You are on page 1of 20

SET POINT SCHEDULE - TOPSIDES

CONFIDENTAL AGREEMENT CLIENT


THIS DOCUMENT AND ITS CONTENTS, SPECIFICATIONS AND DESIGN TROUNG SON
CONTENTS ARE PROPERIETARY INFORMATION AND MAY NOT BE JOINT OPERATING COMPANY
REPRODUCED, TRANSFERRED OR ISSUED FOR MANUFACTURE

WITHOUT WRITTEN COSENT FROM MODEC,INC. Kavin Engineering And Services Pvt. Ltd. PROJECT

1 17-Mar-08 RE-ISSUED FOR CONSTRUCTION VK AA Sramach AKN www.kavinengg.com TSJOC SRKP PHASE 1 DEVELOPMENT PROJECT
0 21-Nov-07 ISSUED FOR CONSTRUCTION VK AA Sramach AKN ORIG. BY PS CHKD BY
AA TITLE PAGE
B 26-Oct-07 ISSUED FOR REVIEW PS AA Sramach AKN DATE 26 October 2007 SCALE
N/A SIZE
A1 SET POINT SCHEDULE 1 Of 20
A 19-Jun-07 ISSUED FOR IDC PS AA Sramach AKN MODEC DOC NO TSJOC DOC NO REV
REV DATE REVISION DESCRIPTION ORIG CHKD LDE EM 0214-MI20-9002-0003 FPS-SH-F-0003 1
Page 1 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - S2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


` FUNCTION SET POINT REMARKS

OUTPUT INSTRUMENT FUNCTION


LOCATION LINE/VESSEL OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

1 PT - 0100 - 25 PRESSURE TRANSMITTER 0214-MI20-9020-3102 12"-PF-D4-01001-PP 4 ~ 20mA @ 24VDC PAH-0100-25 0-6000 kPag 4000 4200 kPag B

2 PT - 0100 - 25 PRESSURE TRANSMITTER 0214-MI20-9020-3102 12"-PF-D4-01001-PP 4 ~ 20mA @ 24VDC PAL-0100-25 0-6000 kPag 3600 kPag B

3 PT - 0100 - 11 PRESSURE TRANSMITTER 0214-MI20-9020-3102 14"-PG-B4-01008-PP 4 ~ 20mA @ 24VDC PAH-0100-11 0-2000 kPag 1100 1350 kPag 1

4 PT - 0100 - 11 PRESSURE TRANSMITTER 0214-MI20-9020-3102 14"-PG-B4-01008-PP 4 ~ 20mA @ 24VDC PAL-0100-11 0-2000 kPag 990 kPag 1

5 PT - 0100 - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC PAHH-0100-03 0-2000 kPag 1490 kPag 0

6 PT - 0100 - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC PALL-0100-03 0-2000 kPag 770 kPag B

Function set points are referred from


7 LT - 0100 - 15 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LAHH-0100-15 350-1163 mm 1100 mm 1
bottom of vessel

Function set points are referred from


8 LT - 0100 - 15 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LALL-0100-15 350-1163 mm 400 mm 0
bottom of vessel

Function set points are referred from


9 LT - 0100 - 06 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LAH-0100-06 350-1163 mm 900 mm 0
bottom of vessel
700
Function set points are referred from
10 LT - 0100 - 06 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LAL-0100-06 350-1163 mm 550 mm 0
bottom of vessel

Function set points are referred from


11 LT - 0100 - 07 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LAHH-0100-07 1200-2013 mm 1900 mm 0
bottom of vessel

Function set points are referred from


12 LT - 0100 - 07 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LALL-0100-07 1200-2013 mm 1300 mm 0
bottom of vessel

Function set points are referred from


13 LT - 0100 - 09 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LAH-0100-09 1200-2013 mm 1750 mm 0
bottom of vessel
1600
Function set points are referred from
14 LT - 0100 - 09 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LAL-0100-09 1200-2013 mm 1450 mm 0
bottom of vessel

Function set points are referred from


15 LT - 0100 - 29 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LAHH-0100-29 1200-2013 mm 1900 mm 0
bottom of vessel

Function set points are referred from


16 LT - 0100 - 29 LEVEL TRANSMITTER 0214-MI20-9020-3102 V-0100 4 ~ 20mA @ 24VDC LALL-0100-29 1200-2013 mm 1300 mm 0
bottom of vessel

17 FT - 0100 - 05 FLOW TRANSMITTER 0214-MI20-9020-3102 4"-PW-B4-01006-PP 4 ~ 20mA @ 24VDC FAH-0100-05 0-51.6 m^3/hr 45.98 m^3/hr 1

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 1 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - S2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


` FUNCTION SET POINT REMARKS

OUTPUT INSTRUMENT FUNCTION


LOCATION LINE/VESSEL OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

18 FT - 0100 - 10 FLOW TRANSMITTER 0214-MI20-9020-3102 8"-PL-B4-01005-PP 4 ~ 20mA @ 24VDC FAH-0100-10 0-202.9 m^3/hr 202.12 m^3/hr 1

19 FT - 0100 - 10 FLOW TRANSMITTER 0214-MI20-9020-3102 8"-PL-B4-01005-PP 4 ~ 20mA @ 24VDC FAL-0100-10 0-202.9 m^3/hr 5.257 m^3/hr 1

20 FT - 0100 - 18 FLOW TRANSMITTER 0214-MI20-9020-3102 14"-PG-B4-01003-PP 4 ~ 20mA @ 24VDC FAL-0100-18 0-250 (0-58630) mbar (Sm^3/hr) 15652 Sm^3/hr 1

DIFFERENTIAL PRESSURE
21 PDT - 0110 - 07 0214-MI20-9020-3103 ACROSS E-0110A/B 4 ~ 20mA @ 24VDC PDAH--0110-07 0-50 kPa 48 kPa B
TRANSMITTER

TEMPERATURE O
22 TT - 0110 - 04
TRANSMITTER
0214-MI20-9020-3103 8"-PL-B4-01026 4 ~ 20mA @ 24VDC TAH-0110-04 0-100 C 65 O
C 1

55
TEMPERATURE O
23 TT - 0110 - 04
TRANSMITTER
0214-MI20-9020-3103 8"-PL-B4-01026 4 ~ 20mA @ 24VDC TAL-0110-04 0-100 C 45 O
C 1

24 PT - 0110 - 06 PRESSURE TRANSMITTER 0214-MI20-9020-3103 6"-SW-N-40016 4 ~ 20mA @ 24VDC PAHH-0110-06 0-1000 kPag 927 kPag B

25 FT - 0110 - 08 FLOW TRANSMITTER 0214-MI20-9020-3103 6"-SW-N-40056 4 ~ 20mA @ 24VDC FAH-0110-08 0-250 (0-185) mbar (m^3/hr) 115 m^3/hr 1

100 (NOTE-2)

26 FT - 0110 - 08 FLOW TRANSMITTER 0214-MI20-9020-3103 6"-SW-N-40056 4 ~ 20mA @ 24VDC FAL-0110-08 0-250 (0-185) mbar (m^3/hr) 80 m^3/hr 1

