You are on page 1of 35

NPQS

A1-60 Stone Cladding

National Productivity and Quality Specifications (NPQS)

A1-60 Stone Cladding

1
Version 1.0
NPQS
A1-60 Stone Cladding

CONTENTS Page

1. GENERAL 3
1.1 Scope 3
1.2 Related Sections 3
1.3 Standards 3
1.4 Trade Preambles 5
1.5 Abbreviations 7

2. PERFORMANCE REQUIREMENTS 8
2.1 Contractors Brief 8

3. MATERIALS AND COMPONENTS 14


3.1 Types of Stone Cladding 14
3.2 General Material Requirements 14
3.3 Stone 14
3.4 Aluminium 18
3.5 Steel 18
3.6 Fixings and Fasteners 19
3.7 Brackets 20
3.8 Cast-in Anchors 20
3.9 Back up walls 20
3.10 Joint Sealants 21
3.11 Gaskets 21
3.12 Joint Mortars 21

4. WORKMANSHIP 22
4.1 Stone Procurement 22
4.2 Fabrication 23
4.3 Installation 25
4.4 Protection and Cleaning 27

5. VERIFICATION AND SUBMISSION 29


5.1 Submissions 29
5.2 Warranty 31
5.3 Quality Control Plan Submission 31
5.4 Samples and Mock-ups 31
5.5 Tests 32

2
Version 1.0
NPQS
A1-60 Stone Cladding

1. GENERAL
Read with the General Requirements section, and all other contract documents.

1.1 Scope
This section covers the work requirements for mechanically fixed stone cladding onto
both internal and external walls.
The following types of stone are covered:
a. Granite
b. Limestone
c. Sandstone
d. Quartzite
e. Marble

1.2 Related Sections


Read this work section in conjunction with the relevant requirements of the other work
sections as follows:
A1-70 External Masonry

1.3 Standards
Unless otherwise agreed by the SO, ensure all of the Works comply with the relevant
requirements of the Standards and Codes listed below or referenced in the body of
the Specification. Alternative Standards and Codes may be proposed for approval by
the SO, provided it can be demonstrated that the alternative Standards and Codes
comply with the requirements of the standards specified. All Standards and Codes
quoted are the current version, unless specific year references are noted.
Singapore Standards
SS CP 33 Lightning protection
Other Standards
BS 6496 Specification for powder organic coatings for application to
aluminium
BS 4842 Specification for liquid organic coatings for application to
aluminium alloy extrusions, sheet and preformed sections for
external architectural purposes, and for the finish on aluminium
alloy extrusions, sheet and preformed sections coated with liquid
organic coatings.
BS 6497 Specification for powder organic coatings for application and
stoving to hot-dip galvanised hot-rolled steel sections and
preformed steel sheet for windows and associated external
architectural purposes, and for the finish on galvanised steel
sections and preformed sheet coated with powder organic
coatings.
BS 5250 Condensation prediction
BS 8298 Code of practice for design and installation of natural stone

3
Version 1.0
NPQS
A1-60 Stone Cladding

cladding and lining


BS1474, Aluminium and aluminium alloys .Extruded rod/bar,tube and
profilel
BS EN 573-3 Aluminium and aluminium alloysChemical composition and form
of wrought products. Chemical composition
BS 1161 Aluminium and aluminium alloys for structural purposes.
BS EN 1925 Natural stone test methods Determination of water absorption
coefficient by capillary
BS EN 1926 Natural stone test methods Determination of compressive
strengths
BS EN 1936 Natural stone test methods Determination of real density and
apparent density and of total porosity and open porosity
BS EN 12372 Natural stone test methods Determination of flexural strength
under concentrated load
BS EN 12407 Natural stone test methods Petrographic examination
BS EN 12440 Natural stone test methods Denomination criteria
ASTM C97 Test method for absorption and bulk specific gravity of
dimension stone
ASTM C99 Test method for modulus of rupture of dimension
ASTM C170 Test method for compressive strength of dimension stone
ASTM C503 Specification for marble dimension stone (exterior)
ASTM C568 Specification for limestone dimension stone
ASTM C615 Specification for granite dimension stone
ASTM C616 Specification for quartz based dimension stone
ASTM C1242 Guide to design, selection, and installation of exterior dimension
stone anchors and anchoring
ASTM C1354 Test method for strength of individual anchorages in dimension
stone
CP 3012 Code of practice for cleaning and preparation of metal surfaces
BS EN 12373 Aluminium and aluminium alloys -Anodizing. Method for
specifying decorative and protective anodic oxidation coatings
on aluminium
BS EN 14713 Protection against corrosion of iron and steel in structures-zinc
and aluminium coatings-guidelines.
ASTM D1400 Standard test method for non-destructive measurement of dry
film thickness of non-conductive coatings applied to a non-
ferrous metal base
ASTM D714 Test method for evaluating degree of blistering of paints
ASTM D2244 Method for instrumental evaluation of colour differences of
opaque materials
ASTM D2247 Method for testing coated metal specimens at 100% relative

4
Version 1.0
NPQS
A1-60 Stone Cladding

humidity
ASTM D3363 Test method for film hardness by pencil

1.4 Trade Preambles

1.4.1 Contractors Proposals and Submissions


The design intent including type and locations of stone claddings for the project are
indicated in the drawings and schedules. Base on the information supplied, engage
qualified and experienced personnel to carry out and submit the following items for
the SOs acceptance:
a. Develop all necessary details for the fabrication and installation of the stone
cladding system(s), and to meet with the performance requirements as set out in
clause 2.1 below. Details to develop may include shape and sizing of
components, structural support, accessories, joints, waterproofing and
connections to the building etc.
b. Propose quarry site/supplier
c. Propose method of fabrication, erection/installation
d. Propose details of weather/waterproofing.

1.4.2 Shop Drawings


Produce shop drawings to enable the fabrication and installation of the cladding
system.

1.4.3 Co-ordination with Other Works


Co-ordinate the stone cladding works particularly with the following trades:
a. Structural frame
b. External windows

1.4.4 Provide Spare Materials


Deliver to site in strong protective packages marked for identification, and store
where directed, components and materials for future replacement and repair. Refer to
PSD for list.

1.4.5 Submission to Authorities


Engage a PE (Structural) to carry out the design of the structural supports for the
cladding system and submit for BCA approval as a QP for this design.

1.4.6 Warranty
Provide a ten-year warranty in accordance with contract conditions for the entire
cladding system including all components and accessories for the specified
performance.

5
Version 1.0
NPQS
A1-60 Stone Cladding

1.4.7 Maintenance Manual


Refer to the PSD for any requirement to provide a maintenance manual.

1.4.8 Quality Control Plan


Refer to the PSD for any requirement to provide a quality control plan.

6
Version 1.0
NPQS
A1-60 Stone Cladding

1.5 Abbreviations
a. AS Australian Standard
b. ASHRAE American Society of Heating, Refrigerating and Air-
conditioning Engineers
c. ASTM American Society for Testing and Materials
d. B(C)R
e. BMS Building Management System
f. BMU Building Maintenance Unit (Also known as Gondola system,
Faade Maintenance Unit)
g. BRE Building Research Establishment
h. BS British Standard
i. CWCT Centre for window and cladding technology
j. EPDM Ethylene propylene diene monomer.
k. IGU Insulating glazing unit (Also known as a double glazing unit)
l. PVF2 Wet applied heat cured polyvinylidene fluoropolymer coating
m. SAA Standards Association of Australia
n. SA Standards Australia
o. SHGC Solar Heat Gain Coefficient
p. SS Singapore Standard
q. STL Sound Transmission Loss value.

