Professional Documents
Culture Documents
ROTOLINE
RLI 700
RLI 900 FC
FC
RLI 900 FC
RLI 1200
RLI 700 EC
FC
RLI 1600
RLI 1200 FC
EC
RLI 2000
RLI 1600 FC
EC English
RLI 2000 EC
RLI 700 EC
RLI 1200 EC
RLI 1600 EC
RLI 2000 EC
www.ruck.eu
English
www.ruck.eu 3
English
declares herewith that the following partly completed machines in The partly completed machine also complies with all requirements
their conception and design, and in the versions marketed by us of the Low Voltage Directive (2006/95/EC) and the Electromagnetic
comply with the requirements of the named EC directives. In the Compatibility Directive (2004/108/EC).
event of any changes to the partly completed machine not approved
by us, this declaration loses its validity. The partly completed machine shall only be taken into service when
it has been established that the machine in which the partly com-
pleted machine is to be installed complies with the requirements of
Product designation: ROTOLINE the Machinery Directive (2006/42/EC).
Type designation: RLI 700, 900, 1200, 1600, 2000
www.ruck.eu 5
English
1. Important information
This manual contains important information on the safe and appropriate assembly, transport, commissio-
ning, operation, maintenance, disassembly and simple troubleshooting of the product.
The product has been manufactured according to the accepted rules of current technology.
There is, however, still a danger of personal injury or damage to equipment if the following general safety
instructions and the warnings before the steps contained in these instructions are not complied with.
Read these instructions completely and thoroughly before working with the product.
Keep these instructions in a location where they are accessible to all users at all times.
Always include the operating instructions when you pass the product on to third parties.
The warranty only applies to the delivered configuration. The warranty will not apply if the
product is incorrectly assembled or handled or not used as intended.
Intended use includes having read and understood these instructions, especially chapter 2 General
safety instructions.
Safety sign
(warning Consequence
triangle)
General warning!
Indicates possible hazardous situations. Failure to observe the war-
nings may result in personal injury and / or damage to property.
www.ruck.eu 7
English
2.5.7. Disposal
Dispose the product in accordance with the currently applicable national regulations in your
country..
! i
F7
FC
EC
M5
f1
f2 F7
119209
F7
F5
Electricity warning (hazardous voltage)!
General warning Failure to observe the hazard may result in death,
! !
Failure to observe the warnings may result in personal
injury and / or damage to property.
injury or damage to property.
F7
Before performing anyF5 work on conductive parts, al-
!
Unauthorized repairs may cause personal inju-
ry and / or damage to property, in which case the
ways disconnect the unit completely from the electricity
supply and make sure that it cannot be switched back
manufacturers guarantee or warranty will not apply. on again.
Caution! Burning hazard. Never reach into the impeller or other rotating or
Failure to observe the hazard may result in personal moving parts.
injury and/or damage to property. Failure to observe the hazard may lead to serious
injury.
have cooled. !
Do not touch the surface until the motor and heater
Work may only be performed once the impeller has
come to a complete halt.
Never reach into rotating or moving parts. Never clean the internal space with flowing water or a
!
Failure to observe the hazard may lead to serious
injury.
high-pressure cleaner. Do not use aggressive or easily
flammable products for cleaning (impellers/housing).
Work may only be performed once the impeller has Only use mild suds. The impeller should be cleaned
come to a complete halt. with a cloth or brush.
www.ruck.eu 9
English
3. Delivery contents
Included in delivery depending on model type:
1 x RLI Rotoline, Air handling unit
2 x ETALINE Tube Fan
2 x compact filter M5 and F7 (integrated)
1 x remote control with control cable
1 x heat exchanger, DX-Coil (Optinal depending on the type)
1 x heat exchanger, Cooling coil (Optinal depending on the type)
1 x installation and operating manual
1 x Cable entries ( incl. 1 x covering cap, 1 x PG gland M20, 1 x PG gland M25)
Data in detail:
Frameless housing made from galvanised steel, without cold bridges.
Extractable rotating heat exchanger with belt drive.
Hot water re-heater
Extractable large compact filters M5 / F7.
Controller installed, wired, ready to plug in.
Integrated isolator switch.
External control unit with control cable.
Optionally with cooling or DX-Coil.
Maximum temperature: 60 C (technical data)
Protection class: in ceiling installation correct duct and cable connection, IP 43 (see connection
diagram).
1
7
10 11
2
9
4 8
5 5
12
7 5 13
5 14
6
15
Fig. 1:
16
128625 00
17
7 1 34 35
18
19
12
20
36
21
38
22
1 i
!
F7
FC
EC
M5
23
37
119209
24
25
Fig. 2: 7 33 32 31 30 5 29 28 27
Typ: RLI 900 FC
www.ruck.eu 11
English
128625 00
17
7 1 34 35
18
19
12
20
36
21
38
1 !
i
22
F7
23
FC
EC
M5
119209
37
24
25
Fig. 3:
Typ: RLI 1200 EC 7 33 32 31 30 5 29 28 27
6. Assembly
Assembly work may only be performed by specialist personnel in accordance with the installation and
operating manual and the regulations and standards in force.
The following points should be noted and followed:
The foundation must be even and levelled. It must not exhibit unevenness or a slope in any direction.
Suitable foundations are: full foundation in concrete, strip foundations or steel bearer structures. In the
case of strip foundations and steel structures, it must be ensured that the machine base sits fair and
square on the bearers. Steel structures must be sufficiently rigid for the size of the machine.
Set up and align the machine with the aid of a water level. Only if the machine is horizontally installed
can proper condensate drainage be guaranteed.
Only suitable installation aids, in accordance with regulations, should be used.
The installation should be easily accessible for maintenance and cleaning and should be easy to
dismantle.
The unit should only be installed with authorized and suitable fastening materials at all fastening
points.
Do not distort the unit when installing.
The unit should be suitably secured.
No holes should be made in the housing, or any screws screwed into it.
The duct system must not be supported on the housing.
It is recommended that the duct system is attached with flexible connections in order to isolate any
structure-borne noise.
Make sure that the duct system cannot be closed off.
Make sure that the intake duct has direct access to the intake air. Warning: branches in
the intake duct, to other fan units for example, may, if the dimensions are too small, lead to low
pressure in the duct and therefore malfunction of the unit.
The pressure loss in the duct system must not be more than the capacity of the unit! The pressure
loss in the duct should not be more than 2/3 the units maximum pressure so that an adequate air
output can still be achieved. This will prevent malfunction. Pressure losses in the duct system are ad-
versely affected by: the length of the duct system, small duct cross-section, elbows, additional filters,
valves, etc.
www.ruck.eu 13
English
Hydraulic circuits
Bypass circuit For air conditioning applications, there are three basic circuits:
+ Bypass circuit
With the bypass circuit, only the hot water is fed to the heating coil. The rest of the water supplied
by the pump bypasses the heating coil. This can lead to a temperature difference between top and
bottom of the heating coil if the flow of water through it is very small. The resulting temperature gra-
dients can lead to false temperature measurements in the duct or to draught effects in the room. The
bypass circuit is usually used in air coolers. In air coolers, the air is partly cooled below the dew point
and thereby dehumidified.
Admixture circuit
Admixture circuit In the admixture circuit, the circulating pump always supplies the full amount of water required by the
heating coil with an amount of hot water determined by the valve setting. The temperature is thus
+ constant over the whole heating surface. The temperature control is thus much better. Furthermore,
the risk of frost damage when the pump is running is reduced as the continuous circulation and incre-
ased pressure reduce the freezing point of the water.
The only advantage of the bypass circuit over the admixture circuit arises when the pipe lengths bet-
ween three-way ball valve and water heater are very long. Because the pump is ahead of the valve,
there is always hot water available at the valve that can be immediately fed to the heat exchanger if
required. When in admixture circuit it is possible the water in the pipe to the valve cools, so when heat
is required there is a short delay before the hot water reaches the heating coil.
