (7.25 to 580 psi gauge)
t-mass I:
0.5 to 20 bar gauge (7.25 to 290 psi gauge)

Limiting medium pressure


range (rated pressure)

The material load diagrams (pressure-temperature diagrams) for the process connections are
provided in the separate "Technical Information" document on the device in question. This can be
downloaded as a PDF file from www.endress.com.
A list of the "Technical Information" documents: 97

Flow limit

See "Measuring range" section 87.


The velocity in the measuring tube should not exceed 130 m/s (427 ft/s).

Process conditions for Hot tap

The Hot tap is permitted for use only with non-toxic, innocuous gases classified as "Group II" in
accordance with the European directive 67/548/EWG art. 2.
Medium pressure version
Max. process pressure: 20 bar (290 psig)
Max. extraction press: 16 bar (230 psig)
Max. extraction temperature: +50C (+122F)
Min. sensor length: 435 mm (17 inch)
Low pressure version
Max. process pressure: 20 bar (290 psig)
Max. extraction press: 4,5 bar (65 psig)
Max. extraction temperature: +50C (+122F)
Min. sensor length: 435 mm (17 inch)

92

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Technical data

10.1.10 Mechanical construction


Design / dimensions

Dimensions and the fitting lengths of the transmitter and sensor are provided in the separate
"Technical Information" document on the device in question. This can be downloaded as a PDF file
from www.endress.com.
A list of the "Technical Information" documents: 97

Weight

Compact version: see table below


Remote version
Sensor: see table below
Wall-mount housing: 5 kg (11 lb)
Weight (SI units)
t-mass F* / DN

15

25

40

50

80

100

Compact version

7.5

8.0

12.5

12.5

18.7

27.9

Remote version (sensor only)

5.5

6.0

10.5

10.5

16.7

25.9

t-mass I / sensor length [mm]

235

335

435

608

Compact version

6.4

6.6

7.0

7.4

Remote version (sensor only)

4.4

4.6

5.0

5.4

Weight dimensions in [kg].


* For flanged versions, all values (weight) refer to devices with EN/DIN PN 40 flanges.
Weight (US units)
t-mass F* / DN [inch]

"

1"

1"

2"

3"

4"

Compact version

16.5

17.6

27.5

27.5

41.2

61.5

Remote version (sensor only)

12.1

13.2

23.1

23.1

36.7

57.1

9.25"

13.2"

17.1"

24.0"

Compact version

t-mass I / sensor length [inch]

14.1

14.5

15.4

16.3

Remote version (sensor only)

9.7

10.1

11.0

11.9

Weight dimensions in [lb].


* For flanged versions, all values (weight) refer to devices with Cl 150 flanges.
Material

Transmitter housing
Compact housing: powder coated die-cast aluminium
Wall-mount housing: powder coated die-cast aluminium
Remote field housing: powder coated die-cast aluminium
Connection housing, sensor (remote version)
Powder coated die-cast aluminium

Endress+Hauser

93

Technical data

Proline t-mass 65 FOUNDATION Fieldbus

t-mass F sensor
Sensor body:
DN 15 to 25 (DN " to DN 1"): stainless steel cast CF3M-A351
DN 40 to 100 (DN 1 " to DN 4"): 1.4404 to EN10216-5 and 316/316L to A312
Flanges (process connections):
According to EN 1092-1 (DIN 2501/DIN 2512N) / ANSI B16.5 / JIS B2220
stainless steel 1.4404 to EN 10222-5 and 316L/316 to A182
Transducer body:
1.4404 to EN10272 and 316L to A479
Alloy C22 (2.4602) and UNS N06022 to B574
Transducer elements:
1.4404 to EN10217-7 and 316L to A249 or
1.4404 to EN 10216-5 and 316L to A213
Alloy C22 (2.4602) and UNS N06022 to B626
Bushing:
PEEK GF30, PVDF
O-ring seals:
EPDM, Kalrez 6375, Viton FKM
t-mass I sensor
Insertion tube:
Sensor length 235 (9"), 335 (13"), 435 (17"), 608 (24")
1.4404 to EN 10216-5 and 316/316L to A312
Transducer body:
1.4404 to EN10272 and 316L to A479
Alloy C22 (2.4602) and UNS N06022 to B574
Transducer elements:
1.4404 to EN10217-7 and 316L to A249 or
1.4404 to EN 10216-5 and 316L to A213
Alloy C22 (2.4602) and UNS N06022 to B626
Protection gaurd:
1.4404 to EN 10088-1 and EN 10088-2 + 2B and 316L to A666
Compression fitting:
1.4404 to EN 10272 and 316/316L to A479
Ferrules:
PEEK 450G, PVDF
Bonded seals:
EPDM, Kalrez 6375, Nitrile and 316/316L (outer ring)
Hot tap
Lower tube section:
1.4404 to EN 10272 and 316/316L to A479
Upper tube section:
1.4404 to EN 10216-5 and 316/316L to A312
Ball valve:
CF3M and CF8M
Seal:
PTFE

94

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Technical data

10.1.11 Human interface


Display elements

Liquid crystal display: illuminated, two lines with 16 characters per line
Selectable display of different measured values and status variables
At ambient temperatures below 20 C (4 F) the readability of the display may be impaired.

Operating elements

Local operation with push buttons (, +, E)


Quick Setup menus for straight forward commissioning

Languages

English, German, French, Spanish, Italian, Dutch, Norwegian, Finnish, Swedish, Portuguese,
Polish, Czech

10.1.12 Certificates and approvals


CE mark

The measuring system is in conformity with the statutory requirements of the EC Directives.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.

C-Tick mark

The measuring system meets the EMC requirements of the Australian Communications and Media
Authority (ACMA).

Ex approval

Information about currently available Ex versions (ATEX, FM, CSA) can be supplied by your
Endress+Hauser representative on request. All explosion protection data are given in a separate
documentation which is available upon request.
Hazardous area
II2GD / Cl. 1 Div. 1

Safe area

II3G / Cl. 1 Div. 2

p cover tight w
Kee ircuits are ali hile
ve
c

over tight wh
i
ep c
Ke ircuits are alive le
c

t unter Spannu
ng
Nich ffnen

vri
pas ou r lappa
Ne sous tension reil
p cover tight w
Kee ircuits are ali hile
ve
c

over tight wh
i
ep c
Ke ircuits are alive le
c

t unter Spannu
ng
Nich ffnen

vr
pas ou ir lapp
Ne sous tension areil
Esc

EX

EX
a0005128-en

Fig. 40:

Endress+Hauser

Example of t-mass devices in the hazardous area (Example t-mass 65F)

95

Technical data

Pressure measuring device


approval

Proline t-mass 65 FOUNDATION Fieldbus

The measuring devices can be ordered with or without PED (Pressure Equipment Directive). If a
device with PED is required, this must be ordered explicitly. For devices with nominal diameters
less than or equal to DN 25 (1"), this is neither possible nor necessary.
With the identification PED/G1/III on the sensor nameplate, Endress+Hauser confirms
conformity with the "Basic safety requirements" of Appendix I of the Pressure Equipment
Directive 97/23/EC.
Devices with this identification (with PED) are suitable for the following types of fluid:
Fluids of Group 1 and 2 with a steam pressure of greater or less than 0.5 bar (7.3 psi)
Unstable gases
Devices without this identification (without PED) are designed and manufactured according to
good engineering practice. They correspond to the requirements of Art. 3, Section 3 of the
Pressure Equipment Directive 97/23/EC. Their application is illustrated in Diagrams 6 to 9 in
Appendix II of the Pressure Equipment Directive 97/23/EC.

Oxygen service

We certify that the wetted parts of the flow sensor have been degreased in accordance with British
Oxygen Company (BOC) specification 0000-N-S-430-00-01 and BS IEC 60877:1999.
After final degreasing there shall be less than 100 milligram/m (0.01 milligram/cm) of oil/grease
contamination on the degreased surface of the component.

Other standards and


guidelines

BS IEC 60877:1999
Procedures for ensuring the cleanliness of industrial-process measurement and control equipment
in oxygen service.
EN 60529
Degrees of protection by housing (IP code)
EN 61010-1
Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory
Procedures.
IEC/EN 61326
"Emission in accordance with requirements for Class A". Electromagnetic compatibility (EMCrequirements).
EN 91/155/EEC
Saftey Data Sheets Directive.
ISO/IEC 17025
General requirements for the competence of testing and calibration laboratories.
ISO 14511
Measurement of fluid flow in closed conduits - Thermal mass flowmeters.
NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.
NAMUR NE 43
Standardisation of the signal level for the breakdown information of digital transmitters with
analogue output signal.
NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics

96

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Technical data

10.1.13 Ordering information


Your Endress +Hauser representative can provide detailed ordering information and information on
the order codes on request.

10.1.14 Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the
transmitter and the sensor 65

10.1.15 Documentation
Technical Information t-mass 65F, 65I (TI00069D/06)
Description of Device Functions t-mass 65 (BA00135D/06)
Supplementary documentation on Ex-ratings: ATEX, FM, CSA, IECEx, NEPSI
Flow measuring technology (FA00005D/06/)

Endress+Hauser

97

Proline t-mass 65 FOUNDATION Fieldbus

Index

Index
A
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 87
Applicator (selection and sizing software) . . . . . . . . . . . . . 66
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10, 95

C
Cable entry
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Cable length (remote version). . . . . . . . . . . . . . . . . . . . . . 91
Cable specifications (FOUNDATION Fieldbus) . . . . . . . . . 27
Cable specifications (remote version) . . . . . . . . . . . . . . . . 30
Calibration
In-situ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Reference conditions. . . . . . . . . . . . . . . . . . . . . . . . . . 90
Calorific value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
CE mark (declaration of conformity) . . . . . . . . . . . . . . . . . 10
Certificates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10, 95
CFF file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Cleaning
External cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Pipe cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Transducer cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Code entry (function matrix) . . . . . . . . . . . . . . . . . . . . . . 39
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Initial operation (FF interface) . . . . . . . . . . . . . . . . . . . 45
Connection
See Electrical connection
Current output
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

D
Data back-up (of device data with T-DAT) . . . . . . . . . . . . 60
Declaration of conformity (CE mark). . . . . . . . . . . . . . . . . 10
Degree of protection. . . . . . . . . . . . . . . . . . . . . . . . . . 34, 91
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 87
Device description files . . . . . . . . . . . . . . . . . . . . . . . . 4142
Device designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 87
Device errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Device functions
See Function description
Display
Display and operating elements . . . . . . . . . . . . . . . . . . 37
Turning the display . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

E
Electrical connection
Cable specifications (remote version) . . . . . . . . . . . . . .
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error messages
Confirming error messages . . . . . . . . . . . . . . . . . . . . .
Process errors (application errors) . . . . . . . . . . . . . . . .
98

30
34
30
77

System errors (device errors) . . . . . . . . . . . . . . . . . . . .


Error types (system and process errors) . . . . . . . . . . . . . . .
European Pressure Equipment Directive . . . . . . . . . . . . . .
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

71
40
96
95
63

F
FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fieldcheck (tester and simulator). . . . . . . . . . . . . . . . . . . .
Flow conditioner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FOUNDATION Fieldbus
Cable specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration program . . . . . . . . . . . . . . . . . . . . . . . .
configuration programs . . . . . . . . . . . . . . . . . . . . . . . .
device certification . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hardware write protection . . . . . . . . . . . . . . . . . . . . .
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . .
Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function description
See "Description of Device Functions" manual
Function groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function matrix (Brief operating instructions) . . . . . . . . . .
Fuse, replacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

41
66
16
27
41
41
10
43
34
44

38
38
85

G
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Gas analyzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Gas compensation input . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Gas mixture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 87
Gas pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Gas programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Gas properties. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 87
Gewicht . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

H
Hardware write protection
FOUNDATION Fieldbus . . . . . . . . . . . . . . . . . . . . . . . 43
Hazardous area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Hazardous substances . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 86
Heat flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
HOME position (operating mode) . . . . . . . . . . . . . . . . . . . 37

I
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Insertion sensor
Insertion depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
In-situ calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation instructions. . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the wall-mount transmitter housing . . . . . . . . . .

11
91
19
19
64
91
24

J
Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

40
77
Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Index

L
Language groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Length of connecting cable . . . . . . . . . . . . . . . . . . . . . . . . 91
Limiting flow
See Measuring range
Local display
See Display

M
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Measuring principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 87
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Medium pressure (Influence) . . . . . . . . . . . . . . . . . . . . . . . 90
Medium pressure range . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Medium pressure range (nominal pressure) . . . . . . . . . . . . 92
Medium temperature range . . . . . . . . . . . . . . . . . . . . . . . . 92
Mounting
Insertion sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
See Installation conditions
Mounting sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

N
Nameplate
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

O
Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Operation
device description files . . . . . . . . . . . . . . . . . . . . . . . . . 42
Display and operating elements . . . . . . . . . . . . . . . . . . 37
Fieldcare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
FOUNDATION Fieldbus configuration programs . . . . . 41
Function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Order code
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Oxygen service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

P
PED (Pressure Equipment Directive) . . . . . . . . . . . . . . . . .
Pipe cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipework requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .
Post connection check. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Post-installation check (checklist) . . . . . . . . . . . . . . . . . . .
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power supply (supply voltage) . . . . . . . . . . . . . . . . . . . . . .
Pressure co-efficient . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure Equipment Directive (PED) . . . . . . . . . . . . . . . . .
Pressure loss (formulas, pressure loss diagrams) . . . . . . . . .
Pressure measuring device approval . . . . . . . . . . . . . . . . . .
Endress+Hauser

96
63
13
26
26
90
90
90
96
92
96

Printed circuit boards (installation/removal)


Field housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80, 84
Wall-mount housing. . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Process error
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Process error messages . . . . . . . . . . . . . . . . . . . . . . . . . 77
Process errors without messages . . . . . . . . . . . . . . . . . . . . 77
Programming mode
Enabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Pulsating flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Q
Quick setup
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data back-up (of device data with T-DAT) . . . . . . . . . .
Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

52
60
55
58
57
54

R
Recalibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Remote transmitter (wall mount housing) . . . . . . . . . . . . . 24
Removing the insertion sensor . . . . . . . . . . . . . . . . . . . . . . 22
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 86
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Replacement
Printed circuit boards (installation/removal) . . . 80, 82, 84
Replacing
Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Returning devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 86

S
Safety icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
S-DAT (HistoROM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Seals
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Medium temperature range . . . . . . . . . . . . . . . . . . . . . 92
Replacing, replacement seals. . . . . . . . . . . . . . . . . . . . . 64
Sensor installation
See Installation conditions
Sensor setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Software
Amplifier display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Versions (history) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Standards, guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Storage temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Supplementary Ex documentation . . . . . . . . . . . . . . . . . . . . 6
Supply voltage (power supply) . . . . . . . . . . . . . . . . . . . . . . 90
System error
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
System error messages . . . . . . . . . . . . . . . . . . . . . . . . . 71
System files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
99

Proline t-mass 65 FOUNDATION Fieldbus

Index

T
T-DAT (HistoROM)
Save/load (data back-up, e.g. for replacing devices) . . .
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature range
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Medium temperature range . . . . . . . . . . . . . . . . . . . . .
Temperature ranges
Ambient temperature range . . . . . . . . . . . . . . . . . . . . .
Medium temperature range . . . . . . . . . . . . . . . . . . . . .
Storage temperature. . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal assignment
FOUNDATION Fieldbus . . . . . . . . . . . . . . . . . . . . . . .
Thermal insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transmitter
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the wall-mount transmitter housing. . . . . . . .
Turning the field housing (aluminium) . . . . . . . . . . . . .
Transporting the sensor . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting instructions . . . . . . . . . . . . . . . . . . . . . . .

60
87
91
92
91
92
91
34
18
63
31
24
23
11
67

V
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

W
Wall-mount housing, installing . . . . . . . . . . . . . . . . . . . . .
Wechselarmatur (Hot tap) . . . . . . . . . . . . . . . . . . . . . . . . .
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Welding socket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring
See Electrical connection
Write protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24
92
93
19

43

Z
Zero point adjustment . . . . . . . . . . . . . . . . . . . . . . . . . 6162

100

Endress+Hauser

Declaration of Hazardous Material and De-Contamination


Erklrung zur Kontamination und Reinigung
Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA#
clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
Bitte geben Sie die von E+H mitgeteilte Rcklieferungsnummer (RA#) auf allen Lieferpapieren an und vermerken Sie diese
auch auen auf der Verpackung. Nichtbeachtung dieser Anweisung fhrt zur Ablehnung ihrer Lieferung.

RA No.

Because of legal regulations and for the safety of our employees and operating equipment, we need the "Declaration of Hazardous Material
and De-Contamination", with your signature, before your order can be handled. Please make absolutely sure to attach it to the outside of the
packaging.
Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, bentigen wir die unterschriebene
"Erklrung zur Kontamination und Reinigung", bevor Ihr Auftrag bearbeitet werden kann. Bringen Sie diese unbedingt auen an der
Verpackung an.
Serial number
Seriennummer ________________________

Type of instrument / sensor


Gerte-/Sensortyp
____________________________________________

Used as SIL device in a Safety Instrumented System / Einsatz als SIL Gert in Schutzeinrichtungen
Process data/Prozessdaten

Pressure / Druck
_____ [psi] _____ [ Pa ]
Viscosity /Viskositt _____ [cp] _____ [mm2/s]

Temperature / Temperatur_____ [F] _____ [C]


Conductivity / Leitfhigkeit ________ [S/cm]

Medium and warnings


Warnhinweise zum Medium
Medium /concentration Identification flammable
CAS No.
Medium /Konzentration
entzndlich

toxic
giftig

corrosive
tzend

harmful/
irritant
gesundheitsschdlich/
reizend

other *
harmless
sonstiges* unbedenklich

Process
medium
Medium im
Prozess
Medium for
process cleaning
Medium zur
Prozessreinigung
Returned part
cleaned with
Medium zur
Endreinigung
* explosive; oxidising; dangerous for the environment; biological risk; radioactive
* explosiv; brandfrdernd; umweltgefhrlich; biogefhrlich; radioaktiv
Please tick should one of the above be applicable, include safety data sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen.
Description of failure / Fehlerbeschreibung __________________________________________________________________________
______________________________________________________________________________________________________________
______________________________________________________________________________________________________________
Company data /Angaben zum Absender

P/SF/Konta XIV

Company /Firma ___________________________________


_________________________________________________
Address / Adresse
_________________________________________________
_________________________________________________

Phone number of contact person /Telefon-Nr. Ansprechpartner:


____________________________________________
Fax / E-Mail ____________________________________________
Your order No. / Ihre Auftragsnr. ____________________________

We hereby certify that this declaration is filled out truthfully and completely to the best of our knowledge.We further certify that the returned
parts have been carefully cleaned. To the best of our knowledge they are free of any residues in dangerous quantities.
Wir besttigen, die vorliegende Erklrung nach unserem besten Wissen wahrheitsgetreu und vollstndig ausgefllt zu haben. Wir besttigen
weiter, dass die zurckgesandten Teile sorgfltig gereinigt wurden und nach unserem besten Wissen frei von Rckstnden in gefahrbringender Menge sind.

(place, date / Ort, Datum)

Name, dept./Abt. (please print /bitte Druckschrift)

Signature / Unterschrift

www.endress.com/worldwide

BA00134D/06/EN/13.10
71128089
FM+SGML6.0 ProMoDo

Description of device functions

Proline t-mass 65
FOUNDATION Fieldbus
Thermal mass flow measuring system

BA00135D/06/EN/13.10
71128091
Valid as of version
V 3.00.XX (Device software)

Proline t-mass 65 FOUNDATION Fieldbus

Table of contents for local operation

Table of contents for local operation


1

The function matrix: layout and use . . . 4

Illustration of the function matrix. . . . . 5

MEASURING VALUES . . . . . . . . . . . . . 7

SYSTEM UNITS . . . . . . . . . . . . . . . . . . 8

QUICK SETUP . . . . . . . . . . . . . . . . . . 12

OPERATION . . . . . . . . . . . . . . . . . . . 23

USER INTERFACE . . . . . . . . . . . . . . . 25

TOTALIZER 1/2. . . . . . . . . . . . . . . . . 28

HANDLING TOTALIZER . . . . . . . . . . 30

10

COMMUNICATION. . . . . . . . . . . . . . 31

11

PROCESS PARAMETER . . . . . . . . . . . 33

12

GAS . . . . . . . . . . . . . . . . . . . . . . . . . . 37

13

HEAT FLOW . . . . . . . . . . . . . . . . . . . 42

14

SYSTEM PARAMETER . . . . . . . . . . . . 44

15

SENSOR DATA . . . . . . . . . . . . . . . . . . 45

16

SUPERVISION . . . . . . . . . . . . . . . . . . 49

17

SIMULATION SYSTEM. . . . . . . . . . . . 50

18

SENSOR VERSION . . . . . . . . . . . . . . . 51

19

AMPLIFIER VERSION . . . . . . . . . . . . 52

20

Factory settings . . . . . . . . . . . . . . . . . 53

Index function matrix . . . . . . . . . . . . . . . . . 57

Endress+Hauser

The function matrix: layout and use

Proline t-mass 65 FOUNDATION Fieldbus

The function matrix: layout and use

The function matrix is a two-level construction: the groups form one level and the groups' functions
the other. The groups are the highest-level grouping of the control options for the measuring device.
A number of functions is assigned to each group. You select a group in order to access the individual
functions for operating and configuring the measuring device.
An overview of all the groups available is provided in the table of contents on Page 3 and in the
graphic representation of the function matrix on Page 6. Page 6 also contains an overview of all the
functions available with the page references to the specific function description. A description of the
individual functions is provided on page 7 and onwards.

Esc

p
m

Esc

>3s

Esc

o
E

Esc

E
E
E
E
A0001142

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

2
Groups/function groups
MEASURING VALUES

Illustration of the function matrix

Illustration of the function matrix

Functions
7

MASS FLOW

CORRECTED VOLUME
FLOW

HEAT FLOW

TEMPERATURE

UNIT MASS FLOW

UNIT MASS

UNIT CORRECTED
VOLUME FLOW

UNIT CORRECTED
VOLUME

UNIT CALORIFIC VALUE


MASS

UNIT CALORIFIC VALUE


CORRECTED VOLUME

UNIT HEAT FLOW

UNIT HEAT

UNIT PRESSURE

UNIT TEMPERATURE

UNIT DENSITY

UNIT LENGTH

QUICK SETUP
COMMISSIONING

QUICK SETUP SENSOR

QUICK SETUP GAS

QUICK SETUP PRESSURE

QUICK SETUP HEAT FLOW

T-DAT SAVE/LOAD

LANGUAGE

ACCESS CODE

DEFINE PRIVATE CODE

STATUS ACCESS

ASSIGN LINE 1

ASSIGN LINE 2

100% VALUE LINE 1

100% VALUE LINE 2

FORMAT

DISPLAY DAMPING

CONTRAST LCD

BACKLIGHT

ASSIGN TOTALIZER

ASSIGN GAS GROUP

SUM

OVERFLOW

UNIT TOTALIZER

RESET TOTALIZER

30

RESET ALL TOTALIZERS

FAILSAFE MODE

31

WRITE PROTECTION

SIMULATION

DEVICE PD-TAG

MANUFACTURER ID

DEVICE TYPE

SERIAL NUMBER

DEVICE REVISION

DD REVISION

BLOCK SELECTION

OUT VALUE

IN VALUE

CASCADE_IN VALUE

PROCESS PRESSURE 1

PROCESS PRESSURE 2

PROCESS PRESSURE

REFERENCE PRESSURE

REFERENCE
TEMPERATURE

REFERENCE DENSITY

NET CALORIFIC VALUE

GROSS CALORIFIC VALUE

MOLE % GAS 1

ASSIGN LOW FLOW CUT


OFF

ON-VALUE LOW FLOW


CUT OFF

OFF-VALUE LOW FLOW


CUT OFF

ZERO POINT ADJUST

INSTALLATION FACTOR

SELECT GROUP

ANALYZER INPUT

NUMBER OF GASES

GAS TYPE 1

MOLE % GAS 1

DESCRIPTION

CORRECTION FACTOR

REFERENCE DENSITY

GAS TYPE 2 to 8

MOLE % GAS 2 to 8

CHECK VALUES

SAVE CHANGES

SYSTEM UNITS

QUICK SETUP

12

OPERATION

23

USER INTERFACE

ACCESS CODE COUNTER

25

TEST DISPLAY

TOTALIZER 1/2

28

HANDLING TOTALIZER

COMMUNICATION

PROCESS PARAMETER

33

GAS

Endress+Hauser

37

Illustration of the function matrix

Groups/function groups
HEAT FLOW

Functions
42

CALORIFIC VALUE TYPE

MODE 1

HEATING VALUE 1

MODE 2

HEATING VALUE 2

REFERENCE
COMBUSTION
TEMPERATURE

44

POSITIVE ZERO RETURN

FLOW DAMPING

45

PIPE TYPE

PIPE STANDARD

NOMINAL DIAMETER

OUTER DIAMETER

WALL THICKNESS

INTERNAL DIAMETER

INTERNAL HEIGHT

INTERNAL WIDTH

MOUNTING

MOUNTING SET LENGTH

INSERTION DEPTH

ZERO POINT

FLOW CONDITIONER

CALIBRATION DATE

ACTUAL SYSTEM
CONDITION

PREVIOUS SYSTEM
CONDITION

ALARM DELAY

SYSTEM RESET

OPERATION HOURS

HOURS SINCE RESET

50

SIMULATION FAILSAFE
MODE

SIMULATION
MEASURAND

VALUE SIMULATION
MEASURAND

51

SENSOR TYPE

SERIAL NUMBER

TRANSDUCER SERIAL
NUMBER

SOFTWARE REVISION
NUMBER S-DAT

PRE-AMPLIFIER SOFTWARE REVISION NUMBER

PRE-AMPLIFIER HARDWARE REVISION NUMBER

DEVICE SOFTWARE

HARDWARE REVISION
NUMBER AMPLIFIER

SOFTWARE REVISION
NUMBER AMPLIFIER

SOFTWARE REVISION
NUMBER T-DAT

I/O MODULE TYPE

SOFTWARE REVISION
NUMBER I/O MODULE

SYSTEM PARAMETER

Proline t-mass 65 FOUNDATION Fieldbus

SENSOR DATA

SUPERVISION

49

SIMULATION SYSTEM

SENSOR VERSION

AMPLIFIER VERSION

52

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

MEASURING VALUES

MEASURING VALUES

Function description, MEASURING VALUES group


Note!
!
The engineering unit of the measured variable displayed here is configured in the SYSTEM UNITS group ( 8)
MASS FLOW

Description
The currently measured mass flow appears on the display.
Display
5-digit floating-point number, including unit
e.g. 462.87 kg/h; 731.63 lb/min

CORRECTED VOLUME
FLOW

Description
The calculated corrected volume flow appears on the display.
The corrected volume flow is calculated from the measured mass flow and the reference
density of the gas.
Display
5-digit floating-point number, including unit
e.g. 104.97 Nm3/h; 110.73 Sm3/h; etc.

HEAT FLOW

Description
The calculated heat flow appears on the display.
Display
5-digit floating-point number, including unit,
(e.g. 175.00 kJ/h; 50.000 kBtu/h; etc.)

TEMPERATURE

Description
The currently measured temperature appears on the display.
Display
5-digit fixed-point number, incl. unit and sign
e.g. 23.4 C, 160.0 F, 295.4 K

Endress+Hauser

SYSTEM UNITS

Proline t-mass 65 FOUNDATION Fieldbus

SYSTEM UNITS

Function description, SYSTEM UNITS group


UNIT MASS FLOW

Description
For selecting the unit required and displayed for the mass flow.
The unit you select here is also valid for:
Low flow cut off
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options
SI:
Gram g/time unit
Kilogram kg/time unit
Metric ton t/time unit
US:
Ounce oz/time unit
Pound lb/time unit
Ton ton/time unit
Factory setting
kg/h or lb/h (country dependent 53)

UNIT MASS

Description
For selecting the unit required and displayed for the mass.
Options
SI:
Gram g
Kilogram kg
Metric ton t
US:
Ounce oz
Pound lb
Ton ton
Factory setting
kg or lb (country dependent 53)

UNIT CORRECTED
VOLUME FLOW

Description
For selecting the unit required and displayed for the corrected volume flow.
The unit you select here is also valid for:
Low flow cut off
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options
SI:
Norm cubic meter Nm/time unit
Norm liter Nl/time unit
US:
Standard cubic meter Sm/time unit
Standard cubic feet Scf/time unit
Factory setting
Nm/h or Sm/h (country dependent 53)

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

SYSTEM UNITS

Function description, SYSTEM UNITS group


UNIT CORRECTED
VOLUME

Description
For selecting the unit required and displayed for the corrected volume.
Options
SI:
Norm cubic meter Nm
Norm liter Nl
US:
Standard cubic meter Sm
Standard cubic feet Scf
Factory setting
Nm or Sm (country dependent 53)

UNIT CALORIFIC
VALUE MASS

Description
For selecting the unit required and displayed for the gross/net calorific value.
Options (SI units)
kJ/kg
MJ/kg
kWh/kg
MWh/kg
kcal/kg
Mcal/kg
Options (US units)
Btu/lb
kBtu/lb
Factory setting
MJ/kg or kBtu/lb (country dependent 53)

UNIT CALORIFIC
VALUE CORRECTED
VOLUME

Description
For selecting the unit required and displayed for the calorific value based on the corrected
volume.
Options (SI units)
kJ/Nm
MJ/Nm
kWh/Nm
MWh/Nm
kcal/Nm
Mcal/Nm
Options (US units)
kJ/Sm
MJ/Sm
kWh/Sm
MWh/Sm
kcal/Sm
Mcal/Sm
Btu/Scf
kBtu/Scf
Factory setting
MJ/Nm or kBtu/Scf (country dependent 53)

Endress+Hauser

SYSTEM UNITS

Proline t-mass 65 FOUNDATION Fieldbus

Function description, SYSTEM UNITS group


UNIT HEAT FLOW

Description
For selecting the unit required and displayed for the heat flow.
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options (SI unit)
kW
MW
kJ/time unit
MJ/time unit
GJ/time unit
kcal/time unit
Mcal/time unit
Gcal/time unit
Options (US unit)
tons
kBtu/time unit
MBtu/time unit
GBtu/time unit
Factory setting
kW or kBtu/h (country dependent 53)

UNIT HEAT

Description
For selecting the unit required and displayed for the heat.
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options (SI units)
kWh
MWh
kJ
MJ
GJ
kcal
Mcal
Gcal
Options (US units)
tonh
kBtu
MBtu
GBtu
Factory setting
kWh or kBtu (country dependent 53)

UNIT PRESSURE

Description
Use this function to select the unit for pressure.
The unit you select here is also valid for:
Process pressure (see PROCESS PARAMETER group, 33)
Reference pressure (see PROCESS PARAMETER group, 33)
Options
bar a (bar absolute)
psi a (pounds per square inch absolute)
kPa a (kilopascal absolute)
mmHg 0C a (millimeter mercury absolute)
inHg 32F a (inch mercury absolute)
mmH2O 4C a (millimeter water absolute)
inH2O 39F a (inch water absolute)
kg/cm2 a (kilogram per centimeter squared absolute)
Factory setting
bar a or psi a (country dependent 53)

10

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

SYSTEM UNITS

Function description, SYSTEM UNITS group


UNIT TEMPERATURE

Description
For selecting the unit required and displayed for the temperature.
Options
C (CELSIUS)
K (KELVIN)
F (FAHRENHEIT)
R (RANKINE)
Factory setting
C or F (country dependent 53)

UNIT DENSITY

Description
For selecting the unit required and displayed for the calculated gas density at process
conditions. The unit you select here is also valid for:
Reference density (see PROCESS PARAMETER group, 34)
Options
SI:
g/cm
g/cc
kg/dm
kg/l
kg/m
US:
lb/ft
Factory setting
kg/m or lb/ft (country dependent 53)

UNIT LENGTH

Prerequisite
This function is only available for the insertion sensor (t-mass 65I)
Description
For selecting the unit of length required and displayed for the pipe internal diameter or
the inner dimensions of rectangular ducts (see SENSOR DATA function group 46).
Options
MILLIMETER
INCH
Factory setting
MILLIMETER or INCH (country dependent 53)

Endress+Hauser

11

QUICK SETUP

Proline t-mass 65 FOUNDATION Fieldbus

QUICK SETUP

Function description, QUICK SETUP group


QUICK SETUP
COMMISSIONING

Description
Starts the Quick Setup menu for commissioning.
For a flowchart of the QUICK SETUP COMMISSIONING: 14
Options
NO
YES
Factory setting
NO

QUICK SETUP SENSOR

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
Description
Use this function to start the application-specific setup to calculate the insertion depth for
the insertion sensor.
For a flowchart of the QUICK SETUP SENSOR: 16:
Options
NO
YES
Factory setting
NO

QUICK SETUP GAS

Description
Use this function to start the application-specific setup for programming the gas or gas
mixture.
For a flowchart of the QUICK SETUP GAS: 17.
Options
NO
YES
Factory setting
NO

QUICK SETUP
PRESSURE

Description
Use this function to start the application-specific setup for programming the process
pressure for each gas group.
For a flowchart of the QUICK SETUP PRESSURE: 19
Options
YES
NO
Factory setting
NO

QUICK SETUP HEAT


FLOW

Description
Use this function to start the application-specific setup for heat flow.
For a flowchart of the QUICK SETUP HEAT FLOW: 20
Options
NO
YES
Factory setting
NO

12

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

QUICK SETUP

Function description, QUICK SETUP group


T-DAT SAVE/LOAD

Description
Use this function to save the configuration/settings of the transmitter to a transmitterDAT (T-DAT), or to load a configuration from the T-DAT to the EEPROM (manual
backup function).
For a flowchart of the T-DAT SAVE/LOAD: 22
Application examples:
After commissioning, the current measuring point parameters can be saved to the
T-DAT as a backup.
If the transmitter is replaced for some reason, the data from the T-DAT can be loaded
into the new transmitter (EEPROM).
Options
CANCEL
SAVE (from the EEPROM to the T-DAT)
LOAD (from the T-DAT to the EEPROM)

Note!
If the target device has an older software version, the message "TRANSM. SW-DAT" is
displayed during startup. Then only the "SAVE" option is available.
LOAD
This option is only possible:
if the target device has the same software version as, or a more recent software
version than, the source device or
if the T-DAT contains valid data that can be called up
SAVE
This function is always available.
Factory setting
CANCEL

Endress+Hauser

13

QUICK SETUP

Proline t-mass 65 FOUNDATION Fieldbus

5.1

"Commissioning" Quick Setup menu


XXX.XXX.XX

Esc

++

Quick Setup

QS
Commission

E+

Language

HOME-POSITION

Pre-setting

Selection pre-settings

Delivery settings

Actual settings

Selection system units

Pressure

Temperature

Mass flow

Corr. Vol. Flow

Heat Flow

Density

Unit
Pressure

Unit
Temperature

Unit
Mass Flow

Unit
Corr. Vol. Flow

Unit Calorific
Value Mass

Unit
Density

Reference
Temperature

Unit Calorific
Val. Corr. Vol.

Reference
Pressure

Unit
Heat Flow

Quit

Unit
Quantity Heat
Yes

Yes

Configure another system unit ?

No

Automatic configuration of display ?

No

Automatic parameterization of the display

u
Sensor

Gas

Carry out another Quick Setup


Pressure

Heat Flow

No

Carry out the selected Quick Setup


A0014984-en

Fig. 1:

QUICK SETUP COMMISSIONING- menu for straightforward configuration of the major device functions

Note!
The display returns to the QUICK SETUP cell if you press the ESC key combination (Q) during
programming of a parameter anywhere in the menu.
QUICK SETUP - COMMISSION
Use the O or S key at the prompt "QS-COMMISSION NO" and the device access code entry appears. Enter the device access
code "65" and press F; programming is enabled. The prompt "QS-COMMISSION NO" appears. Use the O or S key to
change NO to YES and press F.
LANGUAGE
Use the O or S key to select the required language and continue with F.
PRE-SETTING.
m Select ACTUAL SETTINGS to continue programming the device and go to the next level or select DELIVERY SETTINGS
to reset the device. The device restarts and returns to the Home position.
- ACTUAL SETTINGS are the actual programmed parameters in the device
- DELIVERY SETTINGS are the programmed parameters (factory settings plus customer
specific settings) originally delivered with the device

14

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

QUICK SETUP

SYSTEM UNITS.
Select required system unit function and carry out parameterization or select QUIT to return to the QUICK SETUP function
if no further programming is required.
n Only units not yet configured in the current setup are available for selection in each cycle.
o The YES option remains visible until all the units have been configured.
NO is the only option displayed when no further units are available.

Automatic configuration of the display


t The "automatic parameterization of the display" option contains the following basic settings/factory settings:
- YES: main line = MASS FLOW, additional line = TOTALIZER 1
- NO: The existing (selected) settings remain.
Carry out another Quick Setup?
u Select additional Quick Setups to complete commissioning or select NO to exit.

Endress+Hauser

15

QUICK SETUP

Proline t-mass 65 FOUNDATION Fieldbus

5.2

"Sensor" Quick Setup menu

It is essential that the insertion sensor is setup according to the actual pipe or duct and then installed
at the calculated insertion depth. This Quick Setup guides you systematically through the procedure
to setup the sensor.

Note!
The QUICK SETUP SENSOR function is not available for flanged type sensors.

XXX.XXX.XX

++

QUICK SETUP

QS
SENSOR

E+

Esc

UNIT
LENGTH

HOME-POSITION

m Selection Pipe Type


PIPE
TYPE
CIRCULAR

RECTANGULAR

PIPE
STANDARD

INTERNAL
HEIGHT

NOMINAL
DIAMETER

INTERNAL
WIDTH

OUTER
DIAMETER

WALL
THICKNESS

WALL
THICKNESS

MOUNTING

INTERNAL
DIAMETER

MOUNTING SET
LENGTH

INSERTION
DEPH
A0009910-en

PIPE TYPE
m CIRCULAR
in case that the pipe is of a standard type, then parameterize functions PIPE STANDARD and NOMINAL
DIAMETER
In case that the pipe is a non-standard type, then select OTHERS in the function PIPE STANDARD and
parameterize the functions WALL THICKNESS and OUTER DIAMETER.
The function INTERNAL DIAMETER displays the calculated internal diameter and is read only.
RECTANGULAR
Enter the INTERNAL HEIGHT, INTERNAL WIDTH and WALL THICKNESS of the duct
Select the MOUNTING orientation of the sensor: HORIZONTAL or VERTICAL
MOUNTING SET LENGTH
n Enter the measured length of the mounting set (including the compression fitting).
INSERTION DEPTH
o This function calculates the insertion depth value for the mounting of the sensor.
This function is read only.
Press F to save settings and return to QUICK SETUP SENSOR group.

16

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

QUICK SETUP

5.3

"Gas" Quick Setup menu

The device can be setup with 1 or 2 individual gas groups in memory. This means that up to 2
different gas flow streams (e.g. nitrogen and argon) can be measured in a single pipe with one
flowmeter.
In the case of 2 gas groups being used, a digital input can be assigned to switch between the gas
groups or, alternatively, the switch can be done manually via a function in the device software.

XXX.XXX.XX

++

QUICK SETUP

E+

QS
GAS

Esc

SELECT
GROUP

HOME-POSITION

Selection of Gas Group

GAS GROUP 1

QUIT

GAS GROUP 2

ANALYZER
INPUT

ANALYZER
INPUT

NUMBER OF
GASES

NUMBER OF
GASES

GAS TYPE 1

GAS TYPE 1

DESCRIPTION 1

MOLE % GAS 1

MOLE % GAS 1

DESCRIPTION 2

CORRECTION
FACTOR 1

GAS TYPE
28

GAS TYPE
28

CORRECTION
FACTOR 2

REFERENCE
DENSITY 1

MOLE % GAS
28

MOLE % GAS
28

REFERENCE
DENSITY 2

CHECK
VALUES

CHECK
VALUES

Selection
SAVE CHANGES?

CANCEL

Configure Another Group?

DISCARD

YES

YES

NO

A0009907-en

Programming a gas group


The device allows flexible change of the gas group parameters, independent of the original factory
setup and calibration
A gas group can be programmed as:
one single gas or
one gas mixture (of up to 8 components)
A single gas can be:
selected from a list of standard gases or
setup for other suitable types of gases, such as Ozone, using manual correction factors and the
option called SPECIAL GAS. This requires application evaluation at the factory - consult your
Endress+Hauser representative prior to using this function.

Endress+Hauser

17

QUICK SETUP

Proline t-mass 65 FOUNDATION Fieldbus

Setting or viewing the active gas group


Go to the function SELECT GROUP ( 38) and simply select 1 or 2 and then exit using
ESC (Q keys simultaneously). No save function is necessary.

Note!
This Quick Setup Gas function is not available if an in-situ calibration function has been performed
on the device as the in-situ calibration curve refers to the sensor power at each recorded flow point.
Therefore, the programmed gas settings become redundant.
Performing the Quick Setup
1. GAS GROUP
Use the O or S key to select the required GAS GROUP and continue with F.
select the NUMBER OF GASES in the group from 1 to 8
select the GAS TYPE from the choose list.
enter the MOLE % for each GAS TYPE (only if NUMBER OF GASES is 2 and more).
The error message CHECK VALUES appears if the total mixture % does not equal 100%. Go
back and check the mixture settings.

18

2.

SAVE CHANGES?
Select YES to save changes to the GAS GROUP and activate them. Press F to continue or
Select CANCEL to save the entered settings in buffer memory but not activate them for
measurement. If this function is selected, then it will be necessary to come back to this gas
group and save it at a later stage.
Select DISCARD to clear the last changes and return to CONFIGURE GROUP to make new
settings.

3.

ANOTHER GAS GROUP?


Select YES to continue to the CONFIGURE GROUP function. Use the + or - key to select
another group and proceed as per above instructions.
Select NO to exit to the Quick Setup.

Note!
You can find more detailed information on the GAS GROUP in chapter GAS 38

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

5.4

QUICK SETUP

"Pressure" Quick Setup menu

Use this Quick Setup to program the individual process pressure for each gas group. If only one gas
group is being used, then only the function PROCESS PRESSURE 1 needs to be programmed,
PROCESS PRESSURE 2 can remain with default settings.

XXX.XXX.XX

Esc

++

QUICK SETUP

E+

QS
PRESSURE

HOME-POSITION

PROCESS
PRESSURE 1
PROCESS
PRESSURE 2

A0009908-en

Endress+Hauser

Note!
The device operates with absolute pressure only. Convert any gauge pressures to absolute
pressure.
If a pressure compensating input is being used, then the input signal value overrides the manually
programmed value. The pressure input value applies to both gas groups. i.e. 2 independent
pressure values are no longer possible.
This Quick Setup Gas function is not available if an in-situ calibration function has been
performed on the device as the in-situ calibration curve refers to the sensor power at each
recorded flow point. Therefore, the programmed pressure settings become redundant.

19

QUICK SETUP

Proline t-mass 65 FOUNDATION Fieldbus

5.5

"Heat Flow" Quick Setup menu

The device can calculate and output the heat of combustion of common fuel gases such as methane,
natural gas, propane, butane, ethane and hydrogen.
Use this Quick Setup menu to program the method used to calculate the heating value or calorific
value (CV). The device can be configured to give two independent heating value outputs and
totalized values. For example, the pipeline has either natural gas or propane running at separate
times and the heating value is required for both gases.

XXX.XXX.XX

++

QUICK SETUP

E+

Esc

QS
HEAT FLOW

CALORIFIC
VALUE TYPE

HOME-POSITION
Selection CALCULATION MODE 1

AUTO NET

AUTO GROSS

MANUAL
CALORIFIC
VALUE 1

Selection CALCULATION MODE 2

AUTO NET

AUTO GROSS

MANUAL
CALORIFIC
VALUE 2

REF. COMBUST.
TEMPERATURE
A0009909-en

5.5.1

Calculation mode 1 and 2

The heating value for CALCULATION MODE 1 corresponds to the settings in the function
GAS GROUP 1.
The heating value for CALCULATION MODE 2 corresponds to the settings in the function
GAS GROUP 2.

Note!
If only one gas group is used, then leave mode 2 as default settings.
The units of measure are selected in the SYSTEM UNITS section 8.
Auto Gross
The gross heating value (or higher heating value) is the total heat obtained by complete combustion
at constant pressure of a volume of gas in air, including the heat released by the water vapor in the
combustion products (gas, air and combustion products taken at reference cumbustion temperature
and standard pressure).
Auto Net
The net heating value (or lower heating value) is determined by subtracting the heat of vaporization
of the water vapor from the higher heating value. This treats any water formed as water vapor. The
energy required to vaporize the water therefore is not realized as heat.

20

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

QUICK SETUP

Manual
This function allows entry of a user-specific heating value if the required value is different to the
following table.
Gas

Formula

Net/lower heating value

Gross/upper heating value

[Mj/kg]

MBtu/lb

[Mj/kg]

MBtu/lb

Hydrogen

H2

119.91

51.56

141.78

60.97

Ammonia

NH3

18.59

7.99

22.48

9.67

Carbon Monoxide

CO

10.1

4.34

10.1

4.34

Hydrogen Sulphide

H2S

15.2

6.54

19.49

8.38

Methane

CH4

50.02

21.51

55.52

23.87

Ethane

C2H6

47.5

20.43

51.93

22.33

Propane

C3H8

46.32

19.92

50.32

21.64

Butane

C4H10

45.71

19.66

49.51

21.29

Ethylene

C2H4

47.16

20.28

50.31

21.63

* According to ISO 6976:1995(E) and GPA Standard 2172-96

Reference combustion temperature


The following reference temperatures are used:
Country

Endress+Hauser

reference combustion temperature

Austria, Belgium, Denmark, Germany, Italy, Luxembourg,


The Netherlands, Poland, Russia, Sweden, Switzerland

25 C

Brazil, China

20 C

France, Japan

0 C

Australia, Canada, Czech Republic, Hungary, India, Ireland, Malaysia,


Mexico, South Africa, Great Britain

15 C

Slovakia

25 C

USA, Venezuela

60 F

21

QUICK SETUP

Proline t-mass 65 FOUNDATION Fieldbus

5.6

Data backup/transmission

Using the T-DAT SAVE/LOAD function, you can transfer data (device parameters and settings)
between the T-DAT (exchangeable memory) and the EEPROM (device storage unit).
This is required in the following instances:
Creating a backup: current data are transferred from an EEPROM to the T-DAT.
Replacing a transmitter: current data are copied from an EEPROM to the T-DAT and then
transferred to the EEPROM of the new transmitter.
Duplicating data: current data are copied from an EEPROM to the T-DAT and then transferred to
EEPROMs of identical measuring points.

Note!
For information on installing and removing the T-DAT see Operating Instructions BA00113D/06

XXX.XXX.XX

Esc

Quick Setup

HOME
POSITION

T-DAT
SAVE/LOAD

LOAD

F
Restart of the
measuring device

CANCEL

F
YES

SAVE

NO

YES

NO

Input is
saved

a0001221-en

Fig. 2:

5.6.1

Data backup/transmission with T-DAT SAVE/LOAD function

Information on the LOAD and SAVE options available

LOAD
Data are transferred from the T-DAT to the EEPROM.

Note!
Any settings already saved on the EEPROM are deleted.
This option is only available, if the T-DAT contains valid data.
This option can only be executed if the software version of the T-DAT is the same or newer than
that of the EEPROM. Otherwise, the error message "TRANSM. SW-DAT" appears after restarting
and the LOAD function is then no longer available.
SAVE
Data are transferred from the EEPROM to the T-DAT

22

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

OPERATION

OPERATION

Function description, OPERATION group


LANGUAGE

Description
For selecting the language in which all messages are shown on the local display.
If you press the P keys simultaneously at startup, the language defaults to "ENGLISH".
Options
ENGLISH
DEUTSCH
FRANCAIS
ESPANOL
ITALIANO
NEDERLANDS
NORSK
SVENSKA
SUOMI
PORTUGUES
POLSKI
CESKI
Factory setting
country dependent 53

ACCESS CODE

Description
All data of the measuring system are protected against inadvertent change. Programming
is disabled and the settings cannot be changed until a code is entered. If you press the P
operating elements in any function, the measuring system automatically goes to this
function and the prompt to enter the code appears on the display (programming
disabled).
You can enable programming by entering the private code (factory setting = 65, see
DEFINE PRIVATE CODE function ( 23).
The programming levels are disabled if you do not press the operating elements within
60 seconds following a return to the HOME position.
Programming can also be disabled by entering any number (other than the private
code).
Your Endress+Hauser representative can be of assistance if you mislay your private
code.
User input
Max. 4-digit number: 0 to 9999

DEFINE PRIVATE CODE

Description
Use this function to specify the private code for enabling programming.
Programming is always enabled if the code defined = 0.
Programming has to be enabled before the code can be changed. When programming
is disabled this function cannot be edited, thus preventing others from accessing your
personal code.
User input
Max. 4-digit number: 0 to 9999
Factory setting
65

STATUS ACCESS

Description
The access status for this function matrix appears on the display.
Display
ACCESS CUSTOMER (parameters can be modified)
LOCKED (parameters cannot be modified)

Endress+Hauser

23

OPERATION

Proline t-mass 65 FOUNDATION Fieldbus

Function description, OPERATION group


ACCESS CODE
COUNTER

Description
The number of times the private and service code was entered to access the device
appears on the display.
Display
Integer
Factory setting
0

24

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

USER INTERFACE

USER INTERFACE

Function description, USER INTERFACE group


ASSIGN LINE 1

Description
For assigning a display value to the main line (top line of the local display).
This value is displayed during normal operation.
Options
OFF
MASS FLOW
MASS FLOW IN %
TEMPERATURE
TOTALIZER 1
TOTALIZER 2
AI(1 to 5) - OUT VALUE
CORRECTED VOLUME FLOW
CORRECTED VOLUME FLOW IN %
HEAT FLOW
HEAT FLOW IN %
AO-VALUE
Factory setting
MASS FLOW

ASSIGN LINE 2

Description
For assigning a display value to the additional line (bottom line of the local display).
This value is displayed during normal operation.
Options
OFF
MASS FLOW
MASS FLOW IN %
MASS FLOW BARGRAPH IN %
TEMPERATURE
TOTALIZER 1
TOTALIZER 2
TAG NAME
OPERATING/SYSTEM CONDITIONS
CORRECTED VOLUME FLOW
CORRECTED VOLUME FLOW IN %
CORRECTED VOLUME FLOW BARGRAPH IN %
AI(1 to 5) - OUT VALUE
HEAT FLOW
HEAT FLOW IN %
HEAT FLOW BARGRAPH IN %
AO-VALUE
Factory setting
TOTALIZER 1

100% VALUE LINE 1

Prerequisite
This function is only available if one of the following options was selected in the ASSIGN
LINE 1 function ( 25):
MASS FLOW IN %
CORRECTED VOLUME FLOW IN %
HEAT FLOW IN %
Description
Use this function to enter the flow value which should be shown on the display as
the 100% value.
User input
5-digit floating-point number
Factory setting
10 kg/h (with mass flow)
10 Nm/h (with corrected volume flow)
10 kW (with heat flow)

Endress+Hauser

25

USER INTERFACE

Proline t-mass 65 FOUNDATION Fieldbus

Function description, USER INTERFACE group


100% VALUE LINE 2

Prerequisite
This function is only available if one of the following options was selected in the ASSIGN
LINE 2 function ( 25):
MASS FLOW IN %
CORRECTED VOLUME FLOW IN %
HEAT FLOW IN %
MASS FLOW BARGRAPH IN %
CORRECTED VOLUME FLOW BARGRAPH IN %
HEAT FLOW BARGRAPH IN %
Description
Use this function to enter the flow value which should be shown on the display as
the 100% value.
User input
5-digit floating-point number
Factory setting
10 kg/h (with mass flow)
10 Nm/h (with corrected volume flow)
10 kW (with heat flow)

FORMAT

Description
For selecting the number of decimal places for the display value in the main line.
Note that this setting only affects the reading as it appears on the display, it has no
influence on the accuracy of the system's calculations.
The places after the decimal point as computed by the measuring device cannot always
be displayed, depending on this setting and the engineering unit. In these instances an
arrow appears on the display between the measured value and the engineering unit
(e.g. 1.2 kg/h), indicating that the measuring system is computing with more
decimal places than can be shown on the display.
Options
XXXXX. - XXXX.X - XXX.XX - XX.XXX -X.XXXX
Factory setting
X.XXXX

DISPLAY DAMPING

Description
For entering a time constant defining how the display reacts to severely fluctuating flow
variables, either very quickly (enter a low time constant) or with damping (enter a high
time constant).
The setting 0 seconds switches off damping.
User input
0 to 100 seconds
Factory setting
3 seconds

CONTRAST LCD

Description
For adjusting the display contrast to suit local operating conditions.
User input
10 to 100%
Factory setting
50%

BACKLIGHT

Description
For adjusting the background lighting to suit local operating conditions.
Entering the value "0" means that the backlight is "switched off". The display then no
longer emits any light, i.e. the display texts can no longer be read in the dark.
User input
0 to 100%
Factory setting
50%

26

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

USER INTERFACE

Function description, USER INTERFACE group


TEST DISPLAY

Description
Use this function to test the operability of the local display and its pixels.
Test sequence:
1. Start the test by selecting ON.
2. All pixels of the main line and additional line are darkened for minimum
0.75 seconds.
3. The main line and additional line show an "8" in each field for minimum
0.75 seconds.
4. The main line and additional line show a "0" in each field for minimum
0.75 seconds.
5. The main line and additional line show nothing (blank display) for minimum
0.75 seconds.
6. When the test is completed, the local display returns to its initial state and displays
the option OFF.
Options
OFF
ON
Factory setting
OFF

Endress+Hauser

27

TOTALIZER 1/2

Proline t-mass 65 FOUNDATION Fieldbus

TOTALIZER 1/2

Function description, TOTALIZER 1/2 group


ASSIGN TOTALIZER

Description
Use this function to assign a measured variable to the totalizer.
The totalizer is reset to 0 as soon as the option selected is changed.
If you select OFF, only the ASSIGN TOTALIZER function is displayed in the
Totalizer 1 or 2 group.
Options
OFF
MASS FLOW
CORRECTED VOLUME FLOW
HEAT FLOW
Factory setting
MASS FLOW

ASSIGN GAS GROUP

Description
Use this function to assign a gas group to a totalizer.
If GAS GROUP 1&2 is selected, the individual values of each gas group are totaled on one
totalizer.
Options
GAS GROUP 1
GAS GROUP 2
GAS GROUP 1&2
Factory setting
GAS GROUP 1

SUM

Description
The total for the totalizer's measured variable aggregated since measuring commenced
appears on the display. The value is positive.
The totalizers' response to errors is defined in the FAILSAFE MODE function ( 30).
Display
Max. 7-digit floating-point number, including unit (e.g. 15467.04 kg)

OVERFLOW

Description
The total for the totalizer's overflow aggregated since measuring commenced appears on
the display.
Total flow is represented by a floating-point number consisting of max. 7 digits. Higher
numerical values (>9,999,999) can be viewed as overflows. The effective quantity is thus
the total of the SUM function ( 28) plus the value displayed in the OVERFLOW
function.
Example:
Reading after 2 overflows: 2 E7 kg (= 20000000 kg)
The value displayed in the SUM function = 196845.7 kg
Effective total quantity = 20196845.7 kg
Display
Integer with exponent, including unit, e.g. 2 E7 kg

28

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

TOTALIZER 1/2

Function description, TOTALIZER 1/2 group


UNIT TOTALIZER

Description
For selecting the unit for the measured variable assigned to the totalizer.
Options (ASSIGN TOTALIZER = MASS FLOW)
SI g , kg, t
US oz, lb, ton
Factory setting
Depends on the nominal diameter and the country 53
Options (ASSIGN TOTALIZER = CORRECTED VOLUME FLOW)
SI Nl, Nm
US Sm, Scf
Factory setting
Depends on the nominal diameter and the country 53
Options (ASSIGN TOTALIZER = HEAT FLOW)
SI kWh, MWh, kJ, MJ, GJ, kcal, Mcal, Gcal
US kBtu, MBtu, GBtu, tonh
Factory setting
MWh or kBtu (country dependent 53)

RESET TOTALIZER

Description
Resets the sum and overflow in the totalizer selected.
Options
NO
YES
Factory setting
NO

Endress+Hauser

29

HANDLING TOTALIZER

Proline t-mass 65 FOUNDATION Fieldbus

HANDLING TOTALIZER

Function description, HANDLING TOTALIZER group


RESET ALL TOTALIZERS

Description
Resets the sums and overflows of both totalizers to "zero" (=RESET).
Options
NO
YES
Factory setting
NO

FAILSAFE MODE

Description
For selecting the behavior of the totalizer in an alarm condition.
Options
STOP
The totalizer does not continue to count the flow if a fault is present. The totalizer stops
at the last value before the alarm condition occurred.
HOLD VALUE
The totalizer continues to count the flow on the basis of the last valid flow data (before
the fault occurred).
ACTUAL VALUE
The totalizers continue to count on the basis of the current flow data. The fault is
ignored.
Factory setting
STOP

30

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

10

COMMUNICATION

COMMUNICATION

Function description, COMMUNICATION group


WRITE PROTECTION

Description
Use this function to check whether the measuring device can be write-accessed.
Write protection is activated and deactivated by means of a jumper on the I/O module
(see Operating Instructions BA00134D/06).
Display
OFF = Data exchange is possible
ON = Data exchange disabled
Factory setting
OFF

SIMULATION

Description
Use this function to check whether a simulation in the Analog Input or Discrete Output
function block is possible.
The simulation mode is activated and deactivated by means of a jumper on the I/
O board (see Operating Instruction BA065D/06)
The status of the simulation mode is also shown in the parameter BLOCK_ERR of the
Resource Block.
Display
OFF
Simulation in the Analog Input and Discrete Output function block is not possible.
ON
Simulation in the Analog Input and Discrete Output function block is possible.
Factory setting
ON

DEVICE PD-TAG

Description
Use this function to enter a tag name for the measuring device.
User input
Max. 32-character text, permissible: A-Z, 0-9, +,-, punctuation marks
Factory setting
E+H_TMASS_65_XXXXXXXXXXX)

MANUFACTURER ID

Description
Use this function to view the manufacturer ID in decimal numerical format.
Display
452B48 (hex) for Endress+Hauser

DEVICE TYPE

Description
Use this function to view the device ID in hexadecimal numerical format.
Display
1065 (hex) for t-mass 65 FOUNDATION Fieldbus

SERIAL NUMBER

Description
Use this function to view the serial number.
Display
11-digit number

Endress+Hauser

31

COMMUNICATION

Proline t-mass 65 FOUNDATION Fieldbus

Function description, COMMUNICATION group


DEVICE REVISION

Description
Use this function to view the device revision number.

Hinweis!
The information displayed here helps ensure that the correct system files (DD = Device
Description) are used for integration into the host system. The system files can be downloaded from the Internet free of charge (www.endress.com).
Example:
Information displayed in the DEVICE REVISION function 01
Information displayed in the DD REVISION function 01
Device description files required (DD) ) 0101.sym / 0101.ffo
Display
1
DD REVISION

Description
Use this function to view the revision number of the Device Description.

Hinweis!
The information displayed here helps ensure that the correct system files (DD = Device
Description) are used for integration into the host system. The system files can be downloaded from the Internet free of charge (www.endress.com).
Example:
Information displayed in the DEVICE REVISION function 01
Information displayed in the DD REVISION function 01
Device description files required (DD) ) 0101.sym / 0101.ffo
Display
1
BLOCK SELECTION

Description
In this function, a function block can be selected, whose value and status is shown in the
following functions.
Display
ANALOG INPUT 1 to 5
ANALOG OUTPUT
PID
Factory setting
ANALOG INPUT 1

OUT VALUE

Description
Displays the output value OUT, incl. unit and status of the Analog Input or PID function
block selected in the function BLOCK SELECTION.

IN VALUE

Prerequisite
This function is not available unless the PID option was selected in the
BLOCK SELECTION function.
Display
Displays the controlled variable IN, incl. unit and status of the Analog Input or PID function block selected in the function BLOCK SELECTION.

CASCADE_IN VALUE

Prerequisite
This function is not available unless the PID option was selected in the
BLOCK SELECTION function.
Display
Displays an analog set value, incl. units and status, taken over from an external function
block.

32

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

11

PROCESS PARAMETER

PROCESS PARAMETER

Function description, PROCESS PARAMETER group


PROCESS PRESSURE 1

Prerequisite
This function is not available if the IN-SITU CALIBRATION function has been enabled.
Refer to your Endress+Hauser service representative for more information.
Description
Use this function to enter the process pressure for GAS GROUP 1.
(Selection and composition by means of the functions in the GAS group).
The unit is taken from the function UNIT PRESSURE ( 10).
Input/display
5-digit floating-point number
Factory setting
1.0130 [bar a] or 14.692 [psi a] (country dependent 53)

PROCESS PRESSURE 2

Prerequisite
This function is not available if the IN-SITU CALIBRATION function has been enabled.
Refer to your Endress+Hauser service representative for more information.
Description
Use this function to enter the process pressure for GAS GROUP 2.
(Selection and composition by means of the functions in the GAS group).
The unit is taken from the function UNIT PRESSURE ( 10).
Input/display
5-digit floating-point number
Factory setting
1.0130 [bar a] or 14.692 [psi a] (country dependent 53)

PROCESS PRESSURE

Description
Use this function to display the pressure value which is used for the flow calculation.
The value is read from the following function:
PROCESS PRESSURE 1 or 2 (depending on which gas group is active)
The unit is taken from the function UNIT PRESSURE ( 10)
Display
5-digit floating-point number
Factory setting
1.0130 [bar a] or 14.692 [psi a] (country dependent 53)

REFERENCE PRESSURE

Description
Use this function to enter the reference pressure for calculating the reference density
(for corrected volume flow measurement).
The unit is taken from the function UNIT PRESSURE ( 10).
User input
5-digit floating-point number
Factory setting
1.0130 [bar a] or 14.692 [psi a] (country dependent 53)

REFERENCE
TEMPERATURE

Description
Use this function to enter the reference temperature for calculating the reference density
(for corrected volume flow measurement).
The unit is taken from the function UNIT TEMPERATURE ( 11).
User input
5-digit floating-point number
Factory setting
0.0 [C] or +32.0 [F] (country dependent 53.)

