Calculate Size of Inveter / UPS with Battery Bank

Electrical Load Details


Sr.No Equiment Name No Watt P.F Type of Load
2 60 0.8 Capacitive Loads
Inductive Loads
Capacitive Loads
Resistive loads
S with Battery Bank
tails
Total (Watt) Total (VA) Starting (VA)
120 150 450
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
120 150 450
Jignesh.Parmar , www.electricalnotes.wordpress.com

Inverter / UPS Details


Total Load 150 VA
Total Starting Load 450 VA
Inverter efficiency 92%
Size of Invertor / UPS 0.49 KVA
Inverter / UPS Battery Details:
Battery Voltage 24 Volts DC
Inverter / UPS Back Up Time 2 Hour
Loose Connection/Wire Loss Factor: 20%
Battery Efficiency 90%
Battery Aging: 20%
Depth of Discharge:(DOD) 50%
Battery Operating Temp: 46 C
Current drain from battery 20.4 Amp
Normal storage capacity of Battery 40.8 Amp.Hr
Average Load 65.2 Amp.Hr
Size of Battery 130.4 Amp.Hr
:Battery Bank Connection Detail :
If You are Select Battery Volt 12 Volts DC 0
If You are Select Battery Size 60 Amp.Hr
Batteries connection for Battery Bank Series-Parallel
Selection of Batteries Connection: O.K
Selection of Each Battery Voltage O.K
Number of String for Battry Bank 2 Nos
Total Amp.Hr of Each String 60 Amp.Hr
Total No of Battery in Each String 2 Nos
Total Battery Bank Amp.Hr 120 Amp.Hr
Total Nos of Batteries in Battery Bank 4 Nos

Results:
Size of Invertor / UPS 0.49 KVA
Size of Battery 130 Amp.Hr
Inverter / UPS Back Up Time 2 Hour
0
0
1
string amp.hr No Total
Series 60 1 2 2 2
Parallel 120 2 2 2 4
Series-Parallel 120 2 2 2 4
Select other Type of Connecion
Select other Type of Connecion
O.K 120 2 2 2 4
C F Correction
6.7 20 1.59
1.1 30 1.4
4 40 1.3
10 50 1.19
15.6 60 1.11
21.2 70 1.04
26.7 80 1
C 1
F 1.3
1.00
Type of Load

Resistive Loads

Inductive Loads

Capacitive Loads
Equipments
toaster, coffee maker, electric range, iron, Incandescent lamps, flood lighting. Laser Printers
use Nichrome resistance wire in their heating
induction motor, reciprocating pumps and compressors, refrigeration, air-conditioning,
Oxygen Concentrators have more starting current.
Switched Mode Power Supplies (SMPS), electronic equipment like battery chargers,
computers, audio and video devices, radio etc.
Times Starting Power