27 AT - 0110 - 09 ANALYSER TRANSMITTER 0214-MI20-9020-3103 6"-SW-N-40016 4 ~ 20mA @ 24VDC AAH-0110-09 0-60 ppm 40 ppm 1

TEMPERATURE O
28 TT - 0111 - 02
TRANSMITTER
0214-MI20-9020-3104 10"-PG-B4-01033 4 ~ 20mA @ 24VDC TAH-0111-02 0-100 C 65 O
C B

TEMPERATURE O
29 TT - 0111 - 02
TRANSMITTER
0214-MI20-9020-3104 10"-PG-B4-01033 4 ~ 20mA @ 24VDC TAL-0111-02 0-100 C 40 O
C B

DIFFERENTIAL PRESSURE
30 PDT - 0111 - 04 0214-MI20-9020-3104 ACROSS E-0111 4 ~ 20mA @ 24VDC PDAH--0111-04 0-50 kPa 40 kPa B
TRANSMITTER

Function set points are referred from


31 LT - 0101 - 04 LEVEL TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC LAH-0101-04 181-1400 mm 1100 mm 0
bottom of vessel
600
Function set points are referred from
32 LT - 0101 - 04 LEVEL TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC LAL-0101-04 181-1400 mm 450 mm 0
bottom of vessel

Function set points are referred from


33 LT - 0101 - 08 LEVEL TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC LAHH-0101-08 181-1400 mm 1250 mm 1
bottom of vessel

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

2.Flow Controller FIC-0110-08 shall be at 100 m^3/hr during normal operation and shall automatically change to 130 m^3/hr during coarse filter backwash mode.

Page 2 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - S2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


` FUNCTION SET POINT REMARKS

OUTPUT INSTRUMENT FUNCTION


LOCATION LINE/VESSEL OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

Function set points are referred from


34 LT - 0101 - 08 LEVEL TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC LALL-0101-08 181-1400 mm 300 mm 0
bottom of vessel

Function set points are referred from


35 LT - 0101 - 05 LEVEL TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC LAHH-0101-05 1300-2113 mm 2000 mm 0
bottom of vessel

Function set points are referred from


36 LT - 0101 - 05 LEVEL TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC LALL-0101-05 1300-2113 mm 1400 mm 0
bottom of vessel

Function set points are referred from


37 LT - 0101 - 07 LEVEL TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC LAH-0101-07 1300-2113 mm 1700 1850 mm 0
bottom of vessel

Function set points are referred from


38 LT - 0101 - 07 LEVEL TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC LAL-0101-07 1300-2113 mm 1550 mm 0
bottom of vessel

39 FT - 0101 - 10 FLOW TRANSMITTER 0214-MI20-9020-3105 6"-PG-A4-01038 4 ~ 20mA @ 24VDC FAH-0101-10 0-250 (0-2510) mbar (Sm^3/hr) 1742.5 Sm^3/hr 1

40 FT - 0101 - 10 FLOW TRANSMITTER 0214-MI20-9020-3105 6"-PG-A4-01038 4 ~ 20mA @ 24VDC FAL-0101-10 0-250 (0-2510) mbar (Sm^3/hr) 1213 Sm^3/hr 1

41 FT - 0101 - 11 FLOW TRANSMITTER 0214-MI20-9020-3105 8"-PL-A4-01040 4 ~ 20mA @ 24VDC FAH-0101-11 0-192.33 m^3/hr 180.41 m^3/hr 1

42 FT - 0101 - 11 FLOW TRANSMITTER 0214-MI20-9020-3105 8"-PL-A4-01040 4 ~ 20mA @ 24VDC FAL-0101-11 0-192.33 m^3/hr 4.8 m^3/hr 1

43 FT - 0101 - 12 FLOW TRANSMITTER 0214-MI20-9020-3105 4"-PW-A4-01042 4 ~ 20mA @ 24VDC FAH-0101-12 0-36.57 m^3/hr 32.27 m^3/hr 1

44 FT - 0101 - 12 FLOW TRANSMITTER 0214-MI20-9020-3105 4"-PW-A4-01042 4 ~ 20mA @ 24VDC FAL-0101-12 0-36.57 m^3/hr 1.673 m^3/hr 1

45 PT - 0101 - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC PAHH-0101-02 0-350 kPag 315 kPag B

46 PT - 0101 - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3105 V-0101 4 ~ 20mA @ 24VDC PALL-0101-02 0-350 kPag 50 kPag B

47 PT - 0101 - 09 PRESSURE TRANSMITTER 0214-MI20-9020-3105 6"-PG-A4-01038 4 ~ 20mA @ 24VDC PAH-0101-09 0-350 kPag 70 200 kPag B

48 PT - 0101 - 09 PRESSURE TRANSMITTER 0214-MI20-9020-3105 6"-PG-A4-01038 4 ~ 20mA @ 24VDC PAL-0101-09 0-350 kPag 55 kPag B

TEMPERATURE O
49 TT - 0101 - 16
TRANSMITTER
0214-MI20-9020-3105 8'-PL-A4-01040 4 ~ 20mA @ 24VDC TAHH-0101-16 0-100 C 60 O
C B

Function set points are referred from


50 LT - 0200 - 04 LEVEL TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC LAH-0200-04 2900-3713 mm 300 400 mm 0
bottom Tan line

GENERAL NOTES:

1. The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 3 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - S2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


` FUNCTION SET POINT REMARKS

OUTPUT INSTRUMENT FUNCTION


LOCATION LINE/VESSEL OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

Function set points are referred from


51 LT - 0200 - 04 LEVEL TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC LAL-0200-04 2900-3713 mm 200 mm 0
bottom Tan line

Function set points are referred from


52 LT - 0200 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC LAHH-0200-03 2900-3713 mm 500 mm 0
bottom Tan line

Function set points are referred from


53 LT - 0200 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC LALL-0200-03 2900-3713 mm 100 mm 0
bottom Tan line

Function set points are referred from


54 LT - 0200 - 01 LEVEL TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC LAH-0200-01 2231-3450 mm 3150 mm 0
bottom Tan line
2950
Function set points are referred from
55 LT - 0200 - 01 LEVEL TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC LAL-0200-01 2231-3450 mm 2750 mm 0
bottom Tan line

Function set points are referred from


56 LT - 0200 - 06 LEVEL TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC LAHH-0200-06 2231-3450 mm 3350 mm 0
bottom Tan line

Function set points are referred from


57 LT - 0200 - 06 LEVEL TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC LALL-0200-06 2231-3450 mm 2550 mm 0
bottom Tan line

58 PT - 0200 - 07 PRESSURE TRANSMITTER 0214-MI20-9020-3106 2"-PG-A4-02011-PP 4 ~ 20mA @ 24VDC PAHH-0200-07 0-350 kPag 315 kPag B

59 PT - 0200 - 07 PRESSURE TRANSMITTER 0214-MI20-9020-3106 2"-PG-A4-02011-PP 4 ~ 20mA @ 24VDC PALL-0200-07 0-350 kPag 20 kPag B

60 PT - 0200 - 16 PRESSURE TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC PAH-0200-16 0-350 kPag 200 kPag B

61 PT - 0200 - 16 PRESSURE TRANSMITTER 0214-MI20-9020-3106 V-0200 4 ~ 20mA @ 24VDC PAL-0200-16 0-350 kPag 25 kPag B

62 PT - 0230A - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3106 6"-PW-A4-02004-PP 4 ~ 20mA @ 24VDC PAHH-0230A-02 0-1400 kPag 945 kPag B

