You are on page 1of 3

Testing and Adjusting

950G Wheel Loader, 962G


Wheel Loader and IT62G
Integrated Toolcarrier Power Train

Media Number -SENR1380-09 Publication Date -01/01/2008 Date Updated -16/01/2008

i00991775

CID 0363 FMI 05 Solenoid Valve (Ride Control) Current


Below Normal - Test
SMCS - 5479-038-R6

/sisw eb/sisw eb/m /sisw eb/mediase

CID 0363 FMI 05 service code is recorded when the power train electronic control module
(ECM) detects that there is not a complete electrical path from the power train ECM to the
ride control solenoid and back to the power train ECM.

Note: Ensure that the service code CID 0363 FMI 05 for the ride control solenoid is active.
Before performing this procedure, refer to table 1 that follows in order to determine the
connector contact number and the wire number that corresponds to the failed circuit.

Table 1

Solenoid Valve Information

Fault Connector Contact No. (1) Wire No.

Ride Control Solenoid J1-18 976-OR


(1)
Connector contact number of the power train ECM.
Note: All ride control solenoid return lines are joined to connect to contacts J1-7 and J2-3
(wire 975-WH) of the power train ECM.

Note: The approximate coil resistance of the ride control solenoid valve is 20 to 60 ohms.

1. Check the resistance of the ride control solenoid.

a. Turn the key start switch and the disconnect switch to the OFF position.

a. Disconnect the machine harness from the suspected ride control solenoid.

a. At the ride control solenoid, measure the resistance between the two contacts
of the solenoid connector.

Expected Result: The resistance should be between 20 - 60 ohms.

Results:

OK - The ride control solenoid resistance is correct. Either the wire for
solenoid signal or the solenoid return circuit (wire 975-WH) is open in
the harness. Reconnect the ride control solenoid and go to Step 2.

NOT OK - The ride control solenoid is failed. Replace the ride control
solenoid. STOP.

2. Check the ride control solenoid circuit for an open.

a. The key start switch and the disconnect switch remain in the OFF position.

a. Disconnect the machine harness connectors J1 and J2 from the power train
ECM.

a. At the machine harness connector J1 and J2, measure the resistance from the
solenoid signal contact (refer to table 1) to J2-3 (return) or J1-7 (return).

Expected Result: The resistance should be between 20 - 60 ohms.

Results:

OK - The machine harness is correct. Suspect an intermittent fault.


Reconnect the connector and recheck. Go to Step 3.

NOT OK - There is an open circuit in the machine harness. The open is


in the wire for the solenoid signal or in wire 975-WH of the machine
harness. Check continuity on each of the circuits. Repair the machine
harness or replace the machine harness. STOP.

3. Check if the fault is still present.


a. Inspect the contacts and clean the contacts of the harness connectors.

a. Reconnect all harness connectors.

a. Turn the disconnect switch and the key start switch to the ON position.

a. Operate the machine. See if the fault reappears.

a. Check to see if the CID 0363 FMI 05 service code for the ride control solenoid
has recurred.

Expected Result: The CID 0363 FMI 05 for the solenoid is not active.

Results:

YES - Fault is NOT active. The fault does not exist at this time. The
initial fault was probably caused by a poor electrical connection.
Another cause could be a short at one of the harness connectors that
was disconnected and reconnected. Resume normal machine operation.
STOP.

NO - The fault has not been corrected. It is unlikely that the power
train ECM is faulty. Perform the previous steps again. If the cause of
the fault is not found, replace the power train ECM. Refer to Testing
and Adjusting, "Electronic Control Module (Power Train) - Replace"
for more information on replacing the power train ECM. STOP.

You might also like