You are on page 1of 5

Applied Thermal Engineering 31 (2011) 3653e3657

Contents lists available at ScienceDirect

Applied Thermal Engineering


journal homepage: www.elsevier.com/locate/apthermeng

A museum storeroom air-conditioning system employing the temperature


and humidity independent control device in the cooling coil
X.J. Zhang a, C.Y. Yu a, S. Li a, Y.M. Zheng b, F. Xiao c, *
a
Institute of Refrigeration and Cryogenics, Zhejiang University, Hangzhou 310027, China
b
Zhejiang Provincial Museum, Hangzhou 310007, China
c
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong

a r t i c l e i n f o a b s t r a c t

Article history: For conservation of cultural heritage, HVAC systems are often necessary for museums to maintain
Received 11 October 2010 suitable indoor environment with precise control of indoor thermal-hygrometric parameters and air
Accepted 21 December 2010 velocity. Large deviations of these parameters from the design values should be prevented, because they
Available online 30 December 2010
may cause degradation of artworks. So, more energy consumption is inevitable.
This paper presents a novel temperature and humidity independent control (THIC) device and its
Keywords:
associated control method in a museum storeroom air-conditioning system. Compared with the
HVAC
conventional HVAC system with the cooling coil (CC), where the apparatus dew point is usually xed, this
Cooling coil
Temperature and humidity independent
system adopting the THIC device can achieve independent temperature and humidity control in an
control (THIC) energy saving way. The experiment study shows that this system can reduce the energy consumption by
Energy saving 21.7%, compared with the conventional HVAC systems using reheat and humidify for an indoor thermal-
hygrometric environment, and the temperature and humidity in the storeroom are also kept stable and
at a higher precision level.
2010 Elsevier Ltd. All rights reserved.

1. Introduction guarantee both the temperature and the humidity ratio are lower
than the supply air parameters, and then results in much more
Conservation of artworks requires precise control of the indoor energy compensation for reheating and re-humidifying. To reduce
microclimatic conditions. Thus, a suitable HVAC system with reli- that compensation, it is necessary for the CC to reduce the over-
able control is often necessary for a museum, to maintain acceptable cooling capacity, so the temperature and humidity independent
indoor thermal-hygrometric parameters and air velocity and also to control (THIC) technique has been studied in many literatures.
minimize the deviations of these parameters from the design values. Generally, substituting desiccant dehumidication for cooling
So it is indispensable for the museum air-conditioning system to dehumidication in the CC, the THIC technique uses solid desic-
comprise heating, humidifying, cooling, dehumidifying and auto- cants [6e8] or liquid desiccants [3,9e11]. But how to realize inde-
matic control units to control the temperature and humidity at the pendent control of temperature and humidity in the same cooling
same time. Considering that the HVAC system in museum always coil in HVAC system is a worthwhile problem, and there are few
has to be operated continually during all the year and 24 h per literatures about this THIC technique.
day, a suitable technique is necessary to obtain considerable In this paper, an HVAC system employing the THIC device in the
energy saving [1], however, guaranteeing a good indoor thermal- CC is proposed and designed. With the PID split-range control, only
hygrometric microclimate. It is shown by some literatures [2e5] that one of the two air thermal-hygrometric parameters after CC, i.e.
the energy consumption will be reduced by about 10e50%, if the temperature or humidity ratio, is to be controlled below the supply
HVAC system adopts a suitable energy-saving technique. air, in order to make the over-cooling capacity as little as possible.
For conventional HVAC system, customarily, the dew point And some experiment tests were done to validate the THIC device.
temperature is xed on the cooling coil (CC) in the air-handling
process, which makes the air after the CC be over-cooling to
2. THIC device

* Corresponding author. Tel./fax: 86 852 27664194.


The THIC device presented in this paper can be used in the CC
E-mail addresses: xuejzhang@zju.edu.cn (X.J. Zhang), befx@polyu.edu.hk of both existing and new conventional HVAC systems, as shown
(F. Xiao). in Fig. 1.

