Appendix 4- Technical Particulars - To be filled in by bidder

TYPE OF EQUIPMENT 12.5/16MVA 33/6.9kV POWER TRANSFORMER


CLIENT PETROLEUM DEVELOPMENT OMAN L.L.C (OMAN)
UNIT or AREA: MABROUK DEEP PHASE-3
REQ.NO: MBR-21-102396-EA-7303-00072-0000-3G
Information Marked with to be completed by the Vendor/Manufacturer.

Sl. No. Description Requirement Bidder's Proposal Remarks


1.00 GENERAL
1.1 Tag No. G21101-TX & G21102-TX
1.2 Quantity 2 Nos
1.3 Reference Design Standard IEC 60076
1.4 Make
1.5 Transformer Model No. / Type No.
1.6 Service Outdoor/Continuous
1.7 Design Life (Years) 25 years
1.8 No. of Windings Two
1.9 Type of cooling ONAN / ONAF
1.10 Tap Changer OCTC
1.11 3 Ph. Symm. Fault level at HV side 25kA
1.12 Short time withstand capability 2 sec as per IEC

Independent and momentary


1.13 Transformer operation Parallel operation with other
Transformer
2.0 DESIGN DATA
2.1 Design Temperature 55C
Continuous Maximum Rating (CMR) of
transformer at 55C
2.2
Natural Cooling Rating (MVA) 12.5 MVA
Forced cooling Rating (MVA) 16 MVA
Supply Voltage 33 kV +/-5%
2.3 System Frequency (Hz) with Variation 50 Hz +/-5%
Rated no load Voltage ratio 33/6.9 kV
Current
No Load Current
Rated Current Primary side/Secondary side @
2.4
ONAN
Rated Current Primary side/Secondary side @

ONAF
2.5 % Impedance 10%
Winding connection
2.6 HV winding Delta
LV winding Star
2.7 Vector Group Designation Dyn11
System Earthing
2.8 HV Side NA
Resistance earthed with
LV Side
current limited to 100A
2.9 Insulation Class Class-A
Temperature rise based on Ambient
Temperature conditions
2.10
Winding
Oil
2.11 Basic Impulse Withstand Voltage
HV Winding (kV Peak) 170
HV Neutral (kV Peak) Not Applicable
LV Winding (kV Peak) 75
LV Neutral (kV Peak) 75
Separate Source Power Frequency withstand
2.12
Voltage
HV Winding (kV rms) 70
HV Neutral (kV rms) -
LV Winding (kV rms) 28
LV Neutral (kV rms) 28
3.0 CONSTRUCTION
3.1 Winding Material for HV and LV Copper
Winding Insulation
3.2 HV side Uniform
LV side Uniform
3.3 Core Material & Grade CRGO
3.4 Type of Tank construction Welded
3.5 Tank Cover Bolted

Page 1 of 5
Appendix 4- Technical Particulars - To be filled in by bidder
TYPE OF EQUIPMENT 12.5/16MVA 33/6.9kV POWER TRANSFORMER
CLIENT PETROLEUM DEVELOPMENT OMAN L.L.C (OMAN)
UNIT or AREA: MABROUK DEEP PHASE-3
REQ.NO: MBR-21-102396-EA-7303-00072-0000-3G
Information Marked with to be completed by the Vendor/Manufacturer.

Sl. No. Description Requirement Bidder's Proposal Remarks


Min. thickness of tank steel (mm)
Top mm
3.4
Bottom mm
Sides mm
3.5 Min. thickness of radiator plates (mm) mm
Maximum pressure withstand of tank & radiator
3.6
(kPa)
3.7 Minimum Vacuum Withstand (kPa)
Oil Conservation system
3.8 Conservator Type
(Conservator / Sealed type)
3.9 Air bag for Transformer Required
3.10 Radiator Type (Detachable / Welded) Detachable
Type of enclosure for marshalling box, cooling
3.11
control cabinet etc.
Vacuum withstand capability
3.12 Main tank
Radiators
Minimum clearance height for lifting core and
3.13
winding from tank
Free space required at the top for removal of
3.14
accessories including bushing.
3.15 Paint Shade RAL 7035
4 Performance data
Rated Design Flux density at Rated Voltage
(Tesla)
4.1
Core
Yoke
4.2 Flux Density at 110% rated voltage (Tesla)
Maximum Current density at CMR
4.3 HV Winding A/mm2
LV winding A/mm2
Hot spot Temperature at CMR as per site
service condition
4.4
ONAN
ONAF
4.5 Design X/R Ratio
Impedance Voltage & reference base @ ref. Resistance/Reactance/Impe
temperature 75oC dance
4.6 At principal tap
At Extreme plus tap
At Extreme minus tap
4.7 LV winding
4.8 Zero sequence impedance and reactance
4.9 Saturation Voltage of core material (%Un)
Maximum symmetrical short circuit current for
which the windings are designed to withstand
4.10 thermally for 2s
HV Winding (kA)
LV Winding (kA)
Maximum Temperature Rise (Guaranteed) At
4.11
Full Load
Top oil by Thermometer
(i) For ONAN type cooling
(ii) For ONAF type cooling
Windings by resistance method
(i) For ONAN type cooling
(ii) For ONAF type cooling
4.12 Estimated maximum cooler losses at full load.
Guaranteed Losses at 75C without positive
tolerance
No Load Loss (kW)
4.13 Load Loss @ 75C (kW)
Capitalization cost of No Load Losses
Capitalization cost of Load Losses
Magnetisation current at rated voltage and
4.14
frequency, percent of full load current

