Application Note

MODBUS
with WAGO Ethernet
Couplers and Controllers

A300003, English Version 2.1.0


2 Imprint

Imprint
Copyright 2015 by WAGO Kontakttechnik GmbH & Co. KG
All rights reserved.

WAGO Kontakttechnik GmbH & Co. KG


Hansastrae 27
D-32423 Minden
Phone: +49 (0) 571/8 87 0
Fax: +49 (0) 571/8 87 1 69
Email: info@wago.com
Web: http://www.wago.com

Technical Support
Phone: +49 (0) 571/8 87 5 55
Fax: +49 (0) 571/8 87 85 55
Email: support@wago.com

Every conceivable measure has been taken to ensure the accuracy and com-
pleteness of this documentation. However, as errors can never be fully exclud-
ed, we always appreciate any information or suggestions for improving the
documentation.

We wish to point out that the software and hardware terms, as well as the
trademarks of companies used and/or mentioned in the present manual, are
generally protected by trademark or patent.

a300003
Contents 3

TABLE OF CONTENTS

1 Important Notes 4

2 Introduction 7
2.1 The IEC 61131-3 Addresses 9
2.2 Structure of the Process Images 11

3 WAGO Controller 750-88x as MODBUS Slave 13


3.1 Example: FC15(Force multiple coils) 16
3.2 Example: FC22 (Mask write) 16
3.3 Example: FC16(Write multiple register) 17

4 WAGO Controller as MODBUS Master 18


4.1 MODBUS Master Configurator 18
4.2 CODESYS Libraries 19

5 PC Application as MODBUS Master 20


5.1 WagoModbusNet 20
5.2 MBT.dll 21

6 Appendix A: The MODBUS Protocol 22


6.1 FC1 (Read Coils) 24
6.2 FC2 (Read Input Discretes) 25
6.3 FC3 (Read multiple registers) 26
6.4 FC4 (Read input registers) 27
6.5 FC5 (Write Coil) 28
6.6 FC6 (Write single register) 29
6.7 FC11 (Get comm event counter) 30
6.8 FC15 (Force Multiple Coils) 31
6.9 FC16 (Write multiple registers) 32
6.10 FC22 (Mask Write Register) 33
6.11 FC23 (Read/Write multiple registers) 34

7 Appendix B: Device-specific Process Images 35


7.1 Fieldbus Coupler 750-342 35
7.2 Fieldbus Coupler 750-352 40
7.3 Fieldbus Coupler 767-1301 43
7.4 Programmable Fieldbus Controller 750-842 48
7.5 Programmable Fieldbus Controller 750-88x 54
7.6 Programmable Fieldbus Controllers PFC200 64

8 Appendix C: Useful Tools 70


8.1 CODESYS Controller Configuration 70
8.2 Wireshark 72

a300003
4 Important Notes

1 Important Notes
To ensure fast installation and start-up of the units, we strongly recommend
that the following information and explanations are carefully read and adhered
to.

1.1 Legal Principles


1.1.1 Copyright
This document, including all figures and illustrations contained therein, is sub-
ject to copyright. Any use of this document that infringes upon the copyright
provisions stipulated herein is prohibited. Reproduction, translation, electronic
and phototechnical filing/archiving (e.g., photocopying), as well as any
amendments require the written consent of WAGO Kontakttechnik GmbH &
Co. KG, Minden, Germany. Non-observance will entail the right of claims for
damages.

WAGO Kontakttechnik GmbH & Co. KG reserves the right to make any alter-
ations or modifications that serve to increase the efficiency of technical pro-
gress. WAGO Kontakttechnik GmbH & Co. KG owns all rights arising from
granting patents or from the legal protection of utility patents. Third-party
products are always mentioned without any reference to patent rights. Thus,
the existence of such rights cannot be excluded.

1.1.2 Personnel Qualification


The use of the product described in this document is exclusively geared to spe-
cialists having qualifications in PLC programming, electrical specialists or
persons instructed by electrical specialists who are also familiar with the ap-
propriate current standards. WAGO Kontakttechnik GmbH & Co. KG as-
sumes no liability resulting from improper action and damage to WAGO
products and third-party products due to non-observance of the information
contained in this document.

1.1.3 Intended Use


For each individual application, the components are supplied from the factory
with a dedicated hardware and software configuration. Modifications are only
admitted within the framework of the possibilities documented in this docu-
ment. All other changes to the hardware and/or software and the non-
conforming use of the components entail the exclusion of liability on part of
WAGO Kontakttechnik GmbH & Co. KG.

Please send your requests for modified and new hardware or software configu-
rations directly to WAGO Kontakttechnik GmbH & Co. KG.

a300003
Important Notes 5

1.2 Scope of Validity


This application note is based on the stated hardware and software from the
specific manufacturer, as well as the associated documentation. This applica-
tion note is therefore only valid for the described installation.
New hardware and software versions may need to be handled differently.

Please note the detailed description in the specific manuals.

1.3 Symbols
DANGER Warning against personal injury!
Indicates a high-risk, imminently hazardous situation which, if not avoided,
will result in death or serious injury.

DANGER Do not work on components while energized!


Indicates a high-risk, imminently hazardous situation which, if not avoided,
will result in death or serious injury.

WARNING Warning against personal injury!


Indicates a moderate-risk, potentially hazardous situation which, if not
avoided, could result in death or serious injury.

CAUTION Warning against personal injury!


Indicates a low-risk, potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.

NOTICE Warning: Damage to property!


Indicates a potentially hazardous situation which, if not avoided, may result
in damage to property.

Note Important note!


Indicates a potential malfunction which will not result in damage to proper-
ty, however, if not avoided.

Information Additional Information


Refers to additional information which is not an integral part of this docu-
mentation (e.g., the Internet).

Pos: 12.4 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21808 @ @ 1

a300003
6 Important Notes

Pos: 12.5 /Alle Serien (Allgemeine Module)/Hinweise zur Dokumentation/Zahlensysteme @ 3\mod_1221059454015_6.doc @ 21709 @ 2 @ 1

1.4 Number Notation


Table 1: Number Notation
Number code Example Remark
Decimal 100 Normal notation
Hexadecimal 0x64 C notation
Binary '100' In quotation marks,
'0110.0100' nibble separated by a period

Pos: 12.6 /Alle Serien (Allgemeine Module)/Hinweise zur Dokumentation/Schriftkonventionen @ 3\mod_1221059521437_6.doc @ 21712 @ 2 @ 1

1.5 Font Conventions


Table 2: Font Conventions
Font type Explanation
italic Names of paths and files are displayed in italics, e.g.:
C:\Programs\WAGO-I/O-CHECK
Menu Menu options are displayed in bold, e.g., :
Save
> A greater than symbol between two names denotes the selection of
a menu option, e.g.:
File > New
Input Designation of input or optional fields are displayed in bold, e.g.:
Start of measurement range
Value Input or selection values are displayed in quotation marks, e.g.:
Enter the value 4mA under Start of measurement range.
[Button] Button labels within the dialogs are bold and enclosed in square
brackets, e.g.:
[Input]
[Key] Keys on the keyboard are bold and enclosed in square brackets, e.g.:
[F5]

a300003
Introduction 7

2 Introduction
This application note explains how to use the MODBUS protocol in conjunc-
tion with the WAGO-I/O-SYSTEM.

The modular design of the WAGO-I/O-SYSTEM makes it possible to attach a


number of different I/O modules to the fieldbus coupler in almost any order.
The variability of the node configuration, however, prevents the static assign-
ment of data points and MODBUS addresses.

This application note shows the relationships between node configuration,


process images, IEC-61131 addresses and MODBUS addresses.

Metaphorically, MODBUS communication is a game of questions and an-


swers. It always involves a MODBUS master and one or more MODBUS
slaves.

The MODBUS master makes a REQUEST to the MODBUS slave. The re-
quest includes the function code (FC), MODBUS address (adr) and the num-
ber (count) of data objects ([data]) to which read or write access is required.
The slave processes the request and returns a corresponding RESPONSE.

MODBUS knows only two data types (coils and register).


A Coil stands for the state of a digital value (1-bit).
A Register is a 16-bit (WORD) analog value.

a300003
8 Introduction

With fieldbus couplers and programmable fieldbus controllers, WAGO offers


two types of head stations.

Fieldbus couplers (remote IO) allow direct access to the data of con-
nected I/O modules via a fieldbus interface.
(e.g., 750-352)

Fieldbus controllers are programmable fieldbus couplers. CODESYS


2.3 is used to program the fieldbus couplers. (e.g., 750-88x, 750-820x).
Additional memory ranges (PFC variables and flags) are available for
data exchange between PLC program and fieldbus.

The MODBUS protocol can be used to read or modify memory location in the
process image. However, the node configuration or PLC program determines
which I/O module or what data is located at a specific memory location.

After the power is turned on, a WAGO fieldbus coupler or programmable


fieldbus controller determines the current node configuration and creates pro-
cess images for inputs and outputs.

Complex and digital I/O modules are differentiated:

Complex I/O modules have a data width of more than one byte, includ-
ing analog modules, counters, steppers, serial interfaces, etc. During
the first step of process image creation, the complex I/O modules are
arranged in the process image based on their physical order after the
fieldbus coupler.

The data of the digital I/O modules is packaged to full bytes in a sec-
ond step based on their position behind the fieldbus coupler and ar-
ranged directly behind those of the Complex I/O modules.

All WAGO fieldbus couplers and programmable fieldbus controllers have ex-
actly one process image for physical inputs and one for physical outputs. The
data of the complex I/O modules is saved in the respective process image, fol-
lowed by the data of the digital I/O modules.

The process image configuration is described by IEC 61131-3 language ele-


ments. This is necessary since the MODBUS protocol only defines services on
the basic data types and does not control their meaning or specific addresses.

a300003
Introduction 9

Address assignment for the PFC200 family looks a bit different. Due to the
system property that I/O modules cannot be accessed directly via the
MODBUS, they also do not appear in the mapping table.

Please also note the following:

Variable monitoring has been optimized in CODESYS 2.3.


The result is that declared variables not used in the program code are not
monitored and are therefore always displayed in the debugger with the value
0.

2.1 The IEC 61131-3 Addresses


In the PLC program, an IEC 61131-3 address is used to access the process im-
age and specific data ranges (PFC variables and flags).

The following table shows the structure of a hardware address in the IEC
61131 syntax.

If the first digital output of the sample node from Section 2.2 is to be set, the
respective assignment appears as follows:

Assignment in FUP:

Assignment in ST:

a300003
10 Introduction

Direct access via hardware addresses in the user program is possible, but not
recommended.

The designation %QX4.0 is not very descriptive and complicates the reada-
bility of the program.

To increase readability, symbolic addressing is recommended. Variables are


explicitly declared to a hardware address.
The advantage is that the output can be give an descriptive name (e.g., func-
tion name or resource ID).

In addition, if the address shifts because a node is added, only the address in
the variable declaration has to be adjusted:

Variable declaration:

Assignment in FUP:

Assignment in ST:

In this way, any typed variables can be positioned in the memory.