63 PT - 0230A - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3106 6"-PW-A4-02004-PP 4 ~ 20mA @ 24VDC PALL-0230A-02 0-1400 kPag 490 kPag B

64 PT - 0230B - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3106 6"-PW-A4-02005-PP 4 ~ 20mA @ 24VDC PAHH-0230B-02 0-1400 kPag 945 kPag B

65 PT - 0230B - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3106 6"-PW-A4-02005-PP 4 ~ 20mA @ 24VDC PALL-0230B-02 0-1400 kPag 490 kPag B

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 4 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - S2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


` FUNCTION SET POINT REMARKS

OUTPUT INSTRUMENT FUNCTION


LOCATION LINE/VESSEL OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

DIFFERENTIAL PRESSURE
66 PDIrC - 0201 - 01 0214-MI20-9020-3107 ACROSS V-0201 4 ~ 20mA @ 24VDC PDAH--0201-01 - 1.8* B
TRANSMITTER
1.7* (NOTE-2)
DIFFERENTIAL PRESSURE
67 PDIrC - 0201 - 01 0214-MI20-9020-3107 ACROSS V-0201 4 ~ 20mA @ 24VDC PDAL--0201-01 - 1.5* B
TRANSMITTER

68 FT - 0201 - 03 FLOW TRANSMITTER 0214-MI20-9020-3107 6"-PW-A4-02019-PP 4 ~ 20mA @ 24VDC FAH-0201-03 0-82.08 m^3/hr 76.68 m^3/hr 1

69 FT - 0201 - 03 FLOW TRANSMITTER 0214-MI20-9020-3107 6"-PW-A4-02019-PP 4 ~ 20mA @ 24VDC FAL-0201-03 0-82.08 m^3/hr 33.32 m^3/hr 1

Function set points are referred from


70 LT - 0202 - 01 LEVEL TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC LAH-0202-01 1381-2600 mm 2300 mm 0
bottom Tan line
2100
Function set points are referred from
71 LT - 0202 - 01 LEVEL TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC LAL-0202-01 1381-2600 mm 1900 mm 0
bottom Tan line

Function set points are referred from


72 LT - 0202 - 10 LEVEL TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC LAHH-0202-10 1381-2600 mm 2500 mm 0
bottom Tan line

Function set points are referred from


73 LT - 0202 - 10 LEVEL TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC LALL-0202-10 1381-2600 mm 1700 mm 0
bottom Tan line

Function set points are referred from


74 LT - 0202 - 05 LEVEL TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC LAH-0202-05 1937-2750 mm 400 mm 1
bottom Tan line
300
Function set points are referred from
75 LT - 0202 - 05 LEVEL TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC LAL-0202-05 1937-2750 mm 200 mm 1
bottom Tan line

Function set points are referred from


76 LT - 0202 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC LAHH-0202-03 1937-2750 mm 500 mm 0
bottom Tan line

Function set points are referred from


77 LT - 0202 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC LALL-0202-03 1937-2750 mm 100 mm 0
bottom Tan line

78 PT - 0202 - 06 PRESSURE TRANSMITTER 0214-MI20-9020-3108 2"-PG-A4-02038-PP 4 ~ 20mA @ 24VDC PAHH-0202-06 0-350 kPag 315 kPag B

79 PT - 0202 - 06 PRESSURE TRANSMITTER 0214-MI20-9020-3108 2"-PG-A4-02038-PP 4 ~ 20mA @ 24VDC PALL-0202-06 0-350 kPag 35 kPag B

80 PT - 0202 - 12 PRESSURE TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC PAH-0202-12 0-350 kPag 200 kPag B

81 PT - 0202 - 12 PRESSURE TRANSMITTER 0214-MI20-9020-3108 V-0202 4 ~ 20mA @ 24VDC PAL-0202-12 0-350 kPag 40 kPag B

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

2.To be confirmed by vendor.

Page 5 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - S2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


` FUNCTION SET POINT REMARKS

OUTPUT INSTRUMENT FUNCTION


LOCATION LINE/VESSEL OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

DIFFERENTIAL PRESSURE
82 PDT - 0210 - 04 0214-MI20-9020-3109 ACROSS E-0210 4 ~ 20mA @ 24VDC PDAH--0210-04 0-30 kPa 25 kPa B
TRANSMITTER

83 FT - 0210 - 02 FLOW TRANSMITTER 0214-MI20-9020-3109 6"-PW-A4-02047 4 ~ 20mA @ 24VDC FAH-0210-02 0-81.59 m^3/hr 76.23 m^3/hr 1

84 FT - 0210 - 02 FLOW TRANSMITTER 0214-MI20-9020-3109 6"-PW-A4-02047 4 ~ 20mA @ 24VDC FAL-0210-02 0-81.59 m^3/hr 33.13 m^3/hr 1

85 AT - 0210 - 01 ANALYSER TRANSMITTER 0214-MI20-9020-3109 6"-PW-A4-02047 4 ~ 20mA @ 24VDC AAH-0210-01 0-60 ppm 40 ppm B

TEMPERATURE O
86 TT - 0210 - 08
TRANSMITTER
0214-MI20-9020-3109 6"-PW-A4-02047 4 ~ 20mA @ 24VDC TAH-0210-08 0-120 C 65 O
C B

TEMPERATURE O
87 TT - 0210 - 08
TRANSMITTER
0214-MI20-9020-3109 6"-PW-A4-02047 4 ~ 20mA @ 24VDC TAL-0210-08 0-120 C 45 O
C B

Function set points are referred from


88 LT - 0410 - 09 LEVEL TRANSMITTER 0214-MI20-9020-3110 V-0410 4 ~ 20mA @ 24VDC LAHH-0410-09 150-963 mm 850 mm 0
bottom Tan line

Function set points are referred from


89 LT - 0410 - 09 LEVEL TRANSMITTER 0214-MI20-9020-3110 V-0410 4 ~ 20mA @ 24VDC LALL-0410-09 150-963 mm 200 mm 0
bottom Tan line

Function set points are referred from


90 LT - 0410 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3110 V-0410 4 ~ 20mA @ 24VDC LAH-0410-03 150-963 mm 750 mm 0
bottom Tan line
500
Function set points are referred from
91 LT - 0410 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3110 V-0410 4 ~ 20mA @ 24VDC LAL-0410-03 150-963 mm 350 mm 0
bottom Tan line

92 PT - 0410 - 05 PRESSURE TRANSMITTER 0214-MI20-9020-3110 V-0410 4 ~ 20mA @ 24VDC PAHH-0410-05 0-1000 kPag 900 kPag B

93 PT - 0410 - 05 PRESSURE TRANSMITTER 0214-MI20-9020-3110 V-0410 4 ~ 20mA @ 24VDC PALL-0410-05 0-1000 kPag 400 kPag B

TEMPERATURE O
94 TT - 0410 - 06
TRANSMITTER
0214-MI20-9020-3110 V-0410 4 ~ 20mA @ 24VDC TAH-0410-06 0-80 C 50 O
C B

TEMPERATURE O
95 TT - 0410 - 06
TRANSMITTER
0214-MI20-9020-3110 V-0410 4 ~ 20mA @ 24VDC TAL-0410-06 0-80 C 35 O
C B

96 PT - 0410 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3111 10"-FG-AS-04008 4 ~ 20mA @ 24VDC PAH-0410-04 0-1000 kPag 700 kPag B