Page 2 of 5
Appendix 4- Technical Particulars - To be filled in by bidder
TYPE OF EQUIPMENT 12.5/16MVA 33/6.9kV POWER TRANSFORMER
CLIENT PETROLEUM DEVELOPMENT OMAN L.L.C (OMAN)
UNIT or AREA: MABROUK DEEP PHASE-3
REQ.NO: MBR-21-102396-EA-7303-00072-0000-3G
Information Marked with to be completed by the Vendor/Manufacturer.

Sl. No. Description Requirement Bidder's Proposal Remarks


Efficiency @ 75C (UPF/0.8PF)
At Full Load
4.15
At 75% Load
At 50% Load
Regulation @ 75C (UPF/0.8 PF)
At Full Load
4.16
At 75% Load
At 50% Load
4.17 % loading at which max. efficency
4.18 Noise Level at full rated power (db)
5.0 TERMINATIONS
5.1 HIGH VOLTAGE TERMINATION
5.1.1 Type of Termination Air insulated cable box
5.1.2 Cable Type Cu/XLPE/AWA/PVC
5.1.3 Cable Size & Material (1C x Sq.mm.) 1C x 240 Sq. mm/Ph
5.1.4 No. of Runs / phase 1
5.1.5 Cable Take-off method Vertically down
5.1.6 Separate Cable box for Neutral Not Applicable
5.1.7 Ingress Protection - Cable Box min IP 55
5.2 HIGH VOLTAGE PHASE BUSHINGS
5.2.1 Manufacturer
5.2.2 Type Designation
5.2.3 Material
5.2.4 Location
5.2.5 Rated Voltage (kV)
5.2.6 Rated current (A)
5.2.7 BIL (kVpeak)
5.2.8 Power Frequency withstand voltage (kVrms)
5.2.9 Creepage distance (mm) 25 mm/kV
5.2.10 Cantilever strength (kN)
5.2.11 Minimum Air Clearances
Live Metal - Metal of different phases (mm)
Live Metal - Earth (mm)
5.3 LOW VOLTAGE TERMINATION

Air insulated cable box


5.3.1 Type of Termination
separate for line and neutral

5.3.2 Cable Type Cu/XLPE/AWA/PVC


5.3.3 Cable Size & Material (1C x Sq.mm.) 1C x 630
5.3.4 No. of Runs / phase 4 Runs/Ph + 1Runs Neutral
5.3.5 Cable Take-off method Vertically down
5.3.6 Separate Cable box/enclosure for Earth Yes
5.3.7 Ingress Protection - Cable Box min IP 55
5.4 LOW VOLTAGE PHASE BUSHINGS
5.4.1 Manufacturer
5.4.2 Type Designation
5.4.3 Material
5.4.4 Location
5.4.5 Rated Voltage (kV)
5.4.6 Rated current (A)
5.4.7 BIL (kVpeak)
5.4.8 Power Frequency withstand voltage (kVrms)
5.4.9 Creepage distance (mm) 25mm/kV
5.4.10 Cantilever strength (kN)
Minimum Air Clearances
5.4.11 Live Metal - Metal of different phases (mm)
Live Metal - Earth (mm)

Page 3 of 5
Appendix 4- Technical Particulars - To be filled in by bidder
TYPE OF EQUIPMENT 12.5/16MVA 33/6.9kV POWER TRANSFORMER
CLIENT PETROLEUM DEVELOPMENT OMAN L.L.C (OMAN)
UNIT or AREA: MABROUK DEEP PHASE-3
REQ.NO: MBR-21-102396-EA-7303-00072-0000-3G
Information Marked with to be completed by the Vendor/Manufacturer.