TYPE TMyType :
STRUCT
wState : WORD; (* actual state *)
dwJobAct : DWORD; (* Actual job *)
dwJobLast : DWORD; (* Last job *)
dwJobNext : DWORD; (* Next job *)
xFlagDoIt : BOOL; (* something should happen *)
xFlagDone : BOOL; (* something have been done *)
END_STRUCT
END_TYPE

VAR
xMyOutput AT %QX0.2 : BOOL; (* A digital output *)
wMyInput AT %IW1 : WORD; (* A analog input *)
oInterface AT %MW0 : TMyType;(* A userdefined type *)
VAR_END

This approach can be advantageous when implementing software interfaces


between the control system and MODBUS field devices. However, caution is
advised because empty bytes are added due to the DWORD alignment and
thus the data is inaccessible via the expected MODBUS address.

a300003
Introduction 11

2.2 Structure of the Process Images


A process image is a part of the memory with a fixed size in which the process
values of the I/O modules are stored.

One input process image and one output process image are generated.
The process values of the individual I/O modules are stored in the respective
process image depending on the type and position behind the fieldbus coupler.

Digital and complex I/O modules are differentiated.

Complex I/O modules (often referred to as analog modules) represent all I/O
modules having a data width greater than one byte.
Examples are analog inputs and outputs, counter modules, I/O modules for an-
gle and distance measurement, communication modules such as RS-232 C,
etc. or in other words, All non-digital I/O modules.

For both the input and the output process image, the data of the I/O modules is
stored in the respective process image according to the order of their position
after the fieldbus coupler.

First, the complex module data is stored in the process image, followed by the
digital module data.

The bits of the digital I/O module are combined into bytes. If the amount of
digital I/O information exceeds eight bits, the controller automatically starts a
new byte.

a300003
12 Introduction

The data width of an I/O module is between 0 and 48 bytes. Please find more
details in the fieldbus coupler manual as well as in the manual of the applica-
ble I/O module.

The following table illustrates this relation using specific example.

I/O Mod- Input image Output image Description


ules
Type run1 run2 run3 run4
C
2 DI 24VDC 3ms:
1 %IX8.0 First digital input module with a data width of two bits.
750-400 Since the complex input modules from run1 already
2 %IX8.1 occupy the first 8 words, the digital inputs are put to lower
order bits in word 8.
2 AO 4-20mA:
1 %QW0
First analog output module with a data width of two
750-554
words. This I/O module occupies the first two words in the
2 %QW1
output process image.
1 %IX8.2 4 DI 24VDC:
2 %IX8.3 The four digital inputs of this I/O module are put behind
750-402 the two inputs of the 750-400 and are in the eighth word
3 %IX8.4
of the input process image.
4 %IX8.5
1 %QX4.0 4 DO 24VDC:
2 %QX4.1 First I/O module of the digital output. The I/O modules of
750-504 the analog outputs already occupy the first four words in
3 %QX4.2
the output process image.
4 %QX4.3
1 %IW0 2 AI 4-20mA:
750-454 First I/O module of the analog inputs. This I/O module
2 %IW1 occupies the first two words of the input table.
%IW2
RS232 C 9600/8/N/1:
%IW3 The serial interface module 750-650 is a complex I/O
750-650 1
%QW2 module represented both in the input and output process
%QW3 images with 4 bytes each.
1 %IW4 4 AI 0-10V S.E:
2 %IW5 The I/O module 750-468 follows the 2 input words of the
750-468 750-454 and the 2 input words of the 750-650. The I/O
3 %IW6 module 750-467 occupies 4 input words (4 channels 0-
4 %IW7 10V).
End module
750-600
The I/O module 750-600 is a passive module.
C* : Channelcount

run1 to run4 in the above table describe the chronological order during
compilation of the input and output process images when a WAGO coupler or
controller is booted.

a300003
WAGO Controller 750-88x as MODBUS Slave 13

3 WAGO Controller 750-88x as MODBUS Slave


For the node configuration from the previous section, the status of the third
channel, digital output module 750-504, is to be changed via the MODBUS
protocol.

In general, each of the following MODBUS services can be used to change the
status of the third channel of the digital output module 750-504.

FC Name Description
FC5 Write coil Write a single digital output
FC6 Write single register Write a single analog output
FC15 Force multiple coils Write several digital outputs
FC16 Write multiple registers Writing several analog outputs
FC22 Mask write Masked writing of a register
FC23 Read/write multiple registers Read/write operation to analog inputs/outputs

First choice would certainly be the FC5 (Write coil), but use of FC15, FC22
and FC16 is displayed for this task.

It is necessary to determine the MODBUS address corresponding to the IEC


address for the selected MODBUS service.

This information can be used to configure the MODBUS master were it not for
the matter of the write permission for programmable fieldbus controllers of the
750-8xx series.

a300003
14 WAGO Controller 750-88x as MODBUS Slave

For fieldbus couplers, control of write permissions to process images is sim-


ple:

Physical inputs can only be read.

Physical outputs can be read and written.

In general, the same applies to programmable fieldbus controllers.


However, only the PLC program has write permission via the outputs.

If a physical output is changed via MODBUS when a PLC program is running,


the controller configuration must be adjusted in the programming environ-
ment.

The output must be explicitly assigned to the MODBUS.

a300003
WAGO Controller 750-88x as MODBUS Slave 15

The write permission can be assigned to the PLC program, MODBUS protocol
or Ethernet/IP protocol.

The write permission assignment is stored in the /etc/EA-config.xml file. If


the actual node configuration differs from that which is configured, all I/O
modules are assigned to the MODBUS protocol and the I/O LED displays er-
ror code 6 with error argument 9.

Error code 6: Node configuration error


Error argument 9: Error mapping the I/O modules to a fieldbus
Remedy:
1) Check the /etc/EA-Config.xml file for your fieldbus controller.
2) Delete the /etc/EA-Config.xml file, e.g., Online -> Reset (original).

In addition to physical inputs and outputs, the programmable fieldbus control-


lers have a non-volatile flag area of typically 24 kB, as well as PFC-IN and
PFC-OUT areas, each 256 words (512 bytes).

Note PFC200 (750-820x)!


The PFC200 (750-820x) has 104 kB flags und 1000 word PFC-IN and PFC-
OUT.

The flag area can be read and written via the MODBUS protocol and via the
PLC program.

The main field of application for the PFC-IN and the PFC-OUT area is the im-
plementation of interfaces to other controls via the MODBUS protocol.
It is only possible to write data to the PFC-IN area via the MODBUS protocol.
From the perspective of the PLC, the PFC-IN area are local inputs that can on-
ly be read.
The PFC-OUT area resembles physical outputs, data can only be written to it
via the PLC program.

a300003
16 WAGO Controller 750-88x as MODBUS Slave

3.1 Example: FC15(Force multiple coils)


The MODBUS service FC15 Force multiple coils allows the user to change
up to 512 digital outputs with one telegram.

750-881: MODBUS vs. IEC 61131 Addresses for FC15


MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 Physical-Output- First 512 digital outputs
... 511 ... 0x00FF Area (1)

Since this is a digital MODBUS service, the complex I/O modules are ig-
nored when calculating the MODBUS address.
The MODBUS address corresponds to the channel number of the digital out-
put.

The MODBUS address of the third channel of the first digital output module
750-504 is 2. (MODBUS addresses begin with zero.)

3.2 Example: FC22 (Mask write)


The MODBUS service FC22 Mask write is a register service that makes it
possible to specifically change bits in a register.
In addition to the MODBUS address of the register, an AND mask and OR
mask is transferred and sent to the MODBUS slave.

Determining the MODBUS address starts with evaluating the node configura-
tion or creating the output process image.
As shown in the previous section, the determination can be made on foot or
for programmable fieldbus controllers with support from the CODESYS con-
troller configuration.

Both methods should output %QX4.2 as the IEC address of the third digital
output of the first 750-504. The third digital output of the first 750-504 has ad-
dress 4 in the MODBUS register.

The mask registers operate according to the following rule:


Result = (Content AND AndMask) OR (OrMask AND (NOT AndMask))

To set the third output and to leave all other outputs unchanged, use 0xFFFB
as AND mask and 0x0004 as OR mask.

To set the third output and to leave all other outputs unchanged, use 0xFFFB
as AND mask and 0x0000 as OR mask.

a300003
WAGO Controller 750-88x as MODBUS Slave 17

3.3 Example: FC16(Write multiple register)


The MODBUS service FC16 Write multiple register is a register service that
allows changing up to 120 registers with a single telegram.
NumberOfPoints not only sends the MODBUS address of the register to the
Modbus slave, but also the number of registers to be changed and the data it-
self.

Determining the MODBUS address starts with evaluating the node configura-
tion or creating the output process image.
As shown in the previous section, the determination can be made on foot or
for programmable fieldbus controllers with support from the CODESYS con-
troller configuration.

Both methods should output %QX4.2 as the IEC address of the third digital
output of the first 750-504. The MODBUS address can now be looked up in
the address assignment table of the 750-881.

750-881: MODBUS vs. IEC 61131 Addresses for FC6, FC16, FC22 and FC23
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %QW0 Physical output area (1)
... 255 ... 0x00FF ... %QW255 First 256 Words of physical output data

The address assignment table is interpreted as follows: The output word


%QW0 can be accessed via MODBUS address 0.
This means that 4 would be the MODBUS address for %QW4.

With this function, it is not possible to set the digital output independently of
the other output, which is not disadvantage when using the state machine in
the PLC program. That way, an output pattern can be defined and the state of
the installation/machine is always known.

If only the third channel of the 750-504 is used, it is possible to set the digital
output with date 0x0004 and to reset it with date 0x0000.

a300003
18 WAGO Controller as MODBUS Master

4 WAGO Controller as MODBUS Master


The programmable fieldbus controller can be used as a MODBUS master and
MODBUS slave. The CODESYS programming environment can be used to
configure the MODBUS master functionality. Generally, there are two ap-
proaches as described in the following sections.

4.1 MODBUS Master Configurator


The MODBUS Master Configurator is an extension application of the
CODESYS 2.3 programming environment and is used directly in the pro-
gramming environment. The MODBUS Master Configurator is part of the
WAGO-I/O-PRO software (759-333) version 2.3.9.40 or higher.

The MODBUS Master Configurator makes configuring a MODBUS network


simple. The documentation for the MODBUS Master Configurator contains a
corresponding compatibility list.

The dialog streamlines network creation in the MODBUS Master Configura-


tor.
An node scan can be used to configure all MODBUS-enabled WAGO devices
in the network. The connected I/O modules are identified and all data points
determined.

For a detailed description of the MODBUS Master Configurator, please refer


to the WAGO homepage:

http://www.wago.de/download.esm?file=%5Cdownload%5C00286500_0.pdf
&name=m07590333_xxxxxxxx_0_en.pdf

a300003
WAGO Controller as MODBUS Master 19

4.2 CODESYS Libraries


Pre-configured libraries can also be used to implement the MODBUS master
functionality. This method offers fewer convenience functions (no node scan
possible), but provides the library functions that the MODBUS Master Con-
figurator does not offer (e.g., function code 23).

The following libraries are available for the programmable fieldbus control-
lers:

Library Depending on the Supported target system


system library
WagoLibMODBUS_IP_01.lib SysLibSockets.lib 750-841
750-88x
750-820x
758-87x
MODBUSEthernet_04.lib Ethernet.lib 750-841
750-842
750-843

The following minimal project uses function code 23 to write 100 words to
the MODBUS slave with IP address 192.168.1.13. In addition, 100 words
from the MODBUS slave are read in the same telegram.