7. Electrical connection
Electricity warning (hazardous voltage)!
Failure to observe the hazard may result in death, injury or damage to property.
Before performing any work on conductive parts, always disconnect the unit completely from
the electricity supply and make sure that it cannot be switched back on again.
Electrical installation may only be performed by qualified electricians in accordance with the installation and
operating manual and the national regulations, standards and guidelines in force:
EN, DIN and VDE specifications, including all safety requirements.
Technical connection conditions.
Safety at work and accident prevention requirements.
www.ruck.eu 15
English
Fig. 7:
Connection compartment
(1) Controller board
1 (2) Terminal box duct cover
(3) Cable duct
3 128625 00
Fig. 8: 4
Cable glands
(4) Cable gland power supply
5 6
(5) Cable gland free
(6) Cable gland Control unit
Motion detector
A motion detector can be connected to the controller. When the contact is closed, the device
changes to the operating mode Intermittent ventilation with the preset follow-up time according
to parameter 30.
External, potential-free contact.
Fire detector
An external, potential-free fire detection contact switches the device off. The display indicates Error
fire protection. This signals requires a manual reset.
Modbus RTU
The communication interface with Modbus RTU protocol is already integrated as standard. The cen-
tral building control system can be connected directly to the integrated interface via Modbus. Multiple
devices can be connected to the bus with an adapter board as accessory.
The unit can be visualized using the ruck view software software. All parameters, measured and set
values can be controlled by ruck view.
2 = Heating and cooling (Water) If contact Enable Cooling opened, 0-10V heating
If contact Enable Cooling closed, 0-10V cooling
3 = Heating condenser and cooling DX-coil If contact Enable Cooling opened, 0-10V heating
If contact Enable Cooling closed, 0-10V cooling
Unit malfunction
If there is a malfunction on the unit, an error message appears on the display and at the same time
switches a relay. A closing and opening signal is available (see wiring diagram). Electrical connection
of the changeover contact with U - 230 VAC and Imax = 2A. (There is not any double insulation on the
mains cables).
www.ruck.eu 17
English
Control unit
The control unit is connected to the supply air units control system with a control cable.
A connector on the control cable is plugged directly into the socket on the control unit from beneath
(see Fig. 9). On the unit, the control cable is first fed through a cable gland (see Fig. 8), placed in the
cable duct and then connected to the RJ10 socket provided in the controller board. The control cable
must not be shortened. Any excess length must be stowed outside of the housing. If the cable is too
short, extensions can be ordered from the manufacturer or supplier. Alternatively, a 4-wire data cable
with 120 Ohm resistance can also be connected. This is fed through the back wall of the control unit
and connected to the spring-loaded terminals. In the unit, instead of being connected to the controller
board in the RJ10 socket, the cable is connected in the spring-loaded terminals next to it (see wiring
diagram).
8. Commissioning
Commissioning by trained technical personnel may only be performed when any risk has been ruled out.
The following checks should be performed in accordance with the installation and operating manual and
the regulations in force:
Correctly sealed installation of the unit and duct system.
Check the duct system, unit and medium lines, if present, remove any foreign bodies if necessary.
The intake opening and inflow into the unit must be clear.
Check all mechanical and electrical protection measures (e.g. earthing).
Voltage, frequency and type of current must correspond with the rating plate.
Check all electrical connections and wiring.
Check any electrical, switching, safety and control devices connected.
The unit may not be switched on when the housing is open.
Measure electricity consumption at operating speed and compare with the rated current.
Check the fan for excessive vibrations and noise generation.
9. Operation
1
A) Button A: Can be used to increase or reduce the set-point
A temperature in the status display or to switch
2 through the individual operating menus or ope-
rating parameters.
B 3
4) Display
Battery
Timer active
Temperature
Filter
Fan stage
1
www.ruck.eu 19
English
A
P 2 Language setting
Use button A () to change to parameter language setting P 2. Now press button B () and the
P 2 V 2.3
control unit will change to input mode. You can now use buttons A ( and ) to select the language
required.
Press button B () again to accept the language selected.
Then press the Mode button (M) for at least 2 seconds. The parameters will be saved and the
menu will close. The display switches into operating mode.
Depending on the application, the devices are delivered with language selection 1 or 2.
Language selection 1: OR Language selection 2: ab V 3.0:
A A A
1 ENGLISH
1 ENGLISH 1 ENGLISH
2 FRANCAIS
A A
3 DANSK
2 FRANCAIS 2 SLOVENCINA
4 ESPAOL
A A
3 DANSK 3 ROMANA 5 NEDERLANDS
A A 6 PORTUGUS
4 ESPAOL 4
7 POLSKI
A A
8 SLOVENCINA
5 NEDERLANDS 5 TURKISH
9 ROMANA
A A
6 PORTUGUS 6 SLOVENSCINA 10
A A 11 TURKISH
7 POLSKI 7 HRVATSKI
12 SLOVENSCINA
A
13 HRVATSKI
8 MAGYAR
14 MAGYAR
M A
2 sec
9 MONGOLOOR 15 MONGOLOOR
OFF 16 SUOMI
4 sec
www.ruck.eu
UNUSED h Control unit outputs
0011001011001111
9.2. Overview menu management
6 sec
21
Constant pressure control with
22
Commissioning level 1 Fixed volumetric flow 2 Constant pressure control 3 volumetric flow balance
(trained personnel)
Variable air volume
P 13 TYP P 13 TYP P 13 TYP
RL-S RL-P RL-PV
P 18 h 400 m/h
BASIC VENT P 14 SENSORTYPE
VOC
P 19 i 600 m/h
P 20 AIR QUALITY
1400 PPM
P 14 SENSORTYPE
EXT.REG.
P 22 P 22 P 22
HEATING HEATING HEATING
P26 EXHAUST AIR FILT P26 EXHAUST AIR FILT P26 EXHAUST AIR FILT
100 Pa 100 Pa 100 Pa
P 27 P 27 P 27
CALIBRATE FILTER CALIBRATE FILTER CALIBRATE FILTER
9 sec
P 2 MAX-VALUE
Maximum set-point value
24,0
P 3 ENABLE
Enable
AUTOMATED
P 4 I-COMPONENT I - component
10
A P 5 P-COMPONENT
P - component
10
P 7 ADDRESS Address
1
www.ruck.eu
P 9 FAN BALANCE Fan calibration supply air
SUPPLY AIR 1.000
23
English
Temperatures
i 20,0 OUT 21,0
IN 21,0 h 22,0
Display of the currently prevailing air temperatures in the device.
i Outside air - temperature
IN Supply air - temperature
A
h Extract air - temperature
OUT Exhaust air - temperature
21,0 0%
4%
From the status display, press button A () and B () for approximately 8 s to get to the menu for
21,0 0%
4% setting the current time and the current day of the week.
8 sec
B The display shows the current time and day set. Set Day
A
1 Monday
Above the DAY display, there is a value indicating the current
1 11:30:45 2 Tuesday
day of the week.
DAY 3 Wednesday
When the value is flashing, the value can now be set. Press but- 4 Thursday
B tons B ( and ) to set the current day of the week (see table). 5 Friday
A
Press button A () to confirm the set value. 6 Saturday
7 Sunday
1 11:30:45 On the display, the hour now starts to flash. The hour is set by
DAY again pressing buttons B ( and ) and then confirmed with but-
ton A (). The display then moves to minutes which can be set
B in the same way with buttons B ( and ) and confirmed with
A button A ().
1 11:30:45
DAY
Press the Mode button (M) to go back to the status display.
M B
21,0 0%
4%
When confirming constant air volume control, the following parameters have to be adjusted/checked.
