You are on page 1of 1

GENERAL

THE GENERAL NOTES AND SPECIAL REQUIREMENTS ARE SUPPLEMENTAL TO AND FORM PARTOF THE
PLANS, DRAWINGS AND SPECIFICATIONS, WHERE DETAILS OR REQUIREMENTS ARE NOT
COVERED BY THE PLANS OR SPECIFICATIONS. THESE GENERAL CONSTRUCTION NOTES SHALL BE
E. UNLESS OTHERWISE NOTED IN THE PLANS, ALL BEDDED SLABS SHALL BE E. UNLESS OTHERWISE NOTED IN THE PLAN, PROVIDED FRAMING STIFFENER COLUMNS AND F. WHEN A BEAM CROSSES A GIRDER, REST BEAM BARS ON TOP OF GIRDER BARS, BEAM
USED INSOFAR AS THEY ARE APPLICABLE TO SATISFY REQUIREMENTS OF GOOD CONSTRUCTION
REINFORCED WITH 10mm DIAMETER REBAR AT 0.25m O.C. EACH WAY AT CENTER STIFFENER BEAMS NOT MORE THAN 3.0M APART. STIFFENER COLUMNS SHALL HAVE REINFORCING BARS SHALL BE SYMMETRICAL ABOUT THE CENTERLINE WHENEVER
PRACTICE. IN CASE OF QUESTIONS ARISING FROM THE INTERPRETATION OF OR CONFLICT WITH
OF SLAB, AND CONSTRUCTION JOINTS FOR SAME SHALL NOT BE MORE THAN 18m A WIDTH EQUAL TO THE WALL THICKNESS BUT NOT LESS THAN 115mm. POSSIBLE. A. MATERIALS
OTHER DOCUMENTS, THE ATTENTION OF THE OWNER/ENGINEERS MUST BE CALLED IN WRITING.
APART. A1. STRUCTURAL STEEL - STEEL TO BE USED FOR FABRICATION AND ERECTION OF
G. GENERALLY NO SPLICE SHALL BE PERMITTED AT POINTS WHERE CRITICAL BENDING THIS STRUCTURE SHALL COMPLY WITH ALL THE PERTINENT PROVISIONS OF AISC
GENERAL NOTES F. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB (TWO ADJACENT STRESSES OCCUR, SPLICES WHERE SO PERMITTED SHALL BE AS INDICATED IN TABLE SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL
DISCON-TINUOUS EDGES AS SHOWN BELOW.) "A" AND "B" WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125% OF THE STEEL FOR BUILDINGS 2005-13th EDITION.
SPECIFIED YIELD STRENGTH OF THE BAR. NO MORE THAN 50% OF THE BARS ANY ONE
A. ALL REINFORCING BARS SHALL BE HIGH GRADE FOR DIA 16mm AND LARGER
SECTION SHALL BE ALLOWED TO BE SPLICED THEREIN. a. STEEL SHAPES
FOR DIA 12mm AND 10mm YIELD STRENGTH OF 275 MPa (40,000 PSi)
MAINTAIN TS/YS RATIO > 1.25. 5-D10 BOTTOM BARS 4-D12mm WITH WIDE FLANGE ASTM A992, ANGLES, CHANNELS, PLATES SHALL BE ASTM A36.
BEAM @ 0.20m. O.C. H. LEAST 900mm
D10 TIES @ 200mm O.C. SPACED AT 250mm O.C. b. BOLTS
B. ALL REINFORCING BARS SHALL BE DEFORMED IN ACCORDANCE WITH ASTM-A615.
ALL BOLTS, NUTS AND WASHERS SHALL CONFORM TO A325
UNLESS OTHERWISE INDICATED. ANCHOR BOLTS SHALL ASTM F1554 UNLESS
C. BARS OF REINFORCED CONCRETE EXPOSED TO THE WEATHER SHALL PREFERABLY BE SB-1 / SC-1 NOTED OTHERWISE
PROTECTED AT LEAST 38mm.THIS PROVISION MAY BE WAIVED WHEN ADEQUATE
WATERPROOFING IS PROVIDED BUT SHALL IN NO CASE BE LESS THAN 20mm. 5-D10 TOP BARS WALL BASE c. WELDS
@ 0.20m. O.C.
ALL WELDS SHALL BE IN ACCORDANCE WITH AWS STRUCTURAL WELD
D. IN THE INTERPRETATION OF DRAWINGS, INDICATED DIMENSIONS SHALL GOVERN AND CODE D1-1 LATEST REVISION FOR SHIELDED METAL ARC WELDING
DISTANCES OR SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. PROCESS, ELECTRODES E-70 SHALL CONFORM TO AWS AS-1 OR LATEST
EDITION. SUBMERGED ARC WELDING PROCESS MAY BE USED AT THE
E. IN REFERENCE TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR DEPRESSIONS LINTEL IN BLOCK WALLS (PER 100mm THICKNESS) OPTION OF FABRICATOR UPON THE APPROVAL OF ENGINEER UNLESS NOTED
IN FLOOR SLABS, OPENING IN WALLS AND SLABS, INTERIOR PARTITIONS, LOCATION OTHERWISE
CLEAR SPAN L TOT. LENGTH MIN. fc' HEIGHT OF REINFORCEMENT
OF DRAINS, ETC.
m L+0.40 MPa LINTEL (cm) BOTTOM TOP B. QUALITY CONTROL