Operating instructions for the example can be found in the example program.

a300003
20 PC Application as MODBUS Master

5 PC Application as MODBUS Master


To create Windows applications, WAGO makes available two MODBUS
Master implementations under item number 759-312.

WagoModbusNet.cs, a C# .NET code class.

MBT.dll, a procedural 32-bit DLL


(does not run on 64-bit operating systems)

While WagoModbusNet requires .NET Framework 2 or higher, MBT.dll


can be used in nearly all programming languages.

5.1 WagoModbusNet
With WagoModbusNet 759-312, WAGO makes a C# coded .NET code
class library available that encapsulates the function of a MODBUS master.

WagoModbusNet can be used in all versions higher than or equal to Visu-


alStudio2005.
In C# projects, just add the WagoModbusNet.cs to the project.
For all other .NET languages such as vb.net, add a reference to the Wago-
ModbusNet.dll to the project.

The following classes are available:


- wmnModbusMasterTCP
- wmnModbusMasterUDP
- wmnModbusMaster-RTU(Serial)
- wmnModbusMaster-ASCII(Serial).

The commands FC1, FC2, FC3, FC4, FC5, FC6, FC11, FC15, FC16, FC22,
and FC23 are supported by the Open MODBUS TCP protocol V1.3.

You can find examples on the CD with item No. 759-312.

a300003
PC Application as MODBUS Master 21

5.2 MBT.dll
With MBT.dll 759-312, WAGO provides a procedural DLL that implements
the MODBUS TCP protocol.

The MBT.dll supports 32-bit operating systems such as Windows 95, Win-
dows 98, Windows NT 4.0 (abSP5), Windows 2000 and Windows XP. Win-
dows 95 requires an update to Windows Socket 2.0.

TCP or UDP can be selected as the transport protocol. WAGO recommends


using UDP as the transport protocol since it allows for better timeout handling.

The MBT.dll can be used in many programming languages. On the included


CD-ROM, you can find examples for VBA(Excel), VB6, LabView, C, VC++
6, Delphi, vb.net and C#.

The commands FC1, FC2, FC3, FC4, FC7, FC15 and FC16 are supported by
Open MODBUS TCP protocol V1.3.

The MBT.dll does not have to be installed or registered.


You just have to copy the DLL to the Windows default directory \system32.
If you select a different directory, you have to add the path to the MBT.dll
for the environment variables in the Windows control panel.

The MBT.dll provides the following functions:


MBTInit(); MBTExit()
MBTConnect(); MBTDisconnect()
MBTReadRegisters();MBTWriteRegisters()
MBTReadCoils();MBTWriteCoils()
MBTSwapWord(); MBTSwapDWord()

All functions of the MBT library have return values in HRESULT format. The
functions of the socket APIs do not return values in this format. The MBT li-
brary converts these return values using the HRESULT_FROM_WIN32. mac-
ro. In the following description, this is identified by HR from.

In a program, MBTInit() should be called once. The function provides the


required resources and initializes the DLL. MBTConnect() establishes a
connection to a remote MODBUS slave (server). Data is exchanged via the
functions MBTWriteRegisters(), MBTReadRegisters(),
MBTWriteCoils() and MBTReadCoils(). Once all data is exchanged, the
connection is disabled using the function MBTDisconnect(). Now, the con-
nection can be established again or the program can be terminated. To make
sure that the resources are released, the function MBTExit() should be exe-
cuted once after program termination and also after program abort.

a300003
22 Appendix A: The MODBUS Protocol

6 Appendix A: The MODBUS Protocol


The MODBUS protocol developed in 1979 is an open Internet Draft Stand-
ard of the IETF (Internet Engineering Task Force) today.
The tried and tested original MODBUS services as well as the object model
have not been modified and have been adopted by TCP/IP as a transmission
medium. Communication occurs via the well-known port 502, which is re-
served for MODBUS.
The MODBUS family thus consists of the classic MODBUS RTU and
MODBUS ASCII (asynchronous transmission via RS-232 or RS-485) and
MODBUS TCP (connection-oriented client-server communication via
ETHERNET).

WAGO Kontakttechnik GmbH & Co. KG expands the MODBUS family with
MODBUS/UDP. This version uses a connectionless, asynchronous client serv-
er communication via ETHERNET.
MODBUS/UDP solves a problem, which arises when a MODBUS slave
(server) is not available (e.g., interrupted power supply). MODBUS TCP pro-
vides retransmission mechanisms of the TCP stack, which causes the
MODBUS master(client) to realize very late that the remote station is not
available.
With MODBUS UDP, the time-out monitoring is done on the application layer
(OSI layer 7) and can hence react immediately to a missing response telegram.
For this reason, we recommend using the MODBUS UDP version, if possible.

MODBUS communication occurs via service calls. The MODBUS master


(client) sends a request telegram to Port 502 of the MODBUS slave (server).
The MODBUS slave returns the result of the service call in a response tele-
gram to the MODBUS master.

The most important elements of a MODBUS telegram are:

Item Description
Function Code (FC) Service identification: Read or write operation in bits or WORDs
Address Operation start address
Count Number of bits or WORDs (bytes) depending on the service
[Data] Process data

First, the service ID or function code (FC) determines whether it is a read or a


write operation, then it determines the basic data type to be used with the oper-
ation. Therefore, the meaning of the parameters Address and Count is also
dependent on the function code. Consequently, Address :=3 can stand for the
fourth bit or word in the input or output process image.

a300003
Appendix A: The MODBUS Protocol 23

The MODBUS protocol is based on the following basic data types:

Data Type Length Description


Discrete Inputs 1 bit Digital inputs
Coils 1 bit Digital Outputs
Input Register 16 bits Analog input data
Holding Register 16 bits Analog output data

One or more function codes are defined for every basic data type.

FC Name Description
FC1 Read coils Re-read several digital outputs
FC2 Read inputs discrete Read several digital inputs
FC3 Read holding registers Read several analog inputs (and outputs)
FC4 Read input registers Read several analog inputs (and outputs)
FC5 Write coil Write a single digital output
FC6 Write single register Write a single analog output
FC11 Get comm event counter Communication event counter
FC15 Force multiple coils Write several digital outputs
FC16 Write multiple registers Writing several analog outputs
FC23 Read/write multiple registers Write/read operation to analog inputs/outputs

Although digital and analog process data from WAGO fieldbus couplers and
programmable fieldbus controllers is combined in a process image, the first
digital output or input is always reached with the digital MODBUS services
at address 0. That means that the digital MODBUS services ignore the com-
plex I/O modules.
On the other hand, however, the status of the digital inputs and outputs can al-
so be determined or changed via the so-called Register service.

All WAGO fieldbus couplers and programmable fieldbus controllers do not


distinguish between the function codes FC1 and FC2.
Both MODBUS services use the same implementation and allow access to
digital input and output modules, as well as the flag area.

All WAGO fieldbus couplers and programmable fieldbus controllers do not


distinguish between the function codes FC3 and FC4. Both MODBUS services
use the same implementation.

The maximum telegram length is determined by the BYTE data type, which
can only accept values between 0 and 255. Depending on the MODBUS ser-
vice, approx. 120 WORDs of user data can be transported.

Please find device-related comparisons of MODBUS addresses and IEC ad-


dresses in Appendix B.

a300003
24 Appendix A: The MODBUS Protocol

6.1 FC1 (Read Coils)


This function reads the content of several input or output bits.

Structure of the request

Example: A request to read bits 0 to 7.

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x0006
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x01
Byte 8, 9 Reference number 0x0000
Byte 10, 11 Bit count 0x0008

Structure of the response

The current values of the bits are entered into the data field. Value 1 = ON,
value 0 = OFF. The least significant bit of the first data byte contains the first
bit of the request. The other bits follow in ascending order. If the number of
inputs is not a multiple of 8, the remaining bits of the last data byte are filled
up with zeros.

Byte Field name Example


.....
Byte 7 MODBUS function code 0x01
Byte 8 Byte count 0x01
Byte 9 Bit values 0x12
The status of inputs 0 to 7 is displayed as byte value 0x12 or binary 0001
0010. Input 7 is the most significant bit of this byte, input 0 is the least signifi-
cant bit. The assignment of 7 to 0 is hence
OFF-OFF-OFF-ON-OFF-OFF-ON-OFF.

Bit: 0 0 0 1 0 0 1 0
Coil: 7 6 5 4 3 2 1 0
Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x81
Byte 8 Exception code 0x01 or 0x02

a300003
Appendix A: The MODBUS Protocol 25

6.2 FC2 (Read Input Discretes)


This function reads the content of several input bits (digital inputs).

Structure of the request

The request determines the start address and the number of bits to be read.
Example: a request to read the bits 0 to 7.

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x0006
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x02
Byte 8, 9 Reference number 0x0000
Byte 10, 11 Bit count 0x0008
Structure of the response

The current values of the bits are entered into the data field. Value 1 = ON,
value 0 = OFF. The least significant bit of the first data byte contains the first
bit of the request. The other bits follow in ascending order. If the number of
inputs is not a multiple of 8, the remaining bits of the last data byte are filled
up with zeros.

Byte Field name Example


.....
Byte 7 MODBUS function code 0x02
Byte 8 Byte count 0x01
Byte 9 Bit values 0x12
The state of the inputs 7 to 0 is indicated as byte value 0x12 or binary 0001
0010. Input 7 is the most significant bit of this byte, input 0 is the least signifi-
cant bit. The assignment of 7 to 0 is hence
OFF-OFF-OFF-ON-OFF-OFF-ON-OFF.

Bit: 0 0 0 1 0 0 1 0
Coil: 7 6 5 4 3 2 1 0
Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x82
Byte 8 Exception code 0x01 or 0x02

a300003
26 Appendix A: The MODBUS Protocol

6.3 FC3 (Read multiple registers)


This function reads a number of input words (also Input Registers).

Structure of the request

The request determines the address of the start word (start register) and the
number of registers to be read. Addressing starts with 0.

Example: request to read registers 0 and 1.

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x0006
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x03
Byte 8, 9 Reference number 0x0000
Byte 10, 11 Word count 0x0002
Structure of the response

The register data of the response is entered into the registers (2 bytes per regis-
ter). The first byte contains the more significant bits, the second byte contains
the less significant bits.

Byte Field name Example


.....
Byte 7 MODBUS function code 0x03
Byte 8 Byte count 0x04
Byte 9, 10 Value register 0 0x1234
Byte 11, 12 Value register 1 0x2345
The response shows that register 0 contains the value 0x1234 and register 1
contains the value 0x2345.

Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x83
Byte 8 Exception code 0x01 or 0x02

a300003
Appendix A: The MODBUS Protocol 27

6.4 FC4 (Read input registers)


This function reads a number of input words (also Input Registers).

Structure of the request

The request determines the address of the start word (start register) and the
number of registers to be read. Addressing starts with 0.

Example: request to read registers 0 and 1.

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x0006
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x04
Byte 8, 9 Reference number 0x0000
Byte 10, 11 Word count 0x0002
Structure of the response

The register data of the response is entered into the registers (2 bytes per regis-
ter). The first byte contains the more significant bits, the second byte contains
the less significant bits.

Byte Field name Example


.....
Byte 7 MODBUS function code 0x04
Byte 8 Byte count 0x04
Byte 9, 10 Value register 0 0x1234
Byte 11, 12 Value register 1 0x2345
The response shows that register 0 contains the value 0x1234 and register 1
contains the value 0x2345.

Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x84
Byte 8 Exception code 0x01 or 0x02

a300003
28 Appendix A: The MODBUS Protocol

6.5 FC5 (Write Coil)


This function writes a digital output bit.

Structure of the requests

The request determines the address of the output bit. Addressing starts with 0.

Example: Setting the second output bit (address 1).

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x0006
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x05
Byte 8, 9 Reference number 0x0001
Byte 10 ON/OFF 0xFF
Byte 11 0x00
Structure of the response

Byte Field name Example


.....
Byte 7 MODBUS function code 0x05
Byte 8, 9 Reference number 0x0001
Byte 10 Value 0xFF
Byte 11 0x00
Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x85
Byte 8 Exception code 0x01, 0x02 or 0x03

a300003
Appendix A: The MODBUS Protocol 29

6.6 FC6 (Write single register)


This function writes a value into a single output word (output register).

Structure of the request

Addressing starts with 0. The request determines the address of the first output
word to be set. The value to be set is determined in the request data field.

Example: Setting the second output channel (address 0) to value 0x1234.

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x0006
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x06
Byte 8, 9 Reference number 0x0001
Byte 10, 11 Register value 0x1234
Structure of the response

The response is an echo of the request.

Byte Field name Example


.....
Byte 7 MODBUS function code 0x06
Byte 8, 9 Reference number 0x0001
Byte 10, 11 Register value 0x1234
Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x85
Byte 8 Exception code 0x01 or 0x02

a300003
30 Appendix A: The MODBUS Protocol

6.7 FC11 (Get comm event counter)


This function returns a status word and an event counter from the communica-
tion register of the controller. The higher level control system can detect by
means of this counter if the controller has accurately processed the messages.

Every time a message is processed successfully, the counter counts up. It does
not count up after exception responses or counter requests.

Structure of the request

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x0002
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x0B
Structure of the response

The response contains a 2-byte status word and a 2-byte event counter. The
status word consists of zeros.

Byte Field name Example


.....
Byte 7 MODBUS function code 0x10
Byte 8, 9 Status 0x0000
Byte 10, 11 Event count 0x0003
The event counter shows that 3 (0x0003) events were counted.

Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x85
Byte 8 Exception code 0x01 or 0x02

a300003
Appendix A: The MODBUS Protocol 31

6.8 FC15 (Force Multiple Coils)


This function is used to set multiple output bits to 1 or 0. The maximum num-
ber is 256 bits.

Structure of the request

The address of the first bit is 0. The request message specifies the bits to be
set. The required state (1 or 0) of the bit is determined by the content of the re-
quest data field.

In this example, 16 bits are set starting with address 0. The request contains 2
bytes with the value 0xA5F0, i.e., 1010 0101 1111 0000 binary.

The first byte assigns the 0xA5 to address 7 to 0, 0 being the least significant
bit. The next byte assigns 0xF0 to address 15 to 8, 8 being the least significant
bit.

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x0009
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x0F
Byte 8, 9 Reference number 0x0000
Byte 10, 11 Bit count 0x0010
Byte 12 Byte count 0x02
Byte 13 Data byte1 0xA5
Byte 14 Data byte2 0xF0
Structure of the response

Byte Field name Example


.....
Byte 7 MODBUS function code 0x0F
Byte 8, 9 Reference number 0x0000
Byte 10, 11 Bit count 0x0010
Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x8F
Byte 8 Exception code 0x01 or 0x02

a300003
32 Appendix A: The MODBUS Protocol

6.9 FC16 (Write multiple registers)


This function writes values to a number of output words (also output regis-
ters).

Structure of the requests

The address of the first register is 0.

The request message specifies the registers to be set. The data is transmitted as
two bytes per register.

Example: The data in the registers 0 and 1 is written.

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x000B
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x10
Byte 8, 9 Reference number 0x0000
Byte 10, 11 Word count 0x0002
Byte 12 Byte count 0x04
Byte 13, 14 Register value 1 0x1234
Byte 15, 16 Register value 2 0x2345
Structure of the response

Byte Field name Example


.....
Byte 7 MODBUS function code 0x10
Byte 8, 9 Reference number 0x0000
Byte 10, 11 Word count 0x0002
Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x85
Byte 8 Exception code 0x01 or 0x02

a300003
Appendix A: The MODBUS Protocol 33

6.10 FC22 (Mask Write Register)


This function manipulates bits within a register.

Structure of the requests

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 length field 0x0002
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x16
Byte 8-9 Reference number 0x0000
Byte 10-11 AND mask 0x0000
Byte 12-13 OR mask 0xAAAA
Structure of the response

Byte Field name Example


.....
Byte 7 MODBUS function code 0x10
Byte 8-9 Reference number 0x0000
Byte 10-11 AND mask 0x0000
Byte 12-13 OR mask 0xAAAA
Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x85
Byte 8 Exception code 0x01 or 0x02

a300003
34 Appendix A: The MODBUS Protocol

6.11 FC23 (Read/Write multiple registers)


This function reads register values and writes values to a number of output
words (also output registers).

Structure of the requests

Example: the data in register 3 are set to 0x0123 and the values 0x1 and
0x0004 are read from the registers 0 and 5678.

Byte Field name Example


Byte 0, 1 Transaction identifier 0x0000
Byte 2, 3 Protocol identifier 0x0000
Byte 4, 5 Length field 0x000F
Byte 6 Unit identifier 0x01 not used
Byte 7 MODBUS function code 0x17
Byte 8-9 Reference number for read 0x0000
Byte 10-11 Word count for read (1-125) 0x0002
Byte 12-13 Reference number for write 0x0003
Byte 14-15 Word count for write (1-100) 0x0001
Byte 16 Byte count 0x02
(B = 2 x word count for write)
Byte Register values 0x0123
17-(B+16)
Structure of the response

Byte Field name Example


....
Byte 7 MODBUS function code 0x17
Byte 8 Byte count 0x04
(B = 2 x word count for read)
Byte 9- Register values 0x0004
(B+1) 0x5678

Structure of the exception

Byte Field name Example


.....
Byte 7 MODBUS function code 0x97
Byte 8 Exception code 0x01 or 0x02

a300003
Appendix B: Device-specific Process Images 35

7 Appendix B: Device-specific Process Images


7.1 Fieldbus Coupler 750-342
7.1.1 Process image of the 750-342
The 750-342 can process a maximum of 3 incoming MODBUS TCP connec-
tions. The MODBUS connection Watchdog is deactivated when delivered.

In addition to the WAGO basic MODBUS services, the 750-342 also supports
the function code FC7 Read exception status.

FC Name Description
FC1 Read coils Re-read several digital outputs
FC2 Read inputs discrete Read several digital inputs
FC3 Read holding registers Read several analog inputs (and outputs)
FC4 Read input registers Read several analog inputs (and outputs)
FC5 Write coil Write a single digital output
FC6 Write single register Write a single analog output
FC7 Read exception status Read the first 8 digital outputs
FC11 Get comm event counter Communication event counter
FC15 Force multiple coils Write several digital outputs
FC16 Write multiple registers Writing several analog outputs
FC23 Read/write multiple registers Read/write operation to analog inputs/outputs

7.1.2 Register Services of the 750-342


Register services are used to determine or change the statuses of complex and
digital I/O modules.

a300003
36 Appendix B: Device-specific Process Images

7.1.2.1 Read registers with FC3 and FC4:

750-342: MODBUS vs IEC 61131 Addresses for FC3 and FC4


MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %IW0 Physical input area
... 255 ... 0x00FF ... %IW255
256 0x0100 - MODBUS Exception:
... 511 ... 0x01FF Illegal data address
512 0x0200 %QW0 Physical output area
... 767 ... 0x02FF ... %QW255
768 0x0300 - MODBUS Exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 - MODBUS Exception:
... 65535 ... 0xFFFF Illegal data address

7.1.2.2 Write registers with FC6 and FC16:

750-342: MODBUS vs IEC 61131 Addresses for FC6 and FC16


MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %QW0 Physical output area
... 255 ... 0x00FF ... %QW255
256 0x0100 - MODBUS Exception:
... 511 ... 0x01FF Illegal data address
512 0x0200 %QW0 Physical output area
... 767 ... 0x02FF ... %QW255
768 0x0300 - MODBUS Exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 - MODBUS Exception:
... 65535 ... 0xFFFF Illegal data address

a300003
Appendix B: Device-specific Process Images 37

7.1.3 Digital MODBUS services of the 750-342


The digital MODBUS services can only determine or change the state of digi-
tal I/O modules. Complex I/O modules are ignored or cannot be accessed.

7.1.3.1 Read coils with FC1 and FC2:

750-342: MODBUS Addresses for FC1 and FC2


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical input area First 512 digital inputs
... 511 ... 0x01FF
512 0x0200 Physical output area First 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

7.1.3.2 Write coils with FC5 and FC15:

750-342: MODBUS Addresses for FC5 and FC15


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical output area max 512 digital outputs
... 511 ... 0x01FF
512 0x0200 Physical output area max. 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

a300003
38 Appendix B: Device-specific Process Images

7.1.4 MODBUS Configuration Registers for the 750-342


The configuration registers make it possible to determine and in part change
the properties of the 750-342.

750-342: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]
4096 0x1000 1 R/W MODBUS Watchdog Time (multiple of 100 ms)
4097 0x1001 1 R/W MODBUS Watchdog coding screen 1-16
4098 0x1002 1 R/W MODBUS Watchdog coding screen 17-32
4099 0x1003 1 R/W MODBUS Watchdog-Trigger
4100 0x1004 1 R Minimum trigger time
4101 0x1005 1 R/W Stop MODBUS Watchdog (0xAAAA and 0x5555)
4102 0x1006 1 R MODBUS Watchdog status
4103 0x1007 1 R/W MODBUS Watchdog restart (0x0001)
4104 0x1008 1 R/W Stop MODBUS Watchdog (0x55AA or 0xAA55)
4105 0x1009 1 R/W Close MODBUS and HTTP port after time-out
4106 0x100A 1 R/W Start MODBUS Watchdog in Modicon Mode
4107 0x100B 1 W Save MODBUS Watchdog parameters

4128 0x1020 1 R LED error code


4129 0x1021 1 R LED error argument
4130 0x1022 1 R Number of analog outputs in the process image
[Bit]
4131 0x1023 1 R Number of analog inputs in the process image [Bit]
4132 0x1024 1 R Number of digital outputs in the process image
[Bit]
4133 0x1025 1 R Number of digital inputs in the process image [Bit]

4135 0x1027 1 R Execute internal bus cycle


4136 0x1028 1 R/W IP configuration: BootP(1) or FIX(0)
4137 0x1029 18 R MODBUS TCP statistics

4144 0x1030 1 R/W Activate MODBUS connection monitoring


4145 0x1031 3 R MAC ID or ETHERNET interface

8192 0x2000 1 R 0x0000 (Constant)


8193 0x2001 1 R 0xFFFF (Constant)
8194 0x2002 1 R 0x1234 (Constant)
8195 0x2003 1 R 0xAAAA (Constant)
8196 0x2004 1 R 0x5555 (Constant)
8197 0x2005 1 R 0x7FFF (Constant)
8198 0x2006 1 R 0x8000 (Constant)
8199 0x2007 1 R 0x3FFF (Constant)
8200 0x2008 1 R 0x4000 (Constant)

8208 0x2010 1 R Firmware release


8209 0x2011 1 R Series code (750)
8210 0x2012 1 R Device code (342)
8211 0x2013 1 R Specific firmware version (0xFFFF)
8212 0x2014 1 R Specific firmware version (0xFFFF)

8224 0x2020 1 .. 125 R Short device description


8225 0x2021 8 R Compile time of the firmware version

a300003
Appendix B: Device-specific Process Images 39

750-342: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]
8226 0x2022 8 R Compile date of the firmware version
8227 0x2023 32 R Version of the Firmware loader (FWL)

8240 0x2030 65 R Description of connected IO modules: 0-64

8245 0x2035 1 R/W Setting process image (Table 0 register 3)


8246 0x2036 1 .. 17 R Diagnostic information device

8256 0x2040 1 W Software reset (write 0x55AA or 0xAA55)

8260 0x2044 1 W Delete MODBUS Configuration file (write


0x55AA)

a300003
40 Appendix B: Device-specific Process Images

7.2 Fieldbus Coupler 750-352


7.2.1 Process image of the 750-352
The 750-352 can process a maximum of 15 incoming MODBUS TCP connec-
tions. The MODBUS connection Watchdog is deactivated when delivered.

