3WL Air Circuit Breakers
Reference Manual April 2009
4 Introduction
Siemens 2009
SENTRON Switching and Protection Devices Air Circuit Breakers
Introduction
Overview
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a
Degree of protection
With cover IP55 IP55
Without cover IP41 IP41
(with door sealing frame)
Dimensions 3-/4-pole
W D Fixed W mm 320/410 460/590 704/914 460/590
mounting H mm 434 434 434 434
H
NSE0_01111a
Rating Plug
4 Siemens 2009
SENTRON Switching and Protection Devices Air Circuit Breakers
Introduction
Switching capacity
Size I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S N S H H C C
N S N S H H C C
3-pole 4-pole
Short-circuit breaking capacity
Rated operational voltage Ue
up to 415 V AC
Icu kA 55 66 66 80 100 100 150 130
Ics kA 55 66 66 80 100 100 150 130
Icm kA 121 145 145 176 220 220 330 286
Rated operational voltage Ue
up to 500 V AC
Icu kA 55 66 66 80 100 100 150 130
Ics kA 55 66 66 80 100 100 150 130
Icm kA 121 145 145 176 220 220 330 286
Rated operational voltage Ue
up to 690 V AC
Icu kA 42 50 50 75 85 85 150 130
Ics kA 42 50 50 75 85 85 150 130
Icm kA 88 105 105 165 187 187 330 286
Rated operational voltage Ue
up to 1000 V/1150 V AC
Icu kA -- -- -- -- 45 50 704) 704)
4)
Ics kA -- -- -- -- 45 50 70 704)
Icm kA -- -- -- -- 95 105 1544) 1544)
Rated short-time withstand current Icw
of the circuit breakers3)
0.5 s kA 50 66 66 80 100 100 100 100
1s kA 42 50 55 66 80 100 100 100
2s kA 29.5 35 39 46 651)/702) 80 80 80
3s kA 24 29 32 37 501)/652) 65 65 65
Short-circuit breaking capacity Icc
of the non-automatic air circuit breakers
Up to kA 50 66 66 80 100 100 100 100
500 V AC
Up to kA 42 50 50 75 85 85 100 100
690 V AC
1)
Circuit breakers with ECO switching capacity N Size II with In max 2500 A.
N 2)
Size II with In max = 3200 A and In max = 4000 A.
(Icu = Ics up to 55 kA size I/up to 66 kA size II at 500 V)
3)
At a rated voltage of 690 V the Icw value of the circuit breaker cannot be
Circuit breakers with standard switching capacity S greater than the Icu or Ics value at 690 V.
S
(Icu = Ics up to 66 kA size I/up to 80 kA size II at 500 V) 4)
Rated operational voltage Ue = 1150 V.
Siemens 2009 5
SENTRON Switching and Protection Devices Air Circuit Breakers
Introduction
SENTRON 3WL:
Superior individual products integrated into uniform power
distribution systems up to and including industry-specific
industrial and infrastructure solutions
7
2
3 8
5
4
9
1
25
21
10
19
22 11
23
12
24 18 13
17
14 NSE0_01887a
20
16
15
6 Siemens 2009
SENTRON Switching and Protection Devices Air Circuit Breakers
Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B solid-state release)
21
Ethernet
19
20
PROFIBUS
4 5 22 14 15 16 17 18 7
8 6
CubicleBUS
10
11 9
1 1
12
13
2 3
NSE0_01105h
1 SENTRON 3VL 12 Electronic ETU release
2 Electronic LCD ETU release 13 Measurement function Plus
3 Electronic ETU release 14 ZSI module
4 COM10 PROFIBUS module complete with ZSI 15 Digital output module with relay contacts
5 COM20 PROFIBUS module2) complete with ZSI 16 Digital output module with relay contacts, configurable
6 Breaker Data Adapter (BDA) 17 Analog output module
7 BDA Plus with Ethernet interface 18 Digital input module
8 Browser-capable input and output device (e.g. notebook) 19 Switch ES Power on PC
9 SENTRON 3WL 20 PLC e.g. SIMATIC S7
10 COM15 PROFIBUS module1) 21 SIMATIC powercontrol
11 Breaker Status Sensor (BSS) 22 PAC
Features
Coordinated communication concept using the PROFIBUS DP Communication:
or MODBUS, ranging from 16 A to 6300 A with SENTRON 3VL For air circuit breakers with optional communication function
and SENTRON 3WL (ETU45B or ETU76B solid-state release)
The high level of modularity of circuit breakers and accessories see Catalog LV 1.
allows easy retrofitting of all communication components For accessories see Catalog LV 1.
Significant additional benefits for the switchboard due to the For more information see also the Chapter "Power
possibility of linking up external input and output modules to Management System" and "Software for Power Distribution".
the circuit breaker-internal CubicleBUS of the SENTRON 3WL
Innovative software products for parameterization, operation,
monitoring, and diagnostics of SENTRON circuit breakers,
both locally or via PROFIBUS DP, MODBUS or Ethernet/
Intranet/Internet
Complete integration of the SENTRON circuit breakers into the
Totally Integrated Power and Totally Integrated Automation
solutions
Siemens 2009 7
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Design
Circuit breaker Breaking capacity Dimensions
rated current n max (A) With-
cu at 500 V AC (kA) or Fixed-mounted, drawable
cc at 300 V DC (kA) 3- /4-pole 3- /4-pole
4000
2500
Size II
2000
434 / 434 460 / 460 Height
1600 DC N S H
1250 30 66 80 100
800
1250
Size I
630
291 / 291 385 / 385 Depth
The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door. NSE0_00887 o
8 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Safety and reliability
Fixed-mounted circuit breakers
To protect the circuit breakers and plant against unauthorized
switching as well as the maintenance and operator personnel, the
system contains many locking devices. Others can be retrofitted.
N S E 0 _ 0 0 9 6 8 b
N S E 0 _ 0 0 9 6 9 b
Other safety features include:
N S E 0 _ 0 0 9 7 9 a
N S E 0 _ 0 0 9 6 7 b
N S E 0 _ 0 0 9 7 3 b
N S E 0 _ 0 0 9 7 2 b
N S E 0 _ 0 0 9 6 7 b
screw terminals connection method Mechanical reclosing lockout after tripping operation
system (SIGUT) (tension springs)
(standard) (optional) Operator panel cannot be taken off with the circuit breaker in
the ON position
Connection options for auxiliary circuit connections
Additional features of the withdrawable version:
Main contacts:
Auxiliary circuit connections Laminated receptacles in the guide frame, penetration blades
The type of connection for the auxiliary switches depends on the on the withdrawable circuit breaker
type of installation: Position indicator in the operator panel of the withdrawable
Withdrawable version: The internal auxiliary switches are con- circuit breaker
nected to the male connector on the switch side. When fully in- Captive manual crank handle for moving the withdrawable
serted, the connector makes a connection with the sliding circuit breaker
contact module (see "Design", graphic "Guide Frame") in the Guide frame with guide rails for easy moving of the withdra-
guide frame. Various adapters can then be used to complete wable circuit breaker
the wiring (see the graphic "Connection Options for Auxiliary
Circuit Connections"). The withdrawable circuit breaker can be locked to prevent it
being pushed out of position
Fixed mounting: In this case the auxiliary supply connectors
are engaged directly onto the circuit breaker. The connectors The withdrawable circuit breaker cannot be moved when it is
are equipped with coding pins that prevent them being mista- in the ON position
kenly interchanged. Coding of the rated current between the guide frame and the
withdrawable circuit breaker
Operator panel
Standards
The operator panel is designed to protrude from a cut-out in the
door providing access to all control elements and displays with SENTRON 3WL circuit breakers comply with:
the control cabinet door closed. IEC 60947-1, IEC 60947-2
The operator panels for all circuit breakers (fixed-mounted/with- EN 60947-1, EN 60947-2
drawable versions, 3-/4-pole) are identical. The operator panel Climate-proof according to IEC 60068-2-30
ensures degree of protection IP41. Versions according to UL 489 also available, see Catalog LV 16.
For further specifications, see Appendix.
Siemens 2009 9
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Withdrawable short-circuit, grounding, and bridging An energy storage device for shunt releases allows the circuit
units breaker to be opened even if the control voltage is no longer
available.
Portable positively-driven grounding and short-circuit devices
are used for the disconnected system sections to verify isolation Undervoltage releases
from the supply at the workplace.
The undervoltage release causes the circuit breaker to be
Withdrawable grounding units allow simple and comfortable opened if the operational voltage falls below a certain value or is
grounding. They are simply inserted into the guide frames in not applied. The circuit breaker cannot be closed manually or by
place of the corresponding withdrawable circuit breakers. This means of an electrical ON command if the undervoltage release
ensures that these devices are always first connected with the is not connected to the operational voltage. The undervoltage re-
grounding electrode and then with the components to be groun- lease has no delay as standard. A delay can be set by the cus-
ded. tomer in the range between td < 80 ms and td < 200 ms.
The grounding terminals are fitted to the side of the switch enc- In addition, an undervoltage release with a delay in the range
losure and establish the connection when inserted into the guide from 0.2 to 3.2 s is available.
frame.
Closing solenoid
Depending on the version, the short-circuiting links are arranged Operating cycles counter
at the top or bottom. The grounding and short-circuit connec- The motorized operating mechanism can be supplied with a 5-
tions are established when the device is inserted. digit operating cycles counter. The display is incremented by "1"
It must be ensured that the side to be short-circuited and groun- as soon as the storage spring is fully loaded.
ded is not live. For this reason it is recommended that the with- Resetting the manual tripped signal
drawable unit is only wound in when the door is closed.
When the circuit breaker has tripped, this is indicated by the
Withdrawable bridging unit protruding red mechanical tripped indicator on the ETU. When
The withdrawable bridging unit consists of a breaker enclosure the mechanical tripped indicator is activated, the tripping sole-
in which all disconnection components and the operating me- noid and tripped signal are reset. If this display is to be reset re-
chanism have been replaced with simple connections between motely, the reset button can be equipped with a reset solenoid.
the upper and lower contacts. This option allows the circuit breaker to be reset both manually
and electrically.
Auxiliary releases
Automatic resetting of reclosing lockout
Up to two auxiliary releases can be installed at the same time.
The following are available: When the ETU is activated, reclosing of the circuit breaker is pre-
vented until the release is either electrically or manually reset. If
1 shunt release the "Automatic resetting of reclosing lockout" option is used, the
or 1 undervoltage release pre-tensioned circuit breaker is ready to close immediately after
or 2 shunt releases tripping. Resetting the manual tripped indicator is not included
or 1 shunt release in this option.
+ 1 undervoltage release
Tripped signal switch
Signal switch for auxiliary releases
If the circuit breaker has tripped due to an overload, short-cir-
One signaling contact is used for each auxiliary release to deter- cuit, ground fault or extended protection function, the tripped si-
mine the positions of the auxiliary releases. gnal switch can indicate this. This signal switch is available as
Shunt releases an option. If the circuit breaker is used for communication, this
option is supplied as standard.
