You are on page 1of 106

OFFER N.

20058-15/IT010034 DATE 17-04-2015 REVISION: 9


CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX3 AIR FLOW m/h 2500 / 2000 TECHNICAL DATA SHEET
UMA-01 - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 820 mm
Panel 50 mm Length 2640 mm
Insulation Injected polyurethane Height 1240 + 140 mm
Internal in galvanized steel 5/10 mm Weight 287 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.85 / 1.48 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G280-AT04-72 MOTOR

Fan type Plug fan Installed power 0.41 kW


Size K3G280-AT04-72 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 2000 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 160 Pa Protection IP 54
Total pressure 390 Pa
Total static pressure 360 Pa
Dynamic pressure 30 Pa Nominal current / current in operating point 2.70 / 2.34 A
Number of revolutions 2184 rpm Motor size M3G 084-FA
Max. number of revolutions 2400 rpm Motor eff. Class IE4
Absorbed power 0.22 kW
Absorbed electric power 0.36 kW Ucontrol 9.1 V
Power level 75.5 dB(A)
Fan total / static efficiency 60,39 / 55,8 %
Air speed on fan outlet (V1) 7 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 69 dB(A) Minimum ambient temperature -25 C
Supply sound power 74.4 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 64 63 68 68 70 69 63 60
Inlet [dB] 61 63 68 66 62 62 59 57

17/04/2015 11.37.35 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 1 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.65 kW/(m/s)
Plate heat recovery unit
BI AL 03 N 0652 M 1 AZ CD SC
External air flow 2500 m/h Exhaust air flow 2000 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.82 C Exhaust air temperature out 10.83 C
External relative humidity out 55.14 % Exhaust air humidity out 87.82 %
External air side pressure drop 161 Pa Exhaust air side pressure drop 120 Pa
Air speed 4.11 m/s Air speed 3.29 m/s
Recovery efficiency 6.5 kW Efficiency/Temp ratio 54/43 %
Dry Efficiency/Temp ratio 52/42 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.17 C Exhaust air temperature out 29.04 C
External relative humidity out 41.99 % Exhaust air humidity out 51.74 %
External air side pressure drop 178 Pa Exhaust air side pressure drop 127 Pa
Recovery efficiency 0.7 kW Efficiency/Temp ratio 52/42 %
Dry Efficiency/Temp ratio 52/42 %
Efficiency for balanced air volume 46.01 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 1 592 x 287 x 98 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 750x210 mm. Air FLOW 2500 m/h
Pressure drop: 40 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 750x210 mm. Air FLOW 2000 m/h
Pressure drop: 40 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 81 191 300 Pa
Filters N/dim 1 592 x 490 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 2500 m/h Water
Entering temperature 9.8 C Entering temperature 80 C
Relative humidity 55.1 % Leaving temperature 60 C
Leaving temperature 17.8 C Fluid flow rate 295 l/h
Relative humidity 32.8 % Pressure drop 1.3 kPa

17/04/2015 11.37.35 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 2 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total heating capacity 6.7 kW Water speed 0.43 m/s
Air pressure drop 15 Pa Condensation 0.00 kg/h
Pressure drop dry air 15 Pa Sensible/Total heat factor 1.00
Face velocity 2.90 m/s Water volume in coil 0.00 m
Input air density 1.237 Kg/m
Cu-Al-FeZn P60AC 1R-7T-570A-2.5pa 1C 1/2"
Geometry/Length/Height P60/570x420 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G280-AU11-C2 MOTOR

Fan type Plug fan Installed power 1 kW


Size 280 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 2500 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 547 Pa Protection IP 54
Total pressure 783 Pa
Total static pressure 747 Pa
Dynamic pressure 36 Pa Nominal current / current in operating point 1.60 / 1.60 A
Number of revolutions 3078 rpm Motor size M3G 084-GF
Max. number of revolutions 3100 rpm Motor eff. Class IE4
Absorbed power 0.54 kW
Absorbed electric power 0.91 kW Ucontrol 9.9 V
Power level 86 dB(A)
Fan total / static efficiency 59,78 / 57,06 %
Air speed on fan outlet (V1) 7.7 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 79.3 dB(A) Minimum ambient temperature -25 C
Supply sound power 84.9 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 74 69 77 80 81 78 74 70
Inlet [dB] 71 67 75 78 73 71 69 66

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.31 kW/(m/s)

17/04/2015 11.37.36 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 3 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 71 64 72 69 64 65 63 60 72
Lw at S.A. Outlet [dB] 74 69 77 80 81 78 74 70 85
Lw at E.A. Inlet [dB] 61 63 68 66 62 62 59 57 69
Lw at E.A. Outlet [dB] 64 60 65 63 65 63 57 54 69
Lw to enviroment [dB] 64 67 68 67 65 46 34 71

17/04/2015 11.37.36 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 4 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.36 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 5 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX10 AIR FLOW m/h 7000 / 5600 TECHNICAL DATA SHEET
UMA-02 - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 1120 mm
Panel 50 mm Length 3590 mm
Insulation Injected polyurethane Height 1840 + 140 mm
Internal in galvanized steel 5/10 mm Weight 559 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 2.32 / 1.86 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G450-AY86-02 MOTOR

Fan type Plug fan Installed power 1.65 kW


Size 450 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 5600 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 141 Pa Protection IP 54
Total pressure 378 Pa
Total static pressure 341 Pa
Dynamic pressure 37 Pa Nominal current / current in operating point 2.50 / 1.40 A
Number of revolutions 1406 rpm Motor size M3G 112-IA
Max. number of revolutions 1750 rpm Motor eff. Class IE4
Absorbed power 0.59 kW
Absorbed electric power 0.96 kW Ucontrol 8.0 V
Power level 82.5 dB(A)
Fan total / static efficiency 61,37 / 55,35 %
Air speed on fan outlet (V1) 7.9 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 73.3 dB(A) Minimum ambient temperature -25 C
Supply sound power 82 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 65 69 74 75 78 76 74 68
Inlet [dB] 57 61 69 67 66 68 66 62

17/04/2015 11.37.37 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 6 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.62 kW/(m/s)
Plate heat recovery unit
BI AL 07 N 1000 L 1 AR CD SC
External air flow 7000 m/h Exhaust air flow 5600 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 10.53 C Exhaust air temperature out 10.25 C
External relative humidity out 52.72 % Exhaust air humidity out 89.69 %
External air side pressure drop 150 Pa Exhaust air side pressure drop 102 Pa
Air speed 3.25 m/s Air speed 2.60 m/s
Recovery efficiency 20 kW Efficiency/Temp ratio 59/47 %
Dry Efficiency/Temp ratio 57/46 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.08 C Exhaust air temperature out 29.15 C
External relative humidity out 42.2 % Exhaust air humidity out 51.42 %
External air side pressure drop 166 Pa Exhaust air side pressure drop 109 Pa
Recovery efficiency 2.15 kW Efficiency/Temp ratio 57/46 %
Dry Efficiency/Temp ratio 57/46 %
Efficiency for balanced air volume 50.54 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 1 592 x 592 x 98 1 287 x 592 x 98 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 1050x310 mm. Air FLOW 7000 m/h
Pressure drop: 39 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 1050x310 mm. Air FLOW 5600 m/h
Pressure drop: 39 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 140 220 300 Pa
Filters N/dim 2 490 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 7000 m/h Water
Entering temperature 10.3 C Entering temperature 80 C
Relative humidity 53.4 % Leaving temperature 60 C
Leaving temperature 18.6 C Fluid flow rate 856 l/h
Relative humidity 31.2 % Pressure drop 13.6 kPa

17/04/2015 11.37.38 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 7 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total heating capacity 19.4 kW Water speed 1.24 m/s
Air pressure drop 17 Pa Condensation 0.00 kg/h
Pressure drop dry air 17 Pa Sensible/Total heat factor 1.00
Face velocity 3.10 m/s Water volume in coil 0.00 m
Input air density 1.234 Kg/m
Cu-Al-FeZn P60AC 1R-12T-870A-2.5pa 1C 1/2"
Geometry/Length/Height P60/870x720 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G500-AP25-01 MOTOR

Fan type Plug fan Installed power 2.83 kW


Size 500 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 7000 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 567 Pa Protection IP 54
Total pressure 799 Pa
Total static pressure 767 Pa
Dynamic pressure 32 Pa Nominal current / current in operating point 4.30 / 3.70 A
Number of revolutions 1646 rpm Motor size M3G 150-IF
Max. number of revolutions 1780 rpm Motor eff. Class IE4
Absorbed power 1.55 kW
Absorbed electric power 2.42 kW Ucontrol 9.2 V
Power level 87.2 dB(A)
Fan total / static efficiency 64,21 / 61,65 %
Air speed on fan outlet (V1) 7.3 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 80 dB(A) Minimum ambient temperature -25 C
Supply sound power 86.2 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 72 77 81 81 82 80 76 72
Inlet [dB] 68 73 81 75 74 73 71 68

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.24 kW/(m/s)

17/04/2015 11.37.38 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 8 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 68 70 78 66 65 67 65 62 74
Lw at S.A. Outlet [dB] 72 77 81 81 82 80 76 72 86
Lw at E.A. Inlet [dB] 57 61 69 67 66 68 66 62 73
Lw at E.A. Outlet [dB] 65 66 71 70 73 70 68 62 77
Lw to enviroment [dB] 72 71 69 68 67 48 36 73

17/04/2015 11.37.38 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 9 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.38 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 10 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX3 AIR FLOW m/h 2400 / 1920 TECHNICAL DATA SHEET
UMA-03 - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 820 mm
Panel 50 mm Length 2640 mm
Insulation Injected polyurethane Height 1240 + 140 mm
Internal in galvanized steel 5/10 mm Weight 287 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.78 / 1.42 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G280-AT04-72 MOTOR

Fan type Plug fan Installed power 0.41 kW


Size K3G280-AT04-72 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 1920 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 153 Pa Protection IP 54
Total pressure 380 Pa
Total static pressure 353 Pa
Dynamic pressure 27 Pa Nominal current / current in operating point 2.70 / 2.20 A
Number of revolutions 2136 rpm Motor size M3G 084-FA
Max. number of revolutions 2400 rpm Motor eff. Class IE4
Absorbed power 0.2 kW
Absorbed electric power 0.34 kW Ucontrol 8.9 V
Power level 75 dB(A)
Fan total / static efficiency 60,25 / 55,93 %
Air speed on fan outlet (V1) 6.7 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 68.5 dB(A) Minimum ambient temperature -25 C
Supply sound power 74 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 64 63 68 68 70 69 63 60
Inlet [dB] 62 62 67 66 62 62 59 56

17/04/2015 11.37.40 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 11 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.64 kW/(m/s)
Plate heat recovery unit
BI AL 03 N 0652 M 1 AZ CD SC
External air flow 2400 m/h Exhaust air flow 1920 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.87 C Exhaust air temperature out 10.79 C
External relative humidity out 54.99 % Exhaust air humidity out 88.01 %
External air side pressure drop 152 Pa Exhaust air side pressure drop 113 Pa
Air speed 3.94 m/s Air speed 3.16 m/s
Recovery efficiency 6.3 kW Efficiency/Temp ratio 55/44 %
Dry Efficiency/Temp ratio 52/42 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.16 C Exhaust air temperature out 29.05 C
External relative humidity out 42 % Exhaust air humidity out 51.72 %
External air side pressure drop 168 Pa Exhaust air side pressure drop 120 Pa
Recovery efficiency 0.67 kW Efficiency/Temp ratio 52/42 %
Dry Efficiency/Temp ratio 52/42 %
Efficiency for balanced air volume 46.25 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 1 592 x 287 x 98 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 750x210 mm. Air FLOW 2400 m/h
Pressure drop: 40 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 750x210 mm. Air FLOW 1920 m/h
Pressure drop: 40 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 79 189 300 Pa
Filters N/dim 1 592 x 490 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 2400 m/h Water
Entering temperature 9.9 C Entering temperature 80 C
Relative humidity 55 % Leaving temperature 60 C
Leaving temperature 17.8 C Fluid flow rate 282 l/h
Relative humidity 32.7 % Pressure drop 1.1 kPa

17/04/2015 11.37.40 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 12 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total heating capacity 6.4 kW Water speed 0.41 m/s
Air pressure drop 14 Pa Condensation 0.00 kg/h
Pressure drop dry air 14 Pa Sensible/Total heat factor 1.00
Face velocity 2.78 m/s Water volume in coil 0.00 m
Input air density 1.236 Kg/m
Cu-Al-FeZn P60AC 1R-7T-570A-2.5pa 1C 1/2"
Geometry/Length/Height P60/570x420 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G280-AU11-C2 MOTOR