Endress+Hauser

33

PROCESS PARAMETER

Proline t-mass 65 FOUNDATION Fieldbus

Function description, PROCESS PARAMETER group


REFERENCE DENSITY

Prerequisite
This function is not available if the IN-SITU CALIBRATION function has been enabled.
Contact your Endress+Hauser service organization for more information.
Description
Use this function to display the calculated reference density (for corrected volume flow
measurement).
The unit is taken from the function UNIT DENSITY ( 11).
Display
5-digit floating-point number

NET CALORIFIC VALUE

Prerequisite
This function is only available if AUTO NET or MANUAL was selected in the
MODE 1 or 2 function ( 42)
Description
Use this function to display the current net calorific value of the gas.
The unit is taken from the function UNIT CALORIFIC VALUE MASS ( 9) or
UNIT CALORIFIC VALUE CORRECTED VOLUME ( 9).
Display
5-digit floating-point number

GROSS CALORIFIC
VALUE

Prerequisite
This function is only available if AUTO GROSS was selected in the MODE 1 or 2
function ( 42).
Description
Use this function to display the current gross calorific value of the gas.
The unit is taken from the function UNIT CALORIFIC VALUE MASS ( 9) or
UNIT CALORIFIC VALUE CORRECTED VOLUME ( 9).
Display
5-digit floating-point number

MOLE % GAS 1

Description
Use this function to display the Mole % of GAS TYPE 1.
Display
0.0 % to 100.0 %

ASSIGN LOW FLOW


CUT OFF

Description
For selecting the process variable on which low flow cut off should act.
Options
OFF
MASS FLOW
CORRECTED VOLUME FLOW
Factory setting
MASS FLOW

34

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

PROCESS PARAMETER

Function description, PROCESS PARAMETER group


ON-VALUE LOW FLOW
CUT OFF

Prerequisite
This function is not available if OFF was selected in the ASSIGN LOW FLOW CUT OFF
function ( 34).
Description
Use this function to enter the on-value for low flow cut off.
The unit is taken from the SYSTEM UNITS group ( 8).
Low flow cut off is switched on if the value entered is not equal to 0. An inverted plus
sign is shown on the local display of the flow value as soon as the low flow cut off is
active.
User input
5-digit floating-point number
Factory setting
1 % of full scale value

OFF-VALUE LOW
FLOW CUT OFF

Description
Use this function to enter the off-value for low flow cut off. Enter the off-value as a
positive hysteresis from the on-value.

H
1

1
c

t
a0001245

Fig. 3:
Q
t
H
a
b
c
1
2

Example for the behavior of low flow cutoff


Flow rate [volume/time]
Time
Hysteresis
ON VALUE LOW FLOW CUT OFF = 20 kg/h
OFF-VALUE LOW FLOW CUTOFF = 10%
Low flow cutoff active
Low flow cut off is switched on at 20 kg/h
Low flow cut off is switched off at 22 kg/h

User input
Integer 0 to 100%
Factory setting
50%
ZERO POINT ADJUST

Description
Use this function to start automatic zero point adjustment.

"

Caution!
Prior to performing zero point adjustment, observe the exact procedure for zero point
adjustment as specified in Operating Instructions BA00113D/06.

Note!
If zero point adjustment is not possible due to unstable flow conditions,
alarm #451 "ADJUST ZERO FAIL" appears on the display.
RESET: reset to factory calibration.
Options
START
CANCEL
RESET
Factory setting
CANCEL

Endress+Hauser

35

PROCESS PARAMETER

Proline t-mass 65 FOUNDATION Fieldbus

Function description, PROCESS PARAMETER group


INSTALLATION
FACTOR

Description
Disturbances in the flow may arise due to the design of the system, such as pipe bends,
reducers, etc. The flow value measured is scaled by entering a constant factor. The flow
disturbance can thus be compensated using the calculated flow signal:
Flow output = measured flow installation factor
Enter a higher value: flow value output is increased.
Enter a lower value: flow value output is decreased.
User input
5-digit floating-point number
0.0000 to 99999
Factory setting
1.0000

36

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

12

GAS

GAS

Function description, GAS group


Prerequisite
This function is not available if the IN-SITU CALIBRATION function is enabled. This function is available again if the
in-situ calibration is reset to the factory setting. Contact your Endress+Hauser service organization for more
information.
Description
Use this function to view or change the gas configuration
The device can be configured with one or two independent gas groups.
Switching between two groups can be performed manually (function SELECT GROUP 38)
General programming rules:
A gas group can be configured with 1 single gas or a gas mixture (max. 8 gas constituents).
The sum of the gas mixture constituents entered must total 100.0 Mole %.
A gas constituent and its corresponding Mole % can be entered in any order within the mixture.
A gas constituent may have a value of 0.0 Mole % within the mixture.
The option NOT USED is only a place holder for functions GAS TYPE 1 and GAS TYPE 2 to 8 where there is no gas
assigned. The program does not use this option for calculations.
The option SPECIAL GAS is a substitute for other gases. The Mole % value is always 100.0%
Note!
!
See the flowchart of the "Gas" Quick Setup menu 17

Programming examples
a.

1 gas group: 1 standard gas


SELECT GROUP
GAS GROUP 1
ANALYZER INPUT
OFF
NUMBER OF GASES
1
GAS TYPE 1
AIR
MOLE % GAS 1
100.0 %

b.

2 gas groups: 2 standard gases


SELECT GROUP
GAS GROUP 1
ANALYZER INPUT
OFF
NUMBER OF GASES
1
GAS TYPE 1
ARGON
MOLE % GAS 1
100.0 %

GAS GROUP 2
OFF
1
NITROGEN
100.0 %

2 gas groups: 1 standard gas, 1 special gas


SELECT GROUP
GAS GROUP 1
ANALYZER INPUT
OFF
NUMBER OF GASES
1
GAS TYPE 1
OXYGEN
MOLE % GAS 1
100.0 %
DESCRIPTION 1

CORRECTION FACTOR

REFERENCE DENSITY

GAS GROUP 2
OFF
1
SPECIAL GAS
100.0 %
O2 90% OZONE 10%
1.2009
1.5005 kg/m3

c.

d.

Endress+Hauser

1 gas groups: 1 gas mixture (with gas analyzer input compensation)


SELECT GROUP
GAS GROUP 1
ANALYZER INPUT
ON
NUMBER OF GASES
1
GAS TYPE 1
METHANE
MOLE % GAS 1
50.0 %
GAS TYPE 2
CARBON DIOXIDE
MOLE % GAS 2
40.0 %
GAS TYPE 3
NITROGEN
MOLE % GAS 3
10.0 %

37

GAS

Proline t-mass 65 FOUNDATION Fieldbus

Function description, GAS group


SELECT GROUP

Description
Use this function to:
select a gas group for editing
set the active gas group manually
Setting the active gas group:
On completion of programming all the necessary functions in the gas group, select YES
in the SAVE CHANGES function, or
If the gas group is already programmed as required, simply select the required gas
group and then exit using the ESC keys (X).

Note!
If the STATUS INPUT is assigned to control switching of the gas groups, then the
STATUS INPUT will over-ride the setting of this function.
Options
GAS GROUP 1
GAS GROUP 2
Factory setting
GAS GROUP 1
ANALYZER INPUT

Description
Use this function to assign automatic updating of a gas group (via a gas analyzer signal
and the current input function). A gas group must contain at least 2 gas types (e.g.
Methane 60%, Carbon Dioxide 40%).
Options
OFF
ON
Factory setting
OFF

NUMBER OF GASES

Description
Use this function to enter the number of gases that are used in the gas group.
User input
1 to 8
Factory setting
1

GAS TYPE 1

Description
Use this function to select gas type 1.
Options
AIR
AMMONIA
ARGON
BUTANE
CARBON DIOXIDE
CARBON MONOXIDE
CHLORINE
ETHANE
ETHYLENE
HELIUM 4
HYDROGEN NORMAL
HYDROGEN CHLORIDE
HYDROGEN SULFIDE
KRYPTON
METHANE
NEON
NITROGEN
OXYGEN
PROPANE
XENON
NOT USED
SPECIAL GAS
Factory setting
AIR

38

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

GAS

Function description, GAS group


MOLE % GAS 1

Prerequisite
This function is not available if the setting in NUMBER OF GASES ( 38) is 1.
(The factory setting 100% is automatically used)
Description
Use this function to enter the Mole % of the gas selected in GAS TYPE 1.
User input
000.00 % to 100.00 %
Factory setting
100.00 %

DESCRIPTION

Prerequisite
This function is only available if the option SPECIAL GAS is selected in the function
GAS TYPE 1 ( 38).
Description
Use this function to enter a description for a special gas configuration.
Example
A special composition consisting of 93% oxygen and 7% ozone.
User input: O2 93% OZONE 7%
User input
xxxx (max. 16 characters)
Valid characters are A-Z, 0-9, +, -, decimal point, blank space or underscore
Factory setting
" " (no text)

CORRECTION FACTOR

Prerequisite
This function is only available if the option SPECIAL GAS is selected in the function
GAS TYPE 1 ( 38).
Description
Use this function to enter a manual correction factor for a special gas configuration.
The correction factor is normally based on air and at the specified process conditions.
The correction factor is determined by the factory. If the gas or process conditions change
from the initial setting, then the correction factor value will also need updating.
User input
5-digit floating-point number
Factory setting
1.0

REFERENCE DENSITY

Prerequisite
This function is only available if the option SPECIAL GAS is selected in the function
GAS TYPE 1 ( 38).
Description
Use this function to enter a reference density for a special gas configuration when
corrected volume flow is required, e.g. Nm (Scf)
The reference density is determined by the factory. If the gas or reference conditions
change from the initial setting, then the reference density value will also need updating.
The unit is taken from the function UNIT DENSITY ( 11).
User input
5-digit floating-point number, with unit
Factory setting
1.2930 [kg/m] or 0.0807 [lb/ft] (country dependent 53)

Endress+Hauser

39

GAS

Proline t-mass 65 FOUNDATION Fieldbus

Function description, GAS group


GAS TYPE 2 to 8

Prerequisite
The number of functions available here is dependent upon the setting in the function
NUMBER OF GASES ( 38).
Description
Use this function to select the gas type.
Options
AIR
AMMONIA
ARGON
BUTANE
CARBON DIOXIDE
CARBON MONOXIDE
CHLORINE
ETHANE
ETHYLENE
HELIUM 4
HYDROGEN NORMAL
HYDROGEN CHLORIDE
HYDROGEN SULFIDE
KRYPTON
METHANE
NEON
NITROGEN
OXYGEN
PROPANE
XENON
NOT USED
Factory setting
NOT USED

MOLE % GAS 2 to 8

Prerequisite
The number of functions available here is dependent upon the setting in the function
NUMBER OF GASES ( 38).
Description
Use this function to enter the Mole % of the gas.
User input
000.00 % to 100.00 %
Factory setting
000.00 %

CHECK VALUES

Prerequisite
This function is only available if there is an error in the Mole % values.
Description
The error message MIXTURE NOT 100% appears if the entered values do not add up to
100%. The entries have to be checked and corrected before the gas group can be saved
and used for flow measurement (see option YES function SAVE CHANGES ( 38).
Display
MIXTURE NOT 100%

40

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

GAS

Function description, GAS group


SAVE CHANGES

Description
Use this function to control the way entries are saved in the gas group and utilized for
flow measurement.
Options
CANCEL
The entered parameters are saved in the gas group but they are not used for flow
measurement. The gas group can be activated, at a later time, by returning to the group,
checking the parameters and then selecting the option YES in this function.
YES
The entered parameters are saved in the gas group and are used for flow measurement.
DISCARD
The entered parameters are not saved. The previous parameters remain valid and are
used for flow measurement.

Endress+Hauser

41

HEAT FLOW

Proline t-mass 65 FOUNDATION Fieldbus

13

HEAT FLOW

Function description, HEAT FLOW group


CALORIFIC VALUE
TYPE

Description
Use this function to select the measured variable on which the combustion value is
based.
Options
MASS
CORRECTED VOLUME
Factory setting
MASS

MODE 1

Description
Use this function to select a mode for calculating the heat flow (GAS GROUP 1).
Options
AUTO NET
AUTO GROSS
MANUAL
Factory setting
AUTO NET

HEATING VALUE 1

Prerequisite
This function is only available if MANUAL was selected in the MODE 1 function
( 42).
Description
Use this function to enter a user-specific calorific value.
Input/display
5-digit floating-point number
Factory setting
0.0
The corresponding unit is taken from the UNIT CALORIFIC VALUE MASS ( 9) or
UNIT CALORIFIC VALUE CORRECTED VOLUME function ( 9).

MODE 2

Description
Use this function to select a mode for calculating the heat flow (GAS GROUP 2).
Options
AUTO NET
AUTO GROSS
MANUAL
Factory setting
AUTO NET

HEATING VALUE 2

Prerequisite
This function is only available if MANUAL was selected in the MODE 2 function
( 42).
Description
Use this function to enter a user-specific calorific value.
Input/display
5-digit floating-point number
Factory setting
0.0
The corresponding unit is taken from the UNIT CALORIFIC VALUE MASS ( 9) or
UNIT CALORIFIC VALUE CORRECTED VOLUME function ( 9).

42

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

HEAT FLOW

Function description, HEAT FLOW group


REFERENCE
COMBUSTION
TEMPERATURE

Prerequisite
This function is not available if the option MANUAL is selected in MODE 1 oder
MODE 2 ( 42).
Description
Use this function to enter the reference combustion temperature of the gas. This function
is used to calculate the calorific value of the gas.
The unit is taken from the function UNIT TEMPERATURE ( 11).
User input
5-digit floating-point number
Factory setting
25.0 C or 60.0 F (country dependent 53)

Endress+Hauser

43

SYSTEM PARAMETER

Proline t-mass 65 FOUNDATION Fieldbus

14

SYSTEM PARAMETER

Function description, SYSTEM PARAMETER group


POSITIVE ZERO
RETURN

Description
Use this function to interrupt evaluation of measured variables. For example, the output
signal should be set to zero flow during operations such as pipe cleaning.
The setting acts on all functions and outputs of the measuring device.
If the positive zero return is active, the notice message #601 "POSITIVE ZERO-RET" is
displayed.
Options
OFF
ON (signal output is set to zero flow value, temperature is as normal)
Factory setting
OFF

FLOW DAMPING

Description
Use this function to enter a value for damping the measured flow and temperature
signals. The sensitivity of the flow measurement signal can be reduced with respect to
transient flows and interference peaks.
The damping acts prior to other damping functions (e. g. display, time constant).
User input
0 to 100 s
Factory setting
1s

44

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

15

SENSOR DATA

SENSOR DATA

Function description, SENSOR DATA group


This group of functions contains the essential data relating to the sensor geometry and calibration.
Flange version (t-mass 65 F): The sensor data cannot be changed and is read only.
Insertion version (t-mass 65 I): The sensor data can be changed to suit the application pipe.
The pipe or duct dimensions are essential for calculating the correct insertion depth.
All the sensor's parameter settings are saved on the S-DAT memory chip.
Note!
!
See the flowchart of the "Sensor" Quick Setup menu 16
Refer to your Endress+Hauser service representative for more information.
PIPE TYPE

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
Description
Use this function to select the type of pipe.
Options
CIRCULAR
RECTANGULAR
Factory setting
CIRCULAR

PIPE STANDARD

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is not available if RECTANGULAR is selected in the PIPE TYPE function
( 45).
Description
Use this function to select a pipe standard.
If the option OTHERS is selected here, then values need to be entered in the functions
OUTER DIAMETER and WALL THICKNESS.
Options
DIN:
PN6, PN10, PN25, PN40
ANSI:
B36.10 SCHEDULE 10, 20, 30, 40, 60, 80
B36.19 SCHEDULE 10, 40, 80
OTHERS
Factory setting
PN10 or B36.10 SCHEDULE 10 (country dependent 53)

NOMINAL DIAMETER

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is not available if OTHER was selected in the PIPE STANDARD function
( 45) or RECTANGULAR in the PIPE TYPE function ( 45).
Description
Use this function to select the nominal diameter of the pipe.
Options
80/3", 100/4", 150/6", 200/8", 250/10", 300/12", 350/14", 400/16", 450/18",
500/20", 600/24", 700/28", 800/32", 900/36", 1000/40"
Factory setting
150/6"

Endress+Hauser

45

SENSOR DATA

Proline t-mass 65 FOUNDATION Fieldbus

Function description, SENSOR DATA group


OUTER DIAMETER

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if CIRCULAR is selected in the function PIPE TYPE
( 45) and OTHER was selected in the function PIPE STANDARD ( 45).
Description
Use this function to enter a value for the outer diameter.
The unit is taken from the function UNIT LENGTH ( 11).
User input
5-digit floating-point number
60 to 99999 (mm) or 2.362 to 3937 (inch) (country dependent 53)
Factory setting
168.3 (mm) or 6.0 (inch) (country dependent 53)

WALL THICKNESS

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is not available if a standard pipe was selected in the function PIPE TYPE
( 45), e.g. PN16.
Description
Use this function to enter a value for the wall thickness of the pipe or duct.
The unit is taken from the function UNIT LENGTH ( 11).
User input
2.0 to 40.0 (mm) or 0.08 to 1.57 (inch) (country dependent 53)
Factory setting
4.5 (mm) or 0.1771 (inch) (country dependent 53)

INTERNAL DIAMETER

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if CIRCULAR is selected in the function PIPE TYPE
( 45) and OTHER was selected in the function PIPE STANDARD ( 45).
Description
Use this function to view the internal diameter of a circular pipe.
The unit is taken from the function UNIT LENGTH ( 11).
Display
5-digit floating-point number
60 to 99999 (mm) or 2.362 to 3937 (inch) (country dependent 53)

INTERNAL HEIGHT

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if RETANGLUAR was selected in the function PIPE TYPE
( 45).
Description
Use this function to enter the internal height of a rectangular duct.
The unit is taken from the function UNIT LENGTH ( 11).
User input
5-digit floating-point number
45 to 99999 (mm) or 1.771 to 3937 (inch) (country dependent 53)
Factory setting
150.0 (mm) or 6.0 (inch) (country dependent 53)

46

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

SENSOR DATA

Function description, SENSOR DATA group


INTERNAL WIDTH

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if RECTANGULAR was selected in the PIPE TYPE
function ( 45).
Description
Use this function to enter the internal width of a rectangular duct.
The unit is taken from the function UNIT LENGTH ( 11).
User input
5-digit floating-point number
45 to 99999 (mm) or 1.771 to 3937 (inch) (country dependent 53)
Factory setting
150.0 (mm) or 6.0 (inch) (country dependent 53)

MOUNTING

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if RECTANGULAR is selected in the function PIPE TYPE
( 45).
Description
Use this function to select the installation direction of the insertion sensor in the
rectangular duct.
If the VERTICAL option is selected, the value from the function
INTERNAL HEIGHT ( 46) is used to calculate the insertion depth
If the HORIZONTAL option is selected, the value from the function
INTERNAL WIDTH ( 47) is used to calculate the insertion depth
Options
HORIZONTAL
VERTICAL
Factory setting
VERTICAL

MOUNTING SET
LENGTH

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
Description
Use this function to enter a value for the length of the mounting set (including the sensor
compression fitting).
The unit is taken from the function UNIT LENGTH ( 11).
User input
5-digit floating-point number
75 to 900 (mm) or 2.953 to 35.433 (inch) (country dependent 53)
Factory setting
106.0 (mm) or 4.173 (inch) (country dependent 53)
The factory setting value is the length of the G1A compression fitting and standard
Endress+Hauser mounting boss.

INSERTION DEPTH

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
Description
This function displays the calculated insertion depth for mounting the sensor.
The unit is taken from the function UNIT LENGTH ( 11).
For more information on insertion depth calculation, please refer to the Operating
Instructions BA00113D/06.
Display
5-digit floating-point number

Endress+Hauser

47

SENSOR DATA

Proline t-mass 65 FOUNDATION Fieldbus

Function description, SENSOR DATA group


ZERO POINT

Description
This function shows the current zero point correction value for the sensor. The zero
point is determined by the ZERO POINT ADJUST ( 35) function.
User input
5-digit floating-point number
20.000 to +20.000
Factory setting
Depends on calibration.

FLOW CONDITIONER

Description
Use this function to indicate if the t-mass 65F sensor has been calibrated with or without
a flow conditioner.
Display
WITH
WITHOUT
Factory setting
WITHOUT

CALIBRATION DATE

Description
Use this function to display the date of the last factory calibration of the measuring
device.
This date is not updated by the IN-SITU CALIBRATION function.
Options
DD.MM.YYYY

48

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

16

SUPERVISION

SUPERVISION

Function description, SUPERVISION group


ACTUAL SYSTEM
CONDITION

Description
The current system status appears on the display.
Display
SYSTEM OK or
The fault/notice message with the highest priority.

PREVIOUS SYSTEM
CONDITION

Description
The last 16 fault and notice messages appear on the display.

ALARM DELAY

Description
Use this function to enter a time delay for which the criteria for an error always has to be
satisfied before a fault or notice message is generated. Depending on the setting and the
type of error, this suppression acts on the display.

Note!
If this function is used, fault and notice messages are delayed by the time corresponding
to the setting before being forwarded to the higher-level controller (PLC, DCS, etc.).
Therefore, check in advance whether a delay of this nature could affect the safety
requirements of the process. If fault and notice messages are not be suppressed, than a
value of 0 seconds must be entered here.
User input
0 to 100 s (in steps of one second)
Factory setting
0s
SYSTEM RESET

Description
Use this function to restart (reset) the measuring device.
Options
NO
The device is not restarted.
RESTART SYSTEM
Restart without disconnecting main power. In doing so, all the data (functions) are
accepted unchanged.
Factory setting
NO

OPERATION HOURS

Description
The hours of operation of the device appear on the display.
Display
Depends on the number of hours of operation elapsed:
Hours of operation < 10 hours display format = 0:00:00 (hr:min:sec)
Hours of operation 10 to 10 000 hours display format = 0000:00 (hr:min)
Hours of operation >10 000 hours display format = 000000 (hr)

HOURS SINCE RESET

Description
The hours of operation since the last reset of the device appear on the display.
Display
Depends on the number of hours of operation elapsed:
Hours of operation < 10 hours display format = 0:00:00 (hr:min:sec)
Hours of operation 10 to 10 000 hours display format = 0000:00 (hr:min)
Hours of operation >10 000 hours display format = 000000 (hr)

Endress+Hauser

49

SIMULATION SYSTEM

Proline t-mass 65 FOUNDATION Fieldbus

17

SIMULATION SYSTEM

Function description, SIMULATION SYSTEM group


SIMULATION FAILSAFE
MODE

Description
Use this function to set all inputs, outputs and the totalizer to their error-response modes,
in order to check whether they respond correctly. During this time, the message #691
"SIMULATION FAILSAFE" appears on the display.
Options
OFF
ON
Factory setting
OFF

SIMULATION
MEASURAND

Description
Use this function to set all the inputs, outputs and the totalizer to their flow-response
modes, in order to check whether they respond correctly. During this time, the message
#692 "SIMULATION MEASURAND" appears on the display.

Note!
The measuring device can only be used for measuring to a certain extent while the
simulation is in progress.
The setting is not saved if the power supply fails.
Options
OFF
MASS FLOW
CORRECTED VOLUME FLOW
TEMPERATURE
HEAT FLOW
Factory setting
OFF
VALUE SIMULATION
MEASURAND

Prerequisite
Function is only available if the SIMULATION MEASURAND function ( 50) is
active.
Description
Use this function to specify an arbitrary value (e.g. 12 kg/s) to check the assigned
functions in the device itself and downstream signal circuits.
The unit depends on the option selected in the SIMULATION MEASURAND function
and is taken from the SYSTEM UNITS group ( 8).

Note!
The setting is not saved if the power supply fails.
User input
5-digit floating-point number
Factory setting
(country dependent 53)
0 kg/h; 0 lb/h (MASS FLOW)
0 Nm/h; 0 Sm/h (CORRECTED VOLUME FLOW)
0 MWh; 0 kBtu (HEAT FLOW)
0 C; +32 F (TEMPERATURE)

50

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

18

SENSOR VERSION

SENSOR VERSION

Function description, SENSOR VERSION group


SENSOR TYPE

Description
Use this function to view the sensor type.
Display
FLOWCELL (t-mass 65F flange sensor)
INSERTION (t-mass 65I insertion sensor)

Endress+Hauser

SERIAL NUMBER

Description
The serial number of the sensor appears on the display.

TRANSDUCER SERIAL
NUMBER

Description
The serial number of the transducer appears on the display.

SOFTWARE REVISION
NUMBER S-DAT

Description
Use this function to view the software revision number of the S-DAT.

PRE-AMPLIFIER
SOFTWARE REVISION
NUMBER

Description
Use this function to view the software revision number of the preamplifier.

PRE-AMPLIFIER
HARDWARE REVISION
NUMBER

Description
Use this function to view the hardware revision number of the preamplifier.

51

AMPLIFIER VERSION

Proline t-mass 65 FOUNDATION Fieldbus

19

AMPLIFIER VERSION

Function description, AMPLIFIER VERSION group

52

DEVICE SOFTWARE

Description
Use this function to display the current device software version.

HARDWARE REVISION
NUMBER AMPLIFIER

Description
Use this function to view the hardware revision number of the amplifier board.

SOFTWARE REVISION
NUMBER AMPLIFIER

Description
Use this function to view the software revision number of the amplifier board.

SOFTWARE REVISION
NUMBER T-DAT

Description
Use this function to view the software revision number of the T-DAT.

I/O MODULE TYPE

Description
Use this function to view the configuration of the I/O module.

SOFTWARE REVISION
NUMBER I/O MODULE

Description
Use this function to view the software revision number of the I/O module.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Factory settings

20

Factory settings

20.1

Language

Country

Language

Country

Language

Australia

English

Luxembourg

French

Austria

German

Malaysia

English

Belgium

English

The Netherlands

Dutch

Czechia

Czech

Norway

Norwegian

Denmark

English

Poland

Polish

England

English

Portugal

Portuguese

Finland

Finnish

Sweden

Swedish

France

French

Switzerland

German

Germany

German

Singapore

English

Hungary

English

Spain

Spanish

Hong Kong

English

South Africa

English

India

English

Thailand

English

Italy

Italian

Other countries

English

20.2

SI units (not for USA and Canada)

20.2.1

Low flow cut off, full scale value, pulse value

t-mass F sensor
With air at ambient conditions (without a flow conditioner)
Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[kg/h]

[kg/h]

[kg/p]

15

0.53

53

0.10

25

2.00

200

1.00

40

5.55

555

1.00

50

9.10

910

10.00

80

20.30

2030

10.00

100

37.50

3750

10.00

t-mass I sensor
With air at ambient conditions (without a flow conditioner)

Endress+Hauser

Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[kg/h]

[kg/h]

[kg/p]

80

20.30

2030

10.0

100

37.50

3750

10.0

150

75.00

7500

100.0

200

125.00

12500

100.0

250

200.00

20000

100.0

53

Factory settings

Proline t-mass 65 FOUNDATION Fieldbus

Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[kg/h]

[kg/h]

[kg/p]

300

280.00

28000

100.0

400

500.00

50000

100.0

500

800.00

80000

100.0

600

1150.00

115000

100.0

700

1590.00

159000

100.0

1000

3200.00

320000

100.0

1500

7200.00

720000

100.0

20.2.2

System units
Unit

Unit

Temperature

Length

mm

Density

kg/m

Pressure

bar a

Reference density

kg/m

Reference Pressure

bar a

Calorific Value Mass

MJ/kg

Calorific Value Corr. Vol.

MJ/m

Heat

kWh

Reference temperature

20.2.3

Unit totalizer 1 and 2


Unit

Mass flow

kg

Heat flow

MWh

20.2.4

Unit
Corrected volume flow

Nm

Other Units
Unit

54

Ref. combustion temp.

43

Pipe standard

according to DIN

45

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Factory settings

20.3

US units (only for USA and Canada)

20.3.1

Low flow cut off, full scale value, pulse value

t-mass F sensor
With air at ambient conditions; (without a flow conditioner)
Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[lb/hr]

[lb/hr]

[lb/p]

"

1.16

116

0.20

1"

4.40

440

2.00

1"

12.20

1220

2.00

2"

20.02

2002

20.00

3"

44.66

4466

20.00

4"

82.50

8250

20.00

t-mass I sensor
With air at ambient conditions; (without a flow conditioner)
Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[lb/hr]

[lb/hr]

[lb/p]

3"

44.66

4466

20.00

4"

82.50

8250

20.00

6"

165.00

16500

200.00

8"

275.00

27500

200.00

10"

440.00

44000

200.00

12"

610.00

61000

200.00

16"

1100.00

110000

200.00

20"

1760.00

176000

200.00

24"

2530.00

253000

200.00

28"

3498.00

349800

200.00

40"

7040.00

704000

200.00

60"

15840.00

1584000

200.00

20.3.2

SYSTEM UNITS
Unit

Endress+Hauser

Unit

Temperature

Length

inch

Density

lb/ft

Pressure

psi a

Reference density

lb/ft

Reference Pressure

psi a

Calorific Value Mass

kBtu/lb

Calorific Value Corr. Vol.

kBtu/Scf

Heat

kBtu

Reference temperature

55

Factory settings

Proline t-mass 65 FOUNDATION Fieldbus

20.3.3

Unit totalizer 1 and 2


Unit

Mass flow

lb

Heat flow

kBtu

20.3.4

Other Units

Unit
Corrected volume flow

Sm

Unit

56

Ref. combustion temp.

43

Pipe standard

according to ANSI

45

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Index function matrix

Index function matrix


Numerics
100% VALUE LINE 1 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . 25
100% VALUE LINE 2 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . 26

A
ACCESS CODE (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ACCESS CODE COUNTER (fct.) . . . . . . . . . . . . . . . . . . . .
ACTUAL SYSTEM CONDITION (fct.) . . . . . . . . . . . . . . . .
ALARM DELAY (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AMPLIFIER HARDWARE REVISION NUMBER (fct.) . . . . .
AMPLIFIER VERSION, function group. . . . . . . . . . . . . . . .
ANALYZER INPUT (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . .
ASSIGN GAS GROUP (fct.) . . . . . . . . . . . . . . . . . . . . . . . .
ASSIGN LINE 1 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ASSIGN LINE 2 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ASSIGN LOW FLOW CUTOFF (fct.) . . . . . . . . . . . . . . . . .
ASSIGN TOTALIZER (fct.). . . . . . . . . . . . . . . . . . . . . . . . .

23
24
49
49
52
52
38
28
25
25
34
28

B
BACKLIGHT (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
BLOCK SELECTION (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . . 32
BUSADRESSE (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

C
CALIBRATION DATE (fct.) . . . . . . . . . . . . . . . . . . . . . . . . 48
Calorific value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
CALORIFIC VALUE TYPE (fct.) . . . . . . . . . . . . . . . . . . . . . 42
CASCADE_IN VALUE (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . 32
CHECK VALUES (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
COMMUNICATION, function group. . . . . . . . . . . . . . . . . 31
CONTRAST LCD (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
CORRECTED VOLUME FLOW (fct.) . . . . . . . . . . . . . . . . . . 7
CORRECTION FACTOR (fct.) . . . . . . . . . . . . . . . . . . . . . . 39

D
Data back-up (of device data with T-DAT) . . . . . . . . . . . . .
DD REVISION (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DEFINE PRIVATE CODE (fct.) . . . . . . . . . . . . . . . . . . . . .
DESCRIPTION (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DEVICE PD-TAG (Fkt.). . . . . . . . . . . . . . . . . . . . . . . . . . .
DEVICE REVISION (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . . .
DEVICE SOFTWARE (fct.) . . . . . . . . . . . . . . . . . . . . . . . .
DEVICE TYPE (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPLAY DAMPING (fct.) . . . . . . . . . . . . . . . . . . . . . . . . .

22
32
23
39
31
32
52
31
26

F
FAILSAFE MODE (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . .
FLOW CONDITIONER (fct.) . . . . . . . . . . . . . . . . . . . . . . .
FLOW DAMPING (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . .
FORMAT (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30
48
44
26

G
Gas pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GAS TYPE 1 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GAS TYPE 2 to 8 (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . . .
Endress+Hauser

19
17
38
40

GAS, function group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37


GROSS CALORIFIC VALUE (fct.). . . . . . . . . . . . . . . . . . . . 34

H
HANDLING TOTALIZER, function group . . . . . . . . . . . . . 30
Heat flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
HEAT FLOW (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
HEAT FLOW, function group. . . . . . . . . . . . . . . . . . . . . . . 42
HEATING VALUE 1 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . 42
HOURS SINCE RESET (fct.). . . . . . . . . . . . . . . . . . . . . . . . 49

I
I/O MODULE (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O-MODULE SOFTWARE REVISION NUMBER (fct.) . . .
IN VALUE (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSERTION DEPTH (fct.) . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION FACTOR (fct.) . . . . . . . . . . . . . . . . . . . . .
INTERNAL DIAMETER (fct.) . . . . . . . . . . . . . . . . . . . . . . .
INTERNAL HEIGHT (fct.) . . . . . . . . . . . . . . . . . . . . . . . . .
INTERNAL WIDTH (fct.). . . . . . . . . . . . . . . . . . . . . . . . . .

52
52
32
47
36
46
46
47

L
LANGUAGE (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

M
MANUFACTURER ID (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . 31
MASS FLOW (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
MEASURED VALUES, function group . . . . . . . . . . . . . . . . . 7
MODE 1 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
MODE 2 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
MOLE % GAS 1 (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
MOLE % GAS 1 (PROCESS PARAMETER) (fct.). . . . . . . . . 34
MOLE % GAS 2 to 8 (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . 40
MOUNTING (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
MOUNTING SET LENGTH (fct.) . . . . . . . . . . . . . . . . . . . . 47

N
NET CALORIFIC VALUE (fct.). . . . . . . . . . . . . . . . . . . . . . 34
NOMINAL DIAMETER (fct.) . . . . . . . . . . . . . . . . . . . . . . . 45
NUMBER OF GASES (fct.). . . . . . . . . . . . . . . . . . . . . . . . . 38

O
OFF-VALUE LOW FLOW CUTOFF (fct.) . . . . . . . . . . . . . .
ON-VALUE LOW FLOW CUTOFF (fct.) . . . . . . . . . . . . . .
OPERATING PRESSURE (fct.) . . . . . . . . . . . . . . . . . . . . . .
OPERATION HOURS (fct.) . . . . . . . . . . . . . . . . . . . . . . . .
OPERATION, function group. . . . . . . . . . . . . . . . . . . . . . .
OUTER DIAMETER (fct.). . . . . . . . . . . . . . . . . . . . . . . . . .
OVERFLOW (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

35
35
33
49
23
46
28

P
PIPE STANDARD (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . .
PIPE TYPE (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
POSITIVE ZERO RETURN (fct.) . . . . . . . . . . . . . . . . . . . . .
PRE-AMPLIFIER HARDWARE REVISION NUMBER (fct.) .
PRE-AMPLIFIER SOFTWARE REVISION NUMBER (fct.) . .
PREVIOUS SYSTEM CONDITION (fct.). . . . . . . . . . . . . . .

45
45
44
51
51
49

57

Proline t-mass 65 FOUNDATION Fieldbus

Index function matrix

PROCESS PARAMETER, function group . . . . . . . . . . . . . . 33


PROCESS PRESSURE 1 (fct.) . . . . . . . . . . . . . . . . . . . . . . . 33
PROCESS PRESSURE 2 (fct.) . . . . . . . . . . . . . . . . . . . . . . . 33

Q
Quick setup
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data back-up (of device data with T-DAT) . . . . . . . . . .
Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICK SETUP COMMISSIONING (fct.) . . . . . . . . . . . . . .
QUICK SETUP GAS (fct.) . . . . . . . . . . . . . . . . . . . . . . . . .
QUICK SETUP HEAT FLOW (fct.) . . . . . . . . . . . . . . . . . . .
QUICK SETUP PRESSURE (fct.). . . . . . . . . . . . . . . . . . . . .
QUICK SETUP SENSOR (fct.) . . . . . . . . . . . . . . . . . . . . . .
QUICK SETUP, function group . . . . . . . . . . . . . . . . . . . . .

14
22
17
20
19
16
12
12
12
12
12
12

R
REF. COMBUSTION TEMPERATURE (fct.) . . . . . . . . . . . .
REFERENCE DENSITY (fct.) . . . . . . . . . . . . . . . . . . . . . . .
REFERENCE DENSITY (PROCESS PARAMETER) (fct.) . . .
REFERENCE PRESSURE (fct.) . . . . . . . . . . . . . . . . . . . . . .
REFERENCE TEMPERATURE (fct.) . . . . . . . . . . . . . . . . . .
RESET ALL TOTALIZERS (fct.) . . . . . . . . . . . . . . . . . . . . .
RESET TOTALIZER (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . .

U
UNIT CALORIFIC VALUE CORRECTED VOLUME (fct.) . . 9
UNIT CALORIFIC VALUE MASS (fct.) . . . . . . . . . . . . . . . . 9
UNIT CORRECTED VOLUME (fct.) . . . . . . . . . . . . . . . . . . 9
UNIT CORRECTED VOLUME FLOW (fct.). . . . . . . . . . . . . 8
UNIT DENSITY (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
UNIT HEAT (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
UNIT HEAT FLOW (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . 10
UNIT LENGTH (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
UNIT MASS (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
UNIT MASS FLOW (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . 8
UNIT PRESSURE (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
UNIT TEMPERATURE (fct.) . . . . . . . . . . . . . . . . . . . . . . . 11
UNIT TOTALIZER (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . 29
USER INTERFACE, function group . . . . . . . . . . . . . . . . . . 25

V
VALUE SIMULATION MEASURAND (fct.) . . . . . . . . . . . . 50

W
43
39
34
33
33
30
29

WALL THICKNESS (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . 46


WRITE PROTECTION (fct.) . . . . . . . . . . . . . . . . . . . . . . . 31

Z
ZERO POINT (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
ZERO POINT ADJUST (fct.) . . . . . . . . . . . . . . . . . . . . . . . 35

S
SAVE CHANGES (fct.). . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
SELECT GROUP (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
SENSOR DATA, function group . . . . . . . . . . . . . . . . . . . . . 45
Sensor setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SENSOR TYPE (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
SENSOR VERSION, function group . . . . . . . . . . . . . . . . . . 51
SERIAL NUMBER (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
SERIAL NUMBER (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SIMULATION (Fkt.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SIMULATION FAILSAFE MODE (fct.) . . . . . . . . . . . . . . . . 50
SIMULATION MEASURAND (fct.) . . . . . . . . . . . . . . . . . . 50
SIMULATION SYSTEM, function group. . . . . . . . . . . . . . . 50
SOFTWARE REVISION NUMBER AMPLIFIER (fct.) . . . . . 52
SOFTWARE REVISION NUMBER S-DAT (fct.) . . . . . . . . . 51
SOFTWARE REVISION NUMBER T-DAT (fct.) . . . . . . . . . 52
STATUS ACCESS (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SUM (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SUPERVISION, function group . . . . . . . . . . . . . . . . . . . . . 49
SYSTEM PARAMETER, function group . . . . . . . . . . . . . . . 44
SYSTEM RESET (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
SYSTEM UNITS, function group . . . . . . . . . . . . . . . . . . . . . 8

T
T-DAT (HistoROM)
Save/load (data back-up, e.g. for replacing devices) . . . 22
T-DAT SAVE/LOAD (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . 13
TEMPERATURE (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
TEST DISPLAY (fct.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
TOTALIZER 1/2, function group . . . . . . . . . . . . . . . . . . . . 28
TRANSDUCER SERIAL NUMBER (fct.) . . . . . . . . . . . . . . . 51

58

Endress+Hauser

Operation via FOUNDATION Fieldbus

Proline t-mass 65 FOUNDATION Fieldbus

Table of contents for FOUNDATION Fieldbus

Table of contents for FOUNDATION Fieldbus


1

Block mode . . . . . . . . . . . . . . . . . . . . . 4

Resource Block. . . . . . . . . . . . . . . . . . . 6

2.1
2.2
2.3
2.4
2.5

Selecting the operating mode . . . . . . . . . . . . . . . . . .


Block status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Write protection and simulation . . . . . . . . . . . . . . . .
Alarm detection and processing . . . . . . . . . . . . . . . .
Resource Block parameters . . . . . . . . . . . . . . . . . . .

Transducer Block . . . . . . . . . . . . . . . . . 9

3.1
3.2
3.3
3.4
3.5
3.6
3.7

Signal processing . . . . . . . . . . . . . . . . . . . . . . . . . .
Important functions and parameters
of the Transducer Blocks . . . . . . . . . . . . . . . . . . . .
"Flow" Transducer Block parameters . . . . . . . . . . .
"Diagnosis" Transducer Block parameters . . . . . . . .
"Display" Transducer Block parameters . . . . . . . . .
"Totalizer"Transducer Block parameters . . . . . . . . .
"Heat Flow"Transducer Block parameters . . . . . . . .

Function blocks . . . . . . . . . . . . . . . . . 42

Analog Input function block . . . . . . . . 43

5.1
5.2

Signal processing . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Important functions and parameters of the
Analog Input function blocks . . . . . . . . . . . . . . . . . 45

Discrete Output function block . . . . . 50

6.1
6.2

Signal processing . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Important functions and parameters of the Discrete
Output function block . . . . . . . . . . . . . . . . . . . . . . 51

Additional function blocks . . . . . . . . . 53

Factory settings . . . . . . . . . . . . . . . . . 54

8.1
8.2
8.3

Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
SI units (not for USA and Canada) . . . . . . . . . . . . . 54
US units (only for USA and Canada) . . . . . . . . . . . . 56

6
6
7
7
8

10
11
13
26
29
33
36

Index FOUNDATION Fieldbus . . . . . . . . . . 58

Endress+Hauser

Block mode

Proline t-mass 65 FOUNDATION Fieldbus

Block mode

In the FOUNDATION Fieldbus all the device parameters are categorized according to their
functional properties and task and are generally assigned to three different blocks. A block may be
regarded as a container in which parameters and the associated functionalities are contained.
A FOUNDATION Fieldbus device has the following block types.
A Resource Block
The Resource Block contains all the device-specific characteristics of the device.
One or more Transducer Blocks (transmission blocks)
The Transducer Block contains all the measuring technology and device-specific parameters of the
device. The measurement principles (e.g. flow, temperature) are depicted in the Transducer
Blocks in accordance with the FOUNDATION Fieldbus specification.
One or more function blocks
Function blocks contain the automation functions of the device. We distinguish between different
function blocks, e.g. Analog Input function block, Analog Output function block, PID function
block (PID controller), etc. Each of these function blocks is used to process different application
functions.
Different automation tasks can be realized depending on the arrangement and connection of the
individual blocks. In addition to these blocks, a field device may have any number of further blocks,
e.g. several Analog Input function blocks if more than one process variable is available from the field
device.
The t-mass 65 FOUNDATION Fieldbus has the following blocks:
1 Resource Block
5 Transducer Blocks
12 function blocks consisting of:
5 Analog Input function blocks
1 Analog Output function blocks
1 Discrete Output function block
1 PID function block
1 Arithmetic function block
1 Input Selector function block
1 Signal Characterizer function block
1 Integrator function block

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Block mode

Analog Input
Function Block

Transducer
Block

Analog Output
Block
FOUNDATION
Fieldbus

Discrete Output
Block

Resource
Block

PID
Block

ARITHMETIC
Block

INPUT
Block

SIGNAL
Block

INTEGRATOR
Block

A0014989-en

Fig. 1:

t-mass 65 FOUNDATION Fieldbus blocks

The sensor signal is first prepared specifically for the flow in the measuring block (the Transducer
Block). The process variables are then passed to the Analog Input function blocks for technical
processing (e.g. scaling, limit value processing).
The process variables go through the complete function block algorithm and are available to other
function blocks, e.g. the PID block, as a starting variable for connecting the desired application
function.
Using the Discrete Output function block (DO), various actions and functions in the t-mass 65
can be initiated and controlled via FOUNDATION Fieldbus.

Endress+Hauser

Note!
Additional function blocks such as the PID, Arithmetic, Input Selector, Signal Characterizer and
Integrator function block are described in the "FOUNDATION Fieldbus Overview" (BA013S)
Operating Instructions (available at: www.endress.com download).

Resource Block

Proline t-mass 65 FOUNDATION Fieldbus

Resource Block

A Resource Block contains all the data that uniquely identifies and characterizes the field device. It
is an electronic version of a nameplate on the field device. Parameters of the Resource Block include
device type, device name, manufacturer ID, serial number, etc.
A further task of the Resource Blocks is the management of overall parameters and functions that
have an influence on the execution of the remaining blocks in the field device. The Resource Block
is thus the central unit that also checks the device status and thereby influences or controls the
operability of the other blocks and thus also of the device. Since the Resource Block has no block
input and block output data, it cannot be linked with other blocks.
The most important functions and parameters of the Resource Block are listed below; you will find
an overview of all the available parameters starting on 8

2.1

Selecting the operating mode

The operating mode is configured via the MODE_BLK parameter group.


The Resource Block supports the following operating modes:
AUTO (automatic mode)
OOS (out of service)

Note!
The block status OOS is also shown via the parameter BLOCK_ERR.In operating mode OOS, if write
protection is not enabled, you can access all the write parameters without restriction.

2.2

Block status

The current operating status of the Resource Block is shown in the parameter RS_STATE.
The Resource Block can take on the following states:
STANDBY
The Resource Block is in the OOS mode.
It is not possible to execute the remaining blocks.
ONLINE LINKING
The connections configured between the function blocks have not yet been linked.
ONLINE
Normal operating status, the Resource Block is in the AUTO operating mode. The configured
connections between the function blocks have been established.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

2.3

Resource Block

Write protection and simulation

Write protection of the device parameters and simulation in the Analog Input and Discrete Output
Function Block can be locked or unlocked via a jumper setting on the FOUNDATION Fieldbus
I/O board (Operating Instructions BA00134D/06).
The parameter WRITE_LOCK shows the status of the hardware write protection. The following
statuses are possible:
LOCKED
Device data cannot be modified via the FOUNDATION Fieldbus interface.
NOT LOCKED
Device data can be modified via the FOUNDATION Fieldbus interface.
The parameter BLOCK_ERR indicates whether a simulation is possible in the Analog Input and
Discrete Output function block:
Simulation Active
Simulation possible in the Analog Input function block via the SIMULATE parameter and in the
Discrete Output function block via the SIMULATE_D parameter.

2.4

Alarm detection and processing

Process alarms provide information on particular block statuses and block events. The status of the
process alarms is communicated to the fieldbus host system via the parameter BLOCK_ALM. The
parameter ACK_OPTION specifies whether an alarm must be acknowledged via the fieldbus host
system.
The following process alarms are generated by the Resource Block:
Block process alarms
The following block process alarms of the Resource Block are shown via the parameter:
OUT OF SERVICE
SIMULATE ACTVE
Write protection process alarm
If write protection is disabled on the FOUNDATION Fieldbus I/O board, then prior to
communicating the change of status to the fieldbus host system the alarm priority specified in the
parameter WRITE_PRI is checked. The alarm priority specifies the action taken when the write
protection alarm WRITE_ALM is enabled.

Endress+Hauser

Note!
If the option of a process alarm has not been enabled in the parameter ACK_OPTION, this process
alarm only has to be acknowledged in the parameter BLOCK_ALM.
The parameter ALARM_SUM shows the current status of all the process alarms.

Resource Block

Proline t-mass 65 FOUNDATION Fieldbus

2.5

Resource Block parameters

The following table shows the Endress+Hauser-specific parameters of the Resource Block.

Note!
FOUNDATION Fieldbus parameters are described in the Operating Instructions "FOUNDATION
Fieldbus Overview" (BA013S) (available at: www.endress.com download).
Resource Block
Parameter

Write access with


operating mode
(MODE_BLK

Description

Sensor - Serial Number

read only

Use this function to view the sensor serial number.

Amp. - HW Rev.Number

read only

Use this parameter to view the hardware revision


number of the amplifier.

Amp. - HW Identification

read only

Use this parameter to view the hardware ID number of


the amplifier.

Amp. - SW Rev.Number

read only

Use this function to view the software revision number


of the amplifier.

Amp. - SW Identification

read only

Use this function to view the software ID number of the


amplifier.

Amp. - Prod.-Number

read only

Use this parameter to view the production number of the


amplifier.

Amp. - SW-Rev.No.
T-DAT

read only

Use this parameter to view the software revision number


of the software used to create the content of the T-DAT.

I/O - Type

read only

Use this function to view the I/O module type.

I/O - HW Rev.Number

read only

Use this function to view the hardware revision number


of the I/O module.

I/O - HW Identification

read only

Use this parameter to view the hardware ID number of


the I/O module.

I/O - SW Rev.Number

read only

Use this function to view the software revision number


of the I/O module.

I/O - SW Identification

read only

Use this parameter to view the software ID number of


the I/O module.

I/O - Prod.Number

read only

Use this function to view the production number of the


I/O module.

Device Software

read only

Use this function to view the device software version.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

Transducer Block

The Transducer Blocks contain all the measurement- and device-specific parameters of the
flowmeter. All the settings directly connected with the flow measurement/application are made
here. They form the interface between the sensor-specific measured value preprocessing and the
Analog Input function blocks required for automation.
A Transducer Block allows you to influence the input and output values of a function block. The
parameters of a Transducer Block include information on the sensor type, sensor configuration,
physical units, calibration, damping, diagnosis, etc. as well as the device-specific parameters. The
device-specific parameters and functions are split into several Transducer Blocks, each covering
different task areas.
"Flow" Transducer Block / base index 1400:
This block contains all the flow-specific parameters and functions, e.g. calibration functions, sensor
data, etc. 13
"Diagnosis" Transducer Block / base index 1600:
This block contains all the parameters for system diagnosis, e.g. current system status etc
usw. 26
"Display" Transducer Block / base index 1800:
This block contains all the parameters for configuring the local display
29
"Totalizer" Transducer Block / base index 1900:
This block contains all the parameters for configuring the totalizers
33
"Heat Flow" Transducer Block / base index 2700:
This block contains all the parameters for configuring gas measurement
36

Endress+Hauser

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

3.1

Signal processing

The following figure shows the internal structure of the individual Transducer Blocks:

Transducer Block Flow


Simulation Value Measurand
Simulation Measurand
Low Flow
Cut Off

Positive Zero
Return

Amplifier

Off Value

Auto

Low Flow Cut Off


Pressure Shock Suppression
Empty Pipe Detection

O/S

Mode_BLK

Signals

On Value

Transducer Block Totalizer

Mass Flow

CH 1

Volume
Flow

CH 2

Temperature

CH 6

Totalizer ... - Mode


Totalizer ... - Reset
Tot. 1 - Assign
Totalizer 1

Mode_BLK
Volume Flow

Auto

CH 7

Tot. 2 - Assign

O/S

Totalizer 2

CH 8

Mass Flow
Auto

Tot. - Reset All

Transducer Block Diagnosis


Transducer Block Display

AI Block

Transducer Block Heat Flow


A0014992-en

Fig. 2:

Internal structure of the individual Transducer Blocks

The Transducer Block receives several signals from the sensor as input values (mass, density,
temperature). Other process variables (volume, standard volume) are derived from these signals.
The input signals further processed via an amplifier. A low flow cut off allows you to hide
measurement inaccuracies in the low-flow sector. The parameter "Low Flow Cut Off -On-Value"
( 17) allows you to define a limit value. If the measured flow value is below this limit value
then the output value of 0 is output.
The parameter "Simulation - Value Measurand" ( 24) allows you to specify a simulation value
for the Transducer Block in order to test assigned parameters in the device and subsequent function
blocks. In addition, the parameter "System Parameter - Positive Zero Return" ( 21) allows you
to switch the measured value to "Zero Flow". This is necessary when a piping system is being
cleaned, for example.
Output variables (process variables) that are made available by the Transducer Blocks 11,
Output Variable Block.
A process variable, e.g. mass flow, volume flow, etc., can be assigned to the individual totalizers.
Each totalizer can be manually reset using the parameter Totalizer (1 - 3) Reset. The most important
functions and parameters of the Transducer Blocks are listed below. You will find an overview of all
the available parameters starting on 13.

10

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

3.2

Important functions and parameters


of the Transducer Blocks

3.2.1

Block output values

The Transducer Blocks make the following output variables (process variables) available. The
CHANNEL parameter in the Analog Input function block is used to assign which process variable is
read in and processed in the downstream Analog Input function block.

Note!
The "Diagnosis" and "Display" Transducer Blocks do not have any output variables.
Block

Process variable

"Flow" Transducer Block

Mass flow

Volume flow

Temperature

Totalizer 1

Totalizer 2

Gas analyzer and Heat flow measurement

53

"Totalizer" Transducer Block

"Heat Flow" Transducer Block

3.2.2

Channel parameter
(AI Block)

Selecting the operating mode

The operating mode is configured via the MODE_BLK parameter group.


The Transducer Blocks support the following operating modes:
AUTO (automatic mode)
OOS (out of service)

Note!
The block status OOS is also shown via the parameter BLOCK_ERR. In operating mode OOS, if
write protection is not enabled and the release code is entered, you can access all the write
parameters without restriction.
The following applies for the "Flow" and "Totalizer" Transducer Blocks: In the "OOS" operating
mode, the process variables are updated but the status of the output value OUT (AI Block) changes
to "BAD".
If problems occur during the configuration of the function blocks See Operating Instructions
BA00135D/06, "Troubleshooting" section.

3.2.3

Alarm detection and processing

The Transducer Blocks do not generate any process alarms. The status of the process variables is
evaluated in the subsequent Analog Input function blocks. If the Analog Input function block does
not receive an input value that can be evaluated from the Transducer Blocks, then a process alarm
is generated. This process alarm is displayed in the BLOCK_ERR parameter of the Analog Input
function block (BLOCK_ERR = Input Failure).
The parameter BLOCK_ERR of the "Diagnosis" Transducer Block displays the device error that
produced the input value that could not be evaluated and thus triggered the process alarm in the
Analog Input function block.
In addition, the active device error is displayed via the "Diagnosis" Transducer Block in the
"Diag. - Act.Sys.Condition" parameter ( 26).
For more information on rectifying errors See Operating Instructions BA00135D/06,
"Troubleshooting" section.

Endress+Hauser

11

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

3.2.4

Diagnosis

The status of the device is displayed via the following parameters specified in the FOUNDATION
Fieldbus specification:
BLOCK_ERR
Transducer Error
Detailed information on the current device status is displayed via the "Diagnosis" Transducer Block
in the manufacturer-specific parameter "Diag. -Act. Sys. Condition" ( 26).
For more information on rectifying errors See Operating Instructions BA00135D/06,
"Troubleshooting" section.

3.2.5

Accessing the device-specific parameters

To access the device-specific parameters the following requirements must be met:

12

1.

Hardware write protection must be deactivated See Operating Instructions BA00135D/06.

2.

The correct code must be entered in the parameter "Access - Code" via the corresponding
Transducer Block.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

3.3

Transducer Block

"Flow" Transducer Block parameters

The following table shows the Endress+Hauser-specific parameters of the "Flow" Transducer Block.
These can only be changed after entering a release code in the "Access - Code" parameter.

Note!
FOUNDATION Fieldbus parameters are described in the Operating Instructions "FOUNDATION
Fieldbus Overview" (BA013S) (available at: www.endress.com download).
"Flow" Transducer Block / base index 1400

Parameter

Access - Code

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
All data of the measuring system are protected against inadvertent change.
Only when the code has been entered in this parameter can the
manufacturer-specific parameters be programmed and the device
configuration modified.
You can enable programming by entering:
Code 65(factory setting)
Personal code (Access Def.Private Code parameter 29)

Note!
If the hardware write protection is enabled then access to the
manufacturer-specific parameters is blocked even if the right code is
entered
You can disable programming again by entering any number (other than
the release code) in this parameter.
The Endress+Hauser service organization can be of assistance if you
mislay your personal code.
Certain parameters are not accessible unless a special service code is
entered. This service code is known only to the Endress+Hauser service
organization. Please contact your Endress+Hauser service center if you
require clarification.
User input
Max. 4-digit number: 0 to 9999
Access - Status

read only

Description
Use this parameter to check the access status for the parameter matrix.
Display
LOCKED (parameterization disabled)
ACCESS CUSTOMER (parameterization enabled)
ACCESS SERVICE (parameterization enabled)

System Value - Mass


Flow

read only

Description
The currently measured mass flow appears on the display.
Display
5-digit floating-point number, including unit
e.g. 462.87 kg/h; 731.63 lb/min

Endress+Hauser

13

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Flow" Transducer Block / base index 1400

Parameter

System Unit - Mass


Flow

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
For selecting the unit required and displayed for the mass flow.
The unit you select here is also valid for:
Low flow cut off
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options
SI:
Gram g/time unit
Kilogram kg/time unit
Metric ton t/time unit
US:
Ounce oz/time unit
Pound lb/time unit
Ton ton/time unit
Factory setting
kg/h or lb/h (country dependent 54)

System Value Corr.Volume Flow

read only

Description
The calculated corrected volume flow appears on the display.
The corrected volume flow is calculated from the measured mass flow and
the reference density of the gas.
Display
5-digit floating-point number, including unit
e.g. 104.97 Nm3/h; 110.73 Sm3/h; etc.

System Unit Corr.Volume Flow

AUTO - OOS

Description
For selecting the unit required and displayed for the corrected volume flow.
The unit you select here is also valid for:
Low flow cut off
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options
SI:
Norm cubic meter Nm/time unit
Norm liter Nl/time unit
US:
Standard cubic meter Sm/time unit
Standard cubic feet Scf/time unit
Factory setting
Nm/h or Sm/h (country dependent 54)

System Unit - Calorific


Value Mass

AUTO - OOS

Description
For selecting the unit required and displayed for the gross/net calorific
value.
Options (SI units)
kJ/kg
MJ/kg
kWh/kg
MWh/kg
kcal/kg
Mcal/kg
Options (US units)
Btu/lb
kBtu/lb
Factory setting
MJ/kg or kBtu/lb (country dependent 54)

14

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Flow" Transducer Block / base index 1400

Parameter

System Unit- Calorific


Value Corrected
Volume

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
For selecting the unit required and displayed for the calorific value based on
the corrected volume.
Options (SI units):
kJ/Nm
MJ/Nm
kWh/Nm
MWh/Nm
kcal/Nm
Mcal/Nm
Options (US units):
kJ/Sm
MJ/Sm
kWh/Sm
MWh/Sm
kcal/Sm
Mcal/Sm
Btu/Scf
kBtu/Scf
Factory setting
MJ/Nm or kBtu/Scf (country dependent 54)

System Value - Heat


Flow

read only

Description
The calculated heat flow appears on the display.
Display
5-digit floating-point number, including unit,
(e.g. 175.00 kJ/h; 50.000 kBtu/h; etc.)

System Unit - Heat


Flow

AUTO - OOS

Description
For selecting the unit required and displayed for the heat flow.
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options (SI unit)
kW
MW
kJ/time unit
MJ/time unit
GJ/time unit
kcal/time unit
Mcal/time unit
Gcal/time unit
Options (US unit)
tons
kBtu/time unit
MBtu/time unit
GBtu/time unit
Factory setting
kW or kBtu/h (country dependent 54)

Endress+Hauser

15

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Flow" Transducer Block / base index 1400

Parameter

System Unit - Heat

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
For selecting the unit required and displayed for the heat.
The following time units can be selected:
s = second, m = minute, h = hour, d = day
Options (SI units)
kWh
MWh
kJ
MJ
GJ
kcal
Mcal
Gcal
Options (US units)
tonh
kBtu
MBtu
GBtu
Factory setting
kWh or kBtu (country dependent 54)

System Unit Pressure

AUTO - OOS

Description
Use this function to select the unit for pressure.
The unit you select here is also valid for:
Process pressure (Process Pressure 1 und 2, 19)
Reference pressure (Reference Pressure, 19)
Options
bar a (bar absolute)
psi a (pounds per square inch absolute)
kPa a (kilopascal absolute)
mmHg 0C a (millimeter mercury absolute)
inHg 32F a (inch mercury absolute)
mmH2O 4C a (millimeter water absolute)
inH2O 39F a (inch water absolute)
kg/cm2 a (kilogram per centimeter squared absolute)
Factory setting
bar a or psi a (country dependent 54)

System Value Temperature

read only

Description
The currently measured temperature appears on the display.
Display
5-digit fixed-point number, incl. unit and sign
e.g. 23.4 C, 160.0 F, 295.4 K

System Unit Temperature

AUTO - OOS

Description
For selecting the unit required and displayed for the temperature.
Options
C (CELSIUS)
K (KELVIN)
F (FAHRENHEIT)
R (RANKINE)
Factory setting
C or F (country dependent 54)

16

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Flow" Transducer Block / base index 1400

Parameter

System Unit Density

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
For selecting the unit required and displayed for the calculated gas density at
process conditions. The unit you select here is also valid for:
Reference density (Process Pressure 1 und 2, 19)
Options
SI:
g/cm
g/cc
kg/dm
kg/l
kg/m
US:
lb/ft
Factory setting
kg/m or lb/ft (country dependent 54)

System Unit Length

AUTO - OOS

Prerequisite
This function is only available for the insertion sensor (t-mass 65I)
Description
For selecting the unit of length required and displayed for the pipe internal
diameter or the inner dimensions of rectangular ducts.
Options
MILLIMETER
INCH
Factory setting
MILLIMETER or INCH (country dependent 54)

Low Flow Cut Off Assign

AUTO - OOS

Description
For selecting the process variable on which low flow cut off should act.
Options
OFF
MASS FLOW
CORRECTED VOLUME FLOW
Factory setting
MASS FLOW

Low Flow Cut Off -On


Value

AUTO - OOS

Prerequisite
This function is not available if OFF was selected in the Low Flow Cut Off Assign ( 17).
Description
Use this function to enter the on-value for low flow cut off.
Low flow cut off is switched on if the value entered is not equal to 0. An
inverted plus sign is shown on the local display of the flow value as soon as
the low flow cut off is active.
User input
5-digit floating-point number
Factory setting
1 % of full scale value

Low Flow Cut Off Unit

read only

Description
Displays the unit of the low flow cut off.

Note!
Depending on the process variable selected, the unit is taken from the
corresponding parameter "System Unit - Mass Flow", "System Unit - Volume
Flow" or "System Unit - Corr.Volume Flow".

Endress+Hauser

17

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Flow" Transducer Block / base index 1400

Parameter

Low Flow Cut Off -Off


Value

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
Use this function to enter the off-value for low flow cut off. Enter the offvalue as a positive hysteresis from the on-value.

H
1

1
c

a0001245

Fig. 3:
Q
t
H
a
b
c
1
2

Example for the behavior of low flow cutoff


Flow rate [volume/time]
Time
Hysteresis
ON VALUE LOW FLOW CUT OFF = 20 kg/h
OFF-VALUE LOW FLOW CUTOFF = 10%
Low flow cutoff active
Low flow cut off is switched on at 20 kg/h
Low flow cut off is switched off at 22 kg/h

User input
Integer 0 to 100%
Factory setting
50%
Adj. - Zeropoint
Adjustment

AUTO - OOS

Description
Use this function to start automatic zero point adjustment.

"

Caution!
Prior to performing zero point adjustment, observe the exact procedure for
zero point adjustment as specified in Operating Instructions BA00135D/06.

Note!
If zero point adjustment is not possible due to unstable flow conditions,
alarm #451 "ADJUST ZERO FAIL" appears on the display.
RESET: reset to factory calibration.
Options
START
CANCEL
RESET
Factory setting
CANCEL
Installation Factor

AUTO - OOS

Description
Disturbances in the flow may arise due to the design of the system, such as
pipe bends, reducers, etc. The flow value measured is scaled by entering a
constant factor. The flow disturbance can thus be compensated using the
calculated flow signal:
Flow output = measured flow installation factor
Enter a higher value: flow value output is increased.
Enter a lower value: flow value output is decreased.
User input
5-digit floating-point number
0.0000 to 99999
Factory setting
1.0000

18

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Flow" Transducer Block / base index 1400

Parameter

Process Pressure 1

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Prerequisite
This function is not available if the In-Situ Calibration function has been
enabled. Refer to your Endress+Hauser service representative for more
information.
Description
Use this function to enter the process pressure for Gas Group 1.
The unit is taken from the function System Unit - Pressure ( 16).
Input/display
5-digit floating-point number
Factory setting
1.0130 [bar a] or 14.692 [psi a] (country dependent 54)

Process Pressure 2

AUTO - OOS

Prerequisite
This function is not available if the In-Situ Calibration function has been
enabled. Refer to your Endress+Hauser service representative for more
information.
Description
Use this function to enter the process pressure for Gas Group 2.
The unit is taken from the function System Unit - Pressure ( 16).
Input/display
5-digit floating-point number
Factory setting
1.0130 [bar a] or 14.692 [psi a] (country dependent 54)

Press.Corr. Pressure

AUTO - OOS

Description
Use this function to display the pressure value which is used for the flow
calculation. The value is read from the following function:
Process Pressure 1 or 2 (depending on which gas group is active)
The unit is taken from the function System Unit - Pressure ( 16).
Display
5-digit floating-point number
Factory setting
1.0130 [bar a] or 14.692 [psi a] (country dependent 54)

Ref.Param. - Ref.
Temperature

AUTO - OOS

Description
Use this function to enter the reference temperature for calculating the
reference density (for corrected volume flow measurement).
The unit is taken from the function System Unit - Temperature ( 16).
User input
5-digit floating-point number
Factory setting
0.0 [C] or +32.0 [F] (country dependent 54.)