When the operational voltage is connected to the shunt release,
the circuit breaker is opened immediately. The shunt release is Ready-to-close indicator switch
available in the versions 5 % ON period for overexcitation and The SENTRON 3WL circuit breakers are equipped with an opti-
100 % ON period for permanent excitation. This means that it is cal ready-to-close indicator as standard. In addition, the ready-
also possible to block the circuit breaker against being jogged to-close status can be transmitted by means of a signal switch
into closing. as an option. If the switch is used for communication, the signal
switch is supplied as standard.
10 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Circuit breakers
Guide frames
(1 2 )
(9 )
(1 1 )
(1 0 ) N S E 0 _ 0 0 9 6 6 b
Siemens 2009 11
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
If the circuit breaker is replaced, closing is no longer prevented The locking set contains covering caps which can be sealed.
unless the new circuit breaker is also protected against unautho- Sealing device for solid-state releases
rized closing.
The transparent cover can be sealed. The parameter setting
To activate the locking device, the circuit breaker must be sections are covered to prevent unauthorized access. Openings
opened. The locking device is disabled when the circuit breaker allow access to the query and test button.
is closed. The lock is only activated when the key is removed.
The safety key can be removed only in the "OFF" position. Locking mechanisms
Locking device for "Electrical ON" Locking mechanism against movement for withdrawable circuit
(see graphic "Circuit breakers") breakers when the control cabinet door is open
This prevents unauthorized electrical closing from the operator The crank handle is blocked when the control cabinet door is
panel. Mechanical closing and remote closing remain possible. open and cannot be removed. The withdrawable circuit breaker
The lock is only activated when the key is removed. cannot be moved. The lock only affects the inserted crank
handle.
Locking device for "Mechanical ON"
(see graphic "Circuit breakers") Locking of the control cabinet door
This prevents unauthorized mechanical closing. The mechanical The control cabinet door cannot be opened if
ON button can only be activated if the key is inserted (key ope- The fixed-mounted circuit breaker is closed (the blocking
ration). Closing with the "Electrical ON" button and remote clo- signal is transmitted via the Bowden wire) or
sing remain possible. The lock is only activated when the key is The withdrawable circuit breaker is in the connected position.
removed.
Blocking mechanism using "Mechanical ON" and "OFF" buttons
"Secure OFF" circuit breaker-independent locking device
against unauthorized closing The "Mechanical ON" and "OFF" buttons are covered with a cap
which only allows actuation with a tool. These covering caps are
This special switch-independent function for withdrawable cir- part of the locking set.
cuit breakers prevents closing and fulfills the specifications for
main switches to EN 60204 (VDE 0113) disconnector unit. Un- Optional equipment for guide frames
authorized closing remains impossible even after the circuit
breaker has been exchanged. Shutters
To activate the lock, the circuit breaker must be opened. The lo- The sealing strips of the shutter seal the laminated contacts of
cking device is disabled when the circuit breaker is closed. The the guide frame when the withdrawable circuit breaker is remo-
lock is only activated when the key is removed. The safety key ved and therefore implement touch protection.
can be removed only in the "OFF" position. The sealing strips can be manually opened using the strip
Locking device for crank handle levers.
Prevents removal of the crank. The circuit breaker is protected The position of the sealing strips can be locked in various posi-
against movement. The lock is only activated when the key is tions using padlocks for securing against tampering.
removed.
Locking device for "Mechanical OFF"
Prevents unauthorized mechanical opening from the operator
panel. The "Mechanical OFF pushbutton" can only be activated
if the key is inserted (key operation). Remote opening remains
possible. The lock is only activated when the key is removed.
Locking device for hand-operated lever
The hand-operated lever can be locked with a padlock. The sto-
rage spring cannot be loaded manually.
Locking device against resetting the "tripped" indicator
A lockable cover prevents manual resetting of the "tripped" indi-
cator after overcurrent tripping. This locking device is supplied
together with the transparent cover for solid-state releases.
12 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Rated current coding unit between circuit breaker and guide Equipment-dependent coding
frame
Withdrawable circuit breakers and guide frames can be retrofit-
Withdrawable circuit breakers and guide frames are equipped ted with an equipment-dependent coding unit.
with a rated current coding unit as standard.
This allows different designs of circuit breakers and guide fra-
This ensures that only circuit breakers whose penetration blades mes to be uniquely assigned. If the circuit breaker and guide
are suited to the laminated contacts of the guide frame can be frame have been assigned different codes, the circuit breaker
inserted into a guide frame (see diagram below). cannot be inserted.
36 different coding options can be selected.
Position indicator switch for guide frames
N S E 0 _ 0 1 0 3 1 a
N S E 0 _ 0 1 0 3 2 a
ches. These can be used to determine the position of the circuit
breaker in the guide frame.
(1 )
Two versions are available:
(4 ) Option 1
Connected position 1 CO contact,
(2 )
test position 1 CO contact,
disconnected position 1 CO contact.
(3 ) (5 )
Option 2
(1) Guide frame, interior of l/h side; interior of r/h side similar Connected position 3 CO contacts,
(2) Coding pin on racking rail in guide frame test position 2 CO contacts,
disconnected position 1 CO contact.
(3) Racking rail
(4) Withdrawable circuit breaker, r/h side; l/h side similar
(5) Coding pin on guide frame
Rated current coding unit between circuit breaker and guide frame
(4 )
DISCON
N S E 0 _ 0 1 0 3 3 a
NSE01037
DISCON
N S E 0 _ 0 1 0 3 4 a
NSE01038
TEST
DISCON
N S E 0 _ 0 1 0 3 5 a
NSE01039
TEST
DISCON
N S E 0 0 1 0 3 6 a NSE01040
(1) Auxiliary circuit (2) Main circuit (3) Control cabinet door (4) Shutter
Siemens 2009 13
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Function
NSE0_00882b
NSE0_00881b
NSE0_00880b
R
R R
s d
s d
J s d
i J s d
g
J g
N S E 0 _ 0 0 9 5 0 c N S E 0 _ 0 0 9 5 1 b N S E 0 _ 0 0 9 5 2 b
Additional functions
N-conductor protection can be switched on/off -- --
N-conductor protection adjustable -- -- --
Instantaneous short-circuit protection can be switched on/off -- -- --
Non-delayed short-circuit protection can be switched on/off -- -- --
Thermal image can be switched on/off -- -- --
Load monitoring -- -- --
Short-time delayed short-circuit protection switchable to I2t -- -- --
Instantaneous short-circuit protection adjustable -- --
Overload protection switchable to I4t -- -- --
Overload protection can be switched on/off -- -- --
Selectable parameter sets -- -- --
Measurement function
Measurement function Plus -- -- --
Communication
CubicleBUS -- -- --
Communication through PROFIBUS DP -- -- --
Communication through MODBUS -- -- --
Communication through Ethernet -- -- --
Standard -- Not available Optional
Detailed information about the functions of the solid-state releases is given in the following.
14 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
ETU76B
Rating Plug
=
12
NSE0_00886c
NSE0_00883b
IR IR
tR tR
Isd Isd
t sd t sd
Ig Ig
Ii Ii
tg tg
ETU45B ETU76B
--
--
--
--
--
--
--
Siemens 2009 15
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
16 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
ETU15B solid-state release
Application:
Option: safety lock
prevents pressing of Simple building and
Mechanical RESET reset button after system protection without time-se-
for reclosing lockout overcurrent release
lective coordination up to 4000 A.
and mechanical
tripped indicator
Not to be used for size III.
Features:
Adjustable overload protection
with I2t characteristic curve
Indicator: overcurrent with preset delay time
release activated
tR = 10 seconds at 6 IR
Indicator: overload alarm Indicator: fault in
overcurrent release Instantaneous short-circuit pro-
tection adjustable in the range
Rotary switch for setting
value, overload release
2 ... 8 In
Overload display
Protection function is set by
Rotary switch for setting
value, instantaneous
means of the rotary coding
Sealing ring
short-circuit release switch
For technical details see the table
"Functional overview of the
solid-state release system"
NSE0_00954b
Siemens 2009 17
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
NSE0_00956c
The same as ETU25B but also
Reversible neutral conductor
Indicator: overcurrent
release activated
ETU27B N-conductor protection protection
on/off
Indicator: overload alarm OFF ON
Permanently integrated ground-
Rating Plug Indicator: fault in
Rated current module overcurrent release
fault protection. Calculation of
the ground-fault current through
Rotary switch for setting N
Indicator: cause of release
vectorial summation current
value, overload release formation
Rotary switch for setting Rotary switch for delay,
value, instantaneous short-circuit release For technical details see the table
short-circuit release "Functional overview of the
Short-circuit protection Sealing ring solid-state release system"
fixed setting OFF under "Technical specifications".
Rotary switch for delay,
Rotary switch for setting
earth-fault protection
value, earth-fault protection
Query pushbutton
Test pushbutton Clear pushbutton
Test socket
Rotary switch for setting short-circuit release Thermal image as restart protection for trip-
value, short-circuit Indicator: cause of release
protection ped motor outgoing feeders
Sealing ring
Selector for
Option: earth-fault module
Reversible and adjustable neutral conduc-
earth-fault protection SI tor protection
Indicator: earth-fault alarm
Rotary switch for setting g
18 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
ETU76B solid-state release
Application:
Mechanical RESET Option: safety lock
for reclosing lockout prevents pressing of The multi-talent with graphical
and mechanical reset button after display for system analysis
tripped indicator ETU76B overcurrent release
"CubicleBUS integrated"
Features:
The same as ETU45B but also
Indicators: including
Overcurrent release
activated Graphical display Two protection parameter sets
Overload alarm
COMMUNICATION
which can be stored separately
EXPANDED in the release (switchover is per-
Indicator: fault in
overcurrent release formed by means of external si-
gnal)
Indicator: cause of release Rating Plug
Control keys for setting With overload protection which
he release parameters can be deactivated for operation
Rated current module in modern drive technology
Option: earth-fault module Indicators: Adjustable delay of
Ground-fault alarm
Ground-fault tripped delayed short-circuit protection
Fields for noting up to 4000 ms
setting values Fields for noting
setting values
Neutral conductor protection ad-
Test pushbutton justable up to IN = 200 % In
Clear pushbutton
Query pushbutton Test socket
Setting of protection functions by
means of Breaker Data Adapter
NSE0_00960b (BDA) or via communications in-
terface
Graphical display of all
parameters and events/
curve trends
Graphics display with high con-
trast, backlit display, and sleep
mode
For technical details see the table
"Functional overview of the
solid-state release system"
under "Technical specifications".
