Aquastat Controllers

L4006; L6006 Aquastat Controller


Aquastat Controllers are immersion type devices for limiting or
regulating the temperature of liquids in boilers, storage tanks, and
other applications where temperature control is required.
Totally enclosed Micro Switch snap-acting switches operate on
temperature rise to setpoint.
Vis ble control point scale and external adjustment screw permit
easy setting.
Horizontal or vertical insertion of the sensing element.
Direct or well immersion of the sensing element.
Models available for strap-on mounting.
Remote bulb model may be used to sense air temperature in ducts
and in outside air sensing applications.

Combustion Controls
TRADELINE models include heat-conductive compound.
Select models have wells.

Residential
Dimensions in inches (millimeters) Case Dimensions: 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep (143 mm
high x 51 mm wide x 54 mm deep)
1 (25) Maximum Ambient Temperature: 150 F (66 C)
Bulb Size: 3/8 in. x 2 7/8 in. copper (10 mm x 73 mm copper)
KNOCKOUT FOR 3/4 (19 ) Approvals
5/16 CONDUIT ON ALL MODELS. SIMILAR
(8) KNOCKOUT ON BOTTOM FOR
American Gas Association IAS: AGA Certified
HORIZONTAL INSERTION AND Canadian Standards Association: Certified: File No. LR95329-1
REMOTE BULB MODELS. Underwriters Laboratories, Inc: UL Component Recognized: File No.
MP466, Vol. 6, Sec.1, Guide No. MBPR2

Electrical Ratings
2 (51) 3/16 2-1/8 (54) Product
(5) Number (Full Load) (Locked Rotor) (Millivolt)
L4006A1009/U 5.1A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
8A @ 120 Vac 48A @ 120 Vac 12 Vdc
L4006A1017/U 5.1A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
8A @ 120 Vac 48A @ 120 Vac 12 Vdc
L4006A1132/U 5.1A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
5-5/8 8A @ 120 Vac 48A @ 120 Vac 12 Vdc
(136)
L4006A1678/U 5.1A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
8A @ 120 Vac 48A @ 120 Vac 12 Vdc
L4006A1959/U 1.3A @ 240 Vac; 7.8A @ 240 Vac;
2.6A @ 120 Vac 15.6A @ 120 Vac
L4006A1967/U 5.1A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
RESET 8A @ 120 Vac 48A @ 120 Vac 12 Vdc
BUTTON
1-7/8 (L4006E, L4006A2007/U 5.1A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
(48) L4008E 8A @ 120 Vac 48A @ 120 Vac 12 Vdc
3/4 3/4
ONLY)
(19) (19) L4006B 5.1A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
8A @ 120 Vac 48A @ 120 Vac 12 Vdc
ELEMENT
KNOCKOUT FOR 3/4 (19) L4006E,H 1.3A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
FOR VERTICAL 11/16
CONDUIT ON VERTICAL 8A @ 120 Vac 48A @ 120 Vac 12 Vdc
IMMERSION (18)
INSERTION MODELS ONLY
ELEMENT FOR HORIZONTAL IMMERSION L6006A,C 5.1A @ 240 Vac; 30.6A @ 240 Vac; 0.25 A @ 0.25 to
M8957A 8A @ 120 Vac 48A @ 120 Vac 12 Vdc

Differential Operating
Temperature Well Spud Size Capillary Length Temperature Range
Product Number Application (F) (F) (inch) (mm) (inch) (mm) Switching Action (F) (F) Mounting Includes
L4006A1009/U High or Low 5 F Fixed 3 C fixed 1/2 in. 13 mm 1 1/2 in. 38 mm SPST, contacts 100 F to 38 C to Horizontal or 1/2 in. well - 123869A
limit NPT NPT break on 240 F 116 C Vertical
temperature rise.
L4006A1017/U High or Low 5 F to 30 3 C to 17 1/2 in. 13 mm 1 1/2 in. 38 mm SPST, contacts 100 F to 38 C to Horizontal or 1/2 in. well - 123869A
limit F adj. C adj. NPT NPT break on 240 F 116 C Vertical
temperature rise.
L4006A1132/U High or Low 5 F Fixed 3 C fixed 3/4 in. 19 mm 3 in. 76 mm SPST, contacts 100 F to 38 C to Horizontal or Stop factory-set at
limit NPT NPT break on 240 F 116 C Vertical 160 F (71 C);
temperature rise. 3/4 in. well - 123871A
* L4006A1678/U High or Low 5 F to 30 3 C to 17 3 in. 76 mm SPST, contacts 100 F to 38 C to Horizontal or Heat-conductive
limit F adj. C adj. break on 240 F 116 C Vertical compound; Stop
temperature rise. factory-set at 240 F
(116 C)
* L4006A1959/U High or Low 5 F Fixed 3 C fixed 3 in. 76 mm SPST, contacts 40 F to 4 C to Horizontal or Heat-conductive
limit break on 180 F 82 C Vertical compound
temperature rise.
* TRADELINE models SUPER TRADELINE models