Constant 6 sec
hold down
P 13 RL-S
P 13 TYP
RL-S Variable control with constant volume operation
Factory setting
A
P 29 ROTOR P 29 ROTOR
700 Diameter of rotation heat exchanger (RL 700, 900, 1200, 1600, 2000)
Factory setting
A
www.ruck.eu 25
English
P 14 SENSORTYPE
W/O EXT.SENSOR
P 14 SENSORTYPE P 14 Sensor type CO2
B Volumetric flow, demand controlled by CO2 of the extract air
......................CO2
B
P 14 Sensor type VOC
P 14 SENSORTYPE
VOC Volumetric flow, demand controlled by external measuring transducer (VOC)
B
P 14 SENSORTYPE P 14 External control
EXT.REG. External volume flow control via 0 - 10 V input (see wiring diagram).
A B
P 23 and P 24
P 23
0 V 0 These settings can be found in the measuring range of the used measuring transdu-
cer. The measuring range is already preset for devices with integrated CO2 sensor.
A B
Example: Measuring area sensor 0 - 5000 ppm
P 23 = 0
P 24 P 24 = 5000
10 V 2000
A B
P 20 P 20 Air quality
AIR QUALITY When using external measuring transducers, the maximum air flow rate can be
adjusted by parameter P 20.
Example:
A
Class room CO: max. set-point e.g. 1400 ppm
VOC: max. set-point e.g. 1400 ppm
P 15 i 100 m/h P 15 Minimum ventilation supply air / P 16 Minimum ventilation extract air
MIN.VENT The volumetric flow can also be adjusted to MINIMUM VENTILATION (night setback). This parame-
Factory setting ter is controlled using the timer switch or Level 1 and can be set across the entire air volume range.
A B
P 16 h 100 m/h
MIN.VENT
Factory setting
A B
P 17 i 400 m/h P 17 Basic ventilation supply air / P 18 Basic ventilation extract air
BASIC VENT The designed volume flow for the BASIC VENTILATION is set in m/h on the control unit and regula-
Factory setting ted via the parameters P17 and P18 at Level 2 The volumetric flows can be individually set for supply
and extract air. To achieve the correct building ventilation, the supply air volume must be adjusted
A B according to the extract air volume. Complex adjustments are thus not necessary and the air volume
for the building ventilation can be adjusted exactly.
P 18 h 400 m/h
BASIC VENT
Factory setting
P 19 i 600 m/h P 19 Intermittent ventilation supply air / P 28 Intermittent ventilation extract air
SHOCK VENT The air handling unit runs on closing the external contact to the motion sensor and in Level 3 at the
Factory setting volume flows set in P19 and P28.
P 28 h 600 m/h
SHOCK VENT
Factory setting
Constant 6 sec
hold down P 13 RL-P Constant pressure control
Factory setting Operating mode P is the common control mode for the operation with variable air vo-
lumes by variable air volume controllers. The desired supply and extract air pressure
P 13 TYP can be set with the control unit. Two pressure sensors SEN P are necessary for this
RL-S operating mode. The device does not balance the air volume. We recommend a rehe-
ater for this operating mode to control the air volume balance.
P 13 TYP
B
RL-P
P 16 h 100 Pa
MIN.VENT
A B
P 18 h 150 Pa
BASIC VENT
www.ruck.eu 27
English
Constant 6 sec
hold down
Factory setting P 13 RL-PV Constant pressure control with balanced air volume
The operating mode PV is set for air-tight low-energy houses with variable air volumes
P 13 TYP by variable air volume controllers. The device automatically balances the air volume
RL-S
when sections will be added on or switched off. The desired supply pressure must only
P 13 TYP be set on the control unit. A response of the air volume controller is not necessary.
B
RL-PV
p Room
WRG
EXHAUST AIR V2 EXTRACT AIR
R1 R3
T T
M7
U2 M5
M2 p
KWR/DVR WWR/EHM*
FRESH AIR V1 - + SUPPLY AIR
R2 R4
T T F T
T
U1 F7
M1
M M
Control
www.ruck.eu 29
English
P 27 P 27 Calibrate filter
CALIBRATE FILTER Calibrating the pressure loss at the unclogged filter.
The calibrated value corresponds to 0% clogging.
For the filters to be calibrated the whole ventilation system has to be set up and
B
P 27
COMPLETED adjusted.
Pushing the B () button opens automatically the calibration mode. Display flashes
FILTER CALIBRATION After calibration, the display shows COMPLETED.
A
P 3 ENABLE P 3 Enable
AUTOMATED Switching the unit on and off with an external contact
The unit must be switched on at the control unit.
B Contact open. The unit is switched off.
P 3 ENABLE
AUTOMATED Contact closed. The unit is switched on / ready for operation.
The unit can only be switched on if the contact is closed. If the contact is open, the
P 3 ENABLE display will show NOT ENABLE. The contact should be closed and then acknow-
ACKNOWLEDGED
ledged with button B ().
The default mode is AUTOMATIC.
P 4 I-COMPONENT P 4 I - component
10 A value between 5-20 can be set for the I component.
The factory setting is at 10.
B
If the value decreases, the control becomes more sensitive.
A CAUTION! Due to highly sensitive settings, the control tends to pulsate.
P 5 P-COMPONENT P 5 P - component
10 A value between 5-20 can be set for the P component.
The factory setting is at 10.
B
If the value increases, the control becomes more sensitive.
CAUTION! Due to highly sensitive settings, the control tends to pulsate.
A
www.ruck.eu 31
English
.
.
.
OFF
1 18:00
DAY 22:00 The display flashes on the top line for the time point in which the device Set Day
starts the night mode on day 1 (Monday). Press buttons B ( and ) to 1 Monday
B set the hour and then confirm the entry with button A (). The display
2 Tuesday
A then moves on to the minutes which can be set in the same way with
3 Wednesday
buttons B ( and ) and confirmed with button A ().
(The minutes are set in 5-minute increments) 4 Thursday
1 18:00
5 Friday
DAY 22:00 The display now flashes on the bottom line for the time point in which
6 Saturday
the device stops the night mode on day 1 (Monday). The hour and
B minutes are again set and confirmed with buttons B ( and ) and 7 Sunday
A button A ().
2 18:30
DAY 21:30
B
Once the entry has been confirmed, the display moves on to day 2 where the individual on and off times
A can be set. Days 3 to 7 then follow.
Once you have set all of the parameters / days, press the Mode button (M) to go back to the units
2 18:30 status display.
DAY 21:30 However, you do not have to go through the whole time switch menu to get back to the status display.
You can press the Mode button (M) at any time to go back to the status display.
B
Note:
A
If the time 0:00 is given in the parameters, the unit will not switch to night operation.
3 18:30 The values set are saved even when there is a power failure or if the battery in the control unit runs
DAY 21:30 down. Only the current time and day of the week have to be reset.
Note: Instructions on changing the clock battery are give in section 10.3.4.
.
.
.
OFF
21,0 0% 21,0 0%
4% 4%
Time switch on Time switch off
www.ruck.eu 33
English
Basic ventilation
Day 1
Basic ventilation
4:00 22:00
Day 1
Basic ventilation
Minimum
ventilation
9.7. Functions
Maintenance and repairs may only be performed by specialist personnel in accordance with this
installation and operating manual and the regulations in force.
Do not repair defective or damaged units yourself, but report the damage or faults to the manufac-
turer in writing.
www.ruck.eu 35
English
10.3. Maintenance
10.3.1. Rotating wheel heat exchanger
Rotating wheel heat exchangers generally require no maintenance. However, cleaning the exchanger
occasionally is recommended. Damage to the blades should always be avoided.
a) c) A (1 : 10)
1
1
b)
3 3
1
d)
2
3
Fig. 18 Fig. 19 Fig. 20
3
Fitting a new drive Welding the drive belt (3) with clamp (1) Make sure that the belt is running
belt. and welding paddle (2). smoothly on the pulley..