Fan type Plug fan Installed power 1 kW


Size 280 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 2400 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 536 Pa Protection IP 54
Total pressure 769 Pa
Total static pressure 736 Pa
Dynamic pressure 33 Pa Nominal current / current in operating point 1.60 / 1.51 A
Number of revolutions 3013 rpm Motor size M3G 084-GF
Max. number of revolutions 3100 rpm Motor eff. Class IE4
Absorbed power 0.51 kW
Absorbed electric power 0.86 kW Ucontrol 9.7 V
Power level 85.5 dB(A)
Fan total / static efficiency 59,8 / 57,25 %
Air speed on fan outlet (V1) 7.4 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 78.8 dB(A) Minimum ambient temperature -25 C
Supply sound power 84.5 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 73 68 77 79 81 78 74 70
Inlet [dB] 71 66 75 78 73 71 68 65

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.29 kW/(m/s)

17/04/2015 11.37.40 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 13 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 71 63 72 69 64 65 62 59 72
Lw at S.A. Outlet [dB] 73 68 77 79 81 78 74 70 85
Lw at E.A. Inlet [dB] 62 62 67 66 62 62 59 56 69
Lw at E.A. Outlet [dB] 64 60 65 63 65 63 57 54 69
Lw to enviroment [dB] 63 67 67 67 65 46 34 71

17/04/2015 11.37.40 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 14 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.40 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 15 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX10 AIR FLOW m/h 6000 / 4800 TECHNICAL DATA SHEET
UMA-04 - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 1020 mm
Panel 50 mm Length 3590 mm
Insulation Injected polyurethane Height 1840 + 140 mm
Internal in galvanized steel 5/10 mm Weight 521 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 2.21 / 1.77 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G400-AY87-02 MOTOR

Fan type Plug fan Installed power 1.85 kW


Size 400 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 4800 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 131 Pa Protection IP 54
Total pressure 364 Pa
Total static pressure 331 Pa
Dynamic pressure 33 Pa Nominal current / current in operating point 2.90 / 1.20 A
Number of revolutions 1664 rpm Motor size M3G 112-IA
Max. number of revolutions 2180 rpm Motor eff. Class IE4
Absorbed power 0.49 kW
Absorbed electric power 0.84 kW Ucontrol 7.6 V
Power level 83.1 dB(A)
Fan total / static efficiency 58,16 / 52,83 %
Air speed on fan outlet (V1) 7.4 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 75.9 dB(A) Minimum ambient temperature -25 C
Supply sound power 82.2 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 67 66 74 77 78 76 70 66
Inlet [dB] 65 65 74 72 69 70 66 64

17/04/2015 11.37.42 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 16 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.63 kW/(m/s)
Plate heat recovery unit
BI AL 07 N 0850 L 1 AR CD SC
External air flow 6000 m/h Exhaust air flow 4800 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 10.43 C Exhaust air temperature out 10.36 C
External relative humidity out 52.75 % Exhaust air humidity out 89.67 %
External air side pressure drop 174 Pa Exhaust air side pressure drop 93 Pa
Air speed 3.30 m/s Air speed 2.64 m/s
Recovery efficiency 16.9 kW Efficiency/Temp ratio 59/47 %
Dry Efficiency/Temp ratio 56/45 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.08 C Exhaust air temperature out 29.15 C
External relative humidity out 42.2 % Exhaust air humidity out 51.42 %
External air side pressure drop 168 Pa Exhaust air side pressure drop 110 Pa
Recovery efficiency 1.84 kW Efficiency/Temp ratio 57/46 %
Dry Efficiency/Temp ratio 57/46 %
Efficiency for balanced air volume 50.49 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 135 142 150 Pa
Filters N/dim 3 287 x 592 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 950x310 mm. Air FLOW 6000 m/h
Pressure drop: 38 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 950x210 mm. Air FLOW 4800 m/h
Pressure drop: 38 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 131 216 300 Pa
Filters N/dim 1 592 x 592 x 292 1 287 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 6000 m/h Water
Entering temperature 10.5 C Entering temperature 80 C
Relative humidity 52.8 % Leaving temperature 60 C
Leaving temperature 17.8 C Fluid flow rate 647 l/h
Relative humidity 32.8 % Pressure drop 8.2 kPa

17/04/2015 11.37.42 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 17 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total heating capacity 14.16 kW Water speed 0.93 m/s
Air pressure drop 16 Pa Condensation 0.00 kg/h
Pressure drop dry air 16 Pa Sensible/Total heat factor 1.00
Face velocity 3.01 m/s Water volume in coil 0.00 m
Input air density 1.234 Kg/m
Cu-Al-FeZn P60AC 1R-12T-770A-2.5pa 1C 1/2"
Geometry/Length/Height P60/770x720 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G500-AP25-01 MOTOR

Fan type Plug fan Installed power 2.83 kW


Size 500 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 6000 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 586 Pa Protection IP 54
Total pressure 809 Pa
Total static pressure 786 Pa
Dynamic pressure 23 Pa Nominal current / current in operating point 4.30 / 3.36 A
Number of revolutions 1604 rpm Motor size M3G 150-IF
Max. number of revolutions 1780 rpm Motor eff. Class IE4
Absorbed power 1.35 kW
Absorbed electric power 2.20 kW Ucontrol 9.0 V
Power level 87.1 dB(A)
Fan total / static efficiency 61,4 / 59,62 %
Air speed on fan outlet (V1) 6.2 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 79.9 dB(A) Minimum ambient temperature -25 C
Supply sound power 86.1 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 73 81 83 81 82 79 75 71
Inlet [dB] 69 80 81 75 73 73 70 68

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.32 kW/(m/s)

17/04/2015 11.37.42 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 18 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 69 77 78 66 64 67 64 62 74
Lw at S.A. Outlet [dB] 73 81 83 81 82 79 75 71 86
Lw at E.A. Inlet [dB] 65 65 74 72 69 70 66 64 76
Lw at E.A. Outlet [dB] 67 63 71 72 73 70 64 60 77
Lw to enviroment [dB] 76 73 69 68 66 47 35 73

17/04/2015 11.37.42 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 19 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.42 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 20 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX6 AIR FLOW m/h 3900 / 3120 TECHNICAL DATA SHEET
UMA-05 - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 1020 mm
Panel 50 mm Length 2990 mm
Insulation Injected polyurethane Height 1440 + 140 mm
Internal in galvanized steel 5/10 mm Weight 399 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.90 / 1.52 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G355-AX56-90 MOTOR

Fan type Plug fan Installed power 1 kW


Size 355 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3120 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 145 Pa Protection IP 54
Total pressure 372 Pa
Total static pressure 345 Pa
Dynamic pressure 27 Pa Nominal current / current in operating point 1.65 / 0.93 A
Number of revolutions 1783 rpm Motor size M3G 112-EA
Max. number of revolutions 2140 rpm Motor eff. Class IE4
Absorbed power 0.32 kW
Absorbed electric power 0.54 kW Ucontrol 8.3 V
Power level 80.2 dB(A)
Fan total / static efficiency 59,7 / 55,31 %
Air speed on fan outlet (V1) 6.7 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 73 dB(A) Minimum ambient temperature -25 C
Supply sound power 79.3 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 70 68 71 74 76 72 67 64
Inlet [dB] 67 66 70 70 66 67 63 60

17/04/2015 11.37.44 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 21 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.62 kW/(m/s)
Plate heat recovery unit
BI AL 04 N 0890 M 1 AR CD SC
External air flow 3900 m/h Exhaust air flow 3120 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.21 C Exhaust air temperature out 11.44 C
External relative humidity out 57.43 % Exhaust air humidity out 85.1 %
External air side pressure drop 151 Pa Exhaust air side pressure drop 109 Pa
Air speed 3.75 m/s Air speed 3.00 m/s
Recovery efficiency 9.4 kW Efficiency/Temp ratio 50/40 %
Dry Efficiency/Temp ratio 48/38 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.23 C Exhaust air temperature out 28.96 C
External relative humidity out 41.84 % Exhaust air humidity out 51.98 %
External air side pressure drop 168 Pa Exhaust air side pressure drop 115 Pa
Recovery efficiency 1 kW Efficiency/Temp ratio 48/38 %
Dry Efficiency/Temp ratio 48/38 %
Efficiency for balanced air volume 42.56 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 1 592 x 490 x 98 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 950x210 mm. Air FLOW 3900 m/h
Pressure drop: 36 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 950x210 mm. Air FLOW 3120 m/h
Pressure drop: 36 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 125 212 300 Pa
Filters N/dim 1 592 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 3900 m/h Water
Entering temperature 9.2 C Entering temperature 80 C
Relative humidity 57.4 % Leaving temperature 60 C
Leaving temperature 16.4 C Fluid flow rate 415 l/h
Relative humidity 35.8 % Pressure drop 2.3 kPa

17/04/2015 11.37.44 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 22 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total heating capacity 9.4 kW Water speed 0.60 m/s
Air pressure drop 15 Pa Condensation 0.00 kg/h
Pressure drop dry air 15 Pa Sensible/Total heat factor 1.00
Face velocity 2.93 m/s Water volume in coil 0.00 m
Input air density 1.239 Kg/m
Cu-Al-FeZn P60AC 1R-8T-770A-2.5pa 1C 1/2"
Geometry/Length/Height P60/770x480 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G400-AY87-02 MOTOR

Fan type Plug fan Installed power 1.85 kW


Size 400 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3900 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 556 Pa Protection IP 54
Total pressure 778 Pa
Total static pressure 756 Pa
Dynamic pressure 22 Pa Nominal current / current in operating point 2.90 / 2.11 A
Number of revolutions 1955 rpm Motor size M3G 112-IA
Max. number of revolutions 2180 rpm Motor eff. Class IE4
Absorbed power 0.84 kW
Absorbed electric power 1.38 kW Ucontrol 8.9 V
Power level 85.9 dB(A)
Fan total / static efficiency 60,94 / 59,21 %
Air speed on fan outlet (V1) 6.1 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 79.2 dB(A) Minimum ambient temperature -25 C
Supply sound power 84.8 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 73 70 84 80 80 79 73 69
Inlet [dB] 68 68 83 75 72 72 67 64

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.27 kW/(m/s)

17/04/2015 11.37.44 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 23 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 68 65 80 66 63 66 61 58 74
Lw at S.A. Outlet [dB] 73 70 84 80 80 79 73 69 85
Lw at E.A. Inlet [dB] 67 66 70 70 66 67 63 60 73
Lw at E.A. Outlet [dB] 70 65 68 69 71 66 61 58 74
Lw to enviroment [dB] 65 74 68 66 66 45 33 72

17/04/2015 11.37.44 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 24 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.44 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 25 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX7 AIR FLOW m/h 4700 / 3800 TECHNICAL DATA SHEET
UMA-06 - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 970 mm
Panel 50 mm Length 3090 mm
Insulation Injected polyurethane Height 1640 + 140 mm
Internal in galvanized steel 5/10 mm Weight 416 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 2.08 / 1.69 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G355-AX56-90 MOTOR

Fan type Plug fan Installed power 1 kW


Size 355 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3800 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 155 Pa Protection IP 54
Total pressure 396 Pa
Total static pressure 355 Pa
Dynamic pressure 41 Pa Nominal current / current in operating point 1.65 / 1.24 A
Number of revolutions 1994 rpm Motor size M3G 112-EA
Max. number of revolutions 2140 rpm Motor eff. Class IE4
Absorbed power 0.42 kW
Absorbed electric power 0.70 kW Ucontrol 9.3 V
Power level 83.2 dB(A)
Fan total / static efficiency 59,59 / 53,48 %
Air speed on fan outlet (V1) 8.2 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 76.4 dB(A) Minimum ambient temperature -25 C
Supply sound power 82.2 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 71 70 74 77 79 75 70 69
Inlet [dB] 68 69 73 73 70 70 66 67

17/04/2015 11.37.45 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 26 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.66 kW/(m/s)
Plate heat recovery unit
BI AL 05 N 0840 L 1 AR CD SC
External air flow 4700 m/h Exhaust air flow 3800 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.22 C Exhaust air temperature out 11.5 C
External relative humidity out 57.39 % Exhaust air humidity out 84.85 %
External air side pressure drop 160 Pa Exhaust air side pressure drop 116 Pa
Air speed 3.71 m/s Air speed 3.00 m/s
Recovery efficiency 11.4 kW Efficiency/Temp ratio 50/40 %
Dry Efficiency/Temp ratio 48/39 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.23 C Exhaust air temperature out 28.95 C
External relative humidity out 41.84 % Exhaust air humidity out 52 %
External air side pressure drop 177 Pa Exhaust air side pressure drop 122 Pa
Recovery efficiency 1.21 kW Efficiency/Temp ratio 48/39 %
Dry Efficiency/Temp ratio 48/39 %
Efficiency for balanced air volume 42.37 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 1 592 x 490 x 98 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 900x310 mm. Air FLOW 4700 m/h
Pressure drop: 40 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 900x210 mm. Air FLOW 3800 m/h
Pressure drop: 40 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 108 204 300 Pa
Filters N/dim 1 490 x 592 x 292 1 287 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 4700 m/h Water
Entering temperature 9.2 C Entering temperature 80 C
Relative humidity 57.4 % Leaving temperature 60 C
Leaving temperature 17.4 C Fluid flow rate 573 l/h
Relative humidity 33.4 % Pressure drop 4.9 kPa