Ground-fault protection Ground-fault releases "G" sense fault currents that flow to ground
and that can cause fire in the plant. Multiple circuit breakers con-
Selector for nected in series can have their delay times adjusted so as to pro-
Indicators: Ground-fault
ground-fault
alarm vide graduated discrimination.
detection
GFM AT 45B Ground-fault
Rotary switch 1
tripped
When setting the parameters for the solid-state release it is pos-
for setting
value,
g TRIP ALARM ALARM J g (s) 1 2J g sible to choose between "alarm" and "trip" in the event that the
ground-fault G A .5 .1
set current value is exceeded. The reason for tripping is indica-
B .4 .2
protection
C TRIP .3 .3 ted by means of an LED when the query button is activated.
D .2 .4
OFF Rotary switch
E .1 .5
NSE0_00962a
for setting The ETU45B and ETU76B solid-state release versions can be re-
Rotary switch value, ground-
for setting value fault protection delay trofitted with a ground-fault protection module. This ground fault
ground-fault alarm J g/1
2
J g
protection function is integrated in ETU27B solid-state releases.
TRIP TRIP 1 2J
1 g= A J g= ms
Fields for Fields for
noting setting NSE0_00964a
noting setting
values values
Siemens 2009 19
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
A standard current transformer with the following data is used for With the exception of the ETU27B solid-state release, all
measurement of the ground-fault current: 1200 A/1 A, Class 1 versions of the ground-fault modules are supplied with an I2t
(the internal load of SENTRON 3WL is 0.11 ). The current trans- characteristic curve which can be activated.
former can be installed directly in the grounded neutral point of Selection criteria for SENTRON 3WL circuit breakers
a transformer.
Basic criteria for selecting circuit breakers are:
Max. short-circuit current at place of installation of circuit brea-
L1 ker I k max.
L2 This value determines the short-circuit breaking capacity
SENTRON WL
L3 or short-circuit current carrying capacity of the circuit breaker.
N It is compared with the value Icu, Ics, Icw of the circuit breaker
T5 PE and essentially determines the size of the circuit breaker.
NSE 00946 See illustration "Overview of SENTRON 3WL Circuit
Breakers/Non-Automatic Air Circuit Breakers".
Rated current In which is to flow through the branch circuit.
3-pole circuit breakers, current transformers in the N conductor This value must not be larger than the maximum rated current
for the circuit breaker.
L1 The rated current for the SENTRON 3WL is set with the rated
L2 current module. See "Design", illustration "Overview of
SENTRON WL
L3 SENTRON 3WL Circuit Breakers/Non-Automatic Air Circuit
N Breakers".
Ambient temperature
T6 for the circuit breaker.
PE This is usually the control cabinet internal temperature.
T6: 1200 A/1 A NSE 00947
Design of the circuit breaker
3-pole circuit breakers, current transformers in the grounded neutral Minimum short-circuit current
point of the transformer which flows through the switching device. The release must
still detect this value as a short-circuit and must respond by
L1 tripping.
L2
Protection functions of the circuit breaker.
SENTRON WL L3
These are determined by the selection of the
N
corresponding solid-state release, see the table
"Functions of the solid-state releases" under "Functions".
T6
PE
NSE 00948
T6: 1200 A/1 A
20 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
SENTRON 3WL for DC applications
This version of the 3WL non-automatic air circuit breaker is sui-
table for direct current applications. The external protective de-
vice DIGmat S100 provides adjustable overload and short-
circuit protection for the SENTRON 3WL non-automatic air circuit
breaker.
This is based on the measuring chain of a shunt resistor and the
DIGmat S100 tripping unit. Shunt resistors are available for
1000 A, 2000 A and 4000 A (special ranges on request). They
are in accordance with DIN 43703 and have a class accuracy
of 0.5.
A measuring-circuit voltage of 60 mV DC is picked off for rated
current In.
The measuring-circuit voltage is a linear image of the primary DIGmat S100
current.
The DIGmat S100 tripping unit monitors the image of the primary Short-circuit protection:
current thus supplied and compares it with the tripping cha- Setting range Ii = 1.25 IR up to max. 4 In
racteristic curve set on the device. The parameter settings on If the set value is exceeded, tripping occurs in less than
the DIGmat S100 apply also for DC feedbacks. 50 ms.
Reversing duty is possible therefore.
In = Rated current of the circuit breaker
The tripping characteristic curve is determined and described IR = Set current value of the adjustable overload release
by the following variables: tR = Assigned tripping time of the overload trip
Overload protection: Ii = Instantaneous tripping current of the adjustable short-
Setting range IR = 0.4 ... 1.0 In circuit releases
The curve has a I2t characteristic.
The components are available only from the company
The tripping time tR is selectable between 2 and 10 s, with tR
mat Maschinen- und Anlagentechnik
defined for 6 IR.
(for address see "Appendix" => "External Partners").
Configuration
Mutual mechanical circuit breaker interlocking The bending radii of the Bowden wire must be greater than
500 mm.
The module for mutual mechanical interlocking can be used for
one or two SENTRON 3WL circuit breakers and can be adapted The sum of all bending angles along the Bowden wire must not
easily to the corresponding versions. The fixed-mounted and exceed 640.
withdrawable circuit breaker versions are fully compatible and In a vertical arrangement of circuit breakers to be interlocked,
can therefore be used in a mixed configuration in an installation. the interlocking mechanisms must be in line.
This also applies to 3WN6 circuit breakers. Circuit breakers to be interlocked must be arranged so that
The circuit breakers can be mounted alongside each other or Bowden cables can be optimally installed in compliance with
one above the other, whereby the distance of the circuit breakers the conditions mentioned in the above points.
is determined solely by the length of the Bowden wire (lengths: The installed Bowden wire must be fixed (with cable ties or the
2 m/3 m/4.5 m). Interlock signals are looped through using the like) before the interlock is adjusted.
Bowden wires. Interlocking is only effective in the connected po-
sition in the case of withdrawable circuit breakers. The mechani- Select the width of switchgear cubicle to allow enough free-
cal endurance of the Bowden cables is 10 000 operating cycles. dom of movement for adjusting the interlock!
Openings and cut-outs in system elements must be designed
Minimum requirements must be fulfilled in the switchgear for the so that Bowden wires are not changed in direction or obs-
interlocking to function: tructed when they are passed through.
Bowden wires must be installed as far as possible in a straight
line with minimum bending.
Mutual mechanical interlocking of circuit breakers examples
Mutual interlocking of two Interlocking between three Mutual interlocking of three Interlocking of three circuit
circuit breakers circuit breakers circuit breakers breakers, two of them mutual
G G G
S1 S2 S1 S3 S1 S3
S1 S2 S3
S2 S1 S2 S3 S2
Siemens 2009 21
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Output device
Ethernet/ e.g. notebook
Intranet/ with browser
Zone Selective
Interlocking module
Digital output module
Relay
Digital output module
Relay, configurable
NSE0_01820a
BDA Plus
MODBUS
Output device
Ethernet/ e.g. notebook
Intranet/ with browser
Zone Selective
Interlocking module
Digital output module
Relay
Digital output module
Relay, configurable
BDAPlus
22 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
SENTRON 3WL communication-capable circuit breakers
Function Solid-state Brea- PROFI- Measu Analog Digital Digital ZSI Brea- Brea-
release version ker Sta- BUS rement output output input modul ker ker
ETU45B ETU76B tus com- func- module module module es Data Data
Sensor munica- tion s s s Adapter Adap-
tion Plus ter Plus
port
Functions of the communication-capable SENTRON 3WL circuit breakers
Indication of measured values in release (current
only)
Indication of measured values in release
(U, I, P, S, Q, p.f., etc.)
Indication of measured values (current only),
--
parameter, diagnostic values etc. on display
Indication of measured values (U, I, P, S, Q, p.f., etc.),
--
parameters, diagnostic values etc. in release
Output of measured values (current only)
to rotary coil instruments in control cabinet door
Output of measured values (U, I, P, S, Q, p.f., etc.) to
rotary coil instruments in control cabinet door
Output of digital signals
(e. g. reason for tripping, alarm signals, status)
through contacts
Automatic changeover between
--
parameter sets A and B
Read in digital signals and forward to
PROFIBUS/MODBUS
Transmission of switch information
on HTML basis locally to a PC
Transmission of switch information
on HTML basis through Ethernet
Short-time grading control for
S tripping and G protection
Local display of harmonic analysis and waveform
--
memory
Local storage of harmonic analysis and waveform
memory and transmission through PROFIBUS
Read out protection parameters through PROFIBUS
Read out and adjust protection parameters through
--
PROFIBUS
Required Not necessary for this function, optionally combinable
Function can optionally be taken over by more than one release. -- Function not available
Function can optionally be taken over by one of these modules.
Siemens 2009 23
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter
All SENTRON 3WLs with ETU45B, ETU76B (CubicleBUS integrated)
Measurement function
Plus
Order code F01+ ... or F02+ ... F05
Additional transmittable circuit breaker data with integrated measurement function
Additional event signals
Threshold value alarms (e. g. over/underfrequency, over/undervoltage)
Parameterization of the extended protection functions and setpoints (threshold values)
Reading out the parameters of the extended protection functions
Settings for the extended protection function parameters can be changed
Reading out and adjusting threshold values
Additional measured values
Voltages, power, energy, power factor, frequency, each with min./max. value
Harmonic analysis
Recording of currents and voltages for configurable events in the curve form memory
1) Data only available in conjunction with the COM15 module (BUS connec- Available
tion not required). -- Not available
2) Only possible with ETU76B.
24 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
CubicleBUS modules
Digital output modules with rotary coding switch
6 items of binary information concerning the state of the circuit
breaker (reasons for tripping and warnings) can be output via
this module to external signaling devices (e. g. LED, horn) or be
used for the selective shut-down of other system components
(e. g. frequency converters).
Digital output modules are available in versions with and without
a rotary coding switch. On modules with a rotary coding switch
it is possible to choose between two signaling blocks each with
6 defined assignments and to set an additional response delay. Analog output module
All the digital output modules are available as a version with re- Digital input modules
lay outputs (CO contacts, up to 12 A). Up to two modules of this With the digital input module, up to 6 additional binary signals
type can be connected to one SENTRON 3WL. (24 V DC) in the circuit breaker environment can be connected
to the system. It is thus possible for example to send messages
concerning the state of a switch disconnector or a control cabi-
net door to the PROFIBUS DP/MODBUS.
With the digital input module on the CubicleBUS it is also pos-
sible for the two different protection parameter sets held in the
ETU76B solid-state releases to be switched over automatically in
a few milliseconds. It is thus possible, for example, to automati-
cally change the parameters of a coupling switch should the
transformer infeed fail.
One module each of this type can be used for holding the six
items of digital information and for automatically switching over
Digital output module with rotary coding switch the parameters.
Digital output modules, configurable
The configurable output module is available for higher-perfor-
mance solutions. With this module, random events on the
CubicleBUS can be switched directly to one of six available out-
puts or three of these outputs can be assigned with up to six
events. In other words, up to six events can be placed on one
physical output with OR operation. Either BDA/BDA Plus or
Switch ES Power is used for configuring.
A relay variant is also available here the same as for the output
modules with rotary coding switch. Only one module of this type
is possible per SENTRON 3WL.