1359-4311/$ e see front matter 2010 Elsevier Ltd. All rights reserved.
doi:10.1016/j.applthermaleng.2010.12.031
3654 X.J. Zhang et al. / Applied Thermal Engineering 31 (2011) 3653e3657

to from
Nomenclature CC CC THIC
Device
mw,3,T w,1
Cp constant pressure specic heat (kJ/kg K) mw,4,T w,1
h enthalpy (kJ/kg)
3
L latent heat of vaporization (kJ/kg) 4
m mass ow rate (kg/s) mw,T w,1 signal from T-PID
5
Q heat load (kW) 2 mw,2,T w,2 signal from RH-PID
T temperature (K)
1
u air humidity ratio (kg/kg) mw,1,T w

Subscripts from to
CCP CCP
a moist air
l latent heat Fig. 2. Schematic diagram of the THIC device in the CC (1 Three-way valve 1#; 2
i indoor air; inlet Pump; 3 CTV 1#; 4 Three-way valve 2#; 5 CTV 2#).
o outlet
s supply air; sensible heat
w chilled water For satisfying different thermal-hygrometric loads of different
seasons, the system is controlled by two split-range PID condi-
tioners. As shown in Fig. 2, the PID conditioner for temperature
(named as T-PID) controls the CTV 1# and the heater, while the PID
Fig. 2 shows the schematic diagram of the THIC device. For conditioner for relative humidity (named as RH-PID) controls the
temperature control, the CC adjusts the mass ow rate of the CTV 2# and the humidier. The two PID conditioner work together
chilled water according to the sensible cooling load; and for to decide how the CC, the heater and the humidier works, as
humidity control, it adjusts the temperature of the chilled water shown in Figs. 3 and 4.
according to the dehumidication load, or the latent load. Before As shown in Fig. 3, when the T-PID signal for temperature
and after the CC, an electric controllable three-way valve (CTV) increases from 0.0 to 0.5, the signal for CTV 1# which represents
is installed respectively. The CTV 1# adjusts the mass ow rate of the mass ow rate of the chilled water decreases from 1.0 to 0.2,
the chilled water through the CC to control the leaving air while the signal for heater remains at zero; and when the T-PID
temperature so that the sensible load is handled. The CTV signal increases from 0.5 to 1.0, the signal for CTV 1# remains at 0.2
2# adjusts the ow rate of the recirculated water that leaves the which guarantees the minimum ow rate of chilled water going
CC and then returns to mix with the chilled water entering the CC. through CC, while the signal for heater increases from 0.0 to 1.0. So,
In this way, the apparatus dew point of the CC can be regulated generally, with the increase of the value of T-PID signal for
and therefore the leaving air humidity can be controlled sepa- temperature, the outlet air temperature of AHU increases.
rately. In this device, the total mass ow rate of the chilled water Similarly, in Fig. 4, the outlet air relative humidity of AHU
(mw mw,1 mw,2 mw,3 mw,4) is determined by the pump, and increases, when the value of RH-PID signal for relative humidity
the supply water temperature (Tw) is determined by the central increases. To avoid sending back all of the recirculated water that
chilling plant (CCP). Both of them can be considered as constants. leaves the CC, the signal for CTV 2# remains at 0.8 when the RH-PID
The mw,1 and mw,2 is determined by the CTV 2#, while the mw,3 signal increases from 0.5 to 1.0.
and mw,4 is determined by the CTV 1#.
The energy conservation Eq. (1) shows that the mixed temper- 3. Experiment setup
ature Tw,1 is determined by mw,1 and mw,2, which is controlled by the
CTV 2# only. And the ow rate mw,3 of the chilled water into the CC An HVAC system employing the TIHC device was manufactured
is only controlled by CTV 1#. Thus the system controls the and installed to air-condition a museum storeroom, the main
temperature and humidity independently. parameters are listed in Table 1. It comprises the following
 subsystems: (1) AHU with a CC, a heater, a humidier and a constant
Tw;1 Tw $mw;1 Tw;2 $mw;2 mw (1) ow rate fan, and the details of the CC are listed in Table 2; (2) Air

a Conventional system b THIC system


Cooling
Cooling Heater Humidifier
Heater Humidifier Coil
Coil Fan
Fan

AHU AHU

THIC
Device
Central PID RH PID RH
Chilling PID T PID T
Plant
Storeroom Central Storeroom
Chilling
Plant

Fig. 1. Comparison of the conventional and THIC system.