Sl. No. Description Requirement Bidder's Proposal Remarks


5.5 LOW VOLTAGE NEUTRAL BUSHING Separate enclosure
5.5.1 Manufacturer
5.5.2 Type Designation
5.5.3 Material
5.5.4 Location
5.5.5 Rated Voltage (kV)
5.5.6 Rated current (A)
5.5.7 BIL (kVpeak)
5.5.8 Power Frequency withstand voltage (kVrms)
5.5.9 Creepage distance (mm) 25 mm/kV
5.5.10 Minimum Air Clearances (Live Metal-Earth (mm)
5.5.11 Cantilever strength (kN)
5.6 LV NEUTRAL CURRENT TRANSFORMERS
5.6.1 Location LV Neutral
5.6.2 No. of cores 2
5.6.3 Core Core 1
Purpose Standby E/F protection
Ratio (A/A) 100/1
Class 5P
Rated Accuracy Limit Factor (ALF) 20

Rated secondary winding resistance (Rct - Ohm)

Rated Secondary burden (VA) 15


5.6.4 Core Core 2
Purpose Standby E/F protection
Ratio (A/A) 100/1
Class 5P
Rated Accuracy Limit Factor (ALF) 20

Rated secondary winding resistance (Rct - Ohm)

Rated Secondary burden (VA) 15


6.0 TAP CHANGER
6.1 Type OCTC
6.2 Tapping on winding High Voltage
6.3 Manufacturer
6.4 Type Designation
6.5 No. of steps 5
6.6 Step Voltage (%) 2.50%
6.7 Tapping range (%) +5% to -5%
Type of enclosure for marshalling box, cooling
6.8
control cabinet etc.
7 WINDING TEMPERATURE INDICATOR
7.1 Manufacturer
7.2 Type Designation
7.3 Adjustment range for 2 stage Alarm contacts
7.4 Adjustment range for forced cooling contacts
7.5 Contact Rating (at 240V AC)
7.6 No. of contacts
8.00 OIL TEMPERATURE INDICATOR
8.10 Manufacturer
8.20 Type Designation
8.30 Adjustment range for 2 stage Alarm contact
8.40 Adjustment range for forced cooling contacts
8.50 Contact Rating (at 240V AC)
8.60 No. of contacts
9.00 BUCHHOLZ RELAY
9.10 Manufacturer
9.20 Type Designation
9.30 Contact Rating (at 240V AC)
9.40 No. of contacts

Page 4 of 5
Appendix 4- Technical Particulars - To be filled in by bidder
TYPE OF EQUIPMENT 12.5/16MVA 33/6.9kV POWER TRANSFORMER
CLIENT PETROLEUM DEVELOPMENT OMAN L.L.C (OMAN)
UNIT or AREA: MABROUK DEEP PHASE-3
REQ.NO: MBR-21-102396-EA-7303-00072-0000-3G
Information Marked with to be completed by the Vendor/Manufacturer.

Sl. No. Description Requirement Bidder's Proposal Remarks


10 PRESSURE RELEIF DEVICE (PRD)
10.1 PRD FOR MAIN TANK
10.10 Manufacturer
10.20 Type Designation
Pressure range for operation (From____ to ____
10.30
kPa)
10.40 Resealing pressure (kPa)
10.50 Contact Rating (at 240V AC)
10.60 No. of contacts
11 COOLING EQUIPMENT
11.1 Manufacturer
One Standby Fan per 50%
11.2 No. of cooling fans
cooler bank
11.3 No. of cooling fan groups
11.4 Power Rating of each fan (kW)
11.5 Supply Voltage
11.6 No. of phases
11.7 Min number of fans to be in operation at full load.
Winding temperature at which forced cooling is
11.8
initiated.
Transformer derating factor after failure of

11.9 (i) One cooling fan


(ii) Two cooling fans
(iii) All cooling fans
11.10 Total fan consumption at full load (kW)
11.11 Overload capacity of transformer
12.0 OIL LEVEL INDICATOR FOR MAIN TANK
12.1 Manufacturer
12.2 Type Designation
12.3 Contact Rating (at 110V DC)
13 OIL LEVEL INDICATOR FOR CONSERVATOR
13.1 Manufacturer
13.2 Type Designation
13.3 Quantity
13.4 Contact Rating (at 110V DC)
14 BREATHER
14.1 Breather type for main tank
15.0 VALVES
15.1 Type & Size of Oil Drain valve
15.2 Type & Size of Oil Filtration valve
15.3 Type & Size of Radiator valve
15.4 Type & Size of sampling valve
17 TRANSFORMER OIL
17.1 Manufacturer
17.2 Make Designation
17.3 Applicable Industry Standards IEC 60296
17.4 Class of Oil Inhibited oil
18 SPECIAL TEST / TYPE TESTS
18.1 Temperature rise test Required
19 WEIGHT & DIMENSIONS
19.1 Overall dimension Transformers (L x B x H)
Maximum Shipping Dimension of Transformer
19.2
(L x B x H) - mm
19.3 Weight of Core & Coil Assembly (kg)
19.4 Weight of Core (kg)
19.5 Weight of radiator banks
19.6 Weight of copper (kg)
19.7 Weight of Oil (kg)
Total weight (kg)
19.8 With Oil
Without oil
19.9 Shipping weight (kg)
19.10 Volume of oil (liters)

Page 5 of 5