97 PT - 0410 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3111 10"-FG-AS-04008 4 ~ 20mA @ 24VDC PAL-0410-04 0-1000 kPag 520 kPag B

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 6 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - S2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


` FUNCTION SET POINT REMARKS

OUTPUT INSTRUMENT FUNCTION


LOCATION LINE/VESSEL OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

98 FT - 0420 - 01 FLOW TRANSMITTER 0214-MI20-9020-3111 10"-FG-AS-04008 4 ~ 20mA @ 24VDC FAH-0420-01 0-250 (0-16547) mbar (Sm^3/hr) 15276.6 Sm^3/hr 1

99 FT - 0420 - 01 FLOW TRANSMITTER 0214-MI20-9020-3111 10"-FG-AS-04008 4 ~ 20mA @ 24VDC FAL-0420-01 0-250 (0-16547) mbar (Sm^3/hr) 10627.2 Sm^3/hr 1

TEMPERATURE O
100 TT - 0420 - 06
TRANSMITTER
0214-MI20-9020-3111 10"-FG-AS-04008 4 ~ 20mA @ 24VDC TAHH-0420-06 0-100 C 60 O
C B

TEMPERATURE O
101 TT - 0420 - 06
TRANSMITTER
0214-MI20-9020-3111 10"-FG-AS-04008 4 ~ 20mA @ 24VDC TALL-0420-06 0-100 C 40 O
C B

TEMPERATURE O
102 TT - 0420 - 07
TRANSMITTER
0214-MI20-9020-3111 10"-FG-AS-04008 4 ~ 20mA @ 24VDC TAH-0420-07 0-100 C 58 O
C B

TEMPERATURE O
103 TT - 0420 - 07
TRANSMITTER
0214-MI20-9020-3111 10"-FG-AS-04008 4 ~ 20mA @ 24VDC TAL-0420-07 0-100 C 45 O
C B

Page 7 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P5U DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT
LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH FUNCTION
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP SETPOINT UNITS
UNITS RANGE

Function set points are referred from


1 LT - 0900 - 04 LEVEL TRANSMITTER 0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC LAHH-0900-04 (-828)-2564 mm 2250 mm 0
bottom of vessel

Function set points are referred from


2 LT - 0900 - 04 LEVEL TRANSMITTER 0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC LALL-0900-04 (-828)-2564 mm 400 mm 0
bottom of vessel

Function set points are referred from


3 LT - 0900 - 10 LEVEL TRANSMITTER 0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC LAHH-0900-10 (-828)-2564 mm 2250 mm 0
bottom of vessel

Function set points are referred from


4 LT - 0900 - 10 LEVEL TRANSMITTER 0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC LALL-0900-10 (-828)-2564 mm 400 mm 0
bottom of vessel

Function set points are referred from


5 LT - 0900 - 02 LEVEL TRANSMITTER 0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC LAH1-0900-02 360-3300 mm 800 mm 0
bottom of vessel

Function set points are referred from


6 LT - 0900 - 02 LEVEL TRANSMITTER 0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC LAH2-0900-02 360-3300 mm 950 mm 0
bottom of vessel

Function set points are referred from


7 LT - 0900 - 02 LEVEL TRANSMITTER 0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC LAL-0900-02 360-3300 mm 500 mm 0
bottom of vessel

8 PT - 0901A - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3130 3"-PL-A4-09029-ET 4 ~ 20mA @ 24VDC PAHH-0901A-03 0-700 kPag 630 kPag B

9 PT - 0901A - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3130 3"-PL-A4-09029-ET 4 ~ 20mA @ 24VDC PALL-0901A-03 0-700 kPag 120 kPag B

10 PT - 0901B - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3130 3"-PL-A4-09028-ET 4 ~ 20mA @ 24VDC PAHH-0901B-03 0-700 kPag 630 kPag B

11 PT - 0901B - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3130 3"-PL-A4-09028-ET 4 ~ 20mA @ 24VDC PALL-0901B-03 0-700 kPag 120 kPag B

12 FT - 0901 - 04 FLOW TRANSMITTER 0214-MI20-9020-3130 3"-PL-A4-09029-ET 4 ~ 20mA @ 24VDC FAH-0901-04 0-250 (0-15) mbar (m^3/hr) 12.65 m^3/hr 1

11

13 FT - 0901 - 04 FLOW TRANSMITTER 0214-MI20-9020-3130 3"-PL-A4-09029-ET 4 ~ 20mA @ 24VDC FAL-0901-04 0-250 (0-15) mbar (m^3/hr) 8.8 m^3/hr 1

TEMPERATURE O O
14 TT - 0900 - 03
TRANSMITTER
0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC TAH-0900-03 0-80 C 63 C B

TEMPERATURE O O
15 TT - 0900 - 03
TRANSMITTER
0214-MI20-9020-3130 V-0900 4 ~ 20mA @ 24VDC TAL-0900-03 0-80 C 21 C B

TEMPERATURE O O
16 TT - 0900 - 07
TRANSMITTER
0214-MI20-9020-3130 3"-PL-A4-09026-ET 4 ~ 20mA @ 24VDC TAHH-0900-07 0-80 C 70 C B

GENERAL NOTES:

1. The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 3 Of 3
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P5U DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT
LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH FUNCTION
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP SETPOINT UNITS
UNITS RANGE

Function set points are referred from


17 LT - 0910 - 01 LEVEL TRANSMITTER 0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC LAHH-0910-01 (-730)-1362 mm 1800 mm 0
bottom of vessel

Function set points are referred from


18 LT - 0910 - 01 LEVEL TRANSMITTER 0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC LALL-0910-01 (-730)-1362 mm 400 mm 0
bottom of vessel

Function set points are referred from


19 LT - 0910 - 10 LEVEL TRANSMITTER 0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC LAHH-0910-10 (-730)-1362 mm 1800 mm 0
bottom of vessel

Function set points are referred from


20 LT - 0910 - 10 LEVEL TRANSMITTER 0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC LALL-0910-10 (-730)-1362 mm 400 mm 0
bottom of vessel

Function set points are referred from


21 LT - 0910 - 09 LEVEL TRANSMITTER 0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC LAH1-0910-09 200-2000 mm 700 mm 0
bottom of vessel

Function set points are referred from


22 LT - 0910 - 09 LEVEL TRANSMITTER 0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC LAH2-0910-09 200-2000 mm 850 mm 0
bottom of vessel

Function set points are referred from


23 LT - 0910 - 09 LEVEL TRANSMITTER 0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC LAL-0910-09 200-2000 mm 500 mm 0
bottom of vessel

24 PT - 0911A - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3132 3"-PL-A4-09051-ET 4 ~ 20mA @ 24VDC PAHH-0911A-03 0-350 kPag 315 kPag B