7
Version 1.0
NPQS
A1-60 Stone Cladding

2. PERFORMANCE REQUIREMENTS

2.1 Contractors Brief


When carrying out the proposals as set out in clause 1.4.1, take account of the
following requirements:
The performance requirements apply to the complete wall assembly consisting of
panels, support frames and backing walls.

2.1.1 Resistance to Loading


2.1.1.1 Loading General
Withstand loading from inside and outside the building determined in accordance with
CP3 using a basic wind speed v = 35 m/s and terrain category suitable for the site.
Transmit all the design loads to the building structure via the points of attachment as
designed with an adequate margin of safety appropriate to each material and product.
2.1.1.2 Gravity Loading
Support the Works self weight and transmit this weight safely back to the supporting
structure without overstressing or permanently deforming any components
2.1.1.3 Wind Loading
Support the design dynamic pressure and transmit these loads safely back to the
supporting structure without overstressing or permanently deforming any of
components. Account shall be taken of all applicable local pressure coefficients.
Sustain no permanent damage to framing members when tested at both positive and
negative applications of the design wind loads multiplied by a factor of 1.5.
Framing members shall not be buckled. Stone panels, decorative capping pieces
shall remain securely held and gaskets shall not be displaced.
Permanent deformation to framing members shall not exceed 1/500 of the span
measured between points of attachment to the structure after loading.
2.1.1.4 Impact Loading
Satisfy the requirements of Tables 3 and 4 of BS 8200 "Design of non-load bearing
vertical enclosures" for category B in table 2 up to 1.5m above ground level where the
cladding is exposed to impact and Category F elsewhere described in table 2 of BS
8200.
2.1.1.5 Maintenance Loading
Sustain and safely transmit a static load of 500 N applied horizontally through a
square of 100 mm side on any stone or its framing in vertical or near vertical wall.
2.1.1.6 Barrier Loading
Sustain and safely transmit each of the following static horizontal loads acting
separately:
a. 0.75 kN/m for all occupied spaces acting in all directions at a height of 1.0 m
above finished floor level
b. A uniformly distributed load of 1.0 kN/m and a point load of 0.5kN acting on any
part, up to and including 1.0 m above finished floor level.

8
Version 1.0
NPQS
A1-60 Stone Cladding

Sustain and safely transmit crowd loading if requirement confirmed by the SO.
2.1.1.7 Loading from Temporary Conditions
Sustain and safely transmit any temporary loading that may arise from lifting, storing,
transporting, hoisting and installing of stone cladding or other Works that may affect
the stone cladding.
2.1.1.8 Combinations of Loading
Sustain and safely transmit combinations of loads determined in accordance with the
procedures set out in BCR.

2.1.2 Structural Design


2.1.2.1 Design Codes
Design stone cladding and its fixings in accordance with the following codes and
standards:
a. BS 8298 Code of practice for design and installation of natural stone cladding
and lining.
b. BS 5950 Structural use of Steelwork in buildings
Undertake the design to achieve the performance requirements with appropriate
factors of safety as required in this specification for the materials and components
used.
Submit calculations to the SO for review.
Submit calculations endorsed by a PE for onward statutory submission.
2.1.2.2 Fixing, Anchor and Bracket Design
Take account of any reduction in safe working loads in fixings due to their spacing,
location in areas of tension, near edges or proximity to cast in inserts/existing fixings,
or thickness of shims.
Design anchors and their connection to the building structure in order to resist
loading. Take account of structural and stone tolerances to determine loading and
eccentricity
2.1.2.3 Cast-in Anchor Design
Design cast-in anchors and their connection to the building structure in order to resist
loading. Take account of tolerances in structure, sub-frame and stone cladding to
determine loading and eccentricity.
Provide calculations verifying that cast in inserts will resist the loading as follows:
a. No permanent deformation of the insert at 1.5 times design load.
b. No failure of the insert at 2 times the designed load.
c. No failure of structural concrete at 3 times the design working load.
Identify locations of cast in anchors and pass this information to the concrete
contractor for incorporation in structure.
2.1.2.4 Components Subject to the Full Wind Load
Design the air seal and all components external to this to resist the full cladding
design pressure.

9
Version 1.0
NPQS
A1-60 Stone Cladding

2.1.2.5 Vibration and Repetitive Loading


Design the fixing systems so that the stone cladding does not work loose due to the
effects of vibrations, or cyclic effects of load, deflections and thermal expansion on
anchors and fixing systems.
2.1.2.6 Locked in Stresses
Avoid the introduction of locked-in stresses that may be detrimental to the
performance of the stone cladding.
Fixings must allow for thermal expansion of stone.

2.1.3 Resistance to Climatic and Environmental Conditions


2.1.3.1 Avoidance of Algae Growth
Where applicable, agree suitable measures with the SO for protecting against algae
growth on the surface of the stone.
Sealants must be tested on sample panels and approved by the SO.
2.1.3.2 Thermal Stress
Resist cracking to stone, glass, and ceramic materials caused by thermal stress.
2.1.3.3 Condensation Performance
Resist the formation of condensation on visible surfaces, interstices or locations
where it is unable to drain.
2.1.3.4 Resistance to Acid Rain
Obtain local pollution data and rainfall data.
Design stone cladding to maintain integrity and appearance for the design life of the
building.
Advise any coatings, maintenance and cleaning treatments necessary.
2.1.3.5 Design for Thermal and Condensation Performance
Use insulation of appropriate performance to provide adequate level of performance
without localised cold bridging where insulation must be locally reduced in thickness
such as anchor positions.
Use vapour barriers as necessary to eliminate condensation around the cladding.
Assess the heat transferred through stone cladding by 2-dimensional numerical
analysis. Use software validated against benchmarks. Summarise the results of the
assessment as thermal transmittance (U-values) for the central and perimeter zone of
each relevant cladding type. Calculate overall U values for each relevant cladding
type as a weighted average of constituent areas, with the weighting method defined.
Take into account the internal and external surface heat transfer resistances. Quote
these resistances and the parameters that affect them. Take into account the effects
of any air spaces, porous materials, and the thermal interaction between elements of
the facade.

10
Version 1.0
NPQS
A1-60 Stone Cladding

2.1.3.6 Climatic Data


Assume:
Ambient temperature range 16C to 40C
Radiant temperature range 16C to 80C
Relative humidity range 90%10%
Environment Coastal

Gather any additional climatic data required from the Singapore Meteorological
Observatory.
Submit for review to the SO any additional assumptions concerning temperatures,
humidity levels, etc.