Reference Pressure

AUTO - OOS

Description
Use this function to enter the reference temperature for calculating the
reference density (for corrected volume flow measurement).
The unit is taken from the function System Unit - Pressure ( 16).
User input
5-digit floating-point number
Factory setting
0.0 [C] or +32.0 [F] (country dependent 54.)

Endress+Hauser

19

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Flow" Transducer Block / base index 1400

Parameter

Reference Density

Write access
with operating
mode
(MODE_BLK)
read only

Description

Prerequisite
This function is not available if the In-Situ Calibration function has been
enabled. Refer to your Endress+Hauser service representative for more
information.
Description
Use this function to display the calculated reference density (for corrected
volume flow measurement).
The unit is taken from the function System Unit - Density ( 17).
Display
5-digit floating-point number

Net Calorific Value

read only

Prerequisite
This function is only available if AUTO NET or MANUAL was selected in
the Group 1 to 2 - Mode 1 to 2 ( 40).
Description
Use this function to display the current net calorific value of the gas.
The unit is taken from the function System Unit - Calorific Value Mass
( 14) or System Unit- Calorific Value Corrected Volume ( 15).
Display
5-digit floating-point number

Gross Calorific Value

read only

Prerequisite
This function is only available if AUTO GROSS or MANUAL was selected in
the Group 1 to 2 - Mode 1 to 2 ( 40).
Description
Use this function to display the current gross calorific value of the gas.
The unit is taken from the function System Unit - Calorific Value Mass
( 14) or System Unit- Calorific Value Corrected Volume ( 15).
Display
5-digit floating-point number

Mole % Gas 1

read only

Prerequisite
This function is not available if OFF was selected in the Group 1 to 2 Analyzer Input ( 37).
Description
Use this function to display the Mole % of Group 1 to 2 - Gas Type 1
37 in accordance with the input signal of the gas analyzer.
Display
0.0 % to 100.0 %

Sys. - Flow Damping

AUTO - OOS

Description
Use this function to enter a value for damping the measured flow and
temperature signals. The sensitivity of the flow measurement signal can be
reduced with respect to transient flows and interference peaks.
The damping acts prior to other damping functions (e. g. display, time
constant).
User input
0 to 100 s
Factory setting
1s

20

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Flow" Transducer Block / base index 1400

Parameter

Sys. - Positive Zero


Return

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
Use this function to interrupt evaluation of measured variables. For example,
the output signal should be set to zero flow during operations such as pipe
cleaning.
The setting acts on all functions and outputs of the measuring device.
If the positive zero return is active, the notice message #601 "POSITIVE
ZERO-RET" is displayed.
Options
OFF
ON (signal output is set to zero flow value, temperature is as normal)
Factory setting
OFF

Sensor Data - Pipe


Type

AUTO - OOS

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
Description
Use this function to select the type of pipe.
Options
CIRCULAR
RECTANGULAR
Factory setting
CIRCULAR

Sensor Data - Pipe


Standard

AUTO - OOS

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is not available if RECTANGULAR is selected in the Sensor
Data - Pipe Type ( 21) function.
Description
Use this function to select a pipe standard.
If the option OTHERS is selected here, then values need to be entered in the
functions Sensor Data - Outer Pipe Diameter and Sensor Data - Wall
Thickness.
Options
DIN:
PN6, PN10, PN25, PN40
ANSI:
B36.10 SCHEDULE 10, 20, 30, 40, 60, 80
B36.19 SCHEDULE 10, 40, 80
OTHERS
Factory setting
PN10 or B36.10 SCHEDULE 10 (country dependent 54)

Sensor Data - Nominal


Diameter

AUTO - OOS

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is not available if OTHER was selected in the Sensor Data Pipe Standard ( 21) OTHERS or RECTANGULAR in the Sensor Data Pipe Type ( 21).
Description
Use this function to select the nominal diameter of the pipe.
Options
80/3", 100/4", 150/6", 200/8", 250/10", 300/12", 350/14", 400/16",
450/18", 500/20", 600/24", 700/28", 800/32", 900/36", 1000/40"
Factory setting
150/6"

Endress+Hauser

21

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Flow" Transducer Block / base index 1400

Parameter

Sensor Data - Outer


Pipe Diameter

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if CIRCULAR is selected in the function
Sensor Data - Pipe Type ( 21) and OTHER was selected in the function
Sensor Data - Pipe Standard ( 21).
Description
Use this function to enter a value for the outer diameter.
The unit is taken from the function System Unit - Length ( 17).
User input
5-digit floating-point number
60 to 99999 (mm) or 2.362 to 3937 (inch) (country dependent 54)
Factory setting
168.3 (mm) or 6.0 (inch) (country dependent 54)

Sensor Data - Internal


Diameter

read only

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if OTHER is selected in the function Sensor
Data - Pipe Standard ( 21) and CIRCULAR was selected in the function
Sensor Data - Pipe Type ( 21) .
Description
Use this function to view the internal diameter of a circular pipe.
The unit is taken from the function System Unit - Length ( 17).
Display
5-digit floating-point number

Sensor Data - Internal


Height

AUTO - OOS

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if RETANGLUAR was selected in the function
Sensor Data - Pipe Type ( 21).
Description
Use this function to enter the internal height of a rectangular duct.
The unit is taken from the function System Unit - Length ( 17).
User input
5-digit floating-point number
45 to 99999 (mm) or 1.771 to 3937 (inch) (country dependent 54)
Factory setting
150.0 (mm) or 6.0 (inch) (country dependent 54)

Sensor Data - Internal


Width

AUTO - OOS

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if RETANGLUAR was selected in the function
Sensor Data - Pipe Type ( 21).
Description
Use this function to enter the internal width of a rectangular duct.
The unit is taken from the function System Unit - Length ( 17).
User input
5-digit floating-point number
45 to 99999 (mm) or 1.771 to 3937 (inch) (country dependent 54)
Factory setting
150.0 (mm) or 6.0 (inch) (country dependent 54)

22

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Flow" Transducer Block / base index 1400

Parameter

Sensor Data - Wall


Thickness

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Prerequisite
This function is only available for insertion sensors.
This function is not available if a standard pipe was selected in the function
Sensor Data - Pipe Standard ( 21) e.g. PN16.
Description
Use this function to enter a value for the outer diameter.
The unit is taken from the function System Unit - Length ( 17).
User input
2.0 to 40.0 (mm) or 0.08 to 1.57 (inch) (country dependent 54)
Factory setting
4.5 (mm) or 0.1771 (inch) (country dependent 54)

Sensor Data Mounting

AUTO - OOS

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
This function is only available if RECTANGULAR is selected in the function
Sensor Data - Pipe Type ( 21).
Description
Use this function to select the installation direction of the insertion sensor in
the rectangular duct.
If the VERTICAL option is selected, the value from the function Sensor
Data - Internal Height ( 22) is used to calculate the insertion depth.
If the HORIZONTAL option is selected, the value from the function
Sensor Data - Internal Width ( 22) is used to calculate the insertion
depth.
Options
HORIZONTAL
VERTICAL
Factory setting
VERTICAL

Sensor Data Mounting Set Length

AUTO - OOS

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
Description
Use this function to enter a value for the length of the mounting set
(including the sensor compression fitting).
The unit is taken from the function System Unit - Length ( 17) .
User input
5-digit floating-point number
75 to 900 (mm) or 2.953 to 35.433 (inch) (country dependent 54)
Factory setting
106.0 (mm) or 4.173 (inch) (country dependent 54)
The factory setting value is the length of the G1A compression fitting and
standard Endress+Hauser mounting boss.

Sensor Data - Insertion


Depth

read only

Prerequisite
This function is only available for insertion sensors (t-mass 65I).
Description
This function displays the calculated insertion depth for mounting the
sensor.
The unit is taken from the function System Unit - Length ( 17) .
For more information on insertion depth calculation, please refer to the
Operating Instructions BA00134D/06.
Display
5-digit floating-point number

Endress+Hauser

23

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Flow" Transducer Block / base index 1400

Parameter

Sensor Data Zeropoint

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
This function shows the current zero point correction value for the sensor.
The zero point is determined by the Adj. - Zeropoint Adjustment ( 18).
User input
5-digit floating-point number
20.000 to +20.000
Factory setting
Depends on calibration.

Sensor Data - Flow


Conditioner

read only

Description
Use this function to indicate if the t-mass 65F sensor has been calibrated
with or without a flow conditioner.
Display
WITH
WITHOUT
Factory setting
WITHOUT

Sensor Data Calibration Date

read only

Description
Use this function to display the date of the last factory calibration of the
measuring device.
This date is not updated by the In-Situ Calibration function.
Options
DD.MM.YYYY

Simulation Measurand

AUTO - OOS

Description
Use this function to set all the inputs, outputs and the totalizer to their flow
response modes, in order to check whether they respond correctly. During
this time, the message #692 "SIMULATION MEASURAND" appears on the
display.

Note!
The measuring device can only be used for measuring to a certain extent
while the simulation is in progress.
The setting is not saved if the power supply fails.
Options
OFF
MASS FLOW
CORRECTED VOLUME FLOW
TEMPERATURE
HEAT FLOW
Factory setting
OFF
Simulation Value
Measurand

AUTO - OOS

Prerequisite
Function is only available if the Simulation - Measurand ( 24) is active.
Description
Use this function to specify an arbitrary value (e.g. 12 kg/s) to check the
assigned functions in the device itself and downstream signal circuits.

Note!
The setting is not saved if the power supply fails.
User input
5-digit floating-point number
Factory setting
(country dependent 54)
0 kg/h; 0 lb/h (MASS FLOW)
0 Nm/h; 0 Sm/h (CORRECTED VOLUME FLOW)
0 MWh; 0 kBtu (HEAT FLOW)
0 C; +32 F (TEMPERATURE)

24

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Flow" Transducer Block / base index 1400

Parameter

Sensor Version Sensor Type

Write access
with operating
mode
(MODE_BLK)
read only

Description

Description
Use this function to view the sensor type.
Display
FLOWCELL (t-mass 65F flange sensor)
INSERTION (t-mass 65I insertion sensor)

Endress+Hauser

Sensor - Prod.Number

read only

Description
The serial number of the sensor appears on the display.

Sensor Version Tra.Ser.No

read only

Description
The serial number of the transducer appears on the display.

Sensor Version - SWRev.No.S-DAT

read only

Description
Use this function to view the software revision number of the S-DAT.

Sensor Version - SWRev.No.Pre-Amp.

read only

Description
Use this function to view the software revision number of the preamplifier.

Sensor Version - HWRev.No.Pre-Amp.

read only

Description
Use this function to view the hardware revision number of the preamplifier.

25

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

3.4

"Diagnosis" Transducer Block parameters

The following table shows the Endress+Hauser-specific parameters of the "Flow" Transducer Block.
These can only be changed after entering a release code in the "Access - Code" parameter.

Note!
FOUNDATION Fieldbus parameters are described in the Operating Instructions "FOUNDATION
Fieldbus Overview" (BA013S) (available at: www.endress.com download).
"Diagnosis" Transducer Block / base index 1600

Parameter

Write access
with operating
mode
(MODE_BLK)

Diag. Act. Sys. Condition

read only

Diag. Prev. Sys. Condition

read only

Access - Code

Description

Displays the current system status.

Note!
A precise error description as well as notes on remedying errors can be
found in the Operating Instructions BA00135D.

AUTO - OOS

Displays the last error message that occurred.


Description
All data of the measuring system are protected against inadvertent change.
Only when the code has been entered in this parameter can the
manufacturer-specific parameters be programmed and the device
configuration modified.
You can enable programming by entering:
Code 65(factory setting)
Personal code (Access Def.Private Code parameter 29)

Note!
If the hardware write protection is enabled then access to the
manufacturer-specific parameters is blocked even if the right code is
entered
You can disable programming again by entering any number (other than
the release code) in this parameter.
The Endress+Hauser service organization can be of assistance if you
mislay your personal code.
Certain parameters are not accessible unless a special service code is
entered. This service code is known only to the Endress+Hauser service
organization. Please contact your Endress+Hauser service center if you
require clarification.
User input
Max. 4-digit number: 0 to 9999
Access - Status

read only

Description
Use this parameter to check the access status for the parameter matrix.
Display
LOCKED (parameterization disabled)
ACCESS CUSTOMER (parameterization enabled)
ACCESS SERVICE (parameterization enabled)

26

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Diagnosis" Transducer Block / base index 1600

Parameter

Sys.- Alarm Delay

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
Use this function to define a time span for which the criteria for an error
have to be satisfied without interruption before a fault or notice message is
generated.
Depending on the setting and the type of error, this suppression acts on:
Display
Output Blocks (AI Blocks), FOUNDATION Fieldbus interface

Note!
If this parameter is used, fault and notice messages are delayed by the time
corresponding to the setting before being forwarded to the downstream
function blocks or the fieldbus host system.
Therefore, check in advance whether a delay of this nature could affect the
safety requirements of the process. If fault and notice messages are not be
suppressed, than a value of 0 seconds must be entered here.
User input
0 to 100 s (in steps of one second)
Factory setting
0s
Sys.- Sim. Failsafe
Mode

AUTO - OOS

Description
Use this parameter to set the Analog Input and Totalizer function blocks
to their defined failsafe modes, in order to check whether they respond
correctly. The failsafe mode of the totalizers is defined via the Tot. - Failsafe
All ( 35).

Note!
Active simulation mode is relayed to downstream function blocks or higher
level process control systems by means of the status "UNCERTAIN" of the
output value OUT (AI Block).
Options
OFF
ON
Factory setting
OFF
Sys.- Reset

AUTO - OOS

Description
Use this function to restart (reset) the measuring device.
Options
NO
The device is not restarted.
RESTART SYSTEM
Restart without disconnecting main power. In doing so, all the data
(functions) are accepted unchanged.
Factory setting
NO

Sys.- Operation Time

read only

Description
The hours of operation of the device appear on the display.
Display
Depends on the number of hours of operation elapsed:
Hours of operation < 10 hours display format = 0:00:00 (hr:min:sec)
Hours of operation 10 to 10 000 hours display format = 0000:00
(hr:min)
Hours of operation >10 000 hours display format = 000000 (hr)

Sys.- Time Since Reset

Endress+Hauser

read only

Description
This parameter is only used for service purposes

27

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Diagnosis" Transducer Block / base index 1600

Parameter

Sys.- T-DAT Save/


Load

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
Use this function to save the configuration/settings of the transmitter to a
transmitter-DAT (T-DAT), or to load a configuration from the T-DAT to the
EEPROM (manual backup function).
Application examples:
After commissioning, the current measuring point parameters can be
saved to the T-DAT as a backup.
If the transmitter is replaced for some reason, the data from the T-DAT
can be loaded into the new transmitter (EEPROM).
Options
CANCEL
SAVE (from the EEPROM to the T-DAT)
LOAD (from the T-DAT to the EEPROM)

Note!
If the target device has an older software version, the message "TRANSM.
SW-DAT" is displayed during startup. Then only the "SAVE" option is
available.
LOAD
This option is only possible:
if the target device has the same software version as, or a more recent
software
version than, the source device or
if the T-DAT contains valid data that can be called up
SAVE
This function is always available.
Factory setting
CANCEL
Sys.- Amp.Device Type

28

read only

Description
This parameter is only used for service purposes

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

3.5

Transducer Block

"Display" Transducer Block parameters

The following table shows the Endress+Hauser-specific parameters of the "Display" Transducer
Block. These can only be changed after entering a release code in the "Access - Code" parameter.

Note!
FOUNDATION Fieldbus parameters are described in the Operating Instructions "FOUNDATION
Fieldbus Overview" (BA013S) (available at: www.endress.com download).
"Display" Transducer Block / base index 1800

Parameter

Access - Code

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
All data of the measuring system are protected against inadvertent change.
Only when the code has been entered in this parameter can the
manufacturer-specific parameters be programmed and the device
configuration modified.
You can enable programming by entering:
Code 65(factory setting)
Personal code (Access Def.Private Code parameter 29)

Note!
If the hardware write protection is enabled then access to the
manufacturer-specific parameters is blocked even if the right code is
entered
You can disable programming again by entering any number (other than
the release code) in this parameter.
The Endress+Hauser service organization can be of assistance if you
mislay your personal code.
Certain parameters are not accessible unless a special service code is
entered. This service code is known only to the Endress+Hauser service
organization. Please contact your Endress+Hauser service center if you
require clarification.
User input
Max. 4-digit number: 0 to 9999
Access - Status

read only

Description
Use this parameter to check the access status for the parameter matrix.
Display
LOCKED (parameterization disabled)
ACCESS CUSTOMER (parameterization enabled)
ACCESS SERVICE (parameterization enabled)

Access Def.Private
Code

AUTO - OOS

Description
Use this function to enter a personal code to enable configuration.
This applies both to manufacturer-specific parameters in the Transducer
Blocks and to operating via the local display
If the code number is "0", programming is always enabled.
Parameter configuration has to be enabled before this code can be
changed.
User input
Max. 4-digit number: 0 to 9999
Factory setting
65

Endress+Hauser

29

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Display" Transducer Block / base index 1800

Parameter

Access Code Counter

Write access
with operating
mode
(MODE_BLK)
read only

Description

Description
The number of times the private and service code was entered to access the
device appears on the display.
Display
Integer
Factory setting
0

Display - Language

AUTO - OOS

Description
For selecting the language in which all messages are shown on the local
display.
Options
ENGLISH
DEUTSCH
FRANCAIS
ESPANOL
ITALIANO
NEDERLANDS
NORSK
SVENSKA
SUOMI
PORTUGUES
POLSKI
CESKI
Factory setting
country dependent 54

Display - Damping

AUTO - OOS

Description
For entering a time constant defining how the display reacts to severely
fluctuating flow variables, either very quickly (enter a low time constant) or
with damping (enter a high time constant).
The setting 0 seconds switches off damping.
User input
0 to 100 seconds
Factory setting
3 seconds

Display - Contrast LCD

AUTO - OOS

Description
For adjusting the display contrast to suit local operating conditions.
User input
10 to 100%
Factory setting
50%

Display - Backlight

AUTO - OOS

Description
For adjusting the background lighting to suit local operating conditions.
Entering the value "0" means that the backlight is "switched off". The display
then no longer emits any light, i.e. the display texts can no longer be read in
the dark.
User input
0 to 100%
Factory setting
50%

30

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Display" Transducer Block / base index 1800

Parameter

Display - Test

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
Use this function to test the operability of the local display and its pixels.
Test sequence:
1. Start the test by selecting ON.
2. All pixels of the main line and additional line are darkened for
minimum 0.75 seconds.
3. The main line and additional line show an "8" in each field for
minimum 0.75 seconds.
4. The main line and additional line show a "0" in each field for minimum
0.75 seconds.
5. The main line and additional line show nothing (blank display) for
minimum 0.75 seconds.
6. When the test is completed, the local display returns to its initial state
and displays the option OFF.
Options
OFF
ON
Factory setting
OFF

Display - Format

AUTO - OOS

Description
For selecting the number of decimal places for the display value in the main
line.
Note that this setting only affects the reading as it appears on the display,
it has no influence on the accuracy of the system's calculations.
The places after the decimal point as computed by the measuring device
cannot always be displayed, depending on this setting and the
engineering unit. In these instances an arrow appears on the display
between the measured value and the engineering unit (e.g. 1.2 kg/h),
indicating that the measuring system is computing with more decimal
places than can be shown on the display.
Options
XXXXX. - XXXX.X - XXX.XX - XX.XXX -X.XXXX
Factory setting
X.XXXX

Line 1 - Assign

AUTO - OOS

Description
For assigning a display value to the main line (top line of the local display).
This value is displayed during normal operation.
Options
OFF
MASS FLOW
MASS FLOW IN %
TEMPERATURE
TOTALIZER 1
TOTALIZER 2
AI(1 to 5) - OUT VALUE
CORRECTED VOLUME FLOW
CORRECTED VOLUME FLOW IN %
HEAT FLOW
HEAT FLOW IN %
AO - VALUE
Factory setting
MASS FLOW

Endress+Hauser

31

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Display" Transducer Block / base index 1800

Parameter

Line 2 - Assign

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
For assigning a display value to the additional line (bottom line of the local
display).
This value is displayed during normal operation.
Options
OFF
MASS FLOW
MASS FLOW IN %
MASS FLOW BARGRAPH IN %
TEMPERATURE
TOTALIZER 1
TOTALIZER 2
TAG NAME
OPERATING/SYSTEM CONDITIONS
CORRECTED VOLUME FLOW
CORRECTED VOLUME FLOW IN %
CORRECTED VOLUME FLOW BARGRAPH IN %
AI(1 to 5) - OUT VALUE
HEAT FLOW
HEAT FLOW IN %
HEAT FLOW BARGRAPH IN %
AO - VALUE
Factory setting
TOTALIZER 1

Line 1 - 100% Value

AUTO - OOS

Prerequisite
This function is only available if one of the following options was selected in
the Line 1 - Assign ( 31) function:
MASS FLOW IN %
CORRECTED VOLUME FLOW IN %
HEAT FLOW IN %
Description
Use this function to enter the flow value which should be shown on the
display as the 100% value.
User input
5-digit floating-point number
Factory setting
10 kg/h (with mass flow)
10 Nm/h (with corrected volume flow)
10 kW (with heat flow)

Line 2 - 100% Value

AUTO - OOS

Prerequisite
This function is only available if one of the following options was selected in
the Line 2 - Assign ( 32) function:
MASS FLOW IN %
CORRECTED VOLUME FLOW IN %
HEAT FLOW IN %
MASS FLOW BARGRAPH IN %
CORRECTED VOLUME FLOW BARGRAPH IN %
HEAT FLOW BARGRAPH IN %
Description
Use this function to enter the flow value which should be shown on the
display as the 100% value.
User input
5-digit floating-point number
Factory setting
10 kg/h (with mass flow)
10 Nm/h (with corrected volume flow)
10 kW (with heat flow)

32

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

3.6

Transducer Block

"Totalizer"Transducer Block parameters

The following table shows the Endress+Hauser-specific parameters of the "Totalizer" Transducer
Block. These can only be changed after entering a release code in the "Access - Code" parameter.

Note!
FOUNDATION Fieldbus parameters are described in the Operating Instructions "FOUNDATION
Fieldbus Overview" (BA013S) (available at: www.endress.com download).
"Totalizer" Transducer Block / base index 1800

Parameter

Access - Code

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
All data of the measuring system are protected against inadvertent change.
Only when the code has been entered in this parameter can the
manufacturer-specific parameters be programmed and the device
configuration modified.
You can enable programming by entering:
Code 65(factory setting)
Personal code (Access Def.Private Code parameter 29)

Note!
If the hardware write protection is enabled then access to the
manufacturer-specific parameters is blocked even if the right code is
entered
You can disable programming again by entering any number (other than
the release code) in this parameter.
The Endress+Hauser service organization can be of assistance if you
mislay your personal code.
Certain parameters are not accessible unless a special service code is
entered. This service code is known only to the Endress+Hauser service
organization. Please contact your Endress+Hauser service center if you
require clarification.
User input
Max. 4-digit number: 0 to 9999
Access - Status

read only

Description
Use this parameter to check the access status for the parameter matrix.
Display
LOCKED (parameterization disabled)
ACCESS CUSTOMER (parameterization enabled)
ACCESS SERVICE (parameterization enabled)

Tot. 1 to 2 - Sum

AUTO - OOS

Description
Use this parameter to view the total for the totalizers measured variable
aggregated since measuring commenced. The value can be positive or
negative, depending on the setting selected in the parameter Tot. 1 to 2 Mode ( 35) and the direction of flow.

Note!
The effect of the setting in the parameter Tot. 1 to 2 - Mode is as follows:
If the setting is BALANCE, the totalizer balances flow in the positive
and negative directions.
If the setting is FORWARD, the totalizer registers only flow in the
positive direction.
If the setting is REVERSE, the totalizer registers only flow in the
negative direction.
The totalizers' response to faults is defined in the parameter "Tot. Failsafe All".
Display
Max. 7-digit floating-point number, including unit and
sign (e.g. 15467,04 kg)

Endress+Hauser

33

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Totalizer" Transducer Block / base index 1800

Parameter

Tot. 1 to 2 - Unit

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
For selecting the unit for the measured variable assigned to the totalizer.
The unit selected here does not have any effect on the desired volume unit
which should be transmitted by means of the FOUNDATION Fieldbus
interface. This setting is made separately by means of the corresponding AI
Block in the XD_SCALE parameter group.
Options (Tot. 1 to 2 - Assign = MASS FLOW):
SI g , kg, t
US oz, lb, ton
Factory setting
kg or lb (country dependent 54)
Options (Tot. 1 to 2 - Assign = CORRECTED VOLUME FLOW)):
SI Nl, Nm
US Sm, Scf
Factory setting
Nm or Sm (country dependent 54)
Options (Tot. 1 to 2 - Assign = HEAT FLOW):
SI kWh, MWh, kJ, MJ, GJ, kcal, Mcal, Gcal
US kBtu, MBtu, GBtu, tonh
Factory setting
MWh or MBtu (country dependent 54)

Tot. 1 to 2 - Assign

AUTO - OOS

Description
For assigning the measured variable to the totalizer.
The totalizer is reset to 0 as soon as the selection is changed.
If you select OFF, only the Tot. 1 to 2 - Assign function is displayed in the
Totalizer 1 or 2 group..
Options
OFF
MASS FLOW
CORRECTED VOLUME FLOW
HEAT FLOW
Factory setting
MASS FLOW

Tot. 1 to 2 - Assign Gas


Group

AUTO - OOS

Description
Use this function to assign a gas group to a totalizer.
If GAS GROUP 1&2 is selected, the individual values of each gas group are
totaled on one totalizer.
Options
GAS GROUP 1
GAS GROUP 2
GAS GROUP 1&2
Factory setting
GAS GROUP 1

34

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Totalizer" Transducer Block / base index 1800

Parameter

Tot. 1 to 2 - Mode

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
Use this parameter to define how the flow components are to be totaled by
the totalizer.
Options
BALANCE
Positive and negative flow components. The positive and negative flow
components are balanced. In other words, net flow in the flow direction is
registered.
FORWARD
Positive flow components only.
REVERSE
Negative flow components only.
Factory setting
Totalizer 1 = BALANCE
Totalizer 2 = FORWARD

Tot. 1 to 2 - Reset

AUTO - OOS

Description
Resets the sum and overflow in the totalizer selected.
Options
NO
YES
Factory setting
NO

Tot. - Reset All

AUTO - OOS

Description
Reset all totalizers simultaneously to zero (Tot. 1 to 2 - Sum parameter).
Options
NO
YES
Factory setting
NO

Tot. - Failsafe All

AUTO - OOS

Description
For selecting the behavior of the totalizer in an alarm condition.
Options
STOP
The totalizer does not continue to count the flow if a fault is present. The
totalizer stops at the last value before the alarm condition occurred.
HOLD VALUE
The totalizer continues to count the flow on the basis of the last valid flow
data (before the fault occurred).
ACTUAL VALUE
The totalizers continue to count on the basis of the current flow data. The
fault is ignored.
Factory setting
STOP

Amp.Device Type

Endress+Hauser

read only

Description
This parameter is only used for service purposes

35

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

3.7

"Heat Flow"Transducer Block parameters

The following table shows the Endress+Hauser-specific parameters of the "Totalizer" Transducer
Block. These can only be changed after entering a release code in the "Access - Code" parameter.

Note!
FOUNDATION Fieldbus parameters are described in the Operating Instructions "FOUNDATION
Fieldbus Overview" (BA013S) (available at: www.endress.com download).
"Heat Flow" Transducer Block / base index 2700

Parameter

Access - Code

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
All data of the measuring system are protected against inadvertent change.
Only when the code has been entered in this parameter can the
manufacturer-specific parameters be programmed and the device
configuration modified.
You can enable programming by entering:
Code 65(factory setting)
Personal code (Access Def.Private Code parameter 29)

Note!
If the hardware write protection is enabled then access to the
manufacturer-specific parameters is blocked even if the right code is
entered
You can disable programming again by entering any number (other than
the release code) in this parameter.
The Endress+Hauser service organization can be of assistance if you
mislay your personal code.
Certain parameters are not accessible unless a special service code is
entered. This service code is known only to the Endress+Hauser service
organization. Please contact your Endress+Hauser service center if you
require clarification.
User input
Max. 4-digit number: 0 to 9999
Access - Status

read only

Description
Use this parameter to check the access status for the parameter matrix.
Display
LOCKED (parameterization disabled)
ACCESS CUSTOMER (parameterization enabled)
ACCESS SERVICE (parameterization enabled)

Gas - Select Group

AUTO - OOS

Description
Use this function to:
select a gas group for editing
set the active gas group manually
Setting the active gas group:
On completion of programming all the necessary functions in the gas
group, select YES in the Group 1 to 2 - Save Changes ( 40) function,
or
If the gas group is already programmed as required, simply select the
required gas group and then exit using the ESC keys (X).
Options
GAS GROUP 1
GAS GROUP 2
Factory setting
GAS GROUP 1

36

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Heat Flow" Transducer Block / base index 2700

Parameter

Group 1 to 2 Analyzer Input

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
Use this function to assign automatic updating of a gas group (via a gas
analyzer signal and the current input function). A gas group must contain at
least 2 gas types (e.g. Methane 60%, Carbon Dioxide 40%).
Options
OFF
ON
Factory setting
OFF

Group 1 to 2 - Number
Of Gases

AUTO - OOS

Description
Use this function to enter the number of gases that are used in the gas
group.
User input
1 to 8
Factory setting
1

Group 1 to 2 - Gas
Type 1

AUTO - OOS

Description
Use this function to select gas type 1.
Options
AIR
AMMONIA
ARGON
BUTANE
CARBON DIOXIDE
CARBON MONOXIDE
CHLORINE
ETHANE
ETHYLENE
HELIUM 4
HYDROGEN NORMAL
HYDROGEN CHLORIDE
HYDROGEN SULFIDE
KRYPTON
METHANE
NEON
NITROGEN
OXYGEN
PROPANE
XENON
NOT USED
SPECIAL GAS
Factory setting
AIR

Endress+Hauser

37

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Heat Flow" Transducer Block / base index 2700

Parameter

Group 1 to 2 - Gas
Type 2 To 8

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Prerequisite
The number of functions available here is dependent upon the setting in the
function Group 1 to 2 - Number Of Gases ( 37).
Description
Use this function to select the gas type.
Options
AIR
AMMONIA
ARGON
BUTANE
CARBON DIOXIDE
CARBON MONOXIDE
CHLORINE
ETHANE
ETHYLENE
HELIUM 4
HYDROGEN NORMAL
HYDROGEN CHLORIDE
HYDROGEN SULFIDE
KRYPTON
METHANE
NEON
NITROGEN
OXYGEN
PROPANE
XENON
NOT USED
Factory setting
NOT USED

Group 1 to 2 Correction Factor

AUTO - OOS

Prerequisite
This function is only available if the option SPECIAL GAS is selected in the
function Group 1 to 2 - Gas Type 1 ( 37).
Description
Use this function to enter a manual correction factor for a special gas
configuration.
The correction factor is normally based on air and at the specified process
conditions.
The correction factor is determined by the factory. If the gas or process
conditions change from the initial setting, then the correction factor value
will also need updating.
User input
5-digit floating-point number
Factory setting
1.0

Group 1 to 2 Reference Density

AUTO - OOS

Prerequisite
This function is only available if the option SPECIAL GAS is selected in the
function Group 1 to 2 - Gas Type 1 ( 37).
Description
Use this function to enter a reference density for a special gas configuration
when corrected volume flow is required, e.g. Nm (Scf).
The unit is taken from the function System Unit - Density ( 17).
The reference density is determined by the factory. If the gas or reference
conditions change from the initial setting, then the reference density value
will also need updating.
User input
5-digit floating-point number, with unit
Factory setting
1.2930 [kg/m] or 0.0807 [lb/ft] (country dependent 54)

38

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Heat Flow" Transducer Block / base index 2700

Parameter

Group 1 to 2 - Mole %
Gas 1

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Prerequisite
This function is not available if the setting in Group 1 to 2 - Number Of
Gases ( 37) is 1. (The factory setting 100% is automatically used)
Description
Use this function to enter the Mole % of the gas selected in Group 1 to 2 Gas Type 1.
User input
000.00 % to 100.00 %
Factory setting
100.00 %

Group 1 to 2 - Mole %
Gas 2 To 8

AUTO - OOS

Prerequisite
The number of functions available here is dependent upon the setting in the
Group 1 to 2 - Number Of Gases ( 37).
Description
Use this function to enter the Mole % of the gas selected in Group 1 to 2 Gas Type 2 To 8.
User input
000.00 % to 100.00 %
Factory setting
000.00 %

Group 1 to 2 Description

AUTO - OOS

Prerequisite
This function is only available if the option SPECIAL GAS is selected in the
function Group 1 to 2 - Gas Type 1 ( 37) .
Description
Use this function to enter a description for a special gas configuration.
Example
A special composition consisting of 93% oxygen and 7% ozone.
User input: O2 93% OZONE 7%
User input
xxxx (max. 16 characters)
Valid characters are A-Z, 0-9, +, -, decimal point, blank space or underscore
Factory setting
" " (no text)

Group 1 to 2 - Check
Values

AUTO - OOS

Prerequisite
This function is only available if there is an error in the Mole % values.
Description
The error message MIXTURE NOT 100% appears if the entered values do
not add up to 100%. The entries have to be checked and corrected before
the gas group can be saved and used for flow measurement (see option YES
function Group 1 to 2 - Save Changes ( 40).
Display
MIXTURE NOT 100%

Endress+Hauser

39

Transducer Block

Proline t-mass 65 FOUNDATION Fieldbus

"Heat Flow" Transducer Block / base index 2700

Parameter

Group 1 to 2 - Save
Changes

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Description
Use this function to control the way entries are saved in the gas group and
utilized for flow measurement.
Options
CANCEL
The entered parameters are saved in the gas group but they are not used for
flow measurement. The gas group can be activated, at a later time, by
returning to the group, checking the parameters and then selecting the
option YES in this function.
YES
The entered parameters are saved in the gas group and are used for flow
measurement.
DISCARD
The entered parameters are not saved. The previous parameters remain
valid and are used for flow measurement.

Gas - Calorific Value


Type

AUTO - OOS

Description
Use this function to select the measured variable on which the combustion
value is based.
Options
MASS
CORRECTED VOLUME
Factory setting
MASS

Group 1 to 2 - Mode 1
to 2

AUTO - OOS

Description
Use this function to select a mode for calculating the heat flow (GAS
GROUP 1).
Options
AUTO NET
AUTO GROSS
MANUAL
Factory setting
AUTO NET

Group 1 to 2 - Heating
Value 2

AUTO - OOS

Prerequisite
This function is only available if MANUAL was selected in the Group 1 to 2
- Mode 1 to 2 ( 40) function.
Description
Use this function to enter a user-specific calorific value.
Input/display
5-digit floating-point number
Factory setting
0,0
The corresponding unit is taken from the System Unit - Calorific Value Mass
( 14) or System Unit- Calorific Value Corrected Volume ( 15)
function.

40

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Transducer Block

"Heat Flow" Transducer Block / base index 2700

Parameter

Gas - Reference
Combustion
Temperature

Write access
with operating
mode
(MODE_BLK)
AUTO - OOS

Description

Prerequisite
This function is not available if the option MANUAL is selected in Group 1
to 2 - Mode 1 to 2 ( 40).
Description
Use this function to enter the reference combustion temperature of the gas.
This function is used to calculate the calorific value of the gas.
The unit is taken from the function System Unit - Temperature ( 16).
User input
5-digit floating-point number
Factory setting
25.0 C or 60.0 F (country dependent 54)

Endress+Hauser

41

Function blocks

Proline t-mass 65 FOUNDATION Fieldbus

Function blocks

The function blocks contain the basic automation functions of the field device. We distinguish
between different function blocks, e.g. Analog Input function block, PID function block
(PID controller), etc.
Each of these function blocks is used to execute different application functions. This means that
local control functions, for example, can be carried out directly in the field, and device errors such
as amplifier errors are reported to the automation system automatically.
The function blocks process the input values in accordance with their specific algorithm and their
internally available parameters. They generate output values that are made available to other
function blocks for further processing by linking the individual function blocks with each other.

42

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Analog Input function block

Analog Input function block

In the Analog Input function block (AI) the process variables from the Transducer Block are
prepared for the subsequent automation functions (e.g. scaling, limit value processing). The
automation function is defined by the connections of the outputs.

AI
OUT

A0003800

OUT = output value and output status of the Analog Input function block

5.1

Signal processing

The figure shows the internal structure of the Analog Input function blocks available:
TB Flow
TB Totalizer
TB Heat Flow

Analog Input 5
Analog Input 4
Analog Input 3
Analog Input 2
Analog Input 1
CHANNEL
SIMULATE
Value, Status

CH 1
CH 2
CH 6
CH 7
CH 8
CH 53

Mass Flow
Volume Flow
Temperature
Totalizer 1
Totalizer 2
Heat Flow

XD_SCALE

OUT_SCALE

L_TYPE

XD_SCALE = OUT_SCALE

Cutoff

LOW_CUT

Filter

PV_FTIME

Direct
XD_SCALE

OUT_SCALE

XD_SCALE

OUT_SCALE

Indirect
PV

Indirect
square root

AUTO

O/S
MAN

MODE

ALARM_HYS
HI_HI_ALM
HI_ALM
LO_LO_ALM
LO_ALM

Alarm detection
HI_HI
HI
LO
LO_LO

FIELD_VAL
OUT
A0014995

Fig. 4:

Internal structure of the individual Analog Input function blocks

The Analog Input function blocks receive their input values from the Transducer Blocks.
The parameter CHANNEL is used to select which input value is to be processed in an Analog Input
function block.
Factory-based configuration of the Transducer Blocks 11
The parameter group SIMULATE allows you to replace the input value with a simulation value and
to activate simulation. By specifying the status and the simulation value the reaction of the complete
Analog Input function block can be tested.

Endress+Hauser

43

Analog Input function block

Proline t-mass 65 FOUNDATION Fieldbus

Note!
The simulation mode is activated by means of jumpers on the I/O board (See Operating
Instructions BA00134D)
The parameter L_TYPE is used to select the linearization type of the input or simulation value:
Direct signal conversion
The value is forwarded without conversion (XD_SCALE = OUT_SCALE). Select this option if the
input value is already in the physical unit you want
Indirect signal conversion
With this setting the measured value from the Transducer Block (input value) is re-scaled linearly
via the input scaling XD_SCALE to the desired output range OUT_SCALE (further information
on rescaling of the input value can be found on 47).
Indirect signal conversion with square root
With this setting the measured value from the Transducer Block (input value) is re-scaled via the
parameter group XD_SCALE and recalculated using a square root function. It is then rescaled
again to the desired output range via the parameter group OUT_SCALE
The parameter LOW_CUT allows a limit value to be specified for the low flow cut off. The low flow
cut off is activated via the parameter IO_OPTS. If the converted primary value (PV) is below the
limit value then it is set to a value of "Zero".
In the parameter PV_FTIME a filter time can be specified for filtering the converted primary value
(PV). If a time of 0 seconds is specified then no filtration takes place.
The parameter group MODE_BLK is used to select the operating mode of the Analog Input function
block. If the operating mode MAN (manual) is selected then the output value OUT can be specified
directly.
The output value OUT is compared with warning and alarm limits (e.g. HI_LIM, LO_LO_LIM, etc.)
that can be entered via various parameters. If one of these limit values is violated then a limit value
process alarm (e.g. HI_ALM, LO_LO_ALM, etc.) is triggered.

44

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

5.2

Analog Input function block

Important functions and parameters of the


Analog Input function blocks

The most important functions and parameters of the Analog Input function blocks are listed below.

Note!
All the FOUNDATION Fieldbus parameters available are described in the Operating Instructions
"FOUNDATION Fieldbus Overview" (BA013S) (available at: www.endress.com download).

5.2.1

Selecting the operating mode

The operating mode is configured via the MODE_BLK parameter group. The Analog Input function
block supports the following operating modes:
AUTO (automatic mode)
MAN (manual mode)
OOS (out of service)

Note!
The block status OOS is also shown via the parameter BLOCK_ERR. In operating mode OOS, if
write protection is not enabled, you can access all the write parameters without restriction.

5.2.2

Assignment of the process variable

The t-mass 65 FOUNDATION Fieldbus has five Analog Input function blocks. The process variables
of the Transducer Block that are to be processed are assigned via the parameter CHANNEL.
Factory-based configuration of the Transducer Blocks 11

5.2.3

Linearization types

In an Analog Input function block, the input value of a Transducer Block can be linearized using the
parameter L_TYPE. The following types of linearization are available:
Direct
With this setting the measured value from the Transducer Block (input value) bypasses the
linearization function and is looped unchanged with the same unit through the Analog Input
function block.
Indirect
With this setting the measured value from the Transducer Block (input value) is re-scaled linearly
via the input scaling XD_SCALE to the desired output range OUT_SCALE.
Indirect Square Root
With this setting the measured value from the Transducer Block (input value) is re-scaled via the
parameter group XD_SCALE and recalculated using an evolution function. It is then rescaled
again to the desired output range via the parameter group OUT_SCALE.

Endress+Hauser

45

Analog Input function block

Proline t-mass 65 FOUNDATION Fieldbus

5.2.4

Selection of units

A change in the unit for a process variable is defined in the relevant Analog Input function block, in
the parameter group XD_SCALE via the element UNIT.
If an unsuitable unit is selected, the function block changes to the OOS mode (out of service).

Note!
If the "Direct" type of linearization was selected via the L_TYPE parameter, the setting of the
XD_SCALE and OUT_SCALE parameter groups must be identical; otherwise, the function block
remains in the OOS operating mode and the "BLOCK CONFIG ERROR" block error is displayed
in the BLOCK_ERROR parameter.
The system units selected in the Transducer Blocks in question do not have any effect on the
setting of the system units in the Analog Input function block. The units are specified
independently of one another and must be configured separately. The unit selected in the
Transducer Blocks is only used for the local display, EPD adjustment, low flow cut off and for
simulation.

5.2.5

Status of the output value OUT

The status of the parameter group OUT communicates to the subsequent function blocks the status
of the Analog Input function block and the validity of the output value OUT. The following status
values can be displayed:
GOOD_NON_CASCADE
The output value OUT is valid and can be used for further processing.
UNCERTAIN
The output value OUT can only be used for further processing to a limited extent. The status tells
the downstream function blocks that a "notice message" is present in the device, e.g. arising from
active positive zero return or simulation.
BAD
The output value OUT is invalid. The following causes are possible:
The Analog Input function block is in the OOS operating mode.
The Resource Block is in operating mode OOS.
The "Flow" or "Totalizer" Transducer Block is in the OOS operating mode. The Analog Input
function block can only process the input value of the Transducer Block in question if the
operating mode is set to AUTO.
A "fault message" is present in the device arising from a critical device error, e.g. an electronics
module defect.

46

Note!
The status of the device (block error) is displayed by means of the BLOCK_ERR parameter.
Detailed information on the current device status is displayed via the "Diagnosis" Transducer
Block in the parameter "Diag. - Act.Sys.Condition". A list of all the error messages, including
remedial measures, can be found in the Operating Instructions BA00135D.

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

5.2.6

Analog Input function block

Simulation of input/output

Parameters of the Analog Input function block allow simulation of the input and output of the
function block:
1.

Simulation of the input of the Analog Input function block:


The parameter group SIMULATE can be used to specify the input value (measured value and
status). Since the simulation value runs through the entire function block, all the parameter
settings of the block can be checked.

Note!
If simulation is blocked by the jumper on the I/O board then simulation mode cannot be
activated in the parameter SIMULATE. In the Resource Block, the parameter BLOCK_ERROR
shows whether simulation of the Analog Input function block is possible.

2.

Simulation of the output of the Analog Input function block:


Set the operating mode in the parameter group MODE_BLK to MAN and specify the desired
output value directly in the parameter OUT.

5.2.7

Diagnosis

The status of the device is displayed via the BLOCK_ERR parameter specified in the FOUNDATION
Fieldbus specification.
Detailed information on the current device status is displayed via the "Diagnosis" Transducer Block
in the manufacturer-specific parameter "Diag. - Act.Sys.Condition" ( 26).
For more information on rectifying errors See Operating Instructions BA00135D,
"Troubleshooting" section.

5.2.8

Rescaling the input value

In the Analog Input function block the input value or input range can be scaled in accordance with
the automation requirements.
Example:
The system unit in the Transducer Block is kg/h.
The measurement range of the sensor is 0 to 30 kg/h.
The output range to the process control system should be 0 to 100%.
The Analog Input function block must be configured as follows:
Parameter CHANNEL
Select: CHANNEL 1 = Mass Flow
Parameter L_TYPE
Select: L_TYPE = Indirect
The process variable "Volume flow" from the "Flow" Transducer Block is rescaled linearly in the
AI Parameter group via input scaling XD_SCALE to the desired output range OUT_SCALE.
Parameter group XD_SCALE
XD_SCALE 0 % = 0
XD_SCALE 100 % = 30
XD_SCALE UNIT = kg/h

Endress+Hauser

47

Analog Input function block

Proline t-mass 65 FOUNDATION Fieldbus

Parameter group OUT_SCALE


OUT_SCALE 0 % = 0
OUT_SCALE 100 % = 100
OUT_SCALE UNIT = %
The result is that with an input value of, for example, 15 kg/h a value of 50% is output via the
parameter OUT.

Analog Input Function Block

Transducer
Block

kg/h
Mass
Flow

XD_SCALE

30

100

OUT_SCALE
OUT
50%

15 kg/h
0

0
0

100%

%
100

0 to 30 kg/h
A0004766-EN

Fig. 5:

5.2.9

Rescaling the input value (example)

Limit values

The limit values are based on the output value OUT. If the output value OUT exceeds or does not
reach the defined limit values then an alarm is sent to the fieldbus host system via the limit value
process alarms. The following limit values can be defined:
HI_HI_LIM (upper alarm limit)
HI_LIM (upper pre-warning limit)
LO_LO_LIM (lower alarm limit)
LO_LIM (lower pre-warning limit)

5.2.10

Alarm detection and processing

Process alarms provide information on particular block statuses and block events. The status of the
process alarms is communicated to the fieldbus host system via the parameter BLOCK_ALM.
The parameter ACK_OPTION specifies whether an alarm must be acknowledged via the fieldbus
host system.
The following process alarms are generated by the Analog Input function block:
Block process alarms
A block process alarm is triggered via the BLOCK_ERR parameter. The parameter BLOCK_ALM is
used to show the block process alarms and communicate them to the fieldbus host system. The
following process alarms can be generated by the Analog Input function block:
SIMULATE ACTIVE
INPUT FAILURE
OUT OF SERVICE
BLOCK CONFIG ERROR
If the option of the process alarm (BLOCK ALM) has not been enabled in the parameter
ACK_OPTION, the process alarms must be acknowledged in the parameter BLOCK_ALM.

48

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Analog Input function block

Limit value process alarms


If a limit value is infringed then the priority specified for the limit value alarm will be checked before
the limit value violation is communicated to the fieldbus host system. The priority that specifies the
action in the event of an active limit value violation is determined by the following parameters:
HI_HI_PRI (upper alarm limit)
HI_PRI (upper pre-warning limit)
LO_LO_PRI (lower alarm limit)
LO_PRI (lower pre-warning limit)
The status of the limit value process alarms is communicated to the fieldbus host system via the
following parameters:
HI_HI_ALM (upper alarm limit)
HI_ALM (upper pre-warning limit)
LO_LO_ALMI (lower alarm limit)
LO_ALM (lower pre-warning limit)
If the option of a limit value process alarm has not been enabled in the parameter ACK_OPTION
then this must be acknowledged directly in its parameter (see list.

Endress+Hauser

Note!
The parameter ALARM_SUM shows the current status of all the process alarms.

49

Discrete Output function block

Proline t-mass 65 FOUNDATION Fieldbus

Discrete Output function block

The Discrete Output function block (DO, Discrete Output) processes a discrete setpoint value
received from an upstream function block or higher level process control system, with which
various instrument functions (e.g. zero point adjustment or totalizer reset) can be initiated in the
subsequent Transducer Block.

DO
CAS_IN_D

OUT_D
BKCAL_OUT_D

A0003816-EN

CAS_IN _D = Remote setpoint value from another function block


OUT_D = Discrete output value and status
BKCAL_OUT_D = Discrete output value and status required by BKCAL_IN_D input of another block for

6.1

Signal processing

The figure shows the internal structure of the Discrete Output function blocks t-mass 65
FOUNDATION Fieldbus:

Discrete Output Function Block


RCAS_IN_D

RCAS_OUT_D
BKCAL_OUT_D
PV_D

(Mode RCAS)

SP_D

Invert.
OUT_D

(Mode CAS)

CAS_IN_D
(Mode Auto)

(Mode Man)
MODE_BLK

IO_OPTS

SIMULATE_D

SIMULATE_D

Discrete
Input

Discrete
Output

Transducer Blocks
A0004771-en

Fig. 6:

Signal processing in the Discrete Output function block

In the CAS operating mode (cascade operation), the Discrete Output function block receives, via
the function block input CAS_IN_D, a discrete signal from an upstream function block. This signal
controls the setpoint value (parameter SP_D) of the function block, and after internal calculation is
sent as an output signal (parameter OUT_D) to the Transducer Block for control of instrument
functions (e.g. zero point adjustment). The output value and status of the Discrete Output
function block is communicated to the upstream block via the output BKCAL_OUT_D.
Signal processing in the RCAS operating mode (remote cascade operation) is largely identical to the
CAS operating mode. However, in this operating mode, control of the parameter SP_D does not take
place via an upstream function block but through a fieldbus host system.

50

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Discrete Output function block

The output value and status of the Discrete Output function block is communicated to the process
control system as an answer message via parameter RCAS_OUT_D.
In the AUTO operating mode (automatic operation), the set point value (parameter SP_D) is
prescribed directly in the Discrete Output function block. In this case, the parameter CAS_IN_D is
not taken into consideration in the internal calculation.
In the MAN operating mode (HAND), the output value (parameter OUT_D) can be prescribed
directly in the Discrete Output function block. No internal calculation takes place.

6.2

Important functions and parameters of the Discrete


Output function block

The most important functions and parameters of the Discrete Output function block are listed below.

Note!
All the FOUNDATION Fieldbus parameters available are described in the Operating Instructions
"FOUNDATION Fieldbus Overview" (BA013S) (available at: www.endress.com download).

6.2.1

Selecting the operating mode

The operating mode is configured via the MODE_BLK parameter group. The Discrete Output
function block supports the following operating modes:
AUTO
MAN
CAS
RCAS
OOS

6.2.2

Safety behavior

There is a safety default available (fault state) for the Discrete Output function block. This is
activated when a fault condition (of the corresponding valid set point value) exists longer than
defined in the parameter FSTATE_TIME, or when the parameter SET_FSTATE in the Resource
Block is activated. The safety operation is determined via the parameters FSTATE_TIME,
FSTATE_VAL_D, and IO_OPTS.

6.2.3

Assignment between the Discrete Output function block and the


Transducer Block

The assignment or connection between the Discrete Output function block and the Transducer
Block takes place in the Discrete Output function block via the parameter CHANNEL.
Parameter CHANNEL 16 (= Discrete Output function block)

Endress+Hauser

51

Discrete Output function block

Proline t-mass 65 FOUNDATION Fieldbus

6.2.4

Values for the parameters CAS_IN_D, RCAS_IN_D, OUT_D,


and SP_D

Via the Discrete Output function block, different instrument functions in the Transducer Block can
be initiated via manufacturer-specific, fixed set point values from an upstream function block.
Here it must be observed that the desired function is only then executed when a status change from
the value 0 (Discrete state 0) to the corresponding function value (following table) takes place. The
value 0 always serves as the starting point for the corresponding control of instrument functions. A
status change from a value not equal to zero to another value has no effect.
Input assignment of the CAS_IN_D, RCAS_IN_D, OUT_D, SP_D parameters
Status changes

Action

Discrete state 0

Discrete state 1

Reserved

Discrete state 0

Discrete state 2

Positive zero return: ON

Discrete state 0

Discrete state 3

Positive zero return: OFF

Discrete state 0

Discrete state 4

Zero adjustements

Discrete state 0

Discrete state 5

Reserved

Discrete state 0

Discrete state 6

Reserved

Discrete state 0

Discrete state 7

Reset totalizers 1, 2

Discrete state 0

Discrete state 8

Reset totalizers 1

Discrete state 0

Discrete state 9

Reset totalizers 2

Example for controlling positive zero return via the Discrete Output function block.
The following example shows how positive zero return can be activated or deactivated via the
Discrete Output function block during a cleaning procedure.
1.

2.

In the first step, the connection between the Discrete Output function block and the
Transducer Block must be established. Here, the value 16 must be assigned to the parameter
CHANNEL in the Discrete Output function block
Parameter CHANNEL 16 (= Discrete Output function block)
In the CAS operating mode, the Discrete Output function block processes the set point value
specified at the input CAS_IN_D by the upstream function block and transfers it to the
Transducer Block
Activating positive zero return
With a starting value of 0 (Discrete state 0), positive zero return is activated by a status change
from 0 to 2 at input CAS_IN_D.
Deactivating the positive zero return
Positive zero return can only then be deactivated when the input value at CAS_IN_D has first
been set to output value 0 (Discrete state 0). Only then can positive zero return be deactivated
through a status change from 0 to 2 at input CAS_IN_D.

52

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Endress+Hauser

Additional function blocks

Additional function blocks

Note!
Additional function blocks such as the PID, Arithmetic, Input Selector, Signal Characterizer and
Integrator function block are described in the "FOUNDATION Fieldbus Overview" (BA013S)
Operating Instructions (available at: www.endress.com download).

53

Factory settings

Proline t-mass 65 FOUNDATION Fieldbus

Factory settings

8.1

Language

Country

Language

Country

Language

Australia

English

Luxembourg

French

Austria

German

Malaysia

English

Belgium

English

The Netherlands

Dutch

Czechia

Czech

Norway

Norwegian

Denmark

English

Poland

Polish

England

English

Portugal

Portuguese

Finland

Finnish

Sweden

Swedish

France

French

Switzerland

German

Germany

German

Singapore

English

Hungary

English

Spain

Spanish

Hong Kong

English

South Africa

English

India

English

Thailand

English

Italy

Italian

Other countries

English

8.2

SI units (not for USA and Canada)

8.2.1

Low flow cut off, full scale value, pulse value

t-mass F sensor
With air at ambient conditions (without a flow conditioner)
Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[kg/h]

[kg/h]

[kg/p]

15

0.53

53

0.10

25

2.00

200

1.00

40

5.55

555

1.00

50

9.10

910

10.00

80

20.30

2030

10.00

100

37.50

3750

10.00

t-mass I sensor
With air at ambient conditions (without a flow conditioner)

54

Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[kg/h]

[kg/h]

[kg/p]

80

20.30

2030

10.0

100

37.50

3750

10.0

150

75.00

7500

100.0

200

125.00

12500

100.0

250

200.00

20000

100.0

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Factory settings

Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[kg/h]

[kg/h]

[kg/p]

300

280.00

28000

100.0

400

500.00

50000

100.0

500

800.00

80000

100.0

600

1150.00

115000

100.0

700

1590.00

159000

100.0

1000

3200.00

320000

100.0

1500

7200.00

720000

100.0

8.2.2

System units
Unit

Unit

Temperature

Length

mm

Density

kg/m

Pressure

bar a

Reference density

kg/m

Reference Pressure

bar a

Calorific Value Mass

MJ/kg

Calorific Value Corr. Vol.

MJ/m

Heat

kWh

Reference temperature

8.2.3

Unit totalizer 1 and 2


Unit

Mass flow

kg

Heat flow

MWh

8.2.4

Unit
Corrected volume flow

Nm

Other Units
Unit

Endress+Hauser

Ref. combustion temp.

41

Pipe standard

according to DIN

21

55

Factory settings

Proline t-mass 65 FOUNDATION Fieldbus

8.3

US units (only for USA and Canada)

8.3.1

Low flow cut off, full scale value, pulse value

t-mass F sensor
With air at ambient conditions; (without a flow conditioner)
Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[lb/hr]

[lb/hr]

[lb/p]

"

1.16

116

0.20

1"

4.40

440

2.00

1"

12.20

1220

2.00

2"

20.02

2002

20.00

3"

44.66

4466

20.00

4"

82.50

8250

20.00

t-mass I sensor
With air at ambient conditions; (without a flow conditioner)
Nominal diameter

Low flow cut off

Full scale value

Pulse value

[mm]

[lb/hr]

[lb/hr]

[lb/p]

3"

44.66

4466

20.00

4"

82.50

8250

20.00

6"

165.00

16500

200.00

8"

275.00

27500

200.00

10"

440.00

44000

200.00

12"

610.00

61000

200.00

16"

1100.00

110000

200.00

20"

1760.00

176000

200.00

24"

2530.00

253000

200.00

28"

3498.00

349800

200.00

40"

7040.00

704000

200.00

60"

15840.00

1584000

200.00

8.3.2

System units
Unit

56

Unit

Temperature

Length

inch

Density

lb/ft

Pressure

psi a

Reference density

lb/ft

Reference Pressure

psi a

Calorific Value Mass

kBtu/lb

Calorific Value Corr. Vol.

kBtu/Scf

Heat

kBtu

Reference temperature

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

8.3.3

Factory settings

Unit totalizer 1 and 2


Unit

Mass flow

lb

Heat flow

kBtu

8.3.4

Unit
Corrected volume flow

Sm

Other Units
Unit

Endress+Hauser

Ref. combustion temp.

41

Pipe standard

according to ANSI

21

57

Proline t-mass 65 FOUNDATION Fieldbus

Index FOUNDATION Fieldbus

Index FOUNDATION Fieldbus


A
Access
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Access - Code
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 26
"Display" Transducer Block . . . . . . . . . . . . . . . . . . . . . 29
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 13
"Heat Flow" Transducer Block. . . . . . . . . . . . . . . . . . . 36
"Totalizer" Transducer Block . . . . . . . . . . . . . . . . . . . . 33
Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 33
Access Code Counter
"Display" Transducer Block . . . . . . . . . . . . . . . . . . . . . 30
Access Def.Private Code
"Display" Transducer Block . . . . . . . . . . . . . . . . . . . . . 29
Adj. - Zeropoint Adjustment
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 18
Alarm detection
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Alarm processing
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Amp. - HW Identification
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Amp. - HW Rev.Number
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Amp. - Prod.Number
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Amp. - SW Identification
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Amp. - SW Rev.No. T-DAT
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Amp. - SW Rev.Number
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Amp.Device Type
Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 35
Amplifier
Hardware identification number . . . . . . . . . . . . . . . . . . 8
Hardware revision number . . . . . . . . . . . . . . . . . . . . . . 8
Production number . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Software identification number . . . . . . . . . . . . . . . . . . . 8
Software revision number . . . . . . . . . . . . . . . . . . . . . . . 8
Assign
DO function block . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

B
Block model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Block status
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

C
Code entry
See Access - Code

D
Device-Software
58

Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Diag. - Act. Sys. Condition
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 26
Diag. - Prev. Sys. Condition
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 26
Diagnosis
AI function block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Discrete Output function block . . . . . . . . . . . . . . . . . . . . . 50
Display
100% value line 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
100% value line 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Access Code Counter . . . . . . . . . . . . . . . . . . . . . . . . . 30
Access status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Assign line 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Assign line 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Backlight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Code entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Contrast LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Mass flow, calculated . . . . . . . . . . . . . . . . . . . . . . . . . 13
Personal code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Display - Damping
"Display" Transducer Block . . . . . . . . . . . . . . . . . . . . . 30
Display - Language
"Display" Transducer Block . . . . . . . . . . . . . . . . . . . . . 30

E
Error messages
See System condition

G
Gas
Access status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calorific Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Code entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ref. Combustion Temperature . . . . . . . . . . . . . . . . . . .
Gas - Calorific Value Type
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Gas - Reference Combustion Temperature
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Gas - Select Group
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Gas group
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas group 1 to 2
Analyzer input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calculation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Check values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas type 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas type 2 to 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mole-% Gas 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

36
40
36
41
40
41
36
36
37
40
39
39
37
38
40
39

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Mole-% Gas 2 to 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Number of gases . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference density. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Save changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gross Calorific Value
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . .
Group 1 to 2
Correction Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Analyzer Input
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Check Values
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Correction Factor
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Description
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Gas Type 1
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Gas Type 2 To 8
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Heating Value 2
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Mode 1 to 2
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Mole % Gas 1
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Mole % Gas 2 to 8
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Number Of Gases
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Reference Density
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .
Group 1 to 2 - Save Changes
"Heat Flow" Transducer Block . . . . . . . . . . . . . . . . . . .

Index FOUNDATION Fieldbus

39
37
38
40

I/O module software . . . . . . . . . . . . . . . . . . . . . . . . . . . 8


Installation Factor
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 18

20

Limit values
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line 1 - 100% Value
"Display" Transducer Block. . . . . . . . . . . . . . . . . . . . . .
Line 1 - Assign
"Display" Transducer Block. . . . . . . . . . . . . . . . . . . . . .
Line 2 - 100% Value
"Display" Transducer Block. . . . . . . . . . . . . . . . . . . . . .
Line 2 - Assign
"Display" Transducer Block. . . . . . . . . . . . . . . . . . . . . .
Low Flow Cut Off - Assign
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . .
Low Flow Cut Off - Off Value
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . .
Low Flow Cut Off - On Value
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . .
Low Flow Cut Off - Unit
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . .

38
37
39
38
39
37
38
40
40
39
39

48
32
31
32
32
17
18
17
17

M
Mole % Gas 1
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 20

37

Net Calorific Value


"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 20

38

40

I
I/O - HW Identification
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O - HW Rev. Number
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O - Prod.Number
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O - SW Identification
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O - SW Rev. Number
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O - Type
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Module
Device software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hardware identification number. . . . . . . . . . . . . . . . . . .
Hardware revision number. . . . . . . . . . . . . . . . . . . . . . .
Production number . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software identification number . . . . . . . . . . . . . . . . . . .
Software revision number . . . . . . . . . . . . . . . . . . . . . . .
Identification number
Amplifier hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Amplifier software . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O module hardware . . . . . . . . . . . . . . . . . . . . . . . . . .