25 PT - 0911A - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3132 3"-PL-A4-09051-ET 4 ~ 20mA @ 24VDC PALL-0911A-03 0-350 kPag 120 kPag B

26 PT - 0911B - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3132 3"-PL-A4-09050-ET 4 ~ 20mA @ 24VDC PAHH-0911B-03 0-350 kPag 315 kPag B

27 PT - 0911B - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3132 3"-PL-A4-09050-ET 4 ~ 20mA @ 24VDC PALL-0911B-03 0-350 kPag 120 kPag B

28 FT - 0911 - 04 FLOW TRANSMITTER 0214-MI20-9020-3132 3"-PL-A4-09051-ET 4 ~ 20mA @ 24VDC FAH-0911-04 0-250(0-25.54) mbar(m^3/hr) 23 m^3/hr 1

20

29 FT - 0911 - 04 FLOW TRANSMITTER 0214-MI20-9020-3132 3"-PL-A4-09051-ET 4 ~ 20mA @ 24VDC FAL-0911-04 0-250(0-25.54) mbar(m^3/hr) 16 m^3/hr 1

TEMPERATURE O O
30 TT - 0910 - 02
TRANSMITTER
0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC TAH-0910-02 0-100 C 63 C B

TEMPERATURE O O
31 TT - 0910 - 02
TRANSMITTER
0214-MI20-9020-3132 V-0910 4 ~ 20mA @ 24VDC TAL-0910-02 0-100 C 45 C B

TEMPERATURE O O
32 TT - 0910 - 07
TRANSMITTER
0214-MI20-9020-3132 4"-PL-A4-09048-ET 4 ~ 20mA @ 24VDC TAHH-0910-07 0-100 C 70 C B

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 3 Of 3
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P5U DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT
LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH FUNCTION
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP SETPOINT UNITS
UNITS RANGE

33 FT - 0920 - 03 FLOW TRANSMITTER 0214-MI20-9020-3133 1"-FG-AS-04014 4 ~ 20mA @ 24VDC FAL-0920-03 0.079 to 0.793 Sm^3/hr 1.13 Sm^3/hr 1

34 FT - 0902 - 03 FLOW TRANSMITTER 0214-MI20-9020-3133 16''-FH-A4-09032 4 ~ 20mA @ 24VDC FAH-0902-03 0-54287 Sm^3/hr 51278 Sm^3/hr 1

35 FT - 0902 - 03 FLOW TRANSMITTER 0214-MI20-9020-3133 16''-FH-A4-09032 4 ~ 20mA @ 24VDC FAL-0902-03 0-54287 Sm^3/hr 12207 Sm^3/hr 1

36 FT - 0912 - 03 FLOW TRANSMITTER 0214-MI20-9020-3133 6''-FL-A4-09057 4 ~ 20mA @ 24VDC FAH-0912-03 0-2567 Sm^3/hr 2268 Sm^3/hr 1

37 FT - 0912 - 03 FLOW TRANSMITTER 0214-MI20-9020-3133 6''-FL-A4-09057 4 ~ 20mA @ 24VDC FAL-0912-03 0-2567 Sm^3/hr 907.4 Sm^3/hr 1

Page 3 Of 3
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

DIFFERENTIAL PRESSURE
1 PDT - 0601A - 06 0214-MI20-9020-3113 ACROSS F-0601A 4 ~ 20mA @ 24VDC PDAH-0601A-06 0-50 kPa 40 kPa B
TRANSMITTER

DIFFERENTIAL PRESSURE
2 PDT - 0601B - 06 0214-MI20-9020-3113 ACROSS F-0601B 4 ~ 20mA @ 24VDC PDAH-0601B-06 0-50 kPa 40 kPa B
TRANSMITTER

TEMPERATURE O O
3 TT - 0601 - 07 0214-MI20-9020-3113 6"-SW-N-06085 4 ~ 20mA @ 24VDC TAH-0601-07 0-100 C 65 C B
TRANSMITTER

DIFFERENTIAL PRESSURE
4 PDT - 0602A - 02 0214-MI20-9020-3114 ACROSS F-0602A 4 ~ 20mA @ 24VDC PDAH-0602A-02 0-50 kPa 40 kPa B
TRANSMITTER

DIFFERENTIAL PRESSURE
5 PDT - 0602B - 02 0214-MI20-9020-3114 ACROSS F-0602B 4 ~ 20mA @ 24VDC PDAH-0602B-02 0-50 kPa 40 kPa B
TRANSMITTER

6 FT - 0603 - 02 FLOW TRANSMITTER 0214-MI20-9020-3115 6"-WI-N-06035 4 ~ 20mA @ 24VDC FAH-0603-02 0-250 (0-142.71) mbar (m^3/hr) 115 m^3/hr 1

7 FT - 0603 - 02 FLOW TRANSMITTER 0214-MI20-9020-3115 6"-WI-N-06035 4 ~ 20mA @ 24VDC FAL-0603-02 0-250 (0-142.71) mbar (m^3/hr) 20 m^3/hr 1

DIFFERENTIAL PRESSURE
8 PDT - 0603 - 06 0214-MI20-9020-3115 V-0603 4 ~ 20mA @ 24VDC PDAH--0603-06 0-50 kPa 40 kPa B
TRANSMITTER

9 PT - 0603 - 05 PRESSURE TRANSMITTER 0214-MI20-9020-3115 4"-WI-N-06052 4 ~ 20mA @ 24VDC PAHH-0603-05 -100 To 100 kPag 315 kPag B

10 FT - 0603 - 10 FLOW TRANSMITTER 0214-MI20-9020-3115 3"-WI-B-06054 4 ~ 20mA @ 24VDC FAH-0603-10 0-250 (0-38.74) mbar (m^3/hr) 2.304 m^3/hr 1

11 FT - 0603 - 10 FLOW TRANSMITTER 0214-MI20-9020-3115 3"-WI-B-06054 4 ~ 20mA @ 24VDC FAL-0603-10 0-250 (0-38.74) mbar (m^3/hr) 0.403 m^3/hr 1

Function set points are referred from


12 LT - 0603 - 04 LEVEL TRANSMITTER 0214-MI20-9020-3115 V-0603 4 ~ 20mA @ 24VDC LAHH-0603-04 545-2250 mm 2019 mm 0
bottom Tan line

Function set points are referred from


13 LT - 0603 - 04 LEVEL TRANSMITTER 0214-MI20-9020-3115 V-0603 4 ~ 20mA @ 24VDC LALL-0603-04 545-2250 mm 734 mm 0
bottom Tan line

Function set points are referred from


14 LT - 0603 - 07 LEVEL TRANSMITTER 0214-MI20-9020-3115 V-0603 4 ~ 20mA @ 24VDC LAH-0603-07 545-2085 mm 1836 mm 0
bottom Tan line
1469
Function set points are referred from
15 LT - 0603 - 07 LEVEL TRANSMITTER 0214-MI20-9020-3115 V-0603 4 ~ 20mA @ 24VDC LAL-0603-07 545-2085 mm 1101 mm 0
bottom Tan line

16 AT - 0603 - 11 ANALYSER TRANSMITTER 0214-MI20-9020-3115 6"-WI-N-06045 4 ~ 20mA @ 24VDC AAH-0603-11 0-10 ppb 10 ppb B

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 11 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