2.1.4 Building Movements and Structural Tolerance


2.1.4.1 Structural Movement and Movement Between Works by Others
Accommodate the following movements in combination; without any reduction in the
specified performance, refer to the SO for further guidance and data for calculation
input:
a. Deflections and movements of the structure and building wall under design loads.
b. Changes in dimension and shape of building elements arising from building
movements, including settlement, shrinkage, elastic shortening, floor beam
deflections, creep, wind sway, twisting and racking and thermal and moisture
movement.
c. Changes due to movement of any joint in the supporting structure or building
frame.
d. Deflection of framing members under design dead loads and live loads.
Incorporate these calculations in the design.
e. Thermal and moisture induced movements of the stone cladding. Incorporate
these in the design based on maximum range of temperature and humidity.
Propose nominal, minimum and maximum joint widths accounting for tolerances and
movements for the SOs acceptance.
Refer to PSD for design movements and deflections to account for.
2.1.4.2 Structural Tolerances
Accommodate construction tolerances on structure and back up walls as indicated in
the PSD.

2.1.5 Fire and Smoke Performance


2.1.5.1 Non-combustible Materials
Do not include materials that readily support combustion or add significantly to the fire
load or give off toxic fumes.

11
Version 1.0
NPQS
A1-60 Stone Cladding

2.1.5.2 Fire and Smoke Stopping


The complete perimeter wall construction shall prevent the passage of smoke from
floor to floor in accordance with the requirements of Building Control Regulations and
BS 476: Parts 20-24.
2.1.5.3 Smoke Vents
Refer to clause 3.1 for the need to include Smoke vents.

2.1.6 Acoustic Performance


Achieve the following STL values against noise break-in:
Frequency (Hz) 125 250 500 1000 2000 4000
STL (dB) 25 27 32 33 30 26
Achieve resistance to flanking and floor to floor sound transmission of STC40 unless
indicated otherwise in clause 3.1.

2.1.7 Functionality
2.1.7.1 Appearance
Agree Range Samples with the SO as described.
Supply stone to meet the visual requirement identified in the Range Samples
Achieve the mandatory geometry and presented in the Architects drawings.
Achieve colours and appearances presented in the Architects drawings.
Use non-rusting granites (i.e. granites that do not develop rust spots or patches).
2.1.7.2 Maintenance and Replacement
Design stone cladding and its fixings to permit removal and replacement of individual
assemblies without affecting adjacent assemblies or supporting framework.
The method of installing panels must make clear where fixing methods are revised for
closing elements.
2.1.7.3 Drainage
Drain rain water predominantly at the outer surface.
Provide passage for any rainwater entering the cavity to allow it to drain to the outside
without being impeded by fixings, flashings etc.
Design fixings and flashings to shed water outwards.
Do not concentrate points of re-emergence that may cause localised staining or
surcharging.
Eliminate possible areas of prolonged wetting that may cause staining.
2.1.7.4 Infestation
Resist attack or infestation by micro organisms, fungi, insects, reptiles, birds or bats
and rodents.
Have no openings in the stone cladding that permit entry of insects, reptiles, birds or
bats and rodents.

2.1.8 Lightning Protection


Design the cladding system as a whole to electrically continuous to earth.

12
Version 1.0
NPQS
A1-60 Stone Cladding

Meet or exceed the requirements of CP SS 33. Where necessary, co-ordinate


between the stone cladding and the main lightning protection systems for the building
and shall propose appropriate connection points. No external tapes will be accepted.

2.1.9 Brackets and Fixings


Carry out the design of all fixings supporting and/or restraining to the stone cladding.
Provide details with supporting calculations of the design for every type of fixing
together with the loading on those fixings, proving compliance with the requirements.
Take note that brackets and anchors may be required to penetrate waterproof
membranes, renders etc.

2.1.10 Design for Durability


2.1.10.1 Do not use carbon steel in locations subject to wetting or condensation or
where this will result in corrosion; shortening their design life or
compromising safety, however long-term; or, causing rust staining; or,
establishing a bimetallic cell with other metals or carbon.
2.1.10.2 Identify materials and components which under normal service conditions
cannot meet the specified design life and design to allow their monitoring
and replacement
2.1.10.3 Identify any recommendations for spare materials.

13
Version 1.0
NPQS
A1-60 Stone Cladding

3. MATERIALS AND COMPONENTS

3.1 Types of Stone Cladding


Refer to the PSD for the types of cladding and component requirement for this
project.

3.2 General Material Requirements

3.2.1 Volatiles in Materials and Components


All materials and components shall be free from volatile components that may
migrate with time, or evaporate and re-condense onto other components.

3.2.2 Compatibility
Materials shall be selected, designed and installed to prevent bimetallic corrosion.
All materials shall be compatible with the other materials around it within its range of
influence for the service life of the stone cladding.

3.3 Stone

3.3.1 General
Stone shall be:
a. Natural stone that is compact and hard.
b. Free of any inherent characteristic that was not brought to the attention of the SO
at the time of agreeing the visual Range Samples.
c. Not exhibit any textural variation or rift that will cause excessive differential
weathering or cracks to develop.
d. Of sound quality, free from defects (e.g. rusting, cracks, voids, fissures,
inclusions of deleterious or foreign matter) liable to affect the physical properties,
durability or appearance, other than those agreed as acceptable by the SO.
Guideline requirements for different types of stone are given below. Take cognisance
that the actual requirement is dependent on panel design and be satisfied that the
stone cladding design (i.e. panel size, thickness, fixing arrangement) is appropriate
given the anticipated wind loading and strength of the proposed stone.

3.3.2 Granite
Granite shall satisfy the technical requirements given below:
(Min. Unless Stated) Requirement Test Method Notes
Density 2560 kg/m3 ASTM C97
Absorption (max) 0.4 % ASTM C97
Compressive 131 MPa ASTM C170
Strength
Flexural Strength *8.27 MPa ASTM C880 * Dependent on panel
design

14
Version 1.0
NPQS
A1-60 Stone Cladding

3.3.3 Limestone
Technical requirements for limestones to be used as external cladding shall satisfy
the technical requirements set out below:

3.3.3.1 Low-Density Limestone


(Min. Unless Requirement Test Method Notes
Stated)
Density 1760 kg/m3 ASTM C97
Absorption 12 % ASTM C97
(max)
Porosity N.A. % BRE 141
Saturation 0.85 BRE 141
Coefficient
(max)
Microporosity When combined with BRE Method Only for
saturation coefficient as per Portland
BRE Report A112, Stone
produces value below 115
Compressive 12 MPa ASTM C170
Strength
Flexural * MPa ASTM C880
Strength

3.3.3.2 Medium-Density Limestone for External Cladding


(Min. Unless Requirement Test Method Notes
Stated)
Density 2160 kg/m3 ASTM C97
Absorption 7.5 % ASTM C97
(max)
Porosity N.A. % BRE 141
Saturation 0.85 BRE 141
Coefficient
(max)
Microporosity When combined with BRE Method Only for
saturation coefficient as per Portland
BRE Report A112, produces Stone
value below 115
Compressive 28 MPa ASTM C170
Strength
Flexural * MPa ASTM C880
Strength

3.3.3.3 High-Density Limestone for External Cladding


(Min. Unless Requirement Test Method Notes
Stated)
Density 2560 kg/m3 ASTM C97
Absorption 3 % ASTM C97
(max)
Porosity N.A. % BRE 141

15
Version 1.0
NPQS
A1-60 Stone Cladding

Saturation 0.85 BRE 141


Coefficient
(max)
Microporosity When combined with BRE Method Only for
saturation coefficient as per Portland
BRE Report A112, Stone
produces value below 115
Compressive 55 MPa ASTM C170
Strength
Flexural * MPa ASTM C880
Strength

3.3.4 Sandstone
Technical requirements for Sandstones to be used as external cladding shall satisfy
the technical requirements set out below.