Endress+Hauser

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Operating mode
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
DO function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Resource Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Output values
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

P
Parameters
Resource Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Press.Corr. - Pressure
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 19
Process Pressure 1
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 19
Process Pressure 2
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 19
Process variable assignment
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

R
Reference Density
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 20
Reference Parameter - Ref. Temperature
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 19
Reference Pressure
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 19
59

Proline t-mass 65 FOUNDATION Fieldbus

Rescaling
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Revision number
Amplifier hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Amplifier software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

S
Safety behavior
DO function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Select units ("Flow" Transducer Block)
Density value, fixed . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Sensor - Prod.Number
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 25
Sensor Data - Calibration Date
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 24
Sensor Data - Flow Conditioner
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 24
Sensor Data - Insertion Depth
T"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . 23
Sensor Data - Internal Diameter
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 22
Sensor Data - Internal Height
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 22
Sensor Data - Internal Width
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 22
Sensor Data - Mounting
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 23
Sensor Data - Mounting Set Length
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 23
Sensor Data - Nominal Diameter
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 21
Sensor Data - Outer Diameter
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 22
Sensor Data - Pipe Standard
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 21
Sensor Data - Pipe Type
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 21
Sensor Data - Wall Thickness
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 23
Sensor Data - Zeropoint
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 24
Sensor Version - HW-Rev.No.Pre-Amp.
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 25
Sensor Version - Sensor Type
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 25
Sensor Version - SW-Rev.No.Pre-Amp.
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 25
Sensor Version - SW-Rev.No.S-DAT
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 25
Sensor Version - Tra.Ser.No
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 25
Serial number sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Set points
DO function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Signal processing
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
DO function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

60

Index FOUNDATION Fieldbus

Simulation
AI function block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Simulation - Measurand
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 24
Status OUT
AI function block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Sys. - Flow Damping
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 20
Sys. - Positive Zero Return
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 21
Sys.- Alarm Delay
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 27
Sys.- Amp.Device Type
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 28
Sys.- Operation Time
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 27
Sys.- Reset
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 27
Sys.- Sim. Failsafe Mode
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 27
Sys.- T-DAT Save/Load
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 28
Sys.- Time Since Reset
"Diagnosis" Transducer Block . . . . . . . . . . . . . . . . . . . 27
System condition
Actual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Previous (error history) . . . . . . . . . . . . . . . . . . . . . . . . 26
System Unit - Calorific Value Corrected Volume
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 15
System Unit - Calorific Value Mass
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 14
System Unit - Density
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 17
System Unit - Heat Flow
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . 1516
System Unit - Length
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 17
System Unit - Mass Flow
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 14
System Unit - Pressure
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 16
System Unit - Temperature
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 16
System Unite - Corr.Volume Flow
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 14
System Value - Corr.Volume Flow
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 14
System Value - Heat Flow
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 15
System Value - Mass Flow
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 13
System Value - Temperature
"Flow" Transducer Block . . . . . . . . . . . . . . . . . . . . . . . 16

T
T-DAT
Amplifier software revision number . . . . . . . . . . . . . . . . 8
Tot. - Failsafe All
Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 35

Endress+Hauser

Proline t-mass 65 FOUNDATION Fieldbus

Index FOUNDATION Fieldbus

Tot. - Reset All


Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 35
Tot. 1 to 2 - Assign
Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 34
Tot. 1 to 2 - Assign Gas Group
Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 34
Tot. 1 to 2 - Mode
Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 35
Tot. 1 to 2 - Reset
Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 35
Tot. 1 to 2 - Sum
"Totalizer" Transducer Block . . . . . . . . . . . . . . . . . . . . 33
Tot. 1 to 2 - Unit
Transducer Block "Totalizer" . . . . . . . . . . . . . . . . . . . . 34
Totalizer
Access status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Amp.Device Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Assign gas group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Code entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Failsafe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Reset all totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Sum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Totalizer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Type of linearization
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

U
Unit select
("Flow" Transducer Block)
Mass flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Units
AI function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

W
Write protection
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Endress+Hauser

61

Proline t-mass 65 FOUNDATION Fieldbus

62

Index FOUNDATION Fieldbus

Endress+Hauser

www.endress.com/worldwide

BA00135D/06/EN/13.10
71128091
FM+SGML6.0 ProMoDo

Brief Operating Instructions

Proline t-mass 65
Thermal Mass Flow Measuring System

6
8
9
MODBUS

These Brief Operating Instructions are not intended to replace the


Operating Instructions provided in the scope of supply.
Detailed information is provided in the Operating Instructions and
the additional documentation on the CD-ROM supplied.
The complete device documentation consists of:
These Brief Operating Instructions
Depending on the device version:
Operating Instructions and the Description of Device Functions
Approvals and safety certificates
Special safety instructions in accordance with the approvals for
the device (e.g. explosion protection, pressure equipment
directive etc.)
Additional device-specific information
KA021D/06/en/06.10
71115118

Table of contents

Proline t-mass 65

Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Installation, commissioning and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Safety conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Transporting to the measuring point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

3 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1 Connecting the various housing types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

4 Hardware settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.1 Device address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.2 Terminating resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.1 Switching on the measuring device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.3 Navigating within the function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4 Calling the Commission Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.5 Software settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Endress+Hauser

Proline t-mass 65

Safety instructions

1.1

Designated use

Safety instructions

The measuring device works based on the thermal measuring principle and is to be used
exclusively for measuring the mass flow of gases (e.g. kg, Nm3, Scf).
The measuring device can be configured to measure pure gases (e.g. oxygen, nitrogen, carbon
dioxide, argon etc.) or gas mixtures (e.g. natural gas).
Any use other than that described here compromises the safety of persons and the entire
measuring system and is, therefore, not permitted.
The manufacturer is not liable for damage caused by improper or non-designated use.

1.2

Installation, commissioning and operation

The measuring device must only be installed, connected, commissioned and maintained by
qualified and authorized specialists (e.g. electrical technicians) in full compliance with the
instructions in these Brief Operating Instructions, the applicable norms, legal regulations and
certificates (depending on the application).
The specialists must have read and understood these Brief Operating Instructions and must
follow the instructions they contain. If you are unclear on anything in these Brief Operating
Instructions, you must read the Operating Instructions (on the CD-ROM). The Operating
Instructions provide detailed information on the measuring device.
The measuring device should only installed in a de-energized state free from outside loads or
strain.
The measuring device may only be modified if such work is expressly permitted in the
Operating Instructions (on the CD-ROM).
Repairs may only be performed if a genuine spare parts kit is available and this repair work is
expressly permitted.
If performing welding work on the piping, the welding unit may not be grounded by means
of the measuring device.

1.3

Operational safety

The measuring device is designed to meet state-of-the-art safety requirements, has been
tested, and left the factory in a condition in which it is safe to operate. Relevant regulations
and European standards have been observed.
The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser distributor will supply you with current information and updates to these
Operating Instructions.
The information on the warning notices, nameplates and connection diagrams affixed to the
device must be observed. These contain important data on the permitted operating conditions,
the range of application of the device and information on the materials used.
If the device is not used at atmospheric temperatures, compliance with the relevant marginal
conditions as specified in the device documentation supplied (on CD-ROM) is mandatory.

Endress+Hauser

Safety instructions

Proline t-mass 65

The device must be wired as specified in the wiring and connection diagrams. Interconnection
must be permitted.
All parts of the device must be included in the potential equalization of the system.
Cables, certified cable glands and certified dummy plugs must be suitable to withstand the
prevailing operating conditions, such as the temperature range of the process. Housing
apertures that are not used must be sealed with dummy plugs.
The device should only be used for fluids to which all the wetted parts of the device are
sufficiently resistant. With regard to special fluids, including fluids used for cleaning,
Endress+Hauser will be happy to assist in clarifying the corrosion-resistant properties of
wetted materials. However, minor changes in temperature, concentration or in the degree of
contamination in the process may result in variations in corrosion resistance. For this reason,
Endress+Hauser does not accept any responsibility with regard to the corrosion resistance of
wetted materials in a specific application. The user is responsible for the choice of suitable
wetted materials in the process.
Hazardous areas
Measuring devices for use in hazardous areas are labeled accordingly on the nameplate.
Relevant national regulations must be observed when operating the device in hazardous areas.
The Ex documentation on the CD-ROM is an integral part of the entire device documentation.
The installation regulations, connection data and safety instructions provided in the Ex
documentation must be observed. The symbol on the front page indicates the approval and
certification body (0 Europe, 2 USA, 1 Canada).
The nameplate also bears the documentation number of this Ex documentation
(XA***D/../..).

1.4

#
"
!

Safety conventions

Warning!
"Warning" indicates an action or procedure which, if not performed correctly, can result in injury
or a safety hazard. Comply strictly with the instructions and proceed with care.
Caution!
Caution indicates an action or procedure which, if not performed correctly, can result in
incorrect operation or destruction of the device. Comply strictly with the instructions.
Note!
"Note" indicates an action or procedure which, if not performed correctly, can have an indirect
effect on operation or trigger an unexpected response on the part of the device.

Endress+Hauser

Proline t-mass 65

Installation

Installation

2.1

Transporting to the measuring point

Transport the measuring device to the measuring point in the original packaging.
The covers or caps fitted on the process connections prevent mechanical damage to the
sensors during transport and storage. For this reason, do not remove the covers or caps until
immediately before installation.
Use slings around the process connections.
Warning!
#
Risk of injury! The device can slip.
The center of gravity of the measuring device may be
higher than the holding points of the slings.
Always ensure that the device cannot slip or turn around
its axis.

A0007408

Do not lift measuring devices by the transmitter housing


or the connection housing in the case of the remote
version. Do not use chains as they could damage the
housing.

A0007409

2.2

Installation conditions

The thermal dispersion principle is sensitive to disturbed flow conditions. Therefore, the
requirements and conditions for installation in this section are especially important
Take measures to reduce or avoid condensation (e.g. install a condensation trap, thermal
insulation, etc.).
2.2.1 Dimensions
For the dimensions of the measuring device see associated Technical Information on the
CD-ROM.

Endress+Hauser

Installation

Proline t-mass 65

2.2.2 Pipework requirements


Good engineering practice should be followed at all times.
Further information is provided in ISO Standard 14511.

Note!
Measuring errors will result due to a mismatch of the pipes or gaskets.
Avoid

A0007520

Pipe diameter one is not equal to pipe


diameter two

A0007521

Incorrectly sized gaskets

A0007522

Incorrectly aligned Flanges and


gaskets

2.2.3 Orientation
Make sure that the direction arrow on the sensor matches the direction of gas flow through the
pipe.
Flanged version

A0007514

A0007512

A0007515

compact

remote

compact

remote

compact

remote

Insertion version

A0007516

A0007517

A0007518

compact

remote

compact

remote

compact

remote

mn

= Recommended orientation
= Orientation recommended in certain situations
mo = See following description

Endress+Hauser

Proline t-mass 65

Installation

m In the case of saturated or unclean gases, upward flow in a vertical pipe section is preferred to minimize
condensation/contamination.
n Not recommended if the vibrations are too high or if the installation is unstable.
o Only suitable for clean/dry gases. On horizontal pipes do not mount the sensor from the bottom, if the gas is very damp
or saturated with water (e. g. Bio Gas). Mount the sensor in a position as indicated below ( =135).

A0009897

2.2.4 Inlet/outlet runs


The thermal dispersion principle is sensitive to disturbed flow conditions.
As a general rule, the installed thermal flow sensor should always be installed as far away as
possible from any flow disturbances. Further information is provided in ISO Standard 14511.

Flanged version

15 x DN

2 x DN

15 x DN

A0007523

20 x DN

2 x DN

A0007526

Endress+Hauser

2 x DN

15 x DN

A0007524

35 x DN

2 x DN

A0007527

2 x DN

A0007525

50 x DN

2 x DN

A0007528

Installation

Proline t-mass 65

Insertion version

20 x DN

5 x DN

20 x DN

A0007529

25 x DN

5 x DN

5 x DN

20 x DN

5 x DN

A0007530

40 x DN

A0007532

5 x DN

A0007531

50 x DN

5 x DN

A0007564

A0007534

Inlet run
15 x DN for the flanged version and 20 x DN for the insertion version
Outlet run
2 x DN for the flanged version and 5 x DN for the insertion version

Note!
Where two or more flow disturbances are located upstream of the meter, the longest indicated
inlet length should prevail.
For example if a control valve and a bend are mounted upstream of the flowmeter, the
recommended inlet length should be according to the control valve (50 DN).
For very light gases such as Helium and Hydrogen all upstream distances should be doubled.
A specially designed perforated plate flow conditioner can be installed if it is not possible to
observe the inlet runs required.
Please refer to the Operating Instructions on the CD-ROM for special details on the perforated
plate flow conditioner
2.2.5 Mounting conditions for the insertion version
Mounting conditions for welding sockets

"

Caution!
When mounting the fitting to a thin wall duct, use a
suitable support bracket for the sensor.

D
90

90

D = 31.0 mm 0.5 mm ( 1.22" 0.019")

A0011843

Endress+Hauser

Proline t-mass 65

Installation

Adjustment of the insertion version

Insert the sensor into the socket and tighten the lower nut of
compression fitting first by hand and then tighten it 1 revolutions
using a wrench (42 mm).
Caution!
"
NPT thread: use a thread sealing tape or paste
G1A thread: the sealing ring supplied must be installed

A0011888

Insertion depth calculation

Note!
All the guidelines and information on the insertion depth refer to a standard welding nozzle
provided by Endress+Hauser.
For detailed remarks on calculation refer to Technical Information on the CD-ROM.
a.
9

230
220
210

200
190

b.

Thickness of the pipe wall or duct wall

c.

Depth of the welding nozzle at the pipe or duct including the


sensor pipe union and Hot tap mounting set (if used).

a.

Calculated insertion depth:


(0.3 a) + b + c + 2 mm or
(0.3 a) + b + c + 0,079 inch

180

Internal diameter for round pipes.


Duct height for a duct if the sensor is to be installed vertically
or the duct width if it is to be installed horizontally.
(a = min. 80 mm or 3 inch)

A0011844

Insertion depth calculation with Quick Setup "Sensor"


The following data are needed for insertion depth calculation:
Round pipes

Duct

Pipe standard (DIN, ANSI or others)


Nominal diameter
Outer diameter
Thickness
Internal diameter (min. 80 mm or 3")

Endress+Hauser

Duct height
Duct width
Thickness
Mounting orientation (installed vertically or
horizontally)

Installation

Proline t-mass 65

Aligning the calculated insertion depth

a.

Tighten the upper nut of compression fitting such that


the sensor can still be adjusted.

b.

Align the scale to the calculated insertion depth.

230
220
210

200

190

180

A0011848

Aligning the insertion version to flow direction

90 (3)

90(7)
A0007536

A0007537

Check and ensure that the sensor is aligned vertically at a 90 angle on the pipe/duct.
Turn the sensor so that the arrow marking matches the direction of flow.

10

Endress+Hauser

Proline t-mass 65

Installation

To fix the insertion version


1.

Tighten the compression fitting (1) by


hand to secure the position of the sensor.
Then, using an open-ended wrench
(36 mm), tighten another 1 revolutions
in a clockwise direction.

2.

Fix the two securing screws (4)


(Allen key 3 mm; 1/8").
Warning!
#
Observe torque:
4 Nm (2.95 lbf ft)

2
3.

Check that the sensor and transmitter do


not turn.

4.

Check the measuring point for leaks at


the maximum operating pressure.

a0010114

2.2.6 Heating
For information on the heating, please see the Operating Instructions on the CD-ROM.
2.2.7 Thermal insulation
For information on the thermal insulation, please see the Operating Instructions on the
CD-ROM.
2.2.8 Vibrations

"

Caution!
Excessive vibration can result in mechanical damage to the measuring device and its mounting.
For information on vibrations, please see the Operating Instructions on the CD-ROM.

Endress+Hauser

11

Installation

Proline t-mass 65

2.3

Installation instructions

2.3.1 Turning the aluminum field housing


Aluminum field housing for non-Ex area
b

180

180

f
A0007540

Aluminum field housing for Zone 1 or Class I Div. 1


max. 360
b

Turn the transmitter housing


gently clockwise until the stop
(end of the thread).

c.

Turn the transmitter


counterclockwise (max. 360)
to the desired position.

d.

Retighten the setscrew.

Nicht-eigensichere
Stromkreise durch
IP40-Abdeckung geschtzt

p cover tight w
Kee ircuits are ali hile
ve
c

p cover tight wh
Kee ircuits are alive ile
c

Release the setscrew.

b.

er Spannu
ht unt
ng
Nic
ffnen

Non-intrinsically safe
circuits Ip40 protected
Boucles de courant
sans scurit intrinsque
protges par Ip40

Ne

a.

uvrir l
pas o te apparei
l
sous nsion

A0008036

2.3.2 Turning the local display

4 x 45

a.

Press in the side latches on the display module and


remove the module from the cover plate of the
electronics compartment.

b.

Turn the display to the desired position (max. 4 x


45 in both directions) and reset it onto the cover
plate of the electronics compartment.

a
A0007541

12

Endress+Hauser

Proline t-mass 65

Installation

2.3.3 Installing the wall-mount housing

"

Caution!
Make sure that the ambient temperature does not exceed the permitted range.
Always install the wall-mount housing in such a way that the cable entries point downwards.

Mounted directly on the wall


35 (1.38)

Connection compartment

2.

Securing screws M6 (max. 6.5 mm (0.25 inch);


screw head max. 10.5 mm (0.4 inch)

3.

Housing bores for securing screws

1
90 (3.54)

1.

81.5 (3.2)

mm (inch)

192 (7.56)
A0007542

Pipe mounting

"

2070
( 0.792.75)

Caution!

mm (inch) Danger of overheating! If the device is mounted on a


warm pipe, make sure that the housing temperature does
not exceed +60 C (+140 F) which is the maximum
temperature permitted.

~155 (~ 6.1)

A0007543

Endress+Hauser

13

Installation

Proline t-mass 65

Panel mounting
+0.5 (+0.019)
0.5 (0.019)

210 (8.27)

+0.5 (+0.019)
0.5 (0.019)

245 (9.65)
mm (inch)

~110 (~4.33)
A0007544

2.4

14

Post-installation check

Is the measuring device damaged (visual inspection)?


Does the device correspond to specifications at the measuring point?
Is the serial number of sensor and the connected transmitter the same?
Are the measuring point number and labeling correct (visual inspection)?
Professional installation (correct pipe internal diameter, correctly sized gaskets)?
Is the alignment of pipe/gasket/flowmeter body correct?
Has the correct sensor orientation been selected in terms of type, fluid properties, fluid
temperature?
Does the arrow on the sensor point in the direction of the flow in the pipe?
Are sufficient inlet and outlet runs available before and after the measuring point?
Is flow conditioner correctly installed (if available)?
Is the sensor immersion depth (only insertion version) correct?
Is the measuring device protected against moisture and sunlight?
Is the measuring device protected against overheating?
Is the measuring device protected against excessive vibrations?
Have the gas conditions been checked for purity, cleanliness and dryness?

Endress+Hauser

Proline t-mass 65

"

Wiring

Wiring

Warning!
Risk of electric shock!
Never mount or wire the measuring device while it is connected to the power supply.
Prior to connecting the power supply, connect the protective earth to the ground terminal on
the housing.
Caution!
Risk of damaging the electronic components!
Connect the power supply in accordance with the specifications on the diagram inside the
connection compartments cover.
Additionally for the remote version:

"

Caution!
Risk of damaging the electronic components!
Maximum cable length: 100 m (328 ft)
Observe the cable specifications of the connecting cable Operating Instructions on the
CD-ROM.
Note!
Install the connecting cable securely to prevent movement.
Additionally for measuring devices with fieldbus communication:

"

Caution!
Risk of damaging the electronic components!
Observe the cable specification of the fieldbus cable Operating Instructions on the
CD-ROM.
Keep the stripped and twisted lengths of cable shield as short as possible.
Screen and ground the signal lines Operating Instructions on the CD-ROM.
When using in systems without potential matching Operating Instructions on the
CD-ROM.
Additionally for Ex-certified measuring devices:

Warning!
When wiring Ex-certified measuring devices, all the safety instructions, wiring diagrams,
technical information etc. of the related Ex documentation must be observed
Ex documentation on the CD-ROM.

Endress+Hauser

15

Wiring

Proline t-mass 65

3.1

Connecting the various housing types

Wire the unit using the terminal assignment diagram inside the cover.
3.1.1 Compact version (transmitter)
Transmitter connection:
1
2
3
4

3
4
2

Connection diagram inside the connection compartment cover


Power supply cable
Signal cable or fieldbus cable
Optional

1
A0007545

3.1.2 Remote version (transmitter)


Transmitter connection:
1
2
3
4

Connection diagram inside the connection compartment cover


Power supply cable
Signal cable
Fieldbus cable

Connecting cable connection:

2 3 4 5

Sensor/transmitter connecting cable

A0007546

3.1.3 Remote version (transmitter)


Transmitter connection:

3
4
2

1
2
3/4

p cover tight w
Kee ircuits are ali hile
ve
c

over tight whi


ep c
Ke ircuits are alive le
c

ht unter Spannun
Nic
g
ffnen

Connection diagram inside the connection compartment cover


Power supply cable
Signal cable or fieldbus cable

vri
pas ou r lappa
Ne sous tension reil

1
Connecting cable connection:

Sensor/transmitter connecting cable

A0007547

3.1.4 Remote version (sensor)


Transmitter connection:
1

Connection diagram inside the connection compartment cover

1
Connecting cable connection:
5

Sensor/transmitter connecting cable

A0007548

16

Endress+Hauser

Proline t-mass 65

3.2

Wiring

Degree of protection

The devices fulfill all the requirements for IP 67 (NEMA 4X).


After mounting in the field or service work, the following points have to be observed to ensure
that IP 67 (NEMA 4X) protection is retained:
Install the measuring device in such a way that the cable entries do not point upwards.
Do not remove the grommet from the cable entry.
Remove all unused cable entries and insert blanking or certified plugs instead.
Use cable entries and drain plugs with a long-term operating temperature range in accordance
with the temperature specified on the nameplate.

A0007549

Tighten the cable entries correctly.

3.3

A0007550

The cables must loop down before they enter the cable
entries ("water trap").

Post-connection check

Are cables or is the device damaged (visual inspection)?


Does the supply voltage match the specifications on the nameplate?
Are the power supply and signal cables correctly connected?
Do the cables used comply with the necessary specifications?
Do the mounted cables have adequate strain relief?
Cables correctly segregated by type? Without loops and crossovers?
Are all screw terminals firmly tightened?
Are all the cable entries installed, correctly tightened and firmly sealed?
Cables looped as "water traps"?
Are all housing covers installed and correctly tightened?

In addition, for measuring devices with fieldbus communication:


Are all the connecting components (T-boxes, junction boxes, connectors, etc.) connected
with each other correctly?
Has each fieldbus segment been terminated at both ends with a bus terminator?
Has the max. length of the fieldbus cable and the spurs been observed in accordance with the
specifications?
Is the fieldbus cable fully shielded and correctly grounded?

Endress+Hauser

17

Hardware settings

Proline t-mass 65

Hardware settings

This section only deals with the hardware settings needed for commissioning. All other settings
(e.g. output configuration, write protection, etc.) are described in the associated Operating
Instructions on the CD-ROM.

Note!
No hardware settings are needed for measuring devices with HART or FOUNDATION Fieldbus
type communication.

4.1

Device address

Has to be set for measuring devices with the following communication methods:
PROFIBUS DP/PA
MODBUS RS485
The device address can be configured via:
Miniature switches see description below
Local operation see software settings section
Addressing via miniature switches

Warning!
Risk of electric shock! Risk of damaging the electronic components!
All the safety instructions for the measuring device must be observed and all the warnings
heeded 3.
ESD (Electrostatic Discharge): Use a workspace, working environment and tools purposely
designed for electrostatic sensitive devices.

Warning!
Switch off the power supply before opening the device.

W
E
N
O

1
2
3
4

Loosen the cheese head screw of the securing clamp


with an Allen key (3 mm)

b.

Unscrew cover of the electronics compartment from


the transmitter housing.

c.

Loosen the securing screws of the display module


and remove the onsite display (if present).

d.

Set the position of the miniature switches on the


I/O board using a sharp pointed object.

Installation is the reverse of the removal procedure.

W
E
N
O

1
2
3
4

W
E
N
O

1
2
3
4

W
E
N
O

1
2
3
4

a.
W
E
N
O

1
2
3
4

W
E
N
O

1
2
3
4

A0007551

18

Endress+Hauser

Proline t-mass 65

Hardware settings

PROFIBUS
Device address range: 0 to 126
Factory setting: 126

OFF ON
1

16

32

64

a.

Miniature switches for the device address


(example shown: 1+16+32 = device address 49)

b.

Miniature switches for the addressing mode:


OFF = software addressing via local
operation/operating program (factory setting)
ON = hardware addressing via miniature switches

c.

Miniature switch not assigned.

1
2

3
4
OFF ON

A0007552

MODBUS RS485
Device address range: 1 to 247
Factory setting: 247

OFF ON
1

a.

Miniature switches for the device address


(example shown: 1+16+32 = device address 49)

b.

Miniature switches for the addressing mode:


OFF = software addressing via local
operation/operating program (factory setting)
ON = hardware addressing via miniature switches

c.

Miniature switch not assigned.

a
1

16

32

64

128

2
c

3
4
OFF ON

A0007554

Endress+Hauser

19

Hardware settings

4.2

Proline t-mass 65

Terminating resistors

Note!
If the measuring device is used at the end of a bus segment, termination is required.
This can be performed in the measuring device by setting the terminating resistors on the I/O
board. Generally, however, it is recommended to use an external bus terminator and not
perform termination at the measuring device itself.
Has to be set for measuring devices with the following communication methods:
PROFIBUS DP
Baudrate 1.5 MBaud Termination can be performed at the measuring device, see
graphic
Baudrate > 1.5 MBaud An external bus terminator must be used
MODBUS RS485 Termination can be performed at the measuring device, see graphic

Warning!
Risk of electric shock! Risk of damaging the electronic components!
All the safety instructions for the measuring device must be observed and all the warnings
heeded 3.
Use a workspace, working environment and tools purposely designed for electrostatically
sensitive devices.
Setting the terminating switch SW1
on the I/O board:
ON - ON - ON - ON

W
E
N
O

1
2
3
4

W
E
N
O

1
2
3
4

W
E
N
O

1
2
3
4

+5V
SW 1
W
E
N
O

1
2
3
4

2
W
E
N
O

1
2
3
4

220 W

W
E
N
O

1
2
3
4

W
E
N
O

1
2
3
4

390 W

3
4
OFF ON

390 W
A0007556

20

Endress+Hauser

Proline t-mass 65

Commissioning

Commissioning

5.1

Switching on the measuring device

On completion of the installation (successful post-installation check), wiring (successful


post-connection check) and after making the necessary hardware settings, where applicable, the
permitted power supply (see nameplate) can be switched on for the measuring device.
When the power supply is switched on, the measuring device performs a number of power-up
checks and device self-checks. As this procedure progresses the following messages can appear
on the local display:
Display examples:
Name of the measuring device

Start-up message

START-UP
RUNNING

Name of the measuring device

Displays the current software

DEVICE SOFTWARE
V XX.XX.XX

SYSTEM OK

Beginning of operation

OPERATION

The measuring device starts operating as soon as the startup procedure is complete.
Various measured values and/or status variables appear on the display.

Note!
If an error occurs during startup, this is displayed by an error message. The error messages that
occur most frequently when a measuring device is commissioned are described in the
Troubleshooting section 26.

Endress+Hauser

21

Commissioning

5.2

Proline t-mass 65

Operation

5.2.1 Display elements

Display lines/fields

48.25 xx/yy
3702.6 x

1
2

1.

Main line for primary measured values

2.

Additional line for additional measured


variables/status variables

3.

Current measured values

4.

Engineering units/time units

A0011838

5.2.2 Operating elements

Operating keys

Esc

E
2

3
A0007559

1.

() Minus key for entering, selecting

2.

(+) Plus key for entering, selecting

3.

Enter key for calling the function matrix, saving

When the +/ keys are pressed simultaneously (Esc):


Exit the function matrix step-by-step:
> 3 sec. = cancel data input and
return to the measured value display

5.2.3 Displaying error messages

1
2

XXXXXXXXXX
#000 00:00:05
3

1.

Type of error:
P = Process error, S = System error

2.

Error message type:


$ = Fault message, ! = Notice message

3.

Error number

4.

Duration of the last error that occurred:


Hours: Minutes: Seconds

5.

Error designation

4
A0007561

List of the most common error messages during


commissioning, 26
List of all error messages, see associated Operating
Instructions on the CD-ROM

22

Endress+Hauser

Proline t-mass 65

5.3

Commissioning

Navigating within the function matrix

Esc

Esc

Esc

>3s

E
o
E

q
n

E
E

A0007562

1.

F Enter the function matrix (starting with measured value display)

2.

P Select the group (e.g. OPERATION)


F Confirm selection

3.

N Select function (e.g. LANGUAGE)

4.

P Enter code 65 (only for the first time you access the function matrix)
F Confirm entry
P Change function/selection (e.g. ENGLISH)
F Confirm selection

5.

Q Return to measured value display step by step

6.

Q > 3 s Return immediately to measured value display

Endress+Hauser

23

Commissioning

5.4

Proline t-mass 65

Calling the Commission Quick Setup

All the functions needed for commissioning are called up automatically with the Quick Setup.
The functions can be changed and adapted to the process in question.

1.

F Enter the function matrix (starting with measured value display)

2.

P Select the group QUICK SETUP


F Confirm selection

3.

QUICK SETUP COMMISSION function appears.

4.

Intermediate step if configuration is blocked:


P Enter the code 65 (confirm with F ) and thus enable configuration

5.

P Go to Commission Quick Setup

6.

P Select YES
F Confirm selection

7.

F Start Commission Quick Setup

8.

Configure the individual functions/settings:


Via P-key, select option or enter number
Via F-key, confirm entry and go to next function
Via Q-key, return to Quick Setup Commission function
(settings already made are retained)

Note!
Observe the following when performing the Quick Setup:
Configuration selection: Select the Actual Settings option
Unit selection: This is not offered again for selection after configuring a unit
Output selection: This is not offered again for selection after configuring an output
Automatic configuration of the display: if YES is selected
Main line = Mass flow
Additional line = Totalizer 1
If asked whether additional Quick Setups should be executed: select YES
All the available functions of the measuring device and their configuration options as well as
additional Quick Setups, if available, are described in detail in the "Description of Device
Functions" Operating Instructions. The related Operating Instructions can be found on the
CD-ROM.
The measuring device is ready for operation on completion of the following Quick Setups:
Commission, Sensor (only for 65 I), Gas, Pressure, Heat Flow (if used)

24

Endress+Hauser

Proline t-mass 65

5.5

Commissioning

Software settings

5.5.1 Device address


Has to be set for measuring devices with the following communication methods:
PROFIBUS DP/PA
Device address range 0 to 126, factory setting 126
MODBUS RS485
Device address range 1 to 247, factory setting 247
The device address can be configured via:
Miniature switches see Hardware settings section
Local operation see "Calling the Communication Quick Setup"

Note!
The COMMISSIONING SETUP must be executed before setting the device address.
Calling the Quick Setup Communication
1.

F Enter the function matrix (starting with measured value display)

2.

P Select the group QUICK SETUP


F Confirm selection

3.

N Select the QUICK SETUP COMMUNICATION function

4.

Intermediate step if configuration is blocked:


P Enter the code 65 (confirm with F ) and thus enable configuration

5.

P Go to Quick Setup Communication

6.

P Select YES
F Confirm selection

7.

F Start Quick Setup Communication

8.

P Select YES
F Confirm selection

9.

Configure the individual functions/settings:


Via P-key, select option or enter number
Via F-key, confirm entry and go to next function
Via Q-key, return to Quick Setup Commission function
(settings already made are retained)

All the available functions of the measuring device and their configuration options as well as
additional Quick Setups, if available, are described in detail in the "Description of Device
Functions" Operating Instructions. The related Operating Instructions can be found on the
CD-ROM.
The measuring device is ready for operation on completion of the Quick Setup Communication.

Endress+Hauser

25

Commissioning

5.6

Proline t-mass 65

Troubleshooting

The error messages that can occur most frequently when a measuring device is commissioned
are described here.
A complete description of all the error messages Operating Instructions on the CD-ROM.
HART
No.

Error message / Type

Cause/remedy

351

352

S: RANGE CUR.OUTn
$: # 351352

Current output:
The actual value for the flow lies outside the set limits.
Change full scale value entered or reduce flow.

359

360

S: RANGE PULSEn
$: # 359360

Pulse output: Pulse output frequency is outside the set range.

422

Remedy:

P: FLOW LIMIT
$: # 422

1.

Increase pulse value

2.

When selecting the pulse width, choose a value that can still
be processed by a connected counter.

3.

Reduce flow.

The measured flow has exceeded the maximum limit.


Reduce the flow rate or replace the instrument with a suitable size
for the application.

! Note!
Error can be configured as a fault or notice message.
PROFIBUS

Extended
Cause/remedy
diagnostic
message in the
PROFIBUS
master
Limits

0x13 BAD Sensor


failure

Quality substatus

422 P: FLOW LIMIT


$: # 422

Quality status

No. Device status message


(local display)

Quality code (hex)


Measured value status

PROFIBUS measured value


status

Constant

Meas. flow The measured flow has exceeded the


exceeded max maximum limit.
limit
Reduce the flow rate or replace the
instrument with a suitable size for the
application.

Note!
Error can be configured as a fault or
notice message.

26

Endress+Hauser

Proline t-mass 65

Commissioning

FOUNDATION Fieldbus
No.

Error messages:
FOUNDATION Fieldbus (FF)*
(onsite display)

Analog Input function block


Error messages

Cause/remedy

422

Device status message (FF):


Measured flow exceeds max limit
Err. No. 422
Onsite display:
P: FLOW LIMIT
!: # 422

OUT. QUALITY = UNCERTAIN

See HART table

OUT. SUBSTATUS = Non-specific

MODBUS RS485
Register 6859 Register 6821
Data type:
Data type:
Integer
String (18 byte)

No. Error message / Type

Cause/remedy

59

422 P: FLOW LIMIT


$: # 422

The measured flow has exceeded the maximum


limit.

FLOW LIMIT

Reduce the flow rate or replace the instrument


with a suitable size for the application.

Note!
Error can be configured as a fault or notice
message.

Endress+Hauser

27

www.endress.com/worldwide

KA021D/06/en/06.10
71115118
FM+SGML 6.0

Technical Information

Proline t-mass 65F, 65I


Thermal Mass Flow Measuring System
Direct Mass Flow Measurement of Gases

Application
For measuring the mass flowrate of a wide range of gas
types e.g.

Your benefits
Direct measurement of gas mass flow. Provides
temperature as an output.

The Proline transmitter concept comprises:


Modular device and operating concept resulting in a
higher degree of efficiency
Quick setup operating menus for ease of
commissioning
On board software freely allows the selection of up to
20 pure gases and creation of mixed gases with a
maximum of 8 components (e. g. Biogas)

Compressed air
Natural gas flow to boilers/dryers
Carbon Dioxide flow in breweries
Biogas and aeration air in waste water plants
Gas production (e. g. Ar, N2, CO2, He, O2)
Leakage detection

Approvals for hazardous area:


ATEX, FM, CSA, IECEx, NEPSI
Connection to all common process control systems:
HART, PROFIBUS DP/PA, FOUNDATION Fieldbus,
MODBUS RS485

TI069D/06/en/06.10
71115124

The t-mass sensors offer:


Negligible pressure drop or loss
Wide turndown of up to 100:1
Insertion version can be programmed for circular pipe
or rectangular ducting installation
Each device individually calibrated and delivered with
a traceable certificate
Can be calibrated with flow conditioner on request.
Optional hot tap device for insertion allowing ease of
removal/replacement for range of process pressure up
to 16 Barg (230 psig) and non-toxic gas applications.

Proline t-mass 65F, 65I

Table of contents
Function and system design. . . . . . . . . . . . . . . . . . . . . 3

Process conditions for Hot tap . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 20

Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Measuring range (air at ambient conditions) . . . . . . . . . . . . . . . . . 4
Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Material load curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Switching output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical connection Measuring unit . . . . . . . . . . . . . . . . . . . . . . 8
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical connection Remote version . . . . . . . . . . . . . . . . . . . . . 10
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Remote version
cable specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Performance characteristics. . . . . . . . . . . . . . . . . . . . 11
Calibration reference conditions . . . . . . . . . . . . . . . . . . . . . . . . . 11
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Influence of medium pressure
(Pressure co-efficient) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Response time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Operating conditions: Installation . . . . . . . . . . . . . . . 12

20
36
36
37
38

39
39
39
39

Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 39


CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C-Tick mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FOUNDATION Fieldbus certification . . . . . . . . . . . . . . . . . . . .
PROFIBUS DP/PA certification . . . . . . . . . . . . . . . . . . . . . . . . .
MODBUS certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure measuring device approval . . . . . . . . . . . . . . . . . . . . . .
Oxygen service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . .

39
39
39
39
40
40
40
40
40

Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 41
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measuring principle-specific accessories . . . . . . . . . . . . . . . . . . .
Service-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication-specific accessories . . . . . . . . . . . . . . . . . . . . . .

41
41
42
42

Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . 43

Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Mounting conditions for the insertion version . . . . . . . . . . . . . . . 17
Length of connecting cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Operating conditions: Environment. . . . . . . . . . . . . . 18


Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . 18

Operating conditions: Process . . . . . . . . . . . . . . . . . . 19


Medium temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Pressure loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Medium pressure range (nominal pressure) . . . . . . . . . . . . . . . . . 19
Flow limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Endress+Hauser

Proline t-mass 65F, 65I

Function and system design


Measuring principle

Thermal dispersion principle


The thermal principle operates by monitoring the cooling effect of a gas stream as it passes over a heated
transducer (PT100).
Gas flowing through the sensing section passes over two PT 100 RTD transducers one of which is used
conventionally as a temperature sensing device, whilst the other is used as a heater. The temperature sensor
monitors the actual process values whilst the heater is maintained at a constant differential temperature above
this by varying the power consumed by the sensor. The greater the mass flow, the greater the cooling effect
and power required to maintain the differential temperature. The measured heater power is therefore a
measure of the gas mass flowrate.

a0005136

Measuring system

The measuring system consists of a transmitter and a sensor. Two versions are available:
Compact version: transmitter and sensor form a single mechanical unit.
Remote version: transmitter and sensor are mounted physically separate from one another.
Transmitter
t-mass 65

Two-line liquid-crystal display


Configuration using push button operation

Esc

a0003671

Sensor
F

a0005137

Flanged version
Nominal diameters DN 15 to 100 (" to 4")
Sensor body material:
- 1.4404, 316L
- CF3M
Transducer body material:
- 1.4404, 316L, Alloy C22
Insertion version
Sensor length 235/335/435/608 for DN 80 to 1500
(9.25"/13.2"/17.1"/23.9" for line size 3" to 60")
Sensor body material:
1.4404, 316/316L
Transducer body material:
1.4404/316L, Alloy C22

a0005138

Endress+Hauser

Proline t-mass 65F, 65I

Input
Measured variable

Mass flow
Gas temperature
Gas heat flow

Measuring range (air at


ambient conditions)

The measuring range is dependant on the gas selection, line size and use of flow conditioner. Each meter is
individually calibrated on air and mathematically converted to suit the customer specific gas, where required.
The table below defines the ranges available for air without flowconditioner. Please refer to your
Endress+Hauser representative or to Applicator, the selection tool, for other gases and process conditions.
Measuring range for the flanged version, metric units:
DN
15
25
40
50
80
100

kg/h
min.
0.5
2
6
10
20
38

max.
53
200
555
910
2030
3750

Nm3/h at 0C, 1.013 bar a


min.
max.
0.38
41
1.5
155
4.6
429
7.7
704
15.5
1570
29
2900

scf/min. at 15C, 1.013 bar a


min.
max.
0.23
25
1.0
96
3.0
266
5.0
436
10
974
18
1800

Measuring range for the flanged version, US units:


DN
"
1"
1 "
2"
3"
4"

lb/h
minimum
1.1
4.4
13.2
22
44
84

maximum
116
440
1220
2002
4466
8250

Sm3/h at 59 F, 14.7 psi a


minimum
maximum
0.4
42
1.6
160
4.8
450
8
740
16
1656
30
3060

scf/min. at 59 F, 14.7 psi a


minimum
maximum
0.23
25
1.0
96
3.0
266
5.0
436
10
974
18
1800

Measuring range for the insertion version, metric units:


DN
80
100
150
200
250
300
400
500
600
700
1000
1500

kg/h
min.
20
38
50
80
120
180
300
500
700
900
2000
2500

max.
2030
3750
7500
12500
20000
28000
50000
80000
115000
159000
320000
720000

Nm3/h at 0C, 1.013 bar a


min.
max.
15.5
1570
29.0
2900
38
5800
62
9666
93
15468
139
21655
232
38670
386
61870
540
88940
696
122970
1546
247846
1933
556844

scf/min. at 15C, 1.013 bar a


min.
max.
9.6
974
18
1800
24
3600
38
6000
58
9600
86
13440
144
24000
240
38400
336
55200
432
76300
960
153 600
1200
345 600

In order to achieve optimum performance it is recommended that under operating conditions the maximum
velocity is limited to a value below 70 m/sec.

Endress+Hauser

Proline t-mass 65F, 65I

The flowrates shown are representative of the calibrated conditions only and do not necessarily reflect what
the meter can measure under operating conditions and actual internal pipe dimensions found on site. To
correctly size and select a meter, it is recommended that you either contact your local Endress+Hauser
representative or refer to the Endress+Hauser software package Applicator. Examples in metric units:
Line Size
DN
50
50
50
50
50
50

Input signal

Gas
Air
Air
CO2
CO2
Methane
Methane

Process pressure
bar a
1
3
1
3
1
3

Temperature
C
25
25
25
25
25
25

Max. Flowrate
kg/h
910
3300
1300
3950
795
1500

Status input (auxiliary input) for HART version


U = 3 to 30 V DC, Ri = 5 k, galvanically isolated; switch level 3 to 30 V DC;
Configurable for: gas group, totalizer reset, positive zero return, start zero point adjustment
Status input (auxiliary input) for PROFIBUS DP
U = 3 to 30 V DC, Ri = 3 k, galvanically isolated; switch level: 3 to 30 V DC, independent of polarity.
Configurable for: positive zero return, error message reset, zero point adjustment start.
Status input (auxiliary input) for MODBUS RS485
U = 3 to 30 V DC, Ri = 3 k, galvanically isolated; switch level: 3 to 30 V DC, independent of polarity.
Configurable for: totalizer reset, positive zero return, error message reset, start zero point adjustment.
Current input:
Active/passive selectable, galvanically isolated, resolution: 2 A
Active: 4 to 20 mA, Ri 150 , Uout = 24 V DC, short-circuit proof
Passive: 0/4 to 20 mA, Ri 150 , Umax = 30 V DC
Configurable for: pressure, gas analyzer

Output
Output signal

Current output
Active/passive selectable, galvanically isolated, time constant selectable (0.0 to 100.0 s), full scale value
selectable, temperature coefficient: typically 0.005% o.f.s./C, resolution: 0.5 A
Active: 0/4 to 20 mA, RL < 700 (for HART: RL 250 )
Passive: 4 to 20 mA; supply voltage VS 18 to 30 V DC; Ri 150
If the current output is used as a temperature output, please observe the following information:
Class B according to EN 6075

Endress+Hauser

Proline t-mass 65F, 65I

Pulse/frequency output
Active/passive selectable, galvanically isolated
Active: 24 V DC, 25 mA (max. 250 mA during 20 ms), RL > 100 (Flexible I/O boards, siehe terminal
assignment 9)
Passive: Open Collector, 30 V DC, 250 mA
Frequency output: full scale frequency 2 to 1000 Hz (fmax = 1250 Hz), on/off ratio 1:1,
pulse width max. 2 s, time constant selectable (0.0 to 100.0 s)
Pulse output: pulse value and pulse polarity can be selected, pulse width adjustable (0.5 to 2000 ms;
factory setting 20 ms)
PROFIBUS DP interface

PROFIBUS DP in accordance with EN 50170 Volume 2


Profile Version 3.0
Data transmission rate: 9.6 kBaud to 12 MBaud
Automatic data transmission rate recognition
Signal encoding: NRZ-Code
Function blocks: 3 Analog Input, 2 Totalizer, 1 Analog Output,
Output data: Mass flow, Corrected volume flow, Temperature, Totalizers 1 to 2
Input data: Positive zero return (ON/OFF), Zero point adjustment, Measuring mode, Totalizer control
Bus address can be configured via miniature switches or via the local display (optional)
Available output combination 9

PROFIBUS PA interface

PROFIBUS PA in accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically isolated
Data transmission rate: 31.25 kBit/s
Current consumption: 11 mA
Permitted supply voltage: 9 to 32 V
Bus connection with integrated reverse polarity protection
Error current FDE (Fault Disconnection Electronic): 0 mA
Signal encoding: Manchester II
Function blocks: 3 Analog Input, 2 Totalizer, 1 Analog Output,
Output data: Mass flow, Corrected volume flow, Temperature, Totalizers 1 to 2
Input data: Positive zero return (ON/OFF), Zero point adjustment, Measuring mode, Totalizer control
Bus address can be configured via miniature switches or via the local display (optional)
Available output combination 9

MODBUS interface

MODBUS device type: slave


Address range: 1 to 247
Supported function codes: 03, 04, 06, 08, 16, 23
Broadcast: supported with the function codes 06, 16, 23
Physical interface: RS485 in accordance with EIA/TIA-485 standard
Supported baud rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Baud
Transmission mode: RTU or ASCII
Response times:
Direct data access = typically 25 to 50 ms
Auto-scan buffer (data range) = typically 3 to 5 ms
Available output combination 9

Endress+Hauser

Proline t-mass 65F, 65I

FOUNDATION Fieldbus interface

Signal on alarm

FOUNDATION Fieldbus H1, IEC 61158-2, galvanically isolated


Data transmission rate: 31.25 kBit/s
Current consumption: 12 mA
Permitted supply voltage: 9 to 32 V
Error current FDE (Fault Disconnection Electronic): 0 mA
Bus connection with integrated reverse polarity protection
Signal encoding: Manchester II
ITK Version 5.01
Function blocks:
7 Analog Input (Execution time: each 18 ms)
1 Analog Output (Execution time: 18 ms)
1 Digital Output (18 ms)
1 PID (25 ms)
1 Arithmetic (20 ms)
1 Input Selector (20 ms)
1 Signal Characterizer (20 ms)
1 Integrator (18 ms)
Number of VCRs: 38
Number of link objects in VFD: 40
Output data: Mass flow, Corrected volume flow, Temperature, Totalizers 1 to 3
Input data: Positive zero return (ON/OFF), Zero point adjustment, Measuring mode, Reset totalizer
Link Master (LM) function is supported
Available output combination 9

Current output:
Failsafe mode selectable (e.g. in accordance with NAMUR Recommendation NE 43)
Current input:
Failsafe value selectable
Pulse/frequency output:
Failsafe mode selectable
Status output:
"Non conductive" in the event of fault or power supply failure.
Relay output:
"De-energized" in the event of fault or power supply failure.
PROFIBUS DP:
Status and alarm messages in accordance with PROFIBUS Profile Version 3.0.
MODBUS RS485:
If an error occurs, the value NaN (not a number) is output for the measured values.

Load

see "Output signal"

Low flow cut off

Switch points for low flow cut off are programmable

Galvanic isolation

All circuits for inputs, outputs, and power supply are galvanically isolated from each other.

Switching output

Relay output:
Normally closed (NC) or normally open (NO) contacts available
(factory setting: relay 1 = NO, relay 2 = NC), max. 30 V / 0.5 A AC; 60 V / 0.1 A DC, galvanically isolated.
Configurable for: error messages, limit values

Endress+Hauser

Proline t-mass 65F, 65I

Power supply
Electrical connection
Measuring unit

A
d
g
b
a

a
b d/(g) (d)
PROFIBUS PA*
FOUNDATION Fieldbus*

HART*
HART**

27
+ 26
25
+ 24
23
+ 22
21
+ 20

N (L-) 2
L1 (L+)1

d
e

PA()/FF()
PA(+)/FF(+)

+
f

27
26
25
24
23
22
21
20

N (L-) 2
L1 (L+) 1

PROFIBUS DP*

A (RxD/TxD-N) 27
B (RxD/TxD-P) 26
25
+ 24
f
23
+ 22
21
+ 20

N (L-) 2
L1 (L+) 1

d
e

c
b

MODBUS RS485*

d
e
g
c
b

A (RxD/TxD-N) 27
B (RxD/TxD-P) 26
25
+ 24
f
23
+ 22
21
+ 20

N (L-) 2
L1 (L+) 1

d
e
g
c
b
a0005135

Connecting the transmitter, cable cross-section: max. 2.5 mm


A
B

View A (field housing)


View C (wall-mount housing)

*)
**)
a
b

fixed communication board


flexible communication board
Connection compartment cover
Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC
Ground terminal for protective ground
Signal cable: see Terminal assignment 9
Fieldbus cable:
Terminal No. 26: DP (B) / PA (+) / FF (+) / MODBUS RS485 (B) / (PA, FF: with reverse polarity protection)
Terminal No. 27: DP (A) / PA () / FF () / MODBUS RS485 (A) / (PA, FF: with reverse polarity protection)
Ground terminal for signal cable shield / fieldbus cable / RS485 line
Service adapter for connecting service interface FXA 193 (Fieldcheck, FieldCare)
Signal cable: see Terminal assignment 9
Cable for external termination (only for PROFIBUS DP with permanent assignment communication board):
Terminal No. 24: +5 V
Terminal No. 25: DGND

c
d

e
f
g

Endress+Hauser

Proline t-mass 65F, 65I

Terminal assignment

Terminal No. (inputs/outputs)


Order version

20 (+) / 21 ()

22 (+) / 23 ()

24 (+) / 25 ()

26 (+) / 27 ()

Fixed communication boards (permanent assignment)


65F**-***********A
65I-*************A

Frequency output

Current output
HART

65F**-***********B
65I-*************B

Relay output

Relay output

Frequency output

Current output
HART

65***-***********F
65I-*************F

PROFIBUS PA, Ex i

65***-***********G
65I-*************G

FOUNDATION
Fieldbus Ex i

65***-***********H
65I-*************H

PROFIBUS PA

65***-***********J
65I-*************J

+5V (ext. termination)

PROFIBUS DP

65***-***********K
65I-*************K

FOUNDATION
Fieldbus

65***-***********Q
65I-*************Q

Status input

MODBUS RS485

65F**-***********R
65I-*************R

Current output 2
Ex i, active

Current output 1
Ex i active, HART

65F**-***********S
65I-*************S

Frequency output
Ex i, passive

Current output Ex i
Active, HART

65F**-***********T
65I-*************T

Frequency output
Ex i, passive

Current output Ex i
Passive, HART

65F**-***********U
65I-*************U

Current output 2
Ex i, passive

Current output 1
Ex i passive, HART

65F**-***********C
65I-*************C

Relay output 2

Relay output 1

Frequency output

Current output
HART

65F**-***********D
65I-*************D

Status input

Relay output

Frequency output

Current output
HART

65F**-***********E
65I-*************E

Status input

Relay output

Current output 2

Current output 1
HART

65F**-***********L
65I-*************L

Status input

Relay output 2

Relay output 1

Current output
HART

65F**-***********2
65I-*************2

Relay output

Current output 2

Frequency output

Current output 1
HART

65F**-***********4
65I-*************4

Current input

Relay output

Frequency output

Current output
HART

65F**-***********5
65I-*************5

Status input

Current input

Frequency output

Current output
HART

65F**-***********6
65I-*************6

Status input

Current input

Current output 2

Current output 1
HART

65F**-***********8
65I-*************8

Status input

Frequency output

Current output 2

Current output
HART

Flexible communication boards

Endress+Hauser

Proline t-mass 65F, 65I

Electrical connection
Remote version

GND
-

6 10V
+

COMMS
+
44

41

42

43

41
GND

42

44
43
+
COMMS

d
d
d
e
c
+
6 10V

A0013669

Connecting the remote version


a
b
c
d
e

Wall-mount housing transmitter: non-hazardous area and ATEX II3G / zone 2 see separate "Ex documentation"
Wall-mount housing transmitter: ATEX II2G / Zone 1; FM/CSA see separate "Ex documentation"
Connection housing sensor
Cover for connection compartment or connection housing
Connecting cable

Terminal No.:
41 = white; 42 = brown; 43 = green; 44 = yellow

Supply voltage

85 to 260 V AC, 45 to 65 Hz
20 to 55 V AC, 45 to 65 Hz
16 to 62 V DC

Cable entries

Power-supply and signal cables (inputs/outputs):


Cable entry M20 1.5 (8 to 12 mm / 0.31" to 0.47")
Thread for cable entries, " NPT, G "
Connecting cable for remote version:
Cable entry M20 1.5 (8 to 12 mm / 0.31" to 0.47")
Thread for cable entries, " NPT, G "

Remote version
cable specifications

2 2 0.5 mm (AWG 20) PVC cable with common shield (2 twisted pairs)
Conductor resistance: 40 /km [ 131.2 / 1000 ft]
Capacitance, core/shield: 0.001 F/m [ 3.280 nF/ft]
Inductance: 0.9 H/m [ 2.952 H/ft]
Operating voltage: 250 V
Temperature range: 40 to +105 C [40 to +221 F]
Overall nominal diameter: 8.5 mm [0.335"]
Maximum cable length: 100 m [328 feet]

Operation in zones of severe electrical interference:


The measuring device complies with the general safety requirements in accordance with EN 61010, the EMC
requirements of IEC/EN 61326, and NAMUR recommendation NE 21/43.
For cable specifications for hazardous area devices please see the additional Ex documentation.
Power consumption

10

AC: 85 to 260 V = 18.2 W ; 20 to 55 V = 14 W ; (including sensor)


DC: 8 W (including sensor)

Endress+Hauser

Proline t-mass 65F, 65I

Power supply failure

Lasting minimum 1 power cycle


EEPROM/HistoROM T-DAT saves measuring system data if the power supply fails
HistoROM S-DAT is on exchangeable data storage chip with sensor specific data (pipe type, nominal
diameter, serial number, flow conditioner, zero point, etc.)
Totalizer stops at the last value determined

Potential equalization

No special measures for potential equalization are required.


For instruments for use in hazardous areas, observe the corresponding guidelines in the specific Ex
documentation.

Performance characteristics
Calibration reference
conditions

Accredited according to ISO/IEC 17025


Traceable to National Standards
Calibration gas: air
Temperature controlled to 24 C 0.5 C (75.2 F 0.9 F) at atmospheric pressure
Humidity controlled < 40% RH

Maximum measured error

t-mass 65F:
1.5 % of reading for 100 % to 10 % of full scale (at reference conditions)
0.15 % of full scale for 10 % to 1 % of full scale (at reference conditions)
t-mass 65I:
1.0% of reading
0.5% of full scale (at reference conditions)

Repeatability

0.4 % of reading for velocities above 1.0 m/s (3.3 ft/s)

Influence of medium pressure


(Pressure co-efficient)

Air: 0.35% per bar (0.02% per psi) of process pressure change
Other gases: on request

Response time

Typically less than 2 seconds for 63 % of a given step change (in either direction).

Endress+Hauser

11

Proline t-mass 65F, 65I

Operating conditions: Installation


Thermal meters require a fully developed flow profile as a prerequisite for correct flow measurement. For this
reason, please note the following points when installing the device.
Installation instructions

Orientation

The thermal dispersion principle is sensitive to disturbed flow conditions.


Observe the recommended inlet and outlet requirements.
Good engineering practice is necessary for the associated pipe work and installation.
Ensure correct alignment and orientation of the sensor.
Take measures to reduce or avoid condensation (e.g. install a condensation trap, thermal insulation, etc.).
The maximum permitted ambient temperatures and the medium temperature range ( 19) must be
observed.
Install the transmitter in a shaded location or use a protective sun shield.
For mechanical reasons, and in order to protect the pipe, it is advisable to support heavy sensors.
Flanged sensor

Insertion sensor

Vertical orientation
compact

remote

compact

remote

m, n

A0013785

Horizontal orientation, transmitter head up


compact/remote

n
A0013786

Horizontal orientation, transmitter head down


compact/remote

o
A0013787

Inclined orientation, transmitter head down


compact/remote

p
A0009897

= Recommended orientation
= Orientation recommended in certain situations
m In the case of saturated or unclean gases, upward flow in a vertical pipe section is preferred to minimize
condensation/contamination.
n Not recommended if the vibrations are too high or if the installation is unstable.
o Only suitable for clean/dry gases. Do not mount the sensor from the bottom, on horizontal pipes, if build-ups or
condensate are likely to be present. Mount the sensor in a position as indicated below
p If the gas is very damp or saturated with water (e. g. Bio Gas), mount in inclined orientation ( = max. 135).

12

Endress+Hauser

Proline t-mass 65F, 65I

Thermal insulation
When the gas is very humid or saturated with water (e. g. Bio Gas), the piping and flowmeter body should be
insulated to prevent water droplets condensing on the measuring sensor.

a0005122

Maximum thermal insulation for t-mass 65F and 65I


a
b

Endress+Hauser

Maximum insulation height for the flanged sensor


Maximum insulation height for the insertion sensor

13

Proline t-mass 65F, 65I

Inlet and outlet runs

The thermal dispersion principle is sensitive to disturbed flow conditions.


As a general rule, the thermal flowmeter should always be installed as far away as possible from any flow
disturbances. For further information please refer to ISO 14511.
Where two or more flow disturbances are located upstream of the meter, the recommended inlet length for
the flow disturbance causing strongest disturbance must be used. E.g. where a valve is mounted before a
bend, upstream of the flowmeter, 50 DN of pipe work is required from the valve to the flowmeter.
For very light gases such as Helium and Hydrogen all upstream distances should be doubled.
The minimum recommendations for inlet and outlet runs (without flow conditioner) are:
Flanged sensor
1

2
15 x DN

a0007523

a0007524

5
20 x DN

2 x DN

15 x DN

2 x DN

15 x DN

2 x DN

2 x DN

a0007525

6
50 x DN

2 x DN

35 x DN

a0007526

2 x DN

a0007527

a0007528

1 = Reduction, 2 = Expansion, 3 = 90 elbow or T-piece, 4 = 2 90 elbow, 5 = 2 90 elbow (3-dimensional),


6 = Control valve

Insertion sensor
2

1
20 x DN

3
20 x DN

5 x DN

a0007529

5 x DN

a0007530

5
25 x DN

20 x DN

5 x DN

5 x DN

a0007531

6
40 x DN

5 x DN

a0007532

50 x DN

5 x DN

a0007564

a0007534

1 = Reduction, 2 = Expansion, 3 = 90 elbow or T-piece, 4 = 2 90 elbow, 5 = 2 90 elbow (3-dimensional),


6 = Control valve or pressure regulator

A specially designed perforated plate flow conditioner can be installed if it is not possible to observe
the inlet runs required ( 15).
Outlet runs with pressure measuring points
The pressure measuring point should be installed downstream of the measuring device, so that there is no
potential influence of the pressure transmitter process connection on the flow entering the measuring point.

PT

2...5 x DN
a0005114

Installing a pressure measuring point (PT = pressure transmitter)

14

Endress+Hauser

Proline t-mass 65F, 65I

Perforated plate flow conditioner


It is recommended to install a perforated plate flow conditioner if the recommended inlet runs are not available.

5 DN

2 DN

5 DN

8 DN

5 DN

2
a0005115

The figure above illustrates the minimum recommended inlet and outlet runs expressed in multiples of the pipe diameter
using a flow conditioner.
1 = Flow conditioner with the flanged sensor, 2 = Flow conditioner with the insertion sensor

Flow conditioner for use with insertion sensors 65I 41


The well known "Mitsubishi" design is recommended for this application DN 80 mm to DN 300 mm (3" to
12"). The flow conditioner must be installed at a distance of 8 DN upstream of the sensor. A further 5 pipe
diameters inlet run is required upstream of the actual conditioner itself.
Flow conditioner for use with flanged sensors 65F 41
This is a special Endress+Hauser version designed specially for use with the t-mass F sensor (sizes DN 25 to
100 / 1" to 4"). The mounting hole patterns and sizing are of a multi-variant design which means that one
plate will fit different flange pressure classes e.g. Cl. 150 and Cl. 300.
The flow conditioner and gaskets are fitted between two pipe flange and the flow meter
flange. Use only bolts which match to the flange bolt hole and this will ensure that the correct positioning of
the plate can be found.
The alignment notch must also be pointing in the same plane as the transmitter.
Incorrect installation of the flow conditioner will have a small effect on the measurement accuracy.

1
a0005116

Flow conditioner mounting arrangement (example)


1 = Perforated plate flow conditioner, 2 = Seal/gasket, 3 = Notch, 4 = correct pointing of alignment notch in the same
plane as the transmitter

Endress+Hauser

15

Proline t-mass 65F, 65I

Note
For optimum performance, it is advised that the t-mass F sensor and flow conditioner are ordered at the same
time such that they are calibrated together. To retrospectively fit a flow conditioner will have a small effect
on the measurement performance.
The use of other types of flow conditioners, other than the Endress+Hauser flow conditioner, with the tmass F sensor will have an impact on the measurement performance due to the effects of flow profile and
pressure drop.
Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer.
Pressure loss calculation
Dp = constant

g2
r

1
4
D

Pressure loss: p in mbar or psi


Mass flow : g in kg/h or lbm/h
Density: in kg/m3 or lbm/ft3
Diameter: D in mm or inch
Constant = 1876 (SI units) or 8.4 107 (US units)
Calculation examples:
g = 148 kg/h or 326 lbm/h
= 5.94 kg/m3 (at 5 bar abs at 20 C) or 0.37 lbm/ft3 (at 72.5 psi abs at 68 F)
D = 28.5 mm (for a DN 25, PN 40) or 1.05 inch (for a 1" Class 150 Sched 40)
SI units

Dp = 1876

US units

1482
5.94

1
= 10.5 mbar
4
28.5

-7

Dp = 8.4 10

3262
1
= 0.198 psi
0.371 1.054

Pipework requirements
Good engineering practice should be followed at all times:

Correct preparation, welding and finishing techniques


Correctly sized gaskets
Correctly aligned flanges and gaskets
Connecting pipe work should match the internal diameter of the flowmeter.
Maximum pipe diameter mismatch should not exceed:
1 mm (0.04 inch) for diameters < DN 200 (8")
3 mm (0.12 inch) for diameters DN 200 (8")
New installations should be free of metallic and abrasive particles to prevent damage to the sensing elements
on start-up
For further information please refer to ISO 14511.
Correctly aligned flanges and gaskets

a0005103

a0005104

Pipe diameter one is not equal pipe


diameter two

16

a0005105

Incorrectly sized gaskets

a0005106

Incorrectly aligned flanges and gaskets

Endress+Hauser

Proline t-mass 65F, 65I

Mounting conditions for the


insertion version

Selecting the length of the insertion sensor


The minimum required length of the insertion sensor can be determined by using Endress+Hauser's sizing tool,
Applicator (version 10.02 or later "Accessories") or according to the following calculation steps.
The minimum required length of the insertion sensor is determined by the necessary insertion depth. The
calculated insertion depth must lie within the adjustable range of the selected insertion sensor.
1.

Determine the dimensions A, B, C1 and C2

9
9

230
220

230

220

210

210

200

190

200
190

200

180

C1 C2

180

C1 C2

230
220

210

190
180

A0014024

A=

For circular pipes: the internal pipe diameter (DN)


For rectangular pipes/ducts: the inner dimension

B=

Wall thickness of pipe or duct

C1+C2 =

Length of mounting set and insertion tube's compression fitting

Determine the dimensions C1 and C2


If only Endress+Hauser accessories are used
DK6MB-BXA Mounting boss G1A:

C1 + C2 = 106 mm (4.173 inch)

DK6MB-AXA Mounting boss 1" NPT:

C1 + C2 = 112 mm (4.409 inch)

If it is intended not to use solely Endress+Hauser accessories


C1

Height of pipe connection (mounting boss) used

C2

46mm (1.811 inch) process connection, G1A threaded fitting


52mm (2.047 inch) process connection, NPT threaded fitting

2.