17/04/2015 11.37.45 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 27 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total heating capacity 13 kW Water speed 0.83 m/s
Air pressure drop 16 Pa Condensation 0.00 kg/h
Pressure drop dry air 16 Pa Sensible/Total heat factor 1.00
Face velocity 3.02 m/s Water volume in coil 0.00 m
Input air density 1.239 Kg/m
Cu-Al-FeZn P60AC 1R-10T-720A-2.5pa 1C 1/2"
Geometry/Length/Height P60/720x600 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G400-AY87-02 MOTOR

Fan type Plug fan Installed power 1.85 kW


Size 400 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 4700 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 560 Pa Protection IP 54
Total pressure 792 Pa
Total static pressure 760 Pa
Dynamic pressure 32 Pa Nominal current / current in operating point 2.90 / 2.47 A
Number of revolutions 2057 rpm Motor size M3G 112-IA
Max. number of revolutions 2180 rpm Motor eff. Class IE4
Absorbed power 1.03 kW
Absorbed electric power 1.60 kW Ucontrol 9.4 V
Power level 86.4 dB(A)
Fan total / static efficiency 64,49 / 61,88 %
Air speed on fan outlet (V1) 7.3 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 79.5 dB(A) Minimum ambient temperature -25 C
Supply sound power 85.4 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 72 70 80 80 81 79 73 70
Inlet [dB] 68 68 80 75 73 73 68 65

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.23 kW/(m/s)

17/04/2015 11.37.45 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 28 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 68 65 77 66 64 67 62 59 73
Lw at S.A. Outlet [dB] 72 70 80 80 81 79 73 70 85
Lw at E.A. Inlet [dB] 68 69 73 73 70 70 66 67 76
Lw at E.A. Outlet [dB] 71 67 71 72 74 69 64 63 77
Lw to enviroment [dB] 65 70 68 67 66 45 34 72

17/04/2015 11.37.45 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 29 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.45 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 30 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX7 AIR FLOW m/h 4700 / 3800 TECHNICAL DATA SHEET
UMA-ADM - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 970 mm
Panel 50 mm Length 3090 mm
Insulation Injected polyurethane Height 1640 + 140 mm
Internal in galvanized steel 5/10 mm Weight 416 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 2.08 / 1.69 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G355-AX56-90 MOTOR

Fan type Plug fan Installed power 1 kW


Size 355 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3800 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 155 Pa Protection IP 54
Total pressure 396 Pa
Total static pressure 355 Pa
Dynamic pressure 41 Pa Nominal current / current in operating point 1.65 / 1.24 A
Number of revolutions 1994 rpm Motor size M3G 112-EA
Max. number of revolutions 2140 rpm Motor eff. Class IE4
Absorbed power 0.42 kW
Absorbed electric power 0.70 kW Ucontrol 9.3 V
Power level 83.2 dB(A)
Fan total / static efficiency 59,59 / 53,48 %
Air speed on fan outlet (V1) 8.2 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 76.4 dB(A) Minimum ambient temperature -25 C
Supply sound power 82.2 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 71 70 74 77 79 75 70 69
Inlet [dB] 68 69 73 73 70 70 66 67

17/04/2015 11.37.47 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 31 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.66 kW/(m/s)
Plate heat recovery unit
BI AL 05 N 0840 L 1 AR CD SC
External air flow 4700 m/h Exhaust air flow 3800 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.22 C Exhaust air temperature out 11.5 C
External relative humidity out 57.39 % Exhaust air humidity out 84.85 %
External air side pressure drop 160 Pa Exhaust air side pressure drop 116 Pa
Air speed 3.71 m/s Air speed 3.00 m/s
Recovery efficiency 11.4 kW Efficiency/Temp ratio 50/40 %
Dry Efficiency/Temp ratio 48/39 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.23 C Exhaust air temperature out 28.95 C
External relative humidity out 41.84 % Exhaust air humidity out 52 %
External air side pressure drop 177 Pa Exhaust air side pressure drop 122 Pa
Recovery efficiency 1.21 kW Efficiency/Temp ratio 48/39 %
Dry Efficiency/Temp ratio 48/39 %
Efficiency for balanced air volume 42.37 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 1 592 x 490 x 98 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 900x310 mm. Air FLOW 4700 m/h
Pressure drop: 40 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 900x210 mm. Air FLOW 3800 m/h
Pressure drop: 40 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 108 204 300 Pa
Filters N/dim 1 490 x 592 x 292 1 287 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 4700 m/h Water
Entering temperature 9.2 C Entering temperature 80 C
Relative humidity 57.4 % Leaving temperature 60 C
Leaving temperature 16.8 C Fluid flow rate 534 l/h
Relative humidity 34.6 % Pressure drop 4.3 kPa

17/04/2015 11.37.47 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 32 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total heating capacity 12.12 kW Water speed 0.77 m/s
Air pressure drop 16 Pa Condensation 0.00 kg/h
Pressure drop dry air 16 Pa Sensible/Total heat factor 1.00
Face velocity 3.02 m/s Water volume in coil 0.00 m
Input air density 1.240 Kg/m
Cu-Al-FeZn P60AC 1R-10T-720A-2.5pa 1C 1/2"
Geometry/Length/Height P60/720x600 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G400-AY87-02 MOTOR

Fan type Plug fan Installed power 1.85 kW


Size 400 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 4700 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 560 Pa Protection IP 54
Total pressure 792 Pa
Total static pressure 760 Pa
Dynamic pressure 32 Pa Nominal current / current in operating point 2.90 / 2.47 A
Number of revolutions 2057 rpm Motor size M3G 112-IA
Max. number of revolutions 2180 rpm Motor eff. Class IE4
Absorbed power 1.03 kW
Absorbed electric power 1.60 kW Ucontrol 9.4 V
Power level 86.4 dB(A)
Fan total / static efficiency 64,49 / 61,88 %
Air speed on fan outlet (V1) 7.3 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 79.5 dB(A) Minimum ambient temperature -25 C
Supply sound power 85.4 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 72 70 80 80 81 79 73 70
Inlet [dB] 68 68 80 75 73 73 68 65

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.23 kW/(m/s)

17/04/2015 11.37.47 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 33 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 68 65 77 66 64 67 62 59 73
Lw at S.A. Outlet [dB] 72 70 80 80 81 79 73 70 85
Lw at E.A. Inlet [dB] 68 69 73 73 70 70 66 67 76
Lw at E.A. Outlet [dB] 71 67 71 72 74 69 64 63 77
Lw to enviroment [dB] 65 70 68 67 66 45 34 72

17/04/2015 11.37.47 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 34 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.47 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 35 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX8 AIR FLOW m/h 3800 / 3800 TECHNICAL DATA SHEET
UMA-AUD - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 1020 mm
Panel 50 mm Length 3840 mm
Insulation Injected polyurethane Height 1640 + 140 mm
Internal in galvanized steel 5/10 mm Weight 527 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.59 / 1.59 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G355-AX56-90 MOTOR

Fan type Plug fan Installed power 1 kW


Size 355 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3800 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 190 Pa Protection IP 54
Total pressure 431 Pa
Total static pressure 390 Pa
Dynamic pressure 41 Pa Nominal current / current in operating point 1.65 / 1.34 A
Number of revolutions 2036 rpm Motor size M3G 112-EA
Max. number of revolutions 2140 rpm Motor eff. Class IE4
Absorbed power 0.45 kW
Absorbed electric power 0.75 kW Ucontrol 9.4 V
Power level 83.5 dB(A)
Fan total / static efficiency 60,37 / 54,68 %
Air speed on fan outlet (V1) 8.2 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 76.6 dB(A) Minimum ambient temperature -25 C
Supply sound power 82.5 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 72 71 74 77 79 76 70 69
Inlet [dB] 69 69 73 74 70 70 66 66

17/04/2015 11.37.49 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 36 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 0.71 kW/(m/s)
Plate heat recovery unit
BI AL 07 N 0550 L 1 AR CD SC
External air flow 3800 m/h Exhaust air flow 3800 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 11.26 C Exhaust air temperature out 11.25 C
External relative humidity out 50.14 % Exhaust air humidity out 85.94 %
External air side pressure drop 154 Pa Exhaust air side pressure drop 160 Pa
Air speed 3.32 m/s Air speed 3.32 m/s
Recovery efficiency 11.8 kW Efficiency/Temp ratio 51/51 %
Dry Efficiency/Temp ratio 50/50 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 28.98 C Exhaust air temperature out 29.02 C
External relative humidity out 42.45 % Exhaust air humidity out 51.82 %
External air side pressure drop 169 Pa Exhaust air side pressure drop 169 Pa
Recovery efficiency 1.29 kW Efficiency/Temp ratio 51/51 %
Dry Efficiency/Temp ratio 51/51 %
Efficiency for balanced air volume 50.48 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 71 111 150 Pa
Filters N/dim 1 490 x 592 x 48 1 287 x 592 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 950x210 mm. Air FLOW 3800 m/h
Pressure drop: 30 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 950x210 mm. Air FLOW 3800 m/h
Pressure drop: 30 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 71 185 300 Pa
Filters N/dim 1 592 x 592 x 292 1 287 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

COOLING COIL
AIR FLUID
Air flow 3800 m/h Water
Entering temperature 29 C Entering temperature 7 C
Relative humidity 42.5 % Leaving temperature 12.5 C
Leaving temperature 12.7 C Fluid flow rate 4065 l/h
Relative humidity 100 % Pressure drop 27.1 kPa
17/04/2015 11.37.49 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 37 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total cooling capacity 26.02 kW Water speed 1.17 m/s
Air pressure drop 128 Pa Condensation 7.00 kg/h
Pressure drop dry air 99 Pa Sensible/Total heat factor 0.80
Face velocity 2.39 m/s Water volume in coil 0.01 m
Input air density 1.158 kg/m
Cu-Al-FeZn P40AR 5R-15T-735A-2.5pa 5C 1"
Geometry/Length/Height P40/735x600 mm
Row N : 5, N circuits 5, fin pitch 2.5 mm, diam. Manifolds 1"/1"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Drain pan made of aluminium
Calculation mode: Standard

HEATING COIL
AIR FLUID
Air flow 3800 m/h Water
Entering temperature 11.3 C Entering temperature 80 C
Relative humidity 50.1 % Leaving temperature 60 C
Leaving temperature 18 C Fluid flow rate 379 l/h
Relative humidity 32.4 % Pressure drop 2.4 kPa
Total heating capacity 8.6 kW Water speed 0.55 m/s
Air pressure drop 10 Pa Condensation 0.00 kg/h
Pressure drop dry air 10 Pa Sensible/Total heat factor 1.00
Face velocity 2.28 m/s Water volume in coil 0.00 m
Input air density 1.230 Kg/m
Cu-Al-FeZn P60AC 1R-10T-770A-2.5pa 1C 1/2"
Geometry/Length/Height P60/770x600 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G400-AY87-02 MOTOR

Fan type Plug fan Installed power 1.85 kW


Size 400 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3800 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 618 Pa Protection IP 54
Total pressure 839 Pa
Total static pressure 818 Pa
Dynamic pressure 21 Pa Nominal current / current in operating point 2.90 / 2.26 A
Number of revolutions 2010 rpm Motor size M3G 112-IA
Max. number of revolutions 2180 rpm Motor eff. Class IE4
Absorbed power 0.89 kW
Absorbed electric power 1.47 kW Ucontrol 9.2 V
Power level 87 dB(A)
Fan total / static efficiency 60,15 / 58,65 %
Air speed on fan outlet (V1) 5.9 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 80.5 dB(A) Minimum ambient temperature -25 C
Supply sound power 86 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 74 72 86 80 81 80 73 69
Inlet [dB] 70 70 85 76 72 73 68 65

17/04/2015 11.37.49 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 38 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 1.39 kW/(m/s)

17/04/2015 11.37.49 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 39 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 70 67 82 67 63 67 62 59 75
Lw at S.A. Outlet [dB] 74 72 86 80 81 80 73 69 86
Lw at E.A. Inlet [dB] 69 69 73 74 70 70 66 66 77
Lw at E.A. Outlet [dB] 72 68 71 72 74 70 64 63 77
Lw to enviroment [dB] 67 76 68 67 67 45 33 73

17/04/2015 11.37.49 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 40 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.49 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 41 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX7 AIR FLOW m/h 3630 / 2900 TECHNICAL DATA SHEET
UMA-TF - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 970 mm
Panel 50 mm Length 3390 mm
Insulation Injected polyurethane Height 1640 + 140 mm
Internal in galvanized steel 5/10 mm Weight 452 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.61 / 1.29 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G310-AX52-90 MOTOR