3.3.4.1 Sandstone (Contains a Minimum of 60% Free Silica)


(Min. Unless Requirement Test Method Notes
Stated)
Density 2003 kg/m3 ASTM C97
Absorption 8 % ASTM C97
(max)
Porosity N.A. % BRE 141
Acid Resistance pass BRE 141 No weight
loss allowed
Compressive 14 MPa ASTM C170
Strength
Flexural *2.5 MPa ASTM C880
Strength

3.3.4.2 Quartzitic Sandstone (Contains a Minimum of 90% Free Silica)


(Min. Unless Requirement Test Method Notes
Stated)
Density 2400 kg/m3 ASTM C97
Absorption 3 % ASTM C97
(max)
Porosity N.A. % BRE 141
Acid Resistance pass BRE 141 No weight
loss allowed
Compressive 70 MPa ASTM C170
Strength
Flexural *2.8 MPa ASTM C880
Strength

3.3.4.3 Quartzite (Contains a Minimum of 95% Free Silica)


(Min. Unless Requirement Test Method Notes
Stated)
Density 2560 kg/m3 ASTM C97

16
Version 1.0
NPQS
A1-60 Stone Cladding

Absorption 1 % ASTM C97


(max)
Porosity N.A. % BRE 141
Acid Resistance pass BRE 141 No weight
loss allowed
Compressive 140 MPa ASTM C170
Strength
Flexural *5.5 MPa ASTM C880
Strength

3.3.5 Marble
Technical requirements for Marble to be used as external cladding as follows:

3.3.5.1 Calcite Marble


(Min. Unless Stated) Requirement Test Method Notes
Density 2595 kg/m3 ASTM C97
Absorption (max) 0.20 % ASTM C97
Compressive Strength 52 MPa ASTM C170
Flexural Strength *7 MPa ASTM C880

3.3.5.2 Dolomite Marble


(Min. Unless Stated) Requirement Test Method Notes
Density 2800 kg/m3 ASTM C97
Absorption (max) 0.20 % ASTM C97
Compressive Strength 52 MPa ASTM C170
Flexural Strength *7 MPa ASTM C880

3.3.5.3 Serpentine Marble


(Min. Unless Stated) Requirement Test Method Notes
Density 2690 kg/m3 ASTM C97
Absorption (max) 0.20 % ASTM C97
Compressive 52 MPa ASTM C170
Strength
Flexural Strength *7 MPa ASTM C880

Travertine
(Min. Unless Stated) Requirement Test Method Notes
Density 2305 kg/m3 ASTM C97
Absorption (max) 0.20 % ASTM C97
Compressive 52 MPa ASTM C170
Strength
Flexural Strength *7 MPa ASTM C880

17
Version 1.0
NPQS
A1-60 Stone Cladding

3.4 Aluminium

3.4.1 Extrusions
Designation 6063, temper T6 of BS 1474 unless otherwise agreed with the SO.
Comply with BS EN 486, BS EN 573-3 and BS 1161.
Minimum wall thickness in structural parts of 2.5mm.
Platforms, webs, flanges, races and screw flutes of sufficient size to satisfy all
structural requirements and eliminate distortion of elements in the works.

3.4.2 Sheet, Strip and Plate


Not less than 1.6mm thick for hidden flashings
Not less than 3mm thick for components exposed to view or to impact
Isolate all components in direct contact with, but not totally encased in, cementitious
surfaces with thin dense PVC or EPDM isolation packs. The use of bituminous paint
shall not be accepted.

3.4.3 Aluminium Finishes


Concealed aluminium in wetted areas to be anodised.
Applicator is to be approved by the coating manufacturer.
Apply PVF2 coating to exposed aluminium in accordance with the coating
manufacturers instructions.
Coating shall be supplied by a single applicator
PVF2 coating shall (be / have)
a. Dense and consistent
b. Minimum cured coating thickness 25 microns.
c. Fully cured
d. No seeding
e. Free from flow lines, streaks, pin holes, blisters, orange peel, tears, damage,
contamination, inclusions and other defects and surface imperfections when
viewed from a distance of 1meter under normal diffused daylight.
f. Neither be significantly thicker or thinner than adjacent areas nor be split at
changes of angle.
g. No exposed areas of uncoated metal.

3.5 Steel

3.5.1 Stainless Steel Components


Stainless steel components shall be austenitic, complying with BS EN 10088 grades:
a. X2CrNi18-10 (formerly 304 S11) for concealed locations only
b. X8CrNi18-9 (formerly 304 S31) for concealed locations only
c. X2CrNiMo17-12-2 (formerly 316 S11) for exposed locations only

18
Version 1.0
NPQS
A1-60 Stone Cladding

d. X2CrNiMo17-12-2 (formerly 316 S13) for exposed locations only

3.5.2 Carbon Steel Components


Refer to structural steelwork specifications for requirements relating to secondary
steel framing.
The use of carbon steel shall only be permitted where the component is readily
accessible for regular inspection and maintenance.
Where used, it shall be one of the following:
a. Hot rolled steel complying with the requirements of BS EN 10025.
b. Hot rolled sections to BS 4: Part 1, BS EN 10210-2 and BS EN 10021-1, tubes to
BS 6323: Parts 1, 2 & 3 and angles to BS 4848: Part 4.
c. Cold formed pre-galvanised steel sections to BS EN 10142, BS EN 10143, BS
EN 10147
d. Steel sheet to BS 1449: Part 1.

3.5.3 Steelwork Corrosion Protection


For general requirements refer to structural specifications.
3.5.3.1 Hot Dip Galvanising
Hot dip galvanise all carbon steel components after forming and drilling in
accordance with BS EN 1461 for items less than 5mm thick and BS EN 14713 for
items more than 5mm thick.
Isolate all galvanised steel components in direct contact with, but not totally encased
in, cementitious surfaces with thin dense PVC or EPDM isolation packs. The use of
bituminous paint shall not be accepted.
3.5.3.2 Paint Finishes
Refer to structural specifications. Colours and gloss levels of any exposed items to
the SOs direction. Finished surfaces shall be:
a. Dense and consistent
b. Free from flow lines, streaks, pin holes, blisters, tears, lumps and other coating
defects or surface imperfections when viewed from a distance of 1 metre under
normal diffused daylight.

3.6 Fixings and Fasteners

3.6.1 Wet areas


Use stainless steel fixings and fasteners with stainless steel and aluminium, or with
non-metallic components wherever wetting may occur.
Stainless steel fasteners may have hardened tips of other composition for self-drill
and self-tap screws only.
a. grade A4 to BS 6105 where visible

19
Version 1.0
NPQS
A1-60 Stone Cladding

b. may be reduced to grade A2 to BS 6105 where not visible

3.6.2 Other areas


Use carbon steel bolts with carbon steel components
a. Ordinary bolts and nuts to BS EN 24032, BS EN 24033, BS EN 24034. All plain
and tapered washers to BS 4320, Form E.
b. Nuts to BS 4190 for grade 8.8.
c. The use of zinc plating to BS 1706 Fe/Zn 8 is acceptable where serrated fixings
are used.