Calculate the insertion depth


Insertion depth = (0,3 A) + B + (C1 + C2) + 2 mm
(Insertion depth = (0,3 A) + B + (C1 + C2) + 0.079 inch)

3.

A suitable insertion sensor length can be determined by comparing the calculated insertion depth with
the following table. The calculated insertion depth must be within the adjusting range of the
corresponding insertion sensor length!
Insertion length

Adjusting range (insertion depth)


G1A Thread

mm

Endress+Hauser

inch

mm

NPT Thread
inch

mm

inch

235

120 to 230

4.7 to 9.0

126 to 230

4.96 to 9.0

335

13

120 to 330

4.7 to 13.0

126 to 330

4.96 to 13.0

435

17

120 to 430

4.7 to 17.0

126 to 430

4.96 to 17.0

608

24

120 to 604

4.7 to 23.8

126 to 604

4.96 to 23.8

17

Proline t-mass 65F, 65I

Mounting conditions for welding sockets

D
90

90

When mounting the fitting to a thin wall duct, use a


suitable support bracket for the sensor.
D = 31.0 mm 0.5 mm ( 1.22" 0.019")

A0011843

Aligning the insertion version to flow direction


Check and ensure that the sensor is aligned vertically at a 90 angle on the pipe/duct.
Turn the sensor so that the arrow marking matches the direction of flow.

90 (3)

90(7)
A0007536

Length of connecting cable

A0007537

Max. 100 m (328 feet), remote version

Operating conditions: Environment


Ambient temperature

Standard: 20 C to +60 C (4 F to +140 F)


Optional: 40 C to +60 C (40 F to +140 F)
Install the device in a shady location. Avoid direct sunlight, particularly in warm climatic regions.
(A protective sun cover is available on request)
At ambient temperatures below 20 C (4 F) the readability of the display may be impaired.

Storage temperature

40 to +80 C (40 to +176 F), recommended: +20 C (+68 F)

Degree of protection

Standard: IP 67 (NEMA 4X) for transmitter and sensor

Shock resistance

According to IEC 60068-2-31

Vibration resistance

Acceleration up to 1 g, 10 to 150 Hz, following IEC 60068-2-6

Electromagnetic compatibility
(EMC)

To IEC/EN 61326 and NAMUR recommendation NE 21

18

Endress+Hauser

Proline t-mass 65F, 65I

Operating conditions: Process


Medium temperature range

Sensor
t-mass F:
40 C to +100 C (40 F to +212 F)
t-mass I:
40 C to +130 C (40 F to +266 F)
Seals t-mass F
O-rings:
Viton FKM 20C to +100C (4F to +212F)
Kalrez 20C to +100C (4F to +212F)
EPDM 40C to +100C (40F to +212F)
Bushing:
PEEK, PVDF 40C to +100C (40F to +212F)
Seals t-mass I
Bonded seals:
Kalrez 20C to +130C (4F to +266F)
EPDM 40C to +130C (40F to +266F)
Nitrile 35C to +130C (31F to +266F)
Ferrule:
PEEK, PVDF 40C to +130C (40F to +266F)

Pressure loss

Negligible (without flow conditioner).


Refer to Applicator for the precise calculation

Medium pressure range


(nominal pressure)

t-mass F:
0.5 to 40 bar gauge (7.25 to 580 psi gauge)
t-mass I:
0.5 to 20 bar gauge (7.25 to 290 psi gauge)

Flow limit

See "Measuring range" section. 4


The velocity in the measuring tube should not exceed 130 m/s (427 ft/s).

Process conditions for Hot tap

The Hot tap is permitted for use only with non-toxic, innocuous gases classified as "Group II" in accordance
with the European directive 67/548/EWG art. 2.
Medium pressure version
Max. process pressure: 20 bar (290 psig)
Max. extraction press: 16 bar (230 psig)
Max. extraction temperature: +50C (+122F)
Min. sensor length: 435 mm (17 inch)
Low pressure version
Max. process pressure: 20 bar (290 psig)
Max. extraction press: 4,5 bar (65 psig)
Max. extraction temperature: +50C (+122F)
Min. sensor length: 435 mm (17 inch)

Endress+Hauser

19

Proline t-mass 65F, 65I

Mechanical construction
Design, dimensions

Dimensions:
Transmitter remote version, connection housing (II2G/Zone 1), flange version

20

Transmitter remote version, connection housing (II2G/Zone 1)

21

Transmitter remote version, wall-mount housing (non Ex-zone and II3G/Zone 2)

22

Installing the wall-mount housing

23

Process connections in SI units


t-mass 65F: Flange connections EN (DIN), JIS

24

t-mass 65F: Flange connections ANSI

26

t-mass 65I: Compact insertion version

28

t-mass 65I: Remote sensor housing insertion version

28

Flow conditioner according to EN (DIN) / JIS / ANSI

29

Hot tap

30

Process connections in US units


t-mass 65F: Flange connections ANSI

31

t-mass 65I: Compact insertion version

33

t-mass 65I: Remote sensor housing insertion version

33

Flow conditioner according to ANSI

34

Hot tap

35

Transmitter remote version, connection housing (II2G/Zone 1), flange version

129 (5.1)

79 (3.1)

102 (4.0)
V

50 (1.96)

52 (2.0)

mm (inch)
a0005158

Dimensions "V": 24 and 26

20

Endress+Hauser

Proline t-mass 65F, 65I

Transmitter remote version, connection housing (II2G/Zone 1)

A
A*
C

B
B*

D
e r Sp annu
ht unt
ng
Nic
ffnen

Esc
+

ove r tight wh
ep c
Ke ircuit s a re aliv ile
c
e

uvrir la
pas o t e pparei
l
sou s nsion

Ne

Non-intrinsically safe
circuits Ip40 protected
Boucles de courant
sans scurit intrinsque
protges par Ip40

p cover tight w
Kee ircuits are ali hile
ve
c

Nicht-eigensichere
Stromkreise durch
IP40-Abdeckung geschtzt

G
H
a0006999

Dimensions in SI units
A

A*

B*

265

242

240

217

206

186

178

8.6 (M8)

100

130

100

144

170

348

* Blind version (without display)


All dimensions in [mm]

Dimensions in US units
A

A*

B*

10.4

9.53

9.45

8.54

8.11

7.32

7.01

0.34 (M8)

3.94

5.12

3.94

5.67

6.69

13.7

* Blind version (without display)


All dimensions in [inch]

Pipe mounting of the remote field housing


If a warm pipe is used for installation, make sure that the housing temperature does not exceed the max.
permitted value of +60 C (+140 F).
240 (9.45)

ht unter Spannun
Nic
g
ffnen

Non-intrinsically safe
circuits Ip40 protected
Boucles de courant
sans scurit intrinsque
protges par Ip40

p cover tight w
Kee ircuits are ali hile
ve
c

over tight wh
i
ep c
Ke ircuits are alive le
c

Nicht-eigensichere
Stromkreise durch
IP40-Abdeckung geschtzt

vri
pas ou r lappa
Ne sous tension reil

mm (inch)

a
a0005157

a = Pipe mounting (separate mounting set, see accessories)

Endress+Hauser

21

Proline t-mass 65F, 65I

Transmitter remote version, wall-mount housing (non Ex-zone and II3G/Zone 2)

Esc

G
E

a0001150

Dimensions in SI units
A

215

250

90.5

159.5

135

90

45

>50

81

53

T 1)

95

53

102

81.5

11.5

192

8 M5

20

2 6.5

1)
Fixing bolt for wall assembly: M6 (screw head max. 10.5 mm)
All dimensions in [mm]

Dimensions in US units
A

8.46

9.84

3.56

6.27

5.31

3.54

1.77

>1.97

3.18

3.74

2.08

4.01

3.20

0.45

7.55

8 M5

0.79

K
2.08
T

1)

2 0.26

1)

Fixing bolt for wall assembly: M6 (screw head max. 0.41 inch)
All dimensions in [inch]

22

Endress+Hauser

Proline t-mass 65F, 65I

Installing the wall-mount housing


Make sure that ambient temperature does not go beyond the permissible range
20 to +60 C (4 to + 140 F), optional 40 to +60 C (40 to +140 F).
Install the device in a shady location. Avoid direct sunlight.
Always install the wall-mount housing in such a way that the cable entries are pointing down.
Mounted directly on the wall

35 (1.38)

81.5 (3.2)

a
90 (3.54)

192 (7.56)

mm (inch)
a0001130

a = Cover of the connection compartment


b = Securing screws (M6): max. 6.5 mm (0.26"); screw head: max. 10.5 mm (0.41")
c = Appropriate bores in the housing.

Pipe mounting and installation in control panel


If a warm pipe is used for installation, make sure that the housing temperature does not exceed the maximum
permitted value of +60 C. (+140 F).

+0.5 (0.02)

20...70
(0.78 to 2.75)

210 (8.27) -0.5 (0.02)

+0.5 (0.02)

245 (9.65) -0.5 (0.02)

~155 (6.1)
mm (inch)

~110 (4.3)
a0005256

A = Pipe mounting of wallmount housing


B = Installation in control panel of wallmount housing

Endress+Hauser

23

Proline t-mass 65F, 65I

Process connections in SI units


t-mass 65F: Flange connections EN (DIN), JIS

168 (6.61)

227 (8.94)

160 (6.3)

LK

207 (8.15)

di

T
L

mm (inch)

+1.5 (0.06)
- 2.0 (0.08)

a0005162

Flange EN 1092-1 (DIN 2501 / DIN 2512N 1)) / PN 16: 1.4404/316L/316


Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 6.3 to 12.5 m
DN
100

di

LK

97

303

220

800

180

8 18

500.5

20

299.5

107.1

143

1) Flange with groove to EN 1092-1 Form D (DIN 2512N) available


All dimensions in [mm]

Flange EN 1092-1 (DIN 2501 / DIN 2512N 1)) / PN 40: 1.4404/316L/316


Surface roughness (flange): EN 1092-1 Form B1 (DIN 2526 Form C), Ra 6.3 to 12.5 m
DN

di

LK

15

13.9

276.5

95

245

65

4 14

132.5

16

112.5

17.3

116.5

25

24.3

276.5

115

245

85

4 14

132.5

18

112.5

28.5

116.5

40

38.1

273.5

150

320

110

4 18

200

18

120

43.1

113.5

50

49.2

278.5

165

400

125

4 18

250

20

150

54.5

118.5

80

73.7

291

200

640

160

8 18

400

24

240

82.5

131

100

97

303

235

800

190

8 22

500.5

24

299.5

107.1

143

1)

Flange with groove to EN 1092-1 Form D (DIN 2512N) available


All dimensions in [mm]

Flange JIS B2220/ 10K / Sched 40: 1.4404/316L/316


Surface roughness (flange): Ra 3.2 to 6.3 m
DN

di

LK

50

49.2

278.5

155

400

120

4 19

250.0

17.5

150.0

52.7

118.5

80

73.7

291.0

185

640

150

8 19

400.0

20

240.0

78.1

131.0

100

97.0

303.0

210

800

175

8 19

500.5

20

299.5

102.3

143.0

All dimensions in [mm]

24

Endress+Hauser

Proline t-mass 65F, 65I

Flange JIS B2220/ 10K / Sched 80: 1.4404/316L/316


Surface roughness (flange): Ra 3.2 to 6.3 m
DN

di

LK

50

49.2

278.5

155

400

120

4 19

250.0

17.5

150.0

49.2

118.5

80

73.7

291.0

185

640

150

8 19

400.0

20

240.0

73.7

131.0

100

97.0

303.0

210

800

175

8 19

500.5

20

299.5

97.0

143.0

All dimensions in [mm]

Flange JIS B2220/ 20K / Sched 40: 1.4404/316L/316


Surface roughness (flange): Ra 3.2 to 6.3 m
DN

di

LK

15

13.9

276.5

95

245

70

4 15

132.5

15

112.5

16.1

116.5

25

24.3

276.5

125

245

90

4 19

132.5

17

112.5

27.2

116.5

40

38.1

273.5

140

320

105

4 19

200

19

120

41.2

113.5

50

49.2

278.5

155

400

120

8 19

250

20

150

52.7

118.5

80

73.7

291.0

200

640

160

8 23

400

22

240

78.1

131.0

100

97

303.0

225

800

185

8 23

500.5

24

299.5

102.3

143.0

All dimensions in [mm]

Flange JIS B2220/ 20K / Sched 80: 1.4404/316L/316


Surface roughness (flange): Ra 3.2 to 6.3 m
DN

di

LK

15

13.9

276.5

95

245

70

4 15

132.5

15

112.5

13.9

116.5

25

24.3

276.5

125

245

90

4 19

132.5

17

112.5

24.3

116.5

40

38.1

273.5

140

320

105

4 19

200

19

120

38.1

113.5

50

49.2

278.5

155

400

120

8 19

250

20

150

49.2

118.5

80

73.7

291.0

200

640

160

8 23

400

22

240

73.7

131.0

100

97

303.0

225

800

185

8 23

500.5

24

299.5

97

143.0

All dimensions in [mm]

Endress+Hauser

25

Proline t-mass 65F, 65I

t-mass 65F: Flange connections ANSI

168 (6.61)

227 (8.94)

160 (6.3)

LK

207 (8.15)

di

T
L

mm (inch)

+1.5 (0.06)
- 2.0 (0.08)

a0005162

Flange ANSI B16.5 / Cl 150 / Sched 40: 1.4404/316L/316


Surface roughness (flange): N9 / 250 inch
DN

di

LK

15

"

13.9

276.4

88.9

245

60.5

4 15.7 132.5

11.2

112.5

15.7

112

25

1"

24.3

276.4

108.0

245

79.2

4 15.7 132.5

14.2

112.5

26.7

112

40

1 "

38.1

273.6

127.0

320

98.6

4 15.7

200

17.5

120

40.9

109

50

2"

49.2

278.4

152.4

400

120.7

4 19.1

250

19.1

150

52.6

114

80

3"

73.7

291.1

190.5

640

152.4

4 19.1

400

23.9

240

78.0

127

100

4"

97

303.0

228.6

800

190.5

8 19.1 500.5

24.5

299.5

102.4

139

All dimensions in [mm]. US units see 31.

Flange ANSI B16.5 / Cl 150 / Sched 80: 1.4404/316L/316


Surface roughness (flange): N9 / 250 inch
DN

di

LK

15

"

13.9

276.4

88.9

245

60.5

4 15.7 132.5

11.2

112.5

13.9

112

25

1"

24.3

276.4

108.0

245

79.2

4 15.7 132.5

14.2

112.5

24.3

112

40

1 "

38.1

273.6

127.0

320

98.6

4 15.7

200

17.5

120

38.1

109

50

2"

49.2

278.4

152.4

400

120.7

4 19.1

250

19.1

150

49.2

114

80

3"

73.7

291.1

190.5

640

152.4

4 19.1

400

23.9

240

73.7

127

100

4"

97

303.0

228.6

800

190.5

8 19.1 500.5

24.5

299.5

97.0

139

All dimensions in [mm]. US units see 31.

26

Endress+Hauser

Proline t-mass 65F, 65I

Flange ANSI B16.5 / Cl 300 / Sched 40: 1.4404/316L/316


Surface roughness (flange): N9 / 250 inch
di

LK

15

DN
"

13.9

276.4

95.2

245

66.5

4 15.7

132.5

14.2

112.5

15.7

112

25

1"

24.3

276.4

124.0

245

88.9

4 19.1

132.5

17.5

112.5

26.7

112

40

1 "

38.1

273.6

155.4

320

114.3

4 22.4

200

20.6

120

40.9

109

50

2"

49.2

278.4

165.1

400

127.0

8 19.1

250

22.4

150

52.6

114

80

3"

73.7

291.1

209.6

640

168.1

8 22.4

400

28.4

240

78.0

127

100

4"

97

303.0

254.0

800

200.2

8 22.4

500.5

31.8

299.5

102.4

139

All dimensions in [mm]. US units see 32.

Flange ANSI B16.5 / Cl 300 / Sched 80: 1.4404/316L/316


Surface roughness (flange): N9 / 250 inch
DN
15

"

di

LK

13.9

276.4

95.2

245

66.5

4 15.7

132.5

14.2

112.5

13.9

112

25

1"

24.3

276.4

124.0

245

88.9

4 19.1

132.5

17.5

112.5

24.3

112

40

1 "

38.1

273.6

155.4

320

114.3

4 22.4

200

20.6

120

38.1

109

50

2"

49.2

278.4

165.1

400

127.0

8 19.1

250

22.4

150

49.2

114

80

3"

73.7

291.1

209.6

640

168.1

8 22.4

400

28.4

240

73.7

127

100

4"

97

303.0

254.0

800

200.2

8 22.4

500.5

31.8

299.5

97.0

139

All dimensions in [mm]. US units see 32.

Endress+Hauser

27

Proline t-mass 65F, 65I

t-mass 65I: Compact insertion version

227 (8.94)

168 (6.61)

55 (2.2)

63 (2.5) 160 (6.3)

207 (8.15)

mm (inch)

G 1 A / 1" MNPT

a0005163

t-mass 65I: Remote sensor housing insertion version

129 (5.1)

79 (3.1)

63(2.5) 102(4.0)
W

LR

55 (2.2)

50 (1.96)

52 (2.0)

mm (inch)

G 1 A / 1" MNPT
a0005159

Length t-mass 65I

LR

235

235.1

252.6

475.6

417.6

335

335.1

352.6

575.6

517.6

435

435.1

452.6

675.6

617.6

608

608.1

625.6

848.6

790.6

All dimensions in [mm]

28

Endress+Hauser

Proline t-mass 65F, 65I

Flow conditioner according to EN (DIN) / JIS / ANSI

B
A
R

D3
D1

D1

D2

D2

a0005166

EN (DIN)
PN 16

PN 40

DN

Type

D1

D2

Weight

Weight

25

83

105

13

2.5

4.5

0.3

40

108

135

17

2.5

7.0

0.7

50

123

150

17

2.5

8.5

1.0

80

158

185

17

2.5

13.0

2.3

100

187

220

22

2.5

17.0

4.1

17.0

4.1

All dimensions in [mm], [kg]

JIS 10K/20K
Sched 40
D1

D2

Sched 80

DN

Type

Weight

Weight

25

87

115

17

2.5

4.5

0.4

4.0

0.4

40

102

130

17

2.5

6.5

0.7

6.0

0.7

50

117

145

17

2.5

8.5

1.2

8.0

1.1

80

157

188

21

2.5

12.5

3.0

12.0

2.8

100

182

214

21

2.5

16.5

5.1

15.5

4.8

All dimensions in [mm], [kg]

ANSI Cl. 150/300


Sched 40
DN

Sched 80

Type

D1

D2

D3

Weight

Weight

85.3

110

17.0

2.5

4.5

0.4

4.5

0.4

1 "

109.5

140

21.5

2.5

6.5

0.9

6.5

0.9

2"

122

150

115.5

19.0

2.5

8.5

1.3

8.5

1.3

80

3"

163

195

144.0

22.0

2.5

12.5

3.2

12.5

3.2

100

4"

179

228

20.5

2.5

16.5

5.3

16.5

5.3

25

1"

40
50

All dimensions in [mm], [kg], US units see 34

Endress+Hauser

29

Proline t-mass 65F, 65I

Hot tap

V0

V2

V1

L2
L5
Q1

Q2

L*

L1
L4

V3

L3
L6

Q3

O
P
A0013815

L* = Dependent on the used version (V1, V2, V3). See dimensions L1, L2, L3.

824 2

262

150

112

254

129

125

110

L3

L4

L5

L6

All dimensions in [mm]

L1

L2
909.5

252.5

45

33.4

All dimensions in [mm]

Q1

Q2

Q3

33.4

123.9

60

123

123

42.2

96

All dimensions in [mm]

Weight
V0*

V1

V2

V3

8.4

2.8

2.4

4.9

* without V1, V2 or V3
Weight in [kg]

30

Endress+Hauser

Proline t-mass 65F, 65I

Process connections in US units


t-mass 65F: Flange connections ANSI

168 (6.61)

227 (8.94)

160 (6.3)

LK

207 (8.15)

di

T
L

mm (inch)

+1.5 (0.06)
- 2.0 (0.08)

a0005162

Flange ANSI B16.5 / Cl 150 / Sched 40: 1.4404/316L/316


Surface roughness (flange): N9 / 250 inch
DN

di

LK

"

0.55

10.9

3.50

9.65

2.38

4 0.62

5.22

0.44

4.43

0.62

4.41

1"

0.96

10.9

4.25

9.65

3.12

4 0.62

5.22

0.56

4.43

1.05

4.41

1 "

1.50

10.8

5.00

12.60

3.88

4 0.62

7.87

0.69

4.72

1.61

4.29

2"

1.94

11.0

6.00

15.75

4.75

4 0.75

9.84

0.75

5.91

2.07

4.49

3"

2.90

11.5

7.50

25.20

6.00

4 0.75

15.75

0.94

9.45

3.07

5.00

4"

3.82

11.9

9.00

31.50

7.50

8 0.75

19.70

0.96

11.79

4.03

5.47

All dimensions in [inch]

Flange ANSI B16.5 / Cl 150 / Sched 80: 1.4404/316L/316


Surface roughness (flange): N9 / 250 inch
DN

di

LK

"

0.55

10.9

3.50

9.65

2.38

4 0.62

5.22

0.44

4.43

0.55

4.41

1"

0.96

10.9

4.25

9.65

3.12

4 0.62

5.22

0.56

4.43

0.96

4.41

1 "

1.50

10.8

5.00

12.6

3.88

4 0.62

7.87

0.69

4.72

1.50

4.29

2"

1.94

11.0

6.00

15.7

4.75

4 0.75

9.84

0.75

5.91

1.94

4.49

3"

2.90

11.5

7.50

25.2

6.00

4 0.75

15.75

0.94

9.45

2.90

5.00

4"

3.82

11.9

9.00

31.5

7.50

8 0.75

19.70

0.96

11.79

3.82

5.47

All dimensions in [inch]

Endress+Hauser

31

Proline t-mass 65F, 65I

Flange ANSI B16.5 / Cl 300 / Sched 40: 1.4404/316L/316


Surface roughness (flange): N9 / 250 inch
DN

di

LK

"

0.55

10.9

3.75

9.65

2.62

4 0.62

5.22

0.56

4.43

0.62

4.41

1"

0.96

10.9

4.88

9.65

3.50

4 0.75

5.22

0.69

4.43

1.05

4.41

1 "

1.50

10.8

6.12

12.6

4.50

4 0.88

7.87

0.81

4.72

1.61

4.29

2"

1.94

11.0

6.50

15.7

5.00

8 0.75

9.84

0.88

5.91

2.07

4.49

3"

2.90

11.5

8.25

25.2

6.62

8 0.88

15.75

1.12

9.45

3.07

5.00

4"

3.82

11.9

10.00

31.5

7.88

8 0.88

19.70

1.25

11.79

4.03

5.47

All dimensions in [inch]

Flange ANSI B16.5 / Cl 300 / Sched 80: 1.4404/316L/316


Surface roughness (flange): N9 / 250 inch
DN

di

LK

"

0.55

10.9

3.75

9.65

2.62

4 0.62

5.22

0.56

4.43

0.55

4.41

1"

0.96

10.9

4.88

9.65

3.50

4 0.75

5.22

0.69

4.43

0.96

4.41

1 "

1.50

10.8

6.12

12.6

4.50

4 0.88

7.87

0.81

4.72

1.50

4.29

2"

1.94

11.0

6.50

15.7

5.00

8 0.75

9.84

0.88

5.91

1.94

4.49

3"

2.90

11.5

8.25

25.2

6.62

8 0.88

15.75

1.12

9.45

2.90

5.00

4"

3.82

11.9

10.00

31.5

7.88

8 0.88

19.70

1.25

11.79

3.82

5.47

All dimensions in [inch]

32

Endress+Hauser

Proline t-mass 65F, 65I

t-mass 65I: Compact insertion version

227 (8.94)

168 (6.61)

55 (2.2)

63 (2.5) 160 (6.3)

207 (8.15)

mm (inch)

G 1 A / 1" MNPT

a0005163

t-mass 65I: Remote sensor housing insertion version

129 (5.1)

79 (3.1)

63(2.5) 102(4.0)
W

LR

55 (2.2)

50 (1.96)

52 (2.0)

mm (inch)

G 1 A / 1" MNPT
a0005159

Length tmass 65I

LR

9"

9.26

9.94

18.72

16.44

13"

13.19

13.88

22.66

20.38

17"

17.13

17.82

26.60

24.31

24"

23.94

24.63

33.41

31.13

All dimensions in [inch]

Endress+Hauser

33

Proline t-mass 65F, 65I

Flow conditioner according to ANSI

B
A
R

D3
D1

D1

D2

D2

a0005166

ANSI Cl. 150/300


Sched 40

Sched 80

DN]

Typ

D1

D2

D3

Weight

Weight

1"

3.36

4.3

0.67

0.2

0.1

0.18

0.8

0.18

0.8

1 "

4.31

5.5

0.85

0.2

0.1

0.26

1.9

0.26

1.9

2"

4.80

5.9

4.55

0.7

0.2

0.1

0.33

2.8

0.33

2.8

3"

6.42

7.7

5.67

0.9

0.2

0.1

0.49

7.0

0.49

7.0

4"

7.05

8.0

0.8

0.2

0.1

0.65

11.7

0.65

11.7

All dimensions in [inch], [lbs]

34

Endress+Hauser

Proline t-mass 65F, 65I

Hot tap

V0

V2

V1

L2
L5
Q1

Q2

L*

L1
L4

V3

L3
L6

Q3

O
P
A0013815

L* = Dependent on the used version (V1, V2, V3). See dimensions L1, L2, L3.

32.44

10.31

5.91

4.41

10.00

5.08

4.92

4.33

L3

L4

L5

L6

All dimensions in [inch]

L1

L2
35.81

9.94

1.77

1.31

All dimensions in [inch]

Q1

Q2

Q3

1.31

4.88

2.36

4.84

4.84

1.66

3.78

All dimensions in [inch]

Weight
V0*

V1

V2

V3

18.5

6.1

5.2

10.8

* without V1, V2 or V3
Weight in [lbs]

Endress+Hauser

35

Proline t-mass 65F, 65I

Weight

Compact version: see table below


Remote version
Sensor: see table below
Wall-mount housing: 5 kg (11 lbs)
Flow conditioner 29, 34
Hot tap 30, 35
Weight (SI units)
t-mass F* / DN

15

25

40

50

80

100

Compact version

7.5

8.0

12.5

12.5

18.7

27.9

Remote version (sensor only)

5.5

6.0

10.5

10.5

16.7

25.9

t-mass I / sensor length [mm]

235

335

435

608

Compact version

6.4

6.6

7.0

7.4

Remote version (sensor only)

4.4

4.6

5.0

5.4

Weight dimensions in [kg].


* For flanged versions, all values (weight) refer to devices with EN/DIN PN 40 flanges.
Weight (US units)
t-mass F* / DN [inch]

"

1"

1"

2"

3"

4"

Compact version

16.5

17.6

27.5

27.5

41.2

61.5

Remote version (sensor only)

12.1

13.2

23.1

23.1

36.7

57.1

t-mass I / sensor length [inch]

9.25"

13.2"

17.1"

24.0"

Compact version

14.1

14.5

15.4

16.3

Remote version (sensor only)

9.7

10.1

11.0

11.9

Weight dimensions in [lbs].


* For flanged versions, all values (weight) refer to devices with Cl 150 flanges.
Materials

Transmitter housing
Compact housing: powder coated die-cast aluminum
Wall-mount housing: powder coated die-cast aluminum
Remote field housing: powder coated die-cast aluminum
Connection housing, sensor (remote version)
Powder coated die-cast aluminum
t-mass F sensor
Sensor body:
DN 15 to 25 (DN " to DN 1"): stainless steel cast CF3M-A351
DN 40 to 100 (DN 1 " to DN 4"): 1.4404 to EN10216-5 and 316/316L to A312
Flanges (process connections):
According to EN 1092-1 (DIN 2501/DIN 2512N) / ANSI B16.5 / JIS B2220
stainless steel 1.4404 to EN 10222-5 and 316L/316 to A182
Transducer body:
1.4404 to EN10272 and 316L to A479
Alloy C22 (2.4602) and UNS N06022 to B574

36

Endress+Hauser

Proline t-mass 65F, 65I

Transducer elements:
1.4404 to EN10217-7 and 316L to A249 or
1.4404 to EN 10216-5 and 316L to A213
Alloy C22 (2.4602) and UNS N06022 to B626
Bushing:
PEEK GF30, PVDF
O-ring seals:
EPDM, Kalrez 6375, Viton FKM
t-mass I sensor
Insertion tube:
Sensor length 235 (9"), 335 (13"), 435 (17"), 608 (24")
1.4404 to EN 10216-5 and 316/316L to A312
Transducer body:
1.4404 to EN10272 and 316L to A479
Alloy C22 (2.4602) and UNS N06022 to B574
Transducer elements:
1.4404 to EN10217-7 and 316L to A249 or
1.4404 to EN 10216-5 and 316L to A213
Alloy C22 (2.4602) and UNS N06022 to B626
Protection guard:
1.4404 to EN 10088-1 and EN 10088-2 + 2B and 316L to A666
Compression fitting:
1.4404 to EN 10272 and 316/316L to A479
Ferrules:
PEEK 450G, PVDF
Bonded seals:
EPDM, Kalrez 6375, Nitrile and 316/316L (outer ring)
Hot tap
Lower tube section:
1.4404 to EN 10272 and 316/316L to A479
Upper tube section:
1.4404 to EN 10216-5 and 316/316L to A312
Ball valve:
CF3M and CF8M
Seal:
PTFE
Material load curves

Flange connections to EN 1092-1 (DIN 2501/DIN 2512N)


Flange material: stainless Steel 1.4404/316L/316
[psi] [bar]

600

40

500

35

PN 40

30
400

25

300

20

200

15

PN 16

10
100
0

5
0
-40 -30 -20 -10 0
-40 -20 0

10 20 30 40 50 60 70 80 90 100 [C]

20 40 60 80 100 120 140 160 180 200 220 [F]


a0005240

Endress+Hauser

37

Proline t-mass 65F, 65I

Flange connections to JIS B2220


Flange material: stainless Steel 1.4404/316L/316
[psi] [bar]
400
25

300

20

200

15

20K

10
100
0

10K

5
0

-40 -30 -20 -10 0


-40 -20 0

10 20 30 40 50 60 70 80 90 100 [C]

20 40 60 80 100 120 140 160 180 200 220 [F]


a0005241

Flange connections to ANSI B16.5


Flange material: stainless Steel 1.4404/316L/316
[psi] [bar]

600

40

500

35

Cl. 300

30
400

25

300

20

200

15

Cl. 150

10
100
0

5
0
-40 -30 -20 -10 0
-40 -20 0

10 20 30 40 50 60 70 80 90 100 [C]

20 40 60 80 100 120 140 160 180 200 220 [F]


A0013825

Process connections

For both the flanged and insertion meters it is possible to have wetted parts degreased for oxygen service.
Contact your Endress+Hauser service representative for further details.
t-mass F:
Flanges according EN 1092-1, JIS B2220 and ANSI B16.5
t-mass I:
G 1A or 1" MNPT thread

38

Endress+Hauser

Proline t-mass 65F, 65I

Human interface
Display elements

Liquid crystal display: illuminated, two lines with 16 characters per line
Selectable display of different measured values and status variables
At ambient temperatures below 20 C (4 F) the readability of the display may be impaired.

Operating elements

Local operation with push buttons (, +, E)


Quick Setup menus for straight forward commissioning

Languages

English, German, French, Spanish, Italian, Dutch, Norwegian, Finnish, Swedish, Portuguese, Polish, Czech

Remote operation

Operation via HART, PROFIBUS PA/DP, FOUNDATION Fieldbus, MODBUS RS485

Certificates and approvals


CE mark

The measuring system is in conformity with the statutory requirements of the EC Directives.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.

C-Tick mark

The measuring system meets the EMC requirements of the Australian Communications and Media Authority
(ACMA).

Ex approval

Information about currently available Ex versions (ATEX, FM, CSA) can be supplied by your Endress+Hauser
representative on request. All explosion protection data are given in a separate documentation which is
available upon request.

Hazardous area
II2GD / Cl. 1 Div. 1

Safe area

II3G / Cl. 1 Div. 2

p cover tight w
Kee ircuits are ali hile
ve
c

over tight wh
i
ep c
Ke ircuits are alive le
c

t unter Spannu
ng
Nich ffnen

vri
pas ou r lappa
Ne sous tension reil
p cover tight w
Kee ircuits are ali hile
ve
c

over tight wh
i
ep c
Ke ircuits are alive le
c

t unter Spannu
ng
Nich ffnen

vr
pas ou ir lapp
Ne sous tension areil

Esc

EX

EX
a0005128-en

Example of t-mass devices in the hazardous area (Example t-mass 65F)

FOUNDATION Fieldbus
certification

The flowmeter has passed all the test procedures implemented and has been certified and registered by the
Fieldbus Foundation. The flowmeter thus meets all the requirements of the specifications listed below:

Endress+Hauser

Certified to FOUNDATION Fieldbus specification


The flowmeter meets all the specifications of the FOUNDATION Fieldbus-H1.
Interoperability Test Kit (ITK), revision status 5.01(Certification on request)
The device can also be operated in conjunction with other-make certified devices.
Physical Layer Conformance Test of the Fieldbus Foundation

39

Proline t-mass 65F, 65I

PROFIBUS DP/PA
certification

The flow device has successfully passed all the test procedures carried out and is certified and registered by the
PNO (PROFIBUS User Organization). The device thus meets all the requirements of the following
specifications:
Certified to PROFIBUS Profile Version 3.0 (device certification number: on request)
The device can also be operated with certified devices of other manufacturers (interoperability)

MODBUS certification

The measuring device meets all the requirements of the MODBUS/TCP conformity and integration test and
has the "MODBUS/TCP Conformance Test Policy, Version 2.0". The measuring device has successfully passed
all the test procedures carried out and is certified by the "MODBUS/TCP Conformance Test Laboratory" of the
University of Michigan.

Pressure measuring device


approval

The measuring devices can be ordered with or without PED (Pressure Equipment Directive). If a device with
PED is required, this must be ordered explicitly. For devices with nominal diameters less than or equal to
DN 25 (1"), this is neither possible nor necessary.
With the identification PED/G1/III on the sensor nameplate, Endress+Hauser confirms conformity with the
"Basic safety requirements" of Appendix I of the Pressure Equipment Directive 97/23/EC.
Devices with this identification (with PED) are suitable for the following types of fluid:
Fluids of Group 1 and 2 with a steam pressure of greater or less than 0.5 bar (7.3 psi)
Unstable gases
Devices without this identification (without PED) are designed and manufactured according to good
engineering practice. They correspond to the requirements of Art. 3, Section 3 of the Pressure Equipment
Directive 97/23/EC. Their application is illustrated in Diagrams 6 to 9 in Appendix II of the Pressure
Equipment Directive 97/23/EC.

Oxygen service

We certify that the wetted parts of the flow sensor have been degreased in accordance with British Oxygen
Company (BOC) specification 0000-N-S-430-00-01 and BS IEC 60877:1999.
After final degreasing there shall be less than 100 milligram/m (0.01 milligram/cm) of oil/grease
contamination on the degreased surface of the component.

Other standards and


guidelines

BS IEC 60877:1999
Procedures for ensuring the cleanliness of industrial-process measurement and control equipment in oxygen
service.
EN 60529
Degrees of protection by housing (IP code)
EN 61010-1
Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory
Procedures.
EN 91/155/EEC
Safety Data Sheets Directive.
IEC/EN 61326
"Emission in accordance with requirements for Class A". Electromagnetic compatibility (EMC- requirements).
ISO 14511
Measurement of fluid flow in closed conduits - Thermal mass flowmeters.
ISO/IEC 17025
General requirements for the competence of testing and calibration laboratories.
NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.
NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with analogue output
signal.
NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics

40

Endress+Hauser

Proline t-mass 65F, 65I

Ordering information
The Endress +Hauser service organization can provide detailed ordering information and information on the
order codes on request.
To ensure each meter is programmed to individual requirements, the following information is essential:
Gas type if not air (composition if more than one gas in % Mole)
Gas pressure
Gas temperature
Line size - internal diameter in metric or US units
20 mA range required
Flow engineering units (kg/h, lb/h etc.)

Accessories
The Endress +Hauser service organization can provide detailed information on request.
Device-specific accessories

Measuring principle-specific
accessories

Accessory

Description

Order code

Mounting boss

Mounting boss for the t-mass insertion version

DK6MB - *

Cable remote version

Connecting cable for the remote version

DK6CA - *

Accessory
Mounting set for
transmitter

Description
Mounting set for remote version. Suitable for:

Hot tap

Flow conditioners
Graphic data manager
Memograph M

Endress+Hauser

Order code
DK6WM - *

Wall mounting
Pipe mounting
Installation in control panel
Mounting set for aluminum field housing:
Suitable for pipe mounting (" to 3")
Mounting set with ball valve and safety chain. Insertion or extraction of Please refer to the
sensor under process pressure (max. 4 bar / 58 psi).
product page of the
Endress+Hauser
Internet page:
Mounting set with ball valve and spindle retractor. Insertion or
www.endress.com
extraction of sensor under process pressure (max. 16 bar (235 psi)).
t-mass F sensor (DN25 to 100, 1"to 4")
t-mass I sensor (DN80 to 300, 3" to 12")
The graphic data manager Memograph M provides information on all
the relevant process variables. Measured values are recorded correctly,
limit values are monitored and measuring points analyzed. The data are
stored in the 256 MB internal memory and also on an SD card or USB
stick.
Memograph M boasts a modular design, intuitive operation and a
comprehensive security concept. The ReadWin 2000 PC software is
part of the standard package and is used for configuring, visualizing and
archiving the data captured.

DK6ST-***
DK7ST-***
RSG40 ************

41

Proline t-mass 65F, 65I

Service-specific accessories

Accessory
Applicator

Description
Order code
Software for selecting and sizing Endress+Hauser measuring devices:
DKA80 - *
Calculation of all the necessary data for identifying the optimum
flowmeter: e.g. nominal diameter, pressure loss, accuracy or process
connections
Graphic illustration of the calculation results
Administration, documentation and access to all project-related data
and parameters over the entire life cycle of a project.

Fieldcheck

FieldCare

Communication-specific
accessories

42

Applicator is available:
Via the Internet: https://wapps.endress.com/applicator
On CD-ROM for local PC installation.
Tester/simulator for testing flowmeters in the field.
When used in conjunction with the "FieldCare" software package, test
results can be imported into a database, printed and used for official
certification.
Contact your Endress+Hauser representative for more information.
FieldCare is Endress+Hauser's FDT based Plant Asset Management
Tool. It can configure all intelligent field devices in your plant and
supports you in managing them. By using status information, it also
provides a simple but effective means of checking their health.

FXA193

The FXA193 service interface connects the device to the PC for


configuration via FieldCare.

Accessory
HART Communicator
Field Xpert SFX 100

Description
Handheld terminal for remote configuration and for obtaining
measured values via the 4 to 20 mA HART current output.
Contact your Endress+Hauser representative for more information.

50098801

Please refer to the


product page of the
Endress+Hauser
Internet page:
www.endress.com
FXA193 *

Order code
SFX100 *******

Endress+Hauser

Proline t-mass 65F, 65I

Documentation

Flow measuring technology (FA005D)


Technical Information (TI069D/06)
Operating Instructions HART (BA111D/06)
Operating Instructions PROFIBUS DP (BA113D/06)
Operating Instructions MODBUS (BA115D/06)
Description of Device Functions HART (BA112D/06)
Description of Device Functions PROFIBUS DP (BA114D/06)
Description of Device Functions MODBUS (BA116D/06)
Supplementary documentation on Ex-ratings: ATEX, FM, CSA, IECEx NEPSI

Registered trademarks
KALREZ and VITON
Registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA
AMS
Registered trademark of Emmerson Process Management, St. Louis, USA
HART
Registered trademark of HART Communication Foundation, Austin, USA
PROFIBUS
Registered trademark of the PROFIBUS User Organisation, Karlsruhe, Germany
FOUNDATION Fieldbus
Registered trademark of the Fieldbus FOUNDATION, Austin, USA
MODBUS
Registered trademark of the MODBUS Organisation
HistoROM, S-DAT, T-DAT, F-CHIP, FieldCare, Field XpertTM, Fieldcheck,
Applicator, t-mass
Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH

Endress+Hauser

43

Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
Tel. +41 61 715 81 00
Fax +41 61 715 25 00
www.endress.com
info@ii.endress.com

TI069D/06/en/06.10
71115124
FM/SGML 6.0

THE
HIGH
PERFORMANCE
COMPANY
PRESENTA LA MS NOVEDOSA
VLVULA DE ALTO RENDIMIENTO

BRAY / McCANNALOK
SERIE 40

ALTO RENDIMIENTO
ALTA PRESIN
ALTA TEMPERATURA
VLVULAS DE
MARIPOSA
21/2- 42 (65 -1050MM)
LOS CUERPOS WAFER
ESTNDAR Y OREJADOS
OFRECEN CIERRE
BIDIRECCIONAL DE CLASE
NORMAL ANSI 150, 300 Y
600 EN PRESIONES DE
OPERACIN
RANGO DE TEMPERATURA:
-20F A 500F
(-120C A 260C)
SERIE 40/41 CLASE ANSI 150
SERIE 42/43 CLASE ANSI 300
SERIE 44/45 CLASE ANSI 600

Bray Controles est orgulloso de


ofrecer la lnea Bray/McCannalok de
alta calidad de vlvulas de mariposa.
Esta lnea de producto est reconocida
como lder por mas de 25 aos de
servicio exitoso en procesos industriales en todo el mundo. La patente del
diseo nico de la Serie 40, recibi el
Premio Valor Chemical Processings
(Industrializacin Qumica) por el
Mejor Producto poco despus de su
introduccin. El diseo sencillo e
innovador ofrece slida confianza, y
limpieza extremadamente fcil en
campo. Pruebas independientes e
internas han comprobado de Bray/
McCannalok su capacidad superior en
vida de servicio, con cierre hermtico
por sobre 100,000 ciclos.
La vlvula de la Serie 40 se puede
automatizar a un bajo costo con los
actuadores neumticos y elctricos de
Bray, que se montan directamente a la
Serie 40 sin necesidad de grandes
soportes o adaptadores.
Cuando se comparan las vlvulas de
compuerta, globo, bola, diafragma y
macho, la vlvula de mariposa de
Bray/McCannaloks es
significantemente mas ligera de peso
y pequea por lo tanto, el tiempo de
instalacin y costos de mantenimiento
se reducen enormemente.
El Alto Rendimiento de la Vlvula
Bray/McCannalok proporciona la mas
alta calidad y el mejor valor disponible
para sus necesidades.

CUERPO (A)
Se ofrecen modelos estndares de wafer de una
sola pieza u orejada bidireccional en clase
ANSI en especificaciones 150,300 o 600
El material del cuerpo es de acero al carbn o
acero inoxidable con una excelente resistencia
a la corrosin. Su cuello extendido permite un
aislamiento de tubera de 2 y un acceso fcil a
los ajustes de los empaques del vstago y
montaje del actuador.
VSTAGO (B)
El vstago altamente resistente de una sola
pieza es de Acero Inoxidable de 17-4 ph. La
punta del vstago es estndar para intercambiar
con los actuadores de Bray.

TOPE DE CARRERA INTERNO (E)


Un tope de carrera interno se ha diseado para
prevenir una sobre carrera del disco,
eliminando un posible dao al asiento.
PALANCA Y PLACA DE
POSICIONAMIENTO (F)
La resistente palanca con liberador de resorte y
placa de posicionamiento ranurada, permite
posicionar al disco de la vlvula en un ngulo
preciso de parada entre las posiciones de
apertura total y cierre total. Ambos, la palanca
y la placa de posicionamiento tienen un
recubrimiento epxico resistente al medio
ambiente y para una suave operacin.

DISCO (C)
El disco de Acero Inoxidable 316 tiene
la tcnica para maximizar el flujo
y minimizar la resistencia,
proporcionando un
alto Cv.

PERNOS (D)
Los pernos tienen
un ajuste preciso
en la perforacin
ensanchada de
los barrenos,
proporcionando
una conexin
positiva de
mxima fuerza
entre el disco de
la vlvula y el
vstago.

B
I
H
G

IS0 9001
Certificate Number: 31938

EMPAQUE DEL VSTAGO AJUSTABLE


El sistema de empaque del vstago presenta
un fcil acceso al ajuste de tuercas de cabeza
hexagonal sin necesidad de quitar el actuador.
El sistema consiste en un anillo prensa estopa
(G) y un retn de prensa estopa (H), pernos,
tuercas de cabeza hexagonal y arandelas de
ajuste (I). Un ligero giro de 1/4 de las tuercas
de cabeza hexagonal usualmente es lo necesario
para ajustar el campo que sea necesario. Ambas
tuercas de cabeza hexagonal deben ser
ajustadas iguales y no demasiado apretadas.

I
H
G
J
N
M
L

SELLO DEL VSTAGO (J)


El sistema de sello del vstago proporciona
constante compresin y excelente resistencia a
la corrosin para un sellado positivo alrededor
del vstago. Los anillos de empaque PTFE
sellan el vstago, y un anillo anti- extrusor de
fibra de carbn sella los empaques. Hay anillos
flexibles de grafito disponibles para
aplicaciones de alta temperatura y son
estndares en vlvulas contra incendio.
Todas las vlvulas Clase 150 y la Clase 300
de 3" 2" tienen un juego de anillos de sello de
empaque del vstago y una tapa posicionadora
del vstago con un sello O-Ring en la base del
cuerpo. Las vlvulas Clase 300 de 14"30" y
toda la Clase 600 tienen sellos de vstago
gemelos en la parte superior y en la base que
nivelan las fuerzas axiales en el vstago y en el
disco bajo todas las condiciones de operacin,
y eliminan cualquier efecto del pistn
en el vstago.
BUJES DEL VSTAGO (K)
Bujes gemelos ajustados en prensa, cada uno
consiste de una capa de Acero Inoxidable 316
con una superficie blindada de recubriemiento
de tejido de vidrio/TFE que soporta el vstago,
El buje del vstago proporciona una excelente
resistencia a la corrosin y distorsin por altas
temperaturas y fuerzas de carga mecnica.

DISEO DEL ASIENTO


EL CORAZN DE LA VLVULA
SERIE 40
El nico, equipo de asiento de dos partes,
consiste en un O-ring activador y resistente (L)
que est totalmente encapsulado por el asiento
RTFE* (M). El equipo est asegurado en
descanso del cuerpo empotrado por un
sujetador de asiento de cara completa (N). Esta
combinacin sencilla, confiable y probada, da
como resultado muchas ventajas
exclusivas, incluyendo:
El O-Ring activador est completamente
aislado de todo contacto con la lnea media
por el asiento RTFE.
Las serraciones en el sujetador del asiento y
cuerpo empotrado aseguran el equipo del
asiento en su lugar. El sujetador de cara
completa est atornillado al cuerpo,
proporcionando fuerza uniforme hacia afuera
para mayor retencin del asiento.
El asiento muy confinado y bien soportado es
es activado por el disco y presin de lnea. A
mas alta presin, mas apretado el sello. En
baja presin y aplicaciones al vaco, el
asiento del activador ofrece un cierre
hermtico y mayor vida de servicio que
muchos otros diseos.
La media del flujo lineal se sella
hermticamente en ambas direcciones.
El asiento es auto ajustable para cambios de
uso y temperatura. El asiento es flexible, y
asegura el mnimo uso del mismo.
El cambio del asiento es extremadamente
fcil, nicamente quite el sujetador del
asiento, gire el disco a la posicin de cierre
y coloque un nuevo equipo de asiento en la
ranura fresada del cuerpo. Este sencillo
procedimiento no perjudicar al disco
o vstago.

VSTAGO
DE DOBLE
COMPENSACIN Y
DISEO DE DISCO
El diseo de doble
compensacin de la serie 40
asegura reduccin en el uso del
asiento y cierre hermtico
bidireccional hacia afuera del
rango completo de presin.
En el punto inicial de
apertura del disco, el disco
compensador produce una
accin semejante a la de la
leva, jalando el disco del
asiento, sin una resistencia
excesiva. Esta accin,
semejante a la de la leva reduce
el uso del asiento y elimina la
deformacin del asiento
cuando el disco est en
posicin de apertura. Cuando
abre, el disco no hace contacto
con el asiento, por lo tanto la
vida de servicio del asiento es
mayor y los torques de
operacin son reducidos.
Mientras la vlvula se cierra, la
accin semejante a la de la leva
convierte el movimiento giratorio del disco a un
movimiento de tipo lineal para empujar con
eficiencia el disco sobre el asiento. La accin de
friccin contra el asiento evita la acumulacin
de material inconveniente de mezcla o
slidos en suspensin.
Los pernos cargan virtualmente cargas
iguales mientras se ancla el disco al vstago,
permitiendo un cierre preciso del disco para un
cierre hermtico consistente y apagado positivo.

Disco en
posicin de
apertura
Cuerpo

Asiento no comprimido
al acercarse el disco

Disco en posicin
de cierre, presin de
lnea aplicada por de
la izquierda.

Disco en posicin
de cierre, sin presin
de lnea

Disco en posicin
de cierre, presin de
lnea aplicada por
la izquierda.

*RTFE es la designacin comn para RPTFE


como la surte Bray.

Asiento

Vstago

Disco en
posicin de
cierre

Despus de una prueba de


mas de 100,00 ciclos a 720
psi, el asiento se conserv en
excelentes condiciones,
proporcionando un cierre
hermtico bidireccional An
despus de mas de 878,000
ciclos a 2 psi, la Serie 40 an
cierra hermticamente en
ambas direcciones.

LAS VLVULAS BRAY/


MCCANNALOK SERIE
40/41 DE ALTO
RENDIMIENTO ESTN
DISPONIBLES A PRUEBA
DE FUEGO, PROBADAS,
CON ASIENTOS
BIDIRECCIONALES A
PRUEBA DE FUEGO, EN
TAMAOS 2 1/2"- 16"
CLASE ANSI 150 Y 300
WAFER Y CUERPOS
OREJADOS.
PARA UN CONTROL
CONFIABLE DE FLUIDOS
INFLAMABLES Y PELIGROSOS
DE PETRLEO, PETROQUMICOS, QUMICOS Y
OTRAS APLICACIONES DE
ALTO RIESGO, LA PRUEBA
DE FUEGO COMBINA UN
RENDIMIENTO SUPERIOR,
MAYOR VIDA DE SERVICIO
Y CUMPLIMIENTO CON
LOS ESTNDARES
MAS DEMANDADOS
MUNDIALMENTE A PRUEBA
DE FUEGOANTES, DURANTE
Y DESPUS DEL FUEGO!
En servicio normal, la
combinacin A PRUEBA DE FUEGO asiento de
metal/flexible y sello hermtico en ambas
direcciones de flujo de lnea media a travs de
presin completa y altos rangos de temperatura.
Al cierre, el disco permanece comprimido contra
el asiento flexible mecnicamente cargado, y est
asegurado en su lugar por un sujetador de cara
completa.La presin de lnea media da fuerza
al sello.
En caso de fuego, si el exceso de calor
destruye los materiales flexibles del asiento, ya
sea total o parcialmente, el asiento proporciona
un respaldo de sello constante de metal metal.
En verdaderas condiciones de fuego, la presin
de lnea, se reduce inmediatamente, y el rea
completa se moja. El resultado por la baja de
presin y rpido enfriamiento da como resultado
el que fallen muchas vlvulas. El diseo A
PRUEBA DE FUEGO no libera la presin en lnea
media al sello, por lo tanto la vlvula ofrece un
rendimiento superior de baja presin que los
diseos de la competencia. El asiento de metal
(INCONEL) funciona como un mecanismo de
resorte, que permite expansin y contraccin sin
romper el contacto con el disco. Adems el
asiento de Inconel ofrece mejor resistencia a la
corrosin y al calor y mayor fuerza que los
asientos de acero inoxidable usados
normalmente.
Bray/McCannalok da una proteccin probada
contra fuego, no solo en el laboratorio, sino
tambin, en dnde cuenta mas, en el campo

*Inconel es una marca registrada de Inco Alloys


International, Inc.

El sistema ajustable de empaques del


sello del vstago est compuesto de grafito
flexible y anillos hechos de grafito. Estos
materiales de los anillos ofrecen mayor
capacidad de sello del vstago. El empaque
puede ser fcilmente ajustado por un ligero
fcil giro de las tuercas de cabeza hexagonal.

OPERACIN DE ASIENTO A

PRUEBA DE FUEGO

El ensamble del asiento en servicio normal hace


contacto del disco con ambos, el asiento de
resilente y el asiento metal metal. Durante y
despus del fuego, cuando el material resilente
ha sido parcial o totalmente destruido, el asiento
de metal metal proporciona un sellado positivo
permaneciendo en contacto constante con el
disco en cualquier direccin del flujo de media.
El Asiento A PRUEBA DE
FUEGO en servicio normal
Asiento Flexible
Bidireccional con
Activador de O-Ring/
Asiento de Inconel

STNDARES DE
PRUEBA DE FUEGO
API 607 4a.. Edicin Certificada.
La PRUEBA DE FUEGO Bray/
McCannalock ha sido
ampliamente probada y rene los
ltimos estndares internacionales
de PRUEBA DE FUEGO desde su
presentacin ha pasado las
pruebas de aplicacin de campo
con excelentes resultados teniendo
rendimiento superior bajo las
condiciones de mayor demanda.

Asiento despus del


fuego, con potencia
hermtica y presin de
lnea media actuando en
el asiento de la izquierda.
(Sujetador del asiento
corriente abajo)

Asiento despus del


fuego, con potencia
hermtica y presin de
lnea media actuando en
el asiento de la derecha.
(Sujetador del asiento
corriente arriba)

La Serie 40 de vlvulas Bray/


McCannolok maneja un amplio
rango de condiciones de medios
tales como, qumicos corrosivos,
agua, gases, cido, alcalinos,
hidrocarbones, adems de muchos
otros fluidos. La lnea estndar
de Bray ha sido diseada
especficamente para cumplir
con la mayora de las aplicaciones.
Cuando las aplicaciones demandan
requerimientos especiales, Bray
ofrece vlvulas y materiales que
cumplan con estas necesidades.
Los servicios y materiales
opcionales incluyen:
VACO
Las vlvulas estndar de la Serie 40 con
asientos de TFE se recomiendan para servicio
de vaco hasta .02 mm Hg de absoluta presin,
o 20 micrones. Para servicio de vaco hasta 1 x
10-3 mm Hg de absoluta presin, o 1 micrn, se
recomiendan vlvulas especialmente
preparadas. Bajo ciertas condiciones, estas
vlvulas sirven bien en un rango de alto vaco
hasta 1 x 10-6 mm Hg en absoluta presin.
VAPOR
Las vlvulas de la Serie 40 estn programadas
para 150 psi (10.3 bar) con vapor saturado a
366 F (185C) nicamente para aplicaciones
de cierre y apertura. El uso del asiento estndar
RTFE se recomienda para estos servicios.
CLORO SECO - GAS O LQUIDO
Materiales especiales as como el equipo
y los procedimientos de prueba se aplican
para asegurar el cierre hermtico en estos
servicios crticos.
CRIOGNICO
Las vlvulas Bray/McCannalok estn
disponibles para servicios de bajas
temperaturas de -320F (-96C). Un vapor
extendido proporciona una barrera trmica
para mantener la temperatura cercana al medio
ambiente alrededor de los sellos de vapor.
Asientos especiales proporcionan el sellado
hermtico necesario mediante baja temperatura
en condiciones de ambiente.

Favor de consultar a su
representante de Bray para
recomendaciones especficas de
acuerdo a sus necesidades.

APROBACIN DE LA
GUARDIA COSTERA
DE EUA
El alto rendimiento de las
Vlvulas Bray McCannalok ha
sido autorizado para aplicaciones
categora A.

MANEJO DE CENIZAS Y ABRASIVOS


Para aplicaciones donde la velocidad del
flujo y la presin diferencial son bajos, se
recomiendan los asientos de RTFE o UHMWPE
y placas de discos electroniquelados. Para
aplicaciones que necesiten una resistencia
mejorada para uso y partculas de mayor dureza,
se recomienda un disco con cara de estelita y
diseo A PRUEBA DE FUEGO
CUSTICA
Los materiales de las vlvulas se seleccionan
para suficientes requerimientos de corrosin.
Para altas concentraciones de sodio o hidrxido
de potasio y altas temperaturas, se recomienda
el acero inoxidable.
CALEFACCIN, VENTILACIN Y
AIRE ACONDICIONADO
Las vlvulas de la Serie 40 se pueden usar
para amortiguacin o balance del flujo de agua,
vlvulas de tope mayor, vlvulas de bloqueo,
vlvulas de estrangulacin y control de bombas
de succin o descarga.
OXGENO
Las vlvulas de la Serie 40 para servicio
crtico de oxgeno gaseoso son especialmente
preparadas, limpiadas, inspeccionadas, armadas
y probadas para asegurar quitar la rebaba,
orillas filosas, tierra, aceite de hidrocarburo o
grasa y otros contaminantes. Cada vlvula se
envuelve individualmente y se sella en
polietileno antes del envo.
GAS AMARGO
Materiales selectos de construccin que renen
los estndares NACE (MR-01-75) permiten una
aplicacin diaria y mxima utilidad en estos
difciles servicios.
SERVICIO EXTREMO
Los cuerpos orejados Bray/McCannalok para
servicio extremo se ofrecen como
completamente estndares en la Clase ANSI en
programacin de 150, 300 y 600

Las vlvulas de la Serie


40 se pueden surtir en
diversos materiales
tanto en el asiento como
en el cuerpo, incluyendo:
Asiento de PTFE y asiento
de UHMWPE con O-Ring
resilente.
O-Rings de fluorosilicn
interno para servicio de cloruro
de metileno.
Empaques A PRUEBA DE FUEGO
de fibra de grafito/carbn o
similar para servicio a prueba
de fuego o de altas
temperatura.
Cuerpos de Hastelloy C para servicio de
cyanide-hidrgeno
Cuerpos de bronce de aluminio para medio
ambientes marinos
Diferente longitud de vstagos para ajustarse
a diferentes reas de control.
20 recortes metlicos de aleacin para
servicio de cido sulfrico
Discos de metal monel para servicio de cloro.
Existen muchos otros materiales, favor de
consultar con la fbrica Bray.

ANSI 150
Tamao de la
vlvula

Serie 40

H* J

L M

ins

mm

2 1/2

65

4.75 1.88 2.28 3.00 4.29 3.81 .63

.43

3.34 2.44 1.56 .38

5/ -18
16

80

5.25 1.88 2.86 3.25 4.54 3.81 .63

.43

3.34 2.44 1.56 .38

5/ -18
16

100 6.72 2.03 3.72 4.38 5.41 3.81 .63

.43

3.34 2.44 1.56 .38

5/ -18
16

125 7.62 2.23 4.83 5.07 5.12 4.32 .75

.51

3.63

1.75 .50

150 8.62 2.23 5.88 5.57 5.62 4.32 .75

.51

3.63

200 10.81 2.40 7.80 6.94 7.12 4.29 .87

.63

3.63

10

250 13.06 2.75 9.78 8.56 8.47 5.50 1.18 .87

12

300 15.42 3.08 11.74 10.18 9.97 5.50 1.18 .87

Informacin del cierre


de la Orejada

BC

N de Roscas
barrenos Unc-2b

Serie Serie
40
41

5/ -11
8

13

6.00

5/ -11
8

15

19

7.50

5/ -11
8

20

28

3/ -16
8

8.50

3/ -10
4

23

39

1.75 .50

3/ -16
8

9.50

3/ -10
4

30

44

1.75 .50

3/ -16
8

11.75

3/ -10
4

43

67

4.28

2.19 .56

1/ -13
2

14.25 12

7/ -9
8

76

106

4.28

2.19 .56

1/ -13
2

17.00 12

7/ -9
8

119

163

14

350 17.27 3.73 12.90 11.95 14.00 7.75 1.38 .39x.39 2.50 5.00 3.13 .69

5/ -11
8

18.75 12

1-8

202

262

16

400 19.50 4.11 14.68 12.94 16.75 10.38 1.97 .39x.47 3.50 7.12 4.38 1.00

3/ -10
4

21.25 16

1-8

291

378

18

450 21.38 4.61 16.97 14.15 19.00 10.38 1.97 .39x.47 3.50 7.12 4.38 1.00

3/ -10
4

22.75 16 11/8-8 382

478

20

500 23.62 5.03 18.86 15.26 21.75 10.38 2.50 .62x.62 5.00 7.12 4.38 1.00

3/ -10
4

25.00 20 11/8-8 640

756

24

600 27.96 6.00 22.73 18.21 24.25 15.38 3.00 .75x.75 4.75 11.25 6.63 1.50

5.50

18

1-8 29.50 20 11/4-8 992 1183

4.50 2.00 11/4-7 36.00 28 11/4-8 1382 1691

36 900 40.25 8.26 35.00 25.28 27.45 12.76 3.75 .88x.62 10.00

5.25 2.50 11/4-7 42.75 32 11/2-8 1850 2405

42 1050 45.00 9.51 40.00 29.00 43.25 19.50 4.50 1.0x.75 6.13

6.00 3.00 11/2-6 49.50 36 11/2-8 3706 4222

30 750 34.50 7.50 29.25 21.12 27.88 19.50 3.50 .88x.62 6.13
L

PESOS

Serie 41

K
F

ANSI 300

Tamao de la
vlvula
J

Serie 42

H* J

L M

BC

*(H= Cuero)

*La rainure de clavette ne concerne que les


robinets de 14" 42" classe 150, de 10"
36" classe 300 et de 8" 14" classe 600.