36 128625 00 Tel. +49 7930 9211-0 Fax +49 7930 9211-150
A (1 : 10) 12862
English
A) B)
C)
Fig. 24
(1) Control cable
(2) Control unit cover
(3) Battery holder
www.ruck.eu 37
English
Control unit
120 Ohm Line
Line
Fig. 25:
www.ruck.eu 39
English
Register
Parameter name Value range
address
RL 700 RL 900 RL 1200 RL1600 RL 2000
40016 Minimum ventilation supply air 500 - 1800 m/h 1500 - 3500 m/h 2500 - 7500 m/h 2500 - 8500 m/h 4500 - 11500 m/h
40017 Minimum ventilation extract air 500 - 1800 m/h 1500 - 3500 m/h 2500 - 7500 m/h 2500 - 8500 m/h 4500 - 11500 m/h
40018 Basic ventilation supply air 500 - 1800 m/h 1500 - 3500 m/h 2500 - 7500 m/h 2500 - 8500 m/h 4500 - 11500 m/h
40019 Basic ventilation extract air 500 - 1800 m/h 1500 - 3500 m/h 2500 - 7500 m/h 2500 - 8500 m/h 4500 - 11500 m/h
40020 Intermittent ventilation supply air 500 - 1800 m/h 1500 - 3500 m/h 2500 - 7500 m/h 2500 - 8500 m/h 4500 - 11500 m/h
40029 Intermittent ventilation extract air 500 - 1800 m/h 1500 - 3500 m/h 2500 - 7500 m/h 2500 - 8500 m/h 4500 - 11500 m/h
Bit 0 1 = Enable_signal_external
Bit 1 1 = Frequency converter ready Fan motor electronic ok
Bit 2 1 = Thermal switch, fan
Bit 3 1 = Frost protection OK
Bit 4 1 = Motion detector
Bit 5 1 = Fire detector ok
Bit 6 1 = Turn control for rotation heat exchanger
Bit 7 1 = Thermocontact rotor motor
Bit 8 Reserved
www.ruck.eu 41
English
Bit 0 Reserved
Bit 1 Reserved
Bit 2 1 = Cooling requirement
Bit 3 1 = Rotor motor
Bit 4 Reserved
Bit 5 1 = Heating valve open
Bit 6 1 = Heating valve closed
Bit 7 1 = Heating pump on
Bit 8 1 = Unit defective
Bit 9 1 = Damper closed
Bit 10 1 = Damper open
Bit 11 1 = Cooling valve open
Bit 12 1 = Cooling valve closed
Bit 13 1 = Enable frequency converter
Bit 14 Reserved
Bit 15 Reserved
alue
V
0 No error
1 Supply-air temperature sensor defective
2 Room-air temperature sensor defective
3 Outlet-air temperature sensor defective
4 Exhaust-air temperature sensor defective
5 Outdoor-air temperature sensor defective
6 Damper position
7 Frost protection triggered
8 Safety thermostat triggered
9 Thermal switch for ventilator triggered
10 Frequency converter defective
11 Reserved
12 Not enabled
13 Cooling plant defective
14 Fire detector
15 Reserved
16 Reserved
17 Supply-air temperature too low
18 Supply-air temperature too hot
19 Reserved
20 Heat exchanger
13.2. Disposal
Careless disposal of the unit may be cause pollution.
Please therefore dispose of the unit in accordance with the national requirements that apply in your
country.
14. Troubleshooting
Please note the following instructions:
Proceed systematically and purposefully when troubleshooting, even when under the pressure of
time. In the worst case, randomly and indiscriminately dismantling and changing settings
may result in it no longer being possible to determine the original cause of the fault.
Get an overview of the units operation in conjunction with the overall installation.
Try to clarify whether the unit provided the required function in the overall installation before the
fault occurred.
Try to find any changes to the overall installation in which the unit is installed:
1. Have the units operating conditions or operating range been changed?
2. Have any changes (e.g. reconfigurations) or repairs been performed on the overall system (in-
stallation, electrics, control) or to the unit? If yes: what?
3. Has the unit been operated correctly?
4. How does the fault appear?
Form a clear idea of the cause of the fault. If necessary, question the immediate operator or the
installation operator.
If you have not been able to remove the fault, please contact the manufacturer. The contact
address can be found at www.ruck.eu or on the back cover of this operating and installation
manual.
F2 / T 6,3 A Valve gear and cable defect. Replace valve gear and cable.
Circulating pump and cable defect. Replace circulating pump and cable.
Damper drive and cable defect. Replace damper drive and cable.
Rotor motor and cable defect. Replace rotor motor and cable.
www.ruck.eu 43
English
ERR ERROR
The control unit has no reception.
Check the connection or replace the cable if necessary.
Supply air temperature sensor fault
F01 FAULT The supply air temperature sensor is defective or the cable is broken.
SUPPLY AIR TEMP Replace the defective temperature sensor or replace the broken cable if necessary.
After removing the cause of the fault, the fault must be acknowledged with button B ().
Specifications:
RLI 700 EC 20
RLI 700 EC 21
RLI 700 EC 22
RLI 700 EC 23
RLI 700 EC 24
RLI 700 EC 25
RLI 900 FC 20
RLI 900 FC 21
RLI 900 FC 22
RLI 900 FC 23
RLI 900 FC 24
RLI 900 FC 25
Units / Model
130052 130051 130050 130049 130048 130047 128908 128910 128913 128916 128919 128922
Length L mm 1150 1270
Width B mm 913 1113
Height H mm 895 1095
Nominal width NW mm 500x300 / 500x250 600x300 / 600x400
Weight kg 267,0 287,0 287,0 315,0 350,0 350,0
Operating voltage V 400V 3~N 400V 3~
Frequency Hz 50 50
Power consumption W 684 2300
Maximum current A 3,3 4,0
Max. ambient temp. C 40 40
Max. air volume m/h 1700 4070
RPM 1/min 3610 2880
Max. pressure Pa 770 1010
Sound intake air LWA 5 dB(A) 80 84
Sound outlet air LWA 6 dB(A) 70 76
Sound extraction LWA 2 dB(A) 53 67
Fan stage 3 3
Filter grade M5 + F7 M5 + F7
Wiring diagrams No. 128371 128370
Heating coil warm water x x x x x x x x x x x x
Cooling coil cold water - - x x - - - - x x - -
Cooling* / DX-Coil* - - - - x x - - - - x x
Diameter RWT mm 700 900
Length driving belt mm 2310 2940
Specifications:
RLI 1200 EC 20
RLI 1200 EC 21
RLI 1200 EC 22
RLI 1200 EC 23
RLI 1200 EC 24
RLI 1200 EC 25
RLI 1600 EC 20
RLI 1600 EC 21
RLI 1600 EC 22
RLI 1600 EC 23
RLI 1600 EC 24
RLI 1600 EC 25
RLI 2000 EC 20
RLI 2000 EC 21
RLI 2000 EC 22
RLI 2000 EC 23
RLI 2000 EC 24
RLI 2000 EC 25
Units / Model
128360 128619 128622 128676 128625 128673 128992 128995 128998 129001 129004 129007 128868 128870 128827 128823 128881 128820
Length L mm 1405 1405 1650
Width B mm 1413 1813 2213
Height H mm 1395 1795 2220
Nominal width NW mm 800x550 / 800x500 1200x600 / 1200x650 1400x710
Weight kg 493,0 456,0 456,0 685,0 685,0 685,0 1070,0 1070,0 1070,0
Operating voltage V 400V 3~N 400V 3~N 400V 3~N
Frequency Hz 50 50 50
Power consumption W 3900 4000 4410
Maximum current A 7,0 7,0 7,8
Max. ambient temp. C 50 50 40
Max. air volume m/h 8530 9750 11210
RPM 1/min 1860 2130 1435
Max. pressure Pa 1100 1180 820
Sound intake air LWA 5 dB(A) 82 81
Sound outlet air LWA 6 dB(A) 75 79
Sound extraction LWA 2 dB(A) 71 60
Fan stage 3 3 3
Filter grade 2 x M5 + 2 x F7 2 x M5 + 2 x F7 3 x M5 + 3 x F7
Wiring diagrams No. 128365 128367 128373
Heating coil warm water x x x x x x x x x x x x x x x x x x
Cooling coil cold water - - x x - - - - x x - - - - x x - -
Cooling* / DX-Coil* - - - - x x - - - - x x - - - - x x
Diameter RWT mm 1200 1600 2000
Length driving belt mm 3890 5200 6500
www.ruck.eu 45
English
B
T
H
B
H
Fig. 27:
Outside dimensions of the Fig. 28:
control unit. Installation dimensions of
the control unit.