3.7 Brackets
Use stainless steel or aluminium brackets and stainless steel fixings wherever wetting
may occur (including condensation)
Brackets shall (have / be):
a. Resist all loads, movements and dimensional changes that may occur in the
building due to thermal changes, deflections, settlement and creep.
b. Resist all loads, movements and dimensional changes that may occur to the
stone cladding.
c. Allow for construction tolerance in the all components and structure.
d. Adjust by small increments in and out, up and down and side to side
e. Use lock nuts to prevent loosening due to movements and/or vibrations.
f. State the torque values for tightening all bolts on the Contractor's drawings
g. State the maximum allowable shim dimension on the Contractor's drawings and
verify the capacity of the bolt by calculation for this case. Shimming shall not be
greater than 10mm.
h. Shims shall be of the same metal as the bracket

3.8 Cast-in Anchors


Use cast in anchors unless otherwise agreed with the SO. Post-fixed anchors will not
normally be accepted.

3.9 Back up walls


Back up walls may be in situ concrete blockwork, brickwork, steel stud and panelling.
The backing wall shall withstand the full design wind pressure.
Do not attach framing members, rails or fixings to non-structural back up walls unless
the wall has been designed to carry these loads.
Compartment the cavity between stone cladding and back up wall
Design and install back up wall to achieve airflow not more than 1.5 cu m/hr/m at 600
Pa. There shall be no region of concentrated airflow through the background wall or
at any interfaces.

20
Version 1.0
NPQS
A1-60 Stone Cladding

Ensure that all flashings, fixings and other items within cavities shed water outwards.
The wall shall incorporate appropriate water barrier appropriate to resist and control
the expected water passing the cladding. Water barriers may include as a single layer
or in combination render, membranes, water resistant coatings, etc.

3.10 Joint Sealants


Use non-staining joint sealants
Provide Trade literature on the proposed sealant and primer at Tender stage
Use the proposed sealant in visual mock up
Select and install sealants in accordance with BS 6213.
Use in accordance with the manufacturers directions, particularly relating to the use
of primers.
Reject all sealant beyond its best before date as identified by the manufacturer on
the packaging
Sealants shall (be / have):
a. Non-gassing polyethylene closed cell foam backing rods
b. Primers and joint preparation materials as recommended by the sealant
manufacturer.
c. Silicone sealants shall comply with BS 5889.
Refer colour selection of any visibly exposed sealants to the SO.

3.11 Gaskets
All gaskets shall (be / have):
a. Extruded EPDM complying with the provisions of BS 4255.
b. Cellular profiled gaskets shall comply with ASTM C509.

3.12 Joint Mortars


Use mortar in accordance with section 2.4 of BS 8298.

21
Version 1.0
NPQS
A1-60 Stone Cladding

4. WORKMANSHIP

4.1 Stone Procurement

4.1.1 Sourcing
Source each type of stone from a single quarry possessing sufficient reserves under
development or available from stock to meet the project requirements.
Before ordering the chosen stone secure an agreement in writing with the quarry
owner which will commit to produce the chosen stone in the quantity and quality
required by the contract documents at the times required by the programme of the
cladding, and that this agreement can be continued in favour of the project client in
the event of default by the contractor.

4.1.2 Range Samples and Quarry Visit


4.1.2.1 Range Samples
Unless otherwise agreed arrange for:
a. 12 number slabs of each stone type at the thickness proposed for the cladding,
to be cut from four randomly selected blocks taken from current workings at the
quarry. That is, 1 number sample each to be taken from each of the 2 outermost
usable slabs of the block, and 1 number sample to be taken from the centre of
the block.
b. The 12 number slabs to have the specified finish applied and shall be set up in
the quarry with a neutral background and orientated facing east or west to enable
viewing in shadow or sunlight.
c. Each slab to be identifiable by a block number and slab number.
d. Visit the quarry with the SO, to view the 12 finished slabs and agree an
acceptable range of colour, veining, blemishes and other relevant visual criteria
with the contractor. Features considered unacceptable shall be clearly marked
on the slabs by the SO. At the same time all parties shall agree the steps that
shall be taken to ensure the correct tonal distribution of stones in the cladding.
e. Sign off, with the SO, at the rear surfaces of each accepted range sample.
f. Cut Range Samples 1000 mm x 450 mm from the accepted slabs. Six range
samples shall be cut and shall be divided into two sets of three. Each set of
three shall illustrate the agreed range. Set up one set of three in the fabrication
yard and one set upon site to the SOs acceptance. Set up the slabs marked
with unacceptable features in the contractors' yard or as directed.
Use these range samples as the reference to control the visual quality of the stones
processed during the fabrication and installation of the cladding. Stones outside the
identified range will be deemed unacceptable unless authorised otherwise by the SO.

4.1.3 Quarrying
Immediately notify the SO of any variations outside the agreed range.
a. Cut all stone from a designated part of the quarry that exhibits consistent
mechanical properties.

22
Version 1.0
NPQS
A1-60 Stone Cladding

b. Undertake the extraction of the stone by experienced and competent quarrymen


and using only those techniques and practices which will not impair the
performance of the finished product.
c. Cut blocks so that their orientation is in sympathy with any natural bedding plane
or rift in the stone. Prepare slabs so that the natural bedding planes or rifts are
arranged to provide the best possible weathering performance.
d. Give individual blocks a unique reference number/block number at the quarry
indicating the location from which they were removed from the quarry face. Keep
a record of the date on which individual blocks were numbered.
e. Should the character of the stone change during the progress of extraction from
the quarry, immediately inform the SO, so that an alternative location of working
can be agreed. Do not obtain stone from another quarry or another part of the
quarry without the prior agreement of the SO.
In the case of stone that requires "seasoning" ensure that sufficient time has been
allowed under suitable storage conditions for the stone to achieve maximum strength
and durability.

4.2 Fabrication

4.2.1 Submissions
4.2.1.1 Submit method statements describing how it is proposed to select,
fabricate and install the Works to the SO for review.
4.2.1.2 Provide calculations to demonstrate that the dimensions of stone as
specified and as shown on the Contract Documents will provide adequate
strength to maintain the structural integrity of the individual elements and
units at all stages during production, fabrication and erection.
4.2.1.3 Make known to the SO at the time of proposal if the prescribed size is not
suitable.
4.2.1.4 Where a thickness is proposed less than that given in table 4 of BS 8298,
prove that the proposed thickness is suitable by means of structural
calculation in accordance with BRE IP 7/98.
4.2.1.5 Refer to clause 5.4.1 for prototypes and demonstrations of fabrication.
4.2.1.6 Following review of samples, prototypes and demonstrations all
subsequent materials and workmanship are to be the same or better
standard.

