Bentel Security was founded in 1983 in Grottammare, Italy and moved to In the technology age the world is
Corropoli in 1994. Global demand for its superior product line grew, and changing quickly. Seasoned Bentel
in 1998 Bentel joined forces with DSC to bring the world the finest engineers discriminate carefully
security product line-up ever offered. In 2001, a veritable intrusion between practical advanced solutions
security powerhouse was formed, as Bentel became a brand within and flashy unsustainable trends. In order
TYCO Fire & Security along with DSC, Sur-Gard and several other to satisfy the changing needs of customers,
complementary brands. Bentel now offers the best value in a very Bentel has developed increasing connectivity
complete line-up of security and fire prevention products. for its products; for example, adding to
communications capability through TCP-IP
protocols and transmission through Ethernet and
GSM/GPRS networks. More exciting innovations
ADVANCED TECHNOLOGY & SUPERIOR VALUE are on the way as Bentel benefits from increased
research and development resources.
Experience, technology, market responsiveness and
extensive research have made Bentel the brand of
choice among customers wishing to ensure the
highest level of protection for families, business QUALITY ASSURANCE
people and property.
To ensure quality control we perform parametric and
Hundreds of thousands of Bentel security & fire functional tests on every board, and follow strict ISO 9001
systems are in use around the corner and around testing procedures. Product controls and continuous
the world. These include installations in hospitals, monitoring are in place in all production phases. Our
banks, manufacturing facilities, shopping manufacturing facilities are among the most modern in the
centres, public buildings, museums and in world and our association with sister companies in other
residential applications far and wide. countries means we benefit from an unparalleled depth of
engineering & production expertise.
Products include security control panels, fire
control pads, keypads and other user Over the course of 20 years Bentel has risen to the highest
interfaces, security programming software, levels in the security business, establishing formidable
alarm communication receivers, mobile phone industry performance benchmarks. We attribute success to
interfaces, telephone dialers, alarm sirens, highly qualified personnel, quality components, product
smoke detectors, motion detectors, glass- innovation and continuous improvement. This results in
break detectors, analogue sensors, advanced security products which are also reliable, flexible,
addressable devices, call points, power and easy-to-use. It also results in very loyal Bentel partners
supplies, accessories and batteries. and customers.
DISTRIBUTOR PARTNERSHIPS
CONVENTIONAL
CONTROL PANELS
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 6
J424 ACCESSORIES
Expandable fire control panel.
J408 ACCESSORIES
8 zone fire control panel
FEATURES
Conforms with EN54
Up to 21 devices can be connected to each zone: conventional fire
detectors, alarm buttons, gas detectors
Gas zone compatible with 4 20 mA gas detectors
One alarm-repeat output (open collector) for each input zone PCJ400BRIDGE
Manual call point recognition Serial interface Management software
Signals missing detectors
2 supervised, silenceable, bypassable 24 V alarm output for the activation TECHNICAL FEATURES TECHNICAL FEATURES
of piezoelectric sirens, fire bells and flashers Enables PC communication with J400 series fire User-friendly Windows software for a quick and
Silenceable fault-warning output for the activation of control panels via RS485 bus. easy way to program the Control Panel,
signalling and auxiliary devices ORDER CODES
Receives data from zones and pheriperals and with event logger and print-out functions.
Supervised fire output for telephone dialler activation transmits commands to the system (bypass,
J408-2 2 zone fire control panel
Programmable open-collector output unbypass,etc). INCLUDED IN BENTEL FIRE SUITE
Dry contact alarm-relay for the activation of auxiliary devices J408-4 4 zone fire control panel Configured as J400-LCD module, maximum 4 pag.32
Day/Night mode modules per system (if J400-LCD module is
Alarm verification time J408-8 8 zone fire control panel need, only 3 PCJ400 Bridge interfaces can be
Programmable restoral and reset times installed).
J400-REP Repeater panel
Programmable from PC or keypad
50 event log viewed via PC
Alarm/fault memory activated until next reset PCJ400BRIDGE Serial interface
Command for silencing sirens
Keypad commands require key or pin code J400-EXT Extinguisher module with microprocessor
control
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 10
CONVENTIONAL
FIRE
DETECTORS
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 12
12 13
Loading
Offices, light Livestock
Clean room bay/warehouse Kitchen
industrial, hospitals, pen mill,
Data with diesel engine room
Fire loading Probable Risk processing
residential,
fork-lifts etc.