Digital input module
ZSI modules (short-time grading control)
The use of ZSI modules is recommended when Siemens circuit
breakers are arranged in several staggered levels but full gra-
ding with the smallest possible delay is to be assured neverthe-
less.
The circuit breakers are interconnected by these modules. In
case of a short-circuit, each affected circuit breaker asks the cir-
cuit breakers directly downstream whether the short-circuit has
also occurred in the next, lower level. The short-circuit is exactly
localized as the result, and only the next upstream circuit brea-
Digital output module, configurable ker in the energy flow direction is switched off.
Analog output modules
The analog output module can be used to output the following
measured values to analog indicators in the control cabinet
door:
IL1, IL2, IL3, IN or
UL12, UL23, UL31, UL1N or
PL1, PL2, PL3, Stot or
p.f.1 , p.f.2 , p.f.3, I % or
favg, ULLavg, Ptot, p.f.avg
Four 4-20-mA/0-10-V interfaces are available for this. The
measured values to be output are selected with a rotary coding
switch. By using the analog output module it is possible to do ZSI module (short-time grading control)
without additional converters and their conventional installa-
tion/wiring in the main current path. Up to two modules of this
type can be connected to one SENTRON 3WL.
Siemens 2009 25
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Technical specifications
Size I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S N S H H C C
N S N S H H C C
3-pole 4-pole
Short-circuit breaking capacity
Rated operational voltage Ue
up to 415 V AC
Icu kA 55 66 66 80 100 100 150 130
Ics kA 55 66 66 80 100 100 150 130
Icm kA 121 145 145 176 220 220 330 286
Rated operational voltage Ue
up to 500 V AC
Icu kA 55 66 66 80 100 100 150 130
Ics kA 55 66 66 80 100 100 150 130
Icm kA 121 145 145 176 220 220 330 286
Rated operational voltage Ue
up to 690 V AC
Icu kA 42 50 50 75 85 85 150 130
Ics kA 42 50 50 75 85 85 150 130
Icm kA 88 105 105 165 187 187 330 286
Rated operational voltage Ue
up to 1000 V/1150 V AC
Icu kA -- -- -- -- 45 50 704) 704)
Ics kA -- -- -- -- 45 50 704) 704)
4)
Icm kA -- -- -- -- 95 105 154 1544)
Rated short-time withstand current Icw
of the circuit breakers3)
0.5 s kA 50 66 66 80 100 100 100 100
1s kA 42 50 55 66 80 100 100 100
2s kA 29.5 35 39 46 651)/702) 80 80 80
3s kA 24 29 32 37 501)/652) 65 65 65
Short-circuit breaking capacity Icc
of the non-automatic air circuit breakers
Up to 500 V AC kA 50 66 66 80 100 100 100 100
Up to 690 V AC kA 42 50 50 75 85 85 100 100
1) Size II with In max 2500 A.
Circuit breakers with ECO switching capacity N 2) Size II with In max = 3200 A and In max = 4000 A.
N
(Icu = Ics up to 55 kA size I/up to 66 kA size II at 500 V) 3) At a rated voltage of 690 V the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V.
Circuit breakers with standard switching capacity S
S 4) Rated operational voltage Ue = 1150 V.
(Icu = Ics up to 66 kA size I/up to 80 kA size II at 500 V)
Circuit breakers with high switching capacity H
H
(Icu = Ics up to 100 kA at 500 V)
Circuit breakers with very high switching capacity C
C
(Icu = Ics up to 150 kA (3-pole)/130 kA (4-pole)
at 500 V)
26 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Size I II
Type ... 3WL11 10 3WL11 12 3WL11 16 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20
Rated current In at 40 C, at 50/60 Hz
Main conductor A ... 1000 1250 1600 800 1000 1250 1600 2000
N conductor (only on 4-pole versions) A ... 1000 1250 1600 800 1000 1250 1600 2000
Rated operational voltage Ue at 50/60 Hz V AC ... 690 ... 690 ... 690 ... ... ... ... ...
(for 1000 V version see Catalog LV 1, "Options") 690/1000 690/1000 690/1000 690/1000 690/1000
Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
Main current paths kV 12 12 12 12 12 12 12 12
Auxiliary circuits kV 4 4 4 4 4 4 4 4
Control circuits kV 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function acc. to EN 60947-2 Yes Yes Yes Yes Yes Yes Yes Yes
Utilization categories B
Permissible ambient temperature
During operation (in operation with LCD max. 55 C)4) C 25/+70 25/+70 25/+70 25/+70 25/+70 25/+70 25/+70 25/+70
During storage (special conditions for LCDs must be C 40/+70 40/+70 40/+70 40/+70 40/+70 40/+70 40/+70 40/+70
observed)
Permissible load Up to 55 C (Cu bare) A 1000 1250 1600 800 1000 1250 1600 2000
At rear horizontal main circuit Up to 60 C (Cu bare)5) A 1000 1250 1600 800 1000 1250 1600 2000
connections Up to 70 C (Cu black A 1000 1210 1490 800 1000 1250 1600 2000
painted) 5)
Rated rotor operational voltage Uer V 2000 2000 2000 2000 2000 2000 2000 2000
Power loss at In
With 3-phase symmetrical load
Fixed-mounted circuit breakers W 100 105 150 40 45 80 85 180
Withdrawable circuit breakers W 195 205 350 85 95 165 175 320
Operating times
Make-time ms 35 35 35 35 35 35 35 35
Opening time ms 38 38 38 34 34 34 34 34
2)
Electrical make-time (through closing solenoid) ms 80 80 80 100 100 100 100 100
Electrical opening time (through shunt release) ms 73 73 73 73 73 73 73 73
Electrical opening time (instant. undervoltage release) ms 73 73 73 73 73 73 73 73
Opening time due to ETU, instant. short-circuit release ms 501) 501) 501) 501) 501) 501) 501) 501)
Endurance
Mechanical (without maintenance) Oper. cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
Mechanical (with maintenance)3) Oper. cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
Electrical (without maintenance) Oper. cycles 10 000 10 000 10 000 7500 7500 7500 7500 7500
1000 V version, electrical (without maintenance) Oper. cycles -- -- -- 1000 1000 1000 1000 1000
1150 V version, electrical (without maintenance) Oper. cycles -- -- -- 500 500 500 500 500
Electrical (with maintenance)3) Oper. cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
Switching frequency
690 V version 1/h 60 60 60 60 60 60 60 60
1000 V version 1/h -- -- -- 20 20 20 20 20
1150 V version 1/h -- -- -- 20 20 20 20 20
Minimum interval between tripping operation by solid-state ms 80 80 80 80 80 80 80 80
release and next making operation of the circuit breaker (only
with autom. mechanical resetting of the lockout device)
Mounting position 3 0 3 0 3 0 3 0
h m a x .
= 1 m m
and/
or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a
Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Main conductor Copper bars, Units 1 2 2 1 1 2 2 3
2
minimum bare mm 60 10 40 10 50 10 50 10 60 10 40 10 50 10 50 10
cross-sections Copper bars, Units 1 2 2 1 1 2 2 3
painted black mm2 60 10 40 10 50 10 50 10 60 10 40 10 50 10 50 10
Auxiliary conductors (Cu) Standard connection =
Max. number of strain-relief clamp
auxiliary conductors Without end sleeve 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14)
cross-section (solid/stranded) With end sleeve acc. to 1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16)
DIN 46228 Part 2
With twin end sleeve 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
Optional connection =
tension spring
Without end sleeve 2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14)
With end sleeve acc. to 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
DIN 46228 Part 2
Position indicator switches Tension spring terminals 1 0.5 mm2 (AWG 20) ... 1 2.5 mm2 (AWG 14)
Weights 3-pole Fixed-mounted circuit kg 43 43 43 56 56 56 56 56
breakers
Withdrawable circuit kg 45 45 45 60 60 60 60 60
4-pole breakers
Guide frames kg 25 25 25 31 31 31 31 31
Fixed-mounted circuit kg 50 50 50 67 67 67 67 67
breakers
Withdrawable circuit kg 54 54 54 72 72 72 72 72
breakers
Guide frames kg 30 30 30 37 37 37 37 37
1) Opening time on instantaneous short-circuit release with 3) Maintenance means: replace main contact elements and arc chutes (see
ETU15B = 85 ms. Operating Manual).
2) Make-time through closing solenoid for synchronization purposes 4) Use of releases from 20 C.
(short-time excited) 50 ms. 5) ETU76B with graphics display can be used up to max. 55 C.
Siemens 2009 27
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Size II III
Type 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
Rated current In at 40 C, at 50/60 Hz
Main conductor A 2500 3200 4000 4000 5000 6300
N conductor (only on 4-pole versions) A 2500 3200 4000 4000 5000 6300
Rated operational voltage Ue at 50/60 Hz V AC ... 690/1000 ... 690/1000 ... 690 ... 690/1000 ... 690/1000 ... 690/1000
(for 1000 V version see Catalog LV 1, "Options")
Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
Main current paths kV 12 12 12 12 12 12
Auxiliary circuits kV 4 4 4 4 4 4
Control circuits kV 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function acc. to EN 60947-2 Yes Yes Yes Yes Yes Yes
Utilization categories B (except switching capacity class DC)
Permissible ambient temperature
During operation (in operation with LCD max. 55 C)4) C 25/+70 25/+70 25/+70 25/+70 25/+70 25/+70
During storage (special conditions for LCDs must be observed) C 40/+70 40/+70 40/+70 40/+70 40/+70 40/+70
6) Up to 55 C (Cu bare) A 2500 3200 3950 4000 5000 5920
Permissible load
Up to 60 C (Cu bare)5) A 2500 3020 3810 4000 5000 5810
Up to 70 C (Cu black painted)5) A 2280 2870 3600 4000 5000 5500
Rated rotor operational voltage Uer V 2000 2000 2000 2000 2000 2000
Power loss at In
With 3-phase symmetrical load
Fixed-mounted circuit breakers W 270 410 750 520 630 900
Withdrawable circuit breakers W 520 710 925 810 1050 1600
Operating times
Make-time ms 35 35 35 35 35 35
Opening time ms 34 34 34 34 34 34
Electrical make-time (through closing solenoid)2) ms 100 100 100 100 100 100
Electrical opening time (through shunt release) ms 73 73 73 73 73 73
Electrical opening time (instantaneous undervoltage release) ms 73 73 73 73 73 73
Opening time due to ETU, instantaneous short-circuit release ms 501) 501) 501) 50 50 50
Endurance
Mechanical (without maintenance) Oper. cycles 10000 10000 10000 5000 5000 5000
Mechanical (with maintenance)3) Oper. cycles 15000 15000 15000 10000 10000 10000
Electrical (without maintenance) Oper. cycles 7500 4000 4000 2000 2000 2000
1000 V version, electrical (without maintenance) Oper. cycles 1000 1000 1000 1000 1000 1000
1150 V version, electrical7) (without maintenance) Oper. cycles 500 500 500 1000 1000 1000
Electrical (with maintenance)3) Oper. cycles 15000 15000 15000 10000 10000 10000
Switching frequency
690 V version 1/h 60 60 60 60 60 60
1000 V version 1/h 20 20 20 20 20 20
1150 V version7) 1/h 20 20 20 20 20 20
Minimum interval between tripping operation by solid-state ms 80 80 80 80 80 80
release and next making operation of the circuit breaker (only
with automatical mechanical resetting of the lockout device)
3 0 3 0 3 0 3 0
h m a x .