4.2.2 General Requirements


a. Use personnel skilled in the trade, with modern, well maintained equipment to
carry out all cutting finishing and edge labours. Use the correct tools for each
task and equipment that is well maintained. Do not use blunt and worn tools.
b. Use experienced operatives skilled in using the techniques involved.
c. Maintain all equipment, to be fit for its intended purpose and capable of achieving
the tolerances prescribed.
d. Carry out grinding, cutting, shaping and finishing materials using tools,
techniques and ancillary materials that will not contaminate stone cladding or
curtain wall components with particles or substances, which could disfigure, stain
or corrode them.

23
Version 1.0
NPQS
A1-60 Stone Cladding

e. Form stones to the required shapes without flaws and defects.


f. Ensure stone is not subjected to excessive heat generated by any grinding,
shaping, drilling or polishing processes.
g. Use suitable lubricants where appropriate to dissipate or reduce the heat
generated, and not cause staining.
h. Do not use percussive tools to undertake drilling.
i. Use only diamond or tungsten tipped bits, together with appropriate cooling
methods and drill speeds.
j. Carry out all drilling in the factory using jigs.
k. Clean exposed surfaces and edges leaving them free of rust stains, iron particles
and cutting fluids.
l. Select methods used for installation that will achieve the specified performance.
m. Use jigs laser lines, and computer controlled methods wherever appropriate to
achieve accuracy.

4.2.3 Stone Tolerances


4.2.3.1 Manufacture individual stone elements to achieve the tolerances
described below, not those given in Section 4 of BS8298.
a. Length 1.0mm
b. Width 1.0mm
c. Thickness 1.0mm
d. Bow or Twist Should not vary by more than 1.5mm in 1200mm
e. Squareness The length of the diagonals should not vary by more than 2.0mm

4.2.3.2 In addition, holes for studs and fixings:


a. Position: 2.0 mm from specified position
b. Depth: 2.0 mm
c. Diameter: 2.0 mm
d. Angle: 0.5 from designated angle

4.2.4 Cracks and Fissures


Inspect all stones, particularly at fixing positions. Notify the SO of all minute cracks or
natural fissures at vulnerable places and seek his approval.

4.2.5 Repairs
Replace all damaged stonework with new stone.
Do not carry out on-site or off-site repair of damaged stonework without the prior
written agreement from the SO.

24
Version 1.0
NPQS
A1-60 Stone Cladding

4.3 Installation

4.3.1 Submissions
Submit method statements describing how it is proposed to install the Works to the
SO for review.

4.3.2 Methods
a. Select methods used for fabrication that will achieve the specified performance.
b. Use jigs and computer controlled tools wherever appropriate to achieve
accuracy.
c. Use the correct tools for each task and equipment that is well maintained. Do not
use blunt and worn tools.
d. Carry out grinding, cutting, shaping and finishing materials using tools,
techniques and ancillary materials that will not contaminate windows components
with particles or substances which could disfigure, stain or corrode them.
e. Use experienced operatives skilled in using the techniques involved.
f. Undertake the assembly of components under factory controlled conditions

4.3.3 Marking
Mark components and materials clearly wherever this is required in order to:
a. identify strong points for lifting,
b. permit assembly or installation in a particular sequence;
or where:
a. interlocks occur;
b. confusion could foreseeably arise between upper and lower faces, left and right
handed pieces, top and bottom,
c. lengths close but critically different from one another.
Mark in such a way as not to affect the performance of the Works with removable or
marks that will be concealed when installed.

4.3.4 Site survey


Before the installation of the Cladding:
a. Undertake a survey of the preceding elements of work including the details of
points of attachments for the primary brackets where appropriate. Carry this out
as soon as possible. Submit the results to the SO without delay.
b. Advise the SO of tolerances that exceed those allowed for at the time of Proposal.
Inform the SO of any preceding elements of work including any prepared fixing points
to be outside the stipulated tolerances,
Agree the remedial action to be taken, allowing sufficient time for rectification, so as
not to delay the construction programme.

25
Version 1.0
NPQS
A1-60 Stone Cladding

4.3.5 Brackets
Use stainless steel or aluminium brackets and stainless steel fixings wherever wetting
may occur (including condensation)
Brackets shall:
a. Resist all loads, movements and dimensional changes that may occur in the
building due to thermal changes, deflections, settlement and creep.
b. Resist all loads, movements and dimensional changes that may occur to the
stone cladding.
c. Allow for construction tolerance in the all components and structure.
d. Adjust by small increments in and out, up and down and side to side
Use lock nuts to prevent loosening due to movements and/or vibrations.
State the torque values for tightening all bolts on the submission drawings
State the maximum allowable shim dimension on the submission drawings. This shall
not be greater than 10mm.

4.3.6 Cast-in anchors


Use cast in anchors unless otherwise agreed with the SO. Postfixed anchors will not
normally be accepted.
Anchors to be hot dipped galvanised after fabrication to give coating of 50-70 microns
or of stainless steel grade A4 to Bs 1449 Part 2.

4.3.7 Tolerances
4.3.7.1 Building Frame Tolerances
a. Review the available documents to establish the anticipated tolerances for the
building frame.
b. Allow for the anticipated tolerances in the design of fixings and components such
that the completed Cladding are always within the tolerances specified. Advise
the SO at the time of proposal.
c. Obtain any further tolerance information required taking into account all criteria
relevant to the design and construction of the stone cladding.

4.3.7.2 Accuracy of Erection for Stone Elements


Erect the Cladding to the more onerous of the following permitted deviations:
a. Line: 2 mm in any one storey height, or structural bay width.
b. Level: 2 mm in any one structural bay.
c. Plumb: 2 mm in any one-storey height.
d. Plane: 2 mm in any one storey height or structural bay width.
e. Intersection: 2 mm in alignment in any direction between any two adjoining
panels, at a 4-way intersection of panels.

26
Version 1.0
NPQS
A1-60 Stone Cladding

4.3.7.3 Accuracy of Junctions Between Stone Components


Construct joints between components to the following permitted deviations:
a. Within the length of any joint (including in line continuations across transverse
joints) the greatest width shall not exceed the least width by more than 10%. Any
variation shall be evenly distributed with no sudden changes.
b. The offset end elevation between nominally in-line edges across a transverse
joint shall be not more than 10% of the width of the transverse joint.
c. The offset in plan or section between flat faces of adjacent panels across any joint
shall not be more than 10% of the width of the joint or 1.5 mm whichever is lesser.

4.3.8 Working on Site


Store stone on wood A frames or pallets with nonstaining separators and nonstaining
waterproof covers.
Do not carry out cutting, drilling or surface finishing (grinding or spinning) of stone on
site.

4.3.9 Visual Appearance of the Cladding


Monitor the stonework in the Cladding on a daily basis. Note the distribution of light,
dark and intermediate tones/colours on elevation drawings and submit to the SO for
review.
Remove and refix any stonework that is outside the agreed tonal variation.

4.3.10 Site Sealant Work


Apply and cure sealants in accordance with their manufacturers directions on
minimum and maximum temperature and RH conditions.
Achieve the depth to width geometry.
Prevent three-sided adhesion.
Use appropriate backer rods, tapes, surface preparation and primers as
manufacturers directions.
Tool off sealants neatly.

4.3.11 Installation of Fire and Smoke Stopping


Install fire and smoke stopping at all voids and penetrations between compartments
at designated locations to achieve the specified fire and smoke stopping
performance.

