Professional Documents
Culture Documents
TEST NO 1 2 3 4 5 6
Gauge Evaporator Pressure Pe (KN/m2) -70 -70 -70 -72 -68 -65
Evaporator Temperature T5 ( C) 11 12 12 13 13 13
Condenser Temp T6 ( C) 36 37 38 38 42 47
Compressor Power Input W (watts) 235 235 235 235 235 235
Compressor Pressure Ratio (Pc/Pe) 5.7877 5.9473 6.1069 6.5915 5.9805 5.8170
Heat Transfer in Evaporator (Qc) 1985.5 1881.0 1776.5 1672.0 1672.0 1672.0
Heat Transfer in Condenser (Qc) 209 209 209 313.5 418 418
Qc = mc cp (t1-t5)
Qc = 25.0 x 10-3 x 4.18 x 103 x (30-11) K
.
Qc = 1985.5 W
T T
TLMTD = Ti e
T e
Tinlet = 30 11
= 19 K
Toutlet = 27 11
= 16 K
TLMTD = 9
= 17.457 K
. W
= . .
Qc = mc cp (t3-t4)
Qc = 25.0 x 10-3 x 4.18 x 103 x (29-27) K
.
Qc = 209 W
T T
TLMTD = Ti e
T e
Tinlet = 36 27
=9K
Toutlet = 36 29
=7K
TLMTD = 9
= 7.958 K
U=
A T T
W
=
. .
Pe = -70
= -70 + 101.325
= 31.325
1 bar = 100
P absolute = 31.325
N
.
=
= 0.3133 bar
Pc = 80
= 80 + 101.325
= 181.325
1 bar = 100
P absolute = 181.325
N
.
=
= 1.8133 bar
Compressor Pressure Ratio:
.
= .
=5.7877
* For the find the value of enthalpy (h), refer to FORANE 141b graph [Absolute pressure (bar)
vs Enthalpy ( )]
Evaporator Temperature:
COP = w
= 8.077
DISCUSSION
The experiments of Refrigeration Cycle was running due to observe the process occur
inside the refrigeration cycle unit as well as understanding the principle of operation to
determine value of parameters for flow rate, temperature, pressure and another several values
that shown in Table 1. The experiment was running for 5 different set of test due to different
set of absolute condenser pressure by adjusting the control valve of condenser to vary the flow
rate. The flow rate required were 50 g/s, 30 g/s, 25 g/s, 20g/s and 10 g/s and the readings was
recorded at every 10 minutes.
Based on the result that obtained through operating this equipment can see that the
temperature of condenser of water inlet temperature is differing from the temperature of the
condenser water outlet. In the meantime, the evaporator water inlet temperature is higher
compared to the outlet of the evaporator water. Therefore, we can determine that the condenser
water outlet temperature is increase because heat transfers occur between the water inside the
evaporator and the condenser.
From the result obtained, that the test No.1 give the highest coefficient of performance
(COP) value than others. The value is 8.077 at condenser water flow rate 50 g/s. The higher
value of COP means more efficient the performance. The test No.1 until No.5 used different
condenser water flow rate but same evaporator water flow rate. So, by changing the condenser
water flow rate it will affect the others parameter values. With this increasing condenser water
flow rate, the values of the coefficient of performance COP will decrease. With small value of
water flow rate, it absorbs less heat that has been rejected at constant pressure in the condenser
part.
From the data, it also can see that by let the evaporator water flow rate flow at constant
value, the temperature inlet higher than the outlet. This is because of the heat enter the
evaporator part to be cooled. The temperature different between the inlet and the outlet, were
used to calculate the total heat transfer that occur in the evaporator part.
At different condenser water flow rate value, the values of the inlet temperature lower
than the outlet temperature. This is because of the heat rejected at constant pressure and the
water absorbs the heat rejected.
All these temperature values affect the refrigeration rate and the condenser heat output.
The heat that entering the evaporator part then go to the expansion valve where the temperature
decrease due to the expansion conduct heat. Then the heat entering the condenser part where the
pressure drops caused by the expansion that brings the refrigerant into vapour of liquid mixture
region. The heat then cooled and these affect the condenser heat output.
The compressor pressure ratio for the test No.4 is higher than others. This is because
value of the absolute condenser pressure higher and the absolute evaporator pressure lower.
When plot the p-h diagram, all these value are used to determine the enthalpy and then calculate
the coefficient of performance (COP) value. The higher compressor pressure ratio give more
pressure different between the condensers than the evaporator parts.
The overall heat transfer coefficient between R141b and water in the evaporator and
condenser is determined by using the inlet and the outlet temperature value for both parts with
the given area and the calculated heat transfer. So, overall heat transfer coefficient can be
determined.
For the evaporator part, the overall heat transfer coefficient values were increasing and
almost constant for the entire test because using the water flow rate constant when running this
experiment. Meanwhile for the condenser part, the overall heat transfer coefficient different each
others because of the condenser water flow rate values didnt constant. Different flows of water
give different heat transfer value. The more water flow in the condenser, the more heat will
absorb
CONCLUSION
The recommendation for this experiment are allowing the system to run with another
percent value of flow rate of water, set the cooling water flow rate at more than 1.0 LPM and
allowing the system to run more than 15 minutes as to obtain more accurate reading. For the
evaporator part, the overall heat transfer coefficient values were increasing and almost constant
for the entire test because using the water flow rate constant when running this experiment.
Meanwhile for the condenser part, the overall heat transfer coefficient different each others
because of the condenser water flow rate values didnt constant. Different flows of water give
different heat transfer value. Thus, the more water flow in the condenser, the more heat will be
absorbed.
The refrigeration cycle demonstration unit not involve direct sunlight for long periods
because the high chamber pressure can be loss of the refrigerant. For avoid this problem, reuse
the insulation for the surface refrigerant. When the condenser and evaporator pressure gauge at
the danger level, to prevent this problem use to PIA (pressure indicator alarm) for the signal.
The construction of thick walled of the condenser and evaporator is higher strength glass
cylinder. Provided the thick wall properly to avoid the leakage with the replace glass cylinder to
stainless steel cylinder.
The bubble cap damage at the condenser base plate cause the refrigerant radiator.The
function of bubble cap is pump liqued vapor to evaporator.To prevent this cause,replace the
bubble cap with another material required.
REFERENCES