In addition to the WAGO basic MODBUS services, the


750-352 also supports the function code FC22 Mask write.

FC Name Description
FC1 Read coils Re-read several digital outputs
FC2 Read inputs discrete Read several digital inputs
FC3 Read holding registers Read several analog inputs (and outputs)
FC4 Read input registers Read several analog inputs (and outputs)
FC5 Write coil Write a single digital output
FC6 Write single register Write a single analog output
FC11 Get comm event counter Communication event counter
FC15 Force multiple coils Write several digital outputs
FC16 Write multiple registers Writing several analog outputs
FC22 Mask write Manipulation of single bits in a register
FC23 Read/write multiple registers Read/write operation to analog inputs/outputs

a300003
Appendix B: Device-specific Process Images 41

7.2.2 Register Services of the 750-352


7.2.2.1 Read registers with FC3 and FC4:

750-352: MODBUS vs. IEC 61131 Addresses for FC3 and FC4
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %IW0 Physical input area (1)
... 255 ... 0x00FF ... %IW255 First 256 words of physical input data
256 0x0100 - MODBUS exception:
... 511 ... 0x01FF Illegal data address
512 0x0200 %QW0 Physical output area (1)
... 767 ... 0x02FF ... %QW255 First 256 words of physical output data
768 0x0300 - MODBUS Exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 - MODBUS Exception:
... 24575 ... 0x5FFF Illegal data address
24576 0x6000 %IW256 Physical input area (2)
... 25339 ... 0x62FB ... %IW1020 Additional 764 words physical input data
25340 0x62FC - MODBUS Exception:
... 28671 ... 0x6FFF Illegal data address
28672 0x7000 %QW256 Physical output area (2)
... 29435 ... 0x72FB ... %QW1020 Additional 764 words physical output data
29436 0x72FC - MODBUS Exception:
... 65535 ... 0xFFFF Illegal data address
7.2.2.2 Write registers with FC6 and FC16:

750-341: MODBUS vs. IEC 61131 Addresses for FC6 and FC16
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %QW0 Physical output area (1)
... 255 ... 0x00FF ... %QW255 First 256 words of physical output data
256 0x0100 - MODBUS exception:
... 511 ... 0x01FF Illegal data address
512 0x0200 %QW0 Physical output area (1)
... 767 ... 0x02FF ... %QW255 First 256 words of physical output data
768 0x0300 - MODBUS Exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 - MODBUS Exception:
... 24575 ... 0x5FFF Illegal data address
24576 0x6000 %QW256 Physical output area (2)
... 25339 ... 0x62FB ... %QW1020 Additional 764 words physical output data
25340 0x62FC - MODBUS Exception:
... 28671 ... 0x6FFF Illegal data address
28672 0x7000 %QW256 Physical output area (2)
... 29435 ... 0x72FB ... %QW1020 Additional 764 words physical output data
29437 0x72FC - MODBUS Exception:
... 65535 ... 0xFFFF Illegal data address

a300003
42 Appendix B: Device-specific Process Images

7.2.3 Digital MODBUS services of the 750-352


The digital MODBUS services can only determine or change the state of digi-
tal I/O modules. Complex I/O modules are ignored or cannot be accessed.

7.2.3.1 Read coils with FC1 and FC2:

750-341: MODBUS Addresses for FC1 and FC2


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical input area (1) First 512 digital inputs
... 511 ... 0x01FF
512 0x0200 Physical output area (1) First 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 - MODBUS Exception:
... 32767 ... 0x7FFF Illegal data address
32768 0x8000 Physical input area (2) Starts with the 513th and ends with
... 34295 ... 0x85F7 the 2039th digital input
34296 0x85F8 MODBUS exception:
... 36863 ... 0x8FFF Illegal data address
36864 0x9000 Physical output area (2) Starts with the 513th and ends with
... 38391 ... 0x95F7 the 2039th digital output
38392 0x95F8 MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

7.2.3.2 Write coils with FC5 and FC15:

750-341: MODBUS Addresses for FC1 and FC2


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical output area (1) First 512 digital outputs
... 511 ... 0x01FF
512 0x0200 Physical output area (1) First 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 - MODBUS Exception:
... 32767 ... 0x7FFF Illegal data address
32768 0x8000 Physical output area (2) Starts with the 513th and ends with
... 34295 ... 0x85F7 the 2039th digital output
34296 0x85F8 MODBUS exception:
... 36863 ... 0x8FFF Illegal data address
36864 0x9000 Physical output area (2) Starts with the 513th and ends with
... 38391 ... 0x95F7 the 2039th digital output
38392 0x95F8 MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

a300003
Appendix B: Device-specific Process Images 43

7.3 Fieldbus Coupler 767-1301


7.3.1 Process Image of 767-1301
The 767-1301 can process a maximum of 15 incoming MODBUS TCP con-
nections. The MODBUS connection Watchdog is deactivated when delivered.

The 767-1301 has two operating modes for MODBUS: V1 and V2.
In the default state, V1 is active, which behaves similar to the MODBUS im-
plementation in the 750 series. For compatibility reasons, V2 is included with
firmware Release 1 and can be activated via the Web-Based Management as
required.

FC Name Description
FC1 Read coils Re-read several digital outputs
FC2 Read inputs discrete Read several digital inputs
FC3 Read holding registers Read several analog inputs (and outputs)
FC4 Read input registers Read several analog inputs (and outputs)
FC5 Write coil Write a single digital output
FC6 Write single register Write a single analog output
FC11 Get comm event counter Communication event counter
FC15 Force multiple coils Write several digital outputs
FC16 Write multiple registers Writing several analog outputs
FC22 Mask write Manipulation of single bits in a register
FC23 Read/write multiple registers Read/write operation to analog inputs/outputs

a300003
44 Appendix B: Device-specific Process Images

7.3.2 Register Services of 767-1301


7.3.2.1 Read registers with FC3, FC4 and FC23:

767-1301: MODBUS vs. IEC 61131 Addresses for FC3, FC4 and FC23
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %IW0 Physical input area (1)
... 255 ... 0x00FF ... %IW255 First 256 words of physical input data
256 0x0100 - MODBUS exception:
... 511 ... 0x01FF Illegal data address
512 0x0200 %QW0 Physical output area (1)
... 767 ... 0x02FF ... %QW255 First 256 words of physical output data
768 0x0300 - MODBUS Exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 - MODBUS Exception:
... 24575 ... 0x5FFF Illegal data address
24576 0x6000 %IW256 Physical input area (2)
... 25339 ... 0x62FB ... %IW1020 Additional 764 words physical input data
25340 0x62FC - MODBUS Exception:
... 28671 ... 0x6FFF Illegal data address
28672 0x7000 %QW256 Physical output area (2)
... 29435 ... 0x72FB ... %QW1020 Additional 764 words physical output data
29436 0x72FC - MODBUS Exception:
... 65535 ... 0xFFFF Illegal data address
7.3.2.2 Write registers with FC6, FC16, FC22, FC23:

767-1301: MODBUS vs. IEC 61131 Addresses for FC6, FC16, FC22, FC23
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %QW0 Physical output area (1)
... 255 ... 0x00FF ... %QW255 First 256 words of physical output data
256 0x0100 - MODBUS exception:
... 511 ... 0x01FF Illegal data address
512 0x0200 %QW0 Physical output area (1)
... 767 ... 0x02FF ... %QW255 First 256 words of physical output data
768 0x0300 - MODBUS Exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 - MODBUS Exception:
... 24575 ... 0x5FFF Illegal data address
24576 0x6000 %QW256 Physical output area (2)
... 25339 ... 0x62FB ... %QW1020 Additional 764 words physical output data
25340 0x62FC - MODBUS Exception:
... 28671 ... 0x6FFF Illegal data address
28672 0x7000 %QW256 Physical output area (2)
... 29435 ... 0x72FB ... %QW1020 Additional 764 words physical output data
29437 0x72FC - MODBUS Exception:
... 65535 ... 0xFFFF Illegal data address

a300003
Appendix B: Device-specific Process Images 45

7.3.3 Digital MODBUS services of 767-1301


The digital MODBUS services can only determine or change the state of digi-
tal I/O modules. Complex I/O modules are ignored or cannot be accessed.

7.3.3.1 Read coils with FC1 and FC2:

767-1301: MODBUS Addresses for FC1 and FC2


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical input area (1) First 512 digital inputs
... 511 ... 0x01FF
512 0x0200 Physical output area (1) First 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 - MODBUS Exception:
... 32767 ... 0x7FFF Illegal data address
32768 0x8000 Physical input area (2) Starts with the 513th and ends with
... 34295 ... 0x85F7 the 2039th digital input
34296 0x85F8 MODBUS exception:
... 36863 ... 0x8FFF Illegal data address
36864 0x9000 Physical output area (2) Starts with the 513th and ends with
... 38391 ... 0x95F7 the 2039th digital output
38392 0x95F8 MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

7.3.3.2 Write coils with FC5 and FC15:

767-1301: MODBUS Addresses for FC1 and FC2


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical output area (1) First 512 digital outputs
... 511 ... 0x01FF
512 0x0200 Physical output area (1) First 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 - MODBUS Exception:
... 32767 ... 0x7FFF Illegal data address
32768 0x8000 Physical output area (2) Starts with the 513th and ends with
... 34295 ... 0x85F7 the 2039th digital output
34296 0x85F8 MODBUS exception:
... 36863 ... 0x8FFF Illegal data address
36864 0x9000 Physical output area (2) Starts with the 513th and ends with
... 38391 ... 0x95F7 the 2039th digital output
38392 0x95F8 MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

a300003
46 Appendix B: Device-specific Process Images

7.3.4 MODBUS configuration register of 767-1301


The configuration registers make it possible to determine and in part change
the properties of the 750-1301.