F. IN CASE OF DISCREPANCIES AS TO THE LAYOUT DIMENSIONS AND ELEVATIONS BETWEEN THE A. CONTRACTOR SHALL REPORT TO THE ENGINEER ACTUAL UNUSUAL SOIL CONDITIONS
STRUCTURAL PLANS AND OTHER DRAWINGS, THE CONTRACTOR SHALL NOTIFY BOTH THE A. FOR ALL TIED COLUMNS AND PEDESTALS PROVIDE EXTRA 4 SETS OF TIES AT 100mm 1.20 1.60 1-D12 1-D12
UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL IN WRITING B1. REFER TO SPECIFICATIONS FOR QUALITY CONTROL TESTING REQUIREMENTS.
O.C. FOR COLUMN REINFORCEMENTS JUST ABOVE THE FLOOR, JUST BELOW THE 1.50 1.90 1-D12 1-D12
STRUCTURAL ENGINEERS AND THE OWNER'S REPRESENTATIVE OR SITE ENGINEER IN WRITING BEFORE DEPOSITING CONCRETE. B2. STEEL SHAPES
GIRDER AND AT CONSTRUCTION JOINTS. 1.80 2.20 1-D12 1-D12
BEFORE PROCEEDING WITH THE AFFECTED WORK. EVERY BATCH OF STRUCTURAL STEEL SHAPE FOR FABRICATION SHALL
B. FOOTING SHALL REST AT LEAST 2.00m BELOW FINISHED GRADE LINE UNLESS 2.10 2.50 27.6 20.0 1-D16 1-D16 HAVE THE MANUFACTURER'S MILL CERTIFICATE SHOWING THEIR
B. COLUMN AND PEDESTAL TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF 2.40 2.80 1-D16 1-D16 CHEMICAL AND PHYSICAL PROPERTIES. OWNER EXERCISES THE RIGHT
OTHERWISE INDICATED.
CONCRETE CAST MONOLITHICALLY WITH THE CORE WITH MINIMUM THICKNESS OF 2.70 3.10 1-D16 1-D16 TO UNDERTAKE DESTRUCTIVE OR NON-DESTRUCTIVE TESTING OF SAMPLES
NOTE ON CONCRETE MIXES AND PLACING 40mm.
C. UNLESS OTHERWISE SPECIFIED, ALL FOOTINGS SHALL REST ON DENSE SAND OR VERY FROM MATERIALS USED FOR THE PROJECT.
3.00 3.40 1-D16 1-D16
HARD CLAY. THIS MAY SOMETIMES REQUIRE OVEREXCAVATION OF ABOUT 1000mm 3.30 3.70 1-D16 1-D16
G. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND LOCATIONS AT FROM PRESCRIBED BOUNDARY LEVEL. SUCH OVEREXCAVATION SHALL BE REPLACED B3. WELD FINISH
3.60 4.00 1-D16 1-D16
CONSTRUCTION JOINTS TO THE FIELD ENGINEER AT LEAST FOUR (4) DAYS PRIOR WITH WELL COMPACTED GRANULAR FILL. COMPACTION SHALL BE TO 95% OF MDD BASED ON ASTM D698. ALL WELDS SHALL BE FREE FROM UNDERCUTS, PINHOLES AND CRACKS,
TO THE POURING FOR APPROVAL. NON-DESTRUCTIVE TESTING MAY BE CONDUCTED AT WELDS DEEMED NOT
C. UNLESS OTHERWISE NOTED IN PLANS, CAMBER ALL BEAMS AND GIRDERS AT LEAST
D. PROVIDE 100mm PLAN OFFSET FOR LEAN CONCRETE POURS. 6.35mm FOR EVERY 457 CENTIMETERS OF SPAN, EXCEPT CANTILEVERS FOR WHICH IN CONFORMITY WITH THE SPECIFICATION AND SHALL BE TO
H. WET CURING OF CONCRETE SHALL BE CONTINUOUS FOR MINIMUM PERIOD OF TEN (10) NOTE: ALL CHB SHALL BE LOAD BEARING AND ALL HOLLOWS SHALL BE COMPLETELY CONTRACTOR'S ACCOUNT.
THE CAMBER SHALL BE AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER BUT
DAYS IMMEDIATELY AFTER POURING. E. CONTINUE COLUMN STIRRUPS SPACING AND CONFIGURATION TOWARDS THE FOUNDING LEVEL. IN NO CASE LESS THAN 19.05mm FOR EVERY 3m OF FREE SPAN. FILLED WITH HIGHLY FLOWABLE MORTAR
C. FABRICATION
I. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS FOR SHORINGS F. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 75mm CLEAR FOR D. TYPICAL BAR BENDING AND CUTTING DETAILS FOR BEAMS AND GIRDERS SHALL BE ALL LINTEL BEAMS SHALL BE PROVIDE WITH 10MM DIAMETER 2 LEGGED STIRRUPS 1 @ 50MM @ C1. WELDS
UNTIL THE CONCRETE MEMBERS HAVE ATTAINED THEIR SUFFICIENT STRENGTH FOR CONCRETE DEPOSITED AGAINST THE GROUND AND 50mm FOR CONCRETE DEPOSITED AS SHOWN IN FIG. 6 FOR FLAT SLABS OR SLAB BENDS REFER TO PLAN. REST @ 100MM FROM BOTH ENDS ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE
THE WORKING CONDITION ANTICIPATED. AGAINST A FORMWORK. MEMBER CONNECTED.