4.4 Protection and Cleaning


Protect vulnerable coated surfaces; glass, metal edges, corners and features. Apply
temporary removable protection against damage from following trades or operations
and the anticipated hazards.
Materials used for temporary protection shall be compatible with and subsequently
removed from the surface and finishes without detriment to the finish. The
component suppliers and finishers shall approve the methods for removal.

27
Version 1.0
NPQS
A1-60 Stone Cladding

Unless agreed otherwise by the SO protection should remain in place until all work
potentially damaging to the components or their finish has been undertaken.
Replace any damaged components in the stone cladding. Carry out repair to
damaged components only with the agreement of the SO and proper warranty to the
works is arranged.

28
Version 1.0
NPQS
A1-60 Stone Cladding

5. VERIFICATION AND SUBMISSION

5.1 Submissions

5.1.1 Tender Submissions


5.1.1.1 General
Submit the following information with the tender:
a. All material descriptions and sources including stone, secondary support structure
for stone, metal parts, gaskets, flashings, seals, linings, stops, vapour barriers,
insulation, inter-layers, thermal breaks, fire stopping and barriers.
b. Test certificate for the stone or for a proposed alternative. Include the following
information:
Requirement Test and method Unit
Density ASTM C97 kg/m
Water Absorption ASTM C97 %
Flexural Strength ASTM C880 MPa
Compressive Strength ASTM C170 MPa
Petrographic Description ISRM method

Obtain the data above from stone at or near the intended extraction zones in the
selected quarries. The data shall reflect as closely as possible the quality and
performance that will be expected of the stone. Ensure that none of the submitted
data is more than 18 months old.
f. The suppliers and location of the stone within the quarry, including
i. A recent history of the quarry.
ii. An assessment of the viability of the quarry.
iii. An estimate of the stone reserves immediately available.
iv. An assessment of the quarry's current workload.
v. A description of the work practices in the quarry.
g. The current rate of output of useable stone and any factors such as adverse
weather access restrictions, block sizes, etc. that could cause an interruption in
the supply of stone.
h. The cost of the stone.
i. The location of prominent buildings clad with the stone.
j. Samples

5.1.1.2 Alternative Stone Proposals


Provide details on alternative stones or thicknesses that may be considered
appropriate as alternative to the specified stone and thickness. Identify where the

29
Version 1.0
NPQS
A1-60 Stone Cladding

stone occur in the quarry and relate all of the above information to these levels.
Submit the necessary test certificates to demonstrate suitability.
5.1.1.3 Samples
a. Provide at least 3 nos. 600x 600mm samples of the proposed stone. The number
of samples submitted should be sufficient to define the colour range, figuring and
normal features (e.g. veining, textural changes, inclusions and spots) of each of
the proposed stones for the project. The SO to retain samples and to use them to
establish an initial range samples.
b. Samples of stone fixings proposed together with relevant trade literature.
Retain the samples and use as control samples.

5.1.2 Work Submissions


Upon commencement submit:
a. Any outstanding submissions required at tender.
b. The location and component referencing system for use throughout the stone
cladding.
c. Assembly and installation drawings: These are to show:
i. Panelisation plans and elevations uniquely identifying and locating
every stone cladding panel in the building
ii. Horizontal and vertical sections identifying requirements for any
cast in anchors, sub-framing, cavity trays and dpcs and windows
and meet the requirements of this specification.
iii. Horizontal and vertical sectional details and elevations illustrating
the stone cladding profiles, anchors, fixings and fasteners, glazing,
gaskets, sub heads and sub sills, storm flashings, baffles and
sealant work and interfaces to adjacent elements of cladding,
masonry and finishes.
iv. Drainage routes and weepholes clearly.
v. Allowance for tolerance and movement and means of adjustment.
d. Range Samples
e. Results of the approval tests
f. Any design assumptions additional to given data.
g. Data and calculations to verify that structural, noise, thermal transmittance,
weathering, risk of thermal breakage and solar control requirements can be met.
h. Detailed testing proposals
i. PVF2 samples onto a typical extrusion 300mm length.
j. Mock-up of panel showing joint. Refer to clause 5.4.2 for details
k. Results of the impact tests
l. Weathertightness specimen and test reports
m. Calculations supporting all design proposals. Clearly state basic data used and
all assumptions

30
Version 1.0
NPQS
A1-60 Stone Cladding

Do not commence fabrication until assembly and installation drawings have been
reviewed.

5.1.3 Certification of Materials


5.1.3.1 Submit to the SO certification from the manufacturers of finishes and
sealants that the manufacturers have reviewed the contractors details and
confirms the appropriateness of the materials for use in their application.
5.1.3.2 Submit to the SO certification from the applicator that finishes have been
properly applied and meet the requirements of the applicators quality
control system

5.1.4 Method Statements


Prepare and submit method statements to the SO for review. These are to describe:
a. Method of fabrication of stone claddings including method of fixing
b. Method of installation of stone claddings, in particular any sequencing issues
requiring other elements to be completed before installation
Do not commence fabrication or installation until method has been accepted.

5.2 Warranty
Submit the warranty for the SOs acceptance upon completion of the works.

5.3 Quality Control Plan Submission


Prepare and submit the quality control plan for SOs acceptance prior to starting work.

5.3.1 Maintenance Manual


Include the following information in the maintenance manual and logbook:
a. Method and frequency for cleaning every type of stone used on the project.

5.4 Samples and Mock-ups

5.4.1 Samples
Refer to clause 5.1.1 above.
Refer to the PSD for additional sample requirement if any.

5.4.2 Mock-ups
Subsequent to acceptance of the contractors detail design and prior to production,
fabricate and build at locations as directed, a full size visual mock up for the SO to
review.
Undertake any modifications throughout the stone cladding identified from the mock-
up by the SO in order to meet the performance requirements and design intent.
Refer to the PSD for additional mock-up requirement if any.

31
Version 1.0
NPQS
A1-60 Stone Cladding

5.5 Tests

5.5.1 Stone Testing


5.5.1.1 General
a. Submit method statements to the SO for review, describing how it is proposed to
test the Works.
b. Test the Works and achieve results that verify to the SO that the performance
requirements have been met.

5.5.1.2 Mechanical and Physical Properties of Stone


Submit to the SO test data for the proposed stone demonstrating compliance with the
mechanical and physical properties as set out in clause 3.1. The test data shall be no
more than 18 months old and from a laboratory accredited to carry out these tests.
5.5.1.3 Sampling
When the quarry has been selected and before any stone is processed for the
cladding:
a. Take samples of each stone type from blocks representative of three widely
spaced numbered locations in the intended extraction zone at the respective
quarry (if all of the blocks for the project have already been delivered to the
production facility then sampling may take place from these blocks rather than the
quarry).
b. Arrange for the samples to be tested by the Testing Authority accredited to carry
out the required tests and previously agreed with the SO. Submit the results to
the SO.
c. If the results do not confirm the information previously submitted prior to
procurement or any modifications agreed at the time of Contract award, identify
other extraction zones and continue sampling and testing until stones are found
which comply with the agreed properties.
Retain all test specimens after testing to allow further inspection if required.
5.5.1.4 Acceptance
Reject all the stones represented by samples which fail to meet the requirements of
mechanical and physical properties prior to procurement.
Remove the rejected blocks and slabs from the factory and place them in a separate
disposal area.