Fan type Plug fan Installed power 1 kW


Size 310 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 2900 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 136 Pa Protection IP 54
Total pressure 376 Pa
Total static pressure 336 Pa
Dynamic pressure 40 Pa Nominal current / current in operating point 1.63 / 0.97 A
Number of revolutions 2166 rpm Motor size M3G 112-EA
Max. number of revolutions 2580 rpm Motor eff. Class IE4
Absorbed power 0.3 kW
Absorbed electric power 0.55 kW Ucontrol 8.3 V
Power level 83.5 dB(A)
Fan total / static efficiency 55,47 / 49,59 %
Air speed on fan outlet (V1) 8.1 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 76.1 dB(A) Minimum ambient temperature -25 C
Supply sound power 82.6 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 64 64 70 72 77 78 75 73
Inlet [dB] 61 62 71 70 68 70 69 68

17/04/2015 11.37.50 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 42 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 0.68 kW/(m/s)
Plate heat recovery unit
BI AL 04 N 0840 M 1 AR CD SC
External air flow 3630 m/h Exhaust air flow 2900 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.22 C Exhaust air temperature out 11.42 C
External relative humidity out 57.41 % Exhaust air humidity out 85.17 %
External air side pressure drop 149 Pa Exhaust air side pressure drop 106 Pa
Air speed 3.71 m/s Air speed 2.96 m/s
Recovery efficiency 8.8 kW Efficiency/Temp ratio 50/40 %
Dry Efficiency/Temp ratio 48/38 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.23 C Exhaust air temperature out 28.96 C
External relative humidity out 41.84 % Exhaust air humidity out 51.97 %
External air side pressure drop 164 Pa Exhaust air side pressure drop 112 Pa
Recovery efficiency 0.94 kW Efficiency/Temp ratio 48/38 %
Dry Efficiency/Temp ratio 48/38 %
Efficiency for balanced air volume 42.61 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 130 140 150 Pa
Filters N/dim 1 592 x 490 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 900x210 mm. Air FLOW 3630 m/h
Pressure drop: 30 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 900x210 mm. Air FLOW 2900 m/h
Pressure drop: 30 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 75 188 300 Pa
Filters N/dim 1 490 x 592 x 292 1 287 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

COOLING COIL
AIR FLUID
Air flow 3630 m/h Water
Entering temperature 29.2 C Entering temperature 7 C
Relative humidity 41.8 % Leaving temperature 12.5 C
Leaving temperature 16 C Fluid flow rate 2747 l/h
Relative humidity 90.5 % Pressure drop 32.3 kPa
17/04/2015 11.37.51 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 43 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total cooling capacity 17.58 kW Water speed 1.32 m/s
Air pressure drop 82 Pa Condensation 2.00 kg/h
Pressure drop dry air 67 Pa Sensible/Total heat factor 0.92
Face velocity 2.44 m/s Water volume in coil 0.01 m
Input air density 1.157 kg/m
Cu-Al-FeZn P40AR 3R-15T-690A-2.5pa 3C 3/4"
Geometry/Length/Height P40/690x600 mm
Row N : 3, N circuits 3, fin pitch 2.5 mm, diam. Manifolds 3/4"/3/4"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Drain pan made of aluminium
Calculation mode: Standard

HEATING COIL
AIR FLUID
Air flow 3630 m/h Water
Entering temperature 9.2 C Entering temperature 80 C
Relative humidity 57.4 % Leaving temperature 60 C
Leaving temperature 18.4 C Fluid flow rate 494 l/h
Relative humidity 31.5 % Pressure drop 3.7 kPa
Total heating capacity 11.2 kW Water speed 0.71 m/s
Air pressure drop 11 Pa Condensation 0.00 kg/h
Pressure drop dry air 11 Pa Sensible/Total heat factor 1.00
Face velocity 2.33 m/s Water volume in coil 0.00 m
Input air density 1.239 Kg/m
Cu-Al-FeZn P60AC 1R-10T-720A-2.5pa 1C 1/2"
Geometry/Length/Height P60/720x600 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G355-AY40-02 MOTOR

Fan type Plug fan Installed power 1.7 kW


Size 355 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3630 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 599 Pa Protection IP 54
Total pressure 836 Pa
Total static pressure 799 Pa
Dynamic pressure 37 Pa Nominal current / current in operating point 2.60 / 2.07 A
Number of revolutions 2387 rpm Motor size M3G 112-GA
Max. number of revolutions 2600 rpm Motor eff. Class IE4
Absorbed power 0.84 kW
Absorbed electric power 1.36 kW Ucontrol 9.1 V
Power level 87.1 dB(A)
Fan total / static efficiency 61,95 / 59,21 %
Air speed on fan outlet (V1) 7.8 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 79.9 dB(A) Minimum ambient temperature -25 C
Supply sound power 86.2 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 75 69 81 79 82 81 75 71
Inlet [dB] 74 66 81 76 72 74 69 67

17/04/2015 11.37.51 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 44 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 1.35 kW/(m/s)

17/04/2015 11.37.51 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 45 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 74 63 78 67 63 68 63 61 74
Lw at S.A. Outlet [dB] 75 69 81 79 82 81 75 71 86
Lw at E.A. Inlet [dB] 61 62 71 70 68 70 69 68 76
Lw at E.A. Outlet [dB] 64 61 67 67 72 72 69 67 77
Lw to enviroment [dB] 64 71 67 68 68 47 35 73

17/04/2015 11.37.51 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 46 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.51 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 47 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX4 AIR FLOW m/h 3100 / 2400 TECHNICAL DATA SHEET
UMA-HALL - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 870 mm
Panel 50 mm Length 2990 mm
Insulation Injected polyurethane Height 1440 + 140 mm
Internal in galvanized steel 5/10 mm Weight 347 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.80 / 1.40 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G280-AU06-B2 MOTOR

Fan type Plug fan Installed power 0.71 kW


Size 280 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 2400 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 149 Pa Protection IP 54
Total pressure 382 Pa
Total static pressure 349 Pa
Dynamic pressure 33 Pa Nominal current / current in operating point 3.10 / 2.21 A
Number of revolutions 2527 rpm Motor size M3G 084-GF
Max. number of revolutions 2800 rpm Motor eff. Class IE4
Absorbed power 0.25 kW
Absorbed electric power 0.50 kW Ucontrol 9.0 V
Power level 84 dB(A)
Fan total / static efficiency 50,84 / 46,47 %
Air speed on fan outlet (V1) 7.4 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 76.9 dB(A) Minimum ambient temperature -25 C
Supply sound power 83 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 66 65 74 74 77 78 75 71
Inlet [dB] 64 63 72 72 69 71 70 67

17/04/2015 11.37.52 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 48 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.75 kW/(m/s)
Plate heat recovery unit
BI AL 04 N 0652 M 1 AZ CD SC
External air flow 3100 m/h Exhaust air flow 2400 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.08 C Exhaust air temperature out 11.34 C
External relative humidity out 57.94 % Exhaust air humidity out 85.48 %
External air side pressure drop 161 Pa Exhaust air side pressure drop 110 Pa
Air speed 3.90 m/s Air speed 3.02 m/s
Recovery efficiency 7.3 kW Efficiency/Temp ratio 51/39 %
Dry Efficiency/Temp ratio 49/38 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.25 C Exhaust air temperature out 28.97 C
External relative humidity out 41.8 % Exhaust air humidity out 51.94 %
External air side pressure drop 179 Pa Exhaust air side pressure drop 116 Pa
Recovery efficiency 0.78 kW Efficiency/Temp ratio 49/38 %
Dry Efficiency/Temp ratio 49/38 %
Efficiency for balanced air volume 42.37 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 100 125 150 Pa
Filters N/dim 1 592 x 490 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 800x210 mm. Air FLOW 3100 m/h
Pressure drop: 39 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 800x210 mm. Air FLOW 2400 m/h
Pressure drop: 39 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 83 192 300 Pa
Filters N/dim 1 592 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 3100 m/h Water
Entering temperature 9.8 C Entering temperature 80 C
Relative humidity 55.1 % Leaving temperature 60 C
Leaving temperature 17.8 C Fluid flow rate 366 l/h
Relative humidity 32.7 % Pressure drop 1.6 kPa

17/04/2015 11.37.52 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 49 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total heating capacity 8.3 kW Water speed 0.53 m/s
Air pressure drop 15 Pa Condensation 0.00 kg/h
Pressure drop dry air 15 Pa Sensible/Total heat factor 1.00
Face velocity 2.89 m/s Water volume in coil 0.00 m
Input air density 1.237 Kg/m
Cu-Al-FeZn P60AC 1R-8T-620A-2.5pa 1C 1/2"
Geometry/Length/Height P60/620x480 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G355-AY43-22 MOTOR

Fan type Plug fan Installed power 1.4 kW


Size 355 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 3100 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 531 Pa Protection IP 54
Total pressure 758 Pa
Total static pressure 731 Pa
Dynamic pressure 27 Pa Nominal current / current in operating point 6.00 / 4.80 A
Number of revolutions 2184 rpm Motor size M3G 112-GA
Max. number of revolutions 2450 rpm Motor eff. Class IE4
Absorbed power 0.65 kW
Absorbed electric power 1.11 kW Ucontrol 9.0 V
Power level 84.6 dB(A)
Fan total / static efficiency 58,81 / 56,71 %
Air speed on fan outlet (V1) 6.7 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 77.8 dB(A) Minimum ambient temperature -25 C
Supply sound power 83.6 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 71 68 81 78 79 77 73 69
Inlet [dB] 67 66 80 74 70 71 67 64

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.29 kW/(m/s)

17/04/2015 11.37.52 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 50 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 67 63 77 65 61 65 61 58 72
Lw at S.A. Outlet [dB] 71 68 81 78 79 77 73 69 84
Lw at E.A. Inlet [dB] 64 63 72 72 69 71 70 67 77
Lw at E.A. Outlet [dB] 66 62 71 69 72 72 69 65 78
Lw to enviroment [dB] 63 71 66 65 64 45 33 70

17/04/2015 11.37.52 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 51 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.52 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 52 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX4 AIR FLOW m/h 3130 / 2500 TECHNICAL DATA SHEET
UMA-REP - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 870 mm
Panel 50 mm Length 2740 mm
Insulation Injected polyurethane Height 1440 + 140 mm
Internal in galvanized steel 5/10 mm Weight 324 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.82 / 1.45 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G280-AU06-B2 MOTOR

Fan type Plug fan Installed power 0.71 kW


Size 280 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 2500 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 143 Pa Protection IP 54
Total pressure 379 Pa
Total static pressure 343 Pa
Dynamic pressure 36 Pa Nominal current / current in operating point 3.10 / 2.33 A
Number of revolutions 2585 rpm Motor size M3G 084-GF
Max. number of revolutions 2800 rpm Motor eff. Class IE4
Absorbed power 0.26 kW
Absorbed electric power 0.53 kW Ucontrol 9.2 V
Power level 84.7 dB(A)
Fan total / static efficiency 50,04 / 45,34 %
Air speed on fan outlet (V1) 7.7 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 77.6 dB(A) Minimum ambient temperature -25 C
Supply sound power 83.7 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 67 66 75 75 78 79 75 72
Inlet [dB] 65 64 73 73 70 71 70 68

17/04/2015 11.37.54 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 53 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.76 kW/(m/s)
Plate heat recovery unit
BI AL 04 N 0740 M 1 AR CD SC
External air flow 3130 m/h Exhaust air flow 2500 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.23 C Exhaust air temperature out 11.41 C
External relative humidity out 57.37 % Exhaust air humidity out 85.22 %
External air side pressure drop 145 Pa Exhaust air side pressure drop 104 Pa
Air speed 3.65 m/s Air speed 2.92 m/s
Recovery efficiency 7.6 kW Efficiency/Temp ratio 50/40 %
Dry Efficiency/Temp ratio 48/39 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.23 C Exhaust air temperature out 28.97 C
External relative humidity out 41.84 % Exhaust air humidity out 51.97 %
External air side pressure drop 160 Pa Exhaust air side pressure drop 109 Pa
Recovery efficiency 0.81 kW Efficiency/Temp ratio 48/39 %
Dry Efficiency/Temp ratio 48/39 %
Efficiency for balanced air volume 42.68 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 101 126 150 Pa
Filters N/dim 1 592 x 490 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 800x210 mm. Air FLOW 3130 m/h
Pressure drop: 40 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 800x210 mm. Air FLOW 2500 m/h
Pressure drop: 40 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 84 192 300 Pa
Filters N/dim 1 592 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

Supply fan
FAN K3G355-AY43-22 MOTOR

Fan type Plug fan Installed power 1.4 kW


Size 355 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 3130 m/h Motor shaft diameter - mm