Control unit
Size B+H+T mm 82+82+30
Fig. 26: L Assembly size B mm 60
Dimensions of the D mm 22
supply air unit
16. Appendix
16.1. List of parameters
The following table lists all of the parameters that are displayed on the control unit, some of which may be changed.
Section 9.3.4. Parameter settings menu gives full instructions on operating and setting the corre-
sponding parameters.
Temperaturbegrenzer Rotorsteuerung
2 A - In 1
D - In
A - Out
A - Out
0V
0V
+24V
3 A - In 2
B1
2 D - In N
3 +24V B4: Filterberwachung Abluft /
Drehkontrolle Rotor 4 D - In B4 5 -A2
Rotor rotary control 5 +24V
Filter monitoring Extract air L1 6 -G1
2 x 0,75mm (102674) D - In N
6 8
7 +24V L1 9
DA(0-10V)
8 D - In
9 +24V
-X6
Hall_C
Hall_A
Hall_B
10 D - In
Break
CCW
Gnd
+5V
11 +24V
Gnd
Gnd
+5V
CW
1
+AT
+ + - -
W
V
U
12 D - In 2
13 +24V 3
N
-X5 L1 5
6
1 Temp 1 N
2 L1 8
3 Temp 2 L1
4 -A1 9
5 Temp 3 0,75mm BU
6 -X16 BU BN
www.ruck.eu
7 Temp 4 L1 1 0.75mm 0.75mm 0,75mm BU
8 L1 2
0V N
A 4
B L1 5 1 2 3 4 5 6 7 8
+24V 6
16.2. Wiring diagrams
7
8
XB1 9
XB3 F2 -X4
GN
GN
RD
BU
BU
YE
YE
BK
N
RL 700 EC
N
N
4
thick thin
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
M
-M10
Rotor Antrieb
Rotor drive
2.50 mm BK
2.50 mm BK
2.50 mm BK
2.50 mm BU
2.50 mm GNYE
1 3 5
-Q1
Einspeisung / Power input
2 4 6
L1 L2 L3 N PE 400V / 3~ / N / 50Hz
Sicherung extern max. 10A
Fuse external max. 10A
English
English
bn / 13
bn/wh / 12 bn / 11
bn/wh / 10
or/wh / 8
gn/wh / 6
=M2
0V -X15 -X14 -X9
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
SL 2 A - In
0-10V 1
D - In
A - Out
A - Out
0V
0V
+24V
3 A - In 2
N 4 A - Out B1 3
5 A - Out 4
230V~
Strung
Strung 6 +24V 5
Fault
7 D - In 6
gn/wh / 7
or/wh / 9
Fault 8 0V B2 7
9 0V 8
10 0V L1 9
11 0V
12 0V
B3: Filterberwachung Zuluft / B3 -X3
M
-X8 Filter monitoring Supply air L1
N
2
1 +24V L1 3
2 D - In N
3 +24V B4: Filterberwachung Abluft / 5
4 D - In Filter monitoring Extract air B4 L1 6
5 +24V N
6 D - In
8
7 +24V L1 9
8 D - In
Abluftventilator 9
10
+24V
D - In -X6
Extract air fan 11
12
+24V
D - In
1
2
13 +24V 3
N
-X5 L1 5
6
1 Temp 1 N
2 L1 8
3 Temp 2 L1 9
4 -A1
5 Temp 3
=M1
6
7 Temp 4
-X16
L1 1
8 L1 2
0V 0V N
SL A 4
0-10V B L1 5
N +24V 6
7
230V~
Strung
Strung 8
XB1
Fault
9
Fault
XB3 F2 -X4
N
N
N
M
4
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
Zuluftventilator
Supply air fan
Frostschutzthermostat 1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
N 3 - Wege - Ventil
0V
0V
+24V
Frost protection thermostat 3 A - In 2
B1
-M5 3-way valve
4 A - Out 3 close
~
5 A - Out
M
4
6 +24V open Khlen Option
1
5
7 D - In 6 Cooling Optional
8 0V B2 7
9 0V N 230V~ max. 2A
Wiring diagrams No.: 128371
8
10 0V L1 9
Brandmelder Option 11 0V
Fire detection 12 0V
-X3 Auenluftklappe
~
Optional B3 -M3
M
-X8 N Fresh air flap
1
L1 2
1 +24V L1 3 L
2 D - In N
3 +24V
B4 5 N
56
4 D - In L1 6
-X1 5 +24V N
6 D - In Abluftklappe
~
8 -M4
M
7 +24V L1 9 Extract air flap
1
8 D - In
9 +24V L
10 D - In -X6
11 +24V 1 Freigabe Kltemaschine
12 D - In 2
13 +24V 3
Enable Cooling unit
N
BN
-X5 L1 5
6
www.ruck.eu
1 Temp 1
WH
BN 2 -A1 L1
N
8
WH 3 Temp 2 L1 9
BN 4
WH 5 Temp 3 N
BN 6 -X16 Zirkulationspumpe
-M6.1 Circulation - pump
~
7 Temp 4
M
WH L1 1
8 L
1
L1 2
0V N 230V~ max. 2A
Fortluft / Exhaust air -R1 A
B
4
L1 5
+24V 6
7
RL 700 EC
8
Auenluft / Fresh air -R2 XB1 9
XB3 F2 -X4
N N 3 - Wege - Ventil
Abluft / Extract air -R3 N
close -M6 3-way valve
3 4
N
~
M
4 open Heizen
1
5
F1 6 Heating
Zuluft / Supply air -R4 7
230V~ max. 2A
1 2
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
-X1
Option
Option Optional
127615
Optional
Bediengert
manuelle Verbindung mit einem Kabel
Remote control manuell connection with a cable --> 120Ohm
+24V Mod Bus
B
A
0V
English
English
0,75mm BU
0,75mm BU
0,75mm BU
0,75mm BU
-X15 -X14 -X9
Temperaturbegrenzer Rotorsteuerung
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
+24V
3 A - In 2
4 A - Out B1 3
5 A - Out 4
6 +24V 5
7 D - In 6
B1: Volumenstrom Zuluft /
Part 1
8 0V B2 7
9 0V Supply air flow
8
10 0V L1 9
11 0V B2: Volumenstrom Abluft /
Extract airflow
12 0V
-X3 L N PE
B3
-X8 B3: Filterberwachung Zuluft / L1
N
2
1 +24V Filter monitoring Supply air
L1 3
Wiring diagrams No.: 128370
DA(0-10V)
8 D - In
9 +24V
-X6
Hall_C
Hall_A
Hall_B
10 D - In
Break
CCW
Gnd
+5V
11 +24V
Gnd
Gnd
+5V
CW
1
+AT
+ + - -
W
V
U
12 D - In 2
13 +24V 3
N
-X5 L1 5
6
1 Temp 1 N BU BN
2 L1 8 0.75mm 0.75mm
3 Temp 2 L1
4 -A1 9
5 Temp 3 0,75mm BU
6
7 Temp 4
-X16 0,75mm BU
L1 1
8 L1 2
0V N
A 4
B
GN
GN
RD
BU
BU
YE
YE
BK
N
RL 900 FC
N
N
4
thick thin
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
M
-M10
Rotor Antrieb
Rotor drive
2.50 mm BK
2.50 mm BK
2.50 mm BK
2.50 mm BU
2.50 mm GNYE
1 3 5
-Q1
Einspeisung / Power input
2 4 6
L1 L2 L3 N PE 400V / 3~ / N / 50Hz
Sicherung extern max. 10A
Fuse external max. 10A
50
51
-X15 -X14 -X9
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