5.5.2 Stone Approval Testing of Granite


From each of three number blocks (selected as part of the Sampling stage above),
perform the following tests.
a. Density and Water Absorption. ASTM C97. From each block take three number
specimens (nine in total).
b. Flexural Strength. ASTM C880. From each block take twenty number specimens
(sixty in total). Ten specimens shall cut perpendicular to the rift in the stone and
ten parallel to the rift. These shall be designated sets A and B. Test five
specimens from set A and five from B in the saturated condition and test the
remaining ten specimens (again 5 from A and 5 from B) in the dry condition.

32
Version 1.0
NPQS
A1-60 Stone Cladding

c. Compressive Strength ASTM C170. From each block take five number
specimens (fifteen in total).

5.5.2.1 Acceptance
For each location calculate an average value for each group of tested samples. Use
the result of all samples tested within each group in determining the average value,
except if any specimen gives a value of 20% or more below/above the average.
Report any results 20% or more below/above the average to the SO and obtain
authorisation of acceptability.

5.5.3 Tests for Fixings in Stone Prior to Processing


5.5.3.1 Samples for Testing
Provide 20 samples for testing unless otherwise directed.
The samples used to carry out the tests shall be taken from blocks taken from at least
three separate parts of the quarry currently being worked. One or two samples shall
be taken from an area as close as possible to that part of the quarry from which the
stone for the project will be cut.
The same blocks shall be used to provide specimens for the stone property tests
described elsewhere in this Contract Document, so that a relationship between the
stone properties and the fixing tests can be established. The bedding plane or rift
shall be marked on the specimens by the quarry.
The test specimens shall be not less than 300 mm x 300 mm by the minimum design
thickness proposed by the Sub-contractor and shall be conditioned in accordance
with the requirements of the most recent edition of ASTM C99. Larger specimens
may be required if the failure cone in the stone is likely to be affected by the testing
equipment.
The Independent Testing Authority shall keep all test specimens after testing to allow
further inspections if necessary.
5.5.3.2 Pull-out Tests for Stud Fixings
a. 20 nos. pull out tests to destruction with the proposed stud fixings inserted into
the appropriate thickness of stone parallel to the bedding plane or rift and with the
stone wet and 20 nos. with the stone dry.
b. 20 nos. pull out tests to destruction with the proposed stud fixings inserted into
the appropriate thickness of stone at right angles to the bedding plane or rift and
with the stone wet and 20 nos. with the stone dry.
Calculate the mean and standard deviation of the failure loads for each set of 20
results.
Calculate the characteristic pull out value for each set as the mean pull out value of
each set minus 1.83 times the standard deviation. The characteristic pull out value to
be used for design shall be the lowest characteristic value calculated.
Submit results to the SO.
5.5.3.3 Shear Tests on Wind Tie Pins in Stone Edges
a. 20 nos. load tests to destruction with the proposed pin fixing inserted into the
edge of the appropriate thickness of stone, with the bedding plane or rift parallel
to the pin and with the stone wet, and 20 nos. with the stone dry.

33
Version 1.0
NPQS
A1-60 Stone Cladding

b. 20 nos. load tests to destruction with the proposed pin fixing inserted into the
edge of the appropriate thickness of stone, with the bedding plane or rift at right
angles to the pin and with the stone wet, and 20 nos. with the stone dry.
Calculate the mean and standard deviation of the failure loads for each set of 20
results.
Calculate the characteristic breaking value for each set as the mean breaking value
of each set minus 1.83 times the standard deviation. The characteristic breaking
strength to be used for the pin fixing shall be the lowest characteristic value
calculated.
Submit results to the SO.
5.5.3.4 Shear Tests on Horizontal Bottom Bracket Slots
a. 20 nos. load tests to destruction with the proposed horizontal kerf bracket design
in the bottom edge of the appropriate thickness of stone, with the bedding plane
or rift parallel to the kerf slot cut in the stone, and with the stone wet, and 20 nos.
with the stone dry.
b. 20 nos. load tests to destruction with the proposed horizontal kerf bracket design
in the bottom edge of the appropriate thickness of stone, with the bedding plane
or rift at right angles to the kerf slot cut in the stone, and with the stone wet, and
20 nos. with the stone dry.
Calculate the mean and standard deviation of the failure loads for each set of 20
results.
Calculate the characteristic breaking strength of each set as the mean strength of
each set minus 1.83 times its standard deviation. The characteristic value to be used
for design shall be the lowest value calculated.
Submit results to the SO.

5.5.4 Production Control Testing


5.5.4.1 General
Closely monitor the quality of the stone during production. Arrange for the
Independent Testing Authority to carry out the following programme of physical
testing.
Carry out the following production control tests.
Block Number Flexural Strength Density and Water Absorption
Blocks 1 to 20 From every 5th Block. Six From every 5th block 3
specimens, 3 from each specimens shall be tested
orientation shall be tested in the
dry condition.
Blocks 21 to As above but from every 10th As above but from every 10th
50 block. block.
Blocks 50+ As above but from every 20th As above but from every 20th
block. block.
Should any significant variation occur in the results of the tests obtained during
production then the testing regime shall revert back to that for blocks 1 to 20.

5.5.5 Visual Inspection


Carry out a visual inspection:

34
Version 1.0
NPQS
A1-60 Stone Cladding

a. After gang sawing and prior to further processing.


b. After initial processing and cutting to size.
c. After edge labours and surface finishing.
Submit a record with substantiating photographs to the SO.

5.5.6 Dye Testing (Granites Only)


Dye test the two outermost usable slabs from the first five blocks to be produced
using a fluorescent dye to determine the presence of potentially harmful cracks and
micro cracks.
The necessity for an additional dye testing shall be determined following the results of
these tests.
Any stone exhibiting cracks deemed to be potentially harmful by the SO shall be
excluded from production.

5.5.7 Impact Testing


Carry out impact tests where required as indicated in the PSD.

5.5.8 Weathertightness and Load Testing of Stone Cladding Specimen


Provide stone for weathertightness and load testing where identified by the SO.

5.5.9 Site Load Testing of Fixings


5.5.9.1 General
Demonstrate by test that fixings are adequate
Laboratory tests shall be carried out generally in accordance with BS 5080 Parts 1
and 2.
Site testing shall be carried out in accordance with the methods described in
Construction Fixing Association Guidance Note Procedure for site testing
construction fixings
Retain all test specimens.
5.5.9.2 Site Inspections of Fixings
As the Works proceed check that:
a. The fixings as detailed on the installation drawings have been installed.
b. Every cladding fixing to structure is the right size and is in the right place and has
been correctly tightened using a calibrated torque wrench.
c. Fixings do not restrain any intended movement and generate locked-up stresses.

5.5.9.3 Quality Control Testing of Bolts Embedded in Concrete


As the Works are installed, carry out 10 nos. tests at each floor level on any
embedded bolts:
Load to a minimum load of 1.1 times the design load acting on the bolt.
Record and submit displacement measurements.
Displacement shall not exceed 0.1 mm.

35
Version 1.0

You might also like