Mounting position
= 1 m m
and/
or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a
Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Main conductor Copper bars, Units 2 3 4 4x 6x 6x
minimum bare mm2 100 10 100 10 120 10 100 x 10 100 x 10 120 x 10
cross-sections Copper bars, Units 2 3 4 4 6 6
painted black mm2 100 10 100 10 100 108) 100 10 100 10 120 10
Auxiliary conductors Standard connection = strain-relief clamp
(Cu) Without end sleeve 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14)
Max. number of With end sleeve acc. to DIN 46228 Part 2 1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16)
auxiliary conductors With twin end sleeve
cross-section 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
(solid/stranded)
Optional connection = tension spring
Without end sleeve 2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14)
With end sleeve acc. to DIN 46228 Part 2 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
Position indicator swit- Tension spring terminals 1 0.5 mm2 (AWG 20) ... 1 2.5 mm2 (AWG 14)
ches
Weights 3-pole Fixed-mounted circuit breakers kg 59 64 85 82 82 90
Withdrawable circuit breakers kg 63 68 121 88 88 96
Guide frames kg 39 45 52 60 60 70
4-pole Fixed-mounted circuit breakers kg 71 77 103 99 99 108
Withdrawable circuit breakers kg 76 82 146 106 106 108
Guide frames kg 47 54 62 84 84 119
1) Opening time on instantaneous short-circuit release with 4) Use of releases from 20 C.
ETU15B = 85 ms. 5) ETU76B with graphics display can be used up to max. 55 C.
2) Make-time through closing solenoid for synchronization purposes 6) 4000 A, size II in fixed-mounted version, 3-pole.
(short-time excited) 50 ms. 7) Size III: data for very high switching capacity.
3) Maintenance means: replace main contact elements and arc chutes (see 8) Minimum main conductor cross-sections for 4-pole withdrawable circuit
Operating Manual). breakers: 4 x 120 x 10 mm.
28 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Size I to III
Type 3WL1
Manual operating mechanism with mechanical closing
Closing/ Max. force required to operate the hand lever N 230
Charging stored- Required number of strokes on the hand lever 9
energy feature
Manual operating mechanism with mechanical and electrical closing
Charging stored-
energy feature
Closing solenoid Operating range 0.85 ... 1.1 Us
(CC)
Extended operating range for battery operation At 24 V DC, 48 V DC 0.7 ... 1.26 Us
60 V DC, 110 V DC
220 V DC
Power consumption AC/DC VA/W 15/15
Minimum command duration at Us for the closing solenoid ms 60
Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
Manual/motorized operating mechanism with mechanical and electrical closing
Manual operating For data see above.
mechanism
Motor Operating range 0.85 ... 1.1 Us
Extended operating range for battery operation At 24 V DC, 48 V DC 0.7 ... 1.26 Us
60 V DC, 110 V DC
220 V DC
Power consumption of motor AC/DC VA/W 135/135
Time required to charge the stored-energy mechanism at 1 Us s 10
Closing solenoid For data see above.
For motor and Short-circuit protection 2 A TDz (slow)/1 A
closing solenoid Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic;
Motor and closing solenoid for the same rated control supply voltages
Smallest permissible DIAZED fuse (gL operational class)/ At Us = 24 ... 30 V 2A
miniature circuit breaker with C characteristic (for different At Us = 48 ... 60 V 2A
rated control supply voltages) At Us = 110 ... 125 V DC/ 1A
110 ... 127 V AC
At Us = 220 ... 250 V DC/ 1A
208 ... 240 V AC
Solid-state release signals
Measuring accuracy of the solid-state release Protection functions according to
EN 60947;
current indication 10 %;
Measurement function
base quantities 1 %;
Measurement function
derived quantities 4 %
Auxiliary releases
Undervoltage Response values Pickup 0.85 Us
releases (circuit breaker can be closed)
UVR (F3) and Dropout 0.35 ... 0.7 Us
UVR-td (F4) (circuit breaker is tripped)
Operating range 0.85 ... 1.1
Extended operating range for battery operation At 24 V DC, 30 V DC, 0.85 ... 1.26
48 V DC, 110 V DC,
220 V DC
Rated control supply voltage Us Instantaneous
AC 50/60 Hz V 110 ... 127/208 ... 240/380 ... 415
DC V 24/30/48/60/110/220 ... 2501)
Delayed
AC 50/60 Hz V 110 ... 127; 208 ... 240; 380 ... 415
DC V 48; 110 ... 125; 220 ... 250
Power consumption (pickup/uninterrupted duty) AC VA 20/5
DC W 20/5
Opening time of circuit breaker at Us = 0 ms 200
- Version UVR (F3)
Instantaneous ms 80
With delay ms 200
- Version UVR-td (F8)
With delay, td = 0.2 to 3.2 s s 0.2 ... 3.2
Reset through additional NC contact direct switching off ms 100
Short-circuit protection 1 A TDz (slow) 1 A
Smallest permissible DIAZED fuse (gL operational class)/
Miniature circuit breaker with C characteristic
1) 24 V and 30 V only with undervoltage release UVR (F3).
Siemens 2009 29
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Size I to III
Type 3WL1
Auxiliary releases
Shunt release (ST) For continuous command - Response value pickup > 0.7 Us
(F1, F2) (100 % ON period), locks (circuit breaker is tripped)
out on momentary-con- - Operating range 0.85 ... 1.1 Us
tact commands
- Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 Us
for battery operation 60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us AC 50/60 Hz V 110; 230
DC V 24; 30; 48; 60; 110; 220
- Power consumption AC/DC VA/W 15/15
- Minimum command duration at Us ms 60
- opening time of circuit breaker at AC/DC ms 80
Us = 100 %
- Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational
class)/ miniature circuit breaker with C characteristic
5 % ON period - Response value Pickup > 0.7 Us
(circuit breaker is tripped)
- Operating range 0.85 ... 1.1 Us
- Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 Us
for battery operation 60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us AC 50/60 Hz V 110 ... 127; 208 ... 240
DC V 24; 48; 110 ... 125; 220 ... 250
- Power consumption AC/DC VA/W 15/15
- Minimum command duration at Us ms 25
- Opening time of circuit breaker at AC/DC ms 50
Us = 100 %
- Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
With stored energy - Rated control supply voltage Us AC 50/60 Hz V 110; 230
feature consisting of DC V 110; 220
shunt release and capa- - Operating range 0.85 ... 1.1 Us
citor storage device
- Power consumption AC/DC VA/W 1/1
- Storage time at Us/ maximum 5 min/minimum 5 s
recharging time at Us
- Opening time of circuit breaker, As with "for continuous
short-circuit protection command"
Remote reset solenoid for mechanical tripped indicator (F7)
Remote reset solenoid for - Operating range 0.85 ... 1.1 Us
mechanical tripped indica- - Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 Us
tor (F7) for battery operation 110 V DC
220 V DC
- Power consumption AC/DC VA/W 50/50
- Minimum command duration at Us for the remote ms 60
reset solenoid
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/ 2 A TDz (slow)/1 A at 24 V DC
miniature circuit breaker with C characteristic and 48 V DC,
1 A TDz (slow)/1 A at 110 V and
208 ... 250 V
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui V AC/DC 500
Rated operational voltage Ue V AC/DC 500
Rated impulse withstand voltage Uimp kV 4
Switching capacity Alternating current - Rated operational voltage Ue V 24 ... 230 380/400 500
50/60 Hz - Rated operational current
Ie /AC-12 A 10 10 10
Ie/AC-15 A 4 3 2
Direct current - Rated operational voltage Ue V 24 48 110 220
- Rated operational current
Ie/DC-12 A 10 8 3.5 1
Ie/DC-13 A 8 4 1.2 0.4
Short-circuit protection Largest permissible DIAZED fuse (gL operational class) 10 A TDz, 10 A Dz
Largest permissible miniature circuit breaker with C characteristic 10 A
30 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Size I to III
Type 3WL1
Ready-to-close signaling switch (S20) (acc. to DIN VDE 0630)
Switching capacity Alternating current - Rated operational voltage Ue V 250
- Rated operational current Ie A 8
Direct current - Rated operational voltage Ue V 125 250
- Rated operational current Ie A 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (gL operational class) 2 A Dz (quick)
Tripped signal switch (S24) and signal switch for auxiliary releases (S22, S23) (acc. to DIN VDE 0630)
Switching capacity Alternating current - Rated operational voltage Ue V 250
- Rated operational current Ie/AC-12 A 8
Direct current - Rated operational voltage Ue V 24 125 250
- Rated operational current Ie/DC-12 A 6 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (gL operational class) 6 A Dz (quick)
Tripped signal switch Signal duration after tripping Until manual or electrical
remote reset (option)
Position indicator switch on guide frame
Type of contact Signal: - "Circuit breaker in connected 3 CO 1 CO
position" 2 CO or 1 CO
- "Circuit breaker in test position" 1 CO 1 CO
- "Circuit breaker in disconnected
position"
Rated insulation voltage Ui AC 50/60 Hz V 440
DC V 250
Rated operational voltage Ue V 250
Rated impulse withstand voltage Uimp kV 4
Switching capacity Rated operational - Ie/AC-12 24 V 10 A, 110/127 V 10 A,
current Ie 220/240 V 10 A, 320/440 V 10 A
- Ie/AC-15 220/240 V 4 A,
320/440 V 3 A,
- Ie/DC-12 24 V 10 A, 48 V 2.5 A,
220/240 V 0.2 A,
- Ie/DC-13 24 V 3.0 A, 220/240 V 0.1 A
Siemens 2009 31
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
s d
S Setting range for delay time tsd
Switchable short-time delayed short-circuit protection
--
--
0-M-100-200-300-400 ms
--
0-M-100-200-300-400 ms
--
(I2t-dependent function)
Setting range for delay time tsd at I2t -- -- --
Zone Selective Interlocking function -- -- --
i Instantaneous short-circuit protection
N S E 0 _ 0 0 8 8 8 b
I Function can be switched on/off
Setting range Ii = In ...