Serie Serie
42
43

65

4.75 1.88 2.28 3.00 4.29 3.81 .63

.43

3.34 2.44 1.56 .38

5/ -18
16

5.88

3/ -10
4

13

18

80

5.25 1.88 2.86 3.25 4.54 3.81 .63

.43

3.34 2.44 1.56 .38

5/ -18
16

6.63

3/ -10
4

15

19

7.88

3/ -10
4

20

28

9.25

3/ -10
4

28

39

BC

100 6.72 2.03 3.72 4.38 5.41 3.81 .63

.43

3.34 2.44 1.56 .38

5/ -18
16

125 8.25 2.23 4.82 5.07 5.63 4.32 .75

.51

3.63

1.75 .50

3/ -16
8

150 8.88 2.42 5.68 6.25 6.37 4.25 .87

.63

3.63

1.75 .50

3/ -16
8

10.62 12

3/ -10
4

34

61

200 10.94 2.82 7.45 7.55 7.72 5.50 1.18 .87

4.28

2.19 .56

1/ -13
2

13.00 12

7/ -9
8

55

103

10

250 13.26 3.28 9.32 9.36 9.10 5.50 1.38 .39x.39 4.28

2.19 .56

1/ -13
2

15.25 16

1-8

100

162

12

300 15.42 3.62 11.20 10.89 13.00 7.75 1.38 .39x.39 2.50

3.13 .69

5/ -11
8

17.75 16 11/8-8 162

248

14

350 17.75 4.62 12.50 11.95 14.00 7.75 1.97 .39x.47 3.00

3.50 1.41

3/ -10
4

20.25 20 11/8-8 352

410

16

400 20.11 5.35 15.25 18.08 15.70 9.00 2.50 .62x.62 8.00

3.62 1.25

7/ -9
8

22.50 20 11/4-8 538

673

18

450 21.99 5.98 16.25 19.60 16.35 9.76 2.50 .62x.62 8.00

4.00 1.88

7/ -9
8

20

500 24.32 6.35 17.93 21.20 17.51 11.00 3.00 .75x.75 8.00

4.50 2.00

1-8 27.00 24 11/4-8 840 1028

24

600 29.23 7.22 21.56 19.56 24.88 19.50 3.50 .88x.62 6.13

5.00 2.25 11/4-7 32.00 24 11/2-8 1352 1839

30 750 35.37 8.98 28.00 29.70 25.80 15.00 4.50 1.0x.75 10.00

6.00 3.00 11/2-6 39.25 28 13/4-8 1750 2850

36 900 43.75 10.67 33.88 28.00 32.86 12.76 5.00 1.25x.8814.10

6.00 3.00 11/2-6 46.00 32

ins

*(H=Planos)

N de Roscas
barrenos Unc-2b

2 1/2

Tamao de la
vlvula

G
H

Informacin del cierre


de la Orejada

mm

ANSI 600

ins

PESOS

Serie 43

mm

Serie 44

24.75 24

11/4-8

H* J

L M

PESOS

Informacin del cierre


de la Orejada

BC

N de Roscas
barrenos Unc-2b

80

.51

3.63 2.62 1.75 .50

3/ -16
8

100 7.00 2.77 3.80 6.86 7.28 5.00 1.00 .63

3.63 3.06 2.00 .75

3/ -16
8

150 9.76 3.34 5.76 8.40 8.57 5.75 1.25 .87

4.27 3.38 2.25 1.00

1/ -13
2

11.50 12

200 12.00 4.23 7.62 11.40 9.25 7.12 1.75 .39x.39 6.00 4.00 2.81 1.25

816

2-8 3700 4500

Serie 45

645

Serie Serie
44
45

3/ -10
4

24

7/ -9
8

33

41

1-8

80

103

5/ -11
8

13.75 12 11/8-8 157

196

10 250 14.17 4.82 9.75 14.35 11.66 8.50 2.00 .39x.47 6.50 4.62 3.50 1.41

3/ -10
4

17.00 16 11/4-8 265

326

12 300 16.50 5.51 11.38 16.04 13.22 9.00 2.25 .39x.47 6.50 5.00 3.62 1.69

7/ -9
8

19.25 20

375

492

14 350 18.20 6.09 12.50 17.74 14.57 9.75 2.50 .62x.62 8.00 5.25 4.00 1.88

7/ -9
8

20.75 20 13/8-8 496

658

5.75 2.30 2.90 5.90 6.26 4.37 .75

6.62
8.50

11/4-8

28

Las dimensiones estn en pulgadas y los pesos en lbs.

Nota: Para el montaje de los actuadores y los operadores manuales las dimensiones estn nicamente como
referencia. Consulte a la fbrica para el tamao exacto. Bray se reserva el derecho de cambiar las dimensiones
del producto sin previo aviso.

VLVULAS CV COEFICIENTE DE CLASIFICACION POR


DIMENSIONES DE LA VLVULA

ANSI 150

Serie 40 / 41

Temperature
TemperaturaCC
0

Posicin del Disco (grados)


90

80

70

60

50

20

10

160

136

100

78

50

30

16

80

185

178

155

123

87

56

32

14

4.8

100

375

365

315

250

175

115

63

31

10

125

790

675

500

360

238

146

78

41

16

150

1350

1070

750

510

330

218

140

81

35

200

2800

2230

1590

1060

685

456

280

165

65

10

250

4300

3450

2430

1630

1050

700

450

250

100

12

300

6650

5330

3750

2530

1630

1080

700

390

155

14

350

7650

6100

4300

2900

1890

1250

810

450

175

16

400

9800

7860

5510

3700

2420

1530

1020

580

230

18

450 10500

9100

6960

5100

3520

2220

1180

500

170

20

500 13500 11700

8800

6500

4500

2820

1530

640

200

24

600 20000 17100 12800

9570

6640

3880

2200

920

240

30

750 32000 27300 20900 15500 10700

6700

3600

1510

320

36

900 48500 41100 31700 23200 16400 10200

5430

2260

480

42 1050 65000 58000 46100 35000 25000 16000

9000

3700

700

70

60

50

40

30

20

10

2 1/2

65

160

136

100

78

50

30

16

80

185

178

155

123

87

56

32

14

4.8

100

375

365

315

250

175

115

63

31

10

125

790

675

500

360

238

146

78

41

16

150

1000

875

710

530

370

240

138

79

26

200

2000

1720

1360

950

630

405

240

121

47

10

250

2650

2250

1740

1200

780

510

295

150

61

12

300

4000

3400

2500

1690

1100

710

430

220

92

14

350

3900

3300

2400

1570

1000

630

390

220

90

16

400

7800

6540

4550

2970

1840

1160

730

420

180

18

450

9500

8000

6170

4530

3110

1970

1080

440

94

20

500 11000

9570

7300

5400

3720

2330

1250

530

110

24

600 18000 15100 11400

8570

5920

3700

2000

830

180

30

750 29000 24400 18900 13700

8500

6000

3230

1330

290

36

900 45000 38100 29200 21000 14800

9100

4660

1730

380

ANSI 600

Serie 44 / 45

Tamao de la
vlvula

ins mm

Posicin del Disco (grados)


90

80

150

10

100
5
50

-20 0

100

200

300

400

Temperature
TemperaturaFF

500

ANSI 300

Serie 42 / 43

Temperature
TemperaturaCC
0

200

100

250

800
50
700

70

60

50

40

30

20

10

80

185

178

155

123

87

56

32

14

4.8

100

375

365

315

250

175

115

63

31

10

150

1000

875

710

530

370

240

138

79

26

200

1865

1585

1200

880

600

370

195

78

14

10

250

2650

2250

1740

1200

780

510

295

150

61

12

300

4000

3400

2500

1690

1100

710

430

220

92

14

350

3900

3300

2400

1570

1000

630

390

220

90

CV se define como el volumen de agua en U.S.G.P.M. que fluir a travs de una restriccin dada o de la apertura
de la vlvula con una prdida de carga de uno (1) p.s.i. a temperatura ambiente. Los ngulos recomendados de
control son entre 25 - 70. El ngulo preferido para el coeficiente de clasificacin por dimensiones de la vlvula
es 60 - 65 abierto

Pressurepsig
psig
Presin

80

15
200

600

Posicin del Disco (grados)


90

20

250

Serie 42 / 43

Tamao de la
vlvula

ins mm

300

40

500
30
400

300

20

200
10
100

-20 0

100

200

300

400

TemperaturaFF
Temperature

500

ANSI 600

Serie 44 / 45

Temperature
Temperatura C
C
0

200

100

250

1600
100
1400

1200

Presin
Pressurepsig
psig

ANSI 300

250

Pressure
Bar
Presin bar

30

65

Pressurepsig
psig
Presin

40

2 1/2

ins mm

200

100

350

Pressure
Bar
Presin bar

Tamao de la
vlvula

Serie 40 / 41

80

1000
60
800

600

Pressure
Bar
Presin bar

ANSI 150

PRESIN / TEMPERATURA

40

400
20
200

-20 0

100

200

300

400

Temperatura F
F
Temperature

500

Cuerpos de Acero al Carbn


Cuerpos de Acero Inoxidable
Asientos de RTFE Y PTFE
Asientos nicamente de RTFE

ANSI 150
Tamao
de la
vlvula

Serie 40 / 41

Estndar

Sistema de Presin P (PSIG)


Menor a 150

150 200

200 250

250 285

Ins

Torque

*Flujo

Torque

*Flujo

Torque

*Flujo

Torque

*Flujo

2 1/2
3
4
5
6
8
10
12
14
16
18
20
24
30
36
42

200
220
320
650
810
1500
2800
4100
6300
9100
14000
18000
29000
47000
64000
83000

350
350
350
360
400
800
1200
2000
2500
3500
5300
6500
7600
10000
16000
25000

240
260
370
800
960
1720
3300
5000
7400
11300
17000
21300
34600
53700
81000
105000

360
360
360
400
480
880
1300
2200
2800
4200
5700
6900
8100
11900
19700
30000

280
300
420
940
1100
1950
3760
5900
8500
13500
20000
24700
40100
67700
98000
127000

390
390
390
450
550
960
1400
2400
3100
4900
6100
7300
8600
13800
23400
35000

300
320
460
1040
1200
2100
4100
6500
9500
15000
22000
27000
44000
75000
110000
143000

400
400
400
500
600
1000
1500
2500
3400
5200
6300
7500
8800
15000
26000
40000

ANSI 150
Po.
Ins

Serie 40 / 41

Con Asientos a Prueba de Fuego

Torque

*Flujo

Torque

*Flujo

Torque

*Flujo

Torque

*Flujo

2 1/2 720
3
780
4
900
5
1500
6
1750
8
2800
10 4200
12 6900
14 17000
16 18000

1000
1000
1200
1300
1400
1800
2500
4000
4600
6000

770
830
980
1630
1880
2950
4530
7350
18100
19850

1040
1040
1310
1410
1510
1950
2760
4300
5050
6800

810
870
1050
1750
2000
3100
4860
7790
19200
21700

1080
1080
1420
1520
1620
2100
3020
4600
5500
7600

840
900
1100
1850
2100
3200
5100
8100
20000
23000

1100
1100
1500
1600
1700
2200
3200
4800
5800
8200

ANSI 300
Tamao
de la
vlvula

Serie 42 / 43

150 350

*Estos son los porcentajes de fluido


en U.S.G.P.M. antes de que los
torques dinamicos sean
considerados para determinar que
torque es mayor (cierre-final/
apertura-inicial o el dinamico).
El equivalente de agua es utilizado.
Para otros fluidos hay que dividir los
flujos que se dan entre SG donde
SG=gravedad especifica.
Para agua SG=1.
NOTA: Los torques de cierre-final/
apertura-inicial que aparecen aqui
tienen un factor razonable de
seguridad para cubrir condiciones
severas. Para aplicaciones noseveras y con el reten del asiento
montado hacia el flujo (upstream),
estos torques pueden reducirse hasta
un 30%. Para fluidos con solidos o
contenido abrasivo, el torque puede
incrementar. Por favor consultar a
fabrica.

ANSI 600

Estndar

Sistema de Presin P (PSIG)


Menor a 150

TORQUES DE CIERREFINAL/APERTURA-INICIAL
(LB.-INS.)

350 550

550 740

Tamao
de la
vlvula

Serie 44 / 45

Sistema de Presin P (PSIG)


Menor a 150

150 600

Ins

Torque

*Flujo

Torque

*Flujo

Torque

*Flujo

Torque

*Flujo

Ins

Torque

*Flujo

Torque

*Flujo

2 1/2
3
4
5
6
8
10
12
14
16
18
20
24
30
36

200
220
320
650
1000
1850
3300
5000
8600
14000
18000
24000
38000
83000
119000

350
350
350
360
390
780
1100
2000
2200
3500
3800
4500
7200
7800
10000

360
380
530
1250
1650
3100
5500
8300
13400
21500
27000
36700
57000
127000
180000

460
460
470
500
640
920
1600
2700
3000
4200
5200
6200
9200
12500
18000

510
530
730
1850
2300
4300
7600
11500
18300
29000
36100
49300
76700
172000
240000

550
550
580
630
880
1060
2100
3400
3800
4900
6600
7900
11200
17200
28000

670
690
1000
2550
3000
5300
10000
15000
22000
38000
45000
61000
95000
210000
290000

640
640
680
820
1100
1200
2600
4000
4500
5600
7900
9500
13000
21700
34000

3
4
6
8
10
12
14

480
960
1700
4100
8300
11800
15000

760
1100
1400
3100
3400
4100
4200

870
1600
3200
7200
14000
12000
24000

850
1200
1500
3300
3600
4300
4500

ANSI 300
Ins

Serie 42 / 43

Con Asientos a Prueba de Fuego

Torque

*Flujo

Torque

*Flujo

Torque

*Flujo

Torque

*Flujo

2 1/2 720
3
800
4
900
5
1500
6
2100
8
3150
10 7300
12 11000
14 19000
16 42000

1000
1000
1200
1500
1800
2400
3200
4000
4100
7800

860
950
1200
2300
2900
4300
10200
14700
24000
48200

1100
1100
1300
1650
2000
2500
3340
4240
4370
8200

1010
1100
1500
3100
3700
5500
13000
18400
26000
54400

1200
1200
1400
1800
2200
2600
3480
4480
4640
8600

1100
1200
1700
3600
4300
6200
15000
21000
28000
57000

1300
1300
1500
1850
2400
2700
3600
4700
4900
9000

Tamao
de la
vlvula

Sistema de Presin P (PSIG)


600 1050

1050 1480

Ins

Torque

*Flujo

Torque

*Flujo

3
4
6
8
10
12
14

1200
2100
4600
10100
18000
26000
33000

1100
1400
1900
3500
3800
4500
4500

1450
2700
5800
14000
24000
30000
43000

1100
1400
2100
3500
4300
4500
4800

Nombre del artculo


1 Cuerpo

Material
Acero Inoxidable, ASTM A351 GR CF8M
Acero al carbn, ASTM A216 GR WCB/A516 GR 70
2 Disco
Acero Inoxidable, ASTM A351 GR CF8M-Standard
con electro-nickel-pulido en el filo del disco-Aprueba de Fuego
3 Vstago
17-4 PH SS, ASTM A564- Tipo 630
4 Perno (2)
17-4 PH SS, ASTM A564- Tipo 630*
Acero Inoxidable 316**, ASTM 276 tipo 316
5 Separador de Disco (2) Acero Inoxidable 316. ASTM 276 Tipo 316
6 Ensamble de buje (2) Acero Inoxidable 316 con TFE y recubrimiento de tejido de vidrio
7 Anillo prensa estopa
Acero Inoxidable 316, ASTM 276 tipo 316
8 Sello del Vstago
Anillos de PTFE mas un anillo de Fibra de Carbono - Valvula Standard
Anillos de Grafito Flexible Vlvula a Prueba de Fuego
9 Arandela de empuje
Acero Inoxidable 316, ASTM 276 tipo 316
10 Retn Prensa Estopa
Acero Inoxidable 304, ASTM A351 CF8M
Acero al carbn, ASTM A216 GR WCB/A516 GR 70 Acero
Inoxidable 316 ASTM A193-B8M
11 Tuerca de Ajuste (2) Acero Inoxidable 316 ASTM A193-B8M
12 Arandela de ajuste (2) Acero Inoxidable 18-8
13 Tuerca Hexagonal (2) Acero Inoxidable 18-8
14 Asiento
RFTFE^ con O-Ring de elastmero de silicn
PTFE con O-Ring de elastmero de silicn
15 Retn de Asiento
Acero Inoxidable, ASTM A351 CF8M/A276-316
Acero al Carbon, ASTM A516 GR 70
16 Tornillo Alen (8)
Acero Inoxidable 18-8
Aleacin de acero
17 O-Ring - Empaque
PTFE - Standard Valve
Grafito Flexible Vlvula a Prueba de Fuego
18 Tapa posicionadora
Acero Inoxidable 316 ASTM 276 Tipo 316
Acero al carbn, fosfatizado
19 Asiento Metlico
Inconel 718, ASTM B670
20 Gasket
Grafito flexible

Vista Detallada
Serie 40
13
12
3
10
11
7
8
4
9
6

No se muestran: Arandela Bellville y Arandela Grounding: Acero Inoxidable 18-8,


para vlvulas Clase 150 14 42, para vlvulas Clase 300 14-36 y para todas las
vlvulas Clase 600.

* Disponible para vlvulas Clase 150 tamao 2 /2" 12", para vlvulas Clase 300 y para vlvulas Clase 600.
** Disponible para vlvulas Clase 150 tamao 14"-42", para vlvulas Clase 300 de 14" 36"
y para vlvulas Clase 600 de 14".
(4) Para vlvulas tamao 14" y vlvulas mayores.
^ Bray substituye RTFE por RPTFE (polietrafluoretileno reforzado).
No aplicable para valvulas de tamanos 21/2, 3" y 4" en Clase 150 y Clase 300.
nicamente para vlvulas a PRUEBA DE FUEGO.

5
2

14

15

Hay otros materiales disponibles,


favor de consultar a la fbrica para
su aplicacin especfica.

5
6
17

Vlvula a PRUEBA

DE FUEGO

18

20

19

16

Tipo Macho

SERIE 40

Globo

ADICIONALMENTE A LAS
EXCELENTES CARACTERSTICAS
DE LA SERIE 40 ESTAS
VLVULAS DE MARIPOSA DE
ALTO RENDIMIENTO OFRECEN
VENTAJAS SUPERIORES SOBRE
OTRAS VLVULAS.
Cuando son acopladas contra vlvulas
macho, globo, de compuerta, bola y
diafragma, de programacin comparable, los
requerimientos del peso reducido y tamao

SERIE 40

De Compuerta

compacto de la Serie 40 es realmente


notable. El ahorro en costo de instalacin
y mantenimiento es substancial.
Los requerimientos de torque de las
Vlvulas de Mariposa de Alto
Rendimiento de la Serie 40 tambin son
significativamente menores. Por ejemplo,
Una Vlvula de 8" Clase 150 de la Serie
40 pesa 45 lbs. y tiene un torque mximo
de 1,500 in/lbs. Las vlvulas comparables
de clavija pesan 319 lbs. con un torque de
1,500 in/lbs. y las vlvulas de baln pesan

SERIE 40

158 lbs. con un torque de 6,400 in/lbs una


vlvula de entrada con peso nominal
comparable de 310 lbs. y que requiera una
unidad lineal para actuacin. Por lo tanto,
las Vlvulas de Mariposa de la Serie 40
necesitan un actuador mucho menor que
otras vlvulas.
Economa eficiencia y rendimiento
superior comprobado determinan a Bray
McCannaalok como la mejor solucin
para aplicaciones que exijan alta presin.

EL MONTAJE DIRECTO DE
ACTUADORES NEUMTICOS Y
ELCTRICOS BRAY DE ALTO
TORQUE COMPACTO
PROPORCIONAN UN BAJO COSTO
DE AUTOMATIZACIN PARA
SERVICIOS DE CONTROL DE
APERTURA Y CIERRE.
Las vlvulas de la Serie 40 pueden ser
automatizadas a un bajo costo con los actuadores
neumticos y elctricos de Bray. Estos
actuadores se complementan completamente
con Bray McCannalok y se montan directamente
sin necesidad de grandes soportes o adaptadores.
Bray ha diseado la lnea mas avanzada y de mas
alta calidad de actuadores y la lnea Bray de
accesorios disponibles en el mercado.
A la izquierda, un actuador neumtico de la Serie 90
montado en una vlvula de 6" de la Serie 40. A la
derecha, un actuador elctrico de la Serie 70 se muestra
montado en una vlvula de 6" de la Serie 40. muestra.
montado en una vlvula de 6" de la Serie 40

DISTRIBUIDOR

Certificate Number: 31938

Todas las instrucciones, informacin tcnica, y


recomendaciones en este folleto son nicamente para
uso general. Consulte a los representantes de Bray o
a la fbrica para requerimientos especiales y
seleccin de material para su propsito de aplicacin.
El derecho de cambiar o modificar el producto o el
diseo del producto sin previo aviso est reservado.
producto o el diseo del producto sin previo aviso

CONTROLES

de MEXICO

Filial de BRAY INTERNATIONAL, Inc.


Volcan Popocatepetl 5431-B El Colli
Zappopan, Jalisco 45070 Mexico
52(3) 628-5454 Fax: 52(3) 628-7167 www.bray.com
2000 Bray International. Derechos reservados
B-1023

11/00

The
High
Performance
Company

ACTUADOR NEUMTICO

SERIE 92/93 Cremallera y Pin


Doble Accin y Cabecera de Retorno

SERIE 92/93

El estilo, fuerza, consistencia y


sencillez del diseo han sido
combinados para producir el mejor
actuador giratorio en el mercado
actual. Bray Controls introduce esta
lnea ms nueva de actuadores
neumticos de alto rendimiento y de
la ms alta calidad, la Serie 92/93.
La excelencia en ingeniera y
precisin en la manufactura han
producido una lnea de producto
modular con requerimientos de
espacio total reducido y ahorros
econmicos. Adems, todos los
Brayline Accesories (Accesorios
Brayline), son totalmente modulares
y se montan directamente en el
actuador proporcionando
flexibilidad y eficiencia a un costo reducido.
Los actuadores de la Serie Bray 92/93 son de
cremallera y pin, actuadores de pistones
opuestos disponibles en dos versiones: de doble
accin para rotacin de 90, 135 y 180, y con
cabecera de retorno para rotacin de 90. Su uso
ideal es accionamiento de vlvulas de mariposa,
bola o de clavija, pero pueden ser aplicados en
donde se requiera una rotacin de 90, 135 y
180. Con rotacin de soportes de acetal de baja
friccin, las unidades Bray estn bien adaptadas
para manejar cargas compensadas al engrane y
montaje del vstago de salida.
La Serie Bray 92/93 fue diseada
bsicamente para operaciones neumticas hasta
de un mximo de presin de 140 psig (10 Bar) y
para rangos de temperatura de -40 F (-40 C) a
+200 F (+95 C). Para aplicaciones de
temperaturas ms altas o ms bajas, consulte a la
fbrica.

de abierta o cerrada y es fcilmente removible


para la FUNCIN DE SOBREPASO
(OPERACIN) MANUAL del actuador.
El CUERPO (G) es de aluminio extrudo con
un recubrimiento anodizado para proteccin de
corrosin. Las TAPAS DE LOS EXTREMOS
(H) tienen un recubrimiento de polister para
resistencia qumica. Este recubrimiento es
resistente a cidos acuosos diluidos, sales,
hidrocarbonos alifticos, detergentes, solventes
de petrleo, grasas y aceites.
Los tornillos de ajuste del TOPE DE
CARRERA (I) limitan el movimiento del
actuador a grados especficos de rotacin, en
direcciones tanto abiertas como cerradas. Los
PISTONES (J) son de aluminio fundido
inyectado.
Los dos PUERTOS NEUMTICOS DE
ALIMENTACIN (K) son de 1/8" NPT en los
actuadores de tamao 48. Los otros tamaos
tienen puertos de 1/4" NPT. La interfase
NAMUR es estndar en todos los tamaos de
actuadores.
Todos los actuadores de la Serie Bray 92/93
tienen los soportes y las guas permanentemente
lubricados embalados de fbrica. No es necesaria
una lubricacin posterior bajo condiciones
normales de operacin. Todos los empaques,
incluyendo los EMPAQUES DE LOS
PISTONES (L), son Buna-N O-Rings de
lubricacin permanente.

Todas las unidades de doble accin y


cabecera de retorno son apropiadas tanto para
aplicaciones de apertura y cierre (on-off) como
de regulacin. Actuadores que puedan ser
accionados por otros medios tales como aceite
hidrulico o agua tambin estn disponibles
como opcin.
La Serie 92/93 es completamente cerrada e
independiente. Las mltiples caractersticas
minimizan el mantenimiento y proporcionan un
desensamble y ensamble seguro y sencillo.
El CONDUCTO INTEGRAL (A) reduce el
costo de tubera externa que tambin es daada
fcilmente. Las GUAS DE PISTN DE
ACETAL nicas, lubricadas (B) y ANILLOS
(C). Ambas tienen un coeficiente muy bajo de
friccin y absorben el golpe lateral de los
pistones. Las paredes cilndricas del pistn en el
cuerpo estn esmeriladas en un terminado muy
fino para reducir el coeficiente total de friccin.
Estas caractersticas aumentan la vida del
actuador y hacen de la serie 92/93 de actuadores
una de las ms eficientes en el mercado.
Los SOPORTES DE SALIDA DEL
VSTAGO (D) en la parte superior e inferior
del pin estn hechos de acetal de baja friccin.
El VSTAGO DE SALIDA y PIN DE
ENGRANE (E) son de una pieza, fabricado en
aleacin de acero reforzado y recubrimiento de
zinc para proteccin de corrosin.
El INDICADOR DE POSICIN DEL
VSTAGO (F) muestra claramente la posicin

B
E

J
A

L
D
K

INGENIERA

Aviso Especial: Los actuadores tamao 210 y 255 tienen

Doble Accin/
Cabecera de Retorno
Q

DIMENSIONES DE LA SERIE 92/93


TAMAO
48
63
83
92

#10 32UNF
.28 de Profundidad
4 Lugares

VISTA SUPERIOR

E
M

1/4

1/4

1/4

1/4

1/4

1.42
F 03

1.97
F 05

1.97
F 05

1.97
F 05

2.76
F 07

2.76
F 07

4.92
F 12

6.50
F 16

1.97
F 05

2.76
F 07

2.76
F 07

2.76
F 07

4.92
F 12

4.92
F 12

4.92
F 12

6.50
F 16

7.87x4.72
Rect.

.55

.55

.75

.75

1.18

1.18

1.18

1.97

2.50

.40

.40

.51

.51

.87

.87

.87

.47

.62

3.88

4.53

5.43

5.78

7.28

8.09

9.36

11.45

13.35

B
C
D
E
F
G

5.58

7.40

8.59

11.90

12.31

15.54

17.80

26.70

1/4-20
x .32

1/4-20
x .32

1/4-20
x .32

5/16-18
x .46

5/16-18
x .46

1/2-13
x .78

M16x2
x 28mm

1/4-20
x .25

5/16-18
x .40

5/16-18
x .40

5/16-18
x .40

1/2-13
x .69

1/2-13
x .69

1/2-13
x .75

5/8-11
x 1.11

M16x2
x 28mm
1.12

.38

.38

.50

.50

1.12

1.12

1.12

1.12

1.30

1.38

1.46

1.46

2.20

2.20

2.20

2.76

4.25

2.50

3.46

4.27

4.61

5.52

6.32

7.80

10.04

11.89

1.60

1.72

2.02

2.18

2.53

2.72

3.07

4.25

4.75

2.19

3.11

3.83

4.17

4.91

5.44

6.82

8.83

10.75

1.58

1.58

1.58

1.58

1.58

1.58

2.56

2.56

2.56

1.25

.89

.89

.94

1.36

1.36

1.39

1.44

1.50

1.10**

.79

.79

.79

.79

.79

1.18

1.18

1.18

.47

.47

.47

.47

.47

.47

.75

.75

.75

doble accin del tamao 48 se encuentra disponible como opcin con tapas de los extremos planas con una
dimensin F de 4.00
ISO F significa brida de montaje patrn de perforacin.
* Dimensiones para el Tamao 160A se encuentran en la tabla. El Tamao 160B (versin vstago con llave) tiene una
dimensin C de 1.38 y D de .39.
Dimensiones para el Tamao 255A se encuentran en la tabla. El Tamao 255B tiene una dimensin C de 3.00 y D de .75.
** El Tamao 48 tiene una dimensin T de .79 con el uso de una placa superior NAMUR.

N
VISTA DEL FRENTE
G

J
L
M
N
P
Q
S
T
U

4.00
10-32
x .23

Nota: Los actuadores de Doble Accin y Cabecera de Retorno tienen las mismas dimensiones totales. La unidad de

Velocidades del Actuador


48 63 83
TAMAO
Movimiento
de Apertura/
Movimiento
de Cierre

B
F

1/4

Pesos del Actuador


48 63
TAMAO

SALIDA NAMUR
PARTE SUPERIOR DEL VSTAGO
J

1/4

1/4

92
1/4

118 127 160 210 255


1/2

.157

83

2 3/4

92

118 127 160 210 255

Doble Accin

1.8

3.4

6.1

8.4

16.4

20.9

38.1

65.0 144.0

Cabecera de Retorno

2.4

4.1

7.9

10.8

21.7

27.3

52.6

95.3 192.6

Los pesos son en libras. Los pesos de las unidades de Cabecera de Retorno son con un juego
completo de resortes por pistn.

Volmenes del Actuador (ins3)


TAMAO
48 63 83 92

M6 x 1
12mm de Profundidad

118 127 160 210 255

En Sentido Contrario

5.7

9.6

24.8

34.8

73.8

En Sentido de las
Manecillas del Reloj

96.7 187.5 360.0 750.0

4.8

13.4 32.6

45.9

95.5 130.8 259.6 450.0 900.0

En sentido contrario:Volumen de aire en pulgadas cbicas requerido para separar los


pistones, recorrido completo.
En sentido de las manecillas del reloj:Volumen de aire en pulgadas cbicas requerido para
unir los pistones, recorrido completo.

MONTAJE DEL
SOLENOIDE NAMUR
.47 Typ.
.63

1.58
Q

.63

.94

1/2

Los tiempos estn en segundos, a 80 PSIG con 6 pies de tubera, dimetro interno de
aproximadamente 1/4.

VISTA DEL FONDO


ACTUADOR ISO 5211
PATRN DE MONTAJE

.16

255

1/4

(AIRE) NPT

210

1/4

(UNC)

VISTA LATERAL

160*

1/4

(UNC)

127

1/8

ISO "F"

.59

118

AIRE
NPT

ISO "F"
=
=

tope de carrera en las tapas de los extremos, no topes de


carrera de doble direccin. Favor de consultar con la fbrica
la fecha en que estarn disponibles los topes de carrera de
doble direccin para los actuadores de tamao S92/93.

1.58
=

#10 32UNF
(M5 x .8 en Tamao 255)
4 Lugares

=
=

DETALLE PARA TALADRAR


EL VSTAGO
TAMAO 210 & 255

Placa para montar


opcional para VDI/VDE
3845 (NAMUR)
Accesorios Estndar

.39

.59
Tamao 48

#10 32UNF
.28 de Profundidad
4 Lugares

TORQUE

Inicio

CURVA DE TORQUE INFORMACIN DEL TORQUE DEL ACTUADOR SERIE 92


DE DOBLE ACCIN Operando neumticamente con doble accin

CURVAS DE TORQUE
DE SIMPLE ACCIN

Serie 92 (Aire a Aire)

Serie 93 (Cabecera de Retorno)

Salida de Torque (Lbs.-Ins.)

Fin

El Actuador de la Serie 92
tiene una salida constante
de torque a travs del
recorrido de inicio a fin,
en rotacin en sentido de
las manecillas del reloj y
en sentido contrario.

Suministro de Presin de Aire (PSIG)

Tamao del
Actuador

40

60

80

100

120

48
63
83
92
118
127
160
210
255

75
145
351
493
1058
1410
2797
5783
14211

113
221
536
753
1615
2152
4270
8826
21691

150
297
721
1013
2171
2894
5742
11870
29171

188
373
906
1272
2728
3636
7214
14914
36650

225
449
1091
1532
3285
4378
8687
17957
44130

Inicio

Fin
En Sentido Contrario
(Presin del Aire)
Inicio

Fin
En Sentido de las Manecillas
del Reloj (Presin del Resorte)

INFORMACIN DEL TORQUE DEL ACTUADOR SERIE 93


Operando con Aire, con Cabecera de Retorno, Salida de Torque (Lbs. - Ins.)
No. de
Tamao del Resortes
por
40
Actuador
Pistn Inicio
Fin
1
51
32
2/1
39
10
2
48
3/2
3
2
91
65
3
64
27
4
63
5
6
2
210
167
3
156
76
4
83
5
6
2
310
232
3
218
101
4
92
5
6
2
692
469
3
509
174
4
118
5
6
2
880
465
3
4
127
5
6
2
1819
1118
3
1399
349
4
160
5
6
2
3833
2508
3
2859
868
4
210
5
6
2
9487
6747
3
7125
3015
4
255
5
6

Suministro de Presin de Aire (PSIG)

60

80

100

120

Presin del Resorte

Inicio

Fin

Inicio

Fin

Inicio

Fin

Inicio

Fin

Inicio

Fin

89
77
64
52

70
48
27
5

167
140
113
86

141
103
65
27

395
341
281
220

352
261
176
97

570
478
386
294

492
361
231
94

1249
1066
883
700

1026
731
437
142

1622
1357
1094

1207
733
261

3292
2872
2452
2030

2591
1822
1123
353

6876
5902
4930
3949

5551
3911
2275
638

16967
14605
12243
9880

14227
10495
6762
3030

126
114
101
89
77
243
216
189
162
135
580
526
466
405
369
830
738
646
554
462
1805
1622
1439
1256
1073
2364
2099
1836
1568
1302
4764
4344
3924
3502
3154
9920
8946
7974
6993
6022
24447
22085
19723
17360
14998

107
85
64
42
21
217
179
141
103
65
537
446
361
282
185
752
621
491
354
229
1582
1287
993
698
404
1949
1475
1003
529
57
4063
3294
2595
1825
1196
8595
6955
5319
3682
2031
21707
17975
14242
10510
6778

164
152
139
127
115
319
292
265
238
211
765
711
651
590
554
1089
997
905
813
721
2362
2179
1996
1813
1630
3106
2841
2578
2310
2044
6236
5816
5396
4974
4626
12964
11990
11018
10037
9066
31926
29564
27202
24839
22477

145
123
102
80
59
293
255
217
179
141
722
631
546
467
370
1011
880
750
613
488
2139
1844
1550
1255
961
2691
2217
1745
1271
799
5535
4766
4067
3297
2668
11639
9999
8363
6726
5075
29186
25454
21721
17989
14257

201
189
176
164
152
395
368
341
314
287
950
896
836
775
739
1349
1257
1165
1073
981
2919
2736
2553
2370
2187
3848
3583
3320
3052
2786
7709
7289
6869
6447
6099
16007
15033
14061
13080
12109
39406
37044
34682
32319
29957

182
160
139
117
96
369
331
293
255
217
907
816
731
652
555
1271
1140
1010
873
748
2696
2401
2107
1812
1518
3433
2959
2487
2013
1541
7008
6239
5540
4770
4141
14682
13042
11406
9769
8118
36666
32934
29201
25469
21737

43
65
86
108
129
80
118
156
194
232
184
275
360
439
536
261
392
522
659
784
589
884
1178
1473
1767
945
1419
1891
2365
2837
1679
2448
3147
3917
4546
3275
4915
6551
8188
9839
7464
11196
14929
18661
22393

24
36
49
61
73
54
81
108
135
162
141
195
255
316
352
183
275
367
459
551
366
549
732
915
1098
530
795
1058
1326
1592
978
1398
1818
2240
2588
1950
2924
3896
4877
5848
4724
7086
9448
11811
14173

ACCESORIOS

TOPES DE CARRERA Dos tornillos de


ajuste independientes estn localizadas en el
centro del vstago de salida para limitar con
precisin la carrera del actuador a grados
especficos de rotacin. El tope de carrera
permite un ajuste bidireccional del
movimiento del actuador tanto en posiciones
abiertas como en cerradas.

CABECERA DE RETORNO Los modelos de


cabecera de retorno de la Serie Bray 93 utilizan
un sistema nico de cartuchos. El actuador fue
diseado para ahorrar tanto espacio como costo.
La longitud del armazn de la unidad de
cabecera de retorno es la misma que la de la
unidad de doble accin. Convertir la actuacin
de doble accin a cabecera de retorno es
solamente el hecho de quitar las tapas de los
extremos y colocar los cartuchos especiales de
resortes. El actuador puede ser desensamblado y
ensamblado sin equipo voluminoso o sin peligro
para el instalador debido a la desconexin de los
resortes. Los servicios de 40, 60, 80 y 100 psi
son estndar, con rangos opcionales disponibles.

MONTAJE DIRECTO Los actuadores Bray


cumplen con las dimensiones de ISO 5211 y
se montan directamente a las vlvulas Bray
sin utilizar accesorios de montaje externos. La
instalacin de campo es sencilla, se minimiza
la desalineacin y se reduce la concentracin
de contaminacin entre la vlvula y el
actuador. Bray puede proporcionar los
accesorios de montaje para montar los
actuadores a otros aparatos que requieran una
rotacin de 90 a 180.

VLVULA DE SOLENOIDE
SERIE 63 DE 3 VAS Y DE
4 VAS Para la operacin elctrica
de funciones de apertura y cierre (onoff) del actuador neumtico, los
solenoides de la Serie Bray 63 se
montan directamente en el actuador
por la interfase NAMUR. La vlvula
de control de embobinado operada
por el piloto se convierte de 3-Vas
(3/2) a 4-Vas (5/2). Tanto las
armazones a prueba de agua (NEMA
4, 4X) y a prueba de explosin
(NEMA 4,4X, 7.9) son estndares.
Las conexiones NPT e IP65 DIN son
ofrecidas en carretes tanto sencillos como
dules. La conexin del suministro del aire es
de 1/4" NPT y la conexin elctrica es de 1/2"
NPT. Un tornillo de sobrepaso (operacin)
manual est localizado en la parte superior del
cuerpo de la vlvula. Tambin estn disponibles
armazones de Acero Inoxidable, solenoides
digitales Bus y un control de velocidad de la
Serie 55 que permite un control independiente
en ambas direcciones de la carrera del actuador.

MONITOR DE CONTROL DE LA
VLVULA SERIE 50 La Serie 50
transmite la posicin del actuador y la vlvula
a estaciones locales y remotas. El monitor
compacto de control de la vlvula se monta
directamente en la parte alta del actuador. Sus
caractersticas incluyen botones de control
de tacto, tapa con tornillos cautivos, indicador
de posicin local y dos conductos de entrada
para facilitar el cableado. Con potencia de 15
amps a 125 o 250 volts AC, la Serie 50 tiene
interruptores de carrera internos que estn
precableados a un bloque terminal. Los
interruptores estndares son dos micro
interruptores conmutadores unipolares
(SPDT). Las opciones disponibles de
interruptor son 4 micro interruptores, 2
interruptores de proximidad, 2 interruptores
neumticos o potencionmetro para lectura
continua. El armazn est disponible a
prueba de agua (NEMA 4, 4X) o a prueba
de explosin (NEMA 4, 4X, 7.9).

MONITOR DE CONTROL DE LA
VLVULA SERIE 52 El Bray 2N1
ProxSensor ofrece dos sensores de proximidad
inductivos en un espacio independiente,
sellado completamente y compacto. Los dos
sensores estn encapsulados completamente
con resina epxica en un espacio de nylon para
una proteccin superior a la humedad,
qumicos y corrosin. Las caractersticas
incluyen indicadores LED, un indicador de alta
visibilidad para indicar la posicin local, un
objetivo no-magntico y un conector de cable
elctrico multi-pin. La Serie 52 se monta
directamente en los actuadores Bray o pueden
ser montados para sealar la posicin de la
vlvula de vlvulas operadas manualmente.
Versiones intrnsicamente seguras de AC, DC
Y NAMUR estn disponibles. Los Sensores de
AC operan con 20-250 VAC con una carga de
corriente mxima de 500mA. Las unidades de
Sensor DC operan con una carga de corriente
mxima de 200mA.

POSICIONADORES ELECTRONEUMTICOS Y NEUMTICOS


SERIE 67 Los posicionadores de la Serie 67
Bray presentan un diseo modular que
permite que las unidades y accesorios sean
combinados libremente. Para uso con
actuadores ya sea de doble accin o sencilla,
proporcionan modos de operacin directa o de
reversa, y se pueden hacer por separado
ajustes nulos y de rango. El posicionador
anlogo electro-neumtico acepta seales de
entrada ya sea de 0-20 mADC o 4-20 mADC.
Para un control digital se ofrecen
posicionadores avanzados Digitales Anlogos
controlados por un microprocesador y electroneumticos BusSmart Intelligent.

Tanto los Accesorios Brayline como los


Actuadores Brayline cumplen con VDI/
VDE 3845 (recomendaciones NAMUR)

ESPECIFICACIONES

LNEA DE PRODUCTO
MODULAR DE TAMAO
COMPACTO El actuador se opera

neumticamente y debe moverse un


mnimo de 90 en cada direccin y
deber ser capaz de rebasar el lmite de
sobrecarrera en 3 en cada direccin
pasados 90. El actuador est
completamente cerrado y contenido en
un espacio sencillo, sin partes externas
movibles. Todos los pasos de trnsito
neumticos son integrales al armazn
del actuador para as eliminar la
necesidad de tubera externa. El
actuador es de diseo de cremallera y
pin, y la salida de torque deber ser
lineal durante todo el movimiento. El
actuador tiene pistones con guas de
acetal de pistones y anillos que
aumentan enormemente la vida del
actuador y reducen la friccin al
mnimo. El actuador se surte con dos
ajustes de tope de carrera
independientes, las posiciones de
carrera de 0 y 90 tienen un ajuste de
carrera de +5 a -5 (ver el diagrama A
abajo). El actuador se surte con un
indicador visual de posicin mecnico y
el indicador podr quitarse fcilmente y
as exponer el vstago de salida para el
sobrepaso (operacin) manual
(override) del actuador cuando sea
necesario. El vstago de salida y pin
debe ser de una pieza y fabricada de
aleacin de acero reforzado y recubrimiento de zinc
para proteccin de corrosin. El actuador debe
poder ser montado en cualquier posicin sin dao
en su funcionamiento. El actuador debe atornillarse
directamente a la brida de montaje de la vlvula
Bray sin necesidad de ningn soporte o adaptador.
El armazn del actuador debe ser de aluminio
anodizado y todos los tornillos externos debern ser
de acero al carbn, con recubrimiento de zinc. Los
resortes deben ser de acero para resortes, recubiertos
con proteccin para corrosin. Todos los empaques
debern ser de Buna-N y los soportes hechos de
resina de acetal lubricados.
El actuador debe estar lubricado de fbrica. El
diseo del actuador debe tener un contorno liso del
armazn para que desage. El actuador debe ser
probado por la fbrica para asegurar su correcta
operacin.

CABECERA DE RETORNO DISEO


MODULAR El Sistema de Retorno de Cabecera
para servicios a prueba de fallas se instala en el
mismo armazn del actuador de doble accin, sin
necesidad de extensiones adicionales, por lo tanto
con ahorro de espacio y peso. El sistema de resorte
se surte como sistema de cartuchos de resorte
independiente. Esta es una caracterstica de
seguridad que asegura desmontar el actuador sin
peligro de liberar el resorte al quitar las tapas de los
extremos. El actuador debe ser de la Serie Bray 92 o
93 o uno igual aprobado.
INFORMACIN DE SERVICIO Los
actuadores son diseados para operaciones
neumticas hasta de un mximo de presin de 140
psig (10 Bar) y para rangos de temperatura de -40 F
(-40 C) a +200 F (+95 C). Se recomienda aire
filtrado pero no es necesario. Todas las unidades de
doble accin y cabecera de retorno son apropiadas
tanto para aplicaciones de apertura y cierre (on-off)
como de regulacin. Las unidades opcionales deben
ser capaces de operar con otros medios tales como
aceite hidrulico o agua; para mayor informacin
consulte a la fbrica.
EQUIPO OPCIONAL Ver el folleto de Bray
#1030 para Solenoide, los folletos #1011 y 1029 para
Posicionadores Neumticos y Electro-neumticos y
los folletos #1012 y #1015 para Monitores de
Control de Vlvulas.
Diagrama A Ajustes de Tope de Carrera
Las posiciones de carrera de 0 y 90 tienen
un ajuste de carrera de +5 max. a -5 min.

COMPONENTES DEL ACTUADOR


Nmero Cantidad
Artculo

1
1
2
2
3
1
4
2
5 * 12 mx.
6
1
7
1
8
1
9
1
10
2
11
2
12
2
13
2
14
2
15
1
16
1
17
8
18
8
19
2
20
2
21
1
22
1
23
1
24
1

Descripcin

Cuerpo
Pistn
Pion
Cubierta de los extremos
Ensamble de cartucho de resorte
Soporte superior
Soporte inferior
Anillo de retencin
Arandela de nylon
Gua de soporte de acetal
Anillo de gua de acetal
Tuerca del interruptor
Tornillo de ajuste del interruptor de carrera
O-Ring del tope de carrera
Rondana de acetal
Tope de carrera
Tornillo de cabeza hexagonal de la cubierta
Arandela
O-Ring del pistn
O-Ring de la cubierta del extremo
O-Ring superior del vstago
O-Ring inferior del vstago
Puntero del indicador
Tornillo del puntero del indicador

5
+5

5 +5
Advertencia: Se deben tomar
precauciones para no sobre
ajustar los topes de carrera
demasiado adentro o
demasiado afuera.

Unidad de Cabecera de
Retorno de la Serie 93
mostrada arriba

MATERIALES ESTNDAR
Cuerpo: Aleacin de aluminio extrudo, anodizado
Tapas de los Extremos: Aleacin de aluminio fundido inyectado con
recubrimiento de polister resistente a corrosin
Pistones: Aleacin de aluminio fundido inyectado
Vstago de Salida/Pin: Acero al carbn, con recubrimiento de zinc
Topes de Carrera: Aleacin de acero
Soportes del Vstago: Acetal
Guas de los Pistones: Acetal
Tornillos: Acero inoxidable
Resortes: Acero para resortes, recubrimiento protector
Sellos O-Ring: Buna-N
Opciones: Cuerpo exterior con
DISTRIBUIDOR
recubrimiento de polister

*Los Cartuchos de Resorte no


estn incluidos en la Serie 92
de Doble Accin

Cuerpo exterior
electro-niquelado
Cuerpo exterior
anodizado profundo
Pin de acero inoxidable
Todas las instrucciones, informacin tcnica y
recomendaciones en este folleto son nicamente para
uso general. Consulte a los representantes de Bray o a
la fbrica para requerimientos especiales y seleccin
de material para su propsito de aplicacin. El
derecho de cambiar o modificar el producto o el
diseo del producto sin previo aviso est reservado.
Patentado y patentes aplicadas en todo el mundo.
Bray es una marca registrada de BRAY INTERNATIONAL, Inc.

CONTROLS S.A.

Una Divisin de BRAY INTERNATIONAL, Inc.


Avda. Presidente Eduardo Frei Montalva 6001-72
855-0189 Centro de Empresas El Cortijo
Conchali - Santiago, Chile
www.bray.com
56-2-949-1875 Fax: 56-2-949-1876 email: sales.chile@bray.com
2006 Bray International. Derechos reservados B-1032 3/06 v3/06

Operating Instructions

Prosonic M FMU40/41/42/43/44
Ultrasonic Level Measurement

BA239F/00/en/01.09
71089089
Valid as of software version:
V 01.04

Short instructions

Prosonic M - FOUNDATION Fieldbus

Short instructions
KA 183F/00/a2/02.02
52010993

Prosonic M - Quick Setup

000
measured value
-

Contrast:

or

Group
selection

00
basic setup

002
003
tank shape medium
property

01
safety settings

- dome
ceiling
- horizontal
cyl.
- bypass

0E
temperature
04
linearisation

004
process
cond.

005
empty
calibr.

- unknown - standard input E


(s. sketch)
- calm
- liquid
surface
- > 4 mm
- < 4 mm - add.
agitator

059
blocking
distance

006
full
calibr.

input F
BD is
displayed (s. sketch)
(s. sketch)

008
dist./
meas value

051
008
check
dist./
meas value distance

052
range of
mapping

D and L are - ok
displayed
- too small
(s. sketch) - too big
- unknown
- manual

confirm
suggestion
or specify
range

053
start
mapping

05
extended calibr.
06
output (HART, FF)
profibus param.(PA)

BD

100%

0E
Envelope curve

0E2
0E1
plot settings recording
curve

09
display

092
language

0A
diagnostics

0A0
present
error

0C
system
parameter

0C0
tag no.

D
E

0A1
previous
error

0A3
reset

0A4
unlock
parameter

100 (HART)
333 (HART)
33333 (PA,FF) 2457 (PA,FF)

0%
BD: blocking distance

52010993
L00-FMU4xxx-05-00-00-en-001

Contents of the operating instructions


This operating instructions describes the installation and commissioning of the Prosonic M
ultrasonic level transmitter. It contains all the functions required for a normal measuring operation.
Also, the Prosonic M provides additional functions for optimising the measuring point and for
converting the measured value. These functions are not included in this operating instructions.
You can find an overview of all the device functions in the Appendix.
You can find a detailed description of all the device functions in the operating instructions BA
240F/00/en "Prosonic M - Description of Instrument Functions". This is located on the supplied
documentation CD-ROM.

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Table of contents

Table of contents
1

Safety instructions . . . . . . . . . . . . . . . . 4

6.5

1.1
1.2
1.3
1.4

Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation, commissioning, operation . . . . . . . . . . .
Hazardous area . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on safety conventions and symbols . . . . . . . . .

6.6

Identification . . . . . . . . . . . . . . . . . . . . 6

2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9

Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Product structure FMU 40 . . . . . . . . . . . . . . . . . . . . 7
Product structure FMU 41 . . . . . . . . . . . . . . . . . . . . 8
Product structure FMU 42 . . . . . . . . . . . . . . . . . . . . 9
Product structure FMU 43 . . . . . . . . . . . . . . . . . . . 11
Product structure FMU 44 . . . . . . . . . . . . . . . . . . . 12
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Certificates and approvals . . . . . . . . . . . . . . . . . . . 14
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 14

Installation . . . . . . . . . . . . . . . . . . . . . 15

3.1
3.2
3.3
3.4
3.5
3.6
3.7

Design; dimensions . . . . . . . . . . . . . . . . . . . . . . . .
Installation variants . . . . . . . . . . . . . . . . . . . . . . . .
Installation conditions . . . . . . . . . . . . . . . . . . . . . .
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation hint for FMU 40/41 . . . . . . . . . . . . . .
Turn housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Post installation check . . . . . . . . . . . . . . . . . . . . . .

Wiring . . . . . . . . . . . . . . . . . . . . . . . . 26

4.1
4.2
4.3
4.4
4.5
4.6

Electrical connection . . . . . . . . . . . . . . . . . . . . . . .
Wiring with Foundation Fieldbus plug . . . . . . . . . .
Cable specifications Foundation Fieldbus . . . . . . . .
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended connection . . . . . . . . . . . . . . . . . .
Post connection check . . . . . . . . . . . . . . . . . . . . . .

Operation . . . . . . . . . . . . . . . . . . . . . . 30

5.1
5.2

Operating options . . . . . . . . . . . . . . . . . . . . . . . . . 30
Operation with the display and operating module
VU331 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Operation with an Endress+Hauser operating program
36
Operation with a FOUNDATION Fieldbus configuration
program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Operation with the handheld terminal DXR375/FC375
42

5.3
5.4
5.5

4
4
4
5

15
18
20
23
25
25
25

26
28
28
28
29
29

Commissioning. . . . . . . . . . . . . . . . . . 44

6.1
6.2
6.3
6.4

Function check . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unlocking the device . . . . . . . . . . . . . . . . . . . . . . .
Resetting the device . . . . . . . . . . . . . . . . . . . . . . .
Commissioning by the display and operatig module
VU331 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Endress+Hauser

44
44
46

6.7

Basic Setup with the Endress+Hauser operating program


58
Commissioning with a FOUNDATION Fieldbus
configuration tool . . . . . . . . . . . . . . . . . . . . . . . . . 62
Commissioning with the handheld terminal DXR375/
FC375 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Troubleshooting . . . . . . . . . . . . . . . . . 68

7.1
7.2

System error messages . . . . . . . . . . . . . . . . . . . . . . 68


Application errors . . . . . . . . . . . . . . . . . . . . . . . . . 72

Maintenance and repairs . . . . . . . . . . . 74

8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
8.10

Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . .
Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repairs to Ex-approved devices . . . . . . . . . . . . . . .
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Spare parts (housing type F12) . . . . . . . . . . . . . . . .
Spare parts (housing type T12) . . . . . . . . . . . . . . . .
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software history . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contact addresses of Endress+Hauser . . . . . . . . . . .

Accessories . . . . . . . . . . . . . . . . . . . . . 83

9.1
9.2
9.3
9.4
9.5
9.6
9.7
9.8
9.9
9.10

Weather protection cover . . . . . . . . . . . . . . . . . . . .


Installation bracket for FMU 40/41 . . . . . . . . . . . .
Adapter flange . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cantilever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting Frame . . . . . . . . . . . . . . . . . . . . . . . . . .
Wall Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting bracket for FMU 42/43/44 . . . . . . . . . .
Commubox FXA291 . . . . . . . . . . . . . . . . . . . . . . .
ToF Adapter FXA291 . . . . . . . . . . . . . . . . . . . . . . .
Remote display FHX40 . . . . . . . . . . . . . . . . . . . . . .

10

Technical Data. . . . . . . . . . . . . . . . . . . 89

10.1

Technical data at a glance . . . . . . . . . . . . . . . . . . . 89

11

Appendix . . . . . . . . . . . . . . . . . . . . . . . 94

11.1
11.2
11.3
11.4
11.5
11.6
11.7
11.8
11.9

Operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Block model of the Prosonic M . . . . . . . . . . . . . . . 96
Resource block . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Sensor Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Diagnostic Block . . . . . . . . . . . . . . . . . . . . . . . . . 101
Display Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Analog input block . . . . . . . . . . . . . . . . . . . . . . . . 103
List of start indices . . . . . . . . . . . . . . . . . . . . . . . . 107
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . 108

74
74
74
74
75
78
81
81
81
82

83
83
84
85
86
86
87
87
87
88

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

48

Safety instructions

Prosonic M - FOUNDATION Fieldbus

Safety instructions

1.1

Designated use

The Prosonic M is a compact measuring device for continuous, non-contact level measurement.
Depending on the sensor, the measuring range is up to 15m in fluids and up to 7m in bulk solids.
By using the linearisation function, the Prosonic M can also be used for flow measurements in open
channels and measuring weirs.

1.2

Installation, commissioning, operation

The Prosonic M is fail-safe and is constructed to the state-of-the-art. It meets the appropriate
standards and EC directives. However, if you use it improperly or other than for its designated use,
it may pose application-specific hazards, e.g. product overflow due to incorrect installation or
configuration. Installation, electrical connection, start-up, operation and maintenance of the
measuring device must therefore be carried out exclusively by trained specialists authorised by the
system operator. Technical personnel must have read and understood these operating instructions
and must adhere to them. You may only undertake modifications or repair work to the device when
it is expressly permitted by the operating instructions.

1.3

Hazardous area

Measuring systems for use in hazardous environments are accompanied by separate "Ex
documentation", which is an integral part of this Operating Manual. Strict compliance with the
installation instructions and ratings as stated in this supplementary documentation is mandatory.
Ensure that all personnel are suitably qualified.
Observe the specifications in the certificate as well as national and local standards and regulations.

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Safety instructions

1.4

Notes on safety conventions and symbols

In order to highlight safety-relevant or alternative operating procedures in the manual, the following
conventions have been used, each indicated by a corresponding symbol in the margin.
Safety conventions

#
"
!

Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to personal
injury, a safety hazard or destruction of the instrument
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal
injury or incorrect functioning of the instrument
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect
operation or may lead to an instrument response which is not planned

Explosion protection

Device certified for use in explosion hazardous area


If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous
area

Explosion hazardous area


Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring
entering areas with the designation explosion hazardous areas must conform with the stated type
of protection.

Safe area (non-explosion hazardous area)


Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in
safe areas still require a certificate if their outputs run into explosion hazardous areas

Electrical symbols

Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied

&

Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or
supplied

Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by means of an
earth grounding system

Protective grounding (earth) terminal


A terminal which must be connected to earth ground prior to making any other connection to the
equipment

+
t >85C

Endress+Hauser

Equipotential connection (earth bonding)


A connection made to the plant grounding system which may be of type e.g. neutral star or
equipotential line according to national or company practice
Temperature resistance of the connection cables
States, that the connection cables must be resistant to a temperature of at least 85 C.

Identification

Prosonic M - FOUNDATION Fieldbus

Identification

2.1

Nameplate

ENDRESS+HAUSER
PROSONIC-M
Order Code:
Ser.-No.:

Made in Germany
D-79689 Maulburg

1
2

IP68 / NEMA 6P

Profibus PA
Foundation Fieldbus

90 253 V AC 4VA
10,5 32 V DC 1W
14 36 V DC 0,8W
4 20 mA HART
TA > 70C : t >85C

2-wire
4-wire

4
if modification
X = see sep. label
Dat./Insp.:

Patents
D01345-B
L00-FMU4xxxx-18-00-00-yy-001

1: Order Code; 2: Serial number; 3: Designation according to Directive 94/9/EC and designation of the type of protection
(only for certified device variants); 4: Reference to additional safety-relevant documentation (only for certified device
variants); 5: Communication variant and supply voltage (the appropriate option is highlighted)

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

2.2

Identification

Product structure FMU 40


Certificates
A Variant for non-hazardous area
E NEPSI Ex nA II T6
G ATEX II 3G EEx nA II T6
I NEPSI Ex ia IIC T6
J NEPSI Ex d(ia) IIC T6
K TIIS Ex ia II C T6
N CSA General Purpose
Q NEPSI DIP
S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2
T FM XP Cl. I,II,III Div. 1 Gr. A-G
U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2
V CSA XP Cl. I,II,III Div. 1 Gr. A-G
1 ATEX II 1/2 G or II 2 G; EEX ia IIC T6
2 ATEX II 1/2D, Alu blind cover
4 ATEX II 1/2 G or II 2 G; EEX d [ia] IIC T6
5 ATEX II 1/3D
Y Special certificate
Process connection
R G 1 threadISO 228
N NPT 1 - 11,5 thread
Y Special version
Power supply/communication
B 2 wire, 4...20mA-loop/HART
H 4 wire, 10,5...32VDC / 4-20mA HART
G 4 wire, 90...253VAC / 4-20mA HART
D 2 wire, PROFIBUS PA
F 2 wire, Foundation Fieldbus
Y Special version
Display / on-site operation
1 Without LC display
2 With LC display VU 331 incl. on-site operation
3 Prepared for remote display FHX 40
9 Special version
Housing
A Aluminium F12 housing coated to IP 68
C Aluminium T12 housing coated to IP 68; with separate terminal compartment
D Aluminium T12 housing coated to IP 68; with separate terminal compartment;
with overvoltage protection
9 Special version
Screw union/entry
2 M20x1.5 screw union
3 G 1/2 entry
4 NPT 1/2 entry
5 M12 PROFIBUS-PA plug-in connector
6 7/8" FF plug
9 Special version

FMU 40 -

Endress+Hauser

Product designation

Identification

Prosonic M - FOUNDATION Fieldbus

2.3

Product structure FMU 41


Certificates
A Variant for non-hazardous area
E NEPSI Ex nA II T6
G ATEX II 3G EEx nA II T6
I NEPSI Ex ia IIC T6
J NEPSI Ex d(Ia) IIC T6
K TIIS Ex ia II C T6
N CSA General Purpose
Q NEPSI DIP
S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2
T FM XP Cl. I,II,III Div. 1 Gr. A-G
U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2
V CSA XP Cl. I,II,III Div. 1 Gr. A-G
1 ATEX II 1/2 G or II 2 G; EEX ia IIC T6
2 ATEX II 1/2D, Alu blind cover
4 ATEX II 1/2 G or II 2 G; EEX d [ia] IIC T6
5 ATEX II 1/3D
Y Special certificate
Process connection
R G 2 threadISO 228
N NPT 2 - 11,5 thread
Y Special version
Power supply/communication
B 2 wire, 4...20mA-loop/HART
H 4 wire, 10,5...32VDC / 4-20mA HART
G 4 wire, 90...253VAC / 4-20mA HART
D 2 wire, PROFIBUS PA
F 2 wire, Foundation Fieldbus
Y Special version
Display / on-site operation
1 Without LC display
2 With LC display VU 331 incl. on-site operation
3 Prepared for remote display FHX 40
9 Special version
Housing
A Aluminium F12 housing coated to IP 68
C Aluminium T12 housing coated to IP 68 with separate terminal compartment
D Aluminium T12 housing coated to IP 68; with separate terminal compartment;
with overvoltage protection
9 Special version
Screw union/entry
2 M20x1.5 screw union
3 G 1/2 entry
4 NPT 1/2 entry
5 M12 PROFIBUS-PA plug-in connector
6 7/8" FF plug
9 Special version

FMU 41 -

Product designation

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

2.4

Identification

Product structure FMU 42


Certificates
A Variant for non-hazardous area
E NEPSI Ex nA II T6
G ATEX II 3G EEx nA II T6
I NEPSI Ex ia IIC T6
J NEPSI Ex d (Ia) IIC T6
K TIIS Ex ia II C T6 (in preparation)
N CSA General Purpose
Q NEPSI DIP
S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2
T FM XP Cl. I,II,III Div. 1 Gr. A-G
U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2
V CSA XP Cl. I,II,III Div. 1 Gr. A-G
1 ATEX II 1/2 G EEX ia IIC T6
2 ATEX II 1/2 D, Alu bond cover
4 ATEX II 1/2 G EEX d [ia] IIC T6
5 ATEX II 1/3D
Y Special certificate
Process connection
M Mounting bracket FAU20
P UNI flange 3"/DN80/80, PP, max. 2.5bar abs./ 36psia
suitable for 3" 150lbs / DN80 PN16 / 10K 80
Q UNI flange 3"/DN80/80, PVDF, max. 2.5bar abs./ 36psia
suitable for 3" 150lbs / DN80 PN16 / 10K 80
S UNI flange 3"/DN80/80, 316L, max. 2.5bar abs./ 36psia
suitable for 3" 150lbs / DN80 PN16 / 10K 80
T UNI flange 4"/DN100/100, PP, max. 2.5bar abs./ 36psia
suitable for 4" 150lbs / DN100 PN16 / 10K100
U UNI flange 4"/DN100/100, PVDF, max. 2.5bar abs./ 36psia
suitable for 4" 150lbs / DN100 PN16 / 10K100
V UNI flange 4"/DN100/100, 316L, max. 2.5bar abs./ 36psia
suitable for 4" 150lbs / DN100 PN16 / 10K100
Y Special version
Power supply/communication
B 2 wire, 4...20mA-loop/HART
H 4 wire, 10,5...32VDC / 4-20mA HART
G 4 wire, 90...253VAC / 4-20mA HART
D 2 wire, PROFIBUS PA
F 2 wire, Foundation Fieldbus
Y Special version
Display / on-site operation
1 Without LC display
2 With LC display VU 331 incl. on-site operation
3 Prepared for remote display FHX 40
9 Special version
Housing
A Aluminium F12 housing coated to IP 68
C Aluminium T12 housing coated to IP 68, with separate terminal compartment
D Aluminium T 12 housing coated to IP 68, with separate terminal compartment; with
overvoltage protection
Y Special version
Gland/Entry
2 M20x1.5 gland
3 G 1/2 entry
4 NPT 1/2 entry
5 M12 PROFIBUS-PA plug
6 7/8" FF plug
9 Special version

Endress+Hauser

Identification

Prosonic M - FOUNDATION Fieldbus

Sealing Sensor/Flange
2 VITON flat sealing
3 EPDM flat sealing
9 special version
Additional options
A Additional options not selected
FMU 42 -

10

Product designation

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

2.5

Identification

Product structure FMU 43


Certificates
A Variant for non-hazardous area
M FM DIP Class II, III, Div. 1, Gr. E,F,G NI
N CSA General Purpose
P CSA DIP, Class II, III, Div. 1, Gr. E,F,G NI
Q NEPSI DIP
2 ATEX II 1/2 D or II 2 D, Aluminium Deckel
5 ATEX II 1/3 D or II 3 D, Sichtdeckel
Y Special version
Process connection/material
P Flange DN 100/ANSI 4"/JIS 16K100, PP (universal slip-on flange included)
S Flange DN 100/ANSI 4"/JIS 16K100, SS 316TI (universal slip-on flange included)
K Without slip-on flange/without mounting bracket (customer mounting equipment)
M With mounting bracket
Y Special version
Power supply/communication
H 4 wire, 10,5...32VDC / 4-20mA HART
G 4 wire, 90...253VAC / 4-20mA HART
D 2 wire, PROFIBUS PA
F 2 wire, Foundation Fieldbus
Y Special version
Display / on-site operation
1 Without LC display
2 With LC display VU 331 incl. on-site operation
3 Prepared for remote display FHX 40
9 Special version
Housing
A Aluminium F12 housing coated to IP 68
9 Special version
Screw union/entry
2 M20x1.5 screw union
3 G 1/2 entry
4 NPT 1/2 entry
5 M12 PROFIBUS-PA plug-in connector
6 7/8" FF plug
9 Special version

FMU 43 -

Endress+Hauser

Product designation

11

Identification

Prosonic M - FOUNDATION Fieldbus

2.6

Product structure FMU 44


Approval
A Non-hazardous area
1 ATEX II 1/2G EEx ia IIC T6 (in preparation)
4 ATEX II 1/2G EEx d (ia) IIC T6 (in preparation)
G ATEX II 3 G EEx nA II T6 (in preparation)
2 ATEX II 1/2 D, Alu blind cover (in preparation)
5 ATEX II 1/3 D
S FM IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.I Div.2 (in preparation)
T FM XP Cl.I,II,III Div.1 Gr.A-G (in preparation)
N CSA General Purpose
U CSA IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.I Div.2
V CSA XP Cl.I,II,III Div.1 Gr.A-G
K TIIS EEx ia IIC T6 (in preparation)
I NEPSI Ex ia IIC T6 (in preparation)
J NEPSI Ex d(ia) IIC T6 (in preparation)
E NEPSI Ex nA II T6 (in preparation)
Q NEPSI DIP (in preparation)
Y Special version, to be specified
Process connection
A 8" 150lbs FF, 316L, max 2.5bar abs./36psia
E UNI flange 6"/DN150/150, PP, max 2.5bar abs./ 36psia,
suitable for 6" 150lbs / DN150 PN16 / 10K 150
F UNI flange 6"/DN150/150, PVDF, max 2.5bar abs./36psia,
suitable for 6" 150lbs /DN150 PN16 / 10K 150
G UNI flange 6"/DN150/150, 316L, max 2.5bar abs. 36psia,
suitable for 6" 150lbs / DN150 PN16 / 10K 150
H UNI flange DN200/200, PP, max 2.5bar abs./ 36 psia,
suitable for DN200 PN16 / 10K 200
J UNI flange DN200/200, PVDF, max 2.5bar abs./ 36psia,
suitable for DN200 PN16 / 10K 200
K UNI flange DN200/200, 316L, max 2.5bar abs./ 36psia,
suitable for DN200 PN16 / 10K 200
L 8" 150lbs FF, PP, max 2.5bar abs./ 36psia
M Mounting bracket FAU20
N 8" 150lbs FF, PVDF, max 2.5bar abs./ 36psia
T UNI flange 4"/DN100/100, PP, max 2.5bar abs./ 36psia,
suitable for 4" 150lbs / DN100 PN16 / 10K 100
U UNI flange 4"/DN100/100, PVDF, max. 2.5bar abs./ 36 psia,
suitable for 4" 150lbs / DN100 PN16 / 10K 100
V UNI flange 4"/DN100/100, 316L, max 2.5bar abs./ 36psia,
suitable for 4" 150lbs / DN100 PN16 / 10K 100
Y Special version, to be specified
Power supply; Output
B 2-wire; 4-20mA HART
D 2-wire; PROFIBUS PA
F 2-wire; FOUNDATION Fieldbus
G 4-wire 90-250VAC; 4-20mA HART
H 4-wire 10.5-32VDC; 4-20mA HART
Y Special version, to be specified
Operation
1 w/o display, via communication
2 4-line display VU331, Envelope curve display on site
3 Prepared for FHX40, Remote display (accessory)
9 Special version, to be specified

FMU 44 -

12

product designation, part 1

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Identification

Housing
A F12 Alu, coated IP68 NEMA6P
C T12 Alu, coated IP68 NEMA6P, Separate conn. compartment
D T12 Alu, coated IP68 NEMA6P + OVP, Sep. conn. compartment, OVP = overvoltage
protection
9 Special version, to be specified
CAble entry
2 Gland M20 (EEx d > thread M20)
3 Thread G1/2
4 Thread NPT 1/2
5 Plug M12
6 Plug 7/8
9 Special version, to be specified
Process Sealing Sensor/ Flange
2 Viton
3 EPDM
9 Special version, to be specified
Additional option
A Basic version
Y Special version, to be specified
FMU 44 -

Endress+Hauser

complete product designation

13

Identification

Prosonic M - FOUNDATION Fieldbus

2.7

Scope of delivery

2.7.1

Instrument and accessories

Instrument according to the version ordered


"ToF Tool - FieldTool Package" (2 CD-ROMs)
for FMU 40/41 in the versions FMU 40 *R**** and FMU 41 *R****: counter nut (PC)
for FMU 40/41: sealing ring (EPDM)
for gland M20x1.5:
1 cable gland for 2-wire instruments
2 cable glands for 4-wire instruments
The cable glands are mounted on delivery.