0V
0V
+24V
3 A - In 2
4 A - Out B1 3
5 A - Out 4
6 +24V 5
Part 2
7 D - In 6
8 0V B2 7
9 0V 8
10 0V L1 9
11 0V
12 0V
B3 -X3
-X8 L1
N
2
Wiring diagrams No.: 128370
1 +24V L1 3
2 D - In N
3 +24V 5
4 D - In B4 L1 6
5 +24V N
6 D - In
8
7 +24V L1 9
8 D - In
9 +24V
10 D - In -X6
11 +24V 1
12 D - In 2
13 +24V -A1 3
N
-X5 L1 5
6
1 Temp 1 N
2 L1 8
3 Temp 2 L1 9
4
5 Temp 3
-X16
www.ruck.eu
6
7 Temp 4 L1 1
8 L1 2
0V N
A 4
B L1 5
+24V 6
7
8
XB1 9
11
13
GN 12
GN 10
1
WH 9
7
2
3
WH 8
BU 6
RD
GY
GY
BU
Zuluftventilator
PK
PK
XB3 F2 -X4
Abluftventilator
RL 900 FC
N
Supply air fan
COM
COM
N
R1C
R1C
R1A
Extract air fan
24V
RIA
AI1
AI1
LI1
LI1
N
4
5
F1 6
7
-U1 8 -U2
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
L1 N PE L1 N PE
ER12 ER12
1 1.50 mm BK 1 1.50 mm BK
2 1.50 mm BK 2 1.50 mm BK
1.50 mm GNYE 1.50 mm GNYE
R1A R1B R1C COM AI1 5V AO1 R1A R1B R1C COM AI1 5V AO1
LO1 CLO COM LI1 LI2 LI3 LI4 24V LO1 CLO COM LI1 LI2 LI3 LI4 24V
U V W U V W
PE PE
Frequenzumformer
Frequency converter
English
English
Frequenzumformer Frequenzumformer
Frequency converter Frequency converter
FU - Parameter:
-U1.1 -U2.1
L1 N PE L1 N PE
ER12 ER12
3,3
Part 3
R1A R1B R1C COM AI1 5V AO1 R1A R1B R1C COM AI1 5V AO1
Wiring diagrams No.: 128370
Thermo M2.1
Thermo M1.2
Thermo M2.2
RL 900 FC
-X30 1 2 -X30 3 4
GNYE
GNYE
BK 1
BK 1
BK 2
BK 3
BK 2
BK 3
BK 4
BK5
BK 4
BK5
U V W PE U V W PE
TW TW
TW M TW M
3 ~ 3 ~
-M1 -M2
Zuluftventilator Abluftventilator
Supply air fan Extract air fan
52
53
Bewegungsmelder
Strung Gert
Motion control Unit fault
Option / Optional potentialfreier Kontakt
0-10V free potential contact
Khlen / Cooling max 250V~ 2A
0V Heizen / Heating Betriebsmeldung
Freigabe Gert Operating message
Unit enable max 250V~ 2A
Thermo M1.1
Thermo M1.2 Thermokontakt
-X15 -X14 -X9 Thermo M2.1
Thermo M2.2 Thermal contact
Part 4
Frostschutzthermostat 1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
N 3 - Wege - Ventil
0V
0V
+24V
Frost protection thermostat 3 A - In 2
B1
-M5 3-way valve
4 A - Out 3 close
~
5 A - Out
M
4
6 +24V open Khlen Option
1
5
7 D - In 6 Cooling Optional
8 0V B2 7
N 230V~ max. 2A
Wiring diagrams No.: 128370
Brandmelder 9 0V 8
Option 10 0V L1 9
Fire detection Optional 11 0V
12 0V
-X3 Auenluftklappe
~
B3 -M3
M
-X8 N Fresh air flap
1
L1 2
1 +24V L1 3 L
2 D - In N
3 +24V
B4 5 N
56
4 D - In
-X1 5 +24V
L1 6
N
6 D - In Abluftklappe
~
8 -M4
M
7 +24V L1 9 Extract air flap
1
8 D - In
9 +24V L
10 D - In -X6
11 +24V 1 Freigabe Kltemaschine
12 D - In 2
13 +24V 3 Enable Cooling unit
N
-X5 L1 5
www.ruck.eu
BN 6
1
WH
BN 2
Temp 1 -A1 L1
N
8
WH 3 Temp 2 L1 9
BN 4
WH 5 Temp 3 N
BN 6 -X16 Zirkulationspumpe
-M6.1 Circulation - pump
~
7 Temp 4
M
WH L1 1
8 L
1
L1 2
0V N 230V~ max. 2A
Fortluft / Exhaust air -R1 A
B
4
L1 5
+24V 6
7
RL 900 FC
8
Auenluft / Fresh air -R2 XB1 9
XB3 F2 -X4
N N 3 - Wege - Ventil
Abluft / Extract air -R3 N
close -M6 3-way valve
3 4
N
~
M
4 open Heizen
1
5
F1 6 Heating
Zuluft / Supply air -R4 7
230V~ max. 2A
1 2
8
-X1 L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
Option
Optional
127615
Bediengert Optional
manuelle Verbindung mit einem Kabel
Remote control
manuell connection with a cable --> 120Ohm
+24V Mod Bus
B
A
0V
English
English
0,75mm BU
0,75mm BU
0,75mm BU
0,75mm BU
-X15 -X14 -X9
Temperaturbegrenzer Rotorsteuerung
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
+24V
3 A - In 2
4 A - Out B1 3
5 A - Out 4
6 +24V 5
7 D - In 6
Part 1
L1 3
DA(0-10V)
8 D - In
9 +24V
-X6
Hall_C
Hall_A
Hall_B
10 D - In
Break
CCW
Gnd
+5V
11 +24V
Gnd
Gnd
+5V
CW
1
+AT
+ + - -
W
V
U
12 D - In 2
13 +24V 3
N
-X5 L1 5
6
1 Temp 1 N
2 BU BN
L1 8 0.75mm 0.75mm
3 Temp 2 L1
4 -A1 9 0,75mm BU
5 Temp 3 0,75mm BU
6
7 Temp 4
-X16
L1 1
8 L1 2
0V N
A 4
XB3 F2
GN
GN
RD
BU
BU
YE
YE
BK
N
N
N
4
thick thin
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
M
-M10
Rotor Antrieb
Rotor drive
2.50 mm BK
2.50 mm BK
2.50 mm BK
2.50 mm BU
2.50 mm GNYE
1 3 5
-Q1
Einspeisung / Power input
2 4 6
L1 L2 L3 N PE 400V / 3~ / N / 50Hz
Sicherung extern max. 16A
Fuse external max. 16A
54
55
-X15 -X14 -X9
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
0V
+24V
0V
3 A - In 2
4 A - Out B1 3
5 A - Out 4
Part 2
6 +24V 5
7 D - In 6
8 0V B2 7
9 0V 8
10 0V 3 8 6 12 13
2 1 9 7 10 11 11 0V
L1 9
12 0V
-X3
WH
RD
GY
BU
PK
B3
Wiring diagrams No.: 128365
-X8 N
WH
RD
GY
BN
BU
PK
L1 2
1 +24V L1 3
2 D - In N
3 +24V 5
4 D - In B4 L1 6
5 +24V N
6 D - In
8
7 +24V L1 9
8 D - In
9 +24V
10 D - In -X6
11 +24V 1
12 D - In 2
-U1
13 +24V -A1 3
-U2
N
-X5 L1 5
17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1
6 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Temp 1 N
2
Freigabe
Freigabe
L1 8
0 - 10V
0 - 10V
+24V
+24V
3
gnd
gnd
Temp 2 L1 9
4
www.ruck.eu
Invento IFT03 5 Temp 3
6 -X16
Invento IFT03
7 Temp 4 L1 1
8 L1 2
0V N
M6 M5 M4 M3 M2 M1 PE L1 L2 L3 PE PE A 4 M6 M5 M4 M3 M2 M1 PE L1 L2 L3 PE PE