laundry,
engine test
passenger chancing
suite Heavy industrial beds
accomodation room
Ferry (car deck)
Electronic equipment - Cable pyrolysis (toxic fumes)
ORDER CODES Electrical switchgear - Electrical arcs (ignition 601P 601P
601P
Electric motors - source) 601H 601HP
601P Optical smoke detector Cable conduit Associated electrical dangers
Fabrics, clothes soft
Smoulderings (difficult to
601PH HPO smoke detector furnishings - paper, 601H
locate toxic fumes) 601CH 601CH
cardboard plastic foams - 601H 601CH 601CH
likelihood of flashover back 601P 601P
Animal bedding, wood 601P
draught)
601H-R Rate-of-Rise heat detector shavings
MUB-RV Relay base Plastic chemicals Type of fire risk may vary as
601H 601PH
Machinery can the type of fire 601P 601CH 601H-R
601CH 601CH 601CH
building materials (may require a mix of 601CH 601P 601CH
Unknown contents
601P 601PH-R
detection types)
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 14
SERIES 600
601P 601CH
601P detectors are capable of detecting the visible smoke 601CH detectors are generally faster than optical detectors in
produced by materials which smoulder or burn slowly, i.e. soft responding to fires that start by smoldering. they are also more
furnishings, plastic foam etc; or smoke produced by overheated tolerant of positioning and can be mounted in locations where
but unburnt PVC. there are likely to be obstacles to free smoke plume movement.
These detectors are particularly suitable for general applications These detectors are particularly well suited to sleeping risk,
and areas. Optical only detectors are not suitable for detecting storage areas and applications where smoke detectors are prone
fast burning fires producing little visible smoke or very black to false alarm. Incorporation of A1R rate of rise heat detector
smoke. within the 601CH provides extra non-selectable detection modes
The novel design of the asymmetrical sampling chamber and which allows the detector to operate in a wide variety of
signal processing techniques stop unwanted alarms caused by ORDER CODES applications where combined risk mean that CO detection alone ORDER CODES
very small insects, i.e. thrips. Smoke entering the sampling would be insufficient.
chamber scatters the infra-red light pulses onto a photodiode. 601P Optical smoke detector The integrated rate-of-rise heat detector acts as a normal heat 601CH Enhanced Carbon Monoxide Fire
These pulses are converted to an electrical signal which is detector, additionally anhancing the sensitivity of the carbon
compared against a preset alarm level. monoxide detector if a rapid change of temperature is detected by
the detectors thermistor.
601PH
Relay base
601PH detectors react to the complete range of fire products,
from slow smoldering fires, producing visible particles to open
flaming fires producing large numbers of very hot smaller sized
aerosols.
43 mm
For normal ambient conditions the HPO behaves as a normal Detector Material FR110 Bayblend fire resistant
detector. Only when a rapid rise in temperature is detected does Dimensions See figure 1
the sensitivity of the detector increase and the presence of smoke Weight See specification summary
will confirm a fire condition which will be trasmitted as an alarm Color Withe
level. ORDER CODES
The 601PH design incorporates a unique mousehole optical ELECTRICAL 109 mm
601PH HPO smoke detector Reset Time 2 5 seconds
chamber whith an unrivaled signal to noise ratio providing high Relative Humidity 0 95% non condensing
resilience to dust and dirt which means reduced servicing cost. Wiring Connections On MUB - Max 2x1,5 mm2 each terminal
In addition a unique chamber cover actually draws slow moving
smoke into the chamber to provide a more responsive detector. CONFORMS WITH:
11,5 mm
EN 54-5:2000 + A1:2002 Fire detection and fire alarm systems - Heat
detectors - Point detectors
601H-R (rate of rise) and 601H-F (fixed temperature) detectors WEIGHT SUPPLY VOLTAGE AVERAGE ALARM OPERATING STORAGE REMOTE LED APPROVAL
detect abnormally high rates of rise of temperature and SPECIFIATION (Kg) (Vdc) QUIESCENT CURRENT TEMPERATURE TEMPERATURE CURRENT
abnormally high (static) temperatures respectively. CURRENT (mA) (NO (NO CONDENSATION (MA)
(uA) CONDENSATION OR ICING) @ 24V (1K1
For general use and particular where the ambient temperature OR ICING) INTERNAL
may be low, a rate of rise heat detector 601H-R is to be RESISTOR
FITTED)
preferred. A fixed temperature limit is also incorporated in
these detectors. In many environments, e.g. kitchens, canteens TYPE Description 10,5V 24V 10,5V 24V 10,5V 24V
ANALOGUE
CONTROL
PANELS
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 18
FC200/REP Repeater
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 20
FEATURES