2.7.2

Supplied documentation

Short instructions (KA 183F, in the instrument)


intended as a memory jogger for users who are familiar with the operating concept of
Endress+Hauser Time-of-Flight instruments.
Operating instructions (BA 239F, this booklet)
This describes the installation and commissioning of the Prosonic M. The operating menu includes
all the functions which are required for standard measurement tasks. Any additional functions are
not included.
Description of Instrument Functions (BA 240F)
contains a detailed description of all the functions of the Prosonic M. You can find this document
as a pdf file on the supplied ToF Tool - FieldTool CD-ROM 1.
Safety instructions
Additional safety instructions (XA, ZE, ZD) are supplied with certified device versions. Refer to the
nameplate for the names of the safety instructions that apply to your device version.

2.8

Certificates and approvals

CE mark, declaration of conformity


The device is designed to meet state-of-the-art safety requirements, has been tested and left the
factory in a condition in which it is safe to operate. The device complies with the applicable
standards and regulations as listed in the EC declaration of conformity and thus complies with the
statutory requirements of the EC directives. Endress+Hauser confirms the successful testing of the
device by affixing to it the CE mark.

2.9

Registered trademarks

ToF
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
PulseMaster
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
FOUNDATION Fieldbus
Registered trademark of Fieldbus Foundation Austin, Texas, USA

14

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Installation

3.1

Design; dimensions

3.1.1

FMU40, FMU41

F12

65
(2.6)

T12
78
(3.1)

94
(3.7)

68
(2.7)

ENDRESS+HAUSER
Prosonic M

ENDRESS+HAUSER
Prosonic M

85
(3.3)

85
(3.3)

22
(0.9)

FMU 41
22
(0.9)

~148 (5.8)

G2
2 NPT

~83 (3.3)

~87
(~3.4)

G1
1 NPT

SW (AF) 60

~148 (5.8)

FMU 40
SW (AF) 60

78
(3.1)
32 (1.3)

150 (5.9)

65
(2.6)

129 (5.1)

~86
(~3.4)

162 (6.4)

Installation

129 (5.1)

39 (1.5)
50 (2.0)
L00-FMU4xxxx-06-00-00-yy-006

Dimensions in mm (inch)

FMU42, FMU44 with slip-on flange

F12
78
(3.1)

68
(2.7)

ENDRESS+HAUSER
Prosonic M

65
(2.6)

94
(3.7)

78
(3.1)
32 (1.3)

150 (5.9)

65
(2.6)

129 (5.1)

~86
(~3.4)

T12

ENDRESS+HAUSER
Prosonic M

85
(3.3)

162 (6.4)

3.1.2

129 (5.1)

Abb. 1:

85
(3.3)

70 (2.8)

~ 145 (5.7)

~ 107
(4.2)

~ 110 (4.3)

FMU 44

~ 85
(3.3)

FMU 42

98 (3.9)
L00-FMU4xxxx-06-00-00-yy-007

Dimensions in mm (inch)

Endress+Hauser

15

Installation

Prosonic M - FOUNDATION Fieldbus

3.1.3

FMU42, FMU44 with mounting bracket


FMU 42

FMU 44

ENDRESS+HAUSER
Prosonic M

ENDRESS+HAUSER
Prosonic M

F12/
T12

F12/
T12
M8

75
(3.0)

30 (1.2)

125 (4.9)

30 (1.2)

105 (4.1)

M8

119 (4.7)
119 (4.7)

98
(3.9)

L00-FMU4xxxx-06-00-00-yy-008

Dimensions in mm (inch)

3.1.4

FMU43

ENDRESS+HAUSER
Prosonic M

F12

2 x M8

ER
HAUS
ESS+
ENDR ic M
Proson

~248 (9.8)

129 (5.1)

78
(3.1)

150 (5.9)

65
(2.6)

~86
(3.4)

75 (3

85 (3.3)

.5)
89 (3
6.2)
158 (

230 (9.1)

ANSI 4 DN 100 *

.0)

L00-FMU4xxxx-06-00-00-yy-009

Abb. 2:

3.1.5

Dimensions in mm (inch);
A: with slip-on flange; B: with mounting bracket

Mounting bracket for FMU42, FMU43 and FMU44


25
(0.98)

120 (4.7)

~123 (4.8)

119 (4.68)

40 (1.6)

40 (1.6)

2 (0.079)
25
(0.98)

11 (0.43)
L00-FMU4xxxx-06-00-00-yy-010

Abb. 3:

16

Dimensions in mm (inch)

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

3.1.6

Installation

Flanges for FMU42 and FMU44

20 (0.79)

G2
ISO228

C
L00-FMU4xxxx-06-00-00-yy-011

Endress+Hauser

suitable for

number of
boreholes

3" 150lbs / DN80 PN16 / 10K 80

150 mm
(5,91")

160 mm
(6,30")

200 mm
(7,87")

19 mm
(0,75")

45

4" 150 lbs / DN100 PN16 / 10K 100

175 mm
(6,90")

190,5 mm
(7,50")

228,6 mm
(9,00")

19 mm
(0,75")

45

6" 150 lbs / DN150 PN16 / 10 K 150

240 mm
(9,45")

241,3 mm
(9,50")

285 mm
(11,22")

23 mm
(0,91")

45

8" 150 lbs

298,5 mm
(11,75")

298,5 mm
(11,75")

342,9 mm
(13,50")

22, 5 mm
(0,89")

45

DN200 PN16 / 10 K 200

290 mm
(11,42")

295 mm
(11,61")

340 mm
(13,39")

23 mm
(0,91")

30

12

17

Installation

Prosonic M - FOUNDATION Fieldbus

3.2

Installation variants

3.2.1

Installation variants FMU 40, FMU 41


Installation with counter nut

Installation with sleeve

Sealing ring
(EPDM)
supplied

counter nut (PC)


supplied
for G 1 and
G 2 instruments

Installation with installation bracket

Installation with adapter flange

ENDRESS+HAUSER
Prosonic M

adapter flange

sensor

Sealing ring
(EPDM)
supplied

nozzle
L00-FMU4xxxx-17-00-00-en-002

For installation bracket or adapter flange s. chapter "Accessories".

18

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

3.2.2

Installation

Installation variants FMU42, FMU44


Installation with universal flange

Installation with mounting bracket

ER
HAUS
ESS+
ENDR nic M
Proso

e.g. Zone 20

Zone 20
L00-FMU42xxxx-17-00-00-en-001

3.2.3

Installation variants FMU 43


Installation with
universal slip-on flange (option)

Installation with
mounting bracket

ER
HAUS
ESS+
ENDR ic M
Proson

slip-on flange

nozzle

e.g.Zone 20

sensor

Zone 20
L00-FMU43xxxx-17-00-00-en-001

Endress+Hauser

19

Installation

Prosonic M - FOUNDATION Fieldbus

3.3

Installation conditions

3.3.1

Installation conditions for level measurements


2

7
1

5
1/6D
D
6

L00-FMU4xxxx-17-00-00-de-005

Do not install the sensor in the middle of the tank (3). We recommend leaving a distance between
the sensor and the tank wall (1) measuring 1/6 of the tank diameter.
Use a protective cover, in order to protect the device from direct sun or rain (2).
Avoid measurements through the filling curtain (4).
Make sure that equipment (5) such as limit switches, temperature sensors, etc. are not located
within the emitting angle . In particular, symmetrical equipment (6) such as heating coils, baffles
etc. can influence measurement.
Align the sensor so that it is vertical to the product surface (7).
Never install two ultrasonic measuring devices in a tank, as the two signals may affect each other.
To estimate the detection range, use the 3 dB emitting angle .
Sensor

Lmax

rmax

FMU40

11

5m

0.48 m

FMU41

11

8m

0.77 m

FMU42

10 m

0.79 m

FMU43

15 m

0.79 m

FMU44

11

20 m

1.93 m

3.3.2

Installation in narrow shafts

In narrow shafts with strong interference


echoes, we recommend using an ultrasound
guide pipe (e.g. PE or PVC wastewater pipe)
with a minimum diameter of 100 mm.
Make sure that the pipe is not soiled by accumulated dirt. If necessary, clean the pipe at regular
intervals.

ENDRESS+HAUSER
Prosonic M

ENDRESS+HAUSER
Prosonic M

venting
hole

L00-FMU4xxxx-17-00-00-en-010

20

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

3.3.3

Installation

Installation conditions for flow measurements

Install the Prosonic M at the inflow side, as close above the maximum water level Hmax as possible
(take into account the blocking distance BD).
Position the Prosonic M in the middle of the channel or weir.
Align the sensor membrane parallel to the water surface.
Keep to the installation distance of the channel or weir.
You can enter the "Flow to Level" linearisation curve ("Q/h curve") using ToF Tool or manually
via the on-site display.
Example: Khafagi-Venturi flume

Khafagi - Venturi - flume

empty calibr.

inflow

outflow

BD

direction of flow

Hmax

1 x b0

b0

L00-FMU4xxxx-17-00-00-en-003

Endress+Hauser

21

Installation

Prosonic M - FOUNDATION Fieldbus

Example: Triangular weir


min. 2 Hmax

Hmax (= full calibr.)


min. 2 Hmax

min. 3 H max
empty calibr.

BD

L00-FMU4xxxx-17-00-00-en-012

22

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Installation

3.4

Measuring range

3.4.1

Blocking distance, Nozzle mounting

Install the Prosonic M at a height so that the blocking distance BD is not undershot, even at
maximum fill level. Use a pipe nozzle if you cannot maintain the blocking distance in any other way.
The interior of the nozzle must be smooth and may not contain any edges or welded joints. In
particular, there should be no burr on the inside of the tank side nozzle end. Note the specified limits
for nozzle diameter and length. To minimise disturbing factors, we recommend an angled socket
edge (ideally 45).
FMU 43
FMU 40/41

FMU 42/44

BD
SD

F
L

L
D

D
D
L00-FMU4xxxx-17-00-00-en-004

BD: blocking distance; SD: safety distance; E: empty calibration; F: full calibration (span); D: nozzle diameter; L: nozzle
length

Maximum nozzle length[mm]

"

Endress+Hauser

Nozzle diameter

FMU40

FMU41

FMU42

DN50/2"

80

DN80/3"

FMU43

FMU44

240

240

250

DN100/4"

300

300

300

300

DN150/6"

400

400

400

300

400

DN200/8"

400

400

400

300

400

DN250/10"

400

400

400

300

400

DN300/12"

400

400

400

300

400

Emitting angle

11

11

11

Blocking distance [m]

0,25

0,35

0,4

0,6

0,5

Max. range [m]


in liquids

10

15

20

Max. range [m]


in solids

3,5

10

Caution!
If the blocking distance is undershot, it may cause device malfunction.

23

Installation

Prosonic M - FOUNDATION Fieldbus

3.4.2

Safety distance

If the level rises to the safety distance SD, the device switches to warning or alarm status.
The size of SD can be set freely in the "Safety distance" (015) function.The "in safety distance"
(016) function defines how the device reacts if the level enters the safety distance.
There are three options:
Warning: The device outputs an error message but continues measurement.
Alarm: The device outputs an error message. The output signal assumes the value defined in the
"Output on alarm" (011) function (MAX, MIN, user-specific value or holds the last value). As
soon as the level drops below the safety distance, the device recommences measurement.
Self holding: The device reacts in the same way as for an alarm. However, the alarm condition
continues after the level drops below the safety distance. The device only recommences
measurement when you cancel the alarm using the "Ackn. alarm" (017) function.

3.4.3

Range

The sensor range is dependent on the measuring conditions. Refer to Technical Information TI
365F/00/en for an estimation. The maximum range is shown in the above diagram (valid for good
conditions).

24

Sensor

maximum range

FMU40

5m

FMU41

8m

FMU42

10 m

FMU43

15 m

FMU44

20 m

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

3.5

Installation

Installation hint for FMU 40/41

Screw the Prosonic M at the screw-in piece


using an 60 AF spanner.
Maximum torque: 20 Nm.

F12 or T12 housing

Caution!
Use only the screw-in
piece to screw in
the Prosonic M

60

AF 60

max torque
20 Nm
L00-FMU4xxxx-17-00-00-en-009

3.6

Turn housing

After mounting, the housing can be turned 350 in order to simplify access to the display and the
terminal compartment. Proceed as follows to turn the housing to the required position:
Undo the fixing screws (1)
Turn the housing (2) in the required direction
Tighten up the fixing screws (1). Maximum torque 0.5 Nm.
Loctite can be used for securing the screw.
F12 housing

T12 housing

allen key
4 mm/0.1
max. torque 0.5 Nm

L00-FMU4xxxx-17-00-00-en-013

3.7

Post installation check

After installing the device, carry out the following checks:


Is the device damaged (visual inspection)?
Does the device correspond to the measuring point specifications for process temperature, process
pressure, ambient temperature, measuring range etc.
If available: Are the measuring point number and labelling correct (visual inspection)?
Is the measuring device sufficiently protected against precipitation and direct sunlight?
Are the cable glands tightened correctly?
After aligning the housing, check the process seal at the nozzle or flange.

Endress+Hauser

25

Wiring

Prosonic M - FOUNDATION Fieldbus

"
#

Wiring

4.1

Electrical connection

Caution!
Before connection please note the following:
The power supply must be identical to the data on the nameplate.
Switch off power supply before connecting up the instrument.
Connect equipotential bonding to transmitter ground terminal before connecting up the
instrument (s. section "Potential matching")
Warning!
When you use the measuring system in hazardous areas, make sure to comply with national
standards and the specifications in the safety instructions (XAs). Make sure you use the specified
cable gland.

4.1.1

Wiring in the housing F12

1.

Unscrew housing cover (1).

2.

Remove display (2) if fitted.

3.

Remove cover plate (3) from terminal


compartment.

4.

Pull out terminal module (4) slightly using


pulling loop.

5.

Insert cable (5) through gland (6).

"

Caution!
If possible, insert the cable from above and
let a draining loop in order to avoid
intrusion of humidity.
6.

ER
US
HA
S+
ES
DR
EN

Connect cable screen to the grounding


terminal (7) within the terminal
compartment.

7.

Make connection according to terminal


assignment (see below).

8.

Re-insert terminal module (4).

9.

Tighten cable gland (6).

10. Tighten screws on cover plate (3).


11. Insert display (2) if fitted.

12. Screw on housing cover (1).


13. Switch on power supply.
1 2 3 4

L00-FMU4xxxx-04-00-00-yy-008

26

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Wiring

4.1.2

Wiring in the housing T12

1.

Unscrew the cover (1) of the separate


connection room.

2.

Insert cable (2) through gland (3).

" Caution!
If possible, insert the cable from above and
let a draining loop in order to avoid
intrusion of humidity.
3.

Connect cable screen to the grounding


terminal (4) within the connection room.

4.

Make connection according to the terminal


assignment (see below).

5.

Tighten cable gland (3).

6.

Screw on housing cover (1).

7.

Switch on power supply.

2
4

1 2 3 4

L00-FMU4xxxx-04-00-00-yy-009

4.1.3

Terminal assignment

1 2 3 4
+

plant
ground

L00-FMxxxxxx-04-00-00-en-013

Endress+Hauser

27

Wiring

Prosonic M - FOUNDATION Fieldbus

4.2

Wiring with Foundation Fieldbus plug

1.

Insert plug (1) into bushing (2).

2.

Screw firmly.

3.

Ground instrument according to the


desired safety concept.

L00-FMU4xxxx-04-00-00-yy-011

4.2.1

Pin assignment of the 7/8" plug connector (FOUNDATION


Fieldbus plug)

+ 4

nc

Pin

Meaning

FF -

FF +

not connected

ground

L00-FMxxxxxx-04-00-00-yy-017

4.3

Cable specifications Foundation Fieldbus

Twisted, shielded pairs must be used. The cable specifications can be taken from the FF specification
or IEC 61158-2. The following have been found suitable:
Non-Ex-area:
Siemens 6XV1 830-5BH10,
Belden 3076F,
Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL.
Ex-area:
Siemens 6XV1 830-5AH10,
Belden 3076F,
Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL.

4.4

Supply voltage

The following values are the voltages across the terminals directly at the instrument:
Type

minimum terminal
voltage

maximum terminal
voltage

standard

9V

32 V

EEx ia (FISCO model

9V

17,5 V

EEx ia (Entity concept)

9V

24 V

The current consumption is approx. 15 mA for the range of voltages given above.

28

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

4.5

Wiring

Recommended connection

L00-FMU4xxxx-17-00-00-yy-014

1: external ground terminal of the transmitter

For maximum EMC protection please observe the following points:


As the metal housing of the Prosonic M is isolated from the tank by the plastic sensor, a lowimpedance connection between the housing and tank/bracket/flange should be installed in order
to ensure electromagnetic compatibility (EMC).
For optimum EMC the connection should be as short as possible. Ideally, a ground strap should
be used.
The continuity of the cable screening between tapping points must be ensured.
If potential equalisation is present between the individual grounding points, ground the screening
at each cable end or connect it to the device housing (as short as possible).
If there are large differences in potential between grounding points, the grounding should run via
a capacitor that is suitable for high frequency use (e.g. ceramic 10 nF/250 V&).

"

Caution!
Applications, which are subject to the explosion prevention, permit only under special conditions
the repeated grounding of the protective screen , see to EN 60 079-14..

4.6

Post connection check

After wiring the device, carry out the following checks:


Are the terminals correctly assigned?
Is the cable gland tight?
If available: Is the Foundation Fieldbus connector screwed tight?
Is the housing cover fully screwed on?
If power supply available: Does a display appear on the display module?

Endress+Hauser

29

Operation

Prosonic M - FOUNDATION Fieldbus

Operation

This chapter gives an overview of the different operating options for the device. The different
methods of parameter access are described and the preconditions for each method are stated.
The meaning of the parameters is not described in this chapter. Instead, refer to:
Chapter 6: "Commissioning"
Operating Instructions BA240F: "Prosonic M - Description of Instrument Functions"
This chapter contains the following sections:
5.1 Operating options
5.2 Operation with the display and operating module VU331
5.3 Operation with an Endress+Hauser operating software
5.4 Operation with a FOUNDATION Fieldbus configuration software
5.5 Operation with the handheld terminal DXR375/FC375

5.1

Operating options
ControlCare
DeltaV
...

FieldCommunicator 375/
FC375
Ethernet

dsdmdm
df das.
asdas fa
asas la.

DELTABAR: * * * * * * * *
ONLINE
1 QUICK SETUP
2 OPERATING MENU
3 PV
4 SV

HELP

SPS
PLC
API

Page
Up

Bksp

6
Delete

Page
On

#%&

ABC

Paste

Hot Key

JKL

MNO

Insert

+ Hot Key

TUV

W XY Z

DEF

1
Copy
GHI

PQRS

,()

_<>

+*/

375
FIELD COMMUNICATOR

FF link

power supply
power conditioner

352 mbar
0 C

SAVE

FOUNDATION Fieldbus

Weitere
Funktionen
(Ventile etc.)

Anzeige- und
Bedienmodul
VU331
ENDRESS + HAUSER

Levelflex M
Micropilot M

Prosonic M

FieldCare
FXA193/291

L00-FMxxxxxx-14-00-06-de-011

30

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

5.1.1

Operation

On-site operation

Options for on-site operation


Display and operating module VU331
Endress+Hauser operating software ("ToF Tool - FieldTool Package" or "FieldCare")
Parameter access by on-site operation
The following parameters can be accessed by on-site operation:
Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block)
Endress+Hauser service parameters
in the Resource Block: "Device Tag", "Device ID", "Device Revision", "DD Revision" (read only)

Sensorblock
Diagnoseblock
Display-Block

Resource Block

Arithmetik-Block

AI-Block 1

Input-Selector-Block

AI-Block 2

Signal-Charact.-Block

PID Block

Integrator-Block

Endress+Hauser
Service-Parameter
L00-FMU4XXXX-02-00-00-YY-005

The highlighted parameters can be edited by on-site operation.

5.1.2

Remote operation

Options for remote operation


FOUNDATION Fieldbus configuration tool (e.g. DeltaV or ControlCare)
Handheld terminal DXR375/FC375
Parameter access by remote operation
The following parameters can be accessed by remote operation:
Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block)
Parameters of the FOUNDATION Fieldbus function blocks

Sensorblock
Diagnoseblock
Display-Block

Resource Block

Arithmetik-Block

AI-Block 1

Input-Selector-Block

AI-Block 2

Signal-Charact.-Block

PID Block

Integrator-Block

Endress+Hauser
Service-Parameter
L00-FMU4XXXX-02-00-00-YY-006

The highlighted parameters can be edited by remote operation.

Endress+Hauser

31

Operation

Prosonic M - FOUNDATION Fieldbus

5.2

Operation with the display and operating module


VU331

The LCD module VU 331 for display and operation is located beneath the housing cover. The
measured value is legible through the glass in the cover. Open the cover to operate the device.
LCD
(liquid crystal display)

ENDR
MICR ESS+
OPIL HAUS
OT
:
II ER

Order
Code:
Ser.-No.

65

A >70C

: t
>85C

Made in Germany

IP

Maulburg

Messbe
Measuri
reich
ng
range
U 16...36
max.
4...20
20
m
mA V DC

Symbols
ENDRESS + HAUSER

3 keys
snap-fit

L00-FMxxxxxx-07-00-00-en-001

5.2.1

Display appearance
position in menu
label

measured value
display

symbol

selection list

value

bargraph

unit

group selection

position in menu
label

help texts

envelope
curve

function with
free parameter

envelope curve
display

L00-FMxxxxxx-07-00-00-en-002

In the measured value display, the bargraph corresponds to the output.


The bargraph is segmented in 10 bars. Each completely filled bar represents a change of 10% of the
adjusted span.

32

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Operation

5.2.2

Display symbols

The following table describes the symbols that appear on the liquid crystal display:
Sybmol

Meaning
ALARM_SYMBOL
This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a
warning.
LOCK_SYMBOL
This lock symbol appears when the instrument is locked,i.e. if no input is possible.
COM_SYMBOL
This communication symbol appears when a data transmission via e.g. HART, PROFIBUS PA or
FOUNDATION Fieldbus is in progress.
SIMULATION_SWITCH_ENABLE
This communication symbol appears when simulation in FOUNDATION Fieldbus is enabled via the DIP
switch.

5.2.3

Function of the keys

Key(s)

Meaning

O or V

Navigate upwards in the selection list


Edit numeric value within a function

S or W

Navigate downwards in the selection list


Edit numeric value within a function

X or Z
F
O and F
or
S and F
O and S and F

Endress+Hauser

Navigate to the left within a function group

Navigate to the right within a function group, confirmation.

Contrast settings of the LCD

Hardware lock / unlock


After a hardware lock, an operation of the instrument via display or
communication is not possible!
The hardware can only be unlocked via the display. An unlock parameter must
be entered to do so.

33

Operation

Prosonic M - FOUNDATION Fieldbus

5.2.4

The operating menu

Function codes
For easy orientation within the function menus, for each function a position is shown on the display.

005
Function group

Function
L00-FMU4xxxx-07-00-00-en-001

The first two digits identify the function group:


basic setup
00
safety settings
01
linearisation
04
...
The third digit numbers the individual functions within the function group:
tank shape
002
medium property
003
process cond.
004
...
Hereafter the position is always given in brackets (e.g. "tank shape" (002)) after the described
function.
basic setup

34

00

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Operation

Navigation within the menu

ENDRESS + HAUSER

2x

F
O

basic setup

temperature
linearisation

...

tank shape

safety settings

>3 s

dome ceiling
horizontal cyl

medium property

Group Selection

liquid
solid<4mm

stilling well

solid>4mm

sphere

Return to

unknown

bypass
flat ceiling

...

no ceiling
...
L00-FMU4xxxx-19-00-00-en-018

1.

Change from Measured Value Display to Group Selection by pressing F.

2.

Press S or O to select the required Function Group and confirm by pressing F.


The active selection is marked by a in front of the menu text.

3.

Activate Edit mode with O or S .


Selection menus
a. Select the required Parameter in selected function with S oder O .
b. F confirms selection; appears in front of the selected parameter.
c. F confirms the edited value; system quits edit mode.
d. O and S (= Q) interrupts selection; system quits edit mode.
Typing in numerals and text
a. Press O or S to edit the first character of the numeral / text.
b. F positions the cursor at the next character; continue with a. until you have completed
your input.
c. If a symbol appears at the cursor, press F to accept the value entered; system quits edit
mode.
d. If a symbol appears at the cursor, press F to return to the previous character (e.g. for
correction of entries).
e. O and S (= Q) interrupts selection; system quits edit mode.

Endress+Hauser

4.

Press F to select the next function.

5.

Press O and S (= Q) once; return to previous function.


Press O and S (= Q) twice; return to Group Selection.

6.

Press O and S (= Q) to return to Measured value display.

35

Operation

Prosonic M - FOUNDATION Fieldbus

5.3

Operation with an Endress+Hauser operating program

5.3.1

ToF Tool Fieldtool Package

The ToF Tool is a graphic and menu-guided operating program for measuring devices from
Endress+Hauser. It is used for the commissioning, data storage, signal analysis and documentation
of the devices. The following operating systems are supported: WinNT4.0, Win2000 and
Windows XP. You can set the parameters of the device specific blocks via the ToF Tool.
The ToF Tool supports the following functions:
Configuration of transmitters in online operation
Singal analysis via envelope curve
Tank linearisation
Loading and saving device data (upload/download)
Documentation of the measuring point
Connection options:
via the FXA193/FXA291 service interface

36

Note!
You can use the ToF Tool to configure the metrological parameters for devices with "FOUNDATION
Fieldbus signal". You need an FF configuration program to be able to configure all the FF-specific
parameters and to integrate the device into a FF network (see sections 5.1.1 and 5.1.2).

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

5.3.2

Operation

FieldCare

FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare,
you can configure all Endress+Hauser devices as well as devices from other manufacturers that
support the FDT standard. The following operating systems are supported: WinNT4.0, Win2000
and Windows XP.
Functions
FieldCare supports the following functions:
Configuration of transmitters in online operation
Singal analysis via envelope curve
Tank linearisation
Loading and saving device data (upload/download)
Documentation of the measuring point
Connection with FXA193 (RS232C)
ToF Tool-Fieldtool Package
FieldCare

FXA193
RS232C

L00-FMxxxxxx-04-00-00-yy-023

For details refer to Technical Information TI063D (FXA193).

Connection with FXA291 (USB)


ToF Tool-Fieldtool Package
FieldCare

ToF
Adapter
FXA291

Commubox
FXA291

USB

L00-FMxxxxxx-04-00-00-yy-024

For details refer to:


Technical Information TI405C (Commubox FXA291)
Operating Instructions KA271 (ToF Adapter FXA291)

Endress+Hauser

37

Operation

Prosonic M - FOUNDATION Fieldbus

Menu-guided commissioning

MicropilotM-en-305

Signal analysis via envelope curve

MicropilotM-en-306

38

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Operation

Tank linearisation

MicropilotM-en-307

Endress+Hauser

39

Operation

Prosonic M - FOUNDATION Fieldbus

5.4

Operation with a FOUNDATION Fieldbus


configuration program

5.4.1

FOUNDATION Fieldbus configuration programs

The user can obtain special configuration and operating programs offered by different manufacturers
for use in configuration. These can be used for configuring both the FOUNDATION Fieldbus
functions and all the device-specific parameters. The predefined function blocks allow uniform
access to all the network and fieldbus device data.

5.4.2

Device Description files

File names
You will need the following files for commissioning and network configuration:
Device Description files: *.sym, *.ffo
These files describe the structure of the blocks and their parameters. They offer guided setups with
the help of menus and methods.
Capability file: *.cff
This file enables offline configuration and describes the device capability in terms of
communication stack and function blocks.
The file names consist of the following parts:
Device Revision (0C3)1)
DD Revision (0C4)1 (use the most current version)
CFF Revision (use the most current version)
Example:
Device Revision (0C3) = 03
DD Revision (0C4) = 01
CFF Revision = 02
-> files to be used: "0301.sym", "0301.ffo", "030102.cff"
Directory structure
The files are normally stored in the following directory structure:
/452B48/1011/*.sym
*.ffo
*.cff
The directory names have the following meaning:
452B48: manufacturer ID of Endress+Hauser
1011: device ID of Prosonic M
Source of supply

1)

40

Host System

Source of supply for the Device Description and Network Configuration files

ABB (Field Controller 800)


Allen Bradley (Control Logix)
Endress+Hauser (ControlCare)
Honeywell (Experion PKS)
Invensys
SMAR (System 302)

www.endress.de (-> Download -> Media type = "Software", "Device Drivers")


CD-ROM (Endress+Hauser order code: 56003896)
www.fieldbus.org

Emerson (Delta V)

www.easydeltav.com

"Device Revision" (0C3) and "DD Revision" (0C4) can be obtained through the display and operating module VU331. For details refer to section 5.2: "Operation
with the display and operating module VU331"

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Operation

Host System

Source of supply for the Device Description and Network Configuration files

Yokogawa (CENTUM CS 3000)

www.yokogawa.com

5.4.3

Representation of parameters

A FOUNDATION Fieldbus configuration tool offers two types of parameter representation:


Representation by parameter name
Examples: "PAROPERATIONCODE", "PARRESET"
Representation by parameter label
(identical to the labels on the display module VU331 and in an Endress+Hauser operation tool)
Examples: "unlock parameter", "reset"

Endress+Hauser

41

Operation

Prosonic M - FOUNDATION Fieldbus

5.5

Operation with the handheld terminal DXR375/FC375

5.5.1

Connection

The handheld terminal is directly connected to the FOUNDATION Fieldbus communication line.
An additonal communication resistor is not required.

5.5.2

Device Descriptions

Make sure you have loaded the valid Device Description files (DDs). DDs can be downloaded from
the internet at "www.fieldcommunicator.com". The DDs can also be updated by the update
functionality of the DXR375/FC375.

5.5.3

User interface

The device parameters are arranged in blocks. The handheld terminal DXR375/FC375 uses this
block structure to access the parameters. You can navigate within the structure by the arrow keys
and the "Enter" key. Alternatively, you can use the touch-screen functionality of the handheld
terminal for navigation. (Double-click on a name opens the respective block or parameter).

42

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

5.5.4

Operation

Example

9
LAS
Fieldbus Live Device List
Number of Devices found = 1
Tag

basic setup
tank shape: dome ceiling

dsdmdm
df das.
asdas fa
asas la.

Address

E+H_PROSONIC_M_XXXXXXX
375 Field Communicator

247
252

dome ceiling
horizontal cyl
bypass
stilling well
flat ceiling
sphere
no ceiling
NEXT

HELP

Page
Dn

Delete

9
LAS
Prosonic M E+H_PROSONIC_M_XXXXXX
Endress+Hauser Device Revision 4
Block Type Actual Mode
Block Tag
dsdmdm
df das.
asdas fa
asas la.

RESOURCE...
SENSOR_B...
DIAGNOSTI...
DISPLAY_B...
ANALOG_IN...
ANALOG_IN...

CANCEL

RES_BL...
Custom
Custom
Custom
AI
AI

Auto
OOS
OOS
OOS
OOS
OOS

basic setup
tank shape: dome ceiling
dome ceiling
horizontal cyl
bypass
stilling well
flat ceiling
sphere
no ceiling
NEXT

CANCEL

HELP

Page
Dn

9
LAS
Prosonic M E+H_PROSONIC_M_XXXXXX
Endress+Hauser Device Revision 4
Block Tag
Block Type Actual Mode
dsdmdm
df das.
asdas fa
asas la.

RESOURCE...
SENSOR_B...
DIAGNOSTI...
DISPLAY_B...
ANALOG_IN...
ANALOG_IN...

RES_BL...
Custom
Custom
Custom
AI
AI

Auto
OOS
OOS
OOS
OOS
OOS

basic setup
medium property: liquid
unknown
liquid
solid<4mm
solid>4mm

NEXT

CANCEL

HELP

Delete

9
LAS
Prosonic M E+H_PROSONIC_M_XXXXXX
SENSOR_BLOCK_XXXXXXXXXXXXXXXX
Label
Value
Units
dsdmdm
df das.
asdas fa
asas la.

Process
Status
Other
All
Calibration Met...

Page
Dn

9
LAS
Prosonic M E+H_PROSONIC_M_XXXXXX
SENSOR_BLOCK_XXXXXXXXXXXXXXXX
Label
Value
Units
dsdmdm
df das.
asdas fa
asas la.

basic setup
method completed successfully

Process
Status
Other
All
Calibration Met...
FINISH CANCEL

HELP

Delete

9
LAS
Prosonic M E+H_PROSONIC_M_XXXXXX
SENSOR_BLOCK_XXXXXXXXXXXXXXXX
Label
Value
Units
dsdmdm
df das.
asdas fa
asas la.

basic setup
safety settings
ackn. alarm
temperature
linearisation
extended calibr.

Delete

L00-FMU4xxxx-07-00-00-yy-010

Endress+Hauser

43

Commissioning

Prosonic M - FOUNDATION Fieldbus

Commissioning

This chapter consists of the following sections:


6.1 Function check
6.2 Unlocking the device
6.3 Parameter reset
6.4 Commissioning with display and operating module VU331
6.5 Commissioning with Endress+Hauser operating software
6.6 Commissioning with FOUNDATION Fieldbus configuration tool
6.7 Commissioning with handheld terminal DXR375/FC375

6.1

Function check

Make sure that all final checks have been completed before you start up your measuring point:
Checklist Post installation check (see page 25).
Checklist Post connection check (see page 29).

6.2

Unlocking the device

Before commissioning, make sure that the device is not locked against parameter changes. On
delivery, the device is unlocked. In other cases, however, it may have been locked in one of the
following ways:

6.2.1

DIP switch (under the housing cover)

Locking and unlocking

END
RES

Messbe
Measur reich
ing

II

IP
T

Maulburg

range
U 16...36
max.
4...20
20
m
mAV DC

65

A >70C

: t
>85C

Made in Germany

Order MICR
S+HA
Code:
OPIL
Ser.-No
OT USE
.:

default settings:
write protection OFF
simulation OFF

on
off
SIM WP

write protection
on
off
SIM WP
simulation
L00-FMxxxxxx-19-00-00-en-002

WP = on: parametrization locked


WP = off: parametrization unlocked
SIM = on: simulation possible in Analog Input Block by configuration tool
SIM = off: simulation not possible in Analog Input Block by configuration tool

Parameters affected
Locking by the DIP switch affects all parameters.

44

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

6.2.2

Commissioning

Key combination (display and operating module VU331)

Locking
Press S, O and F simultaneously.
Unlocking
If you try to change a parameter, the following appears:

L00-fmrxf0a4-20-00-00-de-001

Press S, O and F simultaneously. The "unlock parameter" (0A4) function appears.


Enter "2457". Now parameters can be changed.
Parameters affected
Locking by the key combination affects the following parameters:
Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block)
Endress+Hauser service parameters

6.2.3

Locking parameter

Locking
Enter a number other than "2457" into the "unlock parameter" (0A4) function.
(FOUNDATION Fieldbus: Diagnsotic Block, parameter PAROPERATIONMODE)
Unlocking
Enter "2457" into the "unlock parameter" (0A4) function.
(FOUNDATION Fieldbus: Diagnostic Block, parameter PAROPERATIONMODE)
Parameters affected
Locking by the locking parameter affects the following parameters:
Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block)
Endress+Hauser service parameters

Endress+Hauser

45

Commissioning

Prosonic M - FOUNDATION Fieldbus

6.3

Resetting the device

It is advisable to reset the device parameters before the commissioning if you want to use a device
with an unknown history.

6.3.1

Resetting the parameters of the FOUNDATION Fieldbus function blocks

Parameters affected
all parameters of the FOUNDATION Fieldbus function blocks

Sensorblock
Diagnoseblock
Display-Block

Resource Block

Arithmetik-Block

AI-Block 1

Input-Selector-Block

AI-Block 2

Signal-Charact.-Block

PID Block

Integrator-Block

Endress+Hauser
Service-Parameter
L00-FMU4XXXX-02-00-00-YY-007

Performing the reset


Resource Block, parameter RESTART; select the option "defaults".

6.3.2

"
!

Resetting the parameters of the transducer blocks

Caution!
A reset may lead to impairment of the measurement. As a rule, a basic calibration is required after
a reset.
Note!
The default values of each parameter are shown in bold in the menu overview in the appendix.
In order to carry out the reset, enter the number "33333" in the "reset" (0A3) function in the
"diagnostics" (0A) function group.
(FOUNDATION Fieldbus: Diagnostic Block, Parameter PARRESET (reset))

Parameters affected
all parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block)

Sensorblock
Diagnoseblock
Display-Block

Resource Block

Arithmetik-Block

AI-Block 1

Input-Selector-Block

AI-Block 2

Signal-Charact.-Block

PID Block

Integrator-Block

Endress+Hauser
Service-Parameter
L00-FMU4XXXX-02-00-00-YY-008

Effects of the reset


All customer parameters are reset to their default values.
Customer interference echo suppression is not deleted.

46

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Commissioning

Linearisation is switched to "linear", but the table values are kept. The table can be switched
back on in the "linearisation" (04) function group in the "linearisation" (041) function.
(FOUNDATION Fieldbus: Sensor Block, Parameter PARLINEARISATION (linearisation))
Performing the reset
"diagnostics" (0A) function group, "reset" (0A3) function; enter "33333"
(FOUNDATION Fieldbus: Diagnostic Block, parameter PARRESET)

6.3.3

Resetting an interference echo suppression (tank map)

It is always adivable to reset the interference echo suppression (tank mapping) when:
a device with an unknown history is used
an incorrect suppression was input
Resetting the tank map with the VU331
1.

In the "extended calibr." (05) function group select the "selection" (050) function.

2.

Select "extended map."

3.

Go to the "cust. tank map" (055) function and select the required option:
"reset": deletes the existing tank map.
"inactive": deactivates the tank map but does not delete it. It can be re-activated when
required.
"active": activates the tank map.

Resetting the tank map with an Endress+Hauser operating program


1.

In the function group "extended calibr." select the "cust. tank map" (055) function.

2.

Select the required option ("reset", "inactive" or "active")

Resetting the tank map with a FOUNDATION Fieldbus configuration tool

Endress+Hauser

1.

In the Sensor Block select the parameter PARCUSTTANKMAP (cust tank map).

2.

Select the required option ("reset", "inactive" or "active").

47

Commissioning

Prosonic M - FOUNDATION Fieldbus

6.4

Commissioning by the display and operatig module


VU331

6.4.1

Power up instrument

After switching on the supply voltage, the


instrument is first initialised.

L00-fmp-fxxx-20-00-00-en-003

Then the following appear for approximately


five seconds:
Device type
Software version
Type of digital communication signal

L00-fmuxfxxx-20-00-00-de-002

Press F to exit this display.


On first power-up, you are requested to select
the language for the display texts.

L00-fmrxf092-20-00-00-en-001

Then you are requested to select the unit of


length for your measurements.

L00-fmrxf0c5-20-00-00-en-001

A measured value is displayed. This is NOT


equivalent to the level in your tank. Firstly carry
out a basic calibration.
L00-fmrxf000-20-00-00-en-001

Press F to switch to the group selection.


Press F again to start the basic calibration.

L00-fmrxfg00-20-00-00-en-001

The "Basic setup" (00) function group lists all the functions which are required for a standard
measurement task to commission the Prosonic M. When you have completed your input for a
function, the next function appears automatically. In this way, you are guided through the complete
calibration.

48

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

6.4.2

Commissioning

Application parameters

Function "tank shape" (002)


In this function, select one of the following options:

dome ceiling

horizontal cyl

bypass

ENDRESS+HAUSER
Prosonic M

no ceiling
e.g. dumps, open levels
chanels, weirs

sphere

stilling well
(ultrasonic guide pipe)

flat ceiling

L00-FMU4xxxx-14-00-06-en-001

Function "medium property" (003)


Set the medium type in this function.
You have the following options:
unknown (e.g. pasty media such as greases, creams, gels etc.)
liquid
solid, grain size < 4mm (fine)
solid, grain size > 4mm (coarse)

Endress+Hauser

49

Commissioning

Prosonic M - FOUNDATION Fieldbus

Function "process conditions" (004)


For this function, you have the following options:
standard liquids

calm surface

turb. surface

For all fluid applications which do not


fit in any of the following groups.

Storage tanks with immersion tube or


bottom filling

Storage / accumulation tanks with


uneven surface due to free filling,
mixing nozzles or small bottom stirrers

L00-FMU4xxxx-14-00-00-xx-001

The filters and output damping are set


to average values.

add. agitator
Moving surfaces (poss. with vortex
formation) due to agitators

L00-FMU4xxxx-14-00-00-xx-003

Special filters for stabilising the input


signal are set to large values.
-> Stable measured value
-> Medium reaction time

50

The averaging filters and output


damping are set to large values.
-> Stable measured value
-> Accurate measurement
-> Slow reaction time

fast change
Rapid level change, particularly in
small tanks

L00-FMU4xxxx-14-00-00-xx-004

The averaging filters are set to small


values.
-> Rapid reaction time
-> Possibly unstable measured value

L00-FMU4xxxx-14-00-00-xx-002

Special filters for stabilising the input


signal are activated.
-> Stable measured value
-> Medium reaction time

standard solid
For all bulk solids applications which
do not fit in any of the following
groups.

L00-FMU4xxxx-14-00-00-xx-006

The filter and output damping are set


to average values.

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Commissioning

solid dusty
Dusty bulk solids

conveyor belt
Bulk solids with rapid level change

Test: no filter
All the filters can be switched off for
purposes of service and diagnosis.

ENDRESS+HAUSER
Prosonic M

L00-FMU4xxxx-14-00-00-xx-007

The filters are set to detect even


relatively weak signals.

Endress+Hauser

L00-FMU4xxxx-14-00-00-xx-005

The averaging filters are set to small


values.
-> Rapid reaction time
Possibly unstable measured value

All filters off

51

Commissioning

Prosonic M - FOUNDATION Fieldbus

6.4.3

Empty and full calibration

BD
SD

20 mA
100%
D
E F

4 mA
0%
L00-FMU4xxxx-19-00-00-yy-019

Function "empty calibration" (005)


In this function, enter the distance E from the sensor membrane to the minimum level (zero point).

"

Caution!
With dished boiler heads or conical outflows, the zero point should not be deeper than the point at
which the ultrasonic wave impinges on the tank bottom.
Function "blocking distance" (059)
In this function the blocking distance (BD) of the sensor is displayed.

"
!

Caution!
When entering the full calibration (span), please take into account, that the maximum level may not
project into the blocking distance (BD)
Note!
After basic calibration, enter a safety distance (SD) in the "safety distance" (015) function. If the
level is within this safety distance, the Prosonic M signals a warning or an alarm, depending on your
selection in the "in safety distance" (016) function.
Function "full calibration" (006)
In this function, enter the span F, i.e. the distance from the minimum level to the maximum level.

52

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

6.4.4

Commissioning

Interference echo suppression (tank mapping)

Function "dist./measured value" (008)


In the "dist./meas.value" (008) function, the measured distance D from the sensor membrane
to the product surface is displayed together with level L. Check these values.
Function "check distance" (051)
The mapping is initialized by this function.

L00-FMR2xxxx-14-00-06-en-010

Select
"distance=ok" if the correct distance is displayed. Any echoes closer to the sensor will be
suppressed by the following interference echo suppression.
"dist. too small" if the displayed distance is too small. In this case, the signal comes from an
interference echo which will be suppressed.
"dist. too big" if the displayed distance is too large. This error cannot be cancelled by suppressing
the interference echo. This means that the following two functions are skipped. Check the
application parameters "tank shape" (002), "medium proerty" (003) and "process
cond." (004) and the "empty calibr."(005) in the "basic setup" (00) function group.
"dist. unknown" if you do not know the actual distance. This means that the following two
functions are skipped.
"manual" if you want to specify the suppression area yourself in the following function.
Function "range of mapping" (052)
The suggested suppression area is displayed in this function. The reference point is always the sensor
membrane. You can still edit the value. With manual suppression, the default value is 0 m.

"

Endress+Hauser

Caution!
The suppression range must end 0.5 m in front of the echo of the actual level. With an empty tank,
do not enter E but E 0.5 m.

53

Commissioning

Prosonic M - FOUNDATION Fieldbus

Function "start mapping" (053)


You have the following options for this function:
off: Nothing is suppressed.
on: Starts suppression.

Note!
If a mapping already exists, it will be overwritten up to the distance specified in the "range of
mapping" (052) function. Beyond this distance the existing mapping remains unchanged.
Function dist./measured value (008)
After suppression, the measured distance D from the sensor membrane to the product surface is
displayed together with the level. Check that the values correspond to the actual level and/or the
actual distance.
The following cases may occur:
Distance correct Level correct -> End of basic calibration
Distance incorrect Level incorrect -> An additional interference echo suppression must be
carried out. Go back to the "check distance" (051) function.
Distance correct Level incorrect -> Check the value of the "empty calibr." (005) function.
Rcksprung zur Gruppenauswahl
Nach der Strechoausblendung ist der Grundabgleich beendet und das Gert springt automatisch
in die Gruppenauswahl zurck.

54

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Commissioning

6.4.5

Envelope curve

After the basic setup, an evaluation of the measurement with the aid of the envelope curve
("envelope curve" (0E) function group) is recommended.
Funxtion "plot settings" (0E1)
In this function, select whether you want to display
just the envelope curve
The envelope curve and the echo evaluation line FAC
The envelope curve and interference echo suppression (map)

Note!
The FAC and the interference echo suppression (map) are explained in BA 240F "Prosonic M Description of Instrument Functions"
Function "recording curve" (0E2)
In this function, specify whether you want to display
an individual envelope curve
The current envelope curve, with cyclical refreshment.
Function "envelope curve display" (0E3)
The envelope curve is displayed in this function. You can use it to obtain the following information:

full calibr.

quality of
evaluated echo

evaluated echo
is marked

empty calibr.

envelope curve
only

minimum distance
of the plot

map

distance of
evaluated echo

interference echo

maximum distance
of the plot

level echo

envelope curve and


interference echo
suppression (map)

L00-FMU4xxxx-07-00-00-en-003

Check that the following conditions are fulfilled:


The echo quality at the end of measuring range should be at least 10dB.
There should be practically no interference echoes in front of the level signal.
If interference echoes cannot be avoided, they must be below the suppression curve.

Endress+Hauser

Note!
If the cyclical envelope curve display is still active on the display, the measured value is updated at
a slower cycle time. We therefore advise you to exit the envelope curve display after optimising the
measuring point. To do this, press F. (The instrument does not leave the envelope curve display
automatically.)

55

Commissioning

Prosonic M - FOUNDATION Fieldbus

Navigation in the envelope curve display


Using navigation, the envelope curve can be scaled horizontally and vertically and shifted to the left
or the right. The active navigation mode is indicated by a symbol in the top left hand corner of the
display.
Horizontal Zoom mode:
- horizontal zoom in

OE3

- horizontal zoom out


Move mode:
- moved to the left
- moved to the right
Vertical Zoom mode:

- vertical zoom (4 steps)


L00-FMxxxxxx-07-00-00-en-004

Horizontal Zoom mode


Firstly, go into the envelope curve display. Then press O or S to switch to the envelope curve
navigation. You are then in Horizontal Zoom mode. Either
or
is displayed.
O increases the horizontal scale.
S reduces the horizontal scale.

O
L00-FMxxxxxx-07-00-00-yy-007

Move mode
Then press F to switch to Move mode. Either
O shifts the curve to the right.
S shifts the curve to the left.

or

is displayed.

L00-FMxxxxxx-07-00-00-yy-008

Vertical Zoom mode


Press F once more to switch to Vertical Zoom mode.
options.
O increases the vertical scale.
S reduces the vertical scale.
The display icon shows the current zoom factor (

is displayed. You now have the following

to

).

O
L00-FMxxxxxx-07-00-00-yy-009

56

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Commissioning

Exiting the navigation


Press F again to run through the different modes of the envelope curve navigation.
Press O and S to exit the navigation. The set increases and shifts are retained. Only when you
reactivate the "recording curve" (0E2) function the display settings return to their standard
values.

Endress+Hauser

57

Commissioning

Prosonic M - FOUNDATION Fieldbus

6.5

Basic Setup with the Endress+Hauser operating


program

To carry out the basic setup with the operating program, proceed as follows:
Start the operating program and establish a connection.2)
Select the "basic setup" function group in the navigation window.
The following display appears on the screen:
Basic Setup step 1/4:
measured value

ProsonicM-en-301

The "Next" button moves you to the next screen display:

2)

58

Note!
Each parameter that is changed must be confirmed with the RETURN key!

If the connection can not be established, make sure that you use the latest versin of the operating program.

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Commissioning

Basic Setup step 2/4:


Enter the application parameters:
tank shape
medium property
process cond.

ProsonicM-en-412

Basic Setup step 3/4:


If "dome ceiling", "horizontal cyl", "..." is selected in the "tank shape" function, the following
display appears on the screen:
empty calibr.
full calibr.

ProsonicM-en-303

Endress+Hauser

59

Commissioning

Prosonic M - FOUNDATION Fieldbus

Basic Setup step 4/4:


This step starts the tank mapping
The measured distance and the current measured value are always displayed in the header

ProsonicM-en-304

6.5.1

Signal analysis via envelope curve

After the basic setup, an evaluation of the measurement using the envelope curve is recommended.

MicropilotM-en-306

60

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

6.5.2

Commissioning

User-specific applications (operation)

For details of setting the parameters of user-specific applications, see separate documentation
BA240F/00/en "Prosonic M - Description of Instrument Functions" on the enclosed CD-ROM.

Endress+Hauser

61

Commissioning

Prosonic M - FOUNDATION Fieldbus

6.6

Commissioning with a FOUNDATION Fieldbus


configuration tool

Note!
For commissioning of the device with a FOUNDATION Fieldbus configuration tool you need to
know the DEVICE_ID, which consists of the following parts:
Device_ID = 452B481011-XXXXXXXX
whereby:
452B48 ID code for Endress+Hauser
1011 ID code for Prosonic M
XXXXXXXX Device serial number, as printed on the nameplate

6.6.1

Fist setup

1.

Open the configuration tool and load the Device Descriptions (*.ffo, *.sym and - if required by
the tool - *.cff). Ensure you use the correct files (see chapter 5.4).

2.

The first time it is connected, the device reports as follows:

NI-FBUS-FMU4x-en-001

3.

62

Identify the device using the DEVICE_ID and assign the desired field device tag name
(PD_TAG).
Factory setting: PD_TAG = E+H_PROSONIC_M_XXXXXXXX

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Commissioning

6.6.2

Parametrization of the Resource Block (Start Index: 400)

1.

Enter the desired block name (optional).


Factory setting: RESOURCE_XXXXXXXX

2.

Opern the Resource Block

3.

On delivery, write protection is disabled so that you can access the write parameters via
FOUNDATION Fieldbus. Check this status by the parameter WRITE_LOCK:
Write protectin activated: WRITE_LOCK = LOCKED
Write protection deactivated: WRITE_LOCK = NOT LOCKED
Deactivate the write protection if necessary, see page 44.

4.

Set the operating mode to AUTO in the parameter group MODE_BLK (parameter TARGET).

6.6.3

Parametrization of the Sensor Block (Start Index: 2000)

1.

Enter the desired block name (optional)


Factory setting: SENSOR_XXXXXXXX

2.

Open the Sensor Block. The following display appears:

NI-FBUS-FMU4x-en-002

Hinweis!
There are two possibilities to edit the parameters of the block:
A parameter from the list can be opened for editing by a double click.
You can open one of the FOUNDATION Fieldbus methods. Each method guides you
automatically through a number of parameters which are required for a specific configuration
task. The following sections describe the parametrization by the "basic setup" method.
3.

Endress+Hauser

Open the FOUNDATION Fieldbus method "basic setup":

63

Commissioning

Prosonic M - FOUNDATION Fieldbus

NI-FBUS-FMU4x-en-003

4.

The method contains the following parameters3):


a. Application parameters (see section 6.4.2)
PARTANKSHAPE (tank shape)
PARMEDIUMCONDITION (medium property)
PARPROCESSCONDITION (process condition)
b. Empty and full calibration (see section 6.4.3)
PAREMPTYCALIBRATION (empty calibration)
PARFULlCALIBRATION (full calibration)
c. Interference echo suppression (see section 6.4.4)
PARCHECKDISTANCE (check distance)
PARSUPPRESSIONDISTANCE (range of mapping)
PARSTARTMAPPINGRECORD (start maping)
PARPRESMAPRANGE (pres. map. dist.)
PARCUSTTANKMAP (cust. tank map)

3)

64

5.

Set the operating mode to AUTO in the parameter group MODE_BLK (parameter TARGET).
Otherwise the measured value can not be processed correctly by the connected Analog Input
Block.

6.

If measuring errors occur or if the measuring value seems unreliable, it is advisable to check
the quality of the measurement by the envelope curve display. This can be done in two
different ways:
by the display and operating module VU331 (see section 6.4.5)
by an Endress+Hauser operating program (see section 6.5.1)

In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display:
- parameter names (e.g. "PARTANKSHAPE")
- label texts (e.g. "tank shape")

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Commissioning

6.6.4

Parametrization of the Analog Input Blocks

Prosonic M has two Analog Input Blocks that can be assigned to the various process variables. The
following descripiton provides an example for the Analog Input Block 1 (Start Index 500).
1.

Enter the desired block name (optional).


Factory setting: ANALOG_INPUT_1_XXXXXXXX

2.

Open the Analog Input Block.

3.

Set the operating mode to OOS (Out of Service) in the parameter group MODE_BLK
(parameter TARGET).

4.

Using the parameter CHANNEL select the process variable that is to be used as the input value
for the function block algorithm (scaling and limit value monitoring). The following settings
are possible:
CHANNEL = 1: level
CHANNEL = 2: distance
CHANNEL = 3: temperature

5.

In the parameter gorup XD_SCALE select the desired engineering unit and the block input
range (measuring range) for the process variable in question (see the example below).

" Caution!
Make sure that the selected unit is suitable for the measurement variable of the selected
process variable. Otherwies the parameter BLOCK_ERROR will display the error message
"Block Configuration Error" and the block operating mode cannot be set to AUTO.
6.

In the L_TYPE prameter, select the mode of linearization for the input variable (Direct,
Indirect, Indirect Sq Root). For details refer to section 11.7 in the Appendix.

" Caution!
Note that with the type of linearization "Direct" the configuration of the parameter group
OUT_SCALE must agree with the configuration of the parameter group XD_SCALE.
Otherwise the block operating mode cannot be set to AUTO. Such incorrect configuration is
indicated in the parameter BLOCK_ERROR by the "Block Configuration Error" message.
Example:
The measuring range of the sensor is 0 to 10 m.
The output range to the automation system should be 0 to 10 m, too.
The following settings are to be made:
Analog Input Block 1, Parameter CHANNEL -> "1" (measured level)
Parameter L_TYPE -> DIRECT
Parameter group XD_SCALE
XD_SCALE 0% -> 0
XD_SCALE 100% -> 10
XD_SCALE_UNIT -> m
Parameter group OUT_SCALE
OUT_SCALE 0% -> 0
OUT_SCALE 100% -> 10
OUT_SCALE_UNIT -> m
7.

Endress+Hauser

If required, use the following parameters to define the limit values for alarm and warning
messages:
HI_HI_LIM -> Limit value for the upper alarm
HI_LIM -> Limit value for the upper warning
LO_LIM -> Limit value for the lower warning
LO_LO_LIM -> Limit value for the lower alarm
The limit values entered must be within the value range specified in the parameter group
OUT_SCALE.

65

Commissioning

Prosonic M - FOUNDATION Fieldbus

8.

In addition to the limit values you must also specify the action taken if a limit value is exceeded
using the alarm priorities (parameters HI_HI_PRI, HI_PRI, LO_PRI, LO_LO_PRI). Reporting
to the the fieldbus host system only takes place if the alarm priority is higher than 2. For details
refer to section 11.7 in the Appendix.

6.6.5
1.

Connection of the function blocks

A concluding overall system configuration is essential so that the operating mode of the Analog
Input Block can be set to AUTO and so that the field device is integrated into the system
application. To do this, a configuration software (e.g. you host system software) is used to
connect the function blocks - normally graphically - to the desired control strategy and then
the sequence of the individual process control functions is specified.

NI-FBUS-FMxxx-en-001

Example: Connection of the function blocks with the NI-FBUS Configurator

66

2.

Download the configuration data into the field devices by the download function of the
FOUNDATION Fieldbus configuration tool.

3.

Set the oerating mode of the AI Block to AUTO (parameter group MODE_BLK, parameter
TARGET). However, this is only possible under the following conditions:
The function blocks are correctly connected with each other.
The parametrization of the AI Block is correct (see 6.6.4, steps 5 and 6).
The Resource Block is in operating mode AUTO.

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

6.7

Commissioning

Commissioning with the handheld terminal DXR375/


FC375

The steps of the commissioning procedure are the same as with a FOUNDATION Fieldbus
configuration tool ( Page 62 ff.).
The blocks should be parametrized in the following order:
the RESOURCE BLOCK
the SENSOR BLOCK
(the "basic setup" method can be used for this, see page 43)
the ANALOG INPUT BLOCKS

Endress+Hauser

67

Troubleshooting

Prosonic M - FOUNDATION Fieldbus

Troubleshooting

7.1

System error messages

7.1.1

Current error

Errors which the Prosonic M detects during commissioning or operation are displayed in the
following way:
VU331:
error symbol in the "measured value" (000) function
VU331 or Endress+Hauser operating program:
in the "diagnostics" (0A) function group in the "present error" (0A0) function
Only the highest priority error is displayed; in the case of multiple errors, you can scroll between
the different error messages by pressing O or S.
FOUNDATION Fieldbus:
by the status of the main value in the cyclic data telegram
Diagnostic Block, parameter PARACTUALERROR (present error)

NI-FBUS-FMU4x-en-004

7.1.2

Last error

The last error is displayed in the "diagnostics" (0A) function group in the "previous error"
(0A1) function. This display can be deleted in the "clear last error" (0A2) function.
(FOUNDATION Fieldbus: Diagnsotic Block;
parameters PARLASTERROR and PARCLEARLASTERROR.

68

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Troubleshooting

7.1.3

Types of error

Type of error

Symbol

Meaning
The output signal assumes a value which can be set using the "output
on alarm" (010) function:

Alarm (A)
continuous

Warning (W)

MAX: 110%
MIN: -10%
Hold: last value is on hold
User-specific value

The device continues measurement. An error message is displayed.


flashing

Alarm/Warning (E)

7.1.4

Endress+Hauser

You can define whether the error should behave as an alarm or as a warning.