17/04/2015 11.37.54 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 54 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
External static pressure 200 Pa Insulation class F
Internal pressure drops 502 Pa Protection IP 54
Total pressure 730 Pa
Total static pressure 702 Pa
Dynamic pressure 28 Pa Nominal current / current in operating point 6.00 / 4.62 A
Number of revolutions 2153 rpm Motor size M3G 112-GA
Max. number of revolutions 2450 rpm Motor eff. Class IE4
Absorbed power 0.63 kW
Absorbed electric power 1.07 kW Ucontrol 8.9 V
Power level 84.2 dB(A)
Fan total / static efficiency 59,16 / 56,93 %
Air speed on fan outlet (V1) 6.8 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 77.3 dB(A) Minimum ambient temperature -25 C
Supply sound power 83.2 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 71 68 80 77 79 77 73 68
Inlet [dB] 66 66 79 73 70 71 67 63

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.23 kW/(m/s)

17/04/2015 11.37.54 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 55 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 66 63 76 64 61 65 61 57 72
Lw at S.A. Outlet [dB] 71 68 80 77 79 77 73 68 83
Lw at E.A. Inlet [dB] 65 64 73 73 70 71 70 68 78
Lw at E.A. Outlet [dB] 67 63 72 70 73 73 69 66 78
Lw to enviroment [dB] 63 70 65 65 64 45 32 70

17/04/2015 11.37.54 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 56 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.54 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 57 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX3 AIR FLOW m/h 2800 / 2200 TECHNICAL DATA SHEET
UMA-PROC - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 920 mm
Panel 50 mm Length 2540 mm
Insulation Injected polyurethane Height 1240 + 140 mm
Internal in galvanized steel 5/10 mm Weight 301 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.82 / 1.43 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G280-AT04-72 MOTOR

Fan type Plug fan Installed power 0.41 kW


Size K3G280-AT04-72 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 2200 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 152 Pa Protection IP 54
Total pressure 388 Pa
Total static pressure 352 Pa
Dynamic pressure 36 Pa Nominal current / current in operating point 2.70 / 2.59 A
Number of revolutions 2261 rpm Motor size M3G 084-FA
Max. number of revolutions 2400 rpm Motor eff. Class IE4
Absorbed power 0.24 kW
Absorbed electric power 0.40 kW Ucontrol 9.4 V
Power level 76.6 dB(A)
Fan total / static efficiency 59,96 / 54,42 %
Air speed on fan outlet (V1) 7.7 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 70.1 dB(A) Minimum ambient temperature -25 C
Supply sound power 75.5 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 63 63 68 69 71 70 65 62
Inlet [dB] 61 62 69 67 63 63 61 58

17/04/2015 11.37.56 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 58 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.65 kW/(m/s)
Plate heat recovery unit
BI AL 03 N 0790 M 1 AR CD SC
External air flow 2800 m/h Exhaust air flow 2200 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.83 C Exhaust air temperature out 10.7 C
External relative humidity out 55.12 % Exhaust air humidity out 88.28 %
External air side pressure drop 154 Pa Exhaust air side pressure drop 112 Pa
Air speed 3.99 m/s Air speed 3.13 m/s
Recovery efficiency 7.3 kW Efficiency/Temp ratio 55/44 %
Dry Efficiency/Temp ratio 53/41 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.17 C Exhaust air temperature out 29.05 C
External relative humidity out 41.98 % Exhaust air humidity out 51.7 %
External air side pressure drop 171 Pa Exhaust air side pressure drop 118 Pa
Recovery efficiency 0.78 kW Efficiency/Temp ratio 53/41 %
Dry Efficiency/Temp ratio 53/41 %
Efficiency for balanced air volume 46.19 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 1 592 x 287 x 98 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 850x210 mm. Air FLOW 2800 m/h
Pressure drop: 40 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 850x210 mm. Air FLOW 2200 m/h
Pressure drop: 40 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 97 198 300 Pa
Filters N/dim 1 592 x 490 x 292 mm
With safety microswitch
Differential manometer with liquid column

Supply fan
FAN K3G310-AX54-22 MOTOR

Fan type Plug fan Installed power 1.27 kW


Size 310 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 2800 m/h Motor shaft diameter - mm

17/04/2015 11.37.56 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 59 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
External static pressure 200 Pa Insulation class F
Internal pressure drops 533 Pa Protection IP 54
Total pressure 770 Pa
Total static pressure 733 Pa
Dynamic pressure 37 Pa Nominal current / current in operating point 5.60 / 4.38 A
Number of revolutions 2584 rpm Motor size M3G 112-EA
Max. number of revolutions 2850 rpm Motor eff. Class IE4
Absorbed power 0.6 kW
Absorbed electric power 1.01 kW Ucontrol 8.9 V
Power level 85.1 dB(A)
Fan total / static efficiency 59,08 / 56,23 %
Air speed on fan outlet (V1) 7.9 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 77.6 dB(A) Minimum ambient temperature -25 C
Supply sound power 84.3 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 74 69 78 76 79 79 76 72
Inlet [dB] 70 67 78 73 70 71 69 67

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.30 kW/(m/s)

17/04/2015 11.37.56 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 60 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 70 64 75 64 61 65 63 61 72
Lw at S.A. Outlet [dB] 74 69 78 76 79 79 76 72 84
Lw at E.A. Inlet [dB] 61 62 69 67 63 63 61 58 70
Lw at E.A. Outlet [dB] 63 60 65 64 66 64 59 56 70
Lw to enviroment [dB] 64 68 64 65 66 48 36 70

17/04/2015 11.37.56 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 61 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.56 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 62 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX5 AIR FLOW m/h 2700 // TECHNICAL DATA SHEET
UMA-CA - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 920 mm
Panel 50 mm Length 2270 mm
Insulation Injected polyurethane Height 720 + 140 mm
Internal in galvanized steel 5/10 mm Weight 220 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.48 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Intake section
Inlet section with frontal damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x L850xH650 mm. Air flow 2700 m/h
Pressure drop 30.0 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Prefilter type/En Class synthetic G4 (eff. 86%) EN779
Pressure drop clean/mean/dirty filter 139 295 450 Pa
Filters N/dim 1 592 x 592 x 292 mm
Filters N/dim 1 592 x 592 x 48 mm
mm
With safety microswitch
Differential manometer with liquid column

COOLING COIL
AIR FLUID
Air flow 2700 m/h Water
Entering temperature 30 C Entering temperature 7 C
Relative humidity 40 % Leaving temperature 12.5 C
Leaving temperature 10.3 C Fluid flow rate 3847 l/h
Relative humidity 100 % Pressure drop 32.3 kPa
Total cooling capacity 24.62 kW Water speed 1.39 m/s
Air pressure drop 139 Pa Condensation 9.00 kg/h
Pressure drop dry air 111 Pa Sensible/Total heat factor 0.73
Face velocity 2.33 m/s Water volume in coil 0.01 m
Input air density 1.154 kg/m
Cu-Al-FeZn P40AR 6R-13T-620A-2.5pa 4C 1 1/2"

17/04/2015 11.37.57 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 63 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Geometry/Length/Height P40/620x520 mm
Row N : 6, N circuits 4, fin pitch 2.5 mm, diam. Manifolds 1 1/2"/1 1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Drain pan made of aluminium
Calculation mode: Standard

HEATING COIL
AIR FLUID
Air flow 2700 m/h Water
Entering temperature 2 C Entering temperature 80 C
Relative humidity 95 % Leaving temperature 60 C
Leaving temperature 20.8 C Fluid flow rate 754 l/h
Relative humidity 27 % Pressure drop 10.2 kPa
Total heating capacity 17.09 kW Water speed 1.09 m/s
Air pressure drop 17 Pa Condensation 0.00 kg/h
Pressure drop dry air 17 Pa Sensible/Total heat factor 1.00
Face velocity 2.15 m/s Water volume in coil 0.00 m
Input air density 1.272 Kg/m
Cu-Al-FeZn P40AC 1R-13T-670A-2.5pa 1C 1/2"
Geometry/Length/Height P40/670x520 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G310-AX52-90 MOTOR

Fan type Plug fan Installed power 1 kW


Size 310 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 2700 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 481 Pa Protection IP 54
Total pressure 716 Pa
Total static pressure 681 Pa
Dynamic pressure 35 Pa Nominal current / current in operating point 1.63 / 1.64 A
Number of revolutions 2518 rpm Motor size M3G 112-EA
Max. number of revolutions 2580 rpm Motor eff. Class IE4
Absorbed power 0.54 kW
Absorbed electric power 0.92 kW Ucontrol 9.7 V
Power level 87.4 dB(A)
Fan total / static efficiency 58,39 / 55,57 %
Air speed on fan outlet (V1) 7.6 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 79.9 dB(A) Minimum ambient temperature -25 C
Supply sound power 86.5 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 67 67 75 75 80 82 80 75
Inlet [dB] 63 65 74 72 71 74 74 70

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
17/04/2015 11.37.58 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 64 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
With inspection window
With safety microswitch
SFP: 1.23 kW/(m/s)

17/04/2015 11.37.58 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 65 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 63 65 74 68 67 74 74 70 79
Lw at S.A. Outlet [dB] 67 67 75 75 80 82 80 75 87
Lw at E.A. Inlet [dB]
Lw at E.A. Outlet [dB]
Lw to enviroment [dB] 62 65 63 66 69 52 39 72

17/04/2015 11.37.58 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 66 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.58 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 67 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX2 AIR FLOW m/h 1870 / 1500 TECHNICAL DATA SHEET
UMA-EST - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 820 mm
Panel 50 mm Length 2990 mm
Insulation Injected polyurethane Height 1240 + 140 mm
Internal in galvanized steel 5/10 mm Weight 323 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.39 / 1.11 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G250-AT39-72 MOTOR

Fan type Plug fan Installed power 0.45 kW


Size K3G250-AT39-72 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 1500 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 146 Pa Protection IP 54
Total pressure 372 Pa
Total static pressure 346 Pa
Dynamic pressure 26 Pa Nominal current / current in operating point 2.80 / 1.93 A
Number of revolutions 2437 rpm Motor size M3G 084-DF
Max. number of revolutions 3000 rpm Motor eff. Class IE4
Absorbed power 0.16 kW
Absorbed electric power 0.30 kW Ucontrol 8.6 V
Power level 77.5 dB(A)
Fan total / static efficiency 52 / 48,31 %
Air speed on fan outlet (V1) 6.6 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 70.7 dB(A) Minimum ambient temperature -25 C
Supply sound power 76.5 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 64 61 66 67 70 72 69 65
Inlet [dB] 61 59 66 66 64 64 64 60

17/04/2015 11.37.59 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 68 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 0.72 kW/(m/s)
Plate heat recovery unit
BI AL 03 N 0502 M 1 AZ CD SC
External air flow 1870 m/h Exhaust air flow 1500 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.86 C Exhaust air temperature out 10.82 C
External relative humidity out 55 % Exhaust air humidity out 87.9 %
External air side pressure drop 155 Pa Exhaust air side pressure drop 116 Pa
Air speed 4.00 m/s Air speed 3.21 m/s
Recovery efficiency 4.9 kW Efficiency/Temp ratio 54/44 %
Dry Efficiency/Temp ratio 52/42 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.16 C Exhaust air temperature out 29.04 C
External relative humidity out 42 % Exhaust air humidity out 51.73 %
External air side pressure drop 171 Pa Exhaust air side pressure drop 123 Pa
Recovery efficiency 0.52 kW Efficiency/Temp ratio 52/42 %
Dry Efficiency/Temp ratio 52/42 %
Efficiency for balanced air volume 46.18 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 105 127 150 Pa
Filters N/dim 1 592 x 287 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 750x110 mm. Air FLOW 1870 m/h
Pressure drop: 30 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 750x110 mm. Air FLOW 1500 m/h
Pressure drop: 30 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 64 182 300 Pa
Filters N/dim 1 592 x 490 x 292 mm
With safety microswitch
Differential manometer with liquid column

COOLING COIL
AIR FLUID
Air flow 1870 m/h Water
Entering temperature 29.2 C Entering temperature 7 C
Relative humidity 42 % Leaving temperature 12.5 C
Leaving temperature 13.5 C Fluid flow rate 1814 l/h
Relative humidity 100 % Pressure drop 29.7 kPa
17/04/2015 11.37.59 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 69 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total cooling capacity 11.61 kW Water speed 1.31 m/s
Air pressure drop 106 Pa Condensation 2.00 kg/h
Pressure drop dry air 87 Pa Sensible/Total heat factor 0.85
Face velocity 2.40 m/s Water volume in coil 0.01 m
Input air density 1.157 kg/m
Cu-Al-FeZn P40AR 4R-10T-540A-2.5pa 2C 3/4"
Geometry/Length/Height P40/540x400 mm
Row N : 4, N circuits 2, fin pitch 2.5 mm, diam. Manifolds 3/4"/3/4"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Drain pan made of aluminium
Calculation mode: Standard