767-1301: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]
4096 0x1000 1 R/W MODBUS Watchdog Time (multiple of 100 ms)
4097 0x1001 1 R/W MODBUS Watchdog coding screen 1-16
4098 0x1002 1 R/W MODBUS Watchdog coding screen 17-32
4099 0x1003 1 R/W MODBUS Watchdog-Trigger
4100 0x1004 1 R Minimum trigger time
4101 0x1005 1 R/W Stop MODBUS Watchdog (0xAAAA and 0x5555)
4102 0x1006 1 R MODBUS Watchdog status
4103 0x1007 1 R/W MODBUS Watchdog restart (0x0001)
4104 0x1008 1 R/W Stop MODBUS Watchdog (0x55AA or 0xAA55)
4105 0x1009 1 R/W Close MODBUS and HTTP port after time-out
4106 0x100A 1 R/W Start MODBUS Watchdog in Modicon Mode
4107 0x100B 1 W Save MODBUS Watchdog parameters

4128 0x1020 1-2 R LED error code, LED error argument


4129 0x1021 1 R LED error argument
4130 0x1022 1-4 R Number of analog outputs in the process image
[Bit]
4131 0x1023 1-3 R Number of analog inputs in the process image [Bit]
4132 0x1024 1-2 R Number of digital outputs in the process image
[Bit]
4133 0x1025 1 R Number of digital inputs in the process image [Bit]

4136 0x1028 1 R/W IP configuration: BootP(1), DHCP(2) or FIX(4)


4137 0x1029 9 R MODBUS TCP statistics
4138 0x102A 1 R Number of established MODBUS TCP connections

4144 0x1030 1 R/W MODBUS TCP time-out (multiple of 100 ms)


4145 0x1031 3 R MAC ID or ETHERNET interface

8192 0x2000 1 R 0x0000 (Constant)


8193 0x2001 1 R 0xFFFF (Constant)
8194 0x2002 1 R 0x1234 (Constant)
8195 0x2003 1 R 0xAAAA (Constant)
8196 0x2004 1 R 0x5555 (Constant)
8197 0x2005 1 R 0x7FFF (Constant)
8198 0x2006 1 R 0x8000 (Constant)
8199 0x2007 1 R 0x3FFF (Constant)
8200 0x2008 1 R 0x4000 (Constant)

8208 0x2010 1 R Firmware index


8209 0x2011 1 R Series designation (767)
8210 0x2012 1 R Device designation (1301)
8211 0x2013 1 R Major firmware version
8212 0x2014 1 R Minor firmware version

8224 0x2020 16 R Short device description


8225 0x2021 8 R Compile time of the firmware version

a300003
Appendix B: Device-specific Process Images 47

767-1301: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]
8226 0x2022 8 R Compile date of the firmware version
8227 0x2023 32 R Firmware loader version (FWL)

8240 0x2030 65 R Description of connected IO modules: 0-64

8256 0x2040 1 W Software reset (write 0x55AA or 0xAA55)


8257 0x2041 1 W Formatting the file system
8258 0x2042 1 W Extracting the file system
8259 0x2043
8345 0x2099 1 R/W MODBUS compatibility mode
1 = MODBUS V1 (similar to 750 series)
2 = MODBUS V2

a300003
48 Appendix B: Device-specific Process Images

7.4 Programmable Fieldbus Controller 750-842


7.4.1 Process Image of the 750-842
The 750-842 can process a maximum of 3 incoming MODBUS TCP connec-
tions at the same time. The MODBUS connection Watchdog is deactivated
when delivered. The PLC program can establish a maximum of two TCP con-
nections to remote servers.

The 750-842 supports the following MODBUS service:

FC Name Description
FC1 Read coils Re-read several digital outputs
FC2 Read inputs discrete Read several digital inputs
FC3 Read holding registers Reading several analog inputs (and outputs)
FC4 Read input registers Reading several analog inputs (and outputs)
FC5 Write coil Write a single digital output
FC6 Write single register Write a single analog output
FC7 Read exception status Read the first 8 digital outputs
FC11 Get comm event counter Communication event counter
FC15 Force multiple coils Write several digital outputs
FC16 Write multiple registers Write several analog outputs
FC23 Read/write multiple registers Read/write operation to analog inputs/outputs

a300003
Appendix B: Device-specific Process Images 49

By using the SET_DIGITAL_INPUT_OFFSET and


SET_DIGITAL_OUTPUT_OFFSET function blocks from the
mod_com.lib library, it is possible to specify the start addresses of the first
digital I/O modules that are connected to WAGO ETHERNET controllers.
This allows for space for later extensions. The OFFSETs are given in bytes.

Memory MODBUS PLC Description


area access access
Physical. Input read read Physical inputs
(%IW0 ... %IW255)
Physical output read/write read/write Physical outputs
(%QW0 ... %QW255)
PFC IN read/write read Volatile PLC input variables
(%IW256 ... %IW511)
PFC OUT read read/write Volatile PLC output variables
(%QW256 ... %QW511)
Configuration read/(write) --- Configuration Registers
register
RETAIN read/write read/write 8kB residual memory
(NOVRAM) (%MW0 ... %MW4095)

Note that the physical outputs can be changed both via the MODBUS services
and the PLC program.

A mnemonic for this behavior could be: The last one wins.

In the 750-842, the flag variables and the retain variables share the same area
in the NOVRAM.
Overlapping could result in unpredictable behavior.
Only use one of the two types in your CODESYS project.

a300003
50 Appendix B: Device-specific Process Images

7.4.2 Register services of the 750-842


7.4.2.1 Read registers with FC3, FC4 and FC23:

750-842: MODBUS vs IEC 61131 Addresses for FC3, FC4 and FC23
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %IW0 Physical input area
... 255 ... 0x00FF ... %IW255
256 0x0100 %QW256 PFC OUT area
... 511 ... 0x01FF ... %QW511 Volatile PLC output variables
512 0x0200 %QW0 Physical output area
... 767 ... 0x02FF ... %QW255
768 0x0300 %IW256 PFC IN area
... 1023 ... 0x03FF ... %IW511 Volatile PLC input variables
1024 0x0400 - MODBUS exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 %MW0 NOVRAM
... 16383 ... 0x3FFF ... %MW4095 8kB retain memory
16384 0x4000 - MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

7.4.2.2 Write registers with FC6, FC16 and FC23:

750-842: MODBUS vs IEC 61131 Addresses for FC6, FC16


MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %QW0 Physical output area
... 255 ... 0x00FF ... %QW255
256 0x0100 %IW256 PFC IN area
... 511 ... 0x01FF ... %IW511 Volatile PLC input variables
512 0x0200 %QW0 Physical output area
... 767 ... 0x02FF ... %QW255
768 0x0300 %IW256 PFC OUT area
... 1023 ... 0x03FF ... %IW511 Volatile PLC output variables
1024 0x0400 - MODBUS exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 8191 ... 0x1FFF (see manual for details)
8192 0x2000 - MODBUS exception:
... 12287 ... 0x2FFF Illegal data address
12288 0x3000 %MW0 NOVRAM
... 16383 ... 0x3FFF ... %MW4095 8kB retain memory
16384 0x4000 - MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

a300003
Appendix B: Device-specific Process Images 51

7.4.3 Digital MODBUS services of the 750-842


The digital MODBUS services can only determine or change the state of digi-
tal I/O modules. Complex I/O modules are ignored or cannot be accessed.

In the PFC-IN and PFC-OUT area, as well as in the flag area (NVRAM), the
coil services and register services access the same memory locations.

Since the address space is limited by the data type WORD, it is not possible
to address all bits in the 8kB flag area via coil services.

7.4.3.1 Read coils with FC1 and FC2:

750-842: MODBUS Addresses for FC1 and FC2


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical input area First 512 digital inputs
... 511 ... 0x01FF
512 0x0200 Physical output area First 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 - MODBUS exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 %QX256.0 PFC OUT area
... 8191 ... 0x1FFF ...%QX511.15 Volatile PLC output variables
8192 0x2000 %IX256.0 PFC IN area
... 12287 ... 0x2FFF ...%IX511.15 Volatile PLC input variables
12288 0x3000 %MX0.0 NOVRAM
... 65535 ... 0xFFFF ... %MX3327.15 Retain memory

7.4.3.2 Write coils with FC5 and FC15:

750-842: MODBUS Addresses for FC5 and FC15


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical output area max 512 digital outputs
... 511 ... 0x01FF
512 0x0200 Physical output area max 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 - MODBUS exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 %IX256.0 PFC IN area
... 8191 ... 0x1FFF ...%IX511.15 Volatile PLC input variables
8192 0x2000 %IX256.0 PFC IN area
... 12287 ... 0x2FFF ...%IX511.15 Volatile PLC input variables
12288 0x3000 %MX0.0 NOVRAM
... 65535 ... 0xFFFF ... %MX3327.15 Retain memory

a300003
52 Appendix B: Device-specific Process Images

7.4.4 MODBUS Configuration Registers for the 750-842


The configuration registers make it possible to determine and in part change
the properties of the 750-842.

750-842: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]
4096 0x1000 1 R/W MODBUS Watchdog Time (multiple of 100 ms)
4097 0x1001 1 R/W MODBUS Watchdog coding mask 1-16
4098 0x1002 1 R/W MODBUS Watchdog coding mask 17-32
4099 0x1003 1 R/W MODBUS Watchdog-Trigger
4100 0x1004 1 R Minimum trigger time
4101 0x1005 1 R/W Stop MODBUS Watchdog (0xAAAA and 0x5555)
4102 0x1006 1 R MODBUS Watchdog status
4103 0x1007 1 R/W MODBUS Watchdog restart (0x0001)
4104 0x1008 1 R/W Stop MODBUS Watchdog (0x55AA or 0xAA55)
4105 0x1009 1 R/W Close MODBUS and HTTP port after time-out
4106 0x100A 1 R/W Start MODBUS Watchdog in Modicon Mode
4107 0x100B 1 W Save MODBUS Watchdog parameters

4128 0x1020 1 R LED error code


4129 0x1021 1 R LED error argument
4130 0x1022 1 R Number of analog outputs in the process image
[Bit]
4131 0x1023 1 R Number of analog inputs in the process image [Bit]
4132 0x1024 1 R Number of digital outputs in the process image
[Bit]
4133 0x1025 1 R Number of digital inputs in the process image [Bit]

4135 0x1027 1 R Execute internal bus cycle


4136 0x1028 1 R/W IP configuration: BootP(1) or FIX(0)
4137 0x1029 18 R MODBUS TCP statistics

4144 0x1030 1 R/W Activate MODBUS connection monitoring


4145 0x1031 3 R MAC ID or ETHERNET interface

4160 0x1040 1 R/W Process data interface

8192 0x2000 1 R 0x0000 (Constant)


8193 0x2001 1 R 0xFFFF (Constant)
8194 0x2002 1 R 0x1234 (Constant)
8195 0x2003 1 R 0xAAAA (Constant)
8196 0x2004 1 R 0x5555 (Constant)
8197 0x2005 1 R 0x7FFF (Constant)
8198 0x2006 1 R 0x8000 (Constant)
8199 0x2007 1 R 0x3FFF (Constant)
8200 0x2008 1 R 0x4000 (Constant)

8208 0x2010 1 R Firmware release


8209 0x2011 1 R Series code (750)
8210 0x2012 1 R Device code (842)
8211 0x2013 1 R Specific firmware version (0xFFFF)
8212 0x2014 1 R Specific firmware version (0xFFFF)

a300003
Appendix B: Device-specific Process Images 53

750-842: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]

8224 0x2020 1 .. 125 R Short device description


8225 0x2021 8 R Compile time of the firmware version
8226 0x2022 8 R Compile date of the firmware version
8227 0x2023 32 R Firmware loader version (FWL)

8240 0x2030 65 R Description of connected IO modules: 0-64

8245 0x2035 1 R/W Setting process image (Table 0 register 3)


8246 0x2036 1 .. 17 R Diagnostic information device

8256 0x2040 1 W Software reset (write 0x55AA or 0xAA55)

8260 0x2044 1 W Delete MODBUS Configuration file (write


0x55AA)

a300003
54 Appendix B: Device-specific Process Images

7.5 Programmable Fieldbus Controller 750-88x


7.5.1 Process Image of the 750-88x
The 750-88x series controllers (750-880, 750-881, 750-882, 750-885) can pro-
cess a maximum of 15 incoming MODBUS TCP connections at the same
time. The MODBUS connection Watchdog is deactivated when delivered.