--
2-3-4-5-6-7-8
--
Fixed for Ii 20 In, max. 50
--
Fixed for Ii 20 In, max. 50
kA kA
Ground-fault protection -- -- Fixed mounted
Tripping and alarm function -- -- --
Tripping function can be switched on/off -- --
Alarm function can be switched on/off -- -- --
Detection of the ground-fault current through summation -- --
g current formation with internal or external neutral con-
ductor transformer
g
G
Detection of ground-fault current through external
current transformer
-- -- --
32 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Siemens 2009 33
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Characteristic curves
Every solid-state release type and every setting has its own cha- 10000
NSE0_01527
racteristic curve. Only a selection is shown in the following. The
R min R max
characteristic curves each show the largest and smallest setting
[s]
range of SENTRON 3WL circuit breakers with 1000 A rated cur- 1000 0,5 ... 1,0 x n
rent at 500 V rated voltage with various releases. In order to ob-
Opening time
tain a complete tripping characteristic, the relevant parts of the 100
characteristics have to be combined.
The characteristic curves show the behavior of the solid-state re- 10
lease when it is activated by a current that is already flowing be-
fore the tripping operation. If the overcurrent tripping occurs im-
mediately after switch on and the solid-state release is therefore 1 i min i max
not yet enabled, the opening time is extended, depending on the 2 ... 8 x n
level of the overcurrent by up to 15 ms. In order to determine the 0,1
break-times of the circuit breakers, approximately 15 ms must
be added to the opening times shown for the arcing time.2)
0,01
Refer to the following legend for tolerances. 0,1 1 10 100
The characteristic curves shown apply to ambient temperatures / n
10000 10000
NSE0_01520
NSE0_01519
R min R max R min R max
Opening time [s]
100 100
10 10
SENTRON 3WL circuit breaker with ETU25B solid-state release, SENTRON 3WL circuit breaker with ETU27B solid-state release,
LSI characteristic curve LSIN characteristic curve
10000 10000
NSE0_01521
NSE0_01523
Opening time [s]
[s]
1000 1000 sd
Opening time
1,25 ... 12 x n
100 100
2
sd = const
g min g max
10 10
SENTRON 3WL circuit breaker with ETU27B solid-state release, SENTRON 3WL circuit breaker with ETU45B solid-state release,
G characteristic curve S characteristic curve
Tolerances for the set currents 1) Sizes I and II: 100 ... 1200 A
L: tripping operations between 1.05 and 1.2 x IR Size III: 400 ... 1200 A.
S: 0 %, +20 % 2) With single-pole loading in the lowest rated current range, the response
I: 0 %, +20 % times of the short-circuit release can be extended by approx. 10 % and
G: 0 %, +20 % the tripping times by approx. 15 % compared to the characteristic curve.
Tolerances for the tripping times
L: 20 %, +0 % for I2t characteristic curve
S: 0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
I: < 50 ms
G: 0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
34 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Every solid-state release type and every setting has its own cha- 10000
NSE0_01525a
racteristic curve. Only a selection is shown in the following. The
characteristic curves each show the largest and smallest setting
NSE0_01526a
10000
NSE0_01522a
10000
Further characteristic curves are shown in the manual and the
NSE0_01524a
1000
Tolerances for the set currents
L: tripping operations between 1.05 and 1.2 IR
100 S: 0 %, +20 %
I: 0 %, +20 %
G: 0 %, +20 %
10
Tolerances for the tripping times
L: 20 %, +0 % for I2t characteristic curve
1 S: 0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
i I: < 50 ms
G: 0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
0,1 1,5 x n ... 0,8 x cs
0,01
1) Sizes I and II: 100 ... 1200 A
0,1 1 10 1 Size III: 400 ... 1200 A.
/ n / cs 2) With single-pole loading in the lowest rated current range, the response
times of the short-circuit release can be extended by approx. 10 % and
SENTRON 3WL circuit breaker with ETU45B and ETU76B solid-state the tripping times by approx. 15 % compared to the characteristic curve.
release, I characteristic curve
Siemens 2009 35
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Dimensional drawings
Voltage transformer for SENTRON 3WL External current transformers for N conductor without copper
277
connection pieces
Size I, 3WL9 111-0AA21-0AA0
6 0
1 6
125
8
R 1 3 ,1
8 ,9
NSE0_01103a
N S E 0 _ 0 1 3 7 5
99
9 6 ,8
2 2
8 1
For mounting on R 2 2
35 mm standard
4 0
mounting rail
1 8 5 1
Current transformers for overload protection in the 3 6
7 0
N conductor 8 3
External current transformers for N conductor with copper Size II, 3WL9 111-0AA22-0AA0
connection pieces
Size I, 3WL9 111-0AA31-0AA0
1 5 4 1 R 2 7
1 3 ,5
1 1 5
1 3 1
5 4
N S E 0 _ 0 1 3 7 6
6 5 ,5
4 4
2 4
8 8 5 1
1 7 0
1 3 0
6 8
9 1
5 1
9 5
1 1 3 3
N S E 0 _ 0 0 6 0 6 b
1 0 7
1 2 3
Size II, 3WL9 111-0AA32-0AA0
N S E 0 _ 0 1 3 7 7
4 5
3 0 3 0 3 1 0
5 0 ,5
3 1
3
1 3 ,5 1 6 0 5 1
1 8 4
4 4
2 4
1 7 0
9 1
6 8
5 1
edge protector
9 0 1 3 1
1 1 3
Size III, 3WL9 111-0AA33-0AA0
3 4 0
3 0 3 0 3 0 3 1 0 5 2
1 3 ,5
2 4 0
4 4
2 4
N S E 0 _ 0 0 1 6 4 c
1 3 0
9 1
6 8
1 7 0
5 1
Door cut-out for operator panel using the door sealing frame
Option with/without door interlocking
N S E 0 _ 0 0 6 0 8 b
3 1 4
1 6 0 1 2 3
1 8 4 3 0 0
1 2 0 4 0
5 ,5 3 )
N S E 0 _ 0 0 6 1 0 c
R 5 R 5
1 8 5
1 4 0
2 )
5 ,5
3 5 0
1 4 0
1 8 0
1 7 5
4 0 1 2 0
1) Mounting surface
2) Center SENTRON 3WL operator panel 1 2
1 1 ,5
1 ) 2 1 4 )
3) 8 mounting holes for door sealing frame
4 0
4) 3 mounting holes for door interlocking
36 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
CubicleBUS module Breaker Data Adapter (BDA)
3WL9 111-0AT2.-0AA0 3WL9 111-0AT28-0AA0
70 86 3WL9 111-0AT33-0AA0
81,9 38
45,5 19
47,5
94
16(B
153
16(B
30
Siemens 2009 37
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Door cut-out for operator panel using protective cover IP55
Protective cover, IP55
400
NSE0_01029c
395
NSE0_01030b
4 x R5
4 x 5,5
85
340-350
72
295-300
72
435
68
70
17
Safety clearances from grounded parts Safety clearances from live parts
Rated operational voltage Above Lateral Rear Rated operational voltage Above Lateral Rear
auxiliary connector (each side) auxiliary connector (each side)
V/AC mm mm mm V/AC mm mm mm
Size I, fixed-mounted version Size I, fixed-mounted version
500 751) 0 0 500 150 20 20
690 751) 0 0 690 300 50 125
Size I, withdrawable version, Size I, withdrawable version,
without arc chute cover without arc chute cover
500 501) 0 0 500 150 20 14
1)
690 50 0 0 690 300 50 14
Size I, withdrawable version, Size I, withdrawable version,
with arc chute cover with arc chute cover
500 0 02) 0 500 14 100 14
690 0 02) 0 690 14 100 14
Size II, fixed-mounted version Size II, fixed-mounted version
500 751) 0 0 500 250 50 20
690 751) 0 0 690 600 100 140
1000 180 0 0 1000 430 100 125
Size II, withdrawable version, Size II, withdrawable version,
without arc chute cover without arc chute cover
500 501) 0 0 500 250 50 14
690 501) 0 0 690 600 100 30
1000 100 0 0 1000 350 100 14
Size II, withdrawable version, Size II, withdrawable version,
with arc chute cover with arc chute cover
500 0 02) 0 500 14 50 14
2)
690 0 0 0 690 14 225 14
Size III, fixed-mounted version Size III, fixed-mounted version
500 751) 0 0 500 75 20 20
690 751) 0 0 690 500 100 125
1000 180 0 0 1000 430 100 125
Size III, withdrawable version, Size III, withdrawable version,
without arc chute cover without arc chute cover
500 501) 0 0 500 50 20 14
690 501) 0 0 690 500 100 14
1000 100 0 0 1000 350 100 14
Size III, withdrawable version, Size III, withdrawable version,
with arc chute cover with arc chute cover
500 0 02) 0 500 14 50 14
2)
690 0 0 0 690 14 200 14
DC non-automatic air circuit breakers 1) Value for plate; 0 mm for struts and grids.
300 45 0 0
600 200 0 0 2) 40 mm (size II: 70 mm) for plates which cover the lateral openings in the
1000 150 0 0 guide frame.
All safety clearances above the circuit breaker refer to the upper
edge of the auxiliary connector - not to the upper edge of the arc
chute! See dimensional drawings on pages 39 to 47, parts 4)
and 5).
38 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size I, up to 1600 A, fixed-mounted version, 3- and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
4) 5) 55 55 55 55
35
NSE0_00611a 4 7
13,5
N S E 0 _ 0 0 6 1 2 c
275
440,5
437,5
3)
NSE00613b
421
11)
e
6
123,5
270 15
300 10
35
60 90 90 90
26
390 c 8 2
d
Front connection (double hole)
according to DIN 43673
13,5
1) 2) 14) 9) 4 7 55 55 55 55
40
60,5
8)
80
33,5
N S E 0 _ 0 0 6 1 5 c 3)
a
NSE00616b
421
541,5
11)
327,5
461,5
516
3)
g
6
a
275
150
5,5
80
f
76
40
14
NSE0_00614e 45 6) c 60 90 90 90
8 2
150 106
210
230 127
Vertical connection
90 90 90 60 1 1 ) 3 5 NSE00619 b
35
55
13,5
11)
6 0
7) 3)
3 0
3)
7)
2 6 7 ,5
N S E 0 _ 0 0 6 1 8 c
M8
1 2 7 ,5
1 1 3 ,5
NSE00617a
139 58 1 3 ,5
320 1 2 8 ,5 60 90 90 90
410
NSE00620
3)
60 90 90 90
Siemens 2009 39
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size I, up to 1600 A, 3- and 4-pole, withdrawable version
Standard version Optional connection variants
Horizontal connection Front connection (single)
320 62,5 3 5 0
270 2 6 0
4) 5)
NSE00622a
NSE0_00621a 5 5 5 5 5 5 5 5
1 3 ,5
3 5
N S E 0 _ 0 0 6 2 3 b
6
275
468,5
403
465,5
1 1 )
3 7 3
3 )
2 8 7
123,5
13 30
6 9
10) c
11
169,5
210 55
300 1 5 9 0 9 0 9 0
3 5
2 6
382,5 Front connection (double hole)
367,5 according to DIN 43673 3 5 0
NSE0_00624c 327 2) 2 6 0
62,5 1 3 ,5 5 5 5 5 5 5 5 5
7) 8)
9)
NSE00625a
9
4 0
8 0
a
519
327,5
3)
460
6
493
a
1 1 )
3 7 3
2 8 7
275
31
N S E 0 _ 0 0 6 2 6 b
150
14
76
10)
34
40
27
6 9
220 45 6)
8 0
4 0
42 58
88,5 c 169,5
1 4
121,5 1 5 9 0 9 0 9 0
140,5
Vertical connection
3 5 0
38
55 55 55 55 2 6 0
11) b
38
13,5 13,5
N S E 0 _ 0 0 6 2 9 a
60
11)
30
NSE00627a
267,5
2 8 7
3 )
127,5
139 68
270 25 NSE00628a 150
320
165
6 9
410
1 5 9 0 9 0 9 0
350 4-pole version
260 2) For guide frame without arc chute cover, arc quenching space facing grounded or
non-conductive surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
3) 6) Dimension to inside surface of the closed cabinet door.