J. ALL CONCRETE WORKS SHALL BE DONE IN ACCORDANCE WITH THE ACI 318-08 G. VERIFY WITH ALL CONCERNED DISCIPLINES, ALL EMBEDDED MECHANICAL & ELECTRICAL ITEMS, BEFORE d. LENGTH OF WELDS:
TOP REINFORCEMENT
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND ALL STRUCTURAL CONCRETE POURING. THE MINIMUM LENGTH OF FILLET SHALL NOT BE LESS
STEEL WORK IN ACCORDANCE WITH A.I.S.C. SPECIFICATIONS 360-05 IN SO FAR AS THEY DO NOT THAN 4 TIMES THE NOMINAL SIZE WHERE INTERMITTENT WELDS
CONFLICT WITH THE REQUIREMENTS OF THE NATIONAL STRUCTURAL CODE FOR BUILDING AND MAY BE USED THE LENGTH OF SEGMENT SHALL NOT BE LESS
LOCAL CODES. THAN 4 TIMES THE WELD SIZE WITH A MIN. OF 40mm.

HEIGHT

LINTEL
e. END RETURN OF FILLET WELDS
SIDE OR END FILLET WELDS TERMINATING AT END OR SIDES

OF
K. A.C.I. REFERS TO AMERICAN CONCRETE INSTITUTE A.I.S.C. TO AMERICAN
TOP REINFORCEMENT SHALL BE RETURNED CONTINUOUSLY FOR A DISTANCE NOT LESS
INSTITUTE OF STEEL CONSTRUCTION AND A.S.T.M. TO AMERICAN SOCIETY FOR SCHEDULE OF CHB & CERAMIC BLOCK REINFORCEMENT THAN TWICE THE NOMINAL SIZE OF THE WELD.
TESTING MATERIALS.
BLOCK REINFORCEMENT TABLE "A"
NOTES: 10mm f. USE E70 ELECTRODES FOR ALL WELDS IN STRUCTURAL STEEL
L. UNLESS OTHERWISE INDICATED IN PLANS OR NOTED IN THE SPECIFICATION, THE THICKNESS
TENSION BARS
MINIMUM 28TH DAY CYLINDER COMPRESSIVE STRENGTH OF CONCRETE SHALL BE (NOMINAL) HORIZONTAL VERTICAL
A. MINIMUM LAPS AT SPLICE=0.25m EMBEDMENT LENGTH & LAP SPLICES g. SEE SPECIFICATIONS FOR NDT TEST REQUIREMENTS.
AS FOLLOWS:
B. PROVIDE RIGHT ANGLED REINFORCE- IN CENTIMETERS
MENT @ CORNERS 1.00m LONG. h. ALL WELDERS SHALL BE CERTIFIED WITH CURRENT CERTIFICATION
1. FOOTINGS, FOOTING TIE BEAMS: 100mm D10 @ 400mm D10 @ 300mm O.C.
C. WHERE CHB OR CERAMIC BLOCK WALLS BAR SIZE fc'=27.6 MPa CARRIED IN PERSON.
fc' = 21 MPa (3,000 psi) 150mm D10 @ 400mm D10 @ 300mm O.C.
2. COLUMNS: ADJOIN COL, RC BEAMS & WALLS. DOWELS W/ DEFORMED EMBEDMENT LAPPED
SAME AS VERT. OR HOR. C2. BOLTS
fc' = 21 MPa (3,000 psi) 200mm D10 @ 400mm D10 @ 300mm O.C.
3. BEAMS AND GIRDERS: REINF. SHALL BE PROVIDED. 10 30 30
i. MINIMUM EDGE DISTANCE:
fc' = 21 MPa (3,000 psi) 12 30 36 A. ALL VERTICALLY EMBEDDED PIPES FOR UTILITIES, ETC. SHALL BE MAXIMUM 100mm DIAMETER
THE MINIMUM EDGE DISTANCE OF BOLTS SHALL CONFORM TO
4. CHB LOAD BEARING WALL 16 36 45 SINGLE RIGID GALVANIZED IRON PIPE UNLESS OTHERWISE SPECIFIED OR APPROVED THE REQUIREMENTS OF AISC STEEL MANUAL 13th EDITION.
fc' = 21 MPa (3,000 psi) 20 36 55 IN WRITING BY THE STRUCTURAL ENGINEER.