X.J. Zhang et al. / Applied Thermal Engineering 31 (2011) 3653e3657 3655

distribution duct system; (3) A storeroom (22 m  16 m  4 m)


1.0 Signal for CTV 1# 1.0
equipped with the HVAC system in order to maintain the suitable
Signal for the heater thermal-hygrometric parameters for cultural heritage conserva-
0.8 0.8 tion; (4) Temperature and relative humidity sensors (VAISALA

Signal for the heater


Sig nal f or CTV 1#

HMW 40); (5) Data acquisition and monitoring system (Advantech


0.6 0.6 ADAM-4018 and PC).
This system was also operated under different heat loads to
0.4 0.4 show the effects of the THIC device. And to investigate the energy
saving effects of the THIC device, a comparison between the
0.2 0.2 conventional and THIC systems was done under the same indoor
and working conditions.
0.0 0.0
4. Results and discussion
0.0 0.2 0.4 0.6 0.8 1.0
T-PID signal for temperature
Table 3 shows the experimental results of 5 cases under
Fig. 3. T-PID signal for temperature in the split-range control process. different indoor heat loads but the same temperature and relative
humidity of the storeroom (22  C, 60%). When the storeroom
temperature and relative humidity was xed, the parameters of the
supply air should be adjusted along with the change of storeroom
heat load. The working conditions are listed as follows:
1.0 Signal for CTV 2# 1.0
Objective temperature and relative humidity of the storeroom: 22  C, 60%
Signal for the humidifier
Ambient temperature and relative humidity: 25  C, 76%
Signal for the humidifier

0.8 0.8 Flow rate of water pump: 20,000 kg/h


Signal for C TV 2#

Flow rate of air: 7000 kg/h


0.6 0.6
The cooling load of the storeroom (Qindoor) is the sum of the
0.4 0.4 sensible and latent heat loads (Qs and Ql), and can be calculated by
the following Equations.
0.2 0.2
Qindoor Qs Ql ma $hi  hs (2)

0.0 0.0
Qs ma $Cp $Ti  Ts (3)
0.0 0.2 0.4 0.6 0.8 1.0
RH-PID signal for relative humidity Ql ma $L$ui  us (4)

Fig. 4. RH-PID signal for relative humidity in the split-range control process. where Qs is the sensible heat load (kW); Ql is the latent heat load
(kW); h is the air enthalpy (kJ/kg); ma is the air ow rate (kg/s); T is
the air dry bulb temperature (K); u is the air humidity ratio (kg/kg);
L is the heat of vaporization for water and assumed constant at the
value for standard conditions (2452 kJ/kg).
Table 1
In case 1, Fig. 5 shows that when the system achieved the
Systematic parameters.
stable state, both the temperature and the relative humidity of
No. Parameter Value the storeroom were kept in an acceptable uctuant range about
1 Rated power of the heater 17.5 kW the set points (22  C and 60%), from 21.9  C to 22.1  C, and from
2 Rated power of the humidier 18 kW 59.3% to 61.1%, respectively. It also shows that the water inlet
3 Rated ow rate of the chilled water pump 25 m3/h
4 Rated power of the chilled water pump 4 kW
temperature matches the room humidity very well; with the
5 Rated power of the fan 7.5 kW water inlet temperature increases, the room relative humidity
increases, vice versa. So it is concluded that the room humidity is

Table 3
Experimental tests under different indoor heat loads.
Table 2
CC details. Case 1 2 3 4 5
Average storerooms T and RH 22  C 22  C 22  C 22  C 22  C
No. Parameter Value
60% 60% 60% 60% 60%
1 Duct (Length  Width  Height) 1269.5 mm  250 mm  825.5 mm Average supply airs T and RH 18.1  C 19.0  C 13.9  C 22.9  C 22.9  C
2 Number of rows 8 74.2% 69.0% 98.3% 57.6% 57.6%
3 Number of tubes 26 Sensible heat load Qs (kW) 8.81 8.17 16.93 2.49 2.49
4 Outside diameter of tube 12.7 mm Latent heat load Ql (kW) 1.38 2.12 0.76 0.67 0.67
5 Inside diameter of tube 12.0 mm Chilled water from the CCP 9.0  C 9.0  C 9.0  C 9.0  C B
6 Center distance of tube 31.8 mm Signal of T-PID 0.69 0.79 0.38 0.98 0.53
7 Number of ns 500 Signal of RH-PID 0.48 0.44 0.52 0.54 0.52
8 Distance of individual ns 2.5 mm Oneoff state of Heater C C B C C
9 Thickness of n 0.115 mm Oneoff state of Humidier B B C C C
10 Material of tube Copper
11 Material of n Aluminum Notes: C means on; B means off; e means the storeroom is to be heated or
humidied.
3656 X.J. Zhang et al. / Applied Thermal Engineering 31 (2011) 3653e3657