HEATING COIL
AIR FLUID
Air flow 1870 m/h Water
Entering temperature 9.9 C Entering temperature 80 C
Relative humidity 55 % Leaving temperature 60 C
Leaving temperature 19.1 C Fluid flow rate 256 l/h
Relative humidity 30.1 % Pressure drop 1 kPa
Total heating capacity 5.81 kW Water speed 0.37 m/s
Air pressure drop 10 Pa Condensation 0.00 kg/h
Pressure drop dry air 10 Pa Sensible/Total heat factor 1.00
Face velocity 2.17 m/s Water volume in coil 0.00 m
Input air density 1.236 Kg/m
Cu-Al-FeZn P60AC 1R-7T-570A-2.5pa 1C 1/2"
Geometry/Length/Height P60/570x420 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G250-AY11-C2 MOTOR

Fan type Plug fan Installed power 0.87 kW


Size 250 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 1870 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 609 Pa Protection IP 54
Total pressure 841 Pa
Total static pressure 809 Pa
Dynamic pressure 32 Pa Nominal current / current in operating point 1.35 / 1.38 A
Number of revolutions 3538 rpm Motor size M3G 084-GF
Max. number of revolutions 3580 rpm Motor eff. Class IE4
Absorbed power 0.44 kW
Absorbed electric power 0.76 kW Ucontrol 9.8 V
Power level 84.8 dB(A)
Fan total / static efficiency 57,77 / 55,59 %
Air speed on fan outlet (V1) 7.3 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 78.4 dB(A) Minimum ambient temperature -25 C
Supply sound power 83.7 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 78 73 74 77 79 79 74 70
Inlet [dB] 72 71 74 75 74 70 68 66

17/04/2015 11.37.59 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 70 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 1.46 kW/(m/s)

17/04/2015 11.37.59 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 71 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 72 68 71 66 65 64 62 60 71
Lw at S.A. Outlet [dB] 78 73 74 77 79 79 74 70 84
Lw at E.A. Inlet [dB] 61 59 66 66 64 64 64 60 71
Lw at E.A. Outlet [dB] 64 58 63 62 65 66 63 59 71
Lw to enviroment [dB] 68 64 65 65 66 46 34 70

17/04/2015 11.37.59 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 72 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.37.59 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 73 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX5 AIR FLOW m/h 3700 / 3000 TECHNICAL DATA SHEET
UMA-CAS - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 920 mm
Panel 50 mm Length 3090 mm
Insulation Injected polyurethane Height 1440 + 140 mm
Internal in galvanized steel 5/10 mm Weight 378 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 2.02 / 1.64 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G355-AX56-90 MOTOR

Fan type Plug fan Installed power 1 kW


Size 355 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3000 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 150 Pa Protection IP 54
Total pressure 375 Pa
Total static pressure 350 Pa
Dynamic pressure 25 Pa Nominal current / current in operating point 1.65 / 0.90 A
Number of revolutions 1756 rpm Motor size M3G 112-EA
Max. number of revolutions 2140 rpm Motor eff. Class IE4
Absorbed power 0.31 kW
Absorbed electric power 0.53 kW Ucontrol 8.2 V
Power level 79.8 dB(A)
Fan total / static efficiency 59,5 / 55,49 %
Air speed on fan outlet (V1) 6.5 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 72.4 dB(A) Minimum ambient temperature -25 C
Supply sound power 78.9 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 70 67 71 73 76 72 67 63
Inlet [dB] 67 65 69 70 66 66 63 59

17/04/2015 11.38.01 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 74 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.64 kW/(m/s)
Plate heat recovery unit
BI AL 05 N 0652 L 1 AZ CD SC
External air flow 3700 m/h Exhaust air flow 3000 m/h
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 9.26 C Exhaust air temperature out 11.48 C
External relative humidity out 57.25 % Exhaust air humidity out 84.93 %
External air side pressure drop 152 Pa Exhaust air side pressure drop 110 Pa
Air speed 3.59 m/s Air speed 2.91 m/s
Recovery efficiency 9 kW Efficiency/Temp ratio 50/40 %
Dry Efficiency/Temp ratio 48/39 %
Efficiency for balanced air volume 42.54 % Ricirculation factor 0.00 %

Aluminium recovery unit


With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 1 592 x 490 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 850x210 mm. Air FLOW 3700 m/h
Pressure drop: 40 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 850x210 mm. Air FLOW 3000 m/h
Pressure drop: 40 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 114 207 300 Pa
Filters N/dim 1 592 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 3700 m/h Water
Entering temperature 9.2 C Entering temperature 80 C
Relative humidity 57.3 % Leaving temperature 60 C
Leaving temperature 17.3 C Fluid flow rate 441 l/h
Relative humidity 33.8 % Pressure drop 2.4 kPa
Total heating capacity 10 kW Water speed 0.64 m/s
Air pressure drop 18 Pa Condensation 0.00 kg/h
Pressure drop dry air 18 Pa Sensible/Total heat factor 1.00
Face velocity 3.20 m/s Water volume in coil 0.00 m
Input air density 1.239 Kg/m
Cu-Al-FeZn P60AC 1R-8T-670A-2.5pa 1C 1/2"
Geometry/Length/Height P60/670x480 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"

17/04/2015 11.38.01 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 75 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G355-AY43-22 MOTOR

Fan type Plug fan Installed power 1.4 kW


Size 355 Source 200/1/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 200 ..277 V
Air flow 3700 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 557 Pa Protection IP 54
Total pressure 795 Pa
Total static pressure 757 Pa
Dynamic pressure 38 Pa Nominal current / current in operating point 6.00 / 5.78 A
Number of revolutions 2311 rpm Motor size M3G 112-GA
Max. number of revolutions 2450 rpm Motor eff. Class IE4
Absorbed power 0.82 kW
Absorbed electric power 1.32 kW Ucontrol 9.6 V
Power level 85.2 dB(A)
Fan total / static efficiency 61,72 / 58,74 %
Air speed on fan outlet (V1) 8 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 78.2 dB(A) Minimum ambient temperature -25 C
Supply sound power 84.3 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 71 68 78 78 80 78 74 70
Inlet [dB] 67 66 79 74 71 72 68 65

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.28 kW/(m/s)

17/04/2015 11.38.01 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 76 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 67 63 76 65 62 66 62 59 72
Lw at S.A. Outlet [dB] 71 68 78 78 80 78 74 70 84
Lw at E.A. Inlet [dB] 67 65 69 70 66 66 63 59 73
Lw at E.A. Outlet [dB] 70 64 68 68 71 66 61 57 74
Lw to enviroment [dB] 63 68 66 66 65 46 34 71

17/04/2015 11.38.01 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 77 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.38.01 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 78 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX12 AIR FLOW m/h 6100 / 6100 TECHNICAL DATA SHEET
UMA-LAB - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 1220 mm
Panel 50 mm Length 4040 mm
Insulation Injected polyurethane Height 2040 + 140 mm
Internal in galvanized steel 5/10 mm Weight 708 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.64 / 1.64 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G500-AP25-01 MOTOR

Fan type Plug fan Installed power 2.83 kW


Size 500 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 6100 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 179 Pa Protection IP 54
Total pressure 403 Pa
Total static pressure 379 Pa
Dynamic pressure 24 Pa Nominal current / current in operating point 4.30 / 1.59 A
Number of revolutions 1247 rpm Motor size M3G 150-IF
Max. number of revolutions 1780 rpm Motor eff. Class IE4
Absorbed power 0.68 kW
Absorbed electric power 1.08 kW Ucontrol 7.0 V
Power level 81.2 dB(A)
Fan total / static efficiency 63,45 / 59,64 %
Air speed on fan outlet (V1) 6.3 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 74.3 dB(A) Minimum ambient temperature -25 C
Supply sound power 80.2 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 65 67 73 75 76 74 70 67
Inlet [dB] 61 63 75 69 67 68 65 64

17/04/2015 11.38.02 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 79 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 0.64 kW/(m/s)
Plate heat recovery unit
BI AL 07 N 0900 L 1 AR CD SC
External air flow 6100 m/h Exhaust air flow 6100 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 11.3 C Exhaust air temperature out 11.22 C
External relative humidity out 50 % Exhaust air humidity out 86.08 %
External air side pressure drop 143 Pa Exhaust air side pressure drop 149 Pa
Air speed 3.16 m/s Air speed 3.16 m/s
Recovery efficiency 19 kW Efficiency/Temp ratio 52/52 %
Dry Efficiency/Temp ratio 51/51 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 28.98 C Exhaust air temperature out 29.02 C
External relative humidity out 42.46 % Exhaust air humidity out 51.8 %
External air side pressure drop 157 Pa Exhaust air side pressure drop 157 Pa
Recovery efficiency 2.08 kW Efficiency/Temp ratio 51/51 %
Dry Efficiency/Temp ratio 51/51 %
Efficiency for balanced air volume 50.69 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 98 124 150 Pa
Filters N/dim 2 490 x 592 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 1150x310 mm. Air FLOW 6100 m/h
Pressure drop: 30 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 1150x310 mm. Air FLOW 6100 m/h
Pressure drop: 30 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 94 197 300 Pa
Filters N/dim 1 592 x 592 x 292 1 490 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

COOLING COIL
AIR FLUID
Air flow 6100 m/h Water
Entering temperature 29 C Entering temperature 7 C
Relative humidity 42.5 % Leaving temperature 12.5 C
Leaving temperature 12.2 C Fluid flow rate 6868 l/h
Relative humidity 100 % Pressure drop 27.3 kPa
17/04/2015 11.38.03 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 80 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Total cooling capacity 43.96 kW Water speed 1.24 m/s
Air pressure drop 121 Pa Condensation 13.00 kg/h
Pressure drop dry air 93 Pa Sensible/Total heat factor 0.78
Face velocity 2.30 m/s Water volume in coil 0.02 m
Input air density 1.158 kg/m
Cu-Al-FeZn P40AR 5R-20T-920A-2.5pa 8C 1 1/2"
Geometry/Length/Height P40/920x800 mm
Row N : 5, N circuits 8, fin pitch 2.5 mm, diam. Manifolds 1 1/2"/1 1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Drain pan made of aluminium
Calculation mode: Standard

HEATING COIL
AIR FLUID
Air flow 6100 m/h Water
Entering temperature 11.3 C Entering temperature 80 C
Relative humidity 50 % Leaving temperature 60 C
Leaving temperature 21 C Fluid flow rate 882 l/h
Relative humidity 26.8 % Pressure drop 21.1 kPa
Total heating capacity 20 kW Water speed 1.27 m/s
Air pressure drop 11 Pa Condensation 0.00 kg/h
Pressure drop dry air 11 Pa Sensible/Total heat factor 1.00
Face velocity 2.31 m/s Water volume in coil 0.00 m
Input air density 1.230 Kg/m
Cu-Al-FeZn P60AC 1R-13T-940A-2.5pa 1C 1/2"
Geometry/Length/Height P60/940x780 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G500-AP25-01 MOTOR

Fan type Plug fan Installed power 2.83 kW


Size 500 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 6100 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 625 Pa Protection IP 54
Total pressure 849 Pa
Total static pressure 825 Pa
Dynamic pressure 24 Pa Nominal current / current in operating point 4.30 / 3.59 A
Number of revolutions 1640 rpm Motor size M3G 150-IF
Max. number of revolutions 1780 rpm Motor eff. Class IE4
Absorbed power 1.44 kW
Absorbed electric power 2.35 kW Ucontrol 9.2 V
Power level 87.6 dB(A)
Fan total / static efficiency 61,3 / 59,55 %
Air speed on fan outlet (V1) 6.3 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 80.4 dB(A) Minimum ambient temperature -25 C
Supply sound power 86.7 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 74 82 84 81 83 80 75 72
Inlet [dB] 70 81 81 75 74 74 70 68

17/04/2015 11.38.03 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 81 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 1.39 kW/(m/s)

17/04/2015 11.38.03 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 82 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 70 78 78 66 65 68 64 62 75
Lw at S.A. Outlet [dB] 74 82 84 81 83 80 75 72 87
Lw at E.A. Inlet [dB] 61 63 75 69 67 68 65 64 74
Lw at E.A. Outlet [dB] 65 64 70 70 71 68 64 61 75
Lw to enviroment [dB] 77 74 69 69 67 47 36 74

17/04/2015 11.38.03 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 83 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.38.03 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 84 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX14 AIR FLOW m/h 12000 / 9600 TECHNICAL DATA SHEET
UMA-HOSP - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 1620 mm
Panel 50 mm Length 3590 mm
Insulation Injected polyurethane Height 1840 + 140 mm
Internal in galvanized steel 5/10 mm Weight 773 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 2.67 / 2.14 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G400-AY87-02 MOTOR

Fan wall mounting 2 elements.