FIRE CLASS 100
The FIRE CLASS 100 is a programmable, modular control EN54 APPROVED
panel (EN54 Approved), suitable for small to medium fire alarm FOR SMALL 1 analogue loop: supports up to 99 analogue
systems. TO MEDIUM Automatic device-drift compensation
1 conventional input line accepts up to buttons
It has 1 analogue loop for the connection of fire control devices FIRE ALARM 16 completely programmable software zones
(sensors, alarm buttons, sirens, etc.), and a conventional SYSTEMS 16 alarm repeat outputs (open collector):
controlled line. During the programming phase each loop device 1 alarm output (relay) controlled and silenceable
can be assigned to 4 of the 16 available software zones, 1 controlled and silenceable alarm output (relay) programmable
these in turn, may be assigned to the 13 controlled and and expandable to 13, by means of FC200/6OUT expander
silenceable outputs (relays), managed by the control panel (1 on modules
the main board and 12 on the 2 optional FC200/6OUT output 1 fault signal output (relay) non controlled and non silenceable
expanders). RS485 interface for the connection of up to 8 FC200/REP
A fault output relay, non-controlled and non-silenceable is also repeaters
provided. Up to 8 FC200/REP annunciator panels (optional) with 200 event log
the same display and fast key functions as the main panel, can be Event action architecture
connected to the control panel by a 2 wires, RS485 bus. RS232 interface for the connection of a control panel or by PC
It is possible to program and manage the control panel from a PC for upload and download
via the FC200/SW software application (optional). Telecom module (optional)
Power supply 230 Vac 10%
The telephone features are supplied by the FC200/COM telecom Available with 2.5 A supply/battery charger
module. Power supply: 2.5 A switching supply/battery charger. Compartment for 2 batteries 12 V, 17 Ah
Dimensions (wxhxd): 432x577x131
Weight (without batteries): max. 9.0 kg
FC200/REP
REPEATER
NEW FEATURES OF SOFTWARE VERSION 4.00
Up to 8 on RS485
LCD 4 rows x 20 columns
Operation-free viewing of all alarm, prealarm and warning
20 Fast keys
FC200/COM
details
21
TELEPHON MODULE
Telephone dialler RS485 protocol upgrade
Digital communicator
Telecontrol
Centralized master panel gathers all the network events
Event broadcast to all the control panels in the network
Event information access from repeater panels
Output module management supervised or dry contact
Output activation by double-knock, zone prealarm/point, zone
1 analogue loop warning/point etc.)
FC200/60UT Alarm verification management upgrade
OUTPUT EXPANDER
Up to 2 expanders Reset and silence management of all the control panels in the
6 output network from any placement
Voice messages
Addressable loop-device management upgrade (infrared barrier,
2in/1out modules)
Differentiated warning threshold for each sensor/input module
Serial printer
Programmable warning-delays for mains failure and telephone-
line down events
PC configuration software with upgraded user interface
Impressive graphic-map software allows one-by-one viewing of all
Parallel printer Dedicated modem the network control panel events
ORDER CODES
FC200/SW
MANAGEMENT SOFTWARE FC100 Programmable modular control
panel
FC200/REP Repeater
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 22
FC200/REP
Pheripherals to be put in strategic points all
around the system.
It displays full system status and allows users
controll of the FireClass100 main functions.
FC200/6OUT
6 controlled and silenceable output expanders
FC200/COM
Module for connection to the telephone line.
Telephone-dialler function which allows a
recordable voice message and a telephone
number (16 digits max.) to be assigned to
22 each channel.
Multiprotocol digital communicator
function.
Telecontrol functions (uploading and
downloading) from remote PC.
ANALOGUE
SENSORS
AND
ADDRESSABLE
DEVICES
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 26
analogue sensors and addressable devices analogue sensors and addressable devices
Two alarm LEDs provide 360 view The list of all sensors and addressable devices is
Stable communication technique with high noise immunity available upon request.
VdS and LPCB approved
Tested and approved to EN54 part 8 grade 1
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 28
ACCESSORIES
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 30
accessories accessories
HS900 MCP900
The HS900 is a high performance HornStrobe The MCP900 is a stylish easy-to-install manual call point, is it
especially designed for audible and visual warning in ideal for internal environments that require manual activation
the event of fire or evacuation. and inhibition of fire alarms and fire extinguishments systems.