30 70 25.0
Room temperature
Room humidity
25 Water temperature at CC inlet 20.0
65

Energy consumption / kW
Relative humidity
Tmeperat ure / C
o

20
15.0
60 THIC system: QCC Qheater
15 Conv. system: QCC Qheater Qdihumidifier
10.0
55
10
5.0
5 50
0 10 20 30 40 50 60 70 80 90 100 110
Time /min 0.0
0 10 20 30 40 50 60 70 80 90 100 110
Fig. 5. The temperature and humidity of the air-conditioned storeroom and the Time / min
corresponding water temperature at CC inlet.
Fig. 6. Energy consumptions of the conventional and THIC systems.

regulated by the water inlet temperature independently, and also


However, in case 3, where the Qs has a larger increase and the Ql
the THIC device can guarantee both the temperature and the
has a large decrease, as so called high temperature low humidity
relative humidity of the air-conditioned storeroom stable and also
condition, the humidier turns on while the heater turns off. Also,
at a higher precision level.
only two equipments (the CC and the humidier) work together in
QCC mw $Cpw $To  Ti this case, where the CC controls the supply air temperature, and the
humidier controls the supply air humidity. In this case, the THIC
Qheater Qhumidifier Qindoor Qoutdoor (5)
system can save energy by about 29.2%.
In this case, the average heat exchange rate of the CC (QCC) is In case 4, where both Qs and Ql decrease below 0, maybe in the
about 17.3 kW, which is calculated from the inlet and outlet water winter, as so called low temperature low humidity condition, both
temperatures and the water ow rate of the CC, as shown in Eq. (5). heater and humidier turn on. And the THIC system can save energy
The heating rate of the heater (Qheater) measured is about 6.1 kW. by about 22.5%. It is necessary to reduce the cooling rate of the CC,
The humidier does not work yet, i.e. Qhumidier 0 kW. That is to even to turn off the CCP and the water pump, as shown in case 5.
say, the CC and the heater, except the humidier, work together to In summary, with PID split-range control, the THIC system can
control the thermal-hygrometric parameter. So, the THIC device make the CC control one of the two thermal-hygrometric param-
with the PID split-range control can regulate one of thermal- eters, and the rest one is controlled by heater or humidier, when
hygrometric parameters, the relative humidity, and the other one, cooling or dehumidication is needed; and when cooling and
the temperature, is controlled by the heater independently. The dehumidication is not needed, the THIC device make the heater
indoor heat load of the storeroom (Qindoor) is 10.2 kW, which is the and humidier work together, but the CCP turn off. Anyway,
sum of Qs and Ql in Table 3. And then the heat load from the outdoor compared with the conventional system, the THIC system can only
air (Qoutdoor) is 1.0 kW, calculated from Eq. (5). appoint two of the three equipments (the CC, the heater and the
Also in case 1, in order to check the energy saving effect of humidier) to work together to maintain suitable indoor thermal-
the THIC system, a comparison of the energy consumptions hygrometric parameters, and also ensure only one of the two air
between the conventional and THIC system was carried out under thermal-hygrometric parameters after CC would be excessive, and
the same working condition, as shown in Fig. 6. In the conventional then the over-cooling capacity of the CC would be little as possible.
system, the heat exchange rate of the CC (QCC) is about 22.6 kW, the So, the temperature and humidity are always controlled by one of
heating rate (Qheater) is about 8.74 kW, and the humidier power the two individual components independently.
(Qdihumidier) is about 2.5 kW. All of them are higher than 17.3 kW,
6.1 kW, and 0 kW in the THIC system, respectively. The total energy 5. Conclusions
consumption can be calculated by
For saving energy of the HVAC system, a temperature and
Qtotal QCC =COP Qheater Qhumidifier Qfan Qpump (6)
humidity independent control (THIC) device is proposed in this
where the COP is the coefcient of performance of the chiller. paper, and the THIC device is implemented in a real HVAC system
Making a denite integral during the test 105 min, the total energy for a museum storeroom. Through the experiment and analysis,
consumption of the conventional and THIC system is about some conclusions can be drawn as follows:
53.4 kWh and 41.8 kWh, respectively. Seen from this, the THIC
system can save energy by about 21.7%. So, it is considerable that (1) The THIC system can guarantee both the temperature and the
the HVAC system in museum should adopt the THIC device to save relative humidity of the conditioned storeroom are at a higher
running cost for a long continuous operation during all the year and precision level under different working conditions.
24 h per day. (2) The THIC device ensures that only two of the CC, the heater and
Case 2 is similar to Case 1, the humidier still does not work yet, the humidier work together to maintain the suitable indoor
although the Qs decreases, and the Ql increases, resulting in the thermal-hygrometric parameters, and the temperature and
increase of the signal value of T-PID and the decrease of that of humidity are always controlled by one of the two individual
RH-PID. In this case, the THIC system can save energy by about 21.6%. components independently.
X.J. Zhang et al. / Applied Thermal Engineering 31 (2011) 3653e3657 3657