RETAIN memory is non-volatile memory, i.e., in the event of a power failure, all
flag memory and variable values explicitly defined with VAR RETAIN are re-
tained.

a300003
Appendix B: Device-specific Process Images 55

The 32 kByte memory range is normally divided into a 16 kByte addressable


range for bit memory (%MW0 ... %MW8191) and a 16 kByte retain area for vari-
ables without memory space addressing or for variables that are explicitly defined
by VAR RETAIN.

If more than 16 kBytes should be used as addressable memory for flags, a cor-
responding adjustment to memory allocation can be made in CODESYS via
the target system settings.

1 Size of the addressable flag area


(16#4000 16 kByte 8192 flag words)

2 Size of the non-addressable retain memory


(16#4000 16 kByte retain memory)

3 Start address of the addressable flag area


(cannot be edited)

4 Start address of the non-addressable retain memory


 Start address flag + flag size
16#20000000 + 16#4000 = 16#20004000

a300003
56 Appendix B: Device-specific Process Images

Example configuration with 24 kByte of addressable flag memory:

1 Size of the addressable flag area


(16#6000 24 kByte 12288 flag words)

2 Size of the non-addressable retain memory


(16#2000 8 kByte retain memory)

3 Start address of the addressable flag area


(cannot be edited)

4 Start address of the non-addressable retain memory


 Start address flag + flag size
16#20000000 + 16#6000 = 16#20006000

Do not exceed the size of the retain memory!


Information The size totals from the sizes specified for the flag area and for the retain area
must not exceed the total size of the memory:
Flag size + retain size must always result in 16 kByte (16#8000)!

a300003
Appendix B: Device-specific Process Images 57

The 750-88x series controllers support the following MODBUS services:

FC Name Description
FC1 Read coils Re-read several digital outputs
FC2 Read inputs discrete Read several digital inputs
FC3 Read holding registers Read several analog inputs (and outputs)
FC4 Read input registers Read several analog inputs (and outputs)
FC5 Write coil Write a single digital output
FC6 Write single register Write a single analog output
FC11 Get comm event counter Communication event counter
FC15 Force multiple coils Write several digital outputs
FC16 Write multiple registers Writing several analog outputs
FC22 Mask write Manipulation of single bits in a register
FC23 Read/write multiple registers Read/write operation to analog inputs/outputs
By using the SET_DIGITAL_INPUT_OFFSET and
SET_DIGITAL_OUTPUT_OFFSET function blocks from the
mod_com.lib library, it is possible to specify the start addresses of the first
digital I/O modules that are connected to WAGO ETHERNET controllers.
This allows for space for later extensions. The OFFSETs are given in bytes.
However, the effectiveness is limited to the PLC. The MODBUS slave ignores
the digital offset.

Memory MODBUS PLC Description


area access access
Physical. Input(1) read read Physical inputs
(%IW0 ... %IW255)
Physical Output(1) read/[write]*1) read/[write]*1) Physical outputs
(%QW0 ... %QW255)
PFC IN read/write read Volatile PLC input variables
(%IW256 ... %IW511)
PFC OUT read read/write Volatile PLC output variables
(%QW256 ... %QW511)
Configuration read/(write) --- Configuration Registers
register
NOVRAM read/write read/write 8 kB retain memory (max 32 kB)
Retain memory (%MW0 ... %MW8191)
Physical. Input(2) read read Physical inputs
(%IW512 ... %IW1275)
Physical Output(2) read/[write]*1) read/[write]*1) Physical outputs
(%QW512 ... %QW1275)
[]*1) The /etc/EA-conf.xml file specifies the write permission

Another feature of the 750-88x controller is that write permissions can or must
be assigned to each I/O module.
The physical outputs can be changed either via MODBUS services or via the
PLC program. The /etc/EA-conf.xml file specifies the write permissions.
If the file is missing or if the number of configured I/O modules differs from
the number of I/O modules actually connected, then write permissions are giv-
en to the MODBUS services.
The /etc/EA-conf.xml file is created automatically when a CODESYS con-
trol configuration is created. It controls the write permissions on the I/O mod-
ule level.
A mnemonic for this behavior could be: There can be only one.

a300003
58 Appendix B: Device-specific Process Images

In the 750-88x, the flag variables and the retain variables share the same area
in the 32 KB NOVRAM. The default configuration includes 16 kB for flag
variables and 16 kB for retain variables. Overlapping, as in the case with 750-
842, is not possible.
The partitioning of the 24 kB NOVRAM can be changed in the CODESYS
target system settings.

When using SysLibSocket, the maximum number of TCP socket connec-


tions that can be generated from a PLC program is almost unlimited. In the
Ethernet.lib the maximum number of TCP socket connections is limited to
5.

7.5.2 Register Services of the 750-88x


7.5.2.1 Read registers with FC3, FC4 and FC23:

750-88x: MODBUS vs IEC 61131 Addresses for FC3, FC4 and FC23
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %IW0 Physical input area (1)
... 255 ... 0x00FF ... %IW255 First 256 words of physical input data
256 0x0100 %QW256 PFC OUT area
... 511 ... 0x01FF ... %QW511 Volatile PLC output variables
512 0x0200 %QW0 Physical output area (1)
... 767 ... 0x02FF ... %QW255 First 256 words of physical output data
768 0x0300 %IW256 PFC IN area
... 1023 ... 0x03FF ... %IW511 Volatile PLC input variables
1024 0x0400 - MODBUS exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 %MW0 NOVRAM
... 24575 ... 0x5FFF ... %MW12287 24 kB
24576 0x6000 %IW512 Physical input area (2)
... 25339 ... 0x62FC ... %IW1275 Additional 764 words physical input data
25340 0x62FD - MODBUS Exception:
... 28671 ... 0x6FFF Illegal data address
28672 0x7000 %QW512 Physical output area (2)
... 29435 ... 0x72FB ... %QW1275 Additional 764 words physical output data
29436 0x72FC - MODBUS Exception:
... 32767 ... 0x7FFF Illegal data address
32768 0x8000 %MW12288 NOVRAM
... 36863 0x8FFF ..%MW16383 8 kB
36864 0x9000 MODBUS exception:
...65535 ...0xFFFF Illegal data address

a300003
Appendix B: Device-specific Process Images 59

7.5.2.2 Write registers with FC6, FC16, FC22 and FC23:

750-88x: MODBUS vs IEC 61131 Addresses for FC6, FC16, FC22 and FC23
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %QW0 Physical output area (1)
... 255 ... 0x00FF ... %QW255 First 256 words of physical output data
256 0x0100 %IW256 PFC IN area
... 511 ... 0x01FF ... %IW511 Volatile PLC input variables
512 0x0200 %QW0 Physical output area (1)
... 767 ... 0x02FF ... %QW255 First 256 words of physical output data
768 0x0300 %IW256 PFC IN area
... 1023 ... 0x03FF ... %IW511 Volatile PLC input variables
1024 0x0400 - MODBUS exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 - Configuration register
... 12287 ... 0x2FFF (see manual for details)
12288 0x3000 %MW0 NOVRAM
... 24575 ... 0x5FFF ... %MW12287 8 kB retain memory (max. 24 kB)
24576 0x6000 %QW512 Physical output area (2)
... 25339 ... 0x62FC ... %QW1275 Additional 764 words physical output data
25340 0x62FD - MODBUS Exception:
... 28671 ... 0x6FFF Illegal data address
28672 0x7000 %QW512 Physical output area (2)
... 29435 ... 0x72FC ... %QW1275 Additional 764 words physical output data
29436 0x72FD MODBUS Exception:
... 32767 ... 0x7FFF Illegal data address
32768 0x8000 %MW12288 NOVRAM
...36863 ...0x8FFF ..%MW16383 8 kB
36864 0x9000 MODBUS exception:
...65535 ...0xFFFF Illegal data address

a300003
60 Appendix B: Device-specific Process Images

7.5.3 Digital MODBUS Services of the 750-88x


The digital MODBUS services can only determine or change the state of digi-
tal I/O modules. Complex I/O modules are ignored or cannot be accessed.

7.5.3.1 Read coils with FC1 and FC2:

750-88x: MODBUS Addresses for FC1 and FC2


MODBUS Address Memory Description
[dec] [hex] Area
0 6143 0x0000 Physical input area (1) First 512 digital inputs
... 0x01FF
512 0x0200 Physical output area (1) First 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 - MODBUS Exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 %QX256.0 PFC OUT area
... 8191 ... 0x1FFF ...%QX511.15 Volatile PLC output variables
8192 0x2000 %IX256.0 PFC IN area
... 12287 ... 0x2FFF ...%IX511.15 Volatile PLC input variables
12288 0x3000 %MX0.0 NOVRAM
... 32767 ... 0x7FFF ... %MX1279.15 Retain area (8 kB default)
32768 0x8000 Physical input area (2) Starts with the 513th and ends with
... 34295 ... 0x85F7 the 2039th digital input
34296 0x85F8 - MODBUS exception:
... 36863 ... 0x8FFF Illegal data address
36864 0x9000 Physical output area (2) Starts with the 513th and ends with
... 38391 ... 0x95F7 the 2039th digital output
38392 0x95F8 - MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

a300003
Appendix B: Device-specific Process Images 61

7.5.3.2 Write coils with FC5 and FC15:

750-88x: MODBUS Addresses for FC5 and FC15


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 Physical output area (1) First 512 digital outputs
... 511 ... 0x01FF
512 0x0200 Physical output area (1) First 512 digital outputs
... 1023 ... 0x03FF
1024 0x0400 - MODBUS Exception:
... 4095 ... 0x0FFF Illegal data address
4096 0x1000 %IX256.0 PFC IN area
... 8191 ... 0x1FFF ...%IX511.15 Volatile PLC input variables
8192 0x2000 %IX256.0 PFC IN area
... 12287 ... 0x2FFF ...%IX511.15 Volatile PLC input variables
12288 0x3000 %MX0.0 NOVRAM
... 32767 ... 0x7FFF ... %MX1279.15 Retain area
32768 0x8000 Physical output area (2) Starts with the 513th and ends with
... 34295 ... 0x85F7 the 2039th digital output
34296 0x85F8 - MODBUS exception:
... 36863 ... 0x8FFF Illegal data address
36864 0x9000 Physical output area (2) Starts with the 513th and ends with
... 38391 ... 0x95F7 the 2039th digital output
38392 0x95F8 - MODBUS exception:
... 65535 ... 0xFFFF Illegal data address

a300003
62 Appendix B: Device-specific Process Images

7.5.4 MODBUS Configuration Registers for the 750-88x


The configuration registers make it possible to determine and in part change
the properties of the 750-88x.