7) SENTRON 3WL in connected position.
287
10) 15 10)
55
90 90 90
40 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size I, up to 1600 A, withdrawable version, 3- and 4-pole
Flange connection
3 5 0
2 6 0
14 5 5 5 5 5 5 5 5
N S E 0 _ 0 0 6 3 2 a
NSE00631
M 1 2
3 3
5 9
2 8 7
2 6
3 )
2 8 2 ,5
5 9
1 4 2 ,5
6 9
121
1 5 9 0 9 0 9 0
Siemens 2009 41
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
4 7 90 90 90 90
35
NSE0_00633a
4) 5) 40 40
N S E 0 _ 0 0 6 3 4 d
275
NSE00635c
437,5
440,5
6
421
11)
e
3)
35
123,5
85 10
270 90 130 130 130 13,5
26
440
570 c 8 2
d
13) 1) 2) Front connection (double hole)
according to DIN 43673
90 90 90 90
12)
40
4 7 40 40
14)
80
N S E 0 _ 0 0 6 3 7 d
a
621
3)
NSE00638c
541,5
421
516
3)
327,5
11)
451,5
461,5
6
g
275
14
5,5
150
80
a
76
40
NSE0_00636e 45
150 6)
210 106 c 8 2
230 127
NSE00641
30
30 30
30
11)
13,5 3) 3)
7) 7)
290
98
9
134,5
35
NSE0_00639f
NSE00642
4-pole version
1) Mounting space for removal of the arc chutes.
2) Arc quenching space, "690 V" circuit breaker facing grounded or non-conductive
3) surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
11) Terminal face.
12) Circuit breaker upper edge, only 1000 V circuit breaker.
90 130 130 130 13) Arc quenching space, 1000 V circuit breaker facing grounded or non-conductive
surfaces.
14) Space for electrical auxiliary circuit connections.
Rated circuit a b c d e f g
breaker
current
A
Up to 2000 10 10 10 11 451 34 541
2500 15 15 20 6 461 39 551
3200/4000 30 30 20 6 461 39 551
For safety clearances to grounded parts and to live parts see
page 38.
For flange connections see following page.
42 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole
Vertical connection 4000 A
1)
2)
30
85 Nm
541,5
461,5
30
13,5
345,5
79,5
NSE0_01868
100
10
4011)
20
142
200 130 200
162
Siemens 2009 43
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 3200 A, withdrawable version, 3- and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
5 3 0
4) 5)
N S E 0 _ 0 0 6 4 5 c
62,5 4 0 0
NSE0_00643b 9 0 9 0
9 0 9 0
NSE00644b
4 0 4 0
3 5
1 3 ,5
275
6
468,5
465,5
403
3 )
1 1 )
3 7 3
2 8 7
123,5
2 6
169,5
11
40
6 9
10) 270 10) 4 5 ,1
350 55 5 5 1 3 0 1 3 0 1 3 0
3 5
480
Front connection (double hole)
382,5 according to DIN 43673
5 3 0
N S E 0 _ 0 0 6 4 8 c
367,5 62,5 4 0 0
1 3 ,5
NSE0_00646f
327 13) 9 0 9 0 9 0 9 0
NSE00647b
2) 4 0 4 0
4 0
12)
8 0
7) 8)
9)
6
493
9 3 )
620
1 1 )
3 7 3
2 8 7
a
518,5
520
327,5
3)
34
460
275
1 4
a
6 9
150
14
8 0
169,5
10)
76
5 5 4 5 1 3 0 1 3 0 1 3 0
4 0
27
31
45
40
220 6)
42 58
88,5
121,5
140,5
4-pole version
30 30 2) For guide frame 690 V, without arc chute cover, arc quenching space facing groun-
ded or non-conductive surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
38
3)
287
69
10) 10)
55 45 130 130 130
44 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 4000 A, withdrawable version, 3- and 4-pole
Vertical connection,
up to 3200 A 5 3 0
4 0 0
11) b
NSE00650a
N S E 0 _ 0 0 6 5 1 a
38
30
30
3 )
2 8 7
290
100
135
6 9
5 5 4 5 1 3 0 1 3 0 1 3 0
157
172
NSE0_01869
109,5
4011) 4,6 10
20
177
197 55 45
200 130 200
Flange connection
5 3 0
NSE00653
4 0 0
M 1 2 9 0
N S E 0 _ 0 0 6 5 4 a
4 0
3 3
2 6
5 9
3 )
2 8 7
2 8 2 ,5
5 9
1 4 2 ,5
6 9
121
4 5 1 3 0 1 3 0 1 3 0
4-pole version
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
11) Terminal face.
For safety clearances to grounded parts and to live parts see
page 38.
For more connection options see previous page.
Siemens 2009 45
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size III, up to 6300 A, fixed-mounted version, 3- and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
4) 5) 47 160 160 160 160
35
NSE0_00655a 50 50
13,5
NSE00656c
3)
NSE00657c
275
437,5
440,5
421
11)
451
26
123,5
130 210 210 210
35
270 205 12 20
11
680 82
890
4 0
12)
14)
8 0
N S E 0 _ 0 0 6 5 9 d
3 )
30
N S E 0 _ 0 0 6 6 0 c
6
621
5 4 1
1 1 )
4 2 1
541,5
516
3)
327,5
451,5
461,5
275
1 4
3 4
5,5
8 0
150
30
76
2 0 1 3 0 2 1 0 2 1 0 2 1 0
4 0
NSE0_00658e 45 8 2
35 150 6)
210 106
230 127
Vertical connection
107 20
30
10
210 210 210 NSE00663
15
35
30 160 15 130
11)
11) 3)
13,5 7) 40
330,5
7) 3)
120
M10
94,5
NSE0_00661e
704 13,5
142
914
162
NSE00664a
3)
4-pole version 13) Arc quenching space, 1000 V circuit breaker facing grounded or
1) Mounting space for removal of the arc chutes. non-conductive surfaces.
2) Arc quenching space, "690 V" circuit breaker facing grounded or 14) Space for electrical auxiliary circuit connections.
non-conductive surfaces. For safety clearances to grounded parts and to live parts see
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the page 38.
system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
11) Terminal face.
12) Circuit breaker upper edge, only 1000 V circuit breaker.
46 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size III, up to 6300 A, withdrawable version, 3- and 4-pole
Standard version Optional connection variants
Horizontal connection up to 5000 A Front connection (single hole),
up to 4000 A 8 4 0
N S E 0 _ 0 0 6 6 7 c
6 3 0
4) 5) 62,5 1 6 0 1 6 0 1 6 0 1 6 0
1 3 ,5
NSE0_00665b
NSE00666b
5 0 5 0
3 5
275
465,5
468,5
6
403
1 1 )
2 8 7
3 7 3
123,5
6 9
800 57 20
8 5 2 1 0 2 1 0 2 1 0
11
169,5
3 5
5 9 0
2 6
5 7 8 0 0
Front connection (double hole)
382,5 according to DIN 43673 up to 8 4 0
N S E 0 _ 0 0 6 7 0 c
367,5 4000 A 6 3 0
1 3 ,5
NSE0_00668d
327 13) 62,5 1 6 0 1 6 0 1 6 0 1 6 0
2) 5 0 5 0
4 0
NSE00669b
12)
8 0
7) 8)
9)
9
6
30
493
1 1 )
2 8 7
3 7 3
620
518,5
520
327,5
3)
460
30
1 4
275
6 9
8 0
150
14
10) 20 8 5 2 1 0 2 1 0 2 1 0
76
4 0
34
169,5 5 9 0
5 7 8 0 0
27
31
45
40
220 6)
42 58
88,5
121,5
140,5
Vertical connection, up to 6300 A
30 8 4 0
38
NSE00672a
30 30 13,5 6 3 0
11) 7 0 4
2 0
1 0
30
38
N S E 0 _ 0 0 6 7 3 b
11)
330,5
NSE00671a
124,5
2 8 7
94,5
139 260 24
270 217 177
6 9
Siemens 2009 47
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size III, up to 6300 A, withdrawable version, 3- and 4-pole
Flange connection, up to 4000 A
8 4 0
NSE00675
6 3 0
7 0 4
N S E 0 _ 0 0 6 7 6 a
1 6 0 1 6 0 1 6 0 1 6 0
1 2
3 3
M
5 9
2 8 7
2 6
2 8 2 ,5
5 9
1 4 2 ,5
5
6 9
3 0
121 5 7 8 5 2 1 0 2 1 0 2 1 0
5 9 0
8 0 0
9 1 4
48 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Schematics
Terminal assignment diagram
14
F1, 2
+ OUT
Trip signalling switch S24 13 /COM16
1 2 3 4 5 6 7 8 9
Open
(position after tripping) 12 (Option F02/F12)
Y1
COM15/COM16 module is at position "-X7".
11
Close
+
8
DPWrite Free
7
Enable
6
5
Signaling contact at the 1 st auxiliary release
External
Internal
4
IN
3
S23 2
Signaling contact at the 2nd auxiliary release
1
14 L+
1st auxiliary release F1 "ST" c
13 L
12
S1 "NO"
11
10
S1 "NC"
9
Closing solenoid 8 L
c
7 L+
6
5
"Ready to close" signal S20
4
S2 "NO"
3
2
S2 "NC"
1
(sw) (br)
Charging motor M 2 L+
c
opt. motor main switch S12 1 L
Siemens 2009 49
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Example of an overall circuit diagram for SENTRON 3WL
(3WL1. .......4GN4Z C11+ C22 + K07) with "UVR" undervoltage release (F3), with "ST" shunt release
(F1), with tripped signal switch (option K07), with auxiliary switch
Manual/motorized operating mechanism with stored-energy fea- 4 NO + 4 NC.
ture with electrical ON button (option C11), with ready-to-close
signaling switch (optionl C22), with LSING solid-state release,
L1 L1
(L+) release (L+)
OFF
contact
ON
-X5.10
-X7.14
-X7.12
-X6.10
-X5.12
-X6.14
-X6.12
-X6.2
-X6.6
-X5.8
-X5.4
-X6.4
-X5.2
-X5.6
-X6.7
-X7.9
5
1
3
-A1 ETU
version L
-S10
S
electr. I
ON
N N
G
R
-S11 -F5
-S20
-S24
-Y1 -T2
mech.