The flashes emitted by the strobes high intensity It is also suitable for door and escalator control and is available in
xenon tube are visible from all angles thus providing a choice of colours. It can be mounted in a custom surface
maximum visual coverage. mounting back box or flush mounted to the majority of outlet box
The smart, low-profile HS900 hornstrobe blends with formats available in europe.
all environments, making it ideal for hotels, hospitals, The MCP900 manual call point can be activated by pushing the
cinemas, offices and households. centre of the operating face (black arrows indicate the exact
point), and reset by means of the special key (without glass
replacement). A special version of the MCP900 provides local led
indication of stand by or alarm status.
ORDER CODES
The product is supplyes complete with surface mount.
FEATURES MCP900RCS Conventional, restorable call point with
alarm LED and choice serie resistor.
ORDER CODES Complete with restore key.
Operating voltage: 19 32 Vdc
Strobe current draw (mean value):135 mA MCP900RCB Conventional, restorable, call point with
Horn current draw (mean value): 90 mA HS900/R24S Horn/Strobe, red, 24 V, synchronized alarm LED. Complete with restore key.
Sound output hight/low volume: 873dB/1003dB @ 3m
MCP900/RS Restorable, call point with free voltage
Candela: 60 cd HS900/W24S Horn/Strobe, white, 24 V, synchronized changeover contact.
Dimensions (wxhxd): 126x132x53 mm Complete with restore key.
Protection class: IP31
Operating temperature: 5 40 C HS900/R24 Horn/Strobe, red, 24 V, MCP900/RY Addressable, restorable call point.
not synchronized Complete with restore key.
Weight: 245 gr
MCP900/RF Frames (10 pcs).
HS900/W24 Horn/Strobe, white, 24 V,
not synchronized
30 MCP900/LN Lexan language 31
dependent (10 pcs).
H900/R24S Horn, Red, 24 V, synchronized
MCP900/DN Security protection (10 pcs).
SYNC900
The SYNC900 synchronizer module interfaces between the
CALL-R24
Control Panel and the HS900.
Self-Powered siren.
The SYNC900 can synchronize a considerable number of HS900
horns and strobes. The strobes will be syncronized with one- High performance siren
second frequency, and the horns will sound consistently. Modulated frequence sound emission
The SYNC900 synchronizer module provides two indipendent Supplementary interior protection in metal, resistant to
IN/OUT channels, a mute input and a sync error output. corrosive agents
SYNC900 can operate in master-slave mode (cascade). Flasher cutout on low battery
Separate controls for acoustic and flasher signalling
Control voltage 27.6 Vdc
ORDER CODES Battery compartment: up to 12 V 6.5 Ah
Sound level: 104 dBA (3 mt.)
SYNC900/W Surface mount synchronizer Carrier frequency: 1750 Hz
Temperature range: -25 +55 C - IP 34 ORDER CODES
Dimensions (wxhxd): 180x270x90 mm
SYNC900/F Flush mount synchronizer
Weight (without battery): 2,8 Kg CALL-R24 Self-Powered siren
Bentel INC_GB.qxt 21-01-2007 19:40 Pagina 32
accessories accessories
ARTICLE OUTPUT (Vdc) CURRENT (A) DIMENSIONS (wxhxd) WEIGHT (without batt.)
BXM24/25-U 27,6 2,5 max 383x408x97 mm 5 Kg
BXM24/50-U 27,6 5,0 max 383x408x97 mm 5 Kg
BXM24/25-B 27,6 2,5 max 383x408x97 mm 5 Kg
BXM24/50-B 27,6 5,0 max 383x408x97 mm 5 Kg
32 33
BAQ
Switching power supplies.
Switching supply/battery-charger
Compact size
Input voltage: 230 Vac 10% 50/60 Hz
Meets EN60950 standard
Insulation class I
Stability over 1% with full load
Overload protection
Short-circuit protection
ORDER CODES
accessories
BATTERIES
MAINTENANCE FREE
No need to check specific gravity or add water.
SEALED CONSTRUCTION
Ensures that no electrolyte leakage can occur
from terminals or cases.
LONG CYCLE LIFE
Over 1,000 discharge/recharge cycles.
ORDER CODES Nominal Rated Capacity Max. Charging Width (mm) Height (mm) Depth (mm) Total Weight
Voltage (V) (Ah) Current (A) Height (mm) (Kg)
www.bentelsecurity.com
The images shown in this catalogue are merely indicative and Bentel Security s.r.l. reserves the right to modify at any time the characteristics of the products here represented.
Bentel INC_GB.COP.qxt 21-01-2007 23:44 Pagina 1
FIRE.EN 03/06
BENTEL SECURITY srl
www.bentelsecurity.com info@bentelsecurity.com
Company subject to the direction and coordinating activity of Tyco International Ltd
EN