70-6910 171
Aquastat Controllers
Differential Operating
Temperature Well Spud Size Capillary Length Temperature Range
Product Number Application (F) (F) (inch) (mm) (inch) (mm) Switching Action (F) (F) Mounting Includes
* L4006A1967/U High or Low 5 F to 30 3 C to 17 1/2 in. 13 mm 1 1/2 in. 38 mm SPST, contacts 100 F to 38 C to Horizontal or Stop factory-set at
limit F adj. C adj. break on 240 F 116 C Vertical 240 F (116 C); 1/2 in.
temperature rise. well - 123869A
L4006A2007/U High or Low 5 F to 30 3 C to 17 3 in. 76 mm SPST, contacts 100 F to 38 C to Horizontal
limit F adj. C adj. break on 240 F 116 C
temperature rise.
L4006B1007/U Circulator 5 F Fixed 3 C fixed 1/2 in. 13 mm 1 1/2 in. 38 mm SPST, contacts 100 F to 38 C to Horizontal or 1/2 in. well - 123869A
make on 240 F 116 C Vertical
temperature rise.
* L4006B1155/U Circulator 5 F to 30 3 C to 17 3 in. 76 mm SPST, contacts 100 F to 38 C to Horizontal or Heat-conductive
F adj. C adj. make on 240 F 116 C Vertical compound; Stop
temperature rise. factory-set at 240 F
(116 C)
L4006B1163/U Circulator 5 F to 30 3 C to 17 3 in. 76 mm SPST, contacts 100 F to 38 C to Horizontal or
F adj. C adj. make on 240 F 116 C Vertical
temperature rise.
* L4006E1067/U High Limit; Manual Manual 3 in. 76 mm SPST, contacts 130 F to 54 C to Horizontal or Well adapter; Stop
Manual Reset Reset break on 270 F 132 C Vertical factory-set at 250 F
Reset temperature rise. (121 C); Heat-
conductive compound
L4006E1091/U High Limit; Manual Manual 3 in. 76 mm SPST, contacts 130 F to 54 C to Horizontal or
Manual Reset Reset break on 270 F 132 C Vertical
Reset temperature rise.
L4006E1109/U High Limit; Manual Manual 1 1/2 in. 38 mm SPST, contacts 130 F to 54 C to Horizontal or
Manual Reset Reset to 3 in. to 76 break on 270 F 132 C Vertical
Reset mm temperature rise.
L4006E1117/U High Limit; Manual Manual 3/4 in. - 19 mm - 1 1/2 in. 38 mm SPST, contacts 100 F to 38 C to Horizontal or 3/4 in. well - 123870A
Manual Reset Reset 14 NPT 14 NPT break on 240 F 116 C Vertical
Reset temperature rise.
L4006E1125/U High Limit; Manual Manual 3 in. 76 mm SPST, contacts 100 F to 38 C to Horizontal or
Manual Reset Reset break on 200 F 93 C Vertical
Reset temperature rise.
* L4006H1004/U High Limit; Manual Manual 1 1/2 in. 38 mm SPST, contacts 100 F to 38 C to Horizontal or Bracket for strap-on
strap-on Reset Reset break on 240 F 116 C Vertical mounting; Heat-
mounting on temperature rise. conductive
well mount. compound; Stop
factory-set at 240 F
(116 C)
L6006A1004/U Circulator 5F 3C 1/2 in. 13 mm 1 1/2 in. 38 mm SPDT 100 F to 38 C to Horizontal or 1/2 in. well - 123869A
Control and 240 F 116 C Vertical
High Limit or
Low Limit
L6006A1012/U Circulator 5 F to 30 3 C to 17 1/2 in. 13 mm 1 1/2 in. 38 mm SPDT 100 F to 38 C to Horizontal or 1/2 in. well - 123869A
Control and F adj. C adj. 240 F 116 C Vertical
High Limit or
Low Limit
L6006A1145/U Circulator 5 F to 30 3 C to 17 3 in. 76 mm SPDT 100 F to 38 C to Horizontal Heat-conductive
Control and F adj. C adj. 240 F 116 C compound; Stop
High Limit or factory-set at 240 F
Low Limit (116 C)
L6006A1244/U Circulator 5 F to 30 3 C to 17 3 in. 76 mm SPDT 100 F to 38 C to Horizontal or
Control and F adj. C adj. 240 F 116 C Vertical
High Limit or
Low Limit
* L6006C1018/U Circulator 5 F to 30 3 C to 17 SPDT 65 F to 18 C to Horizontal or Stop factory-set at
Control and F adj. C adj. 200 F 93 C Vertical or 200 F (93 C)
High Limit or Strap-on-
Low Limit mounting
* TRADELINE models SUPER TRADELINE models

172 customer.honeywell.com 70-6910