ON
-T3
NSE0_01558b
mech. -S12
-F1
OFF
-X5.9
6
2
4
-X6.1
-X5.7
-X5.3
-X6.9
-X6.13
-X6.3
-X5.5
-X6.11
-X7.13
-X5.11
-X8.9
-X5.1
-X8.10
-X6.8
-X6.5
N N
(L-) (L-)
* Short terminals, if no N sensor
50 Siemens 2009
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Example of the mode of operation of Zone Selective
Interlocking functionality in power distribution
module
module
4 4 4
ZSI
ZSI
ZSI
5 5 5
6 6 6 SENTRON 3WL SENTRON 3WL
3 3
module
module
4
5
6
1
2
3
4
4
ZSI
ZSI
5 ZSI module 5
SENTRON 3WL SENTRON 3WL 6 6
3 3
module
module
4 4
ZSI
ZSI
5 5 NSE0_01898
6 6
SENTRON 3WL
SENTRON 3VL SENTRON 3WL
Connection diagram for a Zone Selective Interlocking functionality with
3 multiple infeed and several outgoing units with SENTRON 3WL circuit
module
4
ZSI
NSE0_01897
breakers
5
6
module
4
5
6
1
2
3
4
4
ZSI
ZSI
5 ZSI module 5
6 6
NSE0_01899
SENTRON 3WL
module
4 4
ZSI
ZSI
5 5
6 6
More information
Up-to-date information on the Internet at:
http://www.siemens.com/sentron
Siemens 2009 51
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
General data
Technical specifications
Size II
Type 3WL12 10 3WL12 20 3WL12 40
Rated current In at 40 C
Main conductor A ... 1000 2000 4000
Rated operational voltage Ue V DC ... 600/1000 ... 600/1000 ... 600/1000
(1000 V version, see Catalog LV 1, order code "A05")
Rated insulation voltage Ui V DC 1000 1000 1000
Rated impulse withstand voltage Uimp
Main current paths kV 12 12 12
Auxiliary circuits kV 4 4 4
Control circuits kV 2.5 2.5 2.5
Isolating function acc. to EN 60947-2 Yes Yes Yes
Permissible ambient temperature
Operation C 25/+75 25/+75 25/+75
Storage C 40/+70 40/+70 40/+70
Permissible load Up to 40 C A 1000 2000 4000
At rear horizontal main circuit Up to 55 C A 1000 2000 3640
connections Up to 60 C A 1000 2000 3500
(Cu painted black) Up to 70 C A 1000 1950 3250
Power loss at In for symmetrical loads
Withdrawable circuit breakers W 280 770 1640
Operating times
Make-time ms 35 35 35
Opening time ms 34 34 34
Electrical make-time (through activation solenoid)1) ms 100 100 100
Electrical opening time (through shunt release) ms 73 73 73
Electrical opening time (instantaneous undervoltage release) ms 73 73 73
Endurance3)
Mechanical (without maintenance) Oper. cycles 10 000 10 000 10 000
Mechanical (with maintenance)2) Oper. cycles 15 000 15 000 15 000
Electrical (without maintenance) Oper. cycles 6000 6000 4000
1000 V version Oper. cycles 1000 1000 1000
Electrical (with maintenance)2) Oper. cycles 15 000 15 000 15 000
Switching frequency
600 V version 1/h 60 60 60
1000 V version 1/h 20 20 20
h m a x .
Mounting position 3 0 3 0 3 0 3 0
= 1 m m
and/
or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a
Degree of protection IP20 without cabinet door, IP41 with door sealing
frame, IP55 with cover
Auxiliary conductors (Cu) Standard connection = strain-relief clamp
Max. number of Without end sleeve 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14)
auxiliary conductors With end sleeve acc. to DIN 46228 Part 2 1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16)
cross-section With twin end sleeve 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
(solid/stranded)
Optional connection = tension spring
Without end sleeve 2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14)
With end sleeve acc. to DIN 46228 Part 2 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
Weights 3-pole Fixed-mounted circuit breakers kg 56 56 64
Withdrawable circuit breakers kg 60 60 68
Guide frames kg 31 31 45
4-pole Fixed-mounted circuit breakers kg 67 67 77
Withdrawable circuit breakers kg 72 72 82
Guide frames kg 37 37 54
1) Make-time through activation solenoid for synchronization purposes 2) Maintenance means: replace main contact elements and arc chutes (see
(short-time excited) 50 ms. Operating Manual).
3) Further technical specifications on request.
Size II
Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC Icc kA 35
Up to 300 V DC Icc kA 30
Up to 600 V DC Icc kA 25
Up to 1000 V DC Icc kA 20
Rated short-time withstand current Icw
0.5 s kA --
1s kA 351)/302)/253)/204)
2s kA --
3s kA --
1) At Ue = 220 V DC. 3) At Ue = 600 V DC.
2) At Ue = 300 V DC. 4) At Ue = 1000 V DC.
52 Siemens 2009
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Characteristic curves
10000
R= 0.4 ... 1.0 n
R= 2 ... 10 s at 6 R
[s]
R= 10 s [B]
100 B
2 s [A]
B
A
A
10
1
MIN MAX
I= 1.5
I=1.25 I=
4 n
R
R
NSE0_01578
0,1
0,01
0,1 1 10
/ n
Dimensional drawings
DIGmat S100
257
DIG S100 3,5
250
AUTO
ON
_
136
R2 + MENUE
NSE0_01576
R1
115
122
NSE0_01575
AUTO MAIN
MAN PEAK DIAG
271
Siemens 2009 53
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
4 7 90 90 90 90
35
NSE0_00633a
4) 5) 40 40
N S E 0 _ 0 0 6 3 4 d
275
NSE00635c
437,5
440,5
6
421
11)
e
3)
35
123,5
85 10
270 90 130 130 130 13,5
26
440
570 c 8 2
d
Front connection (double hole)
16) 17) 1) 2) according to DIN 43673
12) 90 90 90 90
40
15) 4 7 40 40
14)
80
N S E 0 _ 0 0 6 3 7 d
a
3)
602
NSE00638c
541,5
421
3)
516
327,5
11)
451,5
461,5
6
447
g
275
14
5,5
150
80
a
76
40
NSE0_02003 45
150 6)
210 106 c 8 2
230 127
Vertical connection
13,5
NSE00641
30
30 30
30
11)
13,5 3) 3)
7) 7)
290
98
9
134,5
35
NSE0_00639f
NSE00642
4-pole version
1) Mounting space for removal of the arc chutes.
2) Arc quenching space, "690 V" circuit breaker facing grounded or non-conductive
3) surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
11) Terminal face.
12) Circuit breaker upper edge, only 1000 V circuit breaker.
90 130 130 130 14) Space for electrical auxiliary circuit connections.
15) Arc quenching space, 300 V circuit breaker facing grounded or non-conductive
surfaces.
16) Arc quenching space, 600 V circuit breaker facing grounded or non-conductive
surfaces.
17) Arc quenching space, 1000 V circuit breaker (with high arc chute) facing grounded or
non-conductive surfaces.
For safety clearances to grounded parts and to live parts see
Rated circuit a b c d e f g page 38.
breaker
current
A
Up to 2000 10 10 10 11 451 34 541
4000 30 30 20 6 461 39 551
54 Siemens 2009
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Size II, up to 4000 A, withdrawable version, 3- and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
5 3 0
4) 5)
N S E 0 _ 0 0 6 4 5 c
62,5 4 0 0
NSE0_00643b 9 0 9 0
9 0 9 0
NSE00644b
4 0 4 0
3 5
1 3 ,5
275 6
468,5
465,5
403
3 )
1 1 )
3 7 3
2 8 7
123,5
2 6
169,5
11
40
6 9
10) 270 10) 4 5 ,1
350 55 5 5 1 3 0 1 3 0 1 3 0
3 5
480
Front connection (double hole)
382,5 according to DIN 43673
5 3 0
N S E 0 _ 0 0 6 4 8 c
367,5 62,5 4 0 0
1 3 ,5
327 16) 17) 9 0 9 0 9 0 9 0
NSE00647b
NSE0_02084 2) 4 0 4 0
4 0
15)
8 0
12)
7) 8) 6
493
9) 3 )
9
1 1 )
3 7 3
2 8 7
651
34
518,5
a
520
327,5
3)
496
460
1 4
c
6 9
275
8 0
169,5
a
150
14
10) 5 5 4 5 1 3 0 1 3 0 1 3 0
4 0
76
27
31
45
40
220 6)
42 58
88,5
121,5
140,5
4-pole version
30 30 2) For guide frame 690 V, without arc chute cover, arc quenching space facing groun-
ded or non-conductive surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
38
17) Arc quenching space, 1000 V circuit breaker (with high arc chute) facing grounded or
non-conductive surfaces.
3)
287
69
10) 10)
55 45 130 130 130
Siemens 2009 55
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Size II, up to 4000 A, withdrawable version, 3- and 4-pole
Vertical connection
5 3 0
11) 4 0 0
NSE00650a
38 b N S E 0 _ 0 0 6 5 1 a
30
30
3 )
2 8 7
290
100
135
6 9
157 5 5 4 5 1 3 0 1 3 0 1 3 0
172
Flange connection
5 3 0
NSE00653
4 0 0
M 1 2 9 0
N S E 0 _ 0 0 6 5 4 a
4 0
3 3
2 6
5 9
3 )
2 8 7
2 8 2 ,5
5 9
1 4 2 ,5
6 9
121
4 5 1 3 0 1 3 0 1 3 0
4-pole version
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
11) Terminal face.
For safety clearances to grounded parts and to live parts see
page 38.
For more connection options see previous page.
56 Siemens 2009
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Schematics
L1
AC230
+
N
PE -
DC24
AC230
12
14
-K1 11 -Q01 1 3 5
Excitation / Alarm
Automatic / Reset
-X6.14 -X5.12
12 14
SENTRON
3WL
-K2 11 -F1 -F3
NSE0_01577a
-X6.13 -X5.11
-Q01 2 4 6
Application examples
Rated operational Required series For 3-pole non-automatic air circuit brea- For 4-pole non-automatic air circuit breakers
voltage breaks at rated voltage kers (operational currents up to 4000 A/conducting path)
(operational currents up to 4000 A/
conducting path)
Up to 300 V + 10 %
The connection to the circuit breakers is not dependent on direc- current. If the parallel or series connection is made at a distance
tion and polarity; the circuit diagrams can be adapted of 1 m from the connecting bars, the circuit breaker can be used
accordingly. at full operational current load.
If the parallel or series connections are made directly to the
connecting bars, for thermal reasons the continuous load on the
] Grounded-neutral system
circuit breakers must only be 80 % of the permissible operational Load
Siemens 2009 57
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)