17 PT - 0640A - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3115 4"-WI-B-06086 4 ~ 20mA @ 24VDC PAHH-0640A-03 0-3000 kPag 2250 kPag B

18 PT - 0640A - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3115 4"-WI-B-06086 4 ~ 20mA @ 24VDC PALL-0640A-03 0-3000 kPag 1400 kPag B

19 PT - 0640B - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3115 4"-WI-B-06048 4 ~ 20mA @ 24VDC PAHH-0640B-03 0-3000 kPag 2250 kPag B

20 PT - 0640B - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3115 4"-WI-B-06048 4 ~ 20mA @ 24VDC PALL-0640B-03 0-3000 kPag 1400 kPag B

21 PT - 0604A - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3116 1"-WI-N-06092 4 ~ 20mA @ 24VDC PAH-0604A-04 0-20 kPag 15 kPag 0

22 PT - 0604A - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3116 1"-WI-N-06092 4 ~ 20mA @ 24VDC PAL-0604A-04 0-20 kPag 8 kPag 0

23 PT - 0604B - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3116 1"-WI-N-06091 4 ~ 20mA @ 24VDC PAH-0604B-04 0-20 kPag 15 kPag 0

24 PT - 0604B - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3116 1"-WI-N-06091 4 ~ 20mA @ 24VDC PAL-0604B-04 0-20 kPag 8 kPag 0

25 PT - 0604A - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3116 4"-WI-N-06062 4 ~ 20mA @ 24VDC PAH-0604A-02 -100 to +100 kPag -86 kPag 0

26 PT - 0604B - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3116 4"-WI-N-06052 4 ~ 20mA @ 24VDC PAH-0604B-02 -100 to +100 kPag -86 kPag 0

27 FT - 0604A - 03 FLOW TRANSMITTER 0214-MI20-9020-3116 1"-WI-N-06092 4 ~ 20mA @ 24VDC FAH-0604A-03 0-2.143 m^3/hr 1.724 m^3/hr 1

28 FT - 0604A - 03 FLOW TRANSMITTER 0214-MI20-9020-3116 1"-WI-N-06092 4 ~ 20mA @ 24VDC FAL-0604A-03 0-2.143 m^3/hr 0.301 m^3/hr 1

29 FT - 0604B - 03 FLOW TRANSMITTER 0214-MI20-9020-3116 1"-WI-N-06091 4 ~ 20mA @ 24VDC FAH-0604B-03 0-2.143 m^3/hr 1.724 m^3/hr 1

30 FT - 0604B - 03 FLOW TRANSMITTER 0214-MI20-9020-3116 1"-WI-N-06091 4 ~ 20mA @ 24VDC FAL-0604B-03 0-2.143 m^3/hr 0.301 m^3/hr 1

31 PT - 0641A - 01 PRESSURE TRANSMITTER 0214-MI20-9020-3117 4"-WI-F-06075 4 ~ 20mA @ 24VDC PAHH-0641A-01 0-25000 kPag 16650 kPag 1

32 PT - 0641A - 01 PRESSURE TRANSMITTER 0214-MI20-9020-3117 4"-WI-F-06075 4 ~ 20mA @ 24VDC PALL-0641A-01 0-25000 kPag 10080 kPag 0

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 12 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

33 PT - 0641B - 01 PRESSURE TRANSMITTER 0214-MI20-9020-3117 4"-WI-F-06074 4 ~ 20mA @ 24VDC PAHH-0641B-01 0-25000 kPag 16650 kPag 1

34 PT - 0641B - 01 PRESSURE TRANSMITTER 0214-MI20-9020-3117 4"-WI-F-06074 4 ~ 20mA @ 24VDC PALL-0641B-01 0-25000 kPag 10080 kPag 0

35 FT - 0641A - 27 FLOW TRANSMITTER 0214-MI20-9020-3117 4"-WI-F-06075 4 ~ 20mA @ 24VDC FAH-0641A-27 0-250 (0-63) mbar (m^3/hr) 57.5 m^3/hr 1

50

36 FT - 0641A - 27 FLOW TRANSMITTER 0214-MI20-9020-3117 4"-WI-F-06075 4 ~ 20mA @ 24VDC FAL-0641A-27 0-250 (0-63) mbar (m^3/hr) 10 m^3/hr 1

37 FT - 0641B - 27 FLOW TRANSMITTER 0214-MI20-9020-3117 4"-WI-F-06074 4 ~ 20mA @ 24VDC FAH-0641B-27 0-250 (0-63) mbar (m^3/hr) 57.5 m^3/hr 1

50

38 FT - 0641B - 27 FLOW TRANSMITTER 0214-MI20-9020-3117 4"-WI-F-06074 4 ~ 20mA @ 24VDC FAL-0641B-27 0-250 (0-63) mbar (m^3/hr) 10 m^3/hr 1

39 PT - 0641 - 28 PRESSURE TRANSMITTER 0214-MI20-9020-3117 6"-WI-F-06076 4 ~ 20mA @ 24VDC PAH-0641A-28 0-25000 kPag 12950 kPag 1

40 PT - 0641 - 28 PRESSURE TRANSMITTER 0214-MI20-9020-3117 6"-WI-F-06076 4 ~ 20mA @ 24VDC PAL-0641A-28 0-25000 kPag 9800 kPag 0

41 PT - 4320 - 06 PRESSURE TRANSMITTER 0214-MI20-9020-3137 V-4320 4 ~ 20mA @ 24VDC PAH-4320-06 0-1500 kPag 1070 kPag B

42 PT - 4320 - 06 PRESSURE TRANSMITTER 0214-MI20-9020-3137 V-4320 4 ~ 20mA @ 24VDC PAL-4320-06 0-1500 kPag 900 kPag B

43 PT - 4320 - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3137 4"-IA-M-43904 4 ~ 20mA @ 24VDC PAH-4320-02 0-1500 kPag 1070 kPag B

1000

44 PT - 4320 - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3137 4"-IA-M-43904 4 ~ 20mA @ 24VDC PAL-4320-02 0-1500 kPag 900 kPag B

45 PT - 4320 - 07 PRESSURE TRANSMITTER 0214-MI20-9020-3137 4"-IA-M-43904 4 ~ 20mA @ 24VDC PAL-4320-07 0-1500 kPag 700 kPag 0

46 PT - 4320 - 05 PRESSURE TRANSMITTER 0214-MI20-9020-3137 4"-IA-M-43904 4 ~ 20mA @ 24VDC PALL-4320-05 0-1500 kPag 550 kPag B

47 PT - 4710 - 07 PRESSURE TRANSMITTER 0214-MI20-9020-3139 V-4710 4 ~ 20mA @ 24VDC PAH-4710-07 0-1400 kPag 1040 kPag B

48 PT - 4710 - 07 PRESSURE TRANSMITTER 0214-MI20-9020-3139 V-4710 4 ~ 20mA @ 24VDC PAL-4710-07 0-1400 kPag 900 kPag B

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 13 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

49 PT - 4710 - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3139 2"-NG-A2-47902 4 ~ 20mA @ 24VDC PAH-4710-02 0-1400 kPag 900 kPag B