750-88x: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]
4096 0x1000 1 R/W MODBUS Watchdog Time (multiple of 100 ms)
4097 0x1001 1 R/W MODBUS Watchdog coding screen 1-16
4098 0x1002 1 R/W MODBUS Watchdog coding screen 17-32
4099 0x1003 1 R/W MODBUS Watchdog-Trigger
4100 0x1004 1 R Minimum trigger time
4101 0x1005 1 R/W Stop MODBUS Watchdog (0xAAAA and 0x5555)
4102 0x1006 1 R MODBUS Watchdog status
4103 0x1007 1 R/W MODBUS Watchdog restart (0x0001)
4104 0x1008 1 R/W Stop MODBUS Watchdog (0x55AA or 0xAA55)
4105 0x1009 1 R/W Close MODBUS and HTTP port after time-out
4106 0x100A 1 R/W Start MODBUS Watchdog in Modicon Mode
4107 0x100B 1 W Save MODBUS Watchdog parameters

4128 0x1020 1 R LED error code


4129 0x1021 1 R LED error argument
4130 0x1022 1 R Number of analog outputs in the process image
[Bit]
4131 0x1023 1 R Number of analog inputs in the process image [Bit]
4132 0x1024 1 R Number of digital outputs in the process image
[Bit]
4133 0x1025 1 R Number of digital inputs in the process image [Bit]

4136 0x1028 1 R/W IP configuration: BootP(1), DHCP(2) or FIX(4)


4137 0x1029 18 R MODBUS TCP statistics
4138 0x102A 1 R Number of established MODBUS TCP connections
4139 0x102B 1 W K-BUS reset

4144 0x1030 1 R/W Activate MODBUS connection monitoring


4145 0x1031 3 R MAC ID or ETHERNET interface

4149 0x1035 1 R/W Time offset RTC (Real Time Clock)


4150 0x1036 1 R/W Daylight Savings
4151 0x1037 1 1 MODBUS Response Delay (ms)

4176 0x1050 3 R Diagnostic information of connected IO modules

8192 0x2000 1 R 0x0000 (Constant)


8193 0x2001 1 R 0xFFFF (Constant)
8194 0x2002 1 R 0x1234 (Constant)
8195 0x2003 1 R 0xAAAA (Constant)
8196 0x2004 1 R 0x5555 (Constant)
8197 0x2005 1 R 0x7FFF (Constant)
8198 0x2006 1 R 0x8000 (Constant)
8199 0x2007 1 R 0x3FFF (Constant)
8200 0x2008 1 R 0x4000 (Constant)

8208 0x2010 1 R Firmware release

a300003
Appendix B: Device-specific Process Images 63

750-88x: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]
8209 0x2011 1 R Series code (750)
8210 0x2012 1 R Device code (841)
8211 0x2013 1 R Major firmware version
8212 0x2014 1 R Minor firmware version

8224 0x2020 1 .. 125 R Short device description


8225 0x2021 8 R Compile time of the firmware version
8226 0x2022 8 R Compile date of the firmware version
8227 0x2023 32 R Firmware loader version (FWL)

8240 0x2030 65 R Description of connected IO modules: 0-64


8241 0x2031 64 R Description of connected IO modules: 65-129
8242 0x2032 64 R Description of connected IO modules: 130-194
8243 0x2033 63 R Description of connected IO modules: 195-255

8245 0x2035 1 R/W Setting process image (Table 0 register 3)


8246 0x2036 1 .. 17 R Diagnostic information device

8256 0x2040 1 W Software reset (write 0x55AA or 0xAA55)


8257 0x2041 1 W Format Flash
8258 0x2042 1 W Extract file system
8259 0x2043 1 W Factory Settings

a300003
64 Appendix B: Device-specific Process Images

7.6 Programmable Fieldbus Controllers PFC200


This section contains the devices of the PFC200 series (750-8202, 750-8203,
750-8204, 750-8206) with CODESYS 2.3 runtime system.

The MODBUS slave integrated in the PFC200 must be activated and parame-
terized via the CODESYS controller configuration.

The MODBUS function is only active if a CODESYS project with MODBUS


activated is loaded to PFC200.

Direct access to the process image of the I/O modules via MODBUS is not
possible.

Further information about configuration the PFC200 MODBUS slave is avail-


able in the manual for the respective PFC200 model.

Note I/O modules not directly accessible via MODBUS.


Direct access to the process image of the I/O modules via MODBUS is not
possible. Only the PFC variables and flags are accessible via MODBUS.
Using a corresponding PLC program, data points of the I/O module can be
assigned to the MODBUS area.

a300003
Appendix B: Device-specific Process Images 65

7.6.1 Process Image of the PFC200

a300003
66 Appendix B: Device-specific Process Images

a300003
Appendix B: Device-specific Process Images 67

7.6.2 Register Services of the PFC200


7.6.2.1 Read registers with FC3, FC4 and FC23:

PFC200: MODBUS vs IEC 61131 Addresses for FC3, FC4 and FC23
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %IW1000 1000 PFC input words in the 2 kB
999 ... 0x03EF ... %IW1999
input process image
1000 0x03E8 %QW1000 1000 PFC output words in the 2 kB
... 1999 ... 0x07CF ... %QW1999
output process image
2000 0x07D0 MODBUS Exception:
4095 0x0FFF Illegal data address
4096 0x1000 Information and configuration register:
12287 0x2FFF Not all MODBUS addresses in this area are
valid. Valid MODBUS addresses are described
in the Section Configuration Registers.
12288 0x3000 %MW0 Flag area: 53248 register/word flags (104 kB)
65535 0xFFFF %MW53247 in the flag area

7.6.2.2 Write registers with FC6, FC16, FC22 and FC23:

PFC200: MODBUS vs IEC 61131 Addresses for FC6, FC16, FC22 and FC23
MODBUS Address IEC 61131 Description
[dec] [hex] Address
0 0x0000 %IW1000 1000 PFC input words in the 2 kB
999 ... 0x03EF ... %IW1999
input process image
1000 0x03E8 MODBUS exception:
... 1999 ... 0x07CF Illegal data address
2000 0x07D0 MODBUS Exception:
4095 0x0FFF Illegal data address
4096 0x1000 Information and configuration register:
12287 0x2FFF Not all MODBUS addresses in this area are
valid. Valid MODBUS addresses are described
in the Section Configuration Registers.
12288 0x3000 %MW0 Flag area: 53248 register/word flags (104 kB)
65535 0xFFFF %MW53247 in the flag area

a300003
68 Appendix B: Device-specific Process Images

7.6.3 Digital MODBUS services of the PFC200


The digital MODBUS services allow bitwise access to the first 768 bytes of
the process images.

7.6.3.1 Read coils with FC1 and FC2:

PFC200: MODBUS Addresses for FC1 and FC2


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 %IX1000.0 6144 PFC input bit variables in the
6143 ... 0x17FF %IX1383.15 first 384 words (768 bytes) of the 2
kB input process image
6144 0x1800 %QX1000.0 6144 PFC output bit variables in the
12287 ... 0x2FFF 1383.15 first 384 words (768 bytes) of the 2
kB MODBUS output process image
12288 0x3000 %MX0.0 Flag area: 53248 bit flags (6.5 kB)
... 65535 ... 0xFFFF %MX3327.15 in the bit-addressable flag area

7.6.3.2 Write coils with FC5 and FC15:

PFC200: MODBUS Addresses for FC5 and FC15


MODBUS Address Memory Description
[dec] [hex] Area
0 0x0000 %IX1000.0 6144 PFC input bit variables in the
6143 ... 0x17FF %IX1383.15 first 384 words (768 bytes) of the 2
kB input process image
6144 0x1800 MODBUS Exception:
12287 ... 0x2FFF Illegal data address
12288 0x3000 %MX0.0 Flag area: 53248 bit flags (6.5 kB)
... 65535 ... 0xFFFF %MX3327.15 in the bit-addressable flag area

a300003
Appendix B: Device-specific Process Images 69

7.6.3.3 MODBUS Configuration Registers of the PFC200

The configuration registers make it possible to determine and in part change


the properties of the PFC200.

PFC200: MODBUS Configuration Register for FC3, FC4, FC6 and FC16
MODBUS Address Length Access Description
[dec] [hex] [Word]
4130 0x1022 1 R Number of registers in
the output process image
4131 0x1023 1 R Number of registers in
the input process image
4132 0x1024 1 R Number of bits in
the output process image
4133 0x1025 1 R Number of bits in
the input process image

4136 0x1028 1 R IP configuration: BootP(1), DHCP(2) or


fixed, coded IP address(4)
4138 0x102A 1 R Number of established TCP connections
4144 0x1030 1 R/W MODBUS TCP time-out
4145 0x1031 3 R MAC ID or ETHERNET interface
4151 0x1037 1 R/W MODBUS TCP response delay
4160 0x1040 1 R PLC status

4352 0x1100 1 W Watchdog Command


4353 0x1101 1 R Watchdog Status
4354 0x1102 1 R/W Watchdog time-out
4355 0x1103 1 R/W Watchdog Config

8192 0x2000 1 R 0x0000 (Constant)


8193 0x2001 1 R 0xFFFF (Constant)
8194 0x2002 1 R 0x1234 (Constant)
8195 0x2003 1 R 0xAAAA (Constant)
8196 0x2004 1 R 0x5555 (Constant)
8197 0x2005 1 R 0x7FFF (Constant)
8198 0x2006 1 R 0x8000 (Constant)
8199 0x2007 1 R 0x3FFF (Constant)
8200 0x2008 1 R 0x4000 (Constant)

8208 0x2010 1 R Revision (Firmware Index)


8209 0x2011 1 R Series code
8210 0x2012 1 R Device code
8211 0x2013 1 R Major Firmware Version
8212 0x2014 1 R Minor Firmware Version
8213 0x2015 1 R MBS Version

a300003
70 Appendix C: Useful Tools

8 Appendix C: Useful Tools


8.1 CODESYS Controller Configuration
The CODESYS controller configuration provides convenience functions such
as node scan and automatic address calculation.
With the import and export function, external tools can be used to process the
controller configuration. That can be useful, for example, when the designa-
tions for the data points have to be applied from a CAE program (e.g., Eplan).

The advantage of the controller configuration is automatic calculation of the


IEC addresses:

In contract to manual addressing, variable names are not bound to an ad-


dress, but to the channel of the respective I/O module. As a result, the variable
name automatically changes if an I/O module is added or removed in the con-
troller configuration.

a300003
Appendix C: Useful Tools 71

PFC variables and flags can also be declared via the controller configuration:

a300003
72 Appendix C: Useful Tools

8.2 Wireshark
A helpful tool at start-up or troubleshooting in the ETHERNET is the open
source tool Wireshark. The tools is a network sniffer. The tool records the
data traffic of a network interface and makes the data available in the form of
individual packets.

Below is a screenshot of the Wireshark program.

You can also see the response telegram from the example. The filter default
tcp.port == 502 ensures that only the telegrams are displayed on MODBUS
port 502.

In contrast to a large group of applications, the recording of a communication


is not started via the File->New menu item but via the menu item Capture.
More information at www.wireshark.org.