The following technical data are related to single fan
Fan type Plug fan Installed power 1.85 kW
Size 400 Source 400/3/50 V/ph/Hz
Quantity / Behavior 2 / 50.0% Voltage range 380 ..480 V
Air flow 4800 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 210 Pa Protection IP 54
Total pressure 443 Pa
Total static pressure 410 Pa
Dynamic pressure 33 Pa Nominal current / current in operating point 2.90 / 1.42 A
Number of revolutions 1742 rpm Motor size M3G 112-IA
Max. number of revolutions 2180 rpm Motor eff. Class IE4
Absorbed power 0.59 kW
Absorbed electric power 0.97 kW Ucontrol 8.0 V
Power level 83.2 dB(A)
Fan total / static efficiency 61,13 / 56,52 %
Air speed on fan outlet (V1) 7.4 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 76 dB(A) Minimum ambient temperature -25 C
Supply sound power 82.3 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 67 66 74 77 79 76 70 66
17/04/2015 11.38.04 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 85 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Inlet [dB] 65 65 75 72 70 70 65 64

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 0.73 kW/(m/s)
Plate heat recovery unit
BI AL 07 N 1300 L 1 AR CD SC
External air flow 12000 m/h Exhaust air flow 9600 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 10.25 C Exhaust air temperature out 10.5 C
External relative humidity out 53.66 % Exhaust air humidity out 88.66 %
External air side pressure drop 249 Pa Exhaust air side pressure drop 170 Pa
Air speed 4.24 m/s Air speed 3.39 m/s
Recovery efficiency 33.2 kW Efficiency/Temp ratio 57/46 %
Dry Efficiency/Temp ratio 55/44 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 29.11 C Exhaust air temperature out 29.12 C
External relative humidity out 42.14 % Exhaust air humidity out 51.52 %
External air side pressure drop 274 Pa Exhaust air side pressure drop 180 Pa
Recovery efficiency 3.58 kW Efficiency/Temp ratio 56/45 %
Dry Efficiency/Temp ratio 56/45 %
Efficiency for balanced air volume 49.01 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 132 141 150 Pa
Filters N/dim 2 592 x 490 x 98 2 592 x 287 x 98 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 1550x410 mm. Air FLOW 12000 m/h
Pressure drop: 40 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 1550x310 mm. Air FLOW 9600 m/h
Pressure drop: 40 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 154 227 300 Pa
Filters N/dim 2 592 x 490 x 292 2 592 x 287 x 292 mm
With safety microswitch
Differential manometer with liquid column

HEATING COIL
AIR FLUID
Air flow 12000 m/h Water
Entering temperature 10.3 C Entering temperature 80 C
Relative humidity 53.4 % Leaving temperature 60 C

17/04/2015 11.38.05 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 86 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Leaving temperature 18.4 C Fluid flow rate 1446 l/h
Relative humidity 31.5 % Pressure drop 17.4 kPa
Total heating capacity 32.79 kW Water speed 1.04 m/s
Air pressure drop 20 Pa Condensation 0.00 kg/h
Pressure drop dry air 20 Pa Sensible/Total heat factor 1.00
Face velocity 3.45 m/s Water volume in coil 0.00 m
Input air density 1.234 Kg/m
Cu-Al-FeZn P60AC 1R-12T-1340A-2.5pa 2C 3/4"
Geometry/Length/Height P60/1340x720 mm
Row N : 1, N circuits 2, fin pitch 2.5 mm, diam. Manifolds 3/4"/3/4"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G500-AP25-01 MOTOR

Fan wall mounting 2 elements.


The following technical data are related to single fan
Fan type Plug fan Installed power 2.83 kW
Size 500 Source 400/3/50 V/ph/Hz
Quantity / Behavior 2 / 50.0% Voltage range 380 ..480 V
Air flow 6000 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 677 Pa Protection IP 54
Total pressure 900 Pa
Total static pressure 877 Pa
Dynamic pressure 23 Pa Nominal current / current in operating point 4.30 / 3.82 A
Number of revolutions 1677 rpm Motor size M3G 150-IF
Max. number of revolutions 1780 rpm Motor eff. Class IE4
Absorbed power 1.5 kW
Absorbed electric power 2.49 kW Ucontrol 9.4 V
Power level 88.2 dB(A)
Fan total / static efficiency 60,19 / 58,62 %
Air speed on fan outlet (V1) 6.2 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 81.1 dB(A) Minimum ambient temperature -25 C
Supply sound power 87.3 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 75 84 85 82 83 80 76 72
Inlet [dB] 71 83 82 76 75 74 71 69

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for dry conditions
With inspection window
With safety microswitch
SFP: 1.49 kW/(m/s)

17/04/2015 11.38.05 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 87 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 71 80 79 67 66 68 65 63 75
Lw at S.A. Outlet [dB] 75 84 85 82 83 80 76 72 87
Lw at E.A. Inlet [dB] 65 65 75 72 70 70 65 64 76
Lw at E.A. Outlet [dB] 67 63 71 72 74 70 64 60 77
Lw to enviroment [dB] 79 75 70 69 67 48 36 74

17/04/2015 11.38.05 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 88 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.38.05 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 89 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX16 AIR FLOW m/h 13200 / 13200 TECHNICAL DATA SHEET
UMA-URG - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 2120 mm
Panel 50 mm Length 3990 mm
Insulation Injected polyurethane Height 2140 + 140 mm
Internal in galvanized steel 5/10 mm Weight 1105 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.87 / 1.87 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G500-AP25-01 MOTOR

Fan wall mounting 2 elements.


The following technical data are related to single fan
Fan type Plug fan Installed power 2.83 kW
Size 500 Source 400/3/50 V/ph/Hz
Quantity / Behavior 2 / 50.0% Voltage range 380 ..480 V
Air flow 6600 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 185 Pa Protection IP 54
Total pressure 413 Pa
Total static pressure 385 Pa
Dynamic pressure 28 Pa Nominal current / current in operating point 4.30 / 1.78 A
Number of revolutions 1296 rpm Motor size M3G 150-IF
Max. number of revolutions 1780 rpm Motor eff. Class IE4
Absorbed power 0.76 kW
Absorbed electric power 1.19 kW Ucontrol 7.3 V
Power level 82.1 dB(A)
Fan total / static efficiency 63,68 / 59,31 %
Air speed on fan outlet (V1) 6.9 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 75.3 dB(A) Minimum ambient temperature -25 C
Supply sound power 81.1 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 65 67 74 76 77 75 71 68
17/04/2015 11.38.06 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 90 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Inlet [dB] 61 64 76 70 68 69 66 65

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 0.65 kW/(m/s)
Plate heat recovery unit
BI AL 07 N 1850 L 1 AE SC
External air flow 13200 m/h Exhaust air flow 13200 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 11.28 C Exhaust air temperature out 11.24 C
External relative humidity out 50.08 % Exhaust air humidity out 86 %
External air side pressure drop 149 Pa Exhaust air side pressure drop 155 Pa
Air speed 3.25 m/s Air speed 3.25 m/s
Recovery efficiency 41 kW Efficiency/Temp ratio 52/52 %
Dry Efficiency/Temp ratio 51/51 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 28.98 C Exhaust air temperature out 29.02 C
External relative humidity out 42.45 % Exhaust air humidity out 51.81 %
External air side pressure drop 164 Pa Exhaust air side pressure drop 164 Pa
Recovery efficiency 4.5 kW Efficiency/Temp ratio 51/51 %
Dry Efficiency/Temp ratio 51/51 %
Efficiency for balanced air volume 50.56 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 86 118 150 Pa
Filters N/dim 3 592 x 490 x 48 3 592 x 287 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 2050x310 mm. Air FLOW 13200 m/h
Pressure drop: 30 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 2050x310 mm. Air FLOW 13200 m/h
Pressure drop: 30 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 80 190 300 Pa
Filters N/dim 3 592 x 592 x 292 3 592 x 287 x 292 mm
With safety microswitch
Differential manometer with liquid column

COOLING COIL
AIR FLUID
Air flow 13200 m/h Water
Entering temperature 29 C Entering temperature 7 C
Relative humidity 42.4 % Leaving temperature 12.5 C
17/04/2015 11.38.07 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 91 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Leaving temperature 14.7 C Fluid flow rate 11537 l/h
Relative humidity 93.9 % Pressure drop 20.9 kPa
Total cooling capacity 73.84 kW Water speed 1.19 m/s
Air pressure drop 106 Pa Condensation 14.00 kg/h
Pressure drop dry air 87 Pa Sensible/Total heat factor 0.86
Face velocity 2.41 m/s Water volume in coil 0.04 m
Input air density 1.158 kg/m
Cu-Al-FeZn P40AR 4R-21T-1810A-2.5pa 14C 2"
Geometry/Length/Height P40/1810x840 mm
Row N : 4, N circuits 14, fin pitch 2.5 mm, diam. Manifolds 2"/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Drain pan made of aluminium
Calculation mode: Standard

HEATING COIL
AIR FLUID
Air flow 13200 m/h Water
Entering temperature 11.3 C Entering temperature 80 C
Relative humidity 50.1 % Leaving temperature 60 C
Leaving temperature 20.2 C Fluid flow rate 1744 l/h
Relative humidity 28.2 % Pressure drop 15.7 kPa
Total heating capacity 39.53 kW Water speed 0.84 m/s
Air pressure drop 11 Pa Condensation 0.00 kg/h
Pressure drop dry air 11 Pa Sensible/Total heat factor 1.00
Face velocity 2.37 m/s Water volume in coil 0.01 m
Input air density 1.230 Kg/m
Cu-Al-FeZn P60AC 1R-14T-1840A-2.5pa 3C 3/4"
Geometry/Length/Height P60/1840x840 mm
Row N : 1, N circuits 3, fin pitch 2.5 mm, diam. Manifolds 3/4"/3/4"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G500-AP25-01 MOTOR

Fan wall mounting 2 elements.


The following technical data are related to single fan
Fan type Plug fan Installed power 2.83 kW
Size 500 Source 400/3/50 V/ph/Hz
Quantity / Behavior 2 / 50.0% Voltage range 380 ..480 V
Air flow 6600 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 604 Pa Protection IP 54
Total pressure 832 Pa
Total static pressure 804 Pa
Dynamic pressure 28 Pa Nominal current / current in operating point 4.30 / 3.70 A
Number of revolutions 1650 rpm Motor size M3G 150-IF
Max. number of revolutions 1780 rpm Motor eff. Class IE4
Absorbed power 1.53 kW
Absorbed electric power 2.42 kW Ucontrol 9.2 V
Power level 87.4 dB(A)
Fan total / static efficiency 63,18 / 61,03 %
Air speed on fan outlet (V1) 6.9 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 80.3 dB(A) Minimum ambient temperature -25 C
Supply sound power 86.5 dB(A) Maximum ambient temperature 50 C

17/04/2015 11.38.07 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 92 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 73 79 82 81 83 80 76 72
Inlet [dB] 69 77 81 75 74 74 70 68

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 1.32 kW/(m/s)

17/04/2015 11.38.07 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 93 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 69 74 78 66 65 68 64 62 74
Lw at S.A. Outlet [dB] 73 79 82 81 83 80 76 72 87
Lw at E.A. Inlet [dB] 61 64 76 70 68 69 66 65 75
Lw at E.A. Outlet [dB] 65 64 71 71 72 69 65 62 76
Lw to enviroment [dB] 74 72 69 69 67 48 36 73

17/04/2015 11.38.07 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 94 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.38.07 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 95 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX5 AIR FLOW m/h 2400 // TECHNICAL DATA SHEET
UMA-PAB - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 770 mm
Panel 50 mm Length 4240 mm
Insulation Injected polyurethane Height 770 + 140 mm
Internal in galvanized steel 5/10 mm Weight 368 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.49 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Intake section
Inlet section with frontal damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x L700xH700 mm. Air flow 2400 m/h
Pressure drop 30.0 Pa

SYNTETIC/METALLIC FILTER
Filter type/En Class/Inspection synthetic G3 - 75%
Pressure drop clean/mean/dirty filter 52 101 150 Pa
Filters N/dim 1 592 x 592 x 48 mm

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F7 - 85% Filters on rails
Prefilter type/En Class synthetic G4 (eff. 86%) EN779
Pressure drop clean/mean/dirty filter 116 283 450 Pa
Filters N/dim 1 592 x 592 x 292 mm
Filters N/dim 1 592 x 592 x 48 mm
mm
With safety microswitch
Differential manometer with liquid column

COOLING COIL
AIR FLUID
Air flow 2400 m/h Water
Entering temperature 30 C Entering temperature 7 C
Relative humidity 40 % Leaving temperature 12.5 C
Leaving temperature 12 C Fluid flow rate 2901 l/h
Relative humidity 100 % Pressure drop 36 kPa
Total cooling capacity 18.57 kW Water speed 1.40 m/s
Air pressure drop 133 Pa Condensation 6.00 kg/h

