You are on page 1of 6

20/KSK/xxxx/0306/EN

KSK
Grease Filter Unit

The KSK grease filter unit is mainly used for air High-efficiency grease filtration using UL- and NSF-
exhaust for light-duty cooking, steamers, kettles and classified KSA multi-cyclone filters - removing up to
other processes with low heat emission levels. 95% of particles with a size of 8 microns or above
Exhaust airflow measurement and control using the
in-built adjustment damper located in the extract
spigot(s) and the T.A.B. testing and balancing tap
Stainless steel (AISI 304), welded construction

KSK - Grease Filter Unit



20/KSK/xxxx/0306/EN
Function Construction

The KSK filter unit is positioned above the equipment The exposed parts of the casing are manufactured
to collect the rising warm airflow (1) and impurities from polished stainless steel (AISI 304) and the
within the casing. This contaminated air is exhausted unexposed parts from galvanised steel.
from the space through the KSA grease filters (2) into The unit comprises duct connections, airflow dampers
the exhaust air duct. and a measurement tap.
Grease and other contaminants are separated from The joints of the lower edges are fully welded and
the exhaust air in the grease filter according to the polished to ensure water-tightness.
cyclone separation principle, and they are drained via a The grease and dirt extracted by the filters can be
channel toward the collection tap/tray (3). removed from the filter unit either via a drain tap or by
emptying the collection tray.

DIMENSIONS Accessories

KSK mm KSA grease filters


Length 500, 1000, 1500 Blind filter in stainless steel
Width 425 for wall model
Non-standard spigot options: choice of size and
825 for Island model
Height 356 position
Top panel of the exhaust plenum in stainless steel

QUICK DATA

Recommended Exhaust air volumes


L l/s m 3/h
500 86...160 309...580
1000 170...320 612...1150
1500 260...480 936...1728
Exhaust air volumes indicated above are for a recommended pressure loss of KSA filter between 35120 Pa - LpA < 56 dB(A)
Halton HELP, computer design program for exhaust airflow and kitchen air conditioning load calculations.
* UL= Underwriters Laboratories (UL is an independent organization founded by the insurance industry in the U.S.A, giving approvals
to safety tested products).
** NSF= National Sanitation Foundation (promoting hygiene and sanitation in the U.S.A)

KSK - Grease Filter Unit



20/KSK/xxxx/0306/EN
DIMENSIONS (mm)

KSK/1- Wall model

Model Filter pcs L D


KSK/1-1 1 500 250
KSK/1-2 2 1000 315
KSK/1-3 3 1500 315

Mounting bracket
DIMENSIONS (mm) 150 mm high

KSK/2- Island model

Model Filter pcs L D


KSK/2-2 2 500 315
KSK/2-4 4 100 400
KSK/2-6 6 1500 500

WEIGHTS (KG)

KSK/1 KSK/2

500 11 500 17
1000 18 1000 29
1500 26 1500 42

KSK - Grease Filter Unit



20/KSK/xxxx/0306/EN
Pressure drop and sound data, exhaust

KSK/1

pm1 = Pressure loss of filters measured from


measuring tap, minimum exhaust pressure
loss when the damper plate is open
pm2 = Maximum exhaust pressure loss when the
damper plate is nearly closed.
TP = Damper plate
0,1. = Numbers of blind filter
Recommended pressure loss of filter pm1 35-120 Pa

KSK-500 KSK-1000
pm2 pm2

KSK-1500
pm2

KSK - Grease Filter Unit



20/KSK/xxxx/0306/EN
Pressure drop and sound data, exhaust

KSK/2

pm1 = Pressure loss of filters measured from


measuring tap, minimum exhaust pressure
loss when the damper plate is open
pm2 = Maximum exhaust pressure loss when the
damper plate is nearly closed.
TP = Damper plate
0,1. = Numbers of blind filter
Recommended pressure loss of filter pm1 35-120 Pa

KSK-500 KSK-1000
pm2 pm2

KSK-1500
pm2

KSK - Grease Filter Unit



20/KSK/xxxx/0306/EN
Suggested specifications

General Grease filters


The filter units shall be constructed mainly from The grease filters shall be supplied in modular size
stainless steel AISI 304 except for the top panel of the 500 x 330 x 50 mm and shall be removable via two
plenum, which is to be of galvanised steel. folding handles.
The filter unit shall be supplied complete with outer The UL - and NSF -classified grease filters shall be
casing / main body, pressure measurement tap, constructed from stainless steel (AISI 304).
extract air spigot connections with airflow damper, The grease filters shall have a honeycomb design to
grease filters, drain tap or collection tray and assembly enable high grease filter efficiency due to the vortex
brackets. flow within the honeycomb.

Pressure measurement taps Spigot connections


The pressure measurement taps shall be located on The spigot connections for exhaust air shall be of
the side of the filter unit. galvanised steel and shall be supplied with a gasket
and airflow adjustment damper also manufactured
from galvanised steel.
The exhaust damper shall be adjustable, and access to
it occurs through the removal of the KSA grease
filters.

Product code

KSK/S-N

S = Model
1 Wall model
2 Island model

N = Number of filters
S=1: 1, 2, 3, 4, 5, 6
S=2: 2, 4, 6, 8, 10, 12

Specifics and accessories

EL = Direction of duct connection


T Top
B Back

Code example

KSK/1-1, EL=T

KSK - Grease Filter Unit




You might also like