(3) Comparing to the conventional system, the THIC system can [3] Y. Li, H. Yang, Investigation on solar desiccant dehumidication process for
energy conservation of central air-conditioning systems, Applied Thermal
save running energy consumption by about 20e30%, with the
Engineering 28 (10) (2008) 1118e1126.
additional cost of two CTVs. So for a long-time running HVAC [4] A. Nguyen, Y. Kim, Y. Shin, Experimental study of sensible heat recovery of
system used in museum, the THIC device is recommended. heat pump during heating and ventilation, International Journal of Refriger-
ation 28 (2) (2005) 242e252.
[5] K. Zhong, Y.M. Kang, Applicability of air-to-air heat recovery ventilators in
Acknowledgements China, Applied Thermal Engineering 29 (5e6) (2009) 830e840.
[6] K. Ghali, Energy savings potential of a hybrid desiccant dehumidication air
conditioning system in Beirut, Energy Conversion and Management 49 (11)
The research work presented in this paper was supported by
(2008) 3387e3390.
a research grant (A-PJ13) in the Hong Kong Polytechnic University, [7] P. Mazzei, F. Minichiello, D. Palma, Desiccant HVAC systems for commercial
the Major State Basic Research Development Program of China (973 buildings, Applied Thermal Engineering 22 (5) (2002) 545e560.
Program) under contract No. 2011CB706501, and the third batch [8] N. Subramanyam, M.P. Maiya, S.S. Murthy, Application of desiccant wheel to
control humidity in air-conditioning systems, Applied Thermal Engineering 24
subsidies of the Zhejiang provincial cultural relic protection in 2008 (17e18) (2004) 2777e2788.
(No. 614841). [9] X.H. Liu, Z. Li, Y. Jiang, B.R. Lin, Annual performance of liquid desiccant based
independent humidity control HVAC system, Applied Thermal Engineering 26
(2006) 1198e1207.
References [10] B.S. Mohan, M.P. Maiya, S. Tiwari, Performance characterization of liquid
desiccant columns for a hybrid air-conditioner, Applied Thermal Engineering
[1] T. Hartman, Library and museum HVAC: new technologies/new opportunities, 28 (2008) 1342e1355.
part 1, HPAC Engineering 4 (1996) 57e60. [11] W.F. Zhu, Z.J. Li, S. Liu, S.Q. Liu, Y. Jiang, In situ performance of independent
[2] F. Ascione, L. Bellia, A. Capozzoli, F. Minichiello, Energy saving strategies in air- humidity control air-conditioning system driven by heat pumps, Energy and
conditioning for museums, Applied Thermal Engineering 29 (4) (2009) 676e686. Buildings 42 (10) (2010) 1747e1752.

You might also like