700

50 PT - 4710 - 02 PRESSURE TRANSMITTER 0214-MI20-9020-3139 2"-NG-A2-47902 4 ~ 20mA @ 24VDC PAL-4710-02 0-1400 kPag 630 B

Function set points are referred from


51 LT - 0710 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3118 T-0710 4 ~ 20mA @ 24VDC LAH-0710-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


52 LT - 0710 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3118 T-0710 4 ~ 20mA @ 24VDC LAL-0710-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


53 LT - 0710 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3118 T-0710 4 ~ 20mA @ 24VDC LALL-0710-03 0-1200 mm 300 mm 0
bottom of Tank

54 PT - 0711 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3118 1/2"-CI-T-07010 4 ~ 20mA @ 24VDC PAH-0711-04 0-10000 kPag 4150 kPag 0

55 PT - 0711 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3118 1/2"-CI-T-07010 4 ~ 20mA @ 24VDC PAL-0711-04 0-10000 kPag 3760 kPag 0

Function set points are referred from


56 LT - 0706 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3119 T-0706 4 ~ 20mA @ 24VDC LAH-0706-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


57 LT - 0706 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3119 T-0706 4 ~ 20mA @ 24VDC LAL-0706-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


58 LT - 0706 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3119 T-0706 4 ~ 20mA @ 24VDC LALL-0706-03 0-1200 mm 300 mm 0
bottom of Tank

59 PT - 0707 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3119 1/2"-CI-T-07025 4 ~ 20mA @ 24VDC PAH-0707-04 0-10000 kPag 4150 kPag 0

60 PT - 0707 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3119 1/2"-CI-T-07025 4 ~ 20mA @ 24VDC PAL-0707-04 0-10000 kPag 3760 kPag 0

Function set points are referred from


61 LT - 0708 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3120 T-0708 4 ~ 20mA @ 24VDC LAH-0708-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


62 LT - 0708 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3120 T-0708 4 ~ 20mA @ 24VDC LAL-0708-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


63 LT - 0708 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3120 T-0708 4 ~ 20mA @ 24VDC LALL-0708-03 0-1200 mm 300 mm 0
bottom of Tank

GENERAL NOTES:

1. The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 14 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

64 PT - 0709 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3120 1/2"-CI-T-07032 4 ~ 20mA @ 24VDC PAH-0709-04 0-6000 kPag 2280 kPag 0

65 PT - 0709 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3120 1/2"-CI-T-07032 4 ~ 20mA @ 24VDC PAL-0709-04 0-6000 kPag 2000 kPag 0

Function set points are referred from


66 LT - 0704 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3121 T-0704 4 ~ 20mA @ 24VDC LAH-0704-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


67 LT - 0704 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3121 T-0704 4 ~ 20mA @ 24VDC LAL-0704-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


68 LT - 0704 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3121 T-0704 4 ~ 20mA @ 24VDC LALL-0704-03 0-1200 mm 300 mm 0
bottom of Tank

69 PT - 0705 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3121 1/2"-CI-T-07048 4 ~ 20mA @ 24VDC PAH-0705-04 0-3000 kPag 1430 kPag 0

70 PT - 0705 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3121 1/2"-CI-T-07048 4 ~ 20mA @ 24VDC PAL-0705-04 0-3000 kPag 1150 kPag 0

Function set points are referred from


71 LT - 0724 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3122 T-0724 4 ~ 20mA @ 24VDC LAH-0724-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


72 LT - 0724 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3122 T-0724 4 ~ 20mA @ 24VDC LAL-0724-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


73 LT - 0724 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3122 T-0724 4 ~ 20mA @ 24VDC LALL-0724-03 0-1200 mm 300 mm 0
bottom of Tank

74 PT - 0725 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3122 1/2"-CI-T-07065 4 ~ 20mA @ 24VDC PAH-0725-04 0-6000 kPag 2050 kPag 0

75 PT - 0725 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3122 1/2"-CI-T-07065 4 ~ 20mA @ 24VDC PAL-0725-04 0-6000 kPag 1760 kPag 0

Function set points are referred from


76 LT - 0700 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3123 T-0700 4 ~ 20mA @ 24VDC LAH-0700-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


77 LT - 0700 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3123 T-0700 4 ~ 20mA @ 24VDC LAL-0700-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


78 LT - 0700 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3123 T-0700 4 ~ 20mA @ 24VDC LALL-0700-03 0-1200 mm 300 mm 0
bottom of Tank

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 15 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

79 PT - 0701 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3123 1/2"-CI-T-07079 4 ~ 20mA @ 24VDC PAH-0701-04 0-10000 kPag 4150 kPag 0

80 PT - 0701 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3123 1/2"-CI-T-07079 4 ~ 20mA @ 24VDC PAL-0701-04 0-10000 kPag 3760 kPag 0

Function set points are referred from


81 LT - 0702 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3124 T-0702 4 ~ 20mA @ 24VDC LAH-0702-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


82 LT - 0702 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3124 T-0702 4 ~ 20mA @ 24VDC LAL-0702-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


83 LT - 0702 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3124 T-0702 4 ~ 20mA @ 24VDC LALL-0702-03 0-1200 mm 300 mm 0
bottom of Tank

84 PT - 0703 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3124 1/2"-CI-T-07092 4 ~ 20mA @ 24VDC PAH-0703-04 0-800 kPag 410 kPag 0

85 PT - 0703 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3124 1/2"-CI-T-07092 4 ~ 20mA @ 24VDC PAL-0703-04 0-800 kPag 210 kPag 0

Function set points are referred from


86 LT - 0720 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3125 T-0720 4 ~ 20mA @ 24VDC LAH-0720-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


87 LT - 0720 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3125 T-0720 4 ~ 20mA @ 24VDC LAL-0720-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


88 LT - 0720 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3125 T-0720 4 ~ 20mA @ 24VDC LALL-0720-03 0-1200 mm 300 mm 0
bottom of Tank

89 PT - 0721 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3125 1/2"-CI-T-07104 4 ~ 20mA @ 24VDC PAH-0721-04 0-10000 kPag 2050 kPag 0

90 PT - 0721 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3125 1/2"-CI-T-07104 4 ~ 20mA @ 24VDC PAL-0721-04 0-10000 kPag 1750 kPag 0

Function set points are referred from


91 LT - 0722 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3126 T-0722 4 ~ 20mA @ 24VDC LAH-0722-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


92 LT - 0722 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3126 T-0722 4 ~ 20mA @ 24VDC LAL-0722-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


93 LT - 0722 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3126 T-0722 4 ~ 20mA @ 24VDC LALL-0722-03 0-1200 mm 300 mm 0
bottom of Tank

94 PT - 0723 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3126 1/2"-CI-T-07121 4 ~ 20mA @ 24VDC PAH-0723-04 0-1000 kPag 490 kPag 0

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 16 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

95 PT - 0723 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3126 1/2"-CI-T-07121 4 ~ 20mA @ 24VDC PAL-0723-04 0-1000 kPag 315 kPag 0

Function set points are referred from


96 LT - 0726 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3127 T-0726 4 ~ 20mA @ 24VDC LAH-0726-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


97 LT - 0726 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3127 T-0726 4 ~ 20mA @ 24VDC LAL-0726-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