PROVIDE HORIZONTAL & VERTICAL STIFFENER BEAMS AND COLUMNS AT 3000mm TYPICAL
5. WAREHOUSE SLAB ON GRADE (BURNISHED FLOOR SLAB) 22 52.5 62.5 THE MAXIMUM EDGE DISTANCE FROM BOLT CENTER SHALL BE
fc' = 21 MPa (3,000 psi) B. SUCH PIPES WHEN SO EMBEDDED SHALL NOT TAKE UP MORE THAN FOUR (4) PERCENT
25 56 95 12 TIMES THICKNESS OF THE PLATE BUT NOT TO EXCEED
ALL MASONRY WALLS SUPPORTED ON SOIL SHALL BE PROVIDED WITH A 600mm WIDE, 300mm THICK WALL FOUNDATION OF THE GROSS AREA OF THE CONCRETE MEMBER.
28 71 121 150mm.
EMBEDED 900mm DEEP FROM FINISHED GRADE LINE REINFORCED WITH 16mm DIAMETER TRANSVERSE BOTTOM BARS
M. 1. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT j. MINIMUM PITCH:
SPACED @ 200mm O.C. & LONGITUDINAL TEMPERATURE BARS ON TOP OF THE TRANSVERSE BARS. MASONRY WALL 32 93 156 C. ALL HORIZONTALLY EMBEDDED PIPES SHALL NOT BE ALLOWED UNLESS SPECIFICALLY INDICATED PLANS OR WITH
SEGREGATION, RE-HANDLING OR FLOWING. PLACING SHALL BE DONE PREFERABLY WITH SHALL BE CENTERED ON THE FOUNDATION. ON CENTER SPACING OF BOLTS SHALL NOT BE LESS THAN
BUGGIES, BUCKETS OR WHEELBARROWS, NO CHUTE WILL BE ALLOWED EXCEPT TO
36 151 179 PRIOR APPROVAL OF THE ENGINEER IN WRITTING. 3 TIMES THE NOMINAL DIAMETER OR 75mm WHICHEVER IS LARGER.
TRANSFER
CONCRETE FROM HOPPERS TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE C3. TOLERANCES
THEY SOME VARIATIONS EXPECTED IN THE FINISH OVERALL DIMENSIONS OF
SHALL NOT EXCEED SIX (6) METERS IN AGGREGATE LENGTH. TABLE "B" FRAMES SHALL NOT EXCEED THE ROLLING TOLERANCES FOR CROSS-
COMPRESSION BARS A. FILL AND SUBGRADES UNDER SLABS AND FOOTINGS SHALL BE COMPACTED TO A SECTIONAL DIMENSIONS, CAMBER AND SWEEP PERMITTED UNDER ASTM
2. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS EMBEDMENT LENGTH & LAP SPLICES MINIMUM 95% OF MAXIMUM DRY DENSITY BASED ON ASTM D-698 SPECIFICATION.
AUTHORIZED IN WRITING BY THE DESIGNER AND ONLY FOR UNUSUAL CONDITIONS WHERE A. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF IN CENTIMETERS D. ERECTION
B. MAXIMUM LIFT THICKNESS FOR COMPACTION SHALL BE 250mm.
VIBRATION IS EXTREMELY DIFFICULT TO ACCOMPLISH. WALL REINFORCEMENT UNLESS OTHERWISE INDICATED IN THE PLANS.
BAR SIZE fc'=27.6 MPa C. MONITOR QUALITY OF COMPACTION USING AN INDEPENDENT TESTING LABORATORY. D1.
BRACING:
B. SEE ARCH. PLANS FOR SEISMIC GAP USING PROPRIETARY ITEMS. REFER TO STRUCTURAL PLANS FOR CUSTOM USE ASTM D-1558 PROCEDURE OR NUCLEAR GAGE ASTM D- THE FRAME OF STEEL STRUCTURE SKELETON SHALL BE CARRIED UP TRUE
3. SAMPLING FOR COMPRESSIVE STRENGTH TESTS SHALL BE MADE IN ACCORDANCE DEFORMED