17/04/2015 11.38.09 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 96 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Pressure drop dry air 104 Pa Sensible/Total heat factor 0.78
Face velocity 2.45 m/s Water volume in coil 0.01 m
Input air density 1.154 kg/m
Cu-Al-FeZn P40AR 5R-14T-485A-2.5pa 3C 1"
Geometry/Length/Height P40/485x560 mm
Row N : 5, N circuits 3, fin pitch 2.5 mm, diam. Manifolds 1"/1"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Drain pan made of aluminium
Calculation mode: Standard

HEATING COIL
AIR FLUID
Air flow 2400 m/h Water
Entering temperature 2 C Entering temperature 80 C
Relative humidity 95 % Leaving temperature 60 C
Leaving temperature 21.4 C Fluid flow rate 692 l/h
Relative humidity 26 % Pressure drop 7.4 kPa
Total heating capacity 15.7 kW Water speed 1.00 m/s
Air pressure drop 19 Pa Condensation 0.00 kg/h
Pressure drop dry air 19 Pa Sensible/Total heat factor 1.00
Face velocity 2.29 m/s Water volume in coil 0.00 m
Input air density 1.272 Kg/m
Cu-Al-FeZn P40AC 1R-14T-520A-2.5pa 1C 1/2"
Geometry/Length/Height P40/520x560 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

STEAM HUMIDIFIER WITH GENERATOR


Producer type KT20
Steam capacity 20.0 kg/h
Entering temperature 21.44 C
Relative humidity in entering air 25.99 %
Leaving temperature 21.44 C
Relative humidity in leaving air 60.78 %
Drop eliminator pressure drop 27 Pa
Pressure drop 27 Pa
Power 15.0 kW
Source 400/3/50
Nominal current 24.0 A
Drop eliminator frame Al/PVC fins - 1 fold
Drain pan made of aluminium
Supply fan
FAN K3G310-BB49-02 MOTOR

Fan type Plug fan Installed power 1.65 kW


Size 310 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 2400 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 899 Pa Protection IP 54
Total pressure 1126 Pa
Total static pressure 1099 Pa
Dynamic pressure 27 Pa Nominal current / current in operating point 2.50 / 2.14 A
Number of revolutions 2937 rpm Motor size M3G 112-GA

17/04/2015 11.38.09 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 97 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Max. number of revolutions 3140 rpm Motor eff. Class IE4
Absorbed power 0.75 kW
Absorbed electric power 1.41 kW Ucontrol 9.3 V
Power level 90.1 dB(A)
Fan total / static efficiency 53,17 / 51,88 %
Air speed on fan outlet (V1) 6.7 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 83.9 dB(A) Minimum ambient temperature -25 C
Supply sound power 88.9 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 77 73 89 83 83 82 80 76
Inlet [dB] 73 72 89 80 75 75 73 70

Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With inspection window
With safety microswitch
SFP: 2.12 kW/(m/s)
Inspection section

ABSOLUT FILTER
Filter type/En Class/Inspection absolute H14=99.999%
Pressure drop clean/mean/dirty filter 162 306 450 Pa
Filters N/dim 1 610 x 610 x 292 mm
Counterframe Galvanized steel 1 629X629X130 mm
With safety microswitch
Differential manometer with liquid column

17/04/2015 11.38.09 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 98 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 73 72 89 76 71 75 73 70 83
Lw at S.A. Outlet [dB] 77 73 89 83 83 82 80 76 89
Lw at E.A. Inlet [dB]
Lw at E.A. Outlet [dB]
Lw to enviroment [dB] 68 79 71 69 69 52 40 76

17/04/2015 11.38.09 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 99 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.38.09 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 100 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OFFER N. 20058-15/IT010034 DATE 17-04-2015 REVISION: 9
CUSTOMER PROKLIMA OFFER REFEREN HOSPITAL DE LANCO USER: Zanchetta

UNIT SIZE: AQX6 AIR FLOW m/h 3400 / 3400 TECHNICAL DATA SHEET
UMA-PM - NO controls Units N.: 1

Altitude: 75 mslm
Working temperatures of the AHU -40/+70 C
STRUCTURAL FEATURES
Profile 50 mm Width 1020 mm
Panel 50 mm Length 3490 mm
Insulation Injected polyurethane Height 1440 + 140 mm
Internal in galvanized steel 5/10 mm Weight 466 kg
External in preplastified galvanized steel 5/10 mm Winter outdoor temperature 2.0 C
Internal guides and suppo Galv. Steel Air velocity through filters section 1.66 / 1.66 m/s
Frame Aluminium AHU's dimensions, weight and divisions are approximate and
Roof Without roof will be optimized during the executive phase

Return fan
FAN K3G355-AX56-90 MOTOR

Fan type Plug fan Installed power 1 kW


Size 355 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3400 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 187 Pa Protection IP 54
Total pressure 419 Pa
Total static pressure 387 Pa
Dynamic pressure 32 Pa Nominal current / current in operating point 1.65 / 1.14 A
Number of revolutions 1915 rpm Motor size M3G 112-EA
Max. number of revolutions 2140 rpm Motor eff. Class IE4
Absorbed power 0.4 kW
Absorbed electric power 0.65 kW Ucontrol 8.9 V
Power level 81.8 dB(A)
Fan total / static efficiency 60,81 / 56,1 %
Air speed on fan outlet (V1) 7.3 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 74.7 dB(A) Minimum ambient temperature -25 C
Supply sound power 80.9 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 71 69 73 75 78 74 69 66
Inlet [dB] 69 68 71 72 68 68 65 62

17/04/2015 11.38.10 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 101 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With safety microswitch
SFP: 0.69 kW/(m/s)
Plate heat recovery unit
BI AL 04 N 0840 C 1 AR CD SC
External air flow 3400 m/h Exhaust air flow 3400 m/h
Winter conditions
External air temperature in 2 C Exhaust air temperature in 20 C
External relative humidity in 95 % Exhaust relative humidity in 50 %
External air temperature out 11.43 C Exhaust air temperature out 11.09 C
External relative humidity out 49.57 % Exhaust air humidity out 86.92 %
External air side pressure drop 151 Pa Exhaust air side pressure drop 157 Pa
Air speed 3.47 m/s Air speed 3.47 m/s
Recovery efficiency 10.7 kW Efficiency/Temp ratio 52/52 %
Dry Efficiency/Temp ratio 51/51 %

Summer conditions
External air temperature in 30 C Exhaust air temperature in 28 C
External relative humidity in 40 % Exhaust relative humidity in 55 %
External air temperature out 28.98 C Exhaust air temperature out 29.02 C
External relative humidity out 42.45 % Exhaust air humidity out 51.82 %
External air side pressure drop 167 Pa Exhaust air side pressure drop 166 Pa
Recovery efficiency 1.16 kW Efficiency/Temp ratio 51/51 %
Dry Efficiency/Temp ratio 51/51 %
Efficiency for balanced air volume 50.81 % Ricirculation factor 0.00 %
Aluminium recovery unit
With frame made of aluminium
With drain pan made of aluminium
Filter type/En Class/Inspection synthetic G4 - 86% Filters on rails
Pressure drop clean/mean/dirty filter 116 133 150 Pa
Filters N/dim 1 592 x 490 x 48 mm
Differential manometer with liquid column
With safety microswitch
Fresh air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 950x210 mm. Air FLOW 3400 m/h
Pressure drop: 30 Pa
Exhaust air damper
Regulation damper, Class 2 leakage Al/PVC,dimensions n1x 950x210 mm. Air FLOW 3400 m/h
Pressure drop: 30 Pa

RIGID BAG FILTER


Filter type/En Class/Inspection rigid bag F8 - 95% Filters on rails
Pressure drop clean/mean/dirty filter 98 199 300 Pa
Filters N/dim 1 592 x 592 x 292 mm
With safety microswitch
Differential manometer with liquid column

COOLING COIL
AIR FLUID
Air flow 3400 m/h Water
Entering temperature 29 C Entering temperature 7 C
Relative humidity 42.4 % Leaving temperature 12.5 C
Leaving temperature 11.3 C Fluid flow rate 4231 l/h
Relative humidity 100 % Pressure drop 28.8 kPa
Total cooling capacity 27.08 kW Water speed 1.22 m/s

17/04/2015 11.38.11 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 102 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Air pressure drop 152 Pa Condensation 9.00 kg/h
Pressure drop dry air 123 Pa Sensible/Total heat factor 0.75
Face velocity 2.47 m/s Water volume in coil 0.02 m
Input air density 1.158 kg/m
Cu-Al-FeZn P40AR 6R-13T-735A-2.5pa 5C 1"
Geometry/Length/Height P40/735x520 mm
Row N : 6, N circuits 5, fin pitch 2.5 mm, diam. Manifolds 1"/1"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Drain pan made of aluminium
Calculation mode: Standard

HEATING COIL
AIR FLUID
Air flow 3400 m/h Water
Entering temperature 11.3 C Entering temperature 80 C
Relative humidity 50.2 % Leaving temperature 60 C
Leaving temperature 21.1 C Fluid flow rate 494 l/h
Relative humidity 26.8 % Pressure drop 5.3 kPa
Total heating capacity 11.2 kW Water speed 0.71 m/s
Air pressure drop 21 Pa Condensation 0.00 kg/h
Pressure drop dry air 21 Pa Sensible/Total heat factor 1.00
Face velocity 2.36 m/s Water volume in coil 0.00 m
Input air density 1.230 Kg/m
Cu-Al-FeZn P40AC 1R-13T-770A-2.5pa 1C 1/2"
Geometry/Length/Height P40/770x520 mm
Row N : 1, N circuits 1, fin pitch 2.5 mm, diam. Manifolds 1/2"/1/2"
Coil frame GI 1.5 mm - Tube Copper 16.45 x 0.4 mm - Fins 0.12 mm Aluminium
Calculation mode: Standard

Supply fan
FAN K3G355-AY40-02 MOTOR

Fan type Plug fan Installed power 1.7 kW


Size 355 Source 400/3/50 V/ph/Hz
Quantity / Behavior 1 / 100.0% Voltage range 380 ..480 V
Air flow 3400 m/h Motor shaft diameter - mm
External static pressure 200 Pa Insulation class F
Internal pressure drops 685 Pa Protection IP 54
Total pressure 917 Pa
Total static pressure 885 Pa
Dynamic pressure 32 Pa Nominal current / current in operating point 2.60 / 2.20 A
Number of revolutions 2442 rpm Motor size M3G 112-GA
Max. number of revolutions 2600 rpm Motor eff. Class IE4
Absorbed power 0.87 kW
Absorbed electric power 1.44 kW Ucontrol 9.3 V
Power level 88.2 dB(A)
Fan total / static efficiency 60,1 / 57,97 %
Air speed on fan outlet (V1) 7.3 m/s
Entering air temperature 20 C
Altitude 75 m.slm
Inlet sound power 81.2 dB(A) Minimum ambient temperature -25 C
Supply sound power 87.2 dB(A) Maximum ambient temperature 50 C
Octave bands sound power level (dB)
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 76 70 84 80 83 82 76 71
Inlet [dB] 75 68 83 77 73 75 70 67

17/04/2015 11.38.11 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 103 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
Motor with integrated electronic speed controller 0-10 Vdc signal with Modbus support
EMC interference immunity acc. to EN 61000-6-2 (industrial enviroment)
EMC interference emission acc. to EN 61000-6-3 (household enviroment)
Conforming to standard EN 61800-5-1; CE
Approval: UL 1004-7 + 60730; GOST; C22.2 Nr.77 + CAN/CSA-E60730-1
Designed for wet conditions
With safety microswitch
SFP: 1.52 kW/(m/s)

17/04/2015 11.38.11 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 104 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
SOUND POWER LEVEL AT AHU
AHU sound levels Lw
Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot. dBA
Lw at O.A. Inlet [dB] 75 65 80 68 64 69 64 61 75
Lw at S.A. Outlet [dB] 76 70 84 80 83 82 76 71 87
Lw at E.A. Inlet [dB] 69 68 71 72 68 68 65 62 75
Lw at E.A. Outlet [dB] 71 66 70 70 73 68 63 60 76
Lw to enviroment [dB] 65 74 68 69 69 48 35 74

17/04/2015 11.38.11 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 105 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014
OPEN SECTION

17/04/2015 11.38.11 CLIVET Spa - Via Camp Lonc, 25 32032 Villapaiera - Feltre (BL) Off. N 20058-15/20
PrzVer:1.0.4.1 - Tel. +39 0439 31.31 - Fax +39 0439 31.33.06 Date 17-04-2015
Page 106 of 106 - info@clivet.it CTAPRO Rel. 1.0.4.1 02-12-2014

You might also like