B L1 5
+24V 6
7
8
XB1 9
RL 1200 EC
1
6
5
4
3
2
6
5
4
3
2
XB3 F2 -X4
N
N
N
4
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
-M1 EC -M2 EC
M M
1.50 mm 1 1.50 mm 1
1.50 mm 2 1.50 mm 2
1.50 mm 3 1.50 mm 3
1.50 mm GNYE 1.50 mm GNYE
Zuluftventilator Abluftventilator
Supply air fan Extract air fan
English
English
Frostschutzthermostat 1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
N 3 - Wege - Ventil
0V
0V
+24V
Frost protection thermostat 3 A - In 2
B1
-M5 3-way valve
4 A - Out 3 close
~
5 A - Out
M
4
6 +24V open Khlen Option
1
5
7 D - In 6 Cooling Optional
8 0V B2 7
Brandmelder 9 0V N 230V~ max. 2A
Wiring diagrams No.: 128365
~
B3 -M3
M
-X8 N Fresh air flap
1
L1 2
1 +24V L1 3 L
2 D - In N
3 +24V
B4 5 N
5 6
4 D - In
-X1 5 +24V
L1 6
N
6 D - In Abluftklappe
~
8 -M4
M
7 +24V L1 9 Extract air flap
1
8 D - In
9 +24V L
10 D - In -X6
11 +24V 1 Freigabe Kltemaschine
12 D - In 2
13 +24V 3 Enable Cooling unit
N
BN
-X5 L1 5
6
1
WH
BN 2
Temp 1 -A1 L1
N
8
WH 3 Temp 2 L1 9
BN 4
5 Temp 3 N
~
7 Temp 4
M
WH L1 1
8 L
1
L1 2
0V N 230V~ max. 2A
Fortluft / Exhaust air -R1 A
B
4
L1 5
+24V 6
RL 1200 EC
7
8
Auenluft / Fresh air -R2 XB1 9
XB3 F2 -X4
N N 3 - Wege - Ventil
Abluft / Extract air -R3 4 N
close
N -M6 3-way valve
~
M
3 4 open Heizen
1
5
F1 6 Heating
Zuluft / Supply air -R4 2 7 230V~ max. 2A
8
-X1 1 L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
Option
Optional
127615
Bediengert Optional
Remote control manuelle Verbindung mit einem Kabel
manuell connection with a cable --> 120Ohm
+24V Mod Bus
B
A
0V
56
57
0,75mm BU
0,75mm BU
0,75mm BU
0,75mm BU
-X15
Temperaturbegrenzer Rotorsteuerung
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
-X14 -X9
+24V
3 A - In 2
4 A - Out B1 3
5 A - Out 4
6 +24V 5
7 D - In 6
8 0V B1: Volumenstrom Zuluft /
B2 7
Part 1
N
Drehkontrolle Rotor 3 +24V B4: Filterberwachung Abluft /
B4 5 -A2
4 D - In
Rotor rotary control 5 +24V
Filter monitoring Extract air L1 6 -G1
D - In N
2 x 0,75mm (102674) 6 8
7 +24V L1 9
DA(0-10V)
8 D - In
9 +24V
-X6
Hall_C
Hall_A
Hall_B
10 D - In
Break
CCW
Gnd
+5V
11 +24V
Gnd
Gnd
+5V
CW
1
+AT
+ + - -
W
V
U
12 D - In 2
13 +24V 3
N
-X5 L1 5
6 BU BN
1 Temp 1 N 0.75mm 0.75mm
2 L1 8
3 Temp 2 L1
4 -A1 9 0,75mm BU
5 Temp 3 0,75mm BU
6 -X16
www.ruck.eu
7 Temp 4 L1 1
8 L1 2
0V N
A 4
B L1 5 1 2 3 4 5 6 7 8
+24V 6
7
8
XB1 9
XB3 F2 -X4
RL 1600 EC
GN
GN
RD
BU
BU
YE
YE
BK
N
N
N
4
thick thin
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
M
-M10
Rotor Antrieb
Rotor drive
2.50 mm BK
2.50 mm BK
2.50 mm BK
2.50 mm BU
2.50 mm GNYE
1 3 5
-Q1
Einspeisung / Power input
2 4 6
L1 L2 L3 N PE 400V / 3~ / N / 50Hz
Sicherung extern max. 16A
Fuse external max. 16A
English
English
+24V
3 A - In 2
4 A - Out B1 3
5 A - Out
Part 2
4
6 +24V 5
7 D - In 6
8 0V B2 7
9 0V 8
10 0V 3 8 6 12 13
2 1 9 7 10 11 11 0V
L1 9
12 0V
-X3
WH
RD
GY
BU
PK
B3
Wiring diagrams No.: 128367
BU
PK
L1 2
1 +24V L1 3
2 D - In N
3 +24V 5
4 D - In B4 L1 6
5 +24V N
6 D - In
8
7 +24V L1 9
8 D - In
9 +24V
10 D - In -X6
11 +24V 1
12 D - In 2
-U1 13 +24V -A1 3 -U2
N
-X5 L1 5
17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1
6 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Temp 1 N
2
Freigabe
Freigabe
L1 8
0 - 10V
0 - 10V
+24V
+24V
3 Temp 2
gnd
gnd
L1 9
4
Invento IFT03 5 Temp 3
6 -X16
Invento IFT03
7 Temp 4 L1 1
8 L1 2
1
6
5
4
3
2
6
5
4
3
2
XB3 F2 -X4
N
N
N
4
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
-M1 EC -M2 EC
M M
1.50 mm 1 1.50 mm 1
1.50 mm 2 1.50 mm 2
1.50 mm 3 1.50 mm 3
1.50 mm GNYE 1.50 mm GNYE
Zuluftventilator Abluftventilator
Supply air fan Extract air fan
58
59
Bewegungsmelder Strung Gert
Motion control
Unit fault
Option / Optional
0-10V Khlen / Cooling potentialfreier Kontakt
0V Heizen / Heating free potential contact
Freigabe Gert
max 250V~ 2A Betriebsmeldung
Unit enable
Operating message
max 250V~ 2A
-X15 -X14 -X9
Part 3
Frostschutzthermostat 1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
N 3 - Wege - Ventil
0V
0V
+24V
Frost protection thermostat 3 A - In 2
B1
-M5 3-way valve
4 A - Out 3 close
~
5 A - Out
M
4
6 +24V open Khlen Option
1
5
7 D - In 6 Cooling Optional
8 0V B2 7
9 0V N 230V~ max. 2A
Wiring diagrams No.: 128367
Brandmelder Option 10 0V
8
L1 9
Fire detection Optional 11 0V
12 0V
-X3 Auenluftklappe
~
B3 -M3
M
-X8 N Fresh air flap
1
L1 2
1 +24V L1 3 L
2 D - In N
3 +24V
B4 5 N
5 6
4 D - In
-X1 5 +24V
L1 6
N
6 D - In Abluftklappe
~
8 -M4
M
7 +24V L1 9 Extract air flap
1
8 D - In
9 +24V L
10 D - In -X6
11 +24V 1 Freigabe Kltemaschine
12 D - In 2
13 +24V 3 Enable Cooling unit
N
-X5 L1 5
www.ruck.eu
BN 6
1
WH
BN 2
Temp 1 -A1 L1
N
8
WH 3 Temp 2 L1 9
BN 4
WH 5 Temp 3 N
BN 6 -X16 Zirkulationspumpe
-M6.1 Circulation - pump
~
7 Temp 4
M
WH L1 1
8 L
1
L1 2
0V N 230V~ max. 2A
Fortluft / Exhaust air -R1 A
B
4
L1 5
+24V
RL 1600 EC
6
7
8
Auenluft / Fresh air -R2 XB1 9
XB3 F2 -X4
N N 3 - Wege - Ventil