MADE GAPS FOR LATERAL MOVEMENT EMBEDMENT LAPPED AND PLUMB, WITHIN THE LIMITS DEFINED IN THE AISC CODE OF STANDARD
WITH SPECIFICATIONS BUT SHALL NOT LESS THAN 1 SET FOR EACH DAY OF POUR.
PRACTICE. TEMPORARY BRACING SHALL BE PROVIDED TO RESIST ALL LOADS
10 20 30
INCLUDING ERECTION EQUIPMENT.
4. ALL FORMED CONCRETE INCLUDING EXTERIOR & INTERIOR WALLS SHALL BE POURED 12 20 30
STRAIGHT TO FINISH. WALL REINFORCEMENT VERTICAL
REMARKS 16 23 32.5 D2. ALIGNMENT:
THICKNESS HORIZONTAL VERTICAL SECTION
20 28 37.5 1.) CONTRACTOR SHALL ENSURE THAT ALL EXISTING STRUCTURES ARE PROPERLY AND NO RIVETTING, PERMANENT BOLTING OR WELDING SHALL BE DONE UNTIL
100mm D12 @ 250mm O.C. D12 @ 300mm O.C. HOR. BARS @
VERT. STAG. BARS
22 25 45 ADEQUATELY SUPPORTED AGAINST SETTLEMENT OR MOVEMENT DURING EXCAVATION. STRUCTURE HAS BEEN PROPERLY ALIGNED.
NOTES ON CONCRETE SLABS 125mm D12 @ 200 O.C. D12 @ 250 O.C. CENTER, VERT. 25 37 51
150mm D12 @ 250 O.C. D12 @ 300 O.C. BARS STAG. OUTSIDE HOR. BARS 28 42 57.5 D3. SAGRODS AND CROSS BRACINGS SHALL BE INSTALLED AND TIGHTENED BEFORE
N. ALL SLAB REINFORCEMENT SHALL BE 20.0mm CLEAR MINIMUM FROM BOTTOM AND FROM 175mm D12 @ 220 O.C. D12 @ 250 O.C. INSTALLATION OF ROOFING OR WALL CLADDING.
32 46 64
THE TOP OF SLAB. 200mm D12 @ 250 O.C.E.F. D12 @ 300 O.C.E.F. BOTH FACES
VERT. BARS 36 51 72 E. PAINTING AND SURFACE PREPARATION
225mm D12 @ 200 O.C.E.F. D12 @ 250 O.C.E.F. HOR. BARS SHALL 1. ALL SLABS ON GRADE SHALL BE DESIGNED WITH A MAXIMUM WATER CEMENT RATIO
250mm D12 @ 300 O.C.E.F. D12 @ 350 O.C.E.F. BE OUTSIDE E1. STEEL TO BE USED FOR ERECTION OF THIS STRUCTURE SHALL BE PAINTED AND
O. UNLESS OTHERWISE DETAILED, IN CONTINUOUS SLAB HAVING SAME REINFORCEMENT HOR. BARS OF 0.42 ANY DECREASE IN WORKABILITY SHALL BE COMPENSATED USING PLASTICIZER.
ITS SURFACE PREPARED IN COMPLIANCE WITH THE SPECIFICATIONS.
RUNNING IN ONE DIRECTION, REINFORCING BARS SHALL BE BENT UP, EXTENDED,
OR CUT AS FOLLOWS : 2. ALL SLOPES SHALL BE POURED INTEGRAL WITH SLAB. OVERLAYS OR TOPPING SHALL
E2. CONTRACTOR TO VERIFY WITH REPRESENTATIVES - PAINTING AND SURFACE
NOT BE ALLOWED.
REINFORCING BARS SHALL HAVE 25mm MINIMUM CLEAR CONCRETE COVER FROM FACE OF WALL EXCEPT PREPARATION SPECIFICATION BEFORE PROCEEDING WITH WORK.
FOR WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 75mm SHALL BE PROVIDED, AND FOR 3. ADDITION OF 15% FLYASH TYPE "F" BY WEIGHT OF CEMENT SHALL BE MADE ON THE
EXPOSED FACES OF FORMED WALLS WHERE THE MINIMUM SHALL BE 50mm CLEAR. SLAB CONCRETE
1] CONTRACTOR TO SUBMIT MILL CERTIFICATE FOR GRADE 60 REBARS WITH
(VERIFY)

