GENERAL NOTES:

(1) DO NOT SCALE FROM THE DRAWINGS.


(2) ALL DIMENSIONS ARE IN METERS AND LEVELS ARE IN METERS UNLESS
NOTED OTHERWISE. ALL DIMENSIONS TO BE VERIFIED ON SITE &
APPROVED BY THE ENGINEER.
(3) ALL DRAWINGS SHOULD BE READ IN CONJUNCTION WITH OTHER
RELEVANT ARCHITECTURAL, STRUCTURAL,MECHANICAL AND ELECTRICAL
DRAWINGS AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS. ANY
DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT AND RESOLVED BEFORE COMMENCEMENT OF ANY WORK.

KEY PLAN

03 07 10 12
01
02 04 05 06 08 09 11

657
L01 650

651
L01 681A L01 681B

L01 681C L01 681D


L01 655

664A
664B

L01 674
L01 639 647

ROAD LEVEL

Rev. Date Description By CHK.


PROJECT:



DUBAI

CLIENT:

SEED COMMENTS:
MINIMUM 50 PA.
SEED COMMENTS:
FRESH AIR INTAKE SAND
TRAP LOUVERS PROJECT MANAGEMENT CONSULTANT:

SERVICE CONSULTANT:

P.O.Box 119146, Dubai, United Arab Emirates.


Tel: +971-4-2564882, Fax: +971-4-2564883,
web: www.seedengineering.com
DUBAI, KOCHI, BANGALORE

MAIN CONTRACTOR:

DRAWING TITLE:

SEED COMMENTS: SEED COMMENTS:


ONLY FURTHEST UNIT CHECK THE LENGTH
MECHANICAL EQUIPMENT SCHEDULE
PRESSURE DROP TO BE SEED COMMENTS:
CONSIDERED. IT CANNOT BE ASSUMED
SEED COMMENTS: SEED COMMENTS: Project No. Size: Scale: Rev:
SINCE IT IS MAJOR FACTOR PU 1713D A1 1:50 01
SOUND ATTENUATOR TO BE QTY. ONLY THE FURTHEST CONTRIBUTING TO THE Drawn: Checked: Approved: Date:
SEED COMMENTS: ADDED. UNIT PRESSURE DROP TO STATIC PRESSURE. PLEASE KA DD 21 JUN. 2017
ADD FAHU UNIT PRESSURE BE CONSIDERED. Drawing No.:
DROP AS SEPERATE PROVIDE AS PER THE
SEED COMMENTS: ACTUAL SELECTIONS. PU1713D-MEC-900
INTERNAL PRESSURE DROP
OF FAN,FILTERS ,
ELECTROSTATIC
PRECIPATOR TO BE ADDED.
TOTAL PRESSURE DROP
SHOULD BE 1000 PA- 1200
PA.