Error codes

Code

Error description

Action

A102
A110
A152
A160

checksum error

Reset;
If alarm still present after reset, replace electronics

W103

initialising

If the message does not disappear after several seconds, replace the electronics

A106

downloading

Wait; Message disappears after load sequence

A111
A113
A114
A115
A121
A125
A155
A164
A171

electronics defect

Reset;
Check system for EMC, improve as necessary
If alarm still present after reset, replace electronics

A116

download error

Check connection; Restart download

W153

initialising

Wait a few seconds; if error is still displayed, switch the power off and on again

A231

sensor defect

Check connection, if necessary replace HF module or electronics

A281

interruption temperature
sensor

Exchange sensor

A502

Sensor type not detected

Exchange sensor and/or electronics

A512

recording of mapping

Alarm disappears after a few seconds

A521

new sensor type detected

Reset

W601

linearisation curve not


monotone

Correct table (enter monotonously increasing table)

W611

less than 2 linea-risation


points

Enter additional value pairs

W621

simulation on

Switch simulation mode off ["output" (06) function group, "simulation"


(065) function]]

E641

no usable echo

Check basic calibration

E651

level in safety distance risk of overspill

Error disappears when the level leaves the safety distance. Possibly reset the
lock. ["safety settings" (01) function group, "ackn. alarm" (017) function]]

A661

Sensor overtemperature

A671

Linearisation incomplete

Activate linearisation table

W681

current out of range

Carry out basic calibration;


check linearisation

69

Troubleshooting

Prosonic M - FOUNDATION Fieldbus

Code

Error description

W691

Filling noise detected, level ramp is active

7.1.5

Action

Influence of the error codes on the output signal

The following table describes the influence of the error codes on the status of the cyclic output
values as well as on the parameters BLOCK_ERR and XD_ERROR in the Sensor Block.
The output values are linked to the following measuring values:
Primary Value (PV): level/volume
Secondary Value (SV): distance between sensor membrane and surface of the material measured
Third Value (TV): sensor temperature
Code

PV Status
SV Status

PV Substatus
SV Substatus

TV Status

TV Substatus

BLOCK_ER

XD_ERROR

A102

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

W103

Uncertain

Non specific

GOOD

Non specific

Other

Unspecified Err

A106

BAD

Device Failure

BAD

Device Failure

Other

Unspecified Err

A110

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance

Electronic Failure

A111

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

A113

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

A114

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

A115

BAD

Device Failure

BAD

Device Failure

Device needs maintenance now

Unspecified Err

A116

BAD

Device Failure

BAD

Device Failure

Device needs maintenance now

Unspecified Err

A121

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

A125

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

W153

Uncertain

Non specific

GOOD

Non specific

Power up

No Error

A155

BAD

Device Failure

BAD

Device Failure

Device needs maintenace now

Electronic Failure

A160

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

A164

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

A171

BAD

Device Failure

BAD

Device Failure

Memory Failure/
Device needs maintenance now

Electronic Failure

A231

BAD

Device Failure

BAD

Device Failure

Device needs maintenance now

Unspecified Err

E281
Uncertain
(Warning)

Device Failure

BAD

Device FAilure

Device needs maintenance now

Electronic Failure

E281
(Alarm)

BAD

Device Failure

BAD

Device Failure

Device needs maintenance now

Unspecified Err

A502

BAD

Device FAilure

BAD

Device Failure

Device needs maintenance now

Unspecified Err

A512

Uncertain

Non specific

GOOD

Non specific

Other

Unspecified Err

A521

BAD

Device FAilure

BAD

Device Failure

Device needs maintenance now

Unspecified Err

W601

Uncertain

configuration error

GOOD

Non specific

Other

Configuration Error

W611

Uncertain

configuration error

GOOD

Non specific

Other

Configuration Error

W621

Uncertain

Non specific

GOOD

Non specific

simulation active

No Error

70

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Troubleshooting

Code

PV Status
SV Status

PV Substatus
SV Substatus

TV Status

TV Substatus

BLOCK_ER

XD_ERROR

E641
(Alarm)

BAD

Device Failure

GOOD

Non specific

Device needs maintenance now

Unspecified Err

E641
Uncertain
(Warning)

Non specific

GOOD

Non specific

Device needs maintenance now

Unspecified Err

E651
(Alarm)

Device Failure

GOOD

Non specific

Other

Unspecified Err

E651
Uncertain
(Warning)

Non specific

GOOD

Non specific

Other

Unspecified Err

A661
(Alarm)

Device Failure

GOOD

Nopn specific

Device needs maintenance now

Unspecified Err

E661
Uncertain
(Warning)

Non specific

GOOD

Non specific

Device needs maintenacne soon

Unspecified Err

A671

BAD

Device Failure

GOOD

Non specific

Configuration Error

No Error

W691

Uncertain

Non specific

GOOD

Non specific

Other

Unspecified Err

BAD

BAD

Endress+Hauser

71

Troubleshooting

Prosonic M - FOUNDATION Fieldbus

7.2
Error

Application errors

Example

D m/ft (008)

Measured value (00) is


incorrect but measured
distance (008) is correct

F m/ft

Elimination
1. Check empty calibration (005) and
full calibration (006).
(FF: Sensor Block, PAREMPTYCALIBRATION, PARFULLCALIBRATION

100%

expected

actual
E m/ft
t

0%

Measured value (000) and


measured distance (008)
are incorrect

L00-FMR2xxxx-19-00-00-en-019

2. Check linearisation
level/ullage (040)
(FF: Sensor Block, PARLEVELULLAGEMODE)
max. scale(046)
(FF: Sensor Block, PARMAXVOLUME)
diameter vessel (047)
(FF: Sensor Block, PARCYLINDERVESSEL
linearisation table
1. For measurements in bypass or stilling well:
Select the according option in the "tank shape" (002) function.
(FF: Sensor Block, PARTANKSHAPE)
2. Carry out interference echo suppression.

No change in
measured value on filling/
emptying

1. Carry out interference echo suppression.


2. Clean sensor if necessary
100%

3. If necessary, select better installation position


4. If necessary due to wide interference echoes, set function "detection
window" (0A7) to "off".
(FF: Sensor Block, PARDETECTIONWINDOW)

actual

expected
t

0%

L00-FMR2xxxx-19-00-00-en-014

With an uneven surface


(e.g. filling, emptying,
running agitator) the
measured value
may jump sporadically to
higher
levels

1. Carry out interference echo suppression


2. Set the process cond. (004) to "calm surface" or "add. agitator"
FF: Sensor Block, PARPROCESSCONDITION)

100%
actual

3. Increase output damping (058).


(FF: Sensor Block, PAROUTPUTDAMPING)

expected

4. If necessary, select a different installation position and/or a larger sensor

0%

L00-FMR2xxxx-19-00-00-en-015

100%
actual

expected
0%

t
L00-FMR2xxxx-19-00-00-en-016

72

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Error

Troubleshooting

Example

Elimination

On filling/emptying the
measured value drops
100%
expected

1.

Check tank shape (002), e.g. "dome ceiling" or "horizontal cyl."


(FF: Sensor Block, PARTANKSHAPE)

2.

If possible, do not select a central installation position

3.

Possible user stilling well/echo guide pipe

1.

Check application parameters (002), (003) and (004)


(FF: Sensor Block, PARTANKSHAPE, PARMEDIUMCONDITION,
PARPROCESSCONDITION)

actual

0%

L00-FMR2xxxx-19-00-00-en-017

E 641 (echo loss)


100%
eingetreten

2.

If necessary, select a different installation position and/or a larger sensor

3.

Align the sensor parallel to the product surface (particularly for bulk solids
applications)

E 641
erwartet
0%

t
L00-FMR2xxxx-19-00-00-en-018

Endress+Hauser

73

Maintenance and repairs

Prosonic M - FOUNDATION Fieldbus

Maintenance and repairs

8.1

Exterior cleaning

When cleaning the exterior, always use cleaning agents that do not attack the surface of the housing
and the seals.

8.2

Repairs

The Endress+Hauser repair concept assumes that the measuring devices have a modular design and
that customers are able to undertake repairs themselves.
Spare parts are contained in suitable kits. They contain the related replacement instructions.
All the spare parts kits which you can order from Endress+Hauser for repairs are listed with their
order numbers in the section "Spare parts".
For more information on service and spare parts, contact the Service Department at
Endress+Hauser.

8.3

Repairs to Ex-approved devices

When carrying out repairs to Ex-approved devices, please note the following:
Repairs to Ex-approved devices may only be carried out by trained personnel or by the
Endress+Hauser Service.
Comply with the prevailing standards, national Ex-area regulations, safety instructions (XA) and
certificates.
Only use original spare parts from Endress+Hauser.
When ordering a spare part, please note the device designation on the nameplate. Only replace
parts with identical parts.
Carry out repairs according to the instructions. On completion of repairs, carry our the specified
routine test on the device.
Only Endress+Hauser Service may convert a certified device into a different certified variant.
Document all repair work and conversions.

8.4

Replacement

After a complete instrument or electronic module has been replaced, the parameters can be
downloaded into the instrument again via the communication interface. Prerequisite to this is that
the data were uploaded to the PC beforehand using ToF Tool /FieldCare. Measurement can
continue without having to carry out a new setup. Only a linearisation and a tank map (interference
echo suppression) have to be recorded again.

74

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

8.5
10

Maintenance and repairs

Spare parts (housing type F12)

65

65
11
35
EN
DR

PR ES
Ord
OS S+
er
ON HA
Se Cod
r.-N
e
IC US
o.: :

ER

Me
Messbere
asu ic
ring h
ran
ge
U1
ma
x. 2
4...26...36
0m
0m VD
A C

IP

65

A >7

0C

: t
>8

5C

Made in Germany

ina

Maulburg

rm
Te

30

12

65 20

12

R
SE
AU
+H
SS
RE
D
EN

65
40

65
65
55
50

58

65

65

65

58

FMU 40

50
FMU 41

FMU 42/44
FMU 43
L00-FMU4x-00-00-00-yy-007

Endress+Hauser

75

Maintenance and repairs

Prosonic M - FOUNDATION Fieldbus

10 Housing
543120-0022 Housing F12, aluminium, G1/2
543120-0023 Housing F12, aluminium, NPT1/2
543120-0024 Housing F12, aluminium, M20
52001992 Housing F12, aluminium, M20, PA connector
52008556 Housing F12, aluminium, M20, FF connector
52013350 Housing F12, aluminium, coated, M20, 4-wire
52013351 Housing F12, aluminium, coated, M20, metal
52013348 Housing F12, aluminium, coated, G1/2, 4-wire
52013349 Housing F12, aluminium, coated, NPT1/2, 4-wire
11 Hood for terminal compartment
52006026 Cover for the connection compartment F12
52019062 Cover for the connection compartment F12, FHX40
12 Set of screws
535720-9020 Set of screws for housing F12/T12
20 Cover
52005936 Cover F12/T12 aluminium, inspection glass, seal
517391-0011 Cover F12/T12 aluminium, coated, seal
30 Electronics
71025600 electronics FMU4x, Ex, 2-wire HART, V4.0
71025602 electronics FMU4x, Ex, 4-wire HART, V4.0
71025603 electronics FMU4x, Ex, PROFIBUS PA, V4.0
52023759 Electronics Prosonic M, Ex, FF, V2.04
35 Terminal module / power unit
52006197 Terminal module 4-pin, HART, 2-wire with connecting cable
52012156 Terminal module 4-pin, PROFIBUS PA, Foundation Fieldbus
52013304 Power unit, 10.5...32V DC (housing F12) for electronics, 4-wire
52013305 Power unit, 90 ...250V AC (housing F12) for electronics, 4-wire
52015585 Power unit, CSA, 10.5...32V DC (housing F12) for electronics, 4-wire
52015586 Power unit, CSA, 90...250V AC (housing F12) for electronics, 4-wire
40 Display
52005585 Display/operating module VU331
50 Probe with process connection
52010509 Sensor FMU40 G1-1/2
52010507 Sensor FMU40 NPT1-1/2
52010510 Sensor FMU41 G2
52010508 Sensor FMU41 NPT2
52023965 Sensor FMU42
52013543 Sensor FMU43 4", gasket

76

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Maintenance and repairs

71037028 Sensor FMU44, gasket


55 Flanges
52023919 Flange, Uni-DN80/ANSI 3"/JIS 80A, PP
52023920 Flange, Uni-DN80/ANSI 3"/JIS 80A, PVDF
52023921 Flange, Uni-DN80/ANSI 3"/JIS 80A, 316L
52023922 Flange, Uni-DN100/ANSI 4"/JIS 100A, PP
52023923 Flange, Uni-DN100/ANSI 4"/JIS 100A, PVDF
58 Hexagon nut
52000599 Hexagon nut (SW60) G1-1/2, bk, PC
52000598 Hexagon nut (SW70) G2, bk, PC
65 Sealing kit
52010526 Sealing kit FMU4x
Miscellaneous
52010545 Nameplate Prosonic M, modification
Spare parts for FHX40
52018204 Adaption kit housing F12, 2-wire, FHX40
52018205 Adaption kit housing F12, 4-wire, FHX40
52016334 Cable FHX40, 20m

Endress+Hauser

77

Maintenance and repairs

Prosonic M - FOUNDATION Fieldbus

8.6

Spare parts (housing type T12)


25
65
35

10
65
11
EN
D

PR RES
Ord
OS S+
er
Se Cod
ON HA
r.-N
e
IC US
o.: :

FM ER
U

65

A >7

0C

30

Maulburg

IP
T

: t
>8

5C

Made in Germany

Me
Messbere
asu ic
ring h
ran
ge
U1
ma
x. 2
4...26...36
0m
0m VD
A C

12

65 20

12
ER

S
AU

+H

SS

RE

D
EN

65

40

65

65
50

55

65

58

65

58
FMU 40

50

FMU 41

FMU 42/44
L00-FMU4x-00-00-00-yy-008

78

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Maintenance and repairs

10 Housing
543180-1023 Housing T12, aluminium, NPT1/2, PEL
52006204 Housing T12, aluminium, G1/2, PEL, cover
52006205 Housing T12, aluminium, M20, PEL, cover
11 Hood for terminal compartment
52005643 Hood T12
12 Set of screws
535720-9020 Set of screws for housing F12/T12
20 Cover
517391-0011 Cover F12/T12 aluminium, coated, seal
52005936 Cover F12/T12 aluminium, inspection glass, seal
25 Cover for the connection compartment
518710-0020 Cover T3/T12, aluminium, coated, seal
30 Electronics
71025600 electronics FMU4x, Ex, 2-wire HART, V4.0
71025603 electronics FMU4x, Ex, PROFIBUS PA, V4.0
52023759 Electronics Prosonic M, Ex, FF, V2.04
35 Terminal module / power unit
52013302 Terminal module Ex d, 4-pin, 2-wire, HART, T12
52013303 Terminal module Ex d, 2-pin, 2-wire, PROFIBUS PA, Foundation Fieldbus, T12
52018949 Terminal module EEx ia, 4-pin, HART, T12, OVP
52018950 Terminal module EEx ia, 4-pin, PROFIBUS PA, Foundation Fieldbus, T12, OVP
40 Display
52005585 Display/operating module VU331
50 Probe with process connection
52010509 Sensor FMU40 G1-1/2
52010507 Sensor FMU40 NPT1-1/2
52010510 Sensor FMU41 G2
52010508 Sensor FMU41 NPT2
52023965 Sensor FMU42
71037028 Sensor FMU44, gasket
55 Flanges
52023919 Flange, Uni-DN80/ANSI 3"/JIS 80A, PP
52023920 Flange, Uni-DN80/ANSI 3"/JIS 80A, PVDF
52023921 Flange, Uni-DN80/ANSI 3"/JIS 80A, 316L
52023922 Flange, Uni-DN100/ANSI 4"/JIS 100A, PP
52023923 Flange, Uni-DN100/ANSI 4"/JIS 100A, PVDF
52023924 Flange, Uni-DN100/ANSI 4"/JIS 100A, 316L

Endress+Hauser

79

Maintenance and repairs

Prosonic M - FOUNDATION Fieldbus

58 Hexagon nut
52000598 Hexagon nut (SW70) G2, bk, PC
52000599 Hexagon nut (SW60) G1-1/2, bk, PC
65 Sealing kit
52010526 Sealing kit FMU4x
Miscellaneous
52010545 Nameplate Prosonic M, modification

80

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

8.7

Maintenance and repairs

Return

The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g.
for repair or calibration:
Remove all residue which may be present. Pay special attention to the gasket grooves and crevices
where fluid may be present. This is especially important if the fluid is dangerous to health, e.g.
corrosive, poisonous, carcinogenic, radioactive, etc.
Always enclose a duly completed "Declaration of contamination" form (a copy of the Declaration
of contamination is included at the end of this operating manual). Only then can Endress
+Hauser transport, examine and repair a returned device.
Enclose special handling instructions if necessary, for example a safety data sheet as per EN 91/
155/EEC.
Additionally specify:
An exact description of the application.
The chemical and physical characteristics of the product.
A short description of the error that occurred (specify error code if possible)
Operating time of the device.

8.8

Disposal

In case of disposal please seperate the different components according to their material consistence.

8.9

Software history

Software version / date

Changes to software

V 01.02.00 / 01.2002
V 01.02.02 / 03.2003

Original software
Compatible with:

Changes to documentation

ToF Tool
Commuwin II (version 2.05.03 and
higher
HART Communicator DXR 275 (from
OS 4.6) with Rev. 1, DD 1
V 01.02.04/02.2004

FMU 42 added
compatible with HART Communicator
DXR 375

FMU 42 added

V 01.04.00/07.2006

"detection window" function added

"detection window" added


Version: 07.06

can be operated via:


ToF Tool from version 4.50
HART Communicator DXR375 with
Rev. 1, DD1

Description of FOUNDATION Fieldbus


interface completely revised.
Version: 11.06

FOUNDATION Fieldbus Transducer Block


divided into:
Sensor Block
Diagnostic Block
Display Block
Execution time of the function blocks
reduced:
AI: 30 ms
PID: 80 ms
AR: 50 ms
IS: 30 ms
SC: 40 ms
IT: 60 ms

Endress+Hauser

81

Maintenance and repairs

Prosonic M - FOUNDATION Fieldbus

8.10

Contact addresses of Endress+Hauser

Contact addresses can be found on our homepage: www.endress.com/worldwide. If you have any
questions, please do not hesitate to contact your Endress+Hauser representative.

82

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Accessories

Accessories

9.1

Weather protection cover

A Weather protection cover made of stainless steel is recommended for outdoor mounting (order
code: 543199-0001). The shipment includes the protective cover and tension clamp.
m

240 m

70 mm

45

mm

EN
D
MIC RES
RO S+H
PIL AU
OT SE
R
II

r Co
r.-N de:
o.:

IP

Maulburg

Me
Messberei
asuri ch
ng
ran
ge
U 16
ma
x. 20
4...20...36
m
mAV DC

65

A >7

0C

: t
>8

5C

Made in Germany

Se

mm

95

F12 / T12 housing

Orde

135

L00-FMR2xxxx-00-00-06-en-001

9.2

Installation bracket for FMU 40/41


400
120

G
A

120
30

250

16

L00-FMU4x-00-00-00-de-001

for FMU 40, G1: Order No. 942669-0000


for FMU 41, G2: Order No. 942669-0001
suited for NPT 1" and 2" as well

Endress+Hauser

83

Accessories

Prosonic M - FOUNDATION Fieldbus

9.3

Adapter flange
sealing ring
EPDM
(supplied)

sensor

adapter flange

nozzle
L00-FMUX3XXX-00-00-00-en-001

9.3.1

Version with metrical thread (FAU 70 E)


Process Connection
12 DN 50 PN 16 A, flange EN1092-1 (DIN2527 B)
14 DN 80 PN 16 A, flange EN1092-1 (DIN2527 B)
15 DN 100 PN 16, A, flange EN1092-1 (DIN2527 B)
Sensor Connection
3 Thread ISO228 G1-1/2
4 Thread ISO228 G2
Flange Material
2 316L
7 Polypropylene

FAU 70 E

9.3.2

Product designation

Version with conical thread(FAU 70 A)


Process Connection
22 2" 150lbs FF, flange ANSI B16.5
24 3" 150lbs FF, flange ANSI B16.5
25 4" 150lbs FF, flange ANSI B16.5
Sensor Connection
5 Thread NPT1-1/2
6 Thread NPT2
Flange Material
2 316L
7 Polypropylene

FAU 70 A

84

Product designation

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

9.4

Accessories

Cantilever

50
100

20

20
C

25

35

100

22

M8

35

15

6.5

75

105

75

50/
62

L00-FMU4xxxx-06-00-00-yy-005

for Sensor

Material

Order Code

585 mm

250 mm

2 mm

200 mm

FMU 40

316Ti/1.4571

52014132

galv. steel

52014131

316Ti/1.4571

52014136

galv. steel

52014135

316Ti/1.4571

52014134

galv. steel

52014133

316Ti/1.4571

52014138

galv. steel

52014137

FMU 41

1085 mm

750 mm

3 mm

300 mm

FMU 40

FMU 41

The 50 mm or 62 mm orifices serve for the mounting of the FMU 40 or FMU 41 sensor,
respecitvely.
The 22 mm orifice may be used for an additional sensor.

Endress+Hauser

85

Accessories

Prosonic M - FOUNDATION Fieldbus

Mounting Frame

25

100

13

9.5

55

3.2
33.7

60
4
76
100
200

45
6.5

700/1400

20

100
150

130

L00-FMU4x-00-00-00-yy-005

Height

Material

Order Code

700 mm

galv. steel

919791-0000

700 mm

1.4301 (AISI 304)

919791-0001

1400 mm

galv. steel

919791-0002

1400 mm

1.4301 (AISI 304)

919791-0003

9.6

Wall Bracket
3.2
5

33.7

13

25

150

110

213

180

6.5

88

110
150
L00-FMU4x-00-00-00-yy-006

86

Material

Order Code

galv. steel

919792-0000

316Ti/1.4571

919792-0001

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

9.7

Accessories

Mounting bracket for FMU 42/43/44


25

120

~123

119

Material: 1.4301
Order-Code.: 942666-0000

25

11
L00-FMU4x-00-00-00-en-003.eps

9.8

Commubox FXA291

The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (=
Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a
notebook. For details refer to TI405C/07/en.

Note!
For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional
accessory:
Cerabar S PMC71, PMP7x
Deltabar S PMD7x, FMD7x
Deltapilot S FMB70
Gammapilot M FMG60
Levelflex M FMP4x
Micropilot FMR130/FMR131
Micropilot M FMR2xx
Micropilot S FMR53x, FMR540
Prosonic FMU860/861/862
Prosonic M FMU4x
Tank Side Monitor NRF590 (with additional adapter cable)
Prosonic S FMU9x

9.9

ToF Adapter FXA291

The ToF Adapter FXA291 connects the Commubox FXA291 via the USB interface of a personal
computer or a notebook to the following Endress+Hauser instruments:
Cerabar S PMC71, PMP7x
Deltabar S PMD7x, FMD7x
Deltapilot S FMB70
Gammapilot M FMG60
Levelflex M FMP4x
Micropilot FMR130/FMR131
Micropilot M FMR2xx
Micropilot S FMR53x, FMR540
Prosonic FMU860/861/862
Prosonic M FMU4x
Tank Side Monitor NRF590 (with additional adapter cable)
Prosonic S FMU9x
For details refer to KA271F/00/a2.
Endress+Hauser

87

Accessories

Prosonic M - FOUNDATION Fieldbus

9.10

Remote display FHX40


Pipe-mounting
(mounting bracket and plate
supplied optionally,
s. product structure)
8,
5

Wall-mounting
(without mounting bracket)

Micropilot M
Levelflex M
Prosonic M

Separate housing
FHX40 (IP 65)

180

122

160

15

80
ES

S+H

AU

SE

Me
Messberei
asuri ch
ng
ran
ge
U 16
ma
x. 20
4...20...36
m
mAV DC

88

Cable
IP

Maulburg

DR

A >7

t >8
5C

118

96

6,
3

0C
:

120
82

65

Made in Germany

EN
Orde
r
Se Code
r.-N
o.: :

122

106

max. 80
min. 30

pipe

L00-FMxxxxxx-00-00-06-en-003

9.10.1

Technical data (cable and housing) and product structure:

Max. cable length

20 m (65 ft)

Temperature range

-30 C...+70 C (-22 F...158 F)

Degree of protection

IP65/67 (housing); IP68 (cable) acc. to IEC 60529

Materials

Housing: AlSi12; cable glands: nickle plated brass

Dimensions [mm] / [inch]

122x150x80 (HxWxD) / 4.8x5.9x3.2

Approval:
A
1
S
U
N
K

Nn-hazardous area
ATEX II 2 G EEx ia IIC T6, ATEX II 3D
FM IS Cl.I Div.1 Gr.A-D
CSA IS Cl.I Div.1 Gr.A-D
CSA General Purpose
TIIS ia IIC T6 (in preparation)

Cable:
1
5

20m/65ft; for HART


20m/65ft; for PROFIBUS PA/FOUNDATION Fieldbus

Additional option:
A
B

FHX40 -

Basic version
Mounting bracket, pipe 1"/ 2"

Complete product designation

For connection of the remote display FHX40 use the cable which fits the communication version of
the respective instrument.

88

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Measured variable

Technical Data

10

Technical Data

10.1

Technical data at a glance

10.1.1

Input

The distance D between the sensor membrane and the product surface is measured.
Using the linearisation function, the device uses D to calculate:
level L in any units
volume V in any units
flow Q across measuring weirs or open channels in any units

Maximum range/blocking
distance

Sensor

Maximum range in liquids1

Maximum range in solids1

blocking distance

FMU40

5m

2m

0.25 m

FMU41

8m

3.5 m

0.35 m

FMU42

10 m

5m

0.4 m

FMU43

15 m

7m

0.6 m

FMU44

20 m

10 m

0.5 m

The actual range is dependent on the measuring conditions. Refer to Technical Information TI
365F/00/en for an estimation.

10.1.2

Output

Output signal

Foundation Fieldbus

Signal Coding

Manchester Bus Powered (MBP); Manchester II

Data transmission rate

31.25 KBit/s, voltage mode

Signal on alarm

Error symbol, error code and plain text description on the on-site display
Status byte of the digital signal input

10.1.3
Basic Data

Data of the FOUNDATION Fieldbus interface

Device Type

1011 (hex)

Device Revision

04 (hex)

DD Revision

01 (hex)

CFF Revision

01 (hex)

ITK Version

4.61

ITK-Certification Driver-No.

IT035900

Link Master (LAS) cabable

yes

Link Master / Basic Device


selectable

yes; Default: Basic Device

Number VCRs

24

Number of Link-Objects in VFD 24

Endress+Hauser

89

Technical Data

Virtual communication
references (VCRs)

Link Settings

Transducer Blocks

Prosonic M - FOUNDATION Fieldbus

Permanent Entries

Client VCRs

Server VCRs

24

Source VCRs

23

Sink VCRs

Subscriber VCRs

23

Publisher VCRs

23

Slot time

Min. Inter PDU delay

Max. response delay

10

Block

Content

Output values

Sensor Block

contains all parameters related to the mesurement

level or volume1) (channel 1)


distance (channel 2)
sensor temperature (channel 3)

Diagnsotic Block contains diagnostic information

no output values

Display Block

no output values

1)

Function Blocks

contains parameters to configure the local display

je nach Konfiguration des Sensor-Blocks

Block

Content

Resource Block

The Resource Block contains all the data that uniquely


identifies the field device. It is an electronic version of a
nameplate of the device.

Analog Input
Block 1

The AI block takes the manufacturer's input data, selected by channel number, and makes it available to other
function blocks at its output.

30 ms

standard

Analog Input
Block 2

The AI block takes the manufacturer's input data, selected by channel number, and makes it available to other
function blocks at its output.

30 ms

standard

PID Block

The PID block serves as proportional-integral-derivative


controller and is used almost universally to do closedloop-control in the field including cascade and feedforward.

80 ms

standard

50 ms

standard

The input selector block provides selection of up to four 30 ms


inputs and generates an output based on the configured
action. This block normally receives its inputs from AI
blocks. The block performs maximum, minimum, middle,
average and first good signal selection.

standard

40 ms
Signal Characte- The signal characterizer block has two sections, each
rizer Block
with an output that is a non-linear function of the respective input. The non-linear function is determined by a single look-up table with 21 arbitrary x-y pairs.

standard

Arithmetic Block This block is designed to permit simple use of popular


measurement math functions. The user does not have to
know how to write equations. The math algorithm is
selected by name, chosen by the user for the function to
be done.
Input Selector
Block

90

Execution time

Functionality
enhanced

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Technical Data

Block

Content

Integrator Block

60 ms
The Integrator Function Block integrates a variable as a
function of the time or accumulates the counts from a
Pulse Input block. The block may be used as a totalizer
that counts up until reset or as a batch totalizer that has a
setpoint, where the integrated or accumulated value is
compared to pre-trip and trip settings, generating discrete
signals when these settings are reached.

10.1.4

Execution time

Functionality
standard

Auxiliary energy

Terminals

Cable cross-section: 0.5 to 2.5 mm (20 to 14 AWG)

Cable entry

Cable gland M20x1.5 (recommended cable diameter 6 ... 10 mm)


Cable entry G or NPT
7/8" Foundation Fieldbus plug

Supply voltage

9 V ... 32 V
There may be additional restrictions for devices with an explosion protection certificate. Refer to the
notes in the appropriate safety instructions (XA).

Lift-off voltage

9V

Basic current

15 mA

In-rush current

15 mA

Error current

0 mA

FISCO

Ui

17,5 V

Ii

500 mA; with surge arrester 273 mA

Pi

5,5 W; with surge arrester1, 2 W

Ci

5 mF

Li

0,01 mH

FNICO compliant

yes

Polarity sensitive

no

10.1.5
Reaction time

Performance characteristics

The reaction time depends on the parameter settings. The minimum values are:
FMU40/41/42/43: min. 2 s
FMU44: min. 3 s

Reference operating
conditions

Endress+Hauser

Temperature = +20 C
Pressure = 1013 mbar abs.
Humidity = 50 %
Ideal reflective surface (e.g. calm, smooth fluid surface)
91

Technical Data

Prosonic M - FOUNDATION Fieldbus

No interference reflections within signal beam


Set application parameters:
Tank shape = flat ceiling
Medium property = liquid
process conditions = calm surface
Measured value resolution

Measuring error

Sensor

Measured value resolution

FMU40

1 mm

FMU41

1 mm

FMU42

2 mm

FMU43

2 mm

FMU44

2 mm

Typical specifications for reference operating conditions (include linearity, repeatability, and
hysteresis):
Sensor

Measuring error

FMU40

2mm or 0.2% of set measuring distance (empty calibration)1

FMU41

2 mm or 0,2% of set measuring distance (empty calibration)1

FMU42

4 mm or 0,2% of set measuring distance (empty calibration)1

FMU43

4 mm or 0,2% of set measuring distance (empty calibration)1

FMU44

4 mm or 0,2% of set measuring distance (empty calibration)1

Influence of the vapor pressure

whichever is greater

The vapor pressure at 20 C (68 F) gives a hint on the accuracy of the ultrasonic level
measurement. If the vapor pressure at 20 C (68 F) is below 50 mbar, ultrasonic level
measurement is possible with a very high accuracy. This is valid for water, aqueous solutions, watersolid-solutions, dilute acids (hydrochloric acid, sulfuric acid, ...), dilute bases (caustic soda, ...), oils,
greases, slurries, pastes, ...
High vapor pressures or outgassing media (ethanol, acetone, ammonia, ...) can influence the
accuracy. If conditions like these are present, please contact the Endress+Hauser support.

10.1.6

Ambient conditions

Ambient temperature

-40 C ... +80 C


The functionality of the LC display becomes restricted at Tu<-20 C and Tu>+60 C.
If the device is operated outdoors in strong sunlight, you should use a protective cover.

Storage temperature

-40 C ... +80 C

Climate class

DIN EN 60068-2-38 (Test Z/AD) DIN/IEC 68 T2-30Db

Ingress protection

With closed housing, tested according to


IP 68, NEMA 6P (24h at 1.83m under water surface)
IP 66, NEMA 4x
With open housing: IP 20, NEMA 1 (also ingress protection of the display)

Vibration resistance

DIN EN 60068-2-64 / IEC 68-2-64: 202000 Hz, 1 (m/s2)2/Hz; 3 x 100 min

92

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Electromagnetic compatibility
(EMC)

Technical Data

Interference emission to EN 61326, Equipment Class B


Interference immunity to EN 61326, Appendix A (Industrial) and NAMUR Recommendation NE
21 (EMC).
A standard installation cable is sufficient if only the analogue signal is used. Use a screened cable
when working with a superimposed communication signal (HART).

10.1.7

Process conditions

Process temperature

-40C ... +80C


A temperature sensor is integrated in the sensor for correction of the temperature-dependent timeof-flight.

Process pressure

FMU 40/41: 0.7 bar ... 3bar abs.


FMU 42/43/44: 0.7 bar ... 2.5bar abs.

Endress+Hauser

93

Appendix

Prosonic M - FOUNDATION Fieldbus

basic setup

00

11

Appendix

11.1

Operating menu

tank shape

002

dome ceiling
horizontal cyl.
bypass
stilling well
flat ceiling
sphere
no ceiling

safety settings

01

output on alarm

medium property

003

liquid
solid < 4mm
solid > 4mm
unknown

process cond.

004

standard liquid
calm surface
turb. surface
add. agitator
fast change
standard solid
solid dusty
conveyor belt
test: no filter

010

outp. echo loss

empty calibr.

005

distance membrane
to min. level
Default:
FMU40: 5 m
FMU41: 8 m
FMU42: 10 m
FMU43: 15 m
FMU44: 20 m

006

span
max.: empty - BD
Default:
FMU40: 4,75 m
FMU41: 7,6 m
FMU42: 9,6 m
FMU43: 14,4 m
FMU44: 19,5 m

012

delay time

hold
alarm

MAX 110%
hold
MIN - 10%

full calibr.

014

in case of echo loss


max. 4000 sec.
Default: 30 s

ramp %/min

Rampe %span/min 013


specify value

temperature

03

measured temp.

030

linearisation

extended calibr.

04

05

max. temp. limit

031

max. meas. temp.

032

is displayed

is displayed

is displayed

040

linearisation

level CU
ullage CU

040

clear table
table on
manual
semi-automatic
horizontal cyl.

customer unit

customer unit

042

linear

customer unit

042

check distance

051

040

selction

050

mapping

dist./meas. value

033

warning
alarm

level/ullage

level DU
ullage DU

react. high temp

defect temp. sens.

034

alarm
warning

041

008

the following are


displayed:
- distance membrane
to level
- measured value

042

manual
distance = ok
distance too small

045

linearisation
TabNo
Level
volum

043
044
045

yes

range of mapping.

052

start mapping

next point
no

053

accept proposed value


or
specify range of
mapping

off
on

pres. map dist.

cust. tank map

dist. unknown
distance too big
common

extended map.

054

is displayed

output

06

envelope curve

0E

plot settings

0E1

envelope curve
env. curve + FAC
env. curve + cust. map
display

recording curve

0E2

single curve
cyclic

language

09

092

back to home

093

specify time
Default: 100 s

diagnostics

0A

present error

0A0

previous error

0A1

clear last error

device tag

0C0

protocol + sw-no.

format display

094

decimal
1/16

0A2

keep
erase
system parameters 0C

055

inactive
active
reset

reset
for reset code
see manual

0C2

no. of decimalas

095

x
x.x
x.xx
x.xxx
0A3

unlock parameter

0A4

for unlock code


see manual
device id

0C4

Note! The Default values of the parameters are typed in bold face.
L00-FMU4xxxx-19-00-01-en-017

94

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

dist./meas. value

008

the following are


displayed:
- distance membrane
to level
- measured value

check distance

Appendix

051

manual
distance = ok
distance too small

range of mapping.

052

accept proposed value


or
specify range of
mapping

start mapping

053

dist./meas. value

008

the following are


displayed:
- distance membrane
to level
- measured value

off
on

dist. unknown
distance too big

015

in safety dist.

016

from blocking distance


Default: 0,1m

warning
self holding
alarm

max. scale

046

diameter vessel

047

max. scale

046

dist./meas. value

008

echo quality

056

ackn. alarm

017

no
yes

the following are


displayed:
- distance membrane
to level
- measured value

is displayed

simulation

offset

057

will be added to the


measured level

output damping

058

Default: 2 s

blocking dist.
is displayed

059

Return to Group selection

safety distance

065

sim. off
sim. level
sim. volume
sim. current

sep. character

096

066

display test

097

off
on

. period
, comma

measured dist.

simulation value

0A5

measured level

0A6

detection window
off
on
reset

distance unit

0C5

temperature unit

0C6

0A7

application par.

0A8

not modified
modified
download mode

0C8

parameter only
param. + cust. map
mapping only
L00-FMU4xxxx-19-00-02-en-017

Endress+Hauser

95

Appendix

Prosonic M - FOUNDATION Fieldbus

11.2

Block model of the Prosonic M

The Prosonic M contains the follwoing blocks:


Resource Block (RB2)
s. Operating Instructions BA013S: "FOUNDATION Fieldbus - Overview"
Sensor Block (TBUL)
contains the parameters relevant to the measurement
Diagnostic Block (DIAG)
contains the diagnostic parameters of the Prosonic M
Display Block (DISP)
contains the configuration parameters for the display module VU331
Analog-Input-Block 1 bzw. 2 (AI)
scale the signal of the Transducer Block and transmit them to the PLCS
PID Block (PID)
s. Operating Instructions BA013S: "FOUNDATION Fieldbus - Overview"
Arithmetic Block (AR)
s. Operating Instructions BA013S: "FOUNDATION Fieldbus - Overview"
Input Selector Block (IS)
s. Operating Instructions BA013S: "FOUNDATION Fieldbus - Overview"
Signal Characterizer Block (SC)
s. Operating Instructions BA013S: "FOUNDATION Fieldbus - Overview"
Integrator Block (IT)
s. Operating Instructions BA013S: "FOUNDATION Fieldbus - Overview"

11.2.1

Default Block configuration

The input and output variables of the blocks can be interconnected by a network configuration tool
(e.g. NI-Fieldbus configurator). The figure below shows, how these connections are set by default.

Sensor
signal evaluation

Display

Physical Block
parameters of the
physical unit, e.g.
tag No.

Sensor Block
Parameters that
Primary value
describe the
device (calibration, (main value)
linearisation etc.)
Secondary value
(distance)
Third value
(temperature)

PID Block
Automation
functions

Analog Input Function Block 1


parameters that are important to
the process control system,
e.g. scaling, status

Analog Input Function Block 2


parameters that are important to
the process control system,
e.g. scaling, status

OUT

OUT

L00-FMU4XXXX-02-00-00-en-003

96

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

11.3

Appendix

Resource block

The resource block contains the parameters used to describe physical resources of the device. It has
no linkable inputs or outputs.

11.3.1

Operation

The resource block is opened by a click on the resource line.


If the NI-FBUS Configurator is being used, a series of file tabs appears on the screen. The files can
be opened to view and/or edit the parameters in the following table. A short description of the
parameter function appears on the side of the screen. A change in the parameter is stored by pressing
the WRITE CHANGES button when the block is out of service. Press the READ ALL button to check
the values stored in the device.

11.3.2

Parameters

Parameter

Description

TAG_DESC

User description of the intended application of the block.

MODE_BLK

Lists the actual, target, permitted and normal operating modes of the block.
Target: changes the operating mode of the block
Actual: indicates the current operating mode of the block
Permitted: states which operating modes are allowed
Normal: indicates the normal operating mode of the block
The possible operating modes of the resources block are:
AUTO: the block is operating as normal
OOS: the block is out of service.
If the resource block is out of service, then all blocks within the device (resource) are
forced into the same status.

RS_STATE

Indicates the state of the resource block application state machine


On-line: block in AUTO mode
Standby: block in OOS mode

WRITE_LOCK

Indicates the status of DIP-switch WP


LOCKED: device data can be modified
NOT LOCKED: device data can be modified

RESTART

Allows a manual restart:


UNINITIALISED: no status
RUN: normal operational status
RESOURCE: resets the resource block parameters
DEFAULTS: Resets all FOUNDATION Fieldbus parameters within the
device, but not the manufacturer specific parameters.
PROCESSOR: make a warm start of the processor

BLOCK_ERROR

Shows error status of software and hardware components


Out-of-Service: the block is in OOS mode
Simulation active: shows the setting of DIP-switch SIM

BLOCK_ALM

Shows any configuration, hardware, connection and system problems in the lock. The
cause of the alert is to be seen in the subcode field.

The function of the resource block parameters not described here can can be taken from the
FOUNDATION Fieldbus specification, see "www.fieldbus.org".

Endress+Hauser

97

Appendix

Prosonic M - FOUNDATION Fieldbus

11.4

Sensor Block

The Sensor block contains the parameters required to calibrate the device. These parameters can
also be addressed by using the VU331 display module. The calibration of the device is described in
Chapter 6.

11.4.1

Operation

Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. Press
the READ ALL button to check the values stored in the device. In order to resume operation, change
MODE_BLK to AUTO4).

11.4.2

Output values

Parameter

Description

PRIMARY_VALUE

Main value (level, volume or flow)

SECONDARY_VALUE

Measured distance

THIRD_VALUE

Measured temperature

11.4.3

Configuration parameters

The Sensor block also contains the configuration parameters, which are used to commission and
calibrate the instrument. They are identical to the functions of the operating menu, except for the
service parameters which are not accessible on the bus. Thus, the calibration procedure via the
display module (chapter "Commissioning") is equally valid for a calibration via a network
configuration tool.
A complete list of the configuration parameters can be found in the "Description of Instrument
Functions", BA240F/00/en.

4)

98

If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK
to AUTO.

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

11.4.4

Appendix

Methods

The FOUNDATION Fieldbus specification provides for the use of so-called methods to simplify the
operation of the device. A method is an interactive sequence of steps that must be followed in order
to obtain a particular function from the device.
The Prosonic M has got the following methods:
Basic setup
Safety settings
Acknowledge alarm
temperature
Linearisation
Extended calibration
Output
System parameters
Lock TB Manufacturer parameters
Most of these methods are identical to the respective function group in the operating menu. A
detailed description of them can be found in the "Description of Instrument functions", BA240F.

11.4.5

Parameter list of the Prosonic M Sensor Block

Parameter

Position rel.
Variable Name
Indicator Index

Size
Type
[bytes]

Access Storage
Class

Changeable
in Mode

measured value

000

18

PARMEASUREDVALUE

FloatingPoint

RO

dynamic

Auto, OOS

tank shape

002

19

PARTANKSHAPE

Unsigned8

RW

static

OOS

medium property

003

20

PARMEDIUMCONDITION

Unsigned8

RW

static

OOS

process cond.

004

21

PARPROCESSCONDITION

Unsigned8

RW

static

OOS

empty calibr.

005

22

PAREMPTYCALIBRATION

FloatingPoint

RW

static

OOS

full calibr.

006

23

PARFULLCALIBRATION

FloatingPoint

RW

static

OOS

echo quality

056

24

PARECHOQUALITY

Unsigned8

RO

dynamic

Auto, OOS

check distance

051

25

PARCHECKDISTANCE

Unsigned8

RW

dynamic

OOS

range of mapping

052

26

PARSUPPRESSIONDISTANCE

FloatingPoint

RW

dynamic

OOS

start mapping

053

27

PARSTARTMAPPINGRECORD

Unsigned8

RW

dynamic

OOS

pres. map dist.

054

28

PARPRESMAPRANGE

FloatingPoint

RO

dynamic

Auto, OOS

cust. tank map

055

29

PARCUSTTANKMAP

Unsigned8

RW

dynamic

OOS

offset

057

30

PAROFFSETOFMEASUREDDISTANCE

FloatingPoint

RW

static

OOS

output damping

058

31

PAROUTPUTDAMPING

FloatingPoint

RW

static

Auto, OOS

blocking dist.

059

32

PARBLOCKINGDISTANCE

FloatingPoint

RW

static

OOS

output on alarm

010

33

PAROUTPUTONALARM

Unsigned8

RW

static

OOS

outp. echo loss

012

34

PARREACTIONLOSTECHO

Unsigned8

RW

static

OOS

ramp %span/min

013

35

PARRAMPINPERCENTPERMIN

FloatingPoint

RW

static

OOS

delay time

014

36

PARDELAYTIMEONLOSTECHO

Unsigned16

RW

static

OOS

safety distance

015

37

PARLEVELWITHINSAFETYDISTANCE

FloatingPoint

RW

static

OOS

in safety dist.

016

38

PARINSAFETYDISTANCE

Unsigned8

RW

static

OOS

ackn. alarm

017

39

PARACKNOWLEDGEALARM

Unsigned8

RW

dynamic

Auto, OOS

measured temp.

030

40

PARMEASUREDTEMPERATURE

FloatingPoint

RO

dynamic

Auto, OOS

max. temp. limit

031

41

PARMAXTEMPLIMIT

FloatingPoint

RO

dynamic

Auto, OOS

max. meas. temp

032

42

PARMAXMEASUREDTEMPERATURE

FloatingPoint

RO

non-vol.

Auto, OOS

react. high temp

033

43

PARONHIGHTEMPERATURE

Unsigned8

RW

static

OOS

defect temp sens

034

44

PARDEFECTTEMPERATURESENSOR

Unsigned8

RW

static

OOS

Endress+Hauser

99

Appendix

Prosonic M - FOUNDATION Fieldbus

Parameter

Position rel.
Variable Name
Indicator Index

Size
Type
[bytes]

Access Storage
Class

Changeable
in Mode

level/ullage

040

45

PARLEVELULLAGEMODE

Unsigned8

RW

static

OOS

linearisation

041

46

PARLINEARISATION

Unsigned8

RW

static

OOS

customer unit

042

47

PARCUSTOMERUNIT

Unsigned16

RW

static

OOS

table no.

043

48

PARTABLENUMBER

Unsigned8

RW

non-vol.

Auto, OOS

input level

044

49

PARINPUTLEVELHALFAUTOMATIC

FloatingPoint

RO

dynamic

Auto, OOS

input level

044

50

PARINPUTLEVELMANUAL

FloatingPoint

RW

dynamic

OOS

input volume

045

51

PARINPUTVOLUME

FloatingPoint

RW

dynamic

OOS

max. scale

046

52

PARMAXVOLUME

FloatingPoint

RW

static

OOS

diameter vessel

047

53

PARCYLINDERVESSEL

FloatingPoint

RW

static

OOS

simulation

065

54

PARSIMULATION

Unsigned8

RW

dynamic

OOS

simulation value

066

55

PARSIMULATIONVALUELEVEL

FloatingPoint

RW

dynamic

Auto, OOS

simulation value

066

56

PARSIMULATIONVALUEVOLUME

FloatingPoint

RW

dynamic

Auto, OOS

unlock parameter

0A4

57

PAROPERATIONCODE

Unsigned16

RW

non-vol.

OOS

measured dist.

0A5

58

PARMEASUREDDISTANCE

FloatingPoint

RO

dynamic

Auto, OOS

measured level

0A6

59

PARMEASUREDLEVEL

FloatingPoint

RO

dynamic

Auto, OOS

detection window

0A7

60

PARDETECTIONWINDOW

Unsigned8

RW

dynamic

OOS

application par.

0A8

61

PARAPPLICATIONPARAMETER

Unsigned8

RO

dynamic

Auto, OOS

distance unit

0C5

62

PARDISTANCEUNIT

Unsigned16

RW

static

OOS

temperature unit

0C6

63

PARTEMPERATUREUNIT

Unsigned16

RW

static

OOS

download mode

0C8

64

PARDOWNLOADMODE

Unsigned8

RW

static

OOS

max meas dist

0D84

65

PARABSMAXMESSDIST

FloatingPoint

RO

dynamic

Auto, OOS

max sample dist.

0D88

66

PAREDITRANGEMAXSAMPLEDIST

FloatingPoint

RO

dynamic

Auto, OOS

present error

0A0

67

PARACTUALERROR

Unsigned16

RO

dynamic

Auto, OOS

100

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

Appendix

11.5

Diagnostic Block

11.5.1

Operation

The diagnostic block contains the error messages of the instrument. These parameters can also be
addressed by using the VU331 display module.
The diagnostic block is opened by clicking on the "diagnostic" line.
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. Press
the READ ALL button to check the values stored in the device. In order to resume operation, change
MODE_BLK to AUTO5).

11.5.2

Block administration parameters

Parameter

Description

MODE_BLK

See description in Resource block. The possible operating modes of the Sensor block are:
AUTO: the block is operating as normal.
OOS: the block is out of service.

TAG_DESC

User description of the intended application of the block.

BLOCK_ERROR

Shows the error status associated with the block components


Out-of-Service: the block is in OOS mode.

11.5.3

Methods

The FOUNDATION Fieldbus specification provides for the use of so-called methods to simplify the
operation of the device. A method is an interactive sequence of steps that must be followed in order
to obtain a particular function from the device.
The Prosonic M has got the following methods:
Set to customer default
Diagnostics
Most of these methods are identical to the respective function group in the operating menu. A
detailed description of them can be found in the "Description of Instrument functions", BA240F.

11.5.4

Instrument specific parameters

Parameter

Position rel.
Variable Name
Indicator Index

Size
Type
[bytes]

Access Storage
Class

Changeable
in Mode

present error

0A0

13

PARACTUALERROR

Unsigned16

RO

dynamic

Auto, OOS

previous error

0A1

14

PARLASTERROR

Unsigned16

RO

non-vol.

Auto, OOS

clear last error

0A2

15

PARCLEARLASTERROR

Unsigned8

RW

dynamic

Auto, OOS

reset

0A3

16

PARRESET

Unsigned16

RW

dynamic

OOS

unlock parameter

0A4

17

PAROPERATIONCODE

Unsigned16

RW

non-vol.

OOS

protocol+sw-no.

0C2

18

PARPROTSOFTVERSIONSTRING

16

VisibleString

RO

const

Auto, OOS

5)

If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK
to AUTO.

Endress+Hauser

101

Appendix

Prosonic M - FOUNDATION Fieldbus

11.6

Display Block

11.6.1

Operation

The display block contains the parameters required to parametrise the display module VU331
(which is contained in the remote display and operating unit FHX40). These parameters can also be
addressed by using the VU331 display module.
The display block is opened by clicking on the "display" line.
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. Press
the READ ALL button to check the values stored in the device. In order to resume operation, change
MODE_BLK to AUTO6).

11.6.2

Block administration parameters

Parameter

Description

MODE_BLK

See description in Resource block. The possible operating modes of the sensor block are:
AUTO: the block is operating as normal.
OOS: the block is out of service.

TAG_DESC

User description of the intended application of the block.

BLOCK_ERROR

Shows the error status associated with the block components


Out-of-Service: the block is in OOS mode.

11.6.3

Methods

The FOUNDATION Fieldbus specification provides for the use of so-called methods to simplify the
operation of the device. A method is an interactive sequence of steps that must be followed in order
to obtain a particular function from the device.
The Prosonic M has got the following methods:
Display
Most of these methods are identical to the respective function group in the operating menu. A
detailed description of them can be found in the "Description of Instrument functions", BA240F.

11.6.4

Instrument specific parameters

Parameter

Position rel.
Variable Name
Indicator Index

Size
Type
[bytes]

Access Storage
Class

Changeable
in Mode

language

092

13

PARLANGUAGE

Unsigned8

RW

non-vol.

Auto, OOS

back to home

093

14

PARBACKTOHOME

Integer16

RW

non-vol.

Auto, OOS

format display

094

15

PARFORMATDISPLAY_FT

Unsigned8

RW

non-vol.

Auto, OOS

no.of decimals

095

16

PARNOOFDECIMALS

Unsigned8

RW

non-vol.

Auto, OOS

sep. character

096

17

PARSEPARATIONCHARACTER

Unsigned8

RW

non-vol.

Auto, OOS

unlock parameter

0A4

18

PAROPERATIONCODE

Unsigned16

RW

non-vol.

OOS

6)

102

If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK
to AUTO.

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

11.7

Appendix

Analog input block

The analog input block condito ns the signal output by the Sensor block andoutputs signal to the
PCL or other function blocks.

L00-FMR2xxxx-05-00-00-en-008

11.7.1

Operation

The resource block is opened by a click on the resource line.


Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. Press
the READ ALL button to check the values stored in the device. Normally operation is resumed as
soon as MODE-BLK is set to AUTO.

11.7.2

Endress+Hauser

Block administration parameters

Parameter

Description

MODE_BLK

See description in Resource block. The possible operating modes of the Sensor block are:
AUTO: the block is operating as normal
MAN: the block is operated with a manually entered primary value.
OOS: the block is out of service.

TAG_DESC

User description of the intended application of the block.

BLOCK_ERROR

Shows error status of software and hardware components


Out-of-Service: the block is in OOS mode
Simulation active: shows the setting of DIP-switch SIM. Input failure/process variable
has BAD status.
configuration error

103

Appendix

Prosonic M - FOUNDATION Fieldbus

11.7.3

Output values

Parameter

Description

PV

Either the primary/secondary Sensor block value used to execute the block or a process
value associated with it. Comprises value and status.

OUT

The primary value output as a result of executing the analog input block. Comprises
value and status.

FIELD_VALUE

Raw value of field device in % of PV range with a status reflecting the Sensor condition
before signal characterisation L_Type or filtering V_TIME. Comprises value and status.

11.7.4

Scaling parameters

Parameter

Description

CHANNEL

Selects the measured value to be input to the analogue input block


0 = no channel defined
1 = primary value: measured level/volume
2 = secondary value: measured distance

XD_SCALE

Scales the Sensor block value in the required engineering units (EU).

OUT_SCALE

Scales the output value in the required engineering units (EU).

L_TYPE

Sets the linearization type:


DIRECT: the Sensor block value bypasses the scaling functions
INDIRECT:the Sensor block value is fed through the linear scaling functions
INDIRECT SQRT: the Sensor block value is fed through the square root scaling functions

The relationship between the output values and scaling paramaters is as follows:

FIELD_VAL = 100 x

CHANNEL_VALUE - XD_SCALE_MIN
XD_SCALE_MAX - XD_SCALE_MIN

The L_TYPE parameter influences the signal conversion:


Direct:
PV = CHANNEL_VALUE

Indirect:

PV =

FIELD_VALUE
x (OUT_SCALE_MAX - OUT_SCALE_MIN) + OUT_SCALE_MIN
100

Indirect square root:

PV =

104

FIELD_VALUE
x (OUT_SCALE_MAX - OUT_SCALE_MIN) + OUT_SCALE_MIN
100

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

11.7.5

Output response parameters

Parameter

Description

LOW_CUT

Not relevant to level measurement!


Determines a threshold for square root linearization below which the output value is set
to zero.

PV_FTIME

Sets the time constant for the output value.

11.7.6

Alarm parameters

Parameter

Description

ACK_OPTION

Sets the way in which alarms and warnings are to be acknowledged.

ALARM_HYS

Sets the hysteresis (in output engineering units) for all configured alarms.
A hysteresis of e.g. 2% on a HI_HI_LIMIT of 95% would cause the alarm to activate
when the level reaches 95% and to deactivate when the level drops below 93%.
A hysteresis of e.g. 2% on a LO_LO_LIMIT of 5% would cause the alarm to activate
when the level drops below 5% and to deactivate when the level rises to 7%.

HI_HI_PRI

The priority (1 15) of the HI_HI alarm

HI_HI_LIM

Sets the HI_HI alarm limit in output engineering units

HI_PRI

The priority (1 15) of the HI alarm

HI_LIM

Sets the HI warning limit in output engineering units

LO_PRI

The priority (1 15) of the LO alarm

LO_LIM

Sets the LO warning limit in output engineering units

LO_LO_PRI

The priority (1 15) of the LO_LO alarm

LO_LO_LIM

Sets the LO_LO alarm limit in output engineering units

11.7.7

Alarm priorities

Parameter

Description

Alarm is suppressed

Recognised by the system but not reported

Reported to the operator, but does not require his attention

3-7

Advisroy alarms of increasing priority

8 - 15

Critical alarms of increasing priority

11.7.8

Endress+Hauser

Appendix

Alarm status

Parameter

Description

HI_HI_ALM

The status of the HI_HI alarm

HI_ALM

The status of the HI alarm

LO_ALM

The status of the LO alarm

LO_LO_ALM

The status of the LO_LO alarm

105

Appendix

Prosonic M - FOUNDATION Fieldbus

11.7.9

Simulation

The SIMULATE parameter allows the Sensor block output value to be simulated, provided
simulation has also been enabled at the device DIP switch. The simulation must be enabled, a value
and/or status entered and the block must be in AUTO mode. During simulation the Sensor output
value is substituted by the simulated value.
A simulation is also possible by switching MODE_BLK to "MAN" and entering a value for OUT.

106

Parameter

Description

SIMULATE

Enables, sets and displays a simulated value, options:


enable/disable
simulated value
output value

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

11.8

Appendix

List of start indices

The following list indicates the start indices for all blocks and objects:

Endress+Hauser

Object

Start Index

Object Dictionary

298

Object

Start Index

Resource Block

400

Analog Input 1 Function Block

500

Analog Input 2 Function Block

600

PID Function Block

700

Arithmetic Function Block

800

Input Selector Function Block

900

Signal Characterizer Function Block

1000

Integrator Function Block

1100

Sensor Block

2000

Diagnostic Block

2200

Display Block

2400

Object

Start Index

View Objects Resource Block

3000

View Objects Analog Input 1 Function Block

3010

View Objects Analog Input 2 Function Block

3020

View Objects PID Function Block

3030

View Objects Arithmetic Function Block

3040

View Objects Input Selector Function Block

3050

View Objects Signal Characterizer Function Block

3060

View Objects Integrator Function Block

3070

View Objects Sensor Block

4000

View Object Diagnostic Block

4100

View Object Display Block

4200

107

Appendix

Prosonic M - FOUNDATION Fieldbus

11.9

Measuring principle

BD

20 mA
100%
D

4 mA
0%
L00-FMU4x-15-00-00-de-001

E: Empty distance; F: Span (full distance); D: Distance from sensor membrane - product surface; L: Level; BD: Blocking
distance

Sensor

BD

Max. range fluids

Max. range bulk materials

FMU40

0.25 m

5m

2m

FMU41

0.35 m

8m

3.5 m

FMU42

0.4 m

10 m

5m

FMU43

0.6 m

15 m

7m

FMU44

0.5 m

20 m

10 m

11.9.1

Time-of-flight method

The sensor of the Prosonic M transmits ultrasonic pulses in the direction of the product surface.
There, they are reflected back and received by the sensor. The Prosonic M measures the time t
between pulse transmission and reception. The instrument uses the time t (and the velocity of sound
c) to calculate the distance D between the sensor membrane and the product surface:
D = c t/2
As the device knows the empty distance E from a user entry, it can calculate the level as follows:
L=E-D
An integrated temperature sensor compensates for changes in the velocity of sound caused by
temperature changes.

11.9.2

Interference echo suppression

The interference echo suppression feature on the Prosonic M ensures that interference echos (e.g.
from edges, welded joints and installations) are not interpreted as a level echo.

11.9.3

Calibration

Enter the empty distance E and the span F to calibrate the device.

108

Endress+Hauser

Prosonic M - FOUNDATION Fieldbus

11.9.4

Appendix

Blocking distance

Span F may not extend into the blocking distance BD. Level echos from the blocking distance cannot
be evaluated due to the transient characteristics of the sensor.

Endress+Hauser

109

Prosonic M - FOUNDATION Fieldbus

Index

Index
A

alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
application errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

process conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

B
basic setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
blocking distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23, 52

range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
repairs to Ex-approved devices . . . . . . . . . . . . . . . . . . . . . 74
return. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

cantilever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

85
14
74
26

14
81
32
33

E
empty calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
envelope curve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service Interface FXA291 . . . . . . . . . . . . . . . . . . . . . . . . . 87


shafts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

T
ToF Tool. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
turn housing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

D
declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . .
declaration of contamination. . . . . . . . . . . . . . . . . . . . . . .
display appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
display symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

59
60
69
68

V
vessel / silo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

W
warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
weather protection cover . . . . . . . . . . . . . . . . . . . . . . . . . 83

F
FHX40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
flow measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
full calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52, 59

H
hazardous area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

I
installation bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
interference echo suppression . . . . . . . . . . . . . . . . . . . . . . 53

K
key assignment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Khafagi-Venturi flume . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

L
level measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

M
mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
medium property . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

N
nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

O
on-site display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

110

Endress+Hauser

Declaration of Hazardous Material and De-Contamination


Erklrung zur Kontamination und Reinigung
Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA#
clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
Bitte geben Sie die von E+H mitgeteilte Rcklieferungsnummer (RA#) auf allen Lieferpapieren an und vermerken Sie diese
auch auen auf der Verpackung. Nichtbeachtung dieser Anweisung fhrt zur Ablehnung ihrer Lieferung.

RA No.

Because of legal regulations and for the safety of our employees and operating equipment, we need the "Declaration of Hazardous Material
and De-Contamination", with your signature, before your order can be handled. Please make absolutely sure to attach it to the outside of the
packaging.
Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, bentigen wir die unterschriebene
"Erklrung zur Kontamination und Reinigung", bevor Ihr Auftrag bearbeitet werden kann. Bringen Sie diese unbedingt auen an der
Verpackung an.
Serial number
Seriennummer ________________________

Type of instrument / sensor


Gerte-/Sensortyp
____________________________________________

Used as SIL device in a Safety Instrumented System / Einsatz als SIL Gert in Schutzeinrichtungen
Process data/Prozessdaten

Pressure / Druck
_____ [psi] _____ [ Pa ]
Viscosity /Viskositt _____ [cp] _____ [mm2/s]

Temperature / Temperatur_____ [F] _____ [C]


Conductivity / Leitfhigkeit ________ [S/cm]

Medium and warnings


Warnhinweise zum Medium
Medium /concentration Identification flammable
CAS No.
Medium /Konzentration
entzndlich

toxic
giftig

corrosive
tzend

harmful/
irritant
gesundheitsschdlich/
reizend

other *
harmless
sonstiges* unbedenklich

Process
medium
Medium im
Prozess
Medium for
process cleaning
Medium zur
Prozessreinigung
Returned part
cleaned with
Medium zur
Endreinigung
* explosive; oxidising; dangerous for the environment; biological risk; radioactive
* explosiv; brandfrdernd; umweltgefhrlich; biogefhrlich; radioaktiv
Please tick should one of the above be applicable, include safety data sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen.
Description of failure / Fehlerbeschreibung __________________________________________________________________________
______________________________________________________________________________________________________________
______________________________________________________________________________________________________________
Company data /Angaben zum Absender

P/SF/Konta XIV

Company /Firma ___________________________________


_________________________________________________
Address / Adresse
_________________________________________________
_________________________________________________

Phone number of contact person /Telefon-Nr. Ansprechpartner:


____________________________________________
Fax / E-Mail ____________________________________________
Your order No. / Ihre Auftragsnr. ____________________________

We hereby certify that this declaration is filled out truthfully and completely to the best of our knowledge.We further certify that the returned
parts have been carefully cleaned. To the best of our knowledge they are free of any residues in dangerous quantities.
Wir besttigen, die vorliegende Erklrung nach unserem besten Wissen wahrheitsgetreu und vollstndig ausgefllt zu haben. Wir besttigen
weiter, dass die zurckgesandten Teile sorgfltig gereinigt wurden und nach unserem besten Wissen frei von Rckstnden in gefahrbringender Menge sind.

(place, date / Ort, Datum)

Name, dept./Abt. (please print /bitte Druckschrift)

Signature / Unterschrift

www.endress.com/worldwide

BA239F/00/en/01.09
71089089
CCS/FM+SGML 6.0/ProMoDo

71089089