2 EDGE 4. CONTINUOUS WET CURING OF CONCRETE BY PONDING SHALL BE DONE FOR AT LEAST CATEGORICAL STATEMENT THAT NO QT/TMT BARS WILL BE IN BATCH TO BE
BARS C. CARRY VERTICAL BARS AT LEAST 600mm ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES, WHEN NECESSARY C. IF BEAM REINFORCING BARS END IN A WALL THE CLEAR DISTANCE FROM THE BAR 14 DAYS.
STOP AT 50mm BELOW TOP SLAB OR SOLID BAND WHERE THE WALL ENDS.VERTICAL AND HORIZONTAL BARS DELIVERED AT SITE. ANY QT/TMT REBARS TESTED AT SITE MAY CAUSE
200 MIN. TO THE FARTHER FACE OF THE WALL SHALL NOT BE LESS THAN 25mm. EMBEDMENT REJECTION OF WHOLE BATCH
SHALL BE SPLICED BY LAPPING A DISTANCE EQUAL TO 40 BAR DIAMETERS AND WIRED SECURELY WITH NO. LENGTH SHALL BE AS SHOWN IN TABLE "A" FOR TENSION BARS AND TABLE "B" FOR 5. SEE ARCHITECTURAL PLANS FOR WAREHOUSE FLOOR FINISH.
16 G.I. WIRE PROVIDED THAT SPLICES IN ADJACENT BARS ARE STAGERED AT LEAST 1.60m O.C.(SEE FIG. 4) COMPRESSION BARS.

D. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS USE 25mm DIAMETER BAR
SEPARATORS SPACED ABOUT 90 CENTIMETERS ON CENTER. IN NO CASE SHALL THERE
BE LESS THAN TWO (2) SEPARATORS BETWEEN LAYERS OF BARS. A MAP LAYOUT OF THE BURIED CREEK AFFECTING VARIOUS STRUCTURES IS
INCLUDED. CONTRACTOR TO DEMARCATE LOCATION DURING SITE EXCAVATION.
E. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS SHALL BE AS SHOWN IN FIG. 7. TREATMENT OF THE BURIED CREEK SHALL BE AS PER PLANS.
REFER TO GEOTECHNICAL REPORT.

SEE NOTE
C. IF SLABS ARE REINFORCED BOTHWAYS, BARS ALONG THE SHORTER SPAN SHALL BE NOTE:
PLACED BELOW THOSE ALONG THE LONG SPAN AT THE CENTER AND OVER AT THE 20mm CLEAR FOR JOIST
SUPPORTS. FOR THE REINFORCING BARS NEAR THE SUPPORTS, THE SPACING OF 40mm CLEAR FOR BEAMS
SPLICE

THE BARS AT THE COLUMN STRIPS SHALL BE APPROXIMATELY ONE AND WEBB BARS
400

& GIRDERS.
h

FLOOR LEVEL SEE NOTE


ONE HALF (1-1/2) THAT IN THE MIDDLE STRIPS BUT IN NO CASE GREATER THAN
TWO AND ONE HALF (2-1/2) TIMES THE SLAB THICKNESS NOR 45 CENTIMETERS.

D. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY DISTRIBUTED AROUND THE SECTION PLANE AND SHALL SEE NOTE D25
NOT BE LESS THAN 0.0018xBT AND THE SPACING NOT GREATER THAN 250mm. b SEPARATOR
D. UNLESS OTHERWISE NOTED IN THE PLAN, ALL OPENINGS IN WALLS 250mm OR LARGER SHALL BE REINFORCED
AROUND WITH 2-D20 BARS FOR 225mm, 175mm 150mm WALLS, USE 2-D16 BARS FOR 125mm AND 100mm WALLS,
USE 2-12mm BARS (SEE FIG. 5). ALL WALLS SPANNING OPENINGS SHALL HAVE VERTICAL REINFORCEMENT BENT
TO U-FORM LIKE STIRRUPS AND SPACED ACCORDING TO THE SCHEDULE UNLESS OTHERWISE NOTED (SEE
SECTION A OF FIG. 5)

2-BARS
U-FORM

OPEN

2-BARS
U-FORM

CONTRACTOR: CLIENT/OWNER : PROJECT TITLE: REGISTERED ENGINEER: PROJECT MANAGER: REFERENCES DRAWING: REVISION: SHEET CONTENT: DRAWN BY: DATE: 1/9/17
TRADE: ARCHITECTURAL STRUCTURAL ELECTRICAL MECHANICAL MARK REV. NO. DATE DESCRIPTION GENERAL NOTES CHECKED BY: NMD SCALE: AS SHOWN
2ND ST. FPIP
Agacons Construction Inc. Philippines Inc. BARANGAY ULANGO TANAUAN TOWER 2 NOEL M. DONATO ** DWG. NO. APPROVED BY: SAVE DATE:
CIVIL * MECHANICAL * ELECTRICAL CONTRACTOR TANAUAN CITY, BATANGAS FIRST PHILIPPINES INDUSTRIAL PARK
Tanauan Factory CIVIL/STRUCTURAL ENGINEER A.C.I PROJECT IN CHARGE REV. DRAWING NO : REV:
PHILIPPINES
APPROVED: DATE: LOCATION:
2ND ST. FPIP, BARANGAY ULANGO,
TANAUAN CITY, BATANGAS PHILIPPINES
REG. NO: 79498
ISSUED ON:*
PTR NO: *
ISSUED AT: QUEZON CITY DATE: CAD FILE NAME : S1 00

You might also like