Abluft / Extract air -R3 4 N
close
N -M6 3-way valve
~
M
3 4 open Heizen
1
5
F1 6 Heating
Zuluft / Supply air -R4 2 7 230V~ max. 2A
8
-X1 1 L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
Option
Optional
127615
Bediengert Optional
manuelle Verbindung mit einem Kabel
Remote control
manuell connection with a cable --> 120Ohm
+24V Mod Bus
B
A
0V
English
English
0,75mm BU
0,75mm BU
0,75mm BU
0,75mm BU
-X15 -X14 -X9
Temperaturbegrenzer Rotorsteuerung
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
+24V
3 A - In 2
4 A - Out B1 3
5 A - Out 4
6 +24V 5
7 D - In 6
8 0V B1: Volumenstrom Zuluft /
B2 7
Part 1
DA(0-10V)
8 D - In
9 +24V
-X6
Hall_C
Hall_A
Hall_B
10 D - In
Break
CCW
Gnd
+5V
11 +24V
Gnd
Gnd
+5V
CW
1
+AT
+ + - -
W
V
U
12 D - In 2
13 +24V 3
N
-X5 L1 5
6 BU BN
1 Temp 1 N 0.75mm 0.75mm
2 L1 8
3 Temp 2 L1
4 -A1 9 0,75mm BU
5 Temp 3 0,75mm BU
6
7 Temp 4
-X16
L1 1
8 L1 2
0V N
A 4
B
GN
GN
RD
BU
BU
YE
YE
BK
N
N
N
4
thick thin
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
M
-M10
Rotor Antrieb
Rotor drive
2.50 mm BK
2.50 mm BK
2.50 mm BK
2.50 mm BU
2.50 mm GNYE
1 3 5
-Q1
Einspeisung / Power input
2 4 6
L1 L2 L3 N PE 400V / 3~ / N / 50Hz
Sicherung extern max. 16A
Fuse external max. 16A
60
61
-X15 -X14 -X9
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
0V
0V
+24V
3 A - In 2
4 A - Out B1 3
5 A - Out 4
6 +24V 5
7 D - In 6
8 0V B2 7
9 0V 8 3 8 6 12 13
Part 2
2 1 9 7 10 11 10 0V L1 9
11 0V
12 0V
-X3
WH
RD
GY
BU
PK
B3
-X8 N
WH
RD
GY
BN
BU
PK
L1 2
1 +24V L1 3
2 D - In N
3 +24V 5
B4
Wiring diagrams No.: 128373
4 D - In L1
-U1 5 +24V
6
N
Freigabe
D - In
0 - 10V
Left / Right
6
T04 7 +24V
8 -U2
Freigabe
+15V
L1 9
0 - 10V
Left / Right
T04
gnd
8 D - In
+15V
9 +24V
gnd
7 8 9 10 11 12 X2 13 14 15 16 17 18 X3 10 D - In -X6
11 +24V 1
12 D - In 2 7 8 9 10 11 12 X2 13 14 15 16 17 18 X3
13 +24V -A1 3
N
-X5 L1 5
6
1 Temp 1 N
2 L1 8
3 Temp 2 L1 9
M1 M2 M3 M4 M5 M6 X4 4
5 Temp 3
25 26 27 28 29 30 X5 6 -X16 M1 M2 M3 M4 M5 M6 X4
7 Temp 4 L1 1 25 26 27 28 29 30 X5
8 L1 2
0V
www.ruck.eu
N
A 4
B L1 5
L1 L2 L3 X6 +24V 6
7
8 L1 L2 L3 X6
XB1 9
XB3 F2 -X4
N
1
2
3
4
5
6
1
2
3
4
5
6
RL 2000 EC
N
4
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
-M1 EC -M2 EC
M M
1.50 mm 1 1.50 mm 1
1.50 mm 2 1.50 mm 2
1.50 mm 3 1.50 mm 3
1.50 mm GNYE 1.50 mm GNYE
1
Zuluftventilator Abluftventilator
Supply air fan Extract air fan
0
1500
English
English
Frostschutzthermostat 1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
N 3 - Wege - Ventil
0V
0V
+24V
Frost protection thermostat 3 A - In 2
B1
-M5 3-way valve
4 A - Out 3 close
~
5 A - Out
M
4
6 +24V open Khlen Option
1
5
7 D - In 6 Cooling Optional
8 0V B2 7
Wiring diagrams No.: 128373
~
B3 -M3
M
-X8 N Fresh air flap
1
L1 2
1 +24V L1 3 L
2 D - In N
3 +24V
B4 5 N
56
4 D - In
-X1 5 +24V
L1 6
N
6 D - In Abluftklappe
~
8 -M4
M
7 +24V L1 9 Extract air flap
1
8 D - In
9 +24V L
10 D - In -X6
11 +24V 1 Freigabe Kltemaschine
12 D - In 2
13 +24V 3 Enable Cooling unit
N
BN
-X5 L1 5
6
1
WH
BN 2
Temp 1 -A1 L1
N
8
WH 3 Temp 2 L1 9
4
~
7 Temp 4
M
WH L1 1
8 L
1
L1 2
0V N 230V~ max. 2A
Fortluft / Exhaust air -R1 A
B
4
L1 5
RL 2000 EC
+24V 6
7
8
Auenluft / Fresh air -R2 XB1 9
XB3 F2 -X4
N N 3 - Wege - Ventil
Abluft / Extract air -R3 4 N
close
N -M6 3-way valve
~
M
3 4 open Heizen
1
5
F1 6 Heating
Zuluft / Supply air -R4 2 7 230V~ max. 2A
8
-X1 1 L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
Option
Optional
127615
Bediengert Optional
manuelle Verbindung mit einem Kabel
Remote control manuell connection with a cable --> 120Ohm
+24V Mod Bus
B
A
0V
62
English
D - In
A - Out
A - Out
0V
0V
+24V
WH 3 A - In
B1 2
4 A - Out 3
5 A - Out 4
6 +24V 5
7 D - In 6
5 8 0V B2 7
0 - 10V YE 9 0V 8
10 0V L1 9
6 11 0V
GND 12 0V
-X3
B3
-X8 L1
N
2
1 +24V L1 3
-B3 2 D - In N
3 +24V 5
4 D - In B4 L1 6
1 5 +24V N
+24V / V+ 6 D - In
8
7 +24V L1 9
2 8 D - In
GND 9 +24V
10 D - In -X6
11 +24V 1
12 D - In 2
13 +24V -A1 3
N
-X5 L1 5
6
1 Temp 1 N
2 L1 8
3 Temp 2 L1 9
4
5 Temp 3
6
7 Temp 4
-X16
L1 1
GN 8 L1 2
0V N
A 4
RD B L1 5
+24V 6
7
8
XB1 9
XB3 F2 -X4
N
N
N
4
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
+24V
XB3 F2 -X4
N
N
N
4
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
www.ruck.eu 63
English
15 - 30 V=
-X15 -X14 -X9
1 A - In 1 2 3 4 5 6 7 8 9 10 11 12 13
2 A - In 1
D - In
A - Out
A - Out
0V
0V
+24V
-B1 0 - 10V
3
4
A - In
A - Out B1 2
3
5 A - Out 4
6 +24V 5
7 D - In 6
8 0V B2 7
0V 9 0V 8
10 0V L1 9
11 0V
12 0V
B3 -X3
-X8 L1
N
2
1 +24V L1 3
-X2 1 2
3
D - In
+24V
N
B4 5
2 4 D - In L1 6
5 +24V N
3 6 D - In
8
4 7 +24V
Differenzdrucksensor 8 D - In
L1 9
0V XB3 F2 -X4
N
N
N
4
5
F1 6
7
8
L1 L11 L2 L21 L3 L31 N N N PE PE PE PE L1 9
Notes:
www.ruck.eu 65
ruck Ventilatoren GmbH
Max-Planck-Str. 5
D-97944 Boxberg-Windischbuch
info@ruck.eu
www.ruck.eu
Information updated
print 28.07.2016
mwr_rli20_pb_05_en
Language:
English