98 LT - 0726 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3127 T-0726 4 ~ 20mA @ 24VDC LALL-0726-03 0-1200 mm 300 mm 0
bottom of Tank

99 PT - 0727 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3127 1/2"-CI-T-07134 4 ~ 20mA @ 24VDC PAH-0727-04 0-1000 kPag 490 kPag 0

100 PT - 0727 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3127 1/2"-CI-T-07134 4 ~ 20mA @ 24VDC PAL-0727-04 0-1000 kPag 315 kPag 0

Function set points are referred from


101 LT - 0728 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3128 T-0728 4 ~ 20mA @ 24VDC LAH-0728-03 0-1200 mm 1050 mm 0
bottom of Tank

Function set points are referred from


102 LT - 0728 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3128 T-0728 4 ~ 20mA @ 24VDC LAL-0728-03 0-1200 mm 600 mm 0
bottom of Tank

Function set points are referred from


103 LT - 0728 - 03 LEVEL TRANSMITTER 0214-MI20-9020-3128 T-0728 4 ~ 20mA @ 24VDC LALL-0728-03 0-1200 mm 300 mm 0
bottom of Tank

104 PT - 0729 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3128 1/2"-CI-T-07147 4 ~ 20mA @ 24VDC PAH-0729-04 0-800 kPag 385 kPag 0

105 PT - 0729 - 04 PRESSURE TRANSMITTER 0214-MI20-9020-3128 1/2"-CI-T-07147 4 ~ 20mA @ 24VDC PAL-0729-04 0-800 kPag 180 kPag 0

TEMPERATURE TAHH-0641A-01 O O
106 TT - 0641A - 01
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC
(NOTE-2)
0-150 C 135 C 0

TEMPERATURE O O
107 TT - 0641A - 01
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAH-0641A-01 0-150 C 130 C 0

TEMPERATURE O O
108 TT - 0641A - 02
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAHH-0641A-02 0-150 C 135 C 0

TEMPERATURE O O
109 TT - 0641A - 02
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAH-0641A-02 0-150 C 130 C 0

GENERAL NOTES:

1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

2.The Final instrument settings (Chemical injection package ,Water injection pump motor ) have to be confirmed by package vendor.

Page 17 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :MODULE - P2 DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT REMARKS REV
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

TEMPERATURE O O
110 TT - 0641A - 03
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAHH-0641A-03 0-150 C 135 C 0

TEMPERATURE O O
111 TT - 0641A - 03
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAH-0641A-03 0-150 C 130 C 0

TEMPERATURE O O
112 TT - 0641A - 04
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAHH-0641A-04 0-150 C 100 C 0

TEMPERATURE O O
113 TT - 0641A - 04
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAH-0641A-04 0-150 C 97 C 0

TEMPERATURE O O
114 TT - 0641A - 05
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAHH-0641A-05 0-150 C 100 C 0

TEMPERATURE O O
115 TT - 0641A - 05
TRANSMITTER
0214-MI20-9020-3117 PM-0641A 4 ~ 20mA @ 24VDC TAH-0641A-05 0-150 C 97 C 0

TEMPERATURE O O
116 TT - 0641B - 01
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAHH-0641B-01 0-150 C 135 C 0

TEMPERATURE O O
117 TT - 0641B - 01
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAH-0641B-01 0-150 C 130 C 0

TEMPERATURE O O
118 TT - 0641B - 02
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAHH-0641B-02 0-150 C 135 C 0

TEMPERATURE O O
119 TT - 0641B - 02
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAH-0641B-02 0-150 C 130 C 0

TEMPERATURE O O
120 TT - 0641B - 03
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAHH-0641B-03 0-150 C 135 C 0

TEMPERATURE O O
121 TT - 0641B - 03
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAH-0641B-03 0-150 C 130 C 0

TEMPERATURE O O
122 TT - 0641B - 04
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAHH-0641B-04 0-150 C 100 C 0

TEMPERATURE O O
123 TT - 0641B - 04
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAH-0641B-04 0-150 C 97 C 0

TEMPERATURE O O
124 TT - 0641B - 05
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAHH-0641B-05 0-150 C 100 C 0

TEMPERATURE O O
125 TT - 0641B - 05
TRANSMITTER
0214-MI20-9020-3117 PM-0641B 4 ~ 20mA @ 24VDC TAH-0641B-05 0-150 C 97 C 0

NOTES:

1.The Final instrument settings (Chemical injection package ,Water injection pump motor ) have to beconfirmed by package vendor.

Page 18 of 20
CLIENT :TSJOC DOC No. : 0214-MI20-9002-0003

PROJECT :TSJOC SRKP Phase 1 Development Project REV No. : 1

www.kavinengg.com PACKAGE :- DATE : 11-Oct-08

INSTRUMENT SET POINT SCHEDULE


FUNCTION SET POINT

OUTPUT INSTRUMENT FUNCTION REMARKS REV


LOCATION OUTPUT SIGNAL CALIBRATED LOW CONTROLLER HIGH
S . No TAG NO ITEM P & ID / DWG NO SIGNAL CALIBRATED SETPOINT
LINE/VESSEL No. SIGNAL FUNCTION RANGE UNIT ALARM/TRIP SET POINT ALARM/TRIP
UNITS RANGE UNITS

1 PT - 0961A - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3135 3"-DO-A4-09090 4 ~ 20mA @ 24VDC PAHH-0961A-03 0-550 kPag 495 kPag 1

2 PT - 0961A - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3135 3"-DO-A4-09090 4 ~ 20mA @ 24VDC PALL-0961A-03 0-550 kPag 140 kPag 1

3 PT - 0961B - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3135 3"-DO-A4-09092 4 ~ 20mA @ 24VDC PAHH-0961B-03 0-550 kPag 495 kPag 1

4 PT - 0961B - 03 PRESSURE TRANSMITTER 0214-MI20-9020-3135 3"-DO-A4-09092 4 ~ 20mA @ 24VDC PALL-0961B-03 0-550 kPag 140 kPag 1

5 FT - 0960 - 03 FLOW TRANSMITTER 0214-MI20-9020-3135 3"-DO-A4-09090 4 ~ 20mA @ 24VDC FAH-0960-03 0-250 (0-25.53) mbar (m^3/hr) 11.5 m^3/hr 1

10

6 FT - 0960 - 03 FLOW TRANSMITTER 0214-MI20-9020-3135 3"-DO-A4-09090 4 ~ 20mA @ 24VDC FAL-0960-03 0-250 (0-25.53) mbar (m^3/hr) 2 m^3/hr 1

Function set points are referred from


7 LT - 0960 - 02 LEVEL TRANSMITTER 0214-MI20-9020-3135 T-0960 4 ~ 20mA @ 24VDC LAH-0960-02 0-1325 mm 1300 mm 1
bottom of Tank

Function set points are referred from


8 LT - 0960 - 02 LEVEL TRANSMITTER 0214-MI20-9020-3135 T-0960 4 ~ 20mA @ 24VDC LAL-0960-02 0-1325 mm 800 mm 1
bottom of Tank

GENERAL NOTES:
1.The above calibrated ranges for level transmitter given are physical units (mm) only,for mmWC please refer to instrument data sheet.